1 DIVISION 13 - SPECIAL CONSTRUCTION SECTION ACOUSTICAL PANEL ENCLOSURE 1 GENERAL 1.01 SUMMARY A. ACOUSTIC ENCLOSURE CONSISTING OF WALLS, CEILING, STRUCTURAL FRAMING, CONNECTING MEMBERS, DOORS, WINDOWS, MISCELLANEOUS MATERIALS AND ALL FASTENERS NECESSARY TO CONSTRUCT THE TEST CELLS. THE TEST CELLS ARE TO BE FIELD ASSEMBLED FROM 4" THICK PRE-MANUFACTURED COMPONENTS. ENCLOSURE TO BE DESIGNED TO MEET THE PERFORMANCE CRITERIA SPECIFIED HEREIN AS A COMPLETE ASSEMBLY. B. PROVIDE LABOR, MATERIAL, TOOLS, EQUIPMENT, SCAFFOLDING, TRANSPORTATION, INSPECTION, CERTIFICATES, AND TEMPORARY PROTECTION NECESSARY TO: 1. PROVIDE ACOUSTICAL ENCLOSURES AS SHOWN ON DRAWINGS AND AS SPECIFIED IN THESE SPECIFICATIONS. PROVIDE ACCESSORIES AND APPURTENANCES REQUIRED FOR COMPLETE WORKING INSTALLATION. 2. CONNECTORS AND FLASHING SHALL MAKE HOLES IN WALLS ACOUSTICALLY TIGHT IN ACCORDANCE WITH PANEL MANUFACTURER'S INSTRUCTIONS C. STRUCTURAL STEEL SUPPORT FRAME AS REQUIRED. D. ALL ELECTRICAL BY OTHERS, REFER TO DRAWINGS. E. ALL DUCTWORK BETWEEN HOST BUILDING AND TEST CELLS FOR AIR INTAKE AND AIR EXHAUST BY OTHERS, REFER TO DRAWINGS QUALITY ASSURANCE: A. REGULATORY REQUIREMENTS: 1. ACOUSTICAL PERFORMANCE: MINIMUM NRC (NOISE REDUCTION COEFFICIENT) RATING OF 1.0 MINIMUM STC (SOUND TRANSMISSION CLASS) OF 42 AFTER PANEL FABRICATION. B. REFERENCE STANDARDS: 1. ASTM E90-99 OR ASTM E90-02 AND E STANDARD TEST METHOD FOR LABORATORY MEASUREMENT OF AIRBORNE SOUND TRANSMISSION LOSS OF BUILDING PARTITIONS. 2. ASTM C423-90A AND ASTM E795-00, SOUND ABSORPTION AND SOUND ABSORPTION COEFFICIENTS BY THE REVERBERATION ROOM METHOD SUBMITTALS: A. PRODUCT DATA: MANUFACTURER'S PRODUCT SPECIFICATIONS. B. SHOP DRAWINGS: COMPLETE DRAWINGS SHOWING COMPONENTS INCLUDING MECHANICAL AND ELECTRICAL REQUIREMENTS. C. CERTIFICATE OF COMPLIANCE: CERTIFY COMPLETED ASSEMBLY MEETS REQUIREMENTS SPECIFIED HEREIN. D. STAMPED (P.E.) CALCULATIONS FOR ALL STRUCTURAL AND PANEL COMPONENTS.

2 1.04 DELIVERY, STORAGE AND HANDLING A. DELIVER PRODUCTS IN SUFFICIENT QUANTITY AND TIME TO MAINTAIN APPROVED CONSTRUCTION SCHEDULE. B. MATERIALS SHALL BE IN ORIGINAL CONTAINERS WITH SEALS UNBROKEN AND LABELS INTACT UNTIL TIME OF USE. WRAPPED OR BUNDLED MATERIALS SHALL BEAR NAME OF MANUFACTURER AND PRODUCT. DAMAGED OR OTHERWISE UNSUITABLE MATERIAL, WHEN SO ASCERTAINED, SHALL BE REMOVED FROM PROJECT SITE. C. STORE PRODUCTS IN SECURE, DRY LOCATION, OUT OF WAY OF CONSTRUCTION OPERATIONS. STORE PRODUCTS OFF GROUND AND PROTECT FROM ELEMENTS. WETTING OF ELEMENTS NOT PERMITTED. D. PREVENT DAMAGE TO MATERIALS, TO OTHER STORED PRODUCTS, TO EXISTING CONSTRUCTION, AND PROJECT WORK WARRANTY A. FINISH WARRANTY: FURNISH PANEL MANUFACTURER'S WRITTEN WARRANTY COVERING FAILURE OF THE FACTORY-APPLIED FINISH ON METAL PANELS WITHIN THE WARRANTY PERIOD. THIS WARRANTY SHALL BE IN ADDITION TO AND NOT A LIMITATION OF OTHER RIGHTS THE OWNER MAY HAVE AGAINST THE CONTRACTOR UNDER THE CONTRACT DOCUMENTS. B. WARRANTY PERIOD: 2 YEARS 1.06 EXPERIENCE A. TEST CELL SUPPLIER MUST PROVIDE A LIST OF TEN (10) SIMILAR SUCCESSFUL INSTALLATIONS OF MODULAR TEST CELLS. 2 PRODUCTS 2.01 ACOUSTICAL METAL PANELS A. ALL PANELS AND THEIR COMPONENTS SHALL BE PRE-FABRICATED, SECTIONAL, ALL-METAL CLAD, MODULAR AND DESIGNED FOR EASY AND ACCURATE FIELD ASSEMBLY. THE PANELS AND COMPONENTS SHALL NOT BE SUSCEPTIBLE TO DAMAGE DUE TO EXTENDED EXPOSURE TO VIBRATION, AIR TEMPERATURE OR HUMIDITY WITH THE PASSAGE OF TIME PANEL CONSTRUCTION A. EXCEPT AS SHOWN ON DRAWINGS OR AT LOCATIONS DESCRIBED BELOW, USE 4 THICK ACOUSTICAL PANELS. EXTERIOR SURFACES ARE SOLID SHEET 16-GA. GALVANNEAL STEEL. INTERIOR SURFACES ARE 22 GA. PERFORATED GALVANNEAL STEEL. B. SOUND-RETARDING AND ABSORBING FILL MATERIAL SHALL BE NONCOMBUSTIBLE, INERT, MILDEW-RESISTANT AND VERMIN PROOF. C. THE PANEL SHELLS, FRAMING MEMBERS AND INTERNAL REINFORCEMENTS SHALL BE WELDED AND/OR RIVETED TOGETHER TO FORM A METAL-SHEATHED PANEL OF SUFFICIENT STRENGTH FOR MAXIMUM OPERATING LOADS. D. PRIOR TO ATTACHING FACE SHEET, PANEL SHALL BE DAMPENED AND FILLED WITH SOUND- RETARDING AND ABSORBING ELEMENTS. FILL SHALL BE SLIGHTLY LARGER AND THICKER THAN INSIDE DIMENSIONS OF PANEL. NO VOIDS WILL BE TOLERATED E. THE OUTER GALVANIZED STEEL SHELL THICKNESS SHALL BE 16-GA. MINIMUM AND THE INNER GALVANIZED STEEL SHELL SHALL BE 22-GA. MINIMUM THICK. F. WEEP HOLES TO PERMIT WATER RUNOFF SHALL BE PROVIDED ON ALL HORIZONTAL SURFACES.

3 G. SPOT WELDS SHALL BE NO MORE THAN 4 IN. APART DOOR PANELS A. DOOR LEAF SHALL BE 4 IN. THICK FABRICATED FROM 16 GAUGE STEEL AND FILLED WITH SOUND ABSORBING AND DAMPING ELEMENTS WITH A CLEAR OPENING OF (REFER TO DRAWINGS). DOORS SHALL HAVE A RATING OF STC 42 MINIMUM. B. FRAME SHALL BE FABRICATED FROM MINIMUM 11 GAUGE STEEL. C. ASSEMBLY AND ADJUSTMENT OF DOOR ASSEMBLY INCLUDING DOOR LEAF, FRAME, ACOUSTIC SEALS AND HINGES SHALL TAKE PLACE AT THE FACTORY AND THE ENTIRE UNIT SHALL SHIP TO THE JOBSITE READY FOR INSTALLATION AND OPERATION. ALL DOORS SHALL BE TESTED FOR PROPER OPERATION IN THE FACTORY PRIOR TO SHIPMENT. D. ACOUSTIC SEALS: SIDES AND HEAD OF DOOR AND FRAME SHALL RECEIVE TWO (2) SETS OF SELF-ALIGNING COMPRESSION SEALS. DOOR TO BE HELD IN PLACE BY FORCE OF PERIMETER SEALS. ACOUSTIC LABYRINTH SHALL BE CREATED WHEN DOOR IS IN CLOSED POSITION. BOTTOM OF DOOR LEAF SHALL CONTAIN CONTINUOUS GRAVITY ACTIVATED SEAL, WHICH SHALL COMPRESS AGAINST FLOOR AS DOOR IS CLOSED. RAISED SILLS AND THRESHOLD DROP SEALS WILL NOT BE PERMITTED. E. HARDWARE: 1. HINGES - TWO (2) CAM-LIFT HINGES FINISHED IN US 26-D SATIN CHROME SHALL BE SUPPLIED WITH EACH DOOR LEAF. 2. LATCHES SHALL NOT E REQUIRED TO HOLD THE DOOR CLOSED OR TO ACHIEVE ACOUSTIC SEAL. 3. SEE THE DRAWINGS IN REGARDS TO THE HARDWARE SCHEDULE FOR EGRESS DOORS WINDOW PANELS A. WINDOWS SHALL BE FURNISHED IN PANELS OF THE TYPE AND CONSTRUCTION SPECIFIED AS SHOWN ON THE DRAWINGS. B. WINDOWS SHALL CONSIST OF TWO (2) LAYERS OF 3/16 IN. SAFETY GLASS SEPARATED BY AN AIR SPACE AND SEALED IN ACOUSTICALLY TIGHT RUBBER SEALS OR ONE LAYER OF 1-3/16 THICK BULLET RESISTANT GLAZING. REFER TO DRAWINGS FOR WINDOW TYPE AND LOCATION. C. AIR SPACE ON DOUBLE GLAZED WINDOWS SHALL CONTAIN A DESICCANT MATERIAL TO PREVENT FOGGING PANEL COMPONENTS A. ALL ACCESSORY TRIM ITEMS SHALL BE OF GALVANIZED STEEL AND SHALL BE FURNISHED IN FACTORY-STANDARD LENGTHS TO BE FIELD CUT TO SPECIFIED DIMENSIONS. LOCATIONS AND QUANTITIES OF SHEET METAL SCREWS AND TRIM REQUIREMENTS SHALL BE IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION DETAILS. B. ALL PANEL CONNECTIONS, TRIM ITEMS, ACCESSORIES, BASE CHANNEL/PANEL INTERFACES, BASE CHANNEL/FLOOR INTERFACES AND OTHER SECTIONS SHALL BE SEALED WITH AN ACOUSTICAL SEALANT THAT SHALL NOT HARDEN AND PREVENT DISASSEMBLY IN THE FUTURE. C. PANEL CONNECTION DESIGN AND FIT SHALL PREVENT NOISE LEAKAGE WHILE ACOUSTICALLY AND STRUCTURALLY JOINING PANELS TOGETHER. JOINERS SHALL BE ROLL FORMED SECTIONS INDEPENDENT OF BASIC PANEL SO THERE IS NO POSSIBILITY OF DIRECT PASSAGE OF NOISE. D. WEEP HOLES TO PERMIT WATER RUNOFF SHALL BE PROVIDED ON ALL HORIZONTAL SURFACES THAT MAY TRAP WATER.

4 2.06 ACCESSORY ITEMS A. DOORS, WINDOWS, ACCESSORY COMPONENTS, ETC., SHALL BE PROVIDED IN ACCORDANCE WITH THE DRAWINGS STRUCTURAL PERFORMANCE A. UNDER THE INDICATED LOADING CONDITIONS, THE ENTIRE ENCLOSURE SYSTEM SHALL BE SELF-SUPPORTING. THE INSTALLER SHALL FURNISH AND ASSEMBLE ALL STRUCTURAL MEMBERS IN STRICT ACCORDANCE WITH THE DRAWINGS AND MANUFACTURER'S INSTALLATION DETAILS. B. THE TEST CELL STRUCTURE SHALL SUPPORT ALL WALL MOUNTED CRANE AND MECHANICAL/ELECTRICAL EQUIPMENT LOADS AS INDICATED ON THE DRAWINGS. C. UNDER THE ABOVE LOADING CONDITIONS, THE ASSEMBLED ACOUSTICAL STRUCTURE SHALL NOT EXHIBIT ANY PANEL JOINT DEFLECTION IN EXCESS OF L/240, WHERE L IS THE UNSUPPORTED SPAN LENGTH OF ANY PANEL SECTION IN THE ERECTED STRUCTURE PRIME AND FINISH PAINT A. STRUCTURAL STEEL MEMBERS AND DOORS A.A. STRUCTURAL STEEL MEMBERS AND DOORS TO RECEIVED PAINT SHALL BE DE-GREASED AND CLEANED IN ACCORDANCE WITH SSPC WITH WELDS GROUND SMOOTH AND FILLED AS NEEDED. EXPOSED SURFACES SHALL THEN BE PRIMED WITH ON COATED MODIFIED ALKYD BAKED ENAMEL PAINT A.B. FINISH PAINT SHALL BE AS INDICATED IN THE PAINT SCHEDULE ON SHEET A-106 A.C. PROVIDED SUFFICIENT PAINT TO TOUCH UP STRUCTURAL MEMBERS AND DOORS AFTER INSTALLATION OF TEST CELLS. B. PANELS AND TRIM B.A. FINISH ACOUSTICAL PANELS IN SHOP PRIOR TO PANEL ASSEMBLY AND ACOUSTIC INSULATION FILL. B.B. PREPARE PANELS AND TRIM BY THOROUGHLY REMOVING GREASE, DIRT, OIL, FLUX, AND OTHER FOREIGN MATTER B.C. TREAT PREPARED ACOUSTICAL PANELS AND COMPONENTS WITH ZINCE-PHOSPATE PRETREATMENT, RINSE, AND SEAL SURFACE. B.D. APPLY THERMOSETTING POLYESTER OR ACRYLIC URETHANE POWDER COATING WITH CURED- FILM THICKNESS NOT LESS THAN 3.0 MILS. B.E. COLOR SHALL BE AS INDICATED IN THE PAINT SCHEDULE ON SHEET A-106. B.F. SURFACE PROTECTION: APPLY A TEMPORARY 3.0 MIL THICKNESS PVC TEMPORARY COVERING TO POWDER COATED SURFACE AFTER CURE FOR SHIPMENT AND INSTALLATION PROTECTION. C. FINISH PAINT SHALL BE AS INDICATED IN THE PAINT SCHEDULE ON SHEET A-106. D. PROVIDE SUFFICIENT PAINT TO TOUCH-UP PANELS AFTER INSTALLATION OF TEST CELLS.

5 2.09 INTERCHANGEABILITY AND REUSE A. ACOUSTIC STRUCTURAL COMPONENTS HAVING SAME PART NUMBERS SHALL BE COMPLETELY INTERCHANGEABLE. B. ACOUSTIC STRUCTURE SHALL BE SUCH THAT NO COMPONENTS WILL BE DAMAGED UPON DISASSEMBLY. DESIGN SHALL ALLOW STRUCTURE TO BE ASSEMBLED, DISASSEMBLED AND REASSEMBLED MINIMUM OF 3 TIMES WITHOUT DETRACTION FROM ACOUSTIC PERFORMANCE PANEL COMPONENT CHARACTERISTICS A. THE MANUFACTURER SHALL PROVIDE CERTIFIED TESTING DATA INCLUDING SOUND ABSORPTION AND TRANSMISSION LOSS CHARACTERISTICS OF THE PANELASSEMBLY OF NOT LESS THAN THE FOLLOWING: SOUND TRANSMISSION LOSS, DB OCTAVE BAND CENTER FREQUENCIES, HZ K 2K 4K 8K STC WALL/CEILING PANELS 4 THICK SOUND ABSORPTION COEFFICIENTS OCTAVE BAND CENTER FREQUENCIES, HZ K 2K 4K 8K NRC 4 THICK B. SUBMIT CERTIFIED FIRE TESTING LABORATORY TEST REPORTS INCLUDING FLAME SPREAD INDEX (FSI) AND SMOKE DEVELOPED INDEX (SDI) VALUES FOR SPECIFIED PANEL TYPE AND CONSTRUCTION OF NOT LESS THAN FOLLOWING: 3 EXECUTION PANEL CONSTRUCTION: FSI 0.00 SDI PANEL SUPPORTS AND ANCHORAGE A. INSTALL COLUMNS, BEAMS AND OTHER SECONDARY STRUCTURAL PANEL SUPPORT MEMBERS AND ANCHORAGE IN ACCORDANCE WITH AISC MANUAL OF STEEL CONSTRUCTION "CODE OF STANDARD PRACTICE" PANEL INSTALLATION A. INSTALL PANELS ACCORDING TO MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS, AS APPLICABLE TO PROJECT CONDITIONS AND SUPPORTING SUBSTRATES. ANCHOR PANELS AND OTHER COMPONENTS OF THE WORK SECURELY IN PLACE, WITH PROVISIONS FOR THERMAL AND STRUCTURAL MOVEMENT. 1. INSTALL PANELS WITH EXPOSED FASTENERS PRE-FINISHED TO MATCH PANEL FINISHES. B. BASE CHANNEL SHALL BE INSTALLED ON A LEVEL AND STRUCTURALLY SOUND SURFACE. C. ACCESSORIES: INSTALL COMPONENTS REQUIRED FOR A COMPLETE ACOUSTICAL PANEL SYSTEM, INCLUDING TRIM, COPING, SUPPORTS AND ATTACHMENTS, CONNECTIONS BETWEEN PANELS, SEAM COVERS, SEALANTS, FILLERS, CLOSURES STRIPS AND SIMILAR ITEMS.

6 3.03 CLEANING AND ADJUSTMENT A. DAMAGED UNITS: REPLACE PANELS AND OTHER COMPONENTS OF THE WORK THAT HAVE BEEN DAMAGED OR HAVE DETERIORATED BEYOND SUCCESSFUL REPAIR BY MEANS OF FINISH TOUCH UP OR SIMILAR MINOR REPAIR PROCEDURES. B. CLEANING: REMOVE TEMPORARY PROTECTIVE COVERINGS AND STRIPPABLE FILMS (IF ANY) AS SOON AS EACH PANEL IS INSTALLED. UPON COMPLETION OF PANEL INSTALLATION, CLEAN FINISHED SURFACES AS RECOMMENDED BY PANEL MANUFACTURER, AND MAINTAIN IN A CLEAN CONDITION DURING CONSTRUCTION.

SOUND BARRIER WALLS. Specializing in Acoustics, Noise & Vibration Control. Phone Fax Penn Street Westfield, IN 46074

SOUND BARRIER WALLS. Specializing in Acoustics, Noise & Vibration Control. Phone Fax Penn Street Westfield, IN 46074 SOUND BARRIER WALLS Specializing in Acoustics, Noise & Vibration Control 129 Penn Street Westfield, IN 46074 Phone Fax 317-774-1911 www.enoisecontrol.com info@enoisecontrol.com Barrier Wall Systems Industrial,

More information

Melhart Music Center Modular Music Practice Rooms - E3 Ready Specifications Section 13034

Melhart Music Center Modular Music Practice Rooms - E3 Ready Specifications Section 13034 Melhart Music Center Modular Music Practice Rooms - E3 Ready Specifications Section 13034 PART 1 - General 1.01 Summary A. Section includes labor, material, equipment, and other considerations required

More information

SECTION / STC 52 METAL SOUND CONTROL DOORS

SECTION / STC 52 METAL SOUND CONTROL DOORS SECTION 08 34 73 / 08 34 73.13 STC 52 METAL SOUND CONTROL DOORS PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including general and Supplementary Conditions

More information

SECTION / / BULLET RESISTANT SOUND CONTROL WINDOWS

SECTION / / BULLET RESISTANT SOUND CONTROL WINDOWS SECTION 08381 / 088856 / 085673 BULLET RESISTANT SOUND CONTROL WINDOWS 1.0 GENERAL 1.1 DESCRIPTION OF WORK A. Furnish and install FACTORY PREGLAZED Bullet Resistant Sound Control Windows specified herein

More information

SECTION SOUND CONTROL DOORS

SECTION SOUND CONTROL DOORS SECTION 08380 SOUND CONTROL DOORS 1.0 GENERAL 1.1 DESCRIPTION OF WORK A. Furnish and install Sound Control Doors specified herein and per the locations and orientations shown on the Contract Documents.

More information

SECTION Motor Operated Horizontal Sliding Sound Control Door

SECTION Motor Operated Horizontal Sliding Sound Control Door SECTION 08 34 73 Motor Operated Horizontal Sliding Sound Control Door PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including general and Supplementary Conditions

More information

Moduline IAC s proven modular range of acoustic construction panels

Moduline IAC s proven modular range of acoustic construction panels Moduline IAC s proven modular range of acoustic construction panels Applications Schools Colleges Universities Music Academies Youth Organisations Features BB9 compliance depending on configuration Provides

More information

SECTION ACCORDION FOLDING PARTITIONS

SECTION ACCORDION FOLDING PARTITIONS PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 10 22 26.13 ACCORDION FOLDING PARTITIONS SPEC WRITER NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information

Moduline. Acoustic Enclosure System. Rugged Noise Control Structures Using Acoustically Rated & Field Proven Demountable Components

Moduline. Acoustic Enclosure System. Rugged Noise Control Structures Using Acoustically Rated & Field Proven Demountable Components Moduline Acoustic Enclosure System Rugged Noise Control Structures Using Acoustically Rated & Field Proven Demountable Components Lab certified acoustic ratings Broad range of performance levels 63 Hz

More information

C. Samples: For each door face material, at least 3 by 5 inches (75 by 125 mm) in size, in specified finish.

C. Samples: For each door face material, at least 3 by 5 inches (75 by 125 mm) in size, in specified finish. SECTION 083113 - ACCESS DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM

GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM 1 GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM 1.01 WORK INCLUDED PART 1: GENERAL A. Provide for all labor, equipment, materials, and services to furnish and install VERSA SHIELD Window

More information

HOLLOW METAL DOORS AND FRAMES SECTION HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL

HOLLOW METAL DOORS AND FRAMES SECTION HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 13686.00 HOLLOW METAL DOORS AND FRAMES 081113-1 SECTION 081113 - HOLLOW METAL DOORS AND FRAMES 1.1 RELATED DOCUMENTS: PART 1 - GENERAL A. Drawings and general provisions of Contract, including General

More information

SECTIONAL OVERHEAD DOORS SECTION SECTIONAL OVERHEAD DOORS PART 1 GENERAL

SECTIONAL OVERHEAD DOORS SECTION SECTIONAL OVERHEAD DOORS PART 1 GENERAL 13686.00 SECTIONAL OVERHEAD DOORS 083613-1 1.1 RELATED DOCUMENTS SECTION 083613 - SECTIONAL OVERHEAD DOORS PART 1 GENERAL A. Drawings and general provisions of Contract, including General and Supplementary

More information

AMBICO Limited Section and RFI\EMI SHEILDED STEEL DOOR AND FRAME ASSEMBLIES Page 1

AMBICO Limited Section and RFI\EMI SHEILDED STEEL DOOR AND FRAME ASSEMBLIES Page 1 Page 1 This section includes AMBICO RFI/EMI Steel Shielding Steel Door and Frame assemblies. This section relies on both the Canadian Steel Door Manufacturers Association (CSDMA.org) industry standard,

More information

SECTION STEEL DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION STEEL DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 08110 - STEEL DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General, Supplementary, and Special Conditions and Division 1 Specification

More information

The fire resistance required for doors in this building is 1 (one) hour resistance in compliance with the below general specifications:

The fire resistance required for doors in this building is 1 (one) hour resistance in compliance with the below general specifications: Query No.1 ; we need more specs. about fire resistant doors Answer to Query No. 1: The fire resistance required for doors in this building is 1 (one) hour resistance in compliance with the below general

More information

RAMAPO COLLEGE OF NEW JERSEY PHASE II HOUSING REHABILITATION C 2012

RAMAPO COLLEGE OF NEW JERSEY PHASE II HOUSING REHABILITATION C 2012 SECTION 10200 - LOUVERS AND VENTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION PERSONNEL DUTY LOCKERS. 1. FPPL Series Police Personnel Duty Lockers, including the following:

SECTION PERSONNEL DUTY LOCKERS. 1. FPPL Series Police Personnel Duty Lockers, including the following: SECTION 10501 PERSONNEL DUTY LOCKERS PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 specifications

More information

Architectural Wall Products Guide Specifications

Architectural Wall Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Wall Products Guide Specifications FORMED METAL WALL PANELS This Guide Specification is

More information

COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100

COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100 COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100 Part 1 General 1.01 Work Included A. The work under this section shall include the furnishing of all items shown on the drawings and as specified,

More information

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07 4243 - PART 1 GENERAL 1.01 SECTION INCLUDES A. Composite wall panel system consisting of aluminum-faced composite panels in a rainscreen application as part of the assembly described below.

More information

A. Access doors and frames are part of an access door and frame allowance.

A. Access doors and frames are part of an access door and frame allowance. SECTION 08 31 13 ACCESS DOORS AND FRAMES PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

ALL-ALUMINUM DOOR & WINDOW FRAMING

ALL-ALUMINUM DOOR & WINDOW FRAMING ALL-ALUMINUM DOOR & WINDOW FRAMING WITH INTEGRATED ALUMINUM DOOR STOP SECTION 08 41 13 ALUMINUM FRAMED ENTRANCES AND STOREFRONTS SPECIFICATION PART 1 GENERAL 1.1 SECTION INCLUDES: A. Prefinished aluminum

More information

Ceiling Tiles C200B - Specification

Ceiling Tiles C200B - Specification Ceiling Tiles C200B - Specification SECTION 09510 ACOUSTICAL CEILING TILES PART 1 GENERAL 1.00 GENERAL A. Sound Quality Acoustical Ceiling Tiles by Sound Seal, 50 H.P. Almgren Drive, Agawam, MA 01001;

More information

AMBICO Limited Section and ACOUSTIC STEEL DOOR AND FRAME ASSEMBLIES Page 1

AMBICO Limited Section and ACOUSTIC STEEL DOOR AND FRAME ASSEMBLIES Page 1 Page 1 This section includes AMBICO Acoustic Steel Doors and Frames as well as perimeter and bottom acoustic seals, and glazing if required all of which can be fire rated or non-rated. The aforementioned

More information

Acoustic Louvers ABSORPTIVE ACOUSTIC LOUVERS

Acoustic Louvers ABSORPTIVE ACOUSTIC LOUVERS ABSORPTIVE ACOUSTIC LOUVERS Developed to provide a solution to applications that require efficient ventilation without the transfer of undesirable noise, Price use acoustic media to absorb sound energy

More information

SECTION MANUAL FOUR FOLD DOORS MODEL 38 DECORATIVE PANEL DESIGN

SECTION MANUAL FOUR FOLD DOORS MODEL 38 DECORATIVE PANEL DESIGN SECTION 08350 MANUAL FOUR FOLD DOORS MODEL 38 DECORATIVE PANEL DESIGN PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

603 Summit Avenue, Suite 102 Greensboro, N.C Voice/FAX (336)

603 Summit Avenue, Suite 102 Greensboro, N.C Voice/FAX (336) Ricky L. Loman, AIA Architect 603 Summit Avenue, Suite 102 Greensboro, N.C. 27405-7700 Voice/FAX (336) 273-7999 ADDENDUM: Number 1 ISSUED: March 14, 2017 SUBJECT: New Agriculture & Equipment Storage Barn

More information

GENERAL SPECIFICATION FOR FIRE RATED APPLICATIONS

GENERAL SPECIFICATION FOR FIRE RATED APPLICATIONS I N SULROCK FIRE RATED METAL PANELS GENERAL SPECIFICATION FOR FIRE RATED APPLICATIONS 1. GENERAL 1.1. Summary Fire-rated panels as shown on the drawings shall be INSULROCK brand panels as supplied by Green

More information

SECTION OVERHEAD COILING FIRE DOORS MODEL 662 OVERHEAD COILING COUNTER FIRE DOORS WITH INTEGRAL FRAME

SECTION OVERHEAD COILING FIRE DOORS MODEL 662 OVERHEAD COILING COUNTER FIRE DOORS WITH INTEGRAL FRAME SECTION 08331 OVERHEAD COILING FIRE DOORS MODEL 662 OVERHEAD COILING COUNTER FIRE DOORS WITH INTEGRAL FRAME Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES

More information

HOTEL SPECIFICATION SECTION 08100

HOTEL SPECIFICATION SECTION 08100 Part 1 General HOTEL SPECIFICATION SECTION 08100 1.01 Work Included A. The work under this section shall include the furnishing of all items shown on the drawings and as specified including, but not limited

More information

K. ASTM F436- Standard Specification for Hardened Steel Washers; 2011.

K. ASTM F436- Standard Specification for Hardened Steel Washers; 2011. DIVISION 05 METALS 05 12 00 STRUCTURAL STEEL FRAMING PART 1 GENERAL 1.1 SECTION INCLUDES A. Structural steel framing members, support members. 1.2 RELATED REQUIREMENTS A. Section 05 50 00 - Metal Fabrications:

More information

SECTION NON-LOAD BEARING WALL FRAMING. B. Section Furring and Lathing: Lath and furring for interior plaster applications.

SECTION NON-LOAD BEARING WALL FRAMING. B. Section Furring and Lathing: Lath and furring for interior plaster applications. SECTION 09.22.16 NON-LOAD BEARING WALL FRAMING PART 1 GENERAL 1.1 SECTION INCLUDES A. Non-load bearing metal studs for wall assemblies. B. Area Separation and shaft wall framing products. 1.2 RELATED SECTIONS

More information

1. Base plates, setting plates and anchor rods for columns. 8. Lintels if connected to structural steel columns.

1. Base plates, setting plates and anchor rods for columns. 8. Lintels if connected to structural steel columns. PAGE 051200-1 SECTION 051200 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification sections,

More information

TRUMAN STATE UNIVERSITY GREENWOOD SCHOOL WINDOW REPLACEMENT

TRUMAN STATE UNIVERSITY GREENWOOD SCHOOL WINDOW REPLACEMENT SECTION 085200 - WOOD WINDOWS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Central Dartmouth Section Exterior Envelope Renovations METAL-CLAD WOOD DOORS Page 1 of 5 Dartmouth, NS

Central Dartmouth Section Exterior Envelope Renovations METAL-CLAD WOOD DOORS Page 1 of 5 Dartmouth, NS Exterior Envelope Renovations METAL-CLAD WOOD DOORS Page 1 of 5 Part 1 General 1. RELATED SECTIONS 1. Section 07 92 10 Joint Sealing 2. Section 08 71 00 Door Hardware 2. REFERENCES 1. American Society

More information

SECTION METAL DOORS & FRAMES

SECTION METAL DOORS & FRAMES SECTION 08100 METAL DOORS & FRAMES PART 1 GENERAL 1.1 SCOPE Drawings and general provisions of the Contract, including General and Supplementary General Conditions and other Division 00 & 01 specification

More information

SPECIAL CONSTRUCTION SECTION SOUND CONDITIONING ROOMS FOR AUDIOMETRIC TESTING & MEDICAL LIFE SCIENCES

SPECIAL CONSTRUCTION SECTION SOUND CONDITIONING ROOMS FOR AUDIOMETRIC TESTING & MEDICAL LIFE SCIENCES PART 1 GENERAL 1.0 SCOPE: This specification prefabricated Audiometric Examination booths and suites suitable for use in testing, calibration and recording of aural acuity. A booth is defined as a freestanding

More information

DIVISION 5 - STRUCTURAL STEEL AND IRON WORK

DIVISION 5 - STRUCTURAL STEEL AND IRON WORK DIVISION 5 - STRUCTURAL STEEL AND IRON WORK SECTION 05100 STRUCTURAL METAL FRAMING PART 1.00 GENERAL 1.01 SCOPE OF WORK A. Work Included: 1. 2. Structural steel complete in place. Steel joists complete

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 102239 - FOLDING PANEL PARTITIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

B. Related Sections: The following Sections contain requirements that relate to this Section:

B. Related Sections: The following Sections contain requirements that relate to this Section: SECTION 08111 - STEEL DOOR FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION STEEL WINDOWS UL Labeled Fire-Rated Fixed Lite (950) Use Tools / Options / View / Hidden Text to view hidden notes and edit.

SECTION STEEL WINDOWS UL Labeled Fire-Rated Fixed Lite (950) Use Tools / Options / View / Hidden Text to view hidden notes and edit. SECTION 08510 STEEL WINDOWS UL Labeled Fire-Rated Fixed Lite (950) Use Tools / Options / View / Hidden Text to view hidden notes and edit. PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire Rated Steel Windows

More information

SECTION ALUMINUM WINDOWS

SECTION ALUMINUM WINDOWS SECTION 08520 ALUMINUM WINDOWS 1. PART 1 GENERAL 1.1 WORK INCLUDED: 1. Provide labor, material, equipment and services to furnish and install aluminum windows shown on drawings and specified herein. Window

More information

SERIES STB30 STEEL FIXED THERMAL BREAK DETENTION WINDOWS SECTION 08651

SERIES STB30 STEEL FIXED THERMAL BREAK DETENTION WINDOWS SECTION 08651 SERIES STB30 STEEL FIXED THERMAL BREAK DETENTION WINDOWS SECTION 08651 PART 1 GENERAL 1.1 DESCRIPTION A. Work Included: 1. Furnish all labor and materials to complete the fabrication of detention windows

More information

SECTION SECURITY PROTECTION PART 1 GENERAL

SECTION SECURITY PROTECTION PART 1 GENERAL SECTION 13 1010 - PART 1 GENERAL 1.01 SECTION INCLUDES A. Bullet Resistant Aluminum Windows. B. Bullet Resistant Transaction Equipment. C. Bullet Resistant Speakers. D. Bullet Resistant Glazing. E. Bullet

More information

A. Pre-Installation Conference: Conduct conference at [project site] <insert location>.

A. Pre-Installation Conference: Conduct conference at [project site] <insert location>. SECTION 074213.23 METAL COMPOSITE MATERIAL WALL PANELS PART 1 GENERAL 1.1 SUMMARY A. Exterior cladding consisting of formed metal composite material (MCM) sheet, secondary supports and anchors to structure,

More information

SECTION (05300) - STEEL DECKING

SECTION (05300) - STEEL DECKING SECTION 05 31 00 (05300) - STEEL DECKING PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Roof Deck 2. Composite Floor Deck 3. Noncomposite Form Deck B. Related Sections: 1.02 SUBMITTALS 1. Section

More information

SECTION FOLDING DOORS AMSTEL AS900CC DIVIDER SOUND

SECTION FOLDING DOORS AMSTEL AS900CC DIVIDER SOUND SECTION 08352 FOLDING DOORS AMSTEL AS900CC DIVIDER SOUND THREE PART SHORT FORM SPECIFICATIONS (CSI) PART 1 GENERAL 1.1 SUMMARY A. Section Includes: manually operated, side folding accordion- type products

More information

JAMISON SOUND DOOR SPECIFICATIONS VERTICAL SLIDING SOUND REDUCTION DOOR - STC 53 POWERED OPERATION

JAMISON SOUND DOOR SPECIFICATIONS VERTICAL SLIDING SOUND REDUCTION DOOR - STC 53 POWERED OPERATION JAMISON SOUND DOOR SPECIFICATIONS VERTICAL SLIDING SOUND REDUCTION DOOR - STC 53 POWERED OPERATION PART 1 - GENERAL 1.1 APPLICABLE PUBLICATIONS: The publications listed below form a part of this specification

More information

SECTION STEEL WINDOWS UL Labeled Fire-Rated Fixed Lite (950) Use Tools / Options / View / Hidden Text to view hidden notes and edit.

SECTION STEEL WINDOWS UL Labeled Fire-Rated Fixed Lite (950) Use Tools / Options / View / Hidden Text to view hidden notes and edit. SECTION 08510 STEEL WINDOWS UL Labeled Fire-Rated Fixed Lite (950) Use Tools / Options / View / Hidden Text to view hidden notes and edit. PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire Rated Steel Windows

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 08 - OPENINGS. A. This Section includes fixed and operable aluminum-framed windows.

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 08 - OPENINGS. A. This Section includes fixed and operable aluminum-framed windows. SECTION 085113 - ALUMINUM WINDOWS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes fixed and operable aluminum-framed windows. 1.2 PERFORMANCE REQUIREMENTS A. General: Provide aluminum windows capable

More information

SECTION STEEL WINDOWS UL Labeled Fire-Rated Horizontal Slider (900) Use Tools / Options / View / Hidden Text to view hidden notes and edit.

SECTION STEEL WINDOWS UL Labeled Fire-Rated Horizontal Slider (900) Use Tools / Options / View / Hidden Text to view hidden notes and edit. SECTION 08510 STEEL WINDOWS UL Labeled Fire-Rated Horizontal Slider (900) Use Tools / Options / View / Hidden Text to view hidden notes and edit. PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire Rated Steel

More information

Product Guide Specification

Product Guide Specification February 2015 528 Pioneer Parkway Clare, Michigan 48617 Toll Free 800-631-0212 Website www.tranquilsystems.com E-mail sales@tranquilsystems.com Product Guide Specification Tranquil Acoustic Walls with

More information

2016 CDM Smith All Rights Reserved July 2016 SECTION COMPOSITE STEEL FLOOR DECK

2016 CDM Smith All Rights Reserved July 2016 SECTION COMPOSITE STEEL FLOOR DECK PART 1 GENERAL 1.01 SCOPE OF WORK SECTION 05 36 00 COMPOSITE STEEL FLOOR DECK A. Furnish all labor, materials, equipment and incidentals required and install composite steel floor deck complete as shown

More information

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017 SECTION 053100 STEEL DECKING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SILVER LINE BUILDING PRODUCTS

SILVER LINE BUILDING PRODUCTS DIVISION 08 / SECTION 08560, VINYL WINDOWS SILVER LINE BUILDING PRODUCTS SPECIFICATIONS: 2200/2300/2600 Vinyl Single Hung Windows R50/R30 Performance for New Construction GENERAL 1. SECTION INCLUDES 2.

More information

B. Shop Drawings: For metal lockers. Include plans, elevations, sections, details, and attachments to other work.

B. Shop Drawings: For metal lockers. Include plans, elevations, sections, details, and attachments to other work. SECTION 10 5113 - METAL LOCKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Series 4900 Vinyl Single Hung Windows R50/R45/R35/R30 Performance for New Construction

Series 4900 Vinyl Single Hung Windows R50/R45/R35/R30 Performance for New Construction SPECIFICATIONS: Series 4900 Vinyl Single Hung Windows R50/R45/R35/R30 Performance for New Construction GENERAL 1. SECTION INCLUDES 2. RELATED SECTIONS 3. QUALITY ASSURANCE A. General. B. Test Units. 1.

More information

SILVER LINE BUILDING PRODUCTS. Series 1700 Heavy Commercial Aluminum Double Hung. HC65 48 x84 / HC50 60 x96 Replacement Window

SILVER LINE BUILDING PRODUCTS. Series 1700 Heavy Commercial Aluminum Double Hung. HC65 48 x84 / HC50 60 x96 Replacement Window DIVISION 08 / SECTION 08505 METAL WINDOWS SILVER LINE BUILDING PRODUCTS SPECIFICATIONS: GENERAL Series 1700 Heavy Commercial Aluminum Double Hung 1. SECTION INCLUDES 2. RELATED SECTIONS 3. QUALITY ASSURANCE

More information

International, Inc Evans Ave. Phone: Akron, OH Fax: SPECIFICATIONS

International, Inc Evans Ave. Phone: Akron, OH Fax: SPECIFICATIONS International, Inc. 1019 Evans Ave. Phone: 888-566-5400 Akron, OH 44305 Fax: 888-566-5415 Website: www.mwintl.net Email: sales@mwintl.net SPECIFICATIONS This section is based on the FC-300 Demountable

More information

WoodTrends Acoustical Wood Ceiling System BASIC Specification

WoodTrends Acoustical Wood Ceiling System BASIC Specification WoodTrends Acoustical Wood Ceiling System BASIC Specification SECTION 09570 WOOD CEILING / WALLS PART 1 GENERAL 1.00 GENERAL 1.01 SCOPE A. WoodTrends Acoustical Wood Systems covered by this specification

More information

SECTION METAL FRAMED SKYLIGHT. A. Engineering, preparation of fabrication drawings and structural calculations for the entire skylight system.

SECTION METAL FRAMED SKYLIGHT. A. Engineering, preparation of fabrication drawings and structural calculations for the entire skylight system. SECTION 08625 METAL FRAMED SKYLIGHT PART 1 GENERAL 1.01 SECTION INCLUDES: A. Engineering, preparation of fabrication drawings and structural calculations for the entire skylight system. B. Fabrication

More information

Product Guide Specification

Product Guide Specification February 2015 528 Pioneer Parkway Clare, Michigan 48617 Toll Free 800-631-0212 Website www.tranquilsystems.com E-mail sales@tranquilsystems.com Product Guide Specification Tranquil Acoustic Walls with

More information

SECTION METAL ATHLETIC LOCKERS

SECTION METAL ATHLETIC LOCKERS SECTION 10 51 13 - METAL ATHLETIC LOCKERS PART 1 GENERAL 1.1 SECTION INCLUDES A. DESCRIPTION: Furnish and install factory-assembled Heavy-Duty MIG-Welded Metal Lockers, complete, as shown and specified

More information

AMBICO Limited Section and ACOUSTIC STEEL WINDOW FRAME ASSEMBLIES Page 1

AMBICO Limited Section and ACOUSTIC STEEL WINDOW FRAME ASSEMBLIES Page 1 Page 1 This section includes AMBICO Acoustic Steel Window Frames that are glazed as part of a complete assembly. Items are designed to be fixed-in place and shall be inoperable. These items are an integral

More information

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Pan System

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Pan System SECTION 13096 RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Pan System Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13096-1 RF MODULAR PAN SYSTEM PART 1 GENERAL 1.1

More information

COLLEGE OF STATEN ISLAND

COLLEGE OF STATEN ISLAND SECTION 07415 ALUMINUM PLATE CEILING PANELS PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. The extent of panel system work is indicated on the drawings and in these specifications. The following specification

More information

SECTION AWNINGS

SECTION AWNINGS SECTION 10 73 13 AWNINGS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Fixed metal awnings. 1.2 DEFINITIONS A. Awning: An architectural projection that provides weather protection,

More information

A. Submit the following in addition to the standard requirements.

A. Submit the following in addition to the standard requirements. SECTION [13120] OMNIFLEX 300 MODULAR WALL SYSTEM SECTION 1 GENERAL 1.01 SECTION INCLUDES A. This Section specifies all requirements necessary to furnish and install a complete modular wall system including,

More information

1. Seismic Loads: Reference structural drawings.

1. Seismic Loads: Reference structural drawings. SECTION 102213 ~WIRE MESH PARTITIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general prov1s1ons of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION GYPSUM BOARD ASSEMBLIES

SECTION GYPSUM BOARD ASSEMBLIES SECTION 09 21 16 GYPSUM BOARD ASSEMBLIES PART 1 GENERAL 1.1 SECTION INCLUDES A. Metal stud wall and ceiling framing, 20 gauge. B. Metal channel suspended ceiling framing. C. Gypsum board. D. Gypsum sheathing.

More information

St. Monica Food Pantry Hollow Metal Doors and Frames SBA-13105

St. Monica Food Pantry Hollow Metal Doors and Frames SBA-13105 St. Monica Food Pantry 08 1113-1 SECTION 08 1113 - HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUBMITTALS: A. Shop drawings: Indicate door and frame elevations and sections, materials, gauges and

More information

COVER SHEET ELEVATION SHEET SECTION DETAILS (MECHANICALLY ASSEMBLY) SECTION DETAILS (WELDED ASSEMBLY)

COVER SHEET ELEVATION SHEET SECTION DETAILS (MECHANICALLY ASSEMBLY) SECTION DETAILS (WELDED ASSEMBLY) COVER SHEET ELEVATION SHEET SECTION DETAILS (MECHANICALLY ASSEMBLY) SECTION DETAILS (MECHANICALLY ASSEMBLY) SECTION DETAILS (WELDED ASSEMBLY) SECTION DETAILS (WELDED ASSEMBLY) SECTION DETAILS (DOOR ASSEMBLY)

More information

SECTION CRC575 UNITARY CLEANROOM WALL SYSTEM STUDLESS CLEANROOMWALL SYSTEM ME175 3-IN-1 CLEANROOM WALL SYSTEM

SECTION CRC575 UNITARY CLEANROOM WALL SYSTEM STUDLESS CLEANROOMWALL SYSTEM ME175 3-IN-1 CLEANROOM WALL SYSTEM SECTION 13200 CRC575 UNITARY CLEANROOM WALL SYSTEM 175-300 STUDLESS CLEANROOMWALL SYSTEM ME175 3-IN-1 CLEANROOM WALL SYSTEM PART 1 GENERAL 1.01 WORK INCLUDED A. This Section provides the requirements necessary

More information

Series 2900 Vinyl Single Hung Windows R50/R45/R35/R30 Performance for New Construction

Series 2900 Vinyl Single Hung Windows R50/R45/R35/R30 Performance for New Construction SPECIFICATIONS: Series 2900 Vinyl Single Hung Windows R50/R45/R35/R30 Performance for New Construction GENERAL 1. SECTION INCLUDES 2. RELATED SECTIONS 3. QUALITY ASSURANCE A. General. B. Test Units. 1.

More information

SECTION ALUMINUM-FRAMED HIGH PERFORMANCE THERMAL ENTRANCE DOORS

SECTION ALUMINUM-FRAMED HIGH PERFORMANCE THERMAL ENTRANCE DOORS PART 1 GENERAL SECTION 08 1116 ALUMINUM-FRAMED HIGH PERFORMANCE THERMAL ENTRANCE DOORS 1.01 SECTION INCLUDES A. Aluminum-framed storefront, with vision glass. B. Infill panels of glass. C. Aluminum doors

More information

.2 Section Metal Fabrications: Steel channel frame to suit metal door and operator.

.2 Section Metal Fabrications: Steel channel frame to suit metal door and operator. Page 1 This section includes AMBICO Acoustic Steel Sliding Door assemblies which includes electric operators as an integral part of the assembly. This section includes proprietary, descriptive and performance

More information

Alply CLASSIC WALL Architectural Insulated Panel Wall System

Alply CLASSIC WALL Architectural Insulated Panel Wall System SECTION 07 42 13 INSULATED METAL WALL PANELS ALPLY Insulated Panels Alply CLASSIC WALL Architectural Insulated Panel Wall System PART 1 / GENERAL 1.1 SYSTEM DESCRIPTION A. Smooth, non-embossed steel, insulated

More information

Doc

Doc ANC-45 ACCORDION DOOR ACCORDION FOLDING PARTITIONS, WALLS OR DOORS GENERAL NOTES TO SPECIFIER: This specification section has been prepared to assist design professionals in the preparation of project

More information

Project No: Pakenham Branch Library, Pakenham, Ontario Section DECEMBER, 2016 Page 1 of 6

Project No: Pakenham Branch Library, Pakenham, Ontario Section DECEMBER, 2016 Page 1 of 6 DECEMBER, 2016 Page 1 of 6 1 GENERAL 1.01 RELATED SECTIONS.1 Section 01 33 00 - Submittal Procedures..2 Section 07 21 16 - Batt and Blanket Insulation..3 Section 07 92 10 - Sealants..4 Section 09 91 00

More information

SERIES SA30 STEEL/ALUMINUM FIXED DETENTION WINDOWS SECTION 08651

SERIES SA30 STEEL/ALUMINUM FIXED DETENTION WINDOWS SECTION 08651 SERIES SA30 STEEL/ALUMINUM FIXED DETENTION WINDOWS SECTION 08651 PART 1 GENERAL 1.1 DESCRIPTION A. Work Included: 1. Furnish all labor and materials to complete the fabrication of detention windows as

More information

1. Temperature Change: 120 deg F (67 deg C), ambient; 180 deg F (100 deg C), material surfaces.

1. Temperature Change: 120 deg F (67 deg C), ambient; 180 deg F (100 deg C), material surfaces. SECTION 05500- METAL FABRICATIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

UFGS (August 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS (August 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-13 21 48 (April 2006) -------------------------- Preparing Activity: NAVFAC Replacing without change UFGS-13034 (August 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

SECTION METAL DECKING. A. Extent of metal decking is indicated on Plans, including basic layout for the following type of deck required:

SECTION METAL DECKING. A. Extent of metal decking is indicated on Plans, including basic layout for the following type of deck required: PART 1 GENERAL 1.1 WORK INCLUDED A. Extent of metal decking is indicated on Plans, including basic layout for the following type of deck required: 1.2 RELATED WORK 1. Metal Roof Deck. A. Structural Steel:

More information

AMBICO Limited Section and DETENTION STEEL DOOR AND FRAME ASSEMBLIES Page 1

AMBICO Limited Section and DETENTION STEEL DOOR AND FRAME ASSEMBLIES Page 1 Page 1 This section includes AMBICO Detention Steel Door and Frame assemblies that can be fire rated or non-rated. This section relies on both the Canadian Steel Door Manufacturers Association (CSDMA.org)

More information

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017 SECTION 10505 - METAL STUDENT LOCKERS PART 1 - GENERAL 1.01 SCOPE OF WORK A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

A. Pre-Installation Conference: Conduct conference at [project site] <insert location>.

A. Pre-Installation Conference: Conduct conference at [project site] <insert location>. SECTION 074213.23 METAL COMPOSITE MATERIAL WALL PANELS PART 1 GENERAL 1.1 SUMMARY A. Exterior cladding consisting of formed metal composite material (MCM) sheet, secondary supports and anchors to structure,

More information

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including:

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including: Page 1 of 7 SECTION 083925 MECHANICAL ROOM FLOOD DOORS AND FRAMES **Note to Specifier** This specification contains component and configuration options. Where indicated, choose the appropriate choice for

More information

SECTION COMPOSITE METAL WALL PANEL SYSTEM (Accu-Trac Low Profile DS)

SECTION COMPOSITE METAL WALL PANEL SYSTEM (Accu-Trac Low Profile DS) SECTION 07412 COMPOSITE METAL WALL PANEL SYSTEM (Accu-Trac Low Profile DS) PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION METAL ATHLETIC LOCKERS

SECTION METAL ATHLETIC LOCKERS SECTION 10 51 13 - METAL ATHLETIC LOCKERS PART 1 GENERAL 1.1 SECTION INCLUDES A. DESCRIPTION: Furnish and install factory-assembled Heavy-Duty MIG-Welded Metal Lockers, complete, as shown and specified

More information

Grimes Elementary School Renovation September 7, 2010 Houston Independent School District SECTION 102800 - TOILET, BATH, AND LAUNDRY ACCESSORIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general

More information

SECTION METAL EQUIPMENT LOCKERS

SECTION METAL EQUIPMENT LOCKERS SECTION 10 51 13 - METAL EQUIPMENT LOCKERS PART 1 GENERAL 1.1 SECTION INCLUDES A. DESCRIPTION: Furnish and install factory-assembled Heavy-Duty MIG-Welded Metal Lockers, complete, as shown and specified

More information

Specifications for FL-100 Soffit Panel

Specifications for FL-100 Soffit Panel Union Corrugating Company Specifications for FL-100 Soffit Panel SECTION 07410 METAL SOFFIT PANELS PART 1 GENERAL 1.1 DESCRIPTON A. Section Includes: 1. Preformed metal soffit panel system 2. Associated

More information

Guideline Specifications GORDON MARQUIS LINEAR CEILING PANEL SYSTEMS

Guideline Specifications GORDON MARQUIS LINEAR CEILING PANEL SYSTEMS Guideline Specifications GDON MARQUIS LINEAR CEILING PANEL SYSTEMS Note to Specifier: MARQUIS Systems are a finished decorative/functional product and should be specified per The Construction Specifications

More information

Gensler 2014/06/16 Hertz Global Headquarters ISSUE FOR BUILDING PERMIT Estero, Florida SECTION

Gensler 2014/06/16 Hertz Global Headquarters ISSUE FOR BUILDING PERMIT Estero, Florida SECTION SECTION 072700 VAPOR PERMEABLE AIR BARRIER LIQUID MEMBRANE PART 1 GENERAL 1.1 GENERAL REQUIREMENTS A. The Work of this Section, as shown or specified, shall be in accordance with the requirements of the

More information

C. All anchors, brackets, and hardware attachments necessary to complete the specified structural assembly, when included within project scope.

C. All anchors, brackets, and hardware attachments necessary to complete the specified structural assembly, when included within project scope. SECTION 08 4519 - POLYCARBONATE WALL SYSTEM PART 1 GENERAL 1.1 SECTION INCLUDES A. Exterior System: The design, manufacture and installation of an aluminum and polycarbonate insulating translucent system.

More information

SECTION DETAILS (MECHANICALLY ASSEMBLY)

SECTION DETAILS (MECHANICALLY ASSEMBLY) COVER SHEET ELEVATION SHEET SECTION DETAILS (MECHANICALLY ASSEMBLY) SECTION DETAILS (MECHANICALLY ASSEMBLY) SECTION DETAILS (WELDED ASSEMBLY) SECTION DETAILS (WELDED ASSEMBLY) SECTION DETAILS (DOOR ASSEMBLY)

More information