Transcription

1 Section 5: Tauranga City Council

2 Contents Scope 5.A General 5.A.1 5.A.2 5.A.3 5.A.4 5.A.5 5.B. Design Standard 5.B.1. 5.B.2 Overall System Design 5..B.3 Secondary Flows 5.B.4. Freeboard 5.B.5 5.B.6 5.B.7 5.B.8 5.B.9 5.B.10 High Levels of Groundwater 5.C Primary System 5.C.1 Connection Destination 5.C.2 5.C.3 Manhole Spacing 5.C.4 5.C.5 Subdivision 4 Lots or More 5.C.6 Infill Subdivision 3 Lots and Less (includes existing Lot) 5.C.7 5.C.8 5.D Service Connections 5.D.1 5.D.2 5.D.3 5.D.4 5.D.5 5.D.6 5.E Manholes 5.E.1 5.E.2 5.E.3 5.E.4 5.E.5 2

3 5.F Layout 5.F.1 5.F.2 5.F.3 5.G Pipe Materials 5.G.1 5.G.2 5.G.3 5.H Bedding and Protection 5.H.1 5.H.2 5.H.3 5.H.4 5.H.5 5.H.6 5.I Testing and Acceptance 5.I.1 5.I.2 5.I.3 5.I.4 Pipe End Caps 5.J Close Proximity Rules 5.J.1 5.J.2 Dispensation 5.J.3 Ancillary Buildings May be Exempt 5.J.4 Carports, Decks and Sunrooms 5.K Resource Consents 5.K.1 5.K.2 5.L Open Stream Systems 5.L.1 5.L.2 5.L.3 5.L.4 5.M Retention Ponds & Detention Ponds 5.M.1 5.M.2 5.M.3 Calculation Criteria 3

4 5.N Pump stations 5.O Construction Provisions 4

5 SECTION 5: STORMWATER DRAINAGE Scope The District Plan chapters; 15, 17, 18, 19 and 20 provide the mechanism for which the Council can provide provisions, guidelines and specifications for stormwater infrastructure, management and disposal. 5.A General 5.A.1 Most developments will modify the pre-development drainage pattern and a stormwater drainage system is typically designed and constructed to adequately manage this situation. The primary goals of a stormwater system are to minimize nuisance flooding and flows, and to minimize the effects on adjacent land. 5.A.2 Affects on the pre-development environment are becoming more important as time goes on. Various methods are available to limit such affects. Auckland Regional Council publication TP124 Low Impact Design Manual is a useful document that gives consideration to the relevant issues and offers various techniques and solutions. Designers are encouraged to use this document where appropriate to minimize affects on the environment. TP124 is a document for the Auckland Region. While this limits its strict applicability in the Bay of Plenty the majority of the document is relevant to the issues in this Region. The economic life of any piped system shall not be less than 100 years. 5.A.3 The stormwater drainage system shall be capable of serving the entire natural upper catchment to provide adequate protection against flooding. The potential of the entire natural upper catchment is defined as the full development of the area as zoned under the current District Plan at time of consent. 5.A.4 The consent holder shall design and construct a stormwater drainage system that will provide an adequate gravity method of disposing of the flow from each allotment or intended building site, including all hardstand areas. Designer shall describe the effect of the proposed development on the upstream, downstream and neighbouring properties The system (5.A.3-4) may not need to be constructed but it must be demonstrated that it can be successfully constructed at the time of building consent and effectively maintained for the life of the building. 5

6 5.A.5 Where a stormwater drainage system has been or is to be installed by the Council to serve the natural catchment, contributions on an area basis shall be made in terms of the development impact fees or other agreed cost sharing arrangement. 5.B Design Standard 5.B.1 Unless otherwise required, the design of the stormwater system shall be in accordance with one of the following techniques: (a) IPENZ Procedure for Hydrological Design of Urban Systems, December 1980; or (b) an approved catchment/stormwater computer modelling system. For (b) above the Council s Engineer can confirm an acceptable modelling system on request 5.B.2 Overall System Design The design storm, Annual Exceedance Probability (AEP) return period shall be as follows: Overall system (primary and secondary) in all urban areas 50 year storm (2% AEP). Primary piped system in all urban areas minimum 10 year storm (10% AEP). Bridge structures 100 year storm (1% AEP) 5.B.3 Secondary Flows Flows generated by events that exceed the capacity of the primary system shall be conveyed by a secondary system. calculations shall demonstrate the performance of the overall system and the primary piped system. The secondary system will typically consist of ground shaping to manage surface flows along flowpaths. Such secondary flowpaths are typically protected by easement. Piped secondary systems are discouraged due to the risk of blockage. Piped secondary systems may be permitted if a totally separate and adequate entry system is provided. 6

7 5.B.4 Freeboard Freeboard above the design top water flood/stormwater level shall be provided as shown. Floor levels may be imposed by consent notice to achieve minimum freeboard. The minimum building platform level shall be defined by the Consent Holder s Representative prior to the s224 Application. This shall incorporate the component of freeboard from the table below. The figures required below are to be read in conjunction with the minimum free board requirements of the NZ Building Code. For all major City infrastructure the following will take precedence. Type of building Non habitable residential buildings, garage floors. Commercial and Industrial. Dwellings (habitable floors) Major Facilities 50 yr Return Period (2% AEP) 200mm 300 mm 500mm 500mm 5.B.5 Drawing D1 details rainfall intensities to be used for the drainage element being designed. 5.B.6 The designer shall identify areas that will be prone to inundation/flooding. This includes ponding areas and secondary flow paths. 5.B.7 The piped system shall be designed to cater for the design flow, without surcharge, based on a Colebrook -White pipe roughness co-efficient Ks=1.50 for pipes up to and including 450 mm diameter and Ks=0.60 for larger concrete pipes. K values for other materials are to be as per manufacturer s specifications or requirements. Inundation information is used to update GIS records identifying land within the District that is prone to inundation or potentially prone to inundation. Diameters quoted refer to nominal internal diameters in millimetres 7

8 5.B.8 The secondary stormwater system shall safely convey stormwater without undue nuisance. Acceptable solutions include: Temporary ponding on local and collector roads Temporary flow along local and collector roads. Flow across private property. Flow must be in a defined channel or swale, clear of existing or future building sites and protected by an easement in favour of the Council and/or Consent Notice which prohibits ground reshaping and the erection of any barriers. 5.B.9 Where the design full pipe velocity is less than 1.3m/s, then measures shall be taken to allow for silt collection. This shall typically take the form of unbenched manhole sumps below lowest invert level. The extra depth required is half the line diameter or as otherwise approved. 5.B.10 High Levels of Groundwater In areas of high or potentially high groundwater, designers shall provide a method for allowing excess groundwater into the stormwater system in a controlled manner. Such a solution may incorporate perforated inlet pipes together with drainage rock and geotextile. Temporary means of the same order as the critical storm s time of concentration Removal of silt from flat lines costs a significant amount of money. Removal from sumps reduces costs dramatically. It is acknowledged that this velocity is greater than that in NZS4404 but this is because full pipe velocities are only achieved in a 10 % AEP event. "TCC has experienced early asset failures where groundwater has entered the stormwater system in an uncontrolled manner and transported surrounding material into the system causing substantial voids externally and excessive silt internally. Controlled entry of excess porewater pressure (but not fines) is the preferred method of dealing with this situation." 8

9 5.C Primary System 5.C.1 Connection Destination The following destinations are possible for stormwater collected on a lot. Any destinations must be approved by Council: (a) (b) (c) (d) (e) A piped system: The first choice in most situations, applies to green and brown field, and infill subdivisions. An open drain: Generally permitted, but only where there is an existing open public drain within or beside the lot and a piped system is not available, or desirable. A road sump or bubble-up sump: These options are not encouraged and are not permitted in greenfield situations. A public roadside kerb and channel: Permitted provided the kerb connection can be shown not to cause or increase flooding in the downstream catchment for the street. See drawing D2a. Soakage: Disposal of stormwater by ground soakage or ground water recharge is suitable in some areas of Tauranga and most areas of Papamoa & Mount Maunganui. In these areas ground soakage is generally permitted where soil and groundwater characteristics are favourable and no adverse run off effects are caused. Design, construction and maintenance of soakage systems shall be in accordance with the Guidelines for Use of Soakage in Tauranga City shown in Appendix D of this Code. 9

10 Where ground soakage is permitted then this usually provides for; Soak Holes/Soakage Rings/Soak Pits Soak holes (soakage pits) are usually utilised in Tauranga and soakage rings in Mount Maunganui and Papamoa. Each method must be designed to cater for the on site disposal of stormwater in a 10% AEP 10 minute storm. Each system must be tested using a soakage test to confirm that the rates of soakage for the system will meet the required disposal rates. Where the rates of soakage do not meet the required disposal rate then the disposal system will need to incorporate storage to cater for the design storm above or a reticulated system is to be provided. Ground soakage systems shall be designed with a factor of safety built into them to ensure that the system is able to cater for the design life of the building. They shall be provided with silt trap mechanisms and inspection lids to ensure they are able to be maintained. Secondary overflow must not enter a building during a 2% AEP storm. All specific designed ground soakage systems will be Consent Noticed prior to any building consent, requiring the ground soakage system to be complied with on an ongoing basis. Alternative Soakage Other methods of disposal that can be used in "soakage" areas are soakage fields or storage modules with soakage or slow release to the ground. These must be specifically designed for the design storm above and take into account access, silt and maintenance issues. Low Impact Disposal Alternative and innovative stormwater disposal use, where appropriate, shall be considered by Council, especially where low impact disposal systems are proposed. Such disposal methods could include swales, rain gardens, or wetland treatment of areas instead of the conventional retention ponds or in conjunction with ponds. (f) Pumps pumps are not permitted in Tauranga City. 10

11 5.C.2 The primary piped stormwater reticulation system shall consist of 225mm diameter and larger pipelines, laid to a true grade and line between access manholes located at each change of direction and grade. Manholes are also required at the upper end of all primary, piped stormwater reticulation. 5.C.3 Manhole Spacing Manhole spacings shall not exceed 120m for pipelines up to 1000mm diameter, above which spacings may extend to 200m. Each branch line shall join the main line at a manhole junction, except: 225/300mm diameter sump leads may be saddled into 600mm diameter pipes or larger, using a factory made fitting. Branch lines 300mm diameter or smaller may be saddled onto pipes 1200mm diameter or larger provided a manhole is supplied on the branch line within 50m of the main line, using a factory made fitting. 5.C.4 Secondary flowpaths shall be in accordance with s5.b.8 above. 5.C.5 Subdivision 4 lots or more Minimum pipe sizes are 225mm diameter for reticulation and 100mm diameter for laterals. In addition, the following shall apply: (a) (b) (c) Lateral with single connection (out of manhole). 100mm dia. up to 50m. Above 50m normal reticulation standards apply, (i.e. 150mm min. dia. pipeline with terminating manhole). 150mm dia. pipes must be used under all road reserves. Lateral with two or three connections (out of manhole). 150mm dia. lengths up to 50m. Above 50m normal reticulation standards apply. Lateral out of line servicing one allotment. 100mm dia. up to 24m. 150mm dia. pipes must be used under all road reserves. 11

12 5.C.6 Infill Subdivision 3 lots and less (includes existing Lot) Reticulation of infill subdivisions shall comply with the following criteria: within the parent lot is to remain private and be protected by appropriate easements. lines are to be separated at the point of connections to the Council s reticulation system and remain separate for each lot unless approved by Council. Infill subdivisions are to be reticulated on a site by site basis to the approval of Council. All private drainage works to be constructed in accordance with NZ Building Code regulations. All private drainage works to be constructed by a Registered Drainlayer. Should the consent holder upgrade and construct the drainage reticulation in accordance with this Code for servicing (other than 5.C.6), then the drains will become public assets. It is recognised that infill subdivisions require flexibility in their reticulation layout. However, normal trade practises and standards still apply to ensure that the desired service life is still achieved. Common private drains are not encouraged so as to alleviate the friction that sometimes occurs between neighbours when shared services are involved. 5.C.7 Where practicable and where connection is to be within 6m of the manhole the connection shall be to the manhole. 5.C.8 Where the main line is within 5m of the property boundary a separate connection shall be provided to each allotment. 5.D Service Connections 5.D.1 To provide a service connection to each allotment, a minimum 100mm diameter line shall be extended from the main reticulation system to terminate at a minimum distance of 1.0m within each site, whether created by cross lease, unit title or fee simple subdivision. In all cases service connections shall serve as much of the site as practically possible, but at least the possible building site. 5.D.2 Service connections shall be brought to within 1.2m of the final ground surface and be constructed in accordance with Drawing D2 or D3 (for pipe depths greater than 2.5m). 5.D.3 All service connections to the site boundary shall form part of Councils public assets. 12

13 5.D.4 Each Connection shall be marked by a 50 x 50mm timber stake which shall extend from the invert to a minimum of 300mm above finished ground level. A blue PVC marker tape shall be attached to the connection pipe, brought up and tied to the top of the stake. The end cap shall be painted blue to distinguish it from a wastewater connection. 5.D.5 All connections to an existing stormwater network shall be undertaken in accordance with S2.8 of this Code. 5.D.6 The following connections can be connected directly to the stormwater main. These connections are all to be factory manufactured. Any combinations outside the following shall connect via a manhole. 100mm diameter connection can connect to 100mm diameter line or greater. Above diameter and 150mm diameter connection can connect to 150mm diameter line or greater. Above diameter and 225mm diameter connection can connect to 600mm diameter line or greater. 300mm diameter connection can connect to 1200mm line or greater. 5.E Manholes 5.E.1 Standard manholes shall be constructed as detailed on Drawings D4 to D11. For Manholes of greater depth than 5m refer to D12. Shallow manholes (Drawing D5) may be used in certain circumstances subject to the approval of Council. 5.E.2 Standard 1050mm manhole risers are not suitable where either pipes are larger that 675mm diameter or where multiple pipes enter a manhole causing loss of manhole wall. Designers shall upsize manholes in these cases to maintain wall integrity. For large diameter manhole risers the lid may be lowered to 2.0m or more above invert with a 1050mm throat above, provided that the lid is of suitable strength. 13

14 5.E.3 The fall through a manhole is either: (a) (b) (c) The invert of the outlet pipe from a manhole shall be 20mm plus 0.5mm per degree of horizontal angle change between the two lines lower than the lowest incoming line invert. The soffit of the outlet pipe shall be level with or below the lowest incoming line s soffit. The extension of the grade of the steepest pipe whichever is the greatest. 5.E.4 All stormwater manhole covers to be painted blue (with road marking paint). 5.E.5 Flexible joints shall be provided on concrete pipes within 0.5m of the manhole for pipes of 450mm diameter or less. 5.F Layout 5.F.1 Reticulation lines shall be sited, where possible on the low side of the proposed sites having more than 1.5m crossfall and in areas that will not reduce the building area available, ie within front, side and rear yard areas. 5.F.2 The minimum desirable cover to all pipes from finished ground level shall generally be 600mm in private land and 1.2m for road crossings, (other than sump leads) provided there is generally a minimum depth to invert, at the service connection point, of 1.2m from the lowest point in the building site. 5.F.3 Pipelines within private property shall generally run parallel to lot boundaries. Where the centreline of a pipeline is further than 1.5m from a lot boundary or not parallel to a lot boundary an easement in favour of Council and/or Consent notices shall be provided to ensure its protection. 5.G Pipe Materials 14

15 5.G.1 Council permits stormwater drainage systems to be constructed of the following materials: Polyethylene in accordance with AS4130. Polypropylene in accordance with AS/NZS5065. PVC in accordance with AS/NZS DN 100mm and 150mm to have minimum wall thickness of 4.1mm and 6.3mm respectively, defined as grade SN 16 for up to 5m depth. DN175 mm and larger to be grade SN 8 minimum or equivalent. Reinforced concrete in accordance with NZS Other pipes, arches and box structures on a specific design basis only. (i) (ii) SN 16 is the recommended equivalent of SEC in DN 100 and 150 SN 8 is the recommended equivalent of SEC in DN 175 or larger. (iii) Stiffness, NOT wall thickness, is the controlling feature in AS/NZS The actual ID (and therefore flow rate) of plain wall pipe is likely to be greater than the same size / SN of sandwich construction pipe. 5.G.2 All joints shall be: Polyethylene: Butt fusion welding to AS2033 with flanged end gibault joints allowable at endpoints. Polypropylene: All jointing and branching to the manufacturers specifications. Structural design and installation and testing requirements for flexible buried pipelines are given in AS/NZS PVC. Factory made spigot and socket, rubber ring jointed to NZS Flush joints are permitted on 1050mm diameter and larger pipes, provided no ground water or geotechnical requirements dictate the need for fully sealed joints. Joints are to be RRJ or steel banded, to manufacturers specifications. 5.G.3 All fittings and service connections to pipes shall be factory fabricated of compatible material to the proposed system chosen and comply with the relevant standards. PVC fittings and service connections to be in accordance with AS/NZS DN 100mm and 150mm injection moulded fitting to be the closest grade currently available to the specified grade. DN 175mm and larger factory fabricated fitting to be made of same grade materials as specified for the pipeline. 5.H Bedding And Protection 5.H.1 All drainage lines shall be thoroughly bedded, haunched and surrounded as in the Drawing D13 unless installed by no-dig technology as per Drawing D4. 15

16 5.H.2 All drainage lines shall be designed and constructed to withstand all the likely loads they will be subject to during the life of the system. The load carrying capacity in relation to their installation conditions shall be calculated in accordance with AS/NZS 3725 Loads on Buried Concrete Pipes and AS/NZS 2566 Plastics Pipe laying Design where appropriate. The manufacturer s specification for bedding shall take precedence. 5.H.3 For drainage pipelines laid at grades steeper than 20% in grade, anti-scour blocks located at pipe joints, not exceeding 6m spacing, are required, as shown on Drawing D15 or as otherwise approved. 5.H.4 Where pipe servicing in the carriageway is required, the trench re-instatement works shall follow the minimum requirements shown in Section 4 drawing R32. Pipe trenches within a carriageway shall be backfilled using an approved hardfill placed immediately above the pipe surround and compacted in layers not exceeding 200mm in depth. In existing sealed streets, the top section of the trench shall be backfilled as specified by TNZ M/4. The depth of base course and type of finishing coat seal shall conform at least to the standard of the existing road construction, but may require being greater. This drawing specification is the minimum standard for all services under the carriageway. 5.H.5 Where the minimum cover as outlined in Section 4.F.2 cannot be achieved, specific design of pipe and cover is required to achieve manufacturers requirements. Concrete capping shall be designed on a site by site basis taking into account both pipe protection and roading integrity requirements. 5.H.6 Where public drains are located within rights of way or private access legs all other utility services such as power, telephone and gas shall be located 300mm horizontally clear of the pipe. 5.I Testing And Acceptance 5.I.1 Prior to acceptance of the completed stormwater drainage system, the subdivider s representative shall supply Council with As Built drawings of the work, including any secondary flowpaths, open channel systems and areas prone to inundation, together with certification and a Certificate of Subdivision Construction (Drawing D19). All testing shall be carried out when backfilling is completed and prior to carriageway surfacing. 16

17 5.I.2 5.I.3 pipes shall not be pressure tested unless specifically required by Council. The Consent Holder s Representative s test will be undertaken in the presence of a Council Engineer. Council shall request the Consent Holder s Representative to undertake a CCTV inspection of pipelines as and when required prior to acceptance. Specifications are given in appendix C. Council may request either a water or air pressure test. 5.I.4 Pipe End Caps See s5.d.4 for requirement. To enable the distinction between stormwater (blue) and wastewater (white) end cap piping when in close proximity. 5.J Close Proximity Rules 5.J.1 No building shall be built over a stormwater pipeline or closer than the greater of: 1.5m from the outside edge of the pipeline. The depth to the centre line of the pipeline from the existing/proposed ground surface, plus the diameter of the pipeline. 5.J.2 Dispensation Dispensation may be approved to site the building to within 800mm off the side of the pipe subject to the following conditions: The depth of the pipeline invert is less than 3.0m deep from the existing/proposed ground surface; Specifically designed footing/piles must be installed to 200mm below the pipeline invert; That all connections be a minimum of 1.0m outside the building; That all buildings be at least 0.5m off the outside wall of manhole structures. 5.J.3 Ancillary buildings may be exempt: Garages (single and double, maximum 7.2m), provided they are detached and do not form an integral part of the house shall be allowed to be built over pipelines, subject to the following conditions: Corner foundations are a minimum of 800mm off the pipeline centre line. Additional foundation requirements of piles are to be installed 200mm below the pipeline invert, a minimum of 800mm either side of the pipeline where it enters and exits the building. Council must be satisfied with the location of the building. Connections closer than 1.0m to the buildings shall be relocated. 17

18 5.J.4 Carports, Decks and Sunrooms These structures may be sited over pipelines provided: There is no connection point closer than 1.0m to the building; The structure is designed such that it can be dismantled easily in sections (bolting is the preferred method of construction); 5.K Resource Consents 5.K.1 Where resource consents from the Regional Council are required for the diversion and or discharge of stormwater, the consent holder is responsible for making the necessary application and obtaining such resource consents before physical work commences on site. 5.K.2 Developers will typically wish to transfer resource consents (and any associated conditions) to the Tauranga City Council when assets are vested. Council reserves the right to decline to accept consents if doing so would be detrimental to the Council s interests. Generally however the Council is prepared to accept consents provided that: In parallel with the EBOP application, subdividers are encouraged to submit copies of stormwater discharge consent applications to Tauranga City Council to assist future transfer. The conditions are considered to be fair and reasonable. The required works have been completed. Full documentation is supplied including the original application, drawings and compliance certification from the Regional Council. 5.L Open Stream Systems 5.L.1 Where natural open stream systems or formed channels are to be incorporated in the stormwater drainage system, they shall generally be located within a drainage reserve of sufficient width to contain the full design flood flow together with a freeboard. Such reserves shall generally have a batter of 20% (1 in 5) and where access for maintenance is required shall include a 4m wide access berm for the full length. Open streams, drains and channels through subdivisions can create maintenance and safety misunderstandings and difficulties. Designers need to carefully consider and describe proposed ownership/maintenance arrangements including easements and consent notices etc. 5.L.2 The flow characteristics of natural open stream systems shall be based on the likely long term stream conditions. 18

19 5.L.3 To encourage the best use of the open stream systems the drainage reserves shall be linked with other reserves and open spaces such as school sites, to accommodate off road pedestrian and cycle access. Access points for public use and maintenance shall be provided at regular intervals along the system together with footpath and pedestrian bridges, as may be defined in the resource consent. 5.L.4 Where natural open stream areas form part of the stormwater drainage system they shall be cleared of all unsuitable plant growth and replanted to a landscape design approved by Council. These works shall include protection of the low flow channel against scour and erosion of the stream bed where necessary. Access shall be provided for maintenance purposes. 5.M Retention & Detention Ponds 5.M.1 detention ponds are an accepted method of improving stormwater quality and reducing downstream flow rates. 5.M.2 Pond design shall follow the guidance of Auckland Regional Council Technical Publication Number 10. Cost of cleaning these ponds is significant hence Council has decided to charge a development contribution bases on 2 cleans in first 5 years Specific points to focus on are: Side slopes with safety considerations. Ease of maintenance including mowing and silt cleanout. Shape and contour for amenity value. An effective outlet structure. Overflow. 5.M.3 Calculation criteria The calculation criteria for retention and detention ponds shall be in accordance with the above ARC Technical Publication #10. 5.N Pumpstations pump stations for use in the stormwater system are generally not permitted. Their use will only be considered in exceptional circumstances. Approval of Council is required. 19

20 5.O Construction Specification The stormwater network shall be constructed in accordance with the construction specifications provided in Appendix C of this Code. 20

TAURANGA CITY COUNCIL

TAURANGA CITY COUNCIL Code of Practice for Development TAURANGA CITY COUNCIL SECTION 4 Stormwater Drainage 4. STORMWATER DRAINAGE MINIMUM REQUIREMENTS 4.A General 4.A.1 Most developments will modify the predevelopment drainage

More information

SECTION 6 STORMWATER AND LAND DRAINAGE

SECTION 6 STORMWATER AND LAND DRAINAGE SECTION 6 STORMWATER AND LAND DRAINAGE Final Version, Approved September 2003 Section 6 and Land Drainage Contents 6.1 PERFORMANCE STANDARDS... 2 6.1.1 General... 2 6.2 MEANS OF COMPLIANCE... 3 6.2.1 General...

More information

DESIGN STANDARD TABLE OF CONTENTS

DESIGN STANDARD TABLE OF CONTENTS DESIGN STANDARD DS-5 STORMWATER TABLE OF CONTENTS DS-5.1 General...1 DS-5.2 Minimum Requirements...1 DS-5.3 Regional Council Requirements...1 DS-5.4 Design...2 DS-5.5 Conveyance - Primary and Secondary

More information

South Waikato District Council Code of Practice for Subdivision and Development PART 4. Drainage. Part 4: Drainage 56

South Waikato District Council Code of Practice for Subdivision and Development PART 4. Drainage. Part 4: Drainage 56 PART 4 Drainage Part 4: Drainage 56 PART 4: DRAINAGE 401 STORMWATER DRAINAGE 401.1 General The stormwater drainage system shall be available to any building site within urban development or subdivision.

More information

STORMWATER BUBBLE UP PIT

STORMWATER BUBBLE UP PIT Cast iron swing grate in cast iron frame A Nominal 90 mm inlet SECTION A x ID concrete chamber. Available chamber depths 400mm or 600mm deep CHAMBER PLAN Stormwater pipe House Chamber location in vehicle

More information

CONTENTS. Section 6 Stormwater and Land Drainage CODE OF PRACTICE FOR SUBDIVISION AND DEVELOPMENT 6.1 SCOPE... 2

CONTENTS. Section 6 Stormwater and Land Drainage CODE OF PRACTICE FOR SUBDIVISION AND DEVELOPMENT 6.1 SCOPE... 2 CONTENTS 6.1 SCOPE... 2 6.2 PERFORMANCE STANDARDS... 2 6.2.1 General... 2 6.3 MEANS OF COMPLIANCE... 4 6.3.1 General... 4 6.3.2 Resource Consents... 6 6.3.3 Gravity Mains Reticulation Layout... 6 6.3.4

More information

SPECIFICATION FOR PIPE CULVERT CONSTRUCTION

SPECIFICATION FOR PIPE CULVERT CONSTRUCTION SPECIFICATION FOR PIPE CULVERT CONSTRUCTION 1. SCOPE Pipe culverts shall be constructed in accordance with this specification and in conformity with the lines, levels and cross-sections shown on the drawings.

More information

SECTION STORM DRAINAGE DESIGN, GRADING, AND WATER QUALITY TECHNICAL CRITERIA TABLE OF CONTENTS PAGE 402 STORM DRAINAGE DESIGN CRITERIA 400-1

SECTION STORM DRAINAGE DESIGN, GRADING, AND WATER QUALITY TECHNICAL CRITERIA TABLE OF CONTENTS PAGE 402 STORM DRAINAGE DESIGN CRITERIA 400-1 CITY OF THORNTON Standards and Specifications Revised: October 2012 SECTION 400 - STORM DRAINAGE DESIGN, GRADING, AND WATER QUALITY TECHNICAL CRITERIA TABLE OF CONTENTS PAGE 401 GENERAL PROVISIONS 400-1

More information

CHECKLIST FOR STREETS, INLETS, AND STORM SEWER DESIGN

CHECKLIST FOR STREETS, INLETS, AND STORM SEWER DESIGN CHECKLIST FOR STREETS, INLETS, I. STREET CLASSIFICATION AND DESIGN CRITERIA A. Determine drainage classification for the roadway section using Table 7-1 or Table 7-2. B. Determine the allowable flow depth

More information

5.1 INTRODUCTION OBJECTIVES PERFORMANCE CRITERIA KEY REFERENCES... 2

5.1 INTRODUCTION OBJECTIVES PERFORMANCE CRITERIA KEY REFERENCES... 2 CONTENTS SECTION 5 - STORMWATER 5.1 INTRODUCTION... 1 5.2 OBJECTIVES... 1 5.3 PERFORMANCE CRITERIA... 1 5.4 KEY REFERENCES... 2 5.5 GENERAL DESIGN REQUIREMENTS... 3 5.5.1 Design Methodology... 3 5.5.2

More information

7 STORMWATER AND DRAINAGE

7 STORMWATER AND DRAINAGE 7 STORMWATER AND DRAINAGE 7.1 Introduction The purpose of Council s stormwater engineering standards is to provide design guidance and minimum standards for the design and construction of stormwater management

More information

Contact the Jurisdictional Engineer for materials allowed by each jurisdiction.

Contact the Jurisdictional Engineer for materials allowed by each jurisdiction. Design Manual Chapter 3 - Sanitary Sewers 3C - Facility Design 3C-1 Facility Design A. Capacity of Pipe Pipe sizes 15 inches and smaller should carry the peak flow at a depth of no more than 0.67 of the

More information

WATER 6.1 GUIDELINES

WATER 6.1 GUIDELINES 6-1 6.0 WATER 6.1 GUIDELINES The requirements of the Queensland Water Resources Commission Guidelines for Planning and Design of Urban Water Supply Schemes shall be followed in general. The requirements

More information

Highway Drainage 1- Storm Frequency and Runoff 1.1- Runoff Determination

Highway Drainage 1- Storm Frequency and Runoff 1.1- Runoff Determination Highway Drainage Proper drainage is a very important consideration in design of a highway. Inadequate drainage facilities can lead to premature deterioration of the highway and the development of adverse

More information

Part 5: Stormwater and Land Drainage

Part 5: Stormwater and Land Drainage Part 5: Stormwater and Land Drainage Part 5: Stormwater and Land Drainage Contents 5.1 Referenced Documents...5-3 5.1.1 Source documents... 5-4 5.2 Introduction... 5-4 5.2.1 Philosophy... 5-4 5.2.2 Objectives...

More information

SECTION 3 DRAINAGE. 3-1 General. 3-2 Drainage Ordinances and Legal Requirements

SECTION 3 DRAINAGE. 3-1 General. 3-2 Drainage Ordinances and Legal Requirements SECTION 3 DRAINAGE 3-1 General All Drainage plans for proposed development shall be prepared by a Professional Engineer registered in Virginia, except as noted below. Further, their seal and signature

More information

Stormwater Local Design Manual For Houston County, Georgia

Stormwater Local Design Manual For Houston County, Georgia Stormwater Local Design Manual For Houston County, Georgia Adopted November 15, 2005 TABLE OF CONTENTS 1. FORWARD... 1 2. GENERAL LEVEL OF SERVICE STANDARDS... 2 2.1. DETENTION REQUIREMENTS... 2 2.1.1.

More information

MODEL Stormwater Local Design Manual. City of Centerville

MODEL Stormwater Local Design Manual. City of Centerville MODEL Stormwater Local Design Manual City of Centerville Adopted December 6, 2005 TABLE OF CONTENTS 1. FORWARD... 1 2. GENERAL LEVEL OF SERVICE STANDARDS... 1 2.1. DETENTION REQUIREMENTS... 1 2.1.1. Discharge

More information

STORMWATER AND EROSION CONTROL PERMIT

STORMWATER AND EROSION CONTROL PERMIT STORMWATER MANAGEMENT AND EROSION CONTROL PERMIT INSTRUCTIONS AND INFORMATION Any project that involves the disturbance of ANY quantity of land requires the applicant to receive approval for the project

More information

LOT GRADING GUIDELINES

LOT GRADING GUIDELINES LOT GRADING GUIDELINES RESIDENTIAL PROPERTIES The Drainage Bylaw 16200 came into effect on June 1, 2013 replacing previous versions of the Surface Drainage Bylaw 11501. This Bylaw requires that all single

More information

Town of New Tecumseth Engineering Design Criteria and Standards for Subdivisions and Capital Works Projects

Town of New Tecumseth Engineering Design Criteria and Standards for Subdivisions and Capital Works Projects 2.0 ROADWAYS 2.1 Road Classification 2.1.1 Standard Drawing Classification All Road Widths and Road Allowances shall be designed in accordance with the most recent Town of New Tecumseth Standards: TNT.SD

More information

Rural-Residential Rural-Residential Explanatory Statement Significant Issues Objectives and Policies...

Rural-Residential Rural-Residential Explanatory Statement Significant Issues Objectives and Policies... Section Contents Rural-Residential... 2 16. Rural-Residential... 2 Explanatory Statement... 2 16.1 Significant Issues... 2 16.2 Objectives and Policies... 3 16.3 Activity Lists... 3 16.4 Activity Performance

More information

Index. Composition and Order of Plan Set. Utility Plan... 5

Index. Composition and Order of Plan Set. Utility Plan... 5 City of Des Plaines Public Works and Engineering Department Revised-October 5, 2012 Index Composition and Order of Plan Set Title Page Number Cover Sheet... 1 Requirements for Site Development... 2 Grading

More information

Chapter 5 Hydraulic Structures

Chapter 5 Hydraulic Structures Chapter 5 Hydraulic Structures 5.1 Flow Splitter Designs 5.1.1 General Design Criteria A flow splitter must be designed to deliver the WQ design flow rate specified in this volume to the WQ treatment facility.

More information

4.8. Subsurface Infiltration

4.8. Subsurface Infiltration 4.8. Subsurface Infiltration Subsurface infiltration systems are designed to provide temporary below grade storage infiltration of stormwater as it infiltrates into the ground. Dry wells, infiltration

More information

SECTION FACILITY SANITARY SEWERS

SECTION FACILITY SANITARY SEWERS SECTION 22 13 13 FACILITY SANITARY SEWERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

PART 3 - STANDARDS FOR SEWERAGE FACILITIES DESIGN OF STORM SEWERS

PART 3 - STANDARDS FOR SEWERAGE FACILITIES DESIGN OF STORM SEWERS PART 3 - STANDARDS FOR SEWERAGE FACILITIES 3.3 - DESIGN OF STORM SEWERS 3.301 Design of Storm Sewers A. General Information B. Investigations and Surveys C. Special Projects 3.302 Design Criteria for Storm

More information

Building over or close to a public sewer

Building over or close to a public sewer Building over or close to a public sewer Place holder image thameswater.co.uk/developerservices Building over or close to a public sewer Did you know Thames Water is legally responsible for more than 100,000

More information

Chapter 7. Street Drainage. 7.0 Introduction. 7.1 Function of Streets in the Drainage System. 7.2 Street Classification

Chapter 7. Street Drainage. 7.0 Introduction. 7.1 Function of Streets in the Drainage System. 7.2 Street Classification 7. Introduction This chapter summarizes methods to evaluate runoff conveyance in various street cross sections and curb types in the Town of Castle Rock and identifies acceptable upper limits of street

More information

BMP 6.4.4: Infiltration Trench

BMP 6.4.4: Infiltration Trench BMP 6.4.4: Infiltration Trench An Infiltration Trench is a leaky pipe in a stone filled trench with a level bottom. An Infiltration Trench may be used as part of a larger storm sewer system, such as a

More information

THIS IS A COURTESY COPY OF THIS RULE. ALL OF THE DEPARTMENT S RULES ARE COMPILED IN TITLE 7 OF THE NEW JERSEY ADMINISTRATIVE CODE.

THIS IS A COURTESY COPY OF THIS RULE. ALL OF THE DEPARTMENT S RULES ARE COMPILED IN TITLE 7 OF THE NEW JERSEY ADMINISTRATIVE CODE. (f) The minimum requirements for construction, materials and foundations of grease traps shall be the same as those required for septic tanks, as prescribed in N.J.A.C. 7:9A-8.2. (g) The inlet and outlet

More information

Summary of the 2011 Changes

Summary of the 2011 Changes The following is a list of amendments to the Residential Site Improvement s, N.J.A.C. 5:21, adopted in 2011. The Notice of Adoption of these changes appeared in the New Jersey Register on May 16, 2011.

More information

DIVISION 3: SEWER. Improvement Design Standards City of Dundee Oregon. Division 3 : Sewer Page 1

DIVISION 3: SEWER. Improvement Design Standards City of Dundee Oregon. Division 3 : Sewer Page 1 DIVISION 3: SEWER 3.1 DESIGN CRITERIA A. APPLICABILITY 1. These Design Standards shall govern all construction and upgrading of public sanitary sewer facilities in the City of Dundee and applicable work

More information

SpencerHolmes engineers - surveyors - planners

SpencerHolmes engineers - surveyors - planners Preliminary Stormwater Design Mary Potter Hospice 48-62 Mein Street Newtown Wellington SpencerHolmes engineers - surveyors - planners PO Box 588 Level 6, 8 Willis Street Wellington New Zealand Phone 04

More information

ITEM D-701 PIPE FOR STORM DRAINS AND CULVERTS

ITEM D-701 PIPE FOR STORM DRAINS AND CULVERTS ITEM D-701 PIPE FOR STORM DRAINS AND CULVERTS 701-1 DESCRIPTION 701-1.1 This item shall consist of the construction of pipe culverts, and storm drains, removal of existing storm pipes, connections to existing

More information

GUIDELINES FOR INSTALLATION OF ON-SITE SEWAGE SYSTEMS

GUIDELINES FOR INSTALLATION OF ON-SITE SEWAGE SYSTEMS UTAH COUNTY HEALTH DEPARTMENT Div. of Environmental Health 151 South University Avenue, Provo 84601 (801) 851-7525 FAX 851-7521 GUIDELINES FOR INSTALLATION OF ON-SITE SEWAGE SYSTEMS This is intended to

More information

SEPTIC TANK CONSTRUCTION GUIDELINES

SEPTIC TANK CONSTRUCTION GUIDELINES SEPTIC TANK CONSTRUCTION GUIDELINES Septic tank for this airport will be designed/ built by the general contractor of the building facilities. At the time of the project design, availability of a septic

More information

C. Foundation stabilization for pipe and utility structures.

C. Foundation stabilization for pipe and utility structures. PART 1 - GENERAL 1.1 SECTION INCLUDES A. Excavating, backfilling, and compacting for utilities, including pipe, structures, and appurtenances. B. Control of water in trenches. C. Foundation stabilization

More information

DRAINAGE & DESIGN OF DRAINAGE SYSTEM

DRAINAGE & DESIGN OF DRAINAGE SYSTEM Drainage on Highways DRAINAGE & DESIGN OF DRAINAGE SYSTEM P. R.D. Fernando Chartered Engineer B.Sc.(Hons), M.Eng. C.Eng., MIE(SL) Drainage Requirement of Highway Drainage System Introduction Drainage means

More information

Chapter 8. Inlets. 8.0 Introduction. 8.1 General

Chapter 8. Inlets. 8.0 Introduction. 8.1 General . Introduction This chapter provides criteria and design guides for evaluating and designing storm sewer inlets in the City of Centennial. The review of all planning submittals will be based on the criteria

More information

CHAPTER 6. Sanitary Sewer

CHAPTER 6. Sanitary Sewer CHAPTER 6 Sanitary Sewer A. Introduction All proposed developments, subdivisions, and buildings must have a properly designed and constructed sanitary sewer collection system. The system shall provide

More information

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017 SECTION 02630 - STORM DRAINAGE PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

INDEX FOR SPECIFICATIONS FOR REMOVING CULVERTS AND PLACING CULVERTS SCOPE... 1

INDEX FOR SPECIFICATIONS FOR REMOVING CULVERTS AND PLACING CULVERTS SCOPE... 1 March 2002 No. 400 INDEX FOR SPECIFICATIONS FOR REMOVING CULVERTS AND PLACING CULVERTS 400. 1 SCOPE... 1 400. 2 REMOVING CULVERTS AND TIMBER STRUCTURES 2.1 Concrete and Metal Pipe Culverts... 1 2.2 Structural

More information

4.8. Subsurface Infiltration

4.8. Subsurface Infiltration 4.8. Subsurface Infiltration Subsurface infiltration systems are designed to provide temporary below grade storage infiltration of storm water as it infiltrates into the ground. Dry wells, infiltration

More information

Design Guidelines. 1. INTRODUCTION 2. SECTION SPECIFICATIONS 3. HOUSE DESIGN RULES

Design Guidelines. 1. INTRODUCTION 2. SECTION SPECIFICATIONS 3. HOUSE DESIGN RULES Design Guidelines. 1. INTRODUCTION Waimakariri District Council (WDC) and Ravenswood Developments Ltd (Ravenswood) have in place a number of rules and covenants that effect the development of sections

More information

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II SECTION 221313 - FACILITY SANITARY SEWERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

9.3.9 Industry uses code

9.3.9 Industry uses code 9.3.9 Industry uses code 9.3.9.1 Application (1) This code applies to accepted development and assessable development identified as requiring assessment against the Industry uses code by the tables of

More information

DIVISION 5 STORM DRAINAGE CRITERIA

DIVISION 5 STORM DRAINAGE CRITERIA DIVISION 5 STORM DRAINAGE CRITERIA Section 5.01 GENERAL The following storm drainage design criteria shall apply to all storm drainage designs in the City. Additional design criteria are specified in the

More information

APPLICATION FOR PUBLIC INFRASTRUCTURE PERMIT

APPLICATION FOR PUBLIC INFRASTRUCTURE PERMIT APPLICATION FOR PUBLIC INFRASTRUCTURE PERMIT Engineering Division 550 Landa Street New Braunfels, Texas 78130 (830) 221-4020 1. Subdivision Plat Name: Location Description/ Nearest Intersection: Acreage:

More information

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE)

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE) SECTION 02623 HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE) PART 1 - GENERAL 1.1 SCOPE OF WORK A. Furnish all labor, materials, equipment and incidentals required and install high density

More information

CHAPTER 13 R-5 MANUFACTURED MOBILE HOME PARK RESIDENTIAL DISTRICT

CHAPTER 13 R-5 MANUFACTURED MOBILE HOME PARK RESIDENTIAL DISTRICT 15.1300 CHAPTER 13 R-5 MANUFACTURED MOBILE HOME PARK RESIDENTIAL DISTRICT 15.1301 SECTION 13.01 STATEMENT OF PURPOSE To provide for manufactured home park development, of long-term duration of stay, in

More information

Initial Construction Costs For Various Pavement and Drainage Options

Initial Construction Costs For Various Pavement and Drainage Options Interpave Initial Construction Costs For Various Pavement and Drainage Options Final Prepared For Interpave Scott Wilson Ltd Interpave Pavement Design CONTENTS 1. Overview 2. Summary of Pavement Types

More information

Section Storm Sewers STORM SEWERS PART 1 - GENERAL 1.01 SECTION INCLUDES. A. Storm Sewers. B. Abandonment of Storm Sewers

Section Storm Sewers STORM SEWERS PART 1 - GENERAL 1.01 SECTION INCLUDES. A. Storm Sewers. B. Abandonment of Storm Sewers STORM SEWERS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Storm Sewers B. Abandonment of Storm Sewers 1.02 DESCRIPTION OF WORK A. Construct storm sewers. B. Abandon storm sewers. 1.03 SUBMITTALS Comply with

More information

GUIDANCE MEMO NO : GUIDANCE CRITERIA FOR THE SEPARATION OF WATER MAINS AND NON-POTABLE PIPELINES

GUIDANCE MEMO NO : GUIDANCE CRITERIA FOR THE SEPARATION OF WATER MAINS AND NON-POTABLE PIPELINES State of California Memorandum Department of Health Services Date: April 4, 2003 To: From: Subject: Regional and District Engineers David P. Spath, Ph.D., Chief (Original signed by Dave) Drinking Water

More information

Stormwater collection products for all NZ stormwater specifications

Stormwater collection products for all NZ stormwater specifications Stormwater collection products for all NZ stormwater specifications Designs to meet your local requirements Stormwater drainage is an essential task, with the need to convey water from the sides of roads

More information

SECTION STORM UTILITY DRAINAGE PIPING PART 1 - GENERAL 1.1 SUMMARY 1.2 SUBMITTALS 1.3 PROJECT CONDITIONS

SECTION STORM UTILITY DRAINAGE PIPING PART 1 - GENERAL 1.1 SUMMARY 1.2 SUBMITTALS 1.3 PROJECT CONDITIONS SECTION 334100 - STORM UTILITY DRAINAGE PIPING PART 1 - GENERAL 1.1 SUMMARY Section Includes: 1. Pipe and fittings. 2. Drain Basin. 3. De-chlorination tablet feeder. 4. Non-pressure transition couplings.

More information

Chapter 21 Stormwater Management Bylaw

Chapter 21 Stormwater Management Bylaw Chapter 21 Stormwater Management Bylaw SECTION 1. PURPOSE The purpose of this Bylaw is to: implement the requirements of the National Pollutant Discharge Elimination System (NPDES) General Permit for Storm

More information

FLOOD PLAIN STANDARDS AND REQUIREMENTS. Adopted by City Council on September 16, 2014 Effective January 1, 2015

FLOOD PLAIN STANDARDS AND REQUIREMENTS. Adopted by City Council on September 16, 2014 Effective January 1, 2015 City of Vancouver Land Use and Development Policies and Guidelines Planning and Development Services, 453 W. 12th Ave Vancouver, BC V5Y 1V4 tel 604.873.7000 fax 604.873.7060 planning@vancouver.ca FLOOD

More information

FENCES. This hand out is for REFERENCE ONLY. For more details see specific code sections.

FENCES. This hand out is for REFERENCE ONLY. For more details see specific code sections. Village of Vernon Hills Community Development Department 290 Evergreen Drive, Vernon Hills, IL 60061 Phone 847-367-3704 - Fax 847-367-2541 - http:// www.vernonhills.org FENCES This hand out is for REFERENCE

More information

ARTICLE V: STORMWATER MANAGEMENT AND DRAINAGE SYSTEMS

ARTICLE V: STORMWATER MANAGEMENT AND DRAINAGE SYSTEMS ARTICLE V: STORMWATER MANAGEMENT AND DRAINAGE SYSTEMS Section 501: Purpose An adequate drainage system including necessary ditches, pipes, culverts, drains, inlets, bridges, detention ponds, etc. shall

More information

NEW CASTLE CONSERVATION DISTRICT. through. (Name of Municipality) PLAN REVIEW APPLICATION DRAINAGE, STORMWATER MANAGEMENT, EROSION & SEDIMENT CONTROL

NEW CASTLE CONSERVATION DISTRICT. through. (Name of Municipality) PLAN REVIEW APPLICATION DRAINAGE, STORMWATER MANAGEMENT, EROSION & SEDIMENT CONTROL NEW CASTLE CONSERVATION DISTRICT through (Name of Municipality) PLAN REVIEW APPLICATION DRAINAGE, STORMWATER MANAGEMENT, EROSION & SEDIMENT CONTROL Office use only: Received by Municipality: Received by

More information

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE - 268-5161 Residential Accessory Structures This information has been compiled for the benefit of any person

More information

Tasman Retaining Wall System

Tasman Retaining Wall System Tasman Retaining Wall System The Tasman Retaining Wall System incorporates purpose made corners and capping units to provide classical reconstructed stone retaining walls for any landscape situation. From

More information

***************************************************************************************************************

*************************************************************************************************************** 02720 STORM DRAINAGE SYSTEM *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number 33 40 00. ***************************************************************************************************************

More information

APPENDIX G HYDRAULIC GRADE LINE

APPENDIX G HYDRAULIC GRADE LINE Storm Drainage 13-G-1 APPENDIX G HYDRAULIC GRADE LINE 1.0 Introduction The hydraulic grade line is used to aid the designer in determining the acceptability of a proposed or evaluation of an existing storm

More information

Learning objectives. Upon successful completion of this lecture, the participants will be able to:

Learning objectives. Upon successful completion of this lecture, the participants will be able to: Solomon Seyoum Learning objectives Upon successful completion of this lecture, the participants will be able to: Describe and perform the required step for designing sewer system networks Outline Design

More information

Design Guidelines. pegasus-town.co.nz

Design Guidelines. pegasus-town.co.nz Design Guidelines pegasus-town.co.nz Welcome to Pegasus Town These guidelines have been developed to help make your home-building process as easy as possible. The contents provide you, or your designer

More information

CATCH BASIN ST-1 ENGINEERING DEPARTMENT PLATE NUMBER 3.33' 3.0' 2.0' 4.33' 3.0' 4.0' 1.00' TO BACK OF CURB LINE

CATCH BASIN ST-1 ENGINEERING DEPARTMENT PLATE NUMBER 3.33' 3.0' 2.0' 4.33' 3.0' 4.0' 1.00' TO BACK OF CURB LINE 3.33' 3.0' 2.0' 4.33' 4.0' 3.0' 1.00' TO BACK OF CURB LINE TOP OF GRATE ELEV. - SEE PLAN NEENAH CASTING R-3067-V OR AS NOTED ON PLANS. "INFA-SHIELD" SEAL OR EQUAL. RINGS (2 MIN., 1' MAX. OF RINGS AND MORTAR).

More information

10.0 Storm Sewer Systems

10.0 Storm Sewer Systems October 2003 Chapter 10.0, Storm Sewer Systems Page 1 10.0 Storm Sewer Systems 10.1 Introduction A storm sewer system consists of a system of inlets, pipes, manholes, junctions, cleanouts, outlets, and

More information

S.O.P. No. HMD

S.O.P. No. HMD Page: 1 of 9 PURPOSE: To establish (SOP) for submission requirements, review process and approval of applications for Non-vehicular Access Permits for the purpose of connection or discharge to any MassDOT

More information

SACHSE EROSION CONTROL GUIDELINES

SACHSE EROSION CONTROL GUIDELINES SACHSE EROSION CONTROL GUIDELINES Section I. Definitions The following words, terms, and phrases, when used in this guideline, shall have the meanings ascribed to them in this Section, except where the

More information

Underground Piping for Private Hydrants & Sprinkler Supply Line

Underground Piping for Private Hydrants & Sprinkler Supply Line City of Brea Brea Fire Department Fire Prevention 1 Civic Center Circle Phone: (714) 990-7655 Underground Piping for Private Hydrants & Sprinkler Supply Line PURPOSE The provision of adequate water supplies

More information

Richland County Department of Public Works Engineering (Land Development) Division

Richland County Department of Public Works Engineering (Land Development) Division Richland County Department of Public Works Engineering (Land Development) Division Commercial Projects What is a Commercial Project? Projects that are not related to residential single family homes and/or

More information

SEWER SYSTEM DESIGN GUIDELINES

SEWER SYSTEM DESIGN GUIDELINES SEWER SYSTEM DESIGN GUIDELINES PART 1 GENERAL 1.1 GENERAL GUIDELINES A. The following sewer system design guidelines are based on Federal, State and Local health requirements, and the Berkeley County Water

More information

SECTION 19 - TRENCH EXCAVATION, BEDDING AND BACKFILL TABLE OF CONTENTS

SECTION 19 - TRENCH EXCAVATION, BEDDING AND BACKFILL TABLE OF CONTENTS SECTION 19 - TRENCH EXCAVATION, BEDDING AND BACKFILL TABLE OF CONTENTS Section Page 19-1 TRENCH EXCAVATION...19.1 19-1.01 Exploratory Excavation...19.1 19-1.02 Trench Width...19.1 19-1.02.A Storm Drain

More information

CITY UTILITIES DESIGN STANDARDS MANUAL

CITY UTILITIES DESIGN STANDARDS MANUAL CITY UTILITIES DESIGN STANDARDS MANUAL () September 2017 Page Chapter 1 Acronyms and Definitions 1.01 Purpose 1 1.02 Acronyms 1 1.03 Definitions 3 Chapter 2 Introduction 2.01 Purpose 1 2.02 Applicability

More information

The Proposed Auckland Unitary Plan (notified 30 September 2013)

The Proposed Auckland Unitary Plan (notified 30 September 2013) ART 3 REGIONAL AND DISTRICT RULES»Chapter H: Auckland wide rules»4 Natural resources» 4.14 Stormwater management Introduction The roposed Auckland Unitary lan (notified 30 September 2013) This section

More information

Providing proper drainage system

Providing proper drainage system Environment Friendly and Cost Effective Alternative to Conventional Graded Filters Providing proper drainage system for structures such as earth retaining structures, pavements, water front structures,

More information

PVC Fittings & Laterals for Solid-Wall PVC Sewer Pipe

PVC Fittings & Laterals for Solid-Wall PVC Sewer Pipe Design and Installation Guide PVC Fittings & Laterals for Solid-Wall PVC Sewer Pipe TABLE OF CONTENTS Introduction 2 Products 3 Main-Line Fittings & Service-Line Fittings 3-4 Connections to Dissimilar

More information

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS SECTION 02620 PART 1 GENERAL 1.1 SCOPE OF WORK A. Furnish all labor, materials, equipment, and incidentals required to install High Density Polyethylene (HDPE) pressure pipe, fittings, and appurtenances

More information

3.0 DESIGN CRITERIA FOR SANITARY SEWER FACILITIES

3.0 DESIGN CRITERIA FOR SANITARY SEWER FACILITIES 3.0 DESIGN CRITERIA FOR SANITARY SEWER FACILITIES All sanitary sewers shall be designed in accordance with these Design Standards, LBWD Rules and Regulations, and to accepted engineering principles. In

More information

LOT GRADING. LOT GRADING REQUIREMENTS The following lot grading requirements came into effect on May 1, 2007:

LOT GRADING. LOT GRADING REQUIREMENTS The following lot grading requirements came into effect on May 1, 2007: LOT GRADING DEFINITION Lot grading is the reshaping or sloping of the land in such a way that surface drainage from rain runoff is directed away from the buildings and is controlled in a manner that eliminates

More information

Landscaping and Fencing

Landscaping and Fencing Landscaping and Fencing Fences, driveways, paving, retaining walls, landscaping & other garden features To be read in conjunction with General Requirements: A guide to building on properties containing

More information

7.00 MANHOLES AND INSPECTION CHAMBERS. Hunter Underground Systems

7.00 MANHOLES AND INSPECTION CHAMBERS. Hunter Underground Systems 7.00 MANHOLES AND INSPECTION CHAMBERS Hunter Underground Systems 7.01 Access to drains 7.02 preformed plastic Inspection Chambers 7.03 Manholes 7.04 450mm diameter inspection chambers Equal 110mm inspection

More information

SECTION TRENCHING & BACKFILLING

SECTION TRENCHING & BACKFILLING SECTION 02225 - TRENCHING & BACKFILLING 1.0 GENERAL 1.1 Work included in this Section includes trenching and backfilling for underground pipelines and related structures only. 1.2 Reference Specifications

More information

Temporary Watercourse Crossing: Culverts

Temporary Watercourse Crossing: Culverts Temporary Watercourse Crossing: Culverts DRAINAGE CONTROL TECHNIQUE Low Gradient Velocity Control Short Term Steep Gradient Channel Lining Medium-Long Term Outlet Control Soil Treatment Permanent Symbol

More information

Chapter 11 Culverts and Bridges

Chapter 11 Culverts and Bridges Chapter 11 Culverts and Bridges Contents 1.0 Introduction... 1 2.0 General Design... 1 2.1 Design Criteria... 1 2.2 Design Flows... 1 2.3 Permitting and Regulations... 1 2.4 Aesthetics and Safety... 2

More information

Standards for Soil Erosion and Sediment Control in New Jersey May 2012 STANDARD FOR SLOPE PROTECTION STRUCTURES. Definition

Standards for Soil Erosion and Sediment Control in New Jersey May 2012 STANDARD FOR SLOPE PROTECTION STRUCTURES. Definition STANDARD FOR SLOPE PROTECTION STRUCTURES Definition Structures to safely conduct surface runoff from the top of a slope to the bottom of the slope. Purpose The purpose of this practice is to convey storm

More information

SANITARY SEWERS. B. Construct or relocate building sanitary sewer services, stubs, and connections.

SANITARY SEWERS. B. Construct or relocate building sanitary sewer services, stubs, and connections. SANITARY SEWERS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Sanitary Sewer Gravity Mains B. Sanitary Sewer Force Mains C. Sanitary Sewer Services 1.02 DESCRIPTION OF WORK A. Construct sanitary sewer gravity

More information

***************************************************************************************************************

*************************************************************************************************************** 02735 WASTE WATER DRAINAGE SYSTEM *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number 22 14 00 ***************************************************************************************************************

More information

Drainage By-law. WM-4 Consolidated as of April 18, 2011

Drainage By-law. WM-4 Consolidated as of April 18, 2011 Drainage By-law WM-4 Consolidated as of April 18, 2011 As Amended by By-law No. Date Passed at Council WM-4 September 20, 1993 WM-4-95001 September 18, 1995 WM-4-96002 August 6, 1996 WM-4-97003 May 5,

More information

INDEX FOR SPECIFICATIONS FOR JACKING CULVERTS THROUGH EMBANKMENTS SCOPE... 2

INDEX FOR SPECIFICATIONS FOR JACKING CULVERTS THROUGH EMBANKMENTS SCOPE... 2 INDEX FOR SPECIFICATIONS FOR JACKING CULVERTS THROUGH EMBANKMENTS 410. 1 SCOPE... 2 410. 2 DEFINITIONS 2.1 Tunneling and Jacking... 2 2.2 Tunneling... 2 2.3 Jacking... 2 410. 3 MATERIALS 3.1 General...

More information

SWIMMING POOL PERMIT AND INSPECTION REQUIREMENTS

SWIMMING POOL PERMIT AND INSPECTION REQUIREMENTS Building Inspections SWIMMING POOL PERMIT AND INSPECTION REQUIREMENTS Permit Applications Pool permit applications are now being accepted online at http://etrakit.flower-mound.com/. Starting November 1,

More information

ENGINEERED SOLUTIONS. Terre Arch Concrete Detention/Infiltration. Solutions Guide

ENGINEERED SOLUTIONS. Terre Arch Concrete Detention/Infiltration. Solutions Guide ENGINEERED SOLUTIONS Terre Arch Concrete Detention/Infiltration Solutions Guide Stormwater Solutions from Contech Selecting the Right Stormwater Solution Just Got Easier... It s simple to choose the right

More information

E5. On-site and small scale wastewater treatment and disposal

E5. On-site and small scale wastewater treatment and disposal E5. On-site and small scale wastewater treatment and disposal E5.1. Background On-site wastewater systems are utilised for residential dwellings, commercial and industrial activities and facilities not

More information

Rainsmart Ellipse Tank O & M Guide Manual for Inspection Row

Rainsmart Ellipse Tank O & M Guide Manual for Inspection Row Rainsmart Ellipse Tank O & M Guide Manual for Inspection Row 1.0 The Inspection Row 1.1 INTRODUCTION An important component of any Stormwater Pollution Prevention Plan is inspection and maintenance. The

More information

BISON PRECAST FLOORING SPECIFICATION

BISON PRECAST FLOORING SPECIFICATION BISON PRECAST FLOORING SPECIFICATION 1.0 SCOPE OF THE SPECIFICATION 1.01 Relates to: This specification covers the design, manufacture and associated site work of the following types of floors:- Hollowcore

More information

Concrete pipe reference manual Issue 1

Concrete pipe reference manual Issue 1 Strength. Performance. Passion. Concrete pipe reference manual Issue 1 Contents 1. Introduction 3 Manufacturing 3 Joint types 3 Durability 4 Hydraulics 4 Size class (DN) 4 Load class 5 6. Pipes for pressure

More information

Section Three, Part 15 Parking and Loading of Vehicles

Section Three, Part 15 Parking and Loading of Vehicles PART 15 PARKING AND LOADING OF VEHICLES 15.1 INTRODUCTION This part of the District Plan sets out the principles and provisions relating to the parking and loading of vehicles. 15.2 OVERVIEW The provision

More information

A. This Section includes subdrainage systems for foundations and underslab areas. A. Product Data: For each type of drainage panel indicated.

A. This Section includes subdrainage systems for foundations and underslab areas. A. Product Data: For each type of drainage panel indicated. ZGF Partnership Page 1 of 7 SECTION 33 46 00 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes subdrainage systems for foundations and underslab areas. 1.2 SUBMITTALS A. Product Data: For each type

More information