.1 National Fire Protection Association (NFPA) NFPA 70: National Electrical Code. September pp.

Size: px
Start display at page:

Download ".1 National Fire Protection Association (NFPA) NFPA 70: National Electrical Code. September pp."

Transcription

1 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES Page 1 of 4 1 General 1.1 SECTION INCLUDES.1 Low-voltage conductors 1.2 REFERENCES.1 National Fire Protection Association (NFPA) NFPA 70: National Electrical Code. September pp. 2 Products 2.1 LOW-VOLTAGE CONDUCTORS.1 Manufacturers.1 BICC/General Cable.2 Okonite.3 Pirelli.4 Other company, as reviewed by the Engineer.2 Description: Single-conductor insulated wire.3 Conductor: Stranded copper.4 Insulation Voltage Rating: 600 volts.5 Insulation: American National Standards Institute/NFPA 70, Type XHHW or THWN insulation for feeders and branch circuits larger than No. 6 American wire gauge (AWG), thermoplastic high heat-resistant nylon-coated/thermoplastic high water-resistant nylon-coated insulation for feeders and branch circuits No. 6 AWG and smaller

2 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES Page 2 of WIRING CONNECTORS.1 Wire Sizes No. 10 AWG and Smaller:.1 Splices and Taps: 3M Scotchlok Type Y & R insulated spring connectors.2 Terminals: Thomas & Betts Sta-Kon Series RA, RB, and RC insulated terminals. Use locking-fork-type terminal for connection to terminal blocks and ring-type terminal for motor terminations..2 Wire Sizes No. 8 AWG through 500 MCM:.1 Splices: Thomas & Betts Series barrel-type, cast copper, heavy duty, two-way compression connector.2 Taps: Thomas & Betts Series color-keyed, C-type compression connector.3 Lugs: Cast copper, heavy duty type:.1 Motor Terminations and Wire Sizes No. 8 AWG to 1/0 AWG: Thomas & Betts Series, one-hole type.2 Wire Sizes 2/0 and Larger: Thomas & Betts Series, two-hole type.4 Install compression-type connectors using a hydraulic tool with correct die for circumferential or hexagon compressions. 3 Execution 3.1 EXAMINATION.1 Verify that mechanical work likely to damage wire and cable has been completed..2 Verify that field measurements are as shown on the Technical Drawings..3 Wire and cable routing shown on the Technical Drawings is approximate unless dimensioned. Route wire and cable as required to meet project conditions. Include wire and cable lengths within 10 feet (ft)..4 Where wire and cable routing is not shown and destination only is indicated, determine exact routing and lengths required.

3 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES Page 3 of PREPARATION.1 Completely and thoroughly swab the raceway before installing wire..2 Determine required separation between the cable and other work..3 Determine cable routing to avoid interference with other work. 3.3 INSTALLATION.1 Install products in accordance with manufacturer s instructions..2 Use stranded conductors for feeders and branch circuits No. 12 AWG and smaller to wiring devices..3 Use conductor not smaller than No. 12 AWG for power and lighting circuits..4 Use conductor not smaller than No. 14 AWG for control circuits and for discretetype instrumentation wiring..5 Use No. 10 AWG conductors for 20 ampere, 120 volt branch circuits longer than 100 ft..6 Pull conductors into raceway at the same time..7 Use suitable wire pulling lubricant for building wire No. 4 AWG and larger..8 Provide a properly sized equipment-grounding conductor in raceways..9 Neatly train and lace wiring inside boxes, equipment, and panelboards..10 Clean conductor surfaces before installing lugs and connectors..11 Make splices, taps, and terminations to carry full ampacity of conductors with no perceptible temperature rise..12 After making splice or tap, tape uninsulated conductors and connector with electrical tape (3M 33+) to 150 percent of insulation rating of conductor..13 Use connector sealing pack for connections in outdoor or underground boxes or in bases of lighting poles.

4 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES Page 4 of FIELD QUALITY CONTROL.1 Inspect wire and cable for physical damage and proper connection..2 Measure tightness of bolted connections and compare torque measurements with manufacturer s stated values. END OF SECTION

5 CONTROL-VOLTAGE ELECTRICAL CABLES Page 1 of 2 1 General 1.1 SECTION INCLUDES.1 Shielded instrumentation cable..2 Wiring connectors. 1.2 REFERENCES.1 Underwriters Laboratory (UL). UL 758 the Standard for Safety of Appliance Wiring Materials. 2 Products 2.1 SHIELDED INSTRUMENTATION CABLE volt insulated analog signal cable: Alpha No. 5430, or as reviewed by the Engineer..2 Description: UL 758, Appliance Wiring Material, Style 2501, two-conductor, stranded tinned copper, No. 18 American wire gauge shielded cable with tinned copper drain wire..3 Insulation: Polyvinyl chloride jacket rated for 600 volts. 2.2 WIRING CONNECTORS.1 Splices and Taps: 3M Scotchlok Type Y & R insulated spring connectors..2 Terminals: Thomas & Betts Sta-Kon Series RA, RB, and RC insulated terminals. Use locking-fork-type terminal for connection to terminal blocks and ring-type terminals for motor terminations. 3 Execution 3.1 EXAMINATION.1 Verify that mechanical work that is likely to damage wire and cable has been completed..2 Verify that field measurements are as shown on the Technical Drawings.

6 CONTROL-VOLTAGE ELECTRICAL CABLES Page 2 of 2.3 Wire and cable routing shown on the Technical Drawings is approximate unless dimensioned. Route wire and cable as required to meet project conditions. Include wire and cable lengths within 10 feet..4 Where wire and cable routing is not shown and destination only is indicated, determine exact routing and lengths required. 3.2 PREPARATION.1 Completely and thoroughly swab the raceway before installing wire..2 Determine required separation between the cable and other work..3 Determine cable routing to avoid interference with other work. 3.3 INSTALLATION.1 Install products in accordance with manufacturer s instructions..2 Use stranded conductors for control circuits..3 Pull conductors into raceway at the same time..4 Provide a properly sized equipment-grounding conductor in raceways..5 Neatly train and lace wiring inside boxes, equipment, and panelboards..6 Clean conductor surfaces before installing lugs and connectors..7 After making splice or tap, tape uninsulated conductors and connector with electrical tape (3M 33+) to 150 percent of insulation rating of conductor..8 Do not terminate shielded instrumentation cable shield at field device. Trim shield and sleeve with heat-shrink tubing. Prevent shield from coming in contact with conductive surfaces at field device. 3.4 FIELD QUALITY CONTROL.1 Inspect wire and cable for physical damage and proper connection. END OF SECTION

7 Page 1 of 14 1 General 1.1 SECTION INCLUDES.1 Steel conduit and tubing.2 Liquid-tight flexible metal conduit.3 Nonmetallic conduit.4 Expansion/deflection couplings for metallic conduit.5 Installation coatings.6 Outlet, pull, and junction boxes 1.2 REFERENCES.1 American National Standards Institute (ANSI) American National Standard for Electrical Rigid Steel Conduit (ERSC). C80.1. August pp..2 ASTM International (ASTM) Standard Specification for Rigid Poly(Vinyl Chloride) (PVC) Compounds and Chlorinated Poly(Vinyl Chloride) (CPVC) Compounds. DOI: /D ASTM International, West Conshohocken, PA..3 Federal Specifications WF406 and WF Federal Specifications WWC581, WWC581D, WWC581E..5 National Electrical Contractors Association (NECA). Standard of Installation..6 National Electrical Manufacturers Association (NEMA) TC-2, TC-3, TC-6, and TC-8..7 Underwriters Laboratory (UL) UL 6, UL 360, UL 514, UL 514B, UL 651, UL 1242.

8 Page 2 of 14 2 Products 2.1 STEEL CONDUIT AND TUBING.1 Allied Tube & Conduit.2 Wheatland Tube Co..3 Western Tube & Conduit Corp..4 Other manufacturer, as reviewed by the Engineer.2 Rigid Steel Conduit: Federal Specification WWC581D, ANSI C80.1, UL-listed, threaded, hot-dip galvanized conduit. Electro-plated conduit is not acceptable..3 Intermediate Metal Conduit (IMC): Federal Specification WWC581, UL 1242, hotdip galvanized inside and out. Electro-plated conduit is not acceptable..4 Fittings (e.g., couplings, bushings):.1 Rigid Steel and IMC: Cast malleable iron, galvanized, or cadmium-plated fittings conforming to Federal Specification WF408. Copper-free aluminum fittings are not acceptable. Provide compression fittings for IMC..2 Manufacturers:.1 Appleton.2 Cooper/Crouse-Hinds.3 Thomas & Betts/Steel City.4 Other manufacturer, as reviewed by the Engineer.5 Conduit Bodies (e.g., Rigid Steel and IMC, lbs, T):.1 Threaded hub, malleable iron body and cover, with captive stainless steel screws, UL Standard Manufacturers:.1 Appleton.2 Cooper/Crouse-Hinds

9 Page 3 of 14.3 Hubbell/Killark.4 Other manufacturer, as reviewed by the Engineer.3 Use mogul units for conduit sizes larger than 2 inches..6 PVC-Coated Rigid Galvanized Steel Conduit:.1 Ocal, Inc..2 Robroy Industries.3 Other manufacturer, as reviewed by the Engineer.2 Federal Specification WWC581E, ANSI Specification C80.1 and UL 6. Hotdip galvanized inside and outside, including the threads. PVC exterior coating 40 mils nominal thickness. Interior urethane coating of 2 mils..3 Accessories: Fittings and conduit bodies will be PVC-coated. 2.2 LIQUID-TIGHT FLEXIBLE METAL CONDUIT.1 American Brass Company.2 American Flexible Conduit Company.3 ANAMET, Inc..4 Electri-Flex Company.5 International Metal Hose Company.6 Other manufacturer, as reviewed by the Engineer.2 Description: Interlocked flexible galvanized steel construction with liquid-tight PVC jacket, conforming to Federal Specification WF406 and UL Fittings: Malleable iron, cadmium-plated fittings with compression-type steel ferrule and neoprene gasket sealing rings with insulated throat, conforming to UL 514B.

10 Page 4 of NON-METALLIC CONDUIT.1 Cantex.2 Carlon Electrical Products.3 Osburn Associates, Inc..4 Robroy Industries.5 Scepter.6 Triangle/PWC, Inc..7 Other manufacturer, as reviewed by the Engineer.2 PVC Conduit Schedule 40:.1 Conforming to ASTM D1784, UL 651, and NEMA TC-2..2 Rated for use with 90 degree Celsius conductors..3 Sunlight-resistant..4 Fittings and Conduit Bodies: NEMA TC-3 and UL Plastic Duct:.1 Rated for use in underground concrete-encased ductbank..2 Type: DB-60 (NEMA TC-6) or EB-35 (NEMA TC-8)..3 Conforming to ASTM D EXPANSION/DEFLECTION COUPLINGS FOR METALLIC CONDUIT.1 Crouse-Hinds.2 O.Z./Gedney.3 Thomas and Betts.4 Other manufacturer, as reviewed by the Engineer

11 Page 5 of 14.2 Description: Coupling with insulating inner sleeve, integral hub bushings, flexible copper grounding strap, and overall watertight, flexible neoprene outer jacket with stainless steel jacket clamps..3 Locations: Where conduits pass through expansion joints. Where axial contraction or expansion, angular misalignment, or parallel misalignment of rigid conduit is likely to occur..4 Movement accommodated without damaging conduit or conductors:.1 Axial expansion or contraction up to ¾ inch..2 Angular misalignment of the axis of coupled conduit runs in any direction to 30 degrees..3 Parallel misalignment of the axis of coupled conduit runs in any direction to ¾ inch. 2.5 INSTALLATION COATINGS.1 Direct-Buried Metallic Conduit (Prior to Burial):.1 DuPont Insulating Coatings.2 Goodyear Adhesive No Other manufacturer, as reviewed by the Engineer.2 Description: Coating directly applied to direct-buried metallic conduits prior to placing in trench to inhibit corrosion..2 Outdoor Metallic Conduit Threads (Prior to Assembly):.1 CRC Chemicals, Lectra-Shield.2 Emhart Corporation (Bostik Division), Never-Seez.3 Ideal Industries, No Other manufacturer, as reviewed by the Engineer

12 .2 Description: Anti-seize and lubricating compound..3 Exposed Metallic Conduit Threads (After Assembly): 2.6 CAST BOXES.1 Clearco.2 Crown.3 Other manufacturer, as reviewed by the Engineer Page 6 of 14.2 Description: Anti-corrosive cold galvanizing compound. Meet American Galvanizers Association Standard a for repair of damaged and uncoated areas of hot-dip galvanized coatings..1 Appleton.2 Crouse-Hinds.3 O-Z/Gedney.4 Other manufacturers, as reviewed by the Engineer.2 Type: Corrosion-resistant, Type FD, flat-flanged, cast device box with threaded hubs and external mounting lugs for securing box to surface..3 Mounting: Surface mount..4 Rating: Weatherproof and dust-tight..5 Material: Malleable cast iron..6 Covers: Malleable cast iron covers; include gasket and stainless steel screws. 2.7 SHEET METAL BOXES.1 Appleton.2 Raco

13 Page 7 of 14.3 Steel City.4 Other manufacturer, as reviewed by the Engineer.2 Type: NEMA OS 1, galvanized steel, flush-mounted..3 Box Depth: 2 inches, unless a shallower depth is required by structural conditions; ½-inch male fixture studs where required..4 Luminaire and Equipment Supporting Boxes: Rated for weight of equipment supported; include ½-inch male fixture studs where required. 2.8 NONMETALLIC BOXES.1 Carlon.2 Kraloy.3 Scepter.4 Other manufacturer, as reviewed by the Engineer.2 Type: Corrosion-resistant, F or FD Series, PVC-molded, surface-mounted boxes with grounding clips..3 Box Depth: 2 inches, minimum..4 Covers: Molded PVC covers; include gasket and stainless steel screws. 2.9 EXPLOSION-PROOF BOXES.1 Appleton.2 Crouse-Hinds.3 Other manufacturer, as reviewed by the Engineer.2 Type: GUB or EJB junction boxes; size for application..3 Conduit Hubs: Factory-order quantity, size, and location of threaded hubs for application..4 Rating: NEMA 7; rated for Class I, Division 1, Group D areas.

14 2.10 LARGE PULL BOXES AND TERMINAL POST JUNCTION BOXES.1 Hoffman.2 Other manufacturer, as reviewed by the Engineer.2 Enclosure Type:.1 Indoor Dry Areas: NEMA 12 with 14-gage minimum steel Page 8 of 14.2 Damp, Corrosive, or Outdoor Areas: NEMA 4X glass fiber-reinforced or stainless steel enclosure..3 Latches: External quick-release..4 Cover: Continuous side-hinge cover..5 Terminal Post Junction Boxes: Include terminal strip on panel back plate for support of wiring entering and leaving box, plus 10 percent spare terminals. 3 Execution 3.1 EXAMINATION.1 Verify that field measurements are as shown on the Technical Drawings..2 Verify routing and termination locations of conduit prior to rough-in..3 Conduit routing is shown on the Technical Drawings in approximate locations unless dimensioned. Route as required to complete wiring system..4 Verify locations of boxes and outlets prior to rough-in..5 Coordinate with other Contractors to avoid conflict between the locations of conduit, outlets, equipment, ducts, plumbing, and other building components. 3.2 INSTALLATION.1 General Conduit Installation:.1 Install conduit in accordance with the NECA s Standard of Installation. Size raceways according to code, but not smaller than indicated.

15 Page 9 of 14.2 Minimum Size: ¾-inch trade size unless otherwise specified. Minimum 1- inch trade size for underground conduit..3 Ground and bond conduit..4 Use suitable caps to protect installed conduit against entrance of dirt and moisture..5 Do not install steel conduit in contact with aluminum where exposed to moisture..6 If conduits are installed against concrete surfaces, space ¼ inch away from the surface by using clamp backs or conduit hangers..7 Except as otherwise specified, if it is necessary to cut holes through existing walls for raceways, make necessary repairs to building structures and match the repairs to the existing walls..8 Cut conduit square using saw or pipe cutter; de-burr cut ends..9 Threaded Joints: Field-cut threads using conduit dies. Clean off cuttings and oil; coat with a cold galvanizing compound. Recoat exposed threads with cold galvanizing compound after installation..10 Nonmetallic Conduit Joints: Wipe nonmetallic conduit dry and clean before joining. Use cleaner/primer and full, even coat of cement in accordance with manufacturer s instructions; allow joint to cure for a minimum of 20 minutes before disturbing..11 If sections of the same conduit are exposed to different temperatures, seal the conduit to prevent condensation and passage of air from one area to the other..12 Do not allow moisture traps. Provide a junction box with a drain fitting at low points in the conduit system..13 Provide suitable pull wire in each empty conduit; secure at both ends..14 Provide suitable expansion coupling every 100 feet (ft) for straight runs of nonmetallic rigid conduit..15 Install expansion/deflection couplings on conduit raceways installed in slab where conduits pass through expansion joints..16 Provide bonding jumpers across expansion/deflection couplings for metallic raceways.

16 Page 10 of Repair damaged coatings of PVC-coated rigid conduit with repair kit and materials manufactured specifically for the purpose..18 Coat conduit threads that are not scheduled for painting with lubricating compound..19 Repair scratched galvanized surfaces and exposed outdoor conduit threads with cold galvanizing compound..2 Conduit Use:.1 Outdoor Locations, Exposed Abovegrade:.1 Rigid steel or intermediate metal conduit..2 Use PVC-coated, rigid conduit or similar barrier protection at locations where conduit enters exposed outside concrete..3 Termination to Motors, Transformers, and Vibrating Equipment: Liquid-tight, flexible metal conduit; length not to exceed 4 ft. Coordinate location of motor connection with Contractors responsible for providing motors..4 Class I and Class II Hazardous Areas: Rigid steel conduit. Use seal-off fittings at transition to nonclassified areas..5 Other Exposed Conduit: Rigid steel or intermediate metallic conduit..2 Conduit in Cast-In-Place Floor Slab or Wall:.1 Schedule 40 PVC conduit..2 Provide PVC-coated metallic conduit and adapter for the transition of a PVC conduit embedded in the floor slab or wall to exposed metallic conduit..3 Maximum Conduit Outside Diameter: ⅓ the slab or wall thickness..4 Minimum Concrete Cover on Conduit: 2 inches..5 Minimum Clearance Between Conduits and Reinforcement: 1½ inches..6 Minimum Center-to-Center Spacing: Three conduit diameters..7 Bends Greater than 45 Degrees: Use rigid steel or intermediate metal conduit for bend.

17 Page 11 of 14.3 Indoor Locations:.3 Conduit Routing:.1 Damp or Humid Environments: Rigid galvanized steel, supported off wall..2 Termination to Motors, Transformers, and Vibrating Equipment: Liquid-tight, flexible metal conduit; length not to exceed 4 ft. Coordinate location of motor connection with Contractors responsible for providing motors..3 Class I and Class II Hazardous Areas: Rigid steel conduit. Use seal-off fittings at transition to nonclassified areas..4 Other Exposed Conduit: Rigid steel or intermediate metallic conduit..1 Separate conduits carrying instrumentation wiring from conduits carrying power wiring by at least 6 inches..2 Maintain 12-inch clearance between conduit and surfaces with temperatures exceeding 104 degrees Fahrenheit..3 Route conduits around gratings, passage or walkway areas, and other obstructions to avoid tripping hazards and obstructions to equipment access areas..4 Exposed Conduit: Route parallel and perpendicular to walls..5 Concealed Conduit: Route point-to-point..4 Conduit Bends:.1 Use factory elbows for 90-degree bends in metal conduit larger than 2 inches..2 No bend will be greater than 90 degrees..3 Use conduit bodies to make sharp changes in direction..5 Conduit Supporting and Hanging:.1 General:.1 Arrange supports to prevent misalignment during wiring installation..2 Fasten conduit supports to building structure and surfaces.

18 Page 12 of 14.3 Do not support conduit with wire or perforated pipe straps. Remove wire used for temporary supports..4 Arrange conduit to maintain headroom and present neat appearance..5 Support conduits away from walls that are likely to condensate..2 Individual Conduits:.1 Support individual conduits directly to structural steel with beam clamps..2 Support individual horizontal conduits not larger than 1½ inches in diameter to concrete walls by means of one-hole, malleable iron straps with clamp back spacers..3 Support individual horizontal conduits larger than 1½ inches in diameter by individual hangers and forged steel conduit strap for vertical runs..3 Groups of Conduits:.1 Construct conduit racks using galvanized steel channel..2 Attach groups of conduit to structural steel with galvanized steel channel attached with beam clamps. Attach conduit to channel with pipe clamps..3 Attach groups of conduit to concrete with cast-in-place galvanized steel channel and anchors. Attach conduit to channel with pipe clamps..4 Suspended Support:.1 Attach horizontally suspended, single conduit plumb with a galvanizedsteel-threaded rod not smaller than ⅜-inch diameter. Attach threaded rods to concrete with anchors and to structural steel with beam clamps. Attach conduit to threaded rod with clamps..2 Attach horizontally suspended groups of conduit plumb with galvanized steel channel suspended from galvanized-steel-threaded rods not smaller than ⅜-inch diameter. Attach threaded rods to concrete with anchors and to structural steel with beam clamps. Attach conduit to strut with pipe clamps..3 Provide sufficient threading on hanger rods at each end to permit at least 2 inches of adjustment.

19 Page 13 of 14.5 Vertical Conduit Support:.1 Space supports not over 10 ft on center for vertical conduits spanning open areas. Securely anchor conduit at each end and install so as not to interfere with the installation and operation of equipment at the location..2 Install conduit support bushings in vertical raceways at intervals stipulated by the National Electrical Code..6 Conduit Terminations:.1 Terminate conduit with insulated bushings..2 Bring conduit to shoulder of fittings; fasten securely..3 Use insulated grounding bushings with bonding jumpers for conduit terminations containing conductors No. 8 American wire gauge (AWG) or larger, to boxes with concentric or eccentric knockouts, and to conduits terminating in or under electrical power distribution cabinets and enclosures..4 For equipment subject to vibration, make connections using liquid-tight flexible conduit. Do not exceed 4 ft in length unless otherwise reviewed by the Engineer..7 Box Use:.1 Cast Boxes: Use in exterior and wet locations and for indoor, surfacemounted boxes..2 Sheet Metal Boxes: Use flush-mounted boxes in office spaces, drywall areas, glazed block walls, and other finished areas. Use in new, abovegrade, poured walls..3 Large Pull Boxes: Use for surface-mounted installation where the required size exceeds standard cast box sizes..4 Nonmetallic Boxes: Use with nonmetallic conduit systems..8 General Box Installation:.1 Install boxes in accordance with NECA s Standard of Installation..2 Install in locations as required for splices, taps, wire pulling, and equipment connections and in compliance with regulatory requirements. Electrical boxes shown on the Technical Drawings are in approximate locations unless dimensioned.

20 .3 Install boxes so that box covers are accessible at all times Page 14 of 14.4 Set wall-mounted boxes at elevations to accommodate mounting heights..5 Orient boxes to accommodate wiring devices..6 Maintain headroom and present neat mechanical appearance..7 Coordinate mounting heights and locations of outlets mounted above counters, benches, and backsplashes..8 Align adjacent wall-mounted outlet boxes for switches, thermostats, and similar devices..9 Support boxes independently of conduit..10 Identify terminals and wiring in terminal post junction boxes..11 Install knockout closures in unused box openings. 3.3 INTERFACE WITH OTHER PRODUCTS.1 Maintain isolation of separate conduits by installing separate pull boxes or sectionalized pull boxes for each conduit..2 Support boxes mounted on walls that are likely to condensate away from the wall using Unistrut framing..3 Coordinate installation of outlet boxes for equipment connections. END OF SECTION

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 1.1. REFERENCE STANDARDS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification

More information

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows: SECTION 16130 (Master Template Final-05) ELECTRICAL BOXES PART 1 GENERAL 1.01 SECTION INCLUDES A. Provide boxes for electrical equipment and wiring devices as follows: 1. Wall and ceiling outlet boxes.

More information

B. Provide a complete conduit system with associated couplings, connectors, and fittings.

B. Provide a complete conduit system with associated couplings, connectors, and fittings. SECTION 26 05 33 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 260500. B. Provide a complete conduit system with associated couplings, connectors, and fittings. 1.02 RELATED

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519 METAL CLAD CABLE - MC-PLUS Neutral

More information

WIRING METHODS CHAPTER 38

WIRING METHODS CHAPTER 38 CHAPTER 38 WIRING METHODS SECTION E3801 GENERAL REQUIREMENTS E3801.1 Scope. This chapter covers the wiring methods for services, feeders and branch circuits for electrical power and distribution. E3801.2

More information

Service Entrance Cable Fittings

Service Entrance Cable Fittings Suggested Specifications for Service Entrance Fittings All service fittings shall be approved for the purpose by a nationally recognized testing laboratory, inspection agency or product evaluation organization.

More information

Electrical Metallic Tubing (EMT) Fittings

Electrical Metallic Tubing (EMT) Fittings Suggested Specifications for Electrical Metallic Tubing (EMT) Fittings Series 2 Insulated EMT Connector (Raintight) (Compression Type) Series 20 EMT Coupling (Raintight) (Compression Type) Series 0 Pipe

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Specifications Electrical Metallic Tubing (EMT)

Specifications Electrical Metallic Tubing (EMT) T& Fittings Specifications Electrical Metallic Tubing (EMT) Ref. CEC Rule 12-000 not exceeding 750 Volts Electrical Metallic Tubing (EMT) is similar to rigid steel conduit but is much lighter, weighing

More information

CHAPTER 11 CONDUITS AND FITTINGS

CHAPTER 11 CONDUITS AND FITTINGS CONDUITS AND FITTINGS CHAPTER 11 CONDUITS AND FITTINGS The standards and requirements for conduits and fittings used for traffic control signal and lighting systems are presented in this chapter. 11.1

More information

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING 2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING E3305.3: now reads The space equal to the width and depth of the panelboard and extending

More information

CONDUITS AND FITTINGS

CONDUITS AND FITTINGS CONDUIT AND FITTINGS Rigid Steel Conduit 3801 Rigid PVC Conduit 3803 HDPE Conduit 3803 Flexible Non Metallic Liquid Tight Conduit Type LFNC-B 3804 PVC Coated Urethane Lined Galvanized Rigid Steel Conduit

More information

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING SECTION 16060 PART 1 GENERAL 1.01 DESCRIPTION A. Section includes requirements for an electrical grounding system, including electrodes, grounding rods, connectors, insulators, equipment grounding and

More information

SECTION WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring.

SECTION WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring. SECTION 16120 WIRE AND CABLE PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 16112 - Raceways and Conduit. 2. 16155 - Motor Power and Control Wiring. 1.02 SYSTEM DESCRIPTION A. Performance Requirements:

More information

SECTION CHAIN-LINK FENCES AND GATES 02821/1

SECTION CHAIN-LINK FENCES AND GATES 02821/1 SECTION 02821 - CHAIN-LINK FENCES AND GATES 02821/1 PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Chain-Link Fences: 2. Gates: horizontal slide or swing. 3. Fences installed where

More information

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT. A. ASME B31.1 (American Society of Mechanical Engineers) - Power Piping

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT. A. ASME B31.1 (American Society of Mechanical Engineers) - Power Piping SECTION 22 05 29 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes pipe and equipment supports, hangers, anchors, bases sleeves and the sealing of

More information

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL). 16450 GROUNDING ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 26 An optional keynote to the

More information

UNDERGROUND SERVICES SECONDARY

UNDERGROUND SERVICES SECONDARY Reference UNDERGROUND SERVICES SECONDARY Underground services secondary... U- 1 General requirements for underground service... U- 2 Name of parts for underground service... U- 3 Conduit layouts... U-

More information

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases.

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases. SECTION 260529 - HANGERS AND SUPPORTS PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases. 1.2

More information

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property 2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical

More information

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS. 1. Hangers and supports for electrical equipment and systems.

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS. 1. Hangers and supports for electrical equipment and systems. SECTION 26 05 29 HANGERS AND SUPPORTS FOR PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Hangers and supports for electrical equipment and systems. 1.2 DEFINITIONS A. EMT: Electrical

More information

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION 23 05 29 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes pipe and equipment supports, hangers, anchors, bases sleeves and the sealing of work

More information

ST. VINCENT COLLEGE SIS AND HERMAN DUPRÉ SCIENCE PAVILLION SECTION LABORATORY ELECTRICAL REQUIREMENTS PART 1 - GENERAL REQUIREMENTS

ST. VINCENT COLLEGE SIS AND HERMAN DUPRÉ SCIENCE PAVILLION SECTION LABORATORY ELECTRICAL REQUIREMENTS PART 1 - GENERAL REQUIREMENTS SECTION 26 11 20 - LABORATORY ELECTRICAL REQUIREMENTS PART 1 - GENERAL REQUIREMENTS 1.01 RELATED DOCUMENTS A. The general conditions, Division 1, and Division 26 are part of this section and the contract

More information

B. Insulated Conductors: Stranded copper wire, green or green with yellow stripe insulation, insulated for 600 V, and complying with UL 83.

B. Insulated Conductors: Stranded copper wire, green or green with yellow stripe insulation, insulated for 600 V, and complying with UL 83. SECTION 270526 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Grounding conductors. 2. Grounding connectors. 3. Grounding busbars. 4. Grounding

More information

SECTION PLUMBING PIPING SYSTEMS

SECTION PLUMBING PIPING SYSTEMS SECTION 15300 PLUMBING PIPING SYSTEMS PART 1 - GENERAL 1.01 SPECIAL NOTICE A. Each contractor shall read all relevant documents, become familiar with the job, the scope of work, type of general construction,

More information

SECTION INSULATED WIRE AND CABLE

SECTION INSULATED WIRE AND CABLE SECTION 16120 INSULATED WIRE AND CABLE PART 1 GENERAL 1.01 DESCRIPTION A. This section covers the contract item Insulated Wire and Cable, which includes the following items with accessories, and appurtenances:

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 6/15/16 Updated division section from 16124 to 2605 - mgl44 13, removed references to other section 10/17/14

More information

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp,

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp, TITLE 14 CHAPTER 10 PART 4 HOUSING AND CONSTRUCTION ELECTRICAL CODES 2011 NEW MEXICO ELECTRICAL CODE 14.10.4.1 ISSUING AGENCY: The Construction Industries Division of the Regulation and Licensing Department.

More information

A. Product Data shall be provided for each type of product indicated.

A. Product Data shall be provided for each type of product indicated. 32 31 13 CHAIN LINK FENCES AND GATES SECTION 1 GENERAL 1.1 SUMMARY This Section includes the following: 1. Chain Link Fences 2. Gates for Chain Link Fences. See electrical specifications for electrical

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES Electrical Manholes and Handholes UNIVERSITY OF MISSOURI

CONSULTANT PROCEDURES & DESIGN GUIDELINES Electrical Manholes and Handholes UNIVERSITY OF MISSOURI GENERAL: The scope of this document is to provide instruction for the installation of concrete electric manholes. DESIGN GUIDELINES: 1. Materials for Manhole 1.1. Cast-in-Place or Pre-Cast concrete may

More information

1. Approved Manufacturers: Carlon Electrical Products, Cantex, or approved equal.

1. Approved Manufacturers: Carlon Electrical Products, Cantex, or approved equal. PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of Texas State University for for Electrical System. B. Texas State University recognizes

More information

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT SECTION 220529 - HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The General Conditions, Special Conditions and Division 1 through Division 22 as set forth in

More information

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and

More information

SECTION HANGERS AND SUPPORTS FOR PLUMBING

SECTION HANGERS AND SUPPORTS FOR PLUMBING SECTION 22 05 29 HANGERS AND SUPPORTS FOR PLUMBING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

A. This Section includes raceways, fittings, boxes, enclosures, and cabinets for electrical wiring.

A. This Section includes raceways, fittings, boxes, enclosures, and cabinets for electrical wiring. PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 DEFINITIONS... 2 1.4 SUBMITTALS... 2 1.5 QUALITY ASSURANCE... 2 1.6 COORDINATION... 2 PART 2 - PRODUCTS... 2 2.1 METAL CONDUIT AND

More information

Daytona Beach Pier Building Renovation Jun 2010

Daytona Beach Pier Building Renovation Jun 2010 SECTION 15060 - HANGERS AND SUPPORTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

A. Pipe Supports: ANSI B 31.1, Power Piping. B. Automatic Sprinkler Pipe Supports: Refer to Section

A. Pipe Supports: ANSI B 31.1, Power Piping. B. Automatic Sprinkler Pipe Supports: Refer to Section SECTION 15140 SUPPORTS, ANCHORS, AND SEALS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract including General and Supplementary Conditions, Division 1 Specification

More information

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS SECTION 270528 PATHWAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Communications equipment coordination and installation. 2. Sleeves for pathways and cables. 3. Raceway

More information

NEC 2014 Code Changes

NEC 2014 Code Changes NEC 2014 Code Changes Articles 280.21-300.50 CHANGES FROM 2011 TO 2014 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 280 Surge Arresters, Over 1000 volts II. Instillation III. Connecting Surge

More information

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers. SECTION 230529 - HANGERS AND SUPPORTS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Sleeves. 6. Mechanical sleeve seals. 7. Firestopping

More information

SECTION 1101 TRAFFIC SIGNALS AND APPURTENANCES END OF SECTION

SECTION 1101 TRAFFIC SIGNALS AND APPURTENANCES END OF SECTION SECTION 1101 SIGNALS AND APPURTENANCES PART 1 GENERAL 1.4 SUBMITTALS E. Submit warranty for all supplied material and workmanship for a period of two years from final acceptance. The warranty must state

More information

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PIPE HANGERS, Section PIPE HANGERS, SUPPORTS, AND RESTRAINTS

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PIPE HANGERS, Section PIPE HANGERS, SUPPORTS, AND RESTRAINTS PART 1 GENERAL 1.01 SUMMARY Section 15140 PIPE HANGERS, This Section includes the furnishing and subsequent installation of: A. Pipe and equipment hangers, supports, and associated anchors B. Equipment

More information

HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 13686.00 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230529-1 SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 1.1 SUMMARY A. Section Includes: 1. Metal pipe hangers and supports.

More information

Cable Terminators COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS. Applications

Cable Terminators COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS. Applications Cable Terminators and Sealing Fittings are used on conduit ends and cable ends to effectively seal the cable and conduit. Terminator The Terminator body is deep enough to provide an ample compound chamber

More information

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION SUPPORTS AND ANCHORS

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION SUPPORTS AND ANCHORS OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 WORK INCLUDED A. Supports and anchors for piping systems and equipment. 1.2 RELATED WORK SPECIFIED ELSEWHERE A. The provisions of Section 15050, Basic

More information

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

SECTION BASIC ELECTRICAL MATERIALS AND METHODS SECTION 26 05 05 BASIC ELECTRICAL MATERIALS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the limited scope construction materials and methods for application with electrical installations as follows:

More information

PIP PCEPA003 Process Analyzer System Field Installation Guidelines

PIP PCEPA003 Process Analyzer System Field Installation Guidelines January 2016 Process Control PIP PCEPA003 Process Analyzer System Field Installation Guidelines PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities,

More information

DIVISION 15-MECHANICAL SECTION SUPPORTS AND ANCHORS PN PART 1 - GENERAL 1.01 SECTION INCLUDES. A. Pipe and equipment support systems.

DIVISION 15-MECHANICAL SECTION SUPPORTS AND ANCHORS PN PART 1 - GENERAL 1.01 SECTION INCLUDES. A. Pipe and equipment support systems. PART 1 - GENERAL 1.01 SECTION INCLUDES A. Pipe and equipment support systems. B. Inserts. 1.02 RELATED SECTIONS A. Section 15890 - Ductwork Supports. 1.03 DEFINITIONS A. Supports: Attachments, hangers,

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING SECTION 221316 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following soil and waste, sanitary drainage and vent piping inside the building: 1. Pipe, tube,

More information

8.1.2 Under no circumstances shall a service entrance be left unmetered. Notify the Company if an unmetered service is encountered.

8.1.2 Under no circumstances shall a service entrance be left unmetered. Notify the Company if an unmetered service is encountered. 2012 Edition Redbook 8.0 REVENUE METERING 8.1 INTRODUCTION The purpose of this section is to outline requirements of the Customer, as set forth herein by LIPA, as they pertain to Electric Revenue Metering

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 27 29 (April 2006) Change 1-08/13 -------------------------- Preparing Activity: NAVFAC Replacing without change UFGS-16407 (August 2004) UNIFIED FACILITIES GUIDE

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Updated format, division title, and removed references to other sections. - mgl44 A. Summary This section contains design criteria for the

More information

B. All materials provided under this section shall be listed by an OSHA-approved, Nationally Recognized Testing Laboratory (NRTL).

B. All materials provided under this section shall be listed by an OSHA-approved, Nationally Recognized Testing Laboratory (NRTL). 16112 RACEWAYS AND CONDUIT ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 33 An optional keynote

More information

(Condensed from National Electric Code)

(Condensed from National Electric Code) WIRING, SPECIFICATIONS, INSPECTION, AND METER INSTALLATION PROCEDURES FOR RESIDENTIAL CUSTOMERS SERVED BY SOUTHWEST ARKANSAS ELECTRIC COOPERATIVE CORPORATION Effective April 1, 1974 Revised February 3,

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less)

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less) SECTION 260523 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less) PART 1 - GENERAL 1.1 SUMMARY A. Related Documents: 1. Drawings and general provisions of the Subcontract apply

More information

PRESTON HEALTH SERVICES ARCHITECT'S NO. 2700

PRESTON HEALTH SERVICES ARCHITECT'S NO. 2700 SECTION 09 5113 - ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT SECTION 220529 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT SECTION 220529 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Steel pipe hangers and supports. 2. Metal framing systems. 3. Thermal-hanger shield inserts. 4. Fastener systems.

More information

BASIC CONCEPTS IN ELECTRICAL DESIGN. Prepared by Engr. John Paul Timola

BASIC CONCEPTS IN ELECTRICAL DESIGN. Prepared by Engr. John Paul Timola BASIC CONCEPTS IN ELECTRICAL DESIGN Prepared by Engr. John Paul Timola ELECTRICAL CONDUCTORS AND INSULATORS Electrical Conductors substances that offer a very low resistance to current flow. Insulators

More information

SECTION CHAIN LINK FENCES AND GATES (GALVANIZED) A. Fence framework, fabric, gates, and accessories.

SECTION CHAIN LINK FENCES AND GATES (GALVANIZED) A. Fence framework, fabric, gates, and accessories. SECTION 02830 CHAIN LINK FENCES AND GATES (GALVANIZED) 1.0 GENERAL 1.1 Section Includes A. Fence framework, fabric, gates, and accessories. B. Excavation for post bases; concrete footing for posts. C.

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 22 1316 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

Diffused Aeration Piping Equipment

Diffused Aeration Piping Equipment 1.0 General 1.1. The specifications in this section include all components of the Diffused Aeration System with the exception of the individual diffuser units. Refer to additional specification sections

More information

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE ONTARIO PROVINCIAL STANDARD SPECIFICATION OPSS.PROV 604 NOVEMBER 2017 CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION SECTION 74 AIRPORT OBSTRUCTION LIGHTS (FAA L-119) 74-1 GENERAL The Contractor shall perform all work required by the plans and specifications for construction of obstruction lights in accordance with the

More information

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR PART 1 - GENERAL Section 26 05 15 SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR 1.1 Cable shall be 15 kv, shielded, three conductor with ground, stranded copper, with continuously welded and corrugated

More information

EFFECTIVE DATE: July 1, 2008, unless a later date is cited at the end of a section. [ NMAC - Rp,

EFFECTIVE DATE: July 1, 2008, unless a later date is cited at the end of a section. [ NMAC - Rp, TITLE 14 CHAPTER 10 PART 4 HOUSING AND CONSTRUCTION ELECTRICAL CODES 2008 NEW MEXICO ELECTRICAL CODE 14.10.4.1 ISSUING AGENCY: The Construction Industries Division of the Regulation and Licensing Department.

More information

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT Page 220529-1 SECTION 220529 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

DIVISION 26 ELECTRICAL Electrical Power Conductors and Cables

DIVISION 26 ELECTRICAL Electrical Power Conductors and Cables PART 1 - GENERAL 1.01 DESIGN REQUIREMENTS A. Scope: Power Conductors and Cables in this section are defined as system voltages above 120V and less than 600V. B. System Voltages Three Phase and Single Phase:

More information

A. All materials shall be listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

A. All materials shall be listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL). 16120 WIRE AND CABLE ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 19 An optional keynote

More information

Underground Exhaust System

Underground Exhaust System Operation and Maintenance Manual Underground Exhaust MONOXIVENT - SOURCE CAPTURE SYSTEMS - info@ Oct. - 2015 Underground Duct Construction Standards 1. Dig trench depth to allow for minimum distance from

More information

SECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 08332 [08 33 13] COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Metal Counter

More information

Daytona Beach Pier Building Renovation Jun 2010

Daytona Beach Pier Building Renovation Jun 2010 SECTION 15150 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

4CS12 4CS-1/2 4X1-7/8D Handybox. Features. Dimensions and Weight. Long Description. Catalog Number

4CS12 4CS-1/2 4X1-7/8D Handybox. Features. Dimensions and Weight. Long Description. Catalog Number 3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 AllenWatson@elliottelectric.com 4CS12 4CS-1/2 4X1-7/8D Handybox Appleton/Oz Gedney Catalog Number 4CS12 Manufacturer Appleton/Oz

More information

SECTION HVAC DUCTS AND CASINGS

SECTION HVAC DUCTS AND CASINGS SECTION 23 31 00 HVAC DUCTS AND CASINGS PART 1 -GENERAL 1.1 SUMMARY A. Section includes metal ductwork, nonmetallic ductwork, casing and plenums, buried ductwork, kitchen hood ductwork, duct cleaning.

More information

1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.

1. Division 23 Section Hangers and Supports for HVAC Piping and Equipment for pipe insulation shields and protection saddles. SECTION 23 07 19 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Electric Service Standards

Electric Service Standards V: 1 of 6 A. Padmounted Requirements Complete requirements are contained in FPL specifications given to Customers for individual projects. Typical pad mounted transformer requirements include, but are

More information

SECTION ACOUSTICAL PANEL CEILINGS

SECTION ACOUSTICAL PANEL CEILINGS SECTION 095113 ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Installation of CSST Gas Piping Systems

Installation of CSST Gas Piping Systems (What Inspectors Need To Know) May 2016 Conventional Arc-Resistant CSST Product Standard National Standard ANSI LC-1 Performance-based standard Listed system installed in accordance with manufacturer s

More information

Permitting and Inspecting PV Systems. PV Codes and Standards 101. Photovoltaic System Basics

Permitting and Inspecting PV Systems. PV Codes and Standards 101. Photovoltaic System Basics Permitting and Inspecting PV Systems Presented by Bill Brooks, PE Brooks Engineering PV Codes and Standards 101 What are the applicable codes and standards for PV systems? Electrical codes - NEC Article

More information

STABILOY Brand MC Cable InSTALLATION GUIDE

STABILOY Brand MC Cable InSTALLATION GUIDE General CABLE STABILOY Brand MC Cable InSTALLATION GUIDE General CABLE STABILOY Brand MC Cable InSTALLATION GUIDE STABILOY Brand MC Cable Installation Guide STABILOY Brand MC Cable Advantage When using

More information

1.2 ACTION AND INFORMATIONAL SUBMITTALS.1 Provide submittals in accordance with Section Submittal Procedures.

1.2 ACTION AND INFORMATIONAL SUBMITTALS.1 Provide submittals in accordance with Section Submittal Procedures. BID OPPORTUNITY NO. 253-2011 PAGE 1 OF 7 PART 1 GENERAL 1.1 REFERENCES.1 American Society of Mechanical Engineers (ASME).1 ASME B31.1, Power Piping, B31.3 Process Piping, B31.9 Building Services Piping..2

More information

SECTION BASIC ELECTRICAL REQUIREMENTS

SECTION BASIC ELECTRICAL REQUIREMENTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions, apply to work of this section. 1.2 SUMMARY A. This section specifies

More information

15 kv EPR Insulated, Jacketed, URD Cable

15 kv EPR Insulated, Jacketed, URD Cable 15 kv EPR Insulated, Jacketed, URD Cable 1000 kcm Copper Conductor with Tape Shield Page 1 of 11 Table Of Contents 1 GENERAL... 3 2 STANDARDS... 3 3 APPROVED CABLE MANUFACTURERS... 3 4 REEL SPECIFICATIONS...

More information

Temporary Wiring Practices And Guidelines For NECA. National Electrical Contractors Association Omaha, Nebraska

Temporary Wiring Practices And Guidelines For NECA. National Electrical Contractors Association Omaha, Nebraska Temporary Wiring Practices And Guidelines For NECA National Electrical Contractors Association Omaha, Nebraska Table of Contents I. Planning II. Lighting and Power III. Maintenance IV. Inspections V. Routing

More information

Trench Duct Class Catalog 5230CT9601R10/08

Trench Duct Class Catalog 5230CT9601R10/08 5230CT9601R10/08 2009 Class 5230 CONTENTS Application.................................................5 Unassembled Trench Duct Components.........................6 Factory Assembled Trench Duct..............................11

More information

Standard of Practice - Campus Electrical Distribution System

Standard of Practice - Campus Electrical Distribution System A26.3 Standard of Practice - Campus Electrical Distribution System NOTE: Significant revisions or additions to the previous standards are highlighted in italics. GENERAL Designers shall verify that all

More information

A. This section includes building wire and cable rated 600V and less Full Short Circuit Device, Coordination and Arc Fault Study

A. This section includes building wire and cable rated 600V and less Full Short Circuit Device, Coordination and Arc Fault Study PART 1: GENERAL 1.01 Underground Ducts and Manholes A. The work included in this section of the construction standards consists of the design requirements for the complete layout and installation of a

More information

Fig. 1 - Standard Clevis Hanger

Fig. 1 - Standard Clevis Hanger Revision 10/24/2007 Fig. 1 - Standard Clevis Hanger Component of State of California OSHPD Approved Seismic Restraints System Size Range Size 1/2" thru 36" pipe. Function Recommended for the suspension

More information

SECTION I -- IRONWORK

SECTION I -- IRONWORK SECTION I -- IRONWORK CONTENTS PAGE 1. GENERAL... I-2 1.1. Introduction... I-2 2. REQUIREMENTS... I-2 2.1. General... I-2 2.2. Auxiliary Framing... I-2 2.3. High Seismic Risk Zone Requirements... I-3 2.4.

More information

Materials Carbon Steel and Malleable Iron are used in the manufacture of concrete inserts. Stainless Steel and other materials are available.

Materials Carbon Steel and Malleable Iron are used in the manufacture of concrete inserts. Stainless Steel and other materials are available. Concrete inserts offered in this section are designed to provide a pre-set support point in concrete ceilings, walls, and floors. A range of inserts with varying design loads are available. Materials Carbon

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 23 0529 - MECHANICAL SUPPORTING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL 8.01 GENERAL This material is not intended to cover service from OPPD s network in the downtown Omaha area. See Chapter 12 for details

More information

A. Codes and Standards that are standard at the University. C. Coordinate cleanout locations with Architect.

A. Codes and Standards that are standard at the University. C. Coordinate cleanout locations with Architect. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999 CANADIAN ELECTRICAL CODE 1 The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999 Repealed by Chapter E-6.3 Reg 8 (effective June 24, 2003). Formerly Chapter E-6.3 Reg 6 (effective March

More information

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466 BUSWAY LOW VOLTAGE (POW-R-WAY III) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein

More information

SECTION GYPSUM BOARD ASSEMBLIES

SECTION GYPSUM BOARD ASSEMBLIES SECTION 09 21 16 GYPSUM BOARD ASSEMBLIES PART 1 GENERAL 1.1 SECTION INCLUDES A. Metal stud wall and ceiling framing, 20 gauge. B. Metal channel suspended ceiling framing. C. Gypsum board. D. Gypsum sheathing.

More information

Details of technical leaflets/write-up on various pieces of equipment.

Details of technical leaflets/write-up on various pieces of equipment. Details of technical leaflets/write-up on various pieces of equipment. (1) Insulator Designs: The insulators are provided in one, two, three, or four insulator designs per location and spaced to provide

More information