DIVISION 7 - THERMAL AND MOISTURE PROTECTION

Size: px
Start display at page:

Download "DIVISION 7 - THERMAL AND MOISTURE PROTECTION"

Transcription

1 DIVISION 7 - THERMAL AND MOISTURE PROTECTION This division contains the following elements: 1.1 Waterproofing and Vapor Retarders. A. Fluid Applied Waterproofing. B. Vapor Radon Retarders. 1.2 Insulation. 1.3 Roofing. A. General. B. Steep Slope Roofs. C. Low Slope Roofs. D. Base Flashing. E. Parapets and Adjoining Walls. F. Roof Venting. G. Re-Roofing. H. Steel Roof Blocking (SRB) and Sheet Metal Flashing. I. Roof Expansion Joints. J. Gutters and Downspouts. 1.4 Roof Hatches and Skylights. 1.5 Fireproofing and Firestopping. 1.6 Joint Sealants. 1.1 WATERPROOFING AND VAPOR RETARDERS A. Fluid Applied Waterproofing. 1. Provide waterproofing protection at floors and walls below grade level to prevent water infiltration into the building interior caused by hydrostatic pressure or other water conditions. 2. Provide waterproofing at the inside face of retaining walls, planter walls and planter floors where the outside face is exposed or part of a finished wall or ceiling assembly. 3. One component moisture curing or two component urethane type waterproofing are suitable for covered, non-traffic, below grade locations. 4. Concrete eyebrows, overhangs, covered areas and walkways shall be roofed in accordance with the requirements stated in this Division. Fluid applied waterproofing systems shall not be used in these areas unless prior written approval is granted from M-DCPS Maintenance & Operations Roofing Division. B. Vapor Radon Retarders: 1. Comply with FBC-Florida Standard for Radon-Resistant New Commercial Building Construction and EPA Handbook for Sub-Slab Depressurization for Low Permeability Fill Material, both obtained from Department of Health Bureau of Environmental Toxicology, Radon and Indoor Air. 2. Specify a puncture resistance single-layer extruded polyolefin membrane, minimum 15 mils thick and maximum of perms, to provide a continuous barrier between compacted fill and the building s ground floor slab. Indicate on the construction drawings details of perimeter, penetrations, and joint conditions. Lap edges a minimum of 6 inches and seal with self-adhering joint tape. Ten mil polyolefin sheets and tape may be used at exterior slabs. April, 2017 Thermal and Moisture Protection 7-1

2 1.2 INSULATION A. Select the appropriate insulation system to comply with FBC and M-DCPS Maintenance & Operations - Roofing Division requirements. B. Design the thermal insulation system to fully protect the building s envelope. C. Specify insulation installation meeting MDCPS Division of Roofing requirements and FPL s roofing insulation rebate program, if available. D. Acceptable thermal wall insulation materials include: 1. According to the Florida Building Code (FBC), foam plastic insulation requires separation from the building interior by a thermal barrier of 1/2" gypsum wallboard or accepted equivalent. Lay-in ceilings do not qualify as an accepted thermal barrier. 2. Foil-faced fiber, fiberglass blanket or batt insulation between wall furring. 3. Other insulation materials or methods at locations where blanket or board insulation cannot be used, as accepted by MDCPS on per condition basis. E. Foamed-in-place insulation, in-cell Styrofoam inserts, and loose fill insulation in CMU walls are not allowed. F. Accepted roofing insulation materials include: 1. Lightweight insulating concrete over embedded styrene boards with minimum R-19 insulating value and 300 psi minimum compressive strength. 2. Rigid-board roof insulation alone is not allowed on new construction or re-roofing applications without prior written approval from M-DCPS Maintenance & Operations Roofing Division. For these cases, comply with the following: a. Rigid-board roof insulation shall be calculated as having a uniform minimum thickness, not an average thickness, and achieve a minimum R-value of 19 with R = 5.6 per inch. Additional tapered insulation to achieve slope shall not be included in this calculation. b. An overlayment or cover shall be used in addition to the HCFC isocyanurate foam board specified in this Division. The overlayment or cover board shall be either a glass faced gypsum roof board with integral surface treatment (Dens-Deck) or asphalt-impregnated glass fiber board (Sopraboard) as approved by the roof system manufacturer. No substitutions are allowed. Particleboard, wood fiber, perlite or wood composite boards shall not be used in a roofing assembly. 3. The perimeter of the lightweight insulating concrete on the roof insulation system, shall be encapsulated in 16-gauge galvanized Steel Roof Blocking (SRB) system that is properly secured to the structural deck to prevent uplift. G. Ceiling Insulation - Do not place thermal blankets insulation directly above suspended acoustical ceilings with recessed lighting fixtures or within 3 inches of the recessed lighting fixture enclosures, wiring compartments, or ballasts unless those fixtures are identified for such contact with insulation. 1.3 ROOFING A. General April, 2017 Thermal and Moisture Protection 7-2

3 1. Prior to submitting the Plans and Specifications to the Building Code Compliance (BCC) Office for permit approval, and prior to bidding or Contract negotiation, the Contract roofing specifications section and detail drawings shall be submitted for review and approval to M-DCPS Maintenance & Operations Roofing Division. 2. Roofing related shop drawings and product submittals from the Contractor shall be submitted for review and approval by M-DCPS Maintenance & Operations Roofing Division, prior to acceptance by the A/E. 3. Concerns of M-DCPS for recycling and other environmental matters apply to roofing systems and their manufacturing process. 4. Metal roofs are not allowed except for prefabricated metal walkway covers, under Division The A/E shall select a roofing system from the options listed in this Division. The A/E has the sole responsibility of designing and specifying roofing system best suited for the project, taking into account the following: a. M-DCPS Maintenance & Operations - Roofing Division requirements. b. Life cycle costs. c. Hurricane and puncture resistant. d. Resistance to vandalism and maintenance traffic. e. Maintenance. f. Warranty. g. Safety of occupants. h. Longevity. i. Reflectivity for energy conservation. j. Aesthetics. k. Compatibility with adjacent existing roofs. l. Weight of existing roof and condition of existing structure. m. Cost. 6. Roofing system and roofing components design shall comply with: a. FBC ASCE-7, FBC Roofing Application Standards (RAS), and FBC Test Application Standards (TAS). b. M-DCPS Maintenance & Operations - Roofing Division latest procedures, practices and System Guidelines Details. c. Missile impact requirements of SSTD d. Miami-Dade County Product Control or State of Florida Product Approval. e. Underwriters Laboratories UL-790 and ASTME-108 requirements for Class A fire rating for roof coverings. f. Factory Mutual requirements for Class I rated assembly and FM uplift classifications as determined by FBC ASCE-7. g. Energy Star roofing systems that comply with M-DCPS Master Specifications Guidelines and Design Criteria shall be evaluated by the A/E and presented to M- DCPS Division of Facilities Design and Standards for considerations and possible approval. 7. Specify job safety standards according to FBC, M-DCPS Safety, Environment, and Hazards Management, and OSHA, including 29 CFR Submit to the Building Code Consultant (BCC) calculations, signed and sealed by a Florida registered professional engineer, establishing wind velocity pressure values in accordance to FBC ASCE-7. Indicate on the construction drawings wind pressure tables applicable to the project. April, 2017 Thermal and Moisture Protection 7-3

4 9. Roof assembly edge guards shall be provided at rooftop equipment that is closer than 10 feet from the edge of the roof. Whenever possible the roof top equipment should be placed more than 10 feet from the edge of the roof so as to leave room for the FBC required edge guards. The edge guards must be engineered by the A/E of record, and shall be firmly anchored to the structure, and flashed. The edge guards should be anchored to the structure at the building fascia in lieu of anchoring through the roof membrane whenever possible. 10. Limit roofing materials to one roofing system at each facility. The use of more than one roofing system at a Facility, requires prior written approval from M-DCPS Maintenance & Operations Roofing Division, on a per condition basis. 11. Different roofing systems shall be separated by a parapet, change of elevations, or any other means of termination to define warranty/liability limits and maintenance responsibilities. 12. Install access ladders at roof-to-roof transitions exceeding 24 inches in height. 13. All roof penetrations (i.e., soil stacks, electrical conduits, mechanical equipment curbs and supports, roof hatches, etc) shall be located no less than 24 inches away from other penetrations, parapet walls, roof edges, and roof equipment curbs, etc. 14. Provide proper disposal of rainwater from roofs by scuppers, collector heads, gutters, rain leaders and downspouts complying with FBC - Plumbing requirements. 15. Ponding, for any period of time on any roof surface, is not allowed. 16. Products containing asbestos are not allowed. 17. Design and locate traffic pads or a surface sacrificial layer at all ladder landings, at the work sides of all roof-mounted equipment that may require maintenance or repair, roof and access doors, and on three sides of roof hatches. Specify a fully adhered non-skid surface of a suitable color different from that of the roof deck that is acceptable to M- DCPS Maintenance & Operations - Roofing Division. 18. See Division 5 and FBC Roof Assemblies and Rooftop Structures for equipment framing support requirements. 19. The construction drawings shall indicate complete flashing details covering all conditions were base flashing, counterflashing, expansion joint assemblies and/or copings occur, including, but not limited to, the structure of the parapets and intersecting walls, exterior finishes on both sides of the parapets and intersecting walls, the roof deck structure, the roofing membrane and roof insulation, cants, base flashings, counterflashings, copings, drainage assemblies (scuppers, overflow scuppers, gutters, collector heads, downspouts, drip edges), equipment supports and curbs, and all other components occurring in the details; all materials, components, assemblies and fabrications shall be called out, and the sizes and thickness of all materials and components shall be identified. B. Steep Sloped Roofs. 1. Use the following systems of roofs for slopes of 3-1/2:12 and greater: a. Barrel, flat, or Spanish S clay tile for historical buildings when accepted by M- DCPS Facilities Design and Standards on a per condition basis. b. Asphalt architectural dimensional-type 40-year or greater shingles, warranted for a 130-mph wind speed. At partial re-roofing projects, match existing conditions. 2. Minimum slopes shall comply with FBC - Building, Table Construction drawings for projects utilizing cement tile, clay tile or asphalt shingle roofs shall include complete details for the roofing installation and related conditions, April, 2017 Thermal and Moisture Protection 7-4

5 including, but not limited to, identification of the underlayment, flashings and drip edges (noting the materials used, their thickness, and methods of attachment to the building structure), and details at ridges, rakes, eaves, fascias and intersecting walls. C. Low Sloped Roofs. 1. Low slope roofs shall not exceed a slope of 2-1/2: Low slope roof design shall include a styrene butadiene styrene (SBS) modified bitumen roofing system with a 20-year no dollar limit manufacturer warranted. 3. Membrane lap seams shall be positioned to shed water. 4. Design the roof deck with 1/4" per foot slope. The use of higher sloping roofs requires prior written approval from M-DCPS Maintenance & Operations Roofing Division on a per condition basis. 5. Verify conformance to Class A fire rating for the proposed slope and comply with FBC - Building Tables A and B. 6. New construction: Styrene butadiene styrene (SBS) roof slopes, including crickets, shall be at least 1/4" per foot. 7. Re-roofing: SBS roof slopes shall be at least 1/8" per foot to existing drains or scuppers, with a minimum 1/4" per foot slope at crickets. Any ponding shall be eliminated in accordance with FBC - Building, High Velocity Hurricane Zones - Re-roofing. 8. Membranes with rubber composition or applied with hot asphalt are not accepted by M- DCPS. 9. Base sheets are required at lightweight concrete roof decks and other nailable substrates. Specify a mechanically attached impermeable polyester or polyesterfiberglass hybrid reinforced base sheet. 10. At granular mineral cap sheets, provide matching granules to cover exposed bitumen. D. Single Ply Roof Systems: 1. A single-ply roofing system shall only be used with prior written approval from M- DCPS Maintenance & Operations Roofing Division, and only on a per project basis. Single-ply roofing systems shall not be used in areas exposed to vandalism, heavy traffic or corrosive atmosphere. 2. Single-ply roofing systems shall be separated from SBS roofing systems with an area divider curb, expansion joint or other M-DCPS approved method, to define warranty/liability and maintenance responsibilities. E. Base Flashing: 1. All base flashings at parapets, walls, roof curbs and expansion joints shall be a 2-ply polyester or polyester/hybrid reinforced membrane with a minimum 8 inch vertical height above the finished roof surface. 2. Provide SRB metal cants at all base flashings locations. F. Parapets and Adjoining Walls: 1. For parapets or adjoining walls 60 inches or less in height a. Provide a termination bar along the top edge of the base flashing and wrap the remaining vertical stucco or pre-cast surface, including the top of the parapet or adjoining wall, with a reinforced one-ply granular surfaced polyester or polyester/glass hybrid, torch grade flashing membrane, placed over a primed substrate, ensuring proper overlap of the base flashing term bar. 2. For parapets or adjoining walls greater than 60 inches in height: April, 2017 Thermal and Moisture Protection 7-5

6 a. Provide a counter flashing at the top edge of the base flashing and the remaining vertical stucco or pre-cast surface above the counter flashing shall be waterproofed in accordance with the requirements noted in this Division. 3. The top of all parapet walls shall be covered by a stainless steel coping cap. a. Metal copings shall be secured by SRB hold-down cleats and be face fastened at inward facing parapet components with removable grommet type fasteners. 4. Slope the top of parapets, metal blocking, cleat, and coping caps 1 inch per foot down toward the wall s interior face. 5. At pre-cast (tilt-up wall construction) parapets: a. Tilt-up wall panel joints shall not have decorative reveals on the roof side of the wall within 2 inches above the counterflashing. Specify that all joint sealants shall be in place before parapet wall flashing or waterproofing/felt are installed. b. The tilt-up wall expansion joint sealant shall be extended all the way down to the roof deck on the roofing side of parapets. c. Provide sloped SRB blocking cleat and stainless steel coping across panel joints, allowing for expansion/contraction at the panel joints. d. Roofing sealants shall be compatible with the tilt-up wall expansion joint sealant. 6. Use the roofing systems manufacturer s published recommended primer at wall areas receiving bitumen type felts. 7. Seal built-up roofing flashing with cold bitumen and roofing tape, according to roofing manufacturer s requirements. 8. Indicate termination bars at the upper felt flashing terminal (horizontal) edge according to RAS 111. Do not omit termination bars due to metal counterflashing installation. G. Roof Venting 1. Mopped down or torched roof systems, or any other system using asphalt as an adhesive, over concrete roof decks shall be designed with a means to provide proper venting to eliminate blistering. a. No finished roof system shall be mopped or torched directly to a concrete deck substrate. Indicate a layer of insulation, such as lightweight insulating concrete, to receive the roofing base sheet on such roof decks. b. A concrete primer and vented base ply or insulation over interior or exterior spaces shall be included following the manufacturer s FM Uplift classifications as determined by FBC ASCE-7. c. Lightweight insulating concrete roof decks and fills shall receive an impermeable base sheet, mechanically anchored to the lightweight insulating concrete with the manufacturer s recommended roofing fasteners. 2. Provide metal roof vents over lightweight insulating concrete roof substrate on roofs located over gymnasiums and/or auditoriums. At all other areas, provide metal roof vents in roofing over lightweight insulating concrete roof decks and fills only if required by FBC or by roofing system manufacturer for its issuance of the 20-year warranty or for the roofing system s NOA (Notice of Acceptance) from the Miami- Dade County Building Department or another agency with the authority to approve decking/roofing systems. H. Re-Roofing. 1. Comply with FBC - Building, High Velocity Hurricane Zones Re-roofing edition designated for the project. April, 2017 Thermal and Moisture Protection 7-6

7 2. For re-roofing projects, the A/E will receive a work order from M-DCPS for the testing/re-roofing of a specific facility and may also receive related re-roofing information. 3. A/E shall identify defective portions of roof decks to be replaced before re-roofing. 4. A/E shall submit a re-roofing data sheet to M-DCPS Maintenance and Operations - Roofing Division before selecting the re-roofing system; the data sheet shall include the following: a. Roof s condition. b. Comments on the failure of the existing roof system. c. Age of roof. d. Verification of working and non-working exhaust vents and other mechanical equipment. e. Type of existing structural deck. f. Visual verification of the roof slope/drainage. g. Type of expansion joints. h. Extent of re-roofing work needed. i. Existing cracking of the roof deck and/or structure and subsurface conditions noted. j. Existing cracking or leaks in the parapet walls and corresponding parapet repair added to scope of work. 5. The A/E shall schedule an on-site pre-design conference with M-DCPS Maintenance & Operations - Roofing Division representatives and the school s principal to review the project data sheet and recommendations. The A/E shall record discussions and agreements and transmit the minutes of the conference to the M-DCPS representatives. 6. The A/E shall request from M-DCPS and schedule necessary test including, but not limited to, the following: a. Existence of asbestos roofing materials. b. Number of existing roof systems. c. Existence of insulation, the value of its thermal performance, and its moisture content. d. Type of existing roofing system and flashings. e. Type of the existing structure to verify its structural capacity, and if it is capable of supporting the proposed new roofing system. 7. After receiving satisfactory test results and if an overlay system is recommended by the A/E, an uplift test and applicable fastener pull out test are necessary to verify compliance with the uplift requirements for the basic wind speed for the project location per the FBC. 8. Specify the insulation installation so as to meet the FPL roofing insulation rebate program and M-DCPS re-roofing projects requirements. 9. On re-roofing projects, when a total roofing system removal is required, specify an adequate temporary seal to ensure weather tightness during re-roofing operations. I. Steel Roof Blocking (SRB) and Sheet Metal Flashing. 1. All SRB shall be galvanized steel and shall be provided with secured anchorage. 2. Wood blocking is not allowed. 3. All exposed metals used for the roofing and flashing systems shall be stainless steel, except roof drains flashing which shall be malleable copper. Use of lead flashing is not allowed. April, 2017 Thermal and Moisture Protection 7-7

8 4. Use SBC Industries flashings for all roof penetrations. 5. Neither pitch pans nor Chem-curbs are allowed 6. All fasteners used shall be removable exposed fasteners shall have grommetted washers. 7. Comply with RAS 111 and FBC Building, High Velocity Hurricane Zones-Weather Protection and Materials. 8. Sheet metal flashing for new and existing roofs shall comply with FM1-49 Loss Prevention Data Perimeter Flashing. 9. Sheet metal flashing shall comply with SMACNA, latest standards: a. New and re-roofing installations: Type 302 or gauge stainless steel. b. Historical buildings: Type 302 or gauge stainless steel or metal to match existing as accepted by M-DCPS, on a per condition basis. 10. Equipment curbs shall be prefabricated and installed on the structural deck so as to achieve the minimum height above the finished roof surface required by FBC, but no less than 14 inches above finish roof surface. Equipment curbs shall be anchored to the roof deck and/or building structure as necessary to resist hurricane wind forces in accordance with FBC - Building. The construction drawings shall indicate details with complete information covering the anchorage of the curbs and base flashing and counterflashing around the curbs. 11. All roof penetrations shall extend a minimum of 14 inches above the finished roof membrane, except 18 inches for mechanical supports. 12. Penetrations through the roof shall be kept to a minimum. Wherever possible, lightning protection penetrations shall be placed on the wall above the base flashing and not in the field of the roof. 13. All curbs shall have a minimum 1/2 inch per foot cricket on the upside slope of the curb. 14. Ensure that equipment (pipes, curbs, stands, roof jacks, lightning protection penetrations, hatches) maintain a minimum 24 inch distance from walls and other penetrations. J. Roof Expansion Joints. 1. Comply with FBC - Building, High Velocity Hurricane Zones - Roof Coverings with Slopes less than 2: Indicate expansion joints to allow for expansion and contraction to minimize cracking and deterioration of building component materials. The construction drawings shall indicate complete details for all roofing expansion joint assembly conditions provided in the project, which shall include, without being limited to, identification of all joint and roofing systems components and the structural roof deck, walls, parapets and other elements that occur at the locations of the details. 3. Roof expansion joints shall be compatible to the roofing manufacturer s specifications and recommendations. 4. Roof expansion joints shall be high profile, and insulated, with a minimum 16-gauge galvanized steel body and a minimum 26-gauge stainless steel cap. Expansion joints shall extend a minimum of 16 inches above the finish roof membrane. Wood nailers or exposed neoprene sheets are not allowed. K. Gutters and Downspouts. April, 2017 Thermal and Moisture Protection 7-8

9 1. Comply with RAS 111 and FBC - Building, High Velocity Hurricane Zones Weather Protection. 2. Interior roof drains, built-in gutters behind parapets, or parapet top gutters are not allowed. 3. Provide gutters and downspouts at edge of roof perimeters. 4. Gutters shall have rollover straps, 18-gauge minimum stainless steel, installed at a maximum of 30 inches on-center. All joints shall be soldered liquid gutter seal is not allowed. 5. The construction drawings shall contain complete details for all drip edges, scuppers, overflow scuppers, collector heads, gutters and downspouts, covering all parapet and roof edge conditions in the project, including, but not limited to, the sizes and sheet metal (stainless steel) gauges for all items, and their method of attachment to the building structure. 6. Specify the provision of a sheet metal sleeve to fill in an oversize scupper opening. Picture frame the inside and outside of all scuppers (working and overflow) and install sealant throughout prior to installing the collector head. 7. At tilt-up wall construction, scuppers and downspouts shall be offset a minimum of 12 inches from any tilt-wall panel joint. 8. Gutters, scuppers, and conductor heads shall be stainless steel. 9. Downspouts from conductor-head to 9 feet above finish grade shall be stainless steel. Downspouts from finish grade up to 9 feet above finish grade shall be Schedule 80 PVC. Provide a watertight connection at all stainless steel to PVC transition points. 10. Downspouts shall be connected to a storm drainage system and shall contain a clean-out at 18" above grade level. Collector heads shall include overflow provisions - a portion at the top of the collector head shall be lower than the top of the scupper draining into it, or an overflow relief opening shall be provided in the collector head near its top, so that water draining off of the roof would spill off of or out of the collector head, and not be able to back up onto the scupper and roof surface under instances of very heavy rain. 11. Downspouts discharging on grade require approval from M-DCPS Facilities Design and Standards on a per condition basis. When grade discharge is approved by M-DCPS, provide a poured in place concrete pads, not a pre-cast splash block, at downspout s discharge; the concrete pad must be indicated sloping away from the building. 12. At roof-to-roof transitions exceeding 24 inches in height, install gutters and downspouts. At discharge point provide an elbow and a polyester or polyester/glass hybrid reinforced, granular surface salvage sheet or traffic pad of a different color than the field of roofing cap sheet and adhered to roof membrane as recommended by the warranted roofing system manufacturer. 13. Paint PVC section of downspouts together with the fastening straps to match adjacent wall color. 14. Solder lap joints. Sealant at joints is not allowed. Provide expansion joints for thermal expansion and contraction. 15. Provide strap reinforcement with hemmed edges and no sharp edges. 16. Comply with SMACNA Architectural Sheet Metal Manual, latest edition, on material selection, fabrication and installation all sheet metal work 17. Sheet metal (stainless steel) diverters may be provided in retrofit projects over exterior door and window openings that do not have overhead roof protection, in order to correct reported water intrusion deficiencies through such openings. The top of such diverters shall have a bent-out flange that shall contain a bead of sealant that shall be April, 2017 Thermal and Moisture Protection 7-9

10 tooled concave to shed water. Such diverters shall be painted to match the wall of the building. The construction drawings shall include details for such diverters when they are provided in the project. 1.4 ROOF HATCHES, SMOKE VENTS, AND SKYLIGHTS A. Roof Hatches. 1. At new facilities, provide for safe and secured access by roof hatches (or, when approved, by steel doors in a penthouse enclosure served by stairs) to each flat roof where the roof deck or parapet exceeds 13 feet above adjacent finish grade or ground floor exterior slabs, or as otherwise required for safe and convenient maintenance access to the roof and rooftop equipment and mechanical appurtenances. a. Access to adjacent roofs, by roof hatches or penthouse door, is required if more than 42 inches above the other roof level. b. Fixed external ladders are allowed only between roof decks, and shall not be anchored to the roof deck or rest on the roof surface. 2. Roof hatches, at least 30 inches wide by 54 inches long, or other M-DCPS accepted means of roof access, shall be located in mechanical rooms, electrical rooms, custodial storage rooms, or other custodian controlled lockable spaces. 3. Roof hatch design and installation shall comply with FBC- Building, High Velocity Hurricane Zones designated for the project. 4. Submit to the Building Code Consultant (BCC) calculations, signed and sealed by a Florida registered professional engineer, establishing wind velocity pressure values in accordance with FBC ASCE See Division 5 for ladders. 6. See Division 8 for steel penthouse doors. 7. Coordinate the location of roof hatches with the roof framing in order to accomplish unobstructed access. 8. Roof hatches shall be connected to the school s intrusion alarm system and have a hasp at the interior. 9. A lift open handle shall be located on the ladder side of the roof hatch. B. Smoke Vents. 1. Provide smoke vents in accordance with FBC. 2. Smoke vents design and installation shall comply with FBC Building, High Velocity Hurricane Zones designated for the project. The latched smoke vent cover shall not deform or detach from the building in winds up to 150 mph. 3. Submit to the BCC calculations signed and sealed by a Florida registered professional engineer, establishing wind velocity pressure values in accordance with FBC ASCE Smoke vents shall be twin leaf, with spring counterbalances, and with fully insulated covers and curbs. 5. Provide each smoke vent a manual override internal cable release system in addition to the automatic latch release required by Code. 6. Provide each smoke vent a vent-open detector to register vent status with the building security system. 7. Coordinate location and orientation of smoke vents to permit cover release to be reached from a ladder. C. Skylights. April, 2017 Thermal and Moisture Protection 7-10

11 1. Skylights are not allowed. 2. Existing skylights shall be removed at re-roofing projects unless otherwise directed by M-DCPS. Indicate on the construction drawings complete details for the closure of openings at removed skylights; the construction of the closures shall match the existing structural deck and roofing system. D. See Division 5 Metals for equipment framing supports and clearances. 1.5 FIREPROOFING AND FIRESTOPPING A. Fireproofing and firestopping methods shall be UL approved and shown with UL assembly number listings, and complete specifications, and details in the construction documents. B. Interior steel structural surfaces requiring fireproofing shall receive non-fibered spray-applied fire resistive materials. C. Indicate on the plans and sections of the construction drawings all code-required fire-rated wall/partition and floor/ceiling/roof assemblies being penetrated by pipes, conduits and ducts, and their required ratings, and indicate UL, FM and other tested, accepted firestopping/sealing assemblies that will maintain the required wall/partition or floor/ceiling/roof fire-rating at the penetrations, with complete details and specifications for the selected assemblies. 1.6 JOINT SEALANTS A. Detail and specify the appropriate joint sealants and backings at the following interior or exterior locations. 1. Vertical and horizontal surfaces. 2. Traffic areas. 3. Kitchen areas for vermin protection. 4. Around door and window openings, at both exterior and interior sides. B. Specify single source responsibility for each joint material type. C. Joint sealants, fillers, and other related materials shall be compatible with one another, the joint substrates, adjacent materials, and different assemblies including finishes and the roofing membrane. Colors of sealants shall preferably match as closely as possible to, or be compatible with, the colors of the surfaces abutting the joint being sealed. D. On tilt-up wall panels, joint sealants shall be of vandal-resistant quality from grade level 10 feet above grade. E. The width of non-expansion joints being sealed shall be minimized, as needed to achieve a neat appearance that does not call undue attention to the joint being sealed; the width of expansion joints shall be determined by the amount of expansion occurring across the joint, as determined the structural calculations, or, when such calculations are not feasible, by generally considered good construction practice. April, 2017 Thermal and Moisture Protection 7-11

12 F. Sealed joints shall be indicated as tooled concave, and the sealant shall be oriented so as to shed water away from the joint and away from the building. G. At masonry openings at windows (including, but not limited to, CMU and tilt-up concrete panel construction), the exterior horizontal surface of the windowsill shall be designed to slope not less than 1:3 away from the window frame. The window frames or sub-bucks around the window frames, when provided, shall be set in thick beads of sealant on all sides (sill, jambs and head) H. Aluminum thresholds and saddles at exterior doors shall be set in (preferably, pressed into) heavy beds of sealant. END OF DIVISION April, 2017 Thermal and Moisture Protection 7-12

DIVISION 7 - THERMAL AND MOISTURE PROTECTION

DIVISION 7 - THERMAL AND MOISTURE PROTECTION I. GENERAL DIVISION 7 - THERMAL AND MOISTURE PROTECTION A. This division contains the following elements: 1. Waterproofing and Vapor Retarders. 2. Insulation. 3. Fireproofing and Firestopping. 4. Roofing.

More information

Update In Progress. Division 7 Thermal and Moisture Protection Page Section ROOFING AND WATERPROOFING

Update In Progress. Division 7 Thermal and Moisture Protection Page Section ROOFING AND WATERPROOFING Section 07 10 00 ROOFING AND WATERPROOFING Page 07 10 00-1 1. GENERAL REQUIREMENTS A. Indicate applicable American Society for Testing and Materials (ASTM) specification in this section. 01. Fire resistance

More information

SECTION FLASHING AND SHEET METAL

SECTION FLASHING AND SHEET METAL SECTION 07600 FLASHING AND SHEET METAL ****** **** **** *** ** * ** *** **** ***** ****** NOTE TO SPECIFIER: See MDCPS Design Criteria for flashing condition requirements. ****** **** **** *** ** * **

More information

DIVISION 07 THERMAL AND MOISTURE PROTECTION ROOFING

DIVISION 07 THERMAL AND MOISTURE PROTECTION ROOFING 07 00 00 PART 1 - GENERAL 1.01 DESIGN CRITERIA A. Preferred roofing types include Membrane, Metal, and Composition Shingles. 1. Membrane roofing is preferred for flat roof decks. 2. Use of asphalt-based

More information

C. Jointing of Exterior Vertical Surfaces. Section D. The Secretary of the US Department of the Interior s Standards for Rehabilitation.

C. Jointing of Exterior Vertical Surfaces. Section D. The Secretary of the US Department of the Interior s Standards for Rehabilitation. PART 1: GENERAL 1.01 Scope Of Standard A. This standard provides general guidance concerning the specific preferences of the University of Texas at Austin for roofing systems. B. UT recognizes that project

More information

Light-Metal Roof Edge, Raised

Light-Metal Roof Edge, Raised NAIL WOOD CANT TO BLOCKING 2 ROWS STAGGERED EACH ROW 24 O.C. 1/2 MIN. 10 0 MAX. FASTEN 18 O.C. WITH NEOPRENE GASKETED FASTENERS 3-1/2 MIN. 4 6 JOINT COVER PLATE SET IN TWO BEADS OF SEALANT 4 MIN. SPECIFIED

More information

Tuscaloosa Police Station

Tuscaloosa Police Station Tuscaloosa Police Station 3801 Trevor S Phillips Ave Tuscaloosa, AL 35401 Core Cut: Spray Foam Roof- ½ thick +- Single Ply Membrane Tapered EPS Insulation 2-6 Metal Deck PART 1 GENERAL 1.1 SCOPE OF WORK

More information

SECTION 07530CP EPDM MEMBRANE ROOFING

SECTION 07530CP EPDM MEMBRANE ROOFING PART 1 GENERAL 1.1 SUMMARY SECTION 07530CP EPDM MEMBRANE ROOFING A. Section includes: 1. Adhered membrane roofing and flashing 2. Mechanically fastened roof insulation 3. Walkway pads 1.2 ARCHITECTURAL

More information

Architectural Wall Products Guide Specifications

Architectural Wall Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Wall Products Guide Specifications FORMED METAL WALL PANELS This Guide Specification is

More information

WICOMICO COUNTY BOARD OF EDUCATION

WICOMICO COUNTY BOARD OF EDUCATION GLEN AVENUE ELEMENTARY SCHOOL RO REPLACEMENT PROJECT NUMBER: PSC #.00.9 SR CURRENT CODES: 05 INTERNATIONAL BUILDING CODE 05 INTERNATIONAL MECHANICAL CODE NATIONAL STANDARD PLUMBING CODE (MBPS) 05 EDITION

More information

1 Exam Prep Architectural Sheet Metal Manual Tabs and Highlights

1 Exam Prep Architectural Sheet Metal Manual Tabs and Highlights 1 Exam Prep Architectural Sheet Metal Manual Tabs and Highlights These 1 Exam Prep tabs are based on the 2012 Sheet Metal and Air Conditioning Contractors' National Association, Inc., seventh edition.

More information

WVU DESIGN GUIDELINES & CONSTRUCTION STANDARDS DIVISION 07 THERMAL AND MOISTURE PROTECTION

WVU DESIGN GUIDELINES & CONSTRUCTION STANDARDS DIVISION 07 THERMAL AND MOISTURE PROTECTION 075000 ROOFING SYSTEMS PART 1 - GENERAL 1.1. Any deviation from the following instructions must be approved during design by WVU Facilities Management Personnel. 1.2. DEFINITIONS A. ASTM American Society

More information

Architectural Roof Products Guide Specifications

Architectural Roof Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Roof Products Guide Specifications FORMED METAL ROOF AND WALL PANELS This Guide Specification

More information

SECTION CLAY BARREL TILE ROOFING. A. American Society for Testing and Materials (ASTM):

SECTION CLAY BARREL TILE ROOFING. A. American Society for Testing and Materials (ASTM): SECTION 07320 CLAY BARREL TILE ROOFING PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 02072 - Removals. 2. 07600 - Flashing and Sheet Metal. 1.02 REFERENCES A. American Society for Testing and Materials

More information

Architectural Roof and Wall Products Guide Specifications

Architectural Roof and Wall Products Guide Specifications Architectural Roof and Wall Products Guide Specifications 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL ROOF AND WALL PANELS This Guide Specification is to be used

More information

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 075423 - THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Division 00 Bidding Requirements and other Division

More information

Architectural Roof Products Guide Specifications

Architectural Roof Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Roof Products Guide Specifications FORMED METAL ROOF AND WALL PANELS This Guide Specification

More information

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof SECTION 07550 MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof This section is based on the products of MFM Building Products Corp., which is located at: 525 Orange St. P. O. Box 340 Coshocton, OH 43812

More information

SAM HOUSTON STATE UNIVERSITY DIVISION 07 THERMAL & MOISTURE PROTECTION SECTION ROOFING SYSTEMS DESIGN AND CONSTRUCTION STANDARDS February 2016

SAM HOUSTON STATE UNIVERSITY DIVISION 07 THERMAL & MOISTURE PROTECTION SECTION ROOFING SYSTEMS DESIGN AND CONSTRUCTION STANDARDS February 2016 PART 1: GENERAL 1.01 Scope Of Standard 1.02 Reference Standards 1.03 Quality Control A. This standard provides general guidance concerning the specific preferences of the Sam Houston State University for

More information

Architectural Roof and Wall Products Guide Specifications

Architectural Roof and Wall Products Guide Specifications Architectural Roof and Wall Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL WALL PANELS This Guide Specification

More information

C. All roofs shall be installed according to manufacturers guidelines. Corrections due to workmanship shall be at contractors expense.

C. All roofs shall be installed according to manufacturers guidelines. Corrections due to workmanship shall be at contractors expense. PART 1: GENERAL 1.01 Scope Of Standard 1.03 Reference Standards 1.04 Quality Control A. This standard provides general guidance concerning the specific preferences of the Sam Houston State University for

More information

SECTION CLAY BARREL TILE ROOFING Removals Flashing and Sheet Metal.

SECTION CLAY BARREL TILE ROOFING Removals Flashing and Sheet Metal. SECTION 07320 CLAY BARREL TILE ROOFING PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 02072 - Removals. 2. 07600 - Flashing and Sheet Metal. 1.02 REFERENCES A. American Society for Testing and Materials

More information

UNIVERSITY OF MISSOURI Division 07 Thermal and Moisture Protection Roofing:

UNIVERSITY OF MISSOURI Division 07 Thermal and Moisture Protection Roofing: Roofing: 1. Materials used for moisture protection will comply with specifications contained in the appropriate American Society for Testing and Material standards (ASTM). 2. General roof specification

More information

B. Coordinate all Roof Assembly components with work before and after. See especially:

B. Coordinate all Roof Assembly components with work before and after. See especially: 07500 ROOF ASSEMBLY ************************************************************************************************************* SPECIFIER: All roof-related items above or outside the structural roof

More information

ROOFING CONTRACTORS GENERAL TRADE KNOWLEDGE EXAMINATION CONTENT INFORMATION

ROOFING CONTRACTORS GENERAL TRADE KNOWLEDGE EXAMINATION CONTENT INFORMATION ROOFING CONTRACTORS GENERAL TRADE KNOWLEDGE EXAMINATION CONTENT INFORMATION Revised September 14 The General Trade Knowledge portion of the examination is administered daily in Computer Based Testing (CBT)

More information

SECTION THERMOPLASTIC MEMBRANE ROOFING. C. Flashings. D. Roofing cant strips, stack boots, roofing expansion joints, and walkway pads.

SECTION THERMOPLASTIC MEMBRANE ROOFING. C. Flashings. D. Roofing cant strips, stack boots, roofing expansion joints, and walkway pads. McClellan Blakemore Architects New Warehouse Facility for SECTION 07540 THERMOPLASTIC MEMBRANE ROOFING PART 1 GENERAL 1.01 SECTION INCLUDES A. Adhered system with thermoplastic roofing membrane. B. Insulation,

More information

1.2 DEFINITIONS, REFERENCES, AND OVERALL STANDARDS Follow 07500

1.2 DEFINITIONS, REFERENCES, AND OVERALL STANDARDS Follow 07500 07721 ROOF ASSEMBLY SUPPORTS FOR ROOFTOP EQUIPMENT ****************************************** SPECIFIER: All roof-related items above or outside the structural roof deck, including such work as blocking,

More information

SECTION ELASTOMERIC MEMBRANE ROOFING ADDENDUM 10 APRIL 20, 2011

SECTION ELASTOMERIC MEMBRANE ROOFING ADDENDUM 10 APRIL 20, 2011 SECTION 07553 ELASTOMERIC MEMBRANE ROOFING ADDENDUM 10 APRIL 20, 2011 PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Elastomeric roofing membrane (EPDM), conventional application at low slope roof

More information

SECTION ROOF SPECIALTIES

SECTION ROOF SPECIALTIES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 71 00 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Seal

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Seal SECTION 07550 MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Seal This section is based on the products of MFM Building Products Corp., which is located at: 525 Orange St. P. O. Box 340 Coshocton, OH 43812

More information

SECTION ROOF ACCESSORIES PART 1 GENERAL 1.1 RELATED DOCUMENTS

SECTION ROOF ACCESSORIES PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 07 72 00 ROOF ACCESSORIES PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION THERMOPLASTIC MEMBRANE ROOFING PART 1 GENERAL 1.01 SECTION INCLUDES

SECTION THERMOPLASTIC MEMBRANE ROOFING PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING PART 1 GENERAL 1.01 SECTION INCLUDES A. Mechanically attached system with thermoplastic roofing membrane. B. Insulation, flat and tapered. C. Flashings. D.

More information

ROOFING EPDM ELASTOMERIC SHEET ROOFING FULLY ADHERED- CONVENTIONAL

ROOFING EPDM ELASTOMERIC SHEET ROOFING FULLY ADHERED- CONVENTIONAL ROOFING EPDM ELASTOMERIC SHEET ROOFING FULLY ADHERED- CONVENTIONAL PART 1 GENERAL 1.1 SECTION INCLUDES A. Insulation, membrane roofing, base flashings roofing membrane accessories joints, and counter flashings.

More information

The Alabama Building Commission has adopted the 2006 International Energy Conservation Code as the State Energy Conservation Code

The Alabama Building Commission has adopted the 2006 International Energy Conservation Code as the State Energy Conservation Code SECTION 07 20 00 THERMAL PROTECTION SCOPE OF WORK This Section includes building wall, floor and ceiling insulation, and roofing. QUALITY ASSURANCE For all new construction projects and renovation projects

More information

DIVISION MEMBRANE ROOFING & ROOFING ACCESSORIES

DIVISION MEMBRANE ROOFING & ROOFING ACCESSORIES DIVISION 07 50 00 MEMBRANE ROOFING & ROOFING ACCESSORIES A. Final selection and approval of the roofing system for new construction and reroofing is reserved by the UAO. These guidelines, in consultation

More information

DUKE UNIVERSITY CONSTRUCTION STANDARDS

DUKE UNIVERSITY CONSTRUCTION STANDARDS 1 07 40 00 Roofing 1. General Several factors repeatedly show up during the inspection of roofs that have failed prematurely. They include inappropriate use of materials, poor drainage systems, poor details

More information

Banyan Air Service November 18, 2011 AVE Aviation and Commerce Center Building 1 Miami, FL

Banyan Air Service November 18, 2011 AVE Aviation and Commerce Center Building 1 Miami, FL SECTION 07543 - THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Hobby Parking Office HOU/ Proj./ No. 738 Houston, Texas 100% Bid and Construction Documents- Addendum #2, January 26, 2017

Hobby Parking Office HOU/ Proj./ No. 738 Houston, Texas 100% Bid and Construction Documents- Addendum #2, January 26, 2017 SECTION 077200 - ROOF ACCESSORIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

DIVISION 7 - THERMAL AND MOISTURE PROTECTION

DIVISION 7 - THERMAL AND MOISTURE PROTECTION 07100 WATERPROOFING 07150 DAMPPROOFING 07175 Water Repellent Coatings 07190 VAPOR AND AIR RETARDERS 07192 Vapor Retarders 07200 INSULATION 07240 Exterior Insulation and Finish Systems 07250 FIREPROOFING

More information

Roof Replacement. Notes: T-1 (Title Sheet) Roof Key Plan Russell House Student Union 1400 Greene Street Columbia, South Carolina 29208

Roof Replacement. Notes: T-1 (Title Sheet) Roof Key Plan Russell House Student Union 1400 Greene Street Columbia, South Carolina 29208 Notes: Drawing Index T-1 Title R-1 Roof Plan - Existing Conditions R-2 Roof Plan - New D-1 Roof Details D-2 Roof Details D-3 Roof Details M-1 Mechanical - Roof Plan M-2 Mechanical - Details Roof Key Plan

More information

DIVISION 07 - THERMAL & MOISTURE PROTECTION

DIVISION 07 - THERMAL & MOISTURE PROTECTION DIVISION 07 - THERMAL & MOISTURE PROTECTION DESIGN CRITERIA General Design Requirements: 1. When designing roof access ladders and stairways to roof shall not be alternating tread type. 2. Provide 18 gauge

More information

SECTION LIGHTWEIGHT INSULATING CONCRETE

SECTION LIGHTWEIGHT INSULATING CONCRETE SECTION 03342 LIGHTWEIGHT INSULATING CONCRETE PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 03300 - Cast-In-Place Concrete. 2. 05310 - Steel Deck. 3. 07511 - Multi-Ply Mineral Surfaced Built-Up Roofing

More information

OREGON ROOF CONSULTING - ROOF INSPECTION FORM

OREGON ROOF CONSULTING - ROOF INSPECTION FORM Oregon CCB: 199121 PO Box 220190, Milwaukie, OR 97222 Washington License: OREGORC871MR OREGON ROOF CONSULTING - ROOF INSPECTION FORM General Roof Conditions: NA = Not Applicable Debris on Roof Physical

More information

ROOF ASSEMBLIES CHAPTER 9

ROOF ASSEMBLIES CHAPTER 9 CHAPTER 9 ROOF ASSEMBLIES SECTION R901 GENERAL R901.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies. SECTION R902 ROOF CLASSIFICATION

More information

Reliance on "after-the-fact" material selections to compensate for a problematic design decision is unacceptable.

Reliance on after-the-fact material selections to compensate for a problematic design decision is unacceptable. Section 07000 - General Discussion This General Discussion Section contains material which is critical to successful moisture protection systems in new construction and renovation, but which is not the

More information

RECOMMENDED DESIGN SPECIFICATION

RECOMMENDED DESIGN SPECIFICATION RECOMMENDED DESIGN SPECIFICATION SILICONE COATED SPF ROOFING 1 General 1.1 Section Includes A. Silicone coated SPF roofing system, including substrate board, roof insulation boards, foam insulation materials,

More information

ZARA & ASSOCIATES, INC. Peter L. Zara 8435 Sunrise Lake Blvd -# Sunrise, Florida Phone

ZARA & ASSOCIATES, INC. Peter L. Zara 8435 Sunrise Lake Blvd -# Sunrise, Florida Phone 12 ZARA & ASSOCIATES, INC. Peter L. Zara 8435 Sunrise Lake Blvd -#43-307 Sunrise, Florida 33322 Phone 305-345-3793 E-Mail: peterizara@hotmail.com COURSE MATERIALS ROOFING COURSE WITH UPDATED MATERIALS

More information

Architectural Roof and Wall Products Guide Specifications

Architectural Roof and Wall Products Guide Specifications Architectural Roof and Wall Products Guide Specifications 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL ROOF AND WALL PANELS This Guide Specification is to be used

More information

SECTION METAL ROOF AND SOFFIT PANELS

SECTION METAL ROOF AND SOFFIT PANELS Metal Panel Systems, Inc. 11506 Reading Road Cincinnati, Ohio 45241-2512 Telephone: 800-554-6126 or 513-554-6120 Fax: 513-554-6121 www.metalpanelsystems.com info@metalpanelsystems.com Specifications for

More information

EverGuard Plaza Deck Roofing For Above-Grade Plaza Deck Applications

EverGuard Plaza Deck Roofing For Above-Grade Plaza Deck Applications EverGuard Plaza Deck Roofing For Above-Grade Plaza Deck Applications Specifications Updated: 12/07 Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer PLAZA DECK ROOFING

More information

A. National Roofing Contractors Association (NRCA) Roofing and Waterproofing Manual

A. National Roofing Contractors Association (NRCA) Roofing and Waterproofing Manual SECTION 07 22 16 - ROOF AND DECK INSULATION Specifier Note: There are numerous types of roof insulation, some which are installed in multiple-layer roof assemblies. Specifier to verify Project requirements

More information

C. Counterflashings at roof-mounted mechanical equipment, vent stacks, curbs, and miscellaneous roof penetrations.

C. Counterflashings at roof-mounted mechanical equipment, vent stacks, curbs, and miscellaneous roof penetrations. ms1505 SECTION 07 60 00 - Page 1 PART 1 GENERAL 1.01 SECTION INCLUDES A. Coping flashing and cleats. B. Counterflashings at roof edge. C. Counterflashings at roof-mounted mechanical equipment, vent stacks,

More information

ROOF MITIGATION STRUCTURE EVALUATION FORM. For Single Family Residential Re-Roof Effective October 1, 2007 (Revised February 2, 2018)

ROOF MITIGATION STRUCTURE EVALUATION FORM. For Single Family Residential Re-Roof Effective October 1, 2007 (Revised February 2, 2018) ROOF MITIGATION STRUCTURE EVALUATION FORM For Single Family Residential Re-Roof Effective October 1, 2007 (Revised February 2, 2018) Check One Value of home does not exceed $300,000 based on insured value

More information

REROOFING ANALYSIS OF K-12 BUILDING. Unified School District 306 Gypsum, Kansas

REROOFING ANALYSIS OF K-12 BUILDING. Unified School District 306 Gypsum, Kansas REROOFING ANALYSIS OF K-12 BUILDING Unified School District 306 Gypsum, Kansas Reroofing Analysis of K-12 Building Unified School District 306 Gypsum, Kansas September 12, 2017 P1711 Introduction This

More information

DIVISION 7 THERMAL AND MOISTURE PROTECTION

DIVISION 7 THERMAL AND MOISTURE PROTECTION DIVISION 7 THERMAL AND MOISTURE PROTECTION UCSC Campus Standards Handbook Waterproofing Standards 07100 1 SECTION 07100: WATERPROOFING STANDARDS A. Guarantee 1. Provide a guarantee on Contractor's letterhead

More information

SECTION MANUFACTURED ROOF EXPANSION JOINTS

SECTION MANUFACTURED ROOF EXPANSION JOINTS SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Section X - Miscellaneous

Section X - Miscellaneous Section X - Miscellaneous A. Introduction This section provides design criteria, specific requests/recommendations and preferences related to specifying and constructing systems and materials used in HRSD

More information

3. Roof Expansion Joints between New Building and Existing Building.

3. Roof Expansion Joints between New Building and Existing Building. SECTION 077200 - ROOF ACCESSORIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Amendments to General Conditions and Division 01 Specification

More information

SECTION THERMAL INSULATION

SECTION THERMAL INSULATION PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 21 13 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT. A. ASME B31.1 (American Society of Mechanical Engineers) - Power Piping

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT. A. ASME B31.1 (American Society of Mechanical Engineers) - Power Piping SECTION 22 05 29 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes pipe and equipment supports, hangers, anchors, bases sleeves and the sealing of

More information

Section 32 - Miscellaneous

Section 32 - Miscellaneous Section 32 - Miscellaneous A. Introduction This section provides design criteria, specific requests/recommendations and preferences related to specifying and constructing systems and materials used in

More information

1. Selective Demolition Section Adhered PVC Roofing System Section Sealants and Caulking Section 07920

1. Selective Demolition Section Adhered PVC Roofing System Section Sealants and Caulking Section 07920 SECTION 07620 - FLASHING AND SHEET METAL PART 1 - GENERAL 1.01 DESCRIPTION A. Work included: Provide all flashing and sheet metal not specifically described in other Sections of these Specifications but

More information

BUILDING ENVELOPE DESIGN GUIDELINES APPENDIX 3

BUILDING ENVELOPE DESIGN GUIDELINES APPENDIX 3 PART 1 GENERAL BUILDING ENVELOPE DESIGN GUIDELINES 1.01 INTRODUCTION A. This is a guideline on the Owner s minimum standards for: 1. Masonry Division 04 2. Copings Division 04 or 07 3. Cavity wall flashings

More information

SECTION ROOF ACCESSORIES

SECTION ROOF ACCESSORIES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 72 00 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information

SECTION Tile Roof Guideline. B. "Pan" Tile: Clay tile on the underlayment, convex in shape.

SECTION Tile Roof Guideline. B. Pan Tile: Clay tile on the underlayment, convex in shape. SECTION 07 32 13 Tile Roof Guideline PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The drawings and general provisions of the contract, including General and Specific Conditions, and Division 1 (General Requirements)

More information

A. Provide all labor, equipment, and materials fabricate and install the following. 2. Counterflashings over bituminous base flashing.

A. Provide all labor, equipment, and materials fabricate and install the following. 2. Counterflashings over bituminous base flashing. SECTION 076200 - FLASHING AND SHEET METAL PART 1 GENERAL 1.1 SECTION INCLUDES: A. Provide all labor, equipment, and materials fabricate and install the following. 1. Edge strip and flashing. 2. Counterflashings

More information

TYPICAL ROOF CONDITION LAYOUT

TYPICAL ROOF CONDITION LAYOUT FIXED POINTS TYPICAL ROOF CONDITION LAYOUT 15 17 9 16 29 12 14 11 3 7 35 20 6 23 30 31 24 13 18 Typical Roof Condition Layout... 1 Low Eave Isometric View - Fixed/ Floating... 2 Low Eave Section - Fixed/

More information

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION METAL ROOF PANELS

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION METAL ROOF PANELS OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 SECTION INCLUDES A. Structural roofing system of preformed steel panels. B. Fastening system. C. Factory finishing. D. Accessories and miscellaneous components.

More information

SECTION ROOF AND DECK INSULATION

SECTION ROOF AND DECK INSULATION SECTION 07 22 00 ROOF AND DECK INSULATION SPEC WRITER NOTES: 1. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. Follow recommendations of National Roofing Contractors

More information

SECTION THERMAL INSULATION

SECTION THERMAL INSULATION Pactiv Building Products 2100 RiverEdge Parkway Suite 175 Atlanta, GA 30328 Toll Free: (800) 241-4402 Web Site: www.green-guard.com SECTION 07210 THERMAL INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS

More information

2002 Advanced Building Products, Inc., P.O. Box 98, Springvale, Maine TEL: ; FAX: ; WEBSITE:

2002 Advanced Building Products, Inc., P.O. Box 98, Springvale, Maine TEL: ; FAX: ; WEBSITE: SECTION 07651 FLEXIBLE COPPER SHEET FLASHINGS Advanced Building Products, Inc. manufacturer many types of flexible copper sheet flashings. Due to their ductility, high tensile strength, and resistance

More information

OREGON CONVENTION CENTER CHILLER PLANT RE-DESIGN CD SET

OREGON CONVENTION CENTER CHILLER PLANT RE-DESIGN CD SET SECTION 07 54 19 - POLYVINYL-CHLORIDE (PVC) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION SELF-ADHERED WATER-RESISTIVE ROOF UNDERLAYMENT

SECTION SELF-ADHERED WATER-RESISTIVE ROOF UNDERLAYMENT SECTION 07 30 05.01 SELF-ADHERED WATER-RESISTIVE ROOF UNDERLAYMENT SPEC WRITERS NOTE: This specification includes materials and installation procedures for SlopeShield SA Self-Adhered Water-Resistive Vapor

More information

DATE R2.2 ROOF DETAILS - BUILT UP ROOF DETAILS CURBS. An Company PHONE:

DATE R2.2 ROOF DETAILS - BUILT UP ROOF DETAILS CURBS. An Company PHONE: A B C D E F G H I J K L M N O P Q R S T U V 5 6 7 8 9 0 5 6 7 8 9 0 5 6 7 8 9 9 GENERAL ROOFING NOTES - VILLAGE POLICE STATION ROOF REPLACEMENT PROJECT - 06 PLANS AND DETAILS - MARCH 0TH, 06. CONTRACTOR

More information

SSL-175. Specifications

SSL-175. Specifications SSL-175 Specifications Everlast Metals 10 Enterprise Court Lebanon, PA 17042 Phone: (717) 270-6554 Fax: (717) 270-6569 www.everlastmetals.com 7410 Preformed Metal Roofing PART 1: GENERAL 1.01 SECTION INCLUDES

More information

SECTION HVAC GRAVITY VENTILATORS

SECTION HVAC GRAVITY VENTILATORS SECTION 23 37 23 HVAC GRAVITY VENTILATORS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

G October 2018

G October 2018 G-13-18 VacuSeal TM Vent Secured Roofing Systems October 2018 The information contained in this supplement serves as a criteria for Specifiers and Authorized Applicators regarding the design and installation

More information

Sheet Metal Flashing and Trim

Sheet Metal Flashing and Trim University of New Hampshire University of New Hampshire Scholars' Repository Division 07 Thermal and Moisture Protection Chapter 5 Technical Construction and Renovation Standards 1-25-2013 076200 - Sheet

More information

A. Coordinate Roof Assembly roof insulation work with work before and after. See especially:

A. Coordinate Roof Assembly roof insulation work with work before and after. See especially: 07620 ROOF ASSEMBLY STEEL BLOCKING AND SHEET METAL ************************************************************************************************************* SPECIFIER: All roof-related items above

More information

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET Environmental Protection and Growth Management Department BUILDING CODE SERVICES DIVISION 1 N. University Drive, Box #302 Plantation, Florida 33324 954-765-4400 Broward.org/Building APPLICATION INFORMATION

More information

Hawthorne Fire Station Repairs Section Page 1 of 8

Hawthorne Fire Station Repairs Section Page 1 of 8 Hawthorne Fire Station Repairs Section 07620 Page 1 of 8 SECTION 07620 - SHEET METAL FLASHING AND TRIM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including

More information

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION 23 05 29 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes pipe and equipment supports, hangers, anchors, bases sleeves and the sealing of work

More information

FirstEnergy Program Overview

FirstEnergy Program Overview FirstEnergy Program Overview Builder incentives $400 per unit + $0.10/kWh in projected savings Eligibility Located in service area of a FirstEnergy Utility Certificate of Occupancy Dates: FirstEnergy Ohio

More information

G October 2018

G October 2018 G-14-18 October 2018 The information contained in this supplement serves as a criteria for Specifiers and Authorized Applicators regarding the design and installation of Carlisle Roofing Systems and use

More information

CITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO

CITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO SECTION 07220 - ROOF INSULATION PART 1 - GENERAL 1.01 DESCRIPTION A. Work included: The Roofing Contractor will provide all polyisocyanurate insulation and high density wood fiber roof insulation (tapered

More information

ROOF ASSEMBLIES CHAPTER 9

ROOF ASSEMBLIES CHAPTER 9 CHAPTER 9 ROOF ASSEMBLIES SECTION R901 GENERAL R901.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies. SECTION R902 ROOF CLASSIFICATION

More information

Coal Tar Application and Design Considerations

Coal Tar Application and Design Considerations Coal Tar Application and Design Considerations 400 Old Reading Pike, Suite 304 Pottstown, PA 19464 Tel: 610-579-9075 Fax: 610-323-0115 www.durapax.com The proper specification of any roof system is extremely

More information

Roof Replacement. Notes: T-1 (Title Page) 709 Bull Street Columbia, South Carolina. University of South Carolina. Callcott Social Science

Roof Replacement. Notes: T-1 (Title Page) 709 Bull Street Columbia, South Carolina. University of South Carolina. Callcott Social Science Notes: Drawing Index T-1 Title R-1 Roof Plan - Existing Conditions R-2 Roof Plan - New D-1 Roof Details D-2 Roof Details S1.0 Safety Anchor Plan Building 709 Bull Street Columbia, 1 10/13 T-1 (Title Page)

More information

When submitting the edited forms to the A/E for approval, provide an additional copy that clearly notes any changes that have been made in the text.

When submitting the edited forms to the A/E for approval, provide an additional copy that clearly notes any changes that have been made in the text. 07501 ROOF ASSEMBLY SPECIAL WARRANTY FORMS ****************************************** Specifier: This section contains two forms that will be used by the Contractor to prepare its Notice of Intent and

More information

SECTION CONCRETE TILE ROOFING. A. American Society for Testing and Materials (ASTM):

SECTION CONCRETE TILE ROOFING. A. American Society for Testing and Materials (ASTM): SECTION 07324 CONCRETE TILE ROOFING PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 06100 - Carpentry. 2. 07600 - Flashing and Sheet Metal. 1.02 REFERENCES A. American Society for Testing and Materials

More information

HALIFAX HUMANE SOCIETY BOARDING AND GROOMING FACILITY SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS

HALIFAX HUMANE SOCIETY BOARDING AND GROOMING FACILITY SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS SECTION 075216 - PART 1 - GENERAL 1.1 SUMMARY A. Section includes styrene-butadiene-styrene (SBS) modified bituminous membrane roofing. 1.2 DEFINITIONS A. Hot Roofing Asphalt: Roofing asphalt heated to

More information

6. ENGINEERING SYSTEMS REQUIREMENTS B30 ROOFING B30 GENERAL SYSTEM DESCRIPTION

6. ENGINEERING SYSTEMS REQUIREMENTS B30 ROOFING B30 GENERAL SYSTEM DESCRIPTION 6. ENGINEERING SYSTEMS REQUIREMENTS B30 ROOFING SYSTEMS REQUIREMENTS ROOFING TEMPLATE 02/18 Instructions for using this template: There are template files for each UNIFORMAT Level 2 Group Elements. This

More information

6. ENGINEERING SYSTEMS REQUIREMENTS B30 ROOFING B30 GENERAL SYSTEM DESCRIPTION

6. ENGINEERING SYSTEMS REQUIREMENTS B30 ROOFING B30 GENERAL SYSTEM DESCRIPTION 6. ENGINEERING SYSTEMS REQUIREMENTS B30 ROOFING SYSTEMS REQUIREMENTS ROOFING TEMPLATE 02/18 Instructions for using this template: There are template files for each UNIFORMAT Level 2 Group Elements. This

More information

ACFoam -III Specifications Atlas Roofing

ACFoam -III Specifications Atlas Roofing Division 07 Thermal and Moisture Protection Section 07 22 00 Roof and Deck Insulation Section 07 22 16 - Roof Board Insulation PART 1 GENERAL 1.1 SECTION INCLUDES A. HCFC FREE Polyiso Rigid board type

More information