AMENDMENT NO.: 2 TO THE TENDER DOCUMENTS Defence Construction (1951) Limited

Size: px
Start display at page:

Download "AMENDMENT NO.: 2 TO THE TENDER DOCUMENTS Defence Construction (1951) Limited"

Transcription

1 (R ) Contract Services AMENDMENT NO.: 2 TO THE TENDER DOCUMENTS Defence Construction (1951) Limited CLOSING DATE/TIME: February 2, :00 hours, (local time) PROJECT NO.: TT AMENDMENT DATE: January 22, 2016 PROJECT TITLE: TO ALL PROPONENTS: Interior Renovations, Sudbury Armoury Sudbury, Ontario THE PURPOSE OF THIS AMENDMENT IS TO GIVE EFFECT TO THE FOLLOWING: 1. To issue Addendum 1, (14 pages) attached. End of Amendment 2

2 Addendum No. 1 Project: Department of National Defence Sudbury Armoury Interior Renovations 333 Riverside Drive, Sudbury Date: January 21, 2016 Project No.: TT ( ) The following information, amendments and revisions shall constitute Addendum No. 1, and shall form an integral part of the Tender Documents and where applicable, shall supersede requirements of other Tender Documents. Bidding Trades shall bring this Addendum to the attention of all sub-trades and suppliers from whom they may be receiving quotations. SPECIFICATIONS ADD-1.1 Refer to specification Section , Construction Sequencing..1 Reference Article 4, Construction Sequencing, Paragraph 4.1:.1 As a clarification note that, in order to minimize the impact on ongoing operations, the Owner will generally vacate the entire building, with the exception of the Main Floor area north of Drill Hall 224, at the commencement of the Work. Accordingly, the Contractor shall schedule all construction Work to suit. Architecture49 Inc Kingsway, Suite 2 Sudbury, ON P3B 2G1 Michael Luciw, BES, B.Arch., OAA, MRAIC Principal Architect

3 Addendum No. 1.2 Add the following Article 6, Commencement and Completion: 6.1 Time shall be the essence of the Contract. 6.2 Work under this Contract shall commence immediately that the Contractor is so instructed by the DCC Representative and shall be continued to completion without interruption. 6.3 Immediately upon award of the Contract, the Contractor shall make every effort to expedite submission of shop drawings in order secure required reviews and approvals in order to maximize delivery of materials to site prior to March 31, The existing Drill Hall may be used for site mobilization and storage of materials. Note that exterior site storage on site will not be possible due to ongoing site redevelopment construction activities that will recommence in the Spring. ADD-1.2 Refer to specification Section , Finish Hardware..1 Reference Article 2.2, Keying System and Interchangeable Core Type Cylinder, Paragraph 2.2.8:.1 As a clarification note that interchangeable core type mortise and/or cylinder locks are not required. Provide construction master keyed cylinders. ADD-1.3 Refer to the Door Schedule..1 As a clarification note that where door numbers only are indicated in BOLD ITALICS it indicates that this is an existing door opening; provide new materials and finishes as scheduled..2 Reference Door 103: Provide new door and frame with 3/4 hour fire-resistance rating..3 Reference Door 201A: As a clarification note that the existing hollow metal door and frame are to remain; paint as scheduled. DND Sudbury Armoury Interior Renovations Page 2

4 Addendum No. 1.4 Reference Door 224B: Rework / raise existing interior and exterior barrier free door operator push buttons to suit new sill elevation..5 Reference Doors 226, G1, G2, G2A, G3, G3A, G4 &G5: As a clarification note that the frame material column should indicate new hollow metal (HM) door frames..6 Reference Door 312A: As a clarification existing hollow metal frame (HM) to remain; paint (PT) as scheduled. Supply and install new solid core wood (SCWD) door as scheduled..7 Reference Doors 318A, 318B, 318C, 319,321, 327B & 327C: As a clarification note that frame type column should indicate new hollow metal (HM) door frames. ADD-1.4 Refer to the Room Finish Schedule..1 Refer to the General Finish Notes. Add the following:.1 Note that for all locations where new suspended acoustic tile ceiling systems are scheduled (AC / ACU) the existing plaster / gypsum board ceiling finishes are to remain, typical unless noted otherwise. Cut and patch, as required, to suit new HVAC system installations. Refer also to the requirements of specification Section , Hazardous Materials..2 All existing exposed sprinkler piping and conduit shall be painted (PT), typical throughout building, except above locations where new acoustic tile ceilings are scheduled..2 Reference Storage 103:.1 As a clarification note that the existing gypsum board wall material scheduled shall be revised to read: new gypsum board (GBD). Remove existing plywood sheathing / planking..2 As a clarification note that the existing plaster (PL) ceiling material scheduled shall be revised to read: new gypsum board (GBD). Remove existing plywood sheathing. DND Sudbury Armoury Interior Renovations Page 3

5 Addendum No. 1.3 Reference Corridor 115: As a clarification note that the wall material scheduled shall include new gypsum board (GBD). Remove existing plywood sheathing..4 Reference Foyer 200: As a clarification note that the wall material scheduled shall also include new gypsum board (GBD) to suit the removal of existing plywood sheathing finishes throughout..5 Reference Lobby 208A: As a clarification note that the floor material scheduled shall also include vinyl plank flooring (VPF) and resilient base (RB) at the top landing..5 Reference Rooms 224, 225, 313A, 314, 315, 316, 316A, 316B, 317, 317A, 318, 318A, 318B, 319, 320, 321, 323, 327, 327A, 327B, R-1, R-2, R-3, R-4, R-5, R-6 & R-7: As a clarification note that the existing painted 2 x 6 wood framing member applied to the bottom chord of the glue-laminated wood roof structure at Drill Hall 224 and all adjacent rooms shall also be painted. Revise Remarks note to read: * Paint wood roof decking and applied framing member at bottom chord only.6 Reference Alcove 311: Revise the terrazzo (TERR) floor and base finishes scheduled to read: vinyl plank flooring (VPF) and resilient base (RB)..7 Reference Corridor 308, Coats 308A and Men s washroom 309: As a clarification note that the ceiling material indicated should read: AC-1..8 Reference Stair 04: Revise the painted steel tread finishes scheduled to read: rubber stair treads (RST). DND Sudbury Armoury Interior Renovations Page 4

6 Addendum No. 1 ADD-1.5 Refer to specification Section , Resilient Sports Flooring..1 Reference Article 2.1, Resilient Sports Flooring Drill Hall (RSF-1), Paragraph Add the following approved alternate product:.5 SportGrain Plus as manufactured by Connor Sports..2 Reference Article 2.2, Resilient Sport Impact Flooring Gym (RSF-2), Paragraph Add the following approved alternate product:.5 PowerDek Fleck as manufactured by Connor Sports. DRAWINGS ADD-1.6 Refer to Drawing A.302, Lower Floor Demolition Plan..1 Reference Storage 103:.1 Add note to: demolish existing plywood / planking on north, east and west partitions and plywood sheathing at ceiling and provide new 16 gypsum board wall and ceiling finishes as scheduled..2 Reference Junior Ranks Mess 109, Corridor 115 & Corridor 116:.1 Add note to: demolish existing plaster / gypsum board ceiling and provide new 16 gypsum board ceiling as scheduled..3 Reference Women s Washroom 106 & Men s Washroom 107:.1 As a clarification note that the existing plaster / gypsum board and ceramic tile wall and ceiling finishes shall be completely gutted and reinstated with new as scheduled..2 As a clarification note that the existing plumbing fixtures scheduled to be removed shall be disposed off-site..3 As a clarification note that the existing concrete slab-on-grade shall be cut and patched, as required, to suit new plumbing installations. -.4 Reference Corridor 116:.1 As a clarification note the existing barrier free operator and push button controls at Door 107 to be removed. Make good existing wall finishes. DND Sudbury Armoury Interior Renovations Page 5

7 Addendum No. 1 ADD-1.7 Refer to Drawing A.303, Main Floor Demolition Plan..1 Reference Foyer 200:.1 As a clarification note that the existing plywood sheathing wall and ceiling finishes shall be completely gutted and reinstated with new gypsum board (GBD) as scheduled..2 Remove existing wood casing and demolish existing south wing wall and header at opening between Foyer 200 and Stair ST01. Extend new gypsum board ceiling scheduled for Foyer 200 to Stair ST01. Reframe lintel, as required, to suit..2 Reference Washroom 203A:.1 As a clarification note that the existing gypsum board chase in the southeast corner of the room, adjacent to the water closet, shall also be demolished..3 Reference Men s Washroom 221, Women s Washroom 203A & Women s Washroom 222:.1 As a clarification note that the existing plaster / gypsum board ceiling finishes shall be completely gutted and reinstated with new as scheduled..2 As a clarification note that the existing plumbing fixtures scheduled to be removed shall be disposed off-site..3 As a clarification note that the existing concrete slab-on-grade shall be cut and patched, as required, to suit new plumbing installations. ADD-1.8 Refer to Drawing A.310, Upper Floor Plan..1 Reference Meeting Room 304:.1 As a clarification note that there is an approximately 600 wide x 450 high screen on the south wall near Door 304 that shall be replaced with new. Add screen reference S-304; note elevation similar to screen S-16B except provide wired plate glass (WPG) and 3/4 hour fire-resistance rating. DND Sudbury Armoury Interior Renovations Page 6

8 Addendum No. 1 ADD-1.9 Refer to Drawing A.311, Roof Plan..1 Reference New Mechanical Units:.1 Provide single ply PVC membrane flashings at mechanical curbs for the new rooftop mounted air handling units. Co-ordinate the membrane flashing installations to suit mechanical and electrical work..2 Apply roofing flashing membranes employing only skilled workers having experience in the work specified, and having an understanding of the design principles of the materials that they are providing..3 Apply roofing / flashing materials in accordance with drawings, specifications, material manufacturer's printed directions, and requirements of jurisdictional authorities. MECHANICAL ADD-1.8 Refer to the enclosed Mechanical Addendum No. 1 prepared by WSP Group Inc., dated January 21, 2016 (4 pages) ELECTRICAL ADD-1.9 Refer to the enclosed Electrical Addendum No. 1 prepared by WSP Group Inc., dated January 21, 2016 (3 pages) DND Sudbury Armoury Interior Renovations Page 7

9 ADDENDUM #1 - MECHANICAL Project: Location: Sudbury Armoury Interior Renovations Sudbury, Ontario Addendum No.: 01 No. pages 4 Project # Date: January 21, 2016 The following change(s) in the Tender Documents are effective immediately. This Addendum forms part of the Contract Documents. MECHANICAL ITEM DESCRIPTION M01.1 Room 307 Officer s Mess; and 306 Officer s Dining. Replace All Existing Rads: For these two rooms, disconnect and remove all existing wall-mounted hydronic radiators. Allow wall repairs to proceed. Use site dimensions to govern the length of new rad enclosures. Install new baseboard rads (per note #25 on drawing M.405) and re-connect existing branch lines. Provide unions and pipe adapters as needed. The existing rad control is intended to remain in service. < see sketch MSK-2> M01.2 Room 200 Foyer Replace Existing Heater for improved appearance. Disconnect and remove existing wall-mounted hydronic rad. Match site dimensions (plus or minus 150 mm) to confirm new rad length. Install 2-tier rad, with 600 mm cabinet height and slope-top, similar to the product in note #25 of dwg M.405. Rad output: minimum 1300 btu/h per foot at 170 F ave. water temp. Prime-coat finish is selected so that the final finish will be applied on-site, by archit. trades. Rad control to remain the same. M01.3 Natural Gas work on drawing M.401, Note #20 is expanded as follows: Where new gas-fired equipment is supplied to the project, the contractor shall confirm the gas pressure available and provide regulators where necessary. The mechanical trade is required to submit the R.F.A form to Union Gas in order to establish the gas meter load and the utility can confirm the gas meter capacity. The added load under this project is 320,000 btu/h. cont d WSP Canada Inc Kingsway Boulevard Unit 2, Sudbury ON P3B 2G1 Tel: Fax:

10 M01.4 Room 103 Storage Install New Janitor Mop Sink: For basement service, refer to the attached sketch for layout of Janitor s Closet. Refer to M.405 for fixture description; complete with stainless steel wall guards. Break basement slab in order to modify sanitary drain and vents. Drains/ vents shall match existing material, or install couplings to join dissimilar materials. Arrange drains and traps to suit. Install trap seal primer on new floor drain. Extend 13 mm copper water supplies as indicated on plumbing plan and connect to new service faucet. Install solid brace in wall to support the faucet s wall bracket. <see sketch MSK-1> END OF WSP ADDENDUM NO. 01 < SKETCHES ATTACHED > WSP Canada Inc Kingsway Boulevard Unit 2, Sudbury ON P3B 2G1 Tel: Fax:

11 BAR OVERSTOCK 104 STORAGE 103 REMOVE EXISTING FLOOR DRAIN. MODIFY PIPING FOR NEW MOP SINK SANITARY DRAIN AND FL.D NEW FL.D 50 APPROX. LIMIT OF SLAB BREAKAGE. TSP NEW JANITOR SINK IN ROOM 103 WITH 38 MM VENT RISER. TERMINATE WITH APPROVED (AAV) AUTO AIR VENT DEVICE. TSP 75 Ø 117 UP STORAGE 103A PROJECT: TITLE: SUDBURY ARMOURY INTERIOR RENOVATIONS STORAGE ROOM 103 PLUMBING EXTRACT FOR: ADDENDUM: DIRECTIVE: CHANGE ORDER: FROM SHEET: X DRAWN BY: HJ SCALE: 1 : 50 DATE: 01/21/2016 CHECKED BY: PROJECT NO: EXTRACT NO: EW TT MSK-1

12 309 COAT ROOM 308A CORR. 308 OFFICER'S MESS BAR ACCESS 307A OFFICER'S DINING HALL 306 (TYP.) ALL EXISTING RADS AND ENCLOSURES, TO BE REMOVED AND REPLACED. APPLIES TO ROOMS 306 AND 307. POSITION OF BRANCH PIPING TO BE CONFIRMED BY CONTRACTOR. PROJECT: TITLE: DRAWN BY: SCALE: DATE: HJ 1 : 80 01/21/2016 CHECKED BY: EW SUDBURY ARMOURY INTERIOR RENOVATIONS OFFICER'S MESS 307 OFFICER'S DINING HALL 306 HEATING PROJECT NO: TT EXTRACT FOR: ADDENDUM: DIRECTIVE: CHANGE ORDER: FROM SHEET: EXTRACT NO: MSK-2 X

13 ADDENDUM #1 - ELECTRICAL Project: Sudbury Armoury Addendum No.: 01 Location: Sudbury, ON No. of Pages: 3 WSP Project # Date: January 21, 2016 The following change(s) in the Tender Documents are effective immediately. This Addendum forms part of the Contract Documents. ITEM DESCRIPTION 1.1 REFER TO ATTACHED SKETCH SKE01, PARTIAL RISER DIAGRAM RVEISED. SUPPLY AND INSTALL NEW 400A MAIN DISTRIBUTION PANEL AS SHOWN. SUPPLY BREAKERS TO MATCH EXISTING. COORDINATE WITH HYDRO ONE FOR ALL REQUIRED SHUT DOWNS AND PROVIDE OWNER WITH ADVANCED NOTICE FOR ANY AND ALL SHUT DOWNS. 1.2 A NEW SLAB ON-GRADE WILL BE INSTALLED IN THE FOLLOWING ROOMS: DRILL HALL 224, MUSEUM 219/219A AND SAT RANGE 219B. ALL ELECTRICAL DEVICES (RECEPTACLES, SWITCHES, COMMUNICATION, ETC ) IN THESE ROOMS SHALL BE RAISED APPROXIMATELY 250mm TO SUIT NEW CONCRETE. BREAK WALLS AS REQUIRED. REPAIR ALL DAMAGED SURFACES AND PAINT TO MATCH EXISTING FINISHES. 1.3 THE CONTRACTOR SHALL CHANGE ALL RECEPTACLES AND STANDARD LIGHT SWITCHES IN THE ENTIRE BUILDING. INSTALL NEW STAINLESS STEEL COVER PLATES FOR ALL THESE DEVICES. CONTRACTOR SHALL ALLOW FOR 500 DEVICES. ALL DEVICES SHALL BE STANDARD COMMERCIAL GRADE. COLOR TO BE SELECTED BY DCC REPRESENTATIVE. 1.4 SUPPLY AND INSTALL BOILER ROOM WET FLOOR ALARM TO BE MOUNTED IN A LOCATION WHICH CAN BE MONITORED BY ARMOURY PERSONNEL OUTSIDE THE BOILER ROOM. IT SHALL BE HARD WIRED TO 120V DEDICATED POWER SUPPLY COMPLETE WITH BATTERY BACK-UP. PROFESSIONALLY CONSTRUCTED SIGNAGE INDICATING THE PURPOSE OF THE ALARM MUST BE PROVIDED AND SECURELY AFFIXED TO THE WALL IN PROXIMITY OF THE ALARM. 1.5 FOR ALL WASHROOMS, REPLACE THE STANDARD TOGGLE SWITCH WITH A WALL MOUNTED SENSOR. SENSOR SHALL BE DUAL TECHNOLOGY (PIR/MICROPHONICS) WITH DUAL RELAY FOR EXHAUST FAN CONTROL. SET EXHAUST FAN DELAY 15 MINUTES LONGER THAN LIGHTING DELAY. FOR THE BASEMENT WASHROOMS, THERE WSP Canada Inc. 823 Birch St. South, Timmins, ON P4N 7C5 Tel: Fax:

14 IS ONLY ONE FAN FOR BOTH WASHROOMS; WIRE TO BOTH SENSORS SO THAT OCCUPANCY IN EITHER WASHROOM TRIGGERS THE EXHAUST FAN. END OF ADDENDUM NO. 01 WSP Canada Inc. 823 Birch St. South, Timmins, ON P4N 7C5 Tel: Fax:

15

Division 09 FINISHES TABLE OF CONTENTS

Division 09 FINISHES TABLE OF CONTENTS Division 09 FINISHES TABLE OF CONTENTS 09 1000 GENERAL... 3 A. RELATED SECTIONS... 3 B. MAINTENANCE OF FINISHES... 3 C. PUBLIC AREAS... 3 D. CUTTING AND PATCHING... 3 E. CLEANING... 3 F. RECOMMENDED FLOORING

More information

HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS

HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS St. Louis County Department of Public Works Division of Code Enforcement HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS This guide is intended to provide the homeowner or contractor with the

More information

CONTRACT DOCUMENTS REVIEW PACKAGE CHECKLIST

CONTRACT DOCUMENTS REVIEW PACKAGE CHECKLIST CONTRACT DOCUMENTS REVIEW PACKAGE CHECKLIST Check off each item that is included within the submitted Contract Documents Review Package. Provide a written explanation for any omissions. The following items,

More information

Building Systems and Design Elements included in SliDeRulE

Building Systems and Design Elements included in SliDeRulE Building Systems and Design Elements included in SliDeRulE No. System Subsystem Design Element 1.1.1 Foundation Deep Foundation Steel H-pile 1.1.2 Foundation Deep Foundation Steel pipe pile 1.1.3 Foundation

More information

A/E Design Deliverable Checklist

A/E Design Deliverable Checklist A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic

More information

The following shall be incorporated into the Contract Documents dated 26 MAR 2018.

The following shall be incorporated into the Contract Documents dated 26 MAR 2018. ADDENDUM NO. 2 DATE: April 12, 2018 PROJECT: OWNER: BID DATE: Munising Public Schools Mather Elementary Renovation Munising Public Schools Friday, April 20, 2018 at 10:00 a.m. The following shall be incorporated

More information

SPACE TYPE: OUTSIDE PARKING (STRUCTURE)

SPACE TYPE: OUTSIDE PARKING (STRUCTURE) SPACE TYPE: OUTSIDE PARKING (STRUCTURE) Construction Criteria The unit costs for Outside Parking (Structure) space types are based on the construction quality and design features in the following table.

More information

SPARTANBURG COUNTY BUILDING CODES DEPARTMENT

SPARTANBURG COUNTY BUILDING CODES DEPARTMENT SPARTANBURG COUNTY BUILDING CODES DEPARTMENT PLAN REVIEW CHECK LIST REQUIREMENTS FOR COMMERCIAL BUILDING PERMITS Plan Review Coordinator Kris Brannon 864-596-3180 366 N. Church St Room 500 Spartanburg,

More information

RESIDENTIAL BUILDING PLAN REQUIREMENTS

RESIDENTIAL BUILDING PLAN REQUIREMENTS CITY OF MANSFIELD BUREAU OF BUILDING AND CODES 30 NORTH DIAMOND STREET 3RD FLOOR MANSFIELD, OHIO 44902 Phone (419) 755-9688 Fax (419) 755-9453 www.ci.mansfield.oh.us RESIDENTIAL BUILDING PLAN REQUIREMENTS

More information

Work Write Up / Specification of Repairs HUD DIVISION 1. MASONRY HUD DIVISION 2. SIDING. Toll Free

Work Write Up / Specification of Repairs HUD DIVISION 1. MASONRY HUD DIVISION 2. SIDING. Toll Free / / Paperport 2000 official estimating report Work Write Up / Specification of Repairs Toll Free 1-877-932-7177 Clients Name. GREAT CLIENT Property Address. NUMBER ONE GOOD ROAD METRO, VA 20000 Primary

More information

CLARIFICATIONS. Item 3. Specification Sections and A. All finish wood shall have sealer coat and two coats of finish material REVISIONS

CLARIFICATIONS. Item 3. Specification Sections and A. All finish wood shall have sealer coat and two coats of finish material REVISIONS Addendum #2 Project Name: Global Campus Interior Renovation Project Address: 2 E. Center Street Fayetteville, AR 72701 Date: 06/14/17 This document is issued as a response to Clarifications. These revisions

More information

QUEEN ALEXANDRA COMMUNITY CENTRE

QUEEN ALEXANDRA COMMUNITY CENTRE BRICK REPOINTING AND NEW BARRIER FREE RAMP 180 BARNARDO AVENUE PETERBOROUGH, ON. ARCHITECTURAL A1 A1 A2 SITE PLAN AND DEMOLITION NOTATION NEW CONSTRUCTION DETAIL PLANS AND SECTIONS NEW CONSTRUCTION SECTION

More information

4. Number of drawings required: ( ) Locations of nearest streets

4. Number of drawings required: ( ) Locations of nearest streets CITY OF MANSFIELD BUREAU OF BUILDING AND CODES 30 NORTH DIAMOND STREET 3RD FLOOR MANSFIELD, OHIO 44902 Phone (419) 755-9688 Fax (419) 755-9453 www.ci.mansfield.oh.us COMMERCIAL BUILDING PLAN REQUIREMENTS

More information

PERMIT APPLICATION CHECKLIST Municipal Address, Phone & Fax NONRESIDENTIAL

PERMIT APPLICATION CHECKLIST Municipal Address, Phone & Fax NONRESIDENTIAL PERMIT APPLICATION CHECKLIST Municipal Address, Phone & Fax NONRESIDENTIAL Permit Application #: Date: mm/dd/yy Project Address Applicant s Name NOTE TO PERMIT APPLICANTS: All permit applications must

More information

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

SECTION BASIC ELECTRICAL MATERIALS AND METHODS SECTION 26 05 05 BASIC ELECTRICAL MATERIALS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the limited scope construction materials and methods for application with electrical installations as follows:

More information

FLOORS 3, 14 & 21 D322, D1422, D2122 Qty. 3 Size 2-6 x 6-0

FLOORS 3, 14 & 21 D322, D1422, D2122 Qty. 3 Size 2-6 x 6-0 entirely and masonry as required for installation of new door & frame (Kitchen Floors 5, 12, & 19). 4. At the DEMOLITION NOTES, DELETE Note D-4 in its entirety and REPLACE with the following: Saw cut and

More information

A/E Design Deliverable Checklist

A/E Design Deliverable Checklist A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic

More information

RESIDENTIAL BUILDING REQUIREMENTS

RESIDENTIAL BUILDING REQUIREMENTS RESIDENTIAL BUILDING REQUIREMENTS Residential Building Requirements This is an informational booklet with some of the general residential construction requirements taken from the codes adopted by Campbell

More information

Element Z General Design Requirements Existing Facilities Information

Element Z General Design Requirements Existing Facilities Information Anderson Central 100B, PART 1 - INTRODUCTION 1.01 OVERVIEW A. This Section provides general information for building systems and components. B. Refer to the Owner s Design Guideline Elements A though G

More information

Kelly Village Apartments 3118 Green Houston, Texas 77020

Kelly Village Apartments 3118 Green Houston, Texas 77020 Kelly Village Apartments 3118 Green Houston, Texas 77020 Houston Housing Authority J. Allen Management Managing Agent Scope for Kelly Village Unit #1125 Overall Scope: Demolition, Renovation, and Restoration

More information

BASEMENT FINISH CONSTRUCTION PLANS REFERENCE: 2015 INTERNATIONAL RESIDENTIAL CODE. PERMITS

BASEMENT FINISH CONSTRUCTION PLANS REFERENCE: 2015 INTERNATIONAL RESIDENTIAL CODE. PERMITS BASEMENT FINISH REFERENCE: 2015 INTERNATIONAL RESIDENTIAL CODE. PERMITS A construction permit is required. A homeowner may perform the construction work on his own property where he resides, without a

More information

Commercial Remodel Permit

Commercial Remodel Permit Commercial Remodel Permit Zoning requirements Staff recommends always verifying the zoning requirements for your project before deciding to build. Warrensburg has eleven separate zoning districts, each

More information

DESIGN AND CONSTRUCTION STANDARDS. Section 2: Standards for Specific Categories of Work. Laboratory Standards

DESIGN AND CONSTRUCTION STANDARDS. Section 2: Standards for Specific Categories of Work. Laboratory Standards Laboratory Standards These criteria include general planning guidelines. They are intended for use of Designers during the design phases of the project. Planning Assumptions Overview In order to maximize

More information

BUREAU Joe Iuviene, AIA January 20, 2017

BUREAU Joe Iuviene, AIA January 20, 2017 architectural BUREAU Joe Iuviene, AIA January 20, 2017 Alterations & Additions NEW TOWN HALL for TOWN OF AUSTERLITZ 816 State Route 203, Spencertown, New York 12165 ADDENDUM NO. 1 This addendum amends

More information

1. Unified Facilities Criteria - Design: General Building Requirements (UFC ).

1. Unified Facilities Criteria - Design: General Building Requirements (UFC ). 1. GENERAL GUIDANCE REGARDING DESIGN A. Commissary facilities are Department of Defense (DoD) projects, and as such must be constructed in accordance with the following criteria, codes, and standards.

More information

2003 International Residential Building Code

2003 International Residential Building Code 2003 International Residential Building Code Section R305 Ceiling Height Habitable rooms, hallways, corridors, bathrooms, toilet rooms, laundry rooms and basements shall have a ceiling height of not less

More information

HURON PUBLIC WORKS BUILDING HURON, SOUTH DAKOTA BID NO R

HURON PUBLIC WORKS BUILDING HURON, SOUTH DAKOTA BID NO R HURON PUBLIC WORKS BUILDING HURON, SOUTH DAKOTA BID NO. 2017-26R Stone Group Architects Project No. 1731 ADDENDUM DATE: September 14, 2017 BID DATE: September 18, 2017 2:00 P.M. C.S.T. SCOPE OF THIS ADDENDUM:

More information

TEXAS DEPARTMENT OF HOUSING AND COMMUNITY AFFAIRS OFFICE OF COLONIA INITIATIVES TEXAS BOOTSTRAP LOAN PROGRAM. Form 15 Work Write-Up

TEXAS DEPARTMENT OF HOUSING AND COMMUNITY AFFAIRS OFFICE OF COLONIA INITIATIVES TEXAS BOOTSTRAP LOAN PROGRAM. Form 15 Work Write-Up TEXAS DEPARTMENT OF HOUSING AND COMMUNITY AFFAIRS OFFICE OF COLONIA INITIATIVES TEXAS BOOTSTRAP LOAN PROGRAM Form 15 Work Write-Up Owner-Builder Applicant Owner-Builder Co-Applicant Physical Address: City,

More information

Demolition Plan A1 A3. Scale: 3/32" = 1'-0" Arch. Men N.I.C. Elev. Lobby. Stairs N.I.C. N.I.C. Women N.I.C. Issued for Tender.

Demolition Plan A1 A3. Scale: 3/32 = 1'-0 Arch. Men N.I.C. Elev. Lobby. Stairs N.I.C. N.I.C. Women N.I.C. Issued for Tender. inc. 400-7 avenue edmonton, alberta, canada tr y t: (780) 48 47 f: (780) 48 00 e: lesnider@shaw.ca 4 door to North Common Corridor doors to door to F. H. C. Men Women ELEC/TEL UP Stairs DN F. H. C. DN

More information

Gerald Desmond Bridge Replacement

Gerald Desmond Bridge Replacement Item # Room # icip. # of Occupants 101 12 Conference / Crew Room 1 400 400 Supervisor Offices Conference and secondary training room for up to 12 people Flooring: VCT Electrical Type: rmal (utility power)

More information

CODE COMPLIANCE PLAN REVIEW PROCEDURES

CODE COMPLIANCE PLAN REVIEW PROCEDURES CODE COMPLIANCE PLAN REVIEW PROCEDURES 1. All construction for state agencies on state-owned or state leased-purchased properties or facilities are to submit design documents for code compliance plan reviews

More information

Building Inspection Report

Building Inspection Report Building Inspection Report Sample Commercial Inspection Report Inspection Date: Prepared For: Prepared By: Professional Property Inspection Consultants 4857 Winterset Drive Columbus, OH 43220 (614) 459-5941

More information

Budget Estimate Basic Tenant Improvement

Budget Estimate Basic Tenant Improvement Building work rules, conditions and insurance: 1. Review the work rules. If they are not available no budget should be provided. 2. Hours available for construction 3. Insurance requirements 4. Entities

More information

Office of Design & Construction State University Plaza Albany, New York

Office of Design & Construction State University Plaza Albany, New York Instructions: Consultant should meet with the Campus and Fund at the work area(s) prior to completing this Checklist. At least two (2) meetings are required, one prior to Schematic Phase submission and

More information

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural %

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural % BartelsRode Gymnasium 8/11/ Building Rating System Percent Site: 1.0 Total 0 13 77% Building: 2.1 Building Exterior Elements 0 8 8% 2.2 Accessibility 0 74 74% 2.3 Structural 0 76 76% 2.4 Building Envelope

More information

NEW YORK STATE MAIN STREET PROGRAM BEFORE & AFTER

NEW YORK STATE MAIN STREET PROGRAM BEFORE & AFTER SUMMARY OGDENSBURG, NY The New York Main Street program (NYMS) is administered by the Office of Community Renewal (OCR) under the direction of the New York State Housing Trust Fund Corporation (HTFC).

More information

Toronto Community Housing Executive Summary 2016/2017. BCA Report. Sample House High FCI

Toronto Community Housing Executive Summary 2016/2017. BCA Report. Sample House High FCI BCA Report Porfolio Development Size Construction TCHC - All Op Units Scattered Units (CHU 20),005 Sq.Ft. 925 Floor Above Grade 2 Divisional Units Page of 43 Description This dwelling unit is a detached

More information

Edouard AVANT GROVE U I C U I C. Modern Living Made Easy uichomes.com

Edouard AVANT GROVE U I C U I C. Modern Living Made Easy uichomes.com Edouard Modern Living Made Easy uichomes.com - new construction - 3 stories + full basement - 4 bedrooms - 2.5 baths - 2,380 s.f. call 314.881.2333 or e-mail sales@uicstl.com PLAN NTS DECK 13' 0" X 12'-0"

More information

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection SECTION 13090 RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13090-1 LOW INTENSITY RADIATION PROTECTION

More information

Structural Inspection

Structural Inspection General: Background: An inspection and structural analysis have been performed for the purpose of evaluating the buildings structural systems and components. A full set of structural drawings was utilized

More information

Property Condition Assessment

Property Condition Assessment Property Condition Assessment Pewaukee, WI 53072 Inspection Date: 1/6/15 Prepared For: Report Number: Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar Dr. Pewaukee, WI 53072

More information

2010 National Building Code Adoption and Associated Process Changes

2010 National Building Code Adoption and Associated Process Changes Building Inspection City of Moncton 655 Main Street Moncton, NB E1C 1E8 Phone: (506) 856-4375 Fax: (506) 856-4348 Bulletin No. 14 From: Randy Richard Date: February 9, 2015 Subject: 2010 National Building

More information

REQUIREMENTS FOR SUBSTANTIALLY DAMAGED AND SUBSTANTIALLY IMPROVED STRUCTURES

REQUIREMENTS FOR SUBSTANTIALLY DAMAGED AND SUBSTANTIALLY IMPROVED STRUCTURES REQUIREMENTS FOR SUBSTANTIALLY DAMAGED AND SUBSTANTIALLY IMPROVED STRUCTURES If your home or business incurred damage, the engineering department, in conjunction with the Flood Mitigation Officer, will

More information

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities Division 1 Requirements Design and Construction Quality Campus Master Plans Texas Tech University System Operating and Building Maintenance Project Administration Historically Underutilized Business (HUB)

More information

C P A. Presented By Jason G. Smith, CCM, LEED AP. Founder and Principal of Construction Analysis and Planning, LLC

C P A. Presented By Jason G. Smith, CCM, LEED AP. Founder and Principal of Construction Analysis and Planning, LLC C P A CONSTRUCTION ANALYSIS AND PLANNING, LLC Presented By Jason G. Smith, CCM, LEED AP Founder and Principal of Author of Construction Management: Subcontractor Scopes of Work 1 Division of work: Primary

More information

March 6, Subject: Addendum No. 2 Invitation for Bid No Toyota Park Transit Center Phase II. Ladies and Gentlemen:

March 6, Subject: Addendum No. 2 Invitation for Bid No Toyota Park Transit Center Phase II. Ladies and Gentlemen: March 6, 2018 Subject: Addendum No. 2 Toyota Park Transit Center Phase II Ladies and Gentlemen: This Addendum No. 2 is being issued to provide responses to questions submitted by potential bidders and

More information

SPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM)

SPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM) SPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM) Construction Criteria The unit costs for the Physical Fitness Center (Exercise Room) space type are based on the construction quality and design features in

More information

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018)

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018) BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018) PERMIT SUBMITTAL CHECKLIST: Signed and completed Building Permit application form. A separate Electrical permit is required from

More information

Typical Finished Basement Details

Typical Finished Basement Details Albemarle County, Virginia Typical Finished Basement Details Based on the 2012 Virginia Residential Code Finished basements must be constructed in conformance with these details. For requirements, details

More information

COOLIDGE SENIOR HIGH SCHOOL

COOLIDGE SENIOR HIGH SCHOOL INITIAL YEAR BUILT 1940 BUILDING AREA 271,300 SF CURRENT PROGRAM CAPACITY 1240 ENROLLMENT 2008 652 WARD 4 PROPOSED PROGRAM CAPACITY 1100 Site Plan COOLIDGE - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

A101 S001 1 SUB-BASEMENT 3/16" = 1'-0" SHEET (906) PH (906) FX 2 S101 NEW CONCRETE WALLS TO FORM WAVE TANK 3' - 0" 5' - 5"

A101 S001 1 SUB-BASEMENT 3/16 = 1'-0 SHEET (906) PH (906) FX 2 S101 NEW CONCRETE WALLS TO FORM WAVE TANK 3' - 0 5' - 5 5' - 5" 3' - 0" 2 S0 NEW CONCRETE WALLS TO FORM WAVE TANK 7 SHEET NOTES (906) 487-2303 PH (906) 487-329 FX 9/22/207 :34:03 AM FILE: \\nas2.dcs.it.mtu.edu\sas_homes\desktop\meem wave tank.rvt 7 2' - 4"

More information

Cheldelin Middle School

Cheldelin Middle School Facility Information Address: 987 NE Conifer Blvd Corvallis Site Size: Building Area: Construction Date: Improved Parking: Grade Levels Served: Regular Classrooms: Portable Classrooms: Sept. 2007 Enrollment:

More information

Repair or replace section of driveway, approach, or sidewalk that are a trip hazard.

Repair or replace section of driveway, approach, or sidewalk that are a trip hazard. City of Gibraltar Pre-Sale Inspection Report Checklist FLATWORK: Repair or replace section of driveway, approach, or sidewalk that are a trip hazard. EXTERIOR PROPERTY: Fences/Sheds/Retaining walls: Repair,

More information

Building Guide. Colorado Chapter of the International Code Council

Building Guide. Colorado Chapter of the International Code Council 12/29/16 Building uide Colorado Chapter of the International Code Council How to Use this uide Check with your jurisdiction regarding type of submittal (paper or electronic) and for additional requirements.draw

More information

TENANT CRITERIA MANUAL INSERT PHOTO HERE

TENANT CRITERIA MANUAL INSERT PHOTO HERE G TENANT CRITERIA MANUAL GREENWOOD MALL INSERT PHOTO HERE General Growth Properties, Inc. 110 N. Wacker Drive Chicago, IL 60606 (312)-960-5000 Tenant shall supply and install an electrical meter

More information

SANDTOWN CROSSING PROFESSIONAL OFFICE PARK Atlanta, GA

SANDTOWN CROSSING PROFESSIONAL OFFICE PARK Atlanta, GA Atlanta, GA LOCATED AT CAMP CREEK PARKWAY AND CAMPBELLTON ROAD For Sale or Lease Single units start at 1,176sf and can be combined to exact specification Custom Designed Medical and Professional finishes

More information

Cherokee Nation Entertainment Casino Ramona, Oklahoma. WORK PACKAGE: Existing Casino Demolition and Dismantling 8/7/12

Cherokee Nation Entertainment Casino Ramona, Oklahoma. WORK PACKAGE: Existing Casino Demolition and Dismantling 8/7/12 SCOPE SUMMARY: DIVISION: 0 - LEGAL DOCUMENTS Complete; DIVISION: 1 - GENERAL REQUIREMENTS As Applicable; SECTION: - ATTACHED SKETCH Complete; Geotechnical Engineering Report as prepared by Building and

More information

SECTION ALTERNATES

SECTION ALTERNATES SECTION 01 23 00 - ALTERNATES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

Communications Page 1 of 9

Communications Page 1 of 9 Page 1 of 9 Last Update: April 23 rd, 2014 Introduction Design In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a

More information

CATAMARAN TOWER - 1 Seef Area Plot 19, 20

CATAMARAN TOWER - 1 Seef Area Plot 19, 20 STATUS REPORT NO 18 [As on September 30, 2017] This report is intended as a status report and covers only the activities completed till date, non-completed works and work-in-progress. A. Project Details

More information

BIDDING SHEET CHECKLIST--SUBCONTRACTORS AND SUPPLIERS SUBCONTRACTOR/ PHONE DATES SUPPLIER NAME: CALLED BID. Sample

BIDDING SHEET CHECKLIST--SUBCONTRACTORS AND SUPPLIERS SUBCONTRACTOR/ PHONE DATES SUPPLIER NAME: CALLED BID. Sample BIDDING SHEET CHECKLIST--SUBCONTRACTORS AND SUPPLIERS Project Name: Address: Owner: Phone/Fax/Email: Architect / General Contractor Name: : BID DEADLINE DATE: SUBCONTRACTOR/ PHONE DATES SUPPLIER NAME:

More information

RFP/GRC/LSV/ : RENOVATION (CIVIL WORKS) OF THR 8th PRIMARY SCHOOL TOILETS IN MYTILENE. Annex A - BILL OF QUANTITIES 1/9

RFP/GRC/LSV/ : RENOVATION (CIVIL WORKS) OF THR 8th PRIMARY SCHOOL TOILETS IN MYTILENE. Annex A - BILL OF QUANTITIES 1/9 RFP/GRC/LSV/2017-005: RENOVATION (CIVIL WORKS) OF THR 8th PRIMARY SCHOOL TOILETS IN MYTILENE Annex A - BILL OF QUANTITIES 1/9 The Contractor shall consider in his price all costs or expenses of all requirements

More information

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS 1 Introduction 1.1 In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a utility. It should be assumed that all new

More information

Pembridge The Country Club Collection TOWNHOMES AT CRYSTAL SPRINGS

Pembridge The Country Club Collection TOWNHOMES AT CRYSTAL SPRINGS Pembridge The Country Club Collection TOWNHOMES AT CRYSTAL SPRINGS STANDARD FEATURES LIST Foundation Concrete walls 4 concrete floor slab Interior basement unfinished Standard nine foot foundation walls

More information

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs November 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements....................................

More information

Commercial Plans Application Checklist

Commercial Plans Application Checklist Botetourt County, Virginia Development Services Construction Compliance 5 West Main Street, Suite 100 Fincastle, Virginia 24090 Phone: (540) 473-8248 Fax: (540) 473-2018 www.botetourtva.gov Commercial

More information

Introduction. Disclaimer. Table of contents

Introduction. Disclaimer. Table of contents Updated July 18, 2012 Introduction The Cambridge Elevating Limited-Use / Limited-Application Elevator is designed to service schools, libraries, low rise, low occupancy commercial buildings, churches and

More information

Basement Renovation Guide For Residential Dwellings

Basement Renovation Guide For Residential Dwellings 1 Development Services Department Building Permit & Inspection Services Basement Renovation Guide For Residential Dwellings This document is a guide for home owners and does not cover all possible conditions.

More information

SECTION OVERHEAD COILING FIRE DOORS MODEL 662 OVERHEAD COILING COUNTER FIRE DOORS WITH INTEGRAL FRAME

SECTION OVERHEAD COILING FIRE DOORS MODEL 662 OVERHEAD COILING COUNTER FIRE DOORS WITH INTEGRAL FRAME SECTION 08331 OVERHEAD COILING FIRE DOORS MODEL 662 OVERHEAD COILING COUNTER FIRE DOORS WITH INTEGRAL FRAME Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES

More information

Building Construction Occupations

Building Construction Occupations Job Ready Assessment Blueprint Building Construction Occupations Test Code: 2011 / Version 01 Measuring What Matters Specific Competencies and Skills Tested in this Assessment: Safety and General Knowledge

More information

LOGAN SCHOOL SCHOOL WITHOUT WALLS AT LOGAN

LOGAN SCHOOL SCHOOL WITHOUT WALLS AT LOGAN INITIAL YEAR BUILT 1935 BUILDING AREA 47,200 SF CURRENT PROGRAM CAPACITY 479 ENROLLMENT 2008 418 WARD 6 PROPOSED PROGRAM CAPACITY 450 Site Plan LOGAN - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION HS

More information

A HOMEOWNER S GUIDE TO ACCESSORY DWELLING UNITS

A HOMEOWNER S GUIDE TO ACCESSORY DWELLING UNITS L3Y 4X7 A HOMEOWNER S GUIDE TO ACCESSORY DWELLING UNITS Planning & Building Services October 2015 TOWN OF NEWMARKET www.newmarket.ca 35 Mulock Drive buildings@newmarket.ca P.O. Box 328 05-53-5300 ext.

More information

Cost Estimate Details

Cost Estimate Details C 0131 1 Inadequate Parking Construct or Expand Parking Lots $67,000 F 0132 1 Inadequate Drop Off Zone Widen Sidewalk, Construct Pathway and $77,000 Canopy RR 0132 2 No Landings at Classroom Exits Construct

More information

Yardmen Arena Expansion & Renovation Project Update

Yardmen Arena Expansion & Renovation Project Update For Immediate Release 25, September,2017 Yardmen Arena Expansion & Renovation Project Update BELLEVILLE ON With 33 days until puck drop of the home opening game of the American Hockey League s Belleville

More information

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board. 1.2 RELATED WORK A. Installation of steel framing members for walls, partitions,

More information

PROFESSIONAL DESIGN MANUAL INDEX

PROFESSIONAL DESIGN MANUAL INDEX PROFESSIONAL DESIGN MANUAL INDEX DIVISION A--GENERAL PROJECT REQUIREMENTS... A2-A15 A.1 INTRODUCTION... A-2 A.2 CODES COMPLIANCE (VERIFY CITY REQUIREMENTS)... A-5 A.3 SPECIAL SUBSURFACE AND LAND CONDITIONS...

More information

Florida Army National Guard Construction Facilities Management Office. Scope of Work:

Florida Army National Guard Construction Facilities Management Office. Scope of Work: Florida Army National Guard Construction Facilities Management Office Florida Armory Revitalization Program (FARP) Design Guidelines October 2008 Scope of Work: To provide complete design for the renovation/alterations

More information

SECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 08332 [08 33 13] COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Metal Counter

More information

BORTOLOTTO ADDENDUM #2

BORTOLOTTO ADDENDUM #2 BORTOLOTTO ADDENDUM #2 Project LI15-028 English Language Program Lakehead University Chancellor Paterson Library Project # el1606 Location 955 Oliver Road Thunder Bay, Ontario Date June 9, 2016 Pages 1

More information

Telecommunication Spaces

Telecommunication Spaces Telecommunication Spaces October 19, 2016 Page 1 Revision History Telecommunication Spaces Standard Effective Date Email Version Contact Phone OIT-TS strevena@csustan.edu 1.0 Stan Trevena 209.667.3137

More information

WALNUT CREEK - DETAILS OF TECHNICAL SPECIFICATIONS SPECS FOR VASWANI PORTION. 200 mm solid concrete blocks. Reinforced Cement Concrete - Flat Roof

WALNUT CREEK - DETAILS OF TECHNICAL SPECIFICATIONS SPECS FOR VASWANI PORTION. 200 mm solid concrete blocks. Reinforced Cement Concrete - Flat Roof WALNUT CREEK - DETAILS OF TECHNICAL SPECIFICATIONS DESCRIPTION BASIC STRUCTURE Foundation Super Structure Internal Walls External Walls Roof RCC footing Framed Structure 200 & 100 mm Solid Concrete Blocks

More information

HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW

HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW 27 September 2007 prepared by: J. CHRIS EVANS ARCHITECT 3220 E. Terra Alta Blvd. No. 9 Tucson, Arizona 85716 520.319.8835 evansarch@hotmail.com

More information

The Inspection Process. Waxhaw N.C.

The Inspection Process. Waxhaw N.C. The Inspection Process In Waxhaw N.C. This information is provided by the Waxhaw Enforcement Division to assist you in the progression of your project. Nothing in this document should be considered "Code"

More information

F.C.L. INTERIOR FINISHES CHECK LIST 2010 PRODUCT SELECTION - FLOORING GENERAL ITEMS PRODUCT SELECTION GENERAL ITEMS

F.C.L. INTERIOR FINISHES CHECK LIST 2010 PRODUCT SELECTION - FLOORING GENERAL ITEMS PRODUCT SELECTION GENERAL ITEMS INTERIOR FINISHES CHECK LIST 2010 Project: Project Number: Wil-Spec # This should not take long to go through, most questions below are listed as options, all you have to do is check off those answers

More information

The Homeowner s Building Application Checklist for Constructing a Residential Addition

The Homeowner s Building Application Checklist for Constructing a Residential Addition The Homeowner s Building Application Checklist for Constructing a Residential Addition This checklist provides homeowners a summary of the Building Permit submission requirements for constructing a residential

More information

DIVISION 9 FINISHES. This Article on Codes, Regulation and Standards shall apply to all Divisions of the Building Standards

DIVISION 9 FINISHES. This Article on Codes, Regulation and Standards shall apply to all Divisions of the Building Standards DIVISION 9 FINISHES This Article on Codes, Regulation and Standards shall apply to all Divisions of the Building Standards 1 Table of Contents SECTION 09 05 13 COMMON FINISHES 2 SECTION 09 51 23 ACOUSTICAL

More information

Each proposed project will be reviewed for compliance with the following codes as applicable.

Each proposed project will be reviewed for compliance with the following codes as applicable. VILLAGE OF PALATINE DEPARTMENT OF BUILDING AND INSPECTION SERVICES 200 EAST WOOD STREET PALATINE, IL 60067-5339 Telephone (847)359-9042 Obtaining a Residential Building Permit: Submittal Requirements The

More information

Velma F Thomas Early Childhood Center

Velma F Thomas Early Childhood Center Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

Residential Accessory Structures & Room Additions

Residential Accessory Structures & Room Additions Residential Accessory Structures & Room Additions Planning and Development Services Department Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email:

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS ************************************************************************** SECTION TABLE OF CONTENTS

UNIFIED FACILITIES GUIDE SPECIFICATIONS ************************************************************************** SECTION TABLE OF CONTENTS USACE / NAVFAC / AFCEC / NASA UFGS-09 06 00 (May 2009) Change 1-11/13 ----------------------------- Preparing Activity: USACE Superseding UFGS-09 06 90 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Completed. Project. Melbourne High School. Comprehensive Additions and Renovations

Completed. Project. Melbourne High School. Comprehensive Additions and Renovations Project Update Project Update September 8, 2006 January 06, 2010 Project Manager Project Manager Anibal Caussade Dennis Bonny Field Coordinator Field Coordinator Bud Ball Paul Friel Project Budget Project

More information

THE STRATA UNIT May 25, 2008

THE STRATA UNIT May 25, 2008 THE STRATA UNIT May 25, 2008 Over the years, we have been asked time and time again from our experience as a cost consultant and a project manager from both a restoration and renovation point of view What

More information

Sewer, Water, Gas, Electric and Cable

Sewer, Water, Gas, Electric and Cable Richardson Commercial, LLC Realtors 52 State Highway #33 Hamilton, NJ 08619-2583 Phone: (609) 586-1000 Fax: (609) 586-8732 www.richardsoncommercial.com SUBJECT: LOCATION: SITE: UTILITIES: ZONING: TAXES:

More information

Application for Commercial Plan Review and Building Permit. Address:

Application for Commercial Plan Review and Building Permit. Address: City of Warrenton 200 West Booneslick Warrenton, MO 63383 : 636-456-3535 Fax: 636-456-1336 www. war r ent o n- mo.org Application for Commercial Plan Review and Building Permit PERMIT# Purpose: Commercial

More information

SUBMISSION GUIDE FOR ARCHITECTS

SUBMISSION GUIDE FOR ARCHITECTS SUBMISSION GUIDE FOR ARCHITECTS CONTENTS TAB 6 - SUBMISSION REQUIREMENTS FOR LIHTC DEVELOPMENTS NOT RECEIVING OR ASSUMING A PHFA LOAN Page Contents... 6.1 6.01 Submission Requirements... 6.2 6.02 Minimum

More information

One and Two Family Additions

One and Two Family Additions One and Two Family Additions An addition to a house, duplex, garage, or an accessory structure requires a building permit prior to performing any construction. Building Department & Permit Office Mon-Fri

More information

DESIGN DEVELOPMENT PHASE

DESIGN DEVELOPMENT PHASE UNIVERSITY OF MICHIGAN DESIGN DELIVERABLES FEBRUARY 2012 As part of the deliverables for formal UM review at each of the major phases of design listed below, the Design Professional shall submit this "Design

More information

BUILDING PERMIT APPLICATION

BUILDING PERMIT APPLICATION Permit Application # Building Permit # Building Project Type: A. Project Information Lot: Plan: District Lot: Legal: PID: Site Address: Project Square Area (Ft 2 or M 2 ) Project Construction Value $ B.

More information

HOW TO OBTAIN A BUILDING PERMIT

HOW TO OBTAIN A BUILDING PERMIT HOW TO OBTAIN A BUILDING PERMIT A GUIDE TO THE HOMEOWNER Copies of this Guide can be obtained from the Building Department upon request THE CORPORATION OF THE TOWNSHIP OF GEORGIAN BAY BUILDING DEPARTMENT

More information

BuildingName The Description of the Project P DOCUMENTS

BuildingName The Description of the Project P DOCUMENTS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information