ITW INSULATION SYSTEMS

Size: px
Start display at page:

Download "ITW INSULATION SYSTEMS"

Transcription

1 ITW INSULATION SYSTEMS 1SCOPE TRYMER RIGID POLYISOCYANURATE INSULATION IN LIQUEFIED NATURAL GAS APPLICATIONS (Cryogenic to -70 F) 1.1 This guideline covers the installation of TRYMER Rigid Polyisocyanurate Insulation on Liquefied Natural Gas (LNG) piping systems, tanks, vessels and equipment. 1.2 Product data sheets and other ITW literature are referenced throughout this guideline. Visit for the latest version of these documents. 1.3 The information contained in this guideline and referenced ITW documents are current as of May This guideline is subject to revision without notice. Contact ITW Insulation Systems Customer Information Group at or your local ITW Representative for the most recent version of this guideline or other ITW referenced literature. 1.4 Due to the variations in service conditions and use, this guideline may not be pertinent for every application. A design or specifying engineer can create specifications tailored to particular applications or owner s needs. Such a design or specification engineering service may be more familiar with local conditions, budgets, environment, and desired service life of the system allowing them to generate a precise specification. 1.5 It is the intent of this document to provide guidelines for the installation of TRYMER insulation and SARAN Vapor Retarder Film and Tape manufactured by ITW Insulation Systems. This guideline may not be suitable and shall not be used for the purpose of installing another insulation manufacturer s products. While supplemental insulation products may be referenced in this guideline, ITW recommends consulting the manufacturers of these products for proper installation and handling. 1.6 This guideline is offered as a guide for the purpose described herein. No warranty of procedures, either expressed or implied is intended. All other express or implied warranties of merchantability or fitness for a particular purpose are disclaimed. 2 GENERAL 2.1 All piping shall be free of foreign substances and free of surface moisture or frost prior to the application of insulation. 2.2 All insulation material shall be delivered to the project site in original, unbroken factory packaging labeled with product designation and thickness. The shipping package should not be air-tight. Shipment of materials from the manufacturer to the installation location shall be in weather-tight transportation. Insulation materials delivered to the job-site shall be stored so as to protect the materials from moisture and weather during storage and installation. Insulation material shall be protected from sunlight to avoid exposure to UV light from the sun. 2.3 All testing of piping systems shall be completed prior to the installation of the insulation system. 2.4 Refer to insulation thickness charts in Appendix C for recommended insulation thickness based on specific design criteria. For additional insulation thickness calculations please call at MATERIALS OF CONSTRUCTION 3.1 INSULATION MATERIALS FOR PIPING, FITTINGS, AND VALVES Insulation shall be TRYMER 2500 and/or 3000 Rigid Polyisocyanurate Insulation manufactured by ITW Insulation Systems Insulation shall have a maximum thermal conductivity of 0.19 BTU-in/hr-ft 2 - F (0.027 W/m- C) at 75 F mean ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 1 of 20

2 3.2 FABRICATION OF INSULATION Insulation shall be fabricated in required shapes from bun stock in accordance with ASTM C-450 Standard Practice for Prefabrication and Field Fabrication of Thermal Insulating Fitting Covers for NPS Piping, Vessel Lagging, and Dished Head Segments and C-585 Standard Practice for Inner and Outer Diameters of Rigid Thermal Insulation for Nominal Sizes of Pipe and Tubing (NPS System). Insulation shall be factory fabricated from bun stock by an Authorized ITW Fabricator Fittings, such as valves, valve stations, flanges, 90 and 45 elbows, and tees shall be two piece flycut or routed as the preferred fabrication method. For diameters, too large for flycutting or routing, the pieces shall be fabricated in two halves with each half made up of mitered sections. Both methods shall be in accordance with ASTM C-450 and ASTM C-585. Refer to applications sections and for related additional information Store the bun stock at normal shop (indoor) conditions for at least 24 hours before fabrication. This will allow the TRYMER bun stock to equilibrate to the shop conditions. For best fabrication quality, it is recommended that TRYMER buns be fabricated into pipe shells in conveyor direction (length direction) to maximize flatness. For factory applied vapor retarder, the fabricated pipe shells shall be aged for 24 hours before vapor retarder attachment. Similarly, after fabrication of the fittings/elbows/tees, allow the cut pieces to age for 24 hours before factory application of the vapor retarder to the fabricated pieces. After application of vapor retarder, fabricated pipe shells shall not be stored for more than one month either in the warehouse or at a job site. 3.3 ADHESIVES, JOINT SEALERS AND MASTICS Solvent based adhesives, joint sealers and mastics may be used in contact with TRYMER insulation. Mastics shall remain flexible at the lowest expected ambient temperature Joint sealers for sealing joints of insulation shall be vapor retarder type, moisture and water resistant, nonhardening, and flexible with a service temperature range from -275 F to +200 F A vapor retarder type joint sealer shall be applied on insulation longitudinal joints and butt joints to prevent moisture and moisture vapor infiltration. Such joint sealers are Fosters sealer or approved equal. Please consult joint sealer manufacturer for recommended products Solvent or water adhesives may be used to attach the SARAN Film to the outer surface of the TRYMER insulation for factory applied SARAN Film. Refer to the SARAN installation guidelines. Consult adhesive manufacturer's literature for instructions on handling adhesives including required operating temperatures. Potential adhesives for use in this application include: a) Childers CP 88 adhesive (solvent based) b) Foster adhesive (solvent based) c) Foster adhesive (water based) d) Foster adhesive (water based) 3.4 VAPOR RETARDER A double layer vapor retarder design shall be used for LNG applications. The secondary vapor retarder shall be applied between the outer most foam insulation layer and the next inner layer of foam insulation. A primary vapor retarder shall be applied to the outer most foam insulation layer. Refer to Figure 2 in Appendix B for details Vapor retarder shall be SARAN 560 Vapor Retarder Film. Refer to ASTM standards C-755 and C-1136 for information on selection and specification of vapor retarders. Refer to product literature and installation guidelines on SARAN Film for recommended application instructions Elbows and fittings shall be wrapped with SARAN 560 Vapor Retarder Tape with a 50% overlap Vapor Retarder shall have a maximum permeance of 0.01 perm For other laminated membrane type vapor retarders, consult manufacturer s literature and installation guidelines Vapor retarder may be factory or field applied to the outer surface of pipe insulation For tanks, vessels, and equipment, use SARAN 560 Vapor Retarder Film or approved equal. 3.5 CONTRACTION/EXPANSION JOINTS The location of contraction/expansion joints should be determined considering the expected pipe movements Contraction/expansion joints should be installed in the inner insulations layers of the horizontal piping and equipment The joints should be installed at maximum intervals of 20 feet. Consult with the appropriate engineer to determine the proper spacing of the contraction/expansion joints for each system Contraction/expansion joints should be filled with a resilient mineral fiber or approve alternate with fibers oriented parallel to the direction of the pipe. The contraction/expansion joint filler should be twice the thickness of the contraction/expansion joint (compressed to _ the thickness). Consult with the appropriate engineer to determine the proper contraction/expansion filler material ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 2 of 20

3 3.6 PROTECTIVE JACKETING MATERIAL Shall be one of the following: A) Aluminum Sheet Jacketing shall be aluminum alloys 3003, 1100 or 3105, H-14 temper, meeting ASTM B-209. Use white painted aluminum jacketing for all outdoor applications. Consult jacketing manufacturer for recommended thicknesses. Typical thickness is (up to 24 pipe) and (> 24 pipe size). Aluminum jacketing for all fittings, tees, elbows, valves, caps, etc. shall be sectional, factory contoured, or field-fabricated to fit closely around insulation. Banding for jacketing shall be 0.02" thick by 1/2" wide stainless steel. Aluminum protective jacketing shall not be considered a vapor retarder. See section 3.4 for vapor retarder recommendations. No fastener capable of penetrating the underlying vapor retarder shall be used to secure the aluminum jacket. B) Stainless Steel The material shall be of a quality meeting the requirements of ASTM A167 Type 304. Use white painted stainless steel jacketing for all outdoor applications. Consult jacketing manufacturer for recommended thicknesses. Banding for jacketing shall be 0.02" thick by 1/2" wide stainless steel. Stainless steel protective jacketing shall not be considered a vapor retarder. See section 3.4 for vapor retarder recommendations. No fastener capable of penetrating the underlying vapor retarder shall be used to secure the stainless steel jacket. 4 APPLICATIONS 4.1 PIPING GENERAL All piping, operating at LNG temperatures, requiring 5 or more of insulations shall be applied in three layers. Comprising of an inner, middle, and outer layer of TRYMER insulation. See Table 1 in Appendix B for details All piping, operating at LNG temperatures, requiring less than 5 of insulations shall be applied in two layers. Comprising of an inner and outer layer of TRYMER insulation. See Table 1 in Appendix B for details Where insulation thickness required is less than 5, utilize a double layer system. Stagger all longitudinal joints between the inner and outer layers. Install the inner and outer layer longitudinal joints 90 to each other with the inner layer joints in the 12 and 6 o clock positions and the outer layer joints in the 3 and 9 o clock positions. All butt joints between the inner and outer layers shall be staggered between 6 and 18 inches. Refer to Figure 1 in Appendix B Where insulation thickness required is greater than 5, utilize a triple layer system. Stagger all longitudinal joints between the inner, middle, and outer layers. Install the inner, middle, and outer layer longitudinal joints 90 to each other with the inner layer joints in the 3 and 9 o clock positions, the middle layer joints in the 12 and 6 o clock positions, and the outer layer joints in the 3 and 9 o clock positions. All butt joints between the inner, middle and outer layers shall be staggered between 6 and 18 inches. Refer to Figure 2 in Appendix B Insulation shall be fabricated with shiplap or tongue and groove longitudinal joints and shiplap ends Install pre-fabricated insulation fittings on elbows, tees, and valves. Insulation shall be the same thickness as pipe sections and fabricated with shiplap ends and shiplap or tongue and groove longitudinal joints. Refer to Figure 3 in Appendix B In a triple layer insulation system, the inner layer shall not be installed with sealants. In triple layer systems, the inner, middle and outer layer shall remain independent of each other so as to allow movement between the layers In double layer insulation system, inner layer shall not be installed with sealants. In double layer systems, the inner and outer layer shall remain independent of each other to allow movement between the layers. Refer to Figure 1 in appendix B Insulation shall be secured to the pipe with 3/4" wide fiber reinforced tape. Tape shall be applied as per Figure 4 in Appendix B Insulation shall be secured with fiber reinforced tape on both inner and outer layers of a multi layered systems except as noted in section Insulation shall be secured with fiber reinforced tape prior to installation of the vapor retarder material when vapor retarder is field applied Outer layer insulation and vapor retarder shall be secured with fiber reinforced tape. Use a 25% circumferential overlap on 12 centers when vapor retarder is factory applied to insulation. Fiber tape shall be applied to the exterior of the insulation/vapor retarder system Contraction/expansion joints shall be installed as described in section 3.5 and illustrated in Figure 5 in Appendix B or approved alternate design. The appropriate designer or engineer must specify the spacing of contraction/expansion joints separately for each system ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 3 of 20

4 All insulation shall be tightly butted and free of voids and gaps at all joints. Vapor retarder must be continuous. All fasteners and bands shall be neatly aligned and overall work must be of high quality appearance and workmanship Vapor stops shall be used on either side of valves frequently removed for servicing, valve stations left exposed, or odd fittings, elbows, tees, etc. where the chance of moisture infiltration is high. Install per detail in Figure 6 in Appendix B or an approved alternate design SARAN Vapor Retarder Film to be cut to length longitudinally and wrapped around the circumference of the pipe with lap joint facing downward avoiding the placement of the joint at the top or bottom of the pipe. Lap joint to be sealed using liquid adhesive. Butt joints shall be covered with SARAN Vapor Retarder Tape. Spiral wrap configuration can be used in lieu of the above installation. Spiral wrapping will require adhesive placed on one edge of the SARAN Film as it is wrapped over the previous layer Elbows and fittings shall be wrapped with SARAN 560 Vapor Retarder Tape or covered with a mastic type vapor retarder product. SARAN Tape to be wrapped in a spiral configuration. If using mastic type vapor retarder at fittings and elbows, form mastic so that fitting covers can be applied true and tight On factory applied SARAN Vapor Retarder Film, lap joint to be sealed with SSL tape. All vapor retarder surfaces should be cleaned and free of dust, grease, oil, etc. before application of the SSL tape to ensure good adhesion between the tape and vapor retarder. Refer to Figure 7 in Appendix. For other types of factory applied vapor retarders, consult manufacturer s recommendations on installation Before jacketing can be installed on a portion of the piping, the vapor retarder system on that portion must be complete and continuous Its good engineering practices to coat the pipes in LNG applications. Consult Appendix A for conditions where pipe coating systems are suggested. 4.2 OUTDOOR PIPING This section covers outdoor areas including, but not limited to, process areas, rooftops and rooftop equipment TRYMER Insulation shall be protected from prolonged exposure to UV light and weather upon installation Outdoors, SARAN Products shall be covered with a jacketing material within two weeks of installation to eliminate longterm exposure to UV light Refer to section 3.6 for material specification on outdoor jacketing Outdoor jacketing overlap shall be a minimum of 2" at butt joints and a minimum of 2 at longitudinal joints. Jacketing shall be caulked before closing and banding and positioned in an orientation to avoid water infiltration Straight sections of jacketing shall be neatly secured with bands and seals with a maximum spacing of 9" on center. End joints shall be secured with bands and seals centered directly over joint. Do not use screws, staples or other fasteners on lines containing a vapor retarder system. 4.3 TANK, VESSEL, AND EQUIPMENT INSULATION All insulation materials shall be the same as those used on the pipe associated with the tank, vessel, or equipment Tank and vessel head segments shall be curved cut to fit in single piece or segments per ASTM C-450. Head segments shall be cut so as to eliminate voids at the head section and in a minimum number of pieces so as to eliminate through joints Curved segments shall be fabricated to fit the contour of the surface in equal size pieces to go around the vessel with a minimum number of through joints. Cutting in the field shall be minimized. All sections shall be tightly butted and free of voids and gaps Vertical vessels greater than 4 feet in diameter require an insulation support ring welded or bolted around the bottom of the tank to prevent the shell insulation from sliding down Seal all outer layer and single layer butt joints with joint sealer. Refer to section In multi-layer applications, the horizontal and vertical joints of the inner and outer layer curved segments shall be staggered (see Figure 8 in Appendix B) The top of the outer layer of wall insulation in a multi-layer system shall be held below the inner layer top a minimum of the insulation thickness. The tank head insulation layers shall be cut so as to meet the staggered joint Secure the shell insulation with stainless steel bands on 12 inch centers Install SARAN 560 Vapor Retarder Film. Tightly wrap the vessel or equipment insulation circumferentially with SARAN Film. Overlap the seams by a minimum of 2 inches. Seal the overlapped seams with SARAN Tape. On vertical vessels apply the SARAN Film starting with the bottom course and work upwards. Each course should overlap on top of the one below it thus providing a joint that will naturally shed water ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 4 of 20

5 The vapor retarder on curved head sections shall be mastic/fab/mastic or approved alternate. Flat head sections can be covered with SARAN 560 film. Lap joints shall be covered with SARAN Vapor Retarder Tape Legs and appendages attached directly to the shell shall be insulated out from the vessel head or wall four times the insulation thickness and the insulation termination sealed with a vapor stop On outdoor equipment use aluminum jacketing per section 3.5. Rivets and screws shall not be used to attach jacketing on systems using a vapor retarder. 5 APPENDICES 5.1 APPENDIX A: CORROSION RESISTANT METAL COATINGS GENERAL NOTE: Corrosion of metal pipe, vessels, and equipment under insulation, while not typically caused by the insulation, is still a significant issue that must be considered during the design of any mechanical insulation system. The propensity for corrosion is dependent on many factors including the ambient environment and the operating temperature of the metal. The recommendations below represent the general practice in the industry but are not meant to take the place of proper system design and specification by a qualified design engineer familiar with this type of construction. We recommend that the owner consult such an engineer and have them work closely with the fabricator, the contractor, and ITW to help insure a properly designed, installed, and long-lasting insulation system free of corrosion SPECIFIC RECOMMENDATIONS: Stainless Steel All 300 series stainless steel shall be coated with an epoxy primer at 5 mil thickness and an epoxy finish coat at 5 mil thickness if operating in a temperature range between 140 F and 300 F or if in a cycling temperature service where the service temperature is between 140 and 300 F for more than 20% of the time. Consult a coating manufacturer for appropriate coating materials and application methods based on the operating temperature range of the equipment Carbon Steel All carbon steel operating at a service temperature between 32 F and 300 F or in cycling temperature service where the service temperature is between 32 F and 300 F for more than 20% of the time shall be at a minimum primer coated with an epoxy coating. Consult a coating manufacturer for appropriate coating materials and application methods for the operating temperature range of the equipment. 5.2 APPENDIX B: DETAILS The following details are referenced in the text of this guideline by their Figure numbers. The diagrams included in this section are representative of details used within the industry. However, they are not intended to display the only accepted method of installation but to serve as an example of commonly used and acceptable practices ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 5 of 20

6 DOUBLE LAYERED INSULATION SYSTEM Detail Notes: Figure 1 Inner Layer longitudinal joints at 12 and 6 O clock. Outer layer joints at 3 and 9 O clock. Stagger half round segments on each layer and between the two layers as shown above. Use thin coat of sealant over whole joint depth. Butter excess down the face of the joint. Use sealant on outer layer only ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 6 of 20

7 TRIPLE LAYERED INSULATION SYSTEM Figure ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 7 of 20

8 Detail Notes: Figure 3 FULL THICKNESS SHIPLAP ELBOW FITTING Shiplap end cut to thickness X to accommodate double layer pipe insulation. Use in lieu of double layered fittings. Wrap elbow with SARAN 520 Vapor Retarder Tape ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 8 of 20

9 TAPING PATTERN Detail Notes: Figure 4 Use two wraps of tape to insure adequate bond. Use nylon or glass filament type tape 3/4 wide ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 9 of 20

10 DOUBLE LAYER EXPANSION/CONTRACTION JOINT DETAIL Detail Notes: Figure 5 Allow sealant beads to cure prior to installation of outer layer. Position outer layer packed glass fiber between sealant dams on inner layer as shown above. After glass fiber in contraction joint is installed, insulation sections on either side of contraction joint shall be forced together as tightly as possible ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 10 of 20

11 VAPOR STOP DETAILS Detail Notes: Figure 6 Mastic should be selected based on the service temperature of the system. Mastic shall be sealed to the pipe face and lapped back over the top of the vapor retarder if fitting is left exposed ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 11 of 20

12 DETAIL OF FACTORY APPLIED VAPOR RETARDER Detail Notes: Figure 7 Vapor Barrier can be installed using SSL tape as shown above or using liquid adhesives. Butt joints to be covered a minimum of 1.5 on each side of joint by SARAN Tape or butt strip ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 12 of 20

13 TANK HEAD INSULATION DETAIL Detail Notes: Figure 8 In multiple layer systems, each layer shall be installed so that the horizontal and vertical joints in that layer are staggered from the corresponding joints in the preceding layer by half the height or width of a full section. At joint between wall and head section, the outer layer shall be staggered below the inner layer by the thickness of a single layer. Where mastics or sealants are required to bond the insulation sections to the tank head consult the manufacturer s recommendations on service and application temperatures ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 13 of 20

14 Table 1: Insulation Thickness Details Total Thickness (in) Inner Layer (in) Middle Layer (in) Outer Layer (in) APPENDIX C: THICKNESS TABLES The following tables show the insulation thickness necessary to prevent condensation on the outer surface of the insulation system jacketing. In a few cases, the tables also include the insulation thickness necessary to limit the heat gain to a specific value (usually 8 btu/hr-ft 2 of outer jacketing surface). These thickness recommendations are solely based on various design conditions that are shown with each table. A number of assumptions are also made, including proper system design and installation. There may be additional factors the tables do not address that could influence the end results. These thickness tables are not meant to replace a proper system design and specification by a qualified design engineer familiar with specific ambient design parameters for a given locality. We recommend you consult a qualified engineer and have them work closely with the contractor, and ITW to help insure a properly designed, installed, and long-lasting insulation system. Thickness calculations are performed using the 3E Plus software program that uses heat flow algorithms based on ASTM C The required insulation thicknesses do not include a safety factor. Actual operating conditions can vary. Consult a design engineer for an appropriate safety factor ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 14 of 20

15 TRYMER 2000 XP, 2500, 3000 Insulation, Outdoors, 90% R.H. Ambient Temp = 90 F Outer surface = White painted metal (e = 0.80) Ambient Relative Humidity = 90% Wind Velocity = 7 mph Dew point = 86.6 F Geometry = Horizontal Pipe Insulation Thickness In Inches Necessary To Prevent Condensation Service Temperature NPS (F) (in) This table is based on ASTM C heat transfer algorithms. The suggested insulation thickness values assume proper system design and installation, do not include a safety factor, and are applicable only for the specified scenario. ITW recommends that the user consult a qualified design engineer familiar with this type of construction for proper system design and specification ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 15 of 20

16 TRYMER 2000 XP, 2500, 3000 Insulation, Outdoors, 85% R.H. Ambient Temp = 90 F Outer surface = Stainless Steel (e = 0.30) Ambient Relative Humidity = 85% Wind Velocity = 7 mph Dew point = 84.9 F Geometry = Horizontal Pipe Insulation Thickness In Inches Necessary To Prevent Condensation Service Temperature NPS (F) (in) This table is based on ASTM C heat transfer algorithms. The suggested insulation thickness values assume proper system design and installation, do not include a safety factor, and are applicable only for the specified scenario. ITW recommends that the user consult a qualified design engineer familiar with this type of construction for proper system design and specification. TRYMER 2000 XP, 2500, 3000 Insulation, Outdoors, 80% R.H ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 16 of 20

17 Ambient Temp = 80 F Outer surface = White painted metal (e = 0.80) Ambient Relative Humidity = 80% Wind Velocity = 7 mph Dew point = 73.3 F Geometry = Horizontal Pipe Insulation Thickness In Inches Necessary To Prevent Condensation Service Temperature NPS (F) (in) This table is based on ASTM C heat transfer algorithms. The suggested insulation thickness values assume proper system design and installation, do not include a safety factor, and are applicable only for the specified scenario. ITW recommends that the user consult a qualified design engineer familiar with this type of construction for proper system design and specification ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 17 of 20

18 TRYMER 2000 XP, 2500, 3000 Insulation, Outdoors, 80% R.H. Ambient Temp = 80 F Outer surface = Stainless Steel (e = 0.30) Ambient Relative Humidity = 80% Wind Velocity = 7 mph Dew point = 73.3 F Geometry = Horizontal Pipe Insulation Thickness In Inches Necessary To Prevent Condensation Service Temperature NPS (F) (in) This table is based on ASTM C heat transfer algorithms. The suggested insulation thickness values assume proper system design and installation, do not include a safety factor, and are applicable only for the specified scenario. ITW recommends that the user consult a qualified design engineer familiar with this type of construction for proper system design and specification 2017 ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 18 of 20

19 TRYMER 2000 XP, 2500, 3000 Insulation, Outdoors, 80% R.H. Ambient Temp = 80 F Outer surface = White painted metal (e = 0.80) Ambient Relative Humidity = 80% Wind Velocity = 7 mph Dew point = 73.3 F Geometry = Horizontal Pipe Insulation Thickness In Inches Necessary To Prevent Condensation or limit heat gain to 8 BTU/hr-sq ft, whichever is greater Service Temperature NPS (F) (in) This table is based on ASTM C heat transfer algorithms. The suggested insulation thickness values assume proper system design and installation, do not include a safety factor, and are applicable only for the specified scenario. ITW recommends that the user consult a qualified design engineer familiar with this type of construction for proper system design and specification ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 19 of 20

20 TRYMER 2000 XP, 2500, 3000 Insulation, Outdoors, 80% R.H. Ambient Temp = 80 F Outer surface = Stainless Steel (e = 0.30) Ambient Relative Humidity = 80% Wind Velocity = 7 mph Dew point = 73.3 F Geometry = Horizontal Pipe Insulation Thickness In Inches Necessary To Prevent Condensation or limit heat gain to 8 BTU/hr-sq ft, whichever is greater Service Temperature NPS (F) (in) This table is based on ASTM C heat transfer algorithms. The suggested insulation thickness values assume proper system design and installation, do not include a safety factor, and are applicable only for the specified scenario. ITW recommends that the user consult a qualified design engineer familiar with this type of construction for proper system design and specification ITW Insulation Systems TRYMER LNG Applications Installation Guide Page 20 of 20

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for LIQUEFIED NATURAL GAS (LNG) CRYOGENIC REFRIGERATION CHILLED WATER

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for LIQUEFIED NATURAL GAS (LNG) CRYOGENIC REFRIGERATION CHILLED WATER INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for LIQUEFIED NATURAL GAS (LNG) CRYOGENIC REFRIGERATION CHILLED WATER Dyplast Products Copyright 2012 1 Rev 0112 DYPLAST PRODUCTS

More information

Installation Guidelines for ITW Insulation Systems Metal Jacketing Used on Insulated Pipe

Installation Guidelines for ITW Insulation Systems Metal Jacketing Used on Insulated Pipe Installation Guidelines for ITW Insulation Systems Metal Jacketing Used on Insulated Pipe 1 SCOPE 1.1 This guideline covers the installation of ITW Insulation Systems Pabco-Childers brand aluminum and

More information

INSTALLATION GUIDELINE FOR TRYMER SUPERCEL PHENOLIC INSULATION

INSTALLATION GUIDELINE FOR TRYMER SUPERCEL PHENOLIC INSULATION INSTALLATION GUIDELINE FOR TRYMER SUPERCEL PHENOLIC INSULATION TRYMER SUPERCEL PHENOLIC INSULATION IN CHILLED WATER APPLICATIONS (35 F to 60 F) Vers. 1.0 1 SCOPE 1.1 This guideline covers the installation

More information

Mechanical Insulation for Refrigeration Systems

Mechanical Insulation for Refrigeration Systems Mechanical Insulation for Refrigeration Systems INDUSTRIAL REFRIGERATION CONSORTIUM RESEARCH & TECHNOLOGY FORUM MAY 2-3, 2012 Peter Gauchel, President/CEO L&C Insulation Inc. Overview Current trends in

More information

ACOUSTICAL INSULATION (LAGGING) FOR PIPING AND EQUIPMENT

ACOUSTICAL INSULATION (LAGGING) FOR PIPING AND EQUIPMENT ACOUSTICAL INSULATION (LAGGING) FOR PIPING AND EQUIPMENT Specification for Acoustical Insulation (Lagging) for Piping and Equipment 1 of 5 TABLE OF CONTENTS 1.0SCOPE..... 3 2.0REFERENCED PUBLICATIONS...

More information

SPECIFICATION GUIDELINES FOR THE USE OF CRYOGEL Z ON COLD PIPING AND EQUIPMENT

SPECIFICATION GUIDELINES FOR THE USE OF CRYOGEL Z ON COLD PIPING AND EQUIPMENT SPECIFICATION GUIDELINES FOR THE USE OF CRYOGEL Z ON COLD PIPING AND EQUIPMENT Page 1 of 15 Ver. 3-0 March 2010 TABLE OF CONTENTS 1. Scope... 3 2. General System Requirements... 3 3. Installation Details...

More information

SECTION PIPING INSULATION

SECTION PIPING INSULATION SECTION 23 07 19 PIPING INSULATION PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Piping insulation for refrigerant piping within building envelope. 2. Furnishing and installation of insulation.

More information

DUNA products for industrial insulation Hot, Cold and Cryogenic

DUNA products for industrial insulation Hot, Cold and Cryogenic Insulated pipe Supports LNG insulation Bunstocks Site Production Chemicals for in situ application DUNA products for industrial insulation Hot, Cold and Cryogenic DUNA products for industrial insulation

More information

1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.

1. Division 23 Section Hangers and Supports for HVAC Piping and Equipment for pipe insulation shields and protection saddles. SECTION 23 07 19 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Pipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems

Pipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems Pipe and Equipment Insulations Zeston PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems Zeston PVC Insulated Fitting Covers Installation Instructions for Hot,

More information

SPECIFICATION FOR COLD INSULATION

SPECIFICATION FOR COLD INSULATION SPECIFICATION FOR COLD INSULATION Specification for Cold Insulation 1 of 21 TABLE OF CONTENTS 1.0. SCOPE..... 3 2.0. REFERENCED PUBLICATIONS... 3 3.0. GENERAL CONDITIONS... 3 4.0. MATERIALS... 5 5.0. APPLICATIONS...

More information

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION SECTION 230713 DUCT INSULATION PART 1 GENERAL 1.1 SUMMARY A. Related Sections: 1. 233113 Ductwork and Accessories 1.2 REFERENCES A. American Society for Testing and Materials (ASTM): 1. E84-96a Test Method

More information

SECTION HVAC INSULATION

SECTION HVAC INSULATION PART 1 GENERAL 1.1 SUMMARY SECTION 23 07 00 HVAC INSULATION A. Section Includes: 1. Ductwork insulation. 2. Duct liner. 3. Insulation jackets. 4. Equipment insulation 5. Piping system insulation. 6. Insulation

More information

CFC & HCFC Free Thermal Insulation INSTALLATION AND SPECIFICATION GUIDE

CFC & HCFC Free Thermal Insulation INSTALLATION AND SPECIFICATION GUIDE Resolco Insul-Phen CFC & HCFC Free Thermal Insulation INSTALLATION AND SPECIFICATION GUIDE TABLE OF CONTENTS RESOLCO INC. Specification: Insul-Phen closed cell CFC & HCFC free phenolic foam Pipe & Equipment

More information

A. Deliver material to job site in original, nonbroken, factory packaging, labeled with manufacturer's density and thickness.

A. Deliver material to job site in original, nonbroken, factory packaging, labeled with manufacturer's density and thickness. SECTION 15250 PIPING AND EQUIPMENT INSULATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract including General and Supplementary Conditions, Division 1 Specification

More information

FOAMGLAS INSULATION SPECIFICATION

FOAMGLAS INSULATION SPECIFICATION FOAMGLAS INSULATION SPECIFICATION PITTSBURGH CORNING CORPORATION FOAMGLAS Products Technical Support 800 Presque Isle Drive Pittsburgh, PA 15239 724-327-6100 SPECIFICATION # I-H/C-89-02-01 REVISION 06/28/2004

More information

FIRE STATION 55 June 14, 2010

FIRE STATION 55 June 14, 2010 SECTION 15250 MECHANICAL INSULATION PART 1 - GENERAL 1.01 DESCRIPTION A. Work Includes 1. Insulation of Domestic Water Piping. 2. Pipe Insulation of refrigerant piping. 3. Insulation of ductwork. 4. Aluminum

More information

Recommended Installation and Repair Guide

Recommended Installation and Repair Guide Revision 1 7/20/2017 Insulation Jacketing Products Recommended Installation and Repair Guide Pipe and Equipment Insulation Jacketed with Factory and Field Installed Products Table of Contents 1. Scope...

More information

Project Specification. Tarec. Insulation for the LNG, Petrochemical and Process Industries

Project Specification. Tarec. Insulation for the LNG, Petrochemical and Process Industries Project Specification & Installation Tarec pir Guide TM Insulation for the LNG, Petrochemical and Process Industries Project Specification CONTENTS 1 Scope 3 2 Codes, Standards & References 4 3 Design

More information

University of Delaware

University of Delaware University Contact: Energy & Engineering Group (302) 831-1744 SECTION 23 07 00_ HVAC INSULATION PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Piping system insulation. 2. Equipment insulation. 3.

More information

HVAC Piping Insulation- FIBERGLAS Insulation

HVAC Piping Insulation- FIBERGLAS Insulation PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.

More information

SECTION (15081) - HVAC INSULATION

SECTION (15081) - HVAC INSULATION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: SECTION 23 07 00 (15081) - HVAC INSULATION 1. Insulation Materials 2. Jackets 3. Accessories and Attachments 4. Vapor Retarders B. Related Sections: 1.02

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

ITWIS is setting the industry standard for reliability, quality, support, and responsiveness.

ITWIS is setting the industry standard for reliability, quality, support, and responsiveness. ITWIS is setting the industry standard for reliability, quality, support, and responsiveness. ITW Insulation Systems (ITWIS), headquartered in Houston, TX, manufactures insulation, vapor retarder, and

More information

PIP INSC1000 Cold Service Insulation Materials and Installation Specification

PIP INSC1000 Cold Service Insulation Materials and Installation Specification COMPLETE REVISION Ocber 2017 Insulation PIP Cold Service Insulation Materials and Installation Specification PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort minimize the cost of process industry

More information

SECTION HVAC PIPING INSULATION

SECTION HVAC PIPING INSULATION SECTION 23 0719 HVAC PIPING INSULATION PART 1 - GENERAL 1.1 SUMMARY A. Includes But Not Limited To: 1. Furnish and install insulation on above ground refrigerant piping and fittings as described in Contract

More information

GUIDE SPECIFICATION: DUCT LINER

GUIDE SPECIFICATION: DUCT LINER GUIDE SPECIFICATION: DUCT LINER This specification guide includes thermal & acoustical insulation for ductwork and air handling systems. This section is based on the format recommended by MICA (Midwest

More information

A. Source Limitations: Obtain each type of building insulation through one source.

A. Source Limitations: Obtain each type of building insulation through one source. SECTION 07210 - BUILDING INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

This Design guideline contained herein includes the requirements for mechanical insulation at The University of Texas at Austin

This Design guideline contained herein includes the requirements for mechanical insulation at The University of Texas at Austin PART 1: GENERAL 1.01 Purpose: This Design guideline contained herein includes the requirements for mechanical insulation at The University of Texas at Austin 1.02 Scope: A. Extent of mechanical insulation

More information

SECTION 07530CP EPDM MEMBRANE ROOFING

SECTION 07530CP EPDM MEMBRANE ROOFING PART 1 GENERAL 1.1 SUMMARY SECTION 07530CP EPDM MEMBRANE ROOFING A. Section includes: 1. Adhered membrane roofing and flashing 2. Mechanically fastened roof insulation 3. Walkway pads 1.2 ARCHITECTURAL

More information

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 075423 - THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Division 00 Bidding Requirements and other Division

More information

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM PART 1- GENERAL 1.1 SUMMARY A. Section Includes: SECTION 084523 - SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM 1. Flat factory prefabricated structural insulated translucent sandwich panels; with glazed endwalls.

More information

Sept 30, 2004 Page 1

Sept 30, 2004 Page 1 Sept 30, 2004 Page 1 This section includes a manufacturer's guide specification for TERRAFOAM EPS building insulation. Refer also to Product Description for detailed product properties, options, and other

More information

K-FLEX K-FONIK INDUSTRIAL

K-FLEX K-FONIK INDUSTRIAL J a n u a r y 2 0 1 3 K-FLEX K-FONIK INDUSTRIAL Sound & Thermal Insulation design compliant with ISO 15665 www.kflexenergy.com Flexible Elastomeric Foam layer INSULATING PIPING WITH K-FLEX SHEETS > FIRST

More information

Redi-Klad 1000 Pipe Insulation

Redi-Klad 1000 Pipe Insulation Knauf Data Sheet PE-DS-16e 12-09 Redi-Klad 1000 Pipe Insulation with ECOSE Technology Knauf Redi-Klad 1000 F Pipe Insulation with ECOSE Technology is offered across a wide range of sizes. For iron pipe

More information

SECTION PRE-ENGINEERED BUILDING INSULATION

SECTION PRE-ENGINEERED BUILDING INSULATION PART 1 GENERAL SECTION 07213 PRE-ENGINEERED BUILDING INSULATION Microsoft Word Instructions: Display hidden notes to specifier by using "Tools"/"Options"/"View"/"Hidden Text". 1.1 SECTION INCLUDES A. Pre-Engineered

More information

FlexClad Duct and Pipe Sealing System

FlexClad Duct and Pipe Sealing System FlexClad Duct and Pipe Sealing System Proven Performance Outperforms Metal Jacketing Waterproof & Weather-Resistant Ideal For Indoor & Outdoor Applications Quick & Easy Self-Stick Installation Meets 25/50

More information

LP SmartSide Perfection Shingle

LP SmartSide Perfection Shingle Application Instructions Fiber Substrate Lap Siding A A - Lap Siding ON SITE STORAGE Store off the ground well supported, on a flat well-drained surface. (Diagram 1a) Additional support may be required

More information

PIP INSA1000 Acoustic Insulation Systems Specification

PIP INSA1000 Acoustic Insulation Systems Specification TECHNICAL REVISION April 2015 Insulation PIP INSA1000 Acoustic Insulation Systems Specification PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities,

More information

NCCER Progress Blvd, Alachua, Florida Tel: (888)

NCCER Progress Blvd, Alachua, Florida Tel: (888) NCCER 13614 Progress Blvd, Alachua, Florida 32615 Tel: (888) 622-3720 E-mail: info@nccer.org INSULATING Competencies / Objectives Level One MODULE 19101 - ORIENTATION 1. Explain what insulation is and

More information

MECHANICAL INSULATION

MECHANICAL INSULATION MECHANICAL INSULATION GENERAL INFORMATION 1.1 Comply with more stringent of following latest edition of Energy Conservation and Construction Code of New York City, ASHRAE and this Guideline. DESIGN REQUIREMENTS

More information

STANDARD SPECIFICATIONS. Followings have been covered in this section. The work is to be carried based on the standard specifications:

STANDARD SPECIFICATIONS. Followings have been covered in this section. The work is to be carried based on the standard specifications: STANDARD SPECIFICATIONS APPENDIX -3 Followings have been covered in this section. The work is to be carried based on the standard specifications: 1) Standard Specifications for Cold Insulation 2) Standard

More information

Cryogenic Pipe Support Systems

Cryogenic Pipe Support Systems Cryogenic Pipe Support Systems Overview Rilco cryogenic pipe supports are developed to support cold piping in various applications ranging from chilled water to liquefied natural gas. The qualified service

More information

Installation Manual PIPE AND EQUIPMENT INSULATION

Installation Manual PIPE AND EQUIPMENT INSULATION PIPE AND EQUIPMENT INSULATION Contents (Click below to jump to section) Safety First 3 Material Handling 3 Preparation and Storage 4 Optimal Work Setup 5 Single Wrap Pipe 6 Double Wrap Pipe 7 Multi-Layer

More information

Cold Work Cladding Fabrication & Application

Cold Work Cladding Fabrication & Application TRADE OF Industrial Insulation PHASE 2 Module 3 Substructures, Advanced Cold Work and Cladding UNIT: 4 Cold Work Cladding Fabrication & Application Produced by In cooperation with subject matter expert:

More information

SECTION HVAC INSULATION

SECTION HVAC INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. B. Related

More information

SECTION HVAC DUCTS AND CASINGS

SECTION HVAC DUCTS AND CASINGS SECTION 23 31 00 HVAC DUCTS AND CASINGS PART 1 -GENERAL 1.1 SUMMARY A. Section includes metal ductwork, nonmetallic ductwork, casing and plenums, buried ductwork, kitchen hood ductwork, duct cleaning.

More information

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection SECTION 13090 RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13090-1 LOW INTENSITY RADIATION PROTECTION

More information

1.2 The Engineer shall select appropriate sections of the specification to ensure that the specification is comprehensive for specified work.

1.2 The Engineer shall select appropriate sections of the specification to ensure that the specification is comprehensive for specified work. STAC Coating System Specification & Installation Guide 1.0 Scope 1.1 This specification may be used for the priming, caulking and wrapping with the STAC Petrolatum Coating System of any of the following

More information

BuildingName The Description of the Project P DOCUMENTS

BuildingName The Description of the Project P DOCUMENTS P00000000 0000 DOCUMENTS ARCHITECTURE ENGINEERING AND CONSTRUCTION ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION DIVISION

More information

SECTION ROOF SPECIALTIES

SECTION ROOF SPECIALTIES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 71 00 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information

SECTION PLUMBING INSULATION

SECTION PLUMBING INSULATION SECTION 22 07 00 PLUMBING INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Ammonia. Product performance for insulation of ammonia piping

Ammonia. Product performance for insulation of ammonia piping Ammonia Product performance for insulation of ammonia piping ABOUT K-FLEX USA K-FLEX USA IS A LEADING MANUFACTURER of flexible, closed cell elastomeric insulation for mechanical piping, air handling units

More information

SECTION ALUMINUM STORM WINDOWS

SECTION ALUMINUM STORM WINDOWS PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 08 51 69.11 ALUMINUM STORM WINDOWS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Also delete any other item or paragraph not applicable

More information

A. Meet at Project site <insert number> days before starting installation.

A. Meet at Project site <insert number> days before starting installation. SECTION 074643 - COMPOSITION SIDING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Engineered wood cladding. 2. Soffit panels. 3. Trim and fascia. 4. Sealant. 5. Weather barrier. 6. Flashing. 1.2

More information

TECHNICAL BULLETIN POLYISOCYANURATE VS. CELLULAR GLASS IN LOW TEMPERATURE MECHANICAL INSULATION

TECHNICAL BULLETIN POLYISOCYANURATE VS. CELLULAR GLASS IN LOW TEMPERATURE MECHANICAL INSULATION TECHNICAL BULLETIN 0114 1 POLYISOCYANURATE VS. CELLULAR GLASS IN LOW TEMPERATURE MECHANICAL INSULATION PURPOSE This Technical Bulletin is an update in our series of white papers aimed at providing our

More information

FIRESTOP JOINT SPRAY CFS-SP WB. 2mm (0.079") WET FILM ± 7.5 ± 5

FIRESTOP JOINT SPRAY CFS-SP WB. 2mm (0.079) WET FILM ± 7.5 ± 5 Design No. CEJ 27 P (HI/JS 20-05) Table. CONCRETE FLOOR ASSEMBLY: Max. two-hour rated concrete floor assembly made from either lightweight or normal weight concrete with a density of 00-50 pcf, with a

More information

PIPE AND EQUIPMENT INSULATION

PIPE AND EQUIPMENT INSULATION Contents (Click below to jump to section) Safety First 2 Material Handling 2 Preparation and Storage 3 Optimal Work Setup 4 Single Wrap Pipe 6 Double Wrap Pipe 7 Multi-Layer Wrap Pipe 8 Pipe Fittings 10

More information

SECTION METAL ROOF PANELS

SECTION METAL ROOF PANELS SECTION 07 41 13 PART 1 GENERAL 1.1 SECTION INCLUDES A. Standing-seam roof panels. B. Metal roofing accessories. 1.2 RELATED SECTIONS A. Section 07 62 00 - Sheet Metal Flashing. B. Section 07 72 00 - Roof

More information

TECHNICAL BULLETIN 0214 (update of 0111) PERFORMANCE/COST COMPARISON OF POLYISO vs. XPS PIPE INSULATION SYSTEMS

TECHNICAL BULLETIN 0214 (update of 0111) PERFORMANCE/COST COMPARISON OF POLYISO vs. XPS PIPE INSULATION SYSTEMS Page 1 of 5 TECHNICAL BULLETIN 0214 (update of 0111) PERFORMANCE/COST COMPARISON OF POLYISO vs. XPS PIPE INSULATION SYSTEMS PURPOSE Increased focus on energy savings and improvements in the properties

More information

SECTION EXPANSION CONTROL

SECTION EXPANSION CONTROL SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION THERMAL INSULATION GENERAL THERMAL INSULATION PART RELATED DOCUMENTS

SECTION THERMAL INSULATION GENERAL THERMAL INSULATION PART RELATED DOCUMENTS SECTION 15250 - THERMAL INSULATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS are a part of this Section. 1.02 SUMMARY A.

More information

INSTALLING WATER-RESISTIVE BARRIERS & FLASHING

INSTALLING WATER-RESISTIVE BARRIERS & FLASHING INSTALLING WATER-RESISTIVE BARRIERS & FLASHING IN A TWO-LAYER STUCCO APPLICATION Fortifiber Building Systems Group provides this guide to assist installers by demonstrating a two-layer installation of

More information

SECTION MANUFACTURED ROOF EXPANSION JOINTS

SECTION MANUFACTURED ROOF EXPANSION JOINTS SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING

SECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING P.O. Box 599 - Mars, PA 16046 800-321-3337 SECTION 07555 COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including

More information

Techna-Duc. Advantages. Features and Benefits. LEED Eligible Product

Techna-Duc. Advantages. Features and Benefits. LEED Eligible Product Techna-Duc Advantages Techna-Duc is shop fabricated and installed with minimal field alterations. Panels are constructed with polyisocyanurate insulation products that do not promote the growth of mold

More information

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof SECTION 07550 MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof This section is based on the products of MFM Building Products Corp., which is located at: 525 Orange St. P. O. Box 340 Coshocton, OH 43812

More information

SECTION EXPANSION CONTROL

SECTION EXPANSION CONTROL SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 23 07 00 - SYSTEM INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01 00, "Mechanical

More information

Pipe & Equipment Insulations Product Selection Guide

Pipe & Equipment Insulations Product Selection Guide Fiber Glass Insulation Pipe & Equipment Insulations Product Selection Guide Icon Key Thermal Acoustical Fire Resistance Moisture Control Formaldehyde-free products for improved indoor air quality For more

More information

Extreme Sealing Tape

Extreme Sealing Tape Extreme Sealing Tape Technical Data September, 2014 Product Description 3M Extreme Sealing Tape is a family of single coated, pressure sensitive adhesive tapes designed for difficult sealing applications.

More information

Recommended Design Considerations. and. Guide Specifications For. Commercial Building Insulation

Recommended Design Considerations. and. Guide Specifications For. Commercial Building Insulation Recommended Design Considerations and Guide Specifications For Commercial Building Insulation Date of Issue: October 1, 2004 Recommended Design Considerations and Guide Specifications For Commercial Building

More information

A M E R I C A N A R C H I T E C T U R A L M A N U F A C T U R E R S A S S O C I A T I O N

A M E R I C A N A R C H I T E C T U R A L M A N U F A C T U R E R S A S S O C I A T I O N A M E R I C A N A R C H I T E C T U R A L AAMA 2410-13 Standard Practice for Installation of Windows with an Exterior Flush Fin Over an Existing Window Frame M A N U F A C T U R E R S A S S O C I A T I

More information

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.

More information

BULLETIN FROM THE FIRST COAST CHAPTER ICC~BOAF

BULLETIN FROM THE FIRST COAST CHAPTER ICC~BOAF FIRST COAST CHAPTER INTERNATIONAL CODE COUNCIL (ICC) AND BUILDING OFFICIALS ASSOCIATION OF FLORIDA, INC. (BOAF) SERVING BAKER, BRADFORD, CLAY, DUVAL, NASSAU, PUTNAM, ST. JOHNS & UNION COUNTIES BULLETIN

More information

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT SECTION 220529 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

TRAC-LOC TANK INSULATION SYSTEM

TRAC-LOC TANK INSULATION SYSTEM TRAC-LOC TANK INSULATION SYSTEM THERMAL MANAGEMENT SOLUTIONS WWW.THERMAL.PENTAIR.COM INDUSTRIAL SOLUTIONS As the world s largest provider of complete electrical heat management systems, primarily for the

More information

Siding and Soffit Installation Guidelines

Siding and Soffit Installation Guidelines Siding and Soffit Installation Guidelines email web phone 07 46 16 Longboard Siding & Soffit INTRODUCTION INSTALLATION GUIDELINES NOTE: These instructions are prepared for persons experienced in the field

More information

SECTION RESILIENT SHEET FLOORING

SECTION RESILIENT SHEET FLOORING SECTION 09 65 16 RESILIENT SHEET FLOORING SPEC WRITER NOTE: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1.

More information

L'ISOLANTE K-FLEX. LNG applications Manual

L'ISOLANTE K-FLEX. LNG applications Manual L'ISOLANTE K-FLEX LNG applications Manual LNG applications Manual The insulation LNG plants may forsee a multilayer design according to the specific characteristics and the working temperatures of the

More information

Signature Series 5 Lap SECTION ALUMINUM WINDOWS

Signature Series 5 Lap SECTION ALUMINUM WINDOWS Signature Series 5 Lap SECTION 08 51 13 ALUMINUM WINDOWS PART 1 GENERAL 1.01 SUMMARY A. Related Documents: Conditions of the Contract, Division 1 - General Requirements, and Drawings apply to Work of this

More information

Guideline Specifications

Guideline Specifications Page 1 of 7 PART 1 Guideline Specifications Exterior Aluminum/Composite Wall Panels GENERAL ARROWHEAD 508 SYSTEM Pressure Equalized Rainscreen SECTION 07410 1.01 SUMMARY A. Work of this section included

More information

Purdue e-pubs. Purdue University. Weiwei Zhu Oklahoma State University, United States of America,

Purdue e-pubs. Purdue University. Weiwei Zhu Oklahoma State University, United States of America, Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Thermal Performance and Moisture Accumulation of Mechanical Pipe Insulation Systems

More information

SPECIFICATIONS FOR AluSystems Aluminum Composite Panels Series 20 Dry Joint 1.00 GENERAL 1.01 RANGE OF WORK Section includes: Laminated panels and attachment systems for use as exterior cladding. A. Provide

More information

Gold Bond BRAND Gypsum Sheathing

Gold Bond BRAND Gypsum Sheathing BRAND 09 06 29 16 00/NGC 43/NGC brand is a moisture-resistant sheathing installed on the outside of exterior framing as a substrate for exterior claddings. It is manufactured with a treated water-resistant

More information

SECTION PANEL AND POST AND PYLON SIGNAGE. 1. Non-illuminated Panel and Post signs. 2. Internal illumination Pylon (Cabinet and Post) signs.

SECTION PANEL AND POST AND PYLON SIGNAGE. 1. Non-illuminated Panel and Post signs. 2. Internal illumination Pylon (Cabinet and Post) signs. PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Non-illuminated Panel and Post signs. 2. Internal illumination Pylon (Cabinet and Post) signs. 1.2 PERFORMANCE REQUIREMENTS A. Structural

More information

DIVISION 7 THERMAL AND MOISTURE PROTECTION SECTION PENETRATION FIRESTOPPING

DIVISION 7 THERMAL AND MOISTURE PROTECTION SECTION PENETRATION FIRESTOPPING DIVISION 7 THERMAL AND MOISTURE PROTECTION SECTION 07 84 13 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SINGLE SWING DOOR PAIRED SWING DOOR

SINGLE SWING DOOR PAIRED SWING DOOR Rev. 091416 SINGLE SWING DOOR PAIRED SWING DOOR Drawing No.: Revision: Date: If you need to contact Customer Service Please complete the following information and retain for future reference: Serial Number:

More information

RPR Insul-Mate Sheet and Roll Jacketing

RPR Insul-Mate Sheet and Roll Jacketing RPR Insul-Mate Sheet and Roll Jacketing ALUMINUM PRODUCTS Rolled Jacketing Sheeting (Flat and Corrugated) Cut to Length Cut & Rolled Width/Length: 36 and 48 wide 100, 50 and cut to length (thicker gauges

More information

SLAB ON GRADE Insul-Joint or Expansion Joint Material as Required by A/E Specifications AquaCheck Liquid Coating 400 (Waterproofing Membrane) with Aqu

SLAB ON GRADE Insul-Joint or Expansion Joint Material as Required by A/E Specifications AquaCheck Liquid Coating 400 (Waterproofing Membrane) with Aqu INSTALLATION INSTRUCTIONS Note: The following installation instructions are based off of ASTM E 1643 (Standard Practice for Installation of Water Vapor Retarders Used in Contact with Earth or Granular

More information

Light-Metal Roof Edge, Raised

Light-Metal Roof Edge, Raised NAIL WOOD CANT TO BLOCKING 2 ROWS STAGGERED EACH ROW 24 O.C. 1/2 MIN. 10 0 MAX. FASTEN 18 O.C. WITH NEOPRENE GASKETED FASTENERS 3-1/2 MIN. 4 6 JOINT COVER PLATE SET IN TWO BEADS OF SEALANT 4 MIN. SPECIFIED

More information

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers. SECTION 230529 - HANGERS AND SUPPORTS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Sleeves. 6. Mechanical sleeve seals. 7. Firestopping

More information

4411N 4411G 4412N 4412G

4411N 4411G 4412N 4412G Extreme Sealing Tape Technical Data October, 2011 Product Description 3M Extreme Sealing Tape is a family of single coated, pressure sensitive adhesive tapes designed for difficult sealing applications.

More information

Fire Barrier Duct Wrap 615+

Fire Barrier Duct Wrap 615+ Fire Barrier Duct Wrap 615+ Duct Wrap Fire Protection System for Commercial Kitchen Grease and Ventilation Air Ducts Product Data Batts and blankets for use in fire resistive duct assemblies see UL fire

More information

FIXED SERIES 6200 AAMA/WDMA/CSA 101/I.S.2/A Structural Performance: Thermal Break: Main Frame Depth: 3 1/4. Glazing Thickness (Maximum): 1

FIXED SERIES 6200 AAMA/WDMA/CSA 101/I.S.2/A Structural Performance: Thermal Break: Main Frame Depth: 3 1/4. Glazing Thickness (Maximum): 1 GUIDE SPECIFICATION Boyd Aluminum Manufacturing Company P.O. Box 1565 3248 E. Division Street Springfield, MO 65801-1565 800-737-2800 417-862-1232 fax boydaluminum.com FIXED SERIES 6200 AAMA/WDMA/CSA 101/I.S.2/A440-08

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC. 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1143 Reissued 04/2017 This report is subject to renewal 04/2018. DIVISION: 07 00 00 THERMAL

More information

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO SECTION 07 53 23 - ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions ofthe Contract, including General and Supplementary Conditions

More information

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017 SECTION 055213 - PIPE AND TUBE RAILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION EXPANSION CONTROL

SECTION EXPANSION CONTROL SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Endotherme Mat ES-5A-12

Endotherme Mat ES-5A-12 Interam TM Endothermic Mat ES-5A-12 Product Data Sheet Supersedes: May 2016 Endothermic Mat ES-5A-12 Endothermique Mat ES-5A-12 Endothermische Matte ES-5A-12 Endotermica Mat ES-5A-12 Endotérmico Mat ES-5A-12

More information