Special Specification 6226 Adjust or Relocate Campsite Utilities

Size: px
Start display at page:

Download "Special Specification 6226 Adjust or Relocate Campsite Utilities"

Transcription

1 Special Specification 6226 Adjust or Relocate Campsite Utilities 1. DESCRIPTION 2. MATERIALS Adjust or relocate water, sewer and electrical utilities at park campsites locations as shown on the plans General. Provide new materials that comply with the details shown on the plans, the requirements of this item and the following items: Item 421, Hydraulic Cement Concrete Item 440, Reinforcement for Concrete Use Class A concrete for cast-in-place water valve box collars unless otherwise shown on the plans Electrical Materials. Submit manufacturers' product data for the following electrical system items: Submersible tap-blocks for splicing in pull boxes Service circuit breaker and enclosure Campsite RV power outlets, 30 amp and 50 amp Pre-cast concrete pads for campsite RV power outlets, 30 amp and 50 amp Conduit Metallic. Provide rigid steel, zinc-coated, and threaded type metal conduit conforming to ANSI C80.1 and UL 6. Provide zinc coating fused to the inside and outside walls. Provide threaded type rigid metal conduit fittings that are cast malleable iron, galvanized or cadmium plated. All fittings must be threaded type. Do not use split couplings. Provide EMT conforming to ANSI C80.3 for galvanized tubing. Provide zinc coating fused to inside and outside walls. Use compression fittings only. Do not use set-screw fittings for EMT Non-metallic. Provide heavy Wall Schedule 40 and Schedule 80 conduit that is 90 C UL rated. Conduit must be construct of polyvinyl chloride and conforming to NEMA TC-2, for direct burial or normal above ground use, UL-listed and in conformity with NEC article 352. Provide fittings for non-metallic conduit that conform to NEMA TC-3 and are specifically manufactured for electrical conduit. Water pipe fittings will not be accepted Wiring. Provide general use single conductor wire that is a minimum size of #12 AWG. Wire must be copper, type THWN, UL listed for general use at a maximum of 600 volts and a maximum temperature of 75 C in wet locations. Wire size #8 AWG and larger must be stranded. Provide wire that meets the color coding requirements of Table 1. Table 1 Wire Color Coding System Phase A Phase B Neutral Ground 240/120 Black Red White Green 1 1. For single conductor ground wiring #8 AWG or smaller

2 Provide colored phase tape for identification of all wires #6 AWG and larger. Apply tape in a spiral, half-lap manner over exposed conductor portions in pull boxes, junction boxes, RV power outlets, and other enclosures. Provide wire marking labels that conform to Section "Identification and Markings.". Adhesive type labels shall have an adhesive backing with a white background and black lettering equal to 3M Scotch-Code or T&B E-Z Code. Markers may be pre-printed, printed with a hand held printer, or write-on style. Other wire marking labels such as heat shrink tubing or Ty-wrap type labels may also be used as approved. Wire must be cleaned of oil, dirt, and pulling compound before wire markers are installed Circuit breakers. Provide circuit breakers that are quick-make, quick-break plug-in type with common trip on all multi-pole breakers. They shall have positive handle indication and an internal tie mechanism with overcenter, toggle-type operating mechanisms. Circuit breaker enclosures should be NEMA 3R, rainproof with a solid neutral block and a separate ground buss/lug. Provide circuit breakers that have a minimum UL listed interrupting rating (RMS SYM. AMPS) of AMP=10,000 AIC for 240 V maximum breakers. Interrupting ratings for load center main circuit breakers will be noted on the plans Campsite RV Power Outlets. Provide power outlets that are pad mounted type for mounting on pre-cast or cast-in-place concrete pads as detailed on the plans. Dimensions of the concrete pad mounting bolts or inserts must match the mounting bolt pattern of the power outlet. See the pad details and specifications on the plans Amp Campsite Power. Provide 30 amp campsite power outlets equal to Midwest Electric Products, Inc. Model #U041GP4, pad mount. Equip the power outlets with one 30 amp, ANSI #R-32U receptacle; one 20 amp, NEMA 5-20R receptacle; one 30 amp, 1-pole circuit breaker to protect the 30 amp receptacle; and one 20 amp, 1-pole, GFCI circuit breaker to protect the duplex receptacle. The power outlets also must have a NEMA 3R rated steel enclosure and pedestal with loop feed lugs in the pedestal suitable for copper or aluminum wiring, load center interior with a neutral buss for circuit breaker mounting, separate ground busses in the power outlet and in the pedestal, lockable hinged door and pedestal cover, heavy duty receptacles pre-wired to the load center breakers and busses, and be UL listed Amp Campsite Power. Provide outlets equal to Midwest Electric Products, Inc. Model #U075GP4, pad mount, equip the power outlets with one 50 amp, NEMA 14-50R receptacle; one 30 amp, ANSI #BR-32U receptacle, and one 20 amp, NEMA 5-20R receptacle, and one 50 amp, 2-pole circuit breaker to protect the 50 amp receptacle, one 30 amp, 1-pole circuit breaker to protect the 30 amp receptacle, and 1-20 amp, 1- pole, GFCI circuit breaker to protect the duplex receptacle. The power outlets also must have a NEMA 3R rated steel enclosure and pedestal with loop feed lugs in the pedestal suitable for copper or aluminum wiring, load center interior with a neutral buss for circuit breaker mounting, separate ground busses in the power outlet and in the pedestal, lockable hinged door & pedestal cover, heavy duty receptacles pre-wired to the load center breakers and busses, and be UL listed Water and Sewer System Materials. Provide Schedule 40 PVC water piping that is 2 in. and smaller. Provide solvent-welded Schedule 40 PVC or SDR-21 gasketed, piping for 4 sewer piping. All PVC piping must be constructed of materials that conform to cell classification B as defined by ASTM D1784 and ASTM D1785. All new pipe and related products must bear the NSF no. 14 seal of approval. Provide new solvent welded type Schedule 80 PVC pipe fittings for 2 in. and smaller piping. Furnish solvent cement that conforms to ASTM #D Provide galvanized steel water pipe conforming to the requirements of ASTM A-53 or ASTM A-120 standard weight and Schedule 40 pipe threading that has standard taper pipe threads conforming to ASME B

3 Provide galvanized malleable iron metal pipe fittings with threaded joints. All fittings for connections to PVC pipe must be threaded joint fittings. Provide lead-free type hose bibbs and vacuum breakers equal to the model numbers listed on the plans. Provide lead-free, ball, type valves with solvent welded ends, and stopped handle. 600 psi rated non-shock valve with a cold water service rating for up to and including 2 in. (50 mm). Provide valves equal to True Union non-metallic ball valves. Provide valve boxes made of high impact, high density polyethylene plastic with locking cast iron cover and the word "water" cast into the cover top. The valve covers and boxes provided must be equal to East Jordan Iron Works 34 Series. Provide two of any special tool required to unlock the new valve box covers. Furnish and install blue, detectable marking tape 6 in. above all water lines that are buried alone in a trench. Provide marking tape consisting of one layer of 0.35 mil thick aluminum foil laminated between two layers of inert plastic film. Where water lines are installed in a common trench with electrical conduits, furnish and install electrical marking tape placed with the writing face upward. Furnish and install green, detectable marking tape 6 in. above all sewer lines that are buried alone in a trench. Provide marking tape consisting of one layer of 0.35 mil thick aluminum foil laminated between two layers of inert plastic film. Install all tape with the writing face upward. Repair any existing water or sewer lines not scheduled to be replaced on this project that are damaged. Repair using materials that are compatible with the type of piping damaged. Repair PVC pipe using only one piece of pipe for each repair. Repairs must have at least one joint that is solvent cemented. 3. CONSTRUCTION 3.1. General. Coordinate all utility adjustment and relocation efforts with the Texas Parks & Wildlife Department (TPWD) facility superintendent before beginning work. Protect all existing electrical, water and wastewater appurtenances at all times during the construction. Promptly repair, at no additional cost, any damage to the existing electrical, water or wastewater systems and/or any interruption to the service such as line stoppages or breakage caused by contractor error. Provide testing for water mains and wastewater lines in conformance to the utility company s requirements or as directed. Perform the following testing as minimum for water mains: hydrostatic test, sterilization test All water lines, sewer lines, electrical lines, and all associated appurtenances installed with this project will be inspected by a representative of TPWD. The TPWD representatives decision of acceptability of the installation will be final Electrical Construction General. Perform all electrical work in accordance with the 2014 edition of the National Electric Code (NEC). The project electrical work must be performed by a contractor licensed with TDLR to perform electrical work. Perform electrical work under the direct, on-site supervision of a licensed, master or journeyman electrician. Submit copies of the state of Texas electrical contractor's license and the licenses for all of the electricians that will perform the work. Submit this information at the preconstruction conference as part of the project submittal information. Before the relocation of the electrical service, disconnect and isolate any existing electrical service equipment in accordance with the utility company s requirements. Use established industry and utility safety practices while removing electrical service equipment near any overhead utilities

4 Remove existing electrical service support a minimum of 2 ft. below finish grade unless otherwise shown on the plans. Repair the remaining hole by backfilling with material equal in composition and density to the surrounding area. Replace any surfacing such as asphalt pavement or concrete riprap with like material to equivalent condition. Disconnect conductors and remove them from the conduit or duct. Cut off all protruding conduit or duct 12 in. below finish grade. Abandoned conduit or duct need not be removed unless shown on the plans Installation of Conduits. Mechanically fasten together metal conduits, enclosures, and raceways for conductors to form continuous electrical conductor. Conduits must have openings temporarily plugged to exclude foreign materials, be reamed after cutting; have joints cut square, and butt solidly into fittings; have the ends terminated in a proper bushed fitting, and be rigidly supported so as to prevent undue stress or strain on the couplings and connectors. Use insulated type bushings on all metal conduits. Use rain tight hubs for conduit entries into the tops of outdoor enclosures. Use sealing locknuts for conduit entries into the sides or backs of outdoor enclosures. Install all conduit systems completely before conductors are pulled in. Metal conduit systems must be electrically continuous throughout Grounding. Provide a ground wire in all new wire runs installed in new or existing conduit. Connect a properly sized ground wire to all metal electrical enclosures that have wiring modifications on the project Underground Conduit Installation. Terminate rigid non-metallic PVC, Type EPC 40 or 80 conduits, with a bell-end fitting or male adapter and plastic bushing in RV power outlets and pull boxes. See trench details on the plans for underground conduit. Run conduit in straight lines except where a change of direction is required. Provide not less than 3 in. clearance from the conduit to each side of the trench. As each conduit run is complete, assure that the conduit interior is free from dirt or debris. Install conduit plugs or otherwise cover end of conduit to prevent entry of foreign material until wire is pulled into conduit. Except at conduit risers; accomplish changes in direction of runs exceeding a total of 10, either vertical or horizontal, with long sweep bends. Manufactured bends must have a minimum radius of 18 in. for use with conduits of less than 3 in. in diameter. Do not install conduit smaller than 3/4 in. below ground. For all rigid metal conduit in contact with earth, provide corrosion protected with corrosion protection tape or by installing PVC coated rigid metal conduit. Extend corrosion protection on the conduit a minimum of 6 in. above grade. Permanently identify all underground electrical conduits with a colored, electrical identification tape over the conduit systems before backfilling trenches. Install all tape with the writing face up Conductor Installation. Do not install conductors in conduit or other types of raceway until the raceway or conduit system has been completed. When installing conductors in conduit, use wire-pulling compound and exercise due care to prevent damage to conductors or insulation. Type THWN wiring with the outer nylon jacket damaged will not be accepted. Replace all damaged conductors at no expense Identification and Markings. Label all new feeder wiring in the pull boxes with the campsite number of the destination of the wiring. Place labeling on the wiring at the new tap-blocks Tests. Coordinate the testing of the electrical system items with TPWD and Construction personnel. All operational tests must be witnessed by TPWD inspection personnel

5 Test the new secondary feeder wiring installation for the relocated RV power outlets using a 500 V DC, generating type insulation tester (Megger tester) after all wiring is completed and ready for the attachment to the equipment and the new tap-blocks. The resistance between the each hot and neutral conductor and between each hot and neutral conductor and the ground conductor must conform to the NEC. The minimum acceptable insulation resistance for each wire must be 50 meg-ohms. Megger test results must be documented, signed by the licensed electrician performing the tests, and submitted to the TPWD engineer as part of the close-out documentation for the project. Perform an operational test after all equipment and loads have been connected and ready to use. These tests must verify the proper operation of all RV power outlet receptacles, circuit breakers, ground fault interrupters, and other electrical equipment or devices in the Park. Assure that the proper voltage is available at all RV power outlets and other receptacles. 3.3 Water and Sewer System Construction General. The exact locations of trench lines for new water lines to the relocated campsite RV power outlet locations and any new valves will be determined in the field at the start of construction. These determinations will be made between TPWD representative and the Contractor. Install new ball valves centered in the new valve boxes so that the sides of the valve box will not impede the operation of the ball valve s handle. Full range of operation of the valve s handle must be accomplished without pinching the operator s hand or fingers or without forcing the handle against the side of the valve box Quality Assurance. Install work in accordance with all applicable TCEQ, AWWA, local and state rules. Perform all water and sewer system work by or under the direct, on-site supervision of a qualified water utility worker. Submit a copy qualified water utility worker's recent work history related to installing potable water piping and utilities as part of the administrative submittal information required for the project Installation of Pipe. For new runs of water and sewer piping, do not damage pipe during laying operations. Lay the pipe so it will receive continuous support throughout its full length. Do not use couplings or gasketed pipe ends to support the piping. Clean and check the pipe for obstructions before joining or laying. Valves must not depend on the PVC piping for support. Place bricks under the body of the valves to provide support before placement of bedding gravel in the valve box. Support new valve boxes above the new piping using bricks. Valve boxes must not rest on the piping. Use solvent cement and primer recommended by the supplier or manufacturer furnishing the pipe and fittings. Apply with strict adherence to the manufacturer's application directions. Wrap all galvanized piping installed below grade with corrosion protection tape to a minimum of 6 in. above grade or 2 in. above the top of the RV power outlet concrete pad. Install water piping in accordance with the TCEQ rules, 30 TAC, Chapter 290, Public Drinking Water, subchapter D, Rules and Regulations for Public Water Systems". Do not exceed the manufacturer's recommendations for the curvature of the line or the deflection of pipe joints. Install pipe fittings for all bends in excess of 10. Maintain a working pressure rating for valves, fittings and appurtenances of 150 psig or greater. Cap the ends of all new lines with piping material that matches line to be capped. All piping and appurtenances must be new. All newly installed piping and related products must conform to American National Standard Institute / National Sanitation Foundation (ANSI/NSF) standard 61. All plastic piping must bear the NSF seal of approval (NSF-PW) for potable water. The plans do not indicate all bends, fittings, and transitions. Furnish and install these items as needed at no additional cost. Install piping to attain minimum TCEQ coverage over new piping

6 Provide for the de-chlorination of highly chlorinated water before discharge from the water system during the testing and chlorination stage of the project. Clean, flush, test, and disinfect the new water line piping per the specifications prior to connection to the park existing water system. Clean, flush and test the new gravity sewer line piping to assure that it does not leak and has the proper slope to maintain flow. Where water and sewer lines are in close proximity to each other, meet the installation requirements of TCEQ, section (e) Hydrostatic Testing. Furnish all labor, equipment, and materials necessary for the hydrostatic tests of new sections of water or sewer piping and valves added to the existing park system. Schedule each water or sewer system test with the TPWD inspector and Park Plant Operator(UPO). Each water or sewer system test must be witnessed by a TPWD inspector or his designated representative. Flush the new piping system with water to remove dirt, sand, etc. in preparation for testing and sterilization. Water for the hydrostatic testing will be provided by the park's existing water system on the park site. Route water from the existing system to each new section of piping through a backflow preventer temporarily installed on a tap off of the existing system. This backflow device will prevent contamination of the existing park water system from non-sterilized water present in the new sections of piping during the construction period. Perform a hydrostatic pressure test on each new section of piping before final connection of each new section of piping to the existing distribution piping. Do not perform final connection of each new section of piping until a hydrostatic pressure test is completed. Before the hydrostatic test and with water pressure applied to the part of the system to be tested, open and close each hose bib several times so that all air can be expelled from the pipeline before beginning the testing procedure. For each new section of piping, after the piping installation is completed and filled with water, and the trench partially backfilled leaving the joints exposed for examination, subject the new piping for two (2) hr. to a hydrostatic pressure test of 150% of the park's water system working pressure. Regardless of the park water system working pressure, the minimum test pressure for all tests on the new sections of piping must be 100 psi. Do not allow the test pressure to exceed the manufacturer's working pressure rating for any part installed in the new parts of the system. Examine the new piping sections for leakage and repair as necessary. Repeat the test until the results are satisfactory as determined by the continuous maintenance of test pressure on the piping for two (2) hr. with no drop in test pressure during the test period. No leaks will be allowed for solvent-cemented joints. Do not install vacuum breakers on the new hose bibs until the new sections of piping have been flushed and passed the hydrostatic test. Install new vacuum breakers before the sterilization of new sections of piping. Do not remove the break-off screw until the results of the water line sterilizations are accepted by the TPWD inspector. Only new piping installed for this project will be subjected to the 150% pressure test. Valve or cap off any existing piping so it will not be exposed to the test pressures. After the hydrostatic pressure testing is complete, cap off each new section of piping until it can be properly sterilized before connecting to the existing water system piping. Perform hydrostatic testing of the piping, fittings, and valves for the new valve on the distribution line in a similar manner to what is described above for the new sections of piping installed for the relocated campsite RV power outlets. Perform a hydrostatic test on the new sewer piping, fittings, and connections by completely filling the new gravity sewer line with water and providing approximately 10 of head pressure with a filled section of piping

7 at the high elevation end of the line. For the sewer system hydrostatic test all sewer system piping and fittings shall be installed except for the final connection to the lift station basin. The hydrostatic sewer piping test shall be conducted for a minimum of 4 hours and all fittings and connection points will be inspected for leakage. No leakage will be allowed for any fitting or connection point. If piping is limited to short runs of service line, at the discretion of the TPWD Inspector and Park UPO, a visual inspection of all newly installed pipe and fittings that are pressurized prior to backfill may be substituted for hydrostatic testing Sterilization of Lines. Coordinate sterilization and sampling with the Park UPO and in accordance with AWWA Standard C MEASUREMENT 5. PAYMENT 6226 Furnish all labor, equipment and materials necessary for the sterilization of new piping for the water system before connecting to the existing park water system and placing the new piping into service. Sterilize all lines and fittings by the application of a chlorinating agent. The chlorinating agent may be liquid chlorine, liquid chlorine/gas water mixture or a calcium hypochlorite solution. feed into the lines through a suitable solution feeding device or other approved method. Apply the chlorinating agent at or near the point from which the line is being filled and through a corporation stop or other approved connection inserted in the horizontal axis of the line. Controll the water used to fill the line so that it flows very slowly into the section being sterilized. Maintain the rate of application of the chlorinating agent in proportion to the rate of water entering the line so that the resulting chlorinated water solution in the piping system section being sterilized has at least 50 ppm of available chlorine. Retain th chlorinated water in the pipelines for a period of not less than 24 hr. At the end of the retention period, thoroughly flush all chlorinated water from the lines until the replacement water in the lines has a chlorine residual of not more than 0.4 ppm. Open and close all valves and all hose bibs on the lines being disinfected several times during the contact period to assure disinfection. Before installation, dose all parts and fittings being installed to repair a line, to tie-in a new section of piping, or to tie-in test equipment to the existing park water system with a chlorine solution that has a concentration of chlorine of at least 50 ppm. Water for the sterilization testing procedure will be provided by the park's water system. after all lines are sterilized and flushed as specified above, the Park UPO will collect samples of water from the water system main lines and submit to a Texas Department of Health (TDH) laboratory for bacteriological tests. Frequency and location of tests will be as directed. If the samples fail to meet the standards. The contractor must repeat the disinfection process as outlined above until the TDH tests show satisfactory results. Copies of the written test results from TDH for each water test sample will be retained by TPWD for the park records and the project file. This Item will be measured by each campsite. The work performed and materials furnished in accordance with this Item and measured as provided under Measurement will be paid for at the unit price bid for Adjust or Relocate Campsite Utilities. This price is full compensation for all materials, equipment and labor required for disconnecting and isolating the existing water, sewer and electrical services; relocating the service supports or pedestals; new service support foundations; trenching; backfilling holes; paying all fees, permits, and other costs; making arrangements with the utility company for all work and materials provided by the utility company; installing and connecting all components including poles, service supports, encasement pipes, foundations, anchor bolts, riprap, enclosures, switches, breakers, conduit (from the service equipment including the elbow below ground), fittings, conductors (from the service equipment including the elbow below ground), brackets, bolts, hangers, and hardware; and equipment, labor, tools, and incidentals

DIVISION 26 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL RELATED DOCUMENTS

DIVISION 26 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL RELATED DOCUMENTS PART 1 - GENERAL 01.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification sections, apply to work of this Section.

More information

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC).

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC). SECTION 16111 CONDUITS PART 1 - GENERAL 1.01 DESCRIPTION A. General: Provide conduits, complete, as shown, specified or required per Contract Documents. Principal items include: 1. Rigid aluminum conduit.

More information

SECTION POLYVINYL CHLORIDE (PVC) WATERLINE

SECTION POLYVINYL CHLORIDE (PVC) WATERLINE SECTION 02632 POLYVINYL CHLORIDE (PVC) WATERLINE PART 1 - GENERAL 1.01 SCOPE OF WORK A. Furnish all labor, materials, equipment, and incidentals required, and install polyvinyl chloride (PVC) waterline,

More information

(Condensed from National Electric Code)

(Condensed from National Electric Code) WIRING, SPECIFICATIONS, INSPECTION, AND METER INSTALLATION PROCEDURES FOR RESIDENTIAL CUSTOMERS SERVED BY SOUTHWEST ARKANSAS ELECTRIC COOPERATIVE CORPORATION Effective April 1, 1974 Revised February 3,

More information

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 1.1. REFERENCE STANDARDS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification

More information

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 41 UNDERGROUND ELECTRICAL CONSTRUCTION A. This section specifies the furnishing, installation, and connection of precast manholes and pullboxes with ducts

More information

2. A preconstruction meeting with the TWA s staff is required prior to initiating construction.

2. A preconstruction meeting with the TWA s staff is required prior to initiating construction. General: 1. Construct utilities in accordance to TWA approved plans and shop drawings. Any deviation from the approved plans shall be approved by the DEVELOPER S ENGINEER and TWA 2. A preconstruction meeting

More information

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets. ALLIANT ENERGY CENTER PAVILIONS Project No. 2013 027 SECTION 27 05 28 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Youngstown State University

Youngstown State University SECTION 260533 - RACEWAYS PART 1 - GENERAL SUMMARY A. This section includes raceways for electrical wiring. Types of raceways in this section include the following: 1. Flexible metal conduit 2. Liquid

More information

SUB WATER DEPARTMENT STANDARD CONSTRUCTION SPECIFICATIONS TABLE OF CONTENTS SECTION POLYETHYLENE PRESSURE PIPE

SUB WATER DEPARTMENT STANDARD CONSTRUCTION SPECIFICATIONS TABLE OF CONTENTS SECTION POLYETHYLENE PRESSURE PIPE SUB WATER DEPARTMENT STANDARD CONSTRUCTION SPECIFICATIONS TABLE OF CONTENTS SECTION 33 11 13.24 POLYETHYLENE PRESSURE PIPE PART 1 GENERAL... 2 1.1 Description... 2 1.2 Reference Specification... 2 1.3

More information

SPECIAL SPECIFICATION 6623 Multi-Duct Conduit System

SPECIAL SPECIFICATION 6623 Multi-Duct Conduit System 2004 Specifications Houston District SPECIAL SPECIFICATION 6623 Multi-Duct Conduit System 1. Description. Furnish and place a Multi-Duct Conduit (MDC) system that is suitable for installation in an outdoor

More information

San Antonio Water System Standard Specifications for Construction ITEM NO. 848 SANITARY SEWERS

San Antonio Water System Standard Specifications for Construction ITEM NO. 848 SANITARY SEWERS ITEM NO. 848 SANITARY SEWERS 848.1 DESCRIPTION: This item shall govern the furnishing, installation and jointing of sanitary sewer pipe of the size and type specified by the project's plans and specifications.

More information

SECTION 401 WATER PIPE AND FITTINGS 2.2 POLYVINYL CHLORIDE (PVC) PIPE AND FITTINGS

SECTION 401 WATER PIPE AND FITTINGS 2.2 POLYVINYL CHLORIDE (PVC) PIPE AND FITTINGS SECTION 401 PIPE AND FITTINGS PART 2 MATERIALS 2.2 POLYVINYL CHLORIDE (PVC) PIPE AND FITTINGS A. PVC Pressure Pipe sizes 4 inch through 12 inch: ANSI/AWWA C 900 1. DR18 B. PVC Pressure Pipe sizes 14 inch

More information

UNIVERSITY OF MISSOURI Hydronic Energy Distribution 2016 Q1

UNIVERSITY OF MISSOURI Hydronic Energy Distribution 2016 Q1 GENERAL: The scope of this document is to provide instruction for the installation and testing of chilled water piping installed for the University of Missouri. DESIGN GUIDELINES: 1. Materials 1.1. Pipe

More information

CONDUITS AND FITTINGS

CONDUITS AND FITTINGS CONDUIT AND FITTINGS Rigid Steel Conduit 3801 Rigid PVC Conduit 3803 HDPE Conduit 3803 Flexible Non Metallic Liquid Tight Conduit Type LFNC-B 3804 PVC Coated Urethane Lined Galvanized Rigid Steel Conduit

More information

CHAPTER 11 CONDUITS AND FITTINGS

CHAPTER 11 CONDUITS AND FITTINGS CONDUITS AND FITTINGS CHAPTER 11 CONDUITS AND FITTINGS The standards and requirements for conduits and fittings used for traffic control signal and lighting systems are presented in this chapter. 11.1

More information

SECTION CONDUITS AND BOXES

SECTION CONDUITS AND BOXES PART 1 GENERAL 1.01 DESCRIPTION A. Work covered by this section includes the furnishing and installation of conduits and boxes and the testing of the completed electrical systems 1.02 SUBMITTALS A. The

More information

Procurement Services SVC East Fowler Avenue Tampa, Florida (813)

Procurement Services SVC East Fowler Avenue Tampa, Florida (813) Procurement Services SVC 1073 4202 East Fowler Avenue Tampa, Florida 33620 (813) 974-2481 Web Address: https://www.usf.edu/business-finance/purchasing/public-bids/rfi.aspx October 12, 2018 Invitation to

More information

SECTION PLUMBING PIPING SYSTEMS

SECTION PLUMBING PIPING SYSTEMS SECTION 15300 PLUMBING PIPING SYSTEMS PART 1 - GENERAL 1.01 SPECIAL NOTICE A. Each contractor shall read all relevant documents, become familiar with the job, the scope of work, type of general construction,

More information

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph

More information

SPECIAL SPECIFICATION 6664 Level (3) Communications System

SPECIAL SPECIFICATION 6664 Level (3) Communications System 2004 Specifications CSJ 1200-05-014 SPECIAL SPECIFICATION 6664 Level (3) Communications System 1. Description. A. This Item will govern the installation of all facilities belonging to Level (3) Communications,

More information

Please check with your local inspection authority for any additional requirements before installation.

Please check with your local inspection authority for any additional requirements before installation. Specifications for Residential Underground Electric Service Installation This brochure addresses most typical residential underground service installations. Variances for the following specifications must

More information

SPECIAL SPECIFICATION 6658 Time Warner Communications System

SPECIAL SPECIFICATION 6658 Time Warner Communications System 2004 Specifications CSJ 1200-05-014 1. Description. SPECIAL SPECIFICATION 6658 Time Warner Communications System A. This Item will govern the installation of all facilities belonging to Time Warner Cable

More information

DIVISION 16. Electrical Specifications

DIVISION 16. Electrical Specifications DIVISION 16 Electrical Specifications 16.1 General - Provide all electrical materials and methods as shown on the Drawings, as specified herein, and as needed for a complete and proper installation, including

More information

SECTION A. Underwriters Laboratories, Inc., listed and NEC approved

SECTION A. Underwriters Laboratories, Inc., listed and NEC approved PART 1 GENERAL 1.01 DESCRIPTION A. Provide all raceways, fittings, and boxes of specified type required for complete project. Install all systems in raceways unless specifically noted otherwise. Provide

More information

CITY OF UNION, OREGON TECHNICAL SPECIFICATIONS SECTION 9 UNDERGROUND UTILITIES

CITY OF UNION, OREGON TECHNICAL SPECIFICATIONS SECTION 9 UNDERGROUND UTILITIES A. GENERAL 1. Scope. These specifications cover the installation of the utility systems and appurtenances for the electrical power, telephone, gas, and television as shown in the Drawings. The Work includes,

More information

SECTION SANITARY SEWERAGE PART 1 GENERAL 1.01 RELATED DOCUMENTS

SECTION SANITARY SEWERAGE PART 1 GENERAL 1.01 RELATED DOCUMENTS SECTION 02530 - SANITARY SEWERAGE PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

CITY OF FARGO SPECIFICATIONS SEWER AND WATER SERVICE CONNECTIONS

CITY OF FARGO SPECIFICATIONS SEWER AND WATER SERVICE CONNECTIONS SEWER AND WATER SERVICE CONNECTIONS PART 1 DESCRIPTION OF WORK The work to be done under this section of the Specifications and the accompanying plans consists of the furnishing of all labor, material,

More information

UNDERGROUND SERVICES SECONDARY

UNDERGROUND SERVICES SECONDARY Reference UNDERGROUND SERVICES SECONDARY Underground services secondary... U- 1 General requirements for underground service... U- 2 Name of parts for underground service... U- 3 Conduit layouts... U-

More information

SECTION GROUNDING

SECTION GROUNDING SECTION 16450 GROUNDING PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies general grounding and bonding requirements of electrical and telecommunication installations for personnel safety, equipment

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract apply to this Section. 1.2 SUMMARY A. This Section

More information

SECTION STORM DRAINAGE

SECTION STORM DRAINAGE SECTION 02720 STORM DRAINAGE PART 1 - GENERAL 1.01 WORK INCLUDED A. Trenching and other excavation. B. Ground water control. C. Pipe bedding. D. Installation of storm drains and appurtenances. E. Installation

More information

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11 Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11 Underground Residential Distribution (URD) Index General Discussion... 1-2 Description... 3-7 Drawings (Available

More information

SPECIAL SPECIFICATION 3504 Septic Tank System

SPECIAL SPECIFICATION 3504 Septic Tank System 1993 Specifications CSJ s 3136-01-126, etc. & 0683-01-070, etc. SPECIAL SPECIFICATION 3504 Septic Tank System 1. Description. This Item shall govern for all materials, equipment and labor necessary for

More information

SECTION ELECTRICAL SITE UTILITIES

SECTION ELECTRICAL SITE UTILITIES SECTION 16402 ELECTRICAL SITE UTILITIES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Electrical site utilities and coordination of requirements with the utility company and service specifications.

More information

A. Section Includes: Electrical site utilities and coordination of requirements with the utility company and service specifications.

A. Section Includes: Electrical site utilities and coordination of requirements with the utility company and service specifications. 16402 ELECTRICAL SITE UTILITIES ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 33 50 00. *************************************************************************************************************

More information

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE)

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE) SECTION 02623 HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE) PART 1 - GENERAL 1.1 SCOPE OF WORK A. Furnish all labor, materials, equipment and incidentals required and install high density

More information

SECTION CONDUITS AND BOXES PART 1- GENERAL. A. Work covered by this section includes the furnishing and installation of conduits and boxes.

SECTION CONDUITS AND BOXES PART 1- GENERAL. A. Work covered by this section includes the furnishing and installation of conduits and boxes. SECTION 16111 CONDUITS AND BOXES 1.01 DESCRIPTION PART 1- GENERAL A. Work covered by this section includes the furnishing and installation of conduits and boxes. 1.02 SUBMITTALS A. The Contractor shall

More information

SECTION RACEWAYS

SECTION RACEWAYS SECTION 16110 RACEWAYS PART 1 GENERAL 1.1 SYSTEM DESCRIPTION A. Provide a complete raceway system suitable for receiving wire and cable and continuous from outlet to outlet. System shall be complete with

More information

This section includes materials and installation of ductile-iron pipe and fittings for potable and recycled water systems.

This section includes materials and installation of ductile-iron pipe and fittings for potable and recycled water systems. NORTH MARIN WATER DISTRICT STANDARD SPECIFICATIONS SECTION 15056 DUCTILE-IRON PIPE AND FITTINGS PART 1 GENERAL 1.01 DESCRIPTION This section includes materials and installation of ductile-iron pipe and

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 8/1/17 Update sections Materials and Special Requirements 3 F. 2. 4 H. 2.; 10. & 11(added) 6/15/16 Updated division

More information

SECTION GRAVITY WASTEWATER LINES

SECTION GRAVITY WASTEWATER LINES SECTION GRAVITY WASTEWATER LINES 1. DESCRIPTION This specification shall govern all work required for furnishing, handling and installing gravity wastewater lines required to complete the project. 2. MATERIALS

More information

SECTION WATER DISTRIBUTION SYSTEM

SECTION WATER DISTRIBUTION SYSTEM Conditions of Use/ Responsibility of Data Montgomery County Public Schools Facilities Guide DIVISION 2 - SITE WORK These guideline specifications are to be used by the A/E as a base document in the development

More information

SECTION ELECTRICAL UTILITY SERVICES

SECTION ELECTRICAL UTILITY SERVICES SECTION 33 71 73 ELECTRICAL UTILITY SERVICES PART 1 GENERAL 1.1 REFERENCES A. American Association of State Highway Officials (AASHO): 1. Standard Specifications B. California Administrative Code (CAC):

More information

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS DAIMLERCHRYSLER MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS ISSUE DATE: 5/1/90 EFFECTIVE DATE: 2/4/92 REVIEW DATE:

More information

Ice Rink Renovation & New Clubhouse

Ice Rink Renovation & New Clubhouse SECTION 331213 - WATER SERVICE CONNECTIONS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe and fittings for domestic water service connections to buildings. 2. Corporation stop assembly. 3. Curb

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 16060 Grounding and Bonding This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or

More information

Design Standard Conduit for Electrical Systems

Design Standard Conduit for Electrical Systems Design Standard Purpose: This design standard has the purpose of creating a consistent application for the installation of conduits throughout the East Side Union High School District, therefore achieving

More information

SECTION C1 DUCTILE IRON PIPE AND FITTINGS GENERAL

SECTION C1 DUCTILE IRON PIPE AND FITTINGS GENERAL SECTION C1 DUCTILE IRON PIPE AND FITTINGS GENERAL This section covers the furnishing and installation of ductile iron water pipe, fittings, thrust restraint and pipe disinfection. Ductile Iron Pipe MATERIALS

More information

CONSTRUCTION STANDARDS SECTION CS 15 STREET LIGHTING

CONSTRUCTION STANDARDS SECTION CS 15 STREET LIGHTING CONSTRUCTION STANDARDS SECTION CS 15 STREET LIGHTING CS 15-0l SCOPE: Street Lighting improvements shall be constructed in conformance with Section 86, Signals, Lighting and Electrical Systems, of the CALTRANS

More information

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION SECTION 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 - GENERAL 1.1 SUMMARY A. This section supplements all sections in this division, including pipe, fittings, valves, and connections for sprinkler

More information

SPECIAL SPECIFICATION 6666 Charter Communications System

SPECIAL SPECIFICATION 6666 Charter Communications System 2004 Specifications CSJ 1200-05-014 SPECIAL SPECIFICATION 6666 Charter Communications System 1. Description. A. This Item will govern the installation of all facilities belonging to Charter Communications,

More information

SECTION 1101 TRAFFIC SIGNALS AND APPURTENANCES END OF SECTION

SECTION 1101 TRAFFIC SIGNALS AND APPURTENANCES END OF SECTION SECTION 1101 SIGNALS AND APPURTENANCES PART 1 GENERAL 1.4 SUBMITTALS E. Submit warranty for all supplied material and workmanship for a period of two years from final acceptance. The warranty must state

More information

SECTION ELECTRICAL CABLE. 1. Trench excavation, backfill, and compaction; Section

SECTION ELECTRICAL CABLE. 1. Trench excavation, backfill, and compaction; Section 02735-1 of 5 SECTION 02735 ELECTRICAL CABLE 02735.01 GENERAL A. Description Electrical cable installation shall include, but not necessarily be limited to, furnishing and placing electrical cable as shown

More information

SECTION POLYVINYL CHLORIDE (PVC) PRESSURE PIPE

SECTION POLYVINYL CHLORIDE (PVC) PRESSURE PIPE SECTION 02622 POLYVINYL CHLORIDE (PVC) PRESSURE PIPE PART 1 - GENERAL 1.1 SCOPE A. The work covered by this section includes furnishing all labor, equipment, and materials required to install and test

More information

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS SECTION 16711-27 05 28.33 PART 1 - GENERAL 1.01 SUMMARY A. This section includes Labor, materials and equipment necessary to complete the installation required for the items specified under this Section,

More information

SECTION OUTLET, PULL, AND JUNCTION BOXES

SECTION OUTLET, PULL, AND JUNCTION BOXES SECTION 16131 OUTLET, PULL, AND JUNCTION BOXES PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 09900 - Painting. 2. 16112 - Raceways and Conduits. 1.02 SYSTEM DESCRIPTION A. Performance Requirements:

More information

B. Provide a complete conduit system with associated couplings, connectors, and fittings.

B. Provide a complete conduit system with associated couplings, connectors, and fittings. SECTION 26 05 33 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 260500. B. Provide a complete conduit system with associated couplings, connectors, and fittings. 1.02 RELATED

More information

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 604 NOVEMBER 2004 CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

SECTION STORM UTILITY DRAINAGE PIPING PART 1 - GENERAL 1.1 SUMMARY 1.2 SUBMITTALS 1.3 PROJECT CONDITIONS

SECTION STORM UTILITY DRAINAGE PIPING PART 1 - GENERAL 1.1 SUMMARY 1.2 SUBMITTALS 1.3 PROJECT CONDITIONS SECTION 334100 - STORM UTILITY DRAINAGE PIPING PART 1 - GENERAL 1.1 SUMMARY Section Includes: 1. Pipe and fittings. 2. Drain Basin. 3. De-chlorination tablet feeder. 4. Non-pressure transition couplings.

More information

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING SECTION 16060 PART 1 GENERAL 1.01 DESCRIPTION A. Section includes requirements for an electrical grounding system, including electrodes, grounding rods, connectors, insulators, equipment grounding and

More information

SECTION 2100 WATER MAIN

SECTION 2100 WATER MAIN SECTION 2100 WATER MAIN WATER MAIN PART 1 GENERAL 1.01 Section Summary A. This section includes product and installation requirements for water main pipe, gate valves, hydrants, fittings, and miscellaneous

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. AFC Cable Systems, Inc. Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519.13 METAL CLAD CABLE-MC

More information

SECTION PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY

SECTION PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY SECTION 280528 - PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Metal conduits, tubing, and fittings. 2. Nonmetallic conduits, tubing, and fittings. 3.

More information

A. American Society for Testing and Materials (ASTM): Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft.

A. American Society for Testing and Materials (ASTM): Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft. SECTION 260000 ELECTRICAL PART 1- GENERAL 2.1 SUMMARY : Provide complete distribution systems for electrical power as shown on the drawings or required by other sections of these specifications. A. Work

More information

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL WARNING Before digging or trenching... Call 811 Indiana Underground Protection Service 1-800-382-5544 AVOID BURIED POWER CABLES 4901 East Park 30 Drive P.O.

More information

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section DUCTILE IRON PIPE AND FITTINGS

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section DUCTILE IRON PIPE AND FITTINGS Section 02501 PART 1 GENERAL 1.01 SUMMARY This Section includes ductile iron pipe and fittings for water lines, wastewater force mains, gravity sanitary sewers, and storm sewers. 1.02 MEASUREMENT AND PAYMENT

More information

Section 2: Underground

Section 2: Underground Section 2: Underground GENERAL INSTALLATION REQUIREMENTS FOR UNDERGROUND FACILITIES Underground electric service and meter location will be established by NHEC upon site visit. In some instances the type,

More information

***************************************************************************************************************

*************************************************************************************************************** 02732 SANITARY FORCE MAIN *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number 33 34 00. ***************************************************************************************************************

More information

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA The following standard specification is intended to be edited according to the specifics of the project. Brackets [ ] and areas shaded in gray [e.g. format] indicate requirements that are optional depending

More information

SECTION ELECTRICAL MATERIALS AND METHODS

SECTION ELECTRICAL MATERIALS AND METHODS SECTION 26 00 20 ELECTRICAL MATERIALS AND METHODS PART 1: GENERAL 1.01 WORK INCLUDED A. Furnish and install all conduit, conduit fittings and boxes to complete the installation of all electrically operated

More information

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR PART 1 - GENERAL Section 26 05 15 SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR 1.1 Cable shall be 15 kv, shielded, three conductor with ground, stranded copper, with continuously welded and corrugated

More information

PIPE AND FITTINGS. Submit product information sheet for joint restraint system to be used.

PIPE AND FITTINGS. Submit product information sheet for joint restraint system to be used. PIPE AND FITTINGS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Pipe B. Fittings C. Special Fittings D. Pipeline Accessories 1.02 DESCRIPTION OF WORK Construct water mains and building service pipes. 1.03

More information

Specifications Electrical Metallic Tubing (EMT)

Specifications Electrical Metallic Tubing (EMT) T& Fittings Specifications Electrical Metallic Tubing (EMT) Ref. CEC Rule 12-000 not exceeding 750 Volts Electrical Metallic Tubing (EMT) is similar to rigid steel conduit but is much lighter, weighing

More information

STREET LIGHTING GENERAL INFORMATION

STREET LIGHTING GENERAL INFORMATION SECTION 1102 STREET LIGHTING GENERAL INFORMATION These specifications are for street lighting that is to be dedicated to the public and maintained by the City of Meridian. Such installations require a

More information

SECTION DUCTILE IRON FITTINGS. A. This section includes materials, installation, and testing of ductile iron fittings 48 inches and smaller.

SECTION DUCTILE IRON FITTINGS. A. This section includes materials, installation, and testing of ductile iron fittings 48 inches and smaller. PART 1 - GENERAL 1.1 DESCRIPTION A. This section includes materials, installation, and testing of ductile iron fittings 48 inches and smaller. 1.2 RELATED WORK SPECIFIED ELSEWHERE A. Section 01300 Record

More information

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL). 16450 GROUNDING ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 26 An optional keynote to the

More information

YAKIMA COUNTY, WASHINGTON. Special Provisions For Water Main Construction

YAKIMA COUNTY, WASHINGTON. Special Provisions For Water Main Construction YAKIMA COUNTY, WASHINGTON Special Provisions For Water Main Construction The 2014 Standard Specifications for Road, Bridge, and Municipal Construction as prepared by the Washington State Department of

More information

SECTION WATER DISTRIBUTION

SECTION WATER DISTRIBUTION SECTION 33 10 00 WATER DISTRIBUTION PART 1 GENERAL 1.01 SUMMARY 1.02 CODES A. Section Includes: 1. Underground water service piping, watermains and appurtenances. A. All work shall comply with the most

More information

Diffused Aeration Piping Equipment

Diffused Aeration Piping Equipment 1.0 General 1.1. The specifications in this section include all components of the Diffused Aeration System with the exception of the individual diffuser units. Refer to additional specification sections

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519 METAL CLAD CABLE - MC-PLUS Neutral

More information

Effective June, Eaton-Durham Model # UTRS223ACH. Siemens, Model # SUAS877-PG. (or Landis & Gyr # UAS877-PG) Milbank. Model # U1980-O.

Effective June, Eaton-Durham Model # UTRS223ACH. Siemens, Model # SUAS877-PG. (or Landis & Gyr # UAS877-PG) Milbank. Model # U1980-O. Siemens, Model # SUAS877-PG (or Landis & Gyr # UAS877-PG) Eaton-Durham Model # UTRS223ACH Milbank Midwest Model # U980-O UTRS223AMEP These are some examples of the single meter sockets we require for underground

More information

Changes for the. TOHOPEKALIGA WATER AUTHORITY Standards, Specifications and Details

Changes for the. TOHOPEKALIGA WATER AUTHORITY Standards, Specifications and Details Changes for the 2017 TOHOPEKALIGA WATER AUTHORITY Standards, Specifications and Details The following changes are made to the existing standards and details to clarify or improve existing information.

More information

SECTION WASTEWATER FORCE MAINS

SECTION WASTEWATER FORCE MAINS SECTION 02732 WASTEWATER FORCE MAINS PART - GENERAL 1.01 GENERAL: A. This section includes the general requirements for design and installation of force main systems serving wastewater lift stations. B.

More information

A. This section is intended to provide design guidelines for Utility Direct Buried Piping and Conduit Systems.

A. This section is intended to provide design guidelines for Utility Direct Buried Piping and Conduit Systems. Date Description of Change Pages / Sections Modified ID 6/15/16 Entire document - mgl44 PART 1 - INTRODUCTION 1.1 PURPOSE A. This section is intended to provide design guidelines for Utility Direct Buried

More information

SECTION SANITARY SEWER SYSTEM

SECTION SANITARY SEWER SYSTEM SECTION 02530 SANITARY SEWER SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Section includes sanitary sewer system piping for collection of wastewater. B. Related Sections include but are not limited to: 1. Division

More information

CHINO VALLEY FIRE DISTRICT FIRE PROTECTION STANDARD

CHINO VALLEY FIRE DISTRICT FIRE PROTECTION STANDARD CHINO VALLEY FIRE DISTRICT FIRE PROTECTION STANDARD SPECIFICATIONS Establishing Minimum Standards for as Related To Fire Protection STANDARD # 103 REVISED 04/01/19 PAGES 7 SCOPE: These specifications shall

More information

SECTION FACILITY SANITARY SEWERS

SECTION FACILITY SANITARY SEWERS SECTION 22 13 13 FACILITY SANITARY SEWERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

GLENWOOD PLACE 2 MAR 2015

GLENWOOD PLACE 2 MAR 2015 PART 1 - GENERAL 1.01 SUMMARY: SECTION 16110 RACEWAYS A. Description: 1. Provide continuous conduit systems - beginning at the service point, to all distribution equipment and to every outlet and piece

More information

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6.2 OVERHEAD SERVICES Wiring of any premises for connection

More information

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL WARNING Before digging or trenching... Call Indiana Underground Protection Service 1-800-382-5544 AVOID BURIED POWER CABLES CONTENTS Page # 100-200 OR 400 AMP

More information

A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein.

A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein. 16470 PANELBOARDS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 16 An optional keynote to

More information

OVERHEAD SERVICES - SECONDARY

OVERHEAD SERVICES - SECONDARY OVERHEAD SERVICES - SECONDARY Contents - Overhead Services... O-1 General Requirements for Overhead Service... O-2 Names of Parts for Overhead Service... O-3 Service Attachment on an Unguyed Service Mast...

More information

OKLAHOMA DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR BRIDGE NAVIGATION LIGHTING

OKLAHOMA DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR BRIDGE NAVIGATION LIGHTING 809-1(a-e) 09 OKLAHOMA DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR BRIDGE NAVIGATION LIGHTING These special provisions amend and where in conflict, supersede applicable sections of the 2009 Standard

More information

University of Delaware

University of Delaware University Contact: Energy & Engineering Group (302) 831-1744 SECTION 22 14 00 _STORM WATER PIPING SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Storm water piping 2. Roof drains. 3. Area

More information

New Conduit Specification

New Conduit Specification New Conduit Specification Combines Portions of Sections 715, 783 & 992 into New Section 630. Coordinated Effort Between Traffic Operations, ITS, Lighting, Construction, and Industry New Conduit Specification

More information

SUPPLEMENTARY SECTION: STANDARD SPECIFICATIONS PAGE 1 STORMWATER MAINS & CULVERTS MAY 2018

SUPPLEMENTARY SECTION: STANDARD SPECIFICATIONS PAGE 1 STORMWATER MAINS & CULVERTS MAY 2018 STANDARD SPECIFICATIONS PAGE 1 STORMWATER MAINS & CULVERTS MAY 2018 PART 1 - GENERAL... 2 1.1 Work Included... 2 1.2 Related Sections... 2 1.3 Reference Standards... 2 1.4 Shop Drawings... 3 1.5 Certificates...

More information

DMS CONDUIT EFFECTIVE DATE: APRIL

DMS CONDUIT EFFECTIVE DATE: APRIL DMS - 11030 EFFECTIVE DATE: APRIL 2014 11030.1. Description. This Specification governs the materials, composition, quality, sampling, and testing of electrical conduit. 11030.2. Units of Measurements.

More information

SECTION UTILITY POLYETHYLENE CONTAINMENT PIPE SYSTEMS

SECTION UTILITY POLYETHYLENE CONTAINMENT PIPE SYSTEMS SECTION 02670 UTILITY POLYETHYLENE CONTAINMENT PIPE SYSTEMS PART 1 - GENERAL 1.01 WORK INCLUDED A. Trenching and other excavation. B. Ground water control. C. Pipe bedding. D. Installation of containment

More information