XAP Series Busduct Storage, Installation, and Maintenance

Size: px
Start display at page:

Download "XAP Series Busduct Storage, Installation, and Maintenance"

Transcription

1 Instruction Booklet IB Joint cover Tap-off Units Contents Description Introduction Receiving Unloading and Handling Storage Preparation and Inspection Installation Identification Joint Installation Joint Cover Installation Expansion Joint Installation End Cover Installation Settlement Joint Installation Horizontal Mounting Vertical Mounting Wall Penetrations Busduct Joint Clearances Tap-off Unit Installation Attentions for Installation Construction after Installation Steps for Energizing Maintenance Procedures Tap-off Unit Inspection Note Page

2 Instruction Booklet IB Introduction This publication contains instructions for the storage, handling, installation, and maintenance of the Eaton XAP busduct. Only those qualified and trained in accordance with established safety procedures should handle, install, and maintain the XAP busduct. Failure to follow danger, warning labels and established safety procedures could result in property damage, serious personal injury, or death. Preparation and Inspection Qualification and Training Only qualified professionals should install, operate and maintain the XAP busduct. Professionals should:. Fully understand the structure, installation, operation of XAP as well as the danger during operation; DANGER. Equipped with PPE such as safety helmet, working cloths. HAZARD OF ELECTRICAL SHOCK OR BURN. TURN THE POWER TO THE BUSDUCT OFF BEFORE INSTALLING, REMOVING, OR WORKING ON THIS EQUIPMENT. This publication does not cover all the details or variation in equipment and hardware nor cover every possible contingency regarding storage, handling, installation, and maintenance for XAP busduct systems. Eaton does not make representation or warranty, expressed or implied and does not assume responsibility for the accuracy or completeness of information contained herein. Receiving Once the material is received, inspect each box/crate for damage. Also check for concealed damage. Should any damage be found, notify the carrier immediately and file any claims as required by the carrier. If no visible or concealed damage is found, the product is ready for storage or installation. Do not remove the busduct from the original shipping container until ready for installation. This will help prevent damage to the busduct from occurring prior to installation.. Well trained about charging and test of the equipment; LIVE EQUIPMENT MAY LEAD TO PHYSICAL HARM. UNLESS OTHERWISE STATED, THE EQUIPMENT MUST BE POWEROFF BEFORE INSTALLING, INSPECTION AND MAINTAINS. DAMP BUSDUCT MUST BE TREATED PROPERLY. AND THE INSULATION RESISTANCE MUST BE TESTED POSITVELY BEFORE INSTALLATION. Instrument and tool The following instruments and tools will be used during installation:. Insulation tester 000V;. 8-0, 0- wrench, sleeve and torque wrench;. Straight and cross screwdriver; 4. Gradienter, tape and filament; Unloading and Handling Suitable device should be used to unload the busduct to avoid damage. Forklift is recommended to use. When lifting or hoisting the busduct, make sure the weight of the busduct is distributed and balanced. Use lifting devices that will not damage the busduct. Terminals of busduct cannot be used to support the weight of busduct. Storage The Eaton XAP busduct should be stored in a covered, clean, dry space which is climate controlled to prevent condensation. Do not allow the busduct to come in contact with corrosive fumes, liquids, salts, or forms of concrete. Storing the busduct outdoors should be avoided at all possible. However, if it cannot be avoided, it must be stored off the ground and securely covered to provide protection from dirt and moisture. Temporary electrical heating must be provided and evenly distributed beneath the cover to prevent condensation. At least watts per cubic foot is adequate for average environments. Failure to properly store and protect the busduct may cause damage and will void the warranty. Outdoor-rated busducts are not rated for outdoor applications until they are completely and properly installed. They should be treated as indoor busducts prior to complete installation. 5. Scaffold, hoist and herringbone ladder;. Drill, cutting machine, welding machine etc. Inspection Deliver all busduct sections and components to the installation location prior to unpacking, if possible. This will help prevent damage. Each crate/box is clearly marked with its contents and quantities. Unpack and inspect each piece for any signs of visible damage. Check the housing for dents or cracks caused by physical damage. Inspect the XAP busduct joints to ensure they are clean and that the insulators are not cracked or broken. Consult the factory regarding any physical damage. Perform an insulation resistance test on each busduct section by Megger testing at 000 volts, phase-to-phase, phase-to-neutral, and phase-to-ground 0M to ensure system integrity. Record the readings of each item and of each installed run. Provide these readings as part of the permanent maintenance records. Once inspected and tested, each busduct section is ready for installation.

3 Instruction Booklet IB Installation One set of construction drawings is sent with the initial shipment of each busduct order. This drawing package will contain the layout of each run, showing where each piece of the run is located, and other possible cut sheets and instructions. The installer should review these drawings prior to and during installation to ensure proper installation. Identification Each piece of the Eaton XAP busduct has a nameplate label as shown in Figure. This label identifies each piece and its ratings. It is recommended that each piece be installed sequentially, starting at the beginning point of the run. This would typically be the cable tap box, transformer, switchboard, or switchgear connection. Joint Installation When connecting pieces of the Eaton XAP busduct together, make certain that contact surfaces are clean and free from contaminants. Some section may have electrical lubricant on the contact surfaces, which was applied by the factory. This will aid in joint installation. Align the left end of one section to the right end of the adjoining section with the "N" label in alignment. Figure illustrates correct joint installation. PE L L L N Type <XAP> Compact Busway Figure. Joint Installation Standard IEC49-/- Ue = V In = A f =50/0Hz Ui = V Icw = ka IP5 Name of contract Contract No. Installation No. Manufacture Date Principal/Producers Eaton Electrical Equipment Co.,LTD. Torque Indication Bolt When the two sections have been properly joined together, the joint bolt may be tightened. This joint bolt is a special torque-indicating bolt with two bolt heads to ensure that the proper installation torque is achieved. Fall away instruction tags are provided between the upper and lower bolt heads. Torque should only be applied to the upper bolt head. When the proper torque is achieved, this bolt head will shear off, allowing the tag to fall to the floor. Production enterprise Chongqing Yiwan Electric Co., LTD. Figure. Nameplate Label Phasing and Orientation Labels Each piece of the Eaton XAP busduct has N labels as shown. The "N" label indicates phasing. From the N side of the busduct, the standard phasing is N-L-L-L-PE. Orange instruction Tag Figure 4. Figure 5. Figure 4. Torque Indicating Bolt as Shipped Figure 5. Torque Indication Bolt after Installation Any joint bolt that is improperly tightened will retain the highly visible tag and should be retightened. The lower bolt head remains intact for future maintenance. PE L L L N Figure. Phasing and Orientation Label The XAP busduct construction is not symmetrical. It is imperative for all sections of the busduct to be installed with all of the labels aligned and consistent throughout the run and per Eaton-supplied construction drawings. Failure to do so may result in damage to the busduct as well as property damage, physical harm or death. DANGER FAILURE TO INSTALL THE BUSDUCT CORRECTLY MAY RESULT IN DAMAGE TO THE BUSDUCT AS WELL AS PROPERTY DAMAGE, PHYSICAL HARM, OR DEATH.

4 Instruction Booklet IB Joint Cover Installation After the connectors are tightened, the joint covers may be installed in turn and tightened with bolts. In the case of four wire housing, please connect ground bolts and ground copper braiding to ground holes. End Cover Installation End Cover is the end of a busduct system. It is composed of insulating pieces and manufactured for field requirements. End Cover is placed onto the end of busduct with correct phase sequence. End cover Joint cover Figure. Joint Cover Installation Expansion Joint Installation This is a transition section to compensate for expansion and contraction due to long time operation of busduct. For detailed mounting position, refer to the installation drawing. The expansion joint has been tightened and assembled in factory. Check the connecting bolts of expansion joints. Make sure that the expansion position has not been damaged due to vibration during transportation. When connect the expansion joint to the straight busduct, please be noted to align the N phase line, to avoid incorrect phase sequence after connection. Expansion joints have the same installation sequence as for the straight busduct. For detailed installation clearance, refer to the installation clearance table and the installation drawing Notes: after completion of one line installation, it is necessary to loosen all M*5 bolts in the expansion joints to ensure expansion effect (see Figure 7). Figure 8. End Cover Installation Settlement Joint Installation Settlement joint is to compensate height difference caused by vertical offset at the joint of two workshops. For detailed mounting position, refer to the installation drawing. The settlement joint has been tightened and assembled in factory. Check the connecting bolts of settlement joints. Make sure that the settlement position has not been damaged due to vibration during transportation. When connect the expansion joint to the straight busduct, please be noted to align the N phase line, to avoid incorrect phase sequence after connection. Settlement joints have the same installation sequence as for the straight busduct. For detailed installation clearance, refer to the routing plan supplied upon delivery. Notes: after completion of one line installation, it is necessary to loosen the M8*0 bolts in the settlement joints to ensure settlement effect. -M*5 Hexagon bolts Figure 7. Expansion Joint Installation 8*0 screws Figure 9. Settlement Joint Installation

5 Instruction Booklet IB Horizontal Mounting For over-head mounting of the Eaton XAP busduct, all-thread drop rods must be provided by the installer and should not be spaced more than m apart.. The mounting clearance for straight busduct should not be longer than m. Detailed clearance requirements shall be requested during routing design according to field conditions and loading situations, and shall be specified in installation drawing. Wall Penetrations When an Eaton XAP busduct passes through a wall or vertical barrier, the opening should be at least 00 mm larger than the outside dimensions of the busduct. For individual and multiple runs of Eaton XAP busduct, thought must be given to horizontal and vertical clearances between runs, walls, and ceilings. Maximum clearance loading weight (kg Mounting clearance (m) XAP-C (kg/m) XAP-A (kg/m) Mounting supports shall be placed at both ends of the joint. Maximum clearance is no longer than m. No load shall be burdened at the joints.. Care should be given when locating drop rods in order to avoid placing hangers at joint and tap-off unit locations. Adequate ceiling clearance must be allowed for tap-off units. Busduct Busduct Vertical Mounting For mounting the busduct vertically, vertical spring hangers must be used. A vertical hanger must be used on every floor or a maximum of every ft. (4.9m). Intermediate hangers are required for floor heights exceeding ft. (4.9m) as shown in Fig. 0. Figure. Horizontal Wall Penetration Installation Maximum tolerance for busduct installation is 5mm per 0m. Busduct Busduct Figure. Vertical Floor Penetration Installation Figure 0. Vertical Busduct Mounting Support 4

6 Instruction Booklet IB Busduct Joint Clearances Busduct joint sections may not fall within walls or floors. Figures through 5 illustrate the minimum clearances required as measured from the center-line of the joint to the wall, floor and ceiling. Note: Busduct joints on outdoor rated busduct should have a minimum of 0 in. (54 mm) clearance on either side of walls. Tap-off Unit Installation Phase sequence shall be made according to field application requirements and construction drawings. Remove the bolts on the busduct socket cover and open the socket protection cover. (See Figure ). Open the tap-off unit door. Open Lock Anchor A and B. Then, aim at the slot in the socket, and insert in the unit smoothly until the unit bottom is closely contacted with the cover (PE pin shall contact the housing first to ensure safe grounding). Move the two lock anchors of A and B inwards to lock up busduct cover (Figure 9). When Lock Anchor A and B are in place, close the unit door and tighten the bolts. Note: When Lock Anchor A and B are in place, it means they are vertical to the cover plate and in parallel to the side of the tap-off unit. Figure. Minimum Outdoor Joint Clearances Note: Busduct joints on Indoor rated busducts should have a minimum of 8 in. (0. mm) clearance on either side of walls. Figure. Socket Lock Anchor A Lock Anchor B Figure 4. Minimum Indoor Joint Clearances Note: Busduct joints on vertically mounted busduct should have a minimum of 8 in. (0. mm) clearance before ceilings and a minimum of in. (40.4 mm) clearance above floors or curbs if used. Figure 7. Tap-off Unit Installation. After the Tap-off unit is installed onto the busduct, fasten the cable to its support in the case that the unit is connected to devices with cable, to avoid movement.. Tap-off unit shall not be burdened with load directly. Loads at the rear end shall be fastened onto the busduct or other fixed positions in accordance with regulations.. When not plugging in busduct, socket protection cover shall not be opened. Otherwise, it will influence the protection degree of busduct system. WHEN UNPLUGGING TAP-OFF UNITS, DISCONNECT LOADS. BEFORE BUSDUCT SYSTEM POWERS ON, LEAD WIRES OF ALL TAP-OFF UNITS SHALL BE CONNECTED TO ELECTRICAL DEVICES AND DISCONNECTED OR PROTECTED. CABLES SHALL NOT BE EXPOSED. Figure 5. Minimum Floor/Ceiling Joint Clearances. 5

7 Instruction Booklet IB Attentions for Installation. Surface of busduct terminals and joint units must be kept clean during installation;. Busducts must be adjusted and kept in the same line before fastening the bolts of joint units. Tolerance of assembly in horizon and vertical direction are 5mm per 0m;. Socket protection cover shall not be opened during installation; 4. Equipment should be power off and grounded safely when connecting the busducts to equipment. Construction after Installation. Complete the decoration work;. Protective grid, rail and fire protection isolation device should be completed;. Isolation for all living parts should be completed; 4. No construction impacts installed busducts should be carried out; 5. Equipment for construction should be removed and the place should be cleaned. Steps for Energizing. The entire busduct systems should be tested by Megger at 000V and insulation resistance should be higher than 0.5 MΩ;. Inspect the tightness of each joint unit to avoid any loosen bolt;. Make sure all tap-off units are in the open position; 4. Make sure the phase sequence of busducts is the same as incoming system; 5. Busducts system should not be loaded before energizing;. Bustucts system should be energized without load for 4 hours before carrying out a full load operation. Maintenance Procedures A preventative maintenance schedule should be established in order to achieve the best possible service from your Eaton XAP busduct. It is recommended that an annual maintenance check and necessary procedures be conducted at a minimum. Busducts subjected to severe operating conditions may require more frequent maintenance. It is recommended that a permanent maintenance record be kept recording the dates of service, work performed and any measured data. DANGER HAZARD OF ELECTRICAL SHOCK OR BURN. TURN THE POWER TO THE BUSDUCT OFF BEFORE INSTALLING, REMOVING, OR WORKING ON THIS EQUIPMENT. Preventative Measures Care should be taken to protect the busduct from contaminants. For in-door applications, inspect the busduct routing area looking for possible moisture points from roof leaks, pipe leaks, dripping condensation from pipes and HVAC equipment, and exhaust fans blowing dust and debris onto the busduct. The busducts should be protected from these hazards. All damaged equipment should be replaced. All equipment subject to moisture intrusion should be replaced. Busduct Inspection. Check the voltage of incoming terminals to make sure the busduct system is de-energized;. Clean the busduct removing accumulated dust, dirt, and other debris. Do not use water, liquid detergent, or chemicals to clean the busduct;. Perform a visual inspection on the busduct looking for stress or damage and moisture intrusion; 4. Inspect the joint unit bolts for tightness; 5. Check the insulation resistance and keep the record;. Perform an infra-red thermal scan on all electrical connections, joint connections, and busduct enclosures while the busduct is fully energized and operating under full load conditions. If readings change with time, further inspection and corrections may be required. If damaged and/or over heating has been found, it is recommended the following procedures be performed. FOR THE FOLLOWING PROCEDURES, THE BUSDUCT MUST BE SHUT OFF AND DE-ENERGIZED. FAILURE TO FOLLOW SAFETY PROCEDURES MAY CAUSE PROPERTY DAMAGE, SERIOUS PERSONAL INJURY AND DEATH.. After the busduct has been de-energized, remove the joint covers and visually inspect the joints looking for gaps in the contact surface areas, cracks in the insulators, and contaminants or corrosion;. Clean, replace damaged parts, and re-torque (70± N m) torque as required;. Perform an insulation resistance test prior to re-energizing; 4. If moisture intrusion be found, remove and replace all affected pieces. ONLY THOSE TRAINED AND QUALIFIED IN RECOGNIZED SAFETY PRACTICES SHOULD PERFORM MAINTENANCE ON THE BUSDUCT.

8 Instruction Booklet IB Tap-off Unit Inspection When inspecting and performing maintenance on tap-off units, ensure the breaker is in the open position and that the power to the busduct is turned off. DANGER HAZARD OF ELECTRICAL SHOCK OR BURN. TURN THE POWER TO THE BUSDUCT OFF BEFORE INSTALLING, REMOVING, OR WORKING ON THIS EQUIPMENT. RECOGNIZED SAFETY PROCEDURES MUST BE FOLLOWED PRIOR TO ANY WORK OR MAINTENANCE BEING PERFORMED.. Make sure the breaker is in the open position;. Turn off power to the busduct;. Using a multi-function meter, open the tap-off unit door and check to ensure there is no voltage present on the line side of the unit; 4. For fusible units, check the fuse clip contact pressure and contact means. If there are any sign of over-heating, replace fuse clips; 5. Look for any signs of deterioration of insulating materials and protective barriers;. Check the operation of all mechanical components. 7. Check the mechanisms of all electrical and mechanical interlocks and padlocking means; 8. Check for missing or broken parts, rusting, corrosion, dirt, and excessive wear; 9. Check the line and load connections to ensure proper torque. 0. Clean off any arc spatter or soot deposits;. Replace any damaged parts;. Operate each switch or circuit breaker several times to ensure proper working order. Note These maintenance instructions and procedures do not represent an exhaustive list of maintenance steps required to maintain safe operation of the busduct and tap-off units under all applications. Specific applications may require additional steps and procedures. For additional information or assistance with issues not covered sufficiently in this publication, contact the local Eaton sales office. 7

9 Eaton is a power management company with 0 sales of $9.7 billion. We provide energy-efficient solutions that help our customers effectively manage electrical, hydraulic and mechanical power more efficiently, safely and sustainably. Eaton is dedicated to improving the quality of life and the environment through the use of power management technologies and services. Eaton has approximately 95,000 employees and sells products to customers in more than 75 countries. For more information, visit Electrical Sector Asia Pacific No., Lane 80, Linhong Road, Changning District, Shanghai 07 Eaton Corporation All Rights Reserved Printed in Singapore June 07 Eaton is a registered trademark of Eaton Corporation. All trademarks are property of their respective owners.

SECTION ENCLOSED BUS ASSEMBLIES

SECTION ENCLOSED BUS ASSEMBLIES SECTION 262500 ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION ENCLOSED BUS ASSEMBLIES

SECTION ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

SECTION BUSWAYS

SECTION BUSWAYS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 25 11 BUSWAYS SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable to the section and

More information

SECTION to 5000 AMPERE PLUG-IN AND FEEDER BUSWAYS - SPECTRA. A. Low-Voltage Plug-in Busway to 5000 ampere, 600 VAC

SECTION to 5000 AMPERE PLUG-IN AND FEEDER BUSWAYS - SPECTRA. A. Low-Voltage Plug-in Busway to 5000 ampere, 600 VAC PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Low-Voltage Plug-in Busway - 225 to 5000 ampere, 600 VAC 1.02 RELATED

More information

NEUTRAL GROUNDING TRANSFORMERS INSTALLATION AND MAINTENANCE INSTRUCTIONS

NEUTRAL GROUNDING TRANSFORMERS INSTALLATION AND MAINTENANCE INSTRUCTIONS 1 Table of Contents SECTION 1 Unpacking... 3 1.1 Shipping... 3 1.2 Receiving... 3 SECTION 2 Installation... 3 SECTION 3 Inspection... 4 SECTION 4 Connection... 4 4.1 Neutral Lead... 5 4.2 Ground Lead...

More information

Ground Fault Protection. Medium Voltage Artificial Neutrals

Ground Fault Protection. Medium Voltage Artificial Neutrals Ground Fault Protection Medium Voltage Artificial Neutrals Installation and Maintenance Instruction Manual 7615 Kimbel Street, Mississauga, Ontario Canada L5S 1A8 Tel: (905)673-1553 Fax: (905)673-8472

More information

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466 BUSWAY LOW VOLTAGE (POW-R-WAY III) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein

More information

A. Section includes busway and fittings including plug-in units.

A. Section includes busway and fittings including plug-in units. SECTION 26 25 00 ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes busway and fittings including plug-in units. 1.2 REFERENCES A. Institute of Electrical and Electronics Engineers:

More information

Instruction Manual. Ventilated Dry-Type Transformers. 600 Volts & Below

Instruction Manual. Ventilated Dry-Type Transformers. 600 Volts & Below Instruction Manual Ventilated Dry-Type Transformers 600 Volts & Below Instructions for the Safe Handling, Installation, Operation and Maintenance of Ventilated Dry-Type Transformers Table of Contents Paragraph

More information

Low Voltage Switchgear Construction Checklist (under 500 kva)

Low Voltage Switchgear Construction Checklist (under 500 kva) Low Voltage Switchgear Checklist (under 500 kva) Project: Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

Unit Substation Transformer Construction Checklist (under 500 kva)

Unit Substation Transformer Construction Checklist (under 500 kva) Unit Substation Transformer Checklist (under 500 kva) Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

Instructions for Installation of Metal Clad Switchgear 38 kv, 150 BIL Outdoor Housings

Instructions for Installation of Metal Clad Switchgear 38 kv, 150 BIL Outdoor Housings Instruction Booklet IB022005EN Instructions for Installation of Metal Clad Switchgear 8 kv, 150 BIL Outdoor Housings Contents Description Page Purpose.... 2 Recommended Safety Practices.... 2 Section 1:

More information

SIEMENS. Instructions. Outdoor Metal Clad Switchgear. Installation Assembly OGM&SGM SG kV and 15kV. www. ElectricalPartManuals.

SIEMENS. Instructions. Outdoor Metal Clad Switchgear. Installation Assembly OGM&SGM SG kV and 15kV. www. ElectricalPartManuals. SIEMENS Outdoor Metal Clad Switchgear 5kV and 15kV Instructions Installation Assembly OGM&SGM SG 3258-00 THIS EQUIPMENT CONTAINS HAZARDOUS VOLTAGES. SEVERE PERSONAL INJURY OR PROPERTY DAMAGE CAN RESULT

More information

www.eaton.eu\busbars Power Xpert XP2 Aluminium Eaton Power Xpert XP2 is a 1000 Volt totally encased, non-ventilated, low impedance sandwich construction. The range is available from 800A - 5000A with multiple

More information

FIELD TEST AND OPERATIONAL CHECK SECTION A. Refer to Section 16010, Electrical General Requirements.

FIELD TEST AND OPERATIONAL CHECK SECTION A. Refer to Section 16010, Electrical General Requirements. FIELD TEST AND OPERATIONAL CHECK SECTION 16080 PART 1 GENERAL 1.1 GENERAL REQUIREMENTS A. Refer to Section 16010, Electrical General Requirements. 1.2 WORK INCLUDED A. General Scope: 1. The Contractor

More information

POWER PINNER BENCH HAND WELDER 7250 OPERATOR S MANUAL

POWER PINNER BENCH HAND WELDER 7250 OPERATOR S MANUAL POWER PINNER BENCH HAND WELDER 7250 OPERATOR S MANUAL Copyright: November 20, 2018 Revised: Serial No. Gripnail Corporation An Employee Owned Company 97 Dexter Road East Providence, Rhode Island 02914-2045

More information

Festoon Manual Heavy Duty C-Track

Festoon Manual Heavy Duty C-Track Festoon Manual Heavy Duty C-Track 966300.3 Heavy Duty C-Track Manual CONDUCTIX INCORPORATED The technical data and images which appear in this manual are for informational purposes only. NO WARRANTIES,

More information

NEMA Standards Publication BU General Instructions for Handling, Installation, Operation, and Maintenance of Busway Rated 600 Volts or Less

NEMA Standards Publication BU General Instructions for Handling, Installation, Operation, and Maintenance of Busway Rated 600 Volts or Less NEMA Standards Publication BU 1.1-2005 General Instructions for Handling, Installation, Operation, and Maintenance of Busway Rated 600 Volts or Less Published by: National Electrical Manufacturers Association

More information

Houston First Corporation Package 1 SECTION MEDIUM VOLTAGE FUSED SWITCH INTERRUPTER

Houston First Corporation Package 1 SECTION MEDIUM VOLTAGE FUSED SWITCH INTERRUPTER PART 1 - GENERAL 1.1 SUMMARY SECTION 26 13 16 MEDIUM VOLTAGE FUSED SWITCH INTERRUPTER A. The scope of this section includes providing and assembling materials and equipment for the dead-front, medium voltage

More information

Model: 770 Light Vehicle Scale Size: 8 x30 x5 Size: 10 x30 x5 Capacity: 40K CLC: 20K Capacity: 60K CLC:30K Installation, Set-Up and Operation Manual

Model: 770 Light Vehicle Scale Size: 8 x30 x5 Size: 10 x30 x5 Capacity: 40K CLC: 20K Capacity: 60K CLC:30K Installation, Set-Up and Operation Manual SCALE WORKS, INC. Model: 770 Light Vehicle Scale Size: 8 x30 x5 Size: 10 x30 x5 Capacity: 40K CLC: 20K Capacity: 60K CLC:30K Installation, Set-Up and Operation Manual Cambridge Scale Works, Inc. P.O. Box

More information

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

B. Provide liquid-filled secondary substation transformers as indicated on drawings. SECTION 26 12 13 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 26 05 00. B. Provide liquid-filled secondary substation transformers as indicated on drawings. 1.02 RELATED

More information

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS DAIMLERCHRYSLER MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS ISSUE DATE: 5/1/90 EFFECTIVE DATE: 2/4/92 REVIEW DATE:

More information

A. This Section includes steel cable trays and accessories.

A. This Section includes steel cable trays and accessories. SECTION 26 05 36 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION FIELD PANELS

SECTION FIELD PANELS Stanford University Facilities Design Guidelines SECTION 25 14 23 FIELD PANELS PART 1 - GENERAL 1.1 SUMMARY A. This section includes control panel and enclosure requirements for building control systems.

More information

SECTION MOTOR CONTROL CENTER

SECTION MOTOR CONTROL CENTER SECTION 16445 MOTOR CONTROL CENTER PART 1 GENERAL 1.01 DESCRIPTION A. This section covers the contract item Motor Control Center (MCC). The contract item includes demolition and removal of existing MCC;

More information

Conergy SolarFamulus II

Conergy SolarFamulus II Conergy SolarFamulus II Installation manual www.conergy.com Table of Contents Table of Contents SolarFamulus II for universal use on flat roofs 1 Introduction 1 1.1 Short description 1 1.2 Intended use

More information

Installation and Operation Manual

Installation and Operation Manual Installation and Operation Manual Maintenance Bypass Panel Model: SU2030KMBP Tripp Lite follows a policy of continuous improvement. Product specifications are subject to change without notice. 1111 West

More information

GROUND MOUNT INSTALLATION MANUAL

GROUND MOUNT INSTALLATION MANUAL GROUND MOUNT INSTALLATION MANUAL Contents DISCLAIMER 1 CHECKLIST 2 1. ERECT BASe 3 2. CONNECT PIPES 3 3. PLACE RAILS 4 4. SECURE LUGS 4 5. CLAMP MODULES 5 DIAGONAL BRACES (OPTIONAL) 6 UNDER CLAMPS (OPTIONAL)

More information

A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein.

A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein. 16470 PANELBOARDS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 16 An optional keynote to

More information

Installation, Operating and Maintenance Instructions Incognito Series Air Curtain

Installation, Operating and Maintenance Instructions Incognito Series Air Curtain Installation, Operating and Maintenance Instructions Incognito Series Air Curtain Models: INC10036, INC10042, INC10048, INC10064, INC10072, INC10084, INC10096, INC10108, INC10120, INC10144. READ THIS OWNER

More information

OWNER S MANUAL SERIES MDS-96-BK, SM, DR

OWNER S MANUAL SERIES MDS-96-BK, SM, DR SERIES MDS-96-BK, SM, DR OWNER S MANUAL Introduction... 1 Bill of Materials... 2 Assembly Instructions. 3 Warranty....12 IMPORTANT NOTES, WARNINGS AND SAFETY INSTRUCTIONS Ensure that all employees understand

More information

Installation. Smart-UPS VT in Parallel kva 380/400/415 V 208/220 V 200/208 V

Installation. Smart-UPS VT in Parallel kva 380/400/415 V 208/220 V 200/208 V Installation Smart-UPS VT in Parallel 10-40 kva 380/400/415 V 208/220 V 200/208 V Contents Safety... 1 IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS.............................. 1 Prepare for

More information

DOOR SHIELD. Owner s/user s Manual

DOOR SHIELD. Owner s/user s Manual DOOR SHIELD Owner s/user s Manual ALLIED SOLUTIONS Division of Systems, Inc. W194 N11481 McCormick Drive Germantown, WI 53022 800.643.5424 fax: 262.255.5917 www.docksystemsinc.com techservices@docksystemsinc.com

More information

Calibrate Accessory Actuators Instructions

Calibrate Accessory Actuators Instructions Instruction Manual Table of Contents Conditions of Sales and Product Warranty 3 Copyright Notice & Disclaimer 4 1.0 Technical Specifications 5 1.1 Features 6 2.0 Description 7 2.1 Components 8 3.0 Receiving

More information

WL Switchgear. Instruction and Installation Guide. 11-C Rev. 4. usa.siemens.com/switchgear

WL Switchgear. Instruction and Installation Guide. 11-C Rev. 4. usa.siemens.com/switchgear WL Switchgear Instruction and Installation Guide 11-C-9100-01 Rev. 4 usa.siemens.com/switchgear Hazardous voltage. Will cause death of serious injury. DANGER Keep out. Qualified personnel only. Disconnect

More information

Car and Counterweight Frames

Car and Counterweight Frames Car and Counterweight Frames CAR FRAME (SLING) AND PLATFORM COUNTERWEIGHT FRAME Every attempt has been made to ensure that this documentation is as accurate and up-to-date as possible. However, Vertical

More information

NEC 2017 Code Changes Chapter 1 - General

NEC 2017 Code Changes Chapter 1 - General NEC 2017 Code Changes Chapter 1 - General Changes from the 2014 code are highlighted in yellow. ARTICLE 110 - Requirements for Electrical Installations Part I. General 110.1 Scope. This article covers

More information

Essex County College - West Essex Campus Addition And Renovations dlb # / SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

Essex County College - West Essex Campus Addition And Renovations dlb # / SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

PD6770 VANTAGEVIEW LOOP-POWERED PROCESS METER

PD6770 VANTAGEVIEW LOOP-POWERED PROCESS METER PD6770 VANTAGEVIEW LOOP-POWERED PROCESS METER 4-20 ma input 1 V drop (4 V with Backlight) 3½ Digits LCD, 1" High Loop-Powered Backlight Option HART Protocol Transparent Plastic NEMA 4X, IP65 Enclosure

More information

Operate Manual. DA-1600i Stud Welding Machine. DA-2000i Stud Welding Machine. DA-2500i Stud Welding Machine

Operate Manual. DA-1600i Stud Welding Machine. DA-2000i Stud Welding Machine. DA-2500i Stud Welding Machine DA-1600i Stud Welding Machine DA-2000i Stud Welding Machine DA-2500i Stud Welding Machine Operate Manual KENT STUD WELDING CO., LTD 1 Content 1. Preface------------------------------------------------------------------------------

More information

WESTERN CONNECTICUT STATE UNIVERSITY ELECTRICAL SAFETY PROCEDURE S-109

WESTERN CONNECTICUT STATE UNIVERSITY ELECTRICAL SAFETY PROCEDURE S-109 WESTERN CONNECTICUT STATE UNIVERSITY ELECTRICAL SAFETY PROCEDURE S-109 Draft Issued 12/10/97 Revised 2/98, 7/09, 10/14 Please direct any questions or comments about the applicability of this document to

More information

DEVICES AND LUMINAIRES

DEVICES AND LUMINAIRES CHAPTER 40 DEVICES AND LUMINAIRES SECTION E4001 SWITCHES E4001.1 Rating and application of snap switches. General-use snap switches shall be used within their ratings and shall control only the following

More information

Glide-Line Standard Lift Locate Unit (SLLU)

Glide-Line Standard Lift Locate Unit (SLLU) V1.0 Glide-Line Standard Lift Locate Unit (SLLU) Installation & Maintenance Manual Easy Flexible Precise Fast i V1.0 Manual Information Throughout this manual are the following information blocks indicated

More information

OWNER S MANUAL SERIES MDS-96-BK, SM, DR

OWNER S MANUAL SERIES MDS-96-BK, SM, DR VESTIL MANUFACTURING CORP. 2999 N. Wayne St., Angola, IN 46703 Ph: 260-665-7586 Fax: 260-665-1339 E-mail: sales@vestil.com Website: www.vestil.com SERIES MDS-96-BK, SM, DR OWNER S MANUAL Introduction...

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 16060 Grounding and Bonding This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or

More information

FORM HEADWALL. FORM HEADWALL (floating) (floating) Installation Manual

FORM HEADWALL. FORM HEADWALL (floating) (floating) Installation Manual FORM HEADWALL (floating) Installation Manual FORM HEADWALL (floating) OVERVIEW The Form is a UL-listed configurable headwall system. This system includes multiple horizontal equipment channels integrated

More information

MS Training Manual. Storage, installation and maintenance for MS busbar systems

MS Training Manual. Storage, installation and maintenance for MS busbar systems Storage, installation and maintenance for MS busbar systems 1 INDEX STORAGE INSTRUCTIONS... 4 HANDLING... 4 GOOD RECEPTION... 5 NOTIFICATIONS... 5 STORAGE... 6 INSTALLATION INSTRUCTIONS... 7 STRAIGHT LENGHTS

More information

ENGLISH Compact Half Coupler 50 mm, SWL: 50 kg

ENGLISH Compact Half Coupler 50 mm, SWL: 50 kg MANUAL ENGLISH Compact Half Coupler 50 mm, SWL: 50 kg V3 Highlite International B.V. Vestastraat 2 6468 EX Kerkrade the Netherlands Table of contents Warning... 2 Safety Instructions... 2 Operating Determinations...

More information

AP5K-C Precision AC Double-Pulse Spot Welding Machine User s Manual Shenzhen Will-Best Electronics Co., Ltd

AP5K-C Precision AC Double-Pulse Spot Welding Machine User s Manual Shenzhen Will-Best Electronics Co., Ltd AP5K-C Precision AC Double-Pulse Spot Welding Machine User s Manual Shenzhen Will-Best Electronics Co., Ltd 1 Content 1. Introduction...3 1.1 Functions...3 1.2 Units of AP5K-C...4 2. The Initial Installation

More information

Bulk Bag Unloader Installation, Operation and Maintenance Manual

Bulk Bag Unloader Installation, Operation and Maintenance Manual Web-Tech Australia Pty Ltd Bulk Bag Unloader Installation, Operation and Maintenance Manual Web-Tech Australia Pty Ltd Manufacturers & Suppliers of Weighing, Level & Batching Equipment 11 Electronics Street

More information

METALWorkS. RH200 Custom Hook-on Panels. General Installation Instructions. Ceiling 1.0 GENERAL Site Conditions Product Description

METALWorkS. RH200 Custom Hook-on Panels. General Installation Instructions. Ceiling 1.0 GENERAL Site Conditions Product Description Ceiling Systems Between us, ideas become reality METALWorkS General Installation Instructions RH200 Custom Hook-on Panels 1.0 GENERAL 1.1. Product Description RH200 system is a downward accessible, metal

More information

LOW PROFILE FLOOR SCALE

LOW PROFILE FLOOR SCALE π LOW PROFILE FLOOR SCALE 1-800-295-5510 uline.com SITE SELECTION Select a site for your new floor scale where it is least likely to be damaged by fork trucks and other material handling devices. Floor

More information

Glide-Line Heavy Duty Lift Locate Unit (HLLU)

Glide-Line Heavy Duty Lift Locate Unit (HLLU) V1.0 Glide-Line Heavy Duty Lift Locate Unit (HLLU) Installation & Maintenance Manual Easy Flexible Precise Fast i V1.0 Manual Information Throughout this manual are the following information blocks indicated

More information

INSTALLATION INSTRUCTIONS AS 2.1 CORRUGATED ETERNIT ROOF

INSTALLATION INSTRUCTIONS AS 2.1 CORRUGATED ETERNIT ROOF INSTALLATION INSTRUCTIONS AS 2.1 CORRUGATED ETERNIT ROOF ALUMERO GROUP YOUR BIG ADVANTAGE! + in-house consulting and design office + competent and reliable staff + aluminium mounting profiles and custom-drawn

More information

DJ Switch 10F V2 ORDERCODE 50365

DJ Switch 10F V2 ORDERCODE 50365 DJ Switch 10F V2 ORDERCODE 5035 Congratulations! You have bought a great, innovative product from Showtec. The Showtec DJ Switch brings excitement to any venue. Whether you want simple plug-&-play action

More information

EXIRA EXPOSED PIPE SHOWER INSTALLATION

EXIRA EXPOSED PIPE SHOWER INSTALLATION SKU(s): 923583 EXIRA EXPOSED PIPE SHOWER INSTALLATION BEFORE YOU BEGIN We recommend consulting a professional if you are unfamiliar with installing plumbing fixtures. Signature Hardware accepts no liability

More information

Maintenance Bypass Breaker Cabinet Series Configuration 2. Installation and Operation Manual

Maintenance Bypass Breaker Cabinet Series Configuration 2. Installation and Operation Manual Maintenance Bypass Breaker Cabinet 90881 Series Configuration 2 Installation and Operation Manual 03/13/2012 2 755-00084-C2 R03 Copyright 2012 C&C Power, Inc. All rights reserved. C&C Power, Inc. 395 Mission

More information

DEVICES AND LUMINAIRES

DEVICES AND LUMINAIRES CHAPTER 39 DEVICES AND LUMINAIRES SECTION E3901 SWITCHES E3901.1 Rating and application of snap switches [404.14(A)]. General-use snap switches shall be used within their ratings and shall control only

More information

TRS100 Rapid Assay System Pre-Installation Guide

TRS100 Rapid Assay System Pre-Installation Guide TRS100 Rapid Assay System Pre-Installation Guide NOTICE: This document contains references to Cobalt or Cobalt Light Systems. Please note that Cobalt Light Systems was purchased by Agilent in July 2017.

More information

V 2.0 ASSEMBLY GUIDE. TS Platform Scale Series 2

V 2.0 ASSEMBLY GUIDE. TS Platform Scale Series 2 V 2.0 ASSEMBLY GUIDE Series 2 TABLE OF CONTENTS OVERVIEW General Specifications...1 Cautions and Disclaimers...1 Contents of Kit...1 Tools Required For Assembly...2 Time Required to Assemble...2 ASSEMBLING

More information

XPM 2. Reflow Soldering / Curing Systems. Site Preparation & Installation

XPM 2. Reflow Soldering / Curing Systems. Site Preparation & Installation XPM 2 Reflow Soldering / Curing Systems Site Preparation & Installation Site Preparation & Installation 1 Revision Date: May 2004 Table of Contents SITE PREPARATION CHECKLIST 3 ROOM PLANNING 4 Oven Clearances

More information

PACKAGED SYSTEMS INSTALLATION INSTRUCTIONS

PACKAGED SYSTEMS INSTALLATION INSTRUCTIONS PACKAGED SYSTEMS INSTALLATION INSTRUCTIONS NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system. Part #FMF-03-333

More information

Model: LoLander Series Truck Scale Model: LL FT Model: LL FT Installation, Set-Up and Operation Manual

Model: LoLander Series Truck Scale Model: LL FT Model: LL FT Installation, Set-Up and Operation Manual SCALE WORKS, INC. Model: LoLander Series Truck Scale Model: LL8035-10FT Model: LL8035-11FT Installation, Set-Up and Operation Manual Cambridge Scale Works, Inc. P.O. Box 670 Honey Brook, PA. 19344 (800)

More information

OPO-SHORT Installation Instructions Manual Version

OPO-SHORT Installation Instructions Manual Version 10200 South Kedzie Avenue Evergreen Park, IL 60805 800.499.0400 708.499.0400 Fax 708.499.4620 OPO-SHORT Installation Instructions Manual Version OPO-1S, OPO-3S, OPO-4S PreSell Main Board (shown as Standard

More information

FrostGuard 120 V 120 V PREASSEMBLED ELECTRIC HEATING CABLES FOR PIPE FREEZE PROTECTION AND ROOF & GUTTER DE-ICING INSTALLATION INSTRUCTIONS

FrostGuard 120 V 120 V PREASSEMBLED ELECTRIC HEATING CABLES FOR PIPE FREEZE PROTECTION AND ROOF & GUTTER DE-ICING INSTALLATION INSTRUCTIONS FrostGuard 120 V 120 V PREASSEMBLED ELECTRIC HEATING CABLES FOR PIPE FREEZE PROTECTION AND ROOF & GUTTER DE-ICING INSTALLATION INSTRUCTIONS DESCRIPTION FrostGuard 120 V preassembled self-regulating heating

More information

SPECIAL SPECIFICATION 6499 Environmentally controlled Communications Building

SPECIAL SPECIFICATION 6499 Environmentally controlled Communications Building 2004 Specifications CSJ 0720-03-095 SPECIAL SPECIFICATION 6499 Environmentally controlled Communications Building 1. Description. Furnish and install Environmentally Controlled Communications Building

More information

SYSTEM 600 BILL CHANGER INSTALLATION INSTRUCTIONS Congratulations...

SYSTEM 600 BILL CHANGER INSTALLATION INSTRUCTIONS Congratulations... www.standardchange.com 1-800-968-6955 Technical Phone Support is from 8:00AM to 7:30PM E.S.T., Monday-Friday Walk-in Service is from 8:00AM to 4:30PM E.S.T., Monday-Friday Parts Department is from 8:00AM

More information

Instructions for Magnum DS Metal-Enclosed Low-Voltage NEMA 3R Assemblies

Instructions for Magnum DS Metal-Enclosed Low-Voltage NEMA 3R Assemblies Instructions for Magnum DS Metal-Enclosed Contents Description Page 1. Introduction........................... 2 2. Receiving, Handling, and Storage.......... 4 3. Equipment Description..................

More information

Operating Instructions April 2010 milltronics WD600

Operating Instructions April 2010 milltronics WD600 Operating Instructions April 2010 milltronics WD600 Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected

More information

FORM HEADWALL. FORM HEADWALL (floor mount) (floor mount) Installation Manual

FORM HEADWALL. FORM HEADWALL (floor mount) (floor mount) Installation Manual FORM HEADWALL (floor mount) Installation Manual FORM HEADWALL (floor mount) OVERVIEW The Form is a UL-listed configurable headwall system. This system includes multiple horizontal equipment channels integrated

More information

OPERATOR S MANUAL. LINKIT Series LKB Roofing Conveyor. Models: LKB-26E & LKB-32E. InterQuip USA LLC interquip.net DISTRIBUTED BY:

OPERATOR S MANUAL. LINKIT Series LKB Roofing Conveyor. Models: LKB-26E & LKB-32E. InterQuip USA LLC interquip.net DISTRIBUTED BY: OPERATOR S MANUAL LINKIT Series LKB Roofing Conveyor Models: LKB-26E & LKB-32E DISTRIBUTED BY: InterQuip USA LLC 203.322.2600 interquip.net 1 IMPORTANT Read, understand and obey these safety rules and

More information

Instructions for the use of the Link 4 Pallet Rack Lifter (PRL) model 5000

Instructions for the use of the Link 4 Pallet Rack Lifter (PRL) model 5000 Instructions for the use of the Link 4 Pallet Rack Lifter (PRL) model 5000 (How to move your pallet racking using the Link 4 Pallet Rack Lifter) This process is for a typical rack move and reset. Each

More information

OPERATOR S MANUAL. LINKIT Series LKS300/LKS450 Portable Conveyor. InterQuip USA LLC interquip.net DISTRIBUTED BY: OPERATOR S MANUAL

OPERATOR S MANUAL. LINKIT Series LKS300/LKS450 Portable Conveyor. InterQuip USA LLC interquip.net DISTRIBUTED BY: OPERATOR S MANUAL OPERATOR S MANUAL LINKIT Series LKS300/LKS450 Portable Conveyor DISTRIBUTED BY: InterQuip USA LLC 203.322.2600 interquip.net 1 IMPORTANT Read, understand and obey these safety rules and operating instructions

More information

INSTALLATION GUIDE. 4-Post Lift. Model United States. United Arab Emirates. Egypt.

INSTALLATION GUIDE. 4-Post Lift. Model United States. United Arab Emirates. Egypt. 4-Post Lift INSTALLATION GUIDE United States 17779 Main Street Suite C Irvine, CA 92614 USA Tel: +1(949) 333-3800 Fax: +1(949) 333-3804 United Arab Emirates Model 46614 P.O. Box 121971 Saif Zone A2-032

More information

1. Hangers and supports for electrical equipment and systems.

1. Hangers and supports for electrical equipment and systems. PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 DEFINITIONS... 1 1.4 PERFORMANCE REQUIREMENTS... 1 1.5 SUBMITTALS... 2 1.6 QUALITY ASSURANCE... 2 1.7 COORDINATION... 2 PART 2 - PRODUCTS...

More information

PATENTS ARE PENDING. Building Dimensions. Exterior Dimensions Roof Edge to Roof Edge

PATENTS ARE PENDING. Building Dimensions. Exterior Dimensions Roof Edge to Roof Edge Assembly Manual 8x5 PATENTS ARE PENDING Approximate Size 7980303 Storage Area Building Dimensions Exterior Dimensions Roof Edge to Roof Edge Interior Dimensions Wall to Wall Sq. Ft. Cu. Ft. Width Depth

More information

SPECIAL SPECIFICATION 8810 Communication Hub Enclosure

SPECIAL SPECIFICATION 8810 Communication Hub Enclosure 2004 Specifications CSJ 0914-00-301 & 0914-00-314 SPECIAL SPECIFICATION 8810 Communication Hub Enclosure 1. Description. Provide Communication Hub Enclosures of various types and sizes, as shown on the

More information

SECTION SECONDARY UNIT SUBSTATIONS

SECTION SECONDARY UNIT SUBSTATIONS SECTION 26 12 16 SECONDARY UNIT SUBSTATIONS PART 1 GENERAL 1.1 SUMMARY This section describes metal-clad, indoor or outdoor, secondary unit substations with integral primary fused disconnect switches,

More information

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION Page 210500-1 SECTION 210500 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

PATENTS ARE PENDING. Building Dimensions. Exterior Dimensions Roof Edge to Roof Edge

PATENTS ARE PENDING. Building Dimensions. Exterior Dimensions Roof Edge to Roof Edge Assembly Manual 8x9 PATENTS ARE PENDING Approximate Size 7640303 Storage Area Building Dimensions Exterior Dimensions Roof Edge to Roof Edge Interior Dimensions Wall to Wall Sq. Ft. Cu. Ft. Width Depth

More information

Porcher Solutions Wall Mount, Pedestal and Above Counter Lavatories

Porcher Solutions Wall Mount, Pedestal and Above Counter Lavatories ASSEMBLY & INSTALLATION INSTRUCTIONS Porcher Solutions Wall Mount, Pedestal and Above Counter Lavatories Thank you for selecting our Porcher product. To ensure that your installation proceeds smoothly,

More information

LIB System for UPS Installation Manual (136S)

LIB System for UPS Installation Manual (136S) LIB System for UPS Installation Manual (136S) ET003193796 English 1/2018. Rev 0.3 Read this manual carefully before starting to install the battery system. Keep these instructions for future reference.

More information

SECTION METAL-ENCLOSED BUS MEDIUM VOLTAGE

SECTION METAL-ENCLOSED BUS MEDIUM VOLTAGE METAL-ENCLOSED BUS MEDIUM VOLTAGE PART 1 GENERAL 1.01 1.02 1.03 1.04 1.05 SCOPE The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings. The medium

More information

2016 V1 SERAPHIM ECLIPSE PHOTOVOLTAIC MODULE JIANGSU SERAPHIM PHOTOVOLTAIC SYSTEM CO. LTD. ADDRESS: JIANGSU CITY OF CHANGZHOU PROVINCE WANG ZHEN HENG

2016 V1 SERAPHIM ECLIPSE PHOTOVOLTAIC MODULE JIANGSU SERAPHIM PHOTOVOLTAIC SYSTEM CO. LTD. ADDRESS: JIANGSU CITY OF CHANGZHOU PROVINCE WANG ZHEN HENG 016 V1 SERAPHIM ECLIPSE JIANGSU SERAPHIM PHOTOVOLTAIC SYSTEM CO. LTD. ADDRESS: JIANGSU CITY OF CHANGZHOU PROVINCE WANG ZHEN HENG ROAD NO. 1-. TELEPHONE: +86-519-8877608 FAX: +86-519-88786181 MAILBOX: info@seraphim-energy.com

More information

SCP Training Manual. Storage, installation and maintenance for SCP busbar systems

SCP Training Manual. Storage, installation and maintenance for SCP busbar systems Storage, installation and maintenance for SCP busbar systems 1 INDEX STORAGE INSTRUCTIONS... 4 HANDLING... 4 GOOD RECEPTION... 10 NOTIFICATIONS... 10 STORAGE... 11 INSTALLATION INSTRUCTIONS... 12 STRAIGHT

More information

Leveling Foot RB210. Leg Extender RLT66

Leveling Foot RB210. Leg Extender RLT66 Landing for Right & Left Turn R342 ITEMS # 0254049, 0254061, 0254072, 0254076, 0016567, 0254099, 0254110, 0054116, 0254117, 0254126, 0254140, 0254150, 0254156 CUSTOM ACCESS RAMP SYSTEM MODELS # R100, R242,

More information

Maintenance Bypass Breaker Cabinet Series Configuration 5. Installation and Operation Manual

Maintenance Bypass Breaker Cabinet Series Configuration 5. Installation and Operation Manual Maintenance Bypass Breaker Cabinet 90881 Series Configuration 5 Installation and Operation Manual 03/13/2012 2 755-00084-C5 R03 Copyright 2012 C&C Power, Inc. All rights reserved. C&C Power, Inc. 395 Mission

More information

Instruction Manual Span Scaffolds! W A R N I N G! Before using Instant UpRight Scaffolds, read, understand and follow all Safety Rules, Erection Instructions and Maintenance Rules. Keep this manual for

More information

E-Series Installing E-Series U Cabinet

E-Series Installing E-Series U Cabinet E-Series Installing E-Series 3040 40U Cabinet September 2018 215-13048_A0 doccomments@netapp.com Table of Contents 3 Contents Overview and specifications... 4 Cabinet features... 4 Power requirements

More information

6x5. Assembly Manual CAUTION. Sharp Edges PATENTS ARE PENDING. Building Dimensions. Approximate Size. Storage Area. Interior Dimensions

6x5. Assembly Manual CAUTION. Sharp Edges PATENTS ARE PENDING. Building Dimensions. Approximate Size. Storage Area. Interior Dimensions Assembly Manual 6x5 PATENTS ARE PENDING Building Dimensions Approximate Size Storage Area Exterior Dimensions Interior Dimensions Roof Edge to Roof Edge Wall to Wall Sq. Ft. Cu. Ft. Width Depth Height

More information

Instruction Manual Span Scaffolds

Instruction Manual Span Scaffolds Instruction Manual Span Scaffolds QUALITY & STRENGTH YOU CAN TRUST! W A R N I N G! Before using Instant UpRight Scaffolds, read, understand and follow all Safety Rules, Erection Instructions and Maintenance

More information

Installation, Inspection and Maintenance of Dry Type Transformers

Installation, Inspection and Maintenance of Dry Type Transformers Dry Type TX 1 of 8 Installation, Inspection and Maintenance of Dry Type Page 1 of 8 Dry Type TX 2 of 8 Table Of Contents Page Number 1. General... 3 2. Installation... 3 3. Safety Inspections... 4 4. Safety

More information

EXECUTION REQUIREMENTS

EXECUTION REQUIREMENTS PART 1 - GENERAL 1.1 SUMMARY A. Section includes: Execution requirements. B. Related Requirements: 1. Specification Sections 2 through 49. PART 2 - PRODUCTS (Not Used). PART 3 - EXECUTION 3.1 SAFETY 01

More information

Zehnder Carboline Radiant Heating and Cooling Ceiling Panels. Installation, Operation and Maintenance. Cooling Fresh Air Clean Air

Zehnder Carboline Radiant Heating and Cooling Ceiling Panels. Installation, Operation and Maintenance. Cooling Fresh Air Clean Air Zehnder Carboline Radiant Heating and Cooling Ceiling Panels Installation, Operation and Maintenance Heating Cooling Fresh Air Clean Air ii General information 1 Safety considerations 1 Unpacking and preparation

More information

OPERATION MANUAL. A220 Arc Welding Machine. Serial Number: Where Purchase: Date of purchased:

OPERATION MANUAL. A220 Arc Welding Machine. Serial Number: Where Purchase: Date of purchased: OPERATION MANUAL A220 Arc Welding Machine Serial Number: Where Purchase: Date of purchased: CONTENT 1.Safety... 2 2. Summary... 4 3. Electrical principle drawing... 5 4. Specifications... 6 5. Operation

More information

CFFWA-XX-1-U. Rev. 1.2

CFFWA-XX-1-U. Rev. 1.2 CFFWA-XX-1-U Rev. 1.2 CFFWA Universal Mount Fan Coils 12,000-60,000 BTUH -------------------------------------- CAUTION -------------------------------------- Care must be taken when handling sheet metal.

More information

SECTION STRUCTURAL METAL FRAMING

SECTION STRUCTURAL METAL FRAMING SECTION 05100 STRUCTURAL METAL FRAMING PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Structural steel framing including lintels, shelf angles, bearing plates, anchor bolts and other items as shown on

More information

TBC Cast Resin Busway Manual

TBC Cast Resin Busway Manual TBC Cast Resin Busway Manual No : SA3001 Pub. Date: Reversion:1.0. CONTENTS Forward. 1 Busway Knowledge..2 Receipt Check... 3 Storage... 4 Handling 5 Installation. 6 Final Check... 7 Operation Conditions

More information

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number PART 1 GENERAL 01 02 03 04 SCOPE Furnish and install Manual Transfer Switches (MTS) and

More information