B. Prismatic acrylic diffusers for fluorescent fixtures shall be A12 pattern and at least 1/8 thick. Do not use styrene lenses.

Size: px
Start display at page:

Download "B. Prismatic acrylic diffusers for fluorescent fixtures shall be A12 pattern and at least 1/8 thick. Do not use styrene lenses."

Transcription

1 PART 1: GENERAL 1.01 Luminaires A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design for new construction and renovations. The responsibility of the engineer is to apply the principles of this section such that the University may achieve a level of quality and consistency in the design and construction of their facilities. Deviations from these guidelines must be justified through Life Cycle Cost (LCC) analysis and submitted to the University for approval. B. Lighting design shall meet the requirements of the currently adopted revision of ASHRAE 90.1 and meet the recommended illumination levels of the current edition of the Illuminating Engineering Society of North America (IESNA) Lighting Handbook. C. Unless specifically approved by Owner, the lighting design shall yield lighting power densities a minimum of 25% below the values allowed in the current ASHRAE 90.1 standard. For fluorescent lighting systems in new construction (or renovations with fixture replacements) and with typical ceiling heights of approximately 9 feet, this can be accomplished by using light colored wall finishes and 2-lamp high efficiency fixtures with the components specified below. Variations in lighting levels resulting from finish color, fixture spacings and height are accommodated by specifying the appropriate ballast factor. D. For renovations where fixture replacements are not desirable, high efficiency retrofit kits are available from fixture manufacturers and third party sources that provide efficiencies equal to new high efficiency fixtures. PART 2: PRODUCTS: 2.01 Interior Luminaires A. All fluorescent lamps installed within conditioned spaces shall be 4-foot straight tube, F28T8, 28-watt, high lumen output energy saving type or 2-foot linear tube, F17T8 high lumen output type. All fluorescent lamps installed in unconditioned or refrigerated spaces shall be 4-foot straight tube, F32T8, 32- watt, high lumen output energy savings type. All linear 17, 28 and 32 watt fluorescent lamps shall have a minimum rated life of 24,000 hours at 3 hours/start (instant start ballast), 95% or higher lumen maintenance and have a color temperature of 4,100 K. No eight-foot lamps allowed. Use combination of 4-foot lengths in 8 foot fixtures. B. Prismatic acrylic diffusers for fluorescent fixtures shall be A12 pattern and at least 1/8 thick. Do not use styrene lenses. Design & Construction Standards, Revised Sept

2 C. The following light fixtures are selected to establish examples of design intent and to set a standard of quality. Equivalent products from other manufacturers may be available and may be submitted for approval. The PSP must closely review the features and performance parameters of any alternate fixtures against the fixtures specified herein. 1. Lensed fluorescent: Energy Planning Associates F2042WT8S series with 28 watt T8 lamps, high efficiency ballast and pattern A12 lens. 2. Parabolic louvered fluorescent (decorative) Paragon PBT24 Parabolic Troffer with two, 800 series 28W T8 lamps, normal ballast factor and a specular reflector. 3. Surface mounted lensed fluorescent: Energy Planning Associates FWC1042ET8S series with 28 watt T8 lamps, high efficiency ballast. 4. High bay fluorescent: Energy Planning Associates High Five One for One series FH5/OFO six lamp fixture equipped with 800 series T8 lamps. 5. Recessed incandescent downlight: Halo H7600T series or equal by Gotham. 6. Recessed compact fluorescent downlight: Kurt Versen Quadlite series 7. Track Lighting: Lightolier or Staff. 8. Exit Lighting: LED (light emitting diode) type only. TCP 20743DRM Series. D. Ballasts: Fluorescent ballasts shall be high frequency, U.L. approved, CBM certified to operate as specified one, two or three T8 lamps; shall be integrated circuit type electronic constant wattage, constant light output instant start; shall have a power factor greater than 95%; shall have Class A sound rating; shall be Class P thermally protected with automatic reset; shall have a crest factor less than 1.5; shall have a total harmonic content less than 10%. Where not separately switched three or four lamp fixtures may contain 3 and 4 lamp ballasts. Ballast factor shall be 0.77 or 0.78 for Low Powered ballasts, between 0.85 and 0.90 for Normal Powered ballasts, and greater than 1.12 for high output ballasts. All ballasts shall have a total harmonic distortion (THD) <10%. All fluorescent ballasts shall be instant start and classified as NEMA premium efficiency. Ballasts shall designed to accommodate multiple voltage input, shall have built in anti-striation technology and utilize parallel lamp operation circuitry. Ballasts shall further be designed such that the output frequency to the lamps does not interfere with common infrared devices (typically 40kHz or greater).. E. Do not use low pressure sodium or mercury vapor lamps 2.02 Exterior Luminaires Design & Construction Standards, Revised Sept

3 A. Exterior luminaires including illumination sources shall be selected based on the following performance criteria unless specifically approved otherwise: 1. Photometric performance and high fixture efficiency. 2. Good to excellent color rendering and minimal color temperature variance. 3. 4,100K fluorescent lamps and 4,000K metal halide lamps. 4. Durable, corrosion resistant fixtures and very long life lamps - Minimal luminaire O&M costs 5. Minimize energy usage of each lighting application 6. Minimize light pollution 7. Exterior lighting must be readily maintainable B. The following luminaires are selected to establish design intent and to set a standard of quality. Equivalent products from other manufacturers may be available and may be submitted for approval. The PSP must closely review the features and performance parameters of any alternate fixtures against the fixtures specified herein. All luminaires shall be UL listed for wet or damp locations depending on the application. 1. Wallpack Luminaires: RAB Lighting WP2 cutoff wallpack, bronze, equipped with a 42 watt compact fluorescent lamp. 2. Surface Mounted Canopy Luminaires: Paragon Series PVT4 vapor tight equipped with two, high lumen output 32 watt T8 lamps, a Miro-4 reflector and a high efficiency low or normal ballast factor ballast. 3. Area and Parking Lot Luminaires: Die-cast aluminum with nominal 1/8" wall thickness minimum cutoff luminaire equipped with a pulse-start metal halide lamp or induction fluorescent lamp. The finish shall be corrosionresistant polyester powder coating. PART 3: DESIGN/DRAWING REQUIREMENTS 3.01 Interior Lighting A. Professional Service Provider (PSP) shall perform detailed calculations of illumination levels in design space. Provide room by room tabulation of calculation input (e.g. reflectivity, fixture height, light output depreciation) and output (min-max-avg footcandles). Also provide tabulated results of lighting power density calculations showing (per room) ASHRAE allowable watts/sqft, the value at 75% of allowable, and actual design watts/sqft. B. Use compact fluorescent lamps instead of incandescent wherever practical. C. Fluorescent lighting may be dimmed if specified with 5% dimming ballasts and wall dimmers as manufactured by Lutron. Design & Construction Standards, Revised Sept

4 D. Lay-in type fluorescent fixtures must have supports to structure at two opposing corners minimum. These supports are to be attached to the fixture housing. Ceiling supports are in addition to these supports. E. Do not provide central building lighting control systems. Use low voltage switching only where there are more than 3 switch locations. F. In rooms or lighting zones requiring bi-level switching, provide two ballasts per fixture and split the lamps between the two ballasts (e.g. for a 2-lamp fixture, wire the north lamp to circuit A and south lamp to B ). Use low voltage switching only where there are more than 3 switch locations. G. Stairwell light fixtures shall be located such that they may be reached safely with no more than a 10-foot ladder. H. Require in-line fuses in fixtures, which are not locally switched, or where lighting circuit should not be turned off for safety reasons. (i.e. stairwells) I. Use dual technology occupancy sensors. Do not use motion sensors in laboratories. J. Lighting contactors shall be electrically actuated, mechanically held. K. Where the opportunity exists, install lighting controls to take advantage of daylighting. L. In buildings where emergency power circuits do not exist, install emergency fluorescent ballasts on an as required based. Ballasts shall provide a minimum of 90 minutes of code required emergency lighting at compliant illumination levels. Battery packs for emergency ballast shall be rated for high temperature operation Exterior Lighting A. All walkways, sidewalks, and parking lots shall be illuminated to levels recommended by the IESNA or as required to meet the Universities security needs, whichever is higher. B. All engineering calculations of illumination levels and lighting power density shall be presented in construction documents and made available to the Utilities Electrical Distribution department upon request. C. Design and location of exterior lighting shall always consider tree and landscaping locations. Design & Construction Standards, Revised Sept

5 D. Lighting Control: Exterior building lighting shall be controlled with an astronomical time clock with manual bypass switch. Outside area and street lighting may be controlled with photoelectric cells or an astronomical time clock. E. Exterior and site lighting shall be shown on site plan. F. Provide pole mounting height and pole base installation detail. G. Pedestrian Walk, Plaza Light Pole: Concrete pole, 12 feet high, equal to Ameron VBS-3.7 (2R3) in Austin, Tan color, with area cut-off HID fixture equal to Spring Catalog #Washington-118 refractive globe with final luminaire. Lamp is to be metal halide, 175W, 277v. Color of luminaire metal shall be equal to Ameron #RAL 8019, Grey Brown. END OF STANDARD Design & Construction Standards, Revised Sept

INTERIOR & EXTERIOR LIGHTING DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 LUMINAIRES

INTERIOR & EXTERIOR LIGHTING DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 LUMINAIRES PART 1: GENERAL 1.01 LUMINAIRES A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design for new construction and renovations.

More information

new equipment & construction

new equipment & construction Note: All fluorescent fixtures must have High formance or Reduced Wattage (HP/RW) lamps & ballast systems or a T5 lamp and ballast systems to be eligible for a fluorescent incentives. Facility lighting

More information

SECTION LIGHTING

SECTION LIGHTING PART 1 - GENERAL 1.1. RELATED SECTIONS: 1.2. SCOPE OF SECTION: This section contains the requirements for equipment and installation related to exterior, interior, and special lighting applications. 1.3

More information

Solano Community College District Lighting Standards

Solano Community College District Lighting Standards Solano Community College District Lighting Standards Prepared for: Solano Community College 4000 Suisun Valley Road Fairfield, CA 94534 FINAL SUBMITTAL 1-29-2016 Approved 3-16-16 by Board of Trustees Kitchell

More information

SECTION LUMINAIRES AND ACCESSORIES

SECTION LUMINAIRES AND ACCESSORIES SECTION 16500 LUMINAIRES AND ACCESSORIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to

More information

Light levels should be appropriate for the task and per the following guide in Part 1 - General.

Light levels should be appropriate for the task and per the following guide in Part 1 - General. DIVISION 16 - ELECTRICAL Section 16510 - Lighting Design Introduction Lighting utilizes approximately 40% of the electrical energy consumed here at the university. In order to conserve the energy it is

More information

Looking for Opportunities in Lighting. Tom Coughlin Program Manager Commercial Lighting

Looking for Opportunities in Lighting. Tom Coughlin Program Manager Commercial Lighting Looking for Opportunities in Lighting Tom Coughlin Program Manager Commercial Lighting Looking for Opportunities simple retrofits Lamp and Ballast Replacement Take a 3 lamp T-12 system 103W 3 lamp standard

More information

Bulbs and Ballast. Regular Product : Bulbs and Ballast

Bulbs and Ballast. Regular Product : Bulbs and Ballast Bulbs and Ballast Bulbs and Ballast Bulbs and Ballast Rating: Not Rated Yet Ask a question about this product Description In the past decade, tremendous advances have been made in the efficiency of virtually

More information

Commercial Rebate Lighting Program Application/Confirmation

Commercial Rebate Lighting Program Application/Confirmation A B Fixtures Rebate per Fixture Estimate Qty BUILDING NAME: Actual Qty Existing Lamp/Fixture Wattage (Actual Draw) Commercial Rebate Lighting Program Application/Confirmation Installed Lamp/Fixture Wattage

More information

Light levels should be appropriate for the task and per the following guide in Part 1 - General.

Light levels should be appropriate for the task and per the following guide in Part 1 - General. DIVISION 16 - ELECTRICAL Section 16510 - Lighting Design Introduction Lighting utilizes approximately 40% of the electrical energy consumed here at the university. In order to conserve the energy it is

More information

This document is provided as a reference for the design team and should not be used directly as written project specifications.

This document is provided as a reference for the design team and should not be used directly as written project specifications. 26 50 00 LIGHTING This document is provided as a reference for the design team and should not be used directly as written project specifications. PAR T 1 GENERAL 1.01 SUMMARY A. This Section includes lighting

More information

Prescriptive Program. Terms And Conditions General Eligibility. Commercial and Industrial Customers. Rebate Checklist

Prescriptive Program. Terms And Conditions General Eligibility. Commercial and Industrial Customers. Rebate Checklist Prescriptive Program Industrial Customers Rebate Checklist Get your rebate check faster by checking off these easy steps before mailing your application form. Incomplete applications may be delayed. q

More information

EarthTronics products. About us. Where Efficiency Meets Innovation T5 & T8 Linear. Founded in 2007, EarthTronics, Inc. is a Michigan based

EarthTronics products. About us. Where Efficiency Meets Innovation T5 & T8 Linear. Founded in 2007, EarthTronics, Inc. is a Michigan based LED Product Guide About us EarthTronics products We are dedicated to developing innovative energy efficient lighting products that provide a positive economic and environmental impact for our customers.

More information

Lighting Energy Management

Lighting Energy Management SBS5312 Lighting Technology http://ibse.hk/sbs5312/ Lighting Energy Management Ir. Dr. Sam C. M. Hui Faculty of Science and Technology E-mail: cmhui@vtc.edu.hk Sep 2017 Content Lighting Energy Use Energy

More information

B. Verify that electrical installation may be made in complete accordance with all pertinent codes and regulations and the original design.

B. Verify that electrical installation may be made in complete accordance with all pertinent codes and regulations and the original design. SECTION 16500 - LIGHTING PART 1 - GENERAL 1.01 General Conditions 1.02 Scope 1. The General Conditions, Supplementary General Conditions, Special Conditions, Alternates, Addenda, Applicable Drawings and

More information

Commercial Lighting Issues. Commercial Lighting Issues

Commercial Lighting Issues. Commercial Lighting Issues Commercial Lighting Issues Conservation Resources Advisory Committee January 28, 2015 Commercial Lighting Issues New Federal GSFL standard: Savings or Not? Interior Proxy measures modeled Equivalent lumens

More information

Light is straightforward SYLVANIA LED Luminaires

Light is straightforward SYLVANIA LED Luminaires Light is straightforward SYLVANIA LED Luminaires SYLVANIA LED Luminaires Table of Contents Table of Contents SYLVANIA LED Luminaires Overview 3 Edge-Lit Panel 4-5 Volumetric Troffer 6-7 Retrofit Door Kit

More information

HEALTHCARE & SCHOOL LIGHTING

HEALTHCARE & SCHOOL LIGHTING HEALTHCARE & SCHOOL LIGHTING Lighting & Control Solutions SLGUS.COM TD Recessed Troffer One Of The Best Value Low-Profile LED Luminaire Popular center-basket design features with an elegant design, shallow

More information

General Lighting Recommendations

General Lighting Recommendations General Lighting Recommendations DESIGN GUIDELINES FOR ENERGY EFFICIENT LIGHTING SYSTEMS According to the US Department of Energy, 51 percent of the energy used in commercial buildings is consumed by lighting

More information

Introduction to LED Lighting

Introduction to LED Lighting Introduction to LED Lighting Presented by: Darrell Huffman Mercer-Zimmerman Learning Objectives LO1: LO2: LO3: LO4: LO5: What is an LED? LED Terminology Why LED? LED Equivalency LED Control LO1: What is

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 16511 Interior Lighting This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in

More information

A. This Section includes lighting design criteria, interior and exterior luminaires, lamps and ballasts, as well as related installation guidelines.

A. This Section includes lighting design criteria, interior and exterior luminaires, lamps and ballasts, as well as related installation guidelines. SECTION 265000 LIGHTING This document is provided as a reference for the design professionals working for the University of Pennsylvania. This document should not be used directly as written project specifications.

More information

m nlighting Compliance Documentation Page 1

m nlighting Compliance Documentation Page 1 m nlighting Compliance Documentation Page 1 Project Name: Lighting Sample renovation project (ASHRAE 90.1 2010) Project Address: 565 Sample St Date: Designer of Record: Email: Telephone: Contact Person:

More information

Suggested Environmental Considerations for Lighting Equipment

Suggested Environmental Considerations for Lighting Equipment Suggested Environmental Considerations for Lighting Equipment Below are suggested environmental considerations for lighting equipment for health care that can be used to inform purchasing decisions in

More information

2010 CA Higher Education Sustainability Conference

2010 CA Higher Education Sustainability Conference 2010 CA Higher Education Sustainability Conference Energy Efficiency Partnership Program Best Practice Awards Application Project Category 11 Rendering Used Courtesy of Cannon Design I. Contact Information

More information

SECTION LIGHTING. A. Section Basic Electrical Materials and Methods

SECTION LIGHTING. A. Section Basic Electrical Materials and Methods SECTION 16500 LIGHTING PART 1 GENERAL 1.01 SECTION INCLUDES A. Provide lighting fixtures of sizes, types and ratings as indicated; complete with, but not necessarily limited to, housings, lamps, lamp holders,

More information

Truss Mini Pendant PENDANT

Truss Mini Pendant PENDANT Overview Realistic steel mini-truss in aluminum Direct, Indirect or Direct/Indirect light distribution Two piece extruded aluminum housing with integral driver Continuous row mounting, standard Can also

More information

VIA 3 LED RECESSED W W W. L U M E N W E R X. C O M

VIA 3 LED RECESSED W W W. L U M E N W E R X. C O M DESCRIPTION Via 3 is a compact linear LED luminaire PROJECT: system for pendant, surface, and recessed or in-wall installation, whether as discrete luminaires, continuous runs, TYPE: NOTES: or patterns.

More information

2019 Lighting Retrofit Rebate Instructions. City of Le Sueur

2019 Lighting Retrofit Rebate Instructions. City of Le Sueur Rebate Instructions By participating in the We Save program, you can save energy and earn a rebate when you replace existing lighting with qualifying, energy-efficient lighting. What Rebate Can I Earn?

More information

2019 Lighting Retrofit Rebate Instructions. City of Brownton

2019 Lighting Retrofit Rebate Instructions. City of Brownton Rebate Instructions By participating in the We Save program, you can save energy and earn a rebate when you replace existing lighting with qualifying, energy-efficient lighting. What Rebate Can I Earn?

More information

September 21, 2016 LED Update: Benefits, Incentives, Action Plan, Case Studies. Ed Evans LEDVANCE SYLVANIA

September 21, 2016 LED Update: Benefits, Incentives, Action Plan, Case Studies. Ed Evans LEDVANCE SYLVANIA September 21, 2016 LED Update: Benefits, Incentives, Action Plan, Case Studies Ed Evans LEDVANCE SYLVANIA Agenda The Current LED market New LED technology for Commercial facilities New LED RETROFIT program

More information

VIA 4 LED RECESSED W W W. L U M E N W E R X. C O M

VIA 4 LED RECESSED W W W. L U M E N W E R X. C O M Grid - regressed lens Drywall - flush lens DESCRIPTION PROJECT: Via 4 is the flexible linear LED luminaire system for pendant, surface and recessed or in-wall installation, whether TYPE: as discrete luminaires,

More information

2019 Lighting Retrofit Rebate Instructions. City of Winthrop

2019 Lighting Retrofit Rebate Instructions. City of Winthrop Rebate Instructions By participating in the We Save program, you can save energy and earn a rebate when you replace existing lighting with qualifying, energy-efficient lighting. What Rebate Can I Earn?

More information

LED Recessed Lighting. Diamond Series LED Retrofit Platinum Series LED Housings and Trims LED Step Lighting. I l l u m i n a t i n g t h e f u t u r e

LED Recessed Lighting. Diamond Series LED Retrofit Platinum Series LED Housings and Trims LED Step Lighting. I l l u m i n a t i n g t h e f u t u r e LED Recessed Lighting Diamond Series LED Retrofit Platinum Series LED Housings and Trims LED Step Lighting RoHS C O M P L I A N T 2008 I l l u m i n a t i n g t h e f u t u r e What is LED? The Light Emitting

More information

Unlock the Extraordinary Potential of Light

Unlock the Extraordinary Potential of Light Unlock the Extraordinary Potential of Light For professionals // For your home Home improve your well-being Office & Industry optimize your building Retail & Hospitality enhance the in-store experience

More information

Lighting Rebates 2017 New Construction Rebate Application

Lighting Rebates 2017 New Construction Rebate Application 2017 New Construction Rebate Application Business Member Information Business Name Installation Address City, State, Zip Contact Name Email Phone Number Account Number Application Check List Rebate application

More information

2017 Lighting Program Colorado: Commercial and Industrial Electric Customers

2017 Lighting Program Colorado: Commercial and Industrial Electric Customers Black Hills Energy offers Colorado Commercial and Industrial electric customers rebates for some of the most commonly installed lighting projects. We offer commercial customers two options to receive rebates.

More information

TSR LIGHTING, ST PAUL, MN JEFF BOUMEESTER

TSR LIGHTING, ST PAUL, MN JEFF BOUMEESTER TSR LIGHTING, ST PAUL, MN JEFF BOUMEESTER LEAD THE LED LIGHTING REVOLUTION to obsolete energy-inefficient lighting. 2014 Cree, Inc. All rights reserved. 2 The Rising Cost of Lighting Lighting accounts

More information

Building Operator Certification Level I

Building Operator Certification Level I Building Operator Certification Level I A Partnership of the CUNY Institute for Urban Systems Building Performance Lab, the CUNY School of Professional Studies, and the New York State Energy Research &

More information

Truss Acoustic ACOUSTIC

Truss Acoustic ACOUSTIC Overview Sound absorbing panels ranging between.45 and.90,nrc based on room size and location. Class A fire rating. Direct, Indirect or Direct/Indirect light distribution Two piece acoustic material over

More information

VIA 3 SKIM LED - PATTERNS W W W. L U M E N W E R X. C O M

VIA 3 SKIM LED - PATTERNS W W W. L U M E N W E R X. C O M DESCRIPTION PROJECT: Via Skim is designed to illuminate textured or polished vertical surfaces with a grazing light from TYPE: the wall/ceiling intersection. Via Skim NOTES: provides continuous illumination

More information

VIA 3 LED RECESSED WALL WASH V. 2 W W W. L U M E N W E R X. C O M

VIA 3 LED RECESSED WALL WASH V. 2 W W W. L U M E N W E R X. C O M DESCRIPTION PROJECT: Elegant and flexible, the Via 3 Recessed Wall Wash features our Asymmetrical Lens Optic for TYPE: smooth, comfortable and efficient NOTES: illumination of vertical surfaces. Via 3

More information

Truss Pendant PENDANT

Truss Pendant PENDANT Overview Realistic steel truss in aluminum Direct, Indirect or Direct/Indirect light distribution Two piece extruded aluminum housing with integral driver Continuous row mounting, standard Can also be

More information

RECESSED MOUNT. Project. Type. Notes

RECESSED MOUNT. Project. Type. Notes Project Type Notes PERFORMANCE PER LINEAR FOOT AT 4K NOMINAL LUMEN OUTPUT INPUT WATTS* EFFICACY 4 lm/ft 3.6 W/ft 111 lm/w 5 lm/ft 4.7 W/ft 16 lm/w 75 lm/ft 7.5 W/ft 1 lm/w 1 lm/ft 1.4 W/ft 96 lm/w * Based

More information

EOS 3.0 RECESSED PERIMETER

EOS 3.0 RECESSED PERIMETER RECESSED PERIMETER RECESSED PERIMETER Spec Guide CROSS SECTION PHOTOMETRICS RECESSED PERIMETER 80 CRI up to 105 lm/w performance Performance based on 4 luminaire at 4000K @ 25 o C Calculated L80 at 80,000

More information

Technical Requirements Table, V3.1 Technical Requirements: Luminaires

Technical Requirements Table, V3.1 Technical Requirements: Luminaires DesignLights Consortium TM Product Qualification Criteria, (FINAL 11/20/1) Technical Table, V3.1 Technical : Luminaires # Category 1 2 3 4 Outdoor General Application Low Mid High Interior Directional

More information

MANDATORY MEASURES OUTDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.2)

MANDATORY MEASURES OUTDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.2) MANDATORY MEASURES CONTROLS (Reference: Sub-Chapter 4, Section 130.2) BACKLIGHT, UPLIGHT, AND GLARE (BUG) RATINGS The BUG system is used to evaluate luminaire performance in relation to lighting trespass,

More information

Challenges When Deploying LED Lighting Retrofits

Challenges When Deploying LED Lighting Retrofits Challenges When Deploying LED Retrofits With many of the opportunities afforded by new lighting technology, such as LED lighting, come new issues. New technology can sometimes create new, unforeseen challenges,

More information

Transitioning to LED Lighting Technology Helps Facilities Reduce Lighting Energy Consumption and Costs

Transitioning to LED Lighting Technology Helps Facilities Reduce Lighting Energy Consumption and Costs Transitioning to LED Lighting Technology Helps Facilities Reduce Lighting Energy Consumption and Costs Overview e Lighting Industry and its Benefits to Facility Managers Reduce costs by replacing existing

More information

Lighting Calculator 3.3 Program Offerings

Lighting Calculator 3.3 Program Offerings Lighting Calculator 3.3 Program Offerings Series A: T8 Linear Fluorescent Series A covers both interior and exterior linear fluorescent lighting including 4, 8 T8 and irregular size products. A1-30% Linear

More information

LIGHTING SUPPLY (SE MICHIGAN) SPECIAL BUY CLOSEOUT

LIGHTING SUPPLY (SE MICHIGAN) SPECIAL BUY CLOSEOUT SPS2GFSVI332UNVH3 Fluorescent Troffer 2X4 Closeout Electronic Fluorescent Recessed 2x4 Troffer - 120V-277V, Spec Grade, Uses (3) F32T8 Lamps Not Included, White Fixture 16 $36.00 2SPG432-FS12-UNV-1/4-EB10R

More information

ENERGY EFFICIENT LIGHTING CONTROLLING THE COST OF ENERGY FOR OFFICE, EDUCATIONAL, RETAIL AND INDUSTRIAL ENVIRONMENTS

ENERGY EFFICIENT LIGHTING CONTROLLING THE COST OF ENERGY FOR OFFICE, EDUCATIONAL, RETAIL AND INDUSTRIAL ENVIRONMENTS ENERGY EFFICIENT LIGHTING CONTROLLING THE COST OF ENERGY FOR OFFICE, EDUCATIONAL, RETAIL AND INDUSTRIAL ENVIRONMENTS COLUMBIA LIGHTING ENERGY SOLUTIONS COLUMBIA Lighting ENERGY SOLUTIONS: A Strategic Financial

More information

COLUMBIA LIGHTING ENERGY SOLUTIONS. VersaBay. Fluorescent High Bay

COLUMBIA LIGHTING ENERGY SOLUTIONS. VersaBay. Fluorescent High Bay COLUMBIA LIGHTING ENERGY SOLUTIONS VersaBay Fluorescent High Bay HIGH-AMBIENT SOLUTION Ambient Issues The increased use of fluorescent high bays in what was traditionally HID spaces has provided an excellent

More information

DEVICES AND LUMINAIRES

DEVICES AND LUMINAIRES CHAPTER 40 DEVICES AND LUMINAIRES SECTION E4001 SWITCHES E4001.1 Rating and application of snap switches. General-use snap switches shall be used within their ratings and shall control only the following

More information

MANDATORY MEASURES OUTDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.2)

MANDATORY MEASURES OUTDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.2) MANDATORY MEASURES CONTROLS (Reference: Sub-Chapter 4, Section 130.2) PARKING GARAGES Parking garages are considered interior nonresidential spaces, except for the top level of a multi-tier garage. General

More information

Business Energy Rebates Application

Business Energy Rebates Application Business Energy Rebates Application Business Energy Rebates make it easy and affordable for you to select energy efficient products for your business. and mail-in rebates are available for energy efficient

More information

SECTION LIGHTING

SECTION LIGHTING SECTION 26 51 00 LIGHTING PART 1 - GENERAL 1.1 SYSTEMS DESCRIPTION A. Illumination Levels: 1. Design illumination levels for different activities shall correspond to those listed under "Lighting Level

More information

Guide to new, energy-efficient lighting applications for your business and properties

Guide to new, energy-efficient lighting applications for your business and properties Guide to new, energy-efficient lighting applications for your business and properties Commercial lighting systems have advanced at a rapid pace, with LEDs now taking center stage. LEDs offer excellent

More information

Technical Requirements Table, V4.1 Table 1: Technical Requirements: Luminaires Requirements

Technical Requirements Table, V4.1 Table 1: Technical Requirements: Luminaires Requirements Technical Table, V4.1 Table 1: Technical : Luminaires # Category General Application Light (lm) Efficacy (lm/w) DLC Standard Warranty (years) CCT / CRI / L 70 Minimu m Efficacy (lm/w) DLC Premium** Warranty

More information

LED. surface/ direct. direct

LED. surface/ direct. direct Alumina surface/ in suspended /in / in LAMPING OPTIONS AT A GLANCE: asymm. The ALUMINA series by is a line of extruded aluminum rectilinear luminaires. The is a /8 wide housing with a 7/8 aperture. Multiple

More information

5 year. 25W led Flood light. led info. 100,000+ hours. lflled TEST FORWARD CURRENT (ma) # OF LEDLinX MODULES

5 year. 25W led Flood light. led info. 100,000+ hours. lflled TEST FORWARD CURRENT (ma) # OF LEDLinX MODULES Cut Sheet: 25W LED Flood Light 25W led Flood light Application Engineered to replace up to 100W MH. Illumination for area lighting, wall washing and flood applications where significant energy reduction

More information

DEEMED SAVINGS TECHNICAL ASSUMPTIONS

DEEMED SAVINGS TECHNICAL ASSUMPTIONS Product: Description: Prescriptive rebates will be offered for replacement lighting equipment. New Construction rebates will be offered for new facilities or spaces overhauled for a new purpose. Custom

More information

DEEMED SAVINGS TECHNICAL ASSUMPTIONS

DEEMED SAVINGS TECHNICAL ASSUMPTIONS Product: Description: Prescriptive rebates will be offered for replacement lighting equipment. New Construction rebates will be offered for new facilities or spaces overhauled for a new purpose. Custom

More information

Catalog # Project. Comments. Prepared by. Warranty Five year warranty mm mm mm mm

Catalog # Project. Comments. Prepared by. Warranty Five year warranty mm mm mm mm DESCRIPTION The Define series by Neo-Ray characterizes the ultimate in minimalist simplicity by providing clean, uniform lines of illumination in virtually any architectural environment. Powered by s most

More information

Please contact Nancy Ramdon-Connolly at NESCO for further inquiries. Tel:

Please contact Nancy Ramdon-Connolly at NESCO for further inquiries. Tel: Please contact Nancy Ramdon-Connolly at NESCO for further inquiries. Tel: 415.307.8579 Email: nramdon@nescoweb.com DESCRIPTION 695-WP Half Pyramid with direct illumination. Catalog # shaperlighting.com

More information

Optics Mounting Lamping Finish Voltage Options. T6 Metal Halide* H039T6 1 39wT6 H070T6 2 70wT6. H w H070 70w H w

Optics Mounting Lamping Finish Voltage Options. T6 Metal Halide* H039T6 1 39wT6 H070T6 2 70wT6. H w H070 70w H w Quadro Project: Type: Qty: QD _ Series Optics Mounting Lamping Finish Voltage _ Option Pole Series Height Finish Options Series QD Quadro Optics Mounting Lamping Finish Voltage Options MA Type III MTR

More information

MANDATORY MEASURES OUTDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.2)

MANDATORY MEASURES OUTDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.2) MANDATORY MEASURES CONTROLS (Reference: Sub-Chapter 4, Section 130.2) Additions and Alterations Over 50% replaced Mandatory Controls 130.0, 130.2, 130.4 + Prescriptive Requirements LPD allowances of 140.7

More information

IITC Custom Search Keywords: 25 SEP 14

IITC Custom Search Keywords: 25 SEP 14 IITC Custom Search Keywords: 25 SEP 14 Under consideration Keyword Description/Value / Example Value List Value List (cont.) Value List (cont.) [_SEARCH_SOURCETYPE] Lamp/Source Type (see Notes below) Select

More information

CESIG Meeting OFFICE LIGHTING ENERGY DASHBOARDS. Prepared by: Casey Gaetz, LC

CESIG Meeting OFFICE LIGHTING ENERGY DASHBOARDS. Prepared by: Casey Gaetz, LC CESIG Meeting OFFICE LIGHTING ENERGY DASHBOARDS Prepared by: Casey Gaetz, LC November 2015 Introductions Prism Engineering provides mechanical and electrical engineering services to improve building performance.

More information

Taking Advantage of the New York City Lighting Upgrade Mandate

Taking Advantage of the New York City Lighting Upgrade Mandate Taking Advantage of the New York City Lighting Upgrade Mandate 17 April, 2012 1 Our members: Lighting manufacturers united through the National Electrical Manufacturers Association (NEMA) Our focus: Informing

More information

SSL Technical Requirements V4.3

SSL Technical Requirements V4.3 SSL Technical V4.3 Table 1: Technical : Luminaires # Category General Application Light Output (lm) Efficacy (lm/w) DLC Standard Warranty (years) CCT / CRI / L 70 Minimu m Efficacy (lm/w) DLC Premium**

More information

Description 5"/6" Retrofit Baffle-Trim Led Module, 120V, 90CRI, 4000 K, Matte White

Description 5/6 Retrofit Baffle-Trim Led Module, 120V, 90CRI, 4000 K, Matte White 3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 LT560WH6940 6" 10W Led Retro 40K Catalog Number LT560WH6940 Manufacturer Description 5"/6" Retrofit Baffle-Trim Led Module,

More information

DEEMED SAVINGS TECHNICAL ASSUMPTIONS

DEEMED SAVINGS TECHNICAL ASSUMPTIONS Product: Prescriptive rebates will be offered for replacement lighting equipment. New Construction rebates will be offered for new facilities or spaces overhauled for a new purpose. Custom rebates are

More information

MANDATORY MEASURES OUTDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.2)

MANDATORY MEASURES OUTDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.2) MANDATORY MEASURES CONTROLS (Reference: Sub-Chapter 4, Section 130.2) Additions and Alterations Over 50% replaced Mandatory Controls 130.0, 130.2, 130.4 + Prescriptive Requirements LPD allowances of 140.7

More information

124.0mm 4.88" 120.7mm 4.75"

124.0mm 4.88 120.7mm 4.75 wall to ceiling corner seem features Narrow " aperture slot fluorescent luminaire that transitions from wall to ceiling for a unique aesthetic. Frosted acrylic flush lens provides even illumination. Allows

More information

Units. Lighting quantity is primarily expressed in three types of units.

Units. Lighting quantity is primarily expressed in three types of units. Lighting Efficiency Units Lighting quantity is primarily expressed in three types of units. Watts measure of electrical power that defines the rate of energy consumption. Lumens output of a lamp, how much

More information

LIGHTPLANE 3.5RWL LP3.5RWL RECESSED, WET LOCATION

LIGHTPLANE 3.5RWL LP3.5RWL RECESSED, WET LOCATION LIGHTPLANE 3.5RWL LP3.5RWL STANDARD SIZES 3.5" Aperture Configurable in straight run sections Longest Uninterrupted Length: 4' / Longest Joined Length: 8' LAMPING LED - Direct - 80/90 CRI - 3000K/3500K/4000K

More information

Project: Type: Qty: Optics. Series. Reflector Mounting Lamping Finish Voltage Options BLC - S BLC-L 21 1 /4" 36 1 /4" 3 1 /2" O.D.

Project: Type: Qty: Optics. Series. Reflector Mounting Lamping Finish Voltage Options BLC - S BLC-L 21 1 /4 36 1 /4 3 1 /2 O.D. Project: Type: Qty: Series Optics Mounting Lamping Finish Voltage Options Pole Series Finish Pole Options Series Optics Mounting Lamping Finish Voltage Options BLC Beta Lantern L S Flat Glass Lens Sagged

More information

DRAFT Technical Requirements V4.3

DRAFT Technical Requirements V4.3 DRAFT Technical V4.3 Table 1: Technical : Luminaires # Category General Application Light (lm) Efficacy (lm/w) DLC Standard Warranty (years) CCT / CRI / L 70 Minimu m Efficacy (lm/w) DLC Premium** Warranty

More information

Technical Requirements Table, V4.0 Technical Requirements: Luminaires

Technical Requirements Table, V4.0 Technical Requirements: Luminaires Technical Table, V4.0 Technical : Luminaires # Category 1 2 3 4 Outdoor General Application Low Mid High terior Directional Case Lighting Light (lm) Efficacy (lm/w) 20-,000 90,000-10,000 DLC Standard Warranty

More information

FLUORESCENT HIGH BAY ENERGY-SAVING LIGHTING SYSTEMS

FLUORESCENT HIGH BAY ENERGY-SAVING LIGHTING SYSTEMS FLUORESCENT HIGH BAY ENERGY-SAVING LIGHTING SYSTEMS Fluorescent lighting has long been the benchmark for delivering reliable and efficient lighting in commercial office spaces. Now those same benefits

More information

Lighting and Daylighting for The 21 st Century School

Lighting and Daylighting for The 21 st Century School Lighting and Daylighting for The 21 st Century School James R Benya PE FIES IALD LC BENYA LIGHTING DESIGN Development funded by Acuity Brands and Finelite This program is registered with the AIA/CES for

More information

SPECIAL SPECIFICATION 8710 Decorative Pole Lighting Assembly

SPECIAL SPECIFICATION 8710 Decorative Pole Lighting Assembly 2004 Specifications CSJ 0902-48-682, 0902-48-825 & 0902-48-826 SPECIAL SPECIFICATION 8710 Decorative Lighting Assembly 1. Description. Furnish and install a Decorative Lighting Assembly (Type A) as shown

More information

Downlighting. LyteProfile LED 6" P6R Round DL & Lensed Wall Wash P6R P6R

Downlighting. LyteProfile LED 6 P6R Round DL & Lensed Wall Wash P6R P6R Downlighting LyteProfile LED " PR LyteProfile LED Downlights are designed for new construction and include downlight and wall wash distributions. They are highly energy efficient with up to lm/w, provide

More information

Lighting. Sections Included In This Section: 1.1 General 1.2 Exterior Lighting 1.3 Interior Lighting 1.4 Exit Lighting 1.

Lighting. Sections Included In This Section: 1.1 General 1.2 Exterior Lighting 1.3 Interior Lighting 1.4 Exit Lighting 1. Sections Included In This Section: 1.1 General 1.2 Exterior Lighting 1.3 Interior Lighting 1.4 Exit Lighting 1.1 GENERAL A. It is the responsibility of each project to provide all security, walkway, plaza,

More information

RLS Recessed Linear Series

RLS Recessed Linear Series Catalog # : Project : Prepared By : Date : RLS The RLS Recessed light fixture adds a truly unique, seamless and sophisticated look to any project requiring an easy to install, upscale lighting unit. The

More information

DEEMED SAVINGS TECHNICAL ASSUMPTIONS

DEEMED SAVINGS TECHNICAL ASSUMPTIONS Product: Prescriptive rebates will be offered for replacement lighting equipment. New Construction rebates will be offered for new facilities or spaces overhauled for a new purpose. Custom rebates are

More information

LED Lighting and Retrofit Design

LED Lighting and Retrofit Design LED Lighting and Retrofit Design 0 Marcus Gioe Senior Project Manager Lighting Division an Energy Efficiency Provider Lighting Solar Thermal Systems Capital Roadmap 1 Lighting Retrofit Process: Audit,

More information

3 WALL ASYMMETRIC W W W. L U M E N W E R X. C O M

3 WALL ASYMMETRIC W W W. L U M E N W E R X. C O M DESCRIPTION PROJECT: Via Wet offers architectural lighting for wet locations in both exterior and interior applications. With a simple TYPE: ¾" high by 4½" wide profile of NOTES: extruded aluminum, Via

More information

SHALO 3 LED RECESSED W W W. L U M E N W E R X. C O M

SHALO 3 LED RECESSED W W W. L U M E N W E R X. C O M PROJECT: TYPE: NOTES: shown with a Vee shaped optic shown with a trapezoid shaped optic DESCRIPTION Shalo - with a depth of 2.75" - provides a uniform luminous appearance without LED pixilation. Choose

More information

TENOCHCA HALL - FAN COIL UNITS, RESTROOM AND FINISH RENOVATION PROJECT NO

TENOCHCA HALL - FAN COIL UNITS, RESTROOM AND FINISH RENOVATION PROJECT NO SECTION 26 51 00 - INTERIOR LIGHTING PART 1 - GENERAL REQUIREMENTS 1.1 RELATED DOCUMENTS A. The general conditions, Division 1, and Basic Electrical Requirements (Section 26 05 00) are part of this section

More information

COMcheck Software Version Interior Lighting Compliance Certificate

COMcheck Software Version Interior Lighting Compliance Certificate COMcheck Software Version 4.0.6.0 Interior Lighting Compliance Certificate Project Information Energy Code: Project Type: 2012 IECC New Construction Construction Site: 224 First Ave Eaton, CO 80615 Additional

More information

LEDs WHAT ARE THE OPTIONS? Published on Business Energy Advisor (

LEDs WHAT ARE THE OPTIONS? Published on Business Energy Advisor ( Published on Business Energy Advisor (https://ouc.bizenergyadvisor.com) Home > LEDs LEDs Light-emitting diode (LED) technology is rapidly improving and becoming more common in business settings. Although

More information

DEEMED SAVINGS TECHNICAL ASSUMPTIONS

DEEMED SAVINGS TECHNICAL ASSUMPTIONS Product: Prescriptive rebates will be offered for replacement lighting equipment. New Construction rebates will be offered for new facilities or spaces overhauled for a new purpose. Custom rebates are

More information

Applying the Latest Technologies for Superior Lighting: New Applications of the Advanced Lighting Guidelines, 2003 Edition

Applying the Latest Technologies for Superior Lighting: New Applications of the Advanced Lighting Guidelines, 2003 Edition Applying the Latest Technologies for Superior Lighting: New Applications of the Advanced Lighting Guidelines, 2003 Edition David E. Weigand, New Buildings Institute, Inc. James Benya, Benya Lighting Design

More information

Driver Info. Construction Thermal Management: Superior thermal management with die-cast aluminum heatsink. Ambient Temperature:

Driver Info. Construction Thermal Management: Superior thermal management with die-cast aluminum heatsink. Ambient Temperature: WP2LED37 Project: Type: Prepared By: Date: Affordable 37W and 24W LED wallpacks with traditional look. 100,000 hour L70 lifespan. 5-Year Warranty. Color: Bronze Weight: 9.6 lbs Driver Info Type: Constant

More information

Catalog # Project. Comments. Prepared by. Warranty Five year warranty mm mm mm mm

Catalog # Project. Comments. Prepared by. Warranty Five year warranty mm mm mm mm DESCRIPTION The Define series by Neo-Ray characterizes the ultimate in minimalist simplicity by providing clean, uniform lines of illumination in virtually any architectural environment. Powered by s most

More information

Lighting and sensors: Reducing energy costs in commercial buildings

Lighting and sensors: Reducing energy costs in commercial buildings Lighting and sensors: Reducing energy costs in commercial buildings Brochure Commercial lighting countless opportunities for energy efficiency in the office R educing energy use makes perfect business

More information

Business lighting guide

Business lighting guide Business lighting guide Table of contents Advantages of energy-efficient lighting... Take Control & Save Business Lighting Program overview... Implementation and lighting audit walk-through... Introduction

More information