1 Mould Investigation Loretto Abbey Catholic Secondary School 101 Mason Boulevard North York, Ontario Prepared for: Toronto Catholic District School Board Prepared by: Stantec Consulting Ltd Derry Road West, Suite 300 Mississauga, ON L5N 0B3 Project No.:

2 Table of Contents 1.0 INTRODUCTION SCOPE OF WORK LIMITATIONS OF SURVEY INDUSTRY STANDARDS AND GUIDELINES INVESTIGATIVE METHODOLOGY ASSESSMENT SAMPLING SUMMARY OF ASSESSMENT FINDINGS GENERAL CONDITIONS INTERIOR INSPECTION SURFACE SAMPLING AIR SAMPLING RECOMMENDATIONS CLOSURE... 7 LIST OF TABLES Table 1 Summary of Inspection... 3 Table 2 Tape Lift Sample Laboratory Analysis Results... 4 LIST OF APPENDICES APPENDIX A LABORATORY ANALYTICAL REPORT... A.1 Project No.: i

3 1.0 Introduction Stantec Consulting Ltd. (Stantec) was commissioned by Toronto Catholic District School Board to conduct a Mould Investigation at the building located at 101 Mason Boulevard in North York, Ontario. It is our understanding that water intrusion occurred in Room 110 of the school and musty odours have been noted by staff. The primary purpose of the assessment was to check if visible deposits on surfaces were mould growth, as well as to provide recommendations for the remediation if necessary. Michael Shortt and William MaddenMacavelia of Stantec conducted the limited mould assessment on September 23 and 24, This report outlines the findings of the assessment. 1.1 SCOPE OF WORK The following scope of work was undertaken: A visual inspection of suspect mould growth on surfaces; Collection of air samples (2 samples indoors, 1 outdoor reference) for submission to an independent laboratory for analysis; and Collection of two (2) bulk/tapelift samples of building materials exhibiting suspect mould growth within the subject areas for submission to an independent laboratory for analysis to identify the mould forms present in the sample submitted. 1.2 LIMITATIONS OF SURVEY The information and observations contained within this report are based on visual assessments of the interior surfaces of the building (i.e., walls, ceilings and floors), as well as laboratory analysis. The conclusions given in this report are based on data obtained during the assessment and can only be extrapolated to an undefined limited area surrounding the sample locations. This assessment does not constitute a building envelope/building systems assessment, which would include an intrusive investigation to assess the internal condition, potential moisture sources, and expected remaining service life of the various components and systems comprising the envelope of a building. Therefore, conclusions made in this report will offer observed and/or potential sources of moisture leading to observed suspect and/or confirmed mould growth and water staining within the subject areas. These conclusions will not necessarily provide the only sources of moisture within the subject areas leading to suitable conditions for mould growth. Project No.:

4 2.0 Industry Standards and Guidelines The scope of work and assessment are based on the recommendations provided in the following documents: Mould Guidelines for The Canadian Construction Industry, Canadian Construction Association 82, 2004 Mould Abatement Guidelines, Environmental Abatement Council of Ontario, Edition 2, 2010 Guidelines on Assessment and Remediation of Fungi in Indoor Environment, New York City Department of Health and Mental Hygiene, November 2008 Bioaerosols: Assessment and Control, American Conference of Governmental Industrial Hygienists (ACGIH), 1999 Fungal Contamination in Public Buildings: Health Effects and Investigation Methods, Federal Provincial Committee on Environmental and Occupational Health, 2004 Field Guide for the Determination of Biological Contaminants in Environmental Samples, American Industrial Hygiene Association (AIHA), 1996 CleanUp Procedures for Mould in Houses, Canada Mortgage and Housing Corporation (CMHC), 2004 Standard and Reference Guide for Professional Water Damage Restoration IICRC S500, Institute of Inspection, Cleaning and Restoration Certification, 2006 Standard and Reference Guide for Professional Mould Remediation IICRC S520, Institute of Inspection, Cleaning and Restoration Certification, / Investigative Methodology 3.1 ASSESSMENT An inspection of the accessible surfaces of the subject areas was completed by Stantec to identify areas where suspect mould was most likely to proliferate (i.e., areas where water damage/staining was visible on building material surfaces). Tape lift sampling was undertaken in selected areas to assess the presence and extent of mould growth on the material where the sample was collected from (refer to Table 1 for findings). Air sampling was also conducted to identify the presence of suspected mould amplifiers within the subject area. 3.2 SAMPLING Samples were analyzed by Sporometrics Inc. of Toronto. Sporometrics has been accredited by the American Industrial Hygiene Association (AIHA) Environmental Microbiology Laboratory Accreditation Program and participates in the AIHA Environmental Microbiology Proficiency Analytical Testing (EMPAT) Program. Sporometrics analysts are certified by the PanAmerican Aerobiology Certification Board. Project No.:

5 The tape lift sample was collected using an optically clear tape. Approximately 5 cm of tape was pressed firmly against the surfaces showing evidence of suspect mould growth. The tape lift was then affixed on the interior side of a separate labeled plastic bag that was sealed and submitted for analysis to the laboratory. Individual air samples for analysis of fungal elements were collected over a fiveminute period, using an SKC Quick Take TM 15, air sampling pump (calibrated to operate at 15 litres per minute) with an AllergencoD TM Air Sampling cassette. This sampling device impacts airborne particles onto a glass slide contained within the cassette housing called the trace. The cassette housing is designed to distribute and deposit the airborne particles equally on the trace. The results are airborne mould spore counts expressed in spores per cubic metre (spores/m 3 ) for each of the identified organisms. The AllergencoD TM method of air sampling is better suited for measuring fungal elements that may be underestimated or missed through viable sampling methods (such as Stachybotrys). 4.0 SUMMARY OF ASSESSMENT FINDINGS 4.1 GENERAL CONDITIONS It is our understanding that musty odours as well as potential water intrusion have occurred in Room 110 of the school. The area of concern includes Music Room 110, specifically underneath the hatch of a sump pump. Stained ceiling tiles were observed in the corridor and change rooms, however, suspect water damage or fungal growth was not observed above ceiling spaces. 4.2 INTERIOR INSPECTION A summary of observations made during the assessment of the subject areas is presented in Table 1 below, including site photographs. Table 1 Summary of Inspection Room Observations Photograph Music Room 110 Distinct damp smell to the room Stream runs alongside exterior of the windows Windows have flaking paint, but no indication of mould growth No indication of flooding from pipes above ceiling Project No.:

6 Room Observations Photograph Music Room 110 Entrance 10 sq m of tiles replaced 7 months ago near room entrance due to reported flooding No stained tiles observed Sump Pump Sump pump used to keep stream from flooding when it rises Moisture was observed along the underside of the hatch 4.3 SURFACE SAMPLING Two (2) tape lift samples were collected. Results of the analysis are noted in Table 2, below: Table 2 Tape Lift Sample Laboratory Analysis Results Sample No. Location Microscopic Observations Rating 101T01 101T02 Underside of North Floor Hatch Window of Earth Wall (Music Room 110) Alternaria mycelia NOS Alternaria spores NOS Aspergillus / Penicillium mycelia NOS Aspergillus / Penicillium spores NOS Cladosporium mycelia NOS Cladosporium spores NOS Alternaria mycelia NOS Alternaria spores NOS Aspergillus / Penicillium mycelia NOS Aspergillus / Penicillium spores NOS Cladosporium mycelia NOS Cladosporium spores NOS tr Growth Indicated Y Y Project No.:

7 Key: + = not observed; tr = elements in total; 1+ = elements in each of ~ 25% fields; 2+ = elements in each of ~50% fields; 3+ = elements in each of ~75% fields; 4+ = >75% fields obscured; Possibility of fungal growth in situ based on microscopic observations; Y = yes; N = no;? = ambiguous. 4.4 AIR SAMPLING Two spore trap samples (2 samples indoors, 1 outdoor reference) were collected. Results of the analysis are noted in Table 3, below: Table 3 Spore Trap Sample Laboratory Analysis Results Sample No. Location Fungal Identification 101M01 Outside Alternaria NOS 101M02 101M03 Music Room #110 North Side Music Room #110 South Side Ascospores NOS Aspergillus / Penicillium NOS Basidiospores NOS Cladosporium NOS Hyphal fragments, pigmented Myxomycete / smut spores NOS Polythrincium NOS Rust spores NOS Alternaria NOS Ascospores NOS Aspergillus / Penicillium NOS Basidiospores NOS Cladosporium NOS Hyphal fragments, pigmented Myxomycete / smut spores NOS Polythrincium NOS Rust spores NOS Alternaria NOS Ascospores NOS Aspergillus / Penicillium NOS Basidiospores NOS Cladosporium NOS Hyphal fragments, pigmented Myxomycete / smut spores NOS Polythrincium NOS Rust spores NOS TOTAL TOTAL (Raw Count) (elements/m 3 ) (1) 260 (4) 1100 (89) (7) 1800 (tr) tr (tr) tr (3) 230 (104) 7800 (1) 75 (tr) tr (2) 110 (14) 740 (51) 2700 (3) 160 (1) 53 (tr) tr (tr) tr Project No.:

8 Key: tr = observed outside of enumerated transects = not detected Total elements / m 3 expressed at two significant digits Negative bias increases with increasing background rating NOS = Not otherwise specified Background ratings: 0+ = no particulate matter detected, 1+ = >0 to approx. 5% 2+ = approx. 5% to 25% 3+ = approx. 25% to 75% 4+ = approx. 75% to 90% 5+ =>90% Aspergillus/Penicillium was not in the outdoor sample, but was identified in the sample collected at south side of Music Room 110. The profile and concentration of mould species detected in the air samples are consistent with the mould growth identified on the floor hatch. A copy of the laboratory Certificate of Analysis is provided in Appendix A. 5.0 Recommendations Based on the findings and conclusions made during the assessment, Stantec recommends that mould impacted materials (North floor hatch and window of earth wall in Music Room 110) should be removed or cleaned following procedures outlined in the Canadian Construction Association document Mould Guidelines for the Canadian Construction Industry During the removal, additional inspection of the materials should be conducted to determine the extent of mould growth. Project No.:

9 6.0 Closure This report has been prepared for the sole benefit of Toronto Catholic District School Board. The report may not be used by any other person or entity without the express written consent of Stantec Consulting Ltd. and Toronto Catholic District School Board. Any use which a third party makes of this report, or any reliance on decisions made based on it, is the responsibility of such third parties. Stantec Consulting Ltd. accepts no responsibility for damages, if any, suffered by any third party as a result of decisions made or actions based on this report. Some of the information presented in this report was provided through existing documents and through interviews. Although attempts were made, whenever possible, to obtain confirmatory sources of information, Stantec Consulting Ltd. in certain instances has been required to assume the information provided is accurate. The information and conclusions contained in this report are based upon work undertaken by trained professional and technical staff in accordance with generally accepted engineering and scientific practices current at the time the work was performed. Conclusions presented in this report should not be construed as legal advice. The conclusions presented in this report represent the best technical judgment of Stantec Consulting Ltd. based on the data obtained from the work. The conclusions are based on the site conditions encountered by Stantec Consulting Ltd. at the time the work was performed at the specific inspection and/or sampling locations, and can only be extrapolated to an undefined limited area around these locations. The extent of the limited area depends on building construction and conditions, weather, building usage and other factors. In addition, analysis has been carried out for mould on a limited number of samples, and it should not be inferred that other mould species are not present. Due to the nature of the assessment and the limited data available, Stantec Consulting Ltd. cannot warrant against undiscovered environmental liabilities. If any conditions become apparent that differ significantly from our understanding of conditions as presented in this report, we request that we be notified immediately to reassess the conclusions provided herein. We trust that the above is satisfactory for your purposes at this time. Should you have any questions or concerns, or require additional information, please do not hesitate to contact the undersigned at your convenience. Project No.:

10 This report was prepared by Christopher Benedetti and reviewed by Rob Robinson. Regards, STANTEC CONSULTING LTD. Christopher Benedetti, B.Sc. Hons. Technician Phone: (905) Fax: (905) Rob Robinson, P.Eng. Principal Phone: (905) Fax: (905) CB/RR/mh \\cd1216f06\work_group\01691\active\ \reports\ _rpt_cb_2014sep29_tcdsb_final.docx Project No.:

11 Appendix A Laboratory Analytical Report Project No.: A.1

12 Sporometrics Inc. 219 Dufferin Street, Suite 20C, Toronto, ON M6K 1Y9 t f RESULTS OF LABORATORY ANALYSES: JOB NO To: Katherine Spence Date of report: 2014/09/27 Company: Stantec Consulting Ltd. Mississauga, ON Date of sampling: 2014/09/24 Client Project: Analyst: Yordanka Gonzalez Guardiola Client Address: Derry Road West, Mississauga, ON L5N 0B3 Date Received: 2014/09/26 SPORE TRAP SAMPLE NO.: a 101M01 101M02 101M03 Location: Outside Music Room #110 North Side Music Room #110 South Side Serial #: Expiry date: 2015/ / /08 Volume (L): Magnification (x): Background (rating) b : No. of transects enumerated: FUNGAL IDENTIFICATION c : COMPOSITION (raw count) approx. elements / m 3 d Alternaria NOS (1) 260 (tr) tr ascospores NOS (4) 1100 (3) 230 (2) 110 Aspergillus / Penicillium NOS (14) 740 basidiospores NOS (89) (104) 7800 (51) 2700 Cladosporium NOS (7) 1800 (1) 75 (3) 160 hyphal fragments, pigmented (tr) tr myxomycete / smut spores NOS (1) 53 Polythrincium NOS (tr) tr rust spores NOS (tr) tr (tr) tr SUMMARY DATA e : TOTAL (raw count) LOD (elements / m 3 ) TOTAL (elements / m³) 27,000 8,100 3,700 AIHA LAP, LLC LAB NO: Samples were received in satisfactory condition and tested in accordance with SOP These results relate only to the samples tested. a Analysis compliant with ASTM D Standard Test Method for Categorization and Quantification of Airborne Fungal Structures in an Inertial Impaction Sample by Optical Microscopy. Note that samples with excessive spore counts or background (4+ or higher) are unsuitable for ASTM compliant analysis. b Rating (amount of trace occluded with particulate matter): 0+ = no particulate matter detected, 1+ = >0 to approx. 5%, 2+ = approx. 5% to 25%, 3+ = approx. 25% to 75%, 4+ = approx. 75% to 90%, 5+ = >90%, Negative bias increases with increasing background rating. c Identification to genus level, taxonomic group or morphological category, where appropriate; NOS = Not otherwise specified. d Evaluated in Nomarski Differential Interference Contrast (DIC) microscopy; tr = observed outside of enumerated transects; = not detected. e Total elements / m 3 expressed at two significant digits; LOD = Limit of detection; NFEO = No fungal elements observed. SPOROMETRICS PAGE 1 OF 4

13 Sporometrics Inc. 219 Dufferin Street, Suite 20C, Toronto, ON M6K 1Y9 t f RESULTS OF LABORATORY ANALYSES: JOB NO To: Katherine Spence Date of report: 2014/09/27 Company: Stantec Consulting Ltd. Mississauga, ON Date of sampling: 2014/09/24 Client Project: Analyst: Yordanka Gonzalez Guardiola Client Address: Derry Road West, Mississauga, ON L5N 0B3 Date Received: 2014/09/26 BULK / TAPELIFT / BIOTAPE SAMPLE NO.: 101T01 101T02 Location: Underside of North Floor Hatch Window of Earth Wall (Music Room 110) Serial #: Expiry date: 2020/ /01 FUNGAL IDENTIFICATION: a ELEMENTS: MICROSCOPIC OBSERVATIONS b (RATING c ): Alternaria NOS mycelia spores tr Aspergillus / Penicillium NOS mycelia spores 2+ Cladosporium NOS mycelia OTHER OBSERVATIONS: spores background rating FUNGAL GROWTH INDICATED? d : Y Y AIHA LAP, LLC LAB NO: Samples were received in satisfactory condition and tested in accordance with SOP These results relate only to the samples tested. a NOS = not otherwise specified. b Mounted in lactofuchsin / lactic acid, or other medium as required, with fields examined in bright field microscopy at 400x magnification. c = not detected; tr = elements in total; 1+ = elements in each of ~25% fields; 2+ = elements in each of ~50% fields; 3+ = elements in each of ~75 fields; 4+ => 75% fields obscured. d Possibility of fungal growth in situ based on microscopic observations; Y = yes; N = no;? = ambiguous. For explanation please refer to the final page of this report. SPOROMETRICS PAGE 2 OF 4

14 Sporometrics Inc. 219 Dufferin Street, Suite 20C, Toronto, ON M6K 1Y9 t f RESULTS OF LABORATORY ANALYSES: JOB NO To: Katherine Spence Date of report: 2014/09/27 Company: Stantec Consulting Ltd. Mississauga, ON Date of sampling: 2014/09/24 Client Project: Analyst: Yordanka Gonzalez Guardiola Client Address: Derry Road West, Mississauga, ON L5N 0B3 Date Received: 2014/09/26 END OF REPORT Examined By Released By Yordanka Gonzalez Guardiola, MSc Analyst Mike Saleh, MHSc Analyst SPOROMETRICS PAGE 3 OF 4

15 Sporometrics Inc. 219 Dufferin Street, Suite 20C, Toronto, ON M6K 1Y9 t f RESULTS OF LABORATORY ANALYSES: JOB NO To: Katherine Spence Date of report: 2014/09/27 Company: Stantec Consulting Ltd. Mississauga, ON Date of sampling: 2014/09/24 Client Project: Analyst: Yordanka Gonzalez Guardiola Client Address: Derry Road West, Mississauga, ON L5N 0B3 Date Received: 2014/09/26 Guidance on the interpretation of microscopic findings Samples of bulk materials as well as tape lift samples from potentially contaminated surfaces may be examined microscopically to assess the potential of these materials to be supporting fungal growth and serving as indoor fungal amplification sites. Guidelines on indoor microbial contamination proposed by Health Canada (HC Indoor air quality in office buildings: A technical guide. FederalProvincial Advisory Committee on Environmental and Occupational Health. Ottawa: Environmental Health Directorate 93EHD166 rev.) state unambiguously that indoor, active fungal growth sites are unacceptable regardless of the extent to which these amplifiers impact on the indoor airborne sporeload. Fungal spores are commonly borne on air currents and settle on flat surfaces as a matter of course. Thus, the observation of fungal spores alone is insufficient to characterize a specimen as a growth site. This judgment primarily requires the microscopic visualization of fungal filaments ("hyphae", or en masse, "mycelia"). Additionally, the identification of different kinds of fungi usually requires the observation of spores (e.g. conidia, ascospores, etc.) along with the organs responsible for their production (e.g. conidiophores, ascomata, etc.). However, the latter rarely persist long after the spores have been produced, making definitive identification difficult or impossible in aged specimens. The rating system used by Sporometrics to score the frequency of structures observed microscopically is based on a 5point assessment of microscopic fields, usually taken at 400 x magnification. This system uses the following rating criteria: Descriptor Criteria (based on fields) Interpretation of growth in situ according to observations: Spores alone Spores and sporebearing structures or mycelia tr 10º10¹ elements in total growth not indicated growth not indicated 1+ 10º10¹ elements per ~25% fields unclear growth indicated 2+ 10¹10² elements per ~50% fields growth indicated growth indicated 3+ 10²10³ elements per ~75% fields growth indicated growth indicated 4+ > 75% fields obscured by elements growth indicated growth indicated SPOROMETRICS PAGE 4 OF 4

Birmingham 2080 Valleydale Road Suite 16 Birmingham, AL f: t:

Birmingham 2080 Valleydale Road Suite 16 Birmingham, AL f: t: Birmingham 2080 Valleydale Road Suite 16 Birmingham, AL 35244 t: 205.986.0270 Decatur 717 Highway 67 South Suite 26 Decatur, AL 35603 t: 256.353.6222 Florence 4050 Helton Drive Suite 111 Florence, AL 35633

More information

S outhwest GEOSCIENCE. Analytical Results/Chain of Custody

S outhwest GEOSCIENCE. Analytical Results/Chain of Custody S outhwest GEOSCIENCE Analytical Results/Chain of Custody Steve Moody Micro Services, LLC 2051 Valley View Lane Farmers Branch, TX 75234 Phone: (972) 241-8460 IAQ Mold Report Summary DSHS License No.:

More information

Table 1: Fungal Particulate Air Sample Results. ST-32 Room 17; post clean-up 5. 2 nd floor; commons area adjacent to Room 617

Table 1: Fungal Particulate Air Sample Results. ST-32 Room 17; post clean-up 5. 2 nd floor; commons area adjacent to Room 617 November 29, 2016 Chuck Doan Yakima School District #7 104 N 4th Avenue Yakima, WA 98902 Via email: Regarding: doan.chuck@yakimaschools.org Fungal Sample Results Blue Wall Room 617 Eisenhower High School

More information

Birmingham 2080 Valleydale Road Suite 16 Birmingham, AL f: t:

Birmingham 2080 Valleydale Road Suite 16 Birmingham, AL f: t: Birmingham 2080 Valleydale Road Suite 16 Birmingham, AL 35244 t: 205.986.0270 Decatur 717 Highway 67 South Suite 26 Decatur, AL 35603 t: 256.353.6222 Florence 4050 Helton Drive Suite 111 Florence, AL 35633

More information

Healthy Home Package: Asbestos & Mould Sampling Report

Healthy Home Package: Asbestos & Mould Sampling Report Healthy Home Package: Asbestos & Mould Sampling Report Client s Address Toronto, ON Postal Code Prepared for: Client s Name Prepared by: Lilja Palsson, B.Sc., Dip. Eng., CRSP Project Number: #### LEAP

More information

INTRODUCTION: METHODOLOGY: November 4, Mr. Tom Heinz 353 West Sawgrass Dakota Dunes, SD 57049

INTRODUCTION: METHODOLOGY: November 4, Mr. Tom Heinz 353 West Sawgrass Dakota Dunes, SD 57049 November 4, 2011 Mr. Tom Heinz 353 West Sawgrass Dakota Dunes, SD 57049 Re: Project #: 4004-050 353 West Sawgrass, Dakota Dunes SD Microbial Clearance Testing INTRODUCTION: This report presents the findings

More information

ANALYSIS OF FUNGI (MOLD) IN THE INDOOR ENVIRONMENTS BY DIRECT MICROSCOPIC EXAMINATION. (Analysis Code: FDE)

ANALYSIS OF FUNGI (MOLD) IN THE INDOOR ENVIRONMENTS BY DIRECT MICROSCOPIC EXAMINATION. (Analysis Code: FDE) Expert Services in Environmental Microbiology Report Supporting Document ANALYSIS OF FUNGI (MOLD) IN THE INDOOR ENVIRONMENTS BY DIRECT MICROSCOPIC EXAMINATION (Analysis Code: FDE) INTRODUCTION Fungi are

More information

Professional remediation of the school began on the weekend of October 5, 2013 and is due to continue until the entire building can be remediated.

Professional remediation of the school began on the weekend of October 5, 2013 and is due to continue until the entire building can be remediated. 1805 Atlantic Avenue Manasquan, New Jersey 08736 Tel: (732) 223-2225 www.brinkenv.com November 4, 2013 Mr. Robert Vogel, Facilities Manager Brick Township Public Schools 346 Chambers Bridge Road Brick,

More information

INTRODUCTION: METHODOLOGY: November 11, Mr. Tim Squier 487 Deerfield Dakota Dunes, SD 57049

INTRODUCTION: METHODOLOGY: November 11, Mr. Tim Squier 487 Deerfield Dakota Dunes, SD 57049 November 11, 2011 Mr. Tim Squier 487 Deerfield Dakota Dunes, SD 57049 Re: Project #: 4004-040 487 Deerfield, Dakota Dunes SD Microbial Clearance Testing INTRODUCTION: This report presents the findings

More information

No dry drains/traps were found, eliminating a potentially concern for odors.

No dry drains/traps were found, eliminating a potentially concern for odors. January 5, 2017 Ms. Alix Zapolski Zapolski Real Estate, LLC. 501 Washington Street Durham, NC 27701 Re: Limited Indoor Air Quality Assessment Women s Restroom 137 E. Franklin Street, Chapel Hill, NC UNC

More information

Report of Limited Indoor Air Quality Services

Report of Limited Indoor Air Quality Services Report of Limited Indoor Air Quality Services Lincoln School 1601 State Street Harrisburg, Pennsylvania 17103 Prepared For: Harrisburg School District 1601 State Street Harrisburg, Pennsylvania 17103 February

More information

April 4, AHERA / Environmental Inspector Environmental Safety Office Old Marlboro Pike Upper Marlboro, MD 20772

April 4, AHERA / Environmental Inspector Environmental Safety Office Old Marlboro Pike Upper Marlboro, MD 20772 April 4, 2017 Mr. Alex Baylor AHERA / Environmental Inspector Environmental Safety Office 13306 Old Marlboro Pike Upper Marlboro, MD 20772 via email: alex.baylor@pgcps.org RE: Indoor Air Quality (IAQ)

More information

TN Tatem Middle School Indoor Air Quality Assessment September 2016

TN Tatem Middle School Indoor Air Quality Assessment September 2016 TN Tatem Middle School Indoor Air Quality Assessment September 2016 Completed by Island Air Quality Services P.O. Box SN139 Southampton SNBX Bermuda Table of Contents 1 Report Summary... 1 2 Introduction

More information

MARTIN AND WILLIAMSON HALL BUILDINGs Eastern Washington University, Cheney, Washington INDOOR AIR QUALITY SAMPLING PLAN

MARTIN AND WILLIAMSON HALL BUILDINGs Eastern Washington University, Cheney, Washington INDOOR AIR QUALITY SAMPLING PLAN MARTIN AND WILLIAMSON HALL BUILDINGs Eastern Washington University, Cheney, Washington INDOOR AIR QUALITY SAMPLING PLAN Prepared for Eastern Washington University Facilities and Planning Department 101

More information

December 28, Lewisville Independent School District 340 Lake Haven Lewisville, Texas Attn: Mr. Paul Siddall

December 28, Lewisville Independent School District 340 Lake Haven Lewisville, Texas Attn: Mr. Paul Siddall December 28, 2015 Lewisville Independent School District 340 Lake Haven Lewisville, Texas 75057 Attn: Mr. Paul Siddall Re: Limited Mold Assessment Services Prairie Trail Elementary School Room 113 5555

More information

Report of Limited Indoor Air Quality Services

Report of Limited Indoor Air Quality Services Report of Limited Indoor Air Quality Services 301 Hale Street Harrisburg, Pennsylvania 17104 Prepared For: Harrisburg School District 1601 State Street Harrisburg, Pennsylvania 17103 February 2015 February

More information

MOLD SCREENING REPORT

MOLD SCREENING REPORT MOLD SCREENING REPORT Mount Washington Middle School 269 Water Street Mt. Washington, KY 40047 Project # 115-7358 Prepared for: Mr. Mark Mitchell Director, Buildings and Grounds Bullitt County Board of

More information

Airborne Mould Spore Assessment and Inspections

Airborne Mould Spore Assessment and Inspections Sterling IAQ Consultants Ltd. Suite 310-1122 Mainland Street Vancouver, B.C., V6B 5L1 (t) 604.681.2701 (f) 604.681.2702 www.sterlingiaqconsultants.com Airborne Mould Spore Assessment and Inspections Sungod

More information

SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD PREPARED FOR:

SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD PREPARED FOR: SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD 21738 PREPARED FOR: HOWARD COUNTY PUBLIC SCHOOL SYSTEM 10910 ROUTE 108 ELLICOTT CITY, MD 21043 PREPARED BY: ARIA ENVIRONMENTAL,

More information

DATE: December 10, TO: Jim Baker, Principal. SUBJECT: DeLay MS - IAQ - Request for Air Test - Room 222

DATE: December 10, TO: Jim Baker, Principal. SUBJECT: DeLay MS - IAQ - Request for Air Test - Room 222 DATE: December 10, 2013 TO: Jim Baker, Principal SUBJECT: DeLay MS - IAQ - Request for Air Test - Room 222 Received your E-mail this morning 12/10, and set up Work Order #172809: We had a leak in a class

More information

NCCEH Mould Investigation Toolkit

NCCEH Mould Investigation Toolkit NCCEH Mould Investigation Toolkit Interpretation of Microbial Laboratory Reports NOVEMBER 2014 Table of Contents Introduction... 2 Generic Information All Microbial Laboratory Reports... 3 Direct Examination

More information

Via . September 5, City of Charlotte Engineering & Property Management 600 E. 4 th Street, 12 th Floor Charlotte, NC

Via  . September 5, City of Charlotte Engineering & Property Management 600 E. 4 th Street, 12 th Floor Charlotte, NC Via Email September 5, 2014 City of Charlotte Engineering & Property Management 600 E. 4 th Street, 12 th Floor Charlotte, NC 28204-2844 Attention: Mr. David Wolfe, PE Re: Moisture Screening and Mold Air

More information

Report of Limited Indoor Air Quality Services

Report of Limited Indoor Air Quality Services Report of Limited Indoor Air Quality Services Camp Curtin School 2900 North 6th Street Harrisburg, Pennsylvania 17110 Prepared For: Harrisburg School District 1601 State Street Harrisburg, Pennsylvania

More information

DATE: October 30, TO: Curtis Martin, Principal. SUBJECT: Hicks ES - IAQ - Air Test Report - Rooms E-209 & E-222

DATE: October 30, TO: Curtis Martin, Principal. SUBJECT: Hicks ES - IAQ - Air Test Report - Rooms E-209 & E-222 DATE: October 30, 2018 TO: Curtis Martin, Principal SUBJECT: Hicks ES - IAQ - Air Test Report - Rooms E-209 & E-222 On Thursday 10/25, Apex-Titan Air tested Rooms E-209 and E-222. It is typically assumed

More information

SPORE TRAP SAMPLING REPORT FOR CENTENNIAL LANE ELEMENTARY SCHOOL 3825 CENTENNIAL LANE ELLICOTT CITY, MARYLAND PREPARED FOR:

SPORE TRAP SAMPLING REPORT FOR CENTENNIAL LANE ELEMENTARY SCHOOL 3825 CENTENNIAL LANE ELLICOTT CITY, MARYLAND PREPARED FOR: SPORE TRAP SAMPLING REPORT FOR CENTENNIAL LANE ELEMENTARY SCHOOL 3825 CENTENNIAL LANE ELLICOTT CITY, MARYLAND 21042 PREPARED FOR: HOWARD COUNTY PUBLIC SCHOOL SYSTEM 10910 ROUTE 108 ELLICOTT CITY, MD 21043

More information

DATE: May 13, TO: Patricia Cuckler, Principal. SUBJECT: Hedrick ES - IAQ - Air Test Results - Room 206

DATE: May 13, TO: Patricia Cuckler, Principal. SUBJECT: Hedrick ES - IAQ - Air Test Results - Room 206 DATE: May 13, 2014 TO: Patricia Cuckler, Principal SUBJECT: Hedrick ES - IAQ - Air Test Results - Room 206 On Wednesday 5/7, SWG Air tested the Room 206. It is typically assumed that indoor spore levels

More information

DATE: June 4, TO: Randall Holder, Associate Principal

DATE: June 4, TO: Randall Holder, Associate Principal DATE: June 4, 2018 TO: Randall Holder, Associate Principal SUBJECT: Dale Jackson Career Center - IAQ - Air Test Results - Hallway Outside Wood Manufacturing and Tech On Thursday 5/24, Apex-Titan Air tested

More information

DATE: October 21, TO: Susan Blockley, Director

DATE: October 21, TO: Susan Blockley, Director DATE: October 21, 2013 TO: Susan Blockley, Director SUBJECT: Campus Support Services-Charles Street - IAQ - Air Test - Storage Rm- Southwest Corner Rm, Martha Fahlund's Office, Storage Rm-Northwest Corner

More information

November 18, Subject Property: Terramar Elementary School 7000 West Happy Valley Road Peoria, Arizona PO#

November 18, Subject Property: Terramar Elementary School 7000 West Happy Valley Road Peoria, Arizona PO# Asbestos Testing Lead Testing Microbial Testing Management Analysis Environmental Assessment November 18, 2014 Attn: Deer Valley Unified School District Jim Migliorino 20402 North 15th Avenue Phoenix,

More information

FILED: NEW YORK COUNTY CLERK 07/14/ :42 PM INDEX NO /2016 NYSCEF DOC. NO. 25 RECEIVED NYSCEF: 07/14/2016

FILED: NEW YORK COUNTY CLERK 07/14/ :42 PM INDEX NO /2016 NYSCEF DOC. NO. 25 RECEIVED NYSCEF: 07/14/2016 FILED: NEW YORK COUNTY CLERK 07/14/2016 01:42 PM INDEX NO. 154125/2016 NYSCEF DOC. NO. 25 RECEIVED NYSCEF: 07/14/2016 Project: Post-Mold Remediation Verification Survey Location: 1045 Park Avenue Apt.

More information

DATE: March 23, TO: Chad Russell, Principal. SUBJECT: Lamar MS - IAQ - Air Test Results - Main Gym

DATE: March 23, TO: Chad Russell, Principal. SUBJECT: Lamar MS - IAQ - Air Test Results - Main Gym DATE: March 23, 2018 TO: Chad Russell, Principal SUBJECT: Lamar MS - IAQ - Air Test Results - Main Gym On Monday 3/19, Apex-Titan Air tested the Main Gym. It is typically assumed that indoor spore levels

More information

Table of Contents. C. Recommended Remediation Firms: upon request

Table of Contents. C. Recommended Remediation Firms: upon request Table of Contents I. Job, Contact & Site Information II. Scope of Work III. Building Overview IV. Findings V. Conclusions and Recommendations VI. Expectations VII. References VIII. Limits of Liability

More information

DATE: September 29, TO: Michael Wetchensky, Assistant Principal. SUBJECT: Rockbrook ES - IAQ - Initial Contact - Room 511

DATE: September 29, TO: Michael Wetchensky, Assistant Principal. SUBJECT: Rockbrook ES - IAQ - Initial Contact - Room 511 DATE: September 29, 2016 TO: Michael Wetchensky, Assistant Principal SUBJECT: Rockbrook ES - IAQ - Initial Contact - Room 511 This morning 9/29, I was following up on W.O. #334260: The room smells of mildew

More information

October 14, Subject Property: Terramar Elementary School 7000 West Happy Valley Road Peoria, Arizona PO#

October 14, Subject Property: Terramar Elementary School 7000 West Happy Valley Road Peoria, Arizona PO# Asbestos Testing Lead Testing Microbial Testing Management Analysis Environmental Assessment October 14, 2014 Attn: Deer Valley Unified School District Jim Migliorino 20402 North 15th Avenue Phoenix, Arizona

More information

Post Remediation Verification For 845 W. Center Street Pocatello, Idaho

Post Remediation Verification For 845 W. Center Street Pocatello, Idaho Post Remediation Verification For 845 W. Center Street Pocatello, Idaho Prepared for: Bank of the Cascades 1070 NW Bond Street, Suite 212 Bend, Oregon 97701 Prepared By: Summit 795 S. Orchard Street Boise,

More information

May 1 st, University of Toronto 255 McCaul Street, Level 4 Toronto, Ontario M5T 1W7

May 1 st, University of Toronto 255 McCaul Street, Level 4 Toronto, Ontario M5T 1W7 May 1 st, 2018 University of Toronto 255 McCaul Street, Level 4 Toronto, Ontario M5T 1W7 Attn: Mr. Irfan Miraj, P.Eng., MHSc. Manager, Hazardous Construction Materials Group Re: Results of PCM and TEM

More information

DATE: February 28, TO: Robin Fry, Principal. SUBJECT: Polser ES - IAQ - Air Test - Room 200, 210 & Hallway outside 210

DATE: February 28, TO: Robin Fry, Principal. SUBJECT: Polser ES - IAQ - Air Test - Room 200, 210 & Hallway outside 210 DATE: February 28, 2014 TO: Robin Fry, Principal SUBJECT: Polser ES - IAQ - Air Test - Room 200, 210 & Hallway outside 210 I received your E-mail on February 24, in regards to Room 210. When we looked

More information

Post Remediation Testing Site Evaluation with Environmental Sampling

Post Remediation Testing Site Evaluation with Environmental Sampling Nationwide Locations Locally Served Corporate Headquarters: 7700 Congress Avenue Suite 1119 Boca Raton, FL 33487 Industrial Hygiene IAQ/Mold Assessments Water Loss Projects Restoration Project Mgmt Post

More information

September 11, University of Toronto 255 McCaul Street, Level 4 Toronto, Ontario M5T 1W7

September 11, University of Toronto 255 McCaul Street, Level 4 Toronto, Ontario M5T 1W7 September 11, 2017 University of Toronto 255 McCaul Street, Level 4 Toronto, Ontario M5T 1W7 Attn: Mr. Irfan Miraj, P.Eng., MHSc. Manager, Hazardous Construction Materials Group Re: Results of PCM and

More information

DATE: March 21, TO: Martha Gooding, Principal. SUBJECT: Ethridge ES - IAQ - Initial contact - Room A-5

DATE: March 21, TO: Martha Gooding, Principal. SUBJECT: Ethridge ES - IAQ - Initial contact - Room A-5 DATE: March 21, 2014 TO: Martha Gooding, Principal SUBJECT: Ethridge ES - IAQ - Initial contact - Room A-5 On Tuesday 3/18, I received W.O. #180591: In A5 the teacher has mentioned that in the morning

More information

Dalrymple Consulting, Inc. "Your Environmental Engineering Source" 7841 SW 1 i b Street, Topeka, Kansas (785) FAX (785)

Dalrymple Consulting, Inc. Your Environmental Engineering Source 7841 SW 1 i b Street, Topeka, Kansas (785) FAX (785) Dalrymple Consulting, Inc. "Your Environmental Engineering Source" 7841 SW 1 i b Street, Topeka, Kansas 66615-1406 (785) 273-0345 FAX (785) 273-3071 January 10,2012 Mr. Steve Wiseman, Superintendent Atchison

More information

MOLD SCREENING REPORT

MOLD SCREENING REPORT MOLD SCREENING REPORT Mount Washington Middle School 269 Water Street Mt. Washington, KY 40047 Project # 115-7346 BCBOE PO#156081 Prepared for: Mr. Mark Mitchell Director, Buildings and Grounds Bullitt

More information

Assessment of Mould Growth Loretto Abbey Catholic Secondary School 101 Mason Boulevard Toronto, Ontario

Assessment of Mould Growth Loretto Abbey Catholic Secondary School 101 Mason Boulevard Toronto, Ontario Assessment of Mould Growth Loretto Abbey Catholic Secondary School 101 Mason Boulevard Toronto, Ontario Prepared for: Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario, M2N

More information

DATE: October 5, TO: Shawn Barr, Director. SUBJECT: Facility Services - IAQ - Air Test results - Jason Hughes' Office

DATE: October 5, TO: Shawn Barr, Director. SUBJECT: Facility Services - IAQ - Air Test results - Jason Hughes' Office DATE: October 5, 2017 TO: Shawn Barr, Director SUBJECT: Facility Services - IAQ - Air Test results - Jason Hughes' Office On Monday 10/2, Apex-Titan Air tested Jason Hughes Office. It is typically assumed

More information

February 8, Post-Remediation Fungal Assessment Blackhawk Intermediate School 603 Shenango Road Beaver Falls, PA PSI Project No.

February 8, Post-Remediation Fungal Assessment Blackhawk Intermediate School 603 Shenango Road Beaver Falls, PA PSI Project No. February 8, 2018 Blackhawk School District 500 Blackhawk Road Beaver Falls, PA 15010-1498 Attention: Dr. Robert Postupac, Superintendent postupacr@bsd.k12.pa.us Re: Post-Remediation Fungal Assessment Blackhawk

More information

DATE: September 6, TO: Tim Greenwell, Principal. SUBJECT: Liberty ES - IAQ Air Test Results - Room 423

DATE: September 6, TO: Tim Greenwell, Principal. SUBJECT: Liberty ES - IAQ Air Test Results - Room 423 DATE: September 6, 2017 TO: Tim Greenwell, Principal SUBJECT: Liberty ES - IAQ Air Test Results - Room 423 On Tuesday 8/29, Apex-Titan Air tested Rooms 423. It is typically assumed that indoor spore levels

More information

Post Remediation Testing Site Evaluation with Environmental Sampling

Post Remediation Testing Site Evaluation with Environmental Sampling Nationwide Locations Locally Served Corporate Headquarters: 7700 Congress Avenue Suite 1119 Boca Raton, FL 33487 Industrial Hygiene IAQ/Mold Assessments Water Loss Projects Restoration Project Mgmt Post

More information

March 29 th, University of Toronto 255 McCaul Street, Level 4 Toronto, Ontario M5T 1W7

March 29 th, University of Toronto 255 McCaul Street, Level 4 Toronto, Ontario M5T 1W7 March 29 th, 2017 University of Toronto 255 McCaul Street, Level 4 Toronto, Ontario M5T 1W7 Attn: Mr. Irfan Miraj, P.Eng., MHSc. Manager, Hazardous Construction Materials Group Re: Results of PCM and TEM

More information

SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD PREPARED FOR:

SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD PREPARED FOR: SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD 21738 PREPARED FOR: HOWARD COUNTY PUBLIC SCHOOL SYSTEM 10910 ROUTE 108 ELLICOTT CITY, MD 21043 PREPARED BY: ARIA ENVIRONMENTAL,

More information

ANALYTICAL REPORT. Airconstruct HVAC Pty Ltd 37 Carlyle Street Mackay QLD Withheld PROPERTY:

ANALYTICAL REPORT. Airconstruct HVAC Pty Ltd 37 Carlyle Street Mackay QLD Withheld PROPERTY: NSJ EnviroSciences Pty Ltd t/a MouldLab ABN 27 143 789 995 PO Box 306 WICKHAM NSW 2293 Phone: 02 4968 8448 Fax: 02 8004 3576 Mobile: 0410 239 848 Email: ---------------------------- ANALYTICAL REPORT CLIENT:

More information

SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD PREPARED FOR:

SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD PREPARED FOR: SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD 21738 PREPARED FOR: HOWARD COUNTY PUBLIC SCHOOL SYSTEM 10910 ROUTE 108 ELLICOTT CITY, MD 21043 PREPARED BY: ARIA ENVIRONMENTAL,

More information

September 25, Re: Results of Initial Tests and Evaluation Willow Grove Elementary School. Dear Ms. Woicekowski,

September 25, Re: Results of Initial Tests and Evaluation Willow Grove Elementary School. Dear Ms. Woicekowski, September 25, 2017 R.K. Occupational and Environmental Analysis, Inc. 401 St. James Ave. Phillipsburg, NJ 08865 908-454-6316/908-454-4818 (fax) rkenvironmental@entermail.net mguinni69@verizon.net Ms. Gail

More information

September 18, 204. Subject Property: Terramar Elementary School 7000 West Happy Valley Road Peoria, Arizona 85383

September 18, 204. Subject Property: Terramar Elementary School 7000 West Happy Valley Road Peoria, Arizona 85383 Asbestos Testing Lead Testing Microbial Testing Management Analysis Environmental Assessment September 18, 204 Attn: Valley Schools Insurance Trust and Pools Scott McCleary PO Box 41760 Phoenix, Arizona

More information

DATE: October 31, TO: Toby Maxson, Principal. SUBJECT: Heritage ES - IAQ - Initial Contact - Room B-16

DATE: October 31, TO: Toby Maxson, Principal. SUBJECT: Heritage ES - IAQ - Initial Contact - Room B-16 DATE: October 31, 2016 TO: Toby Maxson, Principal SUBJECT: Heritage ES - IAQ - Initial Contact - Room B-16 On Friday 10/28, I received Work Order #344295: Principal would like room tested: Per teacher

More information

DATE: May 27, TO: Sam Russell, Director. SUBJECT: Administration - IAQ - Initial Contact - Suite 225-Copy Room

DATE: May 27, TO: Sam Russell, Director. SUBJECT: Administration - IAQ - Initial Contact - Suite 225-Copy Room DATE: May 27, 2015 TO: Sam Russell, Director SUBJECT: Administration - IAQ - Initial Contact - Suite 225-Copy Room This morning 5/27, I received Work Order 220274: Suite 225 -The carpet in the copier room

More information

DATE: September 5, TO: Chris Mattingly, Principal. SUBJECT: Briarhill MS - IAQ - Air Test Results - Room 307

DATE: September 5, TO: Chris Mattingly, Principal. SUBJECT: Briarhill MS - IAQ - Air Test Results - Room 307 DATE: September 5, 2017 TO: Chris Mattingly, Principal SUBJECT: Briarhill MS - IAQ - Air Test Results - Room 307 On Tuesday 8/29, Apex-Titan Air tested Rooms 307. It is typically assumed that indoor spore

More information

Limited Mold Sampling Investigation Report

Limited Mold Sampling Investigation Report Page 1 of 13 Limited Mold Sampling Investigation Report 9811 W. Charleston Blvd Suite 2403 Las Vegas, NV 89117 Tel: 702.255.2457 * Fax: 702.953.0286 www.msenational.com * info@msenational.com Customer

More information

Sampling for Mould in Red Bluff Elementary School, Quesnel

Sampling for Mould in Red Bluff Elementary School, Quesnel Sampling for Mould in Red Bluff Elementary School, Quesnel Introduction What are moulds? Moulds are part of the fungi kingdom and serve an important role in breaking down organic matter. They are found

More information

Appendix D Location Specific Technical Reports

Appendix D Location Specific Technical Reports Appendix D Location Specific Technical Reports SEL Project Number 119917 March 29, 2017 Air Sampling Program University of Toronto Medical Sciences Building 1 King s College Circle, Toronto, Ontario Page

More information

The attached report is the result of a mold and bacterial assessment conducted at th Street, Franklin, Ohio on April 24 and 25, 2008.

The attached report is the result of a mold and bacterial assessment conducted at th Street, Franklin, Ohio on April 24 and 25, 2008. May 8, 2008 Jon Lampros President Clean Air Systems 701 Rockland Rd. Lake Bluff, IL 60044 Re: Assessment of Ozone Treatment on Microbial Populations Dear Mr. Lampros, The attached report is the result

More information

February 21, Mold Assessment. 400 East Avenue, Warwick, Rhode Island. Dear Mr. McCabe:

February 21, Mold Assessment. 400 East Avenue, Warwick, Rhode Island. Dear Mr. McCabe: February 21, 2014 Mr. Ken McCabe Lincoln Campus Physical Plant Director Community College of Rhode Island Knight Campus 400 East Avenue Warwick, Rhode Island 02866 Re: Mold Assessment Community College

More information

INTERPRETING MICROBIAL MEASUREMENT AND ANALYSIS

INTERPRETING MICROBIAL MEASUREMENT AND ANALYSIS INTERPRETING MICROBIAL MEASUREMENT AND ANALYSIS T Nathanson* Public Works and Government Services Canada, Ottawa, Canada ABSTRACT The potential for microbial contamination exists in every building and

More information

Background Air Sampling Auburn Village School, New Modular Classrooms SLGL File Number

Background Air Sampling Auburn Village School, New Modular Classrooms SLGL File Number March 20, 2014 Mr. Peter Barbuto, Director of Maintenance School Administrative Unit No. 15 Hooksett School District 90 Farmer Road Hooksett, New Hampshire 03106 Re: Background Air Sampling Auburn Village

More information

Basic Industrial Hygiene Sampling Overview of Indoor Air Quality

Basic Industrial Hygiene Sampling Overview of Indoor Air Quality Basic Industrial Hygiene Sampling Overview of Indoor Air Quality Bryan K. Stolte, Ph.D., C.I.H. Alcatel-Lucent Corporate EHS Office International Telecommunication Safety Conference Denver, CO Sept 14

More information

BIOAIRE CASSETTE Impaction Particle Sampler

BIOAIRE CASSETTE Impaction Particle Sampler USER MANUAL FOR BIOAIRE CASSETTE Impaction Particle Sampler A.P. Buck, Inc. 7101 Presidents Drive Suite 110 Orlando, FL 32809 USA Tel 1-800-330-2825 407-851-8602 Fax 407-851-8910 12 bioaire@apbuck.com

More information

Mabbett. January 3, 2018

Mabbett. January 3, 2018 Mabbett January 3, 2018 Mabbett & Associates, Inc, 1442 Duke Street Alexandria, VA 22314 Tel: (703) 997-6051 info@mabbett.com www.mabbett.com James Hodges, CHMM Branch Chief General Services Administration

More information

UNIVERSAL HOME & MOLD INSPECTIONS Where Quality and Details Count!

UNIVERSAL HOME & MOLD INSPECTIONS Where Quality and Details Count! Project # PRV140519 UNIVERSAL HOME & MOLD INSPECTIONS Where Quality and Details Count! Post Remediation Verification Visual Post-Remediation Verification With Non-viable Mold Sampling Client: Lauren Gash

More information

RESIDENTIAL MOLD ASSESSMENT. Final Report. Your Address Here

RESIDENTIAL MOLD ASSESSMENT. Final Report. Your Address Here 2847 Barnard Street San Diego California 92110 Phone 619.501.0185 Mobile 619.203.9774 Fax 619.501.9843 hoveyenv@cox.net RESIDENTIAL MOLD ASSESSMENT Final Report Your Address Here September 1, 2003 Prepared

More information

Mr. Jody Davis PO Box 1475 Montgomery, TX

Mr. Jody Davis PO Box 1475 Montgomery, TX Texas Association of School Boards P.O. Box 400 Austin, TX 78767-0400 512-467-0222 Serving Texas School Boards since 1949 January 7, 2014 Mr. Jody Davis PO Box 1475 Montgomery, TX 77356-1475 Dear Mr. Davis:

More information

Powers Environmental LLC

Powers Environmental LLC Powers Environmental LLC POST-REMEDIATION VERIFICATION CLEARANCE REPORT GENERAL INFORMATION Report Date: 09/06/2017 Assessment Date: 09/05/2017 Project Number: 2017222 Time: 7:00 AM Ground Condition: Dry

More information

Limited Indoor Air Quality Assessment

Limited Indoor Air Quality Assessment Limited Indoor Quality Assessment Salinas Elementary School 000 Century Drive West Laredo, Webb County, Texas September 5, 20 Terracon Project No. 9045-R Prepared for: United Independent School District

More information

Limited Indoor Air Quality Assessment

Limited Indoor Air Quality Assessment Young Rainey STAR Center Areas 121 and 133 7887 Bryan Dairy Road Largo, Florida March 3, 2014 Terracon Project No. H4147022 Prepared for: Young Rainey STAR Center Pinellas County BOCC 7887 Bryan Dairy

More information

Rowan University Department of Environmental Health and Safety. A Brief Overview for Building Maintenance

Rowan University Department of Environmental Health and Safety. A Brief Overview for Building Maintenance Rowan University Department of Environmental Health and Safety A Brief Overview for Building Maintenance Mold Overview Wide variety of molds may be present in building materials Common ones include: Alternaria

More information

PROJECT NO REPORT TO CITY OF STRATFORD ASBESTOS CONTAINING MATERIALS SURVEY ROW HOUSES STRATFORD, ONTARIO CONDUCTED BY:

PROJECT NO REPORT TO CITY OF STRATFORD ASBESTOS CONTAINING MATERIALS SURVEY ROW HOUSES STRATFORD, ONTARIO CONDUCTED BY: PROJECT NO. 1197 REPORT TO CITY OF STRATFORD ON ASBESTOS CONTAINING MATERIALS SURVEY ROW HOUSES STRATFORD, ONTARIO CONDUCTED BY: 1099 KINGSTON ROAD, SUITE 260 PICKERING, ONTARIO L1V 1B5 Tel: (416) 410-4333

More information

INDOOR AIR QUALITY ASSESSMENT

INDOOR AIR QUALITY ASSESSMENT INDOOR AIR QUALITY ASSESSMENT Biddeford Intermediate School Biddeford Primary School JFK Memorial Kindergarten Center Biddeford High School Air Quality Management Services, Inc. PREPARED FOR Biddeford

More information

TYPE 3 ASBESTOS ABATEMENT UNIVERSITY OF WINDSOR BIOLOGY BUILDING LABS 204 & 206 WINDSOR, ONTARIO. Issued: March 15 th, 2010

TYPE 3 ASBESTOS ABATEMENT UNIVERSITY OF WINDSOR BIOLOGY BUILDING LABS 204 & 206 WINDSOR, ONTARIO. Issued: March 15 th, 2010 Environmental Consultants 931 Commissioners Rd East, Suite 100 London, Ontario N5Z 3H9 Tel: (519) 685-9048 Fax: (519) 685-1042 TYPE 3 ASBESTOS ABATEMENT UNIVERSITY OF WINDSOR BIOLOGY BUILDING LABS 204

More information

MOLD REMEDIATION PROCEDURES AT A NEW JERSEY ELEMENTARY SCHOOL

MOLD REMEDIATION PROCEDURES AT A NEW JERSEY ELEMENTARY SCHOOL MOLD REMEDIATION PROCEDURES AT A NEW JERSEY ELEMENTARY SCHOOL M McGuinness * R.K. Occupational and Environmental Analysis, Phillipsburg, NJ, USA ABSTRACT Microbiological remediation procedures at an Elementary

More information

Indoor Air Quality Report

Indoor Air Quality Report Indoor Air Quality Report Shawnee City Hall 222 N. Broadway, Shawnee, Oklahoma 74801 INDOOR AIR QUALITY SAMPLING REPORT Project Locations: Shawnee City Hall 222 N. Broadway, Shawnee, Oklahoma 74801 Prepared

More information

The basic qualifications for mold investigators and remediation contractors should include:

The basic qualifications for mold investigators and remediation contractors should include: Technical Analysis Mold Inspections - What To Expect Mark Misner CIE, CMI, CMRC Introduction If you are in the market for a mold inspector, then you already have a pretty good idea that your home has a

More information

INTRODUCTION. The evaluation was performed in the morning and afternoon on a weekday during normal building operations.

INTRODUCTION. The evaluation was performed in the morning and afternoon on a weekday during normal building operations. INTRODUCTION A preliminary indoor air quality (IAQ) evaluation was performed at the City of Stockton Police Department on March 23, 20. John J. Sacco, P.E., CIH of Earthshine Consulting, Inc (ECI) performed

More information

All questions regarding the attached study should be directed to the Howard County Government s public information office at

All questions regarding the attached study should be directed to the Howard County Government s public information office at All questions regarding the attached study should be directed to the Howard County Government s public information office at 410-313-2022. 449 Eisenhower Boulevard, Suite 300 Harrisburg, PA 17111-2302

More information

Limited Visual Assessment Report

Limited Visual Assessment Report Terramar School Peoria, Arizona July 27, 2015 Terracon Project No. 65157316 Prepared for: Deer Valley Unified School District Glendale, Arizona Prepared by: Terracon Consultants, Inc. Tempe, Arizona July

More information

POST-REMEDIATION MOLD ASSESSMENT AND CLEARANCE REPORT. Bolin Administrative Center Suite W. Main Street Lewisville, Texas

POST-REMEDIATION MOLD ASSESSMENT AND CLEARANCE REPORT. Bolin Administrative Center Suite W. Main Street Lewisville, Texas POST-REMEDIATION MOLD ASSESSMENT AND CLEARANCE REPORT Bolin Administrative Center Suite 105 1585 W. Main Street Lewisville, Texas May 30, 2017 Apex Project No. 72501027079 Prepared for: Lewisville Independent

More information

STANDARD OPERATING PROCEDURES FOR MOLD REMEDIATION

STANDARD OPERATING PROCEDURES FOR MOLD REMEDIATION West Virginia University Environmental Health and Safety STANDARD OPERATING PROCEDURES FOR MOLD REMEDIATION Revised February 2016 West Virginia University P.O Box 6551 Morgantown WV 26506 # 304-293-3792

More information

MODULE 2D ENVIRONMENTAL MICROBIOLOGICAL LABORATORY ACCREDITATION PROGRAM (EMLAP) ADDITIONAL REQUIREMENTS

MODULE 2D ENVIRONMENTAL MICROBIOLOGICAL LABORATORY ACCREDITATION PROGRAM (EMLAP) ADDITIONAL REQUIREMENTS MODULE 2D ENVIRONMENTAL MICROBIOLOGICAL LABORATORY ACCREDITATION PROGRAM (EMLAP) ADDITIONAL REQUIREMENTS 2D.1 SCOPE The AIHA- Laboratory Accreditation Programs (AIHA-LAP), LLC s Environmental Microbiological

More information

Conducting Mold Assessments at a Remote Location following Extensive Flooding of an Entire Community

Conducting Mold Assessments at a Remote Location following Extensive Flooding of an Entire Community Presented By: Andreas Wagner, M.Eng., CIH, ROH Principal Conducting Mold Assessments at a Remote Location following Extensive Flooding of an Entire Community PO124 From Meth Labs to Lead: Policies and

More information

Indoor Air Quality Report Bixby Public Schools Central Elementary Liberty OHM File Number

Indoor Air Quality Report Bixby Public Schools Central Elementary Liberty OHM File Number Indoor Air Quality Report Bixby Public Schools Central Elementary Liberty OHM File Number 14-157 Survey Location: Bixby Public Schools Central Elementary Art Room 201 South Main Street Bixby, OK 74008

More information

A L A R A Environmental Health & Safety Ltd.

A L A R A Environmental Health & Safety Ltd. Metro Home Inspections October 4, 2010 7626 Arvin Court Burnaby, BC V5A 4M9 ATTENTION: Mr. Mark Fagrie RE: Indoor Air Quality Investigation at Little Mountain Housing, 159 Grouse Walk, Vancouver, BC Dear

More information

MODULE 2D ENVIRONMENTAL MICROBIOLOGICAL LABORATORY ACCREDITATION PROGRAM (EMLAP) ADDITIONAL REQUIREMENTS

MODULE 2D ENVIRONMENTAL MICROBIOLOGICAL LABORATORY ACCREDITATION PROGRAM (EMLAP) ADDITIONAL REQUIREMENTS MODULE 2D ENVIRONMENTAL MICROBIOLOGICAL LABORATORY ACCREDITATION PROGRAM (EMLAP) ADDITIONAL REQUIREMENTS 2D.1 SCOPE The AIHA- Laboratory Accreditation Programs (AIHA-LAP), LLC s Environmental Microbiological

More information

January 27, 2017 Pinchin File No

January 27, 2017 Pinchin File No January 27, 2017 Pinchin File No. 01-03-02225 16 Cemetery Road Port Hastings, Nova Scotia, B9A 1K6 Attention: Karen MacDonald Re: Limited Mould Assessment and Bulk Asbestos Sampling Dr. John Hugh Gillis

More information

INDOOR AIR QUALITY TESTING AT CARLISLE COUNTY ELEMENTARY SCHOOL

INDOOR AIR QUALITY TESTING AT CARLISLE COUNTY ELEMENTARY SCHOOL INDOOR AIR QUALITY TESTING AT CARLISLE COUNTY ELEMENTARY SCHOOL For: Keith Shoulders Carlisle County Schools 4557 State Route 1377 Bardwell, Kentucky 42023 Testing Performed By: Christopher K. Adkins Air

More information

POST-REMEDIATION MOLD ASSESSMENT AND CLEARANCE REPORT. BB Owen Elementary School Library 5640 Squires The Colony, Texas

POST-REMEDIATION MOLD ASSESSMENT AND CLEARANCE REPORT. BB Owen Elementary School Library 5640 Squires The Colony, Texas POST-REMEDIATION MOLD ASSESSMENT AND CLEARANCE REPORT BB Owen Elementary School Library 5640 Squires The Colony, Texas May 20, 2013 Project No. 0113H113 Prepared for: Lewisville Independent School District

More information

Assessment of Mould Growth Berens River School Berens River, Manitoba

Assessment of Mould Growth Berens River School Berens River, Manitoba Assessment of Mould Growth Berens River School Berens River, Manitoba Prepared for: Frontier School Division 30 Speers Road, Winnipeg, Manitoba R2J 1L9 Attention: Doug Nicholson, Manager of Facilities

More information

Asbestos Inventory Survey of Glenwood Elementary, Avenue, Langley, BC

Asbestos Inventory Survey of Glenwood Elementary, Avenue, Langley, BC October 25, 2016 200753 AIS R1 Glenwood Elementary School District #35 (Langley) 20260 64 th Avenue Langley, BC V2Y 1N3 E mail: Attention: Reference: KWagner@sd35.bc.ca Karen Wagner Asbestos Inventory

More information

NORTH DAKOTA DEPARTMENT OF TRANSPORTATION REQUEST FOR PROPOSAL ASBESTOS AIR MONITORING SERVICES

NORTH DAKOTA DEPARTMENT OF TRANSPORTATION REQUEST FOR PROPOSAL ASBESTOS AIR MONITORING SERVICES NORTH DAKOTA DEPARTMENT OF TRANSPORTATION REQUEST FOR PROPOSAL ASBESTOS AIR MONITORING SERVICES September 12, 2008 INTRODUCTION North Dakota Department of Transportation (NDDOT) is seeking an asbestos

More information

Asbestos Inventory Survey of James Anderson Learning Centre, Avenue, Langley (Formerly Langley Fundamental Middle School)

Asbestos Inventory Survey of James Anderson Learning Centre, Avenue, Langley (Formerly Langley Fundamental Middle School) October 31, 2016 200753 AIS R1 James Anderson Learning Centre School District #35 (Langley) 20260 64 th Avenue Langley, BC V2Y 1N3 E mail: Attention: Reference: KWagner@sd35.bc.ca Karen Wagner Asbestos

More information

Health & Public Safety Management

Health & Public Safety Management . Health & Public Safety Management Indoor Air Quality Investigation White Hall Building Assessment Period March 24 9th, 2004 Phase II Prepared 5/5/2004 By Luigi Marcone Director of Health and Public Safety

More information

DRAFT. UNR Fungi Assessment & Remediation Program

DRAFT. UNR Fungi Assessment & Remediation Program DRAFT UNR Fungi Assessment & Remediation Program TABLE OF CONTENTS SCOPE AND APPLICATION... 3 ROLES AND RESPONSIBILITIES... 3 BUILDINGS AND GROUNDS / FACILITIES MANAGMENT... 3 ENVIRONMENTAL HEALTH AND

More information

NCCEH Mould Investigation Toolkit

NCCEH Mould Investigation Toolkit NCCEH Mould Investigation Toolkit Overview of Microbial Sampling Methods NOVEMBER 2014 Table of Contents Air Sampling... 2 Liquid Impinger... 2 Fungal Spore Sampling/Spore Traps... 3 Impactor Samplers

More information

FINAL REPORT. Asbestos-Containing Building Material Assessment. Toronto Catholic District School Board

FINAL REPORT. Asbestos-Containing Building Material Assessment. Toronto Catholic District School Board FINAL REPORT Asbestos-Containing Building Material Assessment Toronto Catholic District School Board Santa Maria Catholic School, 25 Avon Avenue Toronto, Ontario PROJECT NO. 1025760 PROJECT NO. 1025760

More information