Subject: TRACE 700 v6.3.0 Compliance with ANSI/ASHRAE Standard
|
|
- Sabina Pope
- 6 years ago
- Views:
Transcription
1 Trane C.D.S. 36 Pammel Creek Rd La Crosse, WI 5461 USA Tel (68) Fax (68) August 3, 213 Subject: TRACE 7 v6.3. Compliance with ANSI/ASHRAE Standard Dear TRACE User: We are pleased to inform you that TRACE 7 v6.3. was tested in compliance with ANSI/ASHRAE Standard 14 27, Standard Method of Test for the Evaluation of Building Energy Analysis Computer Programs. Test results, supplemented by graphs and explanatory notes, accompany this letter. As you may know, ANSI/ASHRAE/IESNA Standard 9.1, Energy Standard for Buildings, Except Low-Rise Residential Buildings, stipulates that any computer program that is used to demonstrate code compliance via the performance path s Energy Cost Budget Method must be tested in accordance with Standard 14. TRACE 7 v6.3. has completed the BESTEST validation for calculation and comparison with similar analysis programs as required by ASHRAE Standard 14. Standard 9.1 defines minimum requirements for the design of energy-efficient buildings and is used by many state and local code-writing bodies as the standard of care in their jurisdictions. Buildingenergy simulation programs, such as TRACE 7, are used to estimate the difference in energy costs between the design- and budget-building models specified in Section 11 of Standard 9.1. If you have questions about the testing documentation that accompanies this letter, or about any of Trane s design and analysis tools, please contact our C.D.S. Support Center by phoning (68) or ing cdshelp@trane.com. Best regards, Charles Jelen ASHRAE Standard 14 Coordinator Trane C.D.S. Attachments: Results and modeling notes from Standard 14 testing of TRACE 7
2 STANDARD 14 OUTPUT FORM - MODELING NOTES SOFTWARE: TRACE 7 Simulated Effect (1): Loads modeling Optional Settings or Modeling Capabilities: Cooling Load Methodology Options: TETD-TA1 -- Response factor TETD/Time-Averaging method CLTD-CLF (ASHRAE TFM) -- Exact Transfer Function Method TETD-TA2 -- Approximate TETD/Time-Averaging method TETD-PO -- Approximate TETD with Post Office Weighting CEC-DOE2 -- Exact TFM method with CEC\DOE 2.1c constraints RP ASHRAE Research Project 359 Method RTS (ASHRAE Tables) -- Radiant time series coefficients based on 21 Hof table lookup RTS (Heat Balance) -- Radiant time series coefficients based on heat balance Setting or Capability Used: RTS (Heat Balance) -- Radiant time series coefficients based on heat balance Physical Meaning of Option Used: Each room s solar and non-solar Radiant Time Series values are calculated based on the rigorous Heat Balance method described in the 21 ASHRAE Handbook of Fundamentals using algorithms found in the ASHRAE Toolkit for Building Load Calculations. This TRACE load methodology also calculates the amount of solar gain lost through retransmission back out through the window. These heat balance-derived RTS values are implemented in a manner similar to custom weighting factors used by the DOE 2.1 energy analysis program. Simulated Effect (2): External heat transfer Optional Settings or Modeling Capabilities: Outside Film Methodology Options: Constant (as defined in construction library) Vary with wind speed: per the 1985 ASHRAE Handbook, P Vary with wind speed & direction, and T: per the MoWiTT model
3 Vary with wind speed & direction, T, and surface roughness: per the TARP model Setting or Capability Used: Constant (as defined in construction library) Physical meaning of option used: The internal and external surface coefficients were set equal to the values provided in the standard.
4 DOCUMENT BELOW THE REASONS FOR OMITTING RESULTS List the case(s) where results were omitted, and which results were omitted for the case(s): CASE96 CASE96 models a passive solar sun room using a modified Trombe wall. In order to model this configuration the associated algorithm would need to compute: a) The hourly proportion of solar radiation absorbed by the individual sunlit surfaces within the sunlit portion of the Trombe wall b) The effect of introducing infiltration in the Trombe wall section c) Adjacent space heat transfer between the Trombe wall and the interior room. The required inputs to model this type of configuration are not available in TRACE.
5 STANDARD 14 EXTENDED COMMENTS E1 TO E2 Action taken to update code: 1) The TRACE room humidity ratios were half of the benchmark results, a result of the TRACE coil curve algorithm being unable to distinguish a "dry coil" condition. This routine (SSCRV.FOR) was therefore modified to test for a dry coil condition by estimated the hourly coil apparatus dew point, ADP. When the hourly coil entering dew point, CEDP > ADP, this indicates a dry coil and so CLWC = CEWC, and only sensible cooling can occur. 2) The TRACE condenser fan energy consumption was found to be excessively higher than the benchmark values. This occurred because TRACE was not taking into account the fact that when unitary equipment cycles off for a portion of an hour; the condenser fan must cycle off the same amount. The CONDFN.FOR routine was therefore modified such that when OADB > 95F, the max condenser fan demand is multiplied times the cycle on ratio. The off cycle time reduction could not be applied to other ambient conditions because of other assumptions built into the routine. 3) The TRACE System Simulation does not currently have the capability to vary the cooling coil capacity as a function of inlet conditions (this is only available in the Equipment Simulation). TRACE simply assumes that the cooling coil can supply the SADBc (and associated CLDBc) calculated at design for all entering conditions. Therefore, in order to get better agreement between TRACE and the benchmark programs, the DSADBc Min/Max values were calculated for each E-series case. Other notes: 4) The agreement between the Envelope latent and sensible values match very closely for all E-cases. This means that the envelope and internal load values defined in the TRACE files were correctly input. 5) After the SADBc Min/Max values were specifically input for each of the E-Cases in alternative 1, the results for the evaporator, supply and condenser fans match the benchmark programs very closely.
6 STANDARD 14 EXTENDED COMMENTS E3 TO E545 Action taken to update code: 1) The TRACE equation for Solair temperature used a constant term (21 Btuh/ft 2 ) to represent the longwave correction T, i.e., SOLAIR(IHR)= OADB(IHR) + RTOT * ALPHA / HOSLAB(IHR) - (21/ HOSLAB(IHR)) * PCSKY. However, this term should actually vary with the outside surface emissivity (see p of the 25 ASHRAE Handbook of Fundamentals) and so was changed to: SOLAIR(IHR)= OADB(IHR) + RTOT * ALPHA / HOSLAB(IHR) - (EMISS*2 / HOSLAB(IHR)) * PCSKY where PCSKY is for vertical surfaces and 1 for horizontal surfaces. This change has no effect on wall heat transfer but will have a slight effect on roof heat transfer since EMISS defaults to.9 and HOSLAB typically is 3 Btu/(hr-ft 2 -F) and so the - EMISS*2/HOSLAB term yields (-.9*2/3) = -6 F TD vs. (-21/3) = -7 F TD for the old method. However, in the Standard 14 E3-545 cases, both HOSLAB and EMIS were defined as very small to model an adiabatic surface and so the (-21 / HOSLAB(IHR)) term yielded a high negative value. Other notes: 1) The Standard 14 test cases E3-5 and H1-245 assume an unrealistically low thermal mass of near zero for the base case building which causes instability in the TRACE temperature drift model. To correct this, the default Room Mass for these cases was changed from "Time delay based on actual mass" to "Light (3 lb m /ft 2 ), 3 hr. lag". 2) As noted for the E1 to E2 comments, the TRACE System Simulation does not currently have the capability to vary the cooling coil capacity as a function of inlet conditions (this is only available in the TRACE Equipment simulation). TRACE simply assumes that the cooling coil can supply the SADBc (and associated CLDBc) calculated at design for all entering conditions. 3) As noted for the E1 to E2 comments, the TRACE System Simulation does not currently have the capability to vary the cooling coil capacity as a function of inlet conditions (this is only available in the TRACE Equipment simulation). TRACE simply assumes that the cooling coil can supply the SADBc (and associated CLDBc) calculated at design for all entering conditions which causes the fan energy to be larger than necessary. Therefore, in order to get better agreement between TRACE and the benchmark programs, the DSADBcMin/Max values were calculated for each these cases and input as follows: E5=17C, E51=16C, E52=7.1C, E522=2C, E525=27C, E53=17C, E54=15C and E545=27C. 4) The capacity and ambient unloading curves used with the Air cooled split condenser used for the E3-E545 datasets were imported from the EnergyPlus dataset provide by Linda Lawrie. Since EnergyPlus does not model the condenser fan separately but TRACE does, the unloading curves could be improved for TRACE by eliminating the
7 condenser fan kw from the raw data used to generate those curves. The power unloading curve is the same as was used for the E1 series.
8 STANDARD 14 EXTENDED COMMENTS POWER UNLOADING CURVE Power unloading curve derivation: Start with CDF = x (1-PLR) from Figure 1, p. 33 FracFLPower = PLR / CDF PLR CDF FracFLPower FracFLPower = x PLR x PLR x PLR x PLR x PLR 5 Created cooling equipment power consumed member: "Std 14 Case E1"
9 HVAC BESTEST: Mean COP COP CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
10 HVAC BESTEST: (Maximum - Minimum)/Mean COP.25 Fractional Variation CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
11 HVAC BESTEST: Mean COP Sensitivities delta COP CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
12 HVAC BESTEST: Total Space Cooling Electricity Consumption 16 Electricity Consumption (kwh) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
13 HVAC BESTEST: Total Space Cooling Electricity Sensitivities delta Electricity Consumption (kwh) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
14 HVAC BESTEST: Compressor Electricity Consumption 14 Electricity Consumption (kwh) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
15 HVAC BESTEST: Total Compressor Electricity Sensitivities delta Electricity Consumption (kwh) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
16 HVAC BESTEST: Total Indoor (Supply) Fan Electricity Consumption 16 Electricity Consumption (kwh) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
17 HVAC BESTEST: Indoor (Supply) Fan Electricity Sensitivities delta Electricity Consumption (kwh) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
18 HVAC BESTEST: Outdoor (Condenser) Fan Electricity Consumption 8 Electricity Consumption (kwh) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
19 HVAC BESTEST: Outdoor (Condenser) Fan Electricity Sensitivities delta Electricity Consumption (kwh) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
20 HVAC BESTEST: Total Coil Load 6 5 Load (kwh thermal) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
21 HVAC BESTEST: Total Coil Load Sensitivities 3 delta Load (kwh thermal) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
22 HVAC BESTEST: Sensible Coil Load 5 45 Load (kwh thermal) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
23 HVAC BESTEST: Sensible Coil Load Sensitivities delta Load (kwh thermal) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
24 HVAC BESTEST: Latent Coil Load 35 3 Load (kwh thermal) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
25 HVAC BESTEST: Latent Coil Load Sensitivities delta Load (kwh thermal) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
26 HVAC BESTEST: Mean Indoor Drybulb Temperature 3 25 Temperature ( C) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
27 HVAC BESTEST: (Maximum - Minimum)/Mean Indoor Drybulb Temperature.9.8 Fractional Variation CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
28 HVAC BESTEST: Mean Indoor Humidity Ratio Humidity Ratio (kg/kg) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
29 HVAC BESTEST: (Maximum - Minimum)/Mean Indoor Humidity Ratio.1.9 Fractional Variation CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
30 HVAC BESTEST: Total Zone Load 6 5 Load (Wh thermal) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
31 HVAC BESTEST: Sensible Zone Load 45 4 Load (Wh thermal) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
32 HVAC BESTEST: Latent Zone Load 3 25 Load (Wh thermal) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
33 HVAC BESTEST: Sensible Coil Load - Zone Load (Fan Heat) 25 Load (kwh thermal) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
34 HVAC BESTEST: Latent Coil Load - Latent Zone Load (Should = ) 6 5 Load (kwh thermal) CASIS/EDF CLIM2/EDF DOE-2.1E/CIEMAT DOE-2.1E/NREL EnergyPlus/GARD TRNSYS-ideal/TUD TRNSYS-real/TUD Analytical/TUD Analytical/HTAL1 Analytical/HTAL2 TRACE 7/Trane
35 HVAC BESTEST: CE3 - CE545 Total Electricity Consumption 6 Electricity Consumption (kwh) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
36 HVAC BESTEST: CE3 - CE545 Total Electricity Consumption, Before BESTESTing 6 Electricity Consumption (kwh) TRNSYS TUD DOE21E-J NREL DOE21E-E NREL EnergyPlus GARD CODYRUN UR HOT3 NRCan
37 HVAC BESTEST: CE3 - CE545 Total Space Cooling Electricity Consumption Sensitivities 8 Electricity Consumption (kwh) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
38 HVAC BESTEST: CE3 - CE545 Peak Hour Total Electricity Consumption 14 Electricity Consumption (Wh) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
39 25 2 HVAC BESTEST: CE3 - CE545 Hourly Maximum Total Space Cooling Consumption Sensitivities Electricity Consumption (Wh) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
40 HVAC BESTEST: CE3 - CE545 Compressor Electricity Consumption 45 Electricity Consumption (kwh) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
41 HVAC BESTEST: CE3 - CE545 Compressor Electricity Consumption Sensitivities 6 Electricity Consumption (kwh) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
42 HVAC BESTEST: CE3 - CE545 Indoor (Supply) Fan Electricity Consumption 12 Electricity Consumption (kwh) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
43 HVAC BESTEST: CE3 - CE545 Indoor (Supply) Fan Electricity Consumption Sensitivities 4 Electricity Consumption (kwh) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
44 HVAC BESTEST: CE3 - CE545 Outdoor (Condenser) Fan Electricity Consumption 5 45 Electricity Consumption (kwh) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
45 8 HVAC BESTEST: CE3 - CE545 Outdoor (Condenser) Fan Electricity Consumption Sensitivities Electricity Consumption (kwh) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
46 HVAC BESTEST: CE3 - CE545 Total Coil Load Load (kwh thermal) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
47 HVAC BESTEST: CE3 - CE545 Peak Hour Total Coil Load 7 6 Load (Wh thermal) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
48 HVAC BESTEST: CE3 - CE545 Hourly Maximum Total Coil Load Sensitivities Load (Wh thermal) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
49 HVAC BESTEST: CE3 - CE545 Sensible Coil Load Load (kwh thermal) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
50 HVAC BESTEST: CE3 - CE545 Sensible Cooling Load Sensitivities Load (kwh thermal) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
51 HVAC BESTEST: CE3 - CE545 Peak Hour Sensible Coil Load Load (Wh thermal) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
52 HVAC BESTEST: CE3 - CE545 Latent Coil Load Load (kwh thermal) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
53 HVAC BESTEST: CE3 - CE545 Latent Cooling Load Sensitivities Load (kwh thermal) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
54 HVAC BESTEST: CE3 - CE545 Peak Hour Latent Coil Load Load (Wh thermal) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
55 HVAC BESTEST: CE3 - CE545 Hourly Maximum Latent Coil Load Sensitivities Load (Wh thermal) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
56 HVAC BESTEST: CE3 - CE545 COP COP CODYRUN/UR HOT3/NRCan TRACE 7/Trane
57 HVAC BESTEST: CE3 - CE545 COP2 Sensitivities COP CODYRUN/UR HOT3/NRCan TRACE 7/Trane
58 HVAC BESTEST: CE3 - CE545 Maximum COP COP CODYRUN/UR HOT3/NRCan TRACE 7/Trane
59 HVAC BESTEST: CE3 - CE545 Hourly Maximum COP2 Sensitivities COP CODYRUN/UR HOT3/NRCan TRACE 7/Trane
60 HVAC BESTEST: CE3 - CE545 Minimum COP COP CODYRUN/UR HOT3/NRCan TRACE 7/Trane
61 HVAC BESTEST: CE3 - CE545 Hourly Minimum COP2 Sensitivities COP CODYRUN/UR HOT3/NRCan TRACE 7/Trane
62 HVAC BESTEST: CE3 - CE545 Indoor Dry-Bulb Temperature Temperature ( C) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
63 HVAC BESTEST: CE3 - CE545 IDB Sensitivities 25 2 Temperature ( C) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
64 HVAC BESTEST: CE3 - CE545 Maximum Indoor Dry-Bulb Temperature Temperature ( C) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
65 HVAC BESTEST: CE3 - CE545 Hourly Maximum IDB Sensitivities 25 2 Temperature ( C) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
66 HVAC BESTEST: CE3 - CE545 Minimum Indoor Dry-Bulb Temperature Temperature ( C) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
67 HVAC BESTEST: CE3 - CE545 Zone Humidity Ratio Humidity Ratio (kg/kg) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
68 HVAC BESTEST: CE3 - CE545 Humidity Ratio Sensitivities Humidity Ratio (kg/kg) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
69 HVAC BESTEST: CE3 - CE545 Maximum Zone Humidity Ratio.25.2 Humidity Ratio (kg/kg) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
70 HVAC BESTEST: CE3 - CE545 Hourly Maximum Humidity Ratio Sensitivities.2.15 Humidity Ratio (kg/kg) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
71 HVAC BESTEST: CE3 - CE545 Minimum Zone Humidity Ratio Humidity Ratio (kg/kg) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
72 HVAC BESTEST: CE3 - CE545 Relative Humidity Relative Humidity (%) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
73 HVAC BESTEST: CE3 - CE545 Relative Humidity Sensitivities 2 15 Relative Humidity (%) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
74 HVAC BESTEST: CE3 - CE545 Maximum Zone Relative Humidity Relative Humidity (%) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
75 HVAC BESTEST: CE3 - CE545 Hourly Maximum Relative Humidity Sensitivities 6 5 Relative Humidity (%) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
76 HVAC BESTEST: CE3 - CE545 Minimum Zone Relative Humidity Relative Humidity (%) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
77 HVAC BESTEST: f(odb) for CE5, CE53 Specific Day Electricity Consumptions 6 Total (compr + both fans) Outdoor Fan Indoor Fan 5 CE53, Dry Coil CE5 CE5, Wet Coil CE53, Dry Coil CE5, Wet Coil CE53, Dry Coil Consumption (Wh) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
78 HVAC BESTEST: f(odb) for CE5, CE53 Specific Day Coil Loads Daily Load (Wh thermal) Total Sensible Latent Loads CE5 CE53, Dry CE5, Wet CE53, Dry CE5, Wet CE53, Dry CODYRUN/UR HOT3/NRCan TRACE 7/Trane
79 HVAC BESTEST: f(odb) for CE5, CE53 Specific Day COP CE5, Wet Coil CE53, Dry Coil COP CODYRUN/UR HOT3/NRCan TRACE 7/Trane
80 HVAC BESTEST: f(odb) for CE5, CE53 Specific Day Humidity Ratio.2.15 CE5, Wet Coil CE53, Dry Coil Humidity Ratio (kg/kg) CODYRUN/UR HOT3/NRCan TRACE 7/Trane
81 HVAC BESTEST: CE3 June 28 Hourly Electricity Consumption Electricity Consumption (Wh) Compressor + OD Fan Hour CODYRUN/UR HOT3/NRCan TRACE 7/Trane
82 HVAC BESTEST: CE3 June 28 Hourly Coil Loads 25 2 Load (Wh thermal) Sensible Latent Hour CODYRUN/UR HOT3/NRCan TRACE 7/Trane TRNSYS/TUD DOE-2.2/NREL DOE-2.1E-E/NREL EnergyPlus/GARD CODYRUN/UR HOT3/NRCan TRACE 7/Trane
83 HVAC BESTEST: CE3 June 28 Hourly COP COP Hour CODYRUN/UR HOT3/NRCan TRACE 7/Trane
84 HVAC BESTEST: CE3 June 28 Hourly Zone Humidity Ratio Humidity Ratio (kg/kg) Hour CODYRUN/UR HOT3/NRCan TRACE 7/Trane
85 HVAC BESTEST: CE3 June 28 Hourly EDB & EWB EDB Temperature ( C) EWB Hour CODYRUN/UR HOT3/NRCan TRACE 7/Trane TRNSYS/TUD DOE-2.2/NREL DOE-2.1E-E/NREL EnergyPlus/GARD CODYRUN/UR HOT3/NRCan TRACE 7/Trane
86 HVAC BESTEST: CE3 June 28 Hourly ODB Temperature ( C) Hour CODYRUN/UR HOT3/NRCan TRACE 7/Trane
87 HVAC BESTEST: CE3 June 28 Hourly OHR.2.18 Humidity Ratio (kg/kg) Hour CODYRUN/UR HOT3/NRCan TRACE 7/Trane
88 8 7 ESP-r /HOT3 Energy Delivered (GJ) EnergyPlus DOE-2.1E Analytical/semi-analytical TRACE7/Trane 2 1 CASE HE1 CASE HE11 CASE HE12 CASE HE13 CASE HE14 CASE HE15 CASE HE16 CASE HE17 CASE HE21 CASE HE22 CASE HE23
89 1. 9. Energy Consumed (GJ) ESP-r /HOT3 EnergyPlus DOE-2.1E Analytical/semi-analytical TRACE7/Trane CASE HE1 CASE HE11 CASE HE12 CASE HE13 CASE HE14 CASE HE15 CASE HE16 CASE HE17 CASE HE21 CASE HE22 CASE HE23
90 .35.3 ESP-r /HOT3 EnergyPlus.25 DOE-2.1E Analytical/semi-analytical TRACE7/Trane Fuel Consumed (m**3/s) CASE HE1 CASE HE11 CASE HE12 CASE HE13 CASE HE14 CASE HE15 CASE HE16 CASE HE17 CASE HE21 CASE HE22 CASE HE23
91 6 ESP-r /HOT3 EnergyPlus 5 DOE-2.1E Analytical/semi-analytical TRACE7/Trane 4 Fan Consumption (kwh) CASE HE15 CASE HE16 CASE HE17 CASE HE21 CASE HE22 CASE HE23
92 25 ESP-r /HOT3 EnergyPlus DOE-2.1E 2 TRACE7/Trane Mean Zone Temperature ( C) CASE HE21 CASE HE22 CASE HE23
93 23 ESP-r /HOT EnergyPlus DOE-2.1E 22 TRACE7/Trane Maximum Zone Temperature ( C) CASE HE21 CASE HE22 CASE HE23
94 25 ESP-r /HOT3 EnergyPlus DOE-2.1E 2 TRACE7/Trane Minimum Zone Temperature ( C) CASE HE21 CASE HE22 CASE HE23
REPORT. January 05, Submitted to the:
REPORT ASHRAE Standard 140-2007 Standard Method of Test for the Evaluation of Building Energy Analysis Computer Programs: Test Results for the DOE-2.1E (v120) incorporated in EnergyGauge Summit 4.0 January
More informationTable of Contents. 1 EnergyPlus Testing with HVAC Equipment Performance Tests CE100 to CE200 from ANSI/ASHRAE Standard
Table of Contents Table of Contents 1 EnergyPlus Testing with HVAC Equipment Performance Tests CE100 to CE200 from ANSI/ASHRAE Standard 140-2011 2 1 Test Objectives and Overview 3 1.1 Introduction 3 1.2
More informationDEVELOPMENT OF NEW SELF-COMPARISON TEST SUITES FOR ENERGYPLUS
DEVELOPMENT OF NEW SELF-COMPARISON TEST SUITES FOR ENERGYPLUS Michael J. Witte 1, Robert H. Henninger 1, and Drury B. Crawley 2 1 GARD Analytics, Inc., Park Ridge, IL 2 U.S. Department of Energy, Washington,
More informationDevelopment of New Self-Comparison Test Suites for EnergyPlus
Development of New Self-Comparison Test Suites for EnergyPlus Michael J. Witte Robert H. Henninger GARD Analytics, Inc., Arlington Hts., IL Drury B. Crawley U.S. Department of Energy, Washington, DC IBPSA-USA
More informationEnergyPlus Testing with HVAC Equipment Component Tests
EnergyPlus Testing with HVAC Equipment Component Tests EnergyPlus Version 4.0.0.024 October 2009 Prepared for: U.S. Department of Energy Energy Efficiency and Renewable Energy Office of Building Technologies
More informationA Report of Task 22, Subtask C Building Energy Analysis Tools. Project C.2 Comparative Evaluation. Julia Purdy and Ian Beausoleil-Morrison
Building Energy Simulation Test and Diagnostic Method for Heating, Ventilation, and Air-Conditioning Equipment Models (HVAC BESTEST): Fuel-Fired Furnace Test Cases A Report of Task 22, Subtask C Building
More informationLoad Estimation. Ir. Dr. Sam C. M. Hui Faculty of Science and Technology
SPD4121 HVAC Technology for Plumbing Engineers http://ibse.hk/spd4121/ Load Estimation Ir. Dr. Sam C. M. Hui Faculty of Science and Technology E-mail: cmhui@vtc.edu.hk Jul 2016 Contents Basic Concepts
More informationHVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya
HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya (vahid.vakiloroaya@engineer.com) ABSTRACT: The overall attainable reduction in energy consumption and enhancement of
More informationLoad Calculations Heat Balance Method - Application
Load Calculations Heat Balance Method - Application Prof. Jeffrey D. Spitler School of Mechanical and Aerospace Engineering, Oklahoma State University Weather Data: Cooling Three types of design days Based
More informationHeat Load Calculation for Air Conditioning System
Heat Load Calculation for Air Conditioning System ADARSH G R 1, ARUN MICHAEL 2 1,2 Mohandas College of Engineering and Technology Abstract: Human comfort is essential now a day because of the improvement
More informationPHPP V9.6 Validation using ANSI/ASHRAE Standard
PHPP V9.6 Validation using ANSI/ASHRAE Standard 140-2017 Prepared for: Passive House Canada, Passive House California, New York Passive House, and the Passive House Institute Prepared by: Remi Charron,
More informationDynamic simulation of buildings: Problems and solutions Università degli Studi di Trento
Dynamic simulation of buildings: Problems and solutions Università degli Studi di Trento Paolo BAGGIO The basic problem To design (and operate) energy efficient buildings, accurate modeling tools are needed.
More informationOpportunities and Limitations of Building Precooling
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1994 Opportunities and Limitations of Building Precooling K. R. Keeney Purdue
More informationEnergy Analysis of Using Thermal Mass in a Hot Humid climate
Energy Analysis of Using Thermal in a Hot Humid climate SARA MOTAMEDI Architecture Department University of Texas at Austin 1 University Station B7500 Austin, Texas, U.S.A, 787us2-0222 s.motamedi@mail.utexas.edu
More informationEnergyPlus Testing with Building Thermal Envelope and Fabric Load Tests from ANSI/ASHRAE Standard
EnergyPlus Testing with Building Thermal Envelope and Fabric Load Tests from ANSI/ASHRAE Standard 140-2007 EnergyPlus Version 4.0.0.024 October 2009 Prepared for: U.S. Department of Energy Energy Efficiency
More informationCHAPTER 3. BUILDING THERMAL LOAD ESTIMATION
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating
More informationA NEW POLYNOMIAL BASED MODEL FOR DETERMINING COOLING TOWER EVAPORATION WATER LOSS. Aaron Powers Johnson Controls, Inc.
ASHRAE and IBPSA-USA SimBuild 2016 Building Performance Modeling Conference Salt Lake City, UT August 8-12, 2016 A NEW POLYNOMIAL BASED MODEL FOR DETERMINING COOLING TOWER EVAPORATION WATER LOSS Aaron
More informationTWO DOE-2 FUNCTIONS. Tianzhen Hong, Charles Eley, and Erik Kolderup Architectural Energy Corporation 142 Minna Street, San Francisco, CA 94105, USA
Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 TWO DOE-2 FUNCTIONS Tianzhen Hong, Charles Eley, and Erik Kolderup Architectural Energy Corporation 142 Minna Street, San Francisco,
More informationIMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS
IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS Daeho Kang 1, Richard K. Strand 2 1 Department of Environmental Control Technology, New York
More informationFULL YEAR PERFORMANCE SIMULATION OF A DIRECT-COOLED THERMAL STORAGE ROOF (DCTSR) IN THE MIDWEST
FULL YEAR PERFORMANCE SIMULATION OF A DIRECT-COOLED THERMAL STORAGE ROOF (DCTSR) IN THE MIDWEST Richard C. Bourne Davis Energy Group, Inc. 123 C Street Davis, CA 95616 and Dr. Bing Chen Passive Solar Research
More informationMeeting the Variable Needs of Energy- Efficient Mechanical Ventilation When and Where You Need It
Meeting the Variable Needs of Energy- Efficient Mechanical Ventilation When and Where You Need It Charles Withers Jr. 1 Introduction Effectively providing mechanical ventilation in commercial buildings
More informationPackaged Refrigerant Based Energy Storage (RBES) Air Conditioning System
Packaged Refrigerant Based Energy Storage (RBES) Air Conditioning System Ram Narayanamurthy Ice Energy, Inc. this technology provides some of the largest opportunities we have right now to address the
More informationRESNET Summit: What s Happening With HERS Rating Software
RESNET Summit: What s Happening With HERS Rating Software EEBA High Performance Home Summit 2017 October 10-12, 2017 Philip Fairey A Research Institute of the University of Central Florida Acknowledgements
More informationModeling Energy Consumption Effects of Glazing
Modeling Energy Consumption Effects of Glazing Daniel Lu 12/7/2012 Table of Contents Introduction... 3 Design Options... 5 Option 1... 5 Option 2... 5 Preliminary Energy Simulation... 7 Objectives... 7
More informationPerformance Mapping for Variable Ductless Heat Pump Systems in Heating, Cooling and Defrost Operation
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Performance Mapping for Variable Ductless Heat Pump Systems in Heating,
More informationReducing Operating Costs with Optimal Maintenance Scheduling
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1994 Reducing Operating Costs with Optimal Maintenance Scheduling T. M. Rossi
More informationCAE 331/513 Building Science Fall 2017
CAE 331/513 Building Science Fall 2017 November 14, 2017 Heating load calculations Advancing energy, environmental, and sustainability research within the built environment www.built-envi.com Twitter:
More informationASHRAE ADDENDA Standard Method of Test for the Evaluation of Building Energy Analysis Computer Programs
ANSI/ASHRAE Addendum c to ANSI/ASHRAE Standard 140-2007 ASHRAE ADDENDA Standard Method of Test for the Evaluation of Building Energy Analysis Computer Programs Approved by the ASHRAE Standards Committee
More informationThe Effects of Residential Energy Efficiency on Electric Demand Response Programs
2014 47th Hawaii International Conference on System Science The Effects of Residential Energy Efficiency on Electric Response Programs Ward Jewell Wichita State University ward.jewell@wichita.edu Abstract
More informationIMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE
IMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE Dr. Essam Al-Sayed Omar Department Manager Kuwait Institute for Scientific Research Kuwait ABSTRACT This paper addresses the
More informationThermal Comfort and Energy Consumption according to the Indoor Control Logic
Thermal Comfort and Energy Consumption according to the Indoor Control Logic S. Kim 1 and D. Song 2 1 Department of Civil and Environmental System Engineering Sungkyunkwan University, Suwon-si, Gyeonggi-do
More informationChilled Water Plant Redesign
17 Chilled Water Plant Redesign OVERVIEW The chilled water plant redesign includes the addition of a thermal energy storage system. This allows for economic and operational benefits for the facility by
More informationEER & SEER AS PREDICTORS OF SEASONAL COOLING PERFORMANCE
EER & SEER AS PREDICTORS OF SEASONAL COOLING PERFORMANCE Southern California Edison Design & Engineering Services 642 N. Irwindale Avenue, Suite B Irwindale, California 9172 October 24 ACKNOWLEDGEMENTS
More informationProcedures for Verification of International Energy Conservation Code (IECC) Performance Path Calculation Tools
Procedures for Verification of International Energy Conservation Code (IECC) Performance Path Calculation Tools RESNET Publication No. 003-14 March, 2014 Published by: Residential Energy Services Network,
More informationSenior Design Project for UNO. Design of the International Studies Building: An Environmental Analysis
Senior Design Project for UNO Design of the International Studies Building: An Environmental Analysis Design Intent Implement Passive & Active design strategies in order to make the building: More Energy
More informationDISPLACEMENT VENTILATION
DISPLACEMENT VENTILATION D3 OVERVIEW The fundamental approach to displacement ventilation utilizes the natural buoyancy forces created by the convective flows from heat sources in the space. As supply
More informationIESVE Compliance for ASHRAE IES Virtual Environment
IESVE Compliance for ASHRAE 90.1 - IES Virtual Environment July 2018 IES Virtual Environment and Compliance with ASHRAE 90.1-2004, 2007, 2010 & 2013; Appendix G, Performance Rating Method and Chapter 11,
More informationBUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1
BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY Dr Mirek Piechowski 1, Adrian Rowe 1 Meinhardt Building Science Group, Meinhardt Australia 1 Level 12, 501
More informationcarbon-neutral architectural design Pablo La Roche CRC Press Taylor & Francis Croup Boca Raton London NewYork CRC Press is an imprint of the
carbon-neutral architectural design Pablo La Roche CRC Press Taylor & Francis Croup Boca Raton London NewYork CRC Press is an imprint of the Taylor fit Francis Group, an informs business Contents Preface
More informationThermal Analysis of CL-TALON Cladding Support System
Report Number: 180181400 February 16, 2018 Thermal Analysis of CL-TALON Cladding Support System Presented to: CL-TALON 3223 Dell Ave. North Bergen, NJ 07047 Morrison Hershfield Suite 310, 4321 Still Creek
More informationThermal Thermal Applications Category Version 6.4. Integrated Environmental Solutions
Thermal Thermal Applications Category Version 6.4 Integrated Environmental Solutions Contents 1. What is the Thermal Applications Category?... 4 1.1. Compliance View... 4 1.2. Apache
More informationAn Optimal Maintenance Scheduler
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1994 An Optimal Maintenance Scheduler T. M. Rossi Purdue University J. E. Braun
More informationAnalysis of Heat Gain in Computer Laboratory and Excellent Centre by using CLTD/CLF/SCL Method
Available online at www.sciencedirect.com Procedia Engineering 53 ( 2013 ) 655 664 Malaysian Technical Universities Conference on Engineering & Technology 2012, MUCET 2012 Part 2 Mechanical And Manufacturing
More informationANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS
ANSI/ASHRAE STANDARD 200-2015, METHODS OF TESTING CHILLED BEAMS NEMIC 2017 Agenda 1. Foreword 2. Purpose & Scope 3. Definitions 4. Instrumentation & Facilities 5. Test Methods 6. Reporting 7. Normative
More informationDEFINING THE METHODOLOGY FOR THE NEXT-GENERATION HOT2000- SIMULATOR
DEFINING THE METHODOLOGY FOR THE NEXT-GENERATION HOT2000- SIMULATOR Debra Haltrecht 1, Radu Zmeureanu 2 and I. Beausoleil-Morrison 1 1 Natural Resources Canada, Ottawa K1A 0E4, Canada 2 Concordia University,
More informationTHERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE
S447 THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE by Bojan V. ANDJELKOVIĆ *,a, Branislav V. STOJANOVIĆ b, Mladen M. STOJILJKOVIĆ b, Jelena N. JANEVSKI
More informationCOPs, EERs, and SEERs
Power Knot LLC 501 Valley Way Milpitas CA 95035 COPs, EERs, and SEERs How Efficient is Your Air Conditioning System? USA +1-408-889-8433 www.powerknot.com 1 Introduction This note discusses performances
More informationCOOLING LOAD ESTIMATION OF A ROOM
COOLING LOAD ESTIMATION OF A ROOM Prof. Deepak Kumar Yadav 1, Aviral Srivastava 2, Ayush Chauhan 3, Gaurang Tripathi 4, Ankur Kumar 5 1Assistant Professor, Mechanical Engineering, IMS Engineering College,
More informationDynamic Simulation of an Office Building in Two Different Softwares
Dynamic Simulation of an Office Building in Two Different Softwares Joana Filipa Das Neves Cartas * * e-mail: joana.cartas@gmail.com Abstract: This project has the goal of performing a comparative analysis
More informationComparative Study On Simulation Tools Of Annual Heat Load For Energy Management Y. Takahashi 1 *, G. Yoon 1, M. Yoshinaga 2, and R. Chiba 3 1 Graduate
Comparative Study On Simulation Tools Of Annual Heat Load For Energy Management Y. Takahashi 1 *, G. Yoon 1, M. Yoshinaga 2, and R. Chiba 3 1 Graduate School of Design and Architecture, Nagoya City University,
More informationEnergy Efficiency Analysis for a Multi-Story Research Office Building (LG Multi V Water IV Heat Recovery VRF System)
Energy Efficiency Analysis for a Multi-Story Research Office Building (LG Multi V Water IV Heat VRF System) (* Source: http://kr.lgeaircon.com/) Commercial Air-Conditioning Engineering Study ES-MultiVWaterIV_EnergyAnalysis-08-14
More informationThe bitterness of poor quality is remembered long after the sweetness of low price is forgotten!
Heat Pump Sizing Using ACCA Manual J8 It s s a Building Code Requirement Size the Equipment BEFORE You Build The bitterness of poor quality is remembered long after the sweetness of low price is forgotten!
More informationBUILDING SERVICE ENGINEERING 2 BUILDING MODELING AND DYNAMIC SIMULATION
BUILDING SERVICE ENGINEERING 2 BUILDING MODELING AND DYNAMIC SIMULATION Asst. Prof. Dr. Norbert Harmathy Budapest University of Technology and Economics OUTLINE Integrated design process Building model
More informationEnergy Efficiency in Building Active Design Part II
Energy Efficiency in Building Active Design Part II Presented by: CK Tang BSEEP Component 4 Manager Veritas Enviornment Sdn Bhd ck.tang@veritas.com.my Air Conditioning System System Sizing 1 Current Industry
More informationTechnical Assignment 2 Building and Plant Energy Analysis
Technical Assignment 2 Building and Plant Energy Analysis Des Places Residence Hall Duquesne University Pittsburgh, PA Peter Edwards Advisor: James Freihaut October 4, 2010 Table of Contents Executive
More informationTHERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE
Andjelković, V., B.et. al.: Thermal Mass Impact on Energy Performance of A Low, Medium and Heavy S507 THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE by Bojan
More informationA Case Study of Energy Demand in Housing Units
A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar 1, Former Graduate Student Dr. Sudhir Misra 1, Professor Dr. Naveen Tiwari 2, Associate Professor 1 Department of Civil Engineering,
More informationMODELLING AND SIMULATION OF BUILDING ENERGY SYSTEMS USING INTELLIGENT TECHNIQUES
MODELLING AND SIMULATION OF BUILDING ENERGY SYSTEMS USING INTELLIGENT TECHNIQUES Ph.D. THESIS by V. S. K. V. HARISH ALTERNATE HYDRO ENERGY CENTRE INDIAN INSTITUTE OF TECHNOLOGY ROORKEE ROORKEE-247667 (INDIA)
More informationESRU. Technical Report. CIBSE TM33 Tests for Software Accreditation and Verification: ESP-r Test Results
ESRU Technical Report CIBSE TM33 Tests for Software Accreditation and Verification: ESP-r Test Paul Strachan, Georgios Kokogiannakis, Aizaz Samuel and Nick Kelly Energy Systems Research Unit 27 March 2008
More informationBUILDING ENVELOPE HEAT FLOW. Building Envelope
BUILDING ENVELOPE HEAT FLOW stuff lots of stuff happens when a building meets a climate Ball State Architecture ENVIRONMENTAL SYSTEMS 1 Grondzik 1 Building Envelope A general term that describes the various
More informationDRAFT METHODOLOGY FOR CALCULATING COOLING AND HEATING ENERGY-INPUT-RATIO (EIR) FROM THE RATED SEASONAL PERFORMANCE EFFICIENCY (SEER OR HSPF)
ESL-TR-13-04-01 DRAFT METHODOLOGY FOR CALCULATING COOLING AND HEATING ENERGY-INPUT-RATIO (EIR) FROM THE RATED SEASONAL PERFORMANCE EFFICIENCY (SEER OR HSPF) A Project for Texas Senate Bill 5 Legislation
More informationCAE 331/513 Building Science Fall 2016
CAE 331/513 Building Science Fall 2016 Week 15: December 1, 2016 Standards and guidelines for energy efficiency Advancing energy, environmental, and sustainability research within the built environment
More informationThe Art of Thermal Mass Modeling for Energy Conservation in Buildings, Part 2
The Art of Thermal Mass Modeling for Energy Conservation in Buildings, Part 2 Linda Lam is a Project Engineer at Transsolar, Inc. She has a traditional mechanical engineering background with an energetic
More informationHourly Analysis Program v.4.1 Page 1 of 1
Air System Design Load Summary for Zona 11 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible
More informationAREN 3050 ENVIRONMENTAL SYSTEMS FOR BUILDINGS I FALL 2005
1. Psychrometrics a) Moist air has a dry bulb temperature of 80 F and a wet bulb temperature of 67 F? What is the enthalpy at sea level? What is the enthalpy at 5000 ft above sea level? b) A building zone
More informationTHE USE OF HEAT RECOVERY DEVICES FOR REDUCING ENERGY CONSUMPTION OF TREATING VENTILATION AIR IN A TROPICAL OPERATING THEATRE
T13-O-15: Air conditioning components Proceedings: EERB-BEPH 2009 THE USE OF HEAT RECOVERY DEVICES FOR REDUCING ENERGY CONSUMPTION OF TREATING VENTILATION AIR IN A TROPICAL OPERATING THEATRE Y.H. Yau *
More informationCAE 331/513 Building Science Fall 2017
CAE 331/513 Building Science Fall 2017 November 28, 2017 Energy estimation and design for efficiency Advancing energy, environmental, and sustainability research within the built environment www.built-envi.com
More informationCOMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING
COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING ABSTRACT F. Bagheri 1, M. Fakoor 1, B. Young 1, C. Cranswick 1 1 BC Building Science Ltd. 611 Bent
More informationEnergy efficiency building standards in Taiwan
www.asiabusinesscouncil.org Energy efficiency building standards in Taiwan Taiwan adopted building energy standards for air-conditioned, non-residential buildings in 1995 and for residential buildings
More informationHourly Analysis Program v.4.1 Page 1 of 1
Air System Design Load Summary for Zona 6 DESIGN COOLING DESIGN HEATING COOLING DATA AT Feb 1600 HEATING DATA AT DES HTG COOLING OA DB / WB 34.5 C / 23.7 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent
More information1 Exam Prep Manual J Residential Load Calculation 8 th Edition Tabs and Highlights
1 Exam Prep Manual J Residential Load Calculation 8 th Edition Tabs and Highlights These 1 Exam Prep tabs are based on the Manual J Residential Load Calculation for Small Commercial Buildings, 8 th Edition.
More informationAC2 Evaporative Condenser. Monitoring Report: 1998 Cooling Season
AC2 Evaporative Condenser Monitoring Report: 1998 Cooling Season Report Issued: December 29, 1998 Presented to: Prepared by: Lance Elberling Pacific Gas and Electric Company Davis Energy Group 123 C Street
More informationERRATA SHEET FOR ANSI/ASHRAE STANDARD Standard Method of Test for the Evaluation of Building Energy Analysis Computer Programs
ERRATA SHEET FOR ANSI/ASHRAE STANDARD 140-2007 Standard Method of Test for the Evaluation of Building Energy Analysis Computer Programs December 4, 2008 The corrections listed in this errata sheet apply
More informationAttaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference
Attaining Thermal Comfort in Buildings with Predominantly Glazed Facades presented to: ANSYS Boston Regional Conference September 14, 2011 Case Study Background High floor to ceiling windows Large skylight
More informationOUTDOOR AIR, HEAT WHEELS AND JCPENNEY: A NEW APPROACH TO RETAIL VENTILATION
OUTDOOR AIR, HEAT WHEELS AND JCPENNEY: A NEW APPROACH TO RETAIL VENTILATION Christopher S. Smith, E.I.T. and Thomas A. Bartlett, P.E. JCPenney Company, Inc. Construction Services Mechanical Engineering
More informationGeorgetown University New Science Center
Georgetown University New Science Center Final Thesis Proposal PENN STATE UNIVERSITY Prepared For: Dr. William P. Bahnfleth Department of Architectural Engineering Prepared By: Kevin M Edstrom Mechanical
More informationRESEARCH ON THE ADVANCED USE OF MULTI-SPLIT TYPE AIR-CONDITIONING SYSTEM
- 1 - RESEARCH ON THE ADVANCED USE OF MULTI-SPLIT TYPE AIR-CONDITIONING SYSTEM Yoshinori Suzuki, Master course Student, Masaya Hiraoka, Kajima Corporation, Shin-ichi Tanabe, Professor, Waseda University,
More informationModelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates
Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Kittitach Pichatwatana, and Fan Wang Abstract This paper examines the TAS computer
More informationBuilding Performance Evaluation Guide
Building Performance Evaluation Guide Version 1.6 April 2012 1. Schematic Design & Design Development Phase Requirements Whole building energy simulation shall be used to determine the basis for the designed
More informationTargeting Energy Efficiency in Commercial Buildings Using Advanced Billing Analysis
Targeting Energy Efficiency in Commercial Buildings Using Advanced Billing Analysis Kelly Kissock and Steve Mulqueen, University of Dayton ABSTRACT This paper describes a four-step method to analyze the
More informationNEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.40
NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.40 By: Carrier Software Systems Carrier Corporation Syracuse, New York rev August 11, 2008 Copyright 2008 Carrier Corporation, All Rights Reserved
More informationHVAC SYSTEM CONFIGURATIONS, AN ENERGY ASPECT
HVAC SYSTEM CONFIGURATIONS, AN ENERGY ASPECT Y Zhang 1,*, JA Wright 2 and VI Hanby 1 1 Institute of Energy and Sustainable Development, De Montfort University, Leicester, LE1 9BH, UK 2 Department of Civil
More informationGreen Star Shopping Centre Design PILOT Energy Calculator Guide
Green Star Shopping Centre Design PILOT Energy Calculator Guide Prepared by: Advanced Environmental Green Building Council of Australia Page 1 of 29 EXECUTIVE SUMMARY The Green Star Shopping Centre Design
More informationEnergy and indoor temperature consequences of adaptive thermal comfort standards
Energy and indoor temperature consequences of adaptive thermal comfort standards L. Centnerova and J.L.M. Hensen Czech Technical University in Prague, Czech Republic (lada@tzb.fsv.cvut.cz) Technische Universiteit
More informationSimulation of Source Energy Utilization and Emissions for HVAC Systems. A report ASHRAE TC 6.9 in response to the 991-TRP workstatement.
Simulation of Energy Utilization and Emissions for HVAC Systems A report ASHRAE TC 6.9 in response to the 991-TRP workstatement submitted by Douglas T. Reindl, Ph. D, P.E. Director of Research University
More informationHourly Analysis Program v.4.1 Page 1 of 1
Air System Design Load Summary for Zona 9 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 1400 HEATING DATA AT DES HTG COOLING OA DB / WB 34.5 C / 23.7 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent
More informationLarge University Central Chiller Plant Design Considerations
Carrier Engineering Newsletter Volume 5, Issue 3 Large University Central Chiller Plant Design Considerations Large campus chilled water plants have unique constraints and need careful evaluation for successful
More informationThermally Driven Cooling
2016 Title 24 Codes & Standards Enhancement (CASE) Proposal Thermally Driven Cooling May 20, 2014 Matt Tyler, PE mtyler@peci.org Stakeholder Meeting 1: Agenda Code change overview Current code requirements
More informationVALIDATION OF THE INTERNATIONAL CODE COMPLIANT CALCULATOR (IC3) v USING THE RESNET VERIFICATION PROCEDURES (NO )
ESL-TR-11-12-01 VALIDATION OF THE INTERNATIONAL CODE COMPLIANT CALCULATOR (IC3) v3.10.3 USING THE RESNET VERIFICATION PROCEDURES (NO. 07-003) Hyojin Kim Juan-Carlos Baltazar, Ph.D. Jeff S. Haberl, Ph.D.,
More informationHourly Analysis Program v.4.1 Page 1 of 1
Air System Design Load Summary for Zona 3 Project Name: Av. Cabildo 3067, 4 piso 02/13/2011 DESIGN COOLING DESIGN HEATING COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 34.9 C / 23.8
More informationQUANTIFYING THE REDUCTION IN COOLING ENERGY DUE TO PASSIVE COOLING TECHNIQUES FOR INDIAN CITIES
2018 Building Performance Analysis Conference and SimBuild co-organized by ASHRAE and IBPSA-USA Chicago, IL September 26-28, 2018 QUANTIFYING THE REDUCTION IN COOLING ENERGY DUE TO PASSIVE COOLING TECHNIQUES
More informationENERGY ANALYSIS AND ENERGY CONSERVATION OPTION FOR THE WAREHOUSE FACILITY AT THE HUMAN SERVICES CENTER COMPLEX DRAFT REPORT.
ESL-TR-86/09-03 ENERGY ANALYSIS AND ENERGY CONSERVATION OPTION FOR THE WAREHOUSE FACILITY AT THE HUMAN SERVICES CENTER COMPLEX DRAFT REPORT Submitted by Mohsen Farzad Dennis O'Neal Prepared For Energy
More informationHourly Analysis Program v.4.1 Page 1 of 1
Air System Design Load Summary for Zona 8 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent
More information1 Project Information. 2 Building Type. 3 Trade Ally/Contractor Information. HVAC Rebate Worksheet. Retrofit New Construction
HVAC Rebate Worksheet Before you start Instructions: Complete all relevant information for your project. Include with complete application package. The HVAC Worksheet should be completed for new construction
More informationPerformance analysis of a new single effect hot water absorption chiller system
University of Technology, Sydney Master Thesis Performance analysis of a new single effect hot water absorption chiller system Author: Saket Sinha Supervisor: Associate Professor Quang Ha A thesis submitted
More informationInverter Drive Control and Seasonal Performance Analysis of a Single Speed Unitary Air-Source Split-System Heat Pump
Inverter Drive Control and Seasonal Performance Analysis of a Single Speed Unitary Air-Source Split-System Heat Pump Abstract Nicholas P. Salts a*, Eckhard A. Groll a a Purdue University, Ray W. Herrick
More informationCoppin State University Physical Education Complex - Technical Report 2
Coppin State University Physical Education Complex - Technical Report 2 Building and Plant Energy Analysis Report Kaylee M Damico Advisor: Dr. Jelena Srebric Location: Baltimore, MD Table of Contents Contents
More informationM. Karagiorgas, M. Tsagouris, K. Galatis BONAIR Meletitiki, Greece. A. Botzios-Valaskakis CRES, Greece ABSTRACT
491 Solar assisted heat pump in dual mode: direct and indirect space. Heating by the air collectors. Simulation results and evaluation with measurement results M. Karagiorgas, M. Tsagouris, K. Galatis
More informationHVAC Efficiency and Baseline Nonresidential HVAC Stakeholder Meeting #2
1 HVAC Efficiency and Baseline Nonresidential HVAC Stakeholder Meeting #2 California Statewide Utility Codes and Standards Program Abhijeet Pande Heschong Mahone Group, Inc. December 9, 2010 12/09/2010
More informationTable of Contents. 1 EnergyPlus Testing with HERS BESTEST Tests from ANSI/ASHRAE Standard Test Objectives and Overview
Table of Contents Table of Contents 1 EnergyPlus Testing with HERS BESTEST Tests from ANSI/ASHRAE Standard 140-2011 2 1 Test Objectives and Overview 3 1.1 Introduction 3 1.2 Test Type: Comparative - Loads
More information