Ministry of Defence Defence Standard 61-12(Part 26)

Size: px
Start display at page:

Download "Ministry of Defence Defence Standard 61-12(Part 26)"

Transcription

1 Ministry of Defence Defence Standard 61-12(Part 26) Issue 3 Publication Date 27 January 2001 Wires, Cords and Cables, Electrical Part 26: Wires, and Cables Electrical, Dual Extruded Insulation Type Olefin/vinylidene-Fluoride and Screened and Jacketed Sectional Specification Reprinted 20 th May 2011 to Incorporate Amendment 2

2 AMENDMENT RECORD Amd No Date Text Affected Signature and Date 1 12/10/01 Clauses 0, 1, 3, 6, 8, 9 and 10 and Tables IA to IG 2 20/05/11 Clauses 1.1, 6.2, 6.3, 9.1, 12.20, 12.32, and Table D REVISION NOTE This standard is raised to Issue 3 to update its content. HISTORICAL RECORD This standard supersedes the following: Defence Standard (Def Stan) (Part 26) Issue 2 dated 14 th December Def Stan (Part 26) Issue 2 dated 14 th December 1994 superseded Def Stan (Part 26) Issue 1 dated 25 th March 1985 Def Stan (Part 26) Issue 1 dated 25 th March 1985 superseded specifications EL 2109 and EL 2109M

3 CONTENT Description Page Content 1 Preface 3 Main Text 4 SECTION 1 GENERAL REQUIREMENTS 0 Introduction 4 1 Scope 4 2 Warning 5 3 Related Documents 5 4 Definitions 6 5 Abbreviations 6 SECTION 2 MATERIALS AND CONSTRUCTION 6 Materials 7 7 Construction 8 SECTION 3 CABLE AND WIRE TYPES, IDENTIFCATION AND PACKAGING 8 Cable and wires types 9 9 Marking and identification 9 10 Packaging and labelling 10 SECTION 4 TESTS AND SAMPLE SIZES 11 List of tests and sample sizes 11 SECTION 5 TESTS AND PARAMETERS 12 Tests 13 Table A Table of tests 12 Table B1 Test parameters (thin wall insulation) 16 Table B2 Test parameters (thick wall insulation) 16 Table C Dynamic cut through forces 17 Table D Fluid test list 19 Table E Scrape abrasion test 21 1

4 Table IA Wire Type 2, Single core, without screen or jacket (suitable for use without additional protection) and Cable Type 2, Single core, with screen and jacket (suitable for use without additional protection). 22 Table IB Wire Type 3, Single core, without screen or jacket (suitable for use without additional protection) and Cable Type 3, Single core, with screen and jacket (suitable for use without additional protection). 23 Table IC Cable Type 2 and Type 3, Two core, without screen or jacket, (suitable for use without additional protection), Cable Type 2 and Type 3, Two core, with screen or jacket (suitable for use without additional protection). 24 Table ID Cable Type 2 and Type 3, Three core, without screen or jacket, (suitable for use without additional protection), Cable Type 2and Type 3, Three core, with screen and jacket (suitable for use without additional protection). 25 Table IE Cable Type 2 and Type 3, Four core, with screen and jacket (suitable for use without additional protection). 26 Table IF Wire Type 8, Single core, without screen or jacket and Cable Type 8, Single core, with screen and jacket. 27 Table IG Table 1G: Wire Type 9, Single core, without screen or jacket and Cable Type 9, Single core, with screen and jacket. 28 2

5 PREFACE Standards for Defence Wires, Cords and Cables, Electrical, Metric Units Part 26: Wires and Cables Electrical, Dual Extruded Insulation Type Olefin/vinylidene -Fluoride and Screened and Jacketed a. This standard specifies the requirements for and lists wires and cables electrical, dual extruded insulation, 135 C tin plated and silver-plated conductors for Ministry of Defence use. Tables 1A to 1E inclusive contain the range of thick wall insulation wires and cables. Tables 1F and 1G contain the range of thin wall insulation wires and cables. b. This standard has been produced on behalf of the Standardization Advisory Group (SAG) by the Defence Airborne Cables Standardization Coittee (DACSC). c. This standard has been agreed by the authorities concerned with its use and is intended to be used whenever relevant in all future designs, contracts, orders etc. and whenever practicable by amendment to those already in existence. If any difficulty arises which prevents application of the Defence Standard, the Directorate of Standardization (DStan) shall be informed so that a remedy may be sought. d. Any enquiries regarding this standard in relation to an invitation to tender or a contract in which it is incorporated are to be addressed to the responsible technical or supervising authority named in the invitation to tender or contract. e. Compliance with this Defence Standard shall not in itself relieve any person from any legal obligations imposed upon them. f. This standard has been devised solely for the use of the Ministry of Defence (MOD) and its contractors in the execution of contracts for the MOD. To the extent permitted by law, the MOD hereby excludes all liability whatsoever and howsoever arising (including, but without limitation, liability resulting from negligence) for any loss or damage however caused when the standard is used for any other purpose. 3

6 TEXT Standards for Defence Wires, Cords and Cables, Electrical, Metric Units Part 26: Wires and Cables Electrical, Dual Extruded Insulation Type Olefin/vinylidene -Fluoride and Screened and Jacketed SECTION 1. GENERAL REQUIREMENTS 0 INTRODUCTION This standard specifies the requirements for wires and cables insulated with cross-linked polyolefin and cross-linked polyvinylidene fluoride and, where applicable, jacketed with cross-linked polyvinylidene fluoride. 1 SCOPE 1.1 This standard specifies requirements for airframe wires and cables in temperature category 135 C, with medium and thin wall insulation. This insulation system has been tested for use in aerospace applications using 115 volts (phase to neutral), 400 hertz ac and 28 volts dc. Verification of the suitability of this product for use in other electrical system configuration levels is the responsibility of the user. 1.2 These wires and cables are suitable for fixed wiring at temperatures from 135 C maximum down to minus 75 C but are not suitable for severe flexing at temperatures below minus 40 C. 1.3 These wires and cables do not support combustion and will withstand contamination by ester based lubricants and by ester based hydraulic fluids. 1.4 The thick wall insulated wires and cables, types 2 and 3, are normally available where dimensional replacements for those wires and cables listed in BS 2G 221 are required for wiring without further protection. 1.5 The thin wall insulated wires and cables, types 8 and 9, are intended for internal wiring of equipment. 4

7 SECTION 1. GENERAL REQUIREMENTS 2 WARNING The Ministry of Defence (MOD), like its contractors, is subject to both United Kingdom and European laws regarding Health and Safety at Work, without exemption. All Defence Standards either directly or indirectly invoke the use of processes and procedures that could be injurious to health if adequate precautions are not taken. Defence Standards or their use in no way absolves users from complying with statutory and legal requirements relating to Health and Safety at Work. 3 RELATED DOCUMENTS 3.1 The publications shown below are referred to in the text of this standard. Publications are grouped and listed in alpha numeric order. Designation BS 2G 221 BS 3G 230 BS 3G 231 BS 1595 BS 2713 BS 6476C BS 7207 Def Stan (Part 0) Def Stan Def Stan Def Stan DTD/900/4725 DTD/900/4907 DTD/900/4955 ISO 1817 MIL-C Title Minyvin Type Electric Cables (Metric Units) General Requirements for Aircraft Electrical Cables Conductors for General Purpose Aircraft Electrical Cables and Aerospace Applications Propan-2-ol (Isopropyl Alcohol) for Industrial Use Specification for 2-ethoxyethanol (ethylene glycol monoethyl ether) Colour Chart for Insulation and Sheath of Electric Cables Specification for crude vegetable fats Wires Cords and Cables Electrical. General Requirements and Test Methods Hydraulic Fluid, Petroleum: Normal NATO Code: H520 Joint Service Designation: OM 18 Turbine Fuel, Aviation: Kerosene Type, Containing Fuel System Icing Inhibitor NATO Code: F 34 Joint Service Designation: AVTUR/FSII Turbine Fuel, Aviation: Kerosene Type, Jet A-1 NATO Code: F35 Joint Service Designation: AVTUR (DERD 2494) Rubber, Vulcanised. Determination of the effect of fluids Cleaning compounds, Aircraft Surface 3.2 Reference in this standard to any related document means in any invitation to tender or contract the edition and all amendments current at the date of such tender or contract unless a specific edition is indicated. 5

8 SECTION 1. GENERAL REQUIREMENTS 3.3 In consideration of 3.2 above, users shall be fully aware of the issue and amendment status of all related documents, particularly when forming part of an invitation to tender or contract. Responsibility for the correct application of standards rests with users. 3.4 DStan can advise regarding where related documents are obtained from. Requests for such information can be made to the DStan Helpdesk. How to contact the helpdesk is shown on the outside rear cover of Def Stans. 4 DEFINITIONS For the purpose of this standard the definitions given in BS 3G 230 apply, with the exception of the following: 4.1 Wire electrical Defined as a single metallic conductor of solid, stranded or tinsel construction designed to carry current in an electrical circuit. It may be bare or insulated but does not have a metallic covering, jacket or shield. 4.2 Cable, power, electrical Defined as one or more wires with an outer overall metallic covering/screen and/or jacket. Two or more insulated conductors twisted or moulded together without a coon covering. The rated working voltage of the item shall be 250V or more and the size of each individual conductor shall be or larger. 5 ABBREVIATIONS Designation BS DACSC Def Stan DMSC DStan Fig MOD NATO NSN SAG Title British Standard Defence Airborne Cables Standardization Coittee Defence Standard Defence Materiel Standardization Coittee Directorate of Standardization Figure Ministry of Defence North Atlantic Treaty Organisation NATO Stock Number Standardization Advisory Group 6

9 SECTION 2. MATERIALS AND CONSTRUCTION 6 MATERIALS 6.1 Conductors and braiding Tinned annealed copper conductors shall comply with BS 3G 231 with respect to basic material and quality of tinning Conductors of high strength silver-plated copper alloy shall comply with BS 3G 231 with respect to basic material and plating and shall be plated to a radial thickness of not less than 1μm Strands taken from the conductors of the finished wires or cables shall meet the tensile strength and elongation at break tests specified in BS 3G 231 clause 4. BS 3G 231 Table 3 shall be considered to be extended to cover strand diameters of 0.08 to 0.2 with the requirements remaining as stated. Strands to be used for braiding shall be tested before being woven. 6.2 Insulation The insulation is made up of two layers of material namely primary and secondary. The insulation shall consist of cross-linked polyolefin and shall be of such a quality that the requirements of this standard are met Secondary layer of insulation The insulation shall consist of UV laser markable cross-linked modified polyvinylidene fluoride and shall be of such a quality that all the requirements of this standard are met. Wire and cable types 8 and 9 are not required to be UV laser markable. 6.3 Jacket The jacket shall consist of UV laser markable cross-linked modified polyvinylidene fluoride and shall be of such a quality that all the requirements of this standard are met. Jacketed variants of wire and cable types 8 and 9 are not required to be UV laser markable. 6.4 Colour The secondary insulation shall be coloured. This insulation and any jacket shall be a reasonable colour match with those of BS 6476C. 7

10 SECTION 2. MATERIALS AND CONSTRUCTION 7 CONSTRUCTION 7.1 Conductors Conductors shall be constructed as specified in BS 3G 231 clause 3 except that the number of strands in the conductor and the diameter of the conductor shall be as stated in the Tables of this Standard. 7.2 Insulation The primary and secondary insulation shall be applied by extrusion to fit closely round the conductor and shall be to a uniform circular cross section with a concentricity of greater than 70% throughout the length of the cable. The insulation shall not be loose but it shall be possible to strip it from the conductor leaving the latter in a condition sufficiently clean to permit satisfactory connection to a termination. The insulation thickness shall comply with the relevant tables for the types of cables and wires covered by this standard Secondary layer of insulation A secondary layer of insulation of cross-linked modified polyvinylidene fluoride shall be applied uniformly over the primary insulation, to a thickness shown in the appropriate tables, having an overall concentricity greater than 70%. 8

11 SECTION 3. CABLE AND WIRE TYPES, IDENTIFICATION AND PACKAGING 8 CABLE AND WIRE TYPES. 8.1 Wires Type 2 Wire and cable, single core, single core screened and jacketed, multicore and multicore screened and jacketed, tinned copper conductors, in sizes 24 to 0000, thick wall insulation. Suitable for wiring without further protection. Table 1A and 1C to 1E. 8.2 Wires Type 3 Wire and cable, single core, single core screened and jacketed, multicore and multicore screened and jacketed, silver-plated high strength copper alloy conductors, in sizes 26 to 24, thick wall insulation. Suitable for wiring without further protection. Tables 1B to 1E. 8.3 Wires Type 8. Wire and cable, single core and single core screened and jacketed, tinned copper conductors, in sizes 28 to 12, thin wall insulation. Suitable for the internal wiring of equipment. Table 1F. 8.4 Wires Type 9 Wire and cable, single core and single core screened and jacketed, silver-plated high strength copper alloy conductors, in sizes 30 to 24, thin wall insulation. Suitable for the internal wiring of equipment. Table IG. 9 MARKING AND IDENTIFICATION 9.1 Unless otherwise specified in the contract, the cable type, the number corresponding to the conductor size and the number of cores and construction, shall identify all wires or cables. On the outside surface, a code to identify the country of origin manufacturer and year of manufacture, in accordance with BS 3G 230, shall be durably and legibly printed iediately after the type and size identification (see example below). Wires type 3, single and multicore, without screen or jacket, size 26 AWG do not require a mark. Wire types 8 and 9 do not require any marking Printing DSP26-2T SJ - GB A Printing shall be in a colour that is a contrast to that of the insulation or jacketed as applicable. The horizontal axis of the characters shall be parallel to the axis of the cable for cables with an outside diameter greater than 1.25 and at right angles to the axis of the cable for cables with an outside diameter of 1.25 or less. The height of the characters 9

12 shall be approximately two thirds of the overall diameter of the cable for sizes up to 10 and shall remain at the height for size 10 for all larger sizes. The printing will be repeated at intervals of 250 to 500. SECTION 3. CABLE AND WIRE TYPES, IDENTIFICATION AND PACKAGING Colours Unless otherwise specified in the contract, the insulation for single core cables shall be coloured white. Multicore cables shall be coloured in accordance with BS 3G 230. If the insulation on a single core or the jacket on any other wire type, requires to be coloured anything other than white, then a number, from the list below, shall be added to the Part No (see example below) Code Colour 0 Black 1 Brown 2 Red 2L Light Red 3 Orange 4 Yellow 5 Green 6 Blue 7 Violet 8 Grey 9 White DSP26-2T SJ -2L 10 PACKAGING AND LABELLING Packaging and labelling shall be as stated in the contract. 10

13 SECTION 4. TESTS AND SAMPLE SIZES 11 LIST OF TESTS AND SAMPLE SIZES 11.1 The manufacturer shall have as a minimum carried out tests on representative samples from Table A, column (a) if conformance to this standard is claimed. Evidence of such tests shall be supplied to the purchaser The tests listed in Table A, column (b) shall be performed in accordance with BS 3G 230 clause 7.1 (b) on separate specimens of representative sample of each cable type The tests specified in Table A, column (c) shall be carried out in accordance with BS 3G 230 clause 7.1 (c) The tests specified in Table A column (d) shall be carried out in accordance with BS 3G 230 clauses 7.1 (d) All specimens shall meet the requirements of this Standard. 11

14 SECTION 4. TESTS AND SAMPLE SIZES Table A: Table of tests Description of tests Clause no a b c d Visual examination 12.1 * * * * Mass 12.2 * * * Conductor composition and visual examination of strands 12.3 * * Overall wire and cable construction and dimensions 12.4 * * * Insulation thickness and concentricity 12.5 * * * Conductor tensile strength and elongation at break 12.6 * * * Strand plating continuity 12.7 * * Strand plating adherence 12.8 * * Strand plating thickness 12.9 * * Electrical resistance * * High voltage iersion * High voltage dry spark * * Voltage test on completed cable * * Insulation resistance * * Surface resistance * Accelerated ageing * * Delamination and shrinkage * * Delamination and insulation blockage * Cold bend * * Dynamic cut through * * Flaability * * Flame propagation * * Resistance to fluids * Flexibility * * Climatic * Tensile strength and elongation at break of insulation * * Scrape abrasion * * Colour fastness * Wire to wire abrasion * Overload resistance * Dry arc tracking * UV marking tests * 12

15 SECTION 5. TESTS AND PARAMETERS 12 TESTS 12.1 Visual examination The specimens shall meet the requirements of Def Stan (Part 0) Clause Mass The specimens shall meet the requirements of Def Stan (Part 0) Clause The mass shall not exceed 105% of the nominal value stated in the appropriate table of this Standard Conductor composition and visual examination of strands The specimens shall meet the requirements of Def Stan (Part 0) clauses 12.1 and Overall wire and cable construction and dimensions Specimens taken from each completed production drum shall be examined, measured and comply with clause 6 and the appropriate tables of this Standard Insulation thickness and concentricity The specimens shall meet the requirements of Def Stan (Part 0) clause and the appropriate tables of this Standard Conductor tensile strength and elongation at break The specimens shall meet the requirements of Def Stan (Part 0) clause Strand plating continuity The specimens shall meet the requirements of Def Stan (Part 0) clause Strand plating adherence The specimens shall meet the requirements of Def Stan (Part 0) clause Strand plating thickness The specimens shall meet the requirements of Def Stan (Part 0) clause Electrical resistance The specimens shall meet the requirements of Def Stan (Part 0) clause12.8 and shall comply with the figure specified in the appropriate table of this Standard. 13

16 SECTION 5. TESTS AND PARAMETERS High voltage iersion The specimens shall meet the requirements of Def Stan (Part 0) clause a. For wires Types 2 and 3 the applied voltage will be 2.5kV rms. b. For wires Types 8 and 9 the applied voltage will be 1 kv rms. c. For multicore cables between braid and test fluid the applied voltage shall be 1kV rms High voltage dry spark Def Stan (Part 0) clause or to be applied to the complete insulation of the wire For the primary insulation of wire Types 2 and 3, the applied voltage for test clause shall be 3 kv rms. and for test clause the peak potential shall be 6 kv. For the secondary insulation of wire Types 2 and 3, the applied voltage for test clause shall be 3 kv rms. and for BS 3G 230 test 16 (c) the peak potential shall be 10 kv For the primary insulation of wire Types 8 and 9, the applied voltage for test clause shall be 1.5 kv rms. and for test clause the peak potential shall be 5 kv. For the secondary insulation of wire Types 8 and 9, the applied voltage for test clause shall be 3 kv rms. and for test clause the peak potential shall be 8 kv Voltage test on completed cable All cable produced shall be subjected to and meet the requirements of BS 3G 230 test 16(d). In addition cables shall have the specified potential applied between the screen and a suitable electrode system on the jacket and shall meet the requirement of BS 3G 230 test 16 (d). For cables 8 and 9 the applied potential between conductor and screen and screen and the outer electrode shall be 1 kv rms Insulation resistance The specimens shall meet the requirements of Def Stan (Part 0) clauses and The test solution and requirements shall be as stated in BS 3G 230 test Surface resistance The specimens shall meet the requirements of Def Stan (Part 0) clauses

17 SECTION 5. TESTS AND PARAMETERS Accelerated ageing. The specimens shall meet the requirements of Def Stan (Part 0) clause Mandrel diameters and tensile forces shall be as specified in Table B. The specimens shall remain in the oven for 168 hours at a temperature of 200 C ± 3 C. The mandrel diameters and tensile forces for the room temperature bend test are given in Table B. 15

18 SECTION 5. TEST METHODS AND PARAMETERS Table B1: Test Parameters (thin wall insulation) Size Maximum Mandrel Minimum Tensile force N Ageing and Room Temperature Bend Flexibility Ageing and Room Temperature Bend Flexibility Cold Bend Wire Cable Wire Cable Table B2: Test Parameters (thick wall insulation) Size Maximum Mandrel Minimum Tensile force N Ageing and Room Temperature Bend Flexibility Ageing and Room Temperature Bend Flexibility Cold Bend Wire Cable Wire Cable

19 SECTION 5. TEST METHODS AND PARAMETERS Delamination and shrinkage The specimens shall meet the requirements of Def Stan (Part 0) clause The total length of conductor or screen exposed on completion of the test shall not exceed Delamination and insulation blockage The specimens shall meet the requirements of Def Stan (Part 0) clause The mandrel diameters and tensile forces are specified in Table B Cold bend The specimens shall meet the requirements of Def Stan (Part 0) clause Mandrel diameters shall be 20 times the nominal overall size of the wire or cable and the tensile force shall be as specified in Table B. The chamber temperature shall be minus 55 C ± 5 C and the pre-conditioning time 4 hours Dynamic cut-through The specimens shall meet the requirements of Def Stan (Part 0) clause Specimens shall be tested at a temperature 135 C ± 3 C the minimum force required to achieve cut through being specified in Table C. The rate of loading of the cutting edge shall be 1± 0.1 N/s. Table C: Dynamic Cut through Forces Size Minimum force N Type 2 and 3 Type 8 and

20 SECTION 5. TESTS AND PARAMETERS Flaability The specimens shall meet the requirements of Def Stan (Part 0) Clause The period of flame application shall be 15 seconds Flame propagation The specimens shall meet the requirements of Def Stan (Part 0) Clause The period of flame application shall be 15 seconds Resistance to fluids The specimens shall meet the requirements of Def Stan (Part 0) Clause The temperature and the fluids shall be as stated in Table D. The iersion time shall be 20 hours minimum. 18

21 SECTION 5. TEST METHODS AND PARAMETERS Table D: Fluid Test List Test fluid Specification Temperature (see note 3) Fuels Hydraulic fluids Aviation turbine Def Stan Def Stan C ± 2 C 70 C ± 2 C Kerosene ISO 1817 Liquid F 70 C ± 2 C Gasoline ISO 1817 Liquid B 40 C ± 2 C Mineral based Def Stan C ± 2 C (see Note 1) 70 C ± 2 C Phosphate ester based DTD 900/ C ± 5 C (synthetic) ISO 1817 Liquid C ± 2 C Silicone Based DTD 9OO/ C ± 5 C Dimethyl silicone, C ± 2 C 2 /s (CST) at 25 C (EX NATO S1714) Non Mineral Based (synthetic) 80% 2 Ethoxyethanol (Ethylene Glycol Monoethyl Ether) to BS 2713 and 20% Castor Oil to BS 7207 by volume 100 C ± 5 C Lubricating oils Mineral based D ENG RD 2450 Grade D C ± 5 C Ester based (synthetic) ISO 1817 Liquid C ± 5 C Solvents and cleaning fluids De-icing and antifreeze fluids Sullage Propan-2-ol (isopropyl alcohol) BS C ± 2 C Detergent cleaning fluid MIL-C C ± 2 C minimum ph 10 Kilfrost ABC DTD 900/ C ± 2 C 4 ± 0.1% formaldehyde plus 1 ± 0.1 % Cresylic acid (mixed isomers general purpose reagent) and 95% water (see Note 2) 23 C ± 2 C Salt water 3.5% NaCl 50 C ± 2 C Deionized water 50 C ± 2 C NOTE 1 NATO H-515 may be used as an alternative. NOTE 2 If difficulty is experienced in producing a solution, pure m-cresol may be used NOTE 3 Some test temperatures exceed the critical flash point temperature. Expert advice shall be sought on the conduct of these tests. 19

22 SECTION 5. TESTS AND PARAMETERS Flexibility Specimens of wire or cable shall be wound on a mandrel under a tensile force at a temperature of 20 C ± 5 C into a close helix of at least three turns. The diameter of the mandrels and the tensile forces applicable are specified in Table B. The test shall comprise of five cycles, each cycle consisting of winding the wire or cable onto the mandrel, unwinding and rewinding in the opposite direction, so that the surface of the cable inside the helix during one winding is on the outside of the helix during the succeeding winding. No part of the wire or cable shall show signs of cracking or other damage The same specimens shall then meet the requirements of the high voltage iersion test, see clause Climatic The specimens shall meet the requirements of Def Stan (Part 0) clause The climatic category shall be 65/135/10 the mandrel diameter shall be 5 times the cable OD and the low air pressure shall be 44.9 millibars (70,000 feet) Tensile strength and elongation at break of insulation The specimens shall meet the requirements of Def Stan (Part 0) clause The average elongation of the insulation achieved for all types of wire shall not be less than 150% The average tensile strength of the insulation achieved for Type 2 shall be: Size 24 to 12 inclusive Size 10 to 4 inclusive 17.5 N/ 2 minimum 14 N/ 2 minimum The average tensile strength of the insulation achieved for Type 3, Type 8 and Type 9 shall be 17.5 N/ 2 minimum Scrape Abrasion. (Applicable only to Types 2 and 3) The specimens shall meet the requirements of Def Stan (Part 0) clause The temperature shall 120 C. The force and number of cycles are given in Table E. 20

23 SECTION 5. TESTS AND PARAMETERS Table E: Scrape Abrasion Test Size Force N Minimum Cycles Colour fastness The specimens shall meet the requirements of Def Stan (Part 0) clauses 13.9 and Wire to wire abrasion The specimens shall meet the requirements of Def Stan (Part 0) clause The test shall be performed on a sample of with a load of 2.5 kg. The minimum number of cycles shall be 1,000,000. Applicable to Types 2 and Overload resistance The specimens shall meet the requirements of Def Stan (Part 0) clause Temperatures T 1 and T 2 shall be 200 C and 250 C respectively Dry arc tracking Specimens shall be subjected to the test specified in BS 3G 230 test 43 except as follows: Three samples of 5 looms shall be tested. If a sample fails, the test shall be repeated. If a failure occurs on re-test, the wire shall be rejected. The results of the test shall show that in a sample, no more than 5 wires of the 25 group A wire in a sample tested shall have open circuited, of which no more than 2 are to be from any one loom. The char length in any wire shall not exceed Requirements for user applied markings Ultra violet laser (excimer laser) A length of cable shall be marked using an ultra violet laser marking system at 150 intervals and tested in accordance with Defence Standard (Part 0) clause The Damp Heat Steady State test may be omitted. 21

24 Table 1A: Wire Type 2, Single core, without screen or jacket (suitable for use without additional protection) and Cable Type 2, Single core, with screen and jacket (suitable for use without additional protection) Part No NSN Size Stranding Number/ Nominal Conductor Maximum Primary Insulation Thickness Nominal Secondary Insulation Thickness Wire Jacket Thickness Cable Outside Nominal min max. min nom nom max DSP26-2T / DSP26-2T-22-1SJ DSP26-2T / DSP26-2T-20-1SJ DSP26-2T / DSP26-2T-18-1SJ DSP26-2T / DSP26-2T-16-1SJ DSP26-2T / DSP26-2T-14-1SJ DSP26-2T / DSP26-2T-12-1SJ DSP26-2T / DSP26-2T-10-1SJ DSP26-2T / DSP26-2T-8-1SJ DSP26-2T / DSP26-2T-6-1SJ DSP26-2T / DSP26-2T-4-1SJ DSP26-2T / DSP26-2T-2-1SJ DSP26-2T / DSP26-2T-0-1SJ DSP26-2T / DSP26-2T-00-1SJ DSP26-2T / DSP26-2T-000-1SJ DSP26-2T / DSP26-2T SJ Note 1: The upper NATO Stock number against each size denotes the wire and is only applicable to a wire which has white insulation Note 2: The lower NATO Stock number against each size denotes the cable and is only applicable to a cable which has white insulation and a white jacket Resistance Ohms/Km at 20 C Wire Nominal Mass Kg/Km Cable Max Mass Kg/Km DEF STAN 61-12(Part 26)/3 Amendment 2

25 Table 1B: Wire Type 3, Single core, without screen or jacket (suitable for use without additional protection) and Cable Type 3, Single core, with screen and jacket (suitable for use without additional protection) Part No NSN Size Stranding Number/ Nominal Conductor Max. Primary Insulation Thickness Nom Secondary Insulation Thickness Nom Wire Jacket Thickness Cable Outside Resistance Ohms/Km at 20 C max. Nominal Mass Kg/Km Cable Mass Max Kg/Km DSP26-3S DSP26-3S-26-1SJ DSP26-3S DSP26-3S-24-1SJ min max. min max. min nom min max / / wire screened Note 1: The upper NATO Stock number against each size denotes the wire and is only applicable to a wire which has white insulation Note 2: The lower NATO Stock number against each size denotes the cable and is only applicable to a cable which has white insulation and a white jacket DEF STAN 61-12(Part 26)/3 Amendment 2

26 Table 1C: Cable Type 2 and Type 3, Two core, without screen or jacket, (suitable for use without additional protection), Cable Type 2 and Type 3, Two core, with screen and jacket (suitable for use without additional protection). Part No NSN Size Jacket Thickness Outside min nom nom max Maximum Mass Kg/Km DSP26-3S DSP26-3S-26-2SJ DSP26-3S DSP26-3S-24-2SJ DSP26-2T DSP26-2T-22-2SJ DSP26-2T DSP26-2T-20-2SJ DSP26-2T DSP26-2T-18-2SJ DSP26-2T DSP26-2T-16-2SJ DSP26-2T DSP26-2T-14-2SJ DSP26-2T DSP26-2T-12-2SJ DEF STAN 61-12(Part 26)/3 Amendment 2 Note 1: 24 AWG and 26 AWG have a silver plated high strength copper alloy (SPHSCA) conductor

27 . Table 1D: Cable Type 2 and Type 3, Three core, without screen or jacket, (suitable for use without additional protection), Cable Type 2and Type 3, Three core, with screen and jacket (suitable for use without additional protection) Part No NSN Size Jacket Thickness Outside Maximum Mass Kg/Km min nom nom max. DSP26-3S DSP26-3S-26-3SJ DSP26-3S DSP26-3S-24-3SJ DSP26-2T DSP26-2T-22-3SJ DSP26-2T DSP26-2T-20-3SJ DSP26-2T DSP26-2T-18-3SJ DSP26-2T DSP26-2T-16-3SJ DSP26-2T DSP26-2T-14-3SJ DSP26-2T DSP26-2T-12-3SJ Note 1: 24 AWG and 26 AWG have a silver plated high strength copper alloy (SPHSCA) conductor DEF STAN 61-12(Part 26)/3 Amendment 2

28 Table 1E: Cable Type 2 and Type 3, Four core, with screen and jacket (suitable for use without additional protection) Part No NSN Size Jacket Thickness Outside min nom nom max Maximum Mass Kg/Km DSP26-3S-24-4SJ DSP26-2T-22-4SJ DSP26-2T-20-4SJ DSP26-2T-18-4SJ DSP26-2T-16-4SJ DSP26-2T-14-4SJ DSP26-2T-12-4SJ DEF STAN 61-12(Part 26)/3 Amendment 2 Note 1: 24 AWG has a silver plated high strength copper alloy (SPHSCA) conductor

29 Table 1F: Wire Type 8, Single core, without screen or jacket and Cable Type 8, Single core, with screen and jacket Part No NSN DSP26-8T DSP26-8T-28-1SJ DSP26-8T DSP26-8T-26-1SJ DSP26-8T DSP26-8T-24-1SJ DSP26-8T DSP26-8T-22-1SJ DSP26-8T DSP26-8T-20-1SJ DSP26-8T DSP26-8T-18-1SJ DSP26-8T DSP26-8T-16-1SJ DSP26-8T DSP26-8T-14-1SJ DSP26-8T DSP26-8T-12-1SJ Size Stranding Number/ Nominal Conductor Maximum Primary Insulation Thickness Nominal Secondary Insulation Thickness Wire min max 28 7/ / / / max / min / / / / Nominal of Braid Wire Dia Over Braid Wire Jacket Thickness Minimum METSH Cable min max Resistance OHMS/ Km at 20 C max wire Nominal Mass Kg/Km metsh Note 1: The upper NATO Stock Number against each size denotes the wire and is only applicable to a wire which has white insulation Note 2: The lower NATO Stock Number against each size denotes the cable and is only applicable to a cable which has white insulation and a white jacket DEF STAN 61-12(Part 26)/3 Amendment 2

30 . Table 1G: Wire Type 9, Single core, without screen or jacket and Cable Type 9, Single core, with screen and jacket Part No NSN DSP26-9S DSP26-9S 30-1SJ DSP26-9S DSP26-9S-28-1SJ DSP26-9S DSP26-9S-26-1SJ DSP26-9S DSP26-9S-24-1SJ Size Stranding Number/ Nominal Conductor Maximum Primary Insulation Thickness Nominal Secondary Insulation Thickness Wire min max 30 7/ / max min 26 19/ / Nominal of Braid Wire Dia Over Braid Wire Jacket Thickness Minimum Cable min max Note 1: The upper NATO Stock Number against each size denotes the wire and is only applicable to a wire which has white insulation Resistance OHMS/ Km at 20 C max Nominal Mass Kg/Km wire metsh DEF STAN 61-12(Part 26)/3 Amendment 2 Note 2: The lower NATO Stock Number against each size denotes the cable and is only applicable to a cable which has white insulation and a white jacket

31 Inside Rear Cover

32 Crown Copyright 2011 Copying Only as Agreed with DStan Defence Standards are Published by and Obtainable from: Defence Equipment & Support UK Defence Standardization Kentigern House 65 Brown Street GLASGOW G2 8EX DStan Helpdesk Tel /2 Fax Internet File Reference The DStan file reference relating to work on this standard is D/DSTAN/61/12/26. Contract Requirements When Defence Standards are incorporated into contracts users are responsible for their correct application and for complying with contractual and statutory requirements. Compliance with a Defence Standard does not in itself confer iunity from legal obligations. Revision of Defence Standards Defence Standards are revised as necessary by an up issue or amendment. It is important that users of Defence Standards should ascertain that they are in possession of the latest issue or amendment. Information on all Defence Standards can be found on the DStan Website updated weekly and supplemented regularly by Standards in Defence News (SID News). Any person who, when making use of a Defence Standard encounters an inaccuracy or ambiguity is requested to notify UK Defence Standardization (DStan) without delay in order that the matter may be investigated and appropriate action taken.

Ministry of Defence Defence Standard 61-19

Ministry of Defence Defence Standard 61-19 Ministry of Defence Defence Standard 61-19 Issue 2 Publication Date 22 August 2003 Guidance to the Transportation, Storage, Handling and Disposal of Lithium Batteries. DEF STAN 61-19/ ISSUE 2 AMENDMENT

More information

Rail Wire Guide. Harnessing and Electro-Mechanical Solutions for Demanding, Harsh Environment Applications... LFH FREE

Rail Wire Guide. Harnessing and Electro-Mechanical Solutions for Demanding, Harsh Environment Applications... LFH FREE Harnessing and Electro-Mechanical Solutions for Demanding, Harsh Environment Applications... Railway Market: 100E Wire ZHPCG Cable SHF260 Flexible Cable Rail Wire Guide LFH Low Fire Hazard HALOGEN FREE

More information

Thermofit MIL-LT Tubing Low Shrink-Temperature Polyolefin, Flexible, Heat-Shrinkable

Thermofit MIL-LT Tubing Low Shrink-Temperature Polyolefin, Flexible, Heat-Shrinkable Tyco Electronics Corporation 300 Constitutional Drive Menlo Park, CA 94025 USA Specification This Issue: Date: Replaces: RT-1171 Issue 7 December 5, 2001 Issue 6 Thermofit MIL-LT Tubing Low Shrink-Temperature

More information

P.V.C. INSULATED UNARMOURED COPPER CABLES

P.V.C. INSULATED UNARMOURED COPPER CABLES 083 : 2007 CEB SPECIFICATION P.V.C. INSULATED UNARMOURED COPPER CABLES CEYLON ELECTRICITY BOARD SRI LANKA Specification for P.V.C. INSULATED UNARMOURED COPPER CABLES CEB Specification 083 : 2007 CEYLON

More information

Defence Standard Specification for the Type 'U' Mounts

Defence Standard Specification for the Type 'U' Mounts Defence Standard 07-287 Issue 2 Date: 28 April 2017 Specification for the Type 'U' Mounts Section 1 Foreword Defence Standard Structure Section 1 (Generated by the StanMIS toolset) Revision Note Historical

More information

ISO 6722 INTERNATIONAL STANDARD. Road vehicles 60 V and 600 V single-core cables Dimensions, test methods and requirements

ISO 6722 INTERNATIONAL STANDARD. Road vehicles 60 V and 600 V single-core cables Dimensions, test methods and requirements INTERNATIONAL STANDARD ISO 6722 Second edition 2006-08-01 Road vehicles 60 V and 600 V single-core cables Dimensions, test methods and requirements Véhicules routiers Câbles monoconducteurs de 60 V et

More information

RAYCHEM NT-MIL TUBING Modified Chlorinated Polyolefin, Elastomeric, Flexible, Flame Retarded, Heat Shrinkable

RAYCHEM NT-MIL TUBING Modified Chlorinated Polyolefin, Elastomeric, Flexible, Flame Retarded, Heat Shrinkable Tyco Electronics Corporation 305 Constitutional Drive Menlo Park, CA 94025 USA Specification This Issue: Date: Replaces: RW-3030 Issue 3 16-Jun-15 Issue 2 RAYCHEM NT-MIL TUBING Modified Chlorinated Polyolefin,

More information

00-40 (PART 6) / Issue 1 (ARMP-6) RELIABILITY AND MAINTAINABILITY PART 6: IN-SERVICE R & M

00-40 (PART 6) / Issue 1 (ARMP-6) RELIABILITY AND MAINTAINABILITY PART 6: IN-SERVICE R & M Ministry of Defence Defence Standard 00-40 (PART 6) / Issue 1 () RELIABILITY AND MAINTAINABILITY 9 December 1988 PART 6: IN-SERVICE R & M DEF STAN 00-40 (PART 6)/1 ( ) AMENDMENTS ISSUED SINCE PUBLICATION

More information

DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +105 C, 1000 VOLTS, TYPE LSFSGU

DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +105 C, 1000 VOLTS, TYPE LSFSGU INCH-POUND MIL-DTL-24643/17F 1 October 2009 SUPERSEDING MIL-DTL-24643/17E 22 August 2002 DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +105 C, 1000 VOLTS, TYPE LSFSGU This specification is approved

More information

SPECIFICATION RW-2514 Document Number NBC MARKER SYSTEM (Ladder Form) NBC-SCE

SPECIFICATION RW-2514 Document Number NBC MARKER SYSTEM (Ladder Form) NBC-SCE SPECIFICATION: RW 2514 THIS ISSUE: ISSUE 2 DATE: February 2014 SPECIFICATION RW-2514 Document Number 108-121017 NBC MARKER SYSTEM (Ladder Form) NBC-SCE 1. SCOPE NBC-SCE Markers are designed for use where

More information

WSD 1800 Issue C Rated Ford Automotive Sensor Cable Specification

WSD 1800 Issue C Rated Ford Automotive Sensor Cable Specification WSD 1800 Issue 4 150 C Rated Ford Automotive Sensor Cable Specification October 2012 WSD 1800 Issue 4, October 2012 Page 1 of 9 Table of Contents 1 Scope... 2 2 Related Documents... 2 3 Quality Assurance

More information

MATERIAL STANDARD FOR CABLES AND WIRES

MATERIAL STANDARD FOR CABLES AND WIRES MATERIAL STANDARD FOR CABLES AND WIRES CONTENTS : PAGE No. 1. SCOPE... 2 2. SERVICE CONDITIONS... 2 3. REFERENCES AND STANDARDS... 2 4. UNITS... 3 5. CABLE DESIGN AND CONSTRUCTION... 3 5.1 Applicable Cable

More information

Technical Specification for PVC Insulated Low Voltage Neutral Screened Copper Cable

Technical Specification for PVC Insulated Low Voltage Neutral Screened Copper Cable Ergon Energy Corporation Limited Technical Specification for PVC Insulated Low Voltage Neutral Screened Copper Cable ETS03-01-05 Specification ETS03-01-05 Ver 4 Contents 1. Purpose and Scope... 1 2. References...

More information

Test Report No.: Page 2 of 35

Test Report No.: Page 2 of 35 Test Report No.: 50093959 001 age 2 of 35 Test Report AS/NZS 5000.1:2005 including amendment 1 Electric cables olymeric insulated for working voltages up to 0.6/1kV Test item particulars: 1C 4mm 2 to 16

More information

6A V CVQ cable (C rank)

6A V CVQ cable (C rank) 6A-31 600V CVQ cable (C rank) Enactment in July 1977 Approved on June 27, 2008 (revised 02) Enforcement on July 28, 2008 Distribution Department Tokyo Electric Power Company, Incorporated. 1. Scope of

More information

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 REVISION NO. 0 NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 PAGE NO. 1 OF 24 DATE OF ISSUE (MONTH/YEAR) TOTAL NO. OF PAGES (Including cover

More information

Raychem RT-555 TUBING Modified Fluoropolymer, Radiation Crosslinked, Flexible, Abrasion Resistant, Flame Retardant, Heat Shrinkable

Raychem RT-555 TUBING Modified Fluoropolymer, Radiation Crosslinked, Flexible, Abrasion Resistant, Flame Retardant, Heat Shrinkable TE Corporation 300 Constitution Drive Menlo Park, CA 94025 USA Raychem Specification This Issue: Date: Replaces: RT-555 Issue 7 29-Apr-14 Issue 6 Raychem RT-555 TUBING Modified Fluoropolymer, Radiation

More information

Wire and Cable SPEC 44 Wire and Cable

Wire and Cable SPEC 44 Wire and Cable High-performance wire and cable sulation system for 65 C to Wire and Cable SPEC 44 Wire and Cable Applications Hookup and signal wire and cable used aircraft, avionics, military electronics, satellites,

More information

SPECIFICATION OF LT AERIAL BUNCHED (AB) CABLES (Size: 3C x 35mm² +1C x mm²) FOR LT LINES (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY)

SPECIFICATION OF LT AERIAL BUNCHED (AB) CABLES (Size: 3C x 35mm² +1C x mm²) FOR LT LINES (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY) SPECIFICATION OF LT AERIAL BUNCHED (AB) CABLES (Size: 3C x 35mm² +1C x16 + 25mm²) FOR LT LINES (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY) 1. SCOPE: This specification covers XLPE insulated

More information

SafeX110 Single Core Flexible Tinned Copper Cable

SafeX110 Single Core Flexible Tinned Copper Cable LSZH 110 C Flexible SafeX110 Single Core Flexible Tinned Copper Cable Application: Wiring of switchboards, control, general wiring, instrumentation and communication systems. Used where low smoke, zero

More information

--> Buy True-PDF --> Auto-delivered in 0~10 minutes. TB/T Translated English of Chinese Standard: TB/T1484.

--> Buy True-PDF --> Auto-delivered in 0~10 minutes. TB/T Translated English of Chinese Standard: TB/T1484. Translated English of Chinese Standard: TB/T1484.2-2010 www.chinesestandard.net Sales@ChineseStandard.net RAILWAY INDUSTRY STANDARD TB OF THE PEOPLE S REPUBLIC OF CHINA ICS 29.280 S 35 Partially replacing

More information

STANDARD SPECIFICATION FOR SIGNAL CABLE. A. This Specification provides for single and multi-conductor insulated and jacketed cable for

STANDARD SPECIFICATION FOR SIGNAL CABLE. A. This Specification provides for single and multi-conductor insulated and jacketed cable for STANDARD SPECIFICATION FOR SIGNAL CABLE 1.01 SCOPE A. This Specification provides for single and multi-conductor insulated and jacketed cable for installation in direct contact with the earth, in ducts,

More information

SPEIFICATION RW-2530 Document No TMS 90 SCE Marker

SPEIFICATION RW-2530 Document No TMS 90 SCE Marker SPECIFICATION: RW 2530 THIS ISSUE: ISSUE 2 DATE: February 2014 SPEIFICATION RW-2530 Document No. 108-121029 TMS 90 SCE Marker TMS 90 SCE Markers are for use in permanent marking applications up to 135

More information

RPPM SCOPE. Quality Assurance Technical Product Management. Tyco Electronics UK: Iain Brown Colin Diss Nick Crofts

RPPM SCOPE. Quality Assurance Technical Product Management. Tyco Electronics UK: Iain Brown Colin Diss Nick Crofts RK 6214 Revision 3 Page 1 of 6 Date Printed 30-Apr-10 R RK 6214 Revision 3 RPPM SCOPE This Quality Assurance Specification establishes the quality standard for a dual wall sleeving which shall consist

More information

2. RATED VOLTAGE: The rated voltage of the AB cables shall be 1100 volts

2. RATED VOLTAGE: The rated voltage of the AB cables shall be 1100 volts TECHNICAL SPECIFICATION OF LT AERIAL BUNCHED CABLES FOR LT LINES (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY) (Size 1C x35mm²+1c x16 + 25mm² and 2C x50mm² +1Cx25 + 35mm²) 1. SCOPE: This specification

More information

Highly flexible, screened control cable with PVC core insulation and abrasion and oil resistant PUR sheath

Highly flexible, screened control cable with PVC core insulation and abrasion and oil resistant PUR sheath Highly flexible, screened control cable with PVC core insulation and abrasion and oil resistant PUR sheath - Highly flexible, screened control cable with PVC core insulation and abrasion and oil resistant

More information

Raychem Fluoroelastomer Tubing Flexible, Fluid Resistant, Heat-Shrinkable

Raychem Fluoroelastomer Tubing Flexible, Fluid Resistant, Heat-Shrinkable Tyco Electronics Corporation 300 Constitution Drive Menlo Park, CA 94025 USA Specification This Issue: Date: Replaces: RW-3037 Issue 2 July 26, 2006 Issue 1 Raychem Fluoroelastomer Tubing Flexible, Fluid

More information

RAYCHEM TAT-125 ADHESIVE LINED TUBING Polyolefin, Flexible, Heat-Shrinkable, Dual Wall

RAYCHEM TAT-125 ADHESIVE LINED TUBING Polyolefin, Flexible, Heat-Shrinkable, Dual Wall Tyco Electronics Corporation 300 Constitution Drive Menlo Park, CA 94025 USA Specification This Issue: Date: Replaces: RW-3032 Issue 1 June 9, 2004 RAYCHEM TAT-125 ADHESIVE LINED TUBING Polyolefin, Flexible,

More information

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT CEB SPECIFICATION 005-1: 2012 P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS PAGE 1. Scope 03

More information

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN Engineering Specification Electrical Networks MESP 030000-04 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN Version: 1 Issued:

More information

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

NPS/002/020 Technical Specification for 11 & 20kV Power Cables Version:- 3.1 of Issue:- Nov - 09 Page 1 of 11 NPS/002/020 Technical Specification for 11 & 20kV Power Cables 1. Purpose The purpose of this document is to detail Northern Powergrid (the Company) requirements

More information

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 23, 2018

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 23, 2018 STANDARDS UPDATE NOTICE (SUN) ISSUED: February 23, 2018 STANDARD INFORMATION Standard Number: UL 83 / CSA C22.2 No 75 / NMX-J-010-ANCE Standard Name: Thermoplastic-Insulated Wires and Cables Standard Edition

More information

Test Report No.: Page 2 of 34

Test Report No.: Page 2 of 34 Test Report No.: 50093985 001 age 2 of 34 Test Report AS/NZS 5000.2:2006 Electric cables olymeric insulated for working voltages up to and including 450/750V Test item particulars: 1C 4mm 2 to 16 mm 2

More information

DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +90 C, TYPE LS3SWU (INCLUDING VARIATION LS3SWUS)

DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +90 C, TYPE LS3SWU (INCLUDING VARIATION LS3SWUS) INCH-POUND 11 July 2011 USED IN LIEU OF MIL-DTL-24643/36F 01 October 2009 DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +90 C, TYPE LS3SWU (INCLUDING VARIATION LS3SWUS) This specification is approved

More information

MILITARY SPECIFICATION WIRE, ELECTRICAL, FLUOROPOLYMER - INSULATED COPPER OR COPPER ALLOY

MILITARY SPECIFICATION WIRE, ELECTRICAL, FLUOROPOLYMER - INSULATED COPPER OR COPPER ALLOY INCH-POUND 16 October 1998 SUPERSEDING AMENDMENT 1 07 May 1991 MILITARY SPECIFICATION WIRE, ELECTRICAL, FLUOROPOLYMER - INSULATED COPPER OR COPPER ALLOY This amendment forms a part of, dated 07 May 1991,

More information

Ministry of Defence Defence Standard Issue 4 Publication Date 31 October The Selection and Introduction of Batteries for Service Use

Ministry of Defence Defence Standard Issue 4 Publication Date 31 October The Selection and Introduction of Batteries for Service Use Ministry of Defence Defence Standard 61-17 Issue 4 Publication Date 31 October 2001 The Selection and Introduction of Batteries for Service Use AMENDMENT RECORD Amd No Date Text Affected Signature and

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION 4 PAIR UTP CABLE CAT6 (CATEGORY 6 PLUS) Page 1 of 5 1. SCOPE This specification is based on the specifications of UL 444, ANSI/TIA/EIA-568-B,ISO/IEC 1801, UL 1685(CM) and covers

More information

THERMOFIT SCL TUBING Polyolefin, Selectively Crosslinked, Semirigid, Heat Shrinkable

THERMOFIT SCL TUBING Polyolefin, Selectively Crosslinked, Semirigid, Heat Shrinkable Tyco Electronics Corporation 300 Constitutional Drive Menlo Park, CA 94025 USA Specification This Issue: Date: Replaces: RT-1301 Issue 7 October 3, 2003 Issue 6 THERMOFIT SCL TUBING Polyolefin, Selectively

More information

Specification This Issue: Date: Replaces: RT-780_Type-I Issue 5 November 10, 2009 Issue 4. Raychem

Specification This Issue: Date: Replaces: RT-780_Type-I Issue 5 November 10, 2009 Issue 4. Raychem Tyco Electronics Corporation 300 Constitution Drive Menlo Park, CA 94025 USA Raychem Specification This Issue: Date: Replaces: RT-780_Type-I Issue 5 November 10, 2009 Issue 4 Raychem RT-780 Type I Tubing

More information

1. All Members of Power Cables Sectional Committee, ET 09; 2. All Members of Electrotechnical Division Council; and 3. All other Interested.

1. All Members of Power Cables Sectional Committee, ET 09; 2. All Members of Electrotechnical Division Council; and 3. All other Interested. DRAFT IN WIDE CIRCULATION DOCUMENT DESPATCH ADVICE Reference Date ET 09/T-45 03-05-2011 TECHNICAL COMMITTEE ETD 09 --------------------------------------------------------------------------------------------------------------

More information

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE SEAL & SIGNATURE OF THE TENDERER PAGE 1 OF 14 TECHNICAL SPECIFICATION FOR LT XLPE POWER CABLES (SPECIFICATION NO.MM/I/LTXLPE/2006) 1. SCOPE: The specification

More information

SPECIFICATION RW-2525 Document Number TMS - CCUV SLEEVING

SPECIFICATION RW-2525 Document Number TMS - CCUV SLEEVING SPECIFICATION: RW 2525 THIS ISSUE: ISSUE 2 DATE: February 2014 SPECIFICATION RW-2525 Document Number 108-121025 TMS - CCUV SLEEVING 1. SCOPE This Quality Assurance Specification establishes the quality

More information

SURFACE VEHICLE STANDARD

SURFACE VEHICLE STANDARD 400 Commonwealth Drive, Warrendale, PA 15096-0001 SURFACE VEHICLE STANDARD J1654 Issued 1994-06 Revised 2000-05 REV. MAY2000 Submitted for recognition as an American National Standard Superseding J1654

More information

3 MODIFICATIONS TO EXISTING STANDARDS

3 MODIFICATIONS TO EXISTING STANDARDS 1 SCOPE This specification covers the requirements for 25 kv rated single-phase primary cable with shielded concentric neutral and an insulating jacket. The cable may be used in single or multi-phase application

More information

DRAFT TANZANIA STANDARD. Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV)

DRAFT TANZANIA STANDARD. Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV) EDC3 (5239) P3 Mini-Grid Systems DRAFT TANZANIA STANDARD Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV) TANZANIA BUREAU OF STANDARDS TBS 2017 First Edition 2017 Table of Contents

More information

Available in 0.75 to 16.0 sq mm. Red, Yellow, Blue, Black, White, Gray and Green (for earthing) Specification IS 694:1990

Available in 0.75 to 16.0 sq mm. Red, Yellow, Blue, Black, White, Gray and Green (for earthing) Specification IS 694:1990 Application These cables are used for wiring domestic and coercial buildings. The multi strand flexible conductors make it ideal for concealed wiring. These cables are ideal for wiring in residential and

More information

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables Version: 4.1 Date of Issue: February 2016 Page: 1 of 25 NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables 1. Purpose The purpose of this document is to detail the requirements

More information

NPS/002/023 Technical Specification for 132kV Power Cables.

NPS/002/023 Technical Specification for 132kV Power Cables. Version:- 2.2 of Issue:- June 09 Page 1 of 11 NPS/002/023 Technical Specification for 132kV Power Cables. 1. Purpose The purpose of this document is to detail the technical requirements of Northern Powergrid

More information

THERMOFIT RNF-150 TUBING Flexible, Heat-Shrinkable, Flame-Retarded Modified Fluoropolymer

THERMOFIT RNF-150 TUBING Flexible, Heat-Shrinkable, Flame-Retarded Modified Fluoropolymer TE Corporation 300 Constitution Drive Menlo Park, CA 94025 USA Raychem Specification This Issue: Date: Replaces: RT-370 Issue 6 24-Sep-12 Issue 5 1. SCOPE THERMOFIT RNF-150 TUBING Flexible, Heat-Shrinkable,

More information

5.2 The phase conductors shall be provided with one, two & three ridges for easy identification.

5.2 The phase conductors shall be provided with one, two & three ridges for easy identification. LT Aerial Bunched Cables for LT Lines (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY) 1. SCOPE: This specification covers XLPE insulated Aluminum cable twisted over a central bare Aluminum Alloy

More information

RELIABILITY AND MAINTAINABILITY PART 5: GUIDANCE ON R & M TRAINING

RELIABILITY AND MAINTAINABILITY PART 5: GUIDANCE ON R & M TRAINING Ministry of Defence Defence Standard 00-40 (PART 5) / Issue 1 (ARMP-5) RELIABILITY AND MAINTAINABILITY 27 February 1989 PART 5: GUIDANCE ON R & M TRAINING AMENDMENTS ISSUED SINCE PUBLICATION AMD NO DATE

More information

Technical Specification for Insulated Low Voltage Single Core Copper Cable

Technical Specification for Insulated Low Voltage Single Core Copper Cable Ergon Energy Corporation Limited Technical Specification for Insulated Low Voltage Single Core Copper Cable ETS03-01-03 Specification ETS03-01-03 Ver 3 Contents 1. Purpose and Scope... 1 2. References...

More information

Protection of A/C connection using a heat shrinkable jacket

Protection of A/C connection using a heat shrinkable jacket Protection of A/C connection using a heat shrinkable jacket 1. Position the heat-shrinkable jacket after the cutting, deburring, inserting of standardized brass nut and flaring operations. 2. Connect the

More information

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables Version: 4.0 Date of Issue: October 2015 Page: 1 of 21 NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables 1. Purpose The purpose of this document is to detail the requirements

More information

ES2000 TUBING Environmental Sealing, Polyolefin, Semirigid, Adhesive-Lined

ES2000 TUBING Environmental Sealing, Polyolefin, Semirigid, Adhesive-Lined Tyco Electronics Corporation 305 Constitution Drive Menlo Park, CA 94025 USA Raychem Tubing SPECIFICATION: THIS ISSUE: DATE: REPLACES: RT-1112 Issue 5 April 22, 2008 Issue 4 ES2000 TUBING Environmental

More information

11-SDMS-01 REV. 03 ( )

11-SDMS-01 REV. 03 ( ) 11-SDMS-01 REV. 03 (19-07-2018) SPECIFICATION FOR LOW-VOLTAGE POWER AND CONTROL CABLES Saudi Electricity Company 1. SCOPE... 3 2. CROSS REFERENCES TO OTHER SEC STANDARDS... 3 3. APPLICABLE CODES AND STANDARDS...

More information

H-FLEX CABLES 10/2017

H-FLEX CABLES 10/2017 10/2017 H-FLEX CABLES CONTENTS H-FLEX PWR PUR 0,6/1kV...2 H-FLEX PWR C-PUR 0,6/1kV...6 H-FLEX CTL PUR 250V...10 H-FLEX CTL C-PUR 250V...12 H-FLEX INS PUR 250V...14 H-FLEX INS C-PUR 250V...16 TECHNICAL

More information

IEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor

IEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor TABLE OF CONTENTS SECTION SUBJECT PAGE I. SCOPE...1 II. APPLICABLE DOCUMENTS...1 III. CONDUCTOR...2 IV. SEPARATOR...2 V. INSULATION...2 A. Physical Properties...2 B. Electrical Properties...3 C. Qualification

More information

DETAIL SPECIFICATION SHEET CABLE, RADIO FREQUENCY, FLEXIBLE, COAXIAL, 50 OHMS, M17/

DETAIL SPECIFICATION SHEET CABLE, RADIO FREQUENCY, FLEXIBLE, COAXIAL, 50 OHMS, M17/ INCH-POUND MIL-DTL-17/196C w/mendment 2 18 May 2018 SUPERSEDING MIL-DTL-17/196C w/ MENDMENT 1 01 October 2015 DETIL SPECIFICTION SHEET CLE, RDIO FREQUENCY, FLEXILE, COXIL, 50 OHMS, M17/196-00001 This specification

More information

Tyco Fluoroelastomer Tubing Flexible, Fluid Resistant, Heat-Shrinkable

Tyco Fluoroelastomer Tubing Flexible, Fluid Resistant, Heat-Shrinkable RT-1146 Page 1 of 7 Rev 7 RT-1146 Tyco Fluoroelastomer Tubing Flexible, Fluid Resistant, Heat-Shrinkable SCOPE: This specification covers the requirements for one type of highly flexible, electrical-insulating

More information

PERFORMANCE SPECIFICATION SHEET

PERFORMANCE SPECIFICATION SHEET METRIC MIL-PRF-85045/25B 17 June 2014 SUPERSEDING MIL-PRF-85045/25A 19 January 2010 PERFORMANCE SPECIFICATION SHEET CABLE, FIBER OPTIC, SEVEN TUBE, BLOWN OPTICAL FIBER, STANDARD AND ENHANCED PERFORMANCE,

More information

6A-38 Jumper Wire (IJP) (Rank A)

6A-38 Jumper Wire (IJP) (Rank A) DISCLAIMER: This translation may be used for reference purpose only. This English version is not an official translation of the original Japanese document. In cases where any differences occur between

More information

VERSAFIT V2 AND V4 TUBING Polyolefin, Flexible, Heat-Shrinkable, Flame-Retardant

VERSAFIT V2 AND V4 TUBING Polyolefin, Flexible, Heat-Shrinkable, Flame-Retardant TE Connectivity 300 Constitution Drive Menlo Park, CA 94025 USA Raychem Tubing Specification This Issue: Date: Replaces: RW-3023 Issue 9 Nov 21, 2016 Issue 8 VERSAFIT V2 AND V4 TUBING Polyolefin, Flexible,

More information

THERMOFIT RT-218 TUBING Modified Polyvinylidene Fluoride, Low Outgassing, Heat-Shrinkable

THERMOFIT RT-218 TUBING Modified Polyvinylidene Fluoride, Low Outgassing, Heat-Shrinkable Tyco Electronics Corporation 300 Constitutional Drive Menlo Park, CA 94025 USA Specification This Issue: Date: Replaces: RT-218 Issue 4 July 3, 1997 Issue 3 THERMOFIT RT-218 TUBING Modified Polyvinylidene

More information

*** Supercedes: BECO E and COM , , & ***

*** Supercedes: BECO E and COM , , & *** 7/27/09 Page 1 of 9 R5 *** Supercedes: BECO E2.9-27.4 and COM 1-0696, 2-0196, & 5-0385 *** 1.0 Scope #2 AWG to 1000 KCMIL CONCENTRIC NEUTRAL JACKETED CABLES RATED 5-35 kv These Specifications cover single

More information

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES 11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE

More information

Single Core, Aluminum Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

Single Core, Aluminum Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable Edition Nº: 7 NPS - 96 Issued date: June, 2017 LV, single core, Aluminum, XLPE Power Cable THE ISRAEL ELECTRIC CORPORATION LTD. Specification No. NPS - 96 for Single Core, Aluminum Conductor Extruded Cross

More information

Mineral Insulated Platinum Resistance Thermometer PT100 Sensor - Available in 3mm or 6mm diameter x 150mm or 250mm probe lengths

Mineral Insulated Platinum Resistance Thermometer PT100 Sensor - Available in 3mm or 6mm diameter x 150mm or 250mm probe lengths Datasheet ENGLISH Mineral Insulated Platinum Resistance Thermometer PT100 Sensor - Available in 3mm or 6mm diameter x 150mm or 250mm probe lengths High temperature, rugged, flexible Pt100 probe Suitable

More information

Title Cables for Railway Signalling Applications - Traction Return Bonding and Track Connection Cables

Title Cables for Railway Signalling Applications - Traction Return Bonding and Track Connection Cables Discipline Engineering Standard NSW Category Signalling Title Cables for Railway Signalling Applications - Traction Return Bonding and Track Connection Cables Reference Number SPS 49 - (RIC Standard: SC

More information

SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW ARROW ROUTE, FONTANA CA

SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW ARROW ROUTE, FONTANA CA SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW THHN/THWN-2/THW/THWN/TW Listed E-492385 / E-472248 APPLICATIONS THHN/THWN-2 building wire is primarily used for general purpose applications in conduit and cable

More information

DCPT SLEEVING SCOPE. This document is electronically reviewed and approved and so no signatures will appear.

DCPT SLEEVING SCOPE. This document is electronically reviewed and approved and so no signatures will appear. RW 2056 Revision 4 Page 1 of 10 Date Printed 3/3/2014 RW 2056 Revision 4 DCPT SLEEVING SCOPE This Quality Assurance Specification establishes the quality standard for a heat-shrinkable, electrically-insulating,

More information

Type 1 Machine Cable. Oxygen free tinned annealed copper wire interwoven with high tensile poly-yarn

Type 1 Machine Cable. Oxygen free tinned annealed copper wire interwoven with high tensile poly-yarn Mining Cable Type 1 Machine Cable Application: Typically used for interconnection of control boxes or motors on non-mobile or fixed apparatus. Used when exposure to heat is not an issue and where added

More information

RBK-ILS-125 SCOPE. This Quality Assurance Specification establishes the quality standard for RBK-ILS-125.

RBK-ILS-125 SCOPE. This Quality Assurance Specification establishes the quality standard for RBK-ILS-125. RK 6638 Revision 9 Page 1 of 22 Date Printed 30-Apr-10 RK 6638 Revision 9 RBK-ILS-125 SCOPE This Quality Assurance Specification establishes the quality standard for RBK-ILS-125. The objective of this

More information

Four Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

Four Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable Edition Nº: 9 THE ISRAEL ELECTRIC CORPORATION LTD. Specification No. NPS-76 for Four Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable for Rated Voltage U0/U = 0.6/1.0

More information

L1-CHE-SPE-171 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE

L1-CHE-SPE-171 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE Engineering Specification Electrical Networks L1-CHE-SPE-171 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM OR COPPER CONDUCTOR 3.8/6.6kV XLPE INSULATED WITHOUT METALLIC SCREEN PVC Version:

More information

THERMOFIT RNF-100 TUBING Polyolefin, Flexible, Heat-Shrinkable

THERMOFIT RNF-100 TUBING Polyolefin, Flexible, Heat-Shrinkable Tyco Electronics Corporation 300 Constitutional Drive Menlo Park, CA 94025 USA Specification This Issue: Date: Replaces: RT-350 Issue 17 April 9, 2004 Issue 16 THERMOFIT RNF-100 TUBING Polyolefin, Flexible,

More information

Article-No. Type. All dimensions in mm. Subject to technical changes. Other dimensions, reel lengths or colours available on request.

Article-No. Type. All dimensions in mm. Subject to technical changes. Other dimensions, reel lengths or colours available on request. 4.4 Installation Devices HelaTape HellermannTyton offers a wide range of PVC and rubber tapes for sealing, insulation and bundling of cable and conduits. PVC based tapes are designed for low voltage applications

More information

PRODUCT SPECIFICATION

PRODUCT SPECIFICATION Sep., 2005 PAGE / 8 Jan. 20, 2007 PRODUCT NAME : STW-F RATING : 55 C, 000V rms No. Revised Date Revised Details Page Report Jan. 20, 2007 Emendation of Specification All - REPORTED BY: APPROVED BY: Q.M.

More information

Purchase Now ANSI/ICEA S STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES

Purchase Now ANSI/ICEA S STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES ANSI/ICEA S-05-692 STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES Approved as an American National Standard ANSI Approval Date: 9/29/ ANSI/ICEA Publication

More information

STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV. Approved by AMERICAN NATIONAL STANDARDS INSTITUTE.

STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV. Approved by AMERICAN NATIONAL STANDARDS INSTITUTE. ANSI/ICEA S-108-720-2012 STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV Approved by AMERICAN NATIONAL STANDARDS INSTITUTE November 27, 2012 Publication # ANSI/ICEA S-108-720-2012

More information

PERFORMANCE SPECIFICATION SHEET

PERFORMANCE SPECIFICATION SHEET METRIC MIL-PRF-85045/17C 17 June 2014 SUPERSEDING MIL-PRF-85045/17B 16 September 1999 PERFORMANCE SPECIFICATION SHEET CABLE, FIBER OPTIC, EIGHT FIBERS, ENHANCED PERFORMANCE, CABLE CONFIGURATION TYPE 2

More information

SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION

SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION 1.0 SCOPE 1.1 This specification covers the construction, mechanical, and electrical requirements of single conductor,

More information

Platinum Resistance Pt100 Autoclave Drain Probe, 4 Wire Compatible with most common makes of Autoclaves

Platinum Resistance Pt100 Autoclave Drain Probe, 4 Wire Compatible with most common makes of Autoclaves ENGLISH Datasheet Platinum Resistance Pt100 Autoclave Drain Probe, 4 Wire Compatible with most common makes of Autoclaves Pt100 Autoclave & steriliser drain temperature probe For use to monitor the fluid

More information

Ministry of Defence Defence Standard Requirements for Nickel Aluminium Bronze Castings and Ingots. Part 1

Ministry of Defence Defence Standard Requirements for Nickel Aluminium Bronze Castings and Ingots. Part 1 Ministry of Defence Defence Standard 02747 Issue 3 Publication Date 21 August 2012 Requirements for Nickel Aluminium Bronze Castings and Ingots Part 1 Nickel Aluminium Bronze Naval Alloy Centrifugally

More information

MATERIAL STANDARD FOR ELECTRICAL HEAT TRACING ORIGINAL EDITION JAN. 1996

MATERIAL STANDARD FOR ELECTRICAL HEAT TRACING ORIGINAL EDITION JAN. 1996 MATERIAL STANDARD FOR ELECTRICAL HEAT TRACING ORIGINAL EDITION JAN. 1996 This Standard is the property of Iranian Ministry of Petroleum. All rights are reserved to the owner. Neither whole nor any part

More information

REQUIREMENTS FOR SAFETY RELATED SOFTWARE IN DEFENCE EQUIPMENT PART 1: REQUIREMENTS

REQUIREMENTS FOR SAFETY RELATED SOFTWARE IN DEFENCE EQUIPMENT PART 1: REQUIREMENTS Ministry of Defence Defence Standard 00-55(PART 1)/Issue 2 1 August 1997 REQUIREMENTS FOR SAFETY RELATED SOFTWARE IN DEFENCE EQUIPMENT PART 1: REQUIREMENTS This Part 1 of Def Stan 00-55 supersedes INTERIM

More information

THERMOFIT CRN TUBING Polyolefin, Semirigid, Heat-Shrinkable

THERMOFIT CRN TUBING Polyolefin, Semirigid, Heat-Shrinkable TE Connectivity 300 Constitution Drive Menlo Park, CA 94025 USA Raychem Tubing Specification This Issue: Date: Replaces: RT-360 Issue 10 30-Jan-15 Issue 9 THERMOFIT CRN TUBING Polyolefin, Semirigid, Heat-Shrinkable

More information

Specification FOR. 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated Copper Wire Screened PVC Sheathed Power Cable.

Specification FOR. 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated Copper Wire Screened PVC Sheathed Power Cable. Spec. No. GO 5821-4361Rev.2 Issued date : July 13, 2005 Revised 1 date : April 29, 2015 Revised 2 date : February 19, 2016 Specification FOR 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated

More information

SPECIFICATION FOR FRLS POWER CABLES

SPECIFICATION FOR FRLS POWER CABLES SPECIFICATION FOR FRLS POWER CABLES 1.0 SCOPE This specification cover the technical requirements of design, manufacture, testing and delivery to site of Power Cables of 1100V grade with FRLS PVC Sheathed,

More information

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/LTPVC & CONTROL/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION

More information

Ceramic Ceramic No. of Lead/Wire Lead Allied RS order Dia Ø Length Wires Type Length Code code

Ceramic Ceramic No. of Lead/Wire Lead Allied RS order Dia Ø Length Wires Type Length Code code Datasheet Platinum Resistance Pt100 Tubular Ceramic Insert Elements with tail wires 2 or 4 wire with choice of Teflon or nickel/glassfibre insulated tail wires up to 450mm long ENGLISH 237-1635 237-1641

More information

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED Version: 1 Issued: March 2014 Owner: Electrical Networks Asset

More information

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 22 kv, SINGLE CORE, 95mm 2 COPPER

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 22 kv, SINGLE CORE, 95mm 2 COPPER Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR ELECTRIC CABLE Version: 1 Issued: March 2014 Owner: Electrical Networks Asset Manager Approved By: George Marulli Electrical Networks

More information

ENGLISH Datasheet Platinum Resistance Pt1000 Class B Sensor with Teflon insulated lead

ENGLISH Datasheet Platinum Resistance Pt1000 Class B Sensor with Teflon insulated lead ENGLISH Datasheet Platinum Resistance Pt1000 Class B Sensor with Teflon insulated lead (Image shows 4 wire) Pt1000 element to IEC 751 Class B 2 wire configuration Temperature range -50 C to + 200 C Pt1000

More information

Raychem brand Moulded Components Flame Retarded, Semi-Rigid, Heat Shrinkable, Elastomer (-25)

Raychem brand Moulded Components Flame Retarded, Semi-Rigid, Heat Shrinkable, Elastomer (-25) RW-2070 Revision 2 Page 1 of 8 Date Printed 18-Jul-12 RW-2070 Revision 2 Raychem brand Moulded Components Flame Retarded, Semi-Rigid, Heat Shrinkable, Elastomer (-25) SCOPE This Quality Assurance Specification

More information

Technical Specification for Low Voltage Aerial Bundled HDPE Insulated Cables

Technical Specification for Low Voltage Aerial Bundled HDPE Insulated Cables Ergon Energy Corporation Limited Technical Specification for Low Voltage Aerial Bundled HDPE Insulated Cables ETS03-01-04 Specification ETS03-01-04 Ver 2 Contents 1. Purpose and Scope... 1 2. References...

More information

THERMOFIT AP2000 TUBING HEAT-SHRINKABLE CROSSLINKED MODIFIED POLYOLEFIN, ADHESIVE LINER

THERMOFIT AP2000 TUBING HEAT-SHRINKABLE CROSSLINKED MODIFIED POLYOLEFIN, ADHESIVE LINER Product Brand:Raychem 305 Constitution Drive, Menlo Park, CA 94025 SPECIFICATION: RW-1001 THIS ISSUE: ISSUE 3 DATE: April 11, 2003 REPLACES: ISSUE 2 THERMOFIT AP2000 TUBING HEAT-SHRINKABLE CROSSLINKED

More information

CERTIFICATE OF ACCREDITATION

CERTIFICATE OF ACCREDITATION CERTIFICATE OF ACCREDITATION In terms of section 22(2)(b) of the Accreditation for Conformity Assessment, Calibration and Good Laboratory Practice Act, 2006 (Act 19 of 2006), read with sections 23(1),

More information

138-1: 2015 CEB SPECIFICATION. AERIAL BUNDLE CONDUCTORS - 33 kv (95mm 2 and 150mm 2 )

138-1: 2015 CEB SPECIFICATION. AERIAL BUNDLE CONDUCTORS - 33 kv (95mm 2 and 150mm 2 ) 138-1: 2015 CEB SPECIFICATION AERIAL BUNDLE CONDUCTORS - 33 kv (95mm 2 and 150mm 2 ) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 8051 Fax: +94 11 232 5387 CONTENTS Page 1.0 Scope 3 2.0 System

More information

Specifications: Ice point resistance: Fundamental interval (0 C to 100 C): 38.5Ω (nominal)

Specifications: Ice point resistance: Fundamental interval (0 C to 100 C): 38.5Ω (nominal) ENGLISH Datasheet Platinum Resistance Pt100 Wire-Wound Detector Elements Pt100 platinum resistance thermometer elements in a choice of sizes single & dual element Pt100 elements to IEC 60751 Class A or

More information