Technical Specification for PVC Insulated Low Voltage Neutral Screened Copper Cable

Size: px
Start display at page:

Download "Technical Specification for PVC Insulated Low Voltage Neutral Screened Copper Cable"

Transcription

1 Ergon Energy Corporation Limited Technical Specification for PVC Insulated Low Voltage Neutral Screened Copper Cable ETS Specification ETS Ver 4

2 Contents 1. Purpose and Scope References Applicable Standards Drawings Drawings by the Purchaser Drawings by the Tenderer Service Conditions Design and Construction General Core Conductors Insulation Neutral Screen Sheath Insect Protection Jacket Oversheath Marking of Cables Performance and Testing Testing Type Tests Sample and Routine Tests Carbon Black Test Risk Assessment Quality Assurance Purchasers Policy Documentary Evidence Samples Production Samples Packaging and Marking Cable Length... 5 i Specification ETS Ver 4

3 10.2 Drum Sizes Drum Durability Lagging Marking of Drums Quarantine Requirements Service Performance Reliability Service Life Evidence in Support of Reliability Training Environmental Considerations Information To Be Provided Specific Technical Requirements Checklist of Supporting Documentation Attachment 1 Technical Details Attachment 2 Technical Documentation Checklist ii Specification ETS Ver 4

4 1. Purpose and Scope This specification sets out the requirements for PVC insulated low voltage neutral screened copper cable for use on underground distribution systems in Queensland. The items covered by this technical specification are listed below: ITEM No. DESCRIPTION Stock Code 1 CABLE ELECTRICAL UNDER GROUND 0.6/1kV, 2 Conductor, 4mm2 (7/0.85) Cu Neutral screened PVC Insulated, PVC Sheathed Nylon Jacket CABLE ELECTRICAL UNDER GROUND, 0.6/1kV, 2 Conductor, 16mm2 (7/1.70) Cu, Neutral Screened, PVC Insulated/PVC Sheathed/Nylon Jacket References 2.1 Applicable Standards The cable shall be designed, manufactured and tested in accordance with the following Australian Standards and all amendments issued prior to the date of closing of tenders except where varied by this specification: STANDARD AS 1125 AS 1574 AS 1660 AS AS/NZS 4961:2003 AS/NZS :2005 AS/NZS 3808 AS/NZS 9001 ASTM D1603 TITLE Conductors in Insulated Electric Cables and Flexible Cords Copper and Copper Alloys - Wire for Electrical Purposes Methods of Test for Electric Cables, Cords and Conductors Timber Drums for Insulated Electric Cables and Bare Conductors Electric cables Polymeric insulated For distribution and service applications Electric Cables - Polymeric Insulated for Working Voltages up to and Including 0.6/1kV Insulating and sheathing materials for electric cables Quality Management Systems Requirements Standard Test Method for Carbon Black Content in Olefin Plastics Should inconsistencies be identified between standards and/or this specification, the Tenderer shall immediately refer such inconsistencies to the Purchaser for resolution. Page 1 of 10 Specification ETS Ver 4

5 3. Drawings 3.1 Drawings by the Purchaser There are no drawings attached to this specification. 3.2 Drawings by the Tenderer The Tenderer shall supply with the tender, detailed drawings or pamphlets of the items tendered. 4. Service Conditions The conditions under which the cables will be required to operate are: DESCRIPTION Installation Ambient Air Temperatures Ambient Ground Temperatures Altitude Humidity CONDITION Installed, directly buried in fine grain bedding material, or, in PVC conduits at a nominal depth of up to 1000 mm, with cable ends rising up concrete or timber poles and exposed to direct sunlight. Not exceeding 50 o C as determined by a shaded thermometer Not exceeding 35 o C Not exceeding 500 metres above sea level 90% high humidity combined with a high temperature (40 o C) followed by a sudden drop in temperature of up to 10 o C Exposed sections of the cable will be subject to the following additional service conditions: DESCRIPTION Solar Radiation Level Precipitation Atmospheric classifications CONDITION 1100 watts per square metre with high ultraviolet content Tropical summer storms with gust wind speeds above 160km/h and an annual rainfall in excess of 1500mm Areas of coastal salt spray and / or industrial pollution with equivalent salt deposit densities in the range of g/m 2 Page 2 of 10 Specification ETS Ver 4

6 5. Design and Construction 5.1 General The cables shall be designed and manufactured in accordance with AS/NZS 4961: Core Conductors The conductors shall be circular plain annealed stranded copper in accordance with Section 2 - Copper Conductors of AS Insulation The insulation material on shall be PVC - V90 complying with AS/NZS The thickness of the cable insulation shall be in accordance with Table 1 of AS/NZS The cable insulation shall be red in colour. 5.4 Neutral Screen The neutral screen shall be of a cross sectional area equal to the phase conductor and be stranded annealed copper conductors to AS The wires shall be applied helically and evenly over the protected core offering a maximum coverage of the core. 5.5 Sheath Sheath shall be PVC-V90 extruded over, and coaxial with, the neutral screen and shall be capable of removal without screen damage. The sheath shall be compatible with other materials with which it is in contact. The thickness of the sheath shall be in accordance of Clause 13.4 of AS/NZS Sheath colour shall be black. 5.6 Insect Protection Jacket A continuous UV stabilised nylon jacket (nylon 12) not less than 0.4 mm radial thickness producing a smooth glossy surface free from defects or scratches shall be extruded to an even thickness over the entire length of the cable. The jacket must be capable of removal without damage to the sheath. Jacket colour shall be black. 5.7 Oversheath The nylon jacket shall be protected by an oversheath of UV stabilised sheathing grade PVC. The oversheath thickness shall be in accordance with Clause 13.4 of AS/NZS to provide adequate protection to the nylon jacket during cable installation in conduit. The colour of the over sheath shall be black. 5.8 Marking of Cables The cables shall be clearly marked with the following information in accordance with clause 16 of AS/NZS (a) Registered name/trade mark of the manufacturer. (b) Year of manufacture. Page 3 of 10 Specification ETS Ver 4

7 (c) The words, "Electric Cable, U/G Neutral Screened V-90 followed by 0.6/1kV. (d) Cross sectional area of the conductor in sq. mm. (e) Metre markings at 1 metre intervals for the purpose of indicating the length of the cable remaining on partially used drums. It is not essential but the sequence of numbering commences at zero. However, start and finish numbers shall be included in the information to be provided on the drum flange. The lower number of the metre markings sequence shall correspond to the end attached to the drum flange. The height of the letters and numerals shall comply with clause 6.4.4(b) of AS / NZS Performance and Testing 6.1 Testing The cable shall be tested in accordance with Clause 17 of AS / NZS The following Routine test shall be carried out, on each completed drum of cable, in addition to those required by Clause 17 of AS/NZS Insulation resistance tests between one core and the other cores joined with readings in MΩ. The test will be carried out at a voltage level of 1.0kV DC and the results recorded after 1 minute or when the reading settles whichever the sooner. Test configurations shall be from active to neutral / earth i.e. A N+E. Acceptance level for new cable is 100MΩ. 6.2 Type Tests Certificates for Type Tests conducted in accordance with clause 17 of AS / ANZ shall be submitted with the tender. 6.3 Sample and Routine Tests Sample and Routine Test Certificates are not required to be despatched with each delivery of cable but shall be made available to the purchaser when requested, within 1 working day. A certificate of compliance shall be provided with each delivery. 6.4 Carbon Black Test Carbon black content of the outer sheath shall be tested in accordance with ASTM D1603. Test Certificates are not required to be despatched with each delivery of cable but shall be made available to the purchaser when requested, within 1 working day. 7. Risk Assessment There is no requirement for the Tenderer to provide a safety risk assessment for the items covered by this specification. Page 4 of 10 Specification ETS Ver 4

8 8. Quality Assurance 8.1 Purchasers Policy It is the Purchaser s policy to procure goods, equipment and services from sources that demonstrate the ability to support quality products. 8.2 Documentary Evidence Documentary evidence shall be provided concerning the level of Quality System Certification associated with the Tenderer and/or manufacturer. This documentation shall include the Capability Statement associated with the Quality System Certification. It is expected that the Tenderer and manufacturer will have a quality system certified to ISO 9001 in operation. 9. Samples 9.1 Production Samples When requested, Tenderers shall submit a production sample of each item offered as part of the tender package. 10. Packaging and Marking 10.1 Cable Length The cable shall be supplied in 250 metre lengths unless specified otherwise by the Purchaser. The cable shall be in one length on each drum Drum Sizes Cable shall be supplied on timber drums manufactured in accordance with AS Operational difficulties are anticipated with the use of timber drums manufactured in accordance with AS Hence this specification is based on cables supplied on timber drums manufactured in accordance with the requirements of superseded standard AS Drum Durability The cable drums shall be sufficiently robust to ensure that the cable is delivered undamaged, giving due consideration to the method of transportation and the distances involved. All cable drums shall withstand a minimum of 24 months exposure to all types of weather conditions during outdoor storage, without deterioration Lagging The outer layer of cable shall be protected by a sheet form wrapping (with an overlap) located between the inner faces of the flanges. Page 5 of 10 Specification ETS Ver 4

9 10.5 Marking of Drums The marking of information on the cable drum shall be in accordance with Clause 16.3 of AS / NZS In addition, the following information shall be provided indelibly and legibly marked directly on the flanges: a) The name Ergon Energy and the relevant stores stock code. b) Contract number. c) Order release authority or purchasing order number. d) Manufacturer's traceability number derived from Manufacturer s first letter, hyphen, batch number, hyphen, drum number for this batch Quarantine Requirements Should cable be supplied from overseas manufacturers, then it is mandatory that all conditions and inspections required by the Australian Quarantine Act are met and that all these costs are included in the tendered price. In particular, timber drums must be fumigated with methyl bromide with a concentration of 48 grams per cubic metre for 24 hours at 210C. The Tenderer shall ensure that the procedure does not produce any deleterious effects to the cable supplied on the drum. 11. Service Performance The Tenderers shall state: a) The period of manufacture of PVC insulated cables for use within Australian service conditions. b) Electricity supply authorities within Australia that have a service history of the items offered; AND c) Contact names and telephone numbers of relevant employees of those supply authorities who can verify the service performance claimed. 12. Reliability 12.1 Service Life Tenderers are required to comment on the reliability of the cable and the performance of the materials offered for a service life of 40 years under the specified service conditions Evidence in Support of Reliability Such comments shall include evidence in support of the reliability and performance claimed including information on Failure Mode and Effect Analysis. 13. Training Training material in the form of drawings, instructions, technical papers and/or audio visuals shall be provided for the items accepted under this offer within one (1) month on request. This material shall include, but is not limited to, the following topics: Handling (especially during installation). Page 6 of 10 Specification ETS Ver 4

10 Storage. Application (particularly in areas of heavy coastal pollution. Installation. Maintenance. Electrical performance. Disposal. 14. Environmental Considerations Tenderers are required to comment on the environmental soundness of the design and the materials used in the manufacture of the items offered. In particular, comments should address such issues as recycling and disposal at the end of service life. 15. Information To Be Provided 15.1 Specific Technical Requirements The Tenderers shall complete Attachment 1 of the specification and guarantee all the details provided Checklist of Supporting Documentation Attachment 2 details a checklist of supporting technical documentation, which shall be submitted with the tender. Page 7 of 10 Specification ETS Ver 4

11 16. Attachment 1 Technical Details Particulars Nominal area of core conductors Number of conductor strands Cross-sectional area of conductor strand Average radial thickness of insulation Minimum radial thickness of insulation Insulation material and grade Neutral screen Material Nominal area of screen conductors Number of screen strands Cross-sectional area of screen strand Cover (as a percentage of area of insulation) Average radial thickness of sheath Material type and grade Thickness of the nylon jacket Grade of nylon Oversheath material and grade Oversheath thickness - Average Outer sheath colour Cable overall diameter ID of recommended minimum duct size Cable mass (kg/m) Recommended maximum pulling tension Recommended minimum bending radius (a) during installation (times cable diameter) (b) setting (times cable diameter) (mm²) (mm²) (mm²) (mm²) (kn) 0.6/1 kv NEUTRAL SCREENED SERVICE CABLE 4mm2 2 Cond. 16mm2 2 Cond. N/S N/S S/C S/C Page 8 of 10 Specification ETS Ver 4

12 Particulars Maximum continuous current rating (Soil Temp. 30 o C,Resistivity 1.2K.m/W) (a) Buried direct (b) In ducts (A) (A) Design maximum conductor operating temperature (a) Normal ( C) (b) Emergency (2 hour) ( C) (c) Short Circuit ( C) Maximum D.C. 20oC (Ω/km) Maximum AC resistance of conductor of completed cable at 50Hz and 90 C (Ω/km) Positive and negative sequence impedance at 50Hz of completed cable (resistive and reactive components) (a) At 20 C (Ω/km) (b) At max. operating temperature (Ω/km) Zero sequence impedance at 50 Hz of completed cable at 20 C (resistive and reactive components) (Ω/km) Capacitance per phase in microfarads per 1000 metres at 20 C (mf/km) Power frequency withstand voltage five minutes (kv RMS) Insulation Megger readings 100 metre section tested with 2.5 kv Megger - Phase/Neutral screen (a) Expected value (GΩ) (b) Minimum acceptable value (GΩ) Type Test copies attached Type Test Certificate Number Length of cable per drum Drum mass complete with cable and lagging Australian Standard drum size ( FxBxW) Spindle Hole Diameter Manufacturer's Name and Address (yes/no) (m) (kg) 0.6/1 kv NEUTRAL SCREENED SERVICE CABLE 4mm2 2 Cond. 16mm2 2 Cond. N/S N/S S/C S/C SIGNATURE OF TENDERER: Page 9 of 10 Specification ETS Ver 4

13 17. Attachment 2 Technical Documentation Checklist Have full and comprehensive details been submitted WITH the tender documents associated with each of the following items: Clause Particulars Units 3.2 Detailed drawings of cable offered Yes / No 6.2 Type Test Certificates Yes / No 8.2 Documentary evidence of the Quality System Certification of BOTH the TENDERER and the MANUFACTURER (including Capability Statement) Yes / No 10.4 Method of lagging protection Yes / No 11 Service Performance Yes / No 12 Reliability Yes / No 13 Training materials Yes / No 14 Environmental considerations Yes / No 15 Completed Attachment 1 and Attachment 2 Yes / No NAME OF TENDERER: ADDRESS OF TENDERER: SIGNATURE: FOR AND ON BEHALF OF TENDERER DATE: Page 10 of 10 Specification ETS Ver 4

Technical Specification for Insulated Low Voltage Single Core Copper Cable

Technical Specification for Insulated Low Voltage Single Core Copper Cable Ergon Energy Corporation Limited Technical Specification for Insulated Low Voltage Single Core Copper Cable ETS03-01-03 Specification ETS03-01-03 Ver 3 Contents 1. Purpose and Scope... 1 2. References...

More information

Technical Specification for Low Voltage Aerial Bundled HDPE Insulated Cables

Technical Specification for Low Voltage Aerial Bundled HDPE Insulated Cables Ergon Energy Corporation Limited Technical Specification for Low Voltage Aerial Bundled HDPE Insulated Cables ETS03-01-04 Specification ETS03-01-04 Ver 2 Contents 1. Purpose and Scope... 1 2. References...

More information

Technical Specification for Substation 11kV and 22kV Single Core Underground Cable

Technical Specification for Substation 11kV and 22kV Single Core Underground Cable Ergon Energy Corporation Limited Technical Specification for Substation 11kV and 22kV Single Core Underground Cable ETS04-05-01 Specification ETS04-05-01 Ver 3 Contents 1. Purpose and Scope... 1 1.1 General...

More information

Technical Specification for Single Core 19/33kV Copper / TR-XLPE Underground Cable

Technical Specification for Single Core 19/33kV Copper / TR-XLPE Underground Cable Ergon Energy Corporation Limited Technical Specification for Single Core 19/33kV Copper / TR-XLPE Underground Cable ETS04-02-01 Specification ETS04-02-01 Ver 1 Contents 1. Purpose and Scope... 1 1.1 General...

More information

Technical Specification for Single Core 38/66kV TR-XLPE Insulated Underground Cable

Technical Specification for Single Core 38/66kV TR-XLPE Insulated Underground Cable Ergon Energy Corporation Limited Technical Specification for Single Core 38/66kV TR-XLPE Insulated Underground Cable ETS04-03-01 Specification ETS04-03-01 Ver 1 Contents 1. Purpose and Scope... 1 1.1 General...

More information

Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols

Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols Ergon Energy Corporation Limited Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols ETS-01-05-01 Check this is the latest Process Zone version before use. Specification ETS 01-05-01

More information

Technical Specification for Helical Fittings for Overhead Power Lines

Technical Specification for Helical Fittings for Overhead Power Lines Ergon Energy Corporation Limited Technical Specification for Helical Fittings for Overhead Power Lines ETS01-09-03 Specification ETS01-09-03 Ver 3 Contents 1. Purpose and Scope... 4 2. References... 4

More information

660 Volts 630 & 800AMP

660 Volts 630 & 800AMP Ergon Energy Corporation Limited Technical Specification for Switch- Disconnectors and Fuse-Switch- Disconnectors 660 Volts 630 & 800AMP ETS-06-02-01 Check this is the latest Process Zone version before

More information

Technical Specification for Live Line Tap Connectors

Technical Specification for Live Line Tap Connectors Ergon Energy Corporation Limited Technical Specification for Live Line Tap ETS-06-01-01 Check this is the latest Process Zone version before use. Specification ETS 06-01-01 Ver 1 Contents 1. Purpose and

More information

Technical Specification for Galvanised Fabricated Steelwork

Technical Specification for Galvanised Fabricated Steelwork Ergon Energy Corporation Limited Technical Specification for Galvanised Fabricated ETS 01-03-01 Check this is the latest Process Zone version before use. Specification ETS 01-03-01 Ver 1 Contents 1. Purpose

More information

Technical Specification for LV ABC Fuse Switch Disconnectors

Technical Specification for LV ABC Fuse Switch Disconnectors Ergon Energy Corporation Limited Technical Specification for LV ABC Fuse ETS-06-02-02 Check this is the latest Process Zone version before use. Specification ETS 06-02-02 Ver 3 Contents 1. Purpose and

More information

Technical Specification for Steel Forged Fittings

Technical Specification for Steel Forged Fittings Ergon Energy Corporation Limited Technical Specification for Steel Forged Fittings ETS 01-01-01 ETS 01-01-01 Ver 2 Contents 1. Purpose and Scope... 1 2. References... 1 2.1 Applicable Standards... 1 3.

More information

L1-CHE-SPE-171 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE

L1-CHE-SPE-171 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE Engineering Specification Electrical Networks L1-CHE-SPE-171 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM OR COPPER CONDUCTOR 3.8/6.6kV XLPE INSULATED WITHOUT METALLIC SCREEN PVC Version:

More information

P.V.C. INSULATED UNARMOURED COPPER CABLES

P.V.C. INSULATED UNARMOURED COPPER CABLES 083 : 2007 CEB SPECIFICATION P.V.C. INSULATED UNARMOURED COPPER CABLES CEYLON ELECTRICITY BOARD SRI LANKA Specification for P.V.C. INSULATED UNARMOURED COPPER CABLES CEB Specification 083 : 2007 CEYLON

More information

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

NPS/002/020 Technical Specification for 11 & 20kV Power Cables Version:- 3.1 of Issue:- Nov - 09 Page 1 of 11 NPS/002/020 Technical Specification for 11 & 20kV Power Cables 1. Purpose The purpose of this document is to detail Northern Powergrid (the Company) requirements

More information

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED Version: 1 Issued: March 2014 Owner: Electrical Networks Asset

More information

NPS/002/023 Technical Specification for 132kV Power Cables.

NPS/002/023 Technical Specification for 132kV Power Cables. Version:- 2.2 of Issue:- June 09 Page 1 of 11 NPS/002/023 Technical Specification for 132kV Power Cables. 1. Purpose The purpose of this document is to detail the technical requirements of Northern Powergrid

More information

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN Engineering Specification Electrical Networks MESP 030000-04 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN Version: 1 Issued:

More information

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 22 kv, SINGLE CORE, 95mm 2 COPPER

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 22 kv, SINGLE CORE, 95mm 2 COPPER Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR ELECTRIC CABLE Version: 1 Issued: March 2014 Owner: Electrical Networks Asset Manager Approved By: George Marulli Electrical Networks

More information

MATERIAL STANDARD FOR CABLES AND WIRES

MATERIAL STANDARD FOR CABLES AND WIRES MATERIAL STANDARD FOR CABLES AND WIRES CONTENTS : PAGE No. 1. SCOPE... 2 2. SERVICE CONDITIONS... 2 3. REFERENCES AND STANDARDS... 2 4. UNITS... 3 5. CABLE DESIGN AND CONSTRUCTION... 3 5.1 Applicable Cable

More information

11-SDMS-01 REV. 03 ( )

11-SDMS-01 REV. 03 ( ) 11-SDMS-01 REV. 03 (19-07-2018) SPECIFICATION FOR LOW-VOLTAGE POWER AND CONTROL CABLES Saudi Electricity Company 1. SCOPE... 3 2. CROSS REFERENCES TO OTHER SEC STANDARDS... 3 3. APPLICABLE CODES AND STANDARDS...

More information

Cables for Railway Signalling Applications General Requirements

Cables for Railway Signalling Applications General Requirements Discipline: Engineering (Signalling) Category: Procedure Cables for Railway Signalling Applications General Requirements ESA-11-01 Applicability ARTC Network Wide Primary Source ESA-02-01 Document Status

More information

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES 11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE

More information

Conduits. Technical Specification for Conduits and Associated Materials. JTS Version 1

Conduits. Technical Specification for Conduits and Associated Materials. JTS Version 1 Conduits Technical Specification for Conduits and Associated Materials JTS-14-05-01 Version 1 Table of Contents 1. Definitions... 1 2. Purpose & Scope... 1 3. Applicable Standards... 8 3.1 Applicable Standards...

More information

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE SEAL & SIGNATURE OF THE TENDERER PAGE 1 OF 14 TECHNICAL SPECIFICATION FOR LT XLPE POWER CABLES (SPECIFICATION NO.MM/I/LTXLPE/2006) 1. SCOPE: The specification

More information

DRAFT TANZANIA STANDARD. Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV)

DRAFT TANZANIA STANDARD. Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV) EDC3 (5239) P3 Mini-Grid Systems DRAFT TANZANIA STANDARD Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV) TANZANIA BUREAU OF STANDARDS TBS 2017 First Edition 2017 Table of Contents

More information

137-1: 2015 CEB SPECIFICATION. XLPE INSULATED SINGLE CORE UNDERGROUND CABLES OF 11 kv RATED VOLTAGE

137-1: 2015 CEB SPECIFICATION. XLPE INSULATED SINGLE CORE UNDERGROUND CABLES OF 11 kv RATED VOLTAGE 137-1: 2015 CEB SPECIFICATION XLPE INSULATED SINGLE CORE UNDERGROUND CABLES OF 11 kv RATED VOLTAGE CEYLON ELECTRICITY BOARD SRILANKA Telephone: +94 11 232 8051 Fax: +94 11 232 5387 CONTENTS Page 1.0 Scope

More information

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables Version: 4.1 Date of Issue: February 2016 Page: 1 of 25 NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables 1. Purpose The purpose of this document is to detail the requirements

More information

TECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1

TECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1 ANNEXURE TO TENDER NO. PUR42396GM DATED 06 th FEBRUARY 2014 SUPPLY OF 1.1KV GRADE LT POWER CABLES FOR THE PERIOD APRIL 2014 MARCH 2016 TECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1 1.1 SCOPE

More information

Four Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

Four Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable Edition Nº: 9 THE ISRAEL ELECTRIC CORPORATION LTD. Specification No. NPS-76 for Four Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable for Rated Voltage U0/U = 0.6/1.0

More information

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT CEB SPECIFICATION 005-1: 2012 P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS PAGE 1. Scope 03

More information

Technical Specification for Low Voltage Regulator

Technical Specification for Low Voltage Regulator Ergon Energy Corporation Limited Technical Specification for Low Voltage Regulator ETS02-05-01 Specification ETS02-05-01 Ver 4 Contents 1. Purpose and Scope... 1 2. References... 1 2.1 Applicable Standards...

More information

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/LTPVC & CONTROL/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION

More information

Specification FOR. 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated Copper Wire Screened PVC Sheathed Power Cable.

Specification FOR. 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated Copper Wire Screened PVC Sheathed Power Cable. Spec. No. GO 5821-4361Rev.2 Issued date : July 13, 2005 Revised 1 date : April 29, 2015 Revised 2 date : February 19, 2016 Specification FOR 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated

More information

Single Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

Single Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable Issued date: June, 2017 THE ISRAEL ELECTRIC CORPORATION LTD. Specification No. NPS-77 for Single Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable for Rated Voltage

More information

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables Version: 4.0 Date of Issue: October 2015 Page: 1 of 21 NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables 1. Purpose The purpose of this document is to detail the requirements

More information

Single Core, Aluminum Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

Single Core, Aluminum Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable Edition Nº: 7 NPS - 96 Issued date: June, 2017 LV, single core, Aluminum, XLPE Power Cable THE ISRAEL ELECTRIC CORPORATION LTD. Specification No. NPS - 96 for Single Core, Aluminum Conductor Extruded Cross

More information

Four Core, Aluminum Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

Four Core, Aluminum Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable Edition Nº: 7 Issued date: February, 2017 NPS 91 Specifications for THE ISRAEL ELECTRIC CORPORATION LTD. Specification No. NPS-91 for Four Core, Aluminum Conductor Extruded Cross - Linked Polyethylene

More information

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES CEB STANDARD 030-1 : 1996 Specification for RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES CEYLON ELECTRICITY BOARD SRI LANKA Specification for RESIN FILLING TYPE JOINTING KITS FOR

More information

10-SDMS-02 SPECIFICATIONS FOR BARE COPPER CONDUCTORS

10-SDMS-02 SPECIFICATIONS FOR BARE COPPER CONDUCTORS SPECIFICATIONS FOR BARE COPPER CONDUCTORS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE

More information

Technical Specification for Aluminium Conductor Underground Power Cables for Nominal System Voltages of 11 and 33 kv

Technical Specification for Aluminium Conductor Underground Power Cables for Nominal System Voltages of 11 and 33 kv Joint Ergon Energy/Energex Technical Specification for Aluminium Conductor Underground Power Cables for Nominal System Voltages of 11 and 33 kv JTS04-01-09 i Specification JTS04-01-09 Ver 1 Table of Contents

More information

SPECIFICATION FOR FRLS POWER CABLES

SPECIFICATION FOR FRLS POWER CABLES SPECIFICATION FOR FRLS POWER CABLES 1.0 SCOPE This specification cover the technical requirements of design, manufacture, testing and delivery to site of Power Cables of 1100V grade with FRLS PVC Sheathed,

More information

Test Report No.: Page 2 of 35

Test Report No.: Page 2 of 35 Test Report No.: 50093959 001 age 2 of 35 Test Report AS/NZS 5000.1:2005 including amendment 1 Electric cables olymeric insulated for working voltages up to 0.6/1kV Test item particulars: 1C 4mm 2 to 16

More information

Technical Specification for 12kV, 24kV and 36kV Disconnector (Isolators)

Technical Specification for 12kV, 24kV and 36kV Disconnector (Isolators) Ergon Energy Corporation Limited Technical Specification for 12kV, 24kV and 36kV Disconnector (Isolators) ETS06-05-01 Specification ETS06-05-01 Ver 4 Contents 1. Purpose and Scope... 1 2. References...

More information

SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR

SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR 458 7.3.1 11 KV Cables 7.3.1.1 General Where a Manufacturer s Standard or a national Standard equal to or better than the appropriate specified

More information

MGVCL/MM/ 3Cx240 mm 2 XLPE Cables/2077 TECHNICAL SPECIFICATION FOR 11 KV XLPE POWER CABLE (CROSS LINKED POLYTHELENE DRY GAS CURED) SECTION I

MGVCL/MM/ 3Cx240 mm 2 XLPE Cables/2077 TECHNICAL SPECIFICATION FOR 11 KV XLPE POWER CABLE (CROSS LINKED POLYTHELENE DRY GAS CURED) SECTION I 1.1 SCOPE MGVCL/MM/ 3Cx240 mm 2 XLPE Cables/2077 TECHNICAL SPECIFICATION FOR 11 KV XLPE POWER CABLE (CROSS LINKED POLYTHELENE DRY GAS CURED) SECTION I 1.1.1 This Section of the Specification covers design,

More information

138-1: 2015 CEB SPECIFICATION. AERIAL BUNDLE CONDUCTORS - 33 kv (95mm 2 and 150mm 2 )

138-1: 2015 CEB SPECIFICATION. AERIAL BUNDLE CONDUCTORS - 33 kv (95mm 2 and 150mm 2 ) 138-1: 2015 CEB SPECIFICATION AERIAL BUNDLE CONDUCTORS - 33 kv (95mm 2 and 150mm 2 ) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 8051 Fax: +94 11 232 5387 CONTENTS Page 1.0 Scope 3 2.0 System

More information

SPECIFICATION FOR STAY INSULATORS (PORCELAIN)

SPECIFICATION FOR STAY INSULATORS (PORCELAIN) Doc. KPLC1/3CB/TSP/04/016-1 Issue 1 Page 1 of 7 TABLE OF CONTENTS 0.1 Circulation List 0.2 Amendment Record FOREWORD 1. SCOPE 2. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION

More information

Technical Specification for Outdoor Porcelain Station Post Insulators

Technical Specification for Outdoor Porcelain Station Post Insulators Ergon Energy Corporation Limited Technical Specification for Outdoor Porcelain ETS10-01-02 Specification ETS10-01-02 Ver 2 Contents 1. Purpose and Scope... 1 2. References... 1 2.1 Applicable Standards...

More information

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 REVISION NO. 0 NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 PAGE NO. 1 OF 24 DATE OF ISSUE (MONTH/YEAR) TOTAL NO. OF PAGES (Including cover

More information

SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR

SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR 003: 2008 CEB SPECIFICATION SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for Specification For All Aluminium Alloy Stranded Conductor CEB Specification

More information

MEDIUM VOLTAGE XLPE INSULATED POWER CABLES [6.35/11kV Copper XLPE Three-Core HDPE Sheathed]

MEDIUM VOLTAGE XLPE INSULATED POWER CABLES [6.35/11kV Copper XLPE Three-Core HDPE Sheathed] [6.35/11kV Copper XLPE Three-Core HDPE Sheathed] APPLICATION Mostly used as feeder electric cable for power distribution network such as power supply station, substation, switching system etc. They are

More information

Specification for UDC Electrical Testing

Specification for UDC Electrical Testing Ergon Energy Corporation Limited Specification for UDC Electrical Testing RSC10 Abstract: Electrical Testing for Underground Distribution Construction (UDC) Specification RSC10 Ver 5 Contents 1. Purpose

More information

093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA

093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA 093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA Specification for MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEB Standard 093 : 2000 CEYLON

More information

Maharashtra State Electricity Distribution Co. Ltd.

Maharashtra State Electricity Distribution Co. Ltd. Maharashtra State Electricity Distribution Co. Ltd. SPECIFICATION NO. MSEDCL/ DIST/MM-III/02/2008/R1(010111) SPECIFICATION FOR L.T. PIN/SHACKLE INSULATORS Page 1 of 12 MAHARASHTRA STATE ELECTRICITY DISTRIBUTION

More information

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR PART 1 - GENERAL Section 26 05 15 SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR 1.1 Cable shall be 15 kv, shielded, three conductor with ground, stranded copper, with continuously welded and corrugated

More information

Type 1 Machine Cable. Oxygen free tinned annealed copper wire interwoven with high tensile poly-yarn

Type 1 Machine Cable. Oxygen free tinned annealed copper wire interwoven with high tensile poly-yarn Mining Cable Type 1 Machine Cable Application: Typically used for interconnection of control boxes or motors on non-mobile or fixed apparatus. Used when exposure to heat is not an issue and where added

More information

NPS/002/013 Technical Specification for Telephone and Pilot Cable Joints

NPS/002/013 Technical Specification for Telephone and Pilot Cable Joints Version: 3.0 Date of Issue: November 2015 Page: 1 of 12 NPS/002/013 Technical Specification for Telephone and Pilot Cable Joints 1. Purpose The purpose of this document is to detail the technical requirements

More information

31-SDMS-03 REV. 01 SPECIFICATIONS FOR

31-SDMS-03 REV. 01 SPECIFICATIONS FOR 31-SDMS-03 REV. 01 SPECIFICATIONS FOR LOW VOLTAGE CABINET FOR POLE MOUNTED TRANSFORMER This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Description

More information

Title Cables for Railway Signalling Applications - Traction Return Bonding and Track Connection Cables

Title Cables for Railway Signalling Applications - Traction Return Bonding and Track Connection Cables Discipline Engineering Standard NSW Category Signalling Title Cables for Railway Signalling Applications - Traction Return Bonding and Track Connection Cables Reference Number SPS 49 - (RIC Standard: SC

More information

SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW ARROW ROUTE, FONTANA CA

SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW ARROW ROUTE, FONTANA CA SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW THHN/THWN-2/THW/THWN/TW Listed E-492385 / E-472248 APPLICATIONS THHN/THWN-2 building wire is primarily used for general purpose applications in conduit and cable

More information

CONSULTATIONS TECHNICAL GUIDELINE. HVDC extruded cable

CONSULTATIONS TECHNICAL GUIDELINE. HVDC extruded cable UNIT, BU1SNESS AREA OUR REFERENCE TR14-02-2E DATE 2018-01-24 CONSULTATIONS TECHNICAL GUIDELINE EDITION 1 APPROVED HVDC extruded cable This technical guideline describes the basic design and construction

More information

Test Report No.: Page 2 of 34

Test Report No.: Page 2 of 34 Test Report No.: 50093985 001 age 2 of 34 Test Report AS/NZS 5000.2:2006 Electric cables olymeric insulated for working voltages up to and including 450/750V Test item particulars: 1C 4mm 2 to 16 mm 2

More information

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

The Contractor shall furnish and install all shielded power cable suitable for use on this project. Section 16122 PRIMARY POWER CABLES PART 1 GENERAL: WORK INCLUDED The Contractor shall furnish and install all shielded power cable suitable for use on this project. RELATED WORK Section 16020: Tests SUBMITTALS

More information

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- T/0018/ DMRC-E-TR-CABLE-2 SPECIFICATIONS FOR 33 kv CABLES FOR ELEVATED AND Issued on: Date Stage

More information

DATA SHEET Single Core 2HR Fire Rated Cable

DATA SHEET Single Core 2HR Fire Rated Cable Features: 2HR Fire Rated 0.6/1kV Insulation Rating 110 o C Continuous Operation AS/NZS 3013 WS52W AS/NZS 5000.1 AS/ACIF S008 RCM Certified Low Smoke Zero Halogen Flame Retardant Flexible Class 6 Conductors

More information

NPS/002/017 Technical Specification for 66 kv and 132 kv Cable Accessories

NPS/002/017 Technical Specification for 66 kv and 132 kv Cable Accessories Version:- 4.0 Date of Issue:- October 2016 Page 1 of 21 NPS/002/017 Technical Specification for 66 kv and 132 kv Cable Accessories 1. Purpose The purpose of this document is to detail the technical requirements

More information

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE ONTARIO PROVINCIAL STANDARD SPECIFICATION OPSS.PROV 604 NOVEMBER 2017 CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

MATERIAL STANDARD FOR ELECTRICAL HEAT TRACING ORIGINAL EDITION JAN. 1996

MATERIAL STANDARD FOR ELECTRICAL HEAT TRACING ORIGINAL EDITION JAN. 1996 MATERIAL STANDARD FOR ELECTRICAL HEAT TRACING ORIGINAL EDITION JAN. 1996 This Standard is the property of Iranian Ministry of Petroleum. All rights are reserved to the owner. Neither whole nor any part

More information

SPECIFICATION FOR DISC INSULATORS (Standard Type)

SPECIFICATION FOR DISC INSULATORS (Standard Type) Doc. KPLC1/3CB/TSP/04/015 1 Page 1 of 6 TABLE OF CONTENTS 0.1 Circulation List 0.2 Amendment Record FOREWORD 1. SCOPE 2. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6. MARKING,

More information

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA 094: 2000 CEB STANDARD MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA Specification for MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEB Standard

More information

Highly flexible, screened control cable with PVC core insulation and abrasion and oil resistant PUR sheath

Highly flexible, screened control cable with PVC core insulation and abrasion and oil resistant PUR sheath Highly flexible, screened control cable with PVC core insulation and abrasion and oil resistant PUR sheath - Highly flexible, screened control cable with PVC core insulation and abrasion and oil resistant

More information

TECHNICAL SPECIFICATION OF UNARMOURED FLAT 1100 VOLTS L.T. PVC INSULATED TWIN CORE 4.0mm² CABLE WITH ROUND ALUMINIUM CONDUCTOR BLACK SHEATHED.

TECHNICAL SPECIFICATION OF UNARMOURED FLAT 1100 VOLTS L.T. PVC INSULATED TWIN CORE 4.0mm² CABLE WITH ROUND ALUMINIUM CONDUCTOR BLACK SHEATHED. TECHNICAL SPECIFICATION OF UNARMOURED FLAT 1100 VOLTS L.T. PVC INSULATED TWIN CORE 4.0mm² CABLE WITH ROUND ALUMINIUM CONDUCTOR BLACK SHEATHED. I. SCOPE: This specification covers Manufacture, testing at

More information

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 604 NOVEMBER 2004 CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

0.6/1 kv LOW VOLTAGE CONTROL CABLES. Conductors. Insulation. Assembly. Standard Colour Code. Armour (Optional) Screening (Optional) Outer Sheath

0.6/1 kv LOW VOLTAGE CONTROL CABLES. Conductors. Insulation. Assembly. Standard Colour Code. Armour (Optional) Screening (Optional) Outer Sheath 0.6/1 kv LOW VOLTAGE CONTROL CABLES PVC OR XLPE INSULATED, PVC SHEATHED AS PER IEC 60502-1 Conductors Conductors shall be Circular Stranded, Class 2 as per IEC 60228, BS EN 60228. Upon request, Solid Circular

More information

SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION The ELECTRICITY (PEDE) TENDER DOCUMENTS FOR

SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION The ELECTRICITY (PEDE) TENDER DOCUMENTS FOR SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION The ELECTRICITY () TENDER DOCUMENTS FOR PREMOULDED CAΒLE TERMINATIONS (INDOOR AND OUTDOOR) AND JOINTS SUITABLE FOR 12/20

More information

Highly flexible, screened control cable with PVC insulation and PVC inner and outer sheath - certified

Highly flexible, screened control cable with PVC insulation and PVC inner and outer sheath - certified Highly flexible, screened control cable with PVC insulation and PVC inner and outer sheath - certified - Screened power and control cable for versatile use in power chains with UL/cUL AWM certification.

More information

ACCELARATED POWER DEVELOPMENT AND REFORM PROGRAMME. Technical Specification (T.S)

ACCELARATED POWER DEVELOPMENT AND REFORM PROGRAMME. Technical Specification (T.S) ACCELARATED POWER DEVELOPMENT AND REFORM PROGRAMME SECTION - V Technical Specification (T.S) 37 (SCHEDULE I) TECHNICAL SPECIFICATION FOR SUPPLY OF AB CABLE 38 1. SCOPE: TECHNICAL SPECIFICATION This specification

More information

SPECIFICATION OF LT AERIAL BUNCHED (AB) CABLES (Size: 3C x 35mm² +1C x mm²) FOR LT LINES (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY)

SPECIFICATION OF LT AERIAL BUNCHED (AB) CABLES (Size: 3C x 35mm² +1C x mm²) FOR LT LINES (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY) SPECIFICATION OF LT AERIAL BUNCHED (AB) CABLES (Size: 3C x 35mm² +1C x16 + 25mm²) FOR LT LINES (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY) 1. SCOPE: This specification covers XLPE insulated

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.14 (2.14/01/0990)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.14 (2.14/01/0990) WESTERN UNDERGROUND COMMITTEE GUIDE 2.14 (2.14/01/0990) ABRASION RESISTANT 600V CABLE NOTE: This "Guide" summarizes the opinions, recommendations, and practices of the Western Underground Committee members

More information

NATIONAL ELECTRIC POWER COMPANY (NEPCO) TENDER NO.8/2013 FOR THE SUPPLY OF CONDUCTORS FOR DOUBLE AND QUADRUPLE CIRCUITS 132 kv OHTL's

NATIONAL ELECTRIC POWER COMPANY (NEPCO) TENDER NO.8/2013 FOR THE SUPPLY OF CONDUCTORS FOR DOUBLE AND QUADRUPLE CIRCUITS 132 kv OHTL's 7.0 SPECIFICATION OF CONDUCTORS 7.1 GENERAL This Technical Specification covers the design, manufacture, testing, Packing, (CFR) supply and delivery into the dock of Aqaba Port in Jordan and guarantee

More information

project 36 MW 1.0 INTRODUCTION AND PROJECT INFORMATION

project 36 MW 1.0 INTRODUCTION AND PROJECT INFORMATION 1.0 INTRODUCTION AND PROJECT INFORMATION Welspun Energy Ltd. is executing 18MW + 18MW + 14MW Solar PV Power Project for Mahagenco in Maharashtra (Site Location: Shirsuphal, Baramati Taluka, District Pune,

More information

HDPE Conduit Specification 2011

HDPE Conduit Specification 2011 General This specification covers the minimum requirements for HDPE conduit and is based on ASTM F 2160. HDPE Conduit is for use primarily in underground applications as conduit, innerduct, direct buried

More information

Highly flexible, screened control cable with PVC insulation and PVC inner and outer sheath - certified

Highly flexible, screened control cable with PVC insulation and PVC inner and outer sheath - certified Highly flexible, screened control cable with PVC insulation and PVC inner and outer sheath - certified - Screened power and control cable for versatile use in power chains with UL/cUL AWM certification.

More information

Engineering Data for Copper and Aluminum Conductor Electrical Cables

Engineering Data for Copper and Aluminum Conductor Electrical Cables 2018 Edition Engineering Data for Copper and Aluminum Conductor Electrical Cables THE OKONITE COMPANY Okonite Cables...A higher Standard! The Okonite Company, 2018 Okonite Cables Table of Contents SECTION

More information

U.V resistance UL Sunlight Resistance. Flame retardant IEC

U.V resistance UL Sunlight Resistance. Flame retardant IEC Cable for underground power distribution and subtransmission. Description Application Underground power distribution and subtransmission. As transformer feeders in substations. In power plants, industrial

More information

Specification Technical Requirements for Overhead Conductors up to and including 33 kv

Specification Technical Requirements for Overhead Conductors up to and including 33 kv Specification Technical Requirements for Overhead Conductors up to and including 33 kv Standard Number: HPC-8DJ-03-0005-2012 Document Control Author Name: Viswa Easwaran Position: Standards Engineer Document

More information

Standard. Extra High Voltage (EHV) Post Insulators Standard R Version 1.0, June Tasmanian Networks Pty Ltd (ABN )

Standard. Extra High Voltage (EHV) Post Insulators Standard R Version 1.0, June Tasmanian Networks Pty Ltd (ABN ) Standard Extra High Voltage (EHV) Post Insulators Standard R574184 Version 1.0, June 2018 Tasmanian Networks Pty Ltd (ABN 24 167 357 299) Authorisations Action Name and title Date Prepared by Michael Verrier,

More information

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 604 NOVEMBER 2008 CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

SPECIFICATION FOR 11 & 33kV COMPOSITE INSULATORS Part 1: Pin Type

SPECIFICATION FOR 11 & 33kV COMPOSITE INSULATORS Part 1: Pin Type Doc. KPLC1/3CB/TSP/04/017/1 1 Page 1 of 7 TABLE OF CONTENTS 0.1 Circulation List 0.2 Amendment Record FOREWORD 1. SCOPE 2. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6.

More information

SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION

SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION 1.0 SCOPE 1.1 This specification covers the construction, mechanical, and electrical requirements of single conductor,

More information

3 MODIFICATIONS TO EXISTING STANDARDS

3 MODIFICATIONS TO EXISTING STANDARDS 1 SCOPE This specification covers the requirements for 25 kv rated single-phase primary cable with shielded concentric neutral and an insulating jacket. The cable may be used in single or multi-phase application

More information

TABLE OF CONTENTS. Page FOREWORD INTRODUCTION SCOPE NORMATIVE REFERENCES

TABLE OF CONTENTS. Page FOREWORD INTRODUCTION SCOPE NORMATIVE REFERENCES TITLE SPECIFICATION FOR STAYS AND REFERENCE DATE: PAGE: 1 REV 1 APRIL 2009 OF 16 TABLE OF CONTENTS Page FOREWORD...... 3 INTRODUCTION...... 4 1 SCOPE...... 4 2 NORMATIVE REFERENCES...... 4 3 DEFINITIONS

More information

Specification No. CSC-70/DH/UH/P&D/

Specification No. CSC-70/DH/UH/P&D/ Specification No. CSC-70/DH/UH/P&D/2011-2012 TECHNICAL SPECIFICATION FOR TWIN CORES PVC SHEATHED PVC INSULATED WEATHER PROOF CABLE FOR WORKING VOLTAGE UPTO & INCLUDING 1100 V, FOR SERVICE CONNECTIONS.

More information

YKY, YKY-żo 0,6/1kV PN-93/E-90401, PN-HD-603 S1, IEC

YKY, YKY-żo 0,6/1kV PN-93/E-90401, PN-HD-603 S1, IEC PVC insulated and PVC sheathed power cable CONSTRUCTION Conductors: annealed copper solid class 1(RE), circular or circular compacted stranded conductor class 2 (RM, RMC) or stranded sector shaped conductor

More information

CONSTRUCTION SPECIFICATION FOR GROUNDING

CONSTRUCTION SPECIFICATION FOR GROUNDING ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 609 NOVEMBER 2001 CONSTRUCTION SPECIFICATION FOR GROUNDING TABLE OF CONTENTS 609.01 SCOPE 609.02 REFERENCES 609.03 DEFINITIONS - Not Used 609.04 DESIGN

More information

EHV XLPE CABLES CDCC LINE

EHV XLPE CABLES CDCC LINE PROFILE THE HINDUSTHAN VIDYUT PRODUCTS LIMITED, established in the year 1959 is a leading manufacturer of Overhead Conductors and Underground Cables. The Company at its Faridabad Works has sophisticated

More information

CE ELECTRIC UK Document reference NPS / 002 / 013 Version:- 2 Date of Issue:- Jan 2011 Page 1 of 11

CE ELECTRIC UK Document reference NPS / 002 / 013 Version:- 2 Date of Issue:- Jan 2011 Page 1 of 11 Version:- 2 Date of Issue:- Jan 2011 Page 1 of 11 NPS/002/013 Technical Specification for Telephone and Pilot Cable Joints 1. Purpose The purpose of this document is detail the technical requirements for

More information

Purchase Now ANSI/ICEA S STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES

Purchase Now ANSI/ICEA S STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES ANSI/ICEA S-05-692 STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES Approved as an American National Standard ANSI Approval Date: 9/29/ ANSI/ICEA Publication

More information

SECTION 07. TECHNICAL SPECIFICATIONS OF 11 KV XLPE CU CABLE (1x500 mm 2 )

SECTION 07. TECHNICAL SPECIFICATIONS OF 11 KV XLPE CU CABLE (1x500 mm 2 ) SECTION 07 TECHNICAL SPECIFICATIONS OF 11 KV XLPE CU CABLE (1x500 2 ) TECHNIC A L SPE C IFIC A TIO NS/RE Q UIRE ME NTS O F 11 KV XLPE C U C A B LE (1x500 2 ) 7.1 GE NE RAL: This section of the document

More information