DESIGN PRACTICE NOTE EARTHING OF TCA SURGE ARRESTORS

Size: px
Start display at page:

Download "DESIGN PRACTICE NOTE EARTHING OF TCA SURGE ARRESTORS"

Transcription

1

2 DESIGN PRACTICE NOTE EARTHING OF TCA SURGE ARRESTORS L1-CHE-INS-016 Version: 2 Effective from: 21 st August 2015 Table of Contents 1. Purpose Scope Abbreviations and Acronyms Background The Issue The Requirement Responsibilities References and Legislation Appendix 1 - Transient Controls Australia Report... 5 Approving Manager: Chief Engineer Approval Date: 21/08/2015 Next Review Date: 21/08/2017 PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 2 of 5

3 DESIGN PRACTICE NOTE EARTHING OF TCA SURGE ARRESTORS L1-CHE-INS-016 Version: 2 Effective from: 21 st August Purpose The purpose of this document is to clarify MTM requirements for the earthing of TCA surge arrestor arrestors. 2. Scope The contents of this document are to be incorporated into all future design or renewal work. 3. Abbreviations and Acronyms MTM Metro Trains Melbourne PCER Prefabricated Communication Equipment Room RRL Regional Rail Link SER Signal Equipment Room TCA Transient Controls Australia VRIOGS Victorian Rail Industry Operators Group Standard 4. Background VRIOGS 012.2, section lists the following Transient Controls Australia type arrestors for power protection: Model No: TC-440/80 3 phase 440VAC incoming power. Model No: TC-150/80EI 2 wire 120VAC incoming power. Model No: TC-150/802WE 2 wire track circuits. Model L No: TC-150/803WE 3 wire track circuits (i.e. Point machines). Model L No: TC-XXS/S4 xx Nominates signal voltages. Model No: TC-RCC Communications lines. The method of earthing for the TCA surge arrestors is not described. 5. The Issue There has been confusion with designers and constructors with regards to the earthing of TCA surge arrestors. Currently there are two (2) identified methods to earth TCA surge arrestors: 1. direct earth wire from the surge arrestor to the earth bar, or 2. by using an EK10 earth connector via the G rail to the earth bar. Earthing by the direct earth wire method results in multiple earth wires that are run in parallel on the same row. MTM do not consider this as good practice. Earthing through an EK10 earth connector via the G rail, is rail industry practice and there have been no identified problems with this type of earthing of the TCA surge arrestors. This is the preferred method of earthing of the TCA surge arrestors by MTM Signal Maintenance. Approving Manager: Chief Engineer Approval Date: 21/08/2015 Next Review Date: 21/08/2017 PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 3 of 5

4 DESIGN PRACTICE NOTE EARTHING OF TCA SURGE ARRESTORS L1-CHE-INS-016 Version: 2 Effective from: 21 st August The Requirement The requirement is that TCA surge arrestors shall be installed on a G mounting rail with an EK10 earthing terminal fitted directly below the TCA surge arrestor. The TCA surge arrestor earth terminal shall be linked from its earthing terminal to the EK10 terminal. Refer to figure 1. Where there is greater than one (1) TCA surge arrestor, one (1) EK10 terminal shall not be connected to more than three (3) TCA surge arrestors. Refer to figure 1. To ensure separation of clean and dirty wiring, the earth wire shall be run on the dirty cable ducting side of the row. To ensure a good earth connection is provided as per the surge protection earthing guidelines, any terminals (EK10) that require an earth connection are to be mounted as close as practicable to the earth bar. Figure 1: Assembly arrangement 7. Responsibilities All planned works to cater for this design requirement. 8. References and Legislation Ref. No. Document Title 1. Specification for Signalling Supply, Construction and Installation 2. Lightning and Surge Protection General Requirements 3. Transport for NSW Signalling Surge Protection Installation Guidelines rence-material/ref-04.pdf Document No. VRIOGS VRIOGS Version B A N/A 15/06/2005 Approving Manager: Chief Engineer Approval Date: 21/08/2015 Next Review Date: 21/08/2017 PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 4 of 5

5 DESIGN PRACTICE NOTE EARTHING OF TCA SURGE ARRESTORS L1-CHE-INS-016 Version: 2 Effective from: 21 st August Appendix 1 - Transient Controls Australia Report Please find the following document after this page. Document Name Document Number Version No. of Sheets Performance Based Specification for Lightning Protection and General Local Earthing Sunshine SER/PCER Building /PE01 A 01/05/ Approving Manager: Chief Engineer Approval Date: 21/08/2015 Next Review Date: 21/08/2017 PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 5 of 5

6 tca Transient Controls Australia Transient Controls Australia PO Box 290 Hillarys W.A Tel : info@transcon.com.au Ref : /PE01 rev A 01 th May 2013 Sunshine SER/PCER Building. Performance Based Specification for Lightning Protection and General local Earthing. Attention: Mr. Mathew Taylor (RRL Footscray-Deer Park). Copy: Mr. Mike Coonan (Transient Controls Australia).

7 Scope of work. Transient Controls Australia to conduct Earthing and Lightning Protection Survey of Sunshine SER/PCER Compound located within the Inner Melbourne railway line and provide an Engineering Report of findings and recommendations. 1. Review existing earthing drawings provided by TBBJV. 2. Conduct a site survey of the Sunshine SER/PCER compound. 3. Rationalize the existing earthing design in accordance with AS3000, VRIOGS 12.2, VRIOGS 12.8 and Victracks standard. 4. Provide a design report with recommended earthing design along with any supporting calculations and assumptions. Specifications/References. 1. VRIOGS Signaling Equipment Housing- Revision VRIOGS Specification for signaling supply, Construction and Installation- Revision B. 3. AS Lightning Protection. 4. AS Electrical Installations. 5. AS/ACIF S TS-AST 026- Victrack- Telecommunication Equipment enclosures (communication huts) specifications. 7. Victrack- Sunshine Prefabricated communication Equipment Room (PCER) specifications. 2

8 Building Grouping. Buildings can be categorized into one main group for general engineering comments. The general engineering comments regarding earthing and lightning protection cover all three buildings along with recommendations. Risk Assessment calculations on all three buildings had the same result of 14 need for protection on all incoming and outgoing cabling, Note : For risk assessment purposes the equipment has been classified as essential public supply equipment, All sites are within the average annual thunder day map zone and have lightning flash rate of 8 flashes per square km per year. These figures would rate the sites as Category C risk external Services. Due to the length and exposure of incoming feeder power supply this area has been classified as Category C High risk external services. The need for structural lightning protection to the buildings is a combination of the following factors : 1. The geographical location of the structure. 2. The effective collection area of the structure. 3. The intended use of the structure. 4. The type of construction. 5. What is housed within the structure. 6. The location of the structure (Is it located in a built up area or isolated area). 7. The topography of the location/countryside. 3

9 Earth Grid Specification. The final earth grid specification is a result of Soil Resistivity tests and Depth site survey tests. These tests were performed at two locations on site and an optimum design has been achieved as a result of these tests. Measurement of soil resistivity and depth site surveys were taken at two locations and it was not possible to vary spike direction in all four directions due to site access restrictions. It is to be noted that a 90deg grid test variation of the Soil resistivity was possible. Soil Resistivity Tests indicated homogeneous soil. Due to the lack of area to perform additional tests Werner depth surveys were incorporated with standard Line of traverse testing to obtain final resistivity results. A resistivity map was not an option due to limited area for testing. The site had Line Traverse Soil Resistivity tests taken using 200mm/4M and 400mm/8M (Four pole a/20 method). From these tests and using the Wenner Resistivity calculation Nomogram, earth grids for each building were mapped out and plotted. (See drawing A4600). The earth grids plotted have an optimal rod spacing resulting in 100% efficiency in rod separation to depth ratio. The calculated earth impedance to discharge high transient currents in this area is under 5 ohms, this value would guarantee a secondary transient in the order of 100kA (8/20uS) current pulse would discharge safely. A target value of 2 ohms has been specified by the customer and to achieve this over the entire year taking into account extreme weather conditions the earth building grids have been designed. Site conditions and soil resistivity tests would indicate parallel rod electrodes in a matrix arrangement with inter rod coupling would be best suited at all buildings. A target figure of 2 ohms should be achieved via this method which will ensure that the local ground dissipates lightning energy and other dangerous electrical fault currents to a safe level at high speed. The earth is (relatively) infinite in its size compared to the grounding system and can absorb a virtually unlimited supply of current. In practice this unlimited path is limited by the metal electrode-earth soil interface. With a rod electrode the resistance of the soil is the sum of the series of resistances of virtual shells of earth, located progressively outward from the electrode. The shell nearest the rod has the smallest circumferential area of cross section so it has the highest resistance. 4

10 Successive shells outside the inner one have progressively larger areas and thus progressively lower resistances. As the radius from the earth rod increases the incremental resistance per unit of radius decreases to nearly zero. The path of ground current outward from the earth rod surface consists of successive cylindrical and hemispherical shells. As the distance from the rod increases, so do the cross-sectional areas of the individual shells. As their areas increase their individual series resistances decrease inversely proportionally with the area. The first 1.5 meters from the earth electrode is the most important as this has the highest resistance. It is recommended from site results that a minimum rod depth of 4 meters be used with a grid layout on the building outer limits, the earth grids should be located a minimum of one meter from the buildings foundations. It is to be noted that the depth/spacing ratio is ideal and no additional spur electrodes were required. It is imperative that good earths be installed locally at each building to effectively dissipate transient faults and maintain a good safety earth for personnel and equipment. The return path from any new local earth grid should be physically routed away from all other clean earthing or clean input/output cabling. Each local earth grid requires a separate earth connection (two connections per grid is recommended) to the local earth buss bar, these connections should be 50mm copper cable routed in an electrically dirty designated path avoiding all electrically clean wiring. This physical barrier is critical to the effective elimination of reentrant transients and cross coupling of multiple low level transients. The Earth grid deep vertical rods are at four meter depth and have been specified at 19mm diameter, the 19mm rods are only required if the rods are to be driven into the ground by Kanga hammer or similar mechanical method. Should the sites be drilled then a 16mm diameter rod is acceptable and the drilled holes should be backfilled with Bentonite. The advantages of the Bentonite backfill are to Increases the surface area of the Earth- Electrode, thus lowering its earth resistance and to reduce the soil resistivity by retaining moisture. The interconnection of the deep driven earth rods is a critical part of the final earth grid design. These connections are in effect used as a radial electrode and form part of the final calculated design. It is essential that the trench depth be at minimum 1 meter depth for final earth resistance value and to reduce the voltage gradient to a safe personnel level. 5

11 Local Earth Grid Hardware Components. 1. Deep driven earth rods. Earth rods 19mm diam * 3meter length, 99.9% pure electrolytic copper, molecularly bonded onto steel core minimum thickness 0.25mm. Low carbon steel core with high tensile strength. Rod threads should be rolled for strength and to ensure uniform layer of copper. 2. Rod coupling. Long length silicon and aluminum bronze counter bored threads. Couplings must ensure rod to rod coupling. (19mm coupling). 3. Rod to cable clamp. Cast gun metal body and phosphor bronze bolt. (19mm rod to mm cable). 4. Inter grid connecting cable. Interconnecting grid cables should be bare copper mm. The interconnecting grid should be buried to a depth of meters. 5. Earth inspection pits. Polymer shatterproof earth inspection pit, chemical resistant, load level 5000kg, resistant to oil, petrol, and diesel. Note : No underground jointing of grid cables, all clamps above ground within the inspection pit. Earth inspection pit must be a minimum of 250mm of clear rod to surface. 6. Air Terminal. Solid Copper Earth Terminal (1m ). 7. Air Terminal Base. Cast gun metal air terminal base. 8. Copper Tape. High conductivity annealed copper tape. Note : The 19mm diameter rods and couplings can be replaced by 16mm rods and couplings if sites are to be drilled for the vertical earth rods. 6

12 Transient Protection. The buildings lend themselves to a physical/electrical barrier approach where all outgoing and incoming cabling can be physically routed via a dirty path and all clean protected cabling can be physically isolated from any dirty areas. Main earth transient return paths are classified as a dirty earth and should be included as part of the physical barrier. This alone will reduce a large amount of damage from cross-coupling of transient faults. All incoming cables should have transient clamps fitted and these clamps should be incorporated in the following areas. 1. Input Power and Backup Power. 2. All signaling cabling. This should include lamps, field contacts, point s machines and track circuits. 3. Communications cabling. This should include the data transfer multidrop system and any modem links. Installing earthing grids/low impedance high current earth discharge paths and bonding at all sites. Equipment location. All equipment is to be located within the buildings. Use of high speed three mode transient clamps of correct clamp levels for all equipment to be protected. All external mains power sources protected on incoming and outgoing lines with correct fault level protection for area classification. As per AS- 1768:2009. (Mains power input 70kA, signal/control inputs/outputs 20kA). All of these measures should be viewed as cumulative and not alternatives. 7

13 Input Power. Input power to SCR building is transformer isolated normally 2.2kV/110V transformer. The power reticulation supply path is underground and is a common source of transient entry to control rooms. Transformer isolation does not provide transient over voltage protection. Distribution transformers will certainly provide a degree of protection but unfortunately they also have the characteristic faults of sneak paths which allow transients from the HV primary directly through to the LV power distribution supply. High voltage to Low voltage transformer action theoretically eliminates transients with respect to earth. That is Line to earth and Neutral to earth. The problem is stray capacitance between primary and secondary windings within the transformer will provide the transient fault with a high frequency path from primary to secondary. In the case of Line to Line transient or differential transients then the transformer is of little or no protective value. These transient faults will pass easily through transformer windings. Also Resistive coupling of transients within transformers is common with differential earth reference points. Live to earth transient laboratory testing on transformers show surprisingly large transient over voltages let-through. The recorded transient let-through level was in the order of half the input due to capacitive coupling. The transformer must not be viewed as an effective transient protection device. A practical solution would be to use a common and differential mode transient clamp at the secondary of the transformer. This would give effective safe transient clamp protection and also in the rare case of unit failure to earth isolation from earth reference. Recommended transient clamp for this purpose would be the TC-150/802EI. The TC-150/802EI would give the required protection in both the common and differential modes with a low let-through voltage that would eliminate transient damage and erroneous system tripping and shutdown. All back-up 240V supplies should be protected using either a TC-440/80 or a TC-150/80, this will ensure integrity of the safe zone and stop transient entry via this path. 8

14 Signal Circuits. Signaling circuits are broken down into three main groups. 1. Direct signaling circuits such as lamp drivers and interface contacts. 2. Points machines, main dive circuits. 3. Track circuits. The direct signaling circuits should be protected by series clamps. These clamps are to be installed as close as possible to the incoming safe area designated zone. The recommended family of clamps is the TC-**S/S4, this family has a working voltage range of 5V to 200V and has been designed specifically for the rail industry with fail to safe functionality. See sample specification below. TC-18S/S4 1. Maximum working Voltage 18V D.C. 2. Peak clamp let thru Voltage 28V peak. 3. Response time less than 10nS. 4. D.C. resistance less than 0.1R end to end. 5. Working current 4amps. 6. Discharge current 20ka (8/20uS) per line, 40kA per unit minimum. 7. Healthy indication. 8. Snap on Din or G rail mounting. 9. Multi strike capability (not one shot fuse type unit). 10. Earth connection isolated from all other wiring and mounting. To avoid dangerous voltage levels occurring within the panel. 11. Earth connection is dirty earth and should be separated from all clean safe wiring, 4mm isolated earth stud mounted on top of unit. 12. No DIN rail earthing of unit should be used as transient reentrant loops will occur. Also the danger of arcing from DIN rail to unit has a high failure due to high discharge currents causing high potential differences. 13. Dimensions are critical low density racking. 12.5W*45H*75L. 14. Plug and base units a not acceptable due to the unsuitability of the pressure wipe contact. Under transient fault conditions the earth and or line contacts have to conduct 20kA, this high energy pulse will either totally destroy the contact or seriously degrade it. The degradation may not be evident initially but will upon next transient fault it will cause a high differential across the contact resulting in very high let thru voltage. 9

15 Points Machines. Point s machines are protected at point of return from field, the transient is effectively clamped at safe area and type of unit used will depend upon power out to point s machine. One such clamp is the TC-150/802WE. Note : Point of entry is the actual physical entry point into the control room or cabinet, of a cable or group of cables. Local earth grid take off points are classified as an entry cable and must be treated as dirty or field wiring. The required segregation distances must be observed when installing such cables. Communications circuits. All communication input and output circuits should have transient clamps fitted. The multidrop communication circuits should have transient protection clamps fitted on every loop input located at point of entry to SER. It is also recommend that this unit have a healthy local indication for maintenance. One such clamp is the TC-RCC. 10

16 Track Based Primary Protection. The primary track protection should be high energy low let thru voltage parallel clamps. These clamps should be high energy 500kA parallel high speed low let thru voltage clamps due to the application and the vulnerability of the equipment to be protected. There is no doubt that a large amount of transient coupling occurs on the long length of the tracks, the tracks are insulated and direct and indirect lightning will be induced on to these tracks. This will result in high elevated voltage levels onto the tracks with respect to ground. The result of this is flashover at various points is large common mode and differential mode transients entering the control cabinets. It is strongly recommended that HIGH energy HIGH speed transient clamps be installed at the track take off points in the field. These clamps should have local earth deep driven rods to dissipate the transient before it has chance to flashover and enter the cabinets via the field wiring. The high energy 500kA clamp should have the following minimum specifications. 1. Response time less than 25nS. 2. Working Voltage 120V A.C. 3. Peak clamp voltage of 327V. 4. Discharge current of 250kA (8/20uS) per line. 5. Provide repeated protection in high lightning intense areas. 6. Local indication of system healthy. Clamps should be connected from rail to a local dedicated earth. All cables lengths to be kept as short as possible. All cables including earth cable should be segregated from any other wiring by a minimum of 100mm. Note : If using high energy spark gaps care should be taken during evaluation and selection. The standard spark gap has a slow response time and a very high let thru voltage. This let thru voltage in the order of 4-5kV is one of the main reasons for the careful selection of HIGH energy HIGH speed primary transient clamps. The very low level let through voltage is critical in this application. (See data sheet TC-150/250) 11

17 Structural Lightning Protection. The rail system is classified as an essential public service and the buildings critical to this operation. The buildings house items of sensitive electronic equipment and from risk management calculations the result is need for structural lightning protection at all buildings. Due to the classification of all the buildings the required minimum earthing resistance should not exceed 5ohms. The structural lightning protection systems can be broken down into five main groups. 1. Air Termination Network. 2. Down conductors. 3. Test links. 4. Earth terminations. 5. Earthing electrodes. Air Termination Network. All buildings having metal clad roofing (coulour bond) fixed to metal roof beams. The roofs have no large variations in height so the roof beams can be used as an Air Termination Network with some additions to make it an electrically continuous network. The roof beams if not continuous in length should be electrically bonded at joints with a 50mm earth strap. All roof beams at edges of roof should be cross bonded with earth strap to adjacent beam. This will ensure a continuous Air Termination Network that covers the entire roof area with a High discharge network with low impedance. The parts of flat or semi flat roofs most likely to be struck by lightning are the corners and edges. Down Conductors. The down conductors should be installed at each external corner of the SCRs and also if the SCRs are greater than 20m in length then a central down conductor is necessary. As the SCRs walls are constructed of precast reinforced concrete it is recommended that the steel mesh reinforcing be used as the down conductors. Any overlapping non continuous steel mesh within the casting should be welded together to form an electrically continuous path. The roof and foundation points of the 12

18 wall casting at the corners (and centre if over 20m) should have take off points exiting the casting for electrical bonding. It is common practice to use a steel strap welded to the mesh exiting the casting with 10mm studs welded for electrical connections. Note : It is possible to use copper tape on the outside of the building clipped to the precast walls at earth electrode points if the internal steel mesh is inaccessible. Test Links. The test links of each down conductor should be provided in the earth pit of each earth electrode and this is for testing purposes only. The test link also serve as the earth termination points. Earthing Electrodes. The Earthing Electrodes are the four (six on buildings over 20m) general earthing points around the building. This in effect is the common bonding network. The concrete reinforced floor should have two exit points from the steel mesh connected directly to the Lightning Protection Network to complete a common bonding network. These exit points should be at opposite corners of the buildings if possible. The electrical network should have as few joints as possible and be mechanically and electrically sound. Where overlapping joints are used the overlap must not be less than 20mm. All joints must be clean and inhibited from oxidation with suitable corrosioninhibiting compound. 13

19 High Voltage supply. The following High Voltage Installation requirements are assumed to have been addressed in the preliminary considerations with the Regulatory Supply Authority before construction. 1. Access. 2. Correct circuit control and protection. 3. Labeling 4. High Voltage control incoming. 5. Busbar /Switchgear design 6. Transformer general. 7. Emergency procedures. 8. Electrical clearances. 9. Fire protection. 10. Safety signs. All of the above items are to comply with Australian Standards and are assumed to have been completed. Earthing. The earthing networks or Local Earth Electrode Grids at each building should be linked at the common earth bar within the building. Two 50mm copper cables should be used for this connection (see drawing A4601). Combined Earthing System. It is recommended that the Combined Earthing System (CES) be adopted. The CES is a system where the high voltage earth and low voltage electrical earths are taken to a common earth bar. The earthing system overview is shown in drawing A4600 reva. The CES is common to all buildings. There are a number of strict rules that must be adhered to for CES installations. 1. There must be at least two earth connections to the main earth grid. These connections should be at diagonally opposite corners of the earth grid network. 2. All accessible exposed conductive parts containing or supporting high voltage equipment must be earthed to the CES. 3. All metal enclosures within the H.V. room are connected to the CES. All exposed metal work in and around the structure must be bonded to the CES. 4. Low voltage Earths and Neutrals to be connected to the CES. 14

20 5. All High and Low voltage cable sheaths are connected to the CES. The H.V. incoming cable metal sheath must have a direct and dedicated earth complete with disconnect link to the CES and marked. 6. All underground services such as water pipes must be bonded to the CES. 7. Low and High Voltage surge diverting devices must have their return paths bonded to the CES. 8. The reinforcing network of the building must be bonded to the CES. 9. Minimum H.V. earthing connection 25mm/sq (Main earth grid earth connections minimum of 50mm/sq copper cable). 10. H.V. insulating matting should be installed in and around all H.V. incoming cable entry, transformers/switchgear. The matting should have a dielectric strength of 30,000V for 1min and a Voltage test of 15,000 for 1min with a continuous rating of 3000V minimum. The CES should have a resistance to earth not greater than 1ohm. Note: This is a requirement of AS3000 and all sites should achieve this with the standard design at present. All sites also have low level step and touch potentials and meet all Australia and International safety standards. H.V. Earth Faults/Step and Touch Potentials. It is assumed that all supplies have been tested for make and break currents at full working load and at fault level load with respect to source impedance. The 2.2kV H.V. supply is a fully floating supply and has no reference to earth in normal operation or in fault conditions. The use of fully floating systems in low level H.V. supplies needs special considerations regarding earthing. The mechanical steel wire armoring and shield screen if any should be earthed at both ends and this earth clearly identified at termination point CES earth bar (H.V. Earth). All standard H.V. precautions should be applied and only authorized personnel have access to H.V. rooms. The H.V. standard earth fault testing does not apply to isolated fully floating supplies other than any return fault path should be capable of carrying fully fault level currents and protection equipment should be able to operate with no damage to any return path. The structural lightning protection earth network has the capacity to discharge a direct lightning strike and precautions have been taken to ensure that the Australian and International standards are meet. The step and touch potential has been addressed with respect to lightning and this also covers a supply fault to earth. The cross bonding of all exposed metalwork with 15

21 insulation of down conductors and rod entry level to ground for the lightning protection system all covers the step and touch potentials. The deep driven earth rods with interconnection copper links act not only as a structural lightning protection earth network but also as a discharge path below ground level (250mm minimum earth rod). The earth resistivity and depth testing results gave final design of deep driven rods the only effective method of creating a local earth. The maximum current discharge over the average rod would occur at a depth of 4/6 meters, the top 300/500mm of soil at all sites would be greatly affected by a number of factors which include temperature, moisture and soil composition. The step potential is greatly affected by these variables and if fault current from source was to be discharged via the grid (which is not possible with fully isolated/floating systems) then under the most severe conditions e.g. 40degC and 30% moisture by weight then step potential would still be extremely low at surface level. Remember that the fault current has a distributive effect over the entire earth network and a step potential is measured at 1metre spacing. Direct lightning strike to the building has to be treated differently and risk factors have to be weighted for practical and effective discharge with safety from step and touch potentials to taken into account. 16

22 General Comments. The need for structural protection to the buildings based upon site viewing would indicate a high level of zone protection exists. However the classification of the rail network and the critical operating nature of the buildings to that network results in the need for Structural Lightning Protection. The protection of all incoming and outgoing cables is essential and the physical separation barrier is critical to ensure an effective transient barrier for the SERs. The earthing grid has been standardized where possible for ease of construction. It is essential that all dirty earths are segregated from all clean wiring. The earth grid should be connected to the main SER isolated earth and all other earths should be common bonded. The communications earth can be isolated from all other earths but it is highly recommended that an electrically isolated earth clamp be used. (ref TC-EC). If communications earth is isolated the perimeter fence must have isolation sections with equalization clamps fitted for personnel safety requirements. A number of data sheets and drawings have been included in this package of standard power/signal protectors and construction sheets as a general guide. Should any further information or clarification be required Transient Controls Australia would be available to provide. Yours sincerely, Peter Evans Engineering Director Transient Controls Australia. 17

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph

More information

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL). 16450 GROUNDING ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 26 An optional keynote to the

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Updated format, division title, and removed references to other sections. - mgl44 A. Summary This section contains design criteria for the

More information

Grounding Principles. The need to ground! Definitions. Introduction. Grounding Codes and Standards. 2 Ph:

Grounding Principles. The need to ground! Definitions. Introduction. Grounding Codes and Standards. 2 Ph: Introduction Grounding and bonding are an integral part of any modern electrical protection system design. An effective, low-impedance ground system is a key element of this system. It is crucial in ensuring

More information

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED Version: 1 Issued: March 2014 Owner: Electrical Networks Asset

More information

TESTING PTE EARTHING

TESTING PTE EARTHING 1 SCOPE This section of the Power Systems Live Working Manual details the procedures to be followed to achieve Safety from the System when carrying out examination, testing and remedial work on PTE (Pole

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN Engineering Specification Electrical Networks MESP 030000-04 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN Version: 1 Issued:

More information

Standard of Practice - Campus Electrical Distribution System

Standard of Practice - Campus Electrical Distribution System A26.3 Standard of Practice - Campus Electrical Distribution System NOTE: Significant revisions or additions to the previous standards are highlighted in italics. GENERAL Designers shall verify that all

More information

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING SECTION 16060 PART 1 GENERAL 1.01 DESCRIPTION A. Section includes requirements for an electrical grounding system, including electrodes, grounding rods, connectors, insulators, equipment grounding and

More information

THE OFFICIAL TRADE JOURNAL OF BICSI

THE OFFICIAL TRADE JOURNAL OF BICSI ICT TODAY THE OFFICIAL TRADE JOURNAL OF BICSI January/February 2017 PLUS + + Information Security and ESS in the Age of the Internet of Things + Grounding System Design and Testing for Critical Facilities

More information

Lightning Protection Practice for Large-Extended Photovoltaic Installations

Lightning Protection Practice for Large-Extended Photovoltaic Installations 202 International Conference on ightning Protection (ICP), Vienna, Austria ightning Protection Practice for arge-extended Photovoltaic Installations Dr. Nikolaos Kokkinos Research and Development Department

More information

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING 2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING E3305.3: now reads The space equal to the width and depth of the panelboard and extending

More information

Electrical Networks Principles and Performance

Electrical Networks Principles and Performance Engineering Standard Electrical Networks Electrical Networks Principles and Performance Version: 1 Issued: January 2015 Owner: Chief Engineer Approved By: Paul O Halloran Chief Engineer PRINTOUT MAY NOT

More information

MTM REQUIREMENTS METROPOLITAN TRAIN MAINTENANCE DEPOT

MTM REQUIREMENTS METROPOLITAN TRAIN MAINTENANCE DEPOT Approval Amendment Records Approval Date Version Description 14/11/2011 1 Initial Version Disclaimer Metro Trains Melbourne makes no warranties, express or implied, that compliance with the contents of

More information

NPS/002/023 Technical Specification for 132kV Power Cables.

NPS/002/023 Technical Specification for 132kV Power Cables. Version:- 2.2 of Issue:- June 09 Page 1 of 11 NPS/002/023 Technical Specification for 132kV Power Cables. 1. Purpose The purpose of this document is to detail the technical requirements of Northern Powergrid

More information

NEC 2014 Code Changes

NEC 2014 Code Changes NEC 2014 Code Changes Articles 280.21-300.50 CHANGES FROM 2011 TO 2014 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 280 Surge Arresters, Over 1000 volts II. Instillation III. Connecting Surge

More information

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11 Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11 Underground Residential Distribution (URD) Index General Discussion... 1-2 Description... 3-7 Drawings (Available

More information

(Condensed from National Electric Code)

(Condensed from National Electric Code) WIRING, SPECIFICATIONS, INSPECTION, AND METER INSTALLATION PROCEDURES FOR RESIDENTIAL CUSTOMERS SERVED BY SOUTHWEST ARKANSAS ELECTRIC COOPERATIVE CORPORATION Effective April 1, 1974 Revised February 3,

More information

UNDERGROUND SERVICES SECONDARY

UNDERGROUND SERVICES SECONDARY Reference UNDERGROUND SERVICES SECONDARY Underground services secondary... U- 1 General requirements for underground service... U- 2 Name of parts for underground service... U- 3 Conduit layouts... U-

More information

Specifications for Residential Overhead Electric Service Installation

Specifications for Residential Overhead Electric Service Installation Specifications for Residential Overhead Electric Service Installation This brochure addresses most typical residential overhead service installations. Variances for the following specifications must be

More information

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

NPS/002/020 Technical Specification for 11 & 20kV Power Cables Version:- 3.1 of Issue:- Nov - 09 Page 1 of 11 NPS/002/020 Technical Specification for 11 & 20kV Power Cables 1. Purpose The purpose of this document is to detail Northern Powergrid (the Company) requirements

More information

Installation, Inspection and Maintenance of Dry Type Transformers

Installation, Inspection and Maintenance of Dry Type Transformers Dry Type TX 1 of 8 Installation, Inspection and Maintenance of Dry Type Page 1 of 8 Dry Type TX 2 of 8 Table Of Contents Page Number 1. General... 3 2. Installation... 3 3. Safety Inspections... 4 4. Safety

More information

Aluminium Excellence Performance in Economical Way

Aluminium Excellence Performance in Economical Way OPPER CLAD Aluminium Excellence Performance in Economical Way www.jmv.co.in Leading The Nation Towards Electrical Safety With the growing industrialization, the demand of electrical safety is increasing

More information

EXTERNAL GROUNDING (EARTHING)

EXTERNAL GROUNDING (EARTHING) EXTERNAL GROUNDING (EARTHING) CHAPTER 4 This chapter provides requirements and guidelines for designing and installing the external grounding (earthing) electrode system at a communications site. This

More information

Revisions for the 2011 National Electrical Code - Part 2

Revisions for the 2011 National Electrical Code - Part 2 PDHonline Course E356 (3 PDH) Revisions for the 2011 National Electrical Code - Part 2 Instructor: Patrick Ouillette 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone &

More information

PATHWAYS FOR COMMUNICATIONS SYSTEMS

PATHWAYS FOR COMMUNICATIONS SYSTEMS 270528 PATHWAYS FOR PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, and equipment for the complete installation of work called for in the Contract Documents. 1.2 SCOPE OF WORK A. This

More information

Technical Specification TS Issue 5 September 2014 EARTHING

Technical Specification TS Issue 5 September 2014 EARTHING EARTHING This document is for internal and contract specific use only. Disclaimer NGG and NGET or their agents, servants or contractors do not accept any liability for any losses arising under or in connection

More information

Technical Specification for LV ABC Fuse Switch Disconnectors

Technical Specification for LV ABC Fuse Switch Disconnectors Ergon Energy Corporation Limited Technical Specification for LV ABC Fuse ETS-06-02-02 Check this is the latest Process Zone version before use. Specification ETS 06-02-02 Ver 3 Contents 1. Purpose and

More information

A. Product Data shall be provided for each type of product indicated.

A. Product Data shall be provided for each type of product indicated. 32 31 13 CHAIN LINK FENCES AND GATES SECTION 1 GENERAL 1.1 SUMMARY This Section includes the following: 1. Chain Link Fences 2. Gates for Chain Link Fences. See electrical specifications for electrical

More information

Cables for Railway Signalling Applications General Requirements

Cables for Railway Signalling Applications General Requirements Discipline: Engineering (Signalling) Category: Procedure Cables for Railway Signalling Applications General Requirements ESA-11-01 Applicability ARTC Network Wide Primary Source ESA-02-01 Document Status

More information

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp,

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp, TITLE 14 CHAPTER 10 PART 4 HOUSING AND CONSTRUCTION ELECTRICAL CODES 2011 NEW MEXICO ELECTRICAL CODE 14.10.4.1 ISSUING AGENCY: The Construction Industries Division of the Regulation and Licensing Department.

More information

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL 8.01 GENERAL This material is not intended to cover service from OPPD s network in the downtown Omaha area. See Chapter 12 for details

More information

C&G 2382 BS7671: th Edition IEE Wiring Regulations. 25 Questions

C&G 2382 BS7671: th Edition IEE Wiring Regulations. 25 Questions C&G 2382 BS7671:2008 17 th Edition IEE Wiring Regulations 25 Questions 1. BS7671 states that installation design must take into account a. current copper prices b. the effects of climate change c. a comparison

More information

ICC-ES Evaluation Report Reissued May 1, 2010 This report is subject to re-examination in two years.

ICC-ES Evaluation Report Reissued May 1, 2010 This report is subject to re-examination in two years. ICC-ES Evaluation Report ESR-1255 Reissued May 1, 2010 This report is subject to re-examination in two years. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council

More information

Electric Service Standards

Electric Service Standards V: 1 of 6 A. Padmounted Requirements Complete requirements are contained in FPL specifications given to Customers for individual projects. Typical pad mounted transformer requirements include, but are

More information

Specifications for Residential Underground Electric Service Installation

Specifications for Residential Underground Electric Service Installation Specifications for Residential Underground Electric Service Installation This brochure addresses most typical residential underground service installations. Variances for the following specifications must

More information

NPS/002/001 Technical Specification for Earthing Materials

NPS/002/001 Technical Specification for Earthing Materials Version:- 6.0 Date of Issue:- October 2017 Page 1 of 14 NPS/002/001 Technical Specification for Earthing Materials 1. Purpose The purpose of this document is to detail the requirements of Northern Powergrid

More information

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property 2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical

More information

2015 Code Rollout Meeting Q & A

2015 Code Rollout Meeting Q & A 1 SECTION QUESTION SaskPower Inspections Dept. ANSWER 2 3 4 5 6 7 8 9 10 11 12 15-02-024 15-02-200 15-02-200 15-02-200 15-02-314 Are existing single or double 'weather proof when not in use' covers allowed

More information

ELECTRICAL BULLETIN

ELECTRICAL BULLETIN PO Box 697 Halifax, Nova Scotia B3J 2T8 ELECTRICAL BULLETIN 2015-01 From: David MacLeod, C.E.I., P.Eng. Pg. 1 of 7 Provincial Chief Electrical Inspector Date: March 10, 2015 Subject: Adoption of the 2015

More information

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

B. Provide liquid-filled secondary substation transformers as indicated on drawings. SECTION 26 12 13 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 26 05 00. B. Provide liquid-filled secondary substation transformers as indicated on drawings. 1.02 RELATED

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519 METAL CLAD CABLE - MC-PLUS Neutral

More information

Basic Requirements for Residential Electrical Installations

Basic Requirements for Residential Electrical Installations Basic Requirements for Residential Electrical Installations Wayne County Building Department 428 West Liberty Street Wooster, Ohio 44691 Phone: 330-287-5525 Fax: 330-287-5649 This brochure is intended

More information

Specification Lightning Protection Systems

Specification Lightning Protection Systems Specification Lightning Protection Systems General: Summary A) This Section specifies the lightning protection system for the building(s) or structure(s). This system provides safety for the building and

More information

The University of Texas at Austin September 30, 2011

The University of Texas at Austin September 30, 2011 SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATIONS PART 1 - GENERAL 1.1 SUMMARY A. This section governs the products and execution requirements relating to furnishing and installing grounding and

More information

Switch Solar. Praveen Raj. [20 KWp Solar Power Plant Technical Proposal] Noble Hospital Chennai, Tamil Nadu.

Switch Solar. Praveen Raj. [20 KWp Solar Power Plant Technical Proposal] Noble Hospital Chennai, Tamil Nadu. 2013 Switch Solar Praveen Raj [20 KWp Solar Power Plant Technical Proposal] Noble Hospital Chennai, Tamil Nadu. Contents 20KW Solar Power Plant Technical Proposal Technical Proposal...1 Section A - Bill

More information

Friday, May 29, Update on Testing Medium Voltage Cable and Switchgear Systems

Friday, May 29, Update on Testing Medium Voltage Cable and Switchgear Systems Update on Testing Medium Voltage Cable and Switchgear Systems Friday, May 29, 2015 Presented by: Ashley Harkness Ashley.Harkness@Emerson.com Electrical Reliability Services Value--- When we find the one

More information

A. This section includes building wire and cable rated 600V and less Full Short Circuit Device, Coordination and Arc Fault Study

A. This section includes building wire and cable rated 600V and less Full Short Circuit Device, Coordination and Arc Fault Study PART 1: GENERAL 1.01 Underground Ducts and Manholes A. The work included in this section of the construction standards consists of the design requirements for the complete layout and installation of a

More information

Document No Amendment No Approved By Approval Date Review Date NS222 MAJOR SUBSTATION EARTHING LAYOUT DESIGN

Document No Amendment No Approved By Approval Date Review Date NS222 MAJOR SUBSTATION EARTHING LAYOUT DESIGN Network Standard NETWORK Document No Amendment No Approved By Approval Date Review Date : : : : : NW000-S0002 0 Chief Engineer 26/02/2015 31/12/2018 Review Amended Date 22/12/2017 NW000-S0002 NS222 MAJOR

More information

thermoweld The Contractors Choice GREAT PRODUCTS GREAT SERVICE GREAT PEOPLE

thermoweld The Contractors Choice GREAT PRODUCTS GREAT SERVICE GREAT PEOPLE The Contractors Choice the Contractors Choice Founded in 1958, with locations in Tulsa and Broken Arrow, Oklahoma. is part of the Quality Brands of Continental Industries. TABLE OF CONTENTS THE PROCESS...4

More information

WIRING METHODS CHAPTER 38

WIRING METHODS CHAPTER 38 CHAPTER 38 WIRING METHODS SECTION E3801 GENERAL REQUIREMENTS E3801.1 Scope. This chapter covers the wiring methods for services, feeders and branch circuits for electrical power and distribution. E3801.2

More information

SECTION CHAIN-LINK FENCES AND GATES 02821/1

SECTION CHAIN-LINK FENCES AND GATES 02821/1 SECTION 02821 - CHAIN-LINK FENCES AND GATES 02821/1 PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Chain-Link Fences: 2. Gates: horizontal slide or swing. 3. Fences installed where

More information

ELECTRICAL BULLETIN

ELECTRICAL BULLETIN PO Box 697 Halifax, Nova Scotia B3J 2T8 Labour and Advanced Education ELECTRICAL BULLETIN 2012-01 From: David MacLeod,C.E.I.,P.Eng. Pg 1 of 8 Provincial Chief Electrical Inspector Date : March 1, 2012

More information

Lightning Protection and Trees

Lightning Protection and Trees Lightning Protection and Trees By Ben Fuest INTRODUCTION This research was established for the purpose of developing a better understanding of lightning protection systems specifically designed to be fitted

More information

Lightning exposure of Carbon Fiber Composites in wind turbine blades

Lightning exposure of Carbon Fiber Composites in wind turbine blades 105 24 th Nordic Insulation Symposium on Materials, Components and Diagnostics Lightning exposure of Carbon Fiber Composites in wind turbine blades Søren Find Madsen, Lisa Carloni Global-Lightning Protection

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES Electrical Manholes and Handholes UNIVERSITY OF MISSOURI

CONSULTANT PROCEDURES & DESIGN GUIDELINES Electrical Manholes and Handholes UNIVERSITY OF MISSOURI GENERAL: The scope of this document is to provide instruction for the installation of concrete electric manholes. DESIGN GUIDELINES: 1. Materials for Manhole 1.1. Cast-in-Place or Pre-Cast concrete may

More information

White Paper SV62/E/0712. General instructions on lightning safety for shelters.

White Paper SV62/E/0712. General instructions on lightning safety for shelters. www.dehn.de ty due to a lack or insufficient number of lightning-proof-shelters or their insufficient equipment, for example by a relevant notice or a written agreement on limitation of liability, shall

More information

Substation Grounding. Presented by: Bruce Kayser, PE Assisted by Danny Seele

Substation Grounding. Presented by: Bruce Kayser, PE Assisted by Danny Seele Substation Grounding Presented by: Bruce Kayser, PE 785-633-5756 Assisted by Danny Seele Introduction Bruce Kayser, PE BSEE from KSU in 1989 Licensed Professional Engineer in KS Employed by ElectriComm,

More information

The Equipotential Plane in New Livestock Facilities

The Equipotential Plane in New Livestock Facilities The Equipotential Plane in New Livestock Facilities Keith G. Tinsey, P.E., Truman C. Surbrook P.E. and Jonathan R. Althouse Agricultural Engineering Department Michigan State University Introduction An

More information

Installation of CSST Gas Piping Systems

Installation of CSST Gas Piping Systems (What Inspectors Need To Know) May 2016 Conventional Arc-Resistant CSST Product Standard National Standard ANSI LC-1 Performance-based standard Listed system installed in accordance with manufacturer s

More information

Part E robustdetails. robustdetails. January 2017 Update Pack. Dear Colleague,

Part E robustdetails. robustdetails. January 2017 Update Pack. Dear Colleague, Part E Pack Dear Colleague, This is the first 2017 update to the Part E Robust Details Handbook. In this update pack, we have focussed on clarifying the situation on incorporating underfloor heating (UFH)

More information

ELECTRIC METERING GENERAL

ELECTRIC METERING GENERAL 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 EQUIPMENT 5.0 METER REQUIREMENTS 6.0 METER FACILITIES 7.0 ELECTRICAL CONNECTIONS 2.0 SCOPE This guide covers general requirements and codes for

More information

ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings

ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings Building Safety Department 400-2 nd Street South St. Cloud, MN 56301 (320) 255-7239 A building permit is required for any accessory

More information

PRY-MOULD. High Voltage Accessories for Extruded Cables

PRY-MOULD. High Voltage Accessories for Extruded Cables PRY-MOULD High Voltage Accessories for Extruded Cables Linking the future As the worldwide leader in the cable industry, Prysmian Group believes in the effective, efficient and sustainable supply of energy

More information

GUIDE TO SUPPLY AND METERING ARRANGEMENT ON CUSTOMER S INTERNAL DISTRIBUTION SYSTEM

GUIDE TO SUPPLY AND METERING ARRANGEMENT ON CUSTOMER S INTERNAL DISTRIBUTION SYSTEM GUIDE TO SUPPLY AND METERING ARRANGEMENT ON CUSTOMER S INTERNAL DISTRIBUTION SYSTEM CLP POWER HONG KONG LIMITED DATE REVISED: Nov 2016 Version 7 11/16 Guide to Supply and Metering Arrangement on Customer

More information

St. Clair County Electrical Code Regulations

St. Clair County Electrical Code Regulations St. Clair County Electrical Code Regulations St. Clair County has adopted the 2011 National Electrical Code as amended with the following listed articles as the St. Clair County version of the National

More information

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR PART 1 - GENERAL Section 26 05 15 SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR 1.1 Cable shall be 15 kv, shielded, three conductor with ground, stranded copper, with continuously welded and corrugated

More information

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE ONTARIO PROVINCIAL STANDARD SPECIFICATION OPSS.PROV 604 NOVEMBER 2017 CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE. See Chapter 3, Section 3.01 for more information about point of entrance (POE).

OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE. See Chapter 3, Section 3.01 for more information about point of entrance (POE). 6.01 GENERAL OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE See Chapter 3, Section 3.01 for more information about point of entrance (POE). In all cases, the customer installs, owns, and maintains the

More information

These Electricity Safety Rules and associated National Safety Instructions are written to safeguard personnel working for or on behalf of National

These Electricity Safety Rules and associated National Safety Instructions are written to safeguard personnel working for or on behalf of National These Electricity Safety Rules and associated National Safety Instructions are written to safeguard personnel working for or on behalf of National Grid, on or near to its electricity apparatus. National

More information

1. Approved Manufacturers: Carlon Electrical Products, Cantex, or approved equal.

1. Approved Manufacturers: Carlon Electrical Products, Cantex, or approved equal. PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of Texas State University for for Electrical System. B. Texas State University recognizes

More information

SECTION P -- CABLE VAULT AND CABLE ENTRANCE FACILITY

SECTION P -- CABLE VAULT AND CABLE ENTRANCE FACILITY INSTLLTION REQUIREMENTS Section P, TT-TP-76300 T&T January 2012 Revised July, 2012 SECTION P -- CLE VULT ND CLE ENTRNCE FCILITY CONTENTS PGE 1. GENERL... P-1 1.1. Introduction... P-1 1.2. Non-Insulating

More information

DOMESTIC ELECTRICAL INSTALLATION PERIODIC INSPECTION REPORT (FOR A SINGLE DWELLING) B ADDRESS AND DETAILS OF THE INSTALLATION Address: SPECIMEN

DOMESTIC ELECTRICAL INSTALLATION PERIODIC INSPECTION REPORT (FOR A SINGLE DWELLING) B ADDRESS AND DETAILS OF THE INSTALLATION Address: SPECIMEN A DETAILS OF THE CLIENT Client / Address: C PURPOSE OF THE REPORT Purpose for which this report is required: E PARTICULARS OF THE CONTRACTOR Trading Title: Address: DOMESTIC ELECTRICAL INSTALLATION PERIODIC

More information

CONDUITS AND FITTINGS

CONDUITS AND FITTINGS CONDUIT AND FITTINGS Rigid Steel Conduit 3801 Rigid PVC Conduit 3803 HDPE Conduit 3803 Flexible Non Metallic Liquid Tight Conduit Type LFNC-B 3804 PVC Coated Urethane Lined Galvanized Rigid Steel Conduit

More information

INSTALLATION AND TESTING PROCEDURES FOR ERM LEAK DETECTION

INSTALLATION AND TESTING PROCEDURES FOR ERM LEAK DETECTION 14.601 Materials & Equipment MATERIALS: 1. Teflon Coated Insulated Wire with Crimps 2. Shop Rags 3. Standard ANALOG Ohmmeter INSTALLATION AND TESTING PROCEDURES FOR ERM 4. Wire Crimping and Stripping Tool

More information

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999 CANADIAN ELECTRICAL CODE 1 The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999 Repealed by Chapter E-6.3 Reg 8 (effective June 24, 2003). Formerly Chapter E-6.3 Reg 6 (effective March

More information

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD. ANSI/SCTE (Formerly IPS SP 100)

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD. ANSI/SCTE (Formerly IPS SP 100) ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 15 2006 (Formerly IPS SP 100) Specification for Trunk, Feeder and Distribution Coaxial Cable NOTICE The Society

More information

Trench Duct Class Catalog 5230CT9601R10/08

Trench Duct Class Catalog 5230CT9601R10/08 5230CT9601R10/08 2009 Class 5230 CONTENTS Application.................................................5 Unassembled Trench Duct Components.........................6 Factory Assembled Trench Duct..............................11

More information

Effective June, Eaton-Durham Model # UTRS223ACH. Siemens, Model # SUAS877-PG. (or Landis & Gyr # UAS877-PG) Milbank. Model # U1980-O.

Effective June, Eaton-Durham Model # UTRS223ACH. Siemens, Model # SUAS877-PG. (or Landis & Gyr # UAS877-PG) Milbank. Model # U1980-O. Siemens, Model # SUAS877-PG (or Landis & Gyr # UAS877-PG) Eaton-Durham Model # UTRS223ACH Milbank Midwest Model # U980-O UTRS223AMEP These are some examples of the single meter sockets we require for underground

More information

ROOF MOUNT KIT OWNERS MANUAL

ROOF MOUNT KIT OWNERS MANUAL ROOF MOUNT KIT OWNERS MANUAL Made in the USA by: Primus Wind Power, Inc. 938 Quail St. Lakewood, CO 80215 Phone: (303) 242-5820 www.primuswindpower.com AIR is a trademark of Primus Wind Power, Inc. ROOF

More information

NPS/003/033 Technical Specification for Substation Support Structures

NPS/003/033 Technical Specification for Substation Support Structures Version:- 2.0 Date of Issue:- April 2015 Page 1 of 21 NPS/003/033 Technical Specification for Substation Support Structures 1. Purpose The purpose of this document is to specify the technical requirements

More information

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection SECTION 13090 RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13090-1 LOW INTENSITY RADIATION PROTECTION

More information

3.0) TRANSMISSION LINES MINIMUM REQUIRED STANDARDS LINES

3.0) TRANSMISSION LINES MINIMUM REQUIRED STANDARDS LINES 3.0) TRANSMISSION LINES MINIMUM REQUIRED STANDARDS LINES 3.2 Underground Lines [below sections will be renumbered at a later date] 5.0 GENERAL REQUIREMENTS 5.1 Underground transmission lines 69 kv and

More information

TEMPORARY METER POLE INSTALLATION

TEMPORARY METER POLE INSTALLATION TEMPARY METER POLE INSTALLATION MEMBER PROVIDED Location to be made by REMC within 50' of our transformer or existing service Temporary pole to be properly braced 24" 3 wire weatherhead (located 24" from

More information

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES CEB STANDARD 030-1 : 1996 Specification for RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES CEYLON ELECTRICITY BOARD SRI LANKA Specification for RESIN FILLING TYPE JOINTING KITS FOR

More information

FREQUENTLY ASKED QUESTIONS

FREQUENTLY ASKED QUESTIONS March 2010 FREQUENTLY ASKED QUESTIONS Wiring Rules The new edition of the Australian/New Zealand Standard for Wiring Rules (AS/NZS 3000:2007) was released in November 2007 and revised by Amendment 1 in

More information

Installation plan. Tumble dryer. PT 8807 EL (Electrically heated) en - US Mat. NR / 02

Installation plan. Tumble dryer. PT 8807 EL (Electrically heated) en - US Mat. NR / 02 Installation plan Tumble dryer PT 8807 EL (Electrically heated) 38.15 en - US Mat. NR. 09 883 210 / 02 U.S.A. Miele, Inc. National Headquarters 9 Independence Way Princeton, NJ 08540 Phone: Fax: 800-991-9380

More information

Douglas County Traffic Signal Installation Guidelines (January 2013)

Douglas County Traffic Signal Installation Guidelines (January 2013) Douglas County Traffic Signal Installation Guidelines (January 2013) The following guidelines are minimum requirements for equipment installation. Section A. Poles and Foundations ( Wood, Concrete, Mast

More information

Details of technical leaflets/write-up on various pieces of equipment.

Details of technical leaflets/write-up on various pieces of equipment. Details of technical leaflets/write-up on various pieces of equipment. (1) Insulator Designs: The insulators are provided in one, two, three, or four insulator designs per location and spaced to provide

More information

Rise of Earth Potential at Electricity Stations

Rise of Earth Potential at Electricity Stations ISIS practice For BT People TEPT/PPS/B012T Issue 7, 7-Dec-2007 Published by Openreach, NCAD Rise of Earth Potential at Electricity Stations About this document... About this document... Author The author

More information

SECTION 1101 TRAFFIC SIGNALS AND APPURTENANCES END OF SECTION

SECTION 1101 TRAFFIC SIGNALS AND APPURTENANCES END OF SECTION SECTION 1101 SIGNALS AND APPURTENANCES PART 1 GENERAL 1.4 SUBMITTALS E. Submit warranty for all supplied material and workmanship for a period of two years from final acceptance. The warranty must state

More information

Revision 1 RAM ELEVATORS. Elevator Electrical Planning Guide. RAM Manufacturing Ltd

Revision 1 RAM ELEVATORS. Elevator Electrical Planning Guide. RAM Manufacturing Ltd RAM ELEVATORS Elevator Electrical Planning Guide This guide is intended for people with an understanding of electricity. If you are not, please consult a licensed electrician as errors in application of

More information

AC Corrosion and Mitigation. Mike Ames Director Technical Operations Chapman Engineering Oct 20/21, 2015 KCC Pipeline Safety Seminar Manhattan, KS

AC Corrosion and Mitigation. Mike Ames Director Technical Operations Chapman Engineering Oct 20/21, 2015 KCC Pipeline Safety Seminar Manhattan, KS AC Corrosion and Mitigation Mike Ames Director Technical Operations Chapman Engineering Oct 20/21, 2015 KCC Pipeline Safety Seminar Manhattan, KS NACE SP0177-2007 The initial publication of the standard,

More information

Soil Resistivity Data Computations; Single and Two - Layer Soil Resistivity Structure and Its Implication on Earthing Design

Soil Resistivity Data Computations; Single and Two - Layer Soil Resistivity Structure and Its Implication on Earthing Design Vol:7, No:, 3 Soil Resistivity Data Computations; Single and Two - Layer Soil Resistivity Structure and Its Implication on Earthing Design M. Nassereddine, J. Rizk, and G. Nasserddine International Science

More information

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES Guidelines effective March 5, 2007 NES is committed to providing safe, reliable electric service at a reasonable price for all of our customers. These guidelines offer direction for activities relating

More information

MEDIUM VOLTAGE XLPE INSULATED POWER CABLES [6.35/11kV Copper XLPE Three-Core HDPE Sheathed]

MEDIUM VOLTAGE XLPE INSULATED POWER CABLES [6.35/11kV Copper XLPE Three-Core HDPE Sheathed] [6.35/11kV Copper XLPE Three-Core HDPE Sheathed] APPLICATION Mostly used as feeder electric cable for power distribution network such as power supply station, substation, switching system etc. They are

More information

nbn Lead-in Trenching Requirements

nbn Lead-in Trenching Requirements nbn Lead-in Trenching Requirements Engineering Document number F0002-31-11578 Document category Guide Author Engineering Status Approved Issue date 15 JULY 2016 Revision number 2.1 Classification Public

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 6/15/16 Updated division section from 16124 to 2605 - mgl44 13, removed references to other section 10/17/14

More information