Recent interpretations Plumbing Code

Size: px
Start display at page:

Download "Recent interpretations Plumbing Code"

Transcription

1 Recent interpretations 2012 Plumbing Code

2 Content This course is designed to provide two hours of credit for continuing education requirements for building inspectors and contractors. The course consists of interpretations that have been made by NCDOI and are provided to illustrate the position of NCDOI on these issues. The interpretations were made on a case by case basis but provide guidance and insight as to the department s position on these issues.

3 Solvent Cement Is ABS to PVC solvent cement as found in the local building supply store allowed to be used to joining PVC and ABS plastic pipes? No. Solvent joints between dissimilar plastics is prohibited Prohibited joints. The following types of joints and connections shall be prohibited: 4. Solvent-cement joints between different types of plastic pipe.

4 Sleeves The contractor has used a long sweep to turn up from under a slab into the wall. Does this require a sleeve per section 305.5? The building is on a slab with a block foundation with cap block.

5 Sleeves Pipes through or under footings or foundation walls. Any pipe that passes within 12 inches (305 mm) under a footing or through a foundation wall shall be provided with a relieving arch, or a pipe sleeve pipe shall be built into the foundation wall. The sleeve shall be two pipe sizes greater than the pipe passing through the wall. Piping shall not be run under pier footing (refer to Section 307).

6 Sleeves No. section refers to pipes passing through a foundation wall or through a foundation where differential settlement of the building and the surrounding soil may shear or damage the pipe. This piping is under the building slab, passing through the slab up through the block where the slab will prevent the shearing action. `

7 Dead ends In a retrofit job they removed the kitchen and kitchen floor drain. Do they have to remove the 20 feet of drain line abandoned under the concrete slab? Yes, the line should be removed and capped. Section prohibits dead ends Dead ends. In the installation or removal of any part of a drainage system, dead ends shall be prohibited. Cleanout extensions and approved future fixture drainage piping shall not be considered as dead ends.

8 Dead ends What is the definition of a dead end? DEAD END. A branch leading from a soil, waste or vent pipe; a building drain; or a building sewer, and terminating at a developed length of 2 feet (610 mm) or more by means of a plug, cap or other closed fitting.

9 Toilet Rooms The city has a fire station being converted to a recreational building. Occupant load is 93. Occupancy type is A3. How many toilets are required? Using A3 for general use male toilet requirements are 1 per 125 and the female are 1 per 65. Therefore only one toilet is required in either the male or female toilet room. Two toilet rooms are required. Both can be labeled unisex.

10 Toilet Rooms The city has a fire station being converted to a recreational building. Occupant load is 93. Occupancy type is A3. Does the disproportionality clause for accessibility apply? Disproportionality does not apply as this is new construction due to the change of occupancy. Both of the required toilet rooms are required to be accessible since the requirement is for each use (i.e. for each sex) even though they are both labeled as unisex.

11 Toilet Rooms This plan would allow us to do male and female ADA compliant toilets within the square footage we have in the existing building for a renovation project with limited floor space. I have checked with our local Health Dept. and they do not have a problem with this plan. I have not found a code reference that speaks to this issue with the lavatory not in the toilet room. One lavatory will serve our occupancy count of 75. What is your opinion?

12 Toilet Rooms NC Plumbing Code Section requires the lavatory to be in the same room as the plumbing fixture. The only exception is for elementary schools for the teacher to observe the students washing their hands from the corridor Public lavatories. In employee and public toilet rooms, the required lavatory shall be located in the same room as the required water closet, except in Education K-5, lavatories may be provided in a common toilet room vestibule, visible from the corridor.

13 Toilet Rooms Is there an exception to permitting a small business to not allow public in their restrooms? This was brought up recently and I cannot find anything in writing confirming it.

14 Toilet Rooms The code requires that the public facilities be available but it does not force the business to allow the public to use them. Public toilets are for those that are customers, patrons or visitors of the business that are there for purposes congruent with the function of the business, i.e., shopping, buying a meal, banking, etc Public facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization.

15 Toilet Rooms The inspector is requiring that I caulk the space between the wall and my pedestal sink. Is this required? If the pedestal sink is mounted in contact with the wall, the sink should be sealed to the wall per section Water-tight joints. Joints formed where fixtures come in contact with walls or floors shall be sealed.

16 Swimming Pools Based on North Carolina's pool code, if the units are within 300' from the pool, and the pool is going to be used only by residents and their guests, we would not need to provide plumbing fixtures for the pool deck (See image below). I have calculated the farthest apartment to be about 240' feet horizontally from the pool and 34' vertically for a total of 275'. See the attached pdf showing the travel path used. Is it your understanding that we would then be exempt from providing additional plumbing fixtures?

17 Swimming Pools

18 Swimming Pools We don t enforce the swimming pool rules of the Environmental Health Section of DEQ. Those are separate requirements. We use the occupant load taken from table of the building code for the pool and pool deck. Use A3 for the fixture count calculation for the pool and pool deck. Note that there was an amendment for swimming pools and apartments toilet fixture count in the cumulative amendments where dwelling units within 500 feet are exempt.

19 Swimming Pools Minutes of the North Carolina Building Code Council June 10, 2014 Item D 2 Request by Ken Szymanski, with the Apartment Association of North Carolina, to amend the 2012 NC Building Code, Section The proposed amendment is as follows: Fixture calculations... Exceptions: 2. In buildings that contain dwellings or sleeping units that have a pool dedicated to the residents, a percentage reduction of the total required fixtures provided for a pool & pool deck without bleachers and grandstands may be taken equal to the percentage of total residential units whose entries fall within 500 feet walking distance of the pool deck. Motion/Second/Adopted with an effective date of January 1, 2015.

20 Swimming Pools [P] Minimum number of fixtures. In new construction or building additions and in changes of occupancy as defined in the North Carolina Building Code, plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table Types of occupancies not shown in Table shall be considered individually by the building official. The number of occupants shall be determined by this code. Occupancy classification shall be determined in accordance with Chapter 3.

21 Swimming Pools Assembly Group A. Assembly Group A occupancy includes, among others, the use of a building or structure, or a portion thereof, for the gathering of persons for purposes such as civic, social or religious functions; recreation, food or drink consumption or awaiting transportation.

22 Swimming Pools A-3 Assembly uses intended for worship, recreation or amusement and other assembly uses not classified elsewhere in Group A including, but not limited to: indoor swimming pools (without spectator seating)

23 Swimming Pools A-5 Assembly uses intended for participation in or viewing outdoor activities including, but not limited to: Amusement park structures Bleachers Grandstands Stadiums

24 Swimming Pools Fixture calculations. To determine the occupant load of each sex, the total occupant load shall be divided in half. To determine the required number of fixtures, the fixture ratio or ratios for each fixture type shall be applied to the occupant load of each sex in accordance with Table Fractional numbers resulting from applying the fixture ratios of Table shall be rounded up to the next whole number..

25 Swimming Pools Exceptions: 1. The total occupant load shall not be required to be divided in half where approved statistical data indicate a distribution of the sexes of other than 50 percent of each sex.

26 Swimming Pools Exceptions: 2. In buildings that contain dwellings or sleeping units that have a pool dedicated to the residents, a percentage reduction of the total required fixtures provided for a pool and pool deck without bleachers and grandstands may be taken equal to the percentage of total residential units whose entries fall within 500 feet of the pool deck.

27 Swimming Pools Code Change Proposal In buildings that contain dwellings or sleeping units that have a pool dedicated to the residents, a percentage reduction of the total required fixtures provided for a pool and pool deck without bleachers and grandstands may be taken equal to the percentage of total residential units whose entries fall within a 500 feet foot horizontal travel distance of the pool deck

28 Swimming Pools Code Change Proposal In multi-story structures, the residential units located not more than one story above or below the pool and pool deck may be included in the percentage. Travel from the pool to the require toilet facilities shall be on an accessible route.

29 Swimming Pools Recent NCBC Code Change The amended language to NCBC (below) is applicable to any Group R-2 or R-3 occupancy, including apartment buildings, condominiums, townhomes, or single family developments which reads: Exception: Pools for single or multiple Group R-2 and Group R-3 occupancy buildings intended for residents only.

30 Swimming Pools Recent NCBC Code Change Correct application of the new exception is dependent on the pool in question not being considered a public accommodation. There are several situations where a pool used only by the residents may be considered a public accommodation and would have to be designed to be accessible per ANSI 1109.

31 Swimming Pools Recent NCBC Code Change 1. Prior to rental of all the apartments, the pool sells memberships to adjacent neighborhoods. 2. Apartment dwellers may rent the pool to be used for parties or events where people from outside the apartment building attend. 3. Classes are held in the pool with participants from outside the apartment building who have paid to attend the class.

32 Swimming Pools DECK AREA 5000 SF/15 = 334 Total occupant load = 358/2 = 179 POOL AREA 1200 SF/50 = RESIDENTS WITHIN THE 500 FT RADIUS PERCENTAGE REDUCTION = 300/1200 = 25% 900 RESIDENTS OUTSIDE OF THE 500 FOOT RADIUS

33 Swimming Pools REDUCTION = number of residents outside of 500 ft radius divided by total number of residents served REDUCTION = 300/( ) = 0.25 If there are no residents outside of the 500 foot radius from the pool there are no fixtures required. The residents will use the toilets in their living space. In other words 300/300 = 100% reduction.

34 Swimming Pools Apartment complex or hotel (one level or multi-level under current rules) 179/65 = = three female toilets 179/125 = 1.39 = two male toilets 179/200 = = one lavatory for each sex 358/500 = = one Hi/Lo drinking fountain Deduct 25% for those within the 500 foot radius 100% - 25% = 75% 179 / 65 * 0.75 = 2.07 = three female toilets 179 / 125 * 0.75 = = two male toilets one lavatory for each sex one Hi/Lo drinking fountain

35 Swimming Pools Apartment complex or hotel 5 story with pool on first floor All residents within 500 feet walking distance of the pool 150 residents per floor Under current code language no additional fixtures are required for the pool since all units are within the 500 foot horizontal travel distance as interpreted by NCDOI. Under the proposed change the top 3 stories are required to have plumbing fixtures so 450 / 750 = 60% of the required fixtures based on the occupant load of the pool and pool deck will be required to be installed at the pool deck.

36 Finding NCDOI interpretations and guidelines on the NCDOI website.

37

38

39

40

41 Private Drinking Water Wells Guidance Paper: Inspection of Well Systems Code: 2012 NC Administrative Code and Policies Date: 09/26/2017 Section: N.C. Gen. Stat and (b17) (2) Question #1: Who is responsible for the inspection of a private drinking water well system from the well head to the outlet of the well pressure tank?

42 Private Drinking Water Wells Opinion: The local health department is responsible for the inspection of a private drinking water well system from the well head to the outlet of the well pressure tank. Session Law (Senate Bill 131) and the subsequent revision to N.C. Gen. Stat for well drillers state that the local health department has the sole authority for the permitting and inspection of well systems described by N.C. Gen. Stat (b17) (2).

43 Private Drinking Water Wells Subsection (b17) (2) defines the well system as the well, the pressure tank, the pressure switch, and all plumbing and electrical equipment in the well and between the well, pressure tank, and pressure switch and does not require a permit for work that does not exceed connecting the well system to the plumbing and electrical systems of the structure(s) being served by the well.

44 Private Drinking Water Wells Important Notes: 1. N.C. Gen. Stat and (b17) (2) shall not be deemed to eliminate the well system from complying with the plumbing or electrical codes. 2. N.C. Gen. Stat and (b17) (2) does not prohibit a local health department from obtaining the services from another agency, such as a local inspections department, for performing the inspections required by N.C. Gen. Stat

45 Private Drinking Water Wells Important Notes: 3. Though not mandated, the Engineering Division for the North Carolina Department of Insurance recommends that each local jurisdiction should establish a written procedure to address this matter so that all parties are aware of the local procedure at the time of permitting. The guidance and opinions contained herein are not legal advice and may not necessarily reflect the most current statutory or code language.

46 Private Drinking Water Wells

47 Private Drinking Water Wells

48 Private Drinking Water Wells General standards and requirements. Private drinking water wells (i) with a designed capacity of 100,000 gallons per day or greater or (ii) that are to be constructed in a geographical area where the Environmental Management Commission has found that prior permission is necessary shall be subject to permitting and inspection by the Environmental Management Commission and shall not be subject to permitting and inspection by a local health department. All other private drinking water wells shall be subject to permitting and inspection by the local health department as provided in G.S

49 Private Drinking Water Wells

50 Private Drinking Water Wells References: Permitting, inspection, and testing of private drinking water wells. (a) Mandatory Local Well Programs. Each county, through the local health department that serves the county, shall implement a private drinking water well permitting, inspection, and testing program. The local health department shall be the exclusive authority for the permitting of wells and well systems as described in G.S (b17) (2).

51 Private Drinking Water Wells References: Local health departments shall administer the program and enforce the minimum well construction, permitting, inspection, repair, and testing requirements set out in this Article and rules adopted pursuant to this Article. No person shall unduly delay or refuse to permit a well that can be constructed or repaired and operated in compliance with the requirements set out in this Article and rules adopted pursuant to this Article.

52 Private Drinking Water Wells (a) Use of Standard Forms. Local well programs shall use the standard forms created by the Department for all required submittals and shall not create their own forms. (b) Permit Required. Except for those wells required to be permitted by the Environmental Management Commission pursuant to G.S , no person shall: 1) Construct or assist in the construction of a private drinking water well unless a construction permit has been obtained from the local health department.

53 Private Drinking Water Wells 2) Repair or assist in the repair of a private drinking water well unless a repair permit has been obtained from the local health department, except that a permit shall not be required for the repair or replacement of a pump or tank. (b1) When a permit is issued under this section, the local health department shall be responsible for notifying the appropriate building inspector of the issuance of the well permit. The appropriate building inspector may request from the local health department the opportunity to inspect the activities authorized by the permit.

54 Private Drinking Water Wells The inspection must be performed prior to the final inspection performed by the local health department, and the well contractor shall not be required to be onsite for the inspection by the building inspector.

55 Private Drinking Water Wells If an inspection by a building inspector after the final inspection has been performed by the local health department is determined to be necessary for the protection of public health, safety, or welfare, the local building inspections department shall be responsible for (i) the additional costs for the inspection and related activities necessary for the inspection and (ii) any damages to the well system caused during the inspection.

56 Private Drinking Water Wells (b2) Permit to Include Authorization for Piping and Electrical. A permit issued under this section shall also be deemed to include authorization for all of the following: (1) The installation, construction, maintenance, or repair of electrical wiring, devices, appliances, or equipment by a person certified as a well contractor under Article 7A of this Chapter when running electrical wires from the well pump to the pressure switch.

57 Private Drinking Water Wells 2) The installation, construction, maintenance, or repair of water pipes by a person certified as a well contractor under Article 7A of this Chapter when running water pipes from the well to the water tank.

58 Private Drinking Water Wells 3) The installation of both water pipes and electrical wiring in a single ditch by a person certified as a well contractor under Article 7A of this Chapter when running electrical wires from the well pump to the pressure switch and water pipes from the well to the water tank. The ditch shall be as deep as the minimum cover requirements for either electrical wiring or water pipes, whichever is greater.

59 Private Drinking Water Wells This subsection shall not be interpreted to prohibit any person licensed by an independent occupational licensing board from performing any authorized services within the scope of practice of the person's license." Well contractor certification required; exemptions. Certification Required. No person shall perform, manage, or supervise any well contractor activity without being certified under this Article.

60 Private Drinking Water Wells (b) Exempt persons and activities. This Article does not apply to any of the following persons or activities: (13) A person who is licensed as a plumbing contractor under Article 2 of Chapter 87 of the General Statutes who installs pumps or pumping equipment; installs, breaks, or reinstalls a well seal in accordance with G.S (6); or disinfects a well incident to the installation, alteration, or replacement of pumps or pumping equipment within or near a well.

61 Private Drinking Water Wells However, the plumbing contractor shall maintain documentation of having attended a continuing education course that covered well seal installation, protection, and sanitation within the last two years prior to the work being performed... The licensed plumbing contractor shall remain on-site while the work is being performed until the well is disinfected and sealed.

62 Private Drinking Water Wells North Carolina State Building Code. (b17) Exclusion for Private Drinking Water Well Installation, Construction, Maintenance, and Repair.

63 Private Drinking Water Wells No permit shall be required under the Code or any local variant approved under subsection (e) of this section for the electrical and plumbing activities associated with the installation, construction, maintenance, or repair of a private drinking water well when all of the following apply: 1) The work is performed by a contractor certified under Article 7A of Chapter 87 of the General Statutes under the terms of a permit issued by the local health department pursuant to G.S

64 Private Drinking Water Wells 2) The scope of work includes only the connection or disconnection of a well system to either the plumbing served by the well system or the electrical service that serves the well system. For purposes of this subsection, a well system includes the well, the pressure tank, the pressure switch, and all plumbing and electrical equipment in the well and between the well, pressure tank, and pressure switch.

65 Occupancy Type We are working on a doctor's office and I have a question about determining the plumbing fixture count. The office is right at 10,000 square feet. The majority of the office is a Business occupancy however, I figured the occupancy of the lobby, break room, and a small group room as an assembly A- 3 occupancy, not business. By doing that it increases the occupancy count by almost 50 people and therefore increases the toilet count from 4 to 6. Do I need to consider the three spaces I listed above as A-3 or can they be considered Business?

66

67

68 Occupancy Type Calculating the number of plumbing fixtures is done using egress loads based on occupancy loadings from table of the building code for the use of each space. Calculations for each use are done separately and the fractional numbers of fixtures determined are summed and rounded up to the next whole integer number of fixtures as per section of the plumbing code.

69 Occupancy Type Minimum number of fixtures. In new construction or building additions and in changes of occupancy as defined in the North Carolina Building Code, plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table Types of occupancies not shown in Table shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code.

70 Occupancy Type Fixture calculations. To determine the occupant load of each sex, the total occupant load shall be divided in half. To determine the required number of fixtures, the fixture ratio or ratios for each fixture type shall be applied to the occupant load of each sex in accordance with Table Fractional numbers resulting from applying the fixture ratios of Table shall be rounded up to the next whole number.

71 Occupancy Type Fixture calculations For calculations involving multiple occupancies, such fractional numbers for each occupancy shall first be summed and then rounded up to the next whole number. Exception: The total occupant load shall not be required to be divided in half where approved statistical data indicates a distribution of the sexes of other than 50 percent of each sex.

72 Lavatories I am sending a small gas station adaptive re-use project that I need some clarification on in regard to the toilet room designs. Basically, the original small gas station allows for 4 individual water closets with shared lavatories. Please advise on the design as it is currently shown, with 2 women s and 2 men s water closets with shared lavatories.

73

74 Lavatories Section of the 2012 NC Plumbing Code requires the required lavatory to be in the same room as the required water closet Public lavatories. In employee and public toilet rooms, the required lavatory shall be located in the same room as the required water closet, except in Education K-5, lavatories may be provided in a common toilet room vestibule, visible from the corridor.

75 Lavatories The plumbing code requires separate male and female toilet rooms unless the unisex toilet room requirements are met in section This design does not meet that requirement Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex.

76 Lavatories Exceptions: 1. Separate facilities shall not be required for dwelling units and sleeping units. 2. Separate facilities shall not be required in structures or tenant spaces with a total occupant load, including both employees and customers, of 25 or less. 3. Separate facilities shall not be required in mercantile occupancies in which the maximum occupant load is 100 or less.

77 Lavatories Exceptions: 4. Except as provided in Section Where the code requires only one toilet facility for each sex, two unisex facilities may be substituted for separate sex facilities. The delayed effective date of this Rule is January 1, The Statutory authority for Rule-making is G. S ;

78 Lavatories This design does not meet the requirements for a unisex toilet room in that there are multiple fixtures in the same room and no lockable door which is a gang toilet room situation.

79 Single User Toilets I have a question in regard to the requirement for water closet compartments (NCPC 310.4) in toilet rooms. In a single user toilet room that also serves as a locker room for staff at an automobile dealership, would a toilet compartment be required? The door to the area is lockable, so if it is being used as a toilet room, it could be locked. However, I am not clear if the room would be considered a single user room if the lockers are also located in the room.

80 Single User Toilets As long as the door is lockable and there is no other access to the toilet room it can be considered as a single user toilet room.

81 Practical Difficulties What are the practical difficulties in enforcing the plumbing code to the point where the code official can use alternative methods of construction? Practical difficulties arise when the code requirements cannot be met in a practical manner. Each situation is different and must be evaluated by the inspector on a case by case basis.

82 Water Heater Pans Concerning plumbing for the required Pan for water heaters, I see PVC pans being used for tankless water heater installations. Has the Code requirement been relaxed for tankless to allow a PVC pan? My interpretation is that the pan needs to be a metal pan unless this is an electric water heater per the exception to section of the 2012 NC plumbing code.

83 Water Heater Pans Required pan. Where water heaters or hotwater storage tanks are installed in: (a) remote locations such as a suspended ceiling, (b) attics, (c) above occupied spaces, or (d) unventilated crawl spaces, the tank or water heater shall be installed in a galvanized steel pan having a material thickness of not less than inch ( mm) (No. 24 gage), or other pans approved for such use. Exceptions: 1. Electric water heaters may rest in a high-impact plastic pan of at least 1/16 inch (1.6 mm) thickness. 2. Water heater mounted on concrete floor for with floor drains.

84 OSHA standard Is the OSHA Standard for F1 and F2 occupancies as shown in Table of the 2012 NCPC a misprint and should it be calculated as 1 per 100, and retaining the old information for drinking fountains? The misprint was that they used the wrong OSHA document number. The 1 per 100 was used from the prior code cycle for lavatories since that is not described in the OSHA document.

85 Toilet Fixtures This farm equipment business is constructing a new building behind their business. The new structure is to be used for the servicing of farm equipment with one bay on the end being used to temporarily store the equipment they have finished working on prior to pickup by the customer. They do not want to put a toilet in the new building since the existing business is within 200 feet of the new building. Will they have to install a toilet room in the new building per the plumbing code requirements?

86

87

88 1500 SF Storage 5500 SF Repair Garage

89 Toilet Fixtures If the submitter would request an adjustment in occupant content per Section 403.3, this proposed building would be qualify for this adjustment provided all proper documentation. Provided the documentation meets the requirement of Section Exception # 2 Separate facilities shall not be required in structures or tenant spaces with a total occupancy load including both employees and customers, of 25 or less. it would allow a single facility within the proposed building.

90 Toilet Fixtures The code section the submitter is referencing is Section Location of employee toilet facilities in occupancies other than assembly or mercantile. Access to toilet facilities in occupancies other than mercantile and assembly occupancies shall be from within the employees working area. Employee facilities shall be either separate facilities or combined employee and public facilities. Exception: facilities that are required for employees in storage structures or kiosks, and are located in adjacent structures under the same ownership, lease, or control, shall be a maximum travel distance of 500 feet (152m) from the employees working area.

91 Toilet Fixtures This building is neither a kiosk or storage structure and a toilet room will be required for the employees. Therefore if the submitter request the use of Section 403.3, documentation is provided, and the code official approves the adjustment, then the submitter would only require a single facility with a single water closet, a single lavatory, and a Hi-Lo water fountain. If the submitter would use an S-1 occupancy for motor vehicle repair garage instead of F-1, the drinking fountain would not be required and the occupancy calculations are simplified since the OSHA regulation is not invoked.

92 Toilets in Doctor s Offices Doctor s offices typically have multiple toilet rooms of one toilet and lavatory scattered through the facility. Can these toilet rooms all be unisex or do they have to be half labeled as male and half labeled as female? Section allows toilet rooms to be labeled as unisex if there is one female and one male toilet room with one toilet each. It is reasonable to allow single seat toilet rooms with lockable doors to be labeled unisex in this instance as long as the required number of fixtures are supplied.

93 Force Mains Section of the NC Plumbing Code indicates that the discharge from a pump be located 10 feet from a fixture drain. At what point does the forced main stop and the sanitary sewer start? Does the vertical distance count towards the 10 feet?

94 Force Mains The force main must connect to the building drain at least 10 feet away from any fixture drain, soil or waste stack connecting to the building drain. The schematic as shown is not acceptable. The measurement is taken along the building drain which is horizontal.

95 Appliance Protection We typically see pipe bollards installed in front of water heaters in garages. We have a contractor wanting to use a curb stop like you would see in a parking lot. Does that meet the intent of the code?

96 Appliance Protection Water heaters installed in garages. Water heaters having an ignition source shall be elevated such that the source of ignition is not less than 18 inches (457 mm) above the garage floor. Appliances shall be located or protected so that they are not subject to physical damage by a moving vehicle. Exception: Elevation of the ignition source is not required for appliances that are listed as flammable vapor ignition resistant.

97 Appliance Protection Elevation and protection. Elevation of water heater ignition sources and mechanical damage protection requirements for water heaters shall be in accordance with the International Mechanical Code and the International Fuel Gas Code. Mechanical Code Protection from damage. Appliances shall not be installed in a location where subject to mechanical damage unless protected by approved barriers.

98 Appliance Protection Mechanical Code Private garages. Appliances located in private garages and carports shall be installed with a minimum clearance of 6 feet (1829 mm) above the floor. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with Section

99

100 Appliance Protection NCDOI web interpretation: Examples of approved barriers for protection of appliances from vehicle impact in a one-and-two family dwelling garage include: a) pipe bollards extending three feet above the floor examples: 2 inch Schedule 40 steel pipe set in a concrete floor; (option 1) 2 inch Schedule 40 steel pipe set in a cored hole in an existing concrete floor and sealed with epoxy (option 1)

101 Appliance Protection 2 inch Schedule 40 steel pipe welded to a ¼ inch steel base plate that is anchored to the concrete floor with four ½ inch x 2 ½ inch (embedment depth 2 ¼ inch) anchor bolts (option 3) b) curb stops and/or raised pads of not less than 5 ½ inches set not less than 40 inches from the appliance. (option 2) Note that if the appliance is located out of the normal path of travel of vehicles, no protection is required.

102 Appliance Protection Protection of components of plumbing system. Components of a plumbing system installed along alleyways, driveways, parking garages or other locations exposed to damage shall be recessed into the wall or otherwise protected in an approved manner. Exception: One- and two-family dwellings and townhouses.

103 Change of Occupancy I have been presented with an existing 575 square foot building which was formerly a mercantile occupancy, and is changing to a business occupancy. There are currently no restrooms within the building. The existing restrooms are located in a separate building approximately 150 feet away. Given the increased occupant load factor from mercantile to business, is NCPC applicable thus requiring a restroom facility within the existing building? Also, is the exception applicable since it will not be a storage structure or kiosk?

104 If an ADA accessible restroom is added, I believe based on the net square footage of the space and a 15 net occupant load factor, a single unisex restroom will be sufficient due to an occupant load of 25 or less. Please advise.

105 Change of Occupancy This change of occupancy will require a single unisex public toilet room per sections 403.1, 403.2, and of the 2012 NC plumbing code. This is contingent on there being 25 or fewer total occupants including employees and customers per item 2 under section The 500 foot travel distance is within the building. Using a toilet in another building 150 feet away is not acceptable under the current plumbing code.

106 Hotel Water Temperatures The attached picture shows information from DHHS guidelines for hotel hot water systems. It states must be between 116 and 128 degrees. How is that reconciled with NC plumbing code that says section 424, 120 degrees maximum?

107 Hotel Water Temperatures There is no direct correlation other than these are two different state agencies, one of which regulates health concerns and the other the plumbing aspects of the building code. The correlation would be scald testing. I would point out that the temperature of the water supply to a dwelling unit is not necessarily what the temperature is that you draw from the tap. Both sets of criteria have to be met.

108 Hotel Water Temperatures So if we have to meet both sets then per the NC Plumbing Code we should not have over 120 degree water out of shower or lavatory, correct? The maximum temperature at a public handwashing sink allowed is 110 F. The NC Building Code Council recently passed an amendment requiring tempered water at public hand washing sinks when hot water is provided.

109 Hotel Water Temperatures NC building code council amendment 2012 NC Plumbing Code Tempered water for public hand-washing facilities. Deleted. When hot water is provided to a public hand-washing facility, such water shall be tempered water delivered through an approved water-temperature limiting device that conforms to ASSE 1070 or CSA B The delayed effective date of this Rule is January 1, The Statutory authority for Rule-making is G. S ;

110 Hotel Water Temperatures Tempered water is defined in the plumbing code as Water having a temperature range between 85 F (29 C) and 110 F (43 C). If the hotel has a restaurant the health department requires a temperature of at least 100 F at hand wash sinks in restaurants as found in the NC Food Code Manual, Rules Governing the Food Protection and Sanitation of Food Establishments.

111 Hotel Water Temperatures NC Food Code (1) "Handwashing sink" means a lavatory, a basin or vessel for washing, a wash basin, or a plumbing fixture especially placed for use in personal hygiene and designed for the washing of the hands.

112 Hotel Water Temperatures Handwashing Sink, Installation. A. A HANDWASHING SINK shall be equipped to provide water at a temperature of at least 38 o C (100 o F) through a mixing valve or combination faucet. B. A steam mixing valve may not be used at a HANDWASHING SINK. C. A self-closing, slow-closing, or metering faucet shall provide a flow of water for at least 15 seconds without the need to reactivate the faucet. D. An automatic handwashing facility shall be installed in accordance with manufacturer s instructions.

113 Hotel Water Temperatures For shower valves (NC Plumbing Code) Individual shower valves. Individual shower and tubshower combination valves shall be balanced-pressure, thermostatic or combination balanced-pressure/thermostatic valves that conform to the requirements of ASSE 1016 or ASME A /CSA B125.1 and shall be installed at the point of use. Shower and tub-shower combination valves required by this section shall be equipped with a means to limit the maximum setting of the valve to 120 F (49 C), which shall be field adjusted in accordance with the manufacturer s instructions. In-line thermostatic valves shall not be utilized for compliance with this section. Scald preventative valves are not required in dwelling units with individual water heaters set at 120 F (49 C).

114 Inspections by Design Professionals Our jurisdiction has allowed third party inspections of building components through SI inspections. These are typically licensed design professionals, though not involved in the design of the element or component in question nor under the direct supervisory control of the designer. Items typically signed off by third party would be reinforcement in footings, vertical reinforcement in masonry walls, etc. I believe this is permitted by NC Admin Code For elements/components not listed under this section of the Admin. Code, my question is, must the design professional completing the inspection be the primary designer of the element or component inspected?

115 Inspections by Design Professionals GS153A-352(c) was modified as shown below. Item #2 was changed to indicate that a licensed architect or licensed engineer is able to perform the inspection. The architect or engineer performing the inspection is no longer required to be the designer of record. NCDOI has also issued a Guidance Paper addressing additional questions regarding design professionals performing inspections of elements and components based on GS 153A- 352(c).

116 Inspections by Design Professionals You can download the paper from our website at: ents/interpretations4/guidance%20papers/gs%20153a- 352%20- %20Acceptance%20of%20Licensed%20Architect%20or%20E ngineer%20inspections.pdf The NC Board of Architects has also issued a Position Statement with regards to this matter. It is included in the NCDOI Guidance Paper.

117 Inspections by Design Professionals 153A-352(c) "Notwithstanding the requirements of this Article, a county shall accept and approve, without further responsibility to inspect, a design or other proposal for a component or element in the construction of buildings from a licensed architect or licensed engineer provided all of the following apply: 1) The submission is completed under valid seal of the licensed architect or licensed engineer. 2) Field inspection of the installation or completion of a construction component or element of the building is performed by a licensed architect or licensed engineer or a person under the direct supervisory control of the licensed architect or licensed engineer. 3) The licensed architect or licensed engineer under subdivision (2) of this subsection provides the county with a signed written document stating the component or element of the building so inspected is in compliance with the North Carolina State Building Code or the North Carolina Residential Code for One- and Two-Family Dwellings.

118 Rubber Trap Seals I have a contractor asking me if the rubber flaps they developed recently for floor drains are acceptable instead of a trap primer or hose bib in a restroom. I told him there not approved, he said another jurisdiction approved them. Will you please verify?

119 Rubber Trap Seals They are not approved for use in the 2012 NC plumbing code. Sure Seal initiated a code change request which was rejected by the NC Building Code Council. You can always add them as a supplemental item but they do not replace putting water in the trap either by trap primer or hose bib in the space with an impervious floor per section 412 of the plumbing code.

120 Shower Pan Test Is a shower pan inspection required when it is installed in a handicap accessible shower with no shower curb? This would be in the case where the floor system is recessed and the installer is not putting in the system until the house is ready for final finishes so that way the Schluter system membranes are not penetrated during the course of construction. The shower pan installation must be inspected and tested per the plumbing code.

121 Shower Pan Test The shower system is required to withstand a standing water test of a minimum of a 2 inch depth for 15 minutes with no leakage per section of the 2012 NC plumbing code Shower liner test. Where shower floors and receptors are made water-tight by the application of materials required by Section , the completed liner installation shall be tested. The pipe from the shower drain shall be plugged water tight for the test. The floor and receptor area shall be filled with potable water to a depth of not less than 2 inches (51 mm) measured at the threshold. Where a threshold of at least 2 inches (51 mm) high does not exist, a temporary threshold shall be constructed to retain the test water in the lined floor or receptor area to a level not less than 2 inches (51 mm) deep measured at the threshold. The water shall be retained for a test period of not less than 15 minutes, and there shall not be evidence of leakage.

122 Main Vent The inspector is stating that in the plumbing code says we have to have a 3" vent out the roof on a single family dwelling. But I am told him that the code of says we can have a vent out the roof, 1/2 the size of the building drain (which is 3" on our particular house), but not less than 2" pipe for the vent exiting the roof. And that the code he cited is dealing with a different scenario. We have worked in multiple counties from the middle part of the state, to the western part of the sate, and this is the first time this has been an issue since the code changed several years ago. I'm not sure how long the official has been on the job, and wanted me to call to get clarification.

123 Main Vent The main vent stack through the roof for a one- or two-family dwelling with a maximum building drain size of 3 inches should be 2 inches in diameter per section Section describes the minimum building drain, building waste stack or branch thereof and not the vent stack size. I think the confusion may come in since there are different definitions of stack and section is poorly written. The frost provisions of which call for a 3-inch vent through the roof are for conditions not found in North Carolina and do not apply. Vent stack sizing is done in accordance with section

124 Main Vent Stack required. Every building in which plumbing is installed shall have at least one stack the size of which is not less than one-half of the required diameter of the building drain, and not less than 2 inches (51 mm) in diameter. Such stack shall run undiminished in size and as directly as possible from the building drain through to the open air or to a vent header that extends to the open air Connection to drainage system. A vent stack shall connect to the building drain or to the base of a drainage stack in accordance with Section A stack vent shall be an extension of the drainage stack. For townhouses and one- and two-family dwellings, the main vent shall connect to the building drain, building stack or branch thereof not less than 3 inches (76 mm) in size.

125 Main Vent Size. Deleted Frost closure. Where the 97.5-percent value for outside design temperature is 0ºF (-18ºC) or less, every vent extension through a roof or wall shall be a minimum of 3 inches (76 mm) in diameter. Any increase in the size of the vent shall be made inside the structure a minimum of 1 foot (305 mm) below the roof or inside the wall. NC does not have the conditions listed in 904.2

126 Main Vent BUILDING DRAIN. That part of the lowest piping of a drainage system that receives the discharge from soil, waste and other drainage pipes inside and that extends to 10 feet (3048 mm) beyond the walls of the building and conveys the drainage to the building sewer. Combined. A building drain that conveys both sewage and storm water or other drainage. Sanitary. A building drain that conveys sewage only. Storm. A building drain that conveys storm water or other drainage, but not sewage.

127 Main Vent STACK. A general term for any vertical line of soil, waste, vent or inside conductor piping that extends through at least one story with or without offsets. STACK VENT. The extension of a soil or waste stack above the highest horizontal drain connected to the stack. VENT STACK. A vertical vent pipe installed primarily for the purpose of providing circulation of air to and from any part of the drainage system.

128 Water fountain spout heights What are the required water fountain spout heights for hi-lo water fountains? Low fountain spout 36 inches maximum, high spout height 38 inch minimum to 43 inches maximum per ANSI A117.1.

129 Water fountain spout heights

130 Faucet Markings I write to you on behalf of our client IKEA regarding the above mentioned faucet, which is under question by your jurisdiction. I wish to provide additional information which may assist you in confirming the status of this faucet as it relates to compliance and certification. To that end, please note the following:

131 Faucet Markings This faucet (model ) is certified under the following IAPMO listings (direct links included): File 5857, This listing covers compliance to ASME A /CSA B125.1 and the Uniform Plumbing Code and International Plumbing Code File N-5858, This listing covers compliance to NSF/ANSI 61 File 6352, This listing covers compliance to NSF/ANSI 372 and the Safe Drinking Water Act, confirming a weight lead content average of less than.25% The 3 above listings cover the required standards for faucets delivering potable water. Each listing is supported by test reports to the respective standards. I hope the information above helps to resolve this issue. If there are any specific concerns, please share them with me so that I can provide what you need. Thank you for your attention to this matter.

132 Faucet Markings The applicable section of the 2012 NC Plumbing Code is Identification. Each length of pipe and each pipe fitting, trap, fixture, material and device utilized in a plumbing system shall bear the identification of the manufacturer, and the applicable standard to which it was manufactured. Underlining indicates a North Carolina amendment to the ICC model plumbing code. The upcoming code edition approved by the NC Building Code Council for 2018 reads

133 Faucet Markings Identification. Each length of pipe and each pipe fitting, trap, fixture, material and device utilized in a plumbing system shall bear the identification of the manufacturer and any markings required by the applicable referenced standards. Nipples created from the cutting and threading of approved pipe shall not be required to be identified. Exception: Where the manufacturer identification cannot be marked on pipe fittings and pipe nipples because of the small size of such fittings, the identification shall be printed on the item packaging or on documentation provided with the item. You can request to use the new language. Basically the information needs to be either on the part or on the packaging from the manufacturer.

134 Faucet Markings With permission from the manufacturer, I ve attached three test reports for the IKEA faucet in question. The reports convey compliance to the application standards: ASME A /CSA B125.1, NSF/ANSI 61 and NSF/ANSI 372. You will note the ASME A /CSA B125.1 report indicates that NSF/ANSI 61 and NSF/ANSI 372 are pending, however those were subsequently completed as evidenced by the other two attachments. Please review and let me know if this information is sufficient to resolve this issue. Thank you for your help.

135 Faucet Markings I have reviewed the test reports that you have furnished and they appear to be complete and acceptable to substantiate compliance with ASME A and NSF 61, section 9, as required by section of the 2012 NC Plumbing Code. If there is any reason for rejection of these fittings, it would seem that it is about the marking of the product and/or its packaging. Since I have not seen the product or its packaging, I am referring you to the chief plumbing code official of the local jurisdiction having authority for resolution of this problem.

136 Treehouses and Toilets Every great journey starts with a single step, so we are planning to build a single house at the outset with plans to build up to 8 or so on any given site. This would have us clearly land in the commercial code. The house will be 12x12 and have plumbing for the sink and drainage for any waste and grey water being disposed of. The whole experience embodies being a part of nature and bringing it inside so the more eco-friendly we can be the better.

137 Treehouses and Toilets

138 Treehouses and Toilets We are doing our best to find alternative options to the traditional septic system due to it being not eco-friendly, cost prohibitive, and a barrier to renting on someone else's site - we believe it is a harder sell for people in the agriculture business if we have to dig up their land and bury septic tanks / have leech fields, etc. Fortunately DHHS has provided me with the guidelines sent to the counties from DHHS regarding alternate systems.

139 Treehouses and Toilets Our first option for black water/ solid waste is the compost toilet as it is the easiest to use from a customer point of view, poses no real safety/health risk, and has been used for many years in the tiny house industry. Grey water will only consist of biodegradable soap from the sink and shower. All water will be collected and go through a filtration system rendering it inert and eco-friendly

140 Treehouses and Toilets

141 Treehouses and Toilets The customer will have the same experience as a regular toilet and will NOT be responsible for either emptying the unit or turning the crank to rotate it. Our cleaning service will empty it and clean it after each customer departs. The average customer stay will only be 2-3 days long and the system is designed to go much longer without needing maintenance. Thank you very much for the time and consideration. While I know it's a little more work for us all we are looking forward to being eco-friendly tax revenue generators for the State and a fresh way for people to enjoy our beautiful state.

142 Treehouses and Toilets

143 Treehouses and Toilets The plumbing code requires that sewage be directed to a public waste system if available or an approved alternate waste disposal system. It is my interpretation that an approved waste system in this case would be a septic system or use of the public water and sewer utilities.

144 Composting Toilets Composting toilets approved only if soil will not perk test or no connection to public sewer. Correct? or am I missing something? We have a memorandum of understanding between NCDOI/OSFM and DHHS about this. A copy is attached. There are quite a few requirements to be met before composting toilets are approved. They are approved by the health department at which we treat them as an approved sanitary waste system similar to a septic tank. All of the other requirements for a toilet room are inspected.

145 Composting Toilets

146 Composting Toilets

147 Plumbing permits for farm buildings Are plumbing permits and inspections exempt from farm buildings? Plumbing in farm buildings is exempt only if it is used solely for livestock or other agricultural purposes. If the plumbing is for human hygiene and sanitation or for water consumption for cooking, ingestion or bathing, then that plumbing is not exempt from inspection.

148 Public Water and Sewer Do new installations have to be connected to public water and sewer if available? It s my interpretation that for new construction or where there is an initial installation being considered that they must connected to the public water and sewer systems if available per sections and of the plumbing code.

149 Public Water and Sewer Do new installations have to be connected to public water and sewer if available? Existing systems that were legally permitted at the time of their installation and that have been maintained in a safe condition can be continued to be used until a system reconfiguration or replacement requires a permit for new construction meeting current codes per sections and of the plumbing code.

150 Public Water and Sewer Existing installations. Plumbing systems lawfully in existence at the time of the adoption of this code shall be permitted to have their use and maintenance continued if the use, maintenance or repair is in accordance with the original design and no hazard to life, health or property is created by such plumbing system Maintenance. All plumbing systems, materials and appurtenances, both existing and new, and all parts thereof, shall be maintained in proper operating condition in accordance with the original design in a safe and sanitary condition. All devices or safeguards required by this code shall be maintained in compliance with the code edition under which they were installed.

151 Public Water and Sewer The owner or the owner s designated agent shall be responsible for maintenance of plumbing systems. To determine compliance with this provision, the code official shall have the authority to require any plumbing system to be re-inspected Individual water supply. Where a potable public water supply is not available, individual sources of potable water supply shall be utilized Sewer required. Every building in which plumbing fixtures are installed and all premises having drainage piping shall be connected to a public sewer, where available, or an approved private sewage disposal system.

152 Public Water and Sewer The jurisdiction may have ordinances that require connection to the public utilities where available. These would be enforced separately from the plumbing code provisions. If the jurisdiction decides to allow the use of a well or another potable water source instead of an available public water supply system then this would be an alternate method to the code.

153 Public parks Would you classify a public park as A5 for bathrooms fixture counts or is there an alternate when figuring bathrooms for a park? A5 seems to be the most appropriate to calculate plumbing fixtures for outdoor activities in a park using table of the plumbing code or table of the NC building code.

154 Horse Barn A home owner is building his own horse barn, farm exempt from building permits. The owner has a plumbing permit. He called for a rough in inspection, but upon arrival he had already installed under slab plumbing and poured the slab. He has a full bath, 2 sinks, and a horse wash down area. The toilet was run out of the building straight to septic tank without a vent installed. The rest of the plumbing was run out to the septic tank tied together. Since the plumbing was installed and covered without inspections, the owner was asked to have an engineer approve the installation. The engineer letter is attached that I received. Will this letter as written cover the installation of the DWV as installed without inspections?

155 Horse Barn Engineer s Letter At your request I made a site visit today to the above address. The purpose was to review plumbing work done without a rough-in inspection. We observed what was visible above the slab and also where the 2 and 3 waste lines exit the building. There is sufficient fall available for the lines to drain appropriately to the septic tank (previously permitted). It appears from the depth of the pipes at the septic tank the contractor sloped pipe appropriately Please note we cannot make statements about work not visible nor do we make functional guarantees.

156 Horse Barn Given that the engineer s letter does not functional guarantees and does not cover plumbing under the slab that is not visible, request that a camera be used to inspect the drainage system. Verify that wye connections were used in the direction of flow, pipe sizes and slopes. The toilet should be individually vented as per the code. There should be at least one vent from the system for a main building vent from the sink associated with the shower. The horse stall sink should also be vented.

157 Private sports complex

158 Private sports complex

159 Private sports complex The property owner has requested an informal interpretation by from your office on a matter of permanent plumbing fixture requirements for structures located on his property. The property has been used for fairs, concerts, bike rallies and other large gatherings since the late 1980 s (all are seasonal/temporary) and a portion of the property contains a dirt racetrack with temporary bleacher seating that is used on weekends during the summer months (less than 180 days).

160 Private sports complex The property has several older buildings and a stage that were built in the 80 s that have fallen into disrepair. Some of the buildings have been torn down and others used for light storage or boarded up due to structural concerns. The property continues to be used for events with temporary bathroom facilities (Porta-Jons) based on the understanding of that if you do not have permanent occupied structures, permanent plumbing fixture requirements do not apply.

161 Private sports complex The property owner has requested your interpretation of the code in the matter of, can temporary bathroom facilities (Porta-Jons) be utilized to serve permanent occupied structures? In addition, he asked if his property would be exempt of code requirements due to the structures being built in the 1980 s. His position is that the buildings have been in use and have had electrical power since they were built.

162 Private sports complex Any permanent structures on the property including bleachers will require some sort of permanent toilet facilities with occupancy based on the use of the building or structure. Even though 180 days is the definition of temporary, this is not meant for events that are recurring over a long period of time. Either the permit to operate would have to be re-issued every year by your department or permanent toilet facilities should be provided. Extensions of the 180 day temporary limit are for cause and should be documented.

163 Drainage Pipes in Metal Stud Cavities Does the drainage pipe have to be protected from the sharp edge where it passes through the metal stud? No. There is little chance that there is enough length of pipe for thermal expansion to cause damage to the drainage pipes.

164 Drainage Pipes in Metal Stud Cavities Stress and strain. Piping in a plumbing system shall be installed so as to prevent strains and stresses that exceed the structural strength of the pipe. Where necessary, provisions shall be made to protect piping from damage resulting from expansion, contraction and structural settlement.

165 Water Pipes in Metal Stud Cavities Do water pipes have to be protected from cut edge of a metal stud web hole? Yes. Water pipes are under pressure and as such if a hole were to develop it can lead to excessive damage to the building. Metal web openings should have plastic grommets placed over the cut edge of the web opening in metal studs or the pipe should be sleeved where it passed through the metal stud web opening.

166 Size of Web Openings in Metal Studs Concerning the diameter of the hole thru metal studs and the size vs. gauge. What size holes are allowed in the various metal stud sizes? Where can I get this information?

167 Size of Web Openings in Metal Studs Cold formed steel is sensitive to any modifications to the stud. They buckle easily unless properly braced and are of the proper gage thickness. That is why any modification of a loadbearing stud should be approved by a design professional. Non-structural studs have code-prescribed web openings. The following is from appendix F of the plumbing code.

168 Size of Web Openings in Metal Studs [B] F101.5 Cutting, notching and boring holes in cold formed steel framing. Flanges and lips of load-bearing coldformed steel framing members shall not be cut or notched. Holes in webs of load-bearing cold-formed steel framing members shall be permitted along the centerline of the web of the framing member and shall not exceed the dimensional limitations, penetration spacing or minimum hole edge distance as prescribed by the registered design professional. Cutting, notching and boring holes of steel floor/roof decking shall be as prescribed by the registered design professional.

169 Size of Web Openings in Metal Studs [B] F101.6 Cutting, notching and boring holes in nonstructural cold-formed steel wall framing. Flanges and lips of nonstructural cold-formed steel wall studs shall not be cut or notched. Holes in webs of non-structural cold-formed steel wall studs shall be permitted along the centerline of the web of the framing member, shall not exceed 1-1/2 inches (38 mm) in width or 4 inches (102 mm) in length, and the holes shall not be spaced less than 24 inches (610 mm) center to center from another hole or less than 10 inches (254 mm) from the bearing end. Design is done per the American Iron and Steel Institute standards.

170 Multi-story Wet Venting Can you give an example of when you would have a wet vent connection downstream of the water closet and what that would look like? We have debated it and can t get a clear understanding of it. How can you have a wet vent downstream of a water closet when every fixture downstream of a water closet is supposed to be individually vented?

171 Multi-story Wet Venting Multistory bathroom groups. On the lower floors of a multistory building, the waste pipe from one or two lavatories may be used as a wet vent for one or two bathtubs or showers provided that: 1. The wet vent and its extension to the vent stack is not less than 2-inch (51 mm) diameter; 2. Each water closet below the top floor is individually back vented; and 3. The vent stack is sized in accordance with Table

172 Multi-story Wet Venting Multistory bathroom groups. Exception: In multistory bathroom groups (does not apply to one- and two-family dwellings), wet vented in accordance with Section 909.4, the water closets below the top floor need not be individually vented if a 2-inch (51 mm) wet vent connects downstream of the water closet.

173 Multi-story Wet Venting Venting required. Every trap and trapped fixture shall be vented in accordance with one of the venting methods specified in this chapter. All fixtures discharging downstream from a water closet shall be individually vented except as provided in Section 911.

174 Multi-story Wet Venting It is my interpretation that what they are trying to say is that if the water closet is downstream of the wet vent, it can be wet vented by the lavatory. See figure 901.9(19) in the commentary. This is if it is properly sized. The 2 inch pipe size seems to be an exception to table for the fixtures described. This is an NC amendment so any basis for this is not documented.

175 Back Water Valve Does Section of the NC Plumbing Code include the manhole that the sewer lateral is connecting? I have a project under review where the manhole they are connect to is the last manhole on the public line. The rim elevation is higher than the finish floor of the project. There are 2 other buildings that also connect to the manhole. They are stating that this is not the upstream manhole but is the downstream manhole and therefore does not require a backwater valve.

176 Back Water Valve RIM elevation

177 Back Water Valve My main question is do I use that manhole cover elevation or does it not apply? The section says upstream manhole but when they are connecting directly to a public manhole is that the elevation we use. In this case this is the last manhole on the line. It is my interpretation that there is no upstream manhole in this case. Therefore backwater valves are not required. If the sewer line is extended in the future and there is an upstream manhole with an elevation higher than the floor elevation, they will have to add a back water valve at that time.

178 Back Water Valve Sewage backflow. Where the flood level rims of plumbing fixtures are below the elevation of the manhole cover of the next upstream manhole in the public sewer, such fixtures shall be protected by a backwater valve installed in the building drain, branch of the building drain or horizontal branch serving such fixtures. Plumbing fixtures having flood level rims above the elevation of the manhole cover of the next upstream manhole in the public sewer shall not discharge through a backwater valve.

179 Test Tees as Cleanouts Can a test tee fitting be accepted as a cleanout installed on a horizontal branch? This has been done all over the state for many years when certain situations are practical for it. It is realized that although a test tee fitting is not designed for clean out use intentionally, that it is referenced in Code Section Exception #5 of the 2012 NCPC as acceptable in a vertical pipe, but does not reference the use or prohibit the use of one in a horizontal branch. The commentary also references the use of test tees being used as clean outs but also does not reference the use in specific installations outside of underneath a sink area.

180 Test Tees as Cleanouts Using the test tee in the horizontal orientation will be acceptable as an alternate method since it is not described that way in the code section Location. Each horizontal drainage pipe shall be provided with a cleanout at the upstream end of the pipe. Exceptions: The following plumbing arrangements are acceptable in lieu of the upstream cleanout. 5. Test tees or cleanouts in a vertical pipe.

181 Outdoor Showers What are the drainage requirements for outdoor pool showers?

182 Outdoor Showers Concerning outdoor poolside showers if the showers are required by the plumbing code or the NC pool rules, then the shower waste must go to the sanitary drainage system. The drainage can go the storm drainage system if the showers are (1) in addition to the number of required showers; (2) are for rinsing only with no soap, shampoo or other detergent products used and are (3) outside of the building.

183 Produce Stands What are the requirements for permanent roadside produce stands? 1. Are bathrooms required? 2. Can the bathrooms be a porta-john? 3. Will the floors under the roof for the isles be concrete? 4. Is handicap parking required?

184 Produce Stands We have a web interpretation on our website. Toilet requirements depend on the situation. 1. If it is a roadside tent or stand that could be considered temporary if in operation less than 180 days per section 110 of the plumbing code. Porta-johns can be used for temporary situations. Temporary is generally limited to events that don t occur on a continual basis.

185 Produce Stands 2. If it is a brick and mortar permanent facility where the public comes into the building to browse and shop, then a public toilet is generally required.

186 Produce Stands 3. If the public access area is 300 sf or less and the business is for quick transactions, i.e., take-out then the 2018 code does not require a public toilet. The 2018 has been approved by the NC building code council and use of it can be requested by the owner.

187 Produce Stands 4. Toilets are always required for employees unless the only employee is the homeowner or his family and the homeowner s house is within 300 feet of the stand.

188 Produce Stands Web Interpretation: Are toilet facilities required for vegetable/fruit stands? 1. No, if the vegetable/fruit stand is located on the same parcel of land as the operator s dwelling and has no entrance into the stand for the customers, then toilet facilities are not required. 2. Yes, if the vegetable/fruit stand allows customers to enter the building, then toilet facilities are required (see table mercantile for required toilet facilities).

189 Produce Stands If bathrooms are required by the NC Plumbing Code, then NCBC requires that the restroom be handicapped accessible. If the NCPC Exc. 5 permits one toilet room for each sex, and two unisex facilities are required, then NCBC Exc. 3 will require that a minimum of one room for each use, i.e., one for men and one for women, be accessible.

190 Produce Stands Toilet and bathing facilities. Each toilet room and bathing room shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing rooms provided within the facility shall not be located on the inaccessible floor. At least one of each type of fixture, element, control or dispenser in each accessible toilet room and bathing room shall be accessible. Exception: Where multiple single-user toilet rooms or bathing rooms are clustered at a single location, at least 50 percent but not less than one room for each use at each cluster shall be accessible.

191 Produce Stands Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. Exceptions: 5. Where the code requires only one toilet facility for each sex, two unisex facilities may be substituted for separate sex facilities.

192 Produce Stands If the customer enters a roofed over area within a permanent roadside produce stand, then the accessible route within the building is required to comply with ANSI and be stable, firm and slip-resistant. If parking is provided, then accessible parking is required per NCBC , Table , NCBC and NCBC

193 Ejector Discharge Regarding the intersection of a ejector discharge pipe into the building drain system, section requires a minimum of ten (10) feet from the base of stacks or fixture drain connections. The project in question has the location 8-8 from a branch connection that connects upstream in the same horizontal drain and another fixture drain downstream but in a vertical position of the pipe (not clearly seen in the attached pictures). The question is whether the 8-8 distance from the intersection of a branch connection would impose the same potential issues to the drainage pattern as if the connect were from a stack or fixture drain.

194 Ejector Discharge The requirement is that the ejector pump connection to the drainage system is a minimum of 10 feet downstream of the base of the fixture drain which in this case is the wye connection to the branch drain.

195 Ejector Discharge The 2018 code will read 10 pipe diameters instead of 10 feet Pump connection to the drainage system. Pumps connected to the drainage system shall connect to a building sewer, building drain, soil stack, waste stack or horizontal branch drain. Where the discharge line connects into horizontal drainage piping, the connection shall be made through a wye fitting into the top of the drainage piping and such wye fitting shall be located not less than 10 pipe diameters from the base of any soil stack, waste stack or fixture drain. I offer this information if you wish to use it as basis for an alternate method for this one case. This has been approved by the building code council and its use can be requested by the owner and/or contractor.

196 Wine Stores We have a proposed wine store which will not sell food, but will be serving wine. (No glass washing/ reuse) There are 2 wine dispensers, an eight bottle and a sixteen bottle unit, nitrogen propelled. They are a retail store and the primary occupancy is M. Would this be considered to be an A-2 occupancy because of the consumption of wine? A-2 is higher hazard, has different restroom requirements, occupant density, etc?

197 Wine Stores If the store is for dispensing wine only and not for congregating to consume wine, then it appears to be Group M.

198 Wine Stores Exception #3 of Section allows a unisex toilet to be used. This will allow the employees and the public to share the same unisex toilet room if the occupancy is less than 100. [P] Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. Exceptions 3. Separate facilities shall not be required in mercantile occupancies in which the maximum occupant load is 100 or less.

199 Water Heater Discharge The new electric water heater was relocated to the garage. Today I meet with the plumbing inspector at the residence and was failed for not insulating the relief valve ( T&P valve) or strapping the relief line. I asked for the inspector and chief plumbing inspector to provide me with a code reference that enforces the requirements of insulating the relief valve and strapping the vertical relief line. The chief plumbing inspector cannot provide me with any such reference but is requiring me to contact DOI for a ruling.

200 Water Heater Discharge The following was passed by the NC Building Code Council on June 20, 2014 after an appeals hearing Request by Al Bass, representing the NC Building Code Council, to amend the 2012 NC Plumbing Code, Section The proposed amendment is as follows: Support. The discharge pipe shall be clamped or otherwise supported per Table with not less than one clamp or support within 12-inches of the point of discharge. Motion/Second/Approved The request was granted. The proposed effective date of this rule is January 1, Reason Given This proposal is to provide clarity to the Plumbing Code, Section 504.6, Item 6 based on an appeal decision.

201 Water Heater Discharge If the relief valve is insulated, care should be taken not to restrict the movement of the relief lever on the valve since this could keep it from operating. The relief lever should be visible after insulation. Section of the plumbing code describes freeze protection of water piping systems. Generally the hot water heater relief valve is not insulated but could be required by the local inspection department per the note under section 305.6, if they have had problems with relief valves freezing when exposed to an internal temperature of 120 degrees F.

202 Water Heater Discharge Freezing. The top of water pipes, installed below grade outside the building, shall be below the frost line or a minimum of 12 inches (305 mm) below finished grade, whichever is greater. Water pipes installed in a wall exposed to the exterior shall be located on the heated side of the wall insulation. Water piping installed in an unconditioned attic or unconditioned utility room shall have insulation with a minimum R-factor of 6.5 determined at 75 F (24 C) in accordance with ASTM C-177. Note: These provisions are minimum requirements, which have been found suitable for normal weather conditions. Abnormally low temperatures for extended periods may require additional provisions to prevent freezing.

203 Water Heater Discharge That covers the strapping but the code pertaining the T&P being insulated is vague at most. This section is not pertaining to water heaters or the section that pertains to water heaters, which addresses relief valves directly. The code your referring only dictates water piping. I see no reason to insulate the pressure relief valve on a water heater but it can be a local requirement if they have had problems with them freezing in the past. If the water heater manufacturer s installation instructions require that the pressure relief valve be insulated, then it is required by code to do so.

204 Water Heater Discharge Also to question how to comply with strapping the discharge on every install, I don t see how it can always be done and would like some clarification on how For example how would I strap a discharge pipe on a water heater in the basement on a slab with no stand? The only place would be to the actual water heater which would be modifying manufacturers product, which would be illegal.

205 Water Heater Discharge The code does not provide guidance on how you should secure the discharge pipe, only that it needs to be secured. If you don t attach it to the water heater due to warranty concerns, pipe stanchions or standoffs can be fabricated from steel angle, steel tube, pipe or unistrut. A U-bolt can fasten the pipe to the stanchion or standoff. Banding the discharge pipe to the water heater may be another option for flexible pipe such as PEX as long as you don t crush the pipe and reduce the inside diameter.

206 Plumbing Fixture Count Higher Ed is classified as a business use. Our facility contains a small office area and a large assembly room around 3,000 SF. The rest of the building area is divided up as labs and classrooms. Previous projects have used actual occupant loads as the room is to be used such as 50 SF for lab rooms and then use the business classification for office areas. The same for classrooms at 20 SF per person.

207 Plumbing Fixture Count 1. Is this the correct procedure? 2. Since the bulk of my building is a net use with only 10% is a gross use, do I add the remaining building areas not included in one of the net use spaces into the occupant count as a business use divided by 100 SF per person? 3. Do you add a higher occupant loads for portions of open lobbies that could be utilized as waiting areas or possible soft seating areas?

208 Plumbing Fixture Count Plumbing fixture counts are based on egress loads and the use of the space. The occupant loadings are calculated using table of the building code. Higher education uses such as community colleges are business use. This applies to building height and area calculations. Labs with fixed tables are taken at 50 sf per person net. Classrooms are calculated a 20 SF per person net. Assembly space occupant loads depend on how the space is set up, i.e., loose chairs, tables and chairs or standing room (the prom, lobbies or spaces without furniture, etc.).

209 Plumbing Fixture Count Plumbing calculations are done by calculating the fixture counts individually for each use, combining the fractional components of each and rounding up Fixture calculations. To determine the occupant load of each sex, the total occupant load shall be divided in half. To determine the required number of fixtures, the fixture ratio or ratios for each fixture type shall be applied to the occupant load of each sex in accordance with Table

210 Plumbing Fixture Count Fractional numbers resulting from applying the fixture ratios of Table shall be rounded up to the next whole number. For calculations involving multiple occupancies, such fractional numbers for each occupancy shall first be summed and then rounded up to the next whole number. Exception: The total occupant load shall not be required to be divided in half where approved statistical data indicates a distribution of the sexes of other than 50 percent of each sex.

211 Plumbing Fixture Count Just to clarify, a lab is 50 SF and its occupancy category in the MFC spreadsheet is still Business since there is no education above grade 12, correct? Also, do I include and occupant load for the corridors since they serve net use spaces?

212 Plumbing Fixture Count The use of the space in the lab is lab at 50 sf per person. You would include corridors in a business use such as a front office where the total business space is taken at 1 per 100 sf. You do not include corridor space for net calculations. The classification of business for community college is for height and area calculations in chapter 5. Plumbing fixtures are determined by the use of the individual spaces in the building.

213 Plumbing Fixture Count Table is the clarification I was seeking. There is no option for education above grade 12. If Business use is for the building and area, what is the category for the occupancy category for lab plumbing count. Use the business category in table for the fixture loading. The lab designation is used for occupancy loading.

214 Condensate Drainage I have a HVAC contractor installing their condensate primary drain from their attic 90% HVAC system both the A/C coil and furnace condensate combining the drain into one drain and same extends down to under the bathroom vanity. Under the vanity, there is a dishwasher tailpiece installed and the condensate is connected DIRECTLY to the tailpiece with a flexible connection. The is NO indirect connection in the system. The condensate is direct connected on both ends. I contend that this install is a violation since there is not any air gap or air break. I understand that if this condensate came off of the drain pan, this may be an air gap, but this is a direct connection to the HVAC system.

215 Condensate Drainage An air gap is required between the AC unit and the sanitary system for condensate drainage Non-potable clear-water waste. Where devices and equipment such as process tanks, filters, drips and boilers discharge non-potable water to the building drainage system, the discharge shall be through an indirect waste pipe by means of an air break or an air gap.

216 Trenchless Water Line Installation Where can I find a list of approved pipe when installing trenchless potable water lines?

217 Trenchless Water Line Installation There will be a trenchless piping installation section in the 2018 plumbing code. The upcoming code language is as shown below. SECTION 717 REPLACEMENT OF UNDERGROUND SEWERS BY PIPE-BURSTING METHODS General. This section shall govern the replacement of existing building sewer piping by pipe-bursting methods.

218 Trenchless Water Line Installation Applicability. The replacement of building sewer piping by pipe-bursting methods shall be limited to gravity drainage piping of sizes 6 inches (152 mm) and smaller. The replacement piping shall be of the same nominal size as the existing piping Pre-installation inspection. The existing piping sections to be replaced shall be inspected internally by a recorded video camera survey. The survey shall include notations of the position of cleanouts and the depth of connections to the existing piping.

219 Trenchless Water Line Installation Pipe. The replacement pipe shall be made of a highdensity polyethylene (HDPE) that conforms to cell classification number PE3608, PE4608 or PE4710 as indicated in ASTM F 714. The replacement piping shall be manufactured with a standard dimension ratio (SDR) of 17 and in compliance with ASTM F Pipe fittings. Pipe fittings to be connected to the replacement piping be made of high-density polyethylene (HDPE) that conforms to cell classification number PE3608, PE4608 or PE4710 as indicated in ASTM F 714. and shall be manufactured with an SDR of 17 and in compliance with ASTM D 2683.

220 Trenchless Water Line Installation Cleanouts. Where the existing building sewer did not have cleanouts meeting the requirements of this code, cleanout fittings shall be installed as required by this code Post-installation inspection. The completed replacement piping section shall be inspected internally by a recorded video camera survey. The video survey shall be reviewed and approved by the code official prior to pressure testing of the replacement piping system Pressure testing. The replacement piping system shall be tested in accordance with Section 312.

221 Trenchless Water Line Installation Will pex or copper be approved in 2018 code? As far as I know at this time pex and copper will not be approved for trenchless installation in the 2018 NC plumbing code.

222 Flexible Plumbing Drain A homeowner recently contacted me asking if flex drain piping under a sink was legal. I looked through the code and really couldn t come up with anything stating they couldn t be used. Am I missing something?

223 Flexible Plumbing Drain The only item I could find was section where fitting shall not have ledges or restrictions to flow. We use flex hose for dishwashers but that is a pumped situation, not gravity flow. It is my interpretation that these fittings can be used but their use is discouraged because of possible development of sediment between the folds and obstruction to flow.

224 Skid Mounted Equipment The inspector thinks the skids need to have UL approved labels on them as an assembly. We have pointed out that all the electrical components on the skid are all UL Listed, including the Electrical Control Box which we built in our UL Listed Panel Shop. We have very similar installations across the country using the same equipment.

225 Skid Mounted Equipment The equipment is used to make Diesel Exhaust Fluid (DEF), which is sold by Pilot at their Travel Plazas for used on diesel powered vehicles fitted with Selective Catalytic Reduction (SCR) technology to remove Nitrogen Oxide (NOx) pollutants from the diesel exhaust. Since the year 2010, nearly all diesel engines require DEF to meet emission standards.

226 Skid Mounted Equipment DEF is a nonhazardous fluid, made from pure water and purified urea. DEF is so effective at cleaning the diesel exhaust, that new diesel engines no longer need to use Exhaust Gas Recirculation (EGR) technology, and can actually get more horsepower per cubic inch of displacement. The DEF pays for itself in improved mileage per gallon of diesel fuel.

227 Skid Mounted Equipment It is my understanding that the entire skid can be UL certified OR the component parts can be UL certified with a set of engineered plans that has be signed and sealed by a licensed professional engineer.

228 Resetting a Toilet It is my interpretation of the code that a pull and reset of a fixture would allow a plumbing contractor use the existing plumbing to reset the fixture. Once a plumbing contractor has to replace the piping servicing these fixtures they would be held to the current plumbing technical code and would need to adhere to all clearances and codes. Am I correct in my interpretation of the code?

229 Resetting a Toilet If the plumbing piping system is altered in any way then the plumbing and the toilet is required to meet the new code requirements. If the toilet or the piping is replaced in place and there are no changes to the size or configuration of the plumbing it is a repair and the code requirements that were effective at the time of the earlier installation are in effect. This only applies to installations that were properly inspected and permitted at the time of installation.

230 Pipe Support Can the branch tie-ins for the lavatory and shower wet vent of a toilet be temporarily supported by steel conduit, zip ties and duct tape until the slab is poured?

231 Pipe Support It is my interpretation that the pipe needs to be bedded and cannot be supported by conduit or rebar with zip ties and duct tape. Buried pipe requires continuous supporter per section Support of piping. Buried piping shall be supported throughout its entire length.

232 Pipe Support My suggestion would be to have the bedding/installation of the long sweep for the toilet done first with a follow-up inspection for the proper bedding/installation of the lavatory and shower branches that are connected to the tee between the toilet and the long sweep. This type of installation can suck the traps dry when the toilet is flushed and is not recommended but is allowed by the current plumbing code.

233 Public Handwashing I have had some questions come my way that I m sure you have already gave answers to dealing with section How are you interpreting public hand washing facilities??? Are you interpreting it to mean hand washing facilities such as Hand wash sinks and Lavatories for customers, patrons, and visitors (not employees/ staff) or are you including those fixtures for Employees and Staff also for this requirement???

234 Public Handwashing Use the definitions of public and private use that are in the plumbing code. PRIVATE. In the classification of plumbing fixtures, private applies to fixtures in residences and apartments, and to fixtures in nonpublic toilet rooms of hotels and motels and similar installations in buildings where the plumbing fixtures are intended for utilization by a family or an individual.

235 Public Handwashing PUBLIC OR PUBLIC UTILIZATION. In the classification of plumbing fixtures, public applies to fixtures in general toilet rooms of schools, gymnasiums, hotels, airports, bus and railroad stations, public buildings, bars, public comfort stations, office buildings, stadiums, stores, restaurants and other installations where a number of fixtures are installed so that their utilization is similarly unrestricted. So public handwashing facility would include situations where a lavatory or handwashing sink is shared by employees.

236 Gas Line Supports Can PVC plastic be used for gas line supports across a roof?

Land Use and Environmental Service Agency (Code Enforcement) NC Plumbing Code. Table of Contents

Land Use and Environmental Service Agency (Code Enforcement) NC Plumbing Code. Table of Contents Chapter 1 Administration Chapter 3 General Regulations Chapter 5 Water Heaters Chapter 7 Sanitary Drainage Chapter 9 Vents Chapter 11 Storm Drainage Policy Statements Table of Contents Chapter 2 Definitions

More information

Copyright 2017, ProVent Systems Inc., All Rights Reserved

Copyright 2017, ProVent Systems Inc., All Rights Reserved Copyright 2017, ProVent Systems Inc., All Rights Reserved Introduction to ProVent Systems A PVC Plastic Single Stack Waste and Vent System The ProVent System is a plumbing engineered single stack system

More information

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below)

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE APPENDIX C - ALTERNATE PLUMBING SYSTEMS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency authority

More information

NC Department of Insurance Office of the State Fire Marshal - Engineering Division 1202 Mail Service Center, Raleigh, NC

NC Department of Insurance Office of the State Fire Marshal - Engineering Division 1202 Mail Service Center, Raleigh, NC NC Department of Insurance Office of the State Fire Marshal - Engineering Division 1202 Mail Service Center, Raleigh, NC 27699-1202 919-647-0000 Guidance Paper: Acceptance of Licensed Architect or Engineer

More information

Amendments to the 2006 International Plumbing Code

Amendments to the 2006 International Plumbing Code Amendments to the 2006 International Plumbing Code Table of Contents, Chapter 7, Section 714; change to read as follows: Section 714 Engineered Drainage Design................... 65 Chapter 1, Administration

More information

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter X X X Adopt Entire Chapter as amended (amended sections listed below) X X X X X X

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter X X X Adopt Entire Chapter as amended (amended sections listed below) X X X X X X CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE CHAPTER 9 - VENTS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency authority and building application.)

More information

Amendments to the 2012 International Plumbing Code

Amendments to the 2012 International Plumbing Code Amendments to the 2012 International Plumbing Code The following sections, paragraphs, and sentences of the 2012 International Plumbing Code are hereby amended as follows: Standard type is text from the

More information

Applying the Building Code During Design

Applying the Building Code During Design Applying the Building Code During Design A Step-By-Step Process AIA Learning Units The Salt Lake City CSI Chapter is a Registered Provider with The American Institute of Architects Continuing Education

More information

City of Rohnert Park When Permits are Required

City of Rohnert Park When Permits are Required Permits are required as provided below based on the applicable code governing the trades involved in a building project. In some instances more than one trade may be involved in a project so be sure to

More information

GRAY WATER SYSTEMS FOR RESIDENTIAL BUILDINGS

GRAY WATER SYSTEMS FOR RESIDENTIAL BUILDINGS INFORMATION BULLETIN / PUBLIC - PLUMBING CODE REFERENCE NO.: LAMC 94.1502.0 Effective: 01-01-2017 DOCUMENT NO.: P/PC 2017-012 Revised: Previously Issued As: P/PC 20014-012 GRAY WATER SYSTEMS FOR RESIDENTIAL

More information

Recommended Amendments to the 2015 International Plumbing Code North Central Texas Council of Governments Region

Recommended Amendments to the 2015 International Plumbing Code North Central Texas Council of Governments Region Recommended Amendments to the 2015 International Plumbing Code North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2015 International Plumbing Code

More information

Advanced Ventilation for Residential applications FBC Res 2010.

Advanced Ventilation for Residential applications FBC Res 2010. Advanced Ventilation for Residential applications FBC Res 2010. Course Description Review of the Residential Ventilation requirements in the Florida Building Code, Residential 2010. I. Introduction Dean

More information

Chapter 1: Application and Administration

Chapter 1: Application and Administration Chapter 1: Application and Administration General Comments This chapter provides provisions regarding the purpose, scope, application, and administration of subsequent requirements of ICC 500. In addition

More information

The Inspection Process. Waxhaw N.C.

The Inspection Process. Waxhaw N.C. The Inspection Process In Waxhaw N.C. This information is provided by the Waxhaw Enforcement Division to assist you in the progression of your project. Nothing in this document should be considered "Code"

More information

ORDINANCE. APPROVED EMERGENCY: (Yes) (No) VETOED: Date

ORDINANCE. APPROVED EMERGENCY: (Yes) (No) VETOED: Date ORDINANCE AN ORDINANCE OF THE COMMISSION OF KNOX COUNTY, TENNESSEE RESCINDING ARTICLE III. CABO ONE- AND TWO-FAMILY DWELLING CODE, SEC. 10-56, SEC. 10-57 AND SEC. 10-58 AND ADOPTING THE 2006 INTERNATIONAL

More information

Read Only Copy Not For Distribution. Chapter 17. Private Potable Water Supply Systems 17.1 GENERAL REGULATIONS 17.2 QUANTITY OF WATER REQUIRED

Read Only Copy Not For Distribution. Chapter 17. Private Potable Water Supply Systems 17.1 GENERAL REGULATIONS 17.2 QUANTITY OF WATER REQUIRED Chapter 17 Private Potable Water Supply Systems 17.1 GENERAL REGULATIONS 17.1.1 Applicability The regulations in this chapter apply to any private potable water supply system where plumbing fixtures are

More information

PRESCRIPTIVE COMPLIANCE METHOD

PRESCRIPTIVE COMPLIANCE METHOD CHAPTER 3 PRESCRIPTIVE COMPLIANCE METHOD [B] SECTION 301 GENERAL 301.1 Scope. The provisions of this chapter shall control the alteration, repair, addition and change of occupancy of existing structures,

More information

2015 IPC Design, Installation and Inspection Principles IPC Design, Installation and Inspection Principles

2015 IPC Design, Installation and Inspection Principles IPC Design, Installation and Inspection Principles Description 2015 IPC Design, Installation and Inspection Principles Based on the 2015 International Plumbing Code (IPC ) The 2015 International Plumbing Code (IPC ) continues to emphasize both prescriptive

More information

Application for Commercial Plan Review and Building Permit. Address:

Application for Commercial Plan Review and Building Permit. Address: City of Warrenton 200 West Booneslick Warrenton, MO 63383 : 636-456-3535 Fax: 636-456-1336 www. war r ent o n- mo.org Application for Commercial Plan Review and Building Permit PERMIT# Purpose: Commercial

More information

Training Certification Categories

Training Certification Categories Training Certification Categories Residential Residential Building Inspector structures are free from hazardous structural conditions and comply with the UCC. Duties include inspection of footings and

More information

PLUMBING FIXTURES. I. The following guideline shall be used when determining the minimum required number of the plumbing fixtures:

PLUMBING FIXTURES. I. The following guideline shall be used when determining the minimum required number of the plumbing fixtures: INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LABC Sec. 2901 Effective: 7-21-03 DOCUMENT NO. P/BC 2002-095 Revised: Previously Issued As: none PLUMBING FIXTURES Section 2901 of the Building

More information

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018)

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018) BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018) PERMIT SUBMITTAL CHECKLIST: Signed and completed Building Permit application form. A separate Electrical permit is required from

More information

RESIDENTIAL FIRE SERVICE METERS Addendum #1

RESIDENTIAL FIRE SERVICE METERS Addendum #1 109 WATER METERS (Addendum #1) 109.1 GENERAL All meters to be used for billing purposes shall be provided by the Water Utility. The Water Utility reserves the right to read, inspect, test or replace the

More information

Water Service Inspection Checklist

Water Service Inspection Checklist Water Service Piping Inspection 4 ;ection P2902 Protection of Potable Water Supply Section P2903 Water-supply System Section P2906 Materials, Joints and Connections Section P2907 Changes in Direction Section

More information

RESIDENTIAL CONSTRUCTION New Dwellings and Additions

RESIDENTIAL CONSTRUCTION New Dwellings and Additions How to Obtain a Building Permit For RESIDENTIAL CONSTRUCTION New Dwellings and Additions MIAMI COUNTY, KANSAS CODE SERVICES DEPARTMENT 201 South Pearl Street, Suite 201 Paola, Kansas 66071-1777 Phone:

More information

SPARTANBURG COUNTY BUILDING CODES DEPARTMENT

SPARTANBURG COUNTY BUILDING CODES DEPARTMENT SPARTANBURG COUNTY BUILDING CODES DEPARTMENT PLAN REVIEW CHECK LIST REQUIREMENTS FOR COMMERCIAL BUILDING PERMITS Plan Review Coordinator Kris Brannon 864-596-3180 366 N. Church St Room 500 Spartanburg,

More information

Educational Course Application

Educational Course Application STATE OF WISCONSIN Department of Safety and Professional Services Educational Course Application Personal information you provide may be used for secondary purposes [Privacy Law, s. 15.04(1)(m)]. Safety

More information

Administrative Changes

Administrative Changes Revised 11/29/06 Knox County Residential Building Codes Significant Changes From The 1995 CABO One And Two Family Dwelling Code To The 2006 International Residential Code All one and two family dwellings

More information

One and Two Family Additions

One and Two Family Additions One and Two Family Additions An addition to a house, duplex, garage, or an accessory structure requires a building permit prior to performing any construction. Building Department & Permit Office Mon-Fri

More information

Analysis of Changes for the 5 th Edition (2014) of the Florida Codes

Analysis of Changes for the 5 th Edition (2014) of the Florida Codes Analysis of Changes for the 5 th Edition (2014) of the Florida Codes Changes to the Florida Building Code, Existing Building This Analysis of Changes for the 5 th Edition (2014) of the Florida Codes is

More information

Building/Zoning Permit Fee Structure

Building/Zoning Permit Fee Structure SECTION A - Calculation of Fees 1. Square Foot Basis The square footage shall be calculated on the out-to-out dimensions of the building or structure and shall include all areas, whether finished or unfinished,

More information

STORM DRAINAGE CHAPTER 11

STORM DRAINAGE CHAPTER 11 CHAPTER 11 STORM DRAINAGE SECTION 11 GENERAL 11.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation of storm drainage. 11.2 Where required. All roofs,

More information

PORT OF SAN FRANCISCO PLUMBING CODE. Based on the 2010 California Plumbing Codes

PORT OF SAN FRANCISCO PLUMBING CODE. Based on the 2010 California Plumbing Codes 2010 PORT OF SAN FRANCISCO PLUMBING CODE Based on the 2010 California Plumbing Codes 2010 Port of San Francisco Plumbing Code The complete 2010 Port of San Francisco Plumbing Code adopts and amends the

More information

2007 Title 24 Accessibility Code Updates and ADA Issues

2007 Title 24 Accessibility Code Updates and ADA Issues 2007 Title 24 Accessibility Code Updates and ADA Issues C.A.S.H. Workshop June 2007 Introduction Update on ADA Certification of the California Building Code Overview of significant changes to accessibility

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING SECTION 221316 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following soil and waste, sanitary drainage and vent piping inside the building: 1. Pipe, tube,

More information

2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES)

2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) 2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Reproduce the following data on the building plans sheet 1 or 2) Name of Project: Address:

More information

Permit Requirements: Building Codes: The City of Clanton has adopted the following codes which are enforced by the Building Department:

Permit Requirements: Building Codes: The City of Clanton has adopted the following codes which are enforced by the Building Department: Permit Requirements: Any owner, authorized agent, or contractor who desires to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install,

More information

Commercial Remodel Permit

Commercial Remodel Permit Commercial Remodel Permit Zoning requirements Staff recommends always verifying the zoning requirements for your project before deciding to build. Warrensburg has eleven separate zoning districts, each

More information

TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit:

TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit: TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION 355-7575 Ext. 395 Needed to Obtain Permit: 1. Building Permit Application, and/or residential plumbing permit application, as applicable, to be

More information

2010 California Green Building Standards Code: Nation s First Mandatory Statewide Standards Code to Green Construction and Fight Climate Change

2010 California Green Building Standards Code: Nation s First Mandatory Statewide Standards Code to Green Construction and Fight Climate Change 2010 California Green Building Standards Code: Nation s First Mandatory Statewide Standards Code to Green Construction and Fight Climate Change Continuing to lead the way in the fight against climate change

More information

Article 10 - ADMINISTRATIVE SECTION

Article 10 - ADMINISTRATIVE SECTION Article 10 - ADMINISTRATIVE SECTION 10.1 TITLE These Administrative Regulations along with the requirements included in the 2005 Edition of the National Electrical Code (NFiPA-70-2005) as approved by the

More information

CHECKLIST Inspecting a Garage

CHECKLIST Inspecting a Garage CHECKLIST Inspecting a Garage By Ben Gromicko This section deals with the details of the garage or carport inspection that may be performed. At the end of this section, you shall be able to: describe the

More information

PRESCRIPTIVE COMPLIANCE METHOD

PRESCRIPTIVE COMPLIANCE METHOD CHAPTER PRESCRIPTIVE COMPLIANCE METHOD 3 SECTION 301 GENERAL 301.2 Building materials. Building materials shall comply with the requirements of this section. 301.2.1 Existing materials. Materials already

More information

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp,

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp, TITLE 14 CHAPTER 10 PART 4 HOUSING AND CONSTRUCTION ELECTRICAL CODES 2011 NEW MEXICO ELECTRICAL CODE 14.10.4.1 ISSUING AGENCY: The Construction Industries Division of the Regulation and Licensing Department.

More information

CLASS K ORDINANCE MENDOCINO COUNTY PLANNING AND BUILDING SERVICES CHAPTER REGULATIONS FOR LIMITED DENSITY RURAL DWELLINGS

CLASS K ORDINANCE MENDOCINO COUNTY PLANNING AND BUILDING SERVICES CHAPTER REGULATIONS FOR LIMITED DENSITY RURAL DWELLINGS CLASS K ORDINANCE MENDOCINO COUNTY PLANNING AND BUILDING SERVICES CHAPTER 18.23 REGULATIONS FOR LIMITED DENSITY RURAL DWELLINGS Sec. 18.23.010 Authority. This chapter is adopted in accordance with the

More information

Sonoma County Code Chapter 7A

Sonoma County Code Chapter 7A Limited Density Owner- Built Rural Dwellings DeWayne Starnes, P.E., C.B.O. County of Sonoma Aka: Class K Sonoma County Code Chapter 7A www.hcd.ca.gov/codes/shl/shlarticle8.pdf d / hl/shla l df Problems

More information

Chapter 2 Definitions. Chapter 2 Definitions COMBINATION WASTE AND VENT SYSTEM.

Chapter 2 Definitions. Chapter 2 Definitions COMBINATION WASTE AND VENT SYSTEM. BEDROOM. A room that can be used for sleeping and that: a. For site-built s has a minimum of 70 square feet (6.50 m 2 ) of conditioned space; b. For manufactured homes is constructed according to the standards

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 22 1316 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

Building Regulations; Construction 11

Building Regulations; Construction 11 Building Regulations; Construction 11 b. Ceilings or roofs shall have a minimum of an "R" factor of 12; and c. Where the roof serves also as the finished ceiling a vent space of two inches shall be required

More information

GUIDELINES FOR SEPTIC SYSTEM DESIGN

GUIDELINES FOR SEPTIC SYSTEM DESIGN GUIDELINES FOR SEPTIC SYSTEM DESIGN Single Family Residential For multi family or commercial buildings, Or If in the Oakdale area, contact the Department of Environmental Resources Regarding septic system

More information

A. Codes and Standards that are standard at the University. C. Coordinate cleanout locations with Architect.

A. Codes and Standards that are standard at the University. C. Coordinate cleanout locations with Architect. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

City of Des Moines. Permit and Development Center 602 Robert D Ray Drive Des Moines, IA Phone: Fax:

City of Des Moines. Permit and Development Center 602 Robert D Ray Drive Des Moines, IA Phone: Fax: City of Des Moines Permit and Development Center 602 Robert D Ray Drive Des Moines, IA 50309 Phone: 515-283-4200 Fax: 515-283-4270 This Code Analysis Form must be completed and returned with the Building

More information

The following is required for a complete permit submittal for each unit.

The following is required for a complete permit submittal for each unit. P: (847)810-3502 OR (847)810-3503/3521, F: (847)615-4383 MULTI-FAMILY OR COMMERCIAL ADDITION OR ALTERATION PERMIT REQUIREMENTS The following is required for a complete permit submittal for each unit. MULTI-FAMILY

More information

CHAPTER 3 GENERAL REGULATIONS

CHAPTER 3 GENERAL REGULATIONS CHAPTER 3 GENERAL REGULATIONS SECTION 301 GENERAL 301.1 Scope. The provisions of this chapter shall govern the general regulations regarding the installation of plumbing not specific to other chapters.

More information

City of Jacksonville Development Guide Building Permits

City of Jacksonville Development Guide Building Permits City of Jacksonville TX City of Jacksonville Development Guide Building Permits A publication to help understand the Building Permit process in the City Jacksonville. Building Department 2011 J Revised

More information

Manufactured Buildings And The Electrical Code

Manufactured Buildings And The Electrical Code 2017 NCDOI Code College Electrical Series Manufactured Buildings And The Electrical Code October 31, 2017 1 Mike Hamm, PE Chief Building Code Consultant NC Department of Insurance Office of State Fire

More information

TOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ FAX

TOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ FAX TOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ 08014 856-467-3626--- FAX 856-467-9260 Application for Certificate of Occupancy for Change of Occupancy Pursuant to Chapter 119 of the Township

More information

GUIDELINES FOR SANITARY DESIGN AND CONSTRUCTION OF MILK PRODUCTS PLANTS (rev )

GUIDELINES FOR SANITARY DESIGN AND CONSTRUCTION OF MILK PRODUCTS PLANTS (rev ) Milk and Dairy Food Safety Branch 1220 N Street, Sacramento, CA 95814 GUIDELINES FOR SANITARY DESIGN AND CONSTRUCTION OF MILK PRODUCTS PLANTS (rev. 10-20-2011) The outline below lists sanitary requirements

More information

Code Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617)

Code Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) Code Requirements for Existing Buildings R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS) was established in 1945 and currently

More information

SECTION PLUMBING FIXTURES

SECTION PLUMBING FIXTURES SECTION 15440 - PLUMBING FIXTURES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, are a part of this Section. 1.02 SUMMARY A.

More information

Division II Contractors

Division II Contractors Division II Contractors (d) "Sheet metal contractor" means a contractor whose services are unlimited in the sheet metal trade and who has the experience, knowledge, and skill necessary for the manufacture,

More information

PLANS REVIEW CRITERIA - COMMERCIAL BUILDINGS

PLANS REVIEW CRITERIA - COMMERCIAL BUILDINGS PLANS REVIEW CRITERIA - COMMERCIAL BUILDINGS NOTE: Building Code compliance is the obligation of design professionals and/or contractors. Plan review and inspection guidelines are to be used to ensure

More information

The following is required for a complete permit submittal for each unit.

The following is required for a complete permit submittal for each unit. P: (847)810-3503 OR (847)810-3503/3521, F: (847)615-4383 NEW MULTI-FAMILY DWELLING OR COMMERCIAL PERMIT REQUIREMENTS The following is required for a complete permit submittal for each unit. NEW MULTI-FAMILY

More information

Application for Zoning Certificate and/or Building Permit

Application for Zoning Certificate and/or Building Permit Application for Zoning Certificate and/or Building Permit 1. Fill out the Zoning Application and NIRA Application (if applicable) and return it to the Harrison Township Zoning Office. 2. Please allow 10

More information

HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS

HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS St. Louis County Department of Public Works Division of Code Enforcement HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS This guide is intended to provide the homeowner or contractor with the

More information

GRAY WATER SYSTEMS (Reference California Plumbing Code Chapter 16 and 16A) Revised: 6/11/14

GRAY WATER SYSTEMS (Reference California Plumbing Code Chapter 16 and 16A) Revised: 6/11/14 Planning and Building Department 525 San Anselmo Avenue Building Division San Anselmo, CA 94960 Phone: (415) 258-4616 Fax: (415) 454-4683 GRAY WATER SYSTEMS (Reference California Plumbing Code Chapter

More information

Hardin County Planning and Development Commission

Hardin County Planning and Development Commission Location by Climate Zone: Hardin County (per Table N1101.2), and the entire state of Kentucky is located in Climate Zone 4, the HDD is 4000 to 4999. Building Requirements; Building Thermal Envelope The

More information

Legalization of Dwelling Units Installed Without a Permit SCREENING FORM No fee to file

Legalization of Dwelling Units Installed Without a Permit SCREENING FORM No fee to file City and County of San Francisco Department of Building Inspection Edwin M. Lee, Mayor Tom C. Hui, S.E., C.B.O., Director Legalization of Dwelling Units Installed Without a Permit SCREENING FORM No fee

More information

Building Permits A Guide for Homeowners

Building Permits A Guide for Homeowners Building Permits A Guide for Homeowners Why Bother With a Building Permit? Building Permits provide the means for Building Officials to ensure the health, safety and welfare of building occupants. The

More information

CITY OF HAGERSTOWN PLANNING & CODE ADMINISTRATION DEPARTMENT. Submittal Requirements

CITY OF HAGERSTOWN PLANNING & CODE ADMINISTRATION DEPARTMENT. Submittal Requirements CITY OF HAGERSTOWN PLANNING & CODE ADMINISTRATION DEPARTMENT 1 East Franklin Street Phone: 301-790-4163 Third Floor Hagerstown, MD 21740 Fax: 301-791-2650 BUILDING PERMIT APPLICATION FOR RESIDENTIAL ACCESSORY

More information

GENERAL PLAN REVIEW REQUIREMENTS

GENERAL PLAN REVIEW REQUIREMENTS GENERAL PLAN REVIEW REQUIREMENTS Cover Letter A letter (or an authorized pre-printed form) authorizing CCIS to perform the Plan Review is required. CCIS performs plan reviews for the ICC International

More information

2016 CALGREEN RESIDENTIAL CHECKLIST MANDATORY ITEMS City of San Carlos - Building Division 600 Elm Street, San Carlos, CA Phone:

2016 CALGREEN RESIDENTIAL CHECKLIST MANDATORY ITEMS City of San Carlos - Building Division 600 Elm Street, San Carlos, CA Phone: 2016 CALGREEN RESIDENTIAL CHECKLIST MANDATORY ITEMS City of San Carlos - Building Division 600 Elm Street, San Carlos, CA 94070 Phone: 650-802-4261 PURPOSE: The residential provisions of the 2016 CalGreen

More information

LAWS AND RULES FOR SEWAGE TREATMENT, AND DISPOSAL SYSTEMS

LAWS AND RULES FOR SEWAGE TREATMENT, AND DISPOSAL SYSTEMS LAWS AND RULES FOR SEWAGE TREATMENT, AND DISPOSAL SYSTEMS 15A NCAC 18A.1900 NORTH CAROLINA DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES DIVISION OF ENVIRONMENTAL HEALTH ON-SITE WASTEWATER SECTION Law

More information

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES SECTION 15420 DRAINAGE AND VENT SYSTEMS PART 1 DESIGN DIRECTIVES 1.1 DESIGN CRITERIA A. All cleanouts above finished (accessible and non-accessible) ceilings shall be extended to the floor above. B. Do

More information

CUSTOMER ASSISTANCE GUIDE BUILDING PERMIT APPLICATION SUBMITTAL REQUIREMENTS COMMERCIAL AND MULTI-FAMILY

CUSTOMER ASSISTANCE GUIDE BUILDING PERMIT APPLICATION SUBMITTAL REQUIREMENTS COMMERCIAL AND MULTI-FAMILY CUSTOMER ASSISTANCE GUIDE BUILDING PERMIT APPLICATION SUBMITTAL REQUIREMENTS COMMERCIAL AND MULTI-FAMILY Please read all of the following information. The following is a check list. You must have a checkmark

More information

CITY OF CAMDENTON OFFICE OF THE BUILDING OFFICIAL Commercial Building & Architectural Review Permit Application

CITY OF CAMDENTON OFFICE OF THE BUILDING OFFICIAL Commercial Building & Architectural Review Permit Application CITY OF CAMDENTON OFFICE OF THE BUILDING OFFICIAL Commercial Building & Architectural Review Permit Application DATE: / / PERMIT # REQUEST FOR: NEW BUILDING ADDITION REMODEL PLUMBING ONLY ELECTRIC ONLY

More information

SECTION DRAINAGE AND VENT SYSTEMS CONSTRUCTION STANDARD

SECTION DRAINAGE AND VENT SYSTEMS CONSTRUCTION STANDARD PART 1: GENERAL 1.01 The design guidelines contained herein include the requirements for drainage and vent systems utilized at The University of Texas at Austin. It is the intention of this document to

More information

University of Delaware

University of Delaware University Contact: Energy & Engineering Group (302) 831-1744 SECTION 22 40 00_PLUMBING FIXTURES PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Water closets. 2. Urinals. 3. Lavatories. 4. Sinks. 5.

More information

II. IDENTIFICATION A. OWNER OR LESSEE ADDRESS (number, street, P. O. Box, Apt., etc.)

II. IDENTIFICATION A. OWNER OR LESSEE ADDRESS (number, street, P. O. Box, Apt., etc.) Montcalm County Department of Building Safety 211 W Main / Box 368 / Stanton, Michigan 48888 Phone 989-831-7394 * FAX 989-831-7392 mkalka@montcalm.us APPLICATION FOR BUILDING PERMIT AND PLAN EXAMINATION

More information

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT. A. ASME B31.1 (American Society of Mechanical Engineers) - Power Piping

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT. A. ASME B31.1 (American Society of Mechanical Engineers) - Power Piping SECTION 22 05 29 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes pipe and equipment supports, hangers, anchors, bases sleeves and the sealing of

More information

BERKELEY COUNTY ENGINEERING AND

BERKELEY COUNTY ENGINEERING AND BERKELEY COUNTY ENGINEERING AND BUILDING INSPECTIONS 400 West Stephen Street - Suite 202, Martinsburg, WV 25401 Telephone: 304-264-1966 Fax: 304-262-3128 Web Page: www.berkeleywv.org SWIMMING POOL REQUIREMENTS

More information

Repair or replace section of driveway, approach, or sidewalk that are a trip hazard.

Repair or replace section of driveway, approach, or sidewalk that are a trip hazard. City of Gibraltar Pre-Sale Inspection Report Checklist FLATWORK: Repair or replace section of driveway, approach, or sidewalk that are a trip hazard. EXTERIOR PROPERTY: Fences/Sheds/Retaining walls: Repair,

More information

Chapter 3: General Regulations

Chapter 3: General Regulations Chapter 3: General Regulations General Comments The content of Chapter 3 is often referred to as miscellaneous, rather than general regulations. Chapter 3 received that label because it is the only chapter

More information

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE - 268-5161 Residential Accessory Structures This information has been compiled for the benefit of any person

More information

Inspection of New One- and Two- Family Dwellings

Inspection of New One- and Two- Family Dwellings Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: permitservices@opkansas.org Inspection of New One- and Two- Family Dwellings Planning and Development

More information

BUILDING CODES & DESIGN CRITERIA

BUILDING CODES & DESIGN CRITERIA BUILDING CODES & DESIGN CRITERIA Adopted Building Codes: 2006 International Building Code (IBC) 2006 International Residential Code (IRC) 2006 International Mechanical Code (IMC) 2006 International Plumbing

More information

Residential Building Inspections

Residential Building Inspections Residential Building Inspections Foundations, Grade Beams, Pile Caps, Foundation Pads 1. All trenches or excavations and formwork shall be in accordance with the size(s) and configuration(s) as per approved

More information

ADMINISTRATION CHAPTER 1

ADMINISTRATION CHAPTER 1 CHAPTER 1 ADMINISTRATION PART 1 SCOPE AND APPLICATION SECTION 101 SCOPE AND GENERAL REQUIREMENTS 101.1 Title. This code shall be known as the Florida Building Code, Energy Conservation, and shall be cited

More information

2015 IBC Exit Systems

2015 IBC Exit Systems Objectives 2015 IBC Exit Systems Based on the 2015 International Building Code Upon completion, participants will be better able to: Determine those means of egress components that are defined as exits

More information

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD Fire Water Supply without a Purveyor Residential & Commercial STANDARD #D-003 EFFECTIVE 01-04-2016 1. PURPOSE 1.1. The California Fire Code (CFC) requires

More information

b. Nonfixed and movable fixtures, cases, racks, counters and partitions not over five (5) feet nine (9) inches high.

b. Nonfixed and movable fixtures, cases, racks, counters and partitions not over five (5) feet nine (9) inches high. Section 17.08.090 Permits. A. Permits Required. No person shall cause any work to be done, regulated by the technical codes, unless a permit has first been obtained. B. Except as specified in this code

More information

2015 IBC Update. Copyright 2014 International Code Council #1000PDF15 1

2015 IBC Update. Copyright 2014 International Code Council #1000PDF15 1 Goal 2015 IBC Update Based on the International Building Code (IBC ) The goal is to familiarize building officials, fire officials, plans examiners, inspectors, design professionals, contractors, and others

More information

2015 IBC Accessible Means of Egress

2015 IBC Accessible Means of Egress 2015 IBC Accessible Means of Egress Based on the 2015 International Building Code Description Upon completion, the participant will be able to apply the accessible means of egress provisions of Section

More information

Ontario s 2012 Building Code Division B, Part 7 Ontario Regulation 332/12

Ontario s 2012 Building Code Division B, Part 7 Ontario Regulation 332/12 Ontario s 2012 Building Code Division B, Part 7 Ontario Regulation 332/12 Notice: This e-learning module is intended for general information purposes only. It only highlights certain provisions of the

More information

CHAPTER 4 PLUMBING FIXTURES AND FIXTURE FITTINGS

CHAPTER 4 PLUMBING FIXTURES AND FIXTURE FITTINGS CHAPTER 4 PLUMBING FIXTURES AND FIXTURE FITTINGS 401.0 Materials General Requirements. 401.1 Quality of Fixtures. Plumbing fixtures shall be constructed of dense, durable, non-absorbent materials and shall

More information

Radon Vent Pipe System. Labeling Performance Indicators

Radon Vent Pipe System. Labeling Performance Indicators Section 6 Radon Vent Pipe Labeling Performance Indicators Radon Vent Pipe System Connected after sub-grade system installed Pipe cannot be trapped Provide space in chases Support at each floor level Discharge

More information

Title 15 BUILDINGS AND CONSTRUCTION

Title 15 BUILDINGS AND CONSTRUCTION Title 15 BUILDINGS AND CONSTRUCTION Chapters: 15.04 International Codes Adopted 15.08 Building Permits 15.12 Movement of Buildings Chapter 15.04 INTERNATIONAL CODE COMMISSION CODES Sections: 15.04.010

More information

SECTION PLUMBING PIPING SYSTEMS

SECTION PLUMBING PIPING SYSTEMS SECTION 15300 PLUMBING PIPING SYSTEMS PART 1 - GENERAL 1.01 SPECIAL NOTICE A. Each contractor shall read all relevant documents, become familiar with the job, the scope of work, type of general construction,

More information

The Building Codes A.R.E. Building Design and Construction Exam Prep

The Building Codes A.R.E. Building Design and Construction Exam Prep Know Thy Codes! The Building Codes Building Codes The Code of Hammurabi 4000bc Developed 19 th and 20 th c. Codes define what you can and can t do Allowable area and height based on degree of danger Fire

More information

1.04 SUBMITTALS PLUMBING FIXTURES

1.04 SUBMITTALS PLUMBING FIXTURES SECTION 15440 - PLUMBING FIXTURES PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information