WATER METER SPECIFICATIONS

Size: px
Start display at page:

Download "WATER METER SPECIFICATIONS"

Transcription

1 City of Langley WATER METER SPECIFICATIONS Page i January 2010 CONTENTS SECTION TITLE PAGE 1. Preamble 1 2. Definitions 1 3. Services to be Metered 2 4. Location of Meters 2 5. Meter Types 2 6. Registers 3 7. Remote Receptacles 3 7A. Remote Radio Read Equipment 4 8. Meter Selection 4 9. Dedicated Fire Services 5 9A. Water Meter Bypass Lines Installation Requirements Pipe and Appurtenances Inspection Procedure Temporary Water Services Water Meter Installation Form Standard Drawings 11

2 City of Langley Water Meter Specifications Page 1 1. Preamble The following specifications detail the City's requirements for the installation of meters on City water services. An applicant is responsible for the supply and installation of meters and associated piping, chambers and equipment on metered water services. The meter information must be provided to the City for our review and acceptance prior to the installation and activation of the service. The specifications detail acceptable water meter types, location and installation requirements. 2. Definitions ANSI: ASTM: AWWA: Activation: American National Standards Institute. American Society for Testing and Materials. American Water Works Association Opening of the service valve to permit the flow of water. Applicant: A person, company or agency that makes application for a water service from the City water system as required by the City's Waterworks Regulation Bylaw City The municipal area comprised within the boundaries of the City of Langley. Director of Engineering, Parks and Environment Parks and Environment of the City and his designates. The Director of Engineering, Engineer: A professional engineer registered in the province of British Columbia practicing in the field of Civil or Mechanical Engineering. FM: Factory Mutual Engineering and Research Organization, a research and testing agency accepted by the Insurance Industry. UL: Underwriters' Laboratories, a research and testing agency accepted by the Insurance Industry. Water Bylaw: Refers to the City of Langley Waterworks Regulation Bylaw 2404 as amended.

3 City of Langley Water Meter Specifications Page 2 3. Services to be Metered The Waterworks Regulation Bylaw identifies services that require meters. This includes but is not limited to all property intended for residential, commercial, industrial, institutional and agricultural or public use. All services to such properties including fire, domestic services and water meter bypass services shall have meters. 4. Location of Meters Meters shall be placed at the interface between the City and private water system. In most circumstances the interface occurs at the property line of the site within the municipal right-of-way. Alternate water meter locations must be approved by the Director of Engineering, Parks and Environment. Where a City Water main is within private property in a right-of-way, place the meter within the right-of-way at the boundary line. 5. Meter Types There are two types of cold water meters accepted for use by the City. These are positive displacement and compound types. The actual meter or combination of meters accepted for use must accurately account for the total water use of the property serviced. All meters must be new; used or reconditioned meters are not acceptable and conform to NSF 61 standards. Positive Displacement meters are to be either oscillating piston or nutating disc type to AWWA C-700. Meters are to have a bronze case with cast iron or plastic frost protection cover. Meters 38mm in size are to have oval two bolt flanged ends. Compound meters are to conform to AWWA C-702. All compound meters are to have a bronze case and flanged connections. Meters 50mm in diameter are to have oval two bolt flanges. Acceptable meters are: Neptune (Jan. 1, 2008) Alternative meters may be accepted at the discretion of the Director of Engineering, Parks and Environment.

4 City of Langley Water Meter Specifications Page 3 6. Registers All meters are to have direct reading, sealed encoder and remote registration. All registers are to have a sweep test hand or electronic flow indication. All registers shall be minimum 6-wheel high-resolution type. The unit of measure shall be cubic metres (m 3 ). Registers must be new; used or reconditioned registers are not acceptable. Registers must be compatible with interrogation equipment used by the City. Registers shall have a receptacle that will allow electronic reading of the meter with a portable data acquisition unit. The receptacle shall be designed for wall mounting or mounting in the meter chamber lid, as appropriate. The unit must, in a digital format simultaneously encode at least six significant digits of the meter reading for transmission through the remotely located receptacle. A unique meter identification number must also be provided with each read. Registers must be easily upgraded to Automated Meter Reading (AMR) by substitution of the remote receptacle with a Radio Meter Interface Unit. All registers must be provided with moisture protection for internal components when operating under flooded pit conditions. The materials employed for contacts and connectors must inhibit corrosion and must suffer minimal effect from environmental conditions to which they are exposed. 7. Remote Receptacles Remote receptacles must be available in both wall and pit mount style. No Identity number storage is permitted at the remote receptacle. The materials employed must be corrosion resistant, resistant to ultraviolet degradation, unaffected by weather or condensation. Pit mounted receptacles must be mounted to the meter box lid mounted in a single 45mm diameter hole. Wall mounted receptacles must be designed for terminal screw connection before being fastened to the wall. The design of the unit must be such that it provides for mechanical and electrical connection between the receptacle and interrogation equipment. Interrogation must be achieved by inductive coupling without physical connection of the reading device (touch pad), or for radio reads (R900i technology).

5 City of Langley Water Meter Specifications Page 4 7A. Remote Radio Read Equipment Installations for Industrial/Commercial/Institutional and Multi-family residential properties shall be radio read type meters. Accepted Devices: Neptune E-Coder R900i For Pit applications must be Neptune E-Coder R900i pit version c/w external antenna 7.62 m in length. 8. Meter Selection The type or combination of types of meters selected for recording water consumption from a service must accurately record consumption for the expected range of flow. The size selected must ensure pressure losses are within acceptable limits and provide long meter life. The Applicant s Engineer must ensure that the meter selection and installation requirements are adequate for the design application. A meter may be one pipe size smaller than the service except for bypass meters. The Applicant s Engineer must ensure that the reduction neither compromises the operating range of the meter nor results in unacceptable head losses. The size selected shall ensure pressure losses are within acceptable limits and provide long meter life. The following table provides a guide for acceptable meter types and sizes for a range of uses and flows. Flow rates are in accordance with AWWA specifications. WATER USE Domestic LAND USE Commercial Institutional Industrial mm SIZE in 5/8 ¾ 1 1 ½ ACCEPTABLE METER TYPE Positive Displacement Positive Displacement Positive Displacement Positive Displacement Positive Displacement Compound Compound Compound Compound FLOW RATES(m3/h) Norm Op Normal Max Cont Range Flow Flow Irrigation Bulk Water Use Agricultural Golf Courses Some Industrial Uses ½ Positive Displacement Compound Compound Compound Compound

6 City of Langley Water Meter Specifications Page 5 9. Dedicated Fire Services Fire services are to be metered to detect unauthorized use and leaks in the system. Provide all fire services with a detector check valve with meter trim package in combination with an appropriately sized "tattle tail" displacement type meter on a bypass. Install tattle tail meters in accordance with these specifications. An approved double detector check assembly with a "tattle tail" meter may be used in place of the detector check valve, to satisfy fire sprinkler system back-flow prevention requirements. 9A. Water Meter Bypass Lines All water meter bypass lines shall have a line-sized water meter installed to detect unauthorized use. The meter shall be equipped with a register (see Section 6) and Radio Read transmitter (see Section 7A). 10. Installation Requirements Installation requirements are summarized on the following table and illustrated on the appended typical drawings. Size Type By pass* Strainer Chamber 2 mm Required Size Required Type Size mm Model 16 Positive No - No Meter 300x500 Brooks 37 Displacement Box 19 Positive No - No Meter 300x500 Brooks 37 Displacement Box 25 Positive No - No Meter 425x750 Brooks 66 Displacement Box 38 Positive Displacement Yes 1 25 mm No Meter Box 600x900 AEC Compound Yes 1 25 mm Yes Vault 1220x2000 AEC Compound Yes 1 50 mm Yes Vault 3260x1760 AEC Compound Yes 1 50 mm Yes Vault 3260x1760 AEC Detector Check No - No Vault 1220x2000 AEC Detector Check No - No Vault 3260x1760 AEC 3151 Note * A by pass is not required for dedicated irrigation meters. Note 1 Bypass size to be determined by Applicant s Engineer. Note 2 Chamber Lids are to be pre-drilled with a 45mm dia. remote receptacle hole. Meter pits should not be installed in vehicular traveled areas. Installations for meters not shown on the above table must be designed by the applicant's engineer.

7 City of Langley Water Meter Specifications Page 6 Installation and Piping Requirements: Contractor shall install meters horizontally with register casings plumb, facing upward. Where installed in a meter box, centre meter in box. All connecting piping valves and fittings shall be equal to the diameter of the meter for a distance of at least 3 pipe diameters up stream of the meter. Where required, contractor shall install strainers immediately upstream of the meter using a flanged connection. Strainers shall be straight type from the same manufacture and size as the meter. Contractor shall provide isolation valves upstream and downstream of the meter, 50mm and larger, to allow removal of meter and strainer cases. Where required, install one valve upstream and one valve downstream of the water meter on bypasses. Provide a lockwing on the operating nut of the bypass valves. For all compound meter installations the contractor shall provide a straight section of horizontal pipe, five pipe diameters in length, between the strainer and the upstream isolating valve or any other appurtenances (i.e. bends, elbows, reducers, etc.). A straight section of horizontal a minimum of three pipe diameters in length shall be provided after the water meter. In the absence of a test plug on the meter case, install a testing tee with a 50mm diameter threaded nipple and cap between the meter and the downstream isolating valve. For meters 50mm in diameter and larger the contractor shall provide a mechanical flange adapter on the downstream side of the meter to provide flexibility for meter and strainer case removal. Contractor must provide adequate insulation for the meter in applications where there is a possibility of the meter freezing. Contractor shall support all meters, valves and bypasses within chambers with adjustable pipe stands. Bricks, concrete or wood blocking are not acceptable means of support.

8 City of Langley Water Meter Specifications Page 7 Receptacle Installation: A remote reading receptacle(s) shall be installed by the contractor. A maximum of two registers may be networked per receptacle. In non-traffic areas mount remote register receptacles in the meter box, vault or chamber lid in accordance with the manufacturer's instructions. Where the lid is in a high traffic area, mount the receptacle on the exterior wall of the serviced building or in a Brooks #37 Box complete with metal lid adjacent to the chamber away from vehicular traffic. Remote wiring connections shall be either factory or field sealed to ensure connections are waterproof. Field seals shall be in accordance with the manufacturer's instructions. Wall mounted remote receptacles must be located at or near 1.2 metres above grade and easily accessible for reading. The Communication cable from the meter to the receptacle must be installed in accordance with the manufacture s instructions. Wire to be run in horizontal or vertical directions only. Where possible, run wire inside the building. Provide 10mm diameter hole sealed with sealing compound at external face to receptacle. 11. Pipe and Appurtenances Piping and Fittings All piping, pipe fittings and jointing methods must comply with the latest requirements of the B.C. Plumbing Codes and AWWA Standards. Valves All valves are to be suitable for buried service. Valves on domestic services up to 50mm in diameter shall be bronze ball or cylinder corporation style valves meeting AWWA C Valves shall have rubber O-ring seals. Connections shall be threaded, compression type or lockwing on the operating nut and case of all bypass valves. Valves on domestic services 75mm to 250mm in diameter are to be cast iron, resilient seat, NRS gate valves to AWWA C-509 with flanged ends. Stem seal to be O-ring type. Actuation of buried valves or valves in vaults shall be by a standard 50mm square operating nut. Valves within man entry chambers shall be operated by hand wheel. Provide a Robar style valve box over buried valves. Fire Service valves within vaults or chambers shall be resilient seat, OS&Y or NRS gate valves to AWWA 509. Detector Check Valves An approved detector check valve or double detector check valves, with meter trim package are to comply with AWWA C-510. Detector check valves for fire service use must be FM and UL approved.

9 City of Langley Water Meter Specifications Page 8 Flange Adapters Mechanical Flange adapters for 38mm to 200mm sizes shall be to AWWA C219. Connections between flanged fittings and Ductile Iron or Steel piping may be made with "Uniflange adapters. Bolts and Nuts Bolts and nuts are to be stainless steel to ASTM F-599 or F-731 for bolts and ASTM F574 or F836 for heavy hex nuts. Rolled threads, fit and dimension to AWWA C-111. Communication Conduit Communication conduit is to be Schedule 40 rigid PVC with solvent welded joints. Minimum cover required over the conduit is 600mm. Minimum radius for a 90 degree bend is 400mm. There shall be no more than two 90 degree bends between the meter box or vault and the terminal junction box. Use 3mm braided nylon rope for the pull string. Secure the pull string at both entrances to conduit to prevent accidental withdrawal. Cleat surface mounted conduit to the exterior of the building at 750mm intervals. The maximum length of conduit without a pull box is 60m. Pull boxes are to be concrete, Brooks 37 style with steel lid. Meter Boxes The box, vault or chamber shall be pre-cast concrete to the dimensions provided in the table above. The minimum head room for man entry chambers shall be 2.0 metres. Boxes shall have steel or iron lids capable of withstanding H-20 loading x2000 vaults shall have two hinged galvanized steel lids providing a 880mm x 1790mm opening x Vaults shall have three hinged galvanized steel lids providing a 810mm x 2590mm opening. Lids of man entry chambers shall be l200mm x 1200mm or 1500mm x 1500mm square split hinged galvanized steel. Vault and chamber lids shall be capable of withstanding H-20 loading. Lids for boxes, vaults and chambers in non-traffic areas shall have pre-drilled 45mm diameter hole for remote reading receptacles. Damp proof the exterior of all man entry chambers by applying asphalt emulsion coating to all exterior surfaces. Make construction joints water tight with an appropriate sealant. Access lids, latches and ladders must comply with the most current requirements of the Workers Compensation Board.

10 City of Langley Water Meter Specifications Page Inspection Procedure A request for water service is initiated by application for a Plumbing Permit through the City s Development Services Department. The Applicant's Engineer shall determine the size of the meter and shall select the appropriate meter type for the intended use in accordance with the City s Water Meter Specifications. Plans submitted, as part of the Plumbing Permit Application must indicate the meter size, type and chamber location. The plans shall also indicate the expected range of flows and the average expected flow for the proposed installation. For non-typical meter installations, or for meters of 200mm diameter and greater, the applicant's Engineer must provide detailed drawings giving complete details of the installation. Applicant must provide information set forth on the City s water meter installation form provided with these specifications prior to the installation of the meter. The City s Engineering and Development Services Departments will inspect the meter installation to ensure conformance to this specification and the B.C. Plumbing Code. Upon approval of the installation, the City Operations Department will lock the bypass valve (where applicable), take the initial meter reading and activate the service. 13. Temporary Water Services Temporary water services required during construction phase of a development project must also be metered. Meters installed on temporary services are to conform to the requirements of this specification in all respects. The meter must be in place prior to the activation of the service. Temporary services may only be deactivated by City Operations personnel. Contact the City Engineering Department at prior to removing a meter from a temporary service.

11

12

13

14

15

16

17

City of Port Moody. Water Meter Specifications

City of Port Moody. Water Meter Specifications City of Port Moody Water Meter Specifications Engineering Division, Updated December 2015 City of Port Moody Water Meter Specifications 1. Preamble... 3 2. Definitions... 3 3. Services to be Metered...

More information

City of Port Moody. Water Meter Specifications

City of Port Moody. Water Meter Specifications City of Port Moody Water Meter Specifications Engineering Division, Updated August 2017 City of Port Moody Water Meter Specifications 1. Preamble... 3 2. Definitions... 3 3. Services to be Metered... 3

More information

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION SECTION 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 - GENERAL 1.1 SUMMARY A. This section supplements all sections in this division, including pipe, fittings, valves, and connections for sprinkler

More information

B. Stipulated Price (Lump Sum). If Contract is Stipulated Price Contract, payment for work is in this Section is included in total Stipulated Price.

B. Stipulated Price (Lump Sum). If Contract is Stipulated Price Contract, payment for work is in this Section is included in total Stipulated Price. Section 02526 PART 1 G E N E R A L 1.01 SECTION INCLUDES A. Water meters, submeters, and fire service meters. 1.02 MEASUREMENT AND PAYMENT A. Unit Prices 1. Measurement for water meters is on unit price

More information

CHINO VALLEY FIRE DISTRICT FIRE PROTECTION STANDARD

CHINO VALLEY FIRE DISTRICT FIRE PROTECTION STANDARD CHINO VALLEY FIRE DISTRICT FIRE PROTECTION STANDARD SPECIFICATIONS Establishing Minimum Standards for as Related To Fire Protection STANDARD # 103 REVISED 04/01/19 PAGES 7 SCOPE: These specifications shall

More information

SERVICE LINES, METERS AND APPURTENANCES

SERVICE LINES, METERS AND APPURTENANCES AUGUST02 SECTION 02646 SERVICE LINES, METERS AND APPURTENANCES PART 1 - GENERAL 1.1 DESCRIPTION A. This section concerns materials and installation of corporation stops, curb stops, service lines, meters,

More information

SPECIFICATIONS - DETAILED PROVISIONS Section Stainless Steel Sluice Gates C O N T E N T S

SPECIFICATIONS - DETAILED PROVISIONS Section Stainless Steel Sluice Gates C O N T E N T S SPECIFICATIONS - DETAILED PROVISIONS Section 11294 - Stainless Steel Sluice Gates C O N T E N T S PART 1 - GENERAL... 1 1.01 SUMMARY... 1 1.02 REFERENCES... 1 1.03 DEFINITIONS... 1 1.04 DESIGN REQUIREMENTS...

More information

Iron Check Valves & Y-Strainers Illustrated Index

Iron Check Valves & Y-Strainers Illustrated Index Iron Check Valves & Y-Strainers Illustrated Index Iron Body Swing Check Valve Bronze Mounted or All Iron 125 lb. SWP 200 lb. CWP Iron Body Swing Check Valve Bronze Mounted 250 lb. SWP 500 lb. CWP Lead

More information

SPECIFICATIONS FOR THE INSTALLATION OF REDUCED PRESSURE BACKFLOW PREVENTERS AND CONCRETE VAULTS FOR METERS 4 AND LARGER

SPECIFICATIONS FOR THE INSTALLATION OF REDUCED PRESSURE BACKFLOW PREVENTERS AND CONCRETE VAULTS FOR METERS 4 AND LARGER SPECIFICATIONS FOR THE INSTALLATION OF REDUCED PRESSURE BACKFLOW PREVENTERS AND CONCRETE VAULTS FOR METERS 4 AND LARGER Updated January 2018 RP-2 Installation Specifications 1. In W.H.U.D s service area

More information

This section includes materials and installation of ductile-iron pipe and fittings for potable and recycled water systems.

This section includes materials and installation of ductile-iron pipe and fittings for potable and recycled water systems. NORTH MARIN WATER DISTRICT STANDARD SPECIFICATIONS SECTION 15056 DUCTILE-IRON PIPE AND FITTINGS PART 1 GENERAL 1.01 DESCRIPTION This section includes materials and installation of ductile-iron pipe and

More information

UNIVERSITY OF MISSOURI Hydronic Energy Distribution 2016 Q1

UNIVERSITY OF MISSOURI Hydronic Energy Distribution 2016 Q1 GENERAL: The scope of this document is to provide instruction for the installation and testing of chilled water piping installed for the University of Missouri. DESIGN GUIDELINES: 1. Materials 1.1. Pipe

More information

452 Series Magnetic Drive Positive Displacement Disc Meters Size 1

452 Series Magnetic Drive Positive Displacement Disc Meters Size 1 Size 1 Features APPLICATIONS: Measurement of cold water for residential and small commercial applications where water volumes are low, and low flow sensitivity is important. CONFORMANCE TO STANDARDS: Hersey

More information

September 6, 2016 Page 1 of 5

September 6, 2016 Page 1 of 5 September 6, 2016 Page 1 of 5 1. SECTION 16100 Drawing E4.3, Note #39: Reference to the radio fire alarm panel and the fire station alerting master panel does not relate to the building fire alarm system.

More information

AMERICAN DARLING MARK

AMERICAN DARLING MARK 2 12 250 p.s.i.g. SERIES 2500 RESILIENT WEDGE GATE VALVE AMERICAN FLOW CONTROL AMERICAN DARLING MARK 73 2 FIRE HYDRANT It s What We Know. CONSTRUCTION UPPER O-RING SEALS can be replaced while the valve

More information

AMERICAN DARLING 5 1 /4" B-62-B FIRE HYDRANT

AMERICAN DARLING 5 1 /4 B-62-B FIRE HYDRANT AMERICAN DARLING 5 1 /4" B-62-B FIRE HYDRANT CONSTRUCTION PIPE PLUG-provides access to lubrication chamber. Pipe plug can be replaced with lubricating fitting to lubricate the rod threads and thrust washers.

More information

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows: SECTION 16130 (Master Template Final-05) ELECTRICAL BOXES PART 1 GENERAL 1.01 SECTION INCLUDES A. Provide boxes for electrical equipment and wiring devices as follows: 1. Wall and ceiling outlet boxes.

More information

1. Required Minimum Flow:

1. Required Minimum Flow: SECTION 6 6. 6.01 General The City of Castle Rock Water System Minimum Standards and Specifications are minimum base level performance, design, and construction standards used to maintain uniformity of

More information

EXHIBIT B. Notice of Non-Compliance

EXHIBIT B. Notice of Non-Compliance Page 1 of 6 EXHIBIT B Town of Flower Mound Large Residential and Commercial Water Meter Installation Policy 3-6 Compound or HP Turbine Meters Or 2 Compound Meter (06/20/05) The Town of Flower Mound has

More information

4 1 /2 MARK 73-5 AMERICAN FLOW CONTROL. It s What We Know. AMERICAN-DARLING FIRE HYDRANT AMERICAN-DARLING 4 1 /2 MARK 73-5 FIRE HYDRANT

4 1 /2 MARK 73-5 AMERICAN FLOW CONTROL. It s What We Know. AMERICAN-DARLING FIRE HYDRANT AMERICAN-DARLING 4 1 /2 MARK 73-5 FIRE HYDRANT AMERICAN-DARLING FIRE HYDRANT AMERICAN-DARLING FIRE HYDRANT AMERICAN FLOW CONTROL It s What We Know. CONSTRUCTION AMERICAN-DARLING FIRE HYDRANT OPERATING NUT Cast one-piece bronze operating nut. Design

More information

CITY OF WARRENVILLE STANDARD SPECIFICATIONS WATER MAIN, SANITARY SEWER AND STORM SEWER

CITY OF WARRENVILLE STANDARD SPECIFICATIONS WATER MAIN, SANITARY SEWER AND STORM SEWER CITY OF WARRENVILLE STANDARD SPECIFICATIONS WATER MAIN, SANITARY SEWER AND STORM SEWER WATER MAIN 1. All open cut water main shall be polyvinyl chloride plastic (PVC) pressure pipe per AWWA specification

More information

WATER METER & BACKFLOW PREVENTION DEVICE DESIGN & INSTALLATION MANUAL

WATER METER & BACKFLOW PREVENTION DEVICE DESIGN & INSTALLATION MANUAL WATER METER & BACKFLOW PREVENTION DEVICE DESIGN & INSTALLATION MANUAL 2018 Edition WATER METER & BACKFLOW PREVENTION PAGE i TABLE OF CONTENTS MAY 2018 1.0 INTRODUCTION... 1 2.0 DEFINITIONS... 3 3.0 WATER

More information

DIVISION 26 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL RELATED DOCUMENTS

DIVISION 26 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL RELATED DOCUMENTS PART 1 - GENERAL 01.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification sections, apply to work of this Section.

More information

2 5 0 P. S. I. G. AMERICAN DARLING 5 1 /4" B-84-B FIRE HYDRANT

2 5 0 P. S. I. G. AMERICAN DARLING 5 1 /4 B-84-B FIRE HYDRANT 2 5 0 P. S. I. G. AMERICAN DARLING 5 1 /4" B-84-B FIRE HYDRANT CONSTRUCTION OPERATING NUT-cast one piece bronze operating nut. Design of the operating thread permits slow closing of the hydrant valve,

More information

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers. SECTION 230529 - HANGERS AND SUPPORTS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Sleeves. 6. Mechanical sleeve seals. 7. Firestopping

More information

SECTION PUBLIC WATER SERVICE CONNECTIONS

SECTION PUBLIC WATER SERVICE CONNECTIONS SECTION 33 14 14 PUBLIC WATER SERVICE CONNECTIONS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe and fittings for water service connections to small commercial, light industrial, and residential

More information

American Flow control 2-12 Series 2500

American Flow control 2-12 Series 2500 American Flow control 2-12 Series 2500 Resilient wedge gate valve FLOW CONTROL Construction Ductile iron operating nut Provides strength and durability. Upper O-ring seals Can be replaced while the valve

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 22 1316 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

CONDUITS AND FITTINGS

CONDUITS AND FITTINGS CONDUIT AND FITTINGS Rigid Steel Conduit 3801 Rigid PVC Conduit 3803 HDPE Conduit 3803 Flexible Non Metallic Liquid Tight Conduit Type LFNC-B 3804 PVC Coated Urethane Lined Galvanized Rigid Steel Conduit

More information

ASTM C857 A -16 AASHTO H -20 (for vaults beneath roadways) ASTM C857 A-8 (for vaults beneath incidental light truck traffic)

ASTM C857 A -16 AASHTO H -20 (for vaults beneath roadways) ASTM C857 A-8 (for vaults beneath incidental light truck traffic) 1 Scope This specification outlines the minimum requirements for 5i 7i (56I 84I) vaults to be used for three-phase sectionalizing cabinets and metering equipment. This specification applies to all 5i 7i

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING SECTION 221316 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following soil and waste, sanitary drainage and vent piping inside the building: 1. Pipe, tube,

More information

Electrical Metallic Tubing (EMT) Fittings

Electrical Metallic Tubing (EMT) Fittings Suggested Specifications for Electrical Metallic Tubing (EMT) Fittings Series 2 Insulated EMT Connector (Raintight) (Compression Type) Series 20 EMT Coupling (Raintight) (Compression Type) Series 0 Pipe

More information

SOLICITATION OVERVIEW

SOLICITATION OVERVIEW Water Meters DUE: 9/22/14 SOLICITATION OVERVIEW The City of Irving is soliciting best value bids for: TITLE: Water Meters ITB Number: 022M-15F Commodity: 9991 Water Meters Due Date: 3:00 p.m., Monday,

More information

Town of Cornwall Water & Sewer Utility Corporation

Town of Cornwall Water & Sewer Utility Corporation Town of Cornwall Water & Sewer Utility Corporation Minimum Standard of Acceptability for Water, Sewer & Sprinkler Connections At the time of application for water, sewer and/or sprinkler service the applicant

More information

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 1.1. REFERENCE STANDARDS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification

More information

Copper-Type K soft Drawn 40, 50 HDPE 100 and larger

Copper-Type K soft Drawn 40, 50 HDPE 100 and larger 1.0 GENERAL 1.1 Scope 1.1.1 The work covered by this section involves the installation of water and sewer service connections and all other associated work. 1.2 Authorization 1.2.1 Do not install service

More information

SECTION 1101 TRAFFIC SIGNALS AND APPURTENANCES END OF SECTION

SECTION 1101 TRAFFIC SIGNALS AND APPURTENANCES END OF SECTION SECTION 1101 SIGNALS AND APPURTENANCES PART 1 GENERAL 1.4 SUBMITTALS E. Submit warranty for all supplied material and workmanship for a period of two years from final acceptance. The warranty must state

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 8/1/17 Update sections Materials and Special Requirements 3 F. 2. 4 H. 2.; 10. & 11(added) 6/15/16 Updated division

More information

SPECIFICATION. Category: Cold Water Meter Type: Ultrasonic Transit-Time Size: 2 12 Applicable AWWA Standard: C750. Version 2.18

SPECIFICATION. Category: Cold Water Meter Type: Ultrasonic Transit-Time Size: 2 12 Applicable AWWA Standard: C750. Version 2.18 SPECIFICATION Category: Cold Water Meter Type: Ultrasonic Transit-Time Size: 2 12 Applicable AWWA Standard: C750 Version 2.18 Master Meter, Inc. 101 Regency Parkway, Mansfield, TX 76063 T: 817-842-8000

More information

SECTION ALUMINUM GATES

SECTION ALUMINUM GATES P.O. Box 1058 370 South Athol Rd. Athol, Massachusetts 01331 Phone: (978) 249-7924 Fax: (978) 249-3072 SECTION ALUMINUM GATES PART 1 GENERAL 1.01 SCOPE OF WORK A. The CONTRACTOR shall furnish all labor,

More information

MATERIAL/MANUFACTURER SPECIFICATIONS FOR DISTRIBUTION WATER MAINS AND APPURTENANCES

MATERIAL/MANUFACTURER SPECIFICATIONS FOR DISTRIBUTION WATER MAINS AND APPURTENANCES MATERIAL/MANUFACTURER SPECIFICATIONS FOR DISTRIBUTION WATER MAINS AND APPURTENANCES REVISION April 2008 1 MATERIAL SPECIFICATIONS T.S. 1 GENERAL Materials incorporated in the finished work and used during

More information

TURBINE WATER & FIRE HYDRANT METERS. BID OPENING: Monday, March 24, 2014

TURBINE WATER & FIRE HYDRANT METERS. BID OPENING: Monday, March 24, 2014 Department of Finance City Hall Room 105A, 30 Church Street Rochester, New York 14614-1281 www.cityofrochester.gov Bureau of Purchasing PRINTED NAME OF BIDDER TURBINE WATER & FIRE HYDRANT METERS Invitation

More information

A. Codes and Standards that are Standard at the University: 1. AGA Compliance: LC 1-91 Interior Fuel Gas Piping Systems

A. Codes and Standards that are Standard at the University: 1. AGA Compliance: LC 1-91 Interior Fuel Gas Piping Systems PART 1: GENERAL 1.01 Purpose: This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is to

More information

University of Central Florida Main Campus. Domestic Water. Service and Meter Installations Requirements. Issued January 26 th, 2017.

University of Central Florida Main Campus. Domestic Water. Service and Meter Installations Requirements. Issued January 26 th, 2017. University of Central Florida Main Campus Domestic Water Service and Meter Installations Requirements Issued January 26 th, 2017 1 P a g e Table of Contents 1. GENERAL INFORMATION... 3 2. DEFINITIONS...

More information

PURCHASING SECTION Avenue, Surrey BC V3T 1V8 Tel: ADDENDUM #2

PURCHASING SECTION Avenue, Surrey BC V3T 1V8 Tel: ADDENDUM #2 PURCHASING SECTION 13450 104 Avenue, Surrey BC V3T 1V8 Tel: 604-590-7274 E-mail: purchasing@surrey.ca ADDENDUM #2 INVITATION TO TENDER (ITT) NO.: 1220-020-2017-004 TITLE: ADDENDUM ISSUE DATE: July 24,

More information

Electrical Metallic Tubing (EMT) Fittings

Electrical Metallic Tubing (EMT) Fittings Suggested Specifications for Electrical Metallic Tubing (EMT) Fittings Series 2 Insulated EMT Connector (Raintight) (Compression Type) Series 20 EMT Coupling (Raintight) (Compression Type) Series 0 Pipe

More information

KENT COUNTY WATER AUTHORITY. ERRATUM to Rules and Regulations of the Kent County Water Authority

KENT COUNTY WATER AUTHORITY. ERRATUM to Rules and Regulations of the Kent County Water Authority KENT COUNTY WATER AUTHORITY ERRATUM to Rules and Regulations of the Kent County Water Authority Section 4.9.1.1 Resilient Seat Gate 4 inch to 12 inch: Replace with the attached. Section 4.9.1.3 Tapping

More information

Water & Industrial Products Catalog

Water & Industrial Products Catalog Water & Industrial Products Catalog www.smith-blair.com info@smith-blair.com Phone: 800..9705 or 870.77.527 After Hours Number: 90.277.998 Fax: 800.8.792 or 870.77.52 EMERGENCY PHONE 90.277.998 In the

More information

SUPPLEMENTAL SPECIFICATIONS TO STANDARD SPECIFICATIONS FOR WATER MAIN AND SERVICE LINE INSTALLATION NO. 2611

SUPPLEMENTAL SPECIFICATIONS TO STANDARD SPECIFICATIONS FOR WATER MAIN AND SERVICE LINE INSTALLATION NO. 2611 Revised October 10, 2014 SUPPLEMENTAL SPECIFICATIONS TO STANDARD SPECIFICATIONS FOR WATER MAIN AND SERVICE LINE INSTALLATION NO. 2611 Water Main and Service Line Installation shall be in accordance with

More information

SECTION FIRE HYDRANTS

SECTION FIRE HYDRANTS SECTION 02080 FIRE HYDRANTS PART 1 - GENERAL 1.01 DESCRIPTION A. Work Specified The work specified shall include all labor, material, equipment, tools, services and incidentals necessary to furnish and

More information

SECTION BASIC FIRE SUPPRESSION MATERIALS AND METHODS. A. Section includes pipe, fittings, valves, and connections for sprinkler systems.

SECTION BASIC FIRE SUPPRESSION MATERIALS AND METHODS. A. Section includes pipe, fittings, valves, and connections for sprinkler systems. SECTION 210500 - BASIC FIRE SUPPRESSION MATERIALS AND METHODS PART 1 GENERAL 1.1 SUMMARY A. Section includes pipe, fittings, valves, and connections for sprinkler systems. B. Related Sections: 1. Section

More information

Bid Opportunity PLUMBING SYSTEMS Section Installation of Boiler Heating Systems Page 1 of 7 Centennial Pool, 90 Sinclair

Bid Opportunity PLUMBING SYSTEMS Section Installation of Boiler Heating Systems Page 1 of 7 Centennial Pool, 90 Sinclair Installation of Boiler Heating Systems Page 1 of 7 SECTION PAGE PART 1 GENERAL 2 1.1 General 2 1.2 Reference 2 1.3 Work Included 2 1.4 Related Work Specified Elsewhere 2 PART 2 PRODUCTS 3 2.1 Pipe and

More information

CHAPTER 11 CONDUITS AND FITTINGS

CHAPTER 11 CONDUITS AND FITTINGS CONDUITS AND FITTINGS CHAPTER 11 CONDUITS AND FITTINGS The standards and requirements for conduits and fittings used for traffic control signal and lighting systems are presented in this chapter. 11.1

More information

GLENWOOD PLACE 2 MAR 2015

GLENWOOD PLACE 2 MAR 2015 PART 1 - GENERAL 1.01 SUMMARY: SECTION 16110 RACEWAYS A. Description: 1. Provide continuous conduit systems - beginning at the service point, to all distribution equipment and to every outlet and piece

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING. A. This Section includes the following storm drainage piping inside the building.

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING. A. This Section includes the following storm drainage piping inside the building. SECTION 221413 - FACILITY STORM DRAINAGE PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following storm drainage piping inside the building. 1. Pipe, tube, and fittings. 2. Special pipe

More information

San Antonio Water System Standard Specifications for Construction ITEM NO. 848 SANITARY SEWERS

San Antonio Water System Standard Specifications for Construction ITEM NO. 848 SANITARY SEWERS ITEM NO. 848 SANITARY SEWERS 848.1 DESCRIPTION: This item shall govern the furnishing, installation and jointing of sanitary sewer pipe of the size and type specified by the project's plans and specifications.

More information

SECTION PIPING SPECIALTIES AND ACCESSORIES

SECTION PIPING SPECIALTIES AND ACCESSORIES SECTION 15120 PIPING SPECIALTIES AND ACCESSORIES PART 1 - GENERAL 1.01 DESCRIPTION A. Work Specified 1. CONTRACTOR shall provide all labor, materials, equipment, tools, services, and incidentals necessary

More information

PART 5 WATER SYSTEMS

PART 5 WATER SYSTEMS PART 5 WATER SYSTEMS Abbreviations and Symbols Plan 501 Abbreviations and symbols for water... 205 Concrete Boxes and Hardware 502 27" Frame and cover... 207 503 38" Frame and cover... 209 505 Concrete

More information

SECTION TAPPING SLEEVES AND VALVES

SECTION TAPPING SLEEVES AND VALVES SECTION 33 12 16.17 TAPPING SLEEVES AND VALVES PART 1: GENERAL 1.01 SCOPE Furnish, install and test all tapping sleeves, tapping valves, and tapping saddles as shown on the Drawings. 1.02 RELATED WORK

More information

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT. A. ASME B31.1 (American Society of Mechanical Engineers) - Power Piping

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT. A. ASME B31.1 (American Society of Mechanical Engineers) - Power Piping SECTION 22 05 29 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes pipe and equipment supports, hangers, anchors, bases sleeves and the sealing of

More information

Combination Air Valves - Stainless Steel/ Sanitary Sewer/ For 2 Thru 12 Mains

Combination Air Valves - Stainless Steel/ Sanitary Sewer/ For 2 Thru 12 Mains D 1 D 1.1 D 1.2 D 1.3 D 1.4 D 1.5 D 2 D 3 D 3.1 D 3.2 D 4 D 4.1 D 5 D 6 D 7 D 8 Valves- Resilient Seat/ 2 (FIPT X FIPT) Valves - AWWA C509/ Resilient Seat/ 2 Thru 12 (MJ X MJ) Tap Valves - AWWA C509/ Resilient

More information

1. B16.1 Cast Iron Pipe Flanges and Flanged Fittings, Class C 111 Rubber Gasket Joints for Ductile Iron Pressure Pipe and Fittings

1. B16.1 Cast Iron Pipe Flanges and Flanged Fittings, Class C 111 Rubber Gasket Joints for Ductile Iron Pressure Pipe and Fittings SECTION 33 34 00 SANITARY FORCE MAIN PART 1 GENERAL 1.1 SCOPE OF WORK A. This section specifies the requirements for furnishing and installing sanitary force main and appurtenances. The pipe shall be of

More information

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS SECTION 16711-27 05 28.33 PART 1 - GENERAL 1.01 SUMMARY A. This section includes Labor, materials and equipment necessary to complete the installation required for the items specified under this Section,

More information

Charlottetown - Water & Sewer Utility Minimum Standard of Acceptability for Water, Sewer & Sprinkler Connections

Charlottetown - Water & Sewer Utility Minimum Standard of Acceptability for Water, Sewer & Sprinkler Connections Charlottetown - Water & Sewer Utility Minimum Standard of Acceptability for Water, Sewer & Sprinkler Connections At the time of application for water, sewer and/or sprinkler service the applicant shall

More information

d.p. Consulting Engineers, Inc.

d.p. Consulting Engineers, Inc. d.p. Consulting Engineers, Inc. 3727 Doctors Drive Port Arthur, Tx 77642 Phone: 409-983-6263 Fax : 409-983-6265 Firm Registration No: F-3356 Email : dp@dpengineersinc.com ADDENDUM NO. 1 ADDENDUM ISSUE

More information

STREET LIGHTING GENERAL INFORMATION

STREET LIGHTING GENERAL INFORMATION SECTION 1102 STREET LIGHTING GENERAL INFORMATION These specifications are for street lighting that is to be dedicated to the public and maintained by the City of Meridian. Such installations require a

More information

CITY OF UNION, OREGON TECHNICAL SPECIFICATIONS SECTION 9 UNDERGROUND UTILITIES

CITY OF UNION, OREGON TECHNICAL SPECIFICATIONS SECTION 9 UNDERGROUND UTILITIES A. GENERAL 1. Scope. These specifications cover the installation of the utility systems and appurtenances for the electrical power, telephone, gas, and television as shown in the Drawings. The Work includes,

More information

ZG Scope. 2 Applicable Documents. 3 General. 4 Stock Item Numbers. Padvault Single-Phase Residential, 2.1 PacifiCorp Material Specifications

ZG Scope. 2 Applicable Documents. 3 General. 4 Stock Item Numbers. Padvault Single-Phase Residential, 2.1 PacifiCorp Material Specifications 1 Scope This specification outlines the minimum requirements for a 48 48 padvault for single-phase primary service. Single-phase transformers and sectionalizers (elbow switched cabinets) can be mounted

More information

A. Product Data shall be provided for each type of product indicated.

A. Product Data shall be provided for each type of product indicated. 32 31 13 CHAIN LINK FENCES AND GATES SECTION 1 GENERAL 1.1 SUMMARY This Section includes the following: 1. Chain Link Fences 2. Gates for Chain Link Fences. See electrical specifications for electrical

More information

C. ASSE 1013 Performance Requirements for Reduced Pressure Principle Backflow Preventers.

C. ASSE 1013 Performance Requirements for Reduced Pressure Principle Backflow Preventers. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets. ALLIANT ENERGY CENTER PAVILIONS Project No. 2013 027 SECTION 27 05 28 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

CHAPTER 4 PIPES. Prof. Dr. Uğur Atikol

CHAPTER 4 PIPES. Prof. Dr. Uğur Atikol CHAPTER 4 PIPES Prof. Dr. Uğur Atikol History Materials: Lead used to be very popular material due to its availability, durability and ease of working. It had environmental problems Industrial developments

More information

RESIDENTIAL FIRE SERVICE METERS Addendum #1

RESIDENTIAL FIRE SERVICE METERS Addendum #1 109 WATER METERS (Addendum #1) 109.1 GENERAL All meters to be used for billing purposes shall be provided by the Water Utility. The Water Utility reserves the right to read, inspect, test or replace the

More information

CALAVERAS COUNTY WATER DISTRICT Ebbetts Pass Water System Reach 3A Pipeline Replacement Project CCWD CIP No ADDENDUM 2

CALAVERAS COUNTY WATER DISTRICT Ebbetts Pass Water System Reach 3A Pipeline Replacement Project CCWD CIP No ADDENDUM 2 CALAVERAS COUNTY WATER DISTRICT Ebbetts Pass Water System Reach 3A Pipeline Replacement Project CCWD CIP No. 11078 ADDENDUM 2 Date Issued: December 2, 2015 **** Receipt of addenda must be acknowledged

More information

SECTION CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION

SECTION CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION SECTION 22 11 16.13 CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION PART 1: GENERAL 1.01 SUMMARY A. This Section includes water-distribution backflow prevention products and installation specifications.

More information

UL / FM D-1 FIRE PROTECTION PRODUCTS TAPPING VALVE. MUELLER Tapping Sleeves and Crosses. MUELLER Tapping Valves

UL / FM D-1 FIRE PROTECTION PRODUCTS TAPPING VALVE. MUELLER Tapping Sleeves and Crosses. MUELLER Tapping Valves UL / FM TAPPING VALVE SECTION Rev. 2-15 MUELLER Tapping Sleeves and Crosses Full range of Tapping Sleeves and Crosses to fit most types of pipe including cast iron, ductile iron, A-C, and cast iron O.D.

More information

SECTION HYDRONIC PIPING

SECTION HYDRONIC PIPING PART 1 GENERAL 1.1 REFERENCES SECTION 23 21 13 HYDRONIC PIPING A. ANSI/ASME SEC 9: Welding and Brazing Qualifications B. ANSI/ASME B16.3: Malleable Iron Threaded Fittings Class 150 and 300 C. ANSI/ASME

More information

D-1 FIRE PROTECTION PRODUCTS TAPPING VALVE. MUELLER Tapping Valves. MUELLER Tapping Sleeves and Crosses. MUELLER Stainless Steel Tapping Sleeves

D-1 FIRE PROTECTION PRODUCTS TAPPING VALVE. MUELLER Tapping Valves. MUELLER Tapping Sleeves and Crosses. MUELLER Stainless Steel Tapping Sleeves TAPPING VALVE MUELLER Tapping Sleeves and Crosses Full range of Tapping Sleeves and Crosses to fit most types of pipe including cast iron, ductile iron, A-C, and cast iron O.D. PVC--Also outlet sealed

More information

ADDENDUM NO. 1. Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities

ADDENDUM NO. 1. Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities ADDENDUM NO. TO Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities Date of Addendum: December, 00 Hethcoat & Davis, Inc. 78 Franklin Road,

More information

SECTION PLUMBING PIPING

SECTION PLUMBING PIPING SECTION 22 1000 PLUMBING PIPING PART 1 GENERAL 1.1 QUALITY ASSURANCE A. Perform Work in accordance with authority having jurisdiction standards. Utilize products as indicated in drawings and as allowed

More information

SECTION CONDUITS AND BOXES PART 1- GENERAL. A. Work covered by this section includes the furnishing and installation of conduits and boxes.

SECTION CONDUITS AND BOXES PART 1- GENERAL. A. Work covered by this section includes the furnishing and installation of conduits and boxes. SECTION 16111 CONDUITS AND BOXES 1.01 DESCRIPTION PART 1- GENERAL A. Work covered by this section includes the furnishing and installation of conduits and boxes. 1.02 SUBMITTALS A. The Contractor shall

More information

SECTION ELECTRICAL SITE UTILITIES

SECTION ELECTRICAL SITE UTILITIES SECTION 16402 ELECTRICAL SITE UTILITIES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Electrical site utilities and coordination of requirements with the utility company and service specifications.

More information

SECTION DRAINAGE AND VENT SYSTEMS CONSTRUCTION STANDARD

SECTION DRAINAGE AND VENT SYSTEMS CONSTRUCTION STANDARD PART 1: GENERAL 1.01 The design guidelines contained herein include the requirements for drainage and vent systems utilized at The University of Texas at Austin. It is the intention of this document to

More information

SECTION 2100 WATER MAIN

SECTION 2100 WATER MAIN SECTION 2100 WATER MAIN WATER MAIN PART 1 GENERAL 1.01 Section Summary A. This section includes product and installation requirements for water main pipe, gate valves, hydrants, fittings, and miscellaneous

More information

Design and Construction Standards SECTION HYDRONIC PIPING

Design and Construction Standards SECTION HYDRONIC PIPING SECTION 15510 HYDRONIC PIPING PART 1 GENERAL 1.1 REFERENCES A. ANSI/ASME SEC 9: Welding and Brazing Qualifications. B. ANSI/ASME B16.3: Malleable Iron Threaded Fittings Class 150 and 300. C. ANSI/ASME

More information

ARTICLE 26 UTILITY LINE INSTALLATION REQUIREMENTS

ARTICLE 26 UTILITY LINE INSTALLATION REQUIREMENTS UTILITY LINE INSTALLATION REQUIREMENTS Index 26.01 JACK AND BORE OPERATIONS 26.02 PRESSURE PIPE RESTRAINT 26.03 PRESSURE CONNECTION BACK TO TABLE OF CONTENTS Section 26.01 JACK AND BORE OPERATIONS 26.01.01

More information

Cast Iron Valves and Strainers

Cast Iron Valves and Strainers Cast Iron Valves and Strainers Proven reliability Robust design Economical Cast Iron Gate Valve F I G G A 1 4 G A T E V A L V E Heavy duty design Dezincification resistant trim Outside screw and yoke,

More information

The Manitoba Water Services Board SECTION Standard Construction Specifications September 2013 Page 1 of 7

The Manitoba Water Services Board SECTION Standard Construction Specifications September 2013 Page 1 of 7 September 2013 Page 1 of 7 Part 1 General 1.1 DESCRIPTION OF WORK.1 The work described herein shall consist of the construction of a wetwell as shown on the Plans and in accordance with Section 01001,

More information

SECTION HYDRONIC PIPING

SECTION HYDRONIC PIPING PART 1 GENERAL 1.1 REFERENCES SECTION 15510 HYDRONIC PIPING A. ANSI/ASME SEC 9: Welding and Brazing Qualifications. B. ANSI/ASME B16.3: Malleable Iron Threaded Fittings Class 150 and 300. C. ANSI/ASME

More information

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION 23 05 29 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes pipe and equipment supports, hangers, anchors, bases sleeves and the sealing of work

More information

SECTION FACILITY STORM DRAINAGE PIPING

SECTION FACILITY STORM DRAINAGE PIPING SECTION 221413 FACILITY STORM DRAINAGE PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

1.02 RELATED SECTIONS: Water supply piping, water use piping, electrical, irrigation, foundations, site plans.

1.02 RELATED SECTIONS: Water supply piping, water use piping, electrical, irrigation, foundations, site plans. INC. ENGINEERING/CONSTRUCTION/MANUFACTURING /WWW.CONTAINWATER.COM SPRINGS, TEXAS. 78620 MODEL SPECIFICATION FOR CONTAIN WATER INC. 30 DEGREE ROOF CORRUGATED STEEL WATER STORAGE Part 1 GENERAL 1.01 SECTION

More information

AMERICAN FLOW CONTROL 2"-12" SERIES 2500 RESILIENT WEDGE GATE VALVE

AMERICAN FLOW CONTROL 2-12 SERIES 2500 RESILIENT WEDGE GATE VALVE AMERICAN FLOW CONTROL 2"-12" SERIES 2500 RESILIENT WEDGE GATE VALVE CONSTRUCTION DUCTILE IRON OPERATING NUT Provides strength and durability. UPPER O-RING SEALS Helps isolate the lubrication chamber as

More information

Specifications Electrical Metallic Tubing (EMT)

Specifications Electrical Metallic Tubing (EMT) T& Fittings Specifications Electrical Metallic Tubing (EMT) Ref. CEC Rule 12-000 not exceeding 750 Volts Electrical Metallic Tubing (EMT) is similar to rigid steel conduit but is much lighter, weighing

More information

SECTION 401 WATER PIPE AND FITTINGS 2.2 POLYVINYL CHLORIDE (PVC) PIPE AND FITTINGS

SECTION 401 WATER PIPE AND FITTINGS 2.2 POLYVINYL CHLORIDE (PVC) PIPE AND FITTINGS SECTION 401 PIPE AND FITTINGS PART 2 MATERIALS 2.2 POLYVINYL CHLORIDE (PVC) PIPE AND FITTINGS A. PVC Pressure Pipe sizes 4 inch through 12 inch: ANSI/AWWA C 900 1. DR18 B. PVC Pressure Pipe sizes 14 inch

More information

Electric Service Standards

Electric Service Standards V: 1 of 6 A. Padmounted Requirements Complete requirements are contained in FPL specifications given to Customers for individual projects. Typical pad mounted transformer requirements include, but are

More information

DIVISION 15-MECHANICAL SECTION SUPPORTS AND ANCHORS PN PART 1 - GENERAL 1.01 SECTION INCLUDES. A. Pipe and equipment support systems.

DIVISION 15-MECHANICAL SECTION SUPPORTS AND ANCHORS PN PART 1 - GENERAL 1.01 SECTION INCLUDES. A. Pipe and equipment support systems. PART 1 - GENERAL 1.01 SECTION INCLUDES A. Pipe and equipment support systems. B. Inserts. 1.02 RELATED SECTIONS A. Section 15890 - Ductwork Supports. 1.03 DEFINITIONS A. Supports: Attachments, hangers,

More information

SECTION HYDRONIC PIPING

SECTION HYDRONIC PIPING PART 1 GENERAL 1.1 REFERENCES SECTION 23 21 13 HYDRONIC PIPING A. ASME BPVC Section IX - Welding and Brazing Qualifications B. ASME B16.3 - Malleable Iron Threaded Fittings Classes 150 and 300 C. ASME

More information

1.02 RELATED SECTIONS: Water supply piping, water use piping, electrical, irrigation, foundations, site plans.

1.02 RELATED SECTIONS: Water supply piping, water use piping, electrical, irrigation, foundations, site plans. INC. ENGINEERING/CONSTRUCTION/MANUFACTURING /WWW.CONTAINWATER.COM SPRINGS, TEXAS. 78620 MODEL SPECIFICATION FOR CONTAIN WATER INC. DOME ROOF CORRUGATED STEEL WATER STORAGE TANKS. Part 1 GENERAL 1.01 SECTION

More information

2. A preconstruction meeting with the TWA s staff is required prior to initiating construction.

2. A preconstruction meeting with the TWA s staff is required prior to initiating construction. General: 1. Construct utilities in accordance to TWA approved plans and shop drawings. Any deviation from the approved plans shall be approved by the DEVELOPER S ENGINEER and TWA 2. A preconstruction meeting

More information

Rockwood Water People s Utility District Cross Connection Implementation and Regulations

Rockwood Water People s Utility District Cross Connection Implementation and Regulations Rockwood Water People s Utility District Cross Connection Implementation and Regulations To ensure clean, safe, potable water, Rockwood Water People s Utility District (PUD) maintains a cross connection

More information