1 INDUSTRIAL SYSTEMS Application Manual for Piping Equipment

2 INDEX Introduction Tools for Installing ArmaSound INTRODUCTION The advice contained within this manual, in general relates to the acoustic treatment of piping equipment with ArmaSound Industrial Systems. Installation of Armaflex (Closed Cell) Layer... 3 Installation of ArmaSound RD 240 (Open Cell) Layer Installation of ArmaSound Barrier E Installation of Arma-Chek R (Outer Jacketing). 6 Pipe Supports & Steel Work Storage of Armacell Products Reference ArmaSound Industrial Systems are flexible thermalacoustic insulation systems, composed of: one or several layers of Armaflex (closed cell elastomer thermal insulation) one or several layers of ArmaSound RD (open cell acoustic insulation) one or several layers of ArmaSound Barrier E one layer of cladding (Arma-Chek R or metal). Where additional layers of Armaflex (closed cell) thermal insulation are required, the additional layers of insulation shall be installed to the procedures, as contained within the Armacell Armaflex Application Manual or Cold Work Application Manual. Where applicable, but not limited to; For Client Project Insulation Specification(s): Armacell Installation Processing Specification(s) - (IPS) shall be used for reference and specific detail(s) of the installation procedure. TOOLS FOR INSTALLING ARMASOUND INDUSTRIAL SYSTEMS Folding rule / tape measure Chalk for marking irregular shapes Silver ink marker pen Dividers Callipers Knifes * Safe edge craft knife Sharpening stone Mastic gun Straight edge Template (printed on every Armaflex carton) Scissors Brushs with short, firm bristles Smooth spatula for smoothing down covering Sharpened pipe ends for the most common pipe diameters Paint fabric rollers for surface gluing and smoothing down covering Gluemaster * A three knife set plus sharpening stone are available together as a tool kit. 2 ArmaSound ARMACELL INTERNATIONAL GMBH

3 Installation of Armaflex (closed cell) layer Armaflex shall be installed according to the recommendations given in the current version of the Armaflex Installation Manual. In addition, any client Insulation Project Specifications or any accompanying Armacell - (IPS) Installation Processing Specifications issued for the project shall also be implemented into the scope of works. All materials shall be kept free from contamination and shall be clean, dry and damage free. 4. No PVC tape or any form of self adhesive tapes shall be installed on any seams or joints without the written permission of but not limited to - the client, specifies, main contractor or Armacell. The following shall be implemented as a minimum: 1. When the insulated pipe work or equipment with an outer diameter greater than 500mm Armaflex sheet materials shall be installed with all over adhesive coverage to both the Armaflex surface and the underlaying substrate on the bottom ¼ for all horizontal piping equipment. Important note: Flat surfaces and ALL vertically positioned piping equipment - regardless of size, shall also require all-over adhesive coverage to all contacting surfaces. 2. All seams and joints shall be staggered on all layers. All Armaflex shall be fitted under compression on all butt joints. Note: It is very important that all material layers are fitted under compression with no gaps present. The installation of materials shall be treated as cold work process at all times. 3. All butt joints, where applicable within the line temperature range between +150 C and -50 C* shall be adhered to the pipe/underlying insulated pipe work and wet sealed with the correct type of Armaflex Adhesive as per the Armaflex Installation Manual and other supporting documents (IPS) from Armacell. * For temperatures at or below -50 ºC please see our Cold Work Application Manual. For temperatures above +125 ºC please consult our Technical Department. INSTALLATION OF ARMASOUND RD 240 (OPEN CELL) LAYER ArmaSound RD 240 shall always be installed as according to the recommendations for fixing, vapour sealing and various fabrication techniques given for Armaflex sheet in the Armaflex Installation Manual. In addition, any client Insulation Project Specifications or any accompanying Armacell - (IPS) Installation Processing Specifications issued for the project shall also be implemented into the scope of works where applicable. All materials shall be kept free from contamination and shall be clean, dry and damage free during construction and when in storage. The following recommendations shall also be implemented: 1. All over adhesive coverage is required on flat surfaces, vessels and all vertical piping equipment. Note: The requirement for all over adhesive coverage on pipes with diameters greater than 500mm does not apply to this ArmaSound RD 240 layer on horizontal piping equipment, unless requested by the project owner / client. 2. All ArmaSound RD 240 shall be fitted under compression on all butt joints. ARMACELL INTERNATIONAL GMBH ArmaSound 3

4 3. All seams and joints shall be staggered on all layers Staggering on pipe-work: cross section view. Staggering on pipe-work: longitudinal view Yellow lines indicate glued seams 4. Where possible seams and joints shall be kept to a minimum. 5. No PVC tape or any form of self adhesive tapes shall be installed on any seams or joints without the written permission of but not limited to - the client, specifies, main contractor or Armacell. 6. Armaflex Adhesive shall be used on all fixing seams and joints on straight lines and other pipe work fitting fabrications. In addition, any seams and joints that have gaps shall be filled with Arma-Chek mastic. 7. All ArmaSound RD 240 materials shall be finally secured with 20mm wide by (0.50mm) thick type 304 stainless steel bands and wing seal fixings. Stainless stell bands to be installed at 250mm intervals. For bends 8. When processing and installing ArmaSound RD 240 materials onto bend fittings, the ArmaSound RD 240 sheet can either be constructed into segments or in the two piece Armaflex fitting cover method. The fabrications shall be finally secured with 20mm wide stainless band fixings. All seams and joints be bonded together with Armaflex adhesive. Note: Stainless steel band fixings shall be used for fixing security of the material on all vertical; and horizontal piping equipment, including fittings, flat surface and vessel equipment. 9. Any gaps present around the installed segmented bend fabrications shall be filled with Arma-Chek mastic. All mastic shall be allowed to dry before covering with additional layers of insulation materials. 10.No PVC tape or any form of self adhesive tapes shall be installed on any seams or joints without the written permission of but not limited to - the client, specifies, main contractor or Armacell. 11. Vertically positioned bends all segment fabrications shall also be fully fixed down with all over adhesive coverage to both contacting surfaces. In addition, all vertically positioned fittings shall also be secularly fixed down with all over adhesive coverage to both contacting surfaces. 12. Avoid using damaged material! INSTALLATION OF ArmaSound Barrier E Where the ArmaSound Barrier E material is required, the following application process shall be followed. All materials shall be kept free from contamination and shall be clean, dry and damage free. 1. The ArmaSound Barrier E shall be applied, fixed and secured tightly around the insulated equipment throughout. The materials shall be arranged and installed to allow for water run-off, with all overlaps fixed down using Armaflex Adhesive. (See below). 2. All fabricated items, where applicable shall have a minimum of 50mm overlapping on all seam and butt jointing details. All overlaps shall be secularly fixed and sealed down; using the projects specified Armaflex Adhesive. 3. The ArmaSound Barrier E shall be finally secured with 20mm wide by (0.50mm) thick. Type 304 stainless steel bands and wing seal fixings. Each one-metre length shall have a minimum of 3 fixing bands installed. Stainless steel bands Minimum 50mm overlaps on seams and butt joints 4 ArmaSound ARMACELL INTERNATIONAL GMBH

5 Note: All butt jointing overlaps, on all vertical piping shall have additional band/s installed. The ArmaSound Barrier E shall at all times be installed to avoid insulation slipping on all piping equipment arrangements. Also see 6. Below. Important Note: In addition, any other mechanical supporting implementations stated within the client s Insulation Project Specification shall also be included within the scope of works. 4. The ArmaSound Barrier E - seam and butt jointing details shall be staggered away from the underlaying insulation seam details, and be positioned to avoid a direct pathway for possible water ingression in external locations. 5. All over adhesive coverage is required to both contacting surfaces on flat surfaces, vessels and ALL vertical piping equipment regardless of pipe size. In addition, the ArmaSound Barrier E shall be additionally supported using S clips on each fabricated section. A minimum of 4 stainless steel S clips shall be used around the circumference of the fabricated section. All ArmaSound Barrier E shall have stainless steel bands installed as required in 3.above within this section. 6. Vertically positioned bends all segment fabrications shall also be secularly fixed down to the under-laying insulation type, with all over adhesive coverage to both contacting surfaces. In addition, all vertically positioned fittings shall also be secularly fixed down with all over adhesive coverage to both contacting surfaces. 7. All segments shall overlap each other by a minimum of 10mm and be arranged to shed water away from the joints. Each segment fabrication shall be fully sealed, and finally secured with the stainless steel bands and wing seal fixings. 8. No PVC tape or any form of self adhesive tapes shall be installed to secure and fix the ArmaSound Barrier E without the written permission of but not limited to - the client, specifies, main contractor and Armacell in all situations. Installation of Arma-Chek R (outer jacketing) Arma-Chek R jacketing. shall be installed as detailed within the current version of the Arma-Chek R Installation Manual and any other supporting project specifications issued relating to the installation of Arma-Chek R jacketing. All materials shall be kept free from contamination and shall be clean, dry and damage free. The following shall be implemented as a minimum: 1. All Arma-Chek R shall be fixed to all under-laying insulation with all over adhesive coverage on both fixing surfaces, when the pipe work installations outer diameter is above 500mm. All flat surface applications and ALL vertically positioned piping equipment shall also have all over adhesive coverage to both contacting surfaces. Note: It is not recommended to spot apply the adhesive in any situation. 2. All fixing seams and butt joint overlap details shall be a minimum of 50mm. For larger bore piping equipment the overlap size is increased. outer - insulated pipe (mm) min. required overlap (mm) and above 150 Flat surface All bend and fitting fabrications shall be installed as per Arma-Chek installation manual. Always allow a minimum of 10mm overlap on segment fabrications on bend applications. 4. All bend and fitting fabrications shall be installed with all over adhesive coverage on both fixing surfaces. Note: It is not recommended to spot apply the adhesive in any situation. 5. All overlaps shall have Armaflex Adhesive applied to both overlapping surfaces and allow to tack dry following instructions of the Arma-Chek installation manual. 6. All bend and fitting fabrications shall be installed as per Arma-Chek installation manual. Always allow a minimum of 10mm overlap on segment fabrications on bend applications. 7. All bend and fitting fabrications shall be installed with all over adhesive coverage on both fixing surfaces. Note: It is not recommended to spot apply the adhesive in any situation. 8. On the final outer Arma-Chek R jacketing layer, apply a bead of Arma-Chek mastic, minimum 10mm wide - 3mm thick, to all seams and joints in order to finish the installation process. Note: Before applying the bead of mastic to all fixing seams and joints, the surface of the Arma-Chek R shall be pre-cleaned around the seam and jointing area s using Armaflex Cleaner or local approved solvent Cleaner. ARMACELL INTERNATIONAL GMBH ArmaSound 5

6 PIPE SUPPORTS & STEEL WORK 1. In situations where there are piping load bearing supports and steel work clash, and the complete specified insulation thickness cannot be implemented, due to space restrictions, the insulation layer shall, where applicable, be cut around the steel leg support. The cut outs shall be neat/tidy and accurate with no gaps present. 2. The cut out details shall be sealed at all times with Armaflex Adhesive / Arma-Chek mastic. 3. Where applicable and required, for optimum performance, in order to avoid acoustic and thermal bridging, all steel work that is directly attached to the main piping equipment shall be insulated to the same thickness and product combination as indicated within the Clients Project Insulation Specification. In addition, where required valves and flanges can be insulated with the same thickness and material combinations as the connecting pipe. The insulation layers, follow the contours of the equipment. Storage of Armacell products Store in a safe place, following all procedures of the client and Armacell relating to Health + Safety, storage and handling procedures. REFERENCE Armaflex Installation Manual Arma-Chek R - Installation Manual Armaflex Cold Work Application Manual 4. Final system appearance All unwanted Armaflex Adhesive marks and spillages on the final outer Arma-Chek R covering layer shall be easily cleaned away using Armaflex Cleaner applied using a clean cloth. It is recommended that this procedure be followed whilst cleaning the seam and joint details prior to applying the mastic as the final application detail of the insulation system. Note: Ensure the Armaflex Cleaner has dried away, before applying the mastic. This should take 1-3 minutes for the solvents to evaporate depending on the ambient air temperature. INSULATION OF VALVES WITH ARMASOUND INDUSTRIAL SYSTEMS For the acoustic treatment of valves, please refer to the Armacell Installation Processing Specification document where applicable. In addition, where valves and flanges are to be insulated with the same insulation system as the connecting pipe, the insulation layers should follow the contours of the equipment. Armacell - Installation Processing Specification (IPS). Project specific issue. NOTE: In order to gain the maximum performance from both the materials and the acoustic value requirements it is important that a high standard of workmanship is achieved during this type of application. All installers are advised to receive or attended an Armacell Installation Training Course and be certificated / approved before commencing the application process as detailed above. 6 ArmaSound ARMACELL INTERNATIONAL GMBH

7 YOUR PERSONAL NOTES: ARMACELL INTERNATIONAL GMBH ArmaSound 7

8 YOUR PERSONAL NOTES: Armacell GmbH Robert-Bosch-Straße 10 D Münster Germany Tel.: +49 (0) 251/ Armacell LLC 7600 Oakwood Street Extension Mebane NC USA Armacell (Guangzhou) Ltd Guanqiao Shilou Town Panyu China All the statements and technical information within this document should be read in conjunction with the customer s specification. It is the responsability of the recipient to inform all involved parties about the content of these documents. The described and recommended methods should be strictly followed. If there is a requirement to deviate from our recommendations, please contact us in advance to discuss possible suitable alternatives. Armacell will not be liable for any claim resulting from non-observance of our IMPS specification or any other agreed solutions and from non-observance of the customer s specification. Armacell International GmbH Subject to alterations Printed in Europe ASIS-0910-EN (WW) 8 ArmaSound ARMACELL INTERNATIONAL GMBH

armaflex cryogenic systems

armaflex cryogenic systems ARMACELL SOLUTIONS FOR OIL & GAS armaflex cryogenic systems FLEXIBLE INSULATION SYSTEMS FOR INDUSTRIAL PROCESS PIPEWORK AND TANKS. CRYOGENIC INSULATION FOR RELIABILITY AND PERFORMANCE. PATENT PENDING.

More information

Pipe Supports Comparison

Pipe Supports Comparison PIPE SUPPORTS: Comparison of the installation costs for various systems ARMAFIX The easy to install and cost effective solution to prevent thermal bridging at the pipe bracket in low-temperature applications.

More information

K-FLEX K-FONIK INDUSTRIAL

K-FLEX K-FONIK INDUSTRIAL J a n u a r y 2 0 1 3 K-FLEX K-FONIK INDUSTRIAL Sound & Thermal Insulation design compliant with ISO 15665 www.kflexenergy.com Flexible Elastomeric Foam layer INSULATING PIPING WITH K-FLEX SHEETS > FIRST

More information

Pipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems

Pipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems Pipe and Equipment Insulations Zeston PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems Zeston PVC Insulated Fitting Covers Installation Instructions for Hot,

More information

10.1 APPLICATION 1 A. HOT PIPING 1 B. ANTI SWEAT PIPING 1 C. COLD PIPING FINISHES 2

10.1 APPLICATION 1 A. HOT PIPING 1 B. ANTI SWEAT PIPING 1 C. COLD PIPING FINISHES 2 SECTION 10: 10.1 APPLICATION 1 A. HOT PIPING 1 B. ANTI SWEAT PIPING 1 C. COLD PIPING 2 10.2 FINISHES 2 10.3 PIPING FORMAT 3 A. PIPE INSULATION 3 B. PIPE INSULATION 3 C. INSULATION ATTACHMENT 3 D. INSULATION

More information

1/2 Ø. application manual

1/2 Ø. application manual 1/2 Ø B H application manual >> ARMAFLEX application manual APPLICATION MANUAL application manual >> ARMAFLEX 1 GENERAL 3» Working with Armaflex 3» Tools for installing Armaflex 3» The correct use of Armaflex

More information

Industrial Systems THE FIRST SOUND CONTROL SYSTEMS TO MINIMISE THE RISK OF UNDER INSULATION CORROSION. Industrial Systems

Industrial Systems THE FIRST SOUND CONTROL SYSTEMS TO MINIMISE THE RISK OF UNDER INSULATION CORROSION. Industrial Systems Industrial Systems THE FIRST SOUND CONTROL SYSTEMS TO MINIMISE THE RISK OF UNDER INSULATION CORROSION ArmaSound Industrial systems Combining thermal insulation and noise reduction The First Sound Control

More information

ACOUSTICAL INSULATION (LAGGING) FOR PIPING AND EQUIPMENT

ACOUSTICAL INSULATION (LAGGING) FOR PIPING AND EQUIPMENT ACOUSTICAL INSULATION (LAGGING) FOR PIPING AND EQUIPMENT Specification for Acoustical Insulation (Lagging) for Piping and Equipment 1 of 5 TABLE OF CONTENTS 1.0SCOPE..... 3 2.0REFERENCED PUBLICATIONS...

More information

armaflex cryogenic systems for oil & gas FLEXIBLE INSULATION SYSTEMS FOR INDUSTRIAL PROCESS PIPEWORK AND TANKS.

armaflex cryogenic systems for oil & gas FLEXIBLE INSULATION SYSTEMS FOR INDUSTRIAL PROCESS PIPEWORK AND TANKS. ARMACELL solutions for oil & gas armaflex cryogenic systems FLEXIBLE INSULATION SYSTEMS FOR INDUSTRIAL PROCESS PIPEWORK AND TANKS. CRYOGENIC INSULATION FOR RELIABILITY AND PERFORMANCE. PATENT PENDING.

More information

079 Quick Installation Guide

079 Quick Installation Guide INSULATION 2212 W. 5th Pl., Tempe, AZ 85268 (480) 967-8888 Step 1: 079 Quick Installation Guide Step 2: *see attached literature for complete installation instructions Step 3: Position the next piece and

More information

INSTALLATION GUIDELINES FOR COLD/CRYOGENIC PIPE INSULATION

INSTALLATION GUIDELINES FOR COLD/CRYOGENIC PIPE INSULATION PermaTherm, Inc. 269 Industrial Park Road Monticello, GA 31064 (706) 468-7500 www.insulate.pipe.com/ Temperature Range -310 F to 32 F INSTALLATION GUIDELINES FOR COLD/CRYOGENIC PIPE INSULATION PERMATHERM,

More information

INSTALLATION GUIDELINES FOR CHILL WATER PIPE INSULATION

INSTALLATION GUIDELINES FOR CHILL WATER PIPE INSULATION PermaTherm, Inc. 269 Industrial Park Road Monticello, GA 31064 (706) 468-7500 www.insulate.pipe.com/ Temperature Range 34 F to 167 F INSTALLATION GUIDELINES FOR CHILL WATER PIPE INSULATION PERMATHERM,

More information

Sheet Insulation - Rectangular ducts. Installation Manual

Sheet Insulation - Rectangular ducts. Installation Manual Sheet Insulation - Rectangular ducts Installation Manual 11 DISCLAIMER: The information in this document is based on our current state of technical knowledge. Due to the variety of possible influences

More information

FLEXIBLE MECHANICAL PROTECTION

FLEXIBLE MECHANICAL PROTECTION FLEXIBLE MECHANICAL PROTECTION Powered by TCPDF (www.tcpdf.org) Insulation and covering in one product Saves installation time Easy to clean Full system with Tape, Elbows and T-Parts Good chemical resistance

More information

L'ISOLANTE K-FLEX. LNG applications Manual

L'ISOLANTE K-FLEX. LNG applications Manual L'ISOLANTE K-FLEX LNG applications Manual LNG applications Manual The insulation LNG plants may forsee a multilayer design according to the specific characteristics and the working temperatures of the

More information

KoolthermTM. Installation Guide. HVAC & Building Services Pipe Insulation

KoolthermTM. Installation Guide. HVAC & Building Services Pipe Insulation FM KoolthermTM Installation Guide HVAC & Building Services Pipe Insulation 2 Installation Guide This installation guide is an extract from the KoolthermTM FM Pipe Insulation Project Specification brochure

More information

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS Dyplast Products Copyright 2014 1 Rev 0414 DYPLAST PRODUCTS INSTALLATION GUIDELINES ISO-C1 POLYISOCYANURATE

More information

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS Dyplast Products Copyright 2018 1 Rev 0618 DYPLAST PRODUCTS INSTALLATION GUIDELINES ISO-C1 POLYISOCYANURATE

More information

K-FLEX K-FONIK INDUSTRIAL

K-FLEX K-FONIK INDUSTRIAL J a n u a r y 2 0 1 3 K-FLEX K-FONIK INDUSTRIAL Sound & Thermal Insulation design compliant with ISO 15665 www.kflexenergy.com INDEX INTRODUCTION: Standard for industry - ISO 15665................ Page

More information

EFRIGERATION INSTALLATION GUIDE

EFRIGERATION INSTALLATION GUIDE R EFRIGERATION INSTALLATION GUIDE Golden Rules for Working with INSTALLATION Armaflex and good adhesive brushes1 fittings. mitered fabricated Use good quality tools and, in particular, fresh 520, 520 Black

More information

1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.

1. Division 23 Section Hangers and Supports for HVAC Piping and Equipment for pipe insulation shields and protection saddles. SECTION 23 07 19 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Addendum to Specifications

Addendum to Specifications Addendum to Specifications SOW #: Construction Specification #: Date: Additions to Specifications: Deletions to Specifications: Engineer Date Design Engineering Manager Date Page 2 of 7 PART 1 - GENERAL

More information

379 Quick Installation Guide

379 Quick Installation Guide Step 1: INSULATION 2212 W. 5th Pl., Tempe, AZ 85268 (480) 967-8888 379 Quick Installation Guide Step 2: Step 3: *see attached literature for complete installation instructions Remove and discard packing

More information

REFERENCE ARMA-CHEK SILVER

REFERENCE ARMA-CHEK SILVER REFERENCE ARMA-CHEK SILVER LENZING GROUP S LYOCELL FIBRE PLANT www.armacell.com Arma-Chek Silver in the world s largest lyocell plant Austrian Vöcklabruck district is the site of Europe s biggest ever

More information

REFERENCE ARMA-CHEK SILVER

REFERENCE ARMA-CHEK SILVER REFERENCE LENZING GROUP S LYOCELL FIBRE PLANT www.armacell.com Arma-Chek Silver in the world s largest lyocell plant Austrian Vöcklabruck district is the site of Europe s biggest ever Arma-Chek project

More information

SECTION HVAC PIPING INSULATION

SECTION HVAC PIPING INSULATION SECTION 23 0719 HVAC PIPING INSULATION PART 1 - GENERAL 1.1 SUMMARY A. Includes But Not Limited To: 1. Furnish and install insulation on above ground refrigerant piping and fittings as described in Contract

More information

ITW INSULATION SYSTEMS

ITW INSULATION SYSTEMS ITW INSULATION SYSTEMS 1SCOPE TRYMER RIGID POLYISOCYANURATE INSULATION IN LIQUEFIED NATURAL GAS APPLICATIONS (-260 F) 1.1 This guideline covers the installation of Trymer* Rigid Polyisocyanurate Insulation

More information

SECTION HVAC INSULATION

SECTION HVAC INSULATION PART 1 GENERAL 1.1 SUMMARY SECTION 23 07 00 HVAC INSULATION A. Section Includes: 1. Ductwork insulation. 2. Duct liner. 3. Insulation jackets. 4. Equipment insulation 5. Piping system insulation. 6. Insulation

More information

Cold Work Cladding Fabrication & Application

Cold Work Cladding Fabrication & Application TRADE OF Industrial Insulation PHASE 2 Module 3 Substructures, Advanced Cold Work and Cladding UNIT: 4 Cold Work Cladding Fabrication & Application Produced by In cooperation with subject matter expert:

More information

ITW INSULATION SYSTEMS

ITW INSULATION SYSTEMS ITW INSULATION SYSTEMS 1SCOPE TRYMER RIGID POLYISOCYANURATE INSULATION IN LIQUEFIED NATURAL GAS APPLICATIONS (Cryogenic to -70 F) 1.1 This guideline covers the installation of TRYMER Rigid Polyisocyanurate

More information

A. Product Data: Identify thermal conductivity, thickness, and jackets (both factory and field applied, if any), for each type of product indicated.

A. Product Data: Identify thermal conductivity, thickness, and jackets (both factory and field applied, if any), for each type of product indicated. SECTION 23 07 13 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

RELIABLE, FLEXIBLE INSULATION TRUSTED TO PREVENT CONDENSATION

RELIABLE, FLEXIBLE INSULATION TRUSTED TO PREVENT CONDENSATION Closed-cell structure increases resistance to water vapor Reduce long-term heat gain and reduce energy loss Engineered wall thickness operates with the same line temperature in the same environment Thermal

More information

FIRE STATION 55 June 14, 2010

FIRE STATION 55 June 14, 2010 SECTION 15250 MECHANICAL INSULATION PART 1 - GENERAL 1.01 DESCRIPTION A. Work Includes 1. Insulation of Domestic Water Piping. 2. Pipe Insulation of refrigerant piping. 3. Insulation of ductwork. 4. Aluminum

More information

This specification describes the minimum requirements for industrial thermal insulation.

This specification describes the minimum requirements for industrial thermal insulation. 016/09/7 1/7 1.0 PURPOSE This specification describes the minimum requirements for industrial thermal insulation. Read it in conjunction with the applicable insulation and insulation finish specifications

More information

Installation Guidelines for ITW Insulation Systems Metal Jacketing Used on Insulated Pipe

Installation Guidelines for ITW Insulation Systems Metal Jacketing Used on Insulated Pipe Installation Guidelines for ITW Insulation Systems Metal Jacketing Used on Insulated Pipe 1 SCOPE 1.1 This guideline covers the installation of ITW Insulation Systems Pabco-Childers brand aluminum and

More information

EXPERIENCE COUNTS! Specializing in more than just products we put the competitive advantage at your fingertips.

EXPERIENCE COUNTS! Specializing in more than just products we put the competitive advantage at your fingertips. EXPERIENCE COUNTS! Specializing in more than just products we put the competitive advantage at your fingertips. Armaflex is a flexible, closed cell, elastomeric, nitrile rubber, insulation. It is a highly

More information

ITW INSULATION SYSTEMS

ITW INSULATION SYSTEMS Installation Guidelines for TRYMER Insulation ITW INSULATION SYSTEMS TRYMER Rigid Polyisocyanurate Insulation in Refrigeration Applications (-70 F to 35 F) 1 SCOPE 1.1 This guideline covers the installation

More information

A. Section Fire Procection, HVAC & Plumbing Penetration Firestopping. B. Section Interior Painting: Painting insulation jacket.

A. Section Fire Procection, HVAC & Plumbing Penetration Firestopping. B. Section Interior Painting: Painting insulation jacket. SECTION 230719 - HVAC PIPING INSULATION PART 1 GENERAL 1.1 SECTION INCLUDES A. Piping insulation. B. Jackets and accessories. 1.2 RELATED REQUIREMENTS A. Section 07813 - Fire Procection, HVAC & Plumbing

More information

ULVAShield non-metallic cladding installation procedures rev7

ULVAShield non-metallic cladding installation procedures rev7 ULVAShield non-metallic cladding installation procedures 9-17-rev7 ULVAShield non-metallic cladding installation procedures 1.0 Introduction Properly applied and maintained, the ULVAShield system is proven

More information

APPLICATION INSTRUCTIONS FOR MUFFL-JAC ACOUSTICAL JACKETING ON HOT PIPE INSULATION

APPLICATION INSTRUCTIONS FOR MUFFL-JAC ACOUSTICAL JACKETING ON HOT PIPE INSULATION APPLICATION INSTRUCTIONS FOR MUFFL-JAC ACOUSTICAL JACKETING ON HOT PIPE INSULATION Jim Young, Director of Technology and Pjeter Skrelji, Eastern Canada Regional Manager Vers. 2 November 19, 2011 Preliminary

More information

ArmAcell solutions for systems refrigeration, Air- conditioning & VeNtilAtioN

ArmAcell solutions for systems refrigeration, Air- conditioning & VeNtilAtioN ARMACELL SOLUTIONS FOR SYSTEMS REFRIGERATION, AIR- CONDITIONING & VENTILATION AF/Armaflex Armafix AF NH/Armaflex Armafix NH HT/Armaflex Armaflex Duct tubolit Split & duosplit Arma-Chek D Arma-Chek R Arma-Chek

More information

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for LIQUEFIED NATURAL GAS (LNG) CRYOGENIC REFRIGERATION CHILLED WATER

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for LIQUEFIED NATURAL GAS (LNG) CRYOGENIC REFRIGERATION CHILLED WATER INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for LIQUEFIED NATURAL GAS (LNG) CRYOGENIC REFRIGERATION CHILLED WATER Dyplast Products Copyright 2012 1 Rev 0112 DYPLAST PRODUCTS

More information

PITTWRAP CW PLUS JACKETING Product Datasheet

PITTWRAP CW PLUS JACKETING Product Datasheet PITTWRAP CW PLUS JACKETING Product Datasheet 1. Description and Area of Application PITTWRAP CW PLUS jacketing is a 1.27 mm (50 mil) thick self-sealing, modified bituminous membrane for protecting underground

More information

ENGINEERED INSULATION TO PREVENT CONDENSATION AND ENERGY LOSSES

ENGINEERED INSULATION TO PREVENT CONDENSATION AND ENERGY LOSSES ENGINEERED INSULATION TO PREVENT CONDENSATION AND ENERGY LOSSES Powered by TCPDF (www.tcpdf.org) Engineered wall thickness operates with the same line temperature in the same environment Minimize long-term

More information

ENGINEERED INSULATION TO PREVENT CONDENSATION AND ENERGY LOSSES

ENGINEERED INSULATION TO PREVENT CONDENSATION AND ENERGY LOSSES ENGINEERED INSULATION TO PREVENT CONDENSATION AND ENERGY LOSSES Powered by TCPDF (www.tcpdf.org) Engineered wall thickness operates with the same line temperature in the same environment Minimize long-term

More information

PIP INSA1000 Acoustic Insulation Systems Specification

PIP INSA1000 Acoustic Insulation Systems Specification TECHNICAL REVISION April 2015 Insulation PIP INSA1000 Acoustic Insulation Systems Specification PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities,

More information

NEW! THE FLEXIBLE PROFESSIONAL INSULATION WITH REVOLUTIONARY CHARACTERISTICS. even easier to use

NEW! THE FLEXIBLE PROFESSIONAL INSULATION WITH REVOLUTIONARY CHARACTERISTICS. even easier to use NEW! THE FLEXIBLE PROFESSIONAL INSULATION WITH even easier to use REVOLUTIONARY CHARACTERISTICS AF/ARMAFLEX the sustainable solution for use in air conditioning, refrigeration and process facilities The

More information

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS TRYMER RIGID POLYISOCYANURATE INSULATION IN HOT APPLICATIONS (80 F to 300 F) 1 SCOPE 1.1 This guideline covers the installation of TRYMER

More information

FLEXIBLE INSULATION TO PREVENT CONDENSATION

FLEXIBLE INSULATION TO PREVENT CONDENSATION FLEXIBLE INSULATION TO PREVENT CONDENSATION Powered by TCPDF (www.tcpdf.org) Closed-cell structure increases resistance to water vapor Reduce long-term heat gain and reduce energy loss Engineered wall

More information

A. This Section includes duct and plenum insulation; accessories and attachments; and sealing compounds.

A. This Section includes duct and plenum insulation; accessories and attachments; and sealing compounds. SECTION 230713 DUCT INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS TRYMER RIGID POLYISOCYANURATE INSULATION IN HOT APPLICATIONS (80 F to 300 F) 1 SCOPE 1.1 This guideline covers the installation of Trymer*

More information

BRANZ Appraisal Certificate # 461 (2010) Internal wet areas.

BRANZ Appraisal Certificate # 461 (2010) Internal wet areas. SPECIFICATION FOR PROTECTO WRAP AFM-WM FOR INTERNAL WET AREAS BRANZ Appraisal Certificate # 461 (2010) Internal wet areas AFM/WM INTERNAL 0104 Page 1 AFM-WM INTERNAL SPECIFICATION PRODUCT DESCRIPTION Anti

More information

THE RIGHT TOOLS & ACCESSORIES TO ENSURE THE BEST ARMAFLEX INSTALLATIONS

THE RIGHT TOOLS & ACCESSORIES TO ENSURE THE BEST ARMAFLEX INSTALLATIONS Powered by TCPDF (www.tcpdf.org) Powered by TCPDF (www.tcpdf.org) THE RIGHT TOOLS & ACCESSORIES TO ENSURE THE BEST ARMAFLEX INSTALLATIONS Complete set of professional tools and accessories Specially designed

More information

ITEM 458 WATERPROOFING FOR STRUCTURES

ITEM 458 WATERPROOFING FOR STRUCTURES ITEM 458 WATERPROOFING FOR STRUCTURES 458.1. Description. This Item shall govern for the furnishing and placing of waterproofing on concrete and steel bridge decks of railroad structures and on other structures

More information

SPECIFICATION GUIDELINES FOR THE USE OF CRYOGEL Z ON COLD PIPING AND EQUIPMENT

SPECIFICATION GUIDELINES FOR THE USE OF CRYOGEL Z ON COLD PIPING AND EQUIPMENT SPECIFICATION GUIDELINES FOR THE USE OF CRYOGEL Z ON COLD PIPING AND EQUIPMENT Page 1 of 15 Ver. 3-0 March 2010 TABLE OF CONTENTS 1. Scope... 3 2. General System Requirements... 3 3. Installation Details...

More information

PITTWRAP B100 JACKETING Product Datasheet

PITTWRAP B100 JACKETING Product Datasheet PITTWRAP B100 JACKETING Product Datasheet 1. Description and Area of Application PITTWRAP B100 jacketing is a self-sealing, aluminum butyl laminate used for protecting above ground FOAMGLAS insulation

More information

THE PRE-COVERED ARMAFLEX INSULATION DESIGNED FOR FAST INSTALLATION, DURABILITY AND EASY CLEANING

THE PRE-COVERED ARMAFLEX INSULATION DESIGNED FOR FAST INSTALLATION, DURABILITY AND EASY CLEANING Arma-Chek Silver THE PRE-COVERED ARMAFLEX INSULATION DESIGNED FOR FAST INSTALLATION, DURABILITY AND EASY CLEANING Suitable for food production areas 2-in-1 pre-covered system, saves installation time compared

More information

SECTION PIPING INSULATION

SECTION PIPING INSULATION SECTION 23 07 19 PIPING INSULATION PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Piping insulation for refrigerant piping within building envelope. 2. Furnishing and installation of insulation.

More information

Plumbing Pipe Insulation Specification Submitted by: Armacell LLC. Plumbing Pipe Insulation Specification Armacell LLC 1

Plumbing Pipe Insulation Specification Submitted by: Armacell LLC. Plumbing Pipe Insulation Specification Armacell LLC 1 Plumbing Pipe Insulation Specification 2005 Armacell LLC 1 Part 1 General 1.01 Scope of Work: A. Provide piping insulation as specified below. The purpose of the thermal pipe insulation is for condensation

More information

PROJ. NO SECTION HVAC DUCT INSULATION

PROJ. NO SECTION HVAC DUCT INSULATION SECTION 23 07 13 HVAC DUCT INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

THE HIGH PERFORMANCE INSULATION FOR AIR CONDITIONING, HEATING, REFRIGERATION AND PLUMBING

THE HIGH PERFORMANCE INSULATION FOR AIR CONDITIONING, HEATING, REFRIGERATION AND PLUMBING THE HIGH PERFORMANCE INSULATION FOR AIR CONDITIONING, HEATING, REFRIGERATION AND PLUMBING Fire tested for vertical pipe chases to NFPA274 Complies with National Construction Code (NCC) Low thermal conductivity,

More information

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS TRYMER RIGID POLYISOCYANURATE INSULATION IN REFRIGERATION APPLICATIONS (-70 F to 35 F) 1 SCOPE 1.1 This guideline covers the installation

More information

Insulation engineered to prevent condensation and energy loss

Insulation engineered to prevent condensation and energy loss Insulation engineered to prevent condensation and energy loss Triple security: effective condensation control, FM Approved and excellent fire performance Highly energy efficient to give long-term energy-saving

More information

Caparol System PRO Data sheet

Caparol System PRO Data sheet System features Expanded polystyrene insulation Cost effective solution Excellent detailing options Proven technology Wide variety of colours Reliable protection and crack resistance Proven track record

More information

Division 15 INSULATION Section 15100

Division 15 INSULATION Section 15100 Page 1 of 5 SECTION PAGE PART 1 GENERAL 2 1.1 General 2 1.2 References 2 1.3 Work Included 2 1.4 Related Work 2 1.5 Quality Assurance 3 PART 2 PRODUCTS 3 2.1 Description 3 PART 3 EXECUTION 3 3.1 Workmanship

More information

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section PIPE AND EQUIPMENT INSULATION

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section PIPE AND EQUIPMENT INSULATION PART 1 GENERAL 1.01 SUMMARY Section 15145 This Section includes insulation for piping and equipment as called out on the Plans. 1.02 MEASUREMENT AND PAYMENT No separate payment will be provided for the

More information

B. Refer to Section : Air Distribution for lined ductwork requirements.

B. Refer to Section : Air Distribution for lined ductwork requirements. SECTION 230700 MECHANICAL INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

LT/ArmaFlex. Industrial INSULATION FOR THE OIL AND GAS INDUSTRY. High density industrial grade FEF installation

LT/ArmaFlex. Industrial INSULATION FOR THE OIL AND GAS INDUSTRY. High density industrial grade FEF installation INSULATION FOR THE OIL AND GAS INDUSTRY LT/ArmaFlex Industrial High density industrial grade FEF installation // Built-in water vapour barrier mitigates risk of corrosion under insulation (CUI) // Low

More information

For wooden fabricated underlay e.g. plywood, care must be taken to store the material in an area where it will not become damp or contaminated.

For wooden fabricated underlay e.g. plywood, care must be taken to store the material in an area where it will not become damp or contaminated. Page 1 The preparation/dryness of the subfloor and installation procedures should all be as BS 8203: 2001. i.e.: The relative humidity of a solid subfloor should be below 75%RH when tested with a Hygrometer

More information

For system application details, refer to the corresponding Baumit Method Statement before submitting a tender.

For system application details, refer to the corresponding Baumit Method Statement before submitting a tender. SPECIFICATION OF MATERIALS EXTERNAL WALL INSULATION SYSTEM (Adhesively Fixed). For system application details, refer to the corresponding Baumit Method Statement before submitting a tender. Baumit Ltd

More information

For system application details, refer to the corresponding Baumit Method Statement before submitting a tender.

For system application details, refer to the corresponding Baumit Method Statement before submitting a tender. SPECIFICATION OF MATERIALS EXTERNAL WALL INSULATION SYSTEM (Adhesively Fixed). For system application details, refer to the corresponding Baumit Method Statement before submitting a tender. Baumit Ltd

More information

Design & Installation Manual

Design & Installation Manual Design & Installation Manual Insert Registered Legal Entity name, address and number, or all other details as required to comply with regional regulations Ceramic Fibre Lining Systems CONTENTS Introduction

More information

Master Insulation Guide Specification for Mechanical Systems

Master Insulation Guide Specification for Mechanical Systems for Mechanical Systems AP Armaflex Pipe Insulation AP Armaflex W Pipe Insulation AP Armaflex SS Pipe Insulation AP Armaflex Sheet and Roll Insulation AP Armaflex SA Sheet and Roll Insulation ArmaTuff Laminated

More information

A. Deliver material to job site in original, nonbroken, factory packaging, labeled with manufacturer's density and thickness.

A. Deliver material to job site in original, nonbroken, factory packaging, labeled with manufacturer's density and thickness. SECTION 15250 PIPING AND EQUIPMENT INSULATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract including General and Supplementary Conditions, Division 1 Specification

More information

For wooden fabricated underlay e.g. plywood, care must be taken to store the material in an area where it will not become damp or contaminated.

For wooden fabricated underlay e.g. plywood, care must be taken to store the material in an area where it will not become damp or contaminated. Page 1 The preparation/dryness of the subfloor and installation procedures should all be as BS 8203: 2001. i.e.: The relative humidity of a solid subfloor should be below 75%RH when tested with a Hygrometer

More information

For wooden fabricated underlay e.g. plywood, care must be taken to store the material in an area where it will not become damp or contaminated.

For wooden fabricated underlay e.g. plywood, care must be taken to store the material in an area where it will not become damp or contaminated. Page 1 1.30MM VERTICAL AND T The preparation/dryness of the wall / subfloor and installation procedures should all be as BS 476. i.e.: The relative humidity of the wall must be below 75%RH when tested

More information

Installation Instructions

Installation Instructions Installation Instructions Installing Real Wood Veneers Wood Veneer Wallcovering Please read these instructions prior to installation. If you have any questions regarding the installation procedures contained

More information

NOTE: Components must be stored at 12 C (min) for at least 24 hours prior to use.

NOTE: Components must be stored at 12 C (min) for at least 24 hours prior to use. PUB. NO. 360.5.2002 LEADERS IN CORROSION PREVENTION THE PROTECTION OF STRUCTURAL STEEL AND PIPEWORK USING THE DENSO STEELCOAT 400 SYSTEM INSTRUCTIONS FOR USE Due to the wide variety of structures, access

More information

SILICONE ROOF COATING RESTORATION (RCR) SYSTEM OVER METAL ROOF PANEL

SILICONE ROOF COATING RESTORATION (RCR) SYSTEM OVER METAL ROOF PANEL SILICONE ROOF COATING RESTORATION (RCR) SYSTEM OVER METAL ROOF PANEL Part 1. 1.1 Description General Conditions A. Scope of Work Provide all materials, labor and equipment required for the installation

More information

1.2 The Engineer shall select appropriate sections of the specification to ensure that the specification is comprehensive for specified work.

1.2 The Engineer shall select appropriate sections of the specification to ensure that the specification is comprehensive for specified work. STAC Coating System Specification & Installation Guide 1.0 Scope 1.1 This specification may be used for the priming, caulking and wrapping with the STAC Petrolatum Coating System of any of the following

More information

Report. Robert-Bosch-Str Münster Germany. Report number: A E. Date: 14 February TS/YW/LvI/A E-RA

Report. Robert-Bosch-Str Münster Germany. Report number: A E. Date: 14 February TS/YW/LvI/A E-RA Report Member ONRI ISO-9001: 2000 certified Laboratory for Acoustics Determination of the insertion loss or sound power insulation of Arma-Chek Sound pipe insulation, manufacturer Armacell Report number

More information

Report. Robert-Bosch-Str Münster Germany. Report number: A E. Date: 14 February TS/YW/LvI/A E-RA

Report. Robert-Bosch-Str Münster Germany. Report number: A E. Date: 14 February TS/YW/LvI/A E-RA Report Member ONRI ISO-9001: 2000 certified Laboratory for Acoustics Determination of the insertion loss or sound power insulation of Arma-Chek Sound pipe insulation, manufacturer Armacell Report number

More information

Sika KAB combination joint waterbars waterstopping systems

Sika KAB combination joint waterbars waterstopping systems PRODUCT DATA SHEET Sika KAB combination joint waterbars Waterbars for waterproofing construction and crack induced shrinkage joints in new reinforced concrete structures PRODUCT- DESCRIPTION KAB 125/KAB

More information

J41 Reinforced bitumen membrane roof coverings

J41 Reinforced bitumen membrane roof coverings J41 Reinforced bitumen membrane roof coverings To be read with Preliminaries/ General conditions. TYPES OF COVERING 115A SINGLE LAYER REINFORCED BITUMEN MEMBRANE WARM DECK ROOF COVERING warm roofing system

More information

KNOW-HOW. Quality characteristics of technical insulation materials: Fast and reliable installation is crucial

KNOW-HOW. Quality characteristics of technical insulation materials: Fast and reliable installation is crucial KNOW-HOW Quality characteristics of technical insulation materials: Fast and reliable installation is crucial TIME IS MONEY Professional application is all-important in cold insulation. So installation

More information

Installation Guidance Note: Flotex Sheet

Installation Guidance Note: Flotex Sheet General Advice The appearance, performance and durability of the installed floorcovering will be determined to a large extent by the quality of the prepared subfloor and the conditions in which they are

More information

Mechanical Insulation for Refrigeration Systems

Mechanical Insulation for Refrigeration Systems Mechanical Insulation for Refrigeration Systems INDUSTRIAL REFRIGERATION CONSORTIUM RESEARCH & TECHNOLOGY FORUM MAY 2-3, 2012 Peter Gauchel, President/CEO L&C Insulation Inc. Overview Current trends in

More information

INSTALLATION GUIDELINE FOR TRYMER INSULATION

INSTALLATION GUIDELINE FOR TRYMER INSULATION INSTALLATION GUIDELINE FOR TRYMER INSULATION TRYMER RIGID POLYISOCYANURATE INSULATION IN CHILLED WATER APPLICATIONS (35 F to 60 F) 1 SCOPE 1.1 This guideline covers the installation of Trymer Rigid Polyisocyanurate

More information

Jointofeu Series Fire Barriers I Installation Instructions

Jointofeu Series Fire Barriers I Installation Instructions Product Description Jointofeu is manufactured from a woven mineral wool and installed into expansion joints with a heat resistant adhesive. It is suitable for both vertical and horizontal expansion joints

More information

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700 SECTION 22 0700 - PLUMBING INSULATION PART 1 - GENERAL 1.1 DESCRIPTION OF WORK: A. All work covered in this section consists of furnishing all labor, equipment, materials and accessories, and performing

More information

PITTWRAP CF JACKETING Product Datasheet

PITTWRAP CF JACKETING Product Datasheet PITTWRAP CF JACKETING Product Datasheet 1. Description and Area of Application PITTWRAP CF jacketing is a cellulose free fiberglass reinforced vapor retarder insulation jacketing, used for protecting above

More information

Recommended Installation & Maintenance Guidelines

Recommended Installation & Maintenance Guidelines T-TUBES CLEAN TECHNOLOGY INSULATION SYSTEM Recommended Installation & Maintenance Guidelines Contents: Description: Page: General.3 Simple Installation Tooling.4 Cutting & Installing..5 Do s...5 Don ts..5

More information

Installation Instructions ALUTRIX 600 ALUTRIX FR

Installation Instructions ALUTRIX 600 ALUTRIX FR SELF-ADHESIVE VAPOUR BARRIER Installation Instructions ALUTRIX 600 ALUTRIX FR WWW.ALUTRIX.COM 3 FOREWORD This publication is designed to assist the contractor when working with ALUTRIX self-adhesive vapour

More information

Revision:C Pipework Insulation Issued:14/11/2012 PIPEWORK INSULATION CU14. 14/11/2012 Page 1 of 10 Pipework Insulation - RevC

Revision:C Pipework Insulation Issued:14/11/2012 PIPEWORK INSULATION CU14. 14/11/2012 Page 1 of 10 Pipework Insulation - RevC PIPEWORK INSULATION CU14 14/11/2012 Page 1 of 10 - RevC Contents INTRODUCTION 5 General 5 Scope 5 Surfaces to be Insulated 5 Pumps, Turbines etc 5 Performance 6 Minimum Pipe Insulation Thickness 6 Physical

More information

Concrete Soffit Direct Fix

Concrete Soffit Direct Fix Installation Guide Concrete Soffit Direct Fix Recommended Pattern insulation boards may be installed in any pattern. The recommended pattern is a square-set pattern, for simplest and quickest configuration

More information

PIPEWORK INSULATION. 14/ Page 1 of 10 Pipework Insulation Rev D

PIPEWORK INSULATION. 14/ Page 1 of 10 Pipework Insulation Rev D PIPEWORK INSULATION 14/10-2014 Page 1 of 10 Pipework Insulation Rev D Contents INTRODUCTION General Scope Surfaces to be Insulated Pumps, Turbines etc Performance Minimum Pipe Insulation Thickness Physical

More information