1 AIRAH Insulation Products for BCA 2010 Vol 1 Section J Energy Efficiency Steve Franetic Technical Services Manager (NSW/ACT) September 2010
2 PART J1 BUILDING FABRIC Topics J1 Building Fabric Insulation J5.2 Ductwork Insulation J5.4 Pipe Insulation Improve the content of your specification - to simply include the clause to meet the requirements of BCA 2010 Part J is NOT acceptable because many contractors are not BCA savy. 2
3 PART J1 BUILDING FABRIC J1.2 Thermal construction - general Insulation must comply with AS/NZS Bulk insulation to be tested by a NATA certified lab - Certification from an independent accredited organisation - not just a statement from a manufacturer or supplier 3
4 PART J1 BUILDING FABRIC J1.2 Thermal construction - general Insulation must be against stud member - Specify 600mm wide insulation to fill steel stud cavity - Standard batts are 580mm wide for timber frame Form a continuous thermal barrier with ceilings, walls, floors - Include insulation under box gutters Reflective insulation must be installed with the necessary airspace to achieve the required R-Value - R-value of reflective insulation is calculated, based on specific criteria that is particular to each building system 4
5 PART J1 BUILDING FABRIC J1.2 Thermal construction - general Bulk insulation must be installed so that it maintains its thickness, other than where it is compressed between cladding and supporting members Metal sheet roofing fixed to metal purlins that does not have a ceiling lining or has a ceiling lining fixed directly to those metal purlins, must have a thermal break with a material R-Value R0.2 - building blanket is a deemed-to-comply thermal break compressed bulk insulation is considered to achieve an R-Value of not less than 0.2 BCA 2010 Vol 2, Part
6 PART J1 BUILDING FABRIC J1.3 Roof and ceiling construction Safety wire to be installed taut 2mm gauge wire will not stretch Insulation spacer raises the roof from the purlin to maintain insulation loft 6
7 J1 BUILDING FABRIC J1.3 Roof and ceiling construction PART Climate Zone 4, 5 and 6 Total R3.2 (downwards) achieved with 100mm (Material R2.5) foil faced blanket with 75mm insulation spacer Climate Zone 7 Total R3.7 (upwards) achieved with 125mm (Material R3.5) foil faced blanket with 100mm insulation spacer 7
8 PART J1 BUILDING FABRIC J1.3 Roof and ceiling construction Climate Zone 8 Total R4.8 (upwards) achieved with 75mm (Material R1.8) foil faced blanket incorporating 40mm high compressive strength (300kpa) extruded foam spacer and R3.0 batts in the ceiling Climate Zone 2 Total R4.2 / 3.7 / 3.2 (downwards) achieved with 125mm (Material R3.5) foil faced blanket with 100mm insulation spacer 8
9 PART J1 BUILDING FABRIC J1.3 Roof and ceiling construction Climate Zone 4, 5 and 6 Total R3.2 (downwards) achieved with 100mm (Material R3.0) 32kg/m3 foil (reflective or non-reflective) faced glasswool sheets 9
10 PART J1 BUILDING FABRIC J1.5 Walls Climate Zone 4, 5 and 6 Total R2.8 (reduced by 0.5 with concessions density and orientation or shading) Climate Zone 7 Total R2.8 (reduced to Total R1.4 with concession glazing) achieved with 90mm (Material R2.5) HD Wall Batts 10
11 PART J1 BUILDING FABRIC J1.5 Walls Climate zone 8 Total R3.8 achieved with 150mm (R4.2) HD Wall Batts Climate zone 2 Total R3.3 achieved with 2 layers of 75mm (R1.8) (reduced by 0.5 with concessions density and orientation or shading) (reduced by 0.5 with concession surface solar adsorptance value 0.6) Lightweight external cladding fixed to a metal frame and has a wall lining that is fixed directly to the same metal frame must have a thermal break, consisting of a material with an R-Value of R0.2 11
12 PART J1 BUILDING FABRIC J1.6 Floors Total R2.0 suspended floor with enclosed conditioned space in zones 1-7 achieved with 75mm (Material R2.3) 32kg/m3 foil (reflective or non-reflective) faced glasswool sheets Total R1.0 suspended floor with enclosed non-conditioned space (2, 5, 6) achieved with 50mm (Material R1.5) 32kg/m3 foil (reflective or non-reflective) faced glasswool sheets 12
13 SPECIFICATION J5.2 Ductwork Insulation Comply with AS/NZS Minimum material R2.0 in climate zones 1-7 achieved with 75mm thick - (R2.3) FI 32 Semi-Rigid or (R2.0) FI 22 Ductwrap Minimum material R1.2 in a conditioned space in climate zones 2 & 5 with 38mm thick - (R1.2) FI 32 Semi-Rigid or 50mm (R1.5) FI 22 Ductwrap Minimum material R1.0 in a conditioned space in climate zones 4, 6 & 7 with 38mm thick - (R1.2) FI 32 Semi-Rigid or 38mm (R1.1) FI 22 Ductwrap Minimum material R1.0 for flexible ductwork 3m in length 13
14 SPECIFICATION J5.4 Pipe Insulation Comply with AS/NZS (Material R-Value or formula) Be able to withstand the temperatures within the piping Heating water pipe - minimum material R1.0 / 1.1 / 1.2 / 1.5 Cooling water pipe too many to restate (R0.6 R2.2) 14
15 SPECIFICATION J5.4 Pipe Insulation Glasswool Thickness Material R-Value Rubber Thickness Material R-Value 20mm 0.8 9mm mm mm mm mm mm mm mm mm
16 SPECIFICATION J5.4 Pipe Insulation Comply with AS/NZS As an alternative to test method ASTM C335, the Material R-value of preformed pipe insulation may be calculated as follows: The thermal conductivity shall be measured (Note: Conductivity varies with temperature) The following formula shall then be applied R = (r 2 log e (r 2 /r 1 ))/k where R = Material R-value of the preformed pipe insulation section r 1 = inner radius of the pipe insulation r 2 = outer radius of the pipe insulation k = thermal conductivity of the insulation in planar form 16
17 SPECIFICATION J5.4 Correct specification to increase productivity Reduce time spent on: misunderstandings corrections disputes and non-compliant works Fletcher Insulation Specifier Advisory Service T E. W. insulation.com.au 17
18 SPECIFICATION J5.4 Avoid risk with fire-resistant insulation 18
NCC Volume Two Energy Efficiency
NCC Volume Two Energy Efficiency Insert Corporate logo here Commonwealth of Australia and States and Territories of Australia, 2016 2016 Commonwealth of Australia and States and Territories of Australia
More informationConcrete Soffit Direct Fix
Installation Guide Concrete Soffit Direct Fix Recommended Pattern insulation boards may be installed in any pattern. The recommended pattern is a square-set pattern, for simplest and quickest configuration
More informationInsulbreak. Insulation. thermal break solution
Insulation A4/8 TB AW2199 Issue 8 May 2017 Insulbreak thermal break solution 3-in-1 Insulation, thermal break and vapour barrier Delivers a R0.20 thermal break solution for steel-framed construction Helps
More informationInsuliner. Insulation REFLECTIVE INSULATION FOR USE WHERE
Insulation A4/8 TB055G2 AW2235 Issue 8 Sep 2017 Insuliner REFLECTIVE INSULATION FOR USE WHERE it acts as the WALL OR CEILING LINING Group 2 NCC fire classification Designed for warehouses and commercial
More informationInsulbreak. Insulation. thermal break solution
Insulation A4/8 TB AW1559 Issue 4 Nov 2013 Insulbreak thermal break solution 3-in-1 Insulation, thermal break and vapour barrier Delivers a R0.20 thermal break solution for steel-framed construction Helps
More informationBuilding regulations now in force
BCA Section J: Guide to compliance Publication date July 2008 Building regulations now in force BCA SECTION J: Mandatory energy efficiency measures for non-residential construction The new BCA Section
More informationEarthwool Glasswool Insulation
Global-Mark Pty Ltd, Suite 4.07, 32 Delhi Road, North Ryde NSW 2113, Australia Tel: +61 (0)2 9886 0222 - www.global-mark.com.au Certificate Holder: Knauf Insulation Pty Ltd Unit 2 44 Borthwick Avenue Murarrie,
More informationSECTION B Steel Frame Wall Systems. Contents. Steel Stud Selection Tables. Introduction. Design Considerations. Installation.
SECTION B Steel Frame Wall Systems. Contents. SUBJECT Steel Stud Selection Tables Introduction Design Considerations Installation Components PAGE B2 B4 B4 B6 B7 System Specifications Single Stud Staggered
More information171 OLD BEGA HOSPITAL
171 OLD BEGA HOSPITAL SECTION J REPORT DESIGN STATEMENT Pursuant to BCA A2.2; this report relies on supplied documentation for assessment in regards to adopting measures contributing to deemed-to- of designed
More informationASHGRID ROOF SPACER. Insulation Product Selector NOW AVAILABLE WITH PRE-LOADED SCREWS
ASHGRID ROOF SPACER Insulation Product Selector NOW AVAILABLE WITH PRE-LOADED SCREWS .0 2 DESIGNING FOR BCA COMPLIANCE WITH SPACERS are mandatory in the Building Code of Australia (BCA) and insulation
More informationSection 10 Residential Zone
231 Section 10 Residential Zone Proposed Draft Amendments to Section 10: Residential Note: new text to be added to the District Plan is shown as coloured underlined and text to be removed is shown in coloured
More informationPRODUCT GUIDE AVAILABLE WITH PRE-LOADED SCREWS
Ashgrid Roof Spacer PRODUCT GUIDE AVAILABLE WITH PRE-LOADED SCREWS 1.0 Designing for BCA compliance with spacers Minimum energy efficiency standards for commercial buildings are mandatory in the National
More informationPINK BATTS INSULATION. Product. Scope. Building Regulations. Appraisal No. 238 [2012]
PINK BATTS INSULATION This Appraisal replaces BRANZ Appraisal No. 238 (2008). Amended 29 March 2017 BRANZ Appraisals Technical Assessments of products for building and construction. Product 1.1 Pink Batts
More informationAirspace R-Values. Educational Overview. Revised 12/6/2016
Airspace R-Values Educational Overview Revised 12/6/2016 Introduction Airspaces contained within building envelope assemblies are known to contribute to thermal performance. But, the actual R-value for
More informationAPPENDIX DETAIL (1) INSULATION HAS 3-INCH TOP INSPECTION GAP AND EXTENDS 24 INCHES BELOW GRADE
The sections and construction details in Details 502.2.1.5(1), 502.2.1.5(2), 502.2.1.5(3), 502.2.1.5(4) and 502.2.1.5(5), and Tables 502.2.3.1(1), 502.2.3.1(2), 502.2.3.1(3), 502.2.3.2, 502.2.3.3, 502.2.3.5
More informationContents. Timber framing to be installed in accordance with AS:1684 Metal framing to be installed in accordance with BCA Volume: 2
Contents BCA Codes 3 General 4 Fire Performances Thermal and Acoustic Insulation Wall Installation 4 Timber Frame Separation Walls 5 Steel Frame Separation Walls 6 External Fire Rated Walls 7 Floor Installation
More informationEARTHWOOL GLASSWOOL INSULATION. Product. Scope. Building Regulations. Appraisal No. 648 [2016]
EARTHWOOL GLASSWOOL This Appraisal replaces BRANZ Appraisal No. 648 (2009) BRANZ Appraisals Technical Assessments of products for building and construction. Product 1.1 Earthwool glasswool insulation is
More informationFire Safety Compliance Guide: Wall and Ceiling Linings
Insulation A4/8 AW2140 Issue 1a Oct 2016 Fire Safety Compliance Guide: Wall and Ceiling Linings FOR WAREHOUSES AND COMMERCIAL OR INDUSTRIAL SHEDS WHERE THE INSULATION ACTS AS THE WALL OR CEILING LINING
More informationGary MacFarlane CMG Contracting. On behalf of. TICA The Insulation Contractors Association
Gary MacFarlane CMG Contracting On behalf of TICA The Insulation Contractors Association Materials Including Types, Availability and Thicknesses Thickness Calculations for Chilled Water Piping Costing
More informationUSGBORAL.COM SYSTEMS+ INTRODUCTION OUTRWALL BRICK VENEER WALLS EXTERNAL WALLS INNOVATIVE SYSTEMS SOLUTIONS
USGBORAL.COM S+ E 2 E 5 E 9 E 10 INTRODUCTION OUTRWALL WALLS FIRECLAD E EXTERNAL WALLS INNOVATIVE S SOLUTIONS E EXTERNAL WALLS INTRODUCTION The following USG Boral external wall systems are outlined in
More informationINSULATION HANDBOOK. Part 1: Thermal Performance. Total R-Value calculations for typical building applications
INSULATION HANDBOOK Part : Thermal Performance Total R-Value calculations for typical building applications An independent publication of the Insulation Council of Australia and New Zealand March 008 RRP
More informationRetroshield XL TM. Insulation THERMO REFLECTIVE INSULATION
Insulation A4/6 TB055F AW2002 Issue 4 Sept 2015 THERMO REFLECTIVE INSULATION Innovative cross-linked closed-cell insulation core Improved Class 0 fire performance to stringent international standards 3-in-1
More informationMulti-layer Insulation Blanket for Walls
Multilayer Insulation Blanket for Walls Thermal Insulation in a 40mm thin, flexible, multilayer membrane Meets requirements of L1A, L1B 2010 High performance wall insulation Full Agrément certification
More informationA4/8 PS AW2324D Issue 10 May Permishield
Insulation A4/8 PS AW2324D Issue 10 May 2018 Vapour-permeable INSULATION MEMBRANE 3-in-1 Insulation, thermal break and vapour-permeable sarking Helps achieve a 6-star house energy rating Fibre-free, non-allergenic,
More informationMulti-layer Insulation Blanket for Walls
Multilayer Insulation Blanket for Walls Thermal Insulation in a 40mm thin, flexible, multilayer membrane Meets requirements of L1A, L1B 2010 High performance wall insulation Full Agrément certification
More informationStart installing now
Start installing now Earthwool insulation is made using recycled glass and with the revolutionary ECOSE Technology binder. It is super-soft to handle, easy to cut and contains no added formaldehyde or
More informationFire Safety Compliance Guide: Wall and Ceiling Linings
Insulation A4/8 KIAU0008 Issue 4 Mar 2019 Fire Safety Compliance Guide: Wall and Ceiling Linings FOR WAREHOUSES AND COMMERCIAL OR INDUSTRIAL SHEDS WHERE THE INSULATION ACTS AS THE WALL OR CEILING LINING
More informationInsulation Installation
passive design 108 4.8 INSULATION INSTALLATION Insulation Installation Installing insulation or additional insulation in an existing dwelling can make a significant difference to the performance of the
More informationMulti-layer Insulation Blanket for
Multi-layer Insulation Blanket for Walls Thermal Insulation in a thin, flexible, multi-layer membrane High performance wall insulation Fully certificated Thermally tested in accordance with EN12667 High
More informationA4/6 PS AW1551 Issue 4 Nov Permishield
Insulation A4/6 PS AW1551 Issue 4 Nov 2013 Vapour-permeable INSULATION MEMBRANE 3-in-1 Insulation, thermal break and vapour-permeable sarking Helps achieve a 6-star house energy rating Fibre-free, non-allergenic,
More informationA4/8 PS AW2002 Issue 6 Sept Permishield
Insulation A4/8 PS AW2002 Issue 6 Sept 2015 Vapour-permeable INSULATION MEMBRANE 3-in-1 Insulation, thermal break and vapour-permeable sarking Helps achieve a 6-star house energy rating Fibre-free, non-allergenic,
More informationHVAC and Industrial Insulation
The future of Insulation HVAC and Industrial Insulation We safely deliver extraordinary value to our customers Our customers At Fletcher Insulation we pride ourselves on delivering extraordinary value
More informationSuperior Performance Phenolic Insulation. SR/FB Insulation for Steel and Timber Frame. Walls AS LOW AS 10/4803
Superior Performance Phenolic Insulation Walls Insulation for Steel and Timber Frame AS LOW AS 020 10/4803 Data Sheet Insulation for Steel and Timber Frame Safe-R Framing Board is designed for use with
More informationSuperior Performance Phenolic Insulation. SR/FB Insulation for Steel and Timber Frame. Walls AS LOW AS 10/4803
Superior Performance Phenolic Insulation Walls Insulation for Steel and Timber Frame AS LOW AS 020 10/4803 Data Sheet Insulation for Steel and Timber Frame Safe-R Framing Board is designed for use with
More informationResCom Board BCA Certificate number: CM40009 Rev6. Date of issue: 22/12/2017. Don Grehan Unrestricted Building Certifier
Certification Body: ABN: 80 111 217 568 JAS-ANZ Accreditation No. Z4450210AK PO Box 7144, Sippy Downs Qld 4556 +61 (07) 5445 2199 www.certmark.org Certificate Holder: ABN: 47 151 952 742 3 Allen Street
More informationSECTION THERMAL INSULATION
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 21 13 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable
More informationPREMIER INSULATION. Product. Scope. Building Regulations. Technical Specification. Appraisal No. 509 [2014]
This Appraisal replaces BRANZ Appraisal No. 509 (2013) Amended 24 May 2018 BRANZ Appraisals Technical Assessments of products for building and construction. Product 1.1 Premier Insulation is a resin bonded
More informationfireseal Party Wall Design Guide CLASS 1 BUILDINGS PARTY WALL DESIGN GUIDE PAGE 1
fireseal Party Wall Design Guide CLASS 1 BUILDINGS PARTY WALL DESIGN GUIDE PAGE 1 1.0 INTRODUCTION CONTENTS The stability of a building in a fire depends upon the performance of all the component parts
More informationProduct Catalogue
www.bluechipgroup.net.au Product Catalogue INSULATION PRODUCTS 4 INSULSARK Heavy Duty Sarking 6 8 INSULBLUE iboard C8 Foam Insulation Cavity Insulation Board 10 iboard S10 Soffit Insulation Board 12 iboard
More informationSECTION E Ceiling Systems. Contents. Introduction. Design Considerations. Installation. Components. System Specifications. Floor/Ceiling Systems
SECTION E Ceiling Systems. Contents. SUBJECT Introduction Design Considerations Installation Components PAGE E2 E2 E4 E4 System Specifications Floor/Ceiling Systems Roof/Ceiling Systems E6 E12 Floor or
More informationINSULATION, PLASTERBOARD & BUILDING REGULATIONS
2016 / 2017 INSULATION, PLASTERBOARD & BUILDING REGULATIONS ENGLA D EDITION N The key to success Keep compliant by using the products MKM stock Continue using traditional construction methods Trust your
More informationPINK BATTS POLYESTER INSULATION. Product. Scope. Building Regulations. Appraisal No. 999 [2018] Appraisal No. 999 (2018) BRANZ Appraisals
OVER 80% RECYCLED GLASS PROVEN SAFE OVER 80% RECYCLED GLASS PROVEN SAFE PINK BATTS POLYESTER BRANZ Appraisals Technical Assessments of products for building and construction. Product 1.1 Pink Batts Polyester
More informationPrice List Effective From 1st March
List Effective From st March 2008 www.pinkbatts.com.au RESIDENTIAL COMMERCIAL INDUSTRIAL INDEX Quantity Calculator How many s will I need...3 Residential Thermal Insulation Pink Batts (Walls)...4 Pink
More informationNATIONAL ANNEX TO STANDARD. SFS-EN 1995 EUROCODE 5: DESIGN OF TIMBER STRUCTURES Part 1-2: General. Structural fire design
1 ANNEX 17 NATIONAL ANNEX TO STANDARD SFS-EN 1995 EUROCODE 5: DESIGN OF TIMBER STRUCTURES Part 1-2: General. Structural fire design Foreword This National Annex is issued to be used together with Standard
More informationEARTHWOOL INSULATION STANDARD SPECIFICATION
EARTHWOOL INSULATION STANDARD SPECIFICATION 1. GENERAL This specification relates to Knauf Insulation EarthWool glasswool insulation installed, laid, hung, fixed or fitted as thermal insulation: It includes:
More informationSuperior Performance PIR Insulation. XO/FB Insulaton for Steel & Timber Frame. Walls 12/4956
Superior Performance PIR Insulation Walls Insulaton for Steel & Timber Frame 021 12/4956 Data Sheet XtroLiner Framing Board is designed for use in a wide range of construction including steel or timber
More informationAustralian/New Zealand Standard
AS/NZS 4859.1:2002 (Incorporating Amendment No. 1) AS/NZS 4859.1:2002 Australian/New Zealand Standard Materials for the thermal insulation of buildings Part 1: General criteria and technical provisions
More informationWhere to Draw the Line with Thermal Boundaries
PHRC Webinar Series Tuesday, October 13, 2015 @ 1pm Where to Draw the Line with Thermal Boundaries Christopher Hine Housing and Land Development Specialist Pennsylvania Housing Research Center 219 Sackett
More informationParty Wall Roof Junction Design Guide
fireseal Party Wall Roof Junction Design Guide CLASS 1 BUILDINGS Party Wall Design Guide 1 Expert insulation advice Project and value engineering support Industry-leading building science research A wealth
More informationSuperior Performance PIR Insulation XO/FB. Insulaton for Steel & Timber Frame. Walls 12/4956
Superior Performance PIR Insulation Walls Insulaton for Steel & Timber Frame 021 12/4956 Data Sheet XtroLiner is a superior performance insulation with a lambda value of 0.021 Wm/K and a Euroclass C fire
More informationMulti-layer Insulation Blanket for Walls
Multilayer Insulation Blanket for Walls Thermal Insulation in a 40mm thin, flexible, multilayer membrane Meets requirements of L1A, L1B 2010 High performance wall insulation Full Agrément certification
More informationLABC REGISTERED THERMAL SYSTEMS TO PART L
LABC REGISTERED THERMAL SYSTEMS TO PART L 2006 AND 2010 MULTI-FOIL INSULATION AND BREATHER MEMBRANES Contents 1 Foreword...4 2 How TLX Multi-foils Work...5 3 The TLX Range...6 4 U Values and Condensation
More informationDivision VII Thermal and Moisture Protection
Division VII Thermal and Moisture Protection SECTION 07200 - BUILDING INSULATION PART 1 - SCOPE A. This Section includes all labor, materials, equipment and related items required to complete the work
More informationSYSTEMS+ SPECIALTY SYSTEMS INNOVATIVE SYSTEMS SOLUTIONS USGBORAL.COM
USGBORAL.COM S+ I 2 INTRODUCTION I 8 LIFT & SERVICES SHAFTS I 8 Shaftwall I 9 Ventshaft I 10 COLUMN PROTECTION I 13 BEAM PROTECTION I 14 FIRE TUNNEL I SPECIALTY S INNOVATIVE S SOLUTIONS I SPECIALTY S INTRODUCTION
More informationLABC RegisteRed thermal systems to PARt L 2006 And 2010 multi-foil insulation And BReAtheR membranes
LABC Registered Thermal Systems to Part L 2006 and 2010 multi-foil insulation and breather membranes Contents 1 Foreword...4 2 How TLX Multi-foils Work...5 3 The TLX Range...6 4 U Values and Condensation
More informationPRODUCT CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE
Certificate No C-9432-13 Issued February 12, 2013 Updated July 20, 2018 PRODUCT CERTIFICATE NAME OF PRODUCT HYBRIS MANUFACTURER ACTIS SA 30 Avenue de Catalogne 11300 Limoux France PRODUCT DESCRIPTION HYBRIS
More informationRefurbishment site guidance for solid-walled houses roofs
GOOD PRACTICE GUIDE 296 Refurbishment site guidance for solid-walled houses roofs What energy savings to aim for Key points to consider Energy savings and SAP ratings Environmental considerations GOOD
More informationNAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. Date of update May 30, 2018 Valid until May 29, 2023 HYBRIS
NAME OF PRODUCT HYBRIS MANUFACTURER ACTIS SA 30 Avenue de Catalogne 11300 Limoux France CERTIFICATE VTT-C-9432-13 Date of update May 30, 2018 Valid until May 29, 2023 PRODUCT DESCRIPTION HYBRIS is a flexible,
More informationDSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION
SECTION 230713 DUCT INSULATION PART 1 GENERAL 1.1 SUMMARY A. Related Sections: 1. 233113 Ductwork and Accessories 1.2 REFERENCES A. American Society for Testing and Materials (ASTM): 1. E84-96a Test Method
More informationBrick Veneer Walls. Insulation
Insulation A4/8 BV AW2157 Issue 7 Nov 2016 Brick Veneer Walls Insulation guide Helps achieve a 6-star house energy rating Rigid Kingspan Kooltherm and flexible Kingspan AIR-CELL solutions available Fibre-free,
More informationGuidance on U Values from Domestic Heating Design Guide
Guidance on U Values from Domestic Heating Design Guide The following U Values are from the Domestic Heating Design Guide, and the complete publication is available for purchase from members of the Domestic
More informationDRY CONSTRUCTION SYSTEMS
DRY CONSTRUCTION SYSTEMS Adrienn LEPEL BUTE Dry construction systems Prefabricated elements assembly on site Minimal use of water dry construction systems Assembled partitions Suspended ceilings Raised
More informationJoint Systems. System No. FF-D-0044
XHBN.FF-D-0044 System No. FF-D-0044 November 05, 2003 Assembly Rating 2 Hr Nom Joint Width 1 in. Class II and III Movement Capabilities 50% Compression or Extension 1. Floor or Wall Assembly Reinforced
More informationRepublicofSouthAfrica
RepublicofSouthAfrica EDICTOFGOVERNMENT± Inordertopromotepubliceducationandpublicsafety,equaljusticeforal, abeterinformedcitizenry,theruleoflaw,worldtradeandworldpeace, thislegaldocumentisherebymadeavailableonanoncommercialbasis,asit
More informationFIREBLOCK/DRAFTSTOPPING INFORMATION CODE INFORMATION FOR 1 & 2-FAMILY DWELLINGS FOR WOOD-FRAMED CONSTRUCTION FIREBLOCK
Building Safety Department 400-2 nd Street South St. Cloud, MN 56301 (320) 255-7239 FIREBLOCK/DRAFTSTOPPING INFORMATION CODE INFORMATION FOR 1 & 2-FAMILY DWELLINGS FOR WOOD-FRAMED CONSTRUCTION FIREBLOCK
More informationContact Details: Phone Fax . Work Description: New Building Extensions Refurbishment Change of Use. Yes No Method:
BCA Section J- Energy Efficiency Deemed- to- Satisfy Provisions Assessment Sheet 1. Project Overview Client Name: Address: Contact Person: Contact Details: Phone Fax Email Project: Work Description: New
More informationREFLECTIVE INSULATION, RADIANT BARRIERS, AND INTERIOR RADIATION CONTROL COATINGS FOR USE IN PRE-ENGINEERED METAL BUILDINGS
Technical Bulletin #107 REFLECTIVE INSULATION, RADIANT BARRIERS, AND INTERIOR RADIATION CONTROL COATINGS FOR USE IN PRE-ENGINEERED METAL BUILDINGS Scope: In both the United States and Canada there is significant
More informationMulti-layer Insulation Blanket for Walls
Multilayer Insulation Blanket for Walls Thermal Insulation in a 40mm thin, flexible, multilayer membrane Meets requirements of L1A, L1B 2010 High performance wall insulation Full Agrément certification
More informationBERS Pro Plus 4.2 New Features and Modelling Changes. Holger Willrath Solar Logic October 2011
BERS Pro Plus 4.2 New Features and Modelling Changes Holger Willrath Solar Logic October 2011 BERS Pro Plus V4.2 New Features and Modelling Changes Holger Willrath Solar Logic This document may not be
More informationKOOLTHERM K12 FRAMING BOARD AND K15 RAINSCREEN BOARD BCA Certificate number: CM Date of issue: 15/08/2017. Date of expiry: 21/03/2020
Certification Body: SAI Global Certification Services Pty Limited (ACN 108 716 669) Trading as SAI Global JAS-ANZ Accreditation No. Z1440295AS Address: 680 George Street, Sydney, NSW 2000 Website: www.saiglobal.com
More informationHebel PowerPanel for House & Low Rise Multi-Residential External Wall
Certification Body: ABN: 80 111 217 568 JAS-ANZ Accreditation No. Z4450210AK PO Box 7144, Sippy Downs Qld 4556 +61 (07) 5445 2199 www.certmark.org Certificate Holder: CSR Hebel ABN: 55 008 631 356 Triniti
More informationInternational Code Council
International Code Council ICC 400-2012 edition Standard on the Design and Construction of Log Structures Public Comments Draft #1 The ICC Standard Development Committee on Log Structures (IS-LOG committee)
More informationInsulation and Technologies
Interior Design Technology Insulation and Technologies By, Mrs. Noshaba Maryam Chapter Six Building insulation refers broadly to any object in a building used as insulation for any purpose. While the majority
More informationTECH SOLUTIONS Hot Box Testing of Four Different Metal Building Roof Assemblies Determines Insulation Efficiency
Summary Using the ASTM 1363, or hot box test, four different metal roofing assemblies were tested to determine their effective R-value versus the design R-value of the insulation. The ratio of these two
More informationBOXSPAN RESIDENTIAL SPAN TABLES
Certification BOX RESIDENTIAL TABLES Non Cyclonic up to N3 Wind Class Joists Bearers Rafters Lintels Roof Beams 1 Contents Introduction 3 Engineering Certification 4 Design Notes 5 Definitions & Terminology
More informationSNUG UNDERFLOOR INSULATION. Product. Scope. Building Regulations. Appraisal No [2018] Appraisal No (2018) Amended 28 June 2018
SNUG UNDERFLOOR INSULATION Amended 28 June 2018 BRANZ Appraisals Technical Assessments of products for building and construction. Product 1.1 Snug Underfloor Insulation is a polyester thermal insulating
More informationCity of High Point Airport Overlay District Noise Level Reduction Design Standards
City of High Point Airport Overlay District Noise Level Reduction Design Standards Part A. Residential Design Standards for Zone 3 I. NOISE LEVEL REDUCTION (NLR) REQUIREMENT FOR ZONE 3. The City of High
More informationSECTION INSULATION. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.
SECTION 072100 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting
More informationPart E robustdetails. robustdetails. January 2018 Update Pack
Part E Pack Dear Colleague, The first Update Pack of the year, and the first welcome from me as Chief Executive. Although new to the role, I have been with the company for nine years with responsibility
More informationPermifloor. Insulation WATER-PERMEABLE UNDERFLOOR INSULATION
Insulation A4/6 PSW AW2324A Issue 11 May 2018 Permifloor WATER-PERMEABLE UNDERFLOOR INSULATION 3x faster to install* than foilfaced polystyrene panels Helps achieve a 6-star house energy rating 2-in-1
More informationWhy Insulate? - Thermal Control Certified Faced Insulation acts as a barrier to slow down the movement of heat, keeping it inside the building in wint
Insulation Why Insulate? - Thermal Control Certified Faced Insulation acts as a barrier to slow down the movement of heat, keeping it inside the building in winter and outside in summer. Why Insulate?
More informationA GUIDE TO WINDOW AND DOOR SELECTION
Australian window association guide series A GUIDE TO WINDOW AND DOOR SELECTION An industry guide to the selection and certification of windows and doors Background Foreword As part of its commitment to
More informationPronto Panel Multi-storey Internal Wall & Low-rise Intertenancy Wall System
Certificate number: CM30050 Rev3 Global-Mark Pty Ltd, Suite 4.07, 32 Delhi Road, North Ryde NSW 2113, Australia Tel: +61 (0)2 9886 0222 - www.global- Mark.com.au Certificate Holder: Brickworks Building
More information- Version 2 Total R-value calculations for typical building applications
- Version 2 Total R-value calculations for typical building applications - Version 2 Total R-value calculations for typical building applications Acknowledgements Version Date Description 1 Nov 2010 Initial
More informationTotal R-value calculations for typical building applications. Version 3
Total R-value calculations for typical building applications - Version 3 Total R-value calculations for typical building applications - Version 3 Acknowledgements Version Date Description 1 Nov 2010 Initial
More informationInsulation. A4/6 AW2242 Issue 1 Oct Kingspan Insulation
Insulation A4/6 AW2242 Issue 1 Oct 2017 Kingspan Insulation Product Snapshot Welcome to Kingspan Insulation The Kingspan Group Kingspan Insulation is a Division of Kingspan Group plc, one of Europe s fastest
More informationAttachment of Exterior Wall Coverings Through Polyiso to Wood or Steel Wall Framing
Attachment of Exterior Wall Coverings Through Polyiso to Wood or Steel Wall Framing Installation Instructions Revised 10/25/2016 Scope For the 2015 IBC (cold-formed Steel) and IRC see ABTG Report No. 1503-02
More informationTotal R-value calculations for typical building applications. Version 3
Total R-value calculations for typical building applications - - Total R-value calculations for typical building applications Acknowledgements Version Date Description 1 Nov 2010 Initial release 2 Jan
More informationEcoTouch Insulation with PureFiber Technology
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
More information1. Section 04300: Concrete Masonry Units
SECTION 072000 BOARD INSULATION PART 1 GENERAL 1.1 DESCRIPTION A. To be read with Division 1 General Requirements, Conditions of Contract and all associated drawings. B. Work of this section, as indicated
More informationBituminous Roofing Underlay & Valley Guard
CONTENTS SUMMARY OF FEATURES... 2 TECHNICAL INFORMATION... 2 Product Description... 2 Applications... 2 Product Information... 2 Handling & Storage... 5 Technical Data... 5 Installation Information...
More informationProject name Gentoo Retrofit Bid 1 Project summary Refurbishment of 2no. Semi Detached houses using Passivhaus principles
http://lowenergybuildings.org.uk Project name Gentoo Retrofit Bid 1 Project summary Refurbishment of 2no. Semi Detached houses using Passivhaus principles Project Description Projected build start date
More informationBBA Information Bulletin No 3
BBA Information Bulletin No 3 APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL APPROVALS FOR CONSTRUCTION Reflective foil insulation Conventions for U value calculations Introduction Reflective foil
More informationROCKWOOL Blanket (and Batt) Insulation Section Master Guide Specification (COMFORTBATT ) Page 1 January 2018
Master Guide Specification (COMFORTBATT ) Page 1 1 GENERAL 1.1 SUMMARY OF WORK.1 This Section specifies mineral fibre batt and blanket thermal insulation for steel stud wall applications. 1.2 RELATED REQUIREMENTS.1
More informationHello Future DUAL TESTING. DUAL PERFORMANCE. HYBRID.
Hello Future DUAL TESTING. DUAL PERFORMANCE. HYBRID. HYBRID INSULATION NHBC acceptance THE HYBRID RANGE: BENEFITS DUAL TESTING, IN A LABORATORY AND ON SITE A range of innovative insulation products that
More informationWASHINGTON STATE ENERGY CODE, APPENDIX CHAPTERS
Chapter 51-11C WAC WASHINGTON STATE ENERGY CODE, APPENDIX CHAPTERS TABLE OF CONTENTS Appendix A Default Heat Loss Coefficients... AE-3 A101 General... AE-3 A101.1 Scope... AE-3 A101.2 Description... AE-3
More informationBUILDING CODE REQUIREMENTS
Wood-frame walls and floors offer designers a unique opportunity to provide structures with economy as well as proven energy performance. Where these assemblies are required by the building codes to achieve
More informationTWO STOREY MASONRY VENEER DESIGN SOLUTION - FIRTH 10 SERIES HOLLOW MASONRY, MANORSTONE
TWO STOREY MASONRY VENEER DESIGN SOLUTION - FIRTH 10 SERIES HOLLOW MASONRY, MANORSTONE & 90MM Masonry VENEERS CBI 3311 4261 4273 October 2012 STRUCTURAL CERTIFICATION PRODUCER STATEMENT PS-1 : DESIGN FIRTH
More informationBC BUILDING CODE ERRATA
BC BUILDING CODE ERRATA The following changes should be made to print and offline copies of the 2012 BC Codes. The 2012 BC Codes subscription products include these changes. Highlighted text is used in
More informationUnderstanding Energy Codes
NRCA University Webinar October 17, 2013 Understanding Energy Codes presented by Mark S. Graham Associate Executive Director, Technical Services National Roofing Contractors Association Some background
More information