1 Compliance Documents Training Series G6 Airborne & Impact Sound 2 LBP skills maintenance points Building Networks Ltd 2014 G6 Airborne and Impact Sound - 1 -
2 Published: Version 1; October, Building Networks. All Rights Reserved. No part of this work may be reproduced, adapted, modified, copied or transmitted in any form or by way of example only, written graphic, electronic, mechanical, reprographic, photocopying, recording, taping or information retrieval systems, without written permission of Building Networks Ltd. Designed by Building Networks Ltd Building Networks Ltd 2014 G6 Airborne and Impact Sound - 2 -
3 Content Introduction Symbols Download Requirements NZ Building Code Clause G6 Activities Navigating Your Way Around the Compliance Document References Definitions Verification Method Acceptable Solution Answers to Activities Building Networks Ltd 2014 G6 Airborne and Impact Sound - 3 -
4 Introduction This training module is based on the Department of Building and Housing (DBH) Compliance Document G6 Airborne and Impact Sound, amendment 2 effective 1 December The New Zealand Building Code clause G6 was first published in July A compliance document is for use in establishing compliance with the New Zealand Building Code. There are also other methods of compliance which are detailed in the New Zealand Building Code Handbook. For the document history please refer to the inside cover of the document. Symbols Where you see the glasses symbol you are being asked to complete an activity using the Clause G6 Document. Activity 1 Tip Where you see the symbol you should pause to read this carefully as it is an important tip or note. For this course you will need to download Compliance Document Clause G6 Airborne and Impact Sound from It is recommended that you make yourself familiar with the preface to the New Zealand Building Code Handbook that both describes the status of Compliance Documents and explains alternative methods of achieving compliance. Tip Building Networks Ltd 2014 G6 Airborne and Impact Sound - 4 -
5 NZ Building Code Clause G6 Airborne and Impact Sound All Compliance Documents commence with a copy of the relevant NZ Building Code clause. Activity 1 All Compliance Documents commence with a copy of the relevant NZ Building Code clause. Review the NZBC clause for G6 [page 3 of the Document] Q.1 What is the objective of clause G6? [G6.1] Q. 2 Fill in the blanks from the functional requirement: [G6.2] Building elements which are between occupancies, shall be constructed to prevent undue noise.from other occupancies or common spaces, to the of household units. Q.3 Consider the performance requirements and answer the questions below: [G6.3.1] The Sound Transmission Class of walls, floors and ceilings shall be no less than what figure? [G6.3.2] Fill in the blanks below: The Impact Insulation Class of..shall be no less than 55. Building Networks Ltd 2014 G6 Airborne and Impact Sound - 5 -
6 Navigating Your Way Around the Compliance Document The Compliance Document G6 Airborne and Impact Sound contains the following sections: [page 5] References Definitions Verification Method G6/VM1 Acceptable Solution G6/AS1 An index Activity 2 Refer to the References section of the G6 Document [page 7 ] Q.1 There are five referenced documents quoted in Verification Method G6/VM1. Please note them below - the first has been done for you. # Source and Standard(s) Description 1 American Society for Testing and Materials Method for measurement of airborne ASTM E 336: 1990 sound insulation in buildings. Building Networks Ltd 2014 G6 Airborne and Impact Sound - 6 -
7 Definitions An abbreviated list of definitions for words or terms particularly relevant to Compliance Document G6 are found on page 9 of the Document. Activity 3 Go to the definitions section of G6 and familiarise yourself with the meaning of the following terms: Adequate Amenity Building Building element Fixture Tip Definitions for any other italicised word may be found in the NZ Building Code Handbook, which contains a full list of definitions. The Handbook can be downloaded from If you do not understand any terms refer back to this reference point and look up the word in alphabetical order. Habitable space Household unit Impact insulation class (IIC) Sound transmission class (STC) Building Networks Ltd 2014 G6 Airborne and Impact Sound - 7 -
8 Verification Method G6/VM1 Sound Tests Airborne Sound Insulation Field Tests Performance Verification Procedures detailed in ASTM E 366 The field sound transmission class may be verified using the described method in ASTM E 413. Shall be within 5 db of the performance requirement Impact Sound Insulation Field Tests Acceptable Solution G6/AS1 Activity 4 Procedures detailed in ISO 140: Part VII The field impact insulation class may be verified using the described method in ASTM E 989. Carefully read Acceptable Solution G6/AS1 [pages 13 17] and test your understanding with the exercises below: Q.1 True or False? Please select the correct answer (a) Sound transmitted through building elements can be minimised (b) Building elements can be used for noise control (c) It is best to mount fixtures such as TV sets on common walls (d) Unsealed air space can sometimes amplify sound (e) Carpet on underlay is an optional part of the Acceptable Solution T/F T/F T/F T/F T/F (f) Additional airborne and impact sound insulation is sometimes required T/F (g) Installations are made airtight by sealing joints between elements T/F Building Networks Ltd 2014 G6 Airborne and Impact Sound - 8 -
9 Q.2 Refer to Figure 1: Location of Building Elements Requiring Noise Control [page 14 of the Document] Which wall assembly details should you refer to for two adjacent units? (a) Numbers 1 and 2 (b) Numbers 1-5 inclusive (c) Numbers 5-10 inclusive (d) Numbers 6 and 7 Q.3 Refer to Figure 2: Acceptable Wall Assemblies for Noise Control [page 15 of the Document] Detail 4 STC 55 requires what concrete wall minimum thickness? (a) 400 mm (b) 150 mm (c) 200 mm (d) 115 mm Q.4 Refer to Figure 3: Acceptable Floor/Ceiling Assemblies for Noise Control [page 16 of the Document] Detail 5 STC 55 / IIC 55 requires how many layers of 12.5 mm plasterboard? (a) 2 (b) 4 (c) 1 (d) none Q.5 Refer to Figure 4: Acceptable Internal/External Wall Junction for Noise Control Between Two Units [page 16 of the Document] Plan Detail D requires what thickness of glass fibre? (a) 25 mm (b) 45 mm (c) 75 mm (d) 52 mm Q.6 Refer to Figure 5: Acceptable Floor/Wall Junctions for Noise Control Between Four Units [page 17 of the Document] Section Detail C requires what kind of sealant? (a) rubber (b) multi layered (c) flexible (d) water based Building Networks Ltd 2014 G6 Airborne and Impact Sound - 9 -
10 Notes: Building Networks Ltd 2014 G6 Airborne and Impact Sound
11 Answers to Activities Activity 1: Q.1 What is the objective of clause G6? [G6.1] ANSWER The objective of this provision is to safeguard people from illness or loss of amenity as a result of undue noise being transmitted between abutting occupancies. Q. 2 Fill in the blanks from the functional requirement: ANSWER [G6.2] Building elements which are common between occupancies, shall be constructed to prevent undue noise transmission from other occupancies or common spaces, to the habitable spaces of household units. Q.3 Consider the performance requirements and answer the questions below: [G6.3.1] The Sound Transmission Class of walls, floors and ceilings shall be no less than what figure? ANSWER 55. [G6.3.2] Fill in the blanks below: ANSWER The Impact Insulation Class of floors shall be no less than 55. Building Networks Ltd 2014 G6 Airborne and Impact Sound
12 Activity 2: Q.1 There are five referenced documents quoted in Verification Method G6/VM1. Please note them below - the first has been done for you. # Source and Standard(s) Description 1 American Society for Testing Method for measurement of airborne and Materials sound insulation in buildings. ASTM E 336: American Society for Testing and Materials ASTM E 413: American Society for Testing and Materials ASTM E 492: American Society for Testing and Materials ASTM E 989: International Standards Organisation Activity 3: ISO 140/VII: 1978 Review as required. Classification for rating sound insulation Test method for laboratory measurement of impact sound transmission through floor-ceiling assemblies using the tapping machine Classification for determination of impact insulation class (IIC) Field measurements of impact sound insulation of floors Building Networks Ltd 2014 G6 Airborne and Impact Sound
13 Activity 4: Q.1 True or False? Please select the correct answer ANSWER (a) Sound transmitted through building elements can be minimised T (b) Building elements can be used for noise control T (c) It is best to mount fixtures such as TV sets on common walls F (d) Unsealed air space can sometimes amplify sound T (e) Carpet on underlay is an optional part of the Acceptable Solution F (f) Additional airborne and impact sound insulation is sometimes required T (g) Installations are made airtight by sealing joints between elements T Q2. (b) Q3. (b) Q4. (a) Q5. (c) Q6. (c) Building Networks Ltd 2014 G6 Airborne and Impact Sound
14 Notes: Building Networks Ltd 2014 G6 Airborne and Impact Sound
15 Building Networks NZ Ltd PO Box 12463, Thorndon, Wellington Phone: (+64) Web: Building Networks Ltd 2014 G6 Airborne and Impact Sound
Compliance Documents Training Series
Compliance Documents Training Series F2 Hazardous Building Materials 2 LBP skills maintenance points Building Networks Ltd 2014 F2 Hazardous Building Materials - 1 - Published: Version 1; October, 2009
More informationCompliance Documents Training Series F3 Hazardous Substances and Processes Second Edition 2 LBP skills maintenance points Building Networks Ltd 2014 F3 Hazardous Substances and Processes - 1 - Published:
More informationCompliance Documents Training Series
Compliance Documents Training Series F5 Construction and Demolition Hazards 2 LBP skills maintenance points Building Networks Ltd 2014 F5 Construction and Demolition Hazards - 1 - Published: Version 1;
More informationCompliance Documents Training Series F1 Hazardous Agents on Site 2 LBP skills maintenance points Building Networks Ltd 2014 F1 Hazardous Agents on Site - 1 - Published: Version 1; October, 2009 2014 Building
More informationARCHIVED. Compliance Document for New Zealand Building Code Clause G2 Laundering. Prepared by the Department of Building and Housing
Compliance Document for New Zealand Building Code Clause G2 Laundering Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building and Housing.
More informationCompliance Document for New Zealand Building Code Clause G15 Solid Waste
Compliance Document for New Zealand Building Code Clause G15 Solid Waste Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building and Housing.
More informationApproved Document for New Zealand Building Code Laundering Clause G2
Approved Document for New Zealand Building Code Laundering Clause G2 Prepared by the Building Industry Authority This Approved Document is prepared by the Building Industry Authority, which is a statutory
More information84 Symonds Street PO Box 5811 Wellesley Street Auckland 1141 New Zealand T: F:
84 Symonds Street PO Box 5811 Wellesley Street Auckland 1141 New Zealand T: +64 9 379 7822 F: +64 9 309 3540 www.marshallday.com DESIGN GUIDE Floors in buildings are often required to achieve certain levels
More informationARCHIVED. Compliance Document for New Zealand Building Code Clause G8 Artificial Light. Prepared by the Department of Building and Housing
Compliance Document for New Zealand Building Code Clause G8 Artificial Light Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building and Housing.
More informationARCHIVED. Compliance Document for New Zealand Building Code Clause G15 Solid Waste. Prepared by the Department of Building and Housing
Compliance Document for New Zealand Building Code Clause G15 Solid Waste Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building and Housing.
More informationDetermination 2015/004
Determination 2015/004 Regarding the authority s exercise of powers in refusing to issue a building consent relating to the compliance of apartment entry doors with Clause G6 of the Building Code 1. The
More informationGIB Quiet Clip GIB CBI March Features and Benefits
CBI - 5113 March 2002 GIB Quiet Clip Features and Benefits No special flooring systems required Easy fit Installation Significantly improves low frequency sound transmission Significantly improves low
More informationVerification Methods For New Zealand Building Code Clause G8 Artificial Light
Acceptable Solutions and Prepared by the Ministry of Business, Innovation and Employment Verification Methods For New Zealand Building Code Clause G8 Artificial Light G8 Status of Verification Methods
More informationDear Customer. Section Old G4 January 2017 Amendment 4. Replace with new title page and document history pages 1 2B
Dear Customer Please find enclosed Amendment 4, effective 1 January 2017, to the Acceptable Solution and Verification Method for Clause G4 Ventilation of the New Zealand Building Code. The previous amendment
More informationFor New Zealand Building Code Clause G9 Electricity
Acceptable Solutions and Verification Methods Prepared by the Ministry of Business, Innovation and Employment For New Zealand Building Code Clause G9 Electricity G9 Status of Verification Methods and Acceptable
More informationStatus: Rev: Comments Date: Author: Reviewer:
ENGINEERED WOOD FLOORING ON SOUNDGUARD EXTREME UNDERLAY IIC OPINION Rp 005 2016596A 4 August 2016 84 Symonds Street PO Box 5811 Wellesley Street Auckland 1141 New Zealand T: +64 9 379 7822 F: +64 9 309
More informationARCHIVED. Compliance Document for New Zealand Building Code Clause G9 Electricity. Prepared by the Department of Building and Housing
Compliance Document for New Zealand Building Code Clause G9 Electricity Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building and Housing.
More informationSection Old G4 February 2014 Amendments to G4
Dear Customer Please find enclosed Amendment 3, effective 14 February 2014, to the Acceptable Solution and Verification Method for Clause G4 Ventilation of the New Zealand Building Code. The previous amendment
More informationLOXO CLADDING SOUND INSULATION PERFORMANCE. Opinion on Acoustic Performance of. Loxo Cladding Systems Utilising Aerated Concrete.
LOXO CLADDING SOUND INSULATION PERFORMANCE Opinion on Acoustic Performance of Loxo Cladding Systems Utilising Aerated Concrete Rp001 2012195C 08 May 2012 Level 369 Cambridge Terrace PO Box 4071 Christchurch
More informationB Page 1 of 21-
Airborne and impact sound transmission measurements were performed on three floor assemblies which comprised the NRC 150 mm reference concrete slab and a 102 mm floating concrete slab. For report purposes,
More informationSection Sound Control
Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B-09-11-01 Ontario-NBC CODE REFERENCE: Division B / 9.11. DESCRIPTION OF THE PROPOSED
More informationDear Customer. Section Old B2 January 2017 Amendment 9. Contents Remove page 5/6 Replace with new page 5/6
Dear Customer Please find enclosed Amendment 9, effective 1 January 2017, to the Acceptable Solution and Verification Method for Clause B2 Durability of the New Zealand Building Code. The previous amendment
More informationKINETICS NOISE CONTROL TEST REPORT #AT001052
KINETICS NOISE CONTROL TEST REPORT #AT001052 KINETICS NOISE CONTROL PRODUCTS: o ISOMAX CLIPS ACOUSTICAL RATINGS: o STC 66 o IIC 44 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA
More informationKINETICS NOISE CONTROL TEST REPORT #AT001049
KINETICS NOISE CONTROL TEST REPORT #AT001049 KINETICS NOISE CONTROL PRODUCTS: o NONE ACOUSTICAL RATINGS: o STC 53 o IIC 27 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA o B-3463.1
More informationKINETICS NOISE CONTROL TEST REPORT #AT001110
KINETICS NOISE CONTROL TEST REPORT #AT001110 KINETICS NOISE CONTROL PRODUCTS: o NONE ACOUSTICAL RATINGS: o STC 53 o IIC 29 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o REPORT NO. A1-010601.1 o DATED:
More informationKINETICS NOISE CONTROL TEST REPORT #AT001021B
KINETICS NOISE CONTROL TEST REPORT #AT001021B KINETICS NOISE CONTROL PRODUCTS: o ICW ACOUSTICAL RATINGS: o STC 76 o IIC 62 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B3463.13 KINETICS DRAWING NUMBER:
More informationLEED for Homes Approved ID Request:
LEED for Homes Approved ID Request: Introduction The following is an Innovative Design Request (IDR) that has been approved for broader use in for the LEED for Homes program. This credit should not be
More informationTerrace Home Guide. An overview of intertenancy options CBI 5113
Terrace Home Guide An overview of intertenancy options CBI 5113 NATIONAL SUPPORT VISIT: Winstone Wallboards Limited 37 Felix Street, Penrose 1061, Auckland, New Zealand POST: PO Box 12 256, Penrose 1642,
More informationKINETICS NOISE CONTROL TEST REPORT #AT001067
KINETICS NOISE CONTROL TEST REPORT #AT001067 KINETICS NOISE CONTROL PRODUCTS: o FLM- NEOPRENE PAD ACOUSTICAL RATINGS: o STC 69 o IIC 61 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA
More informationTechnical Supplement. Internal Fire and Acoustic Rated Floor Solution INTERIORS
Technical Supplement Internal Fire and Acoustic Rated Floor Solution INTERIORS Australia June 2017 Make sure your information is up to date. When specifying or installing James Hardie products, ensure
More informationCopyright 2018 American Wood Council 1
for Wood Frame Assemblies BCD800 Jason Smart, P.E. Manager, Engineering Technology American Wood Council The American Wood Council is a Registered Provider with The American Institute of Architects Continuing
More informationFor New Zealand Building Code Clause F4 Safety from Falling
Acceptable Solutions and Verification Methods Prepared by by the the Ministry of of Business, Innovation and and Employment For New Zealand Building Code Clause F4 Safety from Falling F4 Status of Verification
More informationResults of FIIC and FSTC Measurements at Harvard Estates
Harvard Estates FIIC and FSTC Tests STEWART AIT ALLAOUA PERKINS 6042 Seaview Ave. NW, Suite 102 Seattle, WA 98107 Phone: (206) 839-0819 Fax: (206) 839-0824 January 21, 2005 Charles Strazzara, AIA Studio
More informationTRIBOARD INTER-TENANCY WALL SYSTEM. Product. Scope. Appraisal No. 593 [2016]
TRIBOARD INTER-TENANCY WALL This Appraisal replaces BRANZ Appraisal No. 593 (2008) Amended 06 October 2017 BRANZ Appraisals Technical Assessments of products for building and construction. Juken New Zealand
More informationAustralian Standard. Methods for determination of sound transmission class and noise isolation class of building partitions AS
AS 1276 1979 Australian Standard Methods for determination of sound transmission class and noise isolation class of building partitions The following scientific, industrial and governmental organizations
More informationKINETICS NOISE CONTROL TEST REPORT #AT001032
KINETICS NOISE CONTROL TEST REPORT #AT001032 KINETICS NOISE CONTROL PRODUCTS: o ICC ACOUSTICAL RATINGS: o STC 84 o IIC 70 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B-3448.12 KINETICS DRAWING NUMBER:
More informationKINETICS NOISE CONTROL TEST REPORT # AT001084
KINETICS NOISE CONTROL TEST REPORT # AT001084 KINETICS NOISE CONTROL PRODUCTS: o MODEL ISOGRID ACOUSTICAL RATINGS: o STC 63 o IIC 50 TESTING AGENCY & REPORT NUMBER: o NRC-CNRC o B-3463.6 KINETICS DRAWING
More informationDear Customer. Section Old F4 January 2017 Amendment 2. Remove title page and document history page 1-2B
Dear Customer Please find enclosed Amendment 2, effective 1 January 2017, to the Acceptable Solution and Verification Method for Clause F4 Safety from Falling of the New Zealand Building Code. The previous
More informationAcoustical Characteristics of Carpet
CRI TECHNICAL BULLETIN Acoustical Characteristics of Carpet Carpet is an outstanding sound absorptive material. When properly selected, carpet absorbs airborne noise as efficiently as many specialized
More informationCompliance Document for New Zealand Building Code Clause F3 Hazardous Substances and Processes Second Edition
Compliance Document for New Zealand Building Code Clause F3 Hazardous Substances and Processes Second Edition Prepared by the Department of Building and Housing This Compliance Document is prepared by
More informationWall Panel Bracing Units Litecrete 2400x 1200 x 150 mm panels achieve 400 bu s (Opus International report).
BUILDING CODE REQUIREMENTS The Litecrete Construction System, which is subject to specific engineering design, meets the following performance requirements of the building code: Clause B1 STRUCTURE: Performance
More informationINTRODUCTION SPECIMEN DESCRIPTION
INTRODUCTION SPECIMEN DESCRIPTION Airborne sound transmission measurements were performed on a wall assembly with a single layer of the product identified by the client as QuietRock QR-530 Serenity on
More informationQuestions and Answers about Madison Crescent and Noise Issues
Questions and Answers about Madison Crescent and Noise Issues Question: What codes were applicable to our condos when they were built? Answer: The Virginia Uniform Statewide Building Code (VUSBC) - The
More informationSOUND INSULATION TESTING SITE READINESS CHECKLIST
04/07/2018 SOUND INSULATION TESTING SITE READINESS CHECKLIST Sound insulation testing is the method of quantifying the level of sound insulation provided by party elements between adjoining dwellings.
More informationCOMPARISON OF THE ACOUSTIC PROVISIONS IN THE NATIONAL BUILDING CODE WITH THE ACOUSTIC BUILDING CODES OF SOME SELECTED COUNTRIES
COMPARISON OF THE ACOUSTIC PROVISIONS IN THE NATIONAL BUILDING CODE WITH THE ACOUSTIC BUILDING CODES OF SOME SELECTED COUNTRIES Sikiru Abiodun Ganiyu Department of Architecture, Federal University of Technology,
More informationacoustics 101 The following is a brief tutorial that describes the use of a flooring underlayment as an acoustic barrier.
acoustics 101 The following is a brief tutorial that describes the use of a flooring underlayment as an acoustic barrier. 1 why use a floor underlayment? IT S WHAT S UNDERNEATH THAT COUNTS - BENEFITS OF
More informationD R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to REGUPOL AMERICA Regupol Sonus HS300 3 mm Underlayment Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632
More informationSound Control Solutions in Floor/Ceiling Assemblies
Sound Control Solutions in Floor/Ceiling Assemblies Controlling sound becomes more important every day. At SAMfloors, it is our mission to provide elegant, functional sound control solutions to meet the
More informationKINETICS NOISE CONTROL TEST REPORT #AT001035
KINETICS NOISE CONTROL TEST REPORT #AT001035 KINETICS NOISE CONTROL PRODUCTS: o RIM I-2-16 ACOUSTICAL RATINGS: o STC 66 o IIC 63 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B-3140.1 KINETICS DRAWING
More informationSignatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.
ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 492: Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using
More informationProduct Guide Specification Pliteq GenieMat FF06, GenieMat FF10, GenieMat FF17, GenieMat FF25, GenieMat FF50, GenieMat FF75
Product Guide Specification Pliteq GenieMat FF06, GenieMat FF10, GenieMat FF17, GenieMat FF25, GenieMat FF50, GenieMat FF75 Specifier Notes: This product guide specification is written according to the
More informationC R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Base 10
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to Series/Model: Base 10 Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results Data File Result
More informationCERTIFICATE OF PERFORMANCE. IMPACT NOISE TESTING (6mm ABODE PRIME RIGID PLANK) PROLINE FLOORS
CERTIFICATE OF PERFORMANCE IMPACT NOISE TESTING (mm ABODE PRIME RIGID PLANK) PROLINE FLOORS DOCUMENT CONTROL Project Title Certificate Performance Impact Noise Testing ( mm Rigid Plank) Proline s Our Project
More informationEdition October May (always refer to the latest manual as set out on
LOXO PANEL INTER AND BLOCK TENANCY SYSTEMS WALLS TECHNICAL FIRE AND ACOUSTIC MANUAL REPORT PRODUCT DESCRIPTION AND BUILDING SYSTEM DETAILS Edition October May 2015 2014 (always refer to the latest manual
More informationQT 4003 (3mm), QT 4005 (5mm) & QT 4010 (10mm)
WILREP LTD. 08 13 48 13 SPECIAL CONSTRUCTION 14 manufactured sound & vibration control components AG242-F QT 4003 (3mm), QT 4005 (5mm) & QT 4010 (10mm) 3 Part Specification DIVISION 9 - SECTION 09 60 00.11
More informationCERTIFICATE OF PERFORMANCE. IMPACT NOISE TESTING (6 mm RIGID PLANK) PROLINE FLOORS
CERTIFICATE OF PERFORMANCE IMPACT NOISE TESTING ( mm RIGID PLANK) PROLINE FLOORS DOCUMENT CONTROL Project Title Certificate Performance Impact Noise Testing ( mm Rigid Plank) Proline s Our Project Number
More informationCompliance Document for New Zealand Building Code Clause E3 Internal Moisture Second Edition
Compliance Document for New Zealand Building Code Clause E3 Internal Moisture Second Edition Prepared by the Department of Building and Housing Amend 3 October 2004 This Compliance Document is prepared
More informationUL- E U C E R T I F I C A T E
UL- E U C E R T I F I C A T E Page 1/6 Certificate Holder Manufacturer Certified Product Type Product Trade Name Trademark Rating/Classification Polyseam AS Ravneveien 7 Linnestad Næringsområde N-3174
More informationAS/NZS 2589:2007 AS/NZS
AS/NZS 2589:2017 Australian/New Zealand Standard Gypsum linings Application and finishing Superseding AS/NZS 2589:2007 AS/NZS 2589:2017 AS/NZS 2589:2017 This joint Australian/New Zealand standard was prepared
More informationA L I O N Technical Center. Test Report
FOR: Beachwood, OH Impact Sound Transmission CONDUCTED: 2017-11-15 Page 1 of 8 ON: LVT flooring over Peacemaker Soundproofing Underlayment over 8" Concrete Slab No Ceiling TEST METHOD Riverbank Acoustical
More informationA L I O N Technical Center. Test Report
FOR: Lebanon, PA Impact Sound Transmission CONDUCTED: 2017-07-12 Page 1 of 8 ON: Quarry Floor Tiles and Regupol SonusPlus (underlayment) over 8 inch Concrete Slab (no Ceiling) TEST METHOD Riverbank Acoustical
More informationThis page was. intentionally. left blank
CONSTRUCTION Measurement of Airborne Sound Insulation of 8 Wall Assemblies Measurement of Airborne and Impact Sound Insulation of 29 Floor Assemblies Nordic Engineered Wood Report No. A1-006070.10 July
More informationSOUND INSULATION TESTING IN DWELLINGS
SOUND INSULATION TESTING IN DWELLINGS Chris Dilworth, AWN Consulting This Presentation Discusses the standards by which we judge sound insulation performance. Presents the results of sound insulation tests
More informationIntertek Testing Services
Acoustical 3933 U.S. Rt. Cortland, NY 13045 Phone: 607-753-6711 Fax: 607-756-9891 Order No. J99031102-003 December 10, 1999 REPORT NO. J99031102-003 SOUND TRANSMISSION LOSS TEST AND CLASSIFICATION OF A
More informationAcoustical Engineering Solutions.
Acoustical Engineering Solutions. Meeting IBC Acoustical Requirements for Multifamily Construction By Scott Harvey, PE, INCE Bd. Cert. Phoenix Noise & Vibration Frederick, Maryland Copyright Materials
More informationProduct Guide Specification Pliteq GenieMat RST-02, RST-05, RST-10, RST-12, RST-15
GenieMat RST SOUND CONTROL UNDERLAYMENT Product Guide Specification Pliteq GenieMat RST-02, RST-05, RST-10, RST-12, RST-15 Specifier Notes: This product guide specification is written according to the
More informationAcoustic. . Absorbs sound reduces noise transmission between rooms for a quieter more relaxing home
Acoustic Application Pink Batts Silencer insulation is a lightweight flexible glass wool insulation product designed to: Provide acoustic insulation in internal walls and midfloors Fit easily into standard
More informationOpinion on Acoustic Performance of. Rockcote Systems Utilising Integra Aerated Concrete. 08 December 2010
Opinion on Acoustic Performance of Rockcote Systems Utilising Integra Aerated Concrete 08 December 2010 84 Symonds Street PO Box 5811 Wellesley Street Auckland 1141 New Zealand T: +64 9 379 7822 F: +64
More informationLaboratory measurements of the reduction of transmitted impact sound by floor coverings on a heavyweight reference floor (According to ISO )
Reference no. T1638-1 Laboratory measurements of the reduction of transmitted impact sound by floor coverings on a heavyweight reference floor (According to ISO 10140 3) AUCKLAND UNISERVICES LIMITED a
More informationDIVISION 9 - SECTION ECOSilence Recycled Rubber Sound Underlayment US Patent No. RE 41,945
April 7 th, 2017- The document is provided solely as a convenience for spec writers in the drafting process. Ecore will not be held responsible for the use or alteration of any information contained herein.
More informationIntertenancy Barrier Systems for Terrace Homes
Intertenancy Barrier Systems for Terrace Homes Specification & Installation Manual CBI5113 NATIONAL SUPPORT VISIT: POST: Winstone Wallboards Limited 37 Felix Street, Penrose, Auckland 1061, New Zealand
More informationSpecific Accreditation Criteria
Specific Accreditation Criteria ISO/IEC 17025 Application Document Manufactured Goods - Annex Physical July 2018 Copyright National Association of Testing Authorities, Australia 2013 This publication is
More informationH R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to URBAN SURFACES. Series/Model: Urban Surfaces Soundtec
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to URBAN SURFACES Series/Model: Urban Surfaces Soundtec Specimen Type: 152 mm Concrete Slab with Drop Ceiling Overall Size: 3048 mm
More informationARCHIVED. Compliance Document for New Zealand Building Code Clause F4 Safety from Falling Second Edition
Compliance Document for New Zealand Building Code Clause F4 Safety from Falling Second Edition Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to REGUPOL AMERICA Series/Model: 3 mm Regupol Sonus Rubber Underlayment Specimen Type: Floor/Ceiling Assembly Overall Size:
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to REGUPOL AMERICA Series/Model: 5 mm Regupol Sonus Rubber Underlayment Specimen Type: Floor/Ceiling Assembly Overall Size:
More informationFIELD IMPACT INSULATION TESTS 133 SCARBOROUGH STREET, SOUTHPORT TEST REPORT
Commissioned by: National Flooring Distributors Pty Ltd Date: 26 June 2015 Project number: 3872 Version: V.0 Author: Eric Huang 24 Mexicanus Drive, PO Box 790, Park Ridge Queensland 4125 Australia p. +61
More informationHorizontal Impact Sound Insulation: Field Observations
Proceedings of ACOUSTICS 6 20-22 November 6, Christchurch, New Zealand Horizontal Impact Sound Insulation: Field Observations Michael Sullivan, Richard Finley and Arif Zaher Acoustic Division, NDY Sound,
More informationD R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to PROTECTO WRAP COMPANY. Series/Model: Whisper Mat CS
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to PROTECTO WRAP COMPANY Series/Model: Whisper Mat CS Specimen Type: Sound Control & Crack Suppression Membrane Overall Size: 3023 mm
More informationKarndean Acoustic Flooring Systems Karndean loose lay and gluedown luxury vinyl
Look inside: Karndean acoustic results in accordance with the NZBC. Karndean Acoustic Flooring Systems Karndean loose lay and gluedown luxury vinyl Boston LLP111 Contents About Karndean Designflooring
More informationLABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF PIR ROOF PANELS (According to ISO )
Ref no: LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF PIR ROOF PANELS (According to ISO 10140 2) AUCKLAND UNISERVICES LIMITED a wholly owned company of THE UNIVERSITY OF AUCKLAND Report prepared
More informationMultiProof -design compliance with Building Code clauses
MultiProof -design compliance with Building Code clauses Applicants and designers should use this table as a starting point for MultiProof. It lists the Building Code clauses, summarises what you need
More informationSilencer Rubber Underlayment
Silencer Rubber Underlayment Specifications Name: Silencer Rubber Color: Beige & Silver Type: Sound + Vapor Barrier Construction: High Density Rubber & foil barrier film Coverage: 100sqft Thickness: 2mm
More informationpalmer acoustics TEST REPORT
FIELD IMPACT INSULATION TESTS Commissioned by: National Flooring Date: 20 February 2018 Project number: 4355 Version: V.0 Author: Rasika Chandrasekara 24 Mexicanus Drive PO Box 790 Park Ridge Queensland
More informationRC CHANNEL ACOUSTIC ASSEMBLY
RC CHANNEL ACOUSTIC ASSEMBLY FLOOR/CEILING ASSEMBLY DIRECT FIX TO TJI DSA TJI rc channel FSTC 53 FIIC 44 PAC INTERNATIONAL CONSTRUCTION * Hardwood Flooring * 1/2" Plywood Fire resistance ratings * 1-1/2"
More informationLABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF STEEL CLAD PIR WALL PANELS (According to ISO )
Ref no: LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF STEEL CLAD PIR WALL PANELS (According to ISO 10140 2) AUCKLAND UNISERVICES LIMITED a wholly owned company of THE UNIVERSITY OF AUCKLAND Report
More informationLaboratory Measurement of Impact Sound Insulation of Floor Coverings on a Heavyweight Concrete Slab Floor
Laboratory Measurement of Impact Sound Insulation of Floor Coverings on a Heavyweight Concrete Slab Floor Report INR183/R1 April 2013 Golden Field Corporation Pty Ltd 13 Olver Street Preston VIC, 3072
More informationImportant Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA
Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure
More informationPREDICTING SOUND INSULATION PERFORMANCE
Auckland Christchurch Kuala Lumpur Melbourne Sydney Wellington www.marshallday.com PREDICTING SOUND INSULATION PERFORMANCE USING SOUND INSULATION SOFTWARE TO PREDICT NON-ACHIEVEMENT OF PERFORMANCE STANDARDS
More informationExternal Façade Sound Insulation and Passive Ventilation
External Façade Sound Insulation and Passive Ventilation Ken McGunnigle Nonrefereed Prendos Ltd, PO Box 33
More informationGuide for Sound Insulation in Wood Frame Construction
National Research Council Canada Conseil national de recherches Canada Guide for Sound Insulation in Wood Frame Construction Research Report 219, March 2006 J.D. Quirt, T.R.T. Nightingale, F. King Preamble
More informationDIVISION 9 - SECTION QTscu Recycled Rubber Sound Underlayment US Patent No. RE 41,945
March 10 th, 2017- The document is provided solely as a convenience for spec writers in the drafting process. Ecore will not be held responsible for the use or alteration of any information contained herein.
More informationImportant Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA
Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure
More informationHYDRATHANE INTERIOR WATERPROOFING MEMBRANE. Product. Scope. Building Regulations. Appraisal No. 957 [2017] Appraisal No. 957 (2017) BRANZ Appraisals
HYDRATHANE INTERIOR WATERPROOFING MEMBRANE BRANZ Appraisals Technical Assessments of products for building and construction. Construction Chemicals NZ Ltd 16 Carpenter Road East Tamaki Auckland Phone (09)
More informationTHE MANAGEMENT OF FLOOR IMPACT NOISE TO MEET OR EXCEED BUILDING CODE OF AUSTRALIA REQUIREMENTS
TO MEET OR EXCEED BUILDING CODE OF AUSTRALIA REQUIREMENTS Ross H. Palmer CPEng, RPEQ (3534), NPER 3 Palmer Acoustics (Australia) Pty Ltd 24 Mexicanus Drive Park Ridge Qld 4125 PO Box 165 Browns Plains
More informationARDEX UNDERTILE SHEET MEMBRANE (WPM 750 AND WPM 1000) Product. Scope. Building Regulations. Appraisal No. 727 [2017]
ARDEX UNDERTILE SHEET MEMBRANE (WPM 750 AND WPM 1000) This Appraisal replaces BRANZ Appraisal No. 727 (2011) BRANZ Appraisals Technical Assessments of products for building and construction. ARDEX New
More informationISO INTERNATIONAL STANDARD
Provläsningsexemplar / Preview INTERNATIONAL STANDARD ISO 10140-2 First edition 2010-09-01 Acoustics Laboratory measurement of sound insulation of building elements Part 2: Measurement of airborne sound
More informationThe purpose of the testing on the mock up specimen was to document the acoustical performance of four underlayments installed under ¾ thick marble.
February 24, 12 Daniel Tormo Green Sound Control 6956 SW 47 th Street Miami, FL 33155 Re: Field Impact Insulation Class Testing Report Paramount Bay, Miami Florida Dear Daniel, This letter presents the
More informationG R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to PROFLEX PRODUCTS, INC.
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to PROFLEX PRODUCTS, INC. Series/Model: 4 mm Luxury Vinyl Plank over LV200 Specimen Type: Concrete Slab - 152 mm Overall Size:
More information