TRUSTEES OF THE CALIFORNIA STATE UNIVERSITY CALIFORNIA STATE UNIVERSITY, FULLERTON REQUEST FOR PROPOSAL NO ADDENDUM NO. 1

Size: px
Start display at page:

Download "TRUSTEES OF THE CALIFORNIA STATE UNIVERSITY CALIFORNIA STATE UNIVERSITY, FULLERTON REQUEST FOR PROPOSAL NO ADDENDUM NO. 1"

Transcription

1 ADDENDUM NO. 1 Date: October 8, 2009 This addendum forms a part of the above-referenced Request for Proposal and modifies the original RFP documents issued September 17, Proposers shall acknowledge receipt of this Addendum in their RFP Cover Letter as indicated in Section IV, Proposal Instructions. Failure to do so may subject the Proposal to be disqualified. This Addendum consists of: PART 1 QUESTIONS AND ANSWERS The following are responses to all submitted questions. Q1. Please provide additional data on the new Co-Gen Plant at California State University Fullerton. A1. The Trigen Co-Generation Plant is scheduled to come on line around April/May The only potential capacity change is if a third cooling tower cell of equivalent size to the existing cells is added. Each existing cooling tower cell is approximately 7200 gpm and a sump of approximately 60,000 gallons. Two (2) absorption chillers of 1200 tons each will be added. Q2. Section 8.1 Cooling Tower Water Treatment The inhibitor specification is indicative of an alkaline (no ph control) type water treatment program. No specific corrosion inhibitor for mild steel is listed. However, the cycles of concentration (four cycles), the type of microbiocide (sodium hypochlorite), and references to acid, indicate that the intention of the specification is a ph controlled (acid feed) type program. What type of program is requested in specification (ph control or alkaline with no ph control)? If the program is (ph controlled) will the product specification be upgraded? Biocide 1 would be ineffective for alkaline type program. Biocide 2 (Glutaraldehyde) at use levels and given the system volume of 160,000 gallons would be very expensive to implement. Page 1 of 5

2 A2. The specification calls for a PBTC based corrosion inhibitor. Yes, you will still use acid. Hypo will work below a ph of 8.3 and you have been running at around 8.0. It works better as the ph drops. Glutaraldehyde is not cheap, we agree. Q3. Can other choices of an oxidizing biocide and non-oxidizing biocide 2 be proposed? A3. Proposers can propose as many alternate programs as they would like. They do need to bid the specification first. Q4. Section 8.2 Chilled TES Loop. The chilled (TES) water system is designed to be also an emergency source of water in an event of fire. This dual function of the chilled water system requires use of only non-hazardous chemical. Molybdate is required in the specification, however, molybdate is also a listed hazardous chemical in the State of California. Will molybdate be removed from the specification or should we propose chemicals that contain molybdate as an active ingredient? A4. If your chill water is also fire water, the treatment will need to be changed. Q5. Section 8.3 Boiler Water Treatment. Polymer minimum level of 100 ppm. Why polymer level required is 100 ppm? This level of polymer may cause severe foaming in the boiler water. Typically only ppm active polymer residuals are used. If this is a typo, will it be corrected? A PPM polymer in a boiler using a polymer program is a standard regime. Phosphate programs would be 50 PPM polymer. Q6. Section 5.1 Testing Program Requirements: This section calls out a Science Lab Center. Was that on the walk through? What are the specific equipment and systems requiring treatment for this location? A6. The Science Lab Center was discussed on the Job Walk. There are two (2) 9.5 hp boilers in the basement. Page 2 of 5

3 Q7. Section 8.1 Cooling Towers Water Treatment specifies that the cooling water inhibitor to contain molybdenum. Will a more environmentally friendly and lower cost substitute be allowed that provides the same control and monitoring benefits as molybdenum? This technology is proven used by more than 10,000 customers in the US and Worldwide. A7. Yes Q8. Section 8.2 Chilled TES Loop Systems Treatment specifies two different treatment approaches, HEDP and HPA. Would you accept an alternate technology (PSO) that has been proven in large TES systems to provide the same or improved corrosion protection as HEDP and or HPA? A8. Propose the specification and PSO as an alternate. Q b - Can you provide a list of the various sections required in the proposal? Would it be possible to provide the sections/descriptions as they should be listed on the Table of Contents? The order that they should be listed would be helpful. Where should the Program Notebook be located? Where should any proof statements, pictures be located? Do they have to be listed in the Table of Contents and in what format? ie as exhibits? A9. Per the instructions provided in Section IV, item 4.6 Proposal Format to include: a. Cover Letter (noting addenda received), b. Table of Contents, c. Exceptions, d. Worksheet Schedule of Values & Summary pages, e. Cost Proposal Sheet, f. Program Notebook. In addition you will also need to include: Exhibit C - Small Business Preference and Certification Request (if applicable), Exhibit D Disabled Veteran Business Enterprise (DVBE) Requirements (Mandatory), Exhibit E - Program Notebook Requirements Checklist/Questionnaire, Exhibit F - Client/System Reference List, Exhibit G - Reference Forms. Each of these sections should be indexed and tabbed. Index tabs with the appropriate title, are required. Proof statements and pictures are not required, but can be included as appendices. Emphasis should be on the completeness and clarity of content. Responses should emphasize the proposers capability to perform work of this type. Page 3 of 5

4 Q a - What are the hours of operation on the tower ie how many hours per day and how many days per year? A hours per day in the summer, 9 hours per day in the winter, approximately 270 to 300 days per year. Q a - What are the hours of operation of each boiler? Do some operate at different times than others? We are looking for hours per day and days per year. What percent of condensate is returned? What is the operating pressure of the boiler? Is there steam pressure reducing on the boiler? What is the distance of the steam lines? Can you verify the hardness of the make up to the boilers measured in ppm? We need this for both soft water and feed water. A hours per day, 365 days per year. No. Do not have an exact number. It is very little, only what comes from the strainers. 70 psi. Yes, DBH is down stream of boilers, MH is at the boilers. DBH is approximately 300 ft. MH is approximately 500 ft. In January 2009 monitoring data, the calcium hardness levels were reported at 0.3 PPM for soft water and 0.24 PPM for the boiler feed water. Q What percent of active azole and PBTC is expected in the Cooling Tower products? A12. The CSUF specifications ask that you maintain a minimum of 1.0 PPM free and available azole in the Cooling Tower system for copper corrosion protection and a minimum of 3.0 PPM phosphonate at all times. Page 4 of 5

5 Q What percent of active HEDP, azole and HPA is expected in the Chilled systems treatment? A13. The CSUF existing minimum range for HEDP is 30 PPM. Recommended HPA is at a minimum of 12 PPM. Chilled water system should have a free and available azole level at a minimum of 5 PPM. Q14. Should we fill out/sign the agreement and include with the proposal? A14. No. The agreement form is provided as a sample to Proposers. If the RFP is awarded, the winning firm will be required to enter into a binding agreement with California State University, Fullerton for the specified Water Treatment services described in the Request for Proposal. All other terms and conditions of the original RFP documents remain the same. - END OF ADDENDUM #1 - Page 5 of 5

Addendum #4. Addendum No. 4

Addendum #4. Addendum No. 4 Addendum #4 Purchasing Services 4202 East Fowler Avenue, SVC 1073 Tampa, Florida 33620 (813) 974-2481 Web Address: http://www.usf.edu/business-finance/purchasing/public-bids/index.aspx October 27, 2017

More information

EXHIBIT A UNIVERSITY OF NEVADA - LAS VEGAS WATER TREATMENT BEST PRACTICES

EXHIBIT A UNIVERSITY OF NEVADA - LAS VEGAS WATER TREATMENT BEST PRACTICES UNIVERSITY OF NEVADA - LAS VEGAS WATER TREATMENT BEST PRACTICES This document is designed to guide the UNIVERSITY OF NEVADA - LAS VEGAS HVAC systems through the difficult task of managing the water treatment

More information

TITLE: WATER TREATMENT PROGRAM FOR CHILLED WATER PLANTS THIS ADDENDUM IS FOR THE PURPOSE OF MAKING THE FOLLOWING CHANGES OR CLARIFICATIONS IN RED:

TITLE: WATER TREATMENT PROGRAM FOR CHILLED WATER PLANTS THIS ADDENDUM IS FOR THE PURPOSE OF MAKING THE FOLLOWING CHANGES OR CLARIFICATIONS IN RED: Procurement Department Bid Section Customer Center 1 st Floor, Room 002 21 W. Church Street Jacksonville, Florida 32202 May 17, 20 ADDENDUM NUMBER: ONE (1) TITLE: WATER TREATMENT PROGRAM FOR CHILLED WATER

More information

Metropolitan Washington Airports Authority PROCUREMENT AND CONTRACTS DEPT. AMENDMENT OF SOLICITATION

Metropolitan Washington Airports Authority PROCUREMENT AND CONTRACTS DEPT. AMENDMENT OF SOLICITATION PROCUREMENT AND CONTRACTS DEPT. AMENDMENT OF SOLICITATION Metropolitan Washington Airports Authority Procurement and Contracts Dept., MA-29 2733 Crystal Drive Arlington, VA 22202 1A. AMENDMENT OF SOLICITATION

More information

PRODUCT PROGRAMMING GUIDELINES CHEMICAL GUIDELINES

PRODUCT PROGRAMMING GUIDELINES CHEMICAL GUIDELINES CHEMICAL GUIDELINES INDEX : BOILER treatment program - Oxygen scavengers - Multi purpose - Deposit controllers - Return line treatment - ph controller /phosphate COOLING treatment program - Scale inhibition

More information

BRINGING WATER TREATMENT IN HOUSE - MONITORING AND CONTROL STRATEGIES AND IMPROVED RESULTS AT NRG PHOENIX

BRINGING WATER TREATMENT IN HOUSE - MONITORING AND CONTROL STRATEGIES AND IMPROVED RESULTS AT NRG PHOENIX BRINGING WATER TREATMENT IN HOUSE - MONITORING AND CONTROL STRATEGIES AND IMPROVED RESULTS AT NRG PHOENIX MICHAEL FEHR, PH.D. FEHR SOLUTIONS, LLC AGENDA A VERY BRIEF HISTORY OF COOLING WATER TREATMENT

More information

Cooling Tower Water Management Plan. 901 Fifth Avenue

Cooling Tower Water Management Plan. 901 Fifth Avenue 2013 Cooling Tower Water Management Plan 901 Fifth Avenue Table of Contents I. INTRODUCTION II. GOAL III. SCOPE IV. RESPONSIBILITIES V. TIME PERIOD VI. PERFORMANCE METRIC VII. PROCEDURES AND STRATEGIES

More information

ADDENDUM 2 TO REQUEST FOR PROPOSAL 673-FG UNLV FULL SERVICE WATER TREATMENT

ADDENDUM 2 TO REQUEST FOR PROPOSAL 673-FG UNLV FULL SERVICE WATER TREATMENT ADDENDUM 2 TO REQUEST FOR PROPOSAL 673-FG UNLV FULL SERVICE WATER TREATMENT University of Nevada, Las Vegas Purchasing Department 4505 Maryland Parkway Las Vegas, Nevada 89154-1033 (702) 895-3521 Date

More information

COOLING TOWER WATER TREATMENT

COOLING TOWER WATER TREATMENT COOLING TOWER WATER TREATMENT 1 2 3 1 2 3 OXIDIZING NON-OXIDIZING Solid BCDMH used to control problems in the system caused by microorganisms. Solid DBNPA used to control problems in the system caused

More information

Sulfuric Acid Plant Cooling Tower Improvements

Sulfuric Acid Plant Cooling Tower Improvements Technical Paper Sulfuric Acid Plant Cooling Tower Improvements Ryan Barbour, Herb Quinones and Tom Refi GE Water & Process Technologies 4636 Somerton Road Trevose, PA 19053 Find a contact near you by visiting

More information

Zero Blowdown Technology - ZBT Arizona Transportation Center

Zero Blowdown Technology - ZBT Arizona Transportation Center Zero Blowdown Technology - ZBT Arizona Transportation Center A major transportation center in Arizona was designed to be certified by the USGBC LEED green building program to its highest level, Platinum.

More information

Higher COC and ph Independent Operation of Cooling Water Systems

Higher COC and ph Independent Operation of Cooling Water Systems Higher COC and ph Independent Operation of Cooling Water Systems CONFER-NERTA 2016 S. M. Mahadik President Technical Vasu Chemicals 31/3/2015 Conventional Coal based Power Plants: Flue Gases Steam Turbine

More information

A. Submit manufacturer s data, qualifying documents, and shop drawings on the proposed water treatment system before starting any work.

A. Submit manufacturer s data, qualifying documents, and shop drawings on the proposed water treatment system before starting any work. 15545 WATER TREATMENT ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 232516 An optional keynote to

More information

HVAC WATER TREATMENT 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. D. Section Plumbing (Potable) Water Treatment

HVAC WATER TREATMENT 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. D. Section Plumbing (Potable) Water Treatment 232500 HVAC WATER TREATMENT PART 1 GENERAL 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS A. Section 230510 Chilled Water Systems B. Section 230520 Heat Generation C. Section 230530 Clean Steam

More information

Real World Experiences with a Plant- Based Alternative to Chemical Treatment in Cooling Water Systems

Real World Experiences with a Plant- Based Alternative to Chemical Treatment in Cooling Water Systems Real World Experiences with a Plant- Based Alternative to Chemical Treatment in Cooling Water Systems Steve Chewning, CWT, Southeastern Laboratories, Inc. September 2018 Companies adopting sustainable

More information

Water Conservation Technology for Recirculating Cooling Systems

Water Conservation Technology for Recirculating Cooling Systems Water Conservation Technology for Recirculating Cooling Systems Karen Golmer New England Water Innovation Network John Rowen Capture H2O, Inc. April 28, 2015, University of Connecticut, Hartford CT Game

More information

Optimizing Steam and Cooling Systems for Reliability and Sustainability. Presented By: Kevin Emery

Optimizing Steam and Cooling Systems for Reliability and Sustainability. Presented By: Kevin Emery Optimizing Steam and Cooling Systems for Reliability and Sustainability Presented By: Kevin Emery Kevine@chemtreat.com 804-317-2381 Optimizing Steam and Cooling Systems for Reliability and Sustainability

More information

COC = ,000/ (CaH x TA) This discovery is the basis of our unique, patented HighCycle water management products.

COC = ,000/ (CaH x TA) This discovery is the basis of our unique, patented HighCycle water management products. Background HighCycle tm - Advanced Technology For Cooling Tower Blowdown Reduction A Safe, Simple, Economic, and Environmentally Responsible Technology for Reduction of Water Usage in Cooling Towers Drought

More information

Boiler/Cooling Water Processes and Parameters

Boiler/Cooling Water Processes and Parameters Boiler/Cooling Water Processes and Parameters Outline Feedwater Internal Boiler Water Condensate Blowdown Cooling Water Process Water Feedwater Objectives of boiler feedwater treatment: Prevent introduction

More information

Wastewater Characterization. Tenaska Westmoreland Generating Station

Wastewater Characterization. Tenaska Westmoreland Generating Station Wastewater Characterization Tenaska Westmoreland Generating Station Issued December 20, 2011 Rev 0 Revised October 23, 2012 Rev 1 Revised November 8, 2012 Rev 2 Prepared by GEWPT: R. Henry Weed, P.E. 1

More information

Zero Discharge Treatment Method for Cooling Towers and Heat Exchangers with SP3, I-SOFT-OB, OXYDES & KATALOX LIGHT

Zero Discharge Treatment Method for Cooling Towers and Heat Exchangers with SP3, I-SOFT-OB, OXYDES & KATALOX LIGHT Zero Discharge Treatment Method for Cooling Towers and Heat Exchangers with SP3, I-SOFT-OB, OXYDES & KATALOX LIGHT By Deepak Chopra Watch Water GmbH Fahrlachstraße 14 68165 Mannheim Germany May 2013 Web:

More information

IWC ZLD: New Silica Based Inhibitor Chemistry Permits Cost Effective Water Conservation for HVAC and Industrial Cooling Towers

IWC ZLD: New Silica Based Inhibitor Chemistry Permits Cost Effective Water Conservation for HVAC and Industrial Cooling Towers IWC 07-11 ZLD: New Silica Based Inhibitor Chemistry Permits Cost Effective Water Conservation for HVAC and Industrial Cooling Towers Report by Dan Duke Water Conservation Technology International water-cti.com

More information

Cooling Tower Treatment Chemicals

Cooling Tower Treatment Chemicals Cooling Tower Treatment 1) Scale & Corrosion Inhibitors 1. Cooling Tower Treatment Code Product Name 2048 Combined Scale Control / Anti-Foulant-cooling Systems 2202 Scale & Corrosion Inhibitor (Hard Water)

More information

OPTIDOSE 4210 Traceable Polymeric Acid Scale Inhibitor and Dispersant

OPTIDOSE 4210 Traceable Polymeric Acid Scale Inhibitor and Dispersant Technical Data Sheet OPTIDOSE 4210 Traceable Polymeric Acid Scale Inhibitor and Dispersant Regional Product Availability Description Benefits North America OPTIDOSE 4210 traceable polymaleic acid polymer

More information

OFFICE OF PROCUREMENT COOLING TOWER REPLACEMENT, CT BUILDING RFP NO.: RFP OPENING DATE: APRIL 16, 3:00 PM ADDENDUM #4.

OFFICE OF PROCUREMENT COOLING TOWER REPLACEMENT, CT BUILDING RFP NO.: RFP OPENING DATE: APRIL 16, 3:00 PM ADDENDUM #4. OFFICE OF PROCUREMENT COOLING TOWER REPLACEMENT, RFP NO.: 618-009 RFP OPENING DATE: APRIL 16, 2018 @ 3:00 PM ADDENDUM #4 April 9, 2018 THIS ADDENDUM IS TO PROVIDE ANSWERS TO THE FOLLOWING QUESTIONS: NOTE:

More information

Electro-Chemical UET Water Treatment System Achieves Sustainability Objectives for Scottsdale Fashion Square Mall.

Electro-Chemical UET Water Treatment System Achieves Sustainability Objectives for Scottsdale Fashion Square Mall. Electro-Chemical UET Water Treatment System Achieves Sustainability Objectives for Scottsdale Fashion Square Mall. By George Chac, Melvin Mathew and Terry Waldo May, 28 Owned by Macerich (NYSE:MAC), Scottsdale

More information

high cycles cooling tower operation using a revolutionary alkaline treatment program Continuum* AEC (Alkyl Epoxy Carboxylate)

high cycles cooling tower operation using a revolutionary alkaline treatment program Continuum* AEC (Alkyl Epoxy Carboxylate) Water Technologies & Solutions technical paper high cycles cooling tower operation using a revolutionary alkaline treatment program Continuum* AEC (Alkyl Epoxy Carboxylate) Authors: Joseph Janeczko (SUEZ),

More information

B. System Design and Performance Requirements

B. System Design and Performance Requirements 15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

ADVERTISEMENT FOR BIDS

ADVERTISEMENT FOR BIDS ADVERTISEMENT FOR BIDS THE City of Craig, Colorado will receive sealed bids for CHEMICALS until 2:00 p.m., January 19, 2016, at the office of the City Clerk, 300 West Fourth Street, Craig, Colorado 81625,

More information

PRESENTED BY: BRAD SWEARINGEN JIM NONNENMANN, PE

PRESENTED BY: BRAD SWEARINGEN JIM NONNENMANN, PE IDEA CAMPUS ENERGY 2016 : THE CHANGING LANDSCAPE PRVN CONSULTANTS, INC. PRESENTED BY: BRAD SWEARINGEN JIM NONNENMANN, PE AGENDA Research Campus Utilities Overview Chilled Water Need and Project Goals Project

More information

Integrating Standby Power and Steam Turbine Chillers for Better Resiliency at UNC Chapel Hill

Integrating Standby Power and Steam Turbine Chillers for Better Resiliency at UNC Chapel Hill Integrating Standby Power and Steam Turbine Chillers for Better Resiliency at UNC Chapel Hill IDEA 28 th Annual Campus Energy Conference Denver, Colorado Philip Barner, P.E. Director of Energy Services

More information

Section A: CUSTOMER INFORMATION. Customer Name Electric Account Number Rate Application Number. Facility Address City State Zip Code

Section A: CUSTOMER INFORMATION. Customer Name Electric Account Number Rate Application Number. Facility Address City State Zip Code New Equipment & Construction 2017 VFD Incentive Section A: CUSTOMER INFORMATION Customer Name Electric Account Number Rate Number Facility Address City State Zip Code Service Location Identification Email

More information

RICHMOND PUBLIC SCHOOLS DIVISION OF PURCHASES 2395 Hermitage Road, Vatex Building RICHMOND, VIRGINIA May 24, 2016 ADDENDUM NO.

RICHMOND PUBLIC SCHOOLS DIVISION OF PURCHASES 2395 Hermitage Road, Vatex Building RICHMOND, VIRGINIA May 24, 2016 ADDENDUM NO. RICHMOND PUBLIC SCHOOLS DIVISION OF PURCHASES 2395 Hermitage Road, Vatex Building RICHMOND, VIRGINIA 23220-1307 May 24, 2016 ADDENDUM NO. 1 Invitation No.: BID#16-6721-5 Dated: May 13, 2016 Opening Date:

More information

BIOBAN CWT Brand of 25% Aqueous TRIS(HYDROXYMETHYL)NITROMETHANE Cooling Water Treatment Microbicide EPA Reg. No

BIOBAN CWT Brand of 25% Aqueous TRIS(HYDROXYMETHYL)NITROMETHANE Cooling Water Treatment Microbicide EPA Reg. No Product Information Brand of 25% Aqueous TRIS(HYDROXYMETHYL)NITROMETHANE Cooling Water Treatment Microbicide EPA Reg. No. 464-668 1 General BIOBAN CWT has been utilized successfully to control the growth

More information

PRODUCT SUMMARY. Water Treatment Chemicals. Aug 2016

PRODUCT SUMMARY. Water Treatment Chemicals. Aug 2016 PRODUCT SUMMARY Water Treatment Chemicals 1 Aug 2016 Man Chemical is a regional specialty chemical company that produces a broad range of advanced materials, additives and functional products, specialty

More information

Industrial Waste Heat Recovery

Industrial Waste Heat Recovery Industrial Waste Heat Recovery Industrial Energy RoundTable Kathey Ferland Project Manager Texas Industries of the Future kferland@mail.utexas.edu Riyaz Papar, PE, CEM Director, Energy Assets & Optimization

More information

NACE CORROSION 2008 TEG 096X Symposia - Paper 1421

NACE CORROSION 2008 TEG 096X Symposia - Paper 1421 NACE CORROSION 2008 TEG 096X Symposia - Paper 1421 Electrochemical Studies with Coupled Multielectrode Array Sensors on Corrosion Inhibition of Copper and Affected Metals in the Presence of Ammonia and

More information

9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax:

9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax: 9707 Key West Avenue, Suite 100 Rockville, MD 20850 Phone: 301-740-1421 Fax: 301-990-9771 E-Mail: awt@awt.org Part of the recertification process is to obtain Continuing Education Units (CEUs). One way

More information

COUNTY OF FRESNO ADDENDUM NUMBER: FOUR (4) RFP NUMBER: HVAC CHEMICAL TREATMENT SERVICES. July 23, 2014

COUNTY OF FRESNO ADDENDUM NUMBER: FOUR (4) RFP NUMBER: HVAC CHEMICAL TREATMENT SERVICES. July 23, 2014 COUNTY OF FRESNO ADDENDUM NUMBER: FOUR (4) RFP NUMBER: 910-5268 HVAC CHEMICAL TREATMENT SERVICES PURCHASING USE ssj IMPORTANT: SUBMIT PROPOSAL IN SEALED PACKAGE WITH PROPOSAL NUMBER, CLOSING DATE AND BUYER

More information

Chilled Ammonia Process Update. Richard Rhudy, EPRI Sean Black, ALSTOM CO 2 Capture Network May 24, 2007 Lyon, France

Chilled Ammonia Process Update. Richard Rhudy, EPRI Sean Black, ALSTOM CO 2 Capture Network May 24, 2007 Lyon, France Chilled Ammonia Process Update Richard Rhudy, EPRI Sean Black, ALSTOM CO 2 Capture Network May 24, 2007 Lyon, France Schematic of the Chilled Ammonia Process Exisiting FGD Existing Stack CO2 Flue Gas Wash

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 25 00 (November 2008) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 25 00 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

In Depth Feasibility Studies Aquifer Thermal Energy Storage (ATES) VAMC Chillicothe and Columbus, OH

In Depth Feasibility Studies Aquifer Thermal Energy Storage (ATES) VAMC Chillicothe and Columbus, OH In Depth Feasibility Studies Aquifer Thermal Energy Storage (ATES) VAMC Chillicothe and Columbus, OH 20 February 2014 Presented to by Mark A. Worthington, Underground Energy, LLC Project Team Outline Purposes

More information

An Introduction to Water Sampling and Testing of Water Systems

An Introduction to Water Sampling and Testing of Water Systems An Introduction to Water Sampling and Testing of Water Systems J. Paul Guyer, P.E., R.A. Paul Guyer is a registered civil engineer, mechanical engineer, fire protection engineer and architect with 35 years

More information

POTENTIAL ENERGY AND COST SAVINGS THROUGH PROPER TREATMENT OF HEATING AND COOLING SYSTEMS

POTENTIAL ENERGY AND COST SAVINGS THROUGH PROPER TREATMENT OF HEATING AND COOLING SYSTEMS POTENTIAL ENERGY AND COST SAVINGS THROUGH PROPER TREATMENT OF HEATING AND COOLING SYSTEMS A Webinar for Facility Managers and Operators at Institutional and Industrial Facilities October 16, 2018 Jeremy

More information

The owner is Oral Roberts University, while management and leasing is handled by Trinity Corporate Real Estate Advisors, LLC.

The owner is Oral Roberts University, while management and leasing is handled by Trinity Corporate Real Estate Advisors, LLC. CityPlex Towers is Oklahoma s largest mixed use office and medical complex comprising of approximately 2.2 million square feet. The structure is reinforced, poured in place concrete, built in 1980. The

More information

ADDENDUM NO. 2 REQUEST FOR PROPOSAL NO. R DESIGN SERVICES FOR RENOVATIONS TO KREILING HALL

ADDENDUM NO. 2 REQUEST FOR PROPOSAL NO. R DESIGN SERVICES FOR RENOVATIONS TO KREILING HALL December 1, 2015 ADDENDUM NO. 2 Attention to Proposers: This constitutes Addendum No. 2 to the referenced Request for Proposals (RFP), and consists of this six (6) page cover letter, and a two (2) page

More information

SECTION HVAC WATER TREATMENT

SECTION HVAC WATER TREATMENT PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 25 00 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between //-----// if not applicable to project. Also delete any other item or paragraph

More information

ESCO Industry Perspective

ESCO Industry Perspective Opportunities Presented by the Utility Grid ESCO Industry Perspective Kevin Johnson Energy Systems Group August 10, 2016 Rhode Island Convention Center Providence, Rhode Island Agenda ESG Nation wide Utility

More information

9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax:

9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax: 9707 Key West Avenue, Suite 100 Rockville, MD 20850 Phone: 301-740-1421 Fax: 301-990-9771 E-Mail: awt@awt.org Part of the recertification process is to obtain Continuing Education Units (CEUs). One way

More information

OPERATIONAL UPDATE ON INNOVATIVE COOLING TOWER PRETREATMENT TECHNOLOGY

OPERATIONAL UPDATE ON INNOVATIVE COOLING TOWER PRETREATMENT TECHNOLOGY OPERATIONAL UPDATE ON INNOVATIVE COOLING TOWER PRETREATMENT TECHNOLOGY Presented By: Joel E. Bowdan III, P.E. PRESENTATION OUTLINE: Subject Introduction Amylin Project Background Cooling Tower Basics Typical

More information

Variable Frequency Drive Retrofit Opportunities. Michael Kuk CERx Solutions LLC

Variable Frequency Drive Retrofit Opportunities. Michael Kuk CERx Solutions LLC Variable Frequency Drive Retrofit Opportunities Michael Kuk CERx Solutions LLC Speaker Introduction» Founder / owner of CERx Solutions LLC» Veteran Owned Small Business Enterprise founded in 2013» 27+

More information

Case Study 3M Corporate Headquarters 2014 Distributed by:

Case Study 3M Corporate Headquarters 2014 Distributed by: Industrial Water Division Case Study 3M Corporate Headquarters 2014 Distributed by: Introduction Creative Water Solutions LLC and 3M conducted a 2 year trial of treatment at their corporate campus cooling

More information

Permanent Load Shifting Program

Permanent Load Shifting Program 1. Program Description Permanent Load Shifting (PLS) can help reduce system peak load by storing energy produced during off-peak period and shifting electricity use from on-peak to off-peak periods on

More information

SPECIALIZED WATER TREATMENT

SPECIALIZED WATER TREATMENT SPECIALIZED WATER TREATMENT One Resource for Water Treatment Technology The AQUATROL Division of MOMAR, Incorporated, formulates and manufactures a variety of technologically advanced products that effectively

More information

Required Treatment of District Thermal Energy in LEED-NC version 2.2 and LEED for Schools

Required Treatment of District Thermal Energy in LEED-NC version 2.2 and LEED for Schools 1 Required Treatment of District Thermal Energy in LEED-NC version 2.2 and LEED for Schools Version 1.0 May 28, 2008 Administrative All LEED-NC v2.2 or LEED for Schools projects that register with USGBC

More information

White Paper. A Reliable Alternative to Chemicals for Cooling Water Treatment. GWS-1107-D 10/31/11 Copyright 2011 All Rights Reserved

White Paper. A Reliable Alternative to Chemicals for Cooling Water Treatment. GWS-1107-D 10/31/11 Copyright 2011 All Rights Reserved White Paper A Reliable Alternative to Chemicals for Cooling Water Treatment GWS-1107-D 10/31/11 Copyright 2011 All Rights Reserved Use Water for Efficient Cooling There are many problems associated with

More information

Cleaning Techniques for Cooling Systems and Boilers

Cleaning Techniques for Cooling Systems and Boilers Cleaning Techniques for Cooling Systems and Boilers Cleaning Applications in Industrial Utility Systems Pre Operational Cleaning and Passivation Removal of Organic Buildup caused by leaks or biofilms Exchanger

More information

Chilled Water Energy Savings Study

Chilled Water Energy Savings Study 1 Chilled Water Energy Savings Study Pressure Dependent Valve Sizing and Valve Authority Pressure Independent Valves (Mechanical and Electronic) Chilled Water System Design MIT Beta Site Study-Correcting

More information

RFB Waco City Hall Chiller Replacement. Date: 3/20/2018 RFP No: Commodity: Waco City Hall Chiller Replacement

RFB Waco City Hall Chiller Replacement. Date: 3/20/2018 RFP No: Commodity: Waco City Hall Chiller Replacement CITY OF WACO RFB 18-022 Waco City Hall Chiller Replacement Purchasing Services Post Office Box 20 Waco, Texas 602-20 Phone: 2 / 0-80 Fax: 2 / 0-8063 kaseyg@wacotx.gov www.waco-texas.com Date: 3//18 RFP

More information

COUNTY OF ROCKLAND Department of General Services Purchasing Division

COUNTY OF ROCKLAND Department of General Services Purchasing Division COUNTY OF ROCKLAND Department of General Services Purchasing Division Title: Contract Period: Water Treatment Services 9/9/13 through 9/8/14 with two additional one-year options, Extend thro ugh 9/8/15

More information

Green FSRU for the future

Green FSRU for the future Green FSRU for the future Presentation at GREEN4SEA Athens April 6 th 2016 Dr. John Kokarakis Vice President Technology & Business Development, Africa, S. Europe Hellenic, Black Sea & Middle East Zone

More information

Coach House: Hunziker Hall:

Coach House: Hunziker Hall: Number: Morristown, NJ From: Sergiu Pelau Sheet: 1 of 5 Date of Visit: 12/7/11 Coach House: 1. Central plant located in Hunziker Wing connecting piping is leaking a. Gas fired plant 10 year old b. Two

More information

Cooling Tower Water Management

Cooling Tower Water Management Cooling Tower Water Management Cooling tower water systems are subject to corrosion, scaling, deposition, and biological fouling; which increase operating costs due to downtime and equipment replacement,

More information

ADDENDUM NO. 01. Include this signed and dated addendum to your proposal.

ADDENDUM NO. 01. Include this signed and dated addendum to your proposal. ADDENDUM NO. 01 To City of College Park RFP FIN 012716 - LEASE ADVERTISEMENT for LEASE for TAX-EXEMPT FINANCING Please note the following additions/changes to this bid. Include this signed and dated addendum

More information

Cooling Tower Water Savings Stakeholder Meeting #1 - DRAFT California Statewide Utility Codes and Standards Program

Cooling Tower Water Savings Stakeholder Meeting #1 - DRAFT California Statewide Utility Codes and Standards Program 1 Cooling Tower Water Savings Stakeholder Meeting #1 - DRAFT California Statewide Utility Codes and Standards Program Energy Solutions August 25, 2010 Cooling Tower Water Savings Agenda CALIFORNIA STATEWIDE

More information

Addendum 3 publishes and answers questions related to the Request for Qualifications ( RFQ ) issued on November 24, 2014:

Addendum 3 publishes and answers questions related to the Request for Qualifications ( RFQ ) issued on November 24, 2014: www.dot.state.pa.us Date: December 18, 2014 Subject: Questions and Answers Regarding RFQ Solicitation: CNG Fueling for Transit Agencies Partnership Project SOQ Due Date: No later than 11:00 a.m. Eastern

More information

Undesirable impurities in boilers. Maximum permissible Cycles of concentration (NC)

Undesirable impurities in boilers. Maximum permissible Cycles of concentration (NC) Maximum permissible Cycles of concentration (NC) From the relationship BD/S = [L/S] / [NC - 1] calculated at material balance in boiler section, as long as L/S is related to system parameters and it is

More information

Puckorius & Associates, Inc.

Puckorius & Associates, Inc. REPORT TO CDG ENVIRONMENTAL, LLC. 205 WEBSTER STREET BETHLEHEM, PA 18015 Volume 1 of 1 SUBJECT: EFFICACY OF A 0.3% CHLORINE DIOXIDE SOLUTION (PRODUCT KNOWN AS CDG SOLUTION 3000) FOR ALGAE CONTROL IN AN

More information

NACE Paper No

NACE Paper No NACE Paper No. 07626 Laboratory and Field Studies of Localized and General Corrosion Inhibiting Behaviors of Silica in Zero Liquid Discharge (High TDS Cooling Water) Using Real Time Corrosion Monitoring

More information

Construction Engineering. Research Laboratory. Green Chemical Treatments for Heating and Cooling Systems ERDC/CERL TR-06-29

Construction Engineering. Research Laboratory. Green Chemical Treatments for Heating and Cooling Systems ERDC/CERL TR-06-29 ERDC/CERL TR-06-29 Green Chemical Treatments for Heating and Cooling Systems Susan A. Drozdz and Vincent F. Hock September 2006 Construction Engineering Research Laboratory Approved for public release;

More information

Operation and Maintenance of Electrochlorination Plant

Operation and Maintenance of Electrochlorination Plant Operation and Maintenance of Electrochlorination Plant Introduction Sodium Hypochlorite is a powerful biocide and oxidizing agent that has been widely used in seawater cooling system to avoid the biofouling

More information

Green Technologies to Minimize Cooling Tower Water Use

Green Technologies to Minimize Cooling Tower Water Use Green Technologies to Minimize Cooling Tower Water Use TAB0411 The environmental footprint of many facilities includes cooling towers, which consume large amounts of water, produce blowdown wastewater,

More information

LABARD AQUASOLVE INDIVIDUAL/ COMPACT TEST KIT

LABARD AQUASOLVE INDIVIDUAL/ COMPACT TEST KIT LABARD AQUASOLVE INDIVIDUAL/ COMPACT TEST KIT Labard Aquasolve presents India's first compact water testing kits. Aquasolve has completely eliminated the powder reagents from these kits which enhances

More information

Evaporative Condenser Passivation. Cameron Klein Strand Associates, Inc.

Evaporative Condenser Passivation. Cameron Klein Strand Associates, Inc. Evaporative Condenser Passivation Cameron Klein Strand Associates, Inc. Evaporative Condenser Wetted Surface Materials of Construction Galvanized Steel Protective zinc coating fused to a steel substrate

More information

Boiler Water Treatment

Boiler Water Treatment Boiler Water Treatment Preventive Solutions and Complete Treatment Programs Corrosion, scaling and deposition can reduce the operating efficiency of the boiler and all the systems connected to the water/steam

More information

Project Proposal Proposal for Investigation of Alternative Systems

Project Proposal Proposal for Investigation of Alternative Systems Project Proposal Proposal for Investigation of Alternative Systems 01.15.2010 Defense Media Activity Building Fort George G. Meade Penn State University Architectural Engineering Faculty Advisor: Dr. Treado

More information

Waste Heat Management Options Industrial Process Heating Systems. Dr. Arvind C. Thekdi E3M, Inc.

Waste Heat Management Options Industrial Process Heating Systems. Dr. Arvind C. Thekdi   E3M, Inc. Waste Heat Management Options Industrial Process Heating Systems By Dr. Arvind C. Thekdi E-mail: athekdi@e3minc.com E3M, Inc. August 20, 2009 Source of Waste Heat in Industries Waste heat is everywhere!

More information

City of Frederick PURCHASING DEPT.

City of Frederick PURCHASING DEPT. ADDENDUM #4 RFP #12-D CITY OF FREDERICK WWTP ENR UPGRADE March 12, 2012 TO: SUBJECT: REF: All Potential Proposers RFP #12-D, CITY OF FREDERICK WWTP ENR UPGRADE Revised Proposal Closing Date, Submitted

More information

2018 Commercial Rebate Program

2018 Commercial Rebate Program Black Hills Energy offers Colorado Commercial and Industrial electric customer rebates for some of the most commonly installed efficiency projects. Follow the checklist below to determine if you are eligible

More information

SPECIFICATIONS FOR TENDER # Repair/Modification to Two (2) Trane Cooling Towers Model BAC VLT550A S/N /5C A

SPECIFICATIONS FOR TENDER # Repair/Modification to Two (2) Trane Cooling Towers Model BAC VLT550A S/N /5C A SPECIFICATIONS FOR TENDER # 0171-1805 Repair/Modification to Two (2) Trane Cooling Towers Model BAC VLT550A S/N 72-3034/5C A CLOSING DATE: February 6 th, 2018 CLOSING TIME: 2:00 PM (Newfoundland Time)

More information

REQUEST FOR PROPOSALS FOR AN INTEGRATED PROJECT DELIVERY METHOD UTILIZING CONSTRUCTION MANAGEMENT/GENERAL CONTRACTING (CM/GC) SERVICES

REQUEST FOR PROPOSALS FOR AN INTEGRATED PROJECT DELIVERY METHOD UTILIZING CONSTRUCTION MANAGEMENT/GENERAL CONTRACTING (CM/GC) SERVICES STATE OF COLORADO OFFICE OF THE STATE ARCHITECT STATE BUILDINGS PROGRAM REQUEST FOR PROPOSALS FOR AN INTEGRATED PROJECT DELIVERY METHOD UTILIZING CONSTRUCTION MANAGEMENT/GENERAL CONTRACTING (CM/GC) SERVICES

More information

D E T E C T D E T E R M I N E D E L I V E R A NEW DIMENSION OF PERFORMANCE FOR PEOPLE, PLANET, PROFITS

D E T E C T D E T E R M I N E D E L I V E R A NEW DIMENSION OF PERFORMANCE FOR PEOPLE, PLANET, PROFITS D E T E C T D E T E R M I N E D E L I V E R A NEW DIMENSION OF PERFORMANCE FOR PEOPLE, PLANET, PROFITS 3D TRASAR TECHNOLOGY DETECTS CHANGING PROCESS PARAMETERS, DETERMINES CORRECT ACTIONS AND DELIVERS

More information

REQUEST FOR PROPOSALS DESAL ANTISCALANT/CLEAN-IN-PLACE CHEMICALS BID NO: ADDENDUM 1

REQUEST FOR PROPOSALS DESAL ANTISCALANT/CLEAN-IN-PLACE CHEMICALS BID NO: ADDENDUM 1 REQUEST FOR PROPOSALS DESAL ANTISCALANT/CLEAN-IN-PLACE CHEMICALS BID NO: 18-18006 ADDENDUM 1 BIDS DUE: April 30, 2018 @ 3:00 PM Central Time To report suspected ethics violations impacting the San Antonio

More information

AN INTRODUCTION HARFST AND ASSOCIATES, INC.

AN INTRODUCTION HARFST AND ASSOCIATES, INC. Harfst and Associates, Inc. Water Management Consultants William F. Harfst AN INTRODUCTION TO HARFST AND ASSOCIATES, INC. William F. Harfst Consultant HARFST AND ASSOCIATES, INC. P.O. Box 276 Crystal Lake,

More information

OPTIDOSE 1000 Traceable Polymer A Tool for Maintaining Maximum Heat Transfer

OPTIDOSE 1000 Traceable Polymer A Tool for Maintaining Maximum Heat Transfer OPTIDOSE 1000 Traceable Polymer A Tool for Maintaining Maximum Heat Transfer Description OPTIDOSE traceable polymer technology is a revolutionary method of tracking polymer levels in cooling water, boiler

More information

PURCHASING DEPARTMENT. Project # Addendum # # of pages Original Issue Date Request Doc # August 28, see text below

PURCHASING DEPARTMENT. Project # Addendum # # of pages Original Issue Date Request Doc # August 28, see text below PURCHASING DEPARTMENT The bid listed below has had addenda issued. Documents are available over the Internet at http://www.norwalkct.org Adobe Acrobat reader is required to view this document. If you do

More information

FLORIDA DEPARTMENT OF TRANSPORTATION

FLORIDA DEPARTMENT OF TRANSPORTATION FLORIDA DEPARTMENT OF TRANSPORTATION ADDENDUM NO. 2 DATE: December 28, 2011 RE: RFP NUMBER: RFP TITLE: ITS Equipment Replacement in Broward County OPENING OF TECHNICAL PROPOSAL DATE: January 5, 2012 Notice

More information

OPTIDOSE Traceable Polymer System OPTIDOSE Test Kits

OPTIDOSE Traceable Polymer System OPTIDOSE Test Kits OPTIDOSE Traceable Polymer System OPTIDOSE Test Kits Ever since polymers have been used as dispersants in cooling water treatment systems, there has been a need for a method of testing the polymer concentration.

More information

Zero Liquid Discharge Cooling Tower Treatment at CSI

Zero Liquid Discharge Cooling Tower Treatment at CSI AIST 2007 Zero Liquid Discharge Cooling Tower Treatment at CSI Dan Duke & John Kubis Water & Enviro Tech Company, Mission Viejo CA Jeff Reed California Steel Industries, Fontana CA This technology is patent*

More information

Mechanical Project Proposal

Mechanical Project Proposal Mechanical Project Proposal Miller Children s Hospital Prepared for: Dr. James Freihaut Department of Architectural Engineering The Pennsylvania State University Prepared by: Stephen Haines December 18

More information

Combustion Turbine Inlet Cooling using Direct Evaporative Cooling

Combustion Turbine Inlet Cooling using Direct Evaporative Cooling Combustion Turbine Inlet Cooling using Direct Evaporative Cooling By Pat Zeller, Munters Corporation Sponsored by: Turbine Inlet Cooling Association (TICA) August 22, 2012; 1 PM (U.S. Central Time) http://www.meetingzone.com/presenter/default.aspx?partcec=4147918

More information

GLIMPSES OF IMPROPER WATER CHEMISTRY IN A SUBCRITICAL PULVERIZED COAL FIRED BOILER AT A THERMAL POWER PLANT

GLIMPSES OF IMPROPER WATER CHEMISTRY IN A SUBCRITICAL PULVERIZED COAL FIRED BOILER AT A THERMAL POWER PLANT GLIMPSES OF IMPROPER WATER CHEMISTRY IN A SUBCRITICAL PULVERIZED COAL FIRED BOILER AT A THERMAL POWER PLANT By K.K.Parthiban / Venus Energy Audit System & Sri Devi Boiler Equipment and Spares. Introduction

More information

9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax:

9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax: 9707 Key West Avenue, Suite 100 Rockville, MD 20850 Phone: 301-740-1421 Fax: 301-990-9771 E-Mail: awt@awt.org Part of the recertification process is to obtain Continuing Education Units (CEUs). One way

More information

2.2 The Purposes and Advantages of a Central Utility Plant

2.2 The Purposes and Advantages of a Central Utility Plant 2.2 The Purposes and Advantages of a Central Utility Plant The purpose of the Central Utility Plant (CUP) at NIST is to provide steam, chilled water, and compressed air for hot and cold water, warm and

More information

R & R IDENTIFICATION CO.

R & R IDENTIFICATION CO. PRESSURE SENSITIVE HV FOR PIPE WITH OUTSIDE DIAMETER OF 6" AND OVER HOT WATER FOR PIPE WITH OUTSIDE DIAMETER OF 2-1/2" TO 6" COLD WATER FOR PIPE WITH OUTSIDE DIAMETER OF 1" TO 2-1/2" DOMESTIC DOMESTIC

More information

Northeast Middle School Cooling Tower Replacement Project

Northeast Middle School Cooling Tower Replacement Project ADDENDUM 2 for Northeast Middle School Cooling Tower Replacement Project TO: FROM: SUBJECT: All Prospective Bidders John Quiocho, Project Manager, Engineered Designs, Inc. Addendum 2 for Northeast Middle

More information

Environment & Power Systems International. VOCGEN /CHP Feasibility Screening Data Form. Level 1 Feasibility Analysis

Environment & Power Systems International. VOCGEN /CHP Feasibility Screening Data Form. Level 1 Feasibility Analysis VOCGEN /CHP Feasibility Screening Data Form VOCGEN /CHP Gensets and Systems (VOCGEN /CHP) can provide significant economic benefits to certain users. Whether VOCGEN /CHP can be economically beneficial

More information

Cooling Water Treatment

Cooling Water Treatment COOL-TREAT Cooling Water Treatment Water Treatment is used to: Optimize most water-based industrial processes Minimize Total Cost Of Operation (TCO) Reduce Risks of operation/production & failures Increase

More information

PREQUALIFICATION OF PROSPECTIVE BIDDERS

PREQUALIFICATION OF PROSPECTIVE BIDDERS Subcontractor* Prequalification for Fullerton College Building 3000 HVAC Equipment Replacement North Orange Coast Community College District, Fullerton California BID #1819-09 PREQUALIFICATION OF PROSPECTIVE

More information

DCP Capacity Upgrade By Adding Thermal Ice Storage. Jelle Wagelmans Sales Manager EVAPCO Middle East DMCC

DCP Capacity Upgrade By Adding Thermal Ice Storage. Jelle Wagelmans Sales Manager EVAPCO Middle East DMCC DCP Capacity Upgrade By Adding Thermal Ice Storage Jelle Wagelmans Sales Manager EVAPCO Middle East DMCC 1 Major Components of a District Cooling Plant 2 Major Components of a DCP Chillers Cooling Capacity

More information