Ventilation standards EN15251 and ANSI/ASHRAE 62.1 Professor Bjarne W. Olesen, Ph.D.
|
|
- Samuel Kenneth Harper
- 6 years ago
- Views:
Transcription
1 Ventilation standards EN15251 and ANSI/ASHRAE 62.1 Professor Bjarne W. Olesen, Ph.D. Technical University of Denmark
2 Energy consumption for ventilation Exhaust Ventilation air Up to 30% of the total energy consumption in buildings Energy for conditioning the ventilation air
3 CRITERIA FOR INDOOR AIR QUALITY ~VENTILATION RATES COMFORT (Perceived Air Quality) HEALTH PRODUCTIVITY ENERGY
4 INTAKE FOR A PERSON PER DAY 1 kg FOOD 2 kg LIQUID 15 kg AIR
5 Odds Rstio for "cases" Odds ratio for being a case, i.e. children with at least two symptoms of possible three (wheezing, rhinitis, eczema) as a function of ventilation rates, in single family houses. (Bornehag et al., 2003) n= 0.17 n= 0.29 n= 0.38 n= 0.62 Mean values for ventilation rates
6 Figure 1. Adjusted odds ratio of SBS for low outdoor air flow rate in commercial buildings [3]
7 Standard 62.1 Definition: What is Acceptable Indoor Air Quality? Air in which there are no known contaminants at harmful concentrations as determined by cognizant authorities and with which a substantial majority (80% or more) of the people exposed do not express dissatisfaction
8 STANDARDS EN Indoor environmental input parameters for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment, lighting and acoustics ASHRAE 62.1 and Ventilation and indoor air quality CR 1752 Ventilation of buildings-design criteria for the indoor environment EN Ventilation for non-residential buildings - performance requirements for ventilation and room-conditioning systems
9 Indoor pollution sources Human bioeffluents Building materials Furnishing HVAC system Equipment Tobacco smoking Building
10 European Audit Project to Optimise Indoor Air Quality and Energy consumption in Office Buildings Sensory pollution load- perceived air quality Materials and activities Outdoor air Occupants Ventilation system
11 TWO PATHWAYS Ventilation Rate Procedure Prescriptively Based Rates by Space Type Rates by occupants level Indoor Air Quality Procedure Performance Based Concentration Targets Occupant Acceptability Air Cleaning Allowed
12 Analytical procedure Ventilation Rate Health
13
14 CEN CR 1752 EN15251 ASHRAE 62.1 Diagram based on studies with Danish subjects (Fanger et.al). Similar results obtained by North-American subjects (Cain et.al.) Similar results obtained with Japanese subjects (Tanabe)
15 Basic required ventilation rates for diluting emissions (bio effluents) from people for different categories Category Expected Percentage Dissatisfied Airflow per person l/s/pers I 15 1O II 20 7 III 30 4 IV > 30 < 4 Adapted persons 2,5 l/s person (Cat. II )
16 Indoor pollution sources Human bioeffluents Building materials Furnishing HVAC system Equipment Tobacco smoking Building
17 Concept for calculation of design ventilation rate People Component Building Component Breathing Zone Outdoor Airflow V bz = R p P z + R s S d + R a A z Minimum l/s/person Number of People Ventilation per Smoker Number of Smokers Building Area Minimum l/s/m²
18
19 7 independent studies have measured sensory pollution loads in 120 buildings (olf/m 2 floor) 97 office buildings & assembly halls (previous ETS) 0.23± office buildings (no ETS) 0.11± kindergartens 0.06± schools 0.06± department store 0.15 European standard (EN15251): Very Low-polluting building 0.05 Low-polluting building 0.1 Non-low-polluting building 0.2
20 Basic Ventilation Airflow for building emissions pollutions (l/s/m²) Category Airflow per person l/s/pers. Very low polluting building Low polluting building Non low polluting building I 1O 0,5 1 2 II 7 0,35 0,7 1,4 III 4 0,2 0,4 0,8
21 Low Polluting Building The majority of the materials are low polluting. Low polluting materials are natural traditional materials, such as stone and glass, which are known to be safe with respect to emissions, and materials which fulfil the following requirements: The emission of total volatile organic compounds (TVOC) is below 0.2 mg/m²h. The emission of formaldehyde is below 0.05 mg/m²h. The emission of ammonia is below 0.03 mg/m²h. The emission of carcinogenic compounds (IARC) is below mg/m²h. The material is not odorous (dissatisfaction with the odour is below 15 %).
22 Very Low Polluting Building All of the materials are very low polluting and smoking has never occurred and is not allowed. Very low polluting materials are natural traditional materials, such as stone, glass and metals, which are known to be safe with respect to emissions, and materials which fulfil the following requirements The emission of total volatile organic compounds (TVOC) is below 0.1 mg/m²h. The emission of formaldehyde is below 0.02 mg/m²h. The emission of ammonia is below 0.01 mg/m²h. The emission of carcinogenic compounds (IARC) is below mg/m²h. The material is not odorous (dissatisfaction with the odour is below 10 %).
23 Recommended ventilation rates for non-residential buildings for three categories (EN15251) Type of building or space Category Per person l/s,person Per floor area l/s,m 2 Per person l/s,person Per floor area l/s,m 2 Per person l/s,person Per floor area l/s,m 2 Very low polluted building, revision Low polluted building, revision Non-low polluted building, revision Single office I 5,0 1,5 10,0 2,0 20,0 3,0 II 3,0 1,0 7,0 1,4 14,0 2,1 III 2,0 0,6 4,0 0,8 8,0 1,2 Landscaped office Conference room I 7,5 1,5 15,0 1,7 30,0 2,7 II 4,5 1,0 10,5 1,2 21,0 1,9 III 3,0 0,6 6,0 0,7 12,0 1,1 I 1,0 1,5 2,0 6,0 4,0 7,0 II 0,6 1,0 1,4 4,2 2,8 4,9 III 0,4 0,6 0,8 2,4 1,6 2,8
24 Type of building/ space Single office (cellular office) Occupancy person/m 2 0,1 Category CEN Occupants only l/s person ASH- CEN RAE Rp Additional ventilation for building (add only one) l/s m 2 CEN lowpolluting building CEN Non-lowpolluting building ASH- RAE Ra Total l/s m 2 CEN Low Pol. A 10 1,0 2,0 2 B 2,5 7 0,7 1,4 0,3 1,4 C 4 0,4 0,8 0,8 ASH- RAE 0,55 Landscaped office 0,07 A 10 1,0 2,0 1,7 B 2,5 7 0,7 1,4 0,3 1,2 C 4 0,4 0,8 0,7 0,48 Conference room 0,5 A 10 1,0 2,0 6 B 2,5 7 0,7 1,4 0,3 4,2 C 4 0,4 0,8 2,4 1,55 1 l/s m 2 = 0.2 cfm/ft 2 International Centre for Indoor Environment And Energy
25 Recommended CO 2 concentrations above outside for non-residential buildings for three categories Compared to 650ppm (1000ppm) VERY LOW POLLUTED LOW POLLUTED NON LOW POLLUTED TYPE OF BUILDING CATEGORY ΔCO2 ΔCO2 ΔCO2 ppm ppm ppm SINGLE OFFICE LANDSCAPED OFFICE CONFERENCE ROOM AUDITORIUM Higher Same Lower
26 Adapted or Un-adapted? Bioeffluents (body odor) Adapted need only one third of outside air (~7 l/s to 2.5 L/s) Tobacco smoke (ETS) Only limited adaptation (odor, irritation) Building materials and HVAC systems No adaptation International Centre for Indoor Environment And Energy
27 Adapted or Un-adapted? Conference rooms. Adapted? Classrooms. Adapted? Restaurants. Un-adapted? Department stores. Un-adapted International Centre for Indoor Environment And Energy
28 v Required ventilation rate The total required system ventilation rate is calculated by taking into acount the ventilation effectiveness: Total system ventilation rate = V/ε v
29 Ventilation effectiveness
30 Inhaled Air Quality V eff 1 V eff 1.4 (6)
31 Ventilation effectiveness
32 Air Distribution Configuration Ceiling supply of cool air 1.0 Ceiling supply of warm air and floor return 1.0 Ceiling supply of warm air 15 F (8 C) or more above space temperature and ceiling return. Ceiling supply of warm air less than 15 F (8 C) above space temperature and ceiling return provided that the 150 fpm (0.8 m/s) supply air jet reaches to within 4.5 ft (1.4 m) of floor level. Note: For lower velocity supply air, Ez= 0.8. Floor supply of cool air and ceiling return provided that the 150 fpm (0.8 m/s) supply jet reaches 4.5 ft (1.4 m) or more above the floor. Note: Most underfloor air distribution systems comply with this proviso. Floor supply of cool air and ceiling return, provided low- velocity displacement ventilation achieves unidirectional flow and thermal stratification Floor supply of warm air and floor return 1.0 Floor supply of warm air and ceiling return 0.7 Makeup supply drawn in on the opposite side of the room from the exhaust and/or return Makeup supply drawn in near to the exhaust and/or return location As an alternative to using the above values, Ez may be regarded as equal to air change effectiveness determined in accordance with ASHRAE Standard for all air distribution configurations except unidirectional flow. Ez
33 Energy Efficient Technologies Indoor air quality Reduce loads (pollution sources) Natural ventilation Heat recovery Air distribution (contaminant removal) effectiveness» Personal ventilation Air cleaning Thermal comfort Reduce loads (building shell, solar screen, internal loads) Low Temperature Heating- and High Temperature Cooling Systems Use of building mass (Thermo-Active-Building-Systems (TABS)) Drifting temperatures
34 Only 0.1 % is inhaled International Centre for Indoor Environment And Energy
35 International Centre for Indoor Environment And Energy
36 Round Movable Panel Headset International Centre for Indoor Environment And
37 Smoke visualization How it works... International Centre for Indoor Environment And Ene
38 Full-scale measurements Exposed Polluting International Centre for Indoor Environment And Energy
39 First results... outstanding performance! Ventilation Effectiveness V C C CEN Report CR 1752 (1998) E I C C S S Concentrations: C E exhaust air C S C I supply air breathing zone Mixing ventilation Mixing ventilation Displacement ventilation Personalized ventilation T supply - Vent. effect. T supply - Vent. effect. T supply - Vent. effect. T supply - Vent. effect. T inhal T inhal T inhal T room C - C - C - C - < 0 0,9-1,0 < -5 0,9 <0 1,2-1,4-6 1,2-2, , ,9-1, ,7-0,9-3 1,3-2, ,8 > 0 1 >2 0,2-0,7 0 1,6-3,5 > 5 0,4-0,7 International Centre for Indoor Environment And Ene
40 AIR CLEANING Filters Photocatalytic Oxidation (PCO) Electrostatic Dessicant air cleaners Others International Centre for Indoor Environment And Energy
41 Clean and dirty filters
42 Why do filters pollute? Particle concentration Percentage Dissatisfied International Centre for Indoor Environment And Energy
43 Hypotheses SVOCs sorbed on particles SVOCs in gas phase Oxidized SVOCs Unreacted SVOCs
44 Gas phase air purification technologies Photo-catalytic oxidation (PCO) Ozone oxidation Thermal catalytic oxidation (TCO) Plasma oxidation Botanic filtration Sorption filtration
45 Number of Published Articles Catalytic Oxidation Filtration Ozone Plasma Sorption UVGI Published Year
46 Photo catalytic Oxidation (PCO) Catalyst:TiO 2 UV H 2 O CO 2 Adsorption of contaminants Photocatalytical reaction Desorption of final products
47 Perceived air quality (decipol) Results: Bldg mat, PCs, filters P<0.017 Purifier Off Purifier On 10 5 P< low (35 L/s) intermediate (59 L/s) Outdoor air supply rate
48 Perceived air quality (decipol) Results: Human bio effluents P<<0.001 Purifier Off Purifier On P<< low (12 L/s) intermediate (25 L/s) Outdoor air supply rate
49 PD % PAQ in PD% with and without desiccant rotor P< P< P< without desiccant rotoer with desiccant rotor Conditions: Room volume: 40m 3 Outdoor airflow: 13L/s Outdoor air exchange Rate: /h Room relative humidity: 40% Room temperature: 23ºC Recirculated airflow: 54L/s 0 Carpet Linoleum Human
50 Effect of air cleaning on perceived Air Quality Sources: Peoplebuilding materialsused filters
51 STANDARDS Test methods for assessing the performance of gas-phase air cleaning media and devices for general ventilation - Part 2: Gas phase air cleaning devices (GPACD) (ISO/DIS :2011) ISO/TC 142, Cleaning equipment for air and other gases CEN/TC 195 Air filters for general air cleaning
52
53 Chemical Air Cleaning Efficiency
54 Perceived Air Quality Air Cleaning Efficiency
55 Clean Air Delivery Rate
56 Reduction of Ventilation Rate Testing with gas concentrations The building component can be reduced according to the air cleaning efficiency Testing of Perceived Air Quality (PAQ) The total ventilation rate can be reduced according to the PAQ air cleaning efficiency.
57 Destilled water
58 Natural mineral water
59 Performance Ventilation vs performance % (R 2 =0.777; P=0.009) Ventilation rate (L/s per olf)
60 Performance Performance of schoolwork as a function of classroom ventilation 1,4 1,2 1 0,8 0,6 R 2 = Ventilation (L/sp) Doubling ventilation rate ~14.5% higher performance
61 Summertime classroom T in C (NB: Different classes with natural/mechanical ventilation) No AC AC 15 Off Low High Mechanical ventilation
62 Hours/week with windows open (NB: Different classes with natural/mechanical ventilation) No AC AC 0 Off Low High Mechanical ventilation
63 Hours/week with windows open (NB: different classes in winter & summer) Summer Winter 2 0 Low High Ventilation (with no cooling)
64 Analytical calculation of required ventilation Comparable to analytical calculation of cooling loads. No table with cooling loads (W/m 2 ) depending on room type.
65 Ventilation rate Cooling load Parameter Ventilation rate Cooling load Comfort requirement % dissatisfied-odor(paq) % dissatisfied Health- TLV Max. t o, 26 o C Analytical Mass balance Heat balance Outside environment Particles, odors, gases Temperature, solar load, humidity Air cleaning Heat recovery Building materials Emissions/adsorption Heat resistance/heat capacity People Bioeffluents Heat emission Evaporation Internal sources Emissions Heat emission Computers Odors, gases Watts HVAC system Outside air, emissions from components Outside air, Cooled air, heat exchange
66 CONCLUSIONS Air Cleaning as substitute for ventilation must be introduced in standards for required ventilation rates in buildings Test standards for gas phase air cleaners must also include measurements of perceived air quality A certification scheme must be introduced
67 CONCLUSIONS There is no standard which directly specifies requirements for the indoor air quality. Instead it is indirectly achieved by specifying a required minimum ventilation rate There is a general agreement between ASHRAE and EN standards that both contributions from people and contributions from buildings (materials, furnishing, HVAC systems) must be taken into account when specifying the required ventilation rate. The standards for specifying ventilation rates should distinguish between buildings with low-emitting materials and buildings with high-emitting materials. This should increase the interest in establishing better test methods and better labelling of building materials.
68 CONCLUSIONS Whether the required ventilation rate should be based on adapted or un-adapted persons should be evaluated on a case-by-case basis between rooms and the activities they serve; but at the same time, the health must be taken into account. For better evaluation of the health risk there is a need for threshold limit values that safeguard health in non-industrial environments In the future the goal must be a full analytical calculation of the minimum required ventilation rate (taking into account material emissions, air cleaning, etc)
How much ventilation and how to ventilate in the future? The EU policy by 2020
How much ventilation and how to ventilate in the future? Professor Bjarne W. Olesen, Ph.D. Department of Civil Engineering Technical University of Denmark The 20-20-20 EU policy by 2020 By 2020 all new
More informationDo European standards for indoor air quality take into account outdoor air quality? Professor Bjarne W. Olesen, PhD, Department of Civil Engineering
Do European standards for indoor air quality take into account outdoor air quality? Professor Bjarne W. Olesen, PhD, Department of Civil Engineering Technical University of Denmark Global impact on people
More informationStandards for Ventilation and Indoor Air Quality in relation to the EPBD
Standards for Ventilation and Indoor Air Quality in relation to the EPBD Bjarne W. Olesen International Center for Indoor Environment and Energy Technical University of Denmark, Denmark bwo@byg.dtu.dk
More informationINTERNATIONAL STANDARDS FOR THE INDOOR ENVIRONMENT Where are we and do they apply Worldwide. Professor Bjarne W. Olesen, PhD Fellow, Treasurer
INTERNATIONAL STANDARDS FOR THE INDOOR ENVIRONMENT Where are we and do they apply Worldwide Professor Bjarne W. Olesen, PhD Fellow, Treasurer Technical University of Denmark INDOOR ENVIRONMENT THERMAL
More informationArticles. Figure 2. Typical set-up of personalized ventilation system.
Revision of 15251: ndoor Environmental Criteria Abstract: 15251 specifies indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality,
More informationProfessor Bjarne W. Olesen, Ph.D., FASHRAE Society President International Center for Indoor Environment and Energy Technical
Professor Bjarne W. Olesen, Ph.D., FASHRAE bwo@byg.dtu.dk Society President International Center for Indoor Environment and Energy Technical University of Denmark COMFORT-PRODUCTIVITY Building costs People
More informationClassification of Indoor Climate, Construction, and Finishing Materials
Classification of Indoor Climate, Construction, and Finishing Materials 0. Seppiinen Department of Mechanical Engineering, Helsinki University of Technology, Espoo, Finland Abstract Good indoor climate
More informationAir distribution and temperature control in classrooms
Air distribution and temperature control in classrooms Jarek Kurnitski D.Sc., Docent HELSINKI UNIVERSITY OF TECHNOLOGY Laboratory of Heating, Ventilation and Air Conditioning Swegon Air Academy 11.6.2008
More informationStandards for Ventilation, IAQ, and Thermal Comfort EVALUATION OF THE INDOOR ENVIRONMENT THERMAL ENVIRONMENT INDOOR ENVIRONMENT.
Standards for Ventilation, IAQ, and Thermal Comfort Bjarne W. Olesen, PhD. Wirsbo-Velta, Germany Adjunct professor, Technical University Denmark Chair ISO/TC159/SC5/WG1 Ergonomics of the thermal environment
More informationTrends and drivers in the Finnish ventilation and AC market
Trends and drivers in the Finnish ventilation and AC market Jarek Kurnitski, D.Sc. Docent Helsinki University of Technology Finnish Society of Indoor Air Quality and Climate, FiSIAQ 1 Contents Indoor climate
More informationIndoor environment for energy performance of buildings a new European draft standard
International Conference Passive and Low Energy Cooling 1109 Indoor environment for energy performance of buildings a new European draft standard O. Seppänen Helsinki University of Technology, Finland
More informationDISPLACEMENT VENTILATION
DISPLACEMENT VENTILATION D3 OVERVIEW The fundamental approach to displacement ventilation utilizes the natural buoyancy forces created by the convective flows from heat sources in the space. As supply
More informationImplementing Demand Controlled Ventilation to Meet ASHRAE Standard By KlasC. Haglid, P.E., R.A., CEM
Implementing Demand Controlled Ventilation to Meet ASHRAE Standard 62.1-2010 By KlasC. Haglid, P.E., R.A., CEM 1 Klas C. Haglid, P.E., R.A., CEM - Bio ASHRAE Distinguished Service Award 2011 ASHRAE Handbook,
More informationAir Cleaning Devices: Towards Design of Sustainable Buildings
Air Cleaning Devices: Towards Design of Sustainable Buildings Fariborz Haghighat, FASHRAE, FISIAQ Concordia Research Chair Tier 1 Department of Building, Civil and Environmental Engineering Concordia University
More informationAPPLICATIONS Filtration
APPLICATIONS Filtration Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They
More informationASHRAE Region VI CRC Track III: Session 1 Ventilation & IAQ Fundamentals. Steven T. Taylor, PE Principal Taylor Engineering
ASHRAE Region VI CRC Track III: Session 1 Ventilation & IAQ Fundamentals Steven T. Taylor, PE Principal Taylor Engineering This program is registered with the AIA/CES for continuing professional education.
More informationThermal comfort recent challenges
Thermal comfort recent challenges Quality and compliance - Thermal comfort and indoor air quality 19 November 2013 Bjarne OLESEN International Centre for Indoor Environment and Energy Technical University
More informationINDOOR AIR QUALITY AND ENERGY EFFICIENCY IN THE DESIGN OF BUILDING SERVICES SYSTEMS FOR SCHOOL CLASSROOMS
INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN THE DESIGN OF BUILDING SERVICES SYSTEMS FOR SCHOOL CLASSROOMS KL Tam * Architectural Services Department, the Government of Hong Kong Special Administrative
More informationExamples of IEQ factors. Healthy IEQ and energy efficiency. What type of system is the best? Ideas and concepts from research and reality.
Healthy IEQ and energy efficiency Ideas and concepts from research and reality Lars Ekberg Energy Management AB A Chalmers Industriteknik Company 1 Examples of IEQ factors Thermal climate -operative temp.
More informationChapter 14 Indoor Air Quality
Chapter 14 Indoor Air Quality 1 Indoor Environment and Built Environment Buildings Transportations vehicles 2 1 Indoor Air Quality (IAQ) Indoor air quality (IAQ) is the quality of air in an indoor environment.
More informationEffect of using low-polluting building materials and increasing ventilation on perceived indoor air quality
Effect of using low-polluting building materials and increasing ventilation on perceived indoor air quality Pawel Wargocki, Henrik N. Knudsen 2, and Pawel Zuczek International Centre for Indoor Environment
More informationIndoor comfort and air quality in spaces equipped with eco-ventilation systems
ICUC9-9 th International Conference on Urban Climate jointly with th Symposium on the Urban Environment Indoor comfort and air quality in spaces equipped with eco-ventilation systems Eusébio Z. E. Conceição,
More informationP U R I F Y I N G T H E A I R Y O U B R E A T H E
P U R I F Y I N G T H E A I R Y O U B R E A T H E Breathing pure air is a human right. World Health Organization (WHO) IAQ Facts Would you be willing to drink 2.5 liters of dirty water a day? We breathe
More informationTEXAS FACILITIES COMMISSION Edit Date: 4/13/2012 ARCHITECTURAL/ENGINEERING GUIDELINES
General The following guidelines must be met by both the Architect/Engineer (A/E) consultant and the contractor to assure indoor air quality of the building being provided. At the direction of the Project
More informationISO INTERNATIONAL STANDARD. Building environment design Indoor air quality Methods of expressing the quality of indoor air for human occupancy
INTERNATIONAL STANDARD ISO 16814 Fist edition 2008-10-15 Building environment design Indoor air quality Methods of expressing the quality of indoor air for human occupancy Conception de l'environnement
More informationLEED v4 Building Design and Construction Quiz #8 EQ
LEED v4 Building Design and Construction Quiz #8 EQ 1. Which of these is considered an unoccupied space? [Choose three] A. School classroom B. Mechanical room C. Meeting room D. Locker room E. Restroom
More informationOptimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016
Optimizing Indoor Environments for Occupant Satisfaction Presented by: Kelli Goldstone April 2016 Outline Function of HVAC Thermal Comfort Air Distribution Radiant Heating / Cooling Case Study Function
More informationChapter 8: Indoor Environmental Quality
Chapter 8: Indoor Environmental Quality 1 Learning Objectives Minimum indoor air quality performance Environmental tobacco smoke control Enhanced indoor air quality strategies Low-emitting materials Construction
More informationIndoor Air Quality Improvement in a School Building in Delhi
Indoor Air Quality Improvement in a School Building in Delhi Maija Virta #1, Suhaas Mathur #1 # Santrupti engineers Private Limited 1083, 35 th D Cross, 4 th T Block, Jayanagar, Bangalore 560041, India
More informationMEP's Letter of Assurance
MEP's Letter of Assurance Instructions Educational Facilities WELL Certification is determined by onsite Performance Verification and documentation, including Letters of Assurance from the appropriate
More informationMEP Engineer's Letter of Assurance
Instructions MEP Engineer's Letter of Assurance WELL Building Standard, Jan 2016 WELL Certification and WELL Core and Shell Compliance are determined by onsite Performance Verification and Documentation,
More informationMEP's Letter of Assurance
MEP's Letter of Assurance Instructions Multifamily Residential WELL Certification is determined by onsite Performance Verification and documentation, including Letters of Assurance from the appropriate
More informationHuman Response to Ductless Personalised Ventilation: Impact of Air Movement, Temperature and Cleanness on Eye Symptoms
Downloaded from orbit.dtu.dk on: Dec 31, 2019 Human Response to Ductless Personalised Ventilation: Impact of Air Movement, Temperature and Cleanness on Eye Symptoms Dalewski, Mariusz; Fillon, Maelys ;
More informationNotes on Indoor Air Quality
Notes on Indoor Air Quality Indoor Air Quality (IAQ) a Health and Safety Concern? Indoor air quality has become an important occupational health and safety concern. Energy conservation measures instituted
More informationHuman Response to Ductless Personalized Ventilation with Local Air Cleaning: Air Quality and Prevalence of SBS Symptoms
Downloaded from orbit.dtu.dk on: Dec 20, 2017 Human Response to Ductless Personalized Ventilation with Local Air Cleaning: Air Quality and Prevalence of SBS Symptoms Dalewski, Mariusz; Bivolarova, Maria
More informationINTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN BUILDINGS
INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN BUILDINGS William P. Bahnfleth, Ph.D., P.E., FASHRAE, FASME Indoor Environment Center, The Pennsylvania State University Outline Connection between
More informationIndoor Air Quality through Design
Indoor Air Quality through Design Kate Goldstein Editor Werner Lang Aurora McClain csd Center for Sustainable Development I-Context Comfort 2 1.7 Indoor Air Quality through Design Indoor Air Quality through
More informationCOMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS
Kazderko Mikhail COMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS Bachelor s Thesis Building Services Engineering December 2012 DESCRIPTION Date of the bachelor's thesis
More informationDEMAND CONTROLLED VENTILATION (DCV) SYSTEMS
DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS Mari-Liis Maripuu, PhD CIT Energy mari-liis.maripuu@cit.chalmers.se Swegon Air Academy, Portugal, 27 May 211 Outline Introduction Concept of a DCV system Adapting
More informationMEP's Letter of Assurance
MEP's Letter of Assurance Instructions WELL Certification is determined by onsite Performance Verification and documentation, including Letters of Assurance from the appropriate professionals overseeing
More informationIndoor Air Quality (IAQ) Requirements
University of New Hampshire University of New Hampshire Scholars' Repository Division 01 General Requirements Chapter 5 Technical Construction and Renovation Standards 1-25-2013 013560 - Indoor Air Quality
More informationSaving energy for ventilation by careful selection of building materials Wargocki, Pawel; Knudsen, Henrik N.
Aalborg Universitet Saving energy for ventilation by careful selection of building materials Wargocki, Pawel; Knudsen, Henrik N. Published in: Proceedings of the 8th Symposium on Building Physics in the
More informationINTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN BUILDINGS
INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN BUILDINGS William P. Bahnfleth, Ph.D., P.E., FASHRAE, FASME Indoor Environment Center, The Pennsylvania State University Outline Connection between
More informationImprove Schools Indoor Environment
Improve Schools Indoor Environment Indoor Air Quality Tools for Schools Can Save Schools Time and Money What is Indoor Air Quality (IAQ)? Indoor Air Quality refers to environmental characteristics inside
More informationThe Front Lines of Residential Indoor Air Quality. Dan Ventura
The Front Lines of Residential Indoor Air Quality Dan Ventura Learning Objectives What are the most common issues related to indoor air quality in single-family and multi-family residential buildings?
More informationIndoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms
Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms Abstract Finland is a country without a debate on natural ventilation. In such a cold climate, it
More informationLEED And Your Indoor Environment
LEED And Your Indoor Environment An overview of LEED v3 and Indoor Air Quality David McCauley, CIE Council Certified Indoor Environmentalist ACAC CIE #1008005 USGBC's Mission To transform the way buildings
More informationIndoor environmental input parameters for the design and assessment of energy performance of buildings. BJARNE W. OLESEN
ndoor environmental input parameters for the design and assessment of energy performance of buildings. The first international standard that dealt with all indoor environmental parameters (thermal comfort,
More informationTHE EFFECT OF USING LOW-POLLUTING BUILDING MATERIALS ON VENTILATION REQUIREMENTS AND ENERGY USE IN BUILDINGS
THE EFFECT OF USING LOW-POLLUTING BUILDING MATERIALS ON VENTILATION REQUIREMENTS AND ENERGY USE IN BUILDINGS Pawel Wargocki, Henrik N. Knudsen 2, and Monika Frontczak International Centre for Indoor Environment
More informationPERSONAL COMPUTERS POLLUTE INDOOR AIR: EFFECTS ON PERCEIVED AIR QUALITY, SBS SYMPTOMS AND PRODUCTIVITY IN OFFICES
PERSONAL COMPUTERS POLLUTE INDOOR AIR: EFFECTS ON PERCEIVED AIR QUALITY, SBS SYMPTOMS AND PRODUCTIVITY IN OFFICES Zs Bakó-Biró 1,2, P Wargocki 1, C. Weschler 1,3 and P. Ole Fanger 1 1 International Centre
More informationMeasuring Indoor Air Quality presented to AAFAME Members Nov. 14, 2017
Measuring Indoor Air Quality presented to AAFAME Members Nov. 14, 2017 What is Indoor Air Quality? Appropriate IAQ can be defined as a function of three different components: 1) appropriate thermal comfort,
More informationASHRAE s. Indoor Air Quality Procedure. in Ventilation Design
Elliott Horner, PhD UL Environment elliott.horner@ul.com M: 678-249-8856 ASHRAE s Indoor Air Quality Procedure Jim Dennison, CIH, PhD Century Environmental Hygiene jim@centuryenvironmental.com O: 970-266-8000
More informationWhat s in the Air - Truths, Myths & Simple Strategies
What s in the Air - Truths, Myths & Simple Strategies Presented By: Marek Plawinski, M.Sc., MPH, R.Kin. About Inc. Workshop Objectives 1. What is indoor Air Quality 2. IAQ Investigation 3. Simple Field
More informationPerformance of radiant cooling ceiling combined with personalized ventilation in an office room: identification of thermal conditions
Downloaded from orbit.dtu.dk on: Oct 29, 2018 Performance of radiant cooling ceiling combined with personalized ventilation in an office room: identification of thermal conditions Lipczynska, Aleksandra
More informationROOM PURIFYING DISINFECTOR HORIZONTAL LAMINAR AIRFLOW
ROOM PURIFYING DISINFECTOR HORIZONTAL LAMINAR AIRFLOW This unique energy-efficient purifying Disinfector has an integrated 6-step sterilization process combining 3 purification methods of disinfecting
More informationProposed Addendum L to Standard , Ventilation for Acceptable Indoor Air Quality
BSR/ASHRAE Addendum L to ANSI/ASHRAE Standard 62.1-2016 Public Review Draft Proposed Addendum L to Standard 62.1-2016, Ventilation for Acceptable Indoor Air Quality Second Public Review (August 2018) (Draft
More informationEvaluation methods for indoor environmental quality assessment according to EN15251
Summary of this article was published in the REHVA European HVAC Journal Vol 49, Issue 4 (August), 2012, pages 14-19, available at http://www.rehva.eu/en/rehva-european-hvac-journal. Evaluation methods
More informationInvestigation of indoor climate in a naturally ventilated building
Investigation of indoor climate in a naturally ventilated building Indoor Air 2008 Tine S. Larsen Assistant professor Department of Civil Engineering Aalborg University tsl@civil.aau.dk 1/9 Introduction
More informationVENTILATION RATES AND IAQ IN EUROPEAN STANDARDS AND NATIONAL REGULATIONS
VENTILATION RATES AND IAQ IN EUPEAN STANDARDS AND NATIONAL REGULATIONS Nejc Brelih *1, Olli Seppänen 1 1 REHVA Federation of European heating, ventilation and air conditioning associations Rue Washington,
More informationHuman response to individually controlled micro environment generated with localized chilled beam
Downloaded from orbit.dtu.dk on: Jan 31, 2019 Human response to individually controlled micro environment generated with localized chilled beam Uth, Simon C. ; Nygaard, Linette; Bolashikov, Zhecho Dimitrov;
More informationIndoor air quality and ventilation
Indoor air quality and ventilation requirements Guangyu Cao (guangyu.cao@ntnu.no) Department of Energy and Process Engineering, NTNU (November, 10, 2016, Hainan, China) Have you used e-clicker or any audience
More informationEnergy and the Built Environment
Energy and the Built Environment Atila Novoselac Wesley Cole Energy Technology & Policy 10/23/12 Lecture Objectives How much energy is consumed in buildings How the energy is consumed How to make them
More informationIndoor Air Quality Assessments during Renovations at Waverly Elementary School Project #J (January 4, 12, 15, 25 and 29, 2018)
March 29, 2018 Mr. Jeff Klenk Howard County Public School System (HCPSS) 10910 Route 108 Ellicott City, MD 21043 RE: Indoor Air Quality Assessments during Renovations at Waverly Elementary School Project
More informationMinimum Outdoor Airflow Using the IAQ Procedure
providing insights for today s hvac system designer Engineers Newsletter volume 40 3 Minimum Outdoor Airflow Using the IAQ Procedure Past Engineers Newsletters 1 and ASHRAE Journal articles 2,3 have discussed
More informationGood indoor air quality (IAQ) management has become paramount in the construction industry as study
Creating and Maintaining Good Indoor Air Quality Good indoor air quality (IAQ) management has become paramount in the construction industry as study after study shows that employee productivity and health
More informationASHRAE Standard INTRODUCTION AND OVERVIEW Plus a few other issues: Outdoor Air Quality and the IAQ Procedure
ASHRAE Standard 62.1-2004 INTRODUCTION AND OVERVIEW Plus a few other issues: Outdoor Air Quality and the IAQ Procedure Andy Persily ASHRAE Fellow National Institute of Standards and Technology ASHRAE Winter
More informationINDOOR AIR QUALITY PROGRAM
INDOOR AIR QUALITY PROGRAM (Adopted from California State University Office of the Chancellor s Sample IAQ Program) 1 TABLE OF CONTENTS Page 1.0 REGULATORY AUTHORITY.........................................
More informationIndex of Addenda to ANSI/ASHRAE Standard 62.1
a b in 62-1989 Published in 1990. The committee withdrew this addendum from consideration, and the issue of existing buildings was addressed by Addenda 62k and 62af. Withdrawn in September 2000. The addendum
More informationRadiant Floor Cooling Combined with Mixing Ventilation in a Residential Room Thermal Comfort and Ventilation Effectiveness
Downloaded from orbit.dtu.dk on: Apr 09, 2019 Radiant Floor Cooling Combined with Mixing Ventilation in a Residential Room Thermal Comfort and Ventilation Effectiveness Krajcik, Michal; Simone, Angela;
More informationIndoor Environmental Quality Policy
University of Florida Indoor Environmental Quality Policy For New Construction and Renovation Environmental Health and Safety Division June 2009 Introduction Effective management of the indoor environmental
More informationMechanical Technical Assignment One ASHRAE Standard Compliance Evaluation
Mechanical Technical Assignment One ASHRAE Standard 62.1-2007 Compliance Evaluation The Prepared By: Maxwell S. Chien October 5 th, 2007 Prepared For: Dr. William P. Bahnfleth, Ph.D., P.E., Professor Department
More informationIndoor Air Quality Backgrounder: The Basics
Indoor Quality Backgrounder: The Basics I ndoor air quality (IAQ) is an increasingly important issue in schools across the nation. IAQ can directly affect the health and comfort of students and staff.
More informationIMPACT OF VENTILATION RATE, OZONE AND LIMONENE ON PERCEIVED AIR QUALITY IN OFFICES
Proceedings: Indoor Air 22 IMPACT OF VENTILATION RATE, OZONE AND LIMONENE ON PERCEIVED AIR QUALITY IN OFFICES HN Knudsen 1*, A Afshari 1, L Ekberg 2,4 and B Lundgren 3,4 1 Energy and Indoor Climate Division,
More informationASHRAE Standard : Ventilation Rate Procedure
engineers newsletter live Course Outline ASHE Standard 62.1-2004: Ventilation Rate Procedure This presentation covers the Ventilation Rate Procedure for calculating zone and system ventilation airflow,
More informationIAQ & Energy Impact of Exhaust Air Transfer Ratio
This article was published in ASHRAE Journal, November 207. Copyright 207 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission
More informationBall State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Indoor Air Quality
INDOOR AIR QUALITY OPR IAQ: one of the key outcomes along with thermal comfort of a climate control system www.todaysfacilitymanager.com/ Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Indoor
More informationDanish Indoor Climate Labelling
Danish Indoor Climate Labelling General test and labelling criteria 6 th Edition, January 2018 Further information: Danish Indoor Climate Labelling Danish Technological Institute Gregersensvej DK-2630
More informationDemand Controlled Ventilation. A Detailed Study of Energy Usage by Simulation
Demand Controlled Ventilation. A Detailed Study of Energy Usage by Simulation B.R. Sørensen Narvik University College, Building Science, NO-8514 Narvik, Norway, e-mail: brs@hin.no ABSTRACT Detailed mathematical
More informationAllowance Table for: General:
Allowance Table for: Adopting Credits from LEED Canada for New Construction and Major Renovations (NC) 2009 and LEED Canada for Core and Shell Development (CS) 2009 for LEED Canada-NC v1.0 (with or without
More informationISO INTERNATIONAL STANDARD. Building environment design Indoor air quality Methods of expressing the quality of indoor air for human occupancy
INTERNATIONAL STANDARD ISO 16814 Fist edition 2008-10-15 Building environment design Indoor air quality Methods of expressing the quality of indoor air for human occupancy Conception de l'environnement
More informationAnalysis of VOCs & Formaldehyde
Analysis of VOCs & Formaldehyde Indoor air quality testing in homes, schools & offices Tim Robinson Waverton Analytics Ltd Tim_Robinson@wavertonanalytics.com Preview Factors that define or influence indoor
More informationIndoor environmental input parameters for the design and assessment of energy performance of buildings
Downloaded from orbit.dtu.dk on: Sep 20, 2018 ndoor environmental input parameters for the design and assessment of energy performance of buildings Olesen, Bjarne W. Published in: REHVA Journal Publication
More informationLOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS
LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS Elena Buchberger - ebuch@iuav.it Luca Porciani, porciani@iuav.it Fabio Peron, fperon@iuav.it Universita IUAV di Venezia,
More informationUpdate to ASHRAE Ventilation Standards. William P. Bahnfleth, PhD, PE, FASHRAE, FASME The Pennsylvania State University University Park, PA, USA
Update to ASHRAE Ventilation Standards William P. Bahnfleth, PhD, PE, FASHRAE, FASME The Pennsylvania State University University Park, PA, USA REHVA Annual Conference Riga, Latvia May 8 9, 2015 Acknowledgements
More informationPersonal Ventilation: from research to practical use
Personal Ventilation: from research to practical use Arsen Melikov 1*, Henning Grønbæk 2, Jan Bach Nielsen 3 1 International Centre for Indoor Environment and Energy, Department of Mechanical Engineering,
More informationIndoor Air Quality Tools for Schools
CT School Indoor Environment Resource Team 2nd Training Session: Walkthrough Investigations Indoor Air Quality Tools for Schools Agenda: Welcome, Introductions Show and Tell: Presentation of Blueprints,
More informationIMPROVING INDOOR AIR QUALITY IMPROVES THE PERFORMANCE OF OFFICE WORK AND SCHOOLWORK
IMPROVING INDOOR AIR QUALITY IMPROVES THE PERFORMANCE OF OFFICE WORK AND SCHOOLWORK Pawel Wargocki International Centre for Indoor Environment and Energy, Department of Mechanical Engineering, Technical
More informationENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS
ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS Farhad Memarzadeh 1, Jane Jiang 2, and Andy Manning 2 1 PhD, PE, National Institutes of Health, Bethesda, MD, USA 2 PhD, Flomerics,
More informationLEED Best Practices Save $$$
16 Savings result where LEED has been applied to improve IAQ! LEED Best Practices Save $$$ A growing body of green building case studies document the benefits of healthy IAQ in the workplace Learn More
More informationPerformance assessment of a ventilated mattress for pollution control of the bed microenvironment in healthcare facilities
Downloaded from orbit.dtu.dk on: Apr 08, 2019 Performance assessment of a ventilated mattress for pollution control of the bed microenvironment in healthcare facilities Bivolarova, Mariya Petrova; Melikov,
More informationBACTERIA MOLD VIRUS POLLEN
2 SBS is a catch-all term that refers to a series of complaints for which there is no obvious cause and where medical tests reveal no particular abnormalities. The symptoms display when individuals are
More informationThermal Environment evaluation in commercial kitchens
Downloaded from orbit.dtu.dk on: Nov 11, 2018 Thermal Environment evaluation in commercial kitchens Simone, Angela; Olesen, Bjarne W. Publication date: 2013 Link back to DTU Orbit Citation (APA): Simone,
More informationWhat Can I Do with IAQ? Seizing the Indoor Air Opportunity Bill Spohn
What Can I Do with IAQ? Seizing the Indoor Air Opportunity Bill Spohn www.trutechtools.com BSME & MSME, PE Engineering, Marketing, Sales, Business 86-88: Fisher Scientific 88-98: Bacharach 98-99: Superior
More informationThe European Approach to Decrease Energy Use in Buildings Towards ZEB (Zero Energy Buildings)
The European Approach to Decrease Energy Use in Buildings Towards ZEB (Zero Energy Buildings) Professor Bjarne W. Olesen, Ph.d., Dr.h.c., R. Centre for Indoor Environment and Energy Technical University
More informationStudent Performance and Absenteeism Related to IAQ
Student Performance and Absenteeism Related to IAQ Balancing IAQ and Energy Conservation/Efficiency Objectives in Schools ASHRAE Summer Meeting Louisville, KY June 21, 2009 by Francis (Bud) J. Offermann
More informationc Dr. M. Zahurul Haq (BUET) Moist Air & Thermal Comfort ME 415 (2011) 2 / 19
Properties of & Dr. M. Zahurul Haq Professor Department of Mechanical Engineering Bangladesh University of Engineering & Technology (BUET) Dhaka-1000, Bangladesh zahurul@me.buet.ac.bd http://teacher.buet.ac.bd/zahurul/
More informationfor decreased exposure risk indoors Arsen K. Melikov Workplace and Indoor Aerosols, April , Lund
Emerging technologies for decreased exposure risk indoors Arsen K. Melikov Workplace and Indoor Aerosols, April 19-20 2012, Lund International Centre for Indoor Environment and Energy Department of Civil
More informationREHVA EUROPEAN GUIDEBOOKS
REHVA EUROPEAN GUIDEBOOKS REHVA REPORTS REHVA EUROPEAN GUIDEBOOKS No.01: DISPLACEMENT VENTILATION IN NON-INDUSTRIAL PREMISES The guidebook serves as a comprehensive and easy-to-understand design manual.
More informationInterior surface materials as sources of indoor hygiene defects
Interior surface materials as sources of indoor hygiene defects Ingrid Juhasova Senitkova 1,* 1 Institute of Technology and Business in České Budějovice, Department of Civil Engineering, Okružní 517/10,
More informationDEA Clandestine Laboratory Training Center Quantico Marine Corps Base, Quantico, VA
Student: David M. Potchak Mechanical Option Faculty Consultant: Jae-Weon Jeong October 5, 2006 DEA Clandestine Laboratory Training Center Quantico Marine Corps Base, Quantico, VA Mechanical Technical Report
More information