DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS

Size: px
Start display at page:

Download "DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS"

Transcription

1 DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS Mari-Liis Maripuu, PhD CIT Energy Swegon Air Academy, Portugal, 27 May 211

2 Outline Introduction Concept of a DCV system Adapting DCV for commercial and public buildings Technical aspects of a DCV system Economical aspects

3 INDOOR CLIMATE HVAC systems should provide: Good indoor air quality no health risk perceived as fresh and pleasant Good thermal comfort no draught risk temperature and humidity in the comfort range Good acoustical environment quiet supply and removal of air

4 HVAC TASKS - THERMAL CLIMATE AND AIR COMPOSITION Thermal Climate Air and radiant temperatures, air velocity, humidity Air Composition Gases (i.e. CO 2, H 2 O, O 3, NO 2, etc.); Particles Heating Supply (+) Cooling Removal(-) Ventilation Supply (+) Exhaust (-) Gases Supply (+) Removal (-) Particles (Supply +) Removal (-) CAV Constant Air Volume Ventilation (1 or 2 steps, i.e. on/off) Examples of CAV: - manual operation (e.g. on/off) - time control (e.g. day/night) - supply-air temperature control (temperature COD) - outdoor-air/recirculation-air control (enthalpy COD) VAV Variable Air Volume Ventilation (>2 steps or continuous variation) Examples of VAV: - Manual Operation or predetermined pattern - Open-loop Control (OCV) - Closed-loop Control (CCV) VAV with automatic control-on-demand DCV

5 5 Energy VAV and DCV DCV is a subgroup of VAV VAV with automatic control-on-demand DCV VAV Variable Air Volume Ventilation (>2 steps or continuous variation) VAV with automatic control in relation to demand DCV Manual Operation or predetermined pattern DCV Demand Control - Automatic variation with demand

6 DEMAND CONTROLLED VENTILATION A ventilation system with feed-forward and/or feedback control of the airflow rate according to measured demand indicator The demand is determined by set of values and parameters affecting thermal comfort and/or air quality

7 DCV-SYSTEM vs CAV-SYSTEM DCV for thermal comfort control (removal of heat) DCV for indoor air quality control (removal of pollutants) Heat surplus Heat deficit Heat supply needed in the room AC in operation Need of space heating Time of day Cooling capacity of the supply air - CAV system Airflow rate CAV system Cooling capacity needed = cooling capacity of a DCV system Airflow rate DCV system Occupancy Time of day

8 ADVANTAGES OF A DCV-SYSTEM Minimizing the energy use for ventilation and space heating/cooling Lower electrical energy use for fans Lower energy use for supply air heating Minimizing the heat supply needed in the room Advantages can be taken from freecooling

9 ADVANTAGES OF A DCV-SYSTEM Low supply air temperatures possible all year around Outside temp C Air flow Supply air temp Cooling effect 14 C 1 kw C 18 C 1 kw Airflow rate m 3 /s Electrical 3 Power kw 2 Airflow rate m 3 /s DCV Measured Airflow rate m 3 /s Electrical Power kw 3 Airflow rate m 3 /s Electrical Power kw 2 CAV Estimated 1 Electical Power kw h/year h/year

10 APPLICATION OF DCV SYSTEMS For premises with varying load conditions Conference rooms/ auditoria; Schools; Restaurants; Theatres ; Offices; The more the loads are varying in time the more energy savings can be expected

11 EXAMPLES OF DCV-SYSTEM PERFORMANCE Refurbishment of an office building (CAV DCV) 35 m 2 including 17 cell office rooms Energy use for ventilation befor and after refurbisment 2 15 yr 2 1 / m h k W5 Energy performance improvement Indoor climate improvement Before renovation After renovation Heating energy for supply air Electical energy for fans Cooling energy for supply air (district cooling)

12 EXAMPLES OF DCV-SYSTEM PERFORMANCE Refurbishment of an office building (CAV DCV) 35 m 2 including 17 cell office rooms Electric Airflow Power [kw] rate [m³/s] Design airflow 5.6 m 3 /s Fan power Supply airflow rate Time, [h/year] Airflow Supply rate airflow m3/s Electricity Power kw Average 4.2 m 3 /s Average 2,6 kw

13 EXAMPLES OF DCV-SYSTEM PERFORMANCE Refurbishment of an office building (university administration) 25 m 2 including 76 office rooms Electric Airflow Power [kw] rate [m³/s] Design airflow 3,6 m 3 /s Supply airflow rate m3/s Electricity kw Average airflow 1,3 m 3 /s Time, [h/year]

14 EXAMPLES OF DCV-SYSTEM PERFORMANCE New office building (Bengt Dahlgren AB - HVAC consultancy) 42 m 2 of offices, conference rooms, restaurant Photo: Bengt Dahlgren AB Total energy use of the building 75 kwh/m 2 yr DCV system for thermal comfort control Sequence control of cooling machines Performance evaluation is ongoing

15 APPLICATION OF DCV-SYSTEMS - KEY-POINTS TO CONSIDER 1) Specify the demand: what is the purpose of ventilation? Removal of pollutants (control of indoor air quality) Removal of heat (control of thermal comfort) Safety, etc 2) Specify the control: What is suitable indicator for controlling the airflow rates? 3) What measurement techniques are available (types of sensors)? 4) What are the requirements to be set on the system, its components and control system?

16 DCV SYSTEMS IN COMMERCIAL AND PUBLIC BUILDINGS Airflow rates are based on the demands on air quality and/or thermal comfort (air cooling) Air quality is influenced by the pollutants emitted by people and their activities people furniture Oudtoor air Building materials Photo: Chalmers

17 CHOICE OF AN INDICATOR FOR IAQ CONTROL Carbon Dioxide is the most common indicator for pollutants due to human occupancy (easy to measure) Airflow rate control based on occupancy (occupancy sensors) Measurement of volatile organic compounds (VOC) Relations unclear: perceived air quality concentration levels comfort and health Sensors need further development for indoor climate control

18 CO 2 AS AN INDICATOR CO 2 is used as an indicator for perceived air quality CO 2 is an indirect measure of pollutants emitted by people CO2 does not influence health and comfort < 5 ppm Recommended CO 2 levels for good IAQ perception is about 1 ppm Percentage of dissatisfied (PPD) % Note: valid for adult visitors! Fanger, 1988 CO 2 concentration (ppm)

19 CO 2 CONCENTRATION AND AIRFLOW RATE CO2 kontsenratsioon, concentration, ppm 3 Õhuvooluhulk Airflow rate 1 l/s inim. per kohta person 2 l/s inim. per kohta person Ruumis viibimise Time, minutes aeg, minutid 4 l/s inim. per kohta person 6 l/s inim. per kohta person 8 l/s inim. per kohta person 1 l/s inim. per person kohta 12 l/s inim. per kohta person

20 TECHNICAL ASPECTS OF A DCV SYSTEM Holistic approach needed - Room, zone and system level Air-handling unit DCV variation in airflow rate variation in pressure Rooms

21 TECHNICAL ASPECTS OF A DCV SYSTEM Airflow control on a room revel Illustration: Fläktwoods VAV- dampers IAQ sensor Airflow control with VAV-dampers + works within a wide pressure range + manages bigger airflow rates - noise problems may occur - limited minimum airflow rates careful supply air diffuser design and higher supply air temperatures required to avoid risk of draught Temp sensor

22 TECHNICAL ASPECTS OF A DCV SYSTEM Airflow control on a room revel Illustration:Swegon Airflow control with VAV-diffusers Supply duct connection VAV- box VAV- diffuser Traversing motor Exhaust air Air quality IAQ sensor Temperature Temp sensor VAV-diffuser Controlling plate

23 TECHNICAL ASPECTS OF A DCV SYSTEM Airflow control on a room revel Illustration:Swegon Airflow control with VAV-diffusers VAV- box VAV- diffuser Exhaust air Air quality IAQ sensor Temperature Temp sensor CAV-diffuser

24 TECHNICAL ASPECTS OF A DCV SYSTEM Airflow control on a room revel Illustration:Swegon VAV- box VAV- diffuser Exhaust air Air quality IAQ sensor Temperature Temp sensor Airflow control with VAV-diffusers + stable air movement pattern within a wide airflow range + good control of low airflow rates + low supply air temperatures + integrated control functions - can be pressure dependent (active control dampers needed) - limited maximum airflow rates per device

25 REQUIREMENTS ON DCV AIRFLOW CONTROL AND SUPPLY AIR DEVICES Selection criteria Stable supply air pattern in the room in a wide airflow range Airflow control in a wide airflow range (1-1 %) and pressure range Quiet operation within the working range Low supply air temperature (approx.+15 C) without risk of draught AHU PS 2-12 Pa

26 MIXING VENTILATION vs DISPLACEMENT VENTILATION DCV-system is commonly based on the mixing ventilation principle Displacement ventilation is more complicated to adapt to DCV-system approach 24 C Exhaust 26 C Supply 16 C 24 C 24 C 18 C Mixing ventilation Displacement ventilation

27 DISPLACEMENT VENTILATION Ventilation effectiveness C exhaust C breath Ventilation effectiveness when cooling Mixing ventilation.9-1. Displacement ventilation Illustration: Skistad (23) Illustration: Skistad (23) 27

28 DISPLACEMENT VENTILATION Ventilation effectiveness C exhaust The ventilation rate required to maintain the stratification at a certain height C breath Illustration: Skistad (23) h The ventilation rate must match the airflow in the plume Illustration: Skistad (23) 28

29 DISPLACEMENT VENTILATION Higher airflow rates are needed Higher supply air temperatures needed (min +18 C) Reduced useable floor area Typical applications are found in the industry (large airflow rates required for removal of heat) Displacement ventilation Illustration: SP

30 REQUIREMENTS ON DCV-SENSORS The sensors must be chosen according to the demands set on indoor climate Uncertainty of measurement must be sufficient for assuring the indoor climate in within the required Response time must be sufficient for controlling the airflow rates Placement of the sensor must consider the activities in the room and physical properties of the room Not in the breading zone Close to the exhaust air duct in bigger rooms

31 TECHNICAL ASPECTS OF A DCV SYSTEM Zone and system level The duct system must manage low supply air temperatures Relative temperature change Ratio = 1 we have lost all the cooling capacity l/s 1 l/s 5 l/s 1 l/s Duct length, m Duct insulation must reduce the duct heat gains (particularly in main ducts)

32 TECHNICAL ASPECTS OF A DCV SYSTEM Zone and system level The duct system must manage low supply air temperatures Pressure control in the system: zone level & system level Pressure sensor VAV Active control damper Pressure sensor 2-5 Pa VAV diffuser

33 TECHNICAL ASPECTS OF A DCV SYSTEM Zone and system level The duct system must manage low supply air temperatures Pressure control in the system: zone level & system level Careful design of central air-handling unit and its components fan system efficiency dependent on airflow rate Optimal design = good control properties and performance of the system Efficiency, % Johan Åström, Chalmers Load, %

34 TECHNICAL ASPECTS OF A DCV SYSTEM Zone and system level The duct system must manage low supply air temperatures Pressure control in the system: zone level & system level Careful design of central air-handling unit and its components For thermal comfort control all supply air devices must manage low supply air temperature Mixing ventilation and deplacement ventilation can not be combined in a DCV system Rooms

35 EVALUATION OF OCCUPANCY- BASIS FOR THE OPTIMAL DESIGN Example 1: office building (university administration) Number of rooms 76 Occupancy factor OF N N occupied _ rooms All _ rooms Occupancy factor OF Measurement every 4,5 minute 5: 6: 7: 8: 9: 1: 11: 12: 13: 14: 15: 16: 17: 18: 19: 2: Time Maximum Average Minimum

36 EVALUATION OF OCCUPANCY Example 2: school building year 7-9 Total number of classrooms 43 Number of classes 16, 35 students Occupancy factor OF N N occupied _ rooms All _ rooms 1, ) F,9 (O,8 r,7 c to,6 fa,5 c y,4 a n p,3 c u,2 O,1, : 8 :3 8 : 9 :3 9 : 1 :3 1 : 1 :3 : Time :3 2 1 : 3 1 :3 3 1 : 4 1 :3 4 1 : 5 1 :3 5 1 : 6 1 :3 6 1 Monday Tuesday Wednesday Thursday Friday

37 EVALUATION OF OCCUPANCY Example 3: Basic school (Tomelilla) 11 classrooms monitored 24 students per classroom Average occupancy in the classrooms

38 OCCUPANCY IN BUILDINGS Depends on the type of activity in the building In office buildings the work tasks define the presence of people In school buildings occupancy dependent on on the type of the school Pre-schools, basic and middle schools use their rooms continuously (few empty rooms) Secondary schools have also rooms for specific courses and group rooms

39 ECONOMICAL ASPECTS OF DCV Evaluate the potential of DCV for the specific building How the loads are varying in time and between the rooms? Occupancy factor for the building? Evaluate the energy use of the system Evaluate the energy savings Evaluate the investments needed

40 EVALUATION OF ENERGY USE OF A DCV-SYSTEM Electrical energy for fans in a DCV-system: Airflow rate and fan power do not follow the traditional cube law Depends on pressure control in the system and placement of the pressure sensor Fan Power, design W t W t Constant static pressure in the system W f ( t V VAV α 2 ) W Airflow rate,v 3 t f ( V VAV design V No pressure control ) Fan power [kw] Example: measured supply fan power at varying airflow rates W W 1.73 t.18.21,73 V VAV f ( ) t V VAV Supply airflow rate [m³/s]

41 INVESTMENTS NEEDED FOR A DCV-SYSTEM Refurbishment projects Dismantling and construction Fan speed control after pressure in the system (frequency inverters+ pressure sensors) New air ducts (when needed) VAV-box and/or VAV-diffuser + sound attenuator Active control dampers (when needed) Sensors + cabling Control systems (+commissioning)

42 INVESTMENTS NEEDED FOR A DCV-SYSTEM New buildings Fan speed control after pressure in the system (frequency inverters+ pressure sensors) VAV-box and/or VAV-diffuser + sound attenuator Active control dampers (when needed) Sensors + cabling Control systems (+commissioning) Duct system can be optimised!

43 THANK YOU FOR YOUR ATTENTION!

Demand controlled ventilation (DCV) for better IAQ and Energy Efficiency

Demand controlled ventilation (DCV) for better IAQ and Energy Efficiency Demand controlled ventilation (DCV) for better IAQ and Energy Efficiency Mari-Liis Maripuu (Ph.D.) CIT Energy Management AB, Sweden mari-liis.maripuu@cit.chalmers.se Introduction In a Demand Controlled

More information

Proceedings of Clima 2007 WellBeing Indoors

Proceedings of Clima 2007 WellBeing Indoors Experimental Study of Thermal Environment and Comfort in an Office Room with a Variable Air Volume (VAV) System under Low Supply Air Temperature Conditions Mari-Liis Maripuu Chalmers University of Technology,

More information

Examples of IEQ factors. Healthy IEQ and energy efficiency. What type of system is the best? Ideas and concepts from research and reality.

Examples of IEQ factors. Healthy IEQ and energy efficiency. What type of system is the best? Ideas and concepts from research and reality. Healthy IEQ and energy efficiency Ideas and concepts from research and reality Lars Ekberg Energy Management AB A Chalmers Industriteknik Company 1 Examples of IEQ factors Thermal climate -operative temp.

More information

Air distribution and temperature control in classrooms

Air distribution and temperature control in classrooms Air distribution and temperature control in classrooms Jarek Kurnitski D.Sc., Docent HELSINKI UNIVERSITY OF TECHNOLOGY Laboratory of Heating, Ventilation and Air Conditioning Swegon Air Academy 11.6.2008

More information

Demand Control Ventilation; Experiences from theory to real projects

Demand Control Ventilation; Experiences from theory to real projects Demand Control Ventilation; Experiences from theory to real projects DCV experience from real projects Demand Control Ventilation John Woollett C.Eng, F.CIBSE, F.REHVA, M.ASHRAE. Working for Swegon for

More information

How to acquire Demand Controlled Ventilation with energy optimal functionality? John Woollett CEng Reserachers from SINTEF; Mads Mysen & Peter Schild

How to acquire Demand Controlled Ventilation with energy optimal functionality? John Woollett CEng Reserachers from SINTEF; Mads Mysen & Peter Schild How to acquire Demand Controlled Ventilation with energy optimal functionality? John Woollett CEng Reserachers from SINTEF; Mads Mysen & Peter Schild 1 John Woollett C.Eng, F.CIBSE, F.REHVA, M.ASHRAE.

More information

Modular Active Chilled Beams

Modular Active Chilled Beams Modular Active Chilled Beams Presented by: Darren Alexander, P.Eng. Modular Active Chilled Beams Current System Solutions Fan Coil Units - Medium/High energy, medium noise solution. Output = 100-200 w/m

More information

DISPLACEMENT VENTILATION

DISPLACEMENT VENTILATION DISPLACEMENT VENTILATION D3 OVERVIEW The fundamental approach to displacement ventilation utilizes the natural buoyancy forces created by the convective flows from heat sources in the space. As supply

More information

Demand Controlled Ventilation. A Detailed Study of Energy Usage by Simulation

Demand Controlled Ventilation. A Detailed Study of Energy Usage by Simulation Demand Controlled Ventilation. A Detailed Study of Energy Usage by Simulation B.R. Sørensen Narvik University College, Building Science, NO-8514 Narvik, Norway, e-mail: brs@hin.no ABSTRACT Detailed mathematical

More information

Underf loor For Schools

Underf loor For Schools The following article was published in ASHRAE Journal, May 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes

More information

PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS. T Karimipanah 1 and H B Awbi 2

PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS. T Karimipanah 1 and H B Awbi 2 PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS T Karimipanah 1 and H B Awbi 2 1 Air Innovation AB, Sweden 2 University of Reading, UK ABSTRACT This paper focuses on evaluating the performance of

More information

Outdoor Airflow Control Fixed point and DCV. Presented by: David S. Dougan, President EBTRON

Outdoor Airflow Control Fixed point and DCV. Presented by: David S. Dougan, President EBTRON Outdoor Airflow Control Fixed point and DCV Presented by: David S. Dougan, President EBTRON OUTSIDE AIR Pressure Changes Damper Issues Intake Flow Rates (Fixed Min or DCV) OUTSIDE AIR Intake Flow Rate

More information

Integrated Design. Architectural Design v/s HVAC Design. HVAC Design after Architectural design

Integrated Design. Architectural Design v/s HVAC Design. HVAC Design after Architectural design Integrated Design A necessity for sustainable buildings Architectural Design v/s HVAC Design or HVAC Design after Architectural design or Integration of Concept, Location, Esthetic and Technical Design

More information

Under-Floor Air Distribution System (UFAD): Energy and Thermal Comfort Analysis

Under-Floor Air Distribution System (UFAD): Energy and Thermal Comfort Analysis Under-Floor Air Distribution System (UFAD): Energy and Thermal Comfort Analysis Ali Alajmi Associate Professor College of Technological Studies, Kuwait Outline Introduction Motivation HVAC s Air Distribution

More information

Work Package 2: Performance of naturally ventilated buildings

Work Package 2: Performance of naturally ventilated buildings Work Package 2: Performance of naturally ventilated buildings Detailed Monitoring Report The architectural office of Malmö (SE1) Åke Blomsterberg, Charlotte Svensson J&W Consulting Engineers Building Physics,

More information

Air-Water Systems. Chilled Ceilings and Beams TROX USA. Principle of Operation. Radiant Effect on Occupants. Early 1980 s. Chilled Ceiling Panels

Air-Water Systems. Chilled Ceilings and Beams TROX USA. Principle of Operation. Radiant Effect on Occupants. Early 1980 s. Chilled Ceiling Panels Air-Water Systems and Beams Early 1980 s 1980 1990 2005 Buildings well insulated for heating Advent of personal computers Need to remove heat from space Limited space available TROX USA 1 2 Principle of

More information

Standards for Ventilation and Indoor Air Quality in relation to the EPBD

Standards for Ventilation and Indoor Air Quality in relation to the EPBD Standards for Ventilation and Indoor Air Quality in relation to the EPBD Bjarne W. Olesen International Center for Indoor Environment and Energy Technical University of Denmark, Denmark bwo@byg.dtu.dk

More information

Investigation of air quality, comfort parameters and effectiveness for two floor level air supply systems in classrooms

Investigation of air quality, comfort parameters and effectiveness for two floor level air supply systems in classrooms Investigation of air quality, comfort parameters and effectiveness for two floor level air supply systems in classrooms T. Karimipanah 1,2,3, H.B. Awbi 2, M. Sandberg 3 and C. Blomqvist 3 1 Fresh AB, Sweden,

More information

Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms

Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms Abstract Finland is a country without a debate on natural ventilation. In such a cold climate, it

More information

MEP Engineer's Letter of Assurance

MEP Engineer's Letter of Assurance Instructions MEP Engineer's Letter of Assurance WELL Building Standard, Jan 2016 WELL Certification and WELL Core and Shell Compliance are determined by onsite Performance Verification and Documentation,

More information

Chapter 8: Indoor Environmental Quality

Chapter 8: Indoor Environmental Quality Chapter 8: Indoor Environmental Quality 1 Learning Objectives Minimum indoor air quality performance Environmental tobacco smoke control Enhanced indoor air quality strategies Low-emitting materials Construction

More information

Does NZEB pose a conflict to Good Indoor Air Quality? REHVA summit November 2017

Does NZEB pose a conflict to Good Indoor Air Quality? REHVA summit November 2017 Does NZEB pose a conflict to Good Indoor Air Quality? REHVA summit November 2017 Version: 2016-07-04 Niels Christensen Strategic Product Manager, ICS Email: niels.christensen@lindab.com Version: 2016-07-04

More information

Halton Chilled beams Janne Summanen Halton Oy

Halton Chilled beams Janne Summanen Halton Oy Halton Chilled beams Janne Summanen Halton Oy Active chilled beam operation principle Beam presentation Active chilled beam for suspended installation Active chilled beams for exposed installation Passive

More information

The pros and cons of chilled beams

The pros and cons of chilled beams The pros and cons of chilled beams Peter Clackett, Technical Director Skanska Rashleigh Weatherfoil William Booth, Operations Manager BSRIA Agenda 09.30 Registration 10.00 Welcome & Introduction - Jo Harris,

More information

Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By KlasC. Haglid, P.E., R.A., CEM

Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By KlasC. Haglid, P.E., R.A., CEM Implementing Demand Controlled Ventilation to Meet ASHRAE Standard 62.1-2010 By KlasC. Haglid, P.E., R.A., CEM 1 Klas C. Haglid, P.E., R.A., CEM - Bio ASHRAE Distinguished Service Award 2011 ASHRAE Handbook,

More information

Published in: Proceedings of the 7th International Conference on Healthy Buildings 2003, Singapore, December 2003, Vol. 2

Published in: Proceedings of the 7th International Conference on Healthy Buildings 2003, Singapore, December 2003, Vol. 2 Aalborg Universitet Design Methods for Air Distribution Systems and Comparison Between Mixing Ventilation and Displacement Ventilation Nielsen, Peter Vilhelm; Larsen, Tine Steen; Topp, Claus Published

More information

Indoor Air 2005, Beijing, China Effectiveness of confluent jets ventilation system for classrooms

Indoor Air 2005, Beijing, China Effectiveness of confluent jets ventilation system for classrooms Effectiveness of confluent jets ventilation system for classrooms T. Karimipanah 1, H.B. Awbi 2, C. Blomqvist 3 and M. Sandberg 3 ABSTRACT 1 Fresh AB, Sweden, taghi.k@comhem.se 2 University of Reading,

More information

PERFORMANCE OF LOW PRESSURE MECHANICAL VENTILATION CONCEPT WITH DIFFUSE CEILING INLET FOR RENOVATION OF SCHOOL CLASSROOMS

PERFORMANCE OF LOW PRESSURE MECHANICAL VENTILATION CONCEPT WITH DIFFUSE CEILING INLET FOR RENOVATION OF SCHOOL CLASSROOMS PERFORMANCE OF LOW PRESSURE MECHANICAL VENTILATION CONCEPT WITH DIFFUSE CEILING INLET FOR RENOVATION OF SCHOOL CLASSROOMS Søren Terkildsen *1, Svend Svendsen 1, 1 Technical University of Denmark Department

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma LEED Green Building Certification The purpose of the LEED Green Building Rating is to provide a national standard that aims to improve environmental, health and economic performance of buildings using

More information

Xavier Energy Initiative

Xavier Energy Initiative Xavier Energy Initiative By Ron Perkins Report of August Site Visit To paraphrase Blaise Pascal, if I had more time I would have written a shorter report. In deference to those who do not share my enthusiasm

More information

Numerical Investigation on Ventilation Strategy for Laboratories: A Novel Approach to Control Thermal Comfort Using Cooling Panels

Numerical Investigation on Ventilation Strategy for Laboratories: A Novel Approach to Control Thermal Comfort Using Cooling Panels Numerical Investigation on Ventilation Strategy for Laboratories: A Novel Approach to Control Thermal Comfort Using Cooling Panels Farhad Memarzadeh 1, Andy Manning 2 and Zheng Jiang 2 1 National Institutes

More information

ENERGY SIMULATION AND ANALYSIS OF AN INTERMITTENT VENTILATION SYSTEM UNDER TWO CLIMATES

ENERGY SIMULATION AND ANALYSIS OF AN INTERMITTENT VENTILATION SYSTEM UNDER TWO CLIMATES ENERGY SIMULATION AND ANALYSIS OF AN INTERMITTENT VENTILATION SYSTEM UNDER TWO CLIMATES Alan Kabanshi, Arman Ameen, Bin Yang, Hans Wigö, Mats Sandberg CORRESPONDENCE ADDRESSES: Alan Kabanshi, Ph.D., University

More information

Articles. Figure 2. Typical set-up of personalized ventilation system.

Articles. Figure 2. Typical set-up of personalized ventilation system. Revision of 15251: ndoor Environmental Criteria Abstract: 15251 specifies indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality,

More information

MEP's Letter of Assurance

MEP's Letter of Assurance MEP's Letter of Assurance Instructions WELL Certification is determined by onsite Performance Verification and documentation, including Letters of Assurance from the appropriate professionals overseeing

More information

Ventilation standards EN15251 and ANSI/ASHRAE 62.1 Professor Bjarne W. Olesen, Ph.D.

Ventilation standards EN15251 and ANSI/ASHRAE 62.1 Professor Bjarne W. Olesen, Ph.D. Ventilation standards EN15251 and ANSI/ASHRAE 62.1 Professor Bjarne W. Olesen, Ph.D. Technical University of Denmark Energy consumption for ventilation Exhaust Ventilation air Up to 30% of the total energy

More information

How much ventilation and how to ventilate in the future? The EU policy by 2020

How much ventilation and how to ventilate in the future? The EU policy by 2020 How much ventilation and how to ventilate in the future? Professor Bjarne W. Olesen, Ph.D. Department of Civil Engineering Technical University of Denmark The 20-20-20 EU policy by 2020 By 2020 all new

More information

2-Pipe fan coil terminal units were selected as the parallel system to handle the remaining sensible cooling load.

2-Pipe fan coil terminal units were selected as the parallel system to handle the remaining sensible cooling load. Redesign Introduction This report is an in depth analysis of the mechanical systems of the Outreach Innovation Building located in University Park, PA and the impact these changes had on other systems

More information

Volume flow rate calculation

Volume flow rate calculation Volume flow rate calculation Edited by: Balázs Both, assistant lecturer (both@epget.bme.hu) Budapest, 13 th September, 2017. General aims Generally, every ventilation system (or air-conditioning system)

More information

Facilitator Base. Helps you to choose the best product for a given application

Facilitator Base. Helps you to choose the best product for a given application Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Tunnel Fans Facilitator Base Helps you to choose the best product for a given application Systemair - Ventilation

More information

Indoor Air Quality Improvement in a School Building in Delhi

Indoor Air Quality Improvement in a School Building in Delhi Indoor Air Quality Improvement in a School Building in Delhi Maija Virta #1, Suhaas Mathur #1 # Santrupti engineers Private Limited 1083, 35 th D Cross, 4 th T Block, Jayanagar, Bangalore 560041, India

More information

Indoor Air Quality Tools for Schools

Indoor Air Quality Tools for Schools CT School Indoor Environment Resource Team 2nd Training Session: Walkthrough Investigations Indoor Air Quality Tools for Schools Agenda: Welcome, Introductions Show and Tell: Presentation of Blueprints,

More information

CAN AIR HEATING ALONE BE USED IN PASSIVE HOUSE OFFICE BUILDING IN COLD CLIMATES? REVIEW OF THE OBTAINED RESULTS

CAN AIR HEATING ALONE BE USED IN PASSIVE HOUSE OFFICE BUILDING IN COLD CLIMATES? REVIEW OF THE OBTAINED RESULTS CAN AIR HEATING ALONE BE USED IN PASSIVE HOUSE OFFICE BUILDING IN COLD CLIMATES? REVIEW OF THE OBTAINED RESULTS Kari Thunshelle *1, Axel Cable 1, Mads Mysen 1,2, and Hugo Lewi Hammer 2 1 SINTEF Pb.124Blindern

More information

Attaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference

Attaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference Attaining Thermal Comfort in Buildings with Predominantly Glazed Facades presented to: ANSYS Boston Regional Conference September 14, 2011 Case Study Background High floor to ceiling windows Large skylight

More information

Dimensioning of Air Ducts in Buildings with Comfort Ventilation

Dimensioning of Air Ducts in Buildings with Comfort Ventilation South-EasternUniversity of Applied Sciences Overview on Dimensioning of Air Ducts in Buildings with Comfort Ventilation Heikki Salomaa Senior Lecturer, M.Sc.(Tech.) South-Eastern University of Applied

More information

Work Package 2: Performance of naturally ventilated buildings

Work Package 2: Performance of naturally ventilated buildings Work Package 2: Performance of naturally ventilated buildings Detailed Monitoring Report BRE Energy Efficient Office of the Future (GB1) M K White, M Kolokotroni, R Shaw, J Pike, C Ni Riain and MDAES Perera

More information

MEP's Letter of Assurance

MEP's Letter of Assurance MEP's Letter of Assurance Instructions Multifamily Residential WELL Certification is determined by onsite Performance Verification and documentation, including Letters of Assurance from the appropriate

More information

Demand-Controlled Ventilation: A Design Guide

Demand-Controlled Ventilation: A Design Guide Demand-Controlled Ventilation: A Design Guide June 2003 This guide is intended to assist those implementing demand-controlled ventilation (DCV) systems. It was written by Marty Stipe, P.E. with the Oregon

More information

Centre for Sustainability of the Built Environment

Centre for Sustainability of the Built Environment Case Study Report Indoor air quality of a demandcontrolled air-conditioning system Mayfield House Lecture Theatre, Falmer Campus, University of Brighton European Regional Development Fund Executive summary

More information

Getting Started with Your First Project: Considering Rules

Getting Started with Your First Project: Considering Rules Getting Started with Your First Project: Considering Rules to Deploy So you re ready to start a pilot project with a new customer. You have identified what data is available and where it is and how you

More information

LIFE CYCLE COSTS FOR INDOOR CLIMATE SYSTEMS WITH REGARDS TO SYSTEM CHOICE, AIRFLOW RATE AND PRODUCTIVITY IN OFFICES

LIFE CYCLE COSTS FOR INDOOR CLIMATE SYSTEMS WITH REGARDS TO SYSTEM CHOICE, AIRFLOW RATE AND PRODUCTIVITY IN OFFICES LIFE CYCLE COSTS FOR INDOOR CLIMATE SYSTEMS WITH REGARDS TO SYSTEM CHOICE, AIRFLOW RATE AND PRODUCTIVITY IN OFFICES Dennis Johansson 1,2 1 Research and Development, Swegon AB, Tomelilla, Sweden 2 Building

More information

Green Schools Track Ensuring Proper Installation and Commissioning of HVAC Systems for Energy Efficiency and Indoor Air Quality

Green Schools Track Ensuring Proper Installation and Commissioning of HVAC Systems for Energy Efficiency and Indoor Air Quality Green Schools Track Ensuring Proper Installation and Commissioning of HVAC Systems for Energy Efficiency and Indoor Air Quality April 10, 2018 Agenda The Importance of Ventilation in Classrooms Ensuring

More information

Carbon Dioxide Levels in Educational Institutions

Carbon Dioxide Levels in Educational Institutions Carbon Dioxide evels in Educational Institutions AAN HANI, TEET-ANDRUS KOIV, AO MIKOA Department of Environmental Engineering Tallinn University of Technology Ehitajate tee, 1986 ESTONIA allan.hani@rkas.ee,

More information

You Can t Afford Discomfort. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

You Can t Afford Discomfort. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas You Can t Afford Discomfort Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Where We Are Today: So You Want To Save Money? Things to consider: 1. First Cost 2. Energy cost 3. Occupant Salary costs

More information

Federation of European Heating, Ventilation and Air-conditioning Associations

Federation of European Heating, Ventilation and Air-conditioning Associations Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu info@rehva.eu Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 Use of

More information

MEP's Letter of Assurance

MEP's Letter of Assurance MEP's Letter of Assurance Instructions Educational Facilities WELL Certification is determined by onsite Performance Verification and documentation, including Letters of Assurance from the appropriate

More information

Natural Ventilation in Schools and Commercial Buildings (CPD No. 31) Issue 2 May 2017

Natural Ventilation in Schools and Commercial Buildings (CPD No. 31) Issue 2 May 2017 Natural Ventilation in Schools and Commercial Buildings (CPD No. 31) Issue 2 May 2017 Passivent Passivent Accreditations ISO 14001 Environmental Management OHSAS 18001 Health and Safety ISO 9001 Quality

More information

INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN THE DESIGN OF BUILDING SERVICES SYSTEMS FOR SCHOOL CLASSROOMS

INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN THE DESIGN OF BUILDING SERVICES SYSTEMS FOR SCHOOL CLASSROOMS INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN THE DESIGN OF BUILDING SERVICES SYSTEMS FOR SCHOOL CLASSROOMS KL Tam * Architectural Services Department, the Government of Hong Kong Special Administrative

More information

Integrated Design. Modern sustainable buildings as a logic consequence of human needs. Markus T. Kalo, M.Sc., Architect

Integrated Design. Modern sustainable buildings as a logic consequence of human needs. Markus T. Kalo, M.Sc., Architect Integrated Design A necessity for sustainable buildings Markus T. Kalo, M.Sc., Architect www.ipad.se Modern sustainable buildings as a logic consequence of human needs Integrated Design Integrated design:

More information

The central atrium acts as a thermal chimney that drives natural ventilation flow in the building

The central atrium acts as a thermal chimney that drives natural ventilation flow in the building 17.0 VENTILATION We took into consideration the design of window sill and window height so that the users are still able to reach across desk and open the windows in order to adjust their thermal comfort.

More information

EXPERIMENTAL STUDY OF DIFFUSE CEILING VENTILATION IN A CLASSROOM

EXPERIMENTAL STUDY OF DIFFUSE CEILING VENTILATION IN A CLASSROOM EXPERIMENTAL STUDY OF DIFFUSE CEILING VENTILATION IN A CLASSROOM Christian Anker Hviid 1, Søren Terkildsen *1 1 Tech.Univ. of Denmark, Dept. of Civil Engineering Brovej, building 118 DK-2800 Kgs. Lyngby,

More information

DEMAND CONTROL VENTILATION SYSTEMS IN SPORT FACILITIES

DEMAND CONTROL VENTILATION SYSTEMS IN SPORT FACILITIES Aleksandr Kutc DEMAND CONTROL VENTILATION SYSTEMS IN SPORT FACILITIES Bachelor s Thesis Building Services Engineering December 2011 DESCRIPTION Date of the bachelor's thesis December 2011 Author Aleksandr

More information

Trends and drivers in the Finnish ventilation and AC market

Trends and drivers in the Finnish ventilation and AC market Trends and drivers in the Finnish ventilation and AC market Jarek Kurnitski, D.Sc. Docent Helsinki University of Technology Finnish Society of Indoor Air Quality and Climate, FiSIAQ 1 Contents Indoor climate

More information

Star. by Fläkt Woods. iq Star Astra Energy efficient chilled beam

Star. by Fläkt Woods. iq Star Astra Energy efficient chilled beam Star by Fläkt Woods iq Star Astra Energy efficient chilled beam Astra The right climate at the right time. Purposefull and energy efficient. T he modern dern office office is dynamic dynamic. With laptops

More information

YKN2open A R C 032 A B

YKN2open A R C 032 A B york air-conditioning products ACTIVA Rooftop ARC-ARG-ARH-ARD A complete range from 17 kw up to 40 kw YKN2open Features High efficiency EER and COP Low noise level EC supply fan All configurations: Cooling

More information

Refurbishment of Ventilation in Respect of Indoor Environment Quality and Energy Efficiency

Refurbishment of Ventilation in Respect of Indoor Environment Quality and Energy Efficiency Refurbishment of Ventilation in Respect of Indoor Environment Quality and Energy Efficiency VIRTA MAIJA, M.Sc.(Eng.), Vice-president of REHVA, maija.virta@halton.com 1 BACKGROUD FOR SUSTAINABLE INDOOR

More information

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016 Optimizing Indoor Environments for Occupant Satisfaction Presented by: Kelli Goldstone April 2016 Outline Function of HVAC Thermal Comfort Air Distribution Radiant Heating / Cooling Case Study Function

More information

TDPs provide you with new technical training materials designed to help your contractors, engineers, and designers to effectively design, specify,

TDPs provide you with new technical training materials designed to help your contractors, engineers, and designers to effectively design, specify, TDP Catalog TDPs provide you with new technical training materials designed to help your contractors, engineers, and designers to effectively design, specify, sell, and apply HVAC equipment in commercial

More information

V entilation control using carbon dioxide

V entilation control using carbon dioxide REAL-TIME VENTILATION Operational control of ventilation systems using sensors that measure concentrations Editors Note: A longer version of this article is available at no cost on HPAC Engineering s Website

More information

personal exposure to indoor pollutants

personal exposure to indoor pollutants Protected zone ventilation for reducing personal exposure to indoor pollutants Guangyu Cao 1, Kai Siren 2, Peter V. Nielsen 3, Atila Novoselac 4 1 VTT Technical Research Centre of Finland, Finland 2 Aalto

More information

Interdisciplinary Science and Engineering Building

Interdisciplinary Science and Engineering Building 1 1 Senior Thesis Capstone Project Treado Thesis Proposal Interdisciplinary Science and Engineering Building University of Delaware Newark, DE 19716 2 2 Table of Contents Executive Summary 3-4 Building

More information

Good indoor air quality (IAQ) management has become paramount in the construction industry as study

Good indoor air quality (IAQ) management has become paramount in the construction industry as study Creating and Maintaining Good Indoor Air Quality Good indoor air quality (IAQ) management has become paramount in the construction industry as study after study shows that employee productivity and health

More information

The Low Energy Ventilation Company. Fiona Dickinson, Consulting Engineer 21 st May 2013

The Low Energy Ventilation Company. Fiona Dickinson, Consulting Engineer 21 st May 2013 The Low Energy Ventilation Company Fiona Dickinson, Consulting Engineer 21 st May 2013 Contents Building Energy Usage Traditional Natural Ventilation Approach Examples of Natural Ventilation Designing

More information

Environmental Stewardship Conference October 05, 2013 Energy Water and Sustainability (EWaS) Program

Environmental Stewardship Conference October 05, 2013 Energy Water and Sustainability (EWaS) Program Environmental Stewardship Conference October 05, 2013 Energy Water and Sustainability (EWaS) Program Agenda EWaS Overview History Who is EWaS? Mission EWaS Standards & Tools Energy Efficiency HVAC equipment

More information

venticool webinar Ventilative cooling and summer comfort: Freevent project in France Peter Wouters April

venticool webinar Ventilative cooling and summer comfort: Freevent project in France Peter Wouters April venticool webinar Ventilative cooling and summer comfort: Freevent project in France Peter Wouters April 25 2018 More focusing on market implementation More focusing on knowledge generation aspects More

More information

Design for Indoor Environmental Quality in schools

Design for Indoor Environmental Quality in schools Design for Indoor Environmental Quality in schools Richard Daniels, Technical Manager, Education Funding Agency 8 th November 2016 Health, Wellbeing and Productivity in Non-Domestic Buildings Conference

More information

COMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS

COMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS Kazderko Mikhail COMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS Bachelor s Thesis Building Services Engineering December 2012 DESCRIPTION Date of the bachelor's thesis

More information

INDDOR ENVIRONMENTAL QUALITY

INDDOR ENVIRONMENTAL QUALITY INDDOR ENVIRONMENTAL QUALITY IEQ- P1: MINIMUM INDOOR AIR QUALITY PERFORMANCE To establish minimum indoor air quality (IAQ) performance to enhance indoor air quality in buildings, thus contributing to the

More information

Energy Efficient and Good Indoor Climate in Buildings

Energy Efficient and Good Indoor Climate in Buildings Energy Efficient and Good Indoor Climate in Buildings Tallinn February 28, 2013 Dr. Risto Kosonen Adjunct Professor, Aalto University Finland Chief Scientific Officer, Halton Oy The construction sector

More information

42% 32% reduction in lighting power density. 98% of lighting load is tied to occupancy sensors 99% 100%

42% 32% reduction in lighting power density. 98% of lighting load is tied to occupancy sensors 99% 100% Pound Hall 2nd Floor leed ci v2009 1563 Massachusetts Ave leed gold Project Profile 2016 Offices are used for a significant part of the day (a third if not more). Therefore, efficient lighting, heating,

More information

APPLICATION GUIDE DISPLACEMENT

APPLICATION GUIDE DISPLACEMENT DISPLACEMENT APPLICATION GUIDE HOW DOES DISPLACEMENT WORK? ventilation provides low velocity air at around 65 F that relies on buoyancy forces to drive the air motion. Supply air spreads across the floor

More information

Personal Ventilation: from research to practical use

Personal Ventilation: from research to practical use Personal Ventilation: from research to practical use Arsen Melikov 1*, Henning Grønbæk 2, Jan Bach Nielsen 3 1 International Centre for Indoor Environment and Energy, Department of Mechanical Engineering,

More information

Valent Packaged Rooftop Units A Fresh Choice for High-Percentage Outdoor Air Designs. Valent is a business of Unison Comfort Technologies.

Valent Packaged Rooftop Units A Fresh Choice for High-Percentage Outdoor Air Designs. Valent is a business of Unison Comfort Technologies. Valent Packaged Rooftop Units A Fresh Choice for High-Percentage Outdoor Air Designs Valent is a business of Unison Comfort Technologies. When your HVAC system design calls for high-percentage or 100%

More information

THERMAL COMFORT IN LECTURE HALLS IN THE TROPICS

THERMAL COMFORT IN LECTURE HALLS IN THE TROPICS Topic 2. Indoor environment THERMAL COMFORT IN LECTURE HALLS IN THE TROPICS Yat Huang Yau *, Bee Teng Chew, Aza Saifullah Department of Mechanical Engineering, University of Malaya, 50603 Kuala Lumpur,

More information

DEMAND CONTROLLED VENTILATION CASE STUDY ON COMFORT AND ENERGY

DEMAND CONTROLLED VENTILATION CASE STUDY ON COMFORT AND ENERGY Università degli Studi di Padova Facoltà di Ingegneria, Dipartimento di Ingegneria industriale Laurea Magistrale in Ingegneria Energetica DEMAND CONTROLLED VENTILATION CASE STUDY ON COMFORT AND ENERGY

More information

Why use VSD in existing HVAC installations

Why use VSD in existing HVAC installations Introduction... 2 Saving energy... 2 - Controlling capacity to actual need... 3 - Examples... 5 - Variable speed duty... 8 - Constant speed duty... 9 - Reducing maximum kw demand... 9 - Removing unneccessary

More information

Energy and Comfort in School Buildings in the South of Portugal

Energy and Comfort in School Buildings in the South of Portugal Energy and Comfort in School Buildings in the South of Portugal Eusébio Z. E. Conceição, Cláudia M. M. Nunes and Mª Manuela J. R. Lúcio CINTAL - Faculdade de Ciências e Tecnologia - Universidade do Algarve

More information

Higher productivity and lower energy cost through better indoor climate and life cycle cost analysis

Higher productivity and lower energy cost through better indoor climate and life cycle cost analysis Higher productivity and lower energy cost through better indoor climate and life cycle cost analysis Dennis Johansson Forskning och utveckling Swegon AB Byggnadsfysik/Installationsteknik LTH dennis.johansson@swegon.se

More information

Indoor Air Quality (IAQ) Requirements

Indoor Air Quality (IAQ) Requirements University of New Hampshire University of New Hampshire Scholars' Repository Division 01 General Requirements Chapter 5 Technical Construction and Renovation Standards 1-25-2013 013560 - Indoor Air Quality

More information

Energy Recovery Ventilation & ERV Basics The New Custom Express Tool

Energy Recovery Ventilation & ERV Basics The New Custom Express Tool Energy Recovery Ventilation & ERV Basics The New Custom Express Tool Presented by: Dinesh Patel dinesh.patel@nationalgrid.com David Gaudet david.gaudet2@nationalgrid.com 1 What is and Why ERV? The recovery

More information

Recommended Methods to Evaluate Performance of Variable Air Volume Fume Hood Systems

Recommended Methods to Evaluate Performance of Variable Air Volume Fume Hood Systems AIHEC VENT 2006 Recommended Methods to Evaluate Performance of Variable Air Volume Fume Hood Systems Thomas C. Smith Exposure Control Technologies, Inc. Safety is the Primary Objective Lab Occupancy 26%

More information

LEED And Your Indoor Environment

LEED And Your Indoor Environment LEED And Your Indoor Environment An overview of LEED v3 and Indoor Air Quality David McCauley, CIE Council Certified Indoor Environmentalist ACAC CIE #1008005 USGBC's Mission To transform the way buildings

More information

Sustainable Chilled Beam Design

Sustainable Chilled Beam Design MAIJA VIRTA HARRI ITKONEN PANU MUSTAKALLIO MIKA RUPONEN RISTO KOSONEN 1 - Halton Oy ABSTRACT Chilled beam technology is seen as a very sustainable technology providing both excellent indoor conditions

More information

For all those with the ability to influence the design, layout or indoor air quality of buildings

For all those with the ability to influence the design, layout or indoor air quality of buildings Natural Selection For all those with the ability to influence the design, layout or indoor air quality of buildings By the end of this presentation you will:- Understand what Natural Ventilation is. Know

More information

BRE Energy Efficient Office of the Future

BRE Energy Efficient Office of the Future BRE Energy of the Future presentation (1...)! The building was designed by Architects Fielden Clegg Design.! The building has three storeys in two blocks connected by an atrium at the west wall. The main

More information

VENTILATION RATES AND IAQ IN EUROPEAN STANDARDS AND NATIONAL REGULATIONS

VENTILATION RATES AND IAQ IN EUROPEAN STANDARDS AND NATIONAL REGULATIONS VENTILATION RATES AND IAQ IN EUPEAN STANDARDS AND NATIONAL REGULATIONS Nejc Brelih *1, Olli Seppänen 1 1 REHVA Federation of European heating, ventilation and air conditioning associations Rue Washington,

More information

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS Magdalena Hajdukiewicz 1,2,3, Padraig O Connor 1, Colin O Neill 1, Daniel Coakley 1,2,3, Marcus M. Keane 1,2,3, Eoghan Clifford 1,2,3 1 Department

More information

ROOF TOP SPACE. SELF-CONTAINED REVERSIBLE AIR-AIR UNITS OF 23 TO 281 kw EVERY EFFICIENT SOLUTION FOR UNIVERSAL COMFORT NA C

ROOF TOP SPACE. SELF-CONTAINED REVERSIBLE AIR-AIR UNITS OF 23 TO 281 kw EVERY EFFICIENT SOLUTION FOR UNIVERSAL COMFORT NA C C O M F O R T A I R Q U A L I T Y E N E R G Y O P T I M I S A T I O N ROOF TOP SPACE SELF-CONTAINED REVERSIBLE AIR-AIR UNITS OF 23 TO 281 kw EVERY EFFICIENT SOLUTION FOR UNIVERSAL COMFORT NA. 0816 C SPACE

More information

Experimental study of diffuse ceiling ventilation in classroom

Experimental study of diffuse ceiling ventilation in classroom Downloaded from orbit.dtu.dk on: Feb 01, 2019 Experimental study of diffuse ceiling ventilation in classroom Hviid, Christian Anker; Terkildsen, Søren Publication date: 2012 Link back to DTU Orbit Citation

More information

Proceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28

Proceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28 HVAC CONTROL SIMULATION STUDY FOR AUSTRALIAN OFFICE BUILDINGS Hongsen Zhang and Paul Bannister Exergy Australia Pty Ltd, Canberra, Australia hongsen@xgl.com.au; paul@xgl.com.au ABSTRACT This paper presents

More information

HOW THE NUMBER AND PLACEMENT OF SENSORS CONTROLLING ROOM AIR DISTRIBUTION SYSTEMS AFFECT ENERGY USE AND COMFORT

HOW THE NUMBER AND PLACEMENT OF SENSORS CONTROLLING ROOM AIR DISTRIBUTION SYSTEMS AFFECT ENERGY USE AND COMFORT HOW THE NUMBER AND PLACEMENT OF SENSORS CONTROLLING ROOM AIR DISTRIBUTION SYSTEMS AFFECT ENERGY USE AND COMFORT Danni Wang Graduate Student Edward Arens Director Tom Webster Research Specialist Center

More information