fan pressure testing for LarGe, complex buildings terry brennan camroden associates, inc.

Size: px
Start display at page:

Download "fan pressure testing for LarGe, complex buildings terry brennan camroden associates, inc."

Transcription

1 fan pressure testing for LarGe, complex buildings terry brennan camroden associates, inc East Carter Road, Westmoreland, NY Phone: Fax: S y m p o S i u m o n B u i l d i n g E n v E l o p E T E c h n o l o g y o c T o B E r B r E n n a n 3 5

2 abstract This paper will present the important lessons learned based on over 30 years of testing the airtightness of buildings. Common problems encountered while setting up and conducting tests and their solutions will be presented. Details and locations that are difficult to air seal and those that are easy to air seal will be presented. Airtightness test targets and methods needed to achieve them will be covered. Buildings tested include commercial and institutional buildings, laboratories, hospitals, museums, pools, schools, warehouses, and industrial applications. They range in size from banana-ripening rooms to 13-story towers to 800,000-sq.-ft. warehouses. The results of the ASHRAE 1478 (Measuring Airtightness of Mid- and High-Rise Nonresidential Buildings) research project are included. SPeaKer terry brennan camroden associates, inc. TERRy BRENNAN is a building scientist and educator and has studied buildings since the 1970s. He has provided research, investigation of building-related problems, training, curriculum development, and program support for the EPA, building owners and managers, architects, engineers, and several state health departments. He is the technical lead for the ASHRAE 1478, Measuring Airtightness of Mid- and High-Rise Nonresidential Buildings research project. Brennan chairs the Air Barrier Association of America s Whole Building Airtightness Testing Committee. This committee revised the Army Corps of Engineers whole-building test protocol in 2012 and is currently an ASTM Task Group (Wk35913) on New Standard Whole-Building Enclosure Airtightness Compliance. He is a member of ASTM E06 and ASHRAE 62.2, the committee on ventilation for low-rise residential buildings. Brennan has served as a consultant to the National Academies of Science Committee on Dampness and Health in Buildings. He is the primary author of the forthcoming EPA Moisture Control Guide. 3 6 B r E n n a n S y m p o S i u m o n B u i l d i n g E n v E l o p E T E c h n o l o g y o c T o B E r

3 fan pressure testing for LarGe, complex buildings INTRODUCTION Fan pressure tests are conducted to test air barrier systems on whole buildings, apartments or suites of rooms, isolated special-use areas within buildings, and air-handling equipment (e.g., ducts, air handlers, and hot-air solar collectors). This paper focuses on testing entire building enclosures or apartments in multifamily buildings. Fan pressurization tests may be conducted for one or more of the following reasons: To measure the airtightness of an enclosure to determine whether or not it meets an airtightness target To help find air leakage sites using infrared scanning, theatrical fog, or chemical smoke tracers As part of a quality assurance (QA) inspection and testing program for air barrier installation To assess the effectiveness of retrofit air-sealing efforts, either quantitatively or qualitatively To measure air leakage rates or leakage areas for use in building energy-use calculations To test the ability of installed air barrier materials to resist specific pressure loads (typically assemblies are tested at pressure differences of 75 and 298 Pascals, and whole buildings are tested at 50 or 75 Pascals). Whole-building fan pressurization tests have been conducted to measure the airtightness of single-family residential buildings in the U.S. and Canada since the 1970s. They have been extensively used in weatherization programs and as part of QA for high-performance homebuilding programs (e.g., EnergyStar, LEED for Homes, and Passive House). Efforts to extend the tests to larger and more complex buildings began in the 1980s. In the past ten years, North American manufacturers of test equipment have developed methods for networking test fans and electronic micro-manometers so that test data can be collected and analyzed by computer software programs. This has made it practical to test larger buildings than ever before. The ASHRAE project, 1478-RP, Measuring Airtightness of Mid- and High-Rise Non- Residential Buildings, developed a test protocol specifically for testing large buildings and conducted tests on 16 buildings built since 2000 (Anis 2014). The buildings ranged between four and 14 stories and between 54,000 and 362,000 sq. ft. in floor area. The tested buildings were located in climate zones 2 through 7 of the International Energy Conservation Code (IECC) Climate Zone Map. Tests were completed between 2011 and Over the last 30 years, manufacturers of building products have developed materials and systems that provide continuous air barrier systems in commercial and institutional buildings. During this time period, the use of air barrier systems in commercial and institutional buildings has become common practice. By limiting airflow through the thermal enclosure, continuous air barriers perform two crucial functions in high-performance enclosures: Limiting heat transfer by accidental air leakage through the enclosure Limiting the transport of water vapor by accidental air leakage (e.g., preventing condensation by keeping warm, humid outdoor air away from air-conditioned, chilled interior surfaces; and keeping warm, humid indoor air from reaching exterior enclosure materials that are chilled by cold outdoor air) In addition to blocking airflow, many air barrier materials act as capillary breaks and serve dual duty as both air barrier and rainwater control. Even in airtight assemblies, condensation may occur if the vapor barrier is located in the wrong spot relative to more permeable insulating materials. Some air barrier materials accidentally or intentionally behave as nearly perfect water vapor barriers, while others are more vaporopen. Condensation control must be evaluated for whole assemblies, because condensation is a function of vapor migration and the surface temperature of materials. Continuous air barriers are also required for buildings or rooms that are intended to shelter vulnerable occupants, materials, equipment, or processes from damaging environmental agents (e.g., bone marrow transplant wards; art, artifact, or musical instrument storage or display; computers and telecommunications equipment; lithium batteries; solid-state chip manufacturing). Air barriers are also used to prevent damaging, annoying, or valuable environmental agents from escaping from contained sources (e.g., biohazard level 3 or 4 containment, paint booths, fruit-ripening rooms). Continuous air barriers are required by code in a dozen U.S. states and Canada. The ICC family of model codes requires continuous air barriers. One path to demonstrate compliance is for the results of a fan pressurization test to be equal to or less than an airtightness target. The Army Corps of Engineers (ACE), General Services Agency (GSA), EnergyStar multifamily high-rises, Passive House U.S. multifamily projects, and projects using the Unified Facilities Guide Specifications are required to have continuous air barriers and to pass a whole-building fan pressurization test. The ACE requirements for air barriers and whole-building testing have resulted in a large increase in the use of air barriers and fan pressure testing in commercial and institutional buildings. TEST METHODS A fan pressure test is conducted on a building enclosure by using fans to exhaust air from or blow air into a test enclosure. At its simplest, a qualitative test can be used to find air leaks in buildings. Air leaks can be found by simply feeling the breeze on the skin. Infrared scanning, theatrical fog, and smoke tracers can be used to make it easier or quicker to find air leaks in build- S y m p o S i u m o n B u i l d i n g E n v E l o p E T E c h n o l o g y o c T o B E r B r E n n a n 3 7

4 Figure 1 A schematic illustration of a fan pressurization test. ings. These methods are described in ASTM E1186, Standard Practices for Air Leakage Site Detection in Building Envelopes and Air Barrier Systems. The fan pressure test becomes a quantitative test by measuring: The indoor/outdoor pressure induced across a building enclosure The exhaust or supply airflow required to induce the measured pressure difference as illustrated in Figure 1 Air is exhausted from the enclosure by a fan that is sealed into the wall. This lowers the air pressure inside the box relative to the outside of the box, drawing air in through the air leaks in the enclosure (for simplicity, represented in Figure 1 as a single hole). The mass of air drawn in is equal to the mass of air exhausted through the fan. The airflow and the resulting change in indoor/outdoor pressure difference are measured. The tighter the box, the smaller the airflow required to induce a particular test pressure difference. Airflow and the resulting pressure difference are measures of enclosure airtightness. Applying this simple concept to buildings, we run into a few practical problems. Buildings are not simple, closed boxes with no interior airflow restrictions. They have open windows and doors. They are filled with partitions and floors that restrict airflow from one place to another. Fanpowered exhaust and outdoor air fans in an operating building induce pressure differences between inside and outside the building. Indoor/outdoor pressure differences are affected by wind and stack effect. To conduct a fan pressurization test, a building must be prepared so that it resembles the condition in Figure 1 as closely as possible. All the exterior windows and doors must be closed (except those containing test fans). Interior doors must be opened to allow air to move freely throughout the building. Exhaust and outdoor air fans must be shut off and sealed, at least by closing dampers. After a building is set up for a test, the effects of wind and stack effect pressures must be subtracted out. This is done by measuring a baseline pressure difference with the test fans turned off and sealed so that wind and stack effects are the only reason there would be an indoor/outdoor pressure difference. It is not the absolute indoor/outdoor pressure difference that is important, it is the amount the indoor/ outdoor pressure difference changes when a measured airflow is exhausted from or supplied to the enclosure. If the mass of air inside the box is an open, single zone, then the change in pressure difference is the same at all points on the enclosure. For the purposes of this paper, the pressure difference induced between inside and outside by the operation of the test fan will be called the enclosure pressure. There are two methods commonly used Figure 2 Repeated-reference pressure test. A baseline is collected, the test fans are turned on, the reference pressure is induced, and the airflow required is measured. Although not shown in this graph, the measured flow for the test was 15,200 cubic feet per minute (cfm) (corrected for temperature and altitude). 3 8 B r E n n a n S y m p o S i u m o n B u i l d i n g E n v E l o p E T E c h n o l o g y o c T o B E r

5 to make a quantitative measurement of building air leakage. The simplest is the repeated single-reference pressure method. In this method, prepare the building as described above, measure a baseline pressure, turn on test fans until a reference enclosure pressure is reached, and measure the airflow required to induce the reference enclosure pressure. Repeat this procedure at least five times. Historically, reference test pressures of 50 Pascals and 75 Pascals have been used for this test. This method is described in ASTM E1827, Standard Test Methods for Determining Airtightness of Buildings Using an Orifice Blower Door, and Chapter 8 of the Residential Energy Services Network s (RESNET s) National Mortgage and Housing Home Energy Rating System (HERS) Standards. Figure 2 shows the results of a repeated single-reference pressure test. This test illustrates the important principle that it is the change in the indoor/ outdoor pressure difference induced by the operation of the test fans that is important. The reference enclosure pressure for the test is 75 Pascals. The baseline averages around -8 Pascals. Baseline enclosure pressures measured at grade are frequently negative due to stack and wind effects. This is the case for low-rise and taller buildings during warm weather in air-conditioned buildings. Test fans provide supply airflow to raise the enclosure pressure 75 Pascals (from -8 to +67 Pascals). The reported result is 15,200 cfm at 75 Pascals. An airflow and an induced enclosure pressure are the fundamental result. Repeating the test provides the data needed to calculate uncertainty in the measurements. (Note: Wind effects during this test seem to contribute plus or minus 2 or 3 Pascal fluctuations to the baseline and enclosure pressure measurements.) If airtightness data at indoor/outdoor enclosure pressures that are typical of ordinary operation are desired, a multipoint regression method is used to collect and analyze the data. Typical operational enclosure pressures are in the range of 4 to 10 Pascals. At these pressure differences, wind and stack effects become a large fraction of the test signal. For that reason, data are collected over a large range of enclosure pressures, and linear regression analysis is applied to transformed nonlinear data. ASTM E779, Standard Test Method for Determining Air Leakage Rate by Fan Figure 3 Multipoint regression method: Regression analysis on transformed nonlinear data fit to Equation 1. Air leakage at enclosure pressure less than 10 Pascals can be extrapolated using this method. Pressurization, details this method. Figure 3 illustrates data from this kind of test. The relationship between the test airflow and the enclosure pressure or a range of enclosure pressures is not linear. It very nearly follows a power law, as shown by Equation 1. Equation 1 Q fan = C( P enclosure ) n Where: Q fan = the measured airflow through the test fan (or fans in the case of large buildings) P enclosure = the change in the indooroutdoor pressure difference induced by operation of the test fans (in this paper called the enclosure pressure) C = a flow coefficient that is a characteristic of the size and shape of the air leakage sites n = is the flow exponent with theoretical limits between 0.5 and 1.0 Analysis includes calculation of the flow coefficient C, exponent n, and a 95% confidence interval. These values allow calculation of flows at the lower reference enclosure pressure of 4 Pascals and 10 Pascals, as well as the higher ones of 50 and 75 Pascals. The following test methods and protocols are the most frequently used in the U.S.: ASTM E779-10, Standard Test Method for Determining Air Leakage Rate by Fan Pressurization ASTM E , Standard Test Methods for Determining Airtightness of Buildings Using an Orifice Blower Door RESNET Chapter 8 of the National Mortgage and Housing HERS Standards U.S. ACE Air Leakage Test Protocol for Measuring Air Leakage in Buildings The Air Barrier Association of America s (ABAA s) Whole-Building Fan Pressure Test Committee Standard Method for Building Enclosure Airtightness Compliance Testing S y m p o S i u m o n B u i l d i n g E n v E l o p E T E c h n o l o g y o c T o B E r B r E n n a n 3 9

6 Figure 4 Test results normalized to enclosure surface area for the 16 mid- to high-rise buildings tested in ASHRAE project The two ASTM standards do not include many of the issues that must be addressed in order to test large, complex buildings. They don t include acceptance criteria for determining whether or not a building meets an airtightness specification. All of the standards and protocols listed above reference one or both of the ASTM methods as the basis for collecting and analyzing data, including calculation of uncertainty. The techniques used to calculate uncertainty are different, depending on how the data are collected and analyzed. Calculated uncertainty is used to determine whether or not the data quality objectives have been met. Data quality objectives depend on the purpose of the test. For example, if the test is being conducted to determine whether or not an enclosure meets an airtightness specification, and the test result is close to the target, a small uncertainty interval is needed. If the test is part of a survey in which the data will be placed in a histogram, a larger uncertainty interval may be acceptable. The RESNET standard allows both repeated single-point and multipoint regression methods and includes acceptance criteria for determining whether or not a building meets airtightness specifications. It does not address preparation of larger, more complex buildings. The ACE test protocol allows only multipoint regression, includes acceptance criteria, and addresses many of the preparation issues found in large, complex buildings. The ABAA Whole Building Test Committee has drafted and balloted a new standard test method, ABAA Whole- Building Fan Pressure Test Committee s Standard Method for Building Enclosure Airtightness Compliance Testing. It allows multipoint regression and repeated singleand two-point test methods, includes acceptance criteria, and addresses the issues found in large, complex buildings, including many not addressed by other standards. It is useful to be able to compare test results between buildings. In order to do so, a variety of metrics have been used over the past 30 years. The most commonly used metrics for large buildings are cfm at an enclosure pressure of 75 Pascals divided by the total surface area of the test enclosure (cfm75/ft 2 ). The surface area of the enclosure includes the roof, walls, and foundation floor. Residential programs often normalize by the building volume, resulting in air changes per hour at 50 Pascals (ACH50). ACH50 is the cfm at an enclosure pressure of 50 Pascals times 60 min./hr. divided by the volume of the building. Neither of these metrics is perfect for comparing buildings. Normalizing to the surface area makes low-rise buildings with large footprints appear more airtight than taller, more complex buildings, because the large roofing membranes and concrete floor slabs dominate. ACH50 runs into problems comparing buildings over a wide range of sizes because as size increases, surface areas and volumes change at different rates. Figure 4 shows the results for the tests conducted during the ASHRAE 1478 research project. In this project, the buildings were tested in pressurization and depressurization mode. The HVAC penetrations had fans off, dampers in the closed position, and HVAC penetrations temporarily sealed. The results are normalized by the enclosure surface area (top, bottom, and sides included). Figure 4 shows the results for a pressurization test, a depressurization test, and the average of the two for each building. The results ranged from a low of 0.06 cfm75/ft 2 to a high of 0.74 cfm75/ft 2. The average is 0.29 and the median is 0.24 cfm75/ft 2. Half of the buildings in the study met the ACE s target of 0.25 cfm75/ft 2, and 75% met the GSA target of 0.40 cfm75/ft 2. All of the buildings in the study were volunteered. All of them were owner-occupied or institutional buildings. Six of the buildings had air barriers specifically included in the drawings and specifications or had an air barrier consultant as part of the design or QA team. It is suspected that the study sample is biased toward tighter buildings. Here is an abbreviated list of codes and building programs that include wholebuilding fan pressure tests and their compliance targets: 2012 IECC Continuous air barriers; 0.40 cfm75/ft 2 enclosure is one path to compliance. GSA Continuous air barriers and the enclosure is less than 0.40 cfm75/ft 2 enclosure (all six sides) P100. ACE Continuous air barriers, and the enclosure is less than 0.25 cfm75/ft 2 enclosure (some ACE projects use 0.15 cfm75/ft 2 ). Passive House requires continuous air barriers, and the enclosure is less than 0.6 ACH50 (around cfm75/ft 2 enclosure [all six sides]). British code for museums and archi 4 0 B r E n n a n S y m p o S i u m o n B u i l d i n g E n v E l o p E T E c h n o l o g y o c T o B E r

7 val storage is less than 0.08 cfm75/ft 2 of enclosure. The results for the 1478 project include: 12 buildings that meet the GSA target 8 buildings that meet the ACE target 5 buildings in the range to meet the Passive House target 1 building that meets the British code for museums and archival storage The following data are needed to successfully conduct tests in accordance with E779 or E1827 and normalize the results to the building surface area: Airflow through test fans Inside/outside pressure difference during baseline condition Inside/outside pressure difference induced by test fans Temperature of air passing through the test fans Altitude of the building Test enclosure surface area or building volume Interior pressure differences to monitor single-zone condition TEST EQUIPMENT There are three North American manufacturers of test equipment for conducting whole-building fan pressurization tests. The equipment includes variable-speed test fans with integrated flow-measuring sensors, adjustable frames and panels to seal test fans into door or window openings, and electronic micro-manometers for measuring air pressure differences. Two of the manufacturers have developed a combination of computer software and networking hardware so data can be collected from multiple micro-manometers measuring test fan air flows and enclosure pressures. The tests can be controlled from a computer, and the data are automatically analyzed in accordance with test standards. One of the manufacturers produces a large, trailermounted test fan capable of providing test flows equal to that of several smaller test fans. In the author s experience, networking smaller fans provides the simplest solution for buildings with many interior partitions and less than 100,000-cfm test flows. In larger, more open buildings, the trailermounted fans have the advantage of a single setup location. It is sometimes possible to test a building using the ventilation fans. A depressurization test can be conducted using the exhaust fans in the building (with all outdoor air intakes closed or sealed). A pressurization test can be conducted using the outdoor air ventilation flows (with all exhaust outlets closed or sealed). The major barrier to this method is making accurate measurements of airflow through the ventilation systems. In the author s experience, this process takes far more time than using manufactured test equipment. This could be overcome in new buildings by designing the ventilation systems to conduct a fan pressure test. SPECIFYING A FAN PRESSURE TEST Whole-building fan pressure tests are being specified for new buildings with increasing frequency. Many of the specifications crossing the author s desk lack crucial information or include requirements that are impractical or inconsistent with other requirements. For example, the specifications may not include the surface area of the test enclosure or even clearly identify the bounding walls, floors, and ceilings of the test enclosure. Some specifications prohibit testing on rainy days or require the testing agency to shovel snow off the roof and two feet away from the ground floor. Some require the testing agency to verify that all air barriers have been installed correctly. At the time of testing, most air barriers are covered by interior or exterior finishes. Here is some guidance for specifying an airtightness test: Make it clear who hires the testing agency. Do not repeat or contradict items that are adequately covered in the referenced test methods. Include a rationale for any specification that contradicts requirements in the referenced test method. Provide the purpose of the test. Require qualifications of the testing agency. List conditions that must be met before the building can be tested. List contractor and owner responsibilities. Designate test methods (E779, E1827, ACE protocol, RESNET, ABAA). State the airtightness target (cfm75/ ft 2 enclosure or ACH50). Name test enclosure boundaries. Test enclosure surface area or building volume. Designate treatment of HVAC penetrations, trash chutes, gas meter rooms, mechanical rooms, coiling doors and dock levelers. List acceptance criteria (how the test result will be interpreted). Describe what happens if the building fails. Include reporting requirements. CONDUCTING A FAN PRESSURE TEST Planning The basics of testing covered in the introduction are the same for all buildings. The logistics, setup, and testing for large, complex buildings include many more issues than when testing single-family residences. There are more people involved: owners, building management, building facilities, contracted HVAC management and maintenance, and security. The building may have multiple occupants. Some areas of the building may be inaccessible for safety or security reasons (e.g., they re not going to let you into IRS offices, banks, law offices, or the executive suite). In the case of new construction, the owner is usually the general contractor, special health and safety issues are in play, and the HVAC systems belong to the HVAC subcontractors. The HVAC systems are more numerous and more complex. Everything is bigger more stairs to climb, more corridors to walk, more windows and doors to close and latch or block open, as well as more test equipment to move, set up, and calibrate. Here s a list of tasks that must be accomplished to plan a test: Determine whether or not it is a new, unoccupied building or an occupied building. It is much easier to test an unoccupied building than an occupied building. Access is easier, and there are fewer nonparticipants who may accidentally interfere with data collection. Identify parties. Parties involved must include someone authorized to approve conducting of the test; someone who can provide access to all rooms, mechanical rooms, and safe access to all locations where HVAC-related penetrations have to be temporarily sealed; and someone S y m p o S i u m o n B u i l d i n g E n v E l o p E T E c h n o l o g y o c T o B E r B r E n n a n 4 1

8 authorized to place the HVAC equip- temporarily masked. If the inten- In practice, making the building a sealed ment into the proper status so that a tion is to test the building in a more box means closing all the doors, windows, test can be conducted and to restore operational condition, then HVAC hatches, and HVAC-related penetrations the equipment to operational status penetrations will have associated in the enclosure. Decisions must be made after the test. In some cases, secu fans turned off and dampers closed, about how to handle situations such as rity personnel, an air sealing crew, but they will not be temporarily mechanical rooms with doors to both the or health and safety personnel will air-sealed. The ABAA test standard interior and exterior. Should both doors be be involved. contains a relatively complete list of closed? Should the exterior door be open Select date. Select a date when treating HVAC equipment and relat and the interior door closed? Or should the there will be the fewest people in the ed penetrations; the list is included interior door be open and the exterior door building. In new buildings, this is in Table 1. Table 1 includes treat- be closed? often easier than in occupied build ment for coiling overhead doors, Creating an open single zone is often ings. In occupied buildings, testing trash disposal systems, and loading achieved by simply opening all the interior may be most practical during eve- dock levelers, as well as HVAC pen- doors. Some situations may create barriers nings, weekends, or holidays. etrations. to single-zone conditions: Identify test enclosure boundar- Calculate how much test air is Rooms that cannot be opened for ies. Test boundaries must be identi needed. How much test capacity is security reasons. Often these rooms fied and agreed to before testing. needed is fairly simple to calculate are so well-connected by ductwork Decisions must be made about how for buildings that have a test specifi that during testing they are within mechanical rooms, basements, crawl cation that includes an airtightness 10% of the enclosure pressure and spaces, attics, and vestibules will be target e.g., area enclosure (ft 2 ) x meet single-zone conditions. treated. The surface area of the test 0.25 cfm/ft 2 at 75 Pascals for ACE Portions of the building that are enclosure should be included in test projects. For other projects, the air- within the test enclosure but isospecifications. If the surface area is tightness target per square foot of lated from the rest of the building not provided, conduct and document enclosure 0.25 cfm/ft 2 at 75 Pascals by firewalls with no access doors the calculation clearly. must be replaced by the specified penetrating the firewall. These Identify adequate power for test target. If it is an existing building have doors opening to the outside equipment. Most test fans use with no specified airtightness tar- and can be tested simultaneously by electric motors. Each fan typically get, then the airtightness must be maintaining zero pressure difference requires a separate 115-volt, 15-amp guessed. For ordinary construction, between them and the main part circuit cfm75/ft 2 is a good rule of of the building using separate test Identify areas that are not clear- thumb. If the building is experienc equipment. (See Figures 5 and 6.) ly inside or outside the test. ing problems associated with leaky Ceiling or floor cavities with large Mechanical rooms, attics, and crawl enclosures, a good rule of thumb air leaks to the outside. spaces are examples of spaces that is 0.6 cfm75/ft 2. Bear in mind that may or may not be inside the test some problem buildings the author The following list includes items that area. Generally, if they are vented has tested are greater than 1.5 cause problems for enclosure measurements: to the outdoors through permanent, cfm75/ft 2. If it is anticipated that the Wind pressures, especially fluctuatnondampered openings, they are building is relatively airtight, bring ing wind pressure considered outside the test enclo enough fans to meet 0.25 cfm75/ft 2. Water in tubing that connects outdoorsure. If the air barrier systems and insulation layers enclose these spac- PREPARING THE BUILDING enclosure pressure taps to manometers es, they are considered inside the For most tests, the intention is to pre Direct sunlight on long lengths of space. pare the test building so that it resembles tubes Identify HVAC equipment that as nearly as possible the simple box in Small air leaks in tubing greater must be turned off, dampers that Figure 1. than 100 feet in length must be closed, and penetrations The box is sealed except where test Someone stepping on a tube that must be temporarily sealed. fans are inserted into door or win- How the HVAC penetrations are dow openings. Although E779 and E1827 recommend treated depends on the test s pur The interior is wide open, creating a wind speeds less than 4 mph, the introducpose. If the goal is to test the quality single-zone condition as far as enclo tion of computerized data acquisition and of design and installation of air bar- sure pressures are concerned. analysis test equipment has made it posrier systems in the building enclo Manometers with pressure taps sible to collect data simultaneously from all sure, then all HVAC-related open- measure representative enclosure enclosure pressure and fan sensors averings typically have their associated pressures. aging over longer time periods and across fans turned off, their dampers in Test fans are placed to provide good multiple façades, providing high-quality the closed position, and outdoor air enclosure pressure distribution. data over a much wider range of wind conand exhaust louvers and grilles are ditions. The ACE test protocol has no upper 4 2 B r E n n a n S y m p o S i u m o n B u i l d i n g E n v E l o p E T E c h n o l o g y o c T o B E r

9 limit on wind speed. Place outdoor enclosure pressure taps away from exterior corners, as close to the intersection of the exterior wall and grade as possible. Protect the open end of the tube from water (e.g., tape tubing to well with open end pointing down, and use an open vessel that shelters the tubing end from rain). Use tubing lengths less than 100 feet when possible. Check tubing for air leaks as part of quality assurance, and place tubing where it is hard for someone to step on it. In a wide-open building, the test fans can be placed anywhere there are doors to the exterior. (Note: On windy days, do not set up a test fan on the windward side of the building.) If interior walls and floors divide the building into spaces connected by a single door or a small number of doors, then the Figure 5 An illustration of testing a building that is divided in two by a test fans must be distributed among these firewall with no openings through it. Test fans are set up in each portion of the somewhat-isolated areas. Some examples: building. The fans in the red-outlined portion of the building are controlled to A single entry door into an area induce the correct enclosure pressures on the building while the test fans in the that is closed off from the rest of green-outlined portion of the building are controlled to maintain zero pressure the building except for a single difference between the two. This provides results for each section separately and door. Imagine three fans set up in for the overall building. the entry door exhausting 15,000 cfm from the area induces an enclosure pressure of -75 Pascals relative to the outside. Some of the 15,000 cfm will come through the exterior walls of the area from outside, but a lot will come through the connecting door from the rest of the building. If 13,000 cfm of the air comes through the connecting door, and 2,000 cfm comes from outdoors and leaks through the demising walls, an 18-Pascal pressure drop will be induced across the connecting door. The portion of the building outside the area with the fans will be at -58 Pascals relative to the outside. In this case, single-zone conditions will not be met. A six-story building in which the major air leakage site is the roof/wall connection on the sixth floor. Two stairwells with single doors to each floor connect the top five floors to the ground floor. Test fans can only be installed on the ground floor (short of removing a panel of glass from a curtain wall on upper floors). If 30% of the test air comes through the air leak on the sixth floor, when the rest of the building is at an enclosure pressure of 75 Pascals relative to the outside, the sixth floor may have a considerably lower enclosure pressure. Single-zone conditions are not maintained. Creating a single-zone test condition in large, complex buildings is something that cannot be taken for granted. For that reason, the ACE and ABAA test standards require that pressure differences between the area where the test fans are located, and portions of the building separated by walls or floor with few interior door openings in them must be measured. This allows singlezone conditions to be verified. For these standards, single-zone conditions mean that the pressure difference between interior zones must be less than 10% of the enclosure pressure. (See Figures 5 and 6.) Figure 6 Two separate zones tested as one building. The first zone is the ground floor and is shaded in purple. The second zone consists of the unshaded floors the basement and the second through the sixth floor. There are no intentional openings between the two zones. A test fan is located in each zone, and zero pressure difference is maintained between zones during the test. S y m p o S i u m o n B u i l d i n g E n v E l o p E T E c h n o l o g y o c T o B E r B r E n n a n 4 3

10 MORE ON HVAC PENETRATIONS Preparation for the HVAC-related openings in the building should be in accordance with the test specification. The ABAA test standard provides guidance for two default test purposes: Air barrier systems enclosure test (HVAC-related openings excluded) Operational enclosure test (air barrier systems and HVAC-related openings included) In the first, the purpose of the test is to determine whether the installed air barrier systems in the walls, ceilings, roofs, and foundation that form the thermal enclosure have met a specified airtightness target. The second test purpose is used if the intention is to test the overall airtightness of the buildings in a way that is more representative of air leakage during more ordinary Intentional Openings Air barrier systems Operational enclosure enclosure test (HVAC-related test (air barrier systems openings excluded) and HVAC-related openings included) Doors, hatches, and operable windows inside the test enclosure Open Open Fire dampers Remain as found Remain as found Windows, doors, skylights, and hatches in the bounding enclosure Closed and latched Closed and latched Windows, doors, hatches, and operable windows in ancillary spaces Treat in accordance Treat in accordance as identified in section with with Dryer doors and air-handler access panels Closed and latched Closed and latched Vented combustion appliance Off, unable to fire Off, unable to fire Pilot light As found As found Chimney or outlet for vented combustion device in a separate As found As found mechanical room B-vent or other insulated chimney serving a vented combustion Sealed* As found appliance located within the test enclosure Solid fuel appliances (fireplaces, wood-burning stoves, pellet stoves) No fires; dampers closed; No fires; dampers closed chimney sealed* Exhaust, outdoor air, make-up air fans, air handlers that serve Off Off areas inside and outside the test enclosure Clothes dryers Off Off Air intake inlet with motorized dampers Dampers closed and sealed* Dampers closed Air intake inlet with gravity dampers Sealed* As found Air intake inlet with no dampers Sealed* Open unless fan(s) serving inlet is operated >8000 hrs./year, then sealed* Exhaust or relief air outlet with motorized dampers Dampers closed and sealed* Dampers closed Exhaust or relief air outlet with gravity dampers Sealed* As found Exhaust or relief air outlet with no damper Sealed* Open unless fan serving outlet is operated >8,000 hours/year, then sealed* Active or passive smoke control systems air reliefs and intakes Sealed* As found Intended powered or nonpowered openings for vented Sealed* As found shafts/stairwells Waste or linen handling systems and equipment Sealed* at rooftop chute Rooftop chute vent open, vent opening. chute intake doors closed, chute intake room and chute discharge room doors closed and latched, fire dampers left as found Clothes dryer outlets Sealed* As found; sealed* if dryers are not yet installed Exhaust, outdoor air, or make-up air fan that runs >8,000 hours per yr. Sealed* Sealed* Ductwork that serves areas inside and outside the test enclosure Sealed* at supply and return Sealed* at supply and return Floor drains and plumbing Traps filled Traps filled *Sealed means that an opening has been temporarily masked airtight (e.g., covered with self-adhering plastic film, taped polyethylene film, or rigid board stock). See Annex A. Also see article Table 1 Default conditions for building preparation. 4 4 Br E n n a n S y m p o S i u m o n B u i l d i n g E n v E l o p E T E c h n o l o g y o c T o B E r

11 operating conditions. Table 1 from the ABAA standard is shown herein. It includes the HVAC-related penetrations, the operational status of certain HVAC equipment, treatment of doors and windows in the test enclosure, treatment of doors and hatches inside the test enclosure, treatment of some specialized spaces that are isolated from the test enclosure (e.g., trash conveyance and compaction systems), and HVAC systems that serve the test enclosure and zones outside the test enclosure. The ASHRAE 1478 project used a simple test procedure to estimate the air leakage through HVAC-related penetrations. The HVAC penetrations were prepared by turning off the exhaust and Figure 7 The triangles are test results with HVAC penetrations sealed, and the dots are with make-up air fans, closing all the HVAC penetrations unsealed. In some buildings, it makes a significant difference; while in the outdoor air and exhaust others, it makes almost no difference. air dampers, and temporarily sealing all the HVAC penetrations. The building s enclosure pressure was then held at 75 Pascals, and a baseline with HVAC penetrations sealed was collected. Next the HVAC penetrations were unsealed (but motorized dampers remained closed; gravity dampers may have been drawn closed or blown open), and undampered openings (e.g., kitchen range exhaust) become open holes. The results of these simplified measurements are shown in Figure 7. THINGS THAT CAN GO WRONG DURING A TEST This is an abbreviated list of things that can go wrong during a test. (Note: At this point, the author fervently hopes he has listed every conceivable error. However, this list does not include the really dumb stuff, like forgetting the fan controllers, going to the wrong building, or conducting a test with a window on the sixth floor open.) An entry door, a gravity damper, or masking on an HVAC-related opening may blow open during a pressurization test. Catch this by noticing that the test result is changing. Someone may open a door or stand Figure 8 Depressurization and pressurization curves for a building with a large gravity damper blowing open during the pressurization test. S y m p o S i u m o n B u i l d i n g E n v E l o p E T E c h n o l o g y o c T o B E r B r E n n a n 4 5

12 on a tube during the test. This is obvious if continuous monitoring is taking place on-screen or if a data point is automatically rejected by internal software quality assurance. An interior door may be blown closed, changing the test boundaries partway through a test (noted by change in the sound of the fans flow or enclosure pressure data). Heavy wind or rain can make a test impractical (pretty obvious). The building depicted in Figure 8 was tested in depressurization first. The data have a small 95% confidence interval and fit the power curve well. The lowest three pressurization data points match the depressurization data points well. However, each succeeding pressurization data point increasingly deviates from the depressurization result. The building is getting progressively more leaky. This is typical of what it looks like when an entry door is unlatched and the pressure in the building is preventing it from closing completely. As the test pressure increases, the door opens further but not all the way because the door closer provides resistance. A large gravity damper and self-adhering duct mask blowing off and HVAC louver also appear the same way. INTERPRETING RESULTS How test results are interpreted depends on the purpose of the test. If one is testing to determine whether or not a building meets an airtightness specification, a test can return one of three results: It clearly passes. It clearly fails. I can t tell. It is, of course, the I can t tell result that causes problems. The situation where the smallest confidence interval is the best is when the test result is within the uncertainty of the measurement. No matter how small, acceptance criteria must be used to determine whether it is a pass or a fail. ACE and ABAA test protocol specify: Calculate 95% confidence intervals (in accordance with test method) Pass: If test result 0.25 cfm75/ ft 2 and 95%CI 8%: If test result 0.25 cfm75/ft 2 and 95%CI > 8%: Pass: If test result + 95%CI 0.25 cfm75/ft 2 Fail: If test result + 95% CI > 0.25 cfm75/ft 2 Fail: If test result >0.25 cfm75/ ft 2 ABAA allows failing a building if the specified airflow produces less than 75% of the reference test pressure. None of the standards include acceptance criteria if the test is being done to compare to other buildings or to compare a post-airtightening test to a pre-airtightening test. Criteria would need to be developed to meet the needs of each project. REPORT A test report should include, at minimum, the following items: Date Weather conditions Building testing agency Building description Test target Test results Location of test equipment Identification of test enclosure boundaries Test configuration of each intentional opening in the building enclosure Test environmental conditions Any departures from test standard or specifications Measured test results in tabular form Conclusions and recommendations FINDING THE BIG AIR LEAKS There are a number of methods used to find air leaks in buildings. Several of these methods are described in ASTM E1186, Standard Practices for Air Leakage Site Detection in Building Envelopes and Air Barrier Systems. Many of them depend on operating a building under negative or positive pressure. As such, after a wholebuilding pressure test has been conducted, it is a good time to seek the leaks. The methods include: Listen Some air leaks whistle, buzz, flap, or whoosh when the building is pressurized or depressurized. Use your skin to feel for air leaks when depressurizing. Stand in stairwell doorways at each floor: The floors with the greatest breeze have the largest leaks. Stand at the ends of corridors where wings join other parts of the building. Use chemical smoke bottles or theatrical fog to track air flows. Use infrared scanners when there is a large enough indoor/outdoor temperature difference to identify air leaks. Using these techniques, the author has found that the largest air leaks in large buildings occur where enclosure systems meet but don t connect. This is the order of most commonly encountered large leaks: Where roofs meet walls at the top of the building Where lower roofs meet walls that rise above them Where there are exterior soffits beneath lower walls, canopies, and plazas Where walls meet foundations Where utility shafts connect two or more of the above items CONCLUSIONS Using modern test equipment, it has become practical to conduct fan pressurization tests on large, complex buildings. A final whole-building airtightness test will: Document compliance or failure to comply with an airtightness specification Provide induced pressure difference to aid in finding remaining air leaks (E1186) Provide motivation to effectively install air barrier assemblies and identify air leakage sites not detailed in drawings and specifications during construction Not otherwise make buildings more airtight REFERENCES Wagdy Anis, 2014, ASHRAE 1478-RP, Measuring Airtightness of Mid- and High-Rise Nonresidential Buildings Research Results and Conclusions, WJE, B r E n n a n S y m p o S i u m o n B u i l d i n g E n v E l o p E T E c h n o l o g y o c T o B E r

2001 National Workshop on State Building Energy Codes July th, 2001 Burlington, Vermont

2001 National Workshop on State Building Energy Codes July th, 2001 Burlington, Vermont 2001 National Workshop on State Building Energy Codes July 16-19 th, 2001 Burlington, Vermont A Systems Engineering Approach to the Design of Energy and Resource Efficient Homes Presented By: Mark LaLiberte

More information

Date Rater Verified. Rater Verified. Slab / Pre-Drywall / Thermal Inspection

Date Rater Verified. Rater Verified. Slab / Pre-Drywall / Thermal Inspection Slab on Grade & Basements: A capillary break is installed on top of all footings Slab / Pre-Drywall / Thermal Inspection A minimum of 4" of clean or washed gravel (0.5" diameter or greater) is placed over

More information

NEW HOMES PROGRAM 2017 PROGRAM GUIDE

NEW HOMES PROGRAM 2017 PROGRAM GUIDE NEW HOMES PROGRAM 2017 PROGRAM GUIDE Focus on Energy, Wisconsin utilities statewide program for energy efficiency and renewable energy, helps eligible residents and businesses save energy and money while

More information

Big Air- Building Air Barrier Testing

Big Air- Building Air Barrier Testing Big Air- Building Air Barrier Testing Torrance Kramer Accurate-Airtight Exteriors Air Barrier Association of America (ABAA) is a Registered Provider with The American Institute of Architects Continuing

More information

Chapter 2: Foundation

Chapter 2: Foundation Chapter 2: Foundation Crawlspace [V502.1.2] [V502.1.2] [V502.1.3] Vents. Vents in the crawlspace help keep floor insulation and floor framing dry. Crawlspace vents also reduce the potential for radon buildup

More information

ASHRAE 62.2: What s New in 2016

ASHRAE 62.2: What s New in 2016 ASHRAE 62.2: What s New in 2016 Rick Karg 2016 Residential Energy Dynamics, LLC What We Will Talk About Overview of mechanics of 62.2-2016. Logic behind the Standard. Sizing local ventilation (exhaust-only).

More information

Questar ThermWise Duct Technical Specifications

Questar ThermWise Duct Technical Specifications Questar ThermWise Duct Technical Specifications 1. Introduction and Scope: This document sets forth the specifications for duct sealing and duct insulation in accordance to Questar ThermWise Weatherization

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-07 05 23 (May 2014) Change 1-11/14 ----------------------------------- Preparing Activity: USACE UFGS-07 08 27.00 10 (February 2013) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Interpretation Variables and Common Areas of Confusion. Of the 2009 IECC

Interpretation Variables and Common Areas of Confusion. Of the 2009 IECC Interpretation Variables and Common Areas of Confusion Of the 2009 IECC 1. (Mandatory) provisions vs. (Prescriptive) provisions: The IECC contains flexibility by allowing different approaches to achieve

More information

Boulder City NV Prepared by (Print Name) Signature Date

Boulder City NV Prepared by (Print Name) Signature Date City of Boulder City Community Development Department Building & Safety Division 401 California Avenue Boulder City, NV 89005-2600 702-293-9282 (Main Line) 702-293-9392 (Fax) 2009 International Energy

More information

Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort

Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort Please add relevant logo here Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort Presented by: Peter J. Arsenault, FAIA, NCARB, LEED-AP Disclaimer: This presentation was developed by

More information

Fenestration Components: Mechanical Summary. Water heater energy factor: Ef Fuel type: Gas Electric Other

Fenestration Components: Mechanical Summary. Water heater energy factor: Ef Fuel type: Gas Electric Other This information must be on the drawing documents not attached to plans. The following Compliance statements must be on the drawings: 2009 International Energy Conservation Code Statement of acknowledgement

More information

PREP + INSULATION. DISCLAIMER: These tools are for illustrative purposes only and

PREP + INSULATION. DISCLAIMER: These tools are for illustrative purposes only and PREP + INSULATION HOME ENERGY UPGRADES What every contractor needs to know. Copyright 2012 Advanced Energy. All Rights Reserved 103 HOME ENERGY UPGRADES Prep + Insulation Contents Air sealing is a challenging

More information

Building Codes and Ordinances ARC 227

Building Codes and Ordinances ARC 227 Building Codes and Ordinances ARC 227 Week 6 Fire Resistive Construction 03.02.10 Instructor: Rick Staub, AIA Email: staub@pointonearchitects.com Phone: 860-434-7707 Fire Resistive Construction Passive

More information

Advanced Ventilation for Residential applications FBC Res 2010.

Advanced Ventilation for Residential applications FBC Res 2010. Advanced Ventilation for Residential applications FBC Res 2010. Course Description Review of the Residential Ventilation requirements in the Florida Building Code, Residential 2010. I. Introduction Dean

More information

Building Envelope Commissioning and Building Diagnostic Test: Case Studies Course Number: CXENERGY1506

Building Envelope Commissioning and Building Diagnostic Test: Case Studies Course Number: CXENERGY1506 AABC Commissioning Group AIA Provider Number: 50111116 Building Envelope Commissioning and Building Diagnostic Test: Case Studies Course Number: CXENERGY1506 Dan Adam, RA, CxA, Facility Commissioning Group

More information

CHAPTER 1: OVERVIEW OF ENERGY EFFICIENT CONSTRUCTION

CHAPTER 1: OVERVIEW OF ENERGY EFFICIENT CONSTRUCTION Chapter 1: Overview of Energy Efficient Construction 1 CHAPTER 1: OVERVIEW OF ENERGY EFFICIENT CONSTRUCTION Chapter 1 is a quick reference guide that discusses the key components and features of energy

More information

Radon Vent Pipe System. Labeling Performance Indicators

Radon Vent Pipe System. Labeling Performance Indicators Section 6 Radon Vent Pipe Labeling Performance Indicators Radon Vent Pipe System Connected after sub-grade system installed Pipe cannot be trapped Provide space in chases Support at each floor level Discharge

More information

ENERGY EFFICIENCY CERTIFICATION

ENERGY EFFICIENCY CERTIFICATION ENERGY EFFICIENCY CERTIFICATION This form must be completed for developments that qualified for competitive points in the Energy Efficient Design category. Complete Part A for single-family and multifamily

More information

THE GEORGIA ENERGY CODE: 2009 IECC + AMENDMENTS

THE GEORGIA ENERGY CODE: 2009 IECC + AMENDMENTS THE GEORGIA ENERGY CODE: 2009 IECC + AMENDMENTS For the Georgia Association of Home Inspectors Bourke Reeve ABOUT SOUTHFACE 1 EARTHCRAFT Regional Green Building Program HISTORY OF ENERGY CODES MEC 1992,

More information

LEED v4 Building Design and Construction Quiz #8 EQ

LEED v4 Building Design and Construction Quiz #8 EQ LEED v4 Building Design and Construction Quiz #8 EQ 1. Which of these is considered an unoccupied space? [Choose three] A. School classroom B. Mechanical room C. Meeting room D. Locker room E. Restroom

More information

BASEMENT FINISH CONSTRUCTION PLANS REFERENCE: 2015 INTERNATIONAL RESIDENTIAL CODE. PERMITS

BASEMENT FINISH CONSTRUCTION PLANS REFERENCE: 2015 INTERNATIONAL RESIDENTIAL CODE. PERMITS BASEMENT FINISH REFERENCE: 2015 INTERNATIONAL RESIDENTIAL CODE. PERMITS A construction permit is required. A homeowner may perform the construction work on his own property where he resides, without a

More information

Corridor Pressurization System Performance in Multi-Unit Residential Buildings

Corridor Pressurization System Performance in Multi-Unit Residential Buildings Corridor Pressurization System Performance in Multi-Unit Residential Buildings Lorne Ricketts Student Member ASHRAE John Straube, PhD, P.Eng. Associate Member ASHRAE ABSTRACT Corridor pressurization based

More information

INTERIOR ENVIRONMENT

INTERIOR ENVIRONMENT CHAPTER 12 INTERIOR ENVIRONMENT > SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter shall govern ventilation, temperature control, lighting, yards and courts, sound transmission, room dimensions,

More information

DESIGNING COMMERCIAL SUB-SLAB DEPRESSURIZATION SYSTEMS

DESIGNING COMMERCIAL SUB-SLAB DEPRESSURIZATION SYSTEMS DESIGNING COMMERCIAL SUB-SLAB DEPRESSURIZATION SYSTEMS Presented at the 2002 - AARST - 12 th Annual International Radon Symposium in Reno, Nevada Bill Brodhead WPB Enterprises, Inc., 2844 Slifer Valley

More information

2015 IECC Whole Building Air Leakage Compliance

2015 IECC Whole Building Air Leakage Compliance 2015 IECC Whole Building Air Leakage Compliance Presented by: Jeffrey Crowe, PE Project Manager www.becx.com www.pieglobal.com September 2012 Learning Objectives Understand 2015 International Energy Code

More information

CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8)

CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8) CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8) Builder or Installer Name Builder or Installer Contact Telephone Plan/Permit (Additions or Alterations) Number Compliance Method (Prescriptive)

More information

Crawl Space Moisture Control

Crawl Space Moisture Control Crawl Space Moisture Control Crawl space foundations are found in many homes. Typically, these foundation types are equipped with operable vents designed to provide ventilation for moisture control. Unfortunately,

More information

7 AIR LEAKAGE TESTING OF INDIVIDUAL SUITES IN MULTI UNIT RESIDENTIAL BUILDINGS

7 AIR LEAKAGE TESTING OF INDIVIDUAL SUITES IN MULTI UNIT RESIDENTIAL BUILDINGS 7 AIR LEAKAGE TESTING OF INDIVIDUAL SUITES IN MULTI UNIT RESIDENTIAL BUILDINGS Air leakage testing of six suites in four multi unit residential buildings in Vancouver, BC was performed to quantify air

More information

Encapsulated, Sealed & Closed Crawlspace Installation Manual

Encapsulated, Sealed & Closed Crawlspace Installation Manual YourCrawlSpace, Inc. 1007 Johnni4 Dodds Blvd. Mt. Pleasant, SC 29464 Toll Free: 877-44-CRAWL (27295) Local: (843) 593-1115 Encapsulated, Sealed & Closed Crawlspace Installation Manual Copyright 2017 Your

More information

10 Steps to Save Energy in Your House

10 Steps to Save Energy in Your House 10 Steps to Save Energy in Your House Sealing and insulating your home is one of the most cost-effective ways to make your home more comfortable and energy efficient. You can do it yourself. In this chapter,

More information

Is Yours? Homes Across Missouri are Being Built to the Latest National Energy Efficiency Standards

Is Yours? Homes Across Missouri are Being Built to the Latest National Energy Efficiency Standards Homes Across Missouri are Being Built to the Latest National Energy Efficiency Standards Is Yours? A home buyers guide to the energy efficiency requirements of the 2012 International Energy Conservation

More information

Compliance Certificate

Compliance Certificate REScheck Software Version 4.6.4 Compliance Certificate Project RESIDENCE Energy Code: 2009 IECC Location: Perkasie, Pennsylvania Construction Type: Single-family Project Type: New Construction Conditioned

More information

Rhode Island Commercial Codes FAQs

Rhode Island Commercial Codes FAQs Rhode Island Commercial Codes FAQs When does the new code go into effect? The new suite of building codes (including the new state energy conservation code, SBC-8) was adopted on July 1, 2013. A brief

More information

ENERGY AUDITOR STUDY GUIDE

ENERGY AUDITOR STUDY GUIDE ENERGY AUDITOR STUDY GUIDE COURSE OVERVIEW The Building Analyst and HERS Rater course is based upon a broad building science curriculum. It presents a solid scientific foundation upon which inspectors

More information

The Role of Control Layers in Building Enclosure Design

The Role of Control Layers in Building Enclosure Design The Role of Control Layers in Building Enclosure Design COLIN SHANE M.ENG., P.ENG. ASSOCIATE, SENIOR PROJECT MANAGER OCTOBER 13, 2016 Disclaimer: This presentation was developed by a third party and is

More information

Passive House II, The Design Process. Ray Rebilas, AIA - Kitchen & Associates. Harry Moody - Pennrose Properties. Mike Ferguson - S.B.

Passive House II, The Design Process. Ray Rebilas, AIA - Kitchen & Associates. Harry Moody - Pennrose Properties. Mike Ferguson - S.B. Passive House II, The Design Process Ray Rebilas, AIA - Kitchen & Associates Harry Moody - Pennrose Properties Mike Ferguson - S.B. Conrad Adam Blackburn, CPHC Innova Sevices Corporation David Salamon,

More information

Building code language is unclear regarding low-slope roof assembly ventilation. by Brian Erickson, P.E., and Liberty Lewis, P.E.

Building code language is unclear regarding low-slope roof assembly ventilation. by Brian Erickson, P.E., and Liberty Lewis, P.E. Building code language is unclear regarding low-slope roof assembly ventilation by Brian Erickson, P.E., and Liberty Lewis, P.E. 32 November 2009 www.professionalroofing.net Because of our current litigious

More information

Indoor Building Survey and Product Inventory

Indoor Building Survey and Product Inventory Indoor Building Survey and Product Inventory Preparer s Name Date/Time Prepared Preparer s Affiliation Phone No. Purpose of Investigation 1. OCCUPANT: Interviewed: Y / N Last Name: First Name: Address:

More information

2012 CLEAResult All rights reserved. Residential Energy Efficiency

2012 CLEAResult All rights reserved. Residential Energy Efficiency Residential Energy Efficiency Presenter Bio Jaymar Davis, PE, CEM, CLEP, CMVP, CEA Sr. Field Engineering Manager 10 Years experience in energy efficiency Johnson Controls, Kohler Co. Certifications: Licensed

More information

February 28, Prepared by: Michael Flatt ICF International 7160 North Dallas Parkway Suite 340 Plano, TX 75024

February 28, Prepared by: Michael Flatt ICF International 7160 North Dallas Parkway Suite 340 Plano, TX 75024 Low-Rise Multifamily Lessons Learned in Utility Programs February 28, 2012 Prepared by: Michael Flatt ICF International 7160 North Dallas Parkway Suite 340 Plano, TX 75024 0 Market Potential Demand for

More information

Insight. The Hollow Building. By Joseph W. Lstiburek, Ph.D., P.Eng., Fellow ASHRAE

Insight. The Hollow Building. By Joseph W. Lstiburek, Ph.D., P.Eng., Fellow ASHRAE Insight The Hollow Building An edited version of this Insight first appeared in the ASHRAE Journal. By Joseph W. Lstiburek, Ph.D., P.Eng., Fellow ASHRAE Buildings today are hollow and multilayered with

More information

Energy Efficiency Programs

Energy Efficiency Programs Program Overviews Efficiency Programs Description Delivery Model Audit Requirement/ Multifamily - Existing Building Efficiency Alliant Services include free energy assessments, rebates for property owners

More information

780 CMR: 9 th Edition Massachusetts State Building Code. Presented to: BSA Codes Committee. DATE: January 20, 2016

780 CMR: 9 th Edition Massachusetts State Building Code. Presented to: BSA Codes Committee. DATE: January 20, 2016 780 CMR: 9 th Edition Massachusetts State Building Code Presented to: BSA Codes Committee DATE: January 20, 2016 This course is registered with AIA CES for continuing professional education. Credit(s)

More information

Of Building Science: From Control Layers to High Performance Enclosures

Of Building Science: From Control Layers to High Performance Enclosures Of Building Science: From Control Layers to High Performance Enclosures Energy Design Conference February 24, 2016 Duluth, MN Patrick H. Huelman Cold Climate Housing Coordinator University of Minnesota

More information

Energy Code Basics for Residential Buildings. Presented by Newport Ventures NEWPORT VENTURES

Energy Code Basics for Residential Buildings. Presented by Newport Ventures NEWPORT VENTURES Energy Code Basics for Residential Buildings Presented by Newport Ventures Course Overview / Introduction 1. Overview of definitions and compliance changes 2. Building envelope requirements including air

More information

Connecticut 2011 Baseline Study of Single-Family Residential New Construction. Final Report

Connecticut 2011 Baseline Study of Single-Family Residential New Construction. Final Report Connecticut 2011 Baseline Study of Single-Family Residential New Construction Final Report October 1, 2012 Submitted to: Connecticut Energy Efficiency Board Submitted by: Group, Inc. KEMA, Inc. Cadmus

More information

MOISTURE CONDITIONS IN WALLS AND CEILINGS OF A SIMULATED OLDER HOME DURING WINTER

MOISTURE CONDITIONS IN WALLS AND CEILINGS OF A SIMULATED OLDER HOME DURING WINTER MOISTURE CONDITIONS IN WALLS AND CEILINGS OF A SIMULATED OLDER HOME DURING WINTER USDA FOREST SERVICE RESEARCH PAPER FPL 290 1977 U.S. DEPARTMENT OF AGRICULTURE FOREST SERVICE FOREST PRODUCTS LABORATORY

More information

Air Sealing Opportunities in New Construction

Air Sealing Opportunities in New Construction Air Sealing Opportunities in New Construction Matt Braman, Energy Trust of Oregon Bruce Manclark, CLEAResult ABSTRACT Advanced air sealing methods are an integral part of energy-efficient new construction

More information

New Montgomery County Elementary School. Construction Indoor Air Quality Management Plan IEQc3.1 IAQ Plan During Construction

New Montgomery County Elementary School. Construction Indoor Air Quality Management Plan IEQc3.1 IAQ Plan During Construction New Montgomery County Elementary School Construction Indoor Air Quality Management Plan IEQc3.1 IAQ Plan During Construction LEED certification promotes environmentally friendly buildings and sites through

More information

BUILDING CODES & DESIGN CRITERIA

BUILDING CODES & DESIGN CRITERIA BUILDING CODES & DESIGN CRITERIA Adopted Building Codes: 2006 International Building Code (IBC) 2006 International Residential Code (IRC) 2006 International Mechanical Code (IMC) 2006 International Plumbing

More information

Crawl Spaces and Basements: Defining the Building Envelope

Crawl Spaces and Basements: Defining the Building Envelope Crawl Spaces and Basements: Defining the Building Envelope Rich Jones: INCAA, Charlie Smith: Kentucky Housing Corporation, Albert McMahon: NYSWDA 1 By attending this session, participants will: Identify

More information

A Field Study of Airflow in Mid to High-Rise Multi-Unit Residential Buildings

A Field Study of Airflow in Mid to High-Rise Multi-Unit Residential Buildings A Field Study of Airflow in Mid to High-Rise Multi-Unit Residential Buildings Lorne Ricketts, MASc, EIT John Straube, PhD, P.Eng. ABSTRACT Airflow into, out of, and within buildings is a fundamental factor

More information

Spray Polyurethane Foam. Insulation and Air Barrier Requirements of the 2012 I-Codes. Spray Foam Coalition

Spray Polyurethane Foam. Insulation and Air Barrier Requirements of the 2012 I-Codes. Spray Foam Coalition Spray Polyurethane Foam Design Guidance Insulation and Air Barrier Requirements of the 2012 I-Codes Spray Foam Coalition about the collaboration the center for the polyurathanes industry (CPI) of the

More information

2013 COMMERCIAL PRODUCTS

2013 COMMERCIAL PRODUCTS 2013 COMMERCIAL PRODUCTS EXPLORE GEOMETRY AND SPACE WITHOUT COMPROMISING BUILDING ENVELOPE PERFORMANCE Commercial design considerations come with very specific challenges that can t be addressed with just

More information

Comparison of the life safety elements of the 1997 UBC and the IBC 2000.

Comparison of the life safety elements of the 1997 UBC and the IBC 2000. Comparison of the life safety elements of the 1997 UBC and the IBC 2000. Introduction The Building Performance Research Institute s mission is primarily one of education on building safety and performance.

More information

Field Determination of Water Penetration of Windows using Blowerdoor and Infrared Camera

Field Determination of Water Penetration of Windows using Blowerdoor and Infrared Camera Field Determination of Water Penetration of Windows using Blowerdoor and Infrared Camera Walter Sebastian BMT Building Enviroment Consultants Ltd., Doktor Neergaards Vej 15, DK-2970 Hoersholm, Denmark

More information

Web-Based Energy Savings Calculator for Building Envelope Air Tightness

Web-Based Energy Savings Calculator for Building Envelope Air Tightness Web-Based Energy Savings Calculator for Building Envelope Air Tightness André Desjarlais Oak Ridge National Laboratory Air Barrier Association of America (ABAA) is a Registered Provider with The American

More information

TOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ FAX

TOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ FAX TOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ 08014 856-467-3626--- FAX 856-467-9260 Application for Certificate of Occupancy for Change of Occupancy Pursuant to Chapter 119 of the Township

More information

Insight. Drainage, Holes and Moderation. By Joseph W. Lstiburek, Ph.D., P.Eng., Fellow ASHRAE

Insight. Drainage, Holes and Moderation. By Joseph W. Lstiburek, Ph.D., P.Eng., Fellow ASHRAE Drainage, Holes and Moderation Insight Drainage, Holes and Moderation An edited version of this Insight first appeared in the ASHRAE Journal. cup. But lo and behold, even though some raindrops enter the

More information

CHECKLIST Inspecting a Garage

CHECKLIST Inspecting a Garage CHECKLIST Inspecting a Garage By Ben Gromicko This section deals with the details of the garage or carport inspection that may be performed. At the end of this section, you shall be able to: describe the

More information

Basement Renovation Guide For Residential Dwellings

Basement Renovation Guide For Residential Dwellings 1 Development Services Department Building Permit & Inspection Services Basement Renovation Guide For Residential Dwellings This document is a guide for home owners and does not cover all possible conditions.

More information

Florida HERO Program Residential Eligible Product List All Products

Florida HERO Program Residential Eligible Product List All Products All Products In addition to the HERO Product Eligibility Specifications listed below, it is the sole responsibility of the HERO Contractor and property owner (Project Stakeholders) to meet or exceed applicable

More information

Thermal Bridging in Residential Construction

Thermal Bridging in Residential Construction PHRC Webinar Series Tuesday, May 12, 2015 @ 1pm Thermal Bridging in Residential Construction Brian Wolfgang Housing Systems Specialist Pennsylvania Housing Research Center 219 Sackett Building University

More information

Renovation of a Detached Single-Family House into an Energy Efficient Low Energy House Larsen, Tine Steen; Maagaard, Steffen; Jensen, Rasmus Lund

Renovation of a Detached Single-Family House into an Energy Efficient Low Energy House Larsen, Tine Steen; Maagaard, Steffen; Jensen, Rasmus Lund Aalborg Universitet Renovation of a Detached Single-Family House into an Energy Efficient Low Energy House Larsen, Tine Steen; Maagaard, Steffen; Jensen, Rasmus Lund Published in: Proceedings of the 9th

More information

Evergreen Project Implementation Plan Instructions Low Income Housing Tax Credit Program

Evergreen Project Implementation Plan Instructions Low Income Housing Tax Credit Program Evergreen Project Implementation Plan Instructions Low Income Housing Tax Credit Program The following table provides a brief description of the documentation that will be required of successful LIHTC

More information

1. When using the REScheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

1. When using the REScheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is. Energy Conservation Code Residential Building CHAPTER 4 WORKSHEET 1. When using the REScheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is _

More information

A/E Design Deliverable Checklist

A/E Design Deliverable Checklist A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic

More information

LEED And Your Indoor Environment

LEED And Your Indoor Environment LEED And Your Indoor Environment An overview of LEED v3 and Indoor Air Quality David McCauley, CIE Council Certified Indoor Environmentalist ACAC CIE #1008005 USGBC's Mission To transform the way buildings

More information

Using a Aerosol Sealant to Reduce Multifamily Envelope Leakage

Using a Aerosol Sealant to Reduce Multifamily Envelope Leakage Using a Aerosol Sealant to Reduce Multifamily Envelope Leakage Dave Bohac PE Director of Research Ben Schoenbauer Senior Research Engineer Jim Fitzgerald Senior Building Analyst Center for Energy and Environment

More information

Achieving acoustical standards in the classroom Study of HVAC systems and classroom acoustics

Achieving acoustical standards in the classroom Study of HVAC systems and classroom acoustics Achieving acoustical standards in the classroom Study of HVAC systems and classroom acoustics Trane believes the facts and suggestions presented here to be accurate. However, final design and application

More information

ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING

ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING Brittany Hanam 1, Lorne Ricketts 2, Andrew Pape-Salmon 3 ABSTRACT The National Institute of Building Sciences estimates that over 70% of the

More information

HCM UNIVERSITY OF ALASKA FAIRBANKS Building Challenges in Alaska UNIVERSITY OF ALASKA FAIRBANKS

HCM UNIVERSITY OF ALASKA FAIRBANKS Building Challenges in Alaska UNIVERSITY OF ALASKA FAIRBANKS HCM-00952 UNIVERSITY OF ALASKA FAIRBANKS UNIVERSITY OF ALASKA FAIRBANKS Building Challenges in Alaska INTRODUCTION Special considerations for building in Alaska are recommended that are normally not included

More information

KITCHEN REMODELS CITY OF MISSION VIEJO BUILDING SERVICES DIVISON 200 CIVIC CENTER, MISSION VIEJO, CA (949)

KITCHEN REMODELS CITY OF MISSION VIEJO BUILDING SERVICES DIVISON 200 CIVIC CENTER, MISSION VIEJO, CA (949) CITY OF MISSION VIEJO BUILDING SERVICES DIVISON 200 CIVIC CENTER, MISSION VIEJO, CA 92691 (949) 470-3054 KITCHEN REMODELS A permit is required for kitchen remodels that include removal and replacement

More information

Airspace R-Values. Educational Overview. Revised 12/6/2016

Airspace R-Values. Educational Overview. Revised 12/6/2016 Airspace R-Values Educational Overview Revised 12/6/2016 Introduction Airspaces contained within building envelope assemblies are known to contribute to thermal performance. But, the actual R-value for

More information

APPROVED. Acceptable to the code official for compliance with the provisions of the applicable Code or referenced Standard.

APPROVED. Acceptable to the code official for compliance with the provisions of the applicable Code or referenced Standard. Chapter 1 101.1 Title. These regulations shall be known as the North Carolina Energy Conservation Code as approved by the North Carolina Building Code Council on March 11, 2008, to be effective January

More information

Margaret Batts Tobin Laboratory

Margaret Batts Tobin Laboratory Roof Evaluation of Margaret Batts Tobin Laboratory The University of Texas At San Antonio Performed for UTSA Zero/Six Consulting, LLC 8423 Stewart Road Galveston, Texas 77554 409 740 0090 voice Table of

More information

COMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program

COMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program COMMERCIAL LOAD ESTIMATING Load Estimating Level 3: Block and Zone Loads Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design,

More information

Size: length ft., bay width ft., number of bays: Square feet of floor space: Sq. ft. of bench/floor space covered by crops:

Size: length ft., bay width ft., number of bays: Square feet of floor space: Sq. ft. of bench/floor space covered by crops: Greenhouse Energy Conservation Checklist/Audit (Adapted by A.J. Both, Rutgers University, and Paul Fisher, University of Florida from a checklist developed by John W. Bartok Jr., Professor Emeritus, University

More information

2016 CALGREEN RESIDENTIAL CHECKLIST MANDATORY ITEMS City of San Carlos - Building Division 600 Elm Street, San Carlos, CA Phone:

2016 CALGREEN RESIDENTIAL CHECKLIST MANDATORY ITEMS City of San Carlos - Building Division 600 Elm Street, San Carlos, CA Phone: 2016 CALGREEN RESIDENTIAL CHECKLIST MANDATORY ITEMS City of San Carlos - Building Division 600 Elm Street, San Carlos, CA 94070 Phone: 650-802-4261 PURPOSE: The residential provisions of the 2016 CalGreen

More information

For building inspections

For building inspections Thermal imaging basics For building inspections An infrared building inspection guidebook Fluke Thermal Imaging Infrared Building Inspection Guidebook Contents Page Section 3 4 5 6 9 10 12 Introduction

More information

Retrofit Installer / Shell

Retrofit Installer / Shell Retrofit Installer / Shell Day1 9:00 Introductions, Housekeeping Agenda Weatherization Introduction 101 (PRQ for all WX Competency Designations) 9:30 History of the Weatherization Program Weatherization

More information

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

Property Condition Assessment

Property Condition Assessment Property Condition Assessment Pewaukee, WI 53072 Inspection Date: 1/6/15 Prepared For: Report Number: Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar Dr. Pewaukee, WI 53072

More information

Radon Mitigation Technology

Radon Mitigation Technology Radon Mitigation Technology Field Exercise Package Includes: Description of Mentoring Program Mentor Selection Criteria Field Exercises Field Exercise Verification Form Course Evaluation This field exercise

More information

MOLD INSPECTION REPORT Block Home Inspections LLC

MOLD INSPECTION REPORT Block Home Inspections LLC Block Home Inspections LLC David Block - 913-220-7762 MOLD INSPECTION REPORT Block Home Inspections LLC David M. Block Certified Mold Inspector #CMI-06-2024 INSPECTION AGREEMENT Mold screening is intended

More information

STEP UP TO THE ENERGY STAR INDOOR AIR PACKAGE. A new opportunity for leading builders to create better environments inside and out

STEP UP TO THE ENERGY STAR INDOOR AIR PACKAGE. A new opportunity for leading builders to create better environments inside and out STEP UP TO THE ENERGY STAR INDOOR AIR PACKAGE A new opportunity for leading builders to create better environments inside and out WHY DOES INDOOR AIR QUALITY MATTER? People are increasingly concerned about

More information

Senior Design Project for UNO. Design of the International Studies Building: An Environmental Analysis

Senior Design Project for UNO. Design of the International Studies Building: An Environmental Analysis Senior Design Project for UNO Design of the International Studies Building: An Environmental Analysis Design Intent Implement Passive & Active design strategies in order to make the building: More Energy

More information

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Loa Andersson Managing Director RLI Byggdata AB rli@termodeck.com Alexander Engström Technical Director RLI Byggdata AB

More information

Air Leakage Control for Multi-Unit Residential Buildings

Air Leakage Control for Multi-Unit Residential Buildings Air Leakage Control for Multi-Unit Residential Buildings CMHC helps Canadians meet their housing needs. Canada Mortgage and Housing Corporation (CMHC) has been helping Canadians meet their housing needs

More information

Open and Closed Cell Spray Foam Insulation

Open and Closed Cell Spray Foam Insulation Open and Closed Cell Spray Foam Insulation Complete Comfort CertaSpray has it covered Comfort starts with thermal performance, but it doesn t end there. Complete Comfort comes in an environment free from

More information

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018)

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018) BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018) PERMIT SUBMITTAL CHECKLIST: Signed and completed Building Permit application form. A separate Electrical permit is required from

More information

Energy Audits. Presented By. Eugene Hoyt Professional Inspector TREC # IECC Energy Inspector/Plans Examiner ICC #

Energy Audits. Presented By. Eugene Hoyt Professional Inspector TREC # IECC Energy Inspector/Plans Examiner ICC # Energy Audits Presented By Eugene Hoyt Professional Inspector TREC # 10117 IECC Energy Inspector/Plans Examiner ICC # 8100852 Real Horizons Inspection Services, LLC To Sam Houston State University Huntsville,

More information

RESIDENTIAL NEW CONSTRUCTION PLAN REVIEW CHECKLIST

RESIDENTIAL NEW CONSTRUCTION PLAN REVIEW CHECKLIST This list is provided as a guide to help you understand the information that must be contained on the construction drawings. This list is not all-inclusive of all building codes but is used as a general

More information

Continuous Insulation Systems for Exterior Walls

Continuous Insulation Systems for Exterior Walls Continuous Insulation Systems for Exterior Walls High performance through sprayed-in-place foam insulation www.icynene.com Program Registration Icynene Inc. is a registered provider with The American Institute

More information

Chilled Beams. The new system of choice?

Chilled Beams. The new system of choice? Chilled Beams The new system of choice? Presented By: Kevin M. Pope P.E. Jason Leffingwell Hammel Green And Abrahamson, Inc. and Ken Bauer, P.E., LEED AP Butters-Fetting Co., Inc. History of Chilled Beams

More information

WP5.5: Product concepts for high efficiency step by step retrofits

WP5.5: Product concepts for high efficiency step by step retrofits WP5.5: Product concepts for high efficiency step by step retrofits Final presentation Product development 1. Aim of Product development 2. Summary of demand - what exists and what is needed 3. Meetings

More information

Balancing the Control of Heat, Air, Moisture, and Competing Interests

Balancing the Control of Heat, Air, Moisture, and Competing Interests Balancing the Control of Heat, Air, Moisture, and Competing Interests Patrick J. Roppel, M.A.Sc. Mark D. Lawton, P.Eng. Brian Hubbs, P.Eng. Building Science Consultant Sr. Building Scientist Specialist

More information

Insulating Basements: Part 1 Fundamentals

Insulating Basements: Part 1 Fundamentals The Pennsylvania Housing Research Center Insulating Basements: Part 1 Fundamentals Builder Brief: BB0510 Brian Wolfgang, PHRC Fellow INTRODUCTION The perception of a basement has changed significantly

More information