Center for Environmental Energy Engineering Department of Mechanical Engineering University of Maryland College Park, MD

Size: px
Start display at page:

Download "Center for Environmental Energy Engineering Department of Mechanical Engineering University of Maryland College Park, MD"

Transcription

1 System Drop-In and Soft Optimization Tests of R-40A Alternative Refrigerants in Split System Heat Pump Jan. 204 Abdullah Alabdulkarem, Radia Eldeeb, Yunho Hwang, Vikrant Aute, Reinhard Radermacher Center for Environmental Energy Engineering Department of Mechanical Engineering University of Maryland College Park, MD

2 Contents Objectives Schematic of test facility Test conditions Performance comparison of R40A vs. alternative refrigerants Simulation results Conclusions 2

3 Objectives Evaluate the performance of an air conditioner and a heat pump using low GWP refrigerants and compare the results against R40A Drop-in tested refrigerants are: R2 L4A D2Y60 Perform soft-optimized system tests to match the capacity to that of R40A

4 Properties of R40A and Low GWP Refrigerants Parameter Unit R40A R2 D2Y60 L4A Temperature C Sat. Vapor Pressure kpa Liquid Density kg/m Vapor Density kg/m Latent Heat kj/kg Liquid kj/(kg-k) Specific Heat Liquid Thermal mw/(m-k) Conductivity Temperature Glide K Liquid Viscosity µpa-s Significant thermophysical property differences 8.68 Vapor Viscosity µpa-s.7 between 2.7R40A 4and alternative refrigerants Vol. Cooling Capacity kj/m Critical Temperature C ct/h fg

5 Thermodynamic Model 40 o C condenser temperature and 0 o C evaporator temperature 70% compressor efficiency, 27. cm displacement volume o C superheat and 2 o C subcooling 2 6 Capacity (kw) 0 8 COP R40A R2 D2Y60 L4A R40A R2 D2Y60 L4A

6 Schematic of Test Facility 6

7 Heat Pump Unit Compressor Single Speed, Scroll Compressor Nominal Cooling Capacity Tons Rated SEER 4 Rated HSPF 8.7 Expansion Device TXV for Cooling / Orifice for Heating 7

8 Test Test ASHRAE Standard 6- and Extended Indoor Outdoor db ( o C) wb ( o C) db ( o C) wb ( o C) Operation Extended 46. Steady State Cooling A.4 Steady State Cooling B 26.7 NA Steady State Cooling C Steady State Cooling, Dry Coil D Cyclic Cooling, Dry Coil High Temp Steady State Heating High Temp Steady State Heating Low Temp Steady State Heating Extended NA Steady State Heating High Temp. Cyclic Cyclic Heating Frost Acc Steady State Defrost 8

9 Drop In Tests

10 Steady State Cooling Test Results R40A R2 D2Y60 L4A R40A R2 D2Y60 L4A Capacity (kw) COP 2 4 Extended A B C Extended Ref. vs. R40A R2 D2Y60 L4A Optimum Charge -% -% -% Avg. Cooling Capacity % -8% -7% Avg. Cooling COP -% -4% -% A B C 0

11 Steady State Heating Test Results. R40A R2 D2Y60 L4A. R40A R2 D2Y60 L4A. Capacity (kw) COP Extended Low Temp. High Temp. 2 High Temp.. Extended Low Temp. High Temp. 2 High Temp. Ref. vs. R40A R2 D2Y60 L4A Avg. Heating Capacity 4% -4% -% Avg. Heating COP -% -2% 2%

12 Drop In Tests Conclusions Charge reduction for all refrigerants compared to R40A R2 Capacity outperformed R40A COP can outperform R40A with optimized compressor D2Y60 Low COP and capacity Low discharge temperature L4A Capacity matched R40A for heating only COP matched R40A Highest values for SEER and HSPF compared to R40A 2

13 Soft Optimized Tests

14 Soft Optimized Tests Plan Refrigerants Challenge Soft- Optimization Tests Soft-Optimization (Long Term) R40A Baseline - TXV for Heating R2 D2Y60 Compressor outlet temp., Slight COP degradation Low capacity - TXV for Heating, Larger Compressor TXV for Heating, Optimized Compressor Optimized Heat Exchangers L4A Two-phase suction TXV for Heating Optimized Heat Exchangers 4

15 Steady State Cooling Test Results R40A D2Y60 Drop In D2Y60 Soft Opt 2 R40A D2Y60 Drop In D2Y60 Soft Opt 0 4 Capacity (kw) 8 7 COP Extended A B C Extended A B C

16 Steady State Heating Test Results R40A D2Y60 Drop In D2Y60 Soft Opt 4 R40A D2Y60 Drop In D2Y60 Soft Opt 2 4 Capacity (kw) COP Extended Low Temp. High Temp. 2 High Temp. Extended Low Temp. High Temp. 2 High Temp. 6

17 L4A Soft Optimized Tests 4 L4A Drop In L4A Soft Optimized 2 Superheat (K) Extended Low Temp. High Temp. 2 High Temp. 7

18 Steady State Heating Tests R40A L4A Drop In L4A Soft Optimized. R40A L4A Drop In L4A Soft Optimized Capacity (kw) COP Extended Low Temp. High Temp. 2 High Temp.. Extended Low Temp. High Temp. 2 High Temp. 8

19 Cyclic Heating Test R40A w/ Orifice L4A TXV Orifice Capacity (kw) 7 Capacity (kw) Time (min.) Heating- Power Air Side Consumption (kw-hr) (kw-hr) COP Heating Load Factor (HLF) Degradation Coefficient (C D ) HSPF R40A L4A Difference (%) Time (min.)

20 Simulation of Drop In Tests 20

21 System Model in VapCyc Condenser and evaporator are CoilDesigner components Compressor is 0 coefficient database compressor model 2

22 Numerical Capacity (kw) Numerical Capacity (kw) Numerical Capacity (kw) Preliminary Simulation Results R40A R2 D2Y60 L4A % Error Lines Experimental Capacity (kw) Experimental Capacity (kw) Experimental Capacity (kw) Cooling Tests Numerical COP Heating Tests Numerical COP Experimental COP Experimental COP 22

23 Conclusions Using larger compressor for D2Y60 enhanced capacity but deteriorated COP Using TXV for L4A enhanced HSPF without significant change in steady state test results Simulation predicted the experiments well except in low and extended heating tests 2

24 Questions/Comments? Thank you! 24

25 Frost Accumulation Test R40A w/ Orifice L4A w/ TXV 7 7 Capacity (kw) Heating-Air side (kw-hr) Average Heating Capacity (kw) COP R40A L4A Difference (%) Capacity (kw) Time (min.) Time (min.) 2

26 Cyclic Cooling Test R40A D2Y60 Soft Optimized Capacity (kw) 7 Capacity (kw) Time (min.) Time (min.) Cooling- Air Side (kw-hr) Power Consumption (kw-hr) COP Cooling Load Factor (CLF) Degradation Coefficient (CD) SEER R40A D2Y Difference (%)

27 Capacity (kw) 7 - Cyclic Heating Test R40A Time (min.) Heating- Power Air Side Consumption (kw-hr) (kw-hr) COP Heating Load Factor (HLF) Time (min.) Degradation Coefficient (C D ) HSPF R40A D2Y Difference (%) Capacity (kw) 7 - D2Y60 Soft Optimized

28 Refrigerant Temperature in A Test 0 R40A R2 D2Y60 L4A Temperature ( C) Compressor Suction Compressor Discharge Condenser Outlet Expansion Device Inlet Evaporator Inlet (Calculated) Evaporator Outlet 28

29 Compressor Discharge Temp. and Mass Flow Rate in Cooling Tests Discharge Temp. ( C) R40A R2 D2Y60 L4A Ref. Mass Flowrate (g/s) R40A R2 D2Y60 L4A 0 Extended A B C Extended Ref. vs. R40A R2 D2Y60 L4A Avg. Compressor Disch. Temp. 4 C -4 C 7 C Avg. Ref. Mass Flow Rate -% -6% -2% A B C 2

30 Compressor Efficiencies Isentropic Efficiency R40A R2 D2Y60 L4A Extended A B C Volumetric Efficiency R40A R2 D2Y60 L4A Extended Ref. vs. R40A R2 D2Y60 L4A Avg. Isentropic Efficiency -6.% -.8% -.% Avg. Volumetric Efficiency -4.4% 0.% -2.4% A B C

31 SEER and HSPF 4 2 SEER (Btu/W-hr) HSPF (Btu/W-hr) R40A R2 D2Y60 L4A Ref. vs. R40A R2 D2Y60 L4A Avg. SEER -.% -8.% -2.4% Avg. HSPF 2.8% 6.% 6.7%

Steady State And Transient Validation Of Heat Pumps Using Alternative Lower-GWP Refrigerants

Steady State And Transient Validation Of Heat Pumps Using Alternative Lower-GWP Refrigerants Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Steady State And Transient Validation Of Heat Pumps Using Alternative Lower-GWP

More information

Arkema technical note. Forane 407A. The low-gwp and energy efficient alternative to R-404A and R-507A

Arkema technical note. Forane 407A. The low-gwp and energy efficient alternative to R-404A and R-507A Arkema technical note Forane 407A The low-gwp and energy efficient alternative to R-404A and R-507A The statements, technical information and recommendations contained herein are believed to be accurate

More information

Investigation of New Low-GWP Refrigerants for Use in Two-Phase Evaporative Cooling of Electronics

Investigation of New Low-GWP Refrigerants for Use in Two-Phase Evaporative Cooling of Electronics Investigation of New Low-GWP Refrigerants for Use in Two-Phase Evaporative Cooling of Electronics Alexis Nicolette-Baker, Elizabeth Garr, Abhijit Sathe, and Steve O'Shaughnessey Precision Cooling Systems

More information

Experimental Investigation of Vapor Injected Compression for Cold Climate Heat Pumps ABSTRACT

Experimental Investigation of Vapor Injected Compression for Cold Climate Heat Pumps ABSTRACT 2111, Page 1 Experimental Investigation of Vapor Injected Compression for Cold Climate Heat Pumps Christian K. BACH 1 *, Bernhard VETSCH 2, Eckhard A. GROLL 1, James E. BRAUN 1, W. Travis HORTON 1 1 Purdue

More information

An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors

An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 An Integrated Solution for Commercial AC Chillers Using Variable Speed

More information

a.k.a. David N. Shaw, P. E.

a.k.a. David N. Shaw, P. E. BOOSTED AIR-SOURCE HEAT PUMPS a.k.a. Ac adia By David N. Shaw, P. E. Chief Technolo gy O fficer Hallowell I nternational w w w.gotohallowell.com HALLOWELL WHITE WHITE PAPER PAPER Hallowell.International

More information

Robert Kebby February BUILDING BLOCKS OF THE FUTURE Commercial Refrigeration Applications

Robert Kebby February BUILDING BLOCKS OF THE FUTURE Commercial Refrigeration Applications Robert Kebby February 2016 BUILDING BLOCKS OF THE FUTURE Commercial Refrigeration Applications Honeywell A History of Innovation CFCs HCFCs HFCs HFOs Very high ODP & GWP High ODP and GWP ODP=0, but high

More information

2010 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment

2010 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment ANSI/AHRI Standard 1230 with Addendum 2 2010 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment Approved by ANSI on 2 August 2010 ANSI/AHRI

More information

Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis

Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis Elias

More information

Modeling of Air-Source Integrated Heat Pumps

Modeling of Air-Source Integrated Heat Pumps 2016 ACEEE Hot Water Forum Heating Water with Integrated Heat Pumps Modeling of Air-Source Integrated Heat Pumps -simulation-driven design Bo Shen, Keith Rice, Oak Ridge National Laboratory February 23,

More information

ENHANCEMENT OF COEFFICIENT OF PERFORMANCE IN VAPOUR COMPRESSION REFRIGERATION CYCLE

ENHANCEMENT OF COEFFICIENT OF PERFORMANCE IN VAPOUR COMPRESSION REFRIGERATION CYCLE ENHANCEMENT OF COEFFICIENT OF PERFORMANCE IN VAPOUR COMPRESSION REFRIGERATION CYCLE Dr Venkata Ramana Reddy Mula 1, H.V.Harish 2 1 Professor and Head, Department of Aeronautical Engineering NMIT BANGALORE

More information

Packaged Refrigerant Based Energy Storage (RBES) Air Conditioning System

Packaged Refrigerant Based Energy Storage (RBES) Air Conditioning System Packaged Refrigerant Based Energy Storage (RBES) Air Conditioning System Ram Narayanamurthy Ice Energy, Inc. this technology provides some of the largest opportunities we have right now to address the

More information

Unitary Air Conditioner Field Performance

Unitary Air Conditioner Field Performance Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2004 Unitary Air Conditioner Field Performance Todd M. Rossi Field Diagnostic

More information

Heating Performance with a Volume Ratio on 2-Stage Compressor

Heating Performance with a Volume Ratio on 2-Stage Compressor Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Heating Performance with a Volume Ratio on 2-Stage Compressor Sangkyoung

More information

Application of Viper Energy Recovery Expansion Device in Transcritical Carbon Dioxide Refrigeration Cycle

Application of Viper Energy Recovery Expansion Device in Transcritical Carbon Dioxide Refrigeration Cycle Abstract Application of Viper Energy Recovery Expansion Device in Transcritical Carbon Dioxide Refrigeration Cycle Riley B. Barta a *, Eckhard A. Groll b a Purdue University, School of Mechanical Engineering,

More information

ALTERNATIVE REFRIGERANTS FOR BUILDING AIR CONDITIONING D. B. BIVENS ENGINEERING FELLOW DUPONT FLUOROPRODUCTS WLZMINGTON, DE.

ALTERNATIVE REFRIGERANTS FOR BUILDING AIR CONDITIONING D. B. BIVENS ENGINEERING FELLOW DUPONT FLUOROPRODUCTS WLZMINGTON, DE. ALTERNATIVE REFRIGERANTS FOR BUILDING AIR CONDITIONING D. B. BIVENS ENGINEERING FELLOW DUPONT FLUOROPRODUCTS WLZMINGTON, DE. ABSTRACT The majority of building air conditioning has traditionally been acheved

More information

Eng Thermodynamics I: Sample Final Exam Questions 1

Eng Thermodynamics I: Sample Final Exam Questions 1 Eng3901 - Thermodynamics I: Sample Final Exam Questions 1 The final exam in Eng3901 - Thermodynamics I consists of four questions: (1) 1st Law analysis of a steam power cycle, or a vapour compression refrigeration

More information

Secondary Coolant Systems for Supermarkets

Secondary Coolant Systems for Supermarkets The following article was published in ASHRAE Journal, September 2006. Copyright 2006 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes

More information

Design and development of a residential gas-fired heat pump

Design and development of a residential gas-fired heat pump Design and development of a residential gas-fired heat pump Edward A Vineyard a*, Ahmad Abu-Heiba a, Isaac Mahderekal b a Oak Ridge National Laboratory, P.O. Box 2008, MS 6070, Oak Ridge, TN, 37831, USA

More information

Performance of a Combined Organic Rankine Cycle and Vapor Compression Cycle for Heat Activated Cooling

Performance of a Combined Organic Rankine Cycle and Vapor Compression Cycle for Heat Activated Cooling Performance of a Combined Organic Rankine Cycle and Vapor Compression Cycle for Heat Activated Cooling Hailei Wang*, Richard Peterson, Kevin Harada, Erik Miller, Robbie Ingram-Goble, Luke Fisher, James

More information

An Investigation of R417a as a Drop-in Alternative for R22 in a Residential Heat Pump

An Investigation of R417a as a Drop-in Alternative for R22 in a Residential Heat Pump An Investigation of R417a as a Drop-in Alternative for in a Residential Heat Pump Zhiming Gao *, Viung C Mei, Fang C Chen, John Tomlinson Oak Ridge National Laboratory, Oak Ridge, TN 37831-67 Heat pumps

More information

A Comprehensive Evaluation of Regression Uncertainty and the Effect of Sample Size on the AHRI-540 Method of Compressor Performance Representation

A Comprehensive Evaluation of Regression Uncertainty and the Effect of Sample Size on the AHRI-540 Method of Compressor Performance Representation Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2016 A Comprehensive Evaluation of Regression Uncertainty and the Effect of Sample Size

More information

Investigations of N 2 O Transcritical Refrigeration Cycle Using Dedicated Mechanical Subcooling. Sanjeev Kumar 1 and Dr. D.K.

Investigations of N 2 O Transcritical Refrigeration Cycle Using Dedicated Mechanical Subcooling. Sanjeev Kumar 1 and Dr. D.K. e t International Journal on Emerging Technologies (Special Issue NCETST-2017) 8(1): 340-344(2017) (Published by Research Trend, Website: www.researchtrend.net) ISSN No. (Print) : 0975-8364 ISSN No. (Online)

More information

EXPERIMENTAL STUDY ON THE REPLACEMENT OF HFC-R134A BY HYDROCARBONS MIXTURE IN AUTOMOTIVE AIR CONDITIONER. Skudai, Johor, Malaysia 81310

EXPERIMENTAL STUDY ON THE REPLACEMENT OF HFC-R134A BY HYDROCARBONS MIXTURE IN AUTOMOTIVE AIR CONDITIONER. Skudai, Johor, Malaysia 81310 International Journal of Technology (2013) 1: 81-92 ISSN 2086-9614 IJTech 2013 EXPERIMENTAL STUDY ON THE REPLACEMENT OF HFC-R134A BY HYDROCARBONS MIXTURE IN AUTOMOTIVE AIR CONDITIONER Mohd Rozi Mohd Perang

More information

1st October Robert Kebby Marketing Manager

1st October Robert Kebby Marketing Manager 1st October 2014 Robert Kebby Marketing Manager Why R-404A? Success of R404A over the last 15 to 20 years - Replaced ODP products such as R12 / R502 & more recently R22 - Marketed well as a one solution

More information

HELICAL OIL SEPARATORS

HELICAL OIL SEPARATORS OIL SEPARATORS HELICAL OIL SEPARATORS The function of a Helical Oil Separator is to efficiently remove oil from the discharge gas and return it to the compressor, either directly or indirectly. This helps

More information

BTO s Heat Pump Research Efforts

BTO s Heat Pump Research Efforts BTO s Heat Pump Research Efforts Antonio M Bouza antonio.bouza@ee.doe.gov March 22, 2016 Outline BTO Ecosystem Introduction Cold Climate Heat Pump Research Projects Heat Exchangers Future Technologies

More information

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Performance Comparison of Air-source Heat Pumps Using Economizer Vapor

More information

Lecture No.3. The Ideal Reheat Rankine Cycle

Lecture No.3. The Ideal Reheat Rankine Cycle Lecture No.3 The Ideal Reheat Rankine Cycle 3.1 Introduction We noted in the last section that increasing the boiler pressure increases the thermal efficiency of the Rankine cycle, but it also increases

More information

COOLING EFFECTIVENESS OF MIST PRECOOLER FOR IMPROVING ENERGY PERFORMANCE OF AIR-COOLED CHILLER

COOLING EFFECTIVENESS OF MIST PRECOOLER FOR IMPROVING ENERGY PERFORMANCE OF AIR-COOLED CHILLER Yu, F. W., et al.: Cooling Effectiveness of Mist Precooler for THERMAL SCIENCE: Year 2018, Vol. 22, No. 1A, pp. 193-204 193 COOLING EFFECTIVENESS OF MIST PRECOOLER FOR IMPROVING ENERGY PERFORMANCE OF AIR-COOLED

More information

UNIT NO-03 [8 hrs] Second Law Of Thermodynamics: Introduction (Law of degradation of energy), Thermal energy reservoirs, Kelvin-Plank & Clausius

UNIT NO-03 [8 hrs] Second Law Of Thermodynamics: Introduction (Law of degradation of energy), Thermal energy reservoirs, Kelvin-Plank & Clausius UNIT NO-03 [8 hrs] Second Law Of Thermodynamics: Introduction (Law of degradation of energy), Thermal energy reservoirs, Kelvin-Plank & Clausius statements, Heat engines, Refrigerator and Heat pump, Perpetual

More information

HPC 2017 Performance simulation and exergy analysis on multi-stage compression high temperature heat pumps with R1234ze(Z) refrigerant

HPC 2017 Performance simulation and exergy analysis on multi-stage compression high temperature heat pumps with R1234ze(Z) refrigerant Performance simulation and exergy analysis on multi-stage compression high temperature heat pumps with R1234ze(Z) refrigerant Bin Hu, Di Wu, R.Z. Wang Institute of Refrigeration and Cryogenics Shanghai

More information

OUTCOME 2 TUTORIAL 2 STEADY FLOW PLANT

OUTCOME 2 TUTORIAL 2 STEADY FLOW PLANT UNIT 47: Engineering Plant Technology Unit code: F/601/1433 QCF level: 5 Credit value: 15 OUTCOME 2 TUTORIAL 2 STEADY FLOW PLANT 2 Be able to apply the steady flow energy equation (SFEE) to plant and equipment

More information

Dresden, Germany ABSTRACT MODELING OF THE CHILLER INTRODUCTION

Dresden, Germany ABSTRACT MODELING OF THE CHILLER INTRODUCTION Eleventh International IBPSA Conference Glasgow Scotland July 27-3 29 TESTING AND VALIDATION OF SIMULATION TOOLS OF HVAC MECHANICAL EQUIPMENT INCLUDING THEIR CONTROL STRATEGIES PART III: VALIDATION OF

More information

DESIGN ANALYSIS OF A REFRIGERATED WAREHOUSE USING LNG COLD ENERGY

DESIGN ANALYSIS OF A REFRIGERATED WAREHOUSE USING LNG COLD ENERGY , Volume 4, Number 1, p.14-23, 2003 DESIGN ANALYSIS OF A REFRIGERATED WAREHOUSE USING LNG COLD ENERGY K.H. Yang and S.C. Wu Mechanical Engineering Department, National Sun Yat-Sen University, Kaohsiung,

More information

VARIABLE REFRIGERANT FLOW MULTI-SPLIT AIR-CONDITIONERS AND HEAT PUMPS CERTIFICATION PROGRAM

VARIABLE REFRIGERANT FLOW MULTI-SPLIT AIR-CONDITIONERS AND HEAT PUMPS CERTIFICATION PROGRAM VARIABLE REFRIGERANT FLOW MULTI-SPLIT AIR-CONDITIONERS AND HEAT PUMPS CERTIFICATION PROGRAM VRF OM JANUARY 2018 2111 Wilson Boulevard, Suite 500 Arlington, Virginia 22201 (703) 524-8800 Sponsored and administered

More information

Rajan Rajendran, Ph.D. Vice President Engineering Services And Sustainability

Rajan Rajendran, Ph.D. Vice President Engineering Services And Sustainability Promising Lower GWP Refrigerants In Air-Conditioning And Refrigeration Systems Rajan Rajendran, Ph.D. Vice President Engineering Services And Sustainability Agenda Landscape Of Promising Lower GWP Refrigerant

More information

Registration Number: Registration Date/Time: HERS Provider: CA Building Energy Efficiency Standards 2013 Residential Compliance June 2014

Registration Number: Registration Date/Time: HERS Provider: CA Building Energy Efficiency Standards 2013 Residential Compliance June 2014 STATE OF CALIFORNIA (Page 1 of 4) A. System Information Each system requiring refrigerant charge verification will be documented on a separate certificate. 01 System Identification or Name 02 System Location

More information

ME ENGINEERING THERMODYNAMICS UNIT III QUESTION BANK SVCET

ME ENGINEERING THERMODYNAMICS UNIT III QUESTION BANK SVCET 1. A vessel of volume 0.04m 3 contains a mixture of saturated water and steam at a temperature of 250 0 C. The mass of the liquid present is 9 kg. Find the pressure, mass, specific volume, enthalpy, entropy

More information

Field Performance Measurements of VRF System with Subcooling Heat Exchanger

Field Performance Measurements of VRF System with Subcooling Heat Exchanger Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 01 Field Performance Measurements of VRF System with Subcooling Heat Exchanger

More information

00 SYLLABUS (rev.01/6/2014)

00 SYLLABUS (rev.01/6/2014) Austin Community College Heating, Air Conditioning & Refrigeration Technology HART2449 HEAT PUMPS 00 SYLLABUS (rev.01/6/2014) Course Description: a study of heat pumps, heat pump control circuits, defrost

More information

DuPont Fluorochemicals. Athens, Greece May 23 rd, 2015

DuPont Fluorochemicals. Athens, Greece May 23 rd, 2015 Zero-ODP, Lower GWP, Non-lammable Refrigerants for Marine Applications: R-452A, R-449A, R-513A, R-1336mzz(Z) for improved sustainability and energy savings Konstantinos (Kostas) Kontomaris, Ph.D. Konstantinos.Kontomaris@DuPont.com

More information

Gregory W. Stevens and Ronald K. Ishii, Alternative Energy Systems Consulting, Inc.

Gregory W. Stevens and Ronald K. Ishii, Alternative Energy Systems Consulting, Inc. A Study of Optimizing the System Integration of Combined Heat and Power (CHP) with Absorption Cooling for Cold Storage Applications: Design Considerations, Modeling and Life Cycle Costing Gregory W. Stevens

More information

Chapter 9: Vapor Power Systems

Chapter 9: Vapor Power Systems Chapter 9: Vapor Power Systems Table of Contents Introduction... 2 Analyzing the Rankine Cycle... 4 Rankine Cycle Performance Parameters... 5 Ideal Rankine Cycle... 6 Example... 7 Rankine Cycle Including

More information

Value of Air Source Heat Pumps in Light of Variable Energy Prices. Jeff Haase. Energy Design Conference February 27, 2013

Value of Air Source Heat Pumps in Light of Variable Energy Prices. Jeff Haase. Energy Design Conference February 27, 2013 Value of Air Source Heat Pumps in Light of Variable Energy Prices Jeff Haase Energy Design Conference February 27, 2013 Agenda Overview of Air Source Heat Pump Technologies History, General Comparison

More information

a. The power required to drive the compressor; b. The inlet and output pipe cross-sectional area. [Ans: kw, m 2 ] [3.34, R. K.

a. The power required to drive the compressor; b. The inlet and output pipe cross-sectional area. [Ans: kw, m 2 ] [3.34, R. K. CHAPTER 2 - FIRST LAW OF THERMODYNAMICS 1. At the inlet to a certain nozzle the enthalpy of fluid passing is 2800 kj/kg, and the velocity is 50 m/s. At the discharge end the enthalpy is 2600 kj/kg. The

More information

Hydrocarbon Refrigerant Performance in UAE Air-Cooled Chillers

Hydrocarbon Refrigerant Performance in UAE Air-Cooled Chillers Hydrocarbon Refrigerant Performance in UAE Air-Cooled Chillers Peter Armstrong, Masdar Institute, October 2014 Research Sponsors: Tabreed Executive Affairs Authority 1 Motivation for Efficient Cooling

More information

Zero-ODP, Low GWP, Non-Flammable Working Fluid for Organic Rankine Cycles: HFO-1336mzz-Z

Zero-ODP, Low GWP, Non-Flammable Working Fluid for Organic Rankine Cycles: HFO-1336mzz-Z Reduce: Primary Energy Use Environmental Impact Zero-ODP, Low GWP, Non-lammable Working luid for Organic Rankine Cycles: HO-1336mzz-Z Kostas Kontomaris, Ph.D. DuPont luorochemicals Kobe, Japan November

More information

Performance Testing of Cold Climate Air Source Heat Pumps

Performance Testing of Cold Climate Air Source Heat Pumps Performance Testing of Cold Climate Air Source Heat Pumps Martin Kegel a*, Jeremy Sager b, Martin Thomas b, Daniel Giguere a, Roberto Sunye a a Natural Resources Canada, CanmetENERGY, 1615 Blvd Lionel

More information

Jones Residence Energy Cost Analysis

Jones Residence Energy Cost Analysis Jones Residence Energy Analysis for Mr. and Mrs. Joe Jones 1234 First Street Warmnister, Pa 18974 Prepared By: Jeffrey A. Smith J.A. Smith Heating & Air Cond Inc 360 Patricia Drive Warminster, Pa 18974

More information

01 Introduction TARGET. Multi Domestic. Commercial. 50, High Efficiency - High Efficiency Operation - Hot water with free of charge (HR)

01 Introduction TARGET. Multi Domestic. Commercial. 50, High Efficiency - High Efficiency Operation - Hot water with free of charge (HR) 01 Introduction TARGET POSITION FEATRE Multi Domestic EHS Mono/Split Low Temperature - Domestic, 50 water EHS High Temperature - Domestic, 80 water All-in-One More Efficient Free of Charge 50 or 80 Water

More information

Residential HVAC Field Verification and Diagnostics

Residential HVAC Field Verification and Diagnostics 2016 Title 24 Codes & Standards Enhancement (CASE) Proposal Residential HVAC Field Verification and Diagnostics Stakeholder Webinar, May 21 st, 2014 Farhad Farahmand, Cathy Chappell TRC Ffarahmand@TRCSolutions.com,

More information

Refrigeration System with Booster Hot Gas Bypass in Tropical Climate

Refrigeration System with Booster Hot Gas Bypass in Tropical Climate Journal of Physics: Conference Series PAPER OPEN ACCESS Simulation of Transcritical CO 2 Refrigeration System with Booster Hot Gas Bypass in Tropical Climate To cite this article: I D M C Santosa et al

More information

Copyright 2012 Neal D. Lawrence

Copyright 2012 Neal D. Lawrence Copyright 2012 Neal D. Lawrence ANALYTICAL AND EXPERIMENTAL INVESTIGATION OF TWO-PHASE EJECTOR CYCLES USING LOW-PRESSURE REFRIGERANTS BY NEAL D. LAWRENCE THESIS Submitted in partial fulfillment of the

More information

Performance Benefits for Organic Rankine Cycles with Flooded Expansion

Performance Benefits for Organic Rankine Cycles with Flooded Expansion Purdue University Purdue e-pubs Publications of the Ray W. Herrick Laboratories School of Mechanical Engineering 6-2-2010 Performance Benefits for Organic Rankine Cycles with Flooded Expansion Brandon

More information

Modeling and Investigation of Refrigeration System Performance with Two-Phase Fluid Injection in a Scroll Compressor

Modeling and Investigation of Refrigeration System Performance with Two-Phase Fluid Injection in a Scroll Compressor Marquette University e-publications@marquette Master's Theses (2009 -) Dissertations, Theses, and Professional Projects Modeling and Investigation of Refrigeration System Performance with Two-Phase Fluid

More information

Experimental Investigation on Heat Pump for Electric Vehicles with different refrigerant injection compressors

Experimental Investigation on Heat Pump for Electric Vehicles with different refrigerant injection compressors Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (25 ) 49 495 The 7 th International Conference on Applied Energy ICAE25 Experimental Investigation on Heat Pump for Electric Vehicles

More information

Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using Waste Heat

Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using Waste Heat HEFAT2012 9 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics 16 18 July 2012 Malta Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using

More information

Air Source Heat Pumps in the Commercial Market. Thursday, February 5, :00-10:30 a.m.

Air Source Heat Pumps in the Commercial Market. Thursday, February 5, :00-10:30 a.m. Air Source Heat Pumps in the Commercial Market Thursday, February 5, 2015 9:00-10:30 a.m. 1. Commercial Equipment Applications, Benefits, Limitations 2. Case Studies 3. Efficiency Vermont Technical & Financial

More information

MCG THERMODYNAMICS II. 22 April 2008 Page 1 of 7 Prof. W. Hallett

MCG THERMODYNAMICS II. 22 April 2008 Page 1 of 7 Prof. W. Hallett Faculté de génie Génie mécanique Faculty of Engineering Mechanical Engineering MCG2131 - THERMODYNAMICS II 22 April 2008 Page 1 of 7 Prof. W. Hallett Closed book. Non-programmable calculators only allowed.

More information

Figure Heat pump model validation in heating mode: power consumption percentage error between model and experiment

Figure Heat pump model validation in heating mode: power consumption percentage error between model and experiment Percent Error 20% 18% 16% 14% 12% 10% 8% 6% 4% 2% Deviation by Uncertainty Analysis RMS Error (10:00 AM -- 11:30 AM):12.1% 0% 9:07 9:50 10:33 11:16 12:00 Time Figure 7.30. Heat pump model validation in

More information

Exergy analysis of transcritical carbon dioxide refrigeration cycle with an expander

Exergy analysis of transcritical carbon dioxide refrigeration cycle with an expander Energy 30 (2005) 1162 1175 www.elsevier.com/locate/energy Exergy analysis of transcritical carbon dioxide refrigeration cycle with an expander Jun Lan Yang, Yi Tai Ma*, Min Xia Li, Hai Qing Guan Thermal

More information

K.S. Rawat 1, H. Khulve 2, A.K. Pratihar 3 1,3 Department of Mechanical Engineering, GBPUAT, Pantnagar , India

K.S. Rawat 1, H. Khulve 2, A.K. Pratihar 3 1,3 Department of Mechanical Engineering, GBPUAT, Pantnagar , India Thermodynamic Analysis of Combined ORC-VCR System Using Low Grade Thermal Energy K.S. Rawat 1, H. Khulve 2, A.K. Pratihar 3 1,3 Department of Mechanical Engineering, GBPUAT, Pantnagar-263145, India 2 Department

More information

ANALYSIS OF ABSORPTION REFRIGERATION SYSTEM WITH AMMONIA-WATER

ANALYSIS OF ABSORPTION REFRIGERATION SYSTEM WITH AMMONIA-WATER ANALYSIS OF ABSORPTION REFRIGERATION SYSTEM WITH AMMONIA-WATER Cavalcanti, Eduardo J. C., educanti@ufrnet.br Souza, Sandi I. S., sandi@ufrnet.br Fernandes, Artur M., arturmfernandes@hotmail.com Department

More information

Relevant parameters on the energy efficiency of closed refrigerated multideck display cases

Relevant parameters on the energy efficiency of closed refrigerated multideck display cases nd This paper is part of the Proceedings of the 2 International Conference on Energy Production and Management (EQ 2016) www.witconferences.com Relevant parameters on the energy efficiency of closed refrigerated

More information

R442A (RS-50) Features and uses of the R442A (RS-50) Lubricants TECHNICAL DATA SHEET. Barcelona Girona Madrid Zaragoza

R442A (RS-50) Features and uses of the R442A (RS-50) Lubricants TECHNICAL DATA SHEET.  Barcelona Girona Madrid Zaragoza SHEET R442A (RS-50) Features and uses of the R442A (RS-50) R442A (RS-50) is a non-flammable HFC blend with an ODP = 0 and low global warming potential (GWP), developed to comply with the new dictates laid

More information

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water

More information

Refrigeration Kylteknik

Refrigeration Kylteknik Värme- och strömningsteknik Thermal and flow engineering Refrigeration 424159.0 Kylteknik Ron Zevenhoven Exam 24-3-2017 4 questions, max. points = 4 + 6 + 10 + 10 = 30 All support material is allowed except

More information

Second Law of Thermodynamics

Second Law of Thermodynamics Second Law of Thermodynamics Content Heat engine and its efficiency. Reversible and irreversible processes. The Carnot machine. Kelvin Planck Statement. Refrigerator and Coefficient of Performance. Statement

More information

Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using Solar Energy

Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using Solar Energy Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 202 Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using

More information

Deployment of a New Series of Eco Turbo ETI Chillers

Deployment of a New Series of Eco Turbo ETI Chillers 56 Deployment of a New Series of Eco Turbo ETI Chillers KENJI UEDA *1 YASUSHI HASEGAWA *2 KAZUKI WAJIMA *3 MASAHARU NITTA *2 YASUHIRO KAMADA *1 AKIMASA YOKOYAMA *2 The use of inverters in heat source equipment

More information

EXTRA CREDIT OPPORTUNITY: Due end of day, Thursday, Dec. 14

EXTRA CREDIT OPPORTUNITY: Due end of day, Thursday, Dec. 14 EXRA CREDI OPPORUNIY: Due end of day, hursday, Dec. 4 his extra credit set of questions is an opportunity to improve your test scores (including an insurance policy for your final exam grade). here are

More information

PAPER-I (Conventional)

PAPER-I (Conventional) 1. a. PAPER-I (Conventional) 10 kg of pure ice at 10 ºC is separated from 6 kg of pure water at +10 O C in an adiabatic chamber using a thin adiabatic membrane. Upon rupture of the membrane, ice and water

More information

II. SYSTEM DESCRIPTION AND MATHEMATICAL MODELING

II. SYSTEM DESCRIPTION AND MATHEMATICAL MODELING Mathematical Modeling and Analysis of Absorption Refrigeration System Using Waste Heat of Diesel Genset Yashvir Singh 1*, Deepak Kumar 2, Ajay Kumar 3, Amneesh Singla 4 1,2,3,4 Mechanical Engineering,

More information

ACTIVA Rooftop. YKN2open. ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw. Nomenclature A R C 045 B B. Features

ACTIVA Rooftop. YKN2open. ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw. Nomenclature A R C 045 B B. Features ACTIVA Rooftop ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw YKN2open Features High efficiency EER and COP Low noise level All configurations: Cooling only, Cooling + gas, Heating, Heating +

More information

Thermodynamic Comparison of Organic Rankine Cycles Employing Liquid-Flooded Expansion or a Solution Circuit

Thermodynamic Comparison of Organic Rankine Cycles Employing Liquid-Flooded Expansion or a Solution Circuit Purdue University Purdue e-pubs CTRC Research Publications Cooling Technologies Research Center 2013 Thermodynamic Comparison of Organic Rankine Cycles Employing Liquid-Flooded Expansion or a Solution

More information

Ejector Expansion Refrigeration Systems

Ejector Expansion Refrigeration Systems Research Inventy: International Journal Of Engineering And Science Vol.5, Issue 2 (February 2015), PP 25-29 Issn (e): 2278-4721, Issn (p):2319-6483, www.researchinventy.com Ejector Expansion Refrigeration

More information

Case 7 Reciprocating Compressor

Case 7 Reciprocating Compressor Case 7 Reciprocating Compressor Copy Right By: Thomas T.S. Wan ) June 24, 2010 All Rights Reserved Case Background: 1.0 An inquiry is received from a customer asking for reciprocating compressor; the operating

More information

UNITARY SMALL AIR-CONDITIONERS AND AIR-SOURCE HEAT PUMPS (INCLUDES MIXED-MATCH COILS) (RATED BELOW 65,000 BTU/H) CERTIFICATION PROGRAM

UNITARY SMALL AIR-CONDITIONERS AND AIR-SOURCE HEAT PUMPS (INCLUDES MIXED-MATCH COILS) (RATED BELOW 65,000 BTU/H) CERTIFICATION PROGRAM UNITARY SMALL AIR-CONDITIONERS AND AIR-SOURCE HEAT PUMPS (INCLUDES MIXED-MATCH COILS) (RATED BELOW 65,000 BTU/H) CERTIFICATION PROGRAM USE AHRI OM JANUARY 2018 2111 Wilson Blvd, Suite 500 Arlington, Virginia

More information

W t. Strategy: We need to step through the equipments and figure out the inlets and outlets to allow us to calculate the work and heat terms.

W t. Strategy: We need to step through the equipments and figure out the inlets and outlets to allow us to calculate the work and heat terms. Problem et G 10.1 olution pring 00 YT ) A schematic of the Rankine cycle and representation on a T- diagram: 1 Boiler P 0 W p pump 0 P 0 Condenser turbine 0 4 C 475 o C Depends on your last name. The information

More information

Energy Savers: Air-Source Heat Pumps

Energy Savers: Air-Source Heat Pumps 1 of 5 4/25/2009 8:55 AM U.S. Department of Energy - Energy Efficiency and Renewable Energy Energy Savers Air-Source Heat Pumps An air-source heat pump can provide efficient heating and cooling for your

More information

COMPARISON OF ENERGY EFFICIENCY BETWEEN VARIABLE AND FIXED SPEED SCROLL COMPRESSORS IN REFRIGERATING SYSTEMS

COMPARISON OF ENERGY EFFICIENCY BETWEEN VARIABLE AND FIXED SPEED SCROLL COMPRESSORS IN REFRIGERATING SYSTEMS COMPARISON OF ENERGY EFFICIENCY BETWEEN VARIABLE AND FIXED SPEED SCROLL COMPRESSORS IN REFRIGERATING SYSTEMS A. BENAMER, D. CLODIC Ecole des Mines de Paris, Centre d Energétique, 6, bd Saint-Michel 75272

More information

Danfoss and Controls for CO2

Danfoss and Controls for CO2 Danfoss and Controls for CO2 CO 2 www.danfoss.com/foodretail Department (slide master) Optional text Date 1 Controllers for various CO2 applications Some examples of Danfoss controllers suited for CO2:

More information

Comparison of Different Gas Turbine Inlet Air Cooling Methods

Comparison of Different Gas Turbine Inlet Air Cooling Methods Comparison of Different Gas Turbine Inlet Air Cooling Methods Ana Paula P. dos Santos, Claudia R. Andrade and Edson L. Zaparoli International Science Index, Aerospace and Mechanical Engineering waset.org/publication/2686

More information

FLOWRATE DEPENDENT HEAT-PUMP MODEL

FLOWRATE DEPENDENT HEAT-PUMP MODEL Poster P.4.10-1 - FLOWRATE DEPENDENT HEAT-PUMP MODEL Andreas, Genkinger, dipl. Phys., Research Associate, University of Applied Sciences and Arts Northwestern Switzerland, School of Architecture, Civil

More information

Dept. of Ag. Eng. Texas A&M University College Station, TX

Dept. of Ag. Eng. Texas A&M University College Station, TX - ESL-HH-94-05-29 FIELD PERFORMANCE OF A GROUND-COUPLED HEAT PUMP IN ABILENE, TEXAS Monte Dobson Research Assistant Dept. of Mech. Eng. University of Illinois urban% IL Dennis L. O'Neal Associate Professor

More information

Liquid-Flooded Ericsson Power Cycle

Liquid-Flooded Ericsson Power Cycle Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 Liquid-Flooded Ericsson Power Cycle Nelson A. James Purdue University, United States

More information

Chapter 5: Thermodynamic Processes and Cycles

Chapter 5: Thermodynamic Processes and Cycles Chapter 5: Thermodynamic Processes and Cycles 5-6) This problem examines the Rankine heat engine introduced in Figure 5-5. Saturated steam at T = 250 C enters the turbine and the condenser operates at

More information

CyberMart A Whole-Building Simulation Model for Supermarkets

CyberMart A Whole-Building Simulation Model for Supermarkets CyberMart A Whole-Building Simulation Model for Supermarkets Div. of Applied Thermodynamics and Refrigeration Contents 1.- Introduction. 2.- CyberMart, Systems and Models. 3.- CyberMart. 4.- Evaluation

More information

EER & SEER AS PREDICTORS OF SEASONAL COOLING PERFORMANCE

EER & SEER AS PREDICTORS OF SEASONAL COOLING PERFORMANCE EER & SEER AS PREDICTORS OF SEASONAL COOLING PERFORMANCE Developed by: Southern California Edison Design & Engineering Services 6042 N. Irwindale Avenue, Suite B Irwindale, California 91702 December 15,

More information

PERFORMANCE STUDY OF SOLAR THERMAL BINARY POWER CYCLES

PERFORMANCE STUDY OF SOLAR THERMAL BINARY POWER CYCLES Jurnal Mekanikal December 2011, No 33, 56-69 PERFORMANCE STUDY OF SOLAR THERMAL BINARY POWER CYCLES Mohd Anas Md Amin and Farid Nasir Ani * Faculty of Mechanical Engineering, Universiti Teknologi Malaysia,

More information

Central Chiller Plants

Central Chiller Plants Central Chiller Plants Institute for Facilities Management New Orleans, LA January 18,2016 Course 319 Presenter: John Vucci Associate Director HVAC Systems University of Maryland College Park, Maryland

More information

Experimental study of an air-source heat pump for simultaneous heating and cooling - Part 1: Basic concepts and performance verification

Experimental study of an air-source heat pump for simultaneous heating and cooling - Part 1: Basic concepts and performance verification Experimental study of an air-source heat pump for simultaneous heating and cooling - Part 1: Basic concepts and performance verification Paul Byrne, Jacques Miriel, Yves Lénat To cite this version: Paul

More information

ScienceDirect. Compact hot water storage systems combining copper tube with high conductivity graphite and phase change materials

ScienceDirect. Compact hot water storage systems combining copper tube with high conductivity graphite and phase change materials Available online at www.sciencedirect.com ScienceDirect Energy Procedia 48 (2014 ) 423 430 SHC 2013, International Conference on Solar Heating and Cooling for Buildings and Industry September 23-25, 2013,

More information

CPRT SERIES 13 SEER PRODUCT SPECIFICATIONS. Split System Heat Pump. 2 to 5 Ton

CPRT SERIES 13 SEER PRODUCT SPECIFICATIONS. Split System Heat Pump. 2 to 5 Ton CPRT SERIES SEER Split System Heat Pump to Ton The CPRT split system heat pump is designed for ground-level or rooftop mount applications. Standard Features High-efficiency Copeland scroll compressor Louvered

More information

Enhancement on the Performance of Refrigeration System Using the Nano-Refrigerant

Enhancement on the Performance of Refrigeration System Using the Nano-Refrigerant Journal of Energy and Power Engineering 11 (2017) 237-243 doi: 10.17265/1934-8975/2017.04.004 D DAVID PUBLISHING Enhancement on the Performance of Refrigeration System Using the Nano-Refrigerant Qasim

More information

Comparative Heating Performances of Ground Source and Air Source Heat. Pump Systems for Residential Buildings in Shanghai

Comparative Heating Performances of Ground Source and Air Source Heat. Pump Systems for Residential Buildings in Shanghai Comparative Heating Performances of Ground Source and Air Source Heat Pump Systems for Residential Buildings in Shanghai Zhaohui Liu 1,2, Hongwei Tan 1,2,3* 1 School of Mechanical Engineering, Tongji University,

More information

Chapter 6 THE SECOND LAW OF THERMODYNAMICS

Chapter 6 THE SECOND LAW OF THERMODYNAMICS Thermodynamics: An Engineering Approach, 6 th Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2008 Chapter 6 THE SECOND LAW OF THERMODYNAMICS Copyright The McGraw-Hill Companies, Inc. Permission

More information

Product Catalog. Variable Refrigerant Flow (VRF) System VRF-PRC008C-EN. Air Source Heat Pump and Heat Recovery Outdoor Units.

Product Catalog. Variable Refrigerant Flow (VRF) System VRF-PRC008C-EN. Air Source Heat Pump and Heat Recovery Outdoor Units. Product Catalog Variable Refrigerant Flow (VRF) System Air Source Heat Pump and Heat Recovery Outdoor Units 4TVH/4TVR0072 0192 4TVH/4TVR0216 0528 Single Unit Modules Multi-Unit Modules January 2016 VRF-PRC008C-EN

More information

SHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT B.Tech. [SEM IV (ME-41, 42,43 & 44)] QUIZ TEST-1 (Session: )

SHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT B.Tech. [SEM IV (ME-41, 42,43 & 44)] QUIZ TEST-1 (Session: ) QUIZ TEST-1 Q.1. In a stage of an impulse turbine provided with a single row wheel, the mean diameter of the blade ring is 80cm and the speed of the rotation is 3000rpm. The steam issues from the nozzle

More information