Center for Environmental Energy Engineering Department of Mechanical Engineering University of Maryland College Park, MD
|
|
- Dorthy Copeland
- 6 years ago
- Views:
Transcription
1 System Drop-In and Soft Optimization Tests of R-40A Alternative Refrigerants in Split System Heat Pump Jan. 204 Abdullah Alabdulkarem, Radia Eldeeb, Yunho Hwang, Vikrant Aute, Reinhard Radermacher Center for Environmental Energy Engineering Department of Mechanical Engineering University of Maryland College Park, MD
2 Contents Objectives Schematic of test facility Test conditions Performance comparison of R40A vs. alternative refrigerants Simulation results Conclusions 2
3 Objectives Evaluate the performance of an air conditioner and a heat pump using low GWP refrigerants and compare the results against R40A Drop-in tested refrigerants are: R2 L4A D2Y60 Perform soft-optimized system tests to match the capacity to that of R40A
4 Properties of R40A and Low GWP Refrigerants Parameter Unit R40A R2 D2Y60 L4A Temperature C Sat. Vapor Pressure kpa Liquid Density kg/m Vapor Density kg/m Latent Heat kj/kg Liquid kj/(kg-k) Specific Heat Liquid Thermal mw/(m-k) Conductivity Temperature Glide K Liquid Viscosity µpa-s Significant thermophysical property differences 8.68 Vapor Viscosity µpa-s.7 between 2.7R40A 4and alternative refrigerants Vol. Cooling Capacity kj/m Critical Temperature C ct/h fg
5 Thermodynamic Model 40 o C condenser temperature and 0 o C evaporator temperature 70% compressor efficiency, 27. cm displacement volume o C superheat and 2 o C subcooling 2 6 Capacity (kw) 0 8 COP R40A R2 D2Y60 L4A R40A R2 D2Y60 L4A
6 Schematic of Test Facility 6
7 Heat Pump Unit Compressor Single Speed, Scroll Compressor Nominal Cooling Capacity Tons Rated SEER 4 Rated HSPF 8.7 Expansion Device TXV for Cooling / Orifice for Heating 7
8 Test Test ASHRAE Standard 6- and Extended Indoor Outdoor db ( o C) wb ( o C) db ( o C) wb ( o C) Operation Extended 46. Steady State Cooling A.4 Steady State Cooling B 26.7 NA Steady State Cooling C Steady State Cooling, Dry Coil D Cyclic Cooling, Dry Coil High Temp Steady State Heating High Temp Steady State Heating Low Temp Steady State Heating Extended NA Steady State Heating High Temp. Cyclic Cyclic Heating Frost Acc Steady State Defrost 8
9 Drop In Tests
10 Steady State Cooling Test Results R40A R2 D2Y60 L4A R40A R2 D2Y60 L4A Capacity (kw) COP 2 4 Extended A B C Extended Ref. vs. R40A R2 D2Y60 L4A Optimum Charge -% -% -% Avg. Cooling Capacity % -8% -7% Avg. Cooling COP -% -4% -% A B C 0
11 Steady State Heating Test Results. R40A R2 D2Y60 L4A. R40A R2 D2Y60 L4A. Capacity (kw) COP Extended Low Temp. High Temp. 2 High Temp.. Extended Low Temp. High Temp. 2 High Temp. Ref. vs. R40A R2 D2Y60 L4A Avg. Heating Capacity 4% -4% -% Avg. Heating COP -% -2% 2%
12 Drop In Tests Conclusions Charge reduction for all refrigerants compared to R40A R2 Capacity outperformed R40A COP can outperform R40A with optimized compressor D2Y60 Low COP and capacity Low discharge temperature L4A Capacity matched R40A for heating only COP matched R40A Highest values for SEER and HSPF compared to R40A 2
13 Soft Optimized Tests
14 Soft Optimized Tests Plan Refrigerants Challenge Soft- Optimization Tests Soft-Optimization (Long Term) R40A Baseline - TXV for Heating R2 D2Y60 Compressor outlet temp., Slight COP degradation Low capacity - TXV for Heating, Larger Compressor TXV for Heating, Optimized Compressor Optimized Heat Exchangers L4A Two-phase suction TXV for Heating Optimized Heat Exchangers 4
15 Steady State Cooling Test Results R40A D2Y60 Drop In D2Y60 Soft Opt 2 R40A D2Y60 Drop In D2Y60 Soft Opt 0 4 Capacity (kw) 8 7 COP Extended A B C Extended A B C
16 Steady State Heating Test Results R40A D2Y60 Drop In D2Y60 Soft Opt 4 R40A D2Y60 Drop In D2Y60 Soft Opt 2 4 Capacity (kw) COP Extended Low Temp. High Temp. 2 High Temp. Extended Low Temp. High Temp. 2 High Temp. 6
17 L4A Soft Optimized Tests 4 L4A Drop In L4A Soft Optimized 2 Superheat (K) Extended Low Temp. High Temp. 2 High Temp. 7
18 Steady State Heating Tests R40A L4A Drop In L4A Soft Optimized. R40A L4A Drop In L4A Soft Optimized Capacity (kw) COP Extended Low Temp. High Temp. 2 High Temp.. Extended Low Temp. High Temp. 2 High Temp. 8
19 Cyclic Heating Test R40A w/ Orifice L4A TXV Orifice Capacity (kw) 7 Capacity (kw) Time (min.) Heating- Power Air Side Consumption (kw-hr) (kw-hr) COP Heating Load Factor (HLF) Degradation Coefficient (C D ) HSPF R40A L4A Difference (%) Time (min.)
20 Simulation of Drop In Tests 20
21 System Model in VapCyc Condenser and evaporator are CoilDesigner components Compressor is 0 coefficient database compressor model 2
22 Numerical Capacity (kw) Numerical Capacity (kw) Numerical Capacity (kw) Preliminary Simulation Results R40A R2 D2Y60 L4A % Error Lines Experimental Capacity (kw) Experimental Capacity (kw) Experimental Capacity (kw) Cooling Tests Numerical COP Heating Tests Numerical COP Experimental COP Experimental COP 22
23 Conclusions Using larger compressor for D2Y60 enhanced capacity but deteriorated COP Using TXV for L4A enhanced HSPF without significant change in steady state test results Simulation predicted the experiments well except in low and extended heating tests 2
24 Questions/Comments? Thank you! 24
25 Frost Accumulation Test R40A w/ Orifice L4A w/ TXV 7 7 Capacity (kw) Heating-Air side (kw-hr) Average Heating Capacity (kw) COP R40A L4A Difference (%) Capacity (kw) Time (min.) Time (min.) 2
26 Cyclic Cooling Test R40A D2Y60 Soft Optimized Capacity (kw) 7 Capacity (kw) Time (min.) Time (min.) Cooling- Air Side (kw-hr) Power Consumption (kw-hr) COP Cooling Load Factor (CLF) Degradation Coefficient (CD) SEER R40A D2Y Difference (%)
27 Capacity (kw) 7 - Cyclic Heating Test R40A Time (min.) Heating- Power Air Side Consumption (kw-hr) (kw-hr) COP Heating Load Factor (HLF) Time (min.) Degradation Coefficient (C D ) HSPF R40A D2Y Difference (%) Capacity (kw) 7 - D2Y60 Soft Optimized
28 Refrigerant Temperature in A Test 0 R40A R2 D2Y60 L4A Temperature ( C) Compressor Suction Compressor Discharge Condenser Outlet Expansion Device Inlet Evaporator Inlet (Calculated) Evaporator Outlet 28
29 Compressor Discharge Temp. and Mass Flow Rate in Cooling Tests Discharge Temp. ( C) R40A R2 D2Y60 L4A Ref. Mass Flowrate (g/s) R40A R2 D2Y60 L4A 0 Extended A B C Extended Ref. vs. R40A R2 D2Y60 L4A Avg. Compressor Disch. Temp. 4 C -4 C 7 C Avg. Ref. Mass Flow Rate -% -6% -2% A B C 2
30 Compressor Efficiencies Isentropic Efficiency R40A R2 D2Y60 L4A Extended A B C Volumetric Efficiency R40A R2 D2Y60 L4A Extended Ref. vs. R40A R2 D2Y60 L4A Avg. Isentropic Efficiency -6.% -.8% -.% Avg. Volumetric Efficiency -4.4% 0.% -2.4% A B C
31 SEER and HSPF 4 2 SEER (Btu/W-hr) HSPF (Btu/W-hr) R40A R2 D2Y60 L4A Ref. vs. R40A R2 D2Y60 L4A Avg. SEER -.% -8.% -2.4% Avg. HSPF 2.8% 6.% 6.7%
Steady State And Transient Validation Of Heat Pumps Using Alternative Lower-GWP Refrigerants
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Steady State And Transient Validation Of Heat Pumps Using Alternative Lower-GWP
More informationArkema technical note. Forane 407A. The low-gwp and energy efficient alternative to R-404A and R-507A
Arkema technical note Forane 407A The low-gwp and energy efficient alternative to R-404A and R-507A The statements, technical information and recommendations contained herein are believed to be accurate
More informationInvestigation of New Low-GWP Refrigerants for Use in Two-Phase Evaporative Cooling of Electronics
Investigation of New Low-GWP Refrigerants for Use in Two-Phase Evaporative Cooling of Electronics Alexis Nicolette-Baker, Elizabeth Garr, Abhijit Sathe, and Steve O'Shaughnessey Precision Cooling Systems
More informationExperimental Investigation of Vapor Injected Compression for Cold Climate Heat Pumps ABSTRACT
2111, Page 1 Experimental Investigation of Vapor Injected Compression for Cold Climate Heat Pumps Christian K. BACH 1 *, Bernhard VETSCH 2, Eckhard A. GROLL 1, James E. BRAUN 1, W. Travis HORTON 1 1 Purdue
More informationAn Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 An Integrated Solution for Commercial AC Chillers Using Variable Speed
More informationa.k.a. David N. Shaw, P. E.
BOOSTED AIR-SOURCE HEAT PUMPS a.k.a. Ac adia By David N. Shaw, P. E. Chief Technolo gy O fficer Hallowell I nternational w w w.gotohallowell.com HALLOWELL WHITE WHITE PAPER PAPER Hallowell.International
More informationRobert Kebby February BUILDING BLOCKS OF THE FUTURE Commercial Refrigeration Applications
Robert Kebby February 2016 BUILDING BLOCKS OF THE FUTURE Commercial Refrigeration Applications Honeywell A History of Innovation CFCs HCFCs HFCs HFOs Very high ODP & GWP High ODP and GWP ODP=0, but high
More information2010 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment
ANSI/AHRI Standard 1230 with Addendum 2 2010 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment Approved by ANSI on 2 August 2010 ANSI/AHRI
More informationEnhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis Elias
More informationModeling of Air-Source Integrated Heat Pumps
2016 ACEEE Hot Water Forum Heating Water with Integrated Heat Pumps Modeling of Air-Source Integrated Heat Pumps -simulation-driven design Bo Shen, Keith Rice, Oak Ridge National Laboratory February 23,
More informationENHANCEMENT OF COEFFICIENT OF PERFORMANCE IN VAPOUR COMPRESSION REFRIGERATION CYCLE
ENHANCEMENT OF COEFFICIENT OF PERFORMANCE IN VAPOUR COMPRESSION REFRIGERATION CYCLE Dr Venkata Ramana Reddy Mula 1, H.V.Harish 2 1 Professor and Head, Department of Aeronautical Engineering NMIT BANGALORE
More informationPackaged Refrigerant Based Energy Storage (RBES) Air Conditioning System
Packaged Refrigerant Based Energy Storage (RBES) Air Conditioning System Ram Narayanamurthy Ice Energy, Inc. this technology provides some of the largest opportunities we have right now to address the
More informationUnitary Air Conditioner Field Performance
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2004 Unitary Air Conditioner Field Performance Todd M. Rossi Field Diagnostic
More informationHeating Performance with a Volume Ratio on 2-Stage Compressor
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Heating Performance with a Volume Ratio on 2-Stage Compressor Sangkyoung
More informationApplication of Viper Energy Recovery Expansion Device in Transcritical Carbon Dioxide Refrigeration Cycle
Abstract Application of Viper Energy Recovery Expansion Device in Transcritical Carbon Dioxide Refrigeration Cycle Riley B. Barta a *, Eckhard A. Groll b a Purdue University, School of Mechanical Engineering,
More informationALTERNATIVE REFRIGERANTS FOR BUILDING AIR CONDITIONING D. B. BIVENS ENGINEERING FELLOW DUPONT FLUOROPRODUCTS WLZMINGTON, DE.
ALTERNATIVE REFRIGERANTS FOR BUILDING AIR CONDITIONING D. B. BIVENS ENGINEERING FELLOW DUPONT FLUOROPRODUCTS WLZMINGTON, DE. ABSTRACT The majority of building air conditioning has traditionally been acheved
More informationEng Thermodynamics I: Sample Final Exam Questions 1
Eng3901 - Thermodynamics I: Sample Final Exam Questions 1 The final exam in Eng3901 - Thermodynamics I consists of four questions: (1) 1st Law analysis of a steam power cycle, or a vapour compression refrigeration
More informationSecondary Coolant Systems for Supermarkets
The following article was published in ASHRAE Journal, September 2006. Copyright 2006 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
More informationDesign and development of a residential gas-fired heat pump
Design and development of a residential gas-fired heat pump Edward A Vineyard a*, Ahmad Abu-Heiba a, Isaac Mahderekal b a Oak Ridge National Laboratory, P.O. Box 2008, MS 6070, Oak Ridge, TN, 37831, USA
More informationPerformance of a Combined Organic Rankine Cycle and Vapor Compression Cycle for Heat Activated Cooling
Performance of a Combined Organic Rankine Cycle and Vapor Compression Cycle for Heat Activated Cooling Hailei Wang*, Richard Peterson, Kevin Harada, Erik Miller, Robbie Ingram-Goble, Luke Fisher, James
More informationAn Investigation of R417a as a Drop-in Alternative for R22 in a Residential Heat Pump
An Investigation of R417a as a Drop-in Alternative for in a Residential Heat Pump Zhiming Gao *, Viung C Mei, Fang C Chen, John Tomlinson Oak Ridge National Laboratory, Oak Ridge, TN 37831-67 Heat pumps
More informationA Comprehensive Evaluation of Regression Uncertainty and the Effect of Sample Size on the AHRI-540 Method of Compressor Performance Representation
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2016 A Comprehensive Evaluation of Regression Uncertainty and the Effect of Sample Size
More informationInvestigations of N 2 O Transcritical Refrigeration Cycle Using Dedicated Mechanical Subcooling. Sanjeev Kumar 1 and Dr. D.K.
e t International Journal on Emerging Technologies (Special Issue NCETST-2017) 8(1): 340-344(2017) (Published by Research Trend, Website: www.researchtrend.net) ISSN No. (Print) : 0975-8364 ISSN No. (Online)
More informationEXPERIMENTAL STUDY ON THE REPLACEMENT OF HFC-R134A BY HYDROCARBONS MIXTURE IN AUTOMOTIVE AIR CONDITIONER. Skudai, Johor, Malaysia 81310
International Journal of Technology (2013) 1: 81-92 ISSN 2086-9614 IJTech 2013 EXPERIMENTAL STUDY ON THE REPLACEMENT OF HFC-R134A BY HYDROCARBONS MIXTURE IN AUTOMOTIVE AIR CONDITIONER Mohd Rozi Mohd Perang
More information1st October Robert Kebby Marketing Manager
1st October 2014 Robert Kebby Marketing Manager Why R-404A? Success of R404A over the last 15 to 20 years - Replaced ODP products such as R12 / R502 & more recently R22 - Marketed well as a one solution
More informationHELICAL OIL SEPARATORS
OIL SEPARATORS HELICAL OIL SEPARATORS The function of a Helical Oil Separator is to efficiently remove oil from the discharge gas and return it to the compressor, either directly or indirectly. This helps
More informationBTO s Heat Pump Research Efforts
BTO s Heat Pump Research Efforts Antonio M Bouza antonio.bouza@ee.doe.gov March 22, 2016 Outline BTO Ecosystem Introduction Cold Climate Heat Pump Research Projects Heat Exchangers Future Technologies
More informationPerformance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Performance Comparison of Air-source Heat Pumps Using Economizer Vapor
More informationLecture No.3. The Ideal Reheat Rankine Cycle
Lecture No.3 The Ideal Reheat Rankine Cycle 3.1 Introduction We noted in the last section that increasing the boiler pressure increases the thermal efficiency of the Rankine cycle, but it also increases
More informationCOOLING EFFECTIVENESS OF MIST PRECOOLER FOR IMPROVING ENERGY PERFORMANCE OF AIR-COOLED CHILLER
Yu, F. W., et al.: Cooling Effectiveness of Mist Precooler for THERMAL SCIENCE: Year 2018, Vol. 22, No. 1A, pp. 193-204 193 COOLING EFFECTIVENESS OF MIST PRECOOLER FOR IMPROVING ENERGY PERFORMANCE OF AIR-COOLED
More informationUNIT NO-03 [8 hrs] Second Law Of Thermodynamics: Introduction (Law of degradation of energy), Thermal energy reservoirs, Kelvin-Plank & Clausius
UNIT NO-03 [8 hrs] Second Law Of Thermodynamics: Introduction (Law of degradation of energy), Thermal energy reservoirs, Kelvin-Plank & Clausius statements, Heat engines, Refrigerator and Heat pump, Perpetual
More informationHPC 2017 Performance simulation and exergy analysis on multi-stage compression high temperature heat pumps with R1234ze(Z) refrigerant
Performance simulation and exergy analysis on multi-stage compression high temperature heat pumps with R1234ze(Z) refrigerant Bin Hu, Di Wu, R.Z. Wang Institute of Refrigeration and Cryogenics Shanghai
More informationOUTCOME 2 TUTORIAL 2 STEADY FLOW PLANT
UNIT 47: Engineering Plant Technology Unit code: F/601/1433 QCF level: 5 Credit value: 15 OUTCOME 2 TUTORIAL 2 STEADY FLOW PLANT 2 Be able to apply the steady flow energy equation (SFEE) to plant and equipment
More informationDresden, Germany ABSTRACT MODELING OF THE CHILLER INTRODUCTION
Eleventh International IBPSA Conference Glasgow Scotland July 27-3 29 TESTING AND VALIDATION OF SIMULATION TOOLS OF HVAC MECHANICAL EQUIPMENT INCLUDING THEIR CONTROL STRATEGIES PART III: VALIDATION OF
More informationDESIGN ANALYSIS OF A REFRIGERATED WAREHOUSE USING LNG COLD ENERGY
, Volume 4, Number 1, p.14-23, 2003 DESIGN ANALYSIS OF A REFRIGERATED WAREHOUSE USING LNG COLD ENERGY K.H. Yang and S.C. Wu Mechanical Engineering Department, National Sun Yat-Sen University, Kaohsiung,
More informationVARIABLE REFRIGERANT FLOW MULTI-SPLIT AIR-CONDITIONERS AND HEAT PUMPS CERTIFICATION PROGRAM
VARIABLE REFRIGERANT FLOW MULTI-SPLIT AIR-CONDITIONERS AND HEAT PUMPS CERTIFICATION PROGRAM VRF OM JANUARY 2018 2111 Wilson Boulevard, Suite 500 Arlington, Virginia 22201 (703) 524-8800 Sponsored and administered
More informationRajan Rajendran, Ph.D. Vice President Engineering Services And Sustainability
Promising Lower GWP Refrigerants In Air-Conditioning And Refrigeration Systems Rajan Rajendran, Ph.D. Vice President Engineering Services And Sustainability Agenda Landscape Of Promising Lower GWP Refrigerant
More informationRegistration Number: Registration Date/Time: HERS Provider: CA Building Energy Efficiency Standards 2013 Residential Compliance June 2014
STATE OF CALIFORNIA (Page 1 of 4) A. System Information Each system requiring refrigerant charge verification will be documented on a separate certificate. 01 System Identification or Name 02 System Location
More informationME ENGINEERING THERMODYNAMICS UNIT III QUESTION BANK SVCET
1. A vessel of volume 0.04m 3 contains a mixture of saturated water and steam at a temperature of 250 0 C. The mass of the liquid present is 9 kg. Find the pressure, mass, specific volume, enthalpy, entropy
More informationField Performance Measurements of VRF System with Subcooling Heat Exchanger
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 01 Field Performance Measurements of VRF System with Subcooling Heat Exchanger
More information00 SYLLABUS (rev.01/6/2014)
Austin Community College Heating, Air Conditioning & Refrigeration Technology HART2449 HEAT PUMPS 00 SYLLABUS (rev.01/6/2014) Course Description: a study of heat pumps, heat pump control circuits, defrost
More informationDuPont Fluorochemicals. Athens, Greece May 23 rd, 2015
Zero-ODP, Lower GWP, Non-lammable Refrigerants for Marine Applications: R-452A, R-449A, R-513A, R-1336mzz(Z) for improved sustainability and energy savings Konstantinos (Kostas) Kontomaris, Ph.D. Konstantinos.Kontomaris@DuPont.com
More informationGregory W. Stevens and Ronald K. Ishii, Alternative Energy Systems Consulting, Inc.
A Study of Optimizing the System Integration of Combined Heat and Power (CHP) with Absorption Cooling for Cold Storage Applications: Design Considerations, Modeling and Life Cycle Costing Gregory W. Stevens
More informationChapter 9: Vapor Power Systems
Chapter 9: Vapor Power Systems Table of Contents Introduction... 2 Analyzing the Rankine Cycle... 4 Rankine Cycle Performance Parameters... 5 Ideal Rankine Cycle... 6 Example... 7 Rankine Cycle Including
More informationValue of Air Source Heat Pumps in Light of Variable Energy Prices. Jeff Haase. Energy Design Conference February 27, 2013
Value of Air Source Heat Pumps in Light of Variable Energy Prices Jeff Haase Energy Design Conference February 27, 2013 Agenda Overview of Air Source Heat Pump Technologies History, General Comparison
More informationa. The power required to drive the compressor; b. The inlet and output pipe cross-sectional area. [Ans: kw, m 2 ] [3.34, R. K.
CHAPTER 2 - FIRST LAW OF THERMODYNAMICS 1. At the inlet to a certain nozzle the enthalpy of fluid passing is 2800 kj/kg, and the velocity is 50 m/s. At the discharge end the enthalpy is 2600 kj/kg. The
More informationHydrocarbon Refrigerant Performance in UAE Air-Cooled Chillers
Hydrocarbon Refrigerant Performance in UAE Air-Cooled Chillers Peter Armstrong, Masdar Institute, October 2014 Research Sponsors: Tabreed Executive Affairs Authority 1 Motivation for Efficient Cooling
More informationZero-ODP, Low GWP, Non-Flammable Working Fluid for Organic Rankine Cycles: HFO-1336mzz-Z
Reduce: Primary Energy Use Environmental Impact Zero-ODP, Low GWP, Non-lammable Working luid for Organic Rankine Cycles: HO-1336mzz-Z Kostas Kontomaris, Ph.D. DuPont luorochemicals Kobe, Japan November
More informationPerformance Testing of Cold Climate Air Source Heat Pumps
Performance Testing of Cold Climate Air Source Heat Pumps Martin Kegel a*, Jeremy Sager b, Martin Thomas b, Daniel Giguere a, Roberto Sunye a a Natural Resources Canada, CanmetENERGY, 1615 Blvd Lionel
More informationJones Residence Energy Cost Analysis
Jones Residence Energy Analysis for Mr. and Mrs. Joe Jones 1234 First Street Warmnister, Pa 18974 Prepared By: Jeffrey A. Smith J.A. Smith Heating & Air Cond Inc 360 Patricia Drive Warminster, Pa 18974
More information01 Introduction TARGET. Multi Domestic. Commercial. 50, High Efficiency - High Efficiency Operation - Hot water with free of charge (HR)
01 Introduction TARGET POSITION FEATRE Multi Domestic EHS Mono/Split Low Temperature - Domestic, 50 water EHS High Temperature - Domestic, 80 water All-in-One More Efficient Free of Charge 50 or 80 Water
More informationResidential HVAC Field Verification and Diagnostics
2016 Title 24 Codes & Standards Enhancement (CASE) Proposal Residential HVAC Field Verification and Diagnostics Stakeholder Webinar, May 21 st, 2014 Farhad Farahmand, Cathy Chappell TRC Ffarahmand@TRCSolutions.com,
More informationRefrigeration System with Booster Hot Gas Bypass in Tropical Climate
Journal of Physics: Conference Series PAPER OPEN ACCESS Simulation of Transcritical CO 2 Refrigeration System with Booster Hot Gas Bypass in Tropical Climate To cite this article: I D M C Santosa et al
More informationCopyright 2012 Neal D. Lawrence
Copyright 2012 Neal D. Lawrence ANALYTICAL AND EXPERIMENTAL INVESTIGATION OF TWO-PHASE EJECTOR CYCLES USING LOW-PRESSURE REFRIGERANTS BY NEAL D. LAWRENCE THESIS Submitted in partial fulfillment of the
More informationPerformance Benefits for Organic Rankine Cycles with Flooded Expansion
Purdue University Purdue e-pubs Publications of the Ray W. Herrick Laboratories School of Mechanical Engineering 6-2-2010 Performance Benefits for Organic Rankine Cycles with Flooded Expansion Brandon
More informationModeling and Investigation of Refrigeration System Performance with Two-Phase Fluid Injection in a Scroll Compressor
Marquette University e-publications@marquette Master's Theses (2009 -) Dissertations, Theses, and Professional Projects Modeling and Investigation of Refrigeration System Performance with Two-Phase Fluid
More informationExperimental Investigation on Heat Pump for Electric Vehicles with different refrigerant injection compressors
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (25 ) 49 495 The 7 th International Conference on Applied Energy ICAE25 Experimental Investigation on Heat Pump for Electric Vehicles
More informationSupersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using Waste Heat
HEFAT2012 9 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics 16 18 July 2012 Malta Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using
More informationAir Source Heat Pumps in the Commercial Market. Thursday, February 5, :00-10:30 a.m.
Air Source Heat Pumps in the Commercial Market Thursday, February 5, 2015 9:00-10:30 a.m. 1. Commercial Equipment Applications, Benefits, Limitations 2. Case Studies 3. Efficiency Vermont Technical & Financial
More informationMCG THERMODYNAMICS II. 22 April 2008 Page 1 of 7 Prof. W. Hallett
Faculté de génie Génie mécanique Faculty of Engineering Mechanical Engineering MCG2131 - THERMODYNAMICS II 22 April 2008 Page 1 of 7 Prof. W. Hallett Closed book. Non-programmable calculators only allowed.
More informationFigure Heat pump model validation in heating mode: power consumption percentage error between model and experiment
Percent Error 20% 18% 16% 14% 12% 10% 8% 6% 4% 2% Deviation by Uncertainty Analysis RMS Error (10:00 AM -- 11:30 AM):12.1% 0% 9:07 9:50 10:33 11:16 12:00 Time Figure 7.30. Heat pump model validation in
More informationExergy analysis of transcritical carbon dioxide refrigeration cycle with an expander
Energy 30 (2005) 1162 1175 www.elsevier.com/locate/energy Exergy analysis of transcritical carbon dioxide refrigeration cycle with an expander Jun Lan Yang, Yi Tai Ma*, Min Xia Li, Hai Qing Guan Thermal
More informationK.S. Rawat 1, H. Khulve 2, A.K. Pratihar 3 1,3 Department of Mechanical Engineering, GBPUAT, Pantnagar , India
Thermodynamic Analysis of Combined ORC-VCR System Using Low Grade Thermal Energy K.S. Rawat 1, H. Khulve 2, A.K. Pratihar 3 1,3 Department of Mechanical Engineering, GBPUAT, Pantnagar-263145, India 2 Department
More informationANALYSIS OF ABSORPTION REFRIGERATION SYSTEM WITH AMMONIA-WATER
ANALYSIS OF ABSORPTION REFRIGERATION SYSTEM WITH AMMONIA-WATER Cavalcanti, Eduardo J. C., educanti@ufrnet.br Souza, Sandi I. S., sandi@ufrnet.br Fernandes, Artur M., arturmfernandes@hotmail.com Department
More informationRelevant parameters on the energy efficiency of closed refrigerated multideck display cases
nd This paper is part of the Proceedings of the 2 International Conference on Energy Production and Management (EQ 2016) www.witconferences.com Relevant parameters on the energy efficiency of closed refrigerated
More informationR442A (RS-50) Features and uses of the R442A (RS-50) Lubricants TECHNICAL DATA SHEET. Barcelona Girona Madrid Zaragoza
SHEET R442A (RS-50) Features and uses of the R442A (RS-50) R442A (RS-50) is a non-flammable HFC blend with an ODP = 0 and low global warming potential (GWP), developed to comply with the new dictates laid
More informationApplication of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water
More informationRefrigeration Kylteknik
Värme- och strömningsteknik Thermal and flow engineering Refrigeration 424159.0 Kylteknik Ron Zevenhoven Exam 24-3-2017 4 questions, max. points = 4 + 6 + 10 + 10 = 30 All support material is allowed except
More informationSecond Law of Thermodynamics
Second Law of Thermodynamics Content Heat engine and its efficiency. Reversible and irreversible processes. The Carnot machine. Kelvin Planck Statement. Refrigerator and Coefficient of Performance. Statement
More informationStudy on Ejector - Vapor Compression Hybrid Air Conditioning System Using Solar Energy
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 202 Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using
More informationDeployment of a New Series of Eco Turbo ETI Chillers
56 Deployment of a New Series of Eco Turbo ETI Chillers KENJI UEDA *1 YASUSHI HASEGAWA *2 KAZUKI WAJIMA *3 MASAHARU NITTA *2 YASUHIRO KAMADA *1 AKIMASA YOKOYAMA *2 The use of inverters in heat source equipment
More informationEXTRA CREDIT OPPORTUNITY: Due end of day, Thursday, Dec. 14
EXRA CREDI OPPORUNIY: Due end of day, hursday, Dec. 4 his extra credit set of questions is an opportunity to improve your test scores (including an insurance policy for your final exam grade). here are
More informationPAPER-I (Conventional)
1. a. PAPER-I (Conventional) 10 kg of pure ice at 10 ºC is separated from 6 kg of pure water at +10 O C in an adiabatic chamber using a thin adiabatic membrane. Upon rupture of the membrane, ice and water
More informationII. SYSTEM DESCRIPTION AND MATHEMATICAL MODELING
Mathematical Modeling and Analysis of Absorption Refrigeration System Using Waste Heat of Diesel Genset Yashvir Singh 1*, Deepak Kumar 2, Ajay Kumar 3, Amneesh Singla 4 1,2,3,4 Mechanical Engineering,
More informationACTIVA Rooftop. YKN2open. ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw. Nomenclature A R C 045 B B. Features
ACTIVA Rooftop ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw YKN2open Features High efficiency EER and COP Low noise level All configurations: Cooling only, Cooling + gas, Heating, Heating +
More informationThermodynamic Comparison of Organic Rankine Cycles Employing Liquid-Flooded Expansion or a Solution Circuit
Purdue University Purdue e-pubs CTRC Research Publications Cooling Technologies Research Center 2013 Thermodynamic Comparison of Organic Rankine Cycles Employing Liquid-Flooded Expansion or a Solution
More informationEjector Expansion Refrigeration Systems
Research Inventy: International Journal Of Engineering And Science Vol.5, Issue 2 (February 2015), PP 25-29 Issn (e): 2278-4721, Issn (p):2319-6483, www.researchinventy.com Ejector Expansion Refrigeration
More informationCase 7 Reciprocating Compressor
Case 7 Reciprocating Compressor Copy Right By: Thomas T.S. Wan ) June 24, 2010 All Rights Reserved Case Background: 1.0 An inquiry is received from a customer asking for reciprocating compressor; the operating
More informationUNITARY SMALL AIR-CONDITIONERS AND AIR-SOURCE HEAT PUMPS (INCLUDES MIXED-MATCH COILS) (RATED BELOW 65,000 BTU/H) CERTIFICATION PROGRAM
UNITARY SMALL AIR-CONDITIONERS AND AIR-SOURCE HEAT PUMPS (INCLUDES MIXED-MATCH COILS) (RATED BELOW 65,000 BTU/H) CERTIFICATION PROGRAM USE AHRI OM JANUARY 2018 2111 Wilson Blvd, Suite 500 Arlington, Virginia
More informationW t. Strategy: We need to step through the equipments and figure out the inlets and outlets to allow us to calculate the work and heat terms.
Problem et G 10.1 olution pring 00 YT ) A schematic of the Rankine cycle and representation on a T- diagram: 1 Boiler P 0 W p pump 0 P 0 Condenser turbine 0 4 C 475 o C Depends on your last name. The information
More informationEnergy Savers: Air-Source Heat Pumps
1 of 5 4/25/2009 8:55 AM U.S. Department of Energy - Energy Efficiency and Renewable Energy Energy Savers Air-Source Heat Pumps An air-source heat pump can provide efficient heating and cooling for your
More informationCOMPARISON OF ENERGY EFFICIENCY BETWEEN VARIABLE AND FIXED SPEED SCROLL COMPRESSORS IN REFRIGERATING SYSTEMS
COMPARISON OF ENERGY EFFICIENCY BETWEEN VARIABLE AND FIXED SPEED SCROLL COMPRESSORS IN REFRIGERATING SYSTEMS A. BENAMER, D. CLODIC Ecole des Mines de Paris, Centre d Energétique, 6, bd Saint-Michel 75272
More informationDanfoss and Controls for CO2
Danfoss and Controls for CO2 CO 2 www.danfoss.com/foodretail Department (slide master) Optional text Date 1 Controllers for various CO2 applications Some examples of Danfoss controllers suited for CO2:
More informationComparison of Different Gas Turbine Inlet Air Cooling Methods
Comparison of Different Gas Turbine Inlet Air Cooling Methods Ana Paula P. dos Santos, Claudia R. Andrade and Edson L. Zaparoli International Science Index, Aerospace and Mechanical Engineering waset.org/publication/2686
More informationFLOWRATE DEPENDENT HEAT-PUMP MODEL
Poster P.4.10-1 - FLOWRATE DEPENDENT HEAT-PUMP MODEL Andreas, Genkinger, dipl. Phys., Research Associate, University of Applied Sciences and Arts Northwestern Switzerland, School of Architecture, Civil
More informationDept. of Ag. Eng. Texas A&M University College Station, TX
- ESL-HH-94-05-29 FIELD PERFORMANCE OF A GROUND-COUPLED HEAT PUMP IN ABILENE, TEXAS Monte Dobson Research Assistant Dept. of Mech. Eng. University of Illinois urban% IL Dennis L. O'Neal Associate Professor
More informationLiquid-Flooded Ericsson Power Cycle
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 Liquid-Flooded Ericsson Power Cycle Nelson A. James Purdue University, United States
More informationChapter 5: Thermodynamic Processes and Cycles
Chapter 5: Thermodynamic Processes and Cycles 5-6) This problem examines the Rankine heat engine introduced in Figure 5-5. Saturated steam at T = 250 C enters the turbine and the condenser operates at
More informationCyberMart A Whole-Building Simulation Model for Supermarkets
CyberMart A Whole-Building Simulation Model for Supermarkets Div. of Applied Thermodynamics and Refrigeration Contents 1.- Introduction. 2.- CyberMart, Systems and Models. 3.- CyberMart. 4.- Evaluation
More informationEER & SEER AS PREDICTORS OF SEASONAL COOLING PERFORMANCE
EER & SEER AS PREDICTORS OF SEASONAL COOLING PERFORMANCE Developed by: Southern California Edison Design & Engineering Services 6042 N. Irwindale Avenue, Suite B Irwindale, California 91702 December 15,
More informationPERFORMANCE STUDY OF SOLAR THERMAL BINARY POWER CYCLES
Jurnal Mekanikal December 2011, No 33, 56-69 PERFORMANCE STUDY OF SOLAR THERMAL BINARY POWER CYCLES Mohd Anas Md Amin and Farid Nasir Ani * Faculty of Mechanical Engineering, Universiti Teknologi Malaysia,
More informationCentral Chiller Plants
Central Chiller Plants Institute for Facilities Management New Orleans, LA January 18,2016 Course 319 Presenter: John Vucci Associate Director HVAC Systems University of Maryland College Park, Maryland
More informationExperimental study of an air-source heat pump for simultaneous heating and cooling - Part 1: Basic concepts and performance verification
Experimental study of an air-source heat pump for simultaneous heating and cooling - Part 1: Basic concepts and performance verification Paul Byrne, Jacques Miriel, Yves Lénat To cite this version: Paul
More informationScienceDirect. Compact hot water storage systems combining copper tube with high conductivity graphite and phase change materials
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 48 (2014 ) 423 430 SHC 2013, International Conference on Solar Heating and Cooling for Buildings and Industry September 23-25, 2013,
More informationCPRT SERIES 13 SEER PRODUCT SPECIFICATIONS. Split System Heat Pump. 2 to 5 Ton
CPRT SERIES SEER Split System Heat Pump to Ton The CPRT split system heat pump is designed for ground-level or rooftop mount applications. Standard Features High-efficiency Copeland scroll compressor Louvered
More informationEnhancement on the Performance of Refrigeration System Using the Nano-Refrigerant
Journal of Energy and Power Engineering 11 (2017) 237-243 doi: 10.17265/1934-8975/2017.04.004 D DAVID PUBLISHING Enhancement on the Performance of Refrigeration System Using the Nano-Refrigerant Qasim
More informationComparative Heating Performances of Ground Source and Air Source Heat. Pump Systems for Residential Buildings in Shanghai
Comparative Heating Performances of Ground Source and Air Source Heat Pump Systems for Residential Buildings in Shanghai Zhaohui Liu 1,2, Hongwei Tan 1,2,3* 1 School of Mechanical Engineering, Tongji University,
More informationChapter 6 THE SECOND LAW OF THERMODYNAMICS
Thermodynamics: An Engineering Approach, 6 th Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2008 Chapter 6 THE SECOND LAW OF THERMODYNAMICS Copyright The McGraw-Hill Companies, Inc. Permission
More informationProduct Catalog. Variable Refrigerant Flow (VRF) System VRF-PRC008C-EN. Air Source Heat Pump and Heat Recovery Outdoor Units.
Product Catalog Variable Refrigerant Flow (VRF) System Air Source Heat Pump and Heat Recovery Outdoor Units 4TVH/4TVR0072 0192 4TVH/4TVR0216 0528 Single Unit Modules Multi-Unit Modules January 2016 VRF-PRC008C-EN
More informationSHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT B.Tech. [SEM IV (ME-41, 42,43 & 44)] QUIZ TEST-1 (Session: )
QUIZ TEST-1 Q.1. In a stage of an impulse turbine provided with a single row wheel, the mean diameter of the blade ring is 80cm and the speed of the rotation is 3000rpm. The steam issues from the nozzle
More information