Attachment 1: RAE Corporation Technical Specification

Size: px
Start display at page:

Download "Attachment 1: RAE Corporation Technical Specification"

Transcription

1 Attachment 1: RAE Corporation Technical Specification

2 RAE Corporation Phone: , ext. 105 Steve Corbin Quote# XXXX Qty Customer Tag Technical Systems Model Number 1 ACC-4 10A0-162-S General Scope of Work does not Include: 1. Labor warranty. 2. Service or maintenance agreement. 3. Compliance to plans and specifications. 4. Re-connection of wires, pipe or sheet metal at any shipping split. 5. Lifting or rigging of the unit. 6. Unit base frame isolation springs or mounting 7. Startup services 8. Refrigerant Charge and POE oil General Scope of Supply RAE Corporation self-contained unit in general accordance with the enclosed reference to drawings, plans and specifications provided to Seller, and more particularly described in a Submittal to be prepared by Seller and approved by the Customer. 1. Freight to first destination. 2. ETL and UL labeled equipment. 3. 5k SCCR rated electrical panel. Page 1 of 5

3 University of N. Florida Model 10A0-162-S (Special) Qty (1) Unit Design Conditions Ambient: 95 F DB Refrigerant: R-407C Differential temperature: 25 F # of Circuits: 3 Performance (per chiller) Actual Full Load Capacity: 2,088,918 at design conditions (12-FPI, 0% subcooling Circuit) Unit Dimensional Data (per chiller) Overall Dimensions: 96 W x 264 L x 75 H Est. Shipping Weight: 5,800 lbs. Number of Sections: 1 Est. Operating Weight: -- Weight of Heaviest Section: 5,800 lbs. Electrical (per ACCU) Controls Power Supply: Qty (1) 460/60/3 RLA each: 36 MCA each: 37 SCCR: 5,000 amps MOCP each: 40 Controls Type: Electromechanical Relay BMS Communication: None Control Voltage: 115/60/1 Page 2 of 5

4 Features, Options, and Accessories Standard Features: Dry nitrogen shipping charge MP05 Painted Cabinet Enamel o TSI Grey MP01 NEMA 3R panel with UL 508 label ETL Certified unit label Fan contactors o For control by others o Fans controlled in groups as in original project o Individual fan fusing Coil guards to protect vertical coils MG13 Grills o Plastic coated 2 x 2 opening wire grills for personnel protection (3) independent refrigerant circuits Electrical Accessories: ET02 Control Circuit transformer build same as PR foot print same as existing equipment field verify refrigerant circuits Refrigerant connections and electrical connections, as close to original locations as possible Page 3 of 5

5 Partial List of Contractor Responsibilities *The following notes are not all inclusive and are not intended to relieve the installing contractor if its responsibilities. By providing this document, we do not accept any responsibility for the proper installation or operation of the equipment General Inspection and acceptance of freight delivery at rigging yard to ensure the equipment has not been bent, twisted, or damaged during shipping, rigging, or installation. Performance of a refrigerant & oil leak check upon initial acceptance of delivery Accounting of all ship loose parts received and stored as per the manufacturer s instructions Check tightness and torque of all electrical connections loosened in transit Additional transport, storage, or offloading of equipment after initial acceptance of delivery Protection and proper storage of equipment and repair of damage from improper storage and handling Provision and installation of external unit vibration isolation, external support steel, or curbs as required Installation of equipment with adequate room for safe startup and service access as well as sufficient airflow supply as to prevent the risk of recirculation of air. Provide technicians to perform startup of the equipment with supervision and training by factory personnel. Complete any additional tasks set forth by the RAE Corporation Startup Checklist two weeks before scheduling of the factory technicians. Any additional responsibilities contained in the specification documents Electrical and Controls Integration Provisions and installation of main 3 phase power connection to each chiller with the proper voltage and connection quantity according to the approved submittal documents and power draw of the chiller Provision of separate control power connection if control transformer is not provided by manufacturer. Installation and termination of all interconnecting wiring noted on the manufacturers wiring diagrams The BMS contractor must have obtained and read the relevant publications from the manufacturer pertaining to whichever protocol he will use before attempting to read / write points to the equipment controller Ensure that the BMS contractor is complete in all aspects of his communication and submit any questions to the manufacturer well in advance of startup. Hardwire connection between standalone chiller controller and building management system. (Applies only if the appropriate BACnet, or Modbus gateway has been furnished by TSI) Fluid Piping Provisions and installation of Supply/Return fluid connections, and any required water makeup and drain connections according to the approved submittal documents. For Evaporative Condenser products, the installing contractor must provide water makeup piping sized to provide the maximum design condenser water makeup rate at a pressure between PSIG. Inadequate supply may result in loss of capacity and / or safety trips. Flushing, filling, cleaning, and pressure testing of the fluid system with the correct type and quantity of glycol as well as completion of flow balancing in all lines prior to date of startup. Installation and wiring of required control valves not provided by manufacturer. Installation and wiring of any noted ship loose parts provided by the manufacturer and installed per their recommendations. Ensure any chilled fluid bypass valves are not located near the refrigeration system. Refrigerant Piping (split systems) Reconnection and installation of refrigerant piping following ASHRAE and industry standards for refrigerant line sizes, trap selection for vertical risers, pitch of horizontal lines, etc Pressure testing of 24 hours with dry nitrogen followed by full evacuation to 500 microns to ensure a leak free and moisture free system. The vacuum must be broken with the system refrigerant. Provision and installation of the required refrigerant and oil according to the proper type and quantity of charge required for proper operation. Page 4 of 5

Architect s Project Number of 5 Decentralized HVAC Equipment District Master Specs 2013 Edition

Architect s Project Number of 5 Decentralized HVAC Equipment District Master Specs 2013 Edition PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 23 81 00 DECENTRALIZED HVAC EQUIPMENT A. The other Contract Documents complement the requirements of this section. The General requirements apply to the work

More information

SECTION COOLING TOWER

SECTION COOLING TOWER PART 1 GENERAL 1.1 SECTION INCLUDES A. Mechanical induced draft Cooling Tower B. Controls C. Ladder and handrails 1.2 REFERENCES SECTION 23 65 00 COOLING TOWER A. ANSI/AFBMA 9 - Load Rating and Fatigue

More information

SECTION AIR COILS

SECTION AIR COILS SECTION 23 82 16 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

START-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician:

START-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician: START-UP INSTRUCTION SERIES 20 J**YC/YD 90000 To 300000 BTU S SPLIT SYSTEM CONDENSING UNITS 7.5 To 25 TON START-UP CHECKLIST Date: _ Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial

More information

MUSC Psychiatric Hospital CRI Air-Cooled Chiller Replacement Project

MUSC Psychiatric Hospital CRI Air-Cooled Chiller Replacement Project MUSC Psychiatric Hospital CRI Air-Cooled Chiller Replacement Project H51-9832-FW-A ADDENDUM NO. 01 The following items shall take precedence over the drawings and specifications for the above named project

More information

SECTION to 5000 AMPERE PLUG-IN AND FEEDER BUSWAYS - SPECTRA. A. Low-Voltage Plug-in Busway to 5000 ampere, 600 VAC

SECTION to 5000 AMPERE PLUG-IN AND FEEDER BUSWAYS - SPECTRA. A. Low-Voltage Plug-in Busway to 5000 ampere, 600 VAC PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Low-Voltage Plug-in Busway - 225 to 5000 ampere, 600 VAC 1.02 RELATED

More information

CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH

CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH Rev. 1.3 HVAC Guide Specifications Chilled and Hot Water Universal Mount Fan Coil 2-Pipe Nominal Size: 60,000

More information

MINNESOTA STATE SECTION ADVERTISEMENT FOR BIDS

MINNESOTA STATE SECTION ADVERTISEMENT FOR BIDS MINNESOTA STATE SECTION 00 11 13 ADVERTISEMENT FOR BIDS Sealed Bids for: will be received by: Ridgewater College Commercial Chiller Purchase Ridgewater College Willmar Campus 2101 15 th Ave. N.W Willmar,

More information

SECTION PACKAGED, SUBMERSIBLE SEWERAGE PUMP UNITS

SECTION PACKAGED, SUBMERSIBLE SEWERAGE PUMP UNITS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 22 13 33 PACKAGED, SUBMERSIBLE SEWERAGE PUMP UNITS SPEC WRITER NOTES: 1. Delete between //----// if not applicable to project. Also delete any other item or paragraph

More information

SECTION PACKAGED, SUBMERSIBLE, DRAINAGE PUMP UNITS

SECTION PACKAGED, SUBMERSIBLE, DRAINAGE PUMP UNITS SECTION 22 14 36 PACKAGED, SUBMERSIBLE, DRAINAGE PUMP UNITS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also delete any other item or paragraph

More information

T-Series SPLIT SYSTEM UNITS TSA R-410A - 60 HZ

T-Series SPLIT SYSTEM UNITS TSA R-410A - 60 HZ REFRIGERANT CONDENSERS Guide Specifications T-Series SPLIT SYSTEM UNITS TSA R-410A - 60 HZ September 5, 2012 Note: This Specification is for Allied Commercial T-Series 6- to 20-ton, outdoor air conditioner

More information

SECTION GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT

SECTION GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT SECTION 23 05 12 GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. Also delete

More information

SECTION ROTARY SCREW WATER CHILLERS

SECTION ROTARY SCREW WATER CHILLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

Central Station Air Handler Specification

Central Station Air Handler Specification Central Station Air Handler Specification PART 1: GENERAL 1.01 WORK INCLUDED (Model CS 3 ) Mechanical Specification A. Provide complete air handling unit(s) suitable for indoor installation. Contractor

More information

Wilo MC Self Priming, Horizontal Multi-Stage, High Pressure Pumps. Engineering Specification

Wilo MC Self Priming, Horizontal Multi-Stage, High Pressure Pumps. Engineering Specification Wilo MC Self Priming, Horizontal Multi-Stage, High Pressure Pumps Engineering Specification PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install horizontal multi-stage, high pressure, self priming pressure

More information

Air Cooled Condensing Units - Technical Catalog. Featuring Bitzer TM Compressors 404A and 507 Refrigerants

Air Cooled Condensing Units - Technical Catalog. Featuring Bitzer TM Compressors 404A and 507 Refrigerants N SERIES Air Cooled Condensing Units - Technical Catalog Featuring Bitzer TM s 404A and 507 Refrigerants 4492 Hunt St - Pryor, OK 74361-918.825.7222 - Fax 800.264.5329 - www.century-refrigeration.com Standard

More information

A. Section includes busway and fittings including plug-in units.

A. Section includes busway and fittings including plug-in units. SECTION 26 25 00 ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes busway and fittings including plug-in units. 1.2 REFERENCES A. Institute of Electrical and Electronics Engineers:

More information

Installation Instructions

Installation Instructions Installation Instructions AquaSnap 010-055 Chilled Water Storage Tank 50/60 Hz Part No: -900---001; -900---009; -900---010 CONTENTS INTRODUCTION.................................. 1 SAFETY CONSIDERATIONS......................

More information

B. System Design and Performance Requirements

B. System Design and Performance Requirements 15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 23 74 13 PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

MRI Chiller Installation Guidelines

MRI Chiller Installation Guidelines MRI Chiller Installation Guidelines *These Items are the responsibility of the installing contractor to complete prior to the startup of the MRI Chiller.* **Please refer to DTS chiller manual for further

More information

OAKDALE CHILLED WATER PLANT CAPACITY UPGRADES UI PROJECT INSTALL CHILLERS SECTION COMMISSIONING

OAKDALE CHILLED WATER PLANT CAPACITY UPGRADES UI PROJECT INSTALL CHILLERS SECTION COMMISSIONING PART I GENERAL 1.01 SECTION INCLUDES A. Commissioning objectives. B. Roles and responsibilities. C. Test Equipment. D. Systems to be commissioned. E. Construction Checklist requirements. SECTION 01 91

More information

PRICE AW-D PACKAGED OUTDOOR HEATING AND COOLING MAKE-UP AIR UNITS

PRICE AW-D PACKAGED OUTDOOR HEATING AND COOLING MAKE-UP AIR UNITS PRICE AW-D PACKAGED OUTDOOR HEATING AND COOLING MAKE-UP AIR UNITS Division 23 Heating, Ventilating, and Air Conditioning Section 23 75 33 Custom-Packaged, Outdoor, Heating and Cooling Makeup Air-Conditioners

More information

FROST TOP - WF SERIES

FROST TOP - WF SERIES FROST TOP - WF SERIES Service and Installation Manual Please read this manual completely before attempting to install or operate this equipment! Notify carrier of damage! Inspect all components immediately.

More information

DAT Commercial ELECTRIC AIR HANDLERS FOR 7½ & 10-TON SPLIT SYSTEMS

DAT Commercial ELECTRIC AIR HANDLERS FOR 7½ & 10-TON SPLIT SYSTEMS DAT Commercial ELECTRIC AIR HANDLERS F 7½ & 0-TON SPLIT SYSTEMS Contents Nomenclature... Product Specifications... Airflow Data... Heating Kit Data...6 Dimensions...7 Wiring Diagrams...8 Standard Features

More information

GUC LNG Facility Phase IIB Expansion 6/20/14 INSTRUMENTATION SPECIFICATION. A. This Section includes instrumentation for process piping systems.

GUC LNG Facility Phase IIB Expansion 6/20/14 INSTRUMENTATION SPECIFICATION. A. This Section includes instrumentation for process piping systems. INSTRUMENTATION SPECIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

SECTION ENCLOSED BUS ASSEMBLIES

SECTION ENCLOSED BUS ASSEMBLIES SECTION 262500 ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Low Voltage Switchgear Construction Checklist (under 500 kva)

Low Voltage Switchgear Construction Checklist (under 500 kva) Low Voltage Switchgear Checklist (under 500 kva) Project: Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

SECTION FUEL-FIRED UNIT HEATERS

SECTION FUEL-FIRED UNIT HEATERS SECTION 23 55 33 PART 1 - GENERAL 1.1 DESCRIPTION A. This Section includes gas-fired unit heaters. SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable

More information

"SRMZ" ROOFTOP PACKAGED MULTIZONE UNITS Self Contained Single Package Units 17.5 to 43 Ton Cooling Capacities

SRMZ ROOFTOP PACKAGED MULTIZONE UNITS Self Contained Single Package Units 17.5 to 43 Ton Cooling Capacities "SRMZ" ROOFTOP PACKAGED MULTIZONE UNITS Self Contained Single Package Units 17.5 to 43 Ton Cooling Capacities Packaged Rooftop Multizone shall be Spinnaker Industries Inc. Model Series SRMZ. Units shall

More information

- 1 - InfraStruXure InRow SC Assembly and Start-Up. Installation Service

- 1 - InfraStruXure InRow SC Assembly and Start-Up. Installation Service Installation Service - 1 - InfraStruXure InRow SC Assembly and Start-Up Statement of Work 1.0 Executive Summary InfraStruXure InRow SC Assembly & Start-Up Service Table of Contents 1.0 Executive Summary

More information

Air Cooled Condensing Units - Technical Catalog. Featuring Copeland TM Compressors 404A and 507 Refrigerants

Air Cooled Condensing Units - Technical Catalog. Featuring Copeland TM Compressors 404A and 507 Refrigerants N SERIES Air Cooled Condensing Units - Technical Catalog Featuring Copeland TM s 0A and 507 Refrigerants 9 Hunt St - Pryor, OK 736-98.85.7 - Fax 800.6.539 - www.century-refrigeration.com Standard Features

More information

Copyright 2004 and 2005 by The American Institute of Architects (AIA)

Copyright 2004 and 2005 by The American Institute of Architects (AIA) Page 232500-1 Copyright 2004 and 2005 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical

More information

Pump Specifications 450 Series 1/2 hp Submersible Sump Pump

Pump Specifications 450 Series 1/2 hp Submersible Sump Pump Pump Specifications 450 Series 1/2 hp Submersible Sump Pump 450_P1 R1/27/2012 Copyright 2012 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice. 450-Series Dimensional

More information

TARRANT COUNTY PURCHASING DEPARTMENT

TARRANT COUNTY PURCHASING DEPARTMENT JACK BEACHAM, C.P.M., A.P.P. PURCHASING AGENT TARRANT COUNTY PURCHASING DEPARTMENT JANUARY 24, 2017 BID NO. 2017-064 ADDENDUM #1 ROB COX, C.P.M., A.P.P. ASSISTANT PURCHASING AGENT TARRANT COUNTY DICK ANDERSEN

More information

WATER-COOLED HELICAL ROTARY CHILLER

WATER-COOLED HELICAL ROTARY CHILLER WATER-COOLED HELICAL ROTARY CHILLER 1.0 GENERAL REQUIREMENTS 1.1 Application. This technical specification applies to equipment and materials furnished and installation work performed by the Contractor.

More information

MRI Chiller Installation Guidelines

MRI Chiller Installation Guidelines MRI Chiller Installation Guidelines *These Items are the responsibility of the installing contractor to complete prior to the startup of the MRI Chiller.* **Please refer to DTS chiller manual for further

More information

Robert E. McMains Date Robert E. McMains Date

Robert E. McMains Date Robert E. McMains Date DESIGN AND CONSTRUCTION STANDARDS Title: Section 230923 Direct-Digital Control System for HVAC & Mechanical Author: Author: Date Active Version Distribution: Date Approved By: Approved By: Robert E. McMains

More information

Bid Package 15A Mechanical

Bid Package 15A Mechanical Bid Package 23A Mechanical & HVAC The successful Subcontractor acknowledges and agrees to the requirements set forth by this bid package and its descriptions and in conjunction with all other Construction

More information

SECTION AIR TERMINAL UNITS

SECTION AIR TERMINAL UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

EFFICIENT 13 SEER 3 PHASE AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT. Nominal Btu/hr. Min. Circuit Ampacity 18.

EFFICIENT 13 SEER 3 PHASE AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT. Nominal Btu/hr. Min. Circuit Ampacity 18. ENVIRONMENTALLY SOUND REFRIGERANT H4A3 Product Specifications EFFICIENT 13 SEER 3 PHASE AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 3 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 3 phase, 60 Hz

More information

Zehnder Carboline Radiant Heating and Cooling Ceiling Panels. Installation, Operation and Maintenance. Cooling Fresh Air Clean Air

Zehnder Carboline Radiant Heating and Cooling Ceiling Panels. Installation, Operation and Maintenance. Cooling Fresh Air Clean Air Zehnder Carboline Radiant Heating and Cooling Ceiling Panels Installation, Operation and Maintenance Heating Cooling Fresh Air Clean Air ii General information 1 Safety considerations 1 Unpacking and preparation

More information

SECTION AIR-TO-AIR ENERGY RECOVERY EQUIPMENT

SECTION AIR-TO-AIR ENERGY RECOVERY EQUIPMENT SECTION 23 72 00 AIR-TO-AIR ENERGY RECOVERY EQUIPMENT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SUGGESTED SPECIFICATION for Low Voltage (600V) Generator Paralleling Switchboard

SUGGESTED SPECIFICATION for Low Voltage (600V) Generator Paralleling Switchboard SUGGESTED SPECIFICATION for Low Voltage (600V) Generator Paralleling Switchboard PART 1 GENERAL 1.1 Scope A. The intent of this specification is to provide power control for the parallel operation of generator

More information

The factory assembled air handler shall conform to the requirements outlined ASHRAE 90.1.

The factory assembled air handler shall conform to the requirements outlined ASHRAE 90.1. PAGE 1 of 5 1.1. REFERENCE STANDARDS 1.1.1. The factory assembled air handler shall conform to the requirements outlined ASHRAE 90.1. 1.1.2. Unit shall be designed to conform to ASHRAE 15. 1.1.3. Unit

More information

MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 9,000 BTUH. Rev. 1.3

MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 9,000 BTUH. Rev. 1.3 MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil Heat / Cool Fan Coil 9,000 BTUH Rev. 1.3 HVAC Guide Specifications Chilled and Hot Water Hi-Wall Fan Coil 2-Pipe Nominal Size: 9,000 BTUH Multiaqua Model

More information

MHWW-18-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 18,000 BTUH. Rev. 1.3

MHWW-18-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 18,000 BTUH. Rev. 1.3 MHWW-18-H-1 Chilled/Hot Water Hi-Wall Fan Coil Heat / Cool Fan Coil 18,000 BTUH Rev. 1.3 HVAC Guide Specifications Chilled and Hot Water Hi-Wall Fan Coil 2-Pipe Nominal Size: 18,000 BTUH Multiaqua Model

More information

MHWW-12-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 12,000 BTUH. Rev. 1.3

MHWW-12-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 12,000 BTUH. Rev. 1.3 MHWW-12-H-1 Chilled/Hot Water Hi-Wall Fan Coil Heat / Cool Fan Coil 12,000 BTUH Rev. 1.3 HVAC Guide Specifications Chilled and Hot Water Hi-Wall Fan Coil 2-Pipe Nominal Size: 12,000 BTUH Multiaqua Model

More information

Product Catalog Split System Air Conditioners Odyssey

Product Catalog Split System Air Conditioners Odyssey Product Catalog Split System Air Conditioners Odyssey R-22 Dry Charge CoolingCondenser 7.5, 10, 15 and 20 Tons 60 Hz July 2018 SS-PRC037J-EN Introduction Wide network availability Flexible applications

More information

Unit Substation Transformer Construction Checklist (under 500 kva)

Unit Substation Transformer Construction Checklist (under 500 kva) Unit Substation Transformer Checklist (under 500 kva) Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

Midlands Technical College Wade Martin Chiller Replacement State Project No.: H59-N975-FW

Midlands Technical College Wade Martin Chiller Replacement State Project No.: H59-N975-FW Midlands Technical College Wade Martin Chiller Replacement State Project No.: H59-N975-FW Midlands Technical College 316 South Beltline Blvd Columbia, SC 29205 https://www.midlandstech.edu/procurement

More information

C o u n t y o f F a i r f a x, V i r g i n i a

C o u n t y o f F a i r f a x, V i r g i n i a 001961 Page 2 C o u n t y o f F a i r f a x, V i r g i n i a A D D E N D U M DATE: August 2, 2016 ADDENDUM NO. 4 TO: REFERENCE: FOR: DUE DATE/TIME: ALL PROSPECTIVE BIDDERS Government Center Generator System

More information

2. Water Pressure Booster Systems. 3. Duplex Pedestal Type Sump Pumps.

2. Water Pressure Booster Systems. 3. Duplex Pedestal Type Sump Pumps. PART 1: GENERAL 1.01 Purpose: A. The design guidelines contained herein includes the requirements for pumps utilized for plumbing systems at Texas State University. It is the intention of this document

More information

Special Specification 6292 Radar Vehicle Detection System for Signalized Intersection Control

Special Specification 6292 Radar Vehicle Detection System for Signalized Intersection Control Special Specification 6292 Radar Vehicle Detection System for Signalized Intersection Control 1. DESCRIPTION 2. MATERIALS Furnish, install, relocate, or remove radar vehicle detection systems (RVDS) of

More information

10, 20 AND 30 RT S-SERIES SERIES WATER FIRED SINGLE-EFFECT EFFECT ABSORPTION CHILLER / CHILLER-HEATER

10, 20 AND 30 RT S-SERIES SERIES WATER FIRED SINGLE-EFFECT EFFECT ABSORPTION CHILLER / CHILLER-HEATER GUIDE SPECIFICATIONS 10, 20 AND 30 RT S-SERIES SERIES WATER FIRED SINGLE-EFFECT EFFECT ABSORPTION CHILLER / CHILLER-HEATER HEATER 1. General Description The Contractor shall furnish and install (Qty) Yazaki

More information

ADDENDUM #1. This Addendum forms a part of the Contract Documents and modifies the Bidding Documents, with amendments and additions noted below.

ADDENDUM #1. This Addendum forms a part of the Contract Documents and modifies the Bidding Documents, with amendments and additions noted below. Rome-Floyd Health Dept. HVAC Upgrades 00410 1 ADDENDUM #1 DATE: Sept. 25, 2014 PROJECT: Rome-Floyd Health Dept. HVAC Upgrades OWNER: Floyd County, GA ENGINEER: Drinkard Engineering Group, Inc. TO: All

More information

Outdoor Enclosure. Installation, Operation and Maintenance Manual

Outdoor Enclosure. Installation, Operation and Maintenance Manual Outdoor Enclosure Installation, Operation and Maintenance Manual f r o m t h e H u m i d i f i c a t i o n E x p e r t s Ta b l e o f c o n t e n t s General information Product overview...3 Dimensions,

More information

University of Delaware

University of Delaware SECTION 22 05 00_COMMON WORK FOR PLUMBING SYSTEM University Contact: Energy & Engineering Group (302) 831-1744 Part 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Start up 2. Factory Training 3. Quality

More information

SECTION MOTOR CONTROL CENTER

SECTION MOTOR CONTROL CENTER SECTION 16445 MOTOR CONTROL CENTER PART 1 GENERAL 1.01 DESCRIPTION A. This section covers the contract item Motor Control Center (MCC). The contract item includes demolition and removal of existing MCC;

More information

SECTION CHEMICAL FEED SYSTEM

SECTION CHEMICAL FEED SYSTEM SECTION 11800 PART 1 GENERAL 1.1 SUMMARY A. This section includes the requirements for the chemical feed system shall be a complete turnkey system inclusive of all necessary fluid handling and ancillary

More information

.2 Section Waste Management and Disposal..4 Section Vibration Isolation and Seismic Control Measures.

.2 Section Waste Management and Disposal..4 Section Vibration Isolation and Seismic Control Measures. Issued 2005/05/16 Section 15641 Cooling Towers Induced Draft Crossflow Page 1 of 5 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK THE FLORIDA DEPARTMENT OF TRANSPORTATION, DISTRICT 4 HEADQUARTERS BUILDING ROOF TOP AIR CONDITIONING CONDENSER COIL REPLACEMENTS TABLE OF CONTENTS 1.0 Purpose 2.0 Definitions 3.0

More information

SECTION ULTRASONIC TRANSIT TIME CLAMP-ON FLOW MEASURING SYSTEM

SECTION ULTRASONIC TRANSIT TIME CLAMP-ON FLOW MEASURING SYSTEM SECTION 40 71 66 ULTRASONIC TRANSIT TIME CLAMP-ON FLOW MEASURING SYSTEM PART 1-GENERAL 1.01 SUMMARY A. Ultrasonic clamp-on flow measurement system designed for non-intrusive external to pipe measurement

More information

PROJECT TITLE PROJECT NO.: CONTRACT TITLE UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

PROJECT TITLE PROJECT NO.: CONTRACT TITLE UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA PRE-START-UP/START-UP CHECKLIST CHILLED WATER SYSTEM NOTE: University s Representative must be notified and scheduled to witness test prior to any start up of equipment. A. Chilled Water Pumps 1. Submittal

More information

A. This Section includes the following sump pumps and accessories, inside the building, for building storm drainage systems:

A. This Section includes the following sump pumps and accessories, inside the building, for building storm drainage systems: SECTION 221429 - SUMP PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

KPHE20 SERIES WATER-TO-AIR HEAT EXCHANGER

KPHE20 SERIES WATER-TO-AIR HEAT EXCHANGER Keep This Manual With Heat Exchanger Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents KPHE20 SERIES WATER-TO-AIR HEAT EXCHANGER

More information

A. The work consists of furnishing a Chiller Noise Reduction System as listed in the specifications.

A. The work consists of furnishing a Chiller Noise Reduction System as listed in the specifications. SECTION 32 31 14 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply

More information

Houston First Corporation Package 1 SECTION MEDIUM VOLTAGE FUSED SWITCH INTERRUPTER

Houston First Corporation Package 1 SECTION MEDIUM VOLTAGE FUSED SWITCH INTERRUPTER PART 1 - GENERAL 1.1 SUMMARY SECTION 26 13 16 MEDIUM VOLTAGE FUSED SWITCH INTERRUPTER A. The scope of this section includes providing and assembling materials and equipment for the dead-front, medium voltage

More information

SUPERSTEAM USG LINE UNFIRED STEAM GENERATOR. Humidification. Sterilization. Pharmaceutical

SUPERSTEAM USG LINE UNFIRED STEAM GENERATOR. Humidification. Sterilization. Pharmaceutical SUPERSTEAM USG LINE UNFIRED STEAM GENERATOR. Humidification. Sterilization. Pharmaceutical Basic USG Package Includes: ASME Code Constructed and National Board Registered Vessel Fiberglass Insulation 20

More information

Product Catalog. Odyssey Split System Heat Pumps R-22 Dry Charge 7½ - 20 Ton, 60 Hz SSP-PRC027-EN. June 2012

Product Catalog. Odyssey Split System Heat Pumps R-22 Dry Charge 7½ - 20 Ton, 60 Hz SSP-PRC027-EN. June 2012 Product Catalog Odyssey Split System Heat Pumps R-22 Dry Charge 7½ - 20 Ton, 60 Hz June 2012 SSP-PRC027-EN General Data Table 1. General Data 7½ - 20 Ton Condensing Units 60 Hz 7½ Tons 10 Tons 15 Tons

More information

McQuay. Air Cooled Condensing Unit. ALP Vintage D. Last Manufactured: Replacement Parts List No Revision E 09/2016

McQuay. Air Cooled Condensing Unit. ALP Vintage D. Last Manufactured: Replacement Parts List No Revision E 09/2016 Replacement Parts List No. 057115300 Revision E 09/2016 McQuay Air Cooled Condensing Unit ALP 012-019 Vintage D Last Manufactured: 2002 To find your Daikin Applied parts distributor, call 1-800-377-2787

More information

WATER-FIRED SINGLE-EFFECT ABSORPTION CHILLER

WATER-FIRED SINGLE-EFFECT ABSORPTION CHILLER INSTALLATION INSTRUCTIONS WFC-SC5 WATER-FIRED SINGLE-EFFECT ABSORPTION CHILLER This product is a water-fired single-effect absorption unit which provides chilled water for cooling in central plant type

More information

PIKES PEAK PARKING RESTORATION TABLE OF CONTENTS

PIKES PEAK PARKING RESTORATION TABLE OF CONTENTS 23 HEATING, VENTILATING AND AIR CONDITIONING TABLE OF CONTENTS TABLE OF CONTENTS DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING - Basic HVAC Requirements 238239.19 - Wall and Ceiling Unit Heaters

More information

SECTION 15A AIR CONDITIONING

SECTION 15A AIR CONDITIONING SECTION 15A AIR CONDITIONING 1. SCOPE This Section covers the air conditioning (AC) system for the Electrical Room as indicated on the Contract Drawings and specified herein. 2. GENERAL The Contractor

More information

SPECIAL SPECIFICATION 8772 Border Safety Inspection Facility Transponder Reader System

SPECIAL SPECIFICATION 8772 Border Safety Inspection Facility Transponder Reader System 2004 Specifications CSJ 0921-02-173 SPECIAL SPECIFICATION 8772 Border Safety Inspection Facility Transponder Reader System 1. Description. Furnish, install and test Transponder Reader System consisting

More information

FXV. Closed Circuit Cooling Towers. Closed Circuit Cooling Towers. Product Detail FXV - C 1. Engineering Data FXV Models... C2

FXV. Closed Circuit Cooling Towers. Closed Circuit Cooling Towers. Product Detail FXV - C 1. Engineering Data FXV Models... C2 - C 1 Product Detail Engineering Data Models... C2 Structural Support Models... C6 Engineering Specifications... C8 - C 2 Engineering Data Models REMARK: Do not use for construction. Refer to factory certified

More information

SPECIAL SPECIFICATION 6683 Border Safety Inspection Facility Transponder Reader System

SPECIAL SPECIFICATION 6683 Border Safety Inspection Facility Transponder Reader System 2004 Specifications CSJ 0922-00-025 SPECIAL SPECIFICATION 6683 Border Safety Inspection Facility Transponder Reader System 1. Description. Furnish, install and test Transponder Reader System consisting

More information

AMCOT COOLING TOWER CORPORATION LRC-H & LRC-LNS CROSS FLOW COOLING TOWER OPERATIONS AND MAINTAINENCE MANUAL

AMCOT COOLING TOWER CORPORATION LRC-H & LRC-LNS CROSS FLOW COOLING TOWER OPERATIONS AND MAINTAINENCE MANUAL AMCOT COOLING TOWER CORPORATION LRC-H & LRC-LNS CROSS FLOW COOLING TOWER 1. Preface OPERATIONS AND MAINTAINENCE MANUAL 1-800-444-8693 Operation and Maintenance Manual For Amcot LRC-H Cooling Tower & LRC-LNS

More information

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466 BUSWAY LOW VOLTAGE (POW-R-WAY III) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein

More information

POWER TRANSFORMER INSTALLATION

POWER TRANSFORMER INSTALLATION Project Procedure POWER TRANSFORMER INSTALLATION No.: P-6.2-8-1 07/20/2011 PAGE 1 OF 6 1.0 PURPOSE The purpose of this procedure is to ensure that power transformer installations are accomplished in compliance

More information

SECTION ENCLOSED BUS ASSEMBLIES

SECTION ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

SECTION SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION

SECTION SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION SECTION 16-372 SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION 1. GENERAL SPECIFICATIONS The work of this Section includes furnishing all labor, equipment, materials (unless specifically identified as Owner-furnished)

More information

SPECIAL SPECIFICATION 8783 Border Safety Inspection Facility Transponder Reader System

SPECIAL SPECIFICATION 8783 Border Safety Inspection Facility Transponder Reader System 2004 Specifications CSJ 0921-02-173 SPECIAL SPECIFICATION 8783 Border Safety Inspection Facility Transponder Reader System 1. Description. Furnish, install and test Transponder Reader System consisting

More information

ADDENDUM 1. Repair and Maintenance of Landfill Gas Chiller System. Return date: Bid must be received no later than 2:00 PM, Monday, June 25, 2018

ADDENDUM 1. Repair and Maintenance of Landfill Gas Chiller System. Return date: Bid must be received no later than 2:00 PM, Monday, June 25, 2018 ADDENDUM 1 Date: June 13, 2018 Bid No.: Title: 18-11/AL Repair and Maintenance of Landfill Gas Chiller System Return date: Bid must be received no later than 2:00 PM, Monday, June 25, 2018 This Addendum

More information

EXHIBIT A SCOPE OF SERVICES DISTRICT FOUR HEADQUARTERS BUILDING ROOF TOP AIR CONDITIONING CONDENSER COIL REPLACEMENTS TABLE OF CONTENTS

EXHIBIT A SCOPE OF SERVICES DISTRICT FOUR HEADQUARTERS BUILDING ROOF TOP AIR CONDITIONING CONDENSER COIL REPLACEMENTS TABLE OF CONTENTS EXHIBIT A SCOPE OF SERVICES DISTRICT FOUR HEADQUARTERS BUILDING ROOF TOP AIR CONDITIONING CONDENSER COIL REPLACEMENTS TABLE OF CONTENTS 1.0 Purpose 2.0 Definitions 3.0 Vendors Qualifications/Certifications

More information

FACILITIES BUILDING STANDARDS

FACILITIES BUILDING STANDARDS FACILITIES BUILDING STANDARDS Section 25 0000 Integrated Automation Revised date: 09/18/18 PART 1 - GENERAL 1.1 SUMMARY A. Section includes the general requirements for the Integrated Automation systems.

More information

Ground Fault Protection. Medium Voltage Artificial Neutrals

Ground Fault Protection. Medium Voltage Artificial Neutrals Ground Fault Protection Medium Voltage Artificial Neutrals Installation and Maintenance Instruction Manual 7615 Kimbel Street, Mississauga, Ontario Canada L5S 1A8 Tel: (905)673-1553 Fax: (905)673-8472

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 1200 - MEDIUM-VOLTAGE TRANSFORMERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

University of Delaware

University of Delaware SECTION 23 05 00_COMMON WORK FOR HVAC SYSTEMS University Contact: Energy & Engineering Group (302) 831-1744 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Start up 2. Factory Training 3. Quality Control

More information

FORM FOOTWALL. FORM FOOTWALL (floating) (floating) Installation Manual

FORM FOOTWALL. FORM FOOTWALL (floating) (floating) Installation Manual FORM FOOTWALL (floating) Installation Manual FORM FOOTWALL (floating) OVERVIEW The Form is a UL-listed configurable footwall system. This system can include any combination of base cabinets, upper cabinets,

More information

SECTION LOW-VOLTAGE TRANSFORMERS

SECTION LOW-VOLTAGE TRANSFORMERS PART 1 GENERAL 1.1 DESCRIPTION SECTION 26 22 00 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between // // if not applicable to project. Also, delete any other item or paragraph not

More information

INSTALLATION MANUAL. FOOTWALL/SINKWALL (floor mount)

INSTALLATION MANUAL. FOOTWALL/SINKWALL (floor mount) INSTALLATION MANUAL FOOTWALL/SINKWALL (floor mount) OVERVIEW The Form is a UL-listed configurable footwall/sinkwall system. This system can include any combination of base cabinets, upper cabinets, wardrobes,

More information

SECTION HVAC AIR CLEANING DEVICES

SECTION HVAC AIR CLEANING DEVICES SECTION 23 40 00 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

SECTION CONVECTORS

SECTION CONVECTORS SECTION 23 82 33 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

A. Pre-proposal meeting Questions and Answers are detailed below:

A. Pre-proposal meeting Questions and Answers are detailed below: Richland County School District One COMPETITIVE SEALED BID FOR Central Services Facility Chiller Replacement AMENDMENT NO. 2 PREPARED BY: Davis & Floyd Address: 1319 Highway 72/221 East, Greenwood, SC

More information

KM-201BAH KM-260BAH KM-201BWH KM-260BWH SELF-CONTAINED CRESCENT CUBER INSTRUCTION MANUAL L1F (100109)

KM-201BAH KM-260BAH KM-201BWH KM-260BWH SELF-CONTAINED CRESCENT CUBER INSTRUCTION MANUAL L1F (100109) SELF-CONTAINED CRESCENT CUBER KM-201BAH KM-260BAH KM-201BWH KM-260BWH INSTRUCTION MANUAL L1F015102 (100109) IMPORTANT Only qualified service technicians should install, service and maintain the product.

More information

DVPEC. Multi-Position, Variable-Speed air handler. Comfortnet Compatible ECM-based Internal EEV, Inverter-tuned 2 to 5 Tons

DVPEC. Multi-Position, Variable-Speed air handler. Comfortnet Compatible ECM-based Internal EEV, Inverter-tuned 2 to 5 Tons DVPEC Multi-Position, Variable-Speed air handler Comfortnet Compatible ECM-based Internal EEV, Inverter-tuned 2 to 5 Tons Contents Nomenclature... 2 Product Specifications... 3 Dimensions... 4 Airflow

More information

SECTION SPORTS FIELD LIGHTING

SECTION SPORTS FIELD LIGHTING SECTION 16500 SPORTS FIELD LIGHTING PART I - GENERAL 1.01 Related Documents Drawings and general provisions of the bid documents, including general and supplementary conditions apply to this section. 1.02

More information

NEBBinar: Technical Commissioning: The most effective commissioning process for new buildings. March 5, 2014

NEBBinar: Technical Commissioning: The most effective commissioning process for new buildings. March 5, 2014 NEBBinar: Technical Commissioning: The most effective commissioning process for new buildings March 5, 2014 0 Moderator Jim Huber, NEBB President-Elect and President of Complete Commissioning Jim Huber

More information