RFI s and RESPONSES Carson Towers

Size: px
Start display at page:

Download "RFI s and RESPONSES Carson Towers"

Transcription

1 RFI s and RESPONSES Carson Towers RFI #1 1. Resilient flooring is blank. Will this spec section be forthcoming? 1. Attached please find spec sections , , and Please note: product selections are shown on drawing A700. (CH&E has placed spec sections on website.) RFI #2 1. Drawing H500 indicates a new kitchen hood for the Community Room. Who is responsible for supplying and installing this hood? Mechanical Contractor or another Contractor? The hood should most likely be part of your appliance package. See appliance legend on drawing A Drawing A105 note R4 indicates removing existing roof drains and installing new. Who is responsible for this work? If it s the Plumbing Contractors are there specification for the roof drains. I didn t see any. I am not aware of the condition of the existing roof drains. If they are in serviceable condition, then the existing drains can be reused. If not the intent of the note is to replace them in kind. If replaced it should be done by the Plumbing subcontractor. We did not provide a specification for new roof drains. 3. Drawings P500, P501 & P502 indicate a different scope of plumbing work for Units A, F, K & W then Architectural drawings A402, A403 & A405. Which drawing scope should be followed? Plumbing drawings missed notes by symbol #1, 2, 3 in bathrooms, and 4 in kitchens of the above referenced units. These notes should reflect the information shown on the Architectural Drawings. As such please include scope of work referenced in notes by symbol #1, 2, 3, and 4 for these units. 4. Drawing A401 thru A406 note 43 indicates evacuating refrigerant from the old refrigerators (this looks to be every Unit except all Type B & C Units). Who is responsible for evacuating the refrigerant? The contractor should contact the local utility company, and the city to see if they have any active programs that might provide removal and evacuation service (similar to the PECO program). If no programs are available then the contractor shall be responsible to remove and dispose of the refrigerators in conformance with the requirements and regulations of the authorities having jurisdiction. RFI #3 1. There are no specs for signage. The drawings call for ADA signs for HC Parking, Apt Unit entrances, common area entrances/exits and elevators. Am I to assume common restrooms, offices, mechanical rooms and stairs will also require ADA signage? Is the signage part of this bid or is ADA signage the responsibility of the owner? Please see attached drawing A701 Schedules

2 sheet for signage information. (CH&E has placed spec sections on website.) RFI #4 1. Will a door schedule be provided. I see letters designated on drawings A400 and A401 but I can find no schedule or key. Door Schedule for common area doors is shown on drawing A301. Hardware sets are indicated in spec section See attached revised drawing A406 for door schedule for Apartment Units. Note: hardware set for Unit entrance doors is also referenced back to spec section (CH&E has placed new drawings on website.) 2. Will a window schedule be provided? Window schedule will not be provided at this time. RFI #5 1. Can you tell me what the make and model of the existing fire alarm system at Carson Towers? Please see attached photographs taken by Ahmad Mahmud of BSEG. This is the only information we have in response to your RFI #5

3

4 RFI #6 1. Do the new Aluminum Replacement windows need to meet the approval of the City of Pittsburgh Historic Review Commision as noted on the Elevation (Dwg A200 and similar)? Yes, the replacement windows will need to meet approval of the City of Pittsburgh Historic Commission. We will need to provide clear closeup photographs of typical existing window frames, and provide cut sheets or details from the manufacturer showing the new frames match the existing in profile, material, and color. Additionally: PHFA requirements for replacement windows reads as follows: Where windows are scheduled for replacement, they should be EnergyStar qualified products, except in buildings over three stories in height, wherein window replacement may comply instead with ASHRAE Standard RFI #7 1. Insulation thickness to be installed - details/spec vary from R22 to R49. Minimum insulation r value shall be R22 with tapered insulation above as required to meet code requirements for roof slope. 2. Is the new roof to be mechanically attached or fully adhered? Specs vary. The roof shall be Fully Adhered. 3. The specs call for a recovery board installed on the deck. Is this a requirement? Yes. Provide 5/8" type "X" or 5/8" Densdeck.IBC Building limits force us into Type IB construction which requires 1hr roof assembly. 4. The spec calls for water based bonding adhesive. Is there a reason this is chosen in lieu of standard Low VOC bonding adhesive? Please use standard Low VOC

5 bonding adhesive (do not use water based bonding adhesive). 5. The spec calls for EPS insulation instead of polyiso. Is this a mistake? Also, you cannot adhere membrane directly to EPS. Insulation shall be Polyisocyanurate (do not use EPS insulation). 6. The spec has some hot asphalt verbiage such as steeping the insulation down in asphalt. Please clarify roofing system to be installed. Ignore verbiage related to hot asphalt. 7. Is the roof currently or does it ever leak? Professional is not aware of history of leaks in existing roof. RFI #8 1. The kitchen sink replacements at Carson Towers are scheduled as Elkay ELUH311845PD, This number does not exist according to Elkay and the closest unit has a cost of over $500. Could you verify the correct model number and the fact that they are under mount and not selfrimming. KS1 model number shall be Dayton DPMSR12722, undermount sink or equal. RFI #9 1. There are skylight windows listed along the front sidewalk area, are the to be replaced? The skylight window wells have narrow sliding window units along the front face (see attached sketch drawing SKA12516). (CH&E has added to website) The sliders are the only component of the areaway cover that are called out to be replaced. The Owner would like an add alternate price to replace the interior window and/or door units at these areaways. 2. Which 9 panels on the front center are being replaced? Please clarify your question. Where are you referencing this from? 3. None of the wood windows are being replaced, is that correct? Correct. The wood windows are not included in the scope of this project. 4. Is the glass block being changed? No. Glass block at the front center basement level is to remain. RFI #10 1. Symbol note #5 on page E500 says, replace existing range receptacle with new NEMA 14-50R receptacle. Verify circuit has proper equipment grounding conductor. If not, replace existing circuit with 3#6 & 1#10G from 50A 2P circuit breaker in unit loadcenter to range

6 receptacle. It appears that these units do not have an equipment grounding conductor. The cost to replace all of these circuits would be excessive. Please note that these circuits are typically not required for code in regards to renovations. Please advise if the existing range receptacles can remain. Also, if these outlets are to be replaced with NEMA 14050R receptacles, please confirm who is to furnish and install the whips for the ranges. Where new appliances are being connected to existing branch circuit wiring, it is permissible to utilize a 3conductor range plug with the existing receptacle. (New ranges are typically provided with a 4conductor cord and plug. If possible, the ranges should be ordered with 3conductor plugs. Otherwise, contractor will need to provide the appropriate cord and plug.) Where the kitchen is being completely renovated, (note by symbol #14), a new 4conductor range branch circuit and 4conductor range plug shall be utilized. RFI #11 1. In reference to that same symbol (Symbol note #10 on page E100). I would like to know if it would be acceptable to use MI cable overhead to maintain the required 2 hour fire rating, in lieu of saw-cutting and patching. MI cable would be a more cost-effective solution, however it would be rather cumbersome to pull above the existing ceiling in the hallway. My suggestion would be to run the cable in a route similar to what is shown on page E100 (Electric Room Janitor Closet cross the Hallway Maintenance Office Tennant Lounge). This would probably require a small bulk head in the corner of the tenant lounge to hide the cable. I think the rest of the rooms would be fine. I guess this question is 2 fold. First we need to see if the engineer will accept MI cable. Then, we will need to determine which path to take. If I go in the hallway, I will just need to figure on some time to pop out/repair/replace some ceiling tiles. BSEG, LLC Response: Type 'MI' (mineral insulated) cable, where allowable by the NEC,can be utilized for the fire pump feeder in lieu of running conduit within the slab. Contractor shall be responsible for properly sizing the new feeders, field verifying actual routing, and coordinating any required soffits/ceiling work with the project Architect. JRD 1/26/16 RFI #12 1. Reference Dwg A106 detail at Termination at Stone Coping. Who is responsible to remove and re-set the stone coping? Would it be the Masonry Restoration contractor or the Roofing contractor? 2. Ref details 4 & Helical Anchors. Please clarify where the anchors are to be used or provide a quantity to establish the basis of the bid. Helical anchors are to be used to secure limestone panels at areas of dutchman repairs or full panel replacement when the repair work compromises the anchorage or support of the limestone panel. They should be spaced approximately 10 below the work area and approximately 12 to 18 horizontally.

7 3. Helical anchors are to be used to secure limestone panels at areas of dutchman repairs or full panel replacement when the repair work compromises the anchorage or support of the limestone panel. They should be spaced approximately 10 below the work area and approximately 12 to 18 horizontally Due to the limited nature of the inspection the quantity of crack injections, limestone dutchman repairs, and limestone full panel replacement is not known. At the commencement of the project the A/E will identify which areas need which repair. The contractor should provide a unit cost to be used as the basis for contract adjustment for the following items: a. Rout and seal cracks per lineal foot b. 12 x12 limestone dutchman repair c. Limestone full panel replacement per square foot (stone sizes vary throughout the facade) d. Helical anchors per anchor 4. Ref details 3,4 & 5/A203. Please provide additional info on a method to quantify the various stone restoration applications A) Crack injection. B) Limestone Dutchman Repair. C) Limestone full panel stone replacement. Or, establish criteria so that the contractor can determine what needs to be don RFI #13 1. Drawing P500 states that the water heaters in the 8 units that are being made ADA complainant need to be relocated. We would like to know from where to where? Existing water heaters are located within the kitchen casework. New locations are as shown on plan. 2. Is cast iron required for the sanitary drains. New sanitary piping shall match existing materials. 3. N/A 4. N/A 5. Who is responsible for moving the furniture and other items to do the work in the ceiling and floors? Coordinate this with general contractor. 6. Any underslab work in the laundry area? Yes, exact locations of existing piping in walls and floors is unknown. Field locate as required. 7. Is Pex permitted for water lines? New domestic water piping shall match existing materials. 8. Do the units have shut off valves for the water to isolate the units so we don t have to shut off the whole floor? Individual unit shut-offs where not discovered therefore it should be shut-downs of the whole floor should be anticipated. RFI #14 1. Reference Lead Joint Covers. Please provide detail and indicate where they are to be used on plan.

8 See Specs Page s A The spec says upward facing joints & coping and as shown on drawings or excepted by Architect Our point is we do not see a detail on the drawings or shown on the drawings where this will apply. Lead Joint Covers are not in scope of this project. Reference to Lead Joint Covers will beremoved from specification section (see attached revised section ). RFI #15 2. Please indicate on roof plan where the coping stone is to be lifted and replaced to accommodate new roofing. Limits of Stone Coping will be defined on drawing A105 (see attached). 1. Does room 003B need painted as it isn't listed on the finish schedule? Please clarify your reference to room 003B. There is no room 003B in the project. Interior of room 003A (Water Meter) is not to receive finishes. 2. The corridors are not listed on the finish schedule to be painted but are mentioned to be painted in Note #5 on the floor plans. Are the walls and ceilings to be painted? Corridors shall be painted as referenced in Note #5. Finish schedule will be revised accordingly 3. Rooms 002, 003, 004, 005, 601, 602, 603, 604, and 605 are listed to have painted drywall ceilings on the finish schedule but are shown to have ACT ceilings on A305; which is correct? Rooms 001B, 002, 003, 005, 601, 602, 603, 604, and 605 shall receive Suspended Acoustical Panel Ceilings as shown on drawing A305. Rooms 003A, 004 are not to receive any ceiling treatment. Rooms 006, and 007 are to receive new paint finish on Gyp. Board ceilings. Finish schedule shall be revised accordingly. RFI #16 1. Is there any exterior painting aside from the metal roof and guard rail? The guardrail / handrail for the new ADA compliant ramp shown on drawing A304,and drawing A105 notes refer to roof hatch, and ladders and cages (price as add alternates).

9 2. What gets done to the handrail in unit type N? Unit type "N" handrails are intended to be wood handrails (either prefinished or stained in field), and will utilize prefinished metal brackets. 3. Does the exposed underside of the mail shelf need painted? No the underside of the mail shelf does not require paint. RFI #17 1. Would it be acceptable to install a wireless door bell system with chime and strobe (Nutone #LA224WH) in lieu of a hard wired unit? It would only require an additional receptacle at 80 AFF from an existing receptacle and would eliminate the cutting and patching from running new wire Yes. MEP Engineer and Owner's rep. have reviewed and approve the use of the wireless doorbell system proposed. RFI #18 1. The scale is incorrect on sheets A401 & A302. Could you check all drawing scales (some sheets do not have measurements to double check with) and re-issue drawings with correct scales. Please see revised drawings A302 and A401 (CH&E has added to Website). Also note: Please do not scale drawings to determine square footages, lengths, distances, etc... RFI #19 1. Reference ramp sections/elevations on Drawing A304. What material is the 42 Guardrail and 36 High Handrail made of? RFI #20 1. Reference Dwg #AS-1 note # 16 Repair and Site Railing and Fencing per Capex Budget. Please clarify. 2. Reference Dwg #AS-1 note # 17 Replace sections of existing concrete sidewalk, and repair select areas as per capex budget. Please quantify (SF) or provide locations that need to be replaced. RFI #21 1. Reference detail 3/A203 Shelf angle repair. The detail provided refers to Alternate 1 Replace existing shelf angle with new 6x4x5/16 galv angle. Are we to assume a certain lineal footage or percentage of what is indicated on elevations? 2. Based on the detail referenced detail above, should we provide a unit price to be used as the basis for contract adjustment? Due to the concealed condition of the shelf angles it is not known what percentage or a lineal foot amount of shelf angles that will need to be replaced as opposed to cleaned and painted. For

10 this reason the contractor should provide a unit cost to be used as the basis for contract adjustment for the following items: 1. Replace the existing shelf angle with new 6x4x5/16 galvanized angle 2. Replace the existing shelf angle with new 4x4x5/16 galvanized angle RFI #22 1. The finish schedule calls for sv (sheet vinyl) in kitchens and baths but notes on the bottom of each page says LVT. Which is it? Finish Schedule governs. Provide sheet vinyl in lieu of LVT referred to on Unit Plan notes for Kitchens and Baths. 2. Vestibule carpet 3 (entire main entrance or just air lock and outer entry?) Please ignore reference to C3 "walk off carpet". Building main entrance vestibule is Not in Contract.

MSA MOORE & SPENCE ARCHITECTS, P.A.

MSA MOORE & SPENCE ARCHITECTS, P.A. MSA MOORE & SPENCE ARCHITECTS, P.A. ADDENDUM NUMBER THREE (3): October 27, 2009 to the Construction Documents dated October 9, 2009 for: HACFM, Covington Meadows Apartments Lehigh Acres, Florida The following

More information

FRANKLIN VILLAGE APARTMENTS Building I Franklin Street Morristown, NJ Block: 3901 Lots: 4,5,6

FRANKLIN VILLAGE APARTMENTS Building I Franklin Street Morristown, NJ Block: 3901 Lots: 4,5,6 PROJECT MANUAL for: FRANKLIN VILLAGE APARTMENTS Building I Morristown, NJ 07960 Block: 3901 Lots: 4,5,6 Owner: Atlantic Health Investment Corp. 200 American Road Morris Plains, NJ 07950 Architect NETTA

More information

Division 09 FINISHES TABLE OF CONTENTS

Division 09 FINISHES TABLE OF CONTENTS Division 09 FINISHES TABLE OF CONTENTS 09 1000 GENERAL... 3 A. RELATED SECTIONS... 3 B. MAINTENANCE OF FINISHES... 3 C. PUBLIC AREAS... 3 D. CUTTING AND PATCHING... 3 E. CLEANING... 3 F. RECOMMENDED FLOORING

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Notice to Bidders

More information

Home Inspection Report

Home Inspection Report Home Inspection Report Example Home Inspection Report. Page 1 of 17 Table of Contents Definitions 2 Company Information 2 General Information 2 Lots and Grounds 3 Exteriors 3 Garage/Carport 4 Roof 5 Attic

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION Section 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Invitation

More information

Timberglen Recreation Center Summary

Timberglen Recreation Center Summary Timberglen Recreation Center Summary Address Building Purpose 3810 Timberglen Road Dallas, TX 75287 Recreation Center Original Year of Construction 2003 Building Area 15,000 SF Inspection Date August 2,

More information

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS INDIANA UNIVERSITY BIDDING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 (REVISED 2005) MINORITY,

More information

Toronto Community Housing Executive Summary 2016/2017. BCA Report. Sample House High FCI

Toronto Community Housing Executive Summary 2016/2017. BCA Report. Sample House High FCI BCA Report Porfolio Development Size Construction TCHC - All Op Units Scattered Units (CHU 20),005 Sq.Ft. 925 Floor Above Grade 2 Divisional Units Page of 43 Description This dwelling unit is a detached

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Notice to Bidders

More information

HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS

HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS St. Louis County Department of Public Works Division of Code Enforcement HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS This guide is intended to provide the homeowner or contractor with the

More information

Communications Page 1 of 9

Communications Page 1 of 9 Page 1 of 9 Last Update: April 23 rd, 2014 Introduction Design In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a

More information

Rental Inspection Checklist

Rental Inspection Checklist Rental Inspection Checklist Address: Date: NOTE: The water, gas and/or electrical services were off at the time of inspection. A re-inspection at a later date SHALL BE required to inspect these items.

More information

ALL DIMENSIONS FROM FINISHED FACE OF PARTITION TO FINISHED FACE OF PARTITION UNLESS OTHERWISE NOTED.

ALL DIMENSIONS FROM FINISHED FACE OF PARTITION TO FINISHED FACE OF PARTITION UNLESS OTHERWISE NOTED. ALL DIMENSIONS FROM FINISHED FACE OF PARTITION TO FINISHED FACE OF PARTITION UNLESS OTHERWISE NOTED. PARTITION CONSTRUCTION TO BE 3 5/8 METAL STUDS 24 ON CENTER WITH 5/8 TYPE X GYPSUM BOARDS BOTH SIDES.

More information

1 data PIC location (with 2 ports) typically asf for multiple staff members

1 data PIC location (with 2 ports) typically asf for multiple staff members 1 Introduction 1.1 In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a utility. It should be assumed that all new

More information

Columbia County Health Care Center Added Amenities

Columbia County Health Care Center Added Amenities Columbia County Health Care Center Added Amenities Columbia County Board Meeting on January 16th, 2013 Building Exterior Added Amenities 1. Upgraded nail-base roofing insulation to 3 thickness on Center

More information

DALLAS-FORT WORTH INTERNATIONAL AIRPORT

DALLAS-FORT WORTH INTERNATIONAL AIRPORT DALLAS-FORT WORTH INTERNATIONAL AIRPORT ADDENDUM NO. 2 TO THE REQUEST FOR BIDS Contract No. 9500445 Restroom Rehabilitation at Terminal B (Phase 3 & 4) December 20, 2010 THE REQUEST FOR BIDS (RFB) FOR

More information

Alabama Home Inspections

Alabama Home Inspections Cover Page Property Inspection Report 1000 Sample Dr., Sampletown USA Inspection prepared for: Report Sample Inspection Date: 1/21/2010 Time: 400pm Size: Approx. 2,200sf Weather: Cloudy 62 Inspector: Bobby

More information

Michael Teller, CBI Consulting Inc. Gymnasium & Auditorium Restoration at South Middle School

Michael Teller, CBI Consulting Inc. Gymnasium & Auditorium Restoration at South Middle School A D D E N D U M # 1 DATE: TO: FROM: PROJECT: All Bidders Michael Teller, CBI Consulting Inc. Gymnasium & Auditorium Restoration at South Middle School CBI JOB NO.: 11063 The following items shall modify

More information

J~e~~r Senior Director of Construction Services Facilities Design and Construction UNIVERSITY OF CALIFORNIA, SAN DIEGO.

J~e~~r Senior Director of Construction Services Facilities Design and Construction UNIVERSITY OF CALIFORNIA, SAN DIEGO. BERKELEY DAVIS IR VINE LOS ANGELES MERCED RIVERSIDE SAN DIEGO SAN FRANCISCO SAN!' A BARBARA SANT A CRUZ OFFICE OF THE ASSIST ANT VICE CHANCELLOR CAMPUS ARCHITECT - FACILITIES DESIGN & CONSTRUCTION TEL:

More information

ADDENDUM 2 TO INVITATION FOR BID 5270-FG UNLV SOUTH RESIDENTIAL COMPLEX RENOVATION

ADDENDUM 2 TO INVITATION FOR BID 5270-FG UNLV SOUTH RESIDENTIAL COMPLEX RENOVATION ADDENDUM 2 TO INVITATION FOR BID 5270-FG UNLV SOUTH RESIDENTIAL COMPLEX RENOVATION University of Nevada, Las Vegas Purchasing Department 4505 Maryland Parkway Las Vegas, Nevada 89154-1033 (702) 895-3521

More information

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS 1 Introduction 1.1 In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a utility. It should be assumed that all new

More information

TABLE OF CONTENTS Public Safety Building

TABLE OF CONTENTS Public Safety Building DOCUMENT 00 01 10 - TABLE OF CONTENTS VOLUME I DIVISION 00 PROCUREMENT AND CONTRACTING REQUIREMENTS 00 01 10 Table of Contents 00 31 32 Geotechnical Data DIVISION 01 GENERAL REQUIREMENTS 01 10 00 Summary

More information

Repair or replace section of driveway, approach, or sidewalk that are a trip hazard.

Repair or replace section of driveway, approach, or sidewalk that are a trip hazard. City of Gibraltar Pre-Sale Inspection Report Checklist FLATWORK: Repair or replace section of driveway, approach, or sidewalk that are a trip hazard. EXTERIOR PROPERTY: Fences/Sheds/Retaining walls: Repair,

More information

HILLSIDE ELEMENTARY SCHOOL. Overview: Livingston School District Hillside Elementary School

HILLSIDE ELEMENTARY SCHOOL. Overview: Livingston School District Hillside Elementary School HILLSIDE ELEMENTARY SCHOOL Overview: The is located at 98 Belmont Drive and consists of a two-story building which has had a number of additions added to it over the years, the latest of which was a two-story

More information

PROCUREMENT AND CONTRACTING DOCUMENTS GROUP

PROCUREMENT AND CONTRACTING DOCUMENTS GROUP PROCUREMENT AND CONTRACTING DOCUMENTS GROUP DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS 00 11 00 Notice To Bidders 00 21 00 Instructions To Bidders 00 22 00 Supplementary Instructions To Bidders

More information

Facility Assessment Report, Montgomery Independent School District

Facility Assessment Report, Montgomery Independent School District NATATORIUM CAMPUS DATA NATATORIUM 22628 Hwy 105 West, Montgomery TX 77356 Year Built 2009 Approx. Total Square Footage Grades Served 30,420 n/a Current Enrollment n/a Building Levels 1 1 MASTER PLAN 2

More information

Inspection Report. Prepared for: Tonia Mann. Property Address: 2557 Briar Valley Way Dacula, GA Date: March 01, 2012

Inspection Report. Prepared for: Tonia Mann. Property Address: 2557 Briar Valley Way Dacula, GA Date: March 01, 2012 Inspection Report Prepared for: Tonia Mann Property Address: Dacula, GA 30019 Date: March 01, 2012 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS CLIENT

More information

A1.01 SITE PLAN 394 W OLENTANGY ST POWELL, OH BUILDING TO BE RENOVATED SITE PLAN. P F www. archa ll.

A1.01 SITE PLAN 394 W OLENTANGY ST POWELL, OH BUILDING TO BE RENOVATED SITE PLAN. P F www. archa ll. N O R T H F I F T H S T R E E T C O L U M B U S O H I O P.. 00 F.. 000 www. archa ll. com W OLENTANGY ST POWELL, OH 0 DRAWING SET 0 0 0 preliminary check bid permit construction REVISIONS BUILDING TO BE

More information

METROPOLITAN PIER AND EXPOSITION AUTHORITY INVITATION FOR BIDS (IFB) # M OFFICE BUILD OUT, 5 TH FLOOR OF ABC BUILDING ADDENDUM NO.

METROPOLITAN PIER AND EXPOSITION AUTHORITY INVITATION FOR BIDS (IFB) # M OFFICE BUILD OUT, 5 TH FLOOR OF ABC BUILDING ADDENDUM NO. METROPOLITAN PIER AND EXPOSITION AUTHORITY INVITATION FOR BIDS (IFB) #2017-20-M OFFICE BUILD OUT, 5 TH FLOOR OF ABC BUILDING ADDENDUM NO. (1) September 28, 2017 This Addendum No. 1 consists of seven (7)

More information

New Raised Courtyard Terrace Pavers and Retaining Walls. Line of Steps Above. New Wood Framed Stair

New Raised Courtyard Terrace Pavers and Retaining Walls. Line of Steps Above. New Wood Framed Stair Building Program Wall Construction to Remain Religious Education New Wall Construction New Furring on Wall Construction, See Partition Types, Community Room New Galvanized Steel Window Well Patch Wall

More information

HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW

HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW 27 September 2007 prepared by: J. CHRIS EVANS ARCHITECT 3220 E. Terra Alta Blvd. No. 9 Tucson, Arizona 85716 520.319.8835 evansarch@hotmail.com

More information

City Of Mendota Construction Procedures

City Of Mendota Construction Procedures City Of Mendota Construction Procedures Building Permit Application: A permit shall be obtained prior to commencing work of any type. Failure to do so may result in doubling the permit fees. At the time

More information

Inspection Report. Prepared for: Gil Turiel. Property Address: 545 Briar Run Court Loganville, GA Date: July 17, 2011

Inspection Report. Prepared for: Gil Turiel. Property Address: 545 Briar Run Court Loganville, GA Date: July 17, 2011 Inspection Report Prepared for: Gil Turiel Property Address: Loganville, GA 30052 Date: July 17, 2011 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS CLIENT

More information

Contractor/Owner initials are verification that items #1 and #2 and items (a) thru (g) above are included in the submitted plan/drawing.

Contractor/Owner initials are verification that items #1 and #2 and items (a) thru (g) above are included in the submitted plan/drawing. FINISH BASEMENT/ADDITION/REMODEL PLAN CORRECTIONS LIST (Based on the current Editions of the International Codes and National Electrical Code) PLAN CHECKED BY: LOT/SUBDIVISION/ADDRESS: CONTRACTOR OR OWNER/BUILDER:

More information

CONSTRUCTION DOCUMENTS CHECKLIST for the 2012 Michigan Building Code Including Building Permit Application Checklist

CONSTRUCTION DOCUMENTS CHECKLIST for the 2012 Michigan Building Code Including Building Permit Application Checklist CONSTRUCTION DOCUMENTS CHECKLIST for the 2012 Michigan Building Code Including Building Permit Application Checklist This checklist is a convenient reference to the 2012 Michigan Building Code. The checklist

More information

Inspection Report. Prepared for: Yossi Berg. Property Address: 4925 Diggers Way Sugar Hill, GA. Date: July 20, 2011

Inspection Report. Prepared for: Yossi Berg. Property Address: 4925 Diggers Way Sugar Hill, GA. Date: July 20, 2011 Inspection Report Prepared for: Yossi Berg Property Address: Sugar Hill, GA. Date: July 20, 2011 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS CLIENT &

More information

BOWIE LEARNING CENTER

BOWIE LEARNING CENTER BOWIE LEARNING CENTER Bowie Learning Center BUILDING DATA BOWIE LEARNING CENTER 900 North Elm St., Weatherford, TX 76086 Year Built 1936 No. of Buildings No. of Portables 0 Approx. Total Square Footage

More information

Building Inspection Report

Building Inspection Report Building Inspection Report Sample Commercial Inspection Report Inspection Date: Prepared For: Prepared By: Professional Property Inspection Consultants 4857 Winterset Drive Columbus, OH 43220 (614) 459-5941

More information

Town of Falmouth FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage COSTS FOR SUBSTANTIAL IMPROVEMENTS / REPAIR OF SUBSTANTIAL DAMAGE:

Town of Falmouth FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage COSTS FOR SUBSTANTIAL IMPROVEMENTS / REPAIR OF SUBSTANTIAL DAMAGE: S FOR SUBSTANTIAL IMPROVEMENTS / REPAIR OF SUBSTANTIAL DAMAGE: Included Costs: Items that must be included in the costs of improvement or costs to repair are those that are directly associated with the

More information

TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS

TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS AIA General Conditions... GC-1 to GC-44 Amendments to General Conditions... AM-1 to AM-2 Supplements to General Conditions... SU-1 to SU-7 00200 Instructions To Bidders... 1 3 00201 Contractor s Bidding

More information

3. Appliances - Free Standing x

3. Appliances - Free Standing x EXHIBIT "B" CARLSBAD CREST HOMES ASSOCIATION, INC. ASSOCIATION/ MAINTENANCE, REP AIR & REPLACEMENT MATRIX The following is a listing of the items within the Development, the maintenance, repair and replacement

More information

HERITAGE MIDDLE SCHOOL. Overview: Livingston School District Heritage Middle School

HERITAGE MIDDLE SCHOOL. Overview: Livingston School District Heritage Middle School HERITAGE MIDDLE SCHOOL Overview: The is located at 20 Foxcroft Drive and consists of a three-story building with Three-Story Classroom and Multi-Purpose Room Additions completed in 2002. The building has

More information

BUILDING CONDITION ASSESSMENT

BUILDING CONDITION ASSESSMENT BUILDING CONDITION ASSESSMENT 500 MacNab Street North, Hamilton ID. No.: EBE 16-0153 Prepared for Corporation By Effective Building Engineering Ltd.. Final Report: July 2016 Project No. 16-0153 Table of

More information

ADDENDUM 2 - JULY 14, 2015

ADDENDUM 2 - JULY 14, 2015 7/9/2015 The Professional(s) of Record above has signed for the following specification sections: DIVISION 1 GENERAL REQUIREMENTS Section 01 10 00 Summary of Work Section 01 25 00 Substitution Procedures

More information

C. Type of Selective Demolition Work: Demolition requires the selective removal and subsequent off-site disposal of:

C. Type of Selective Demolition Work: Demolition requires the selective removal and subsequent off-site disposal of: 02070 - SELECTIVE DEMOLITION PART 1 - GENERAL 1.1 STIPULATIONS A. The specifications sections " General Conditions of the Construction Contract ", "Special Conditions", and "Division 1 - General Requirements"

More information

ADDENDUM NO. 2 Consisting of 3 pages and Attachments

ADDENDUM NO. 2 Consisting of 3 pages and Attachments 10404-125 Street, Edmonton, AB. T5N 1T2 Tel: 780.455.5975 Fax: 780.454.2397 info@cdyarchitect.com ADDENDUM NO. 2 Consisting of 3 pages and Attachments PROJECT: Maina Centre Ville Phase II, Beaumont, Alberta

More information

Carter's Oshkosh (SIS) # The Center at Pearland Parkway - Pearland, TX Scope Of Work / Bid Qualifications

Carter's Oshkosh (SIS) # The Center at Pearland Parkway - Pearland, TX Scope Of Work / Bid Qualifications Carter's Oshkosh (SIS) #1185 - The Center at Pearland Parkway - Pearland, TX 77581 - Scope Of Work / Bid Qualifications Please fill out the blanks associated with your trade scope or work with the words

More information

Standards and Procedures Security Room Construction/Renovations At University of North Carolina Wilmington

Standards and Procedures Security Room Construction/Renovations At University of North Carolina Wilmington Standards and Procedures Security Room Construction/Renovations At University of North Carolina Wilmington Rev 062017 Provided by UNCW Physical Security and Access OVERVIEW... 3 CABLE INSTALLATION... 3

More information

INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS

INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS November 2018 Contents 1. Introduction... 1 2. Ontario Building Code and Second Dwelling Units... 1 3. How Do I Make My Secondary Dwelling Unit

More information

REO Client Safety Hazard Requirements

REO Client Safety Hazard Requirements REO Client Safety Hazard Requirements Safety Hazards Safeguards clients are continually reporting missing safety hazards or allowables across the nation and it is jeopardizing our relationship with our

More information

REQUEST FOR QUALIFICATIONS ARCHITECTURAL/ENGINEERING SERVICES

REQUEST FOR QUALIFICATIONS ARCHITECTURAL/ENGINEERING SERVICES I. PURPOSE REQUEST FOR QUALIFICATIONS ARCHITECTURAL/ENGINEERING SERVICES The Greensboro Housing Authority (GHA) invites qualifications for the Architectural/Engineering Services for RAD Renovations at

More information

Evansville Public Schools. Facility Assessment Report January 28, 2 , General Building Data

Evansville Public Schools. Facility Assessment Report January 28, 2 , General Building Data Evansville Public Schools Facility Assessment Report January 28, 2, 2013 SGN/Wendel Architects, Design Tree Engineering and R.A. Morton Construction Managers were retained by the Evansville Public School

More information

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural %

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural % 8/11/ Building Rating System Percent Site: 1.0 Total 0 163 82% Building: 2.1 Building Exterior Elements 0 82 82% 2.2 Accessibility 0 92 92% 2.3 Structural 0 91 91% 2.4 Building Envelope 0 84 84% 2. Interior

More information

GROUNDS Grading General Grading, slope and drainage: Satisfactory N/A See Notes. Grading and slope at house wall

GROUNDS Grading General Grading, slope and drainage: Satisfactory N/A See Notes. Grading and slope at house wall GROUNDS Grading General Grading, slope and drainage: Satisfactory Grading and slope at house wall Satisfactory (within 5 feet from building) Sidewalk Concrete Brick Flagstone Other Patio stones Driveway

More information

City of Maryland Heights. Residential Occupancy Permits & Home Inspection Process

City of Maryland Heights. Residential Occupancy Permits & Home Inspection Process City of Maryland Heights Residential Occupancy Permits & Home Inspection Process Residential Occupancy Permits An occupancy permit is required when there is: Any change of ownership or representation of

More information

City of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage

City of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage City of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage Property Address: Company Name: Contractor Name: Contractor Address: City: State: Zip: License Number: Phone Number

More information

LASALLE - BACKUS EDUCATION CAMPUS

LASALLE - BACKUS EDUCATION CAMPUS INITIAL YEAR BUILT 1957 BUILDING AREA 63,000 SF CURRENT PROGRAM CAPACITY 406 ENROLLMENT 2008 349 WARD 4 PROPOSED PROGRAM CAPACITY 425 Site Plan LASALLE - BACKUS - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

Dr. Edward Livingston Trudeau Building. 118 Main Street, Saranac Lake, NY. Building Systems Report. June 24, 2018

Dr. Edward Livingston Trudeau Building. 118 Main Street, Saranac Lake, NY. Building Systems Report. June 24, 2018 G2 Gordon + Gordon Architecture. LLC Dr. Edward Livingston Trudeau Building 118 Main Street, Saranac Lake, NY Building Systems Report June 24, 2018 Harry Gordon, FAIA 164 Otter Slide Road Saranac Lake

More information

City of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage

City of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage City of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage Property Address: Company Name: Contractor Name: Contractor Address: City: State: Zip: License Number: Phone Number

More information

UCC Permit Application Procedures

UCC Permit Application Procedures How do I apply for a permit? UCC Permit Application Procedures 1. Please complete the CodeMaster Pan Review Application 2. Please provide the scope of work description and/or construction documents/plans.

More information

pershing+ desperes uichomes.com 6005 and 6007 Pershing Avenue pershing+desperes call or

pershing+ desperes uichomes.com 6005 and 6007 Pershing Avenue pershing+desperes call or pershing+ desperes modern homes in the skinker-debaliviere neighborhood 6005 and 6007 Pershing Avenue - new construction - 3 bedrooms - 2.5 baths - 2,237sf TRANSPARENT site plan 6007 6005 floor plans upper

More information

NYC Department of Education

NYC Department of Education Architectural Inspection Building Assessment Survey 2017-2018 Asset: P.S./I.S. 266 - QUEENS, 74-10 COMMONWEALTH BLVD, New York, 11426 Inspection Id Inspection Type Time In Last Edited SA : Architectural

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 65 - BROOKLYN, 158 RICHMOND STREET, New York, 11208 Inspection Id Inspection Type Time In Last Edited Architectural - Senior 2018-05-15 11:22 AM 2018-06-12

More information

Building Permit Application

Building Permit Application Building Permit Application Administrative Use Only PARENT PERMIT NUMBER (Required if part of another project) PERMITTEE: PERMITTEE ADDRESS: E-MAIL ADDRESS: ARCHITECT/ENGINEER: ARCHITECT/ENGINEER ADDRESS:

More information

LOS RIOS COMMUNITY COLLEGE DISTRICT 1919 Spanos Court, Sacramento, CA Phone (916) FAX (916) Purchasing Department

LOS RIOS COMMUNITY COLLEGE DISTRICT 1919 Spanos Court, Sacramento, CA Phone (916) FAX (916) Purchasing Department LOS RIOS COMMUNITY COLLEGE DISTRICT 1919 Spanos Court, Sacramento, CA 95825 Phone (916) 568-3071 FAX (916) 568-3145 Purchasing Department Sacramento City College American River College Cosumnes River College

More information

REBECCA LG BOSTICK, ARCHITECTS, INC

REBECCA LG BOSTICK, ARCHITECTS, INC REBECCA LG BOSTICK, ARCHITECTS, INC 703-768-2250 ADDENDUM NO. 3 Page 1 of 4 (plus attachments -2 pages) SILVERBROOK ELEMENTARY SCHOOL RENOVATION Fairfax County Public Schools 9350 Crosspointe Drive, Fairfax

More information

Watercrest - Sand Hill - Columbia, SC TABLE OF CONTENTS PROCUREMENT AND CONTRACTING REQUIREMENTS

Watercrest - Sand Hill - Columbia, SC TABLE OF CONTENTS PROCUREMENT AND CONTRACTING REQUIREMENTS Watercrest - Sand Hill - Columbia, SC 00 0110-1 TABLE OF CONTENTS DIVISION 00 PROCUREMENT AND CONTRACTING REQUIREMENTS INTRODUCTORY INFORMATION Document 00 0101 Document 00 0110 Project Title Page CONTRACTING

More information

REQUEST FOR PROPOSALS March 4, 2010 PROJECT OVERVIEW:

REQUEST FOR PROPOSALS March 4, 2010 PROJECT OVERVIEW: Police Headquarters Project REQUEST FOR PROPOSALS March 4, 2010 PROJECT OVERVIEW: General description The objective is to renovate an approximately 18 x 24 section of the two-bay attached garage at Town

More information

The Inspector. Property Inspection Report

The Inspector. Property Inspection Report Cover Page The Inspector Property Inspection Report Inspection prepared for: ******** ******* Date of Inspection: 11/18/2013 Time: 12PM Age of Home: unknown Size: 2000sf Weather: overcast / 40 Inspector:

More information

.2 These guidelines should be read with the specific technical sections of McGill s Building Design and Technical Standards.

.2 These guidelines should be read with the specific technical sections of McGill s Building Design and Technical Standards. Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when planning for Corridors and Hallways. These standards are not intended to restrict or replace professional judgment..2

More information

RAYMOND EDUCATION CAMPUS

RAYMOND EDUCATION CAMPUS INITIAL YEAR BUILT 1924 BUILDING AREA 73,600 SF CURRENT PROGRAM CAPACITY 479 ENROLLMENT 2008 302 WARD 1 PROPOSED PROGRAM CAPACITY 600 Site Plan RAYMOND - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

SECTION TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS. ADD the following sections: Commissioning Requirements...

SECTION TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS. ADD the following sections: Commissioning Requirements... ADDENDUM NO. 01 PULASKI COUNTY MIDDLE SCHOOL FOR THE PULASKI COUNTY PUBLIC SCHOOLS PULASKI COUNTY, VIRGINIA STATE PROJECT CODE NO. 077-30-00-100 COMM. NO. 16196-00 RRMM ARCHITECTS ROANOKE, VA AUGUST 14,

More information

BIDDER REQUEST FOR INFORMATION #001 CONSOLIDATED

BIDDER REQUEST FOR INFORMATION #001 CONSOLIDATED BIDDER REQUEST FOR INFORMATION #001 CONSOLIDATED Project: Los Chingones and HashTAG Location: 10155 E. 29 th Drive Denver, CO 80238 Date: 12/5/16 1. There are existing PVC roof drains in the space and

More information

APPENDIX 1 PROJECT REQUIREMENTS

APPENDIX 1 PROJECT REQUIREMENTS APPENDIX 1 PROJECT REQUIREMENTS I) Scope of Work This section contains a general summary of the work the Contractor shall perform under this contract. If any conflict exists between the work described

More information

ANNEX A.1 TECHNICAL SPECIFICATIONS. Open Call for Tender. No F/SE/10/05. Provision of Building Inspection, Maintenance, Alteration and Repair services

ANNEX A.1 TECHNICAL SPECIFICATIONS. Open Call for Tender. No F/SE/10/05. Provision of Building Inspection, Maintenance, Alteration and Repair services ANNEX A.1 TECHNICAL SPECIFICATIONS Open Call for Tender No F/SE/10/05 Provision of Building Inspection, Maintenance, Alteration and Repair services Building Inspection, Maintenance, Alteration and Repair

More information

Inspection Report. Prepared for: Tonia Mann. Property Address: 56 Riverview Place Douglasville, GA Date: September 19, 2012

Inspection Report. Prepared for: Tonia Mann. Property Address: 56 Riverview Place Douglasville, GA Date: September 19, 2012 Inspection Report Prepared for: Tonia Mann Property Address: Douglasville, GA 30134 Date: September 19, 2012 Inspector: Charles Mann Edifice Inspections, Inc. (770) 594-2222 www.edificeinspections.com

More information

CLARIFICATIONS. Item 3. Specification Sections and A. All finish wood shall have sealer coat and two coats of finish material REVISIONS

CLARIFICATIONS. Item 3. Specification Sections and A. All finish wood shall have sealer coat and two coats of finish material REVISIONS Addendum #2 Project Name: Global Campus Interior Renovation Project Address: 2 E. Center Street Fayetteville, AR 72701 Date: 06/14/17 This document is issued as a response to Clarifications. These revisions

More information

REHABILITATION STANDARDS CHECKLIST

REHABILITATION STANDARDS CHECKLIST Project Name Date Built Date Last Rehabilitated (If applicable) EXTERIORS REHABILITATION STANDARDS CHECKLIST ROOF Age (Yrs) Poor Fair Good Excellent Roof /Pitch/Flat # of Layers Substrate Material Insulation

More information

PHASE I ACADEMIC BUILDING CORE RENOVATIONS RCNJ Project No C

PHASE I ACADEMIC BUILDING CORE RENOVATIONS RCNJ Project No C PHASE I ACADEMIC BUILDING CORE RENOVATIONS RCNJ Project No. 20140101C CONSTRUCTION ESTIMATE AND PROJECT BUDGET Dated June 7. 2014 Estimated Cost HARD COSTS $ 1,560,284 Core Renovations (Toilet Rooms, Ceilings

More information

SECTION The specification section is organized by placing information in three standard parts:

SECTION The specification section is organized by placing information in three standard parts: SECTION 14244 LIMITED USE HYDRAULIC ELEVATOR ***** Since 1982 Liftavator, Inc. has provided limited use/limited application (LU/LA) elevators, residential elevators, hydraulic vertical platform wheelchair

More information

Harry Stone Recreation Center Summary

Harry Stone Recreation Center Summary Harry Stone Recreation Center Summary Address Building Purpose 2400 Millmar Drive Dallas, TX 75228 Recreation Center Original Year of Construction 1957 (Expansion 2013) Building Area 22,281 SF Inspection

More information

March 2018 Progress. Work Completed, Week Ending 3/23/18:

March 2018 Progress. Work Completed, Week Ending 3/23/18: March 2018 Progress Work Completed, Week Ending 3/23/18: Continued draft curtains and liner panels. Continued running power to hangar doors. Continued installation of bath accessories in the gang bathrooms.

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Notice to Bidders

More information

Existing Site Aerial Frederick High School Feasibility Study September 5, 2012

Existing Site Aerial Frederick High School Feasibility Study September 5, 2012 Existing Site Aerial Building Developmental History 1981 1966 1939 1977 1978 1955 1966 Exterior Roof: Most of existing roof has multi ply built up roofing. Some areas have gravel ballast, others have cap

More information

FACILITY COMPONENTS - ELEMENTARY SCHOOL

FACILITY COMPONENTS - ELEMENTARY SCHOOL SITE AREAS Parking and Access - Buses 1.0 2.0 0.16 Five fewer bus stalls than minimum standard. Parking and Access - Service / Delivery 1.0 1.0 0.08 No delivery parking adjacent to delivery entrance. Parking

More information

1234 Main St. Buyer Name. Table of Contents

1234 Main St. Buyer Name. Table of Contents AMERICAN PROFESSIONAL HOME INSPECTION 719.648.4098 drew@americanprofessionalhomeinspection.com http://www.amproinspection.com RESIDENTIAL REPORT 1234 Main St. Colorado Springs CO 80903 Buyer Name 10/02/2017

More information

Mills Elementary School Site Summary

Mills Elementary School Site Summary 1 Mills Elementary School Site Summary Address 6201 Davis Lane Austin, TX 78749 Number of Permanent Campus Facilities 1 Original Year of Construction 1998 Total Campus Building Area (combined) 81,368 SF

More information

FINEGAN INSPECTION SERVICES, INC.

FINEGAN INSPECTION SERVICES, INC. FINEGAN INSPECTION SERVICES, INC. TERRY FINEGAN 76 WEST FOSTER MAINEVILLE ROAD MAINEVILLE, OHIO 45039 683-0733-PHONE 697-0163-FAX Email- finegan @ fuse.net CLIENT: 1/14/08 Mr. BUILDING LOCATION As in all

More information

FACILITY COMPONENTS - MIDDLE SCHOOL

FACILITY COMPONENTS - MIDDLE SCHOOL SITE AREAS Parking and Access - Buses 2.0 2.0 0.30 Parking and Access - Serv. / Delivery 3.0 1.0 0.22 Parking and Access - Staff 4.0 3.0 0.89 Parking and Access - Visitors 1.0 3.0 0.22 Four fewer stalls

More information

Property Condition Assessment

Property Condition Assessment Property Condition Assessment Pewaukee, WI 53072 Inspection Date: 1/6/15 Prepared For: Report Number: Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar Dr. Pewaukee, WI 53072

More information

SECTION GYPSUM BOARD ASSEMBLIES

SECTION GYPSUM BOARD ASSEMBLIES SECTION 09260 GYPSUM BOARD ASSEMBLIES PART 1 GENERAL 1.1 SUMMARY A. Provide gypsum board assemblies. 1.2 SUBMITTALS A. Product Data: Submit manufacturer's product data and installation instructions for

More information

City of South Pasadena COMMUNITY IMPROVEMENT

City of South Pasadena COMMUNITY IMPROVEMENT City of South Pasadena COMMUNITY IMPROVEMENT Office Address: Mailing Address: 6940 Hibiscus Ave S 7047 Sunset Dr S South Pasadena, FL 33707 South Pasadena, FL 33707 *PHONE: (727) 343-4192 * FAX: (727)

More information

SPARTANBURG COUNTY BUILDING CODES DEPARTMENT

SPARTANBURG COUNTY BUILDING CODES DEPARTMENT SPARTANBURG COUNTY BUILDING CODES DEPARTMENT PLAN REVIEW CHECK LIST REQUIREMENTS FOR COMMERCIAL BUILDING PERMITS Plan Review Coordinator Kris Brannon 864-596-3180 366 N. Church St Room 500 Spartanburg,

More information

Requests for Information pm Draft for Request for Proposals Sprouts - Shell/Civil Issued on April 25, 2018

Requests for Information pm Draft for Request for Proposals Sprouts - Shell/Civil Issued on April 25, 2018 Requests for Information - 05.0.1 5pm Draft for Request for Proposals Sprouts - Shell/Civil Issued on April 25, 201 RFI 01 Is the RFP due at 4pm or 5pm on May 16th? Response: RFI 02 Do you have an anticipated

More information

NYC Department of Education

NYC Department of Education Architectural Inspection Asset: Building Assessment Survey 2017-2018 NYC SCHOOL CONSTR. AUTHORITY - QUEENS, 30-30 THOMSON AVE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Architectural

More information

City of Westerville Guide to Commercial Inspections

City of Westerville Guide to Commercial Inspections City of Westerville Guide to Commercial Inspections FOOTINGS - After the excavation, with the form work and any required reinforcing steel in place. All footings shall have loose soil removed, reinforcing

More information

Thurgood Marshall Recreation Center Summary

Thurgood Marshall Recreation Center Summary Thurgood Marshall Recreation Center Summary Address Building Purpose 5150 Mark Trail Way Dallas, TX 75232 Recreation Center Original Year of Construction 1970 Building Area 21,300 SF Inspection Date August

More information

NORMAL HILLS BUILDING 8 COSMESTIC UPGRADES PROJECT

NORMAL HILLS BUILDING 8 COSMESTIC UPGRADES PROJECT NORMAL HILLS BUILDING 8 COSMESTIC UPGRADES PROJECT Bid No. 2K18-04 Addendum III The following shall be added to the indicated specification sections. (Changes are in red) SECTION 011000 SUMMARY / SCOPE

More information

NORMAL HILLS BUILDING 6 COSMESTIC UPGRADES PROJECT

NORMAL HILLS BUILDING 6 COSMESTIC UPGRADES PROJECT NORMAL HILLS BUILDING 6 COSMESTIC UPGRADES PROJECT Bid No. 2K18-03 Addendum III The following shall be added to the indicated specification sections. (Changes are in red) SECTION 011000 SUMMARY / SCOPE

More information