1 SECTION PART 1 - GENERAL 1.01 WORK INCLUDED A. Air distribution registers, grilles, and diffusers B. Fire dampers C. Smoke dampers D. Combination fire and smoke dampers E. Access doors F. Outside air louvers and louvered penthouses G. Flex Duct 1.02 RELATED WORK A. Section : Building Automation & Direct Digital Controls B. Section : Sheetmetal Ductwork C. Section : Sheetmetal - Special Ductwork 1.03 QUALITY CONTROL A. Air diffusers, grilles, and registers: Ratings certified by Air Diffusion Council. B. Fire dampers: Comply with requirements of UL 555, NFPA 90A and NFPA 90B. C. Smoke and combination fire/smoke dampers: Comply with requirements of UL 555S. D. Roof Ceiling Assembly: Comply with requirements of UL Fire Resistance Index SUBMITTALS A. Submit manufacturer's product data for review. PART 2 - PRODUCTS 2.01 REGISTERS, GRILLES AND DIFFUSERS A. Acceptable Manufacturers: Titus, Metalire, Krueger, Nailor, Price and Carnes. B. Ceiling diffusers, grilles and registers shall be of steel construction in accordance with the roof/ceiling assembly as detailed in the UL Fire Resistance Index. C. Sidewall Supply Registers: Titus, Model 300-FL with OBD, plaster frame Extruded aluminum, removable core, opposed blade damper with baked-on, off-white enamel finish Page 1

2 D. Sidewall Return and Exhaust Registers: Titus, Model 350-FL OBD, plaster frame. Extruded aluminum, removable core, with baked-on, off white enamel finish. When installed below seven feet above the finished floor shall heavy duty grille similar to Titus Model 33R, with maximum 1/2" spacing. Unless noted on drawings, blades shall be parallel to the floor. E. Ceiling Supply Air Registers and Grilles 1. Architectural plaque diffuser: Square deflection plate centered in a square housing, Titus OMNI. For diffusers noted on drawings as 2 or 3 way blow, provide blank off plates in diffuser. 2. Coordinate ceiling device frame type with architectural ceiling type. 3. Provide ceiling diffusers complete with opposed blade volume dampers where diffuser is installed in inaccessible ceilings. Do not furnish volume damper for diffusers installed in accessible ceilings or exposed diffusers. F. Linear Bar Diffusers: 1. Titus, Model CT-541 frame 14,Type C fastening, continuous bar type, extruded aluminum, 1/2" spacing, 1/4" bars, 15 degrees deflection, with or without volume dampers as noted on Drawings. G. Linear Slot Diffusers: 1. Titus ML-37, ML-38, or ML-39, as indicated on Drawings. 2. Pattern Controller: Full 180 degree pattern controller to adjust both air direction and volume. 3. Borders and mounting: Provide frame and border as required for specific conditions or as specifically indicated on Drawings. 4. Construction: Extruded aluminum with steel pattern controllers. 5. Finish: #25 White border and black pattern controllers. 6. Provide with Clear anodized aluminum finish. H. Ceiling Laminar Flow Supply Diffusers: 1. O.R., Cathology Lab, and Isolation Room supply diffusers (no HEPA filter): Titus TLF, for low velocity, unidirectional flow. Provide with internal baffles, volume damper in neck, safety chain. Perforated face shall be removable from room. Diffuser shall be nominal 24"x 48" face area, 10" neck and shall deliver air into room at 25 fpm through gross area of face at maximum of 0.039" W.C.s.p. and maximum NC of 19 (based on room absorption of 10 db, re 10 (-12) watts). 2. Coordinate ceiling device frame type with architectural ceiling type. 3. Provide ceiling diffusers complete with opposed blade volume dampers where diffuser is installed in inaccessible ceilings. Do not furnish volume damper for diffusers installed in accessible ceilings or exposed diffusers. I. Ceiling Exhaust and Return Registers: 1. Titus Model 50-F, 1/2" egg-crate aluminum with baked-on, off-white enamel finish, for operating rooms and smoke evacuation. 2. Titus Model OMNI, architectural square panel ceiling panel. 3. Provide register complete with opposed blade volume dampers where installed in inaccessible ceilings. Do not furnish volume damper for registers installed in accessible ceilings or exposed registers. 4. Coordinate ceiling device frame type with architectural ceiling type. 5. Provide a minimum 6" deep square-to-round transition at connections to return/exhaust devices. Volume dampers shall not extend into transition when fully open Page 2

3 J. Air Troffers: Furnished under Division 26 for installation and balancing under this Division. Furnish and install supply and return air boots under this Division. 1. Provide Titus Model LTTI externally insulated supply air boot with capacity as scheduled on drawings. Static pressure drop shall not exceed.20" WC and NC shall not exceed Provide Titus Model LTTRI, externally insulated return air boot with capacity as scheduled on drawings. Static pressure drop shall not exceed.05" WC and NC shall not exceed 35. Titus, model 300-RL with OBD 2.02 FIRE AND SMOKE DAMPERS A. Acceptable manufacturers: 1. Ruskin 2. Air Balance 3. Greenheck 4. Nailor 5. Potttorff B. Damper fire ratings: See drawings for fire ratings of walls and floors in which dampers are installed. Coordinate damper fire rating with wall and floor rating. Dampers with asbestos paper or coating are unacceptable. C. Fusible link: Provide fusible links which will melt at 165 degrees causing damper to close and lock in closed position. D. Provide type "C" multi-leaf fire dampers rated for use in dynamic systems with airflow up to 4000 fpm at 6" w.c. Construct dampers of steel with rust resistant finish. E. Smoke dampers: 1. Low pressure duct (2" pressure class and lower): Ruskin SD Medium pressure duct (4" - 6" pressure class): Ruskin SD Minimum Class II rated 4. Operators: Electric. 5. Install and mount qualified operator at time of fabrication by damper manufacturer. Operator shall be mounted out of airstream in accessible location. Furnish damper and operator by a single entity meeting applicable UL 555S qualifications for both damper and operator. Damper operator shall be adequate size to open or close damper in 15 seconds. F. Combination Fire and Smoke Dampers: 1. Low pressure ductwork: Ruskin Model FSD Medium pressure ductwork: Ruskin Model FSD Minimum Class II rated 4. Operator: Electric.5. Install and mount qualified operator at time of fabrication by damper manufacturer. Furnish damper and operator by a single entity meeting applicable UL 555S qualifications for both damper and operator. Damper operator shall be of adequate size to open or close damper in 15 seconds. G. Sleeves: 1. Unless otherwise required by the authority having jurisdiction, sleeves for fire dampers and fire and smoke combination dampers shall be the rigid type of construction recommended in Schedule 2 of SMACNA Publication for "Fire Damper and Heat Stop Guide for Air Handling Systems". Use 16 gauge for ducts 24" or less in diameter or either rectangular dimension and 14 for ducts over 24". Provide minimum 18" long sleeves. Coordinate required length with wall thicknesses Page 3

4 2. Conform to the requirements of UL 555S. Test damper and operator as a unit to comply with UL 555S. 3. Install 1-1/2"x1-1/2"x1/8" angle bar on four sides of sleeves and both sides of wall. 4. Fasten angles to sleeve only. 5. Do not fasten angles to the wall. H. Maximum pressure drop for combination fire/smoke dampers: 1. Supply ducts: 0.25" at 2500 FPM 2. Return and exhaust ducts: 0.15 at 1500 FPM I. Provide integral end switches with damper as required by control drawings. J. Provide UL listed ceiling fire dampers at ceiling diffusers, grilles, and registers in accordance with UL Fire Resistive Index AIR BLENDERS A. Acceptable manufacturers: 1. Blender Products, Inc. 2. Kees, Inc. B. Provide static mixing device in mixed air plenums for A/C systems as indicated on drawings. C. Type, size, pressure drop and capacity as indicated on drawings. D. Minimum.080" thick aluminum or 16 gauge galvanized steel with all welded construction. E. Install in accordance with manufacturer's instructions. F. Given the following entering conditions, mixing device shall mix the two airstreams to yield a maximum standard deviation of 6 degrees from the mixed air temperature. 1. Outside Air: 25% at 0 degrees 2. Return Air: 75% at 75 degrees 3. Mixed Air: 55 degrees 2.04 ACCESS DOORS A. Acceptable manufacturers: 1. Ruskin, Model ADH22 2. Venco CAD Flexmaster (The Inspector Series) B. Provide insulated doors in ductwork for access to service equipment such as automatic dampers, fire dampers, smoke dampers, humidifiers duct coils (each side), casing mounted coils (each side), filters (each side), duct mounted smoke detectors duct mounted air flow measuring stations (each side) and elsewhere as noted on drawings. C. Size access doors as follows: 1. Duct Sizes under 12": Door sized sufficient to service equipment or replace fusible link 2. Duct sizes 12" to 20": 12"x12" door 3. Duct sizes 20" to 36": 18"x18" door 4. Duct sizes 36" and above: 24"x24" door D. Apparatus casing access doors: Prehung door frame assemblies, size 22" x 58" Ruskin ADW Page 4

5 E. Provide reinforced wire glass view windows, 12"x12", in access doors at humidifiers. F. Use double panel construction, two sheets of at least 24 gauge galvanized steel with 1" thick insulation between panels. G. Mount doors in a rigid frame of at least 22 gauge formed galvanized steel or aluminum. H. Use angle iron bracing as required to make the door frame a rigid assembly. I. Provide latches that permit easy removal of access door while maintaining positive closing and minimum leakage. J. Provide sponge rubber gaskets for all doors. K. In accordance with NFPA 90A, identify each access door with 1/2" high stenciled letters as 'Fire Damper', 'Smoke Damper', or 'Combination Fire/Smoke Damper' LOUVERS AND LOUVERED PENTHOUSES A. Verify size, location, and placement of louvers prior to fabrication; coordinate field measurements and shop drawings and shop assembly to minimize field adjustments, splicing, mechanical joints and field assembly of units. B. Preassemble louvers in sections as large as practical. C. Exterior louvers and screens: Dowco Corporation, Model DBE-04 or DBE-06 (to match wall thickness), Penn Airstream, Model M44 or M63 (to match wall thickness Ruskin Model ELF-375D or ELF-6375D, Airolite, Construction Specialties, or Louvers and Dampers, Inc. D. Material: Extruded aluminum with 12 gauge,.081" thick aluminum blades and frame and welded construction. E. Blade angle: Minimum 35 degrees from horizontal. F. Use blades minimum 4" or 6" deep, blades to match wall thickness, with drain gutter on each blade and downspouts in jams and mullions. G. Set blades on 3" or 4-1/2" centers. H. Provide internally braced corners with caulking slots. I. Provide slidable interlocked mullions with a provision for expansion and contraction. J. Design structural supports to carry a wind load of not less than 20 pounds per square foot. K. Provide bird screen, 1/2" square mesh of 16 gauge,.051", expanded flattened aluminum. Screens shall be on the interior side of louver and shall be in a removable frame. L. Provide formed metal sills of the same gauge and material as the louver, sized to lap under the louver sill and over the outside edge of the wall. M. Louver finish: As selected by Architect from submitted color samples from: Duranotic finish. Mill finish for painting. Clear anodized finish Page 5

6 N. Provide louvers with the AMCA Certified Ratings Seal for Air Performance and Water Penetration. O. Size louvers as shown on the drawings. P. Select intake louvers at or below the "Point of Zero Water Penetration". Q. Do not exceed 0.2" of water pressure drop across louvers. R. Acceptable manufacturers for louvered penthouses are: Dowco. Penn Airstream. Ruskin. 1. Airolite 2. Construction Specialties 3. Louvers and Dampers, Inc. S. Submit for review finish on louvered penthouses FLEXIBLE DUCT A. Acceptable manufacturers: 1. If they meet the requirements of these specifications, products of the following manufacturers shall be acceptable: Flexmaster U.S.A.; Thermaflex; Omniair (ATCO); J. P. Lanburn. B. For hospital critical areas including Surgery, Recovery, Labor and Delivery, Nursery, LDRP, ICU, CCU and Trauma, flexible duct shall be corrugated aluminum type with water and airtight mechanically formed seams. Duct shall be fabricated without the use of adhesives or sealants. Omniair 1800, Flexmaster TLM, or equal by listed manufacturer. C. For other area, flexible duct construction shall consist of a triple lamination of aluminum foil, aluminized polyester and fiberglass mechanically locked to a corrosion resistant galvanized steel helix. Omniair 1200, Flexmaster 5M, or equal by listed manufacturer. D. Characteristics of flexible duct to air terminals and all distribution devices: 1. Approved as UL Class 1 air duct. 2. Flame spread less than 25, smoke developed rating less than Insulation shall have a maximum thermal conductivity of 0.17 BTU -in/hr - ft2 - degree F at 75 degrees mean temperature, or as required to meet energy code. 4. Do not exceed five feet of length. 5. Flexible duct shall meet standards of local building code. 6. Jacket shall be fire retardant, reinforced, metalized type. 7. Duct shall be suitable for 6" positive pressure, 1" negative pressure, velocities up to 4,000 FPM. E. Seal off the insulation jacket at its ends and at joints with mastic, Hardcast, or similar material. Replace flex if jacket is punctured. F. Complete insulation coverage up to the boxes. G. Do not route flexible duct through corridor walls, fire or smoke partitions. H. No bends shall be made in flexible duct with the center line radius less than one and one-half duct diameter and only one bend may occur per four foot length of duct material. I. Install UL listed flexible duct connectors made of 28 ounce, heavy glass fabric double coated with neoprene between duct and fan discharge Page 6

7 2.07 FLEXIBLE CONNECTORS A. Install UL listed flexible duct connectors made of 28 oz, heavy glass fabric double coated with neoprene between duct and fan discharge. B. Install UL listed flex connections to fan inlet and outlets as shown on drawings. C. Connections to be a minimum of 3 inches wide, crimped into metal edging strip, and air tight. Connections to have adequate flexibility and width to allow for thermal expansion/contraction, vibration of connected equipment, and other movement. D. Coated glass fiber fabric shall be used for all applications. For inside applications other than corrosive environments, fume exhaust, or kitchen exhaust material shall be double coated with neoprene, air and water tight, suitable for temperatures between -10 degrees F and 200 degrees F, having a nominal weight of 30 ounces per square yard. For outdoor applications other than corrosive environments, fume exhaust, or kitchen exhaust material shall be double coated with Hypalon, air and water tight, suitable for temperatures between -10 degrees F and 250 degrees F, having a nominal weight of 26 ounces per square yard. If they meet the requirements of this specification, products of Ventfabrics, Inc. shall be acceptable. (Ventglas and Ventlon). E. For hot corrosive environments or fume exhaust applications indoors or outdoors, material shall be coated with Teflon that is air and water tight, suitable for temperatures between -20 degrees F and 500 degrees F, having a nominal weight of 14 ounces per square yard. If it meets the requirements of this specification, Ventfabrics "Ventel" shall be acceptable. F. Flexible connectors shall not be used in kitchen exhaust ducts MANUAL VOLUME DAMPERS A. Type: Opposed blade. B. Material: Steel, 3V type blades mounted in steel channel frame. C. Shaft: 1/2" square rod operator with end bearings and gasket seal at duct penetrations. Terminate shaft in damper frame with bushings. D. Operator: Locking quadrant handle with damper position indicator and insulation stand off mounting bracket for externally insulated ductwork. PART 3 - EXECUTION 3.01 INSTALLATION A. Install sheet metal accessories in locations shown on drawings. B. Install accessories in accordance with manufacturer's published recommendations as well as applicable sections of SMACNA manual and other standards set forth in Part 1. C. Provide all screws, bolts, nuts, inserts, and material required for attaching sheet metal to duct, walls, floors, and ceilings. D. Where diffusers or grilles and registers are not provided with volume dampers, install spin-in fitting with balancing damper in duct runout Page 7

8 3.02 TESTING A. Check work for satisfactory installation and performance. B. Insure that adequate access does in fact exist for fire and smoke dampers and that damper operator motors are not hindered in operation by proximity to walls or other objects. C. Provide label on each access door for fire, fire/smoke or smoke dampers with the date inspected, the name of certified technician that inspected the damper, the damper pass status, and the damper identification number provided in close out documentation. D. Check duct connections at access doors for air leakage or condensation. Correct conditions found. END OF SECTION Page 8

A. This Section includes ceiling- and wall-mounted diffusers, registers, grilles and louvers.

A. This Section includes ceiling- and wall-mounted diffusers, registers, grilles and louvers. SECTION 23 37 13 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

University of Houston Master Construction Specifications Insert Project Name SECTION AIR DISTRIBUTION DEVICES PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION AIR DISTRIBUTION DEVICES PART 1 - GENERAL SECTION 23 37 13 - AIR DISTRIBUTION DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01

More information

ELM6375DX DRAINABLE ADJUSTABLE LOUVER EXTRUDED ALUMINUM

ELM6375DX DRAINABLE ADJUSTABLE LOUVER EXTRUDED ALUMINUM RUSKIN 3900 Dr. Greaves Rd. Grandview, MO 64030 (816) 761-7476 FAX (816) 966-1655 ELM6375DX DRAINABLE ADJUSTABLE LOUVER EXTRUDED ALUMINUM STANDARD CONSTRUCTION FRAME 6 (152) deep, 6063T5 extruded aluminum

More information

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

SECTION LOUVERS AND VENTS

SECTION LOUVERS AND VENTS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 08 90 00 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

SECTION HVAC DUCTS AND CASINGS

SECTION HVAC DUCTS AND CASINGS SECTION 23 31 00 HVAC DUCTS AND CASINGS PART 1 -GENERAL 1.1 SUMMARY A. Section includes metal ductwork, nonmetallic ductwork, casing and plenums, buried ductwork, kitchen hood ductwork, duct cleaning.

More information

SECTION AIR DUCT CLEANING

SECTION AIR DUCT CLEANING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

ESD-635. Stationary Louver Drainable Blade. Application and Design. Standard Construction. Options (at additional cost)

ESD-635. Stationary Louver Drainable Blade. Application and Design. Standard Construction. Options (at additional cost) Application and Design Stationary Louver Drainable Blade is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates drain gutters in the head

More information

SECTION HVAC GRAVITY VENTILATORS

SECTION HVAC GRAVITY VENTILATORS SECTION 23 37 23 HVAC GRAVITY VENTILATORS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

EDD-601. Stationary Louver Dual Drainable Blade. Application and Design. Standard Construction

EDD-601. Stationary Louver Dual Drainable Blade. Application and Design. Standard Construction Application and Design is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates a drainable head member and stationary horizontal blades to

More information

ESJ-401RM. Stationary Louver J Blade. Application and Design. Standard Construction. Options (at additional cost)

ESJ-401RM. Stationary Louver J Blade. Application and Design. Standard Construction. Options (at additional cost) Stationary Louver J Blade Application and Design is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates J style blades, sloped sill and

More information

ESD-435X. Florida Product Approved Drainable Blade Louver. Application and Design. Standard Construction. Qualified Shapes

ESD-435X. Florida Product Approved Drainable Blade Louver. Application and Design. Standard Construction. Qualified Shapes Application and Design Florida Product Approved Drainable Blade Louver is a Florida Product Approved stationary drainable blade extruded aluminum louver designed to protect air intake and exhaust openings

More information

ESD-403. Stationary Louver Drainable Blade. Application and Design. Standard Construction. Options (at additional cost)

ESD-403. Stationary Louver Drainable Blade. Application and Design. Standard Construction. Options (at additional cost) Application and Design Stationary Louver Drainable Blade is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates a drainable head member

More information

EAD-635. Adjustable Louver Drainable Blades. Application and Design. Standard Construction. Options (at additional cost)

EAD-635. Adjustable Louver Drainable Blades. Application and Design. Standard Construction. Options (at additional cost) Application and Design Adjustable Louver Drainable Blades is an adjustable louver designed to protect air intake and exhaust openings in building exterior walls that require tight air shut off. Design

More information

Fire Dampers. Required information:

Fire Dampers. Required information: Fire Dampers Description: Fire dampers are designed to restrict the spread of fire through ventilation systems by snapping shut when the fusible link melts. 1. What are the dimensions of the damper? Width

More information

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION SECTION 230713 DUCT INSULATION PART 1 GENERAL 1.1 SUMMARY A. Related Sections: 1. 233113 Ductwork and Accessories 1.2 REFERENCES A. American Society for Testing and Materials (ASTM): 1. E84-96a Test Method

More information

Wall Louvers (10200)

Wall Louvers (10200) Wall Louvers 08 90 00 (10200) PART 1 GENERAL SECTION INCLUDES A. Fixed, extruded-aluminum horizontal storm resistant louver RELATED SECTIONS A. Section 05120 - Structural Steel: Supports for penthouses.

More information

SED-501. Sightproof Louver Drainable Blade. Application and Design

SED-501. Sightproof Louver Drainable Blade. Application and Design Application and Design is a sightproof weather louver designed to protect air intake and exhaust openings in building exterior walls when visual see through prevention is needed. Design incorporates a

More information

EME6325D WIND-DRIVEN RAIN RESISTANT STATIONARY LOUVER

EME6325D WIND-DRIVEN RAIN RESISTANT STATIONARY LOUVER 3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 EME6325D WIND-DRIVEN RAIN RESISTANT STATIONARY LOUVER MIAMI-DADE APPROVED MIAMI-DADE COUNTY, FLORIDA NOTICE OF ACCEPTANCE NUMBER:

More information

EDK-402. Stationary Louver K Blade. Application and Design. Standard Construction. Options (at additional cost)

EDK-402. Stationary Louver K Blade. Application and Design. Standard Construction. Options (at additional cost) Application and Design Stationary Louver K Blade is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates drainable head, K style blades,

More information

Price Egg Crate Grille

Price Egg Crate Grille Price Egg Crate Grille Division 23 Heating, Ventilating, and Air Conditioning Section 23 37 13 Diffusers, Registers, and Grilles The following specification is for a defined application. Price would be

More information

Louvers Selection, Design Considerations and Details Written by Matt Trentham, R.L. Craig Company, Inc.

Louvers Selection, Design Considerations and Details Written by Matt Trentham, R.L. Craig Company, Inc. Louvers Selection, Design Considerations and Details Written by Matt Trentham, R.L. Craig Company, Inc. Louvers are a basic and simple part of many HVAC systems and buildings, but they are often overlooked

More information

EACC-601. Combination Louver/Damper Concealed Actuator. Application and Design. Standard Construction

EACC-601. Combination Louver/Damper Concealed Actuator. Application and Design. Standard Construction Application and Design Concealed Actuator is a combination louver/damper designed to protect air intake and exhaust openings in building exterior walls that, at times, require tight air shut off. Design

More information

SECTION METAL DUCTS

SECTION METAL DUCTS SECTION 15815 METAL DUCTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

6 Drainable Louver. Update to Louvers Catalog C-1.0. Catalogue Page 2 Page 7. Page LP-13. Submittals Drawing

6 Drainable Louver. Update to Louvers Catalog C-1.0. Catalogue Page 2 Page 7. Page LP-13. Submittals Drawing 6 Drainable Louver Section Page Number Catalogue Page 2 Page 7 Performance Data Page LP-12 Page LP-13 Submittals Drawing 237947 Update to Louvers Catalog C-1.0 April 2010 Louvers General Product Overview

More information

SECTION ALUMINUM STORM WINDOWS

SECTION ALUMINUM STORM WINDOWS PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 08 51 69.11 ALUMINUM STORM WINDOWS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Also delete any other item or paragraph not applicable

More information

Price Single Duct Terminal Units

Price Single Duct Terminal Units Price Single Duct Terminal Units Division 23 Heating, Ventilating, and Air Conditioning Section 23 36 00 Air Terminal Units The following specification is for a defined application. Price would be pleased

More information

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM PART 1- GENERAL 1.1 SUMMARY A. Section Includes: SECTION 084523 - SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM 1. Flat factory prefabricated structural insulated translucent sandwich panels; with glazed endwalls.

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

ESF-145. Thin-line Louver Flat Blade. Application and Design. Standard Construction. Options (at additional cost)

ESF-145. Thin-line Louver Flat Blade. Application and Design. Standard Construction. Options (at additional cost) Application and Design Flat Blade is a thin-line stationary louver commonly used for interior or exterior applications where high free area and low airflow resistance is required. The narrow depth makes

More information

1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.

1. Division 23 Section Hangers and Supports for HVAC Piping and Equipment for pipe insulation shields and protection saddles. SECTION 23 07 19 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Sample Specification

Sample Specification POWERS FASTENERS Sample Specification Section 23 30 xx HVAC Ducts and Casings The intent of this Sample Specification is to illustrate the use of ICC ES Acceptance Criteria as reference standards in the

More information

ESU-150. Thin-line Louver Thin-line Blade. Application and Design. Standard Construction. Options (at additional cost)

ESU-150. Thin-line Louver Thin-line Blade. Application and Design. Standard Construction. Options (at additional cost) Application and Design Thin-line Blade is a thin-line stationary louver commonly used for interior or exterior applications where high free area and low airflow resistance is required. The narrow depth

More information

GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM

GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM 1 GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM 1.01 WORK INCLUDED PART 1: GENERAL A. Provide for all labor, equipment, materials, and services to furnish and install VERSA SHIELD Window

More information

Questar ThermWise Duct Technical Specifications

Questar ThermWise Duct Technical Specifications Questar ThermWise Duct Technical Specifications 1. Introduction and Scope: This document sets forth the specifications for duct sealing and duct insulation in accordance to Questar ThermWise Weatherization

More information

GUIDE SPECIFICATION: DUCT LINER

GUIDE SPECIFICATION: DUCT LINER GUIDE SPECIFICATION: DUCT LINER This specification guide includes thermal & acoustical insulation for ductwork and air handling systems. This section is based on the format recommended by MICA (Midwest

More information

SECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 08332 [08 33 13] COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Metal Counter

More information

SECTION HVAC INSULATION

SECTION HVAC INSULATION PART 1 GENERAL 1.1 SUMMARY SECTION 23 07 00 HVAC INSULATION A. Section Includes: 1. Ductwork insulation. 2. Duct liner. 3. Insulation jackets. 4. Equipment insulation 5. Piping system insulation. 6. Insulation

More information

11/2 HOUR UL CLASSIFIED CURTAIN TYPE (D)IBD2, (D)IBD2SS AND IBDT FIRE DAMPERS

11/2 HOUR UL CLASSIFIED CURTAIN TYPE (D)IBD2, (D)IBD2SS AND IBDT FIRE DAMPERS 3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 INSTALLATION INSTRUCTIONS 11/2 HOUR UL CLASSIFIED CURTAIN TYPE (D)IBD2, (D)IBD2SS AND IBDT FIRE DAMPERS APPLICATION The fire

More information

SECTION AIR FILTERS

SECTION AIR FILTERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

SP Standard Profile. Flanged to Duct Install Type THERMAL BREAKS OPPOSED ACTION PARALLEL ACTION. T.A. Morrison & Co. Inc.

SP Standard Profile. Flanged to Duct Install Type THERMAL BREAKS OPPOSED ACTION PARALLEL ACTION.  T.A. Morrison & Co. Inc. 1 SUBMITTAL DATA Series 9000 BF Thermally Insulated Damper with Thermally Broken Frames & Blades SP Standard Profile Flanged to Duct Install Type THERMAL BREAKS OPPOSED frame is 4 (101.6 mm) deep x 1 (25.4

More information

A. Access doors and frames are part of an access door and frame allowance.

A. Access doors and frames are part of an access door and frame allowance. SECTION 08 31 13 ACCESS DOORS AND FRAMES PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

ALUMINIUM SAND TRAP LOUVER : CONSTRUCTION

ALUMINIUM SAND TRAP LOUVER : CONSTRUCTION ALUMINIUM SAND TRAP LOUVER : CONSTRUCTION RUSKIN sand trap louvers are specially designed to separated the sand and dust from the air. It is effective and necessary to apply for ventilations and inlet

More information

GUIDE SPECIFICATION EXETER SECURITY SHIELD SECURITY WINDOW BARRIER SYSTEM

GUIDE SPECIFICATION EXETER SECURITY SHIELD SECURITY WINDOW BARRIER SYSTEM 1 GUIDE SPECIFICATION EXETER SECURITY SHIELD SECURITY WINDOW BARRIER SYSTEM 1.01 WORK INCLUDED PART 1: GENERAL A. Provide for all labor, equipment, materials and services to furnish and install SECURITY

More information

Section BUILDINGS, SHELTERS, ENCLOSURES

Section BUILDINGS, SHELTERS, ENCLOSURES Section 13121 BUILDINGS, SHELTERS, ENCLOSURES Part 1 GENERAL 1.1 SECTION INCLUDES 1.2 A. Pre-engineered buildings. B. Pre-engineered shelters. C. Pre-engineered enclosures. D. Electrical wiring and devices

More information

A. Pipe Supports: ANSI B 31.1, Power Piping. B. Automatic Sprinkler Pipe Supports: Refer to Section

A. Pipe Supports: ANSI B 31.1, Power Piping. B. Automatic Sprinkler Pipe Supports: Refer to Section SECTION 15140 SUPPORTS, ANCHORS, AND SEALS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract including General and Supplementary Conditions, Division 1 Specification

More information

PRESTON HEALTH SERVICES ARCHITECT'S NO. 2700

PRESTON HEALTH SERVICES ARCHITECT'S NO. 2700 SECTION 09 5113 - ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

DIVISION 11 - EQUIPMENT FOOD SERVICE EQUIPMENT LABORATORY FUME HOODS. A. Design Considerations

DIVISION 11 - EQUIPMENT FOOD SERVICE EQUIPMENT LABORATORY FUME HOODS. A. Design Considerations DIVISION 11 - EQUIPMENT 11400 FOOD SERVICE EQUIPMENT A. Design Considerations 1. The A/E shall use the services of a food service equipment specialist in preparation of kitchen areas and other food preparation

More information

INDIA HABITAT CENTRE New Delhi

INDIA HABITAT CENTRE New Delhi INDIA HABITAT CENTRE New Delhi Tender For Renovation of Exhaust Air Ducting Works in Basements Date: January, 2014 Prepared by Sterling India Consulting Engineers New Delhi, India TABLE OF CONTENTS S.No.

More information

Sheet Metal Connectors, Inc.

Sheet Metal Connectors, Inc. Sheet Metal Connectors, Inc. HVAC ACCESSORY PRICE CATALOG JANUARY 1, 2004 CONTRACTOR PRICES POLYKEN TAPES ELGEN PRODUCTS TEK & ZIP SCREWS DP1010 DUCT SEALANT MINNEAPOLIS, MN ROCKFORD, IL 5850 Main Street

More information

SPECIFICATION SECTION PART 1 GENERAL

SPECIFICATION SECTION PART 1 GENERAL PART 1 GENERAL 1.01 Summary A. Furnish and install louvers, bird screens, blank-off panels, structural supports and attachment brackets as shown on the drawings, as specified, and as needed for a complete

More information

This Design guideline contained herein includes the requirements for mechanical insulation at The University of Texas at Austin

This Design guideline contained herein includes the requirements for mechanical insulation at The University of Texas at Austin PART 1: GENERAL 1.01 Purpose: This Design guideline contained herein includes the requirements for mechanical insulation at The University of Texas at Austin 1.02 Scope: A. Extent of mechanical insulation

More information

Aluminum-Framed Entrances and Storefronts

Aluminum-Framed Entrances and Storefronts University of New Hampshire University of New Hampshire Scholars' Repository Division 08 Openings Chapter 5 Technical Construction and Renovation Standards 1-25-2013 084113 - Aluminum-Framed Entrances

More information

DIVISION 10 SPECIALTIES SECTION OPERABLE PARTITIONS

DIVISION 10 SPECIALTIES SECTION OPERABLE PARTITIONS DIVISION 10 SPECIALTIES SECTION 10 22 26 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board. 1.2 RELATED WORK A. Installation of steel framing members for walls, partitions,

More information

TYP. SINGLE PLY ROOFING ROOF SHEETING BROAN VENT CAP #10 x 1" GASKETED SMS TYP. 4 SIDES 8" FRAMED CURB HVAC SYSTEMS "BASIS OF DESIGN" ROOF INSULATION R-19 WALL INSULATION R-13 LIGHTING EFFIECNCY PER STANDARDS

More information

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017 SECTION 10505 - METAL STUDENT LOCKERS PART 1 - GENERAL 1.01 SCOPE OF WORK A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION SECTIONAL OVERHEAD DOORS

SECTION SECTIONAL OVERHEAD DOORS SECTION 08360 SECTIONAL OVERHEAD DOORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Aluminum Doors B. Track and Framing 1.2 RELATED SECTIONS A. Section 04810 - Unit Masonry Assemblies: Prepared opening in masonry.

More information

SECTION METAL ROOF PANELS

SECTION METAL ROOF PANELS SECTION 07 41 13 PART 1 GENERAL 1.1 SECTION INCLUDES A. Standing-seam roof panels. B. Metal roofing accessories. 1.2 RELATED SECTIONS A. Section 07 62 00 - Sheet Metal Flashing. B. Section 07 72 00 - Roof

More information

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and

More information

SECTION PRE-ENGINEERED MEMBRANE STRUCTURE

SECTION PRE-ENGINEERED MEMBRANE STRUCTURE SECTION 13125 PART 1 - GENERAL 1.1 SUMMARY A. Section includes the design, engineering, fabrication and erection of a frame-supported, tensilemembrane structure complete with entrance and exit doors and

More information

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2) Inspection of Fabricators (1704.2) Furnish inspection reports (1704.2.1) - Fabricators that have not been approved Provide a Certificate of Compliance (1704.2.2) - Approved Fabricators Steel Construction

More information

PROJECT LOCATION SECTION COPPER METAL PLATE WALL PANELS

PROJECT LOCATION SECTION COPPER METAL PLATE WALL PANELS SECTION 07 4213.25 PART 1- GENERAL 1.01 SECTION INCLUDES A. Copper metal plate wall panels. 1.02 RELATED REQUIREMENTS A. Section 05 4000 Cold-Formed Metal Framing: Wall panel substrates support framing.

More information

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows: SECTION 16130 (Master Template Final-05) ELECTRICAL BOXES PART 1 GENERAL 1.01 SECTION INCLUDES A. Provide boxes for electrical equipment and wiring devices as follows: 1. Wall and ceiling outlet boxes.

More information

B. Polyethylene samples shall be submitted for Owner approval of color and quality.

B. Polyethylene samples shall be submitted for Owner approval of color and quality. Glass Rail ENGINEERED DASHERBOARD SPECIFICATIONS PART 1 - GENERAL 1.01 PROJECT SCOPE A. Contractor shall furnish and install one complete set of steel framed dasherboards as indicated on the drawings and

More information

Alply CLASSIC WALL Architectural Insulated Panel Wall System

Alply CLASSIC WALL Architectural Insulated Panel Wall System SECTION 07 42 13 INSULATED METAL WALL PANELS ALPLY Insulated Panels Alply CLASSIC WALL Architectural Insulated Panel Wall System PART 1 / GENERAL 1.1 SYSTEM DESCRIPTION A. Smooth, non-embossed steel, insulated

More information

SECTION PIPING INSULATION

SECTION PIPING INSULATION SECTION 23 07 19 PIPING INSULATION PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Piping insulation for refrigerant piping within building envelope. 2. Furnishing and installation of insulation.

More information

SECTION ALUMINUM WINDOWS

SECTION ALUMINUM WINDOWS SECTION 08520 ALUMINUM WINDOWS PART 1 - GENERAL 1.01 SUMMARY A. Section includes: 1. Storefront systems and aluminum framed glass doors. 2. Hardware, fasteners, accessories, filler pieces, etc., required

More information

BEARING METAL STUD FRAMING

BEARING METAL STUD FRAMING L-1 Section 05410 Long Form Specification LOAD BEARING METAL STUD FRAMING This section includes axially loaded steel studs, with unique slotted top channels, usually of 0.91, 1.2 and 1.5 mm (16, 18, or

More information

SECTION PERSONNEL DUTY LOCKERS. 1. FPPL Series Police Personnel Duty Lockers, including the following:

SECTION PERSONNEL DUTY LOCKERS. 1. FPPL Series Police Personnel Duty Lockers, including the following: SECTION 10501 PERSONNEL DUTY LOCKERS PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 specifications

More information

PRE-ENGINEERED METAL BUILDING SYSTEM

PRE-ENGINEERED METAL BUILDING SYSTEM PRE-ENGINEERED METAL BUILDING SYSTEM PART 1 GENERAL 1.1 SUMMARY A. The building shall include all primary and secondary structural framing members, connection bolts, roof and wall covering, flashing, gutter,

More information

DIVISION 13 - SPECIAL CONSTRUCTION SECTION ACOUSTICAL PANEL ENCLOSURE

DIVISION 13 - SPECIAL CONSTRUCTION SECTION ACOUSTICAL PANEL ENCLOSURE DIVISION 13 - SPECIAL CONSTRUCTION SECTION 13080 - ACOUSTICAL PANEL ENCLOSURE 1 GENERAL 1.01 SUMMARY A. ACOUSTIC ENCLOSURE CONSISTING OF WALLS, CEILING, STRUCTURAL FRAMING, CONNECTING MEMBERS, DOORS, WINDOWS,

More information

Document number CURTAIN FIRE DAMPERS

Document number CURTAIN FIRE DAMPERS Document number 481324 CURTAIN FIRE DAMPERS DFD, DFD-150X, FD, FD-150X, SSDFD, SSFD, AND KFD Series 1 1 2 and 3 Hour Curtain Fire s Vertical and Horizontal Mount Installation, Operation and Maintenance

More information

SECTION EXPANSION CONTROL

SECTION EXPANSION CONTROL SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

FIBERGLASS ROUND CONTROL DAMPERS. Model K-RD INTRODUCTION M.K. PLASTICS PROVIDES FOUR DAMPER MODELS K-RD SUGGESTED SPECIFICATION

FIBERGLASS ROUND CONTROL DAMPERS. Model K-RD INTRODUCTION M.K. PLASTICS PROVIDES FOUR DAMPER MODELS K-RD SUGGESTED SPECIFICATION INTRODUCTION The M.K. Plastics series K-RD are manufactured to meet the needs of the odor control and corrosive HVAC industries by providing a corrosion-resistant FRP Damper that is used to regulate an

More information

Hardin County Planning and Development Commission

Hardin County Planning and Development Commission Location by Climate Zone: Hardin County (per Table N1101.2), and the entire state of Kentucky is located in Climate Zone 4, the HDD is 4000 to 4999. Building Requirements; Building Thermal Envelope The

More information

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

Noise Control. Commercial, Industrial, and Environmental Products and Solutions.

Noise Control. Commercial, Industrial, and Environmental Products and Solutions. Noise Control Commercial, Industrial, and Environmental Products and Solutions www.kineticsnoise.com Commercial Duct Silencers Kinetics Noise Control offers the design and engineering assistance to integrate

More information

Aluminum Flush Doors and Frames SPECIFICATIONS. Section [8120] PART 1 GENERAL

Aluminum Flush Doors and Frames SPECIFICATIONS. Section [8120] PART 1 GENERAL Aluminum Flush Doors and Frames SPECIFICATIONS Section 081116 [8120] Cline Aluminum Doors, Inc. 112 32nd Avenue West Bradenton, FL 34205-8907 Toll-Free (800) 648-6736 Office (941) 746-4104 Fax (941) 746-5153

More information

MODERNFOLD GWS 100SR-G MOVEABLE GLASS WALLS

MODERNFOLD GWS 100SR-G MOVEABLE GLASS WALLS MODERNFOLD GWS 100SR-G MOVEABLE GLASS WALLS Ideal for applications requiring space division, visibility and security Used in bank lobbies, offices, conference areas, interior storefronts and arena skyboxes

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: CITADEL ARCHITECTURAL PRODUCTS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: CITADEL ARCHITECTURAL PRODUCTS, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1015 Reissued 04/2017 This report is subject to renewal 04/2019. DIVISION: 07 00

More information

SPECIFICATIONS FOR AluSystems Aluminum Composite Panels Series 20 Dry Joint 1.00 GENERAL 1.01 RANGE OF WORK Section includes: Laminated panels and attachment systems for use as exterior cladding. A. Provide

More information

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

SECTION BASIC ELECTRICAL MATERIALS AND METHODS SECTION 26 05 05 BASIC ELECTRICAL MATERIALS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the limited scope construction materials and methods for application with electrical installations as follows:

More information

A. This Section includes acoustical panel ceilings installed with exposed suspension systems.

A. This Section includes acoustical panel ceilings installed with exposed suspension systems. SECTION 09511 ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Acousti-Seal Encore Paired Panel (10650) Operable Partitions

Acousti-Seal Encore Paired Panel (10650) Operable Partitions Acousti-Seal Encore Paired Panel 10 22 26 (10650) Operable Partitions Optimal choice for straight-line openings that do not require multiple locations or offset storage Panels are hinged together in groups

More information

SECTION COMPOSITE METAL WALL PANEL SYSTEM (Accu-Trac Low Profile DS)

SECTION COMPOSITE METAL WALL PANEL SYSTEM (Accu-Trac Low Profile DS) SECTION 07412 COMPOSITE METAL WALL PANEL SYSTEM (Accu-Trac Low Profile DS) PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Series - 1

Series - 1 SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word

More information

Signature Series 5 Lap SECTION ALUMINUM WINDOWS

Signature Series 5 Lap SECTION ALUMINUM WINDOWS Signature Series 5 Lap SECTION 08 51 13 ALUMINUM WINDOWS PART 1 GENERAL 1.01 SUMMARY A. Related Documents: Conditions of the Contract, Division 1 - General Requirements, and Drawings apply to Work of this

More information

COMPLETE REVISION November Process Industry Practices Architectural. PIP ARS08111 Standard Steel Doors and Frames Supplier Specification

COMPLETE REVISION November Process Industry Practices Architectural. PIP ARS08111 Standard Steel Doors and Frames Supplier Specification November 2012 Process Industry Practices Architectural PIP ARS08111 Standard Steel Doors and Frames Supplier Specification PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost

More information

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018)

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018) BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018) PERMIT SUBMITTAL CHECKLIST: Signed and completed Building Permit application form. A separate Electrical permit is required from

More information

Architectural Single-Hung Aluminum Window Series L701T SH-AW130 GUIDE SPECIFICATION

Architectural Single-Hung Aluminum Window Series L701T SH-AW130 GUIDE SPECIFICATION Architectural Single-Hung Aluminum Window Series L701T SH-AW130 GUIDE SPECIFICATION Section 08520 Aluminum Windows PART 1: WORK INCLUDED A. The conditions of the contract and applicable sections of Division

More information

Crawl Space Moisture Control

Crawl Space Moisture Control Crawl Space Moisture Control Crawl space foundations are found in many homes. Typically, these foundation types are equipped with operable vents designed to provide ventilation for moisture control. Unfortunately,

More information

WHERE HIGH EFFICIENCY IS THE STANDARD

WHERE HIGH EFFICIENCY IS THE STANDARD ACCESS DOORS 2017 WHERE HIGH EFFICIENCY IS THE STANDARD EXPERIENCE Milcor offers years of experience in the manufacture of a broad range of products and services for residential, commercial, institutional

More information

MERCHANTS METALS. A. ASTM F552 Standard Terminology Relating to Chain Link Fencing

MERCHANTS METALS. A. ASTM F552 Standard Terminology Relating to Chain Link Fencing MERCHANTS METALS SECTION 32 31 13 COLORBOND CHAIN LINK FENCE AND GATES 2014 PART 1 GENERAL 1.1 RELATED DOCUMENTS A. DIVISION 01 - GENERAL REQUIREMENTS: Drawings, quality, product and performance requirements,

More information

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION CHAPTER 26 PLASTIC SECTION BC 2601 GENERAL 2601.1 Scope. These provisions shall govern the materials, design, application, construction and installation of foam plastic, foam plastic insulation, plastic

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 12 2113 - LOUVER BLINDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519 METAL CLAD CABLE - MC-PLUS Neutral

More information

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck)

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck) SECTION 13125 ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck) PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1 Louis Armstrong New Orleans International Airport NOAB Project # 8910-01233 PART 1 - GENERAL SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS 1.1 RELATED DOCUMENTS A. Drawings and general provisions

More information

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT SECTION 230548 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Elastomeric Isolation pads. 2. Elastomeric Isolation mounts. 3. [Freestanding] [Restrained] [Freestanding and restrained]

More information