SDI-C-2011 Standard for Composite Steel Floor Deck-Slabs 30 November General

Size: px
Start display at page:

Download "SDI-C-2011 Standard for Composite Steel Floor Deck-Slabs 30 November General"

Transcription

1 General SDI-C-2011 Standard for Composite Steel Floor Dek-Slabs 30 November Sope: A. This Standard for Composite Steel Floor Dek-Slabs, hereafter referred to as the Standard, shall govern the materials, design, and eretion of omposite onrete slabs utilizing old formed steel dek funtioning as a permanent form and as reinforement for positive moment in floor and roof appliations in buildings and similar strutures. B. The Appendies shall be part of the Standard. C. The User Notes, User Note Attahments, and Commentary shall not be part of the Standard. User Note: User Notes, User Note Attahments, and Commentary are intended to provide pratial guidane in the use and appliation of this Standard. D. Where the Standard refers to designer, this shall mean the entity that is responsible to the Owner for the overall strutural design of the projet, inluding the steel dek. User Note: This is usually the Strutural Engineer of Reord. E. Equations that appear in this Standard are ompatible with the inh-pounds system of units. However, any onsistent system of units shall be permitted to be used. SI units or equations shown in parentheses in this standard are for information only, and are not part of this Standard. F. Terms not defined in this Standard, AISI S100 or AISI/AISC shall have the ordinary aepted meaning for the ontext for whih they are intended. G. It shall be permitted to speify dek base metal thikness either by dimensional thikness, or by gage when the relationship of base metal thikness to gage has been defined by the dek manufaturer. However, for the purpose of design, the dimensional thikness shall be used. User Note: Both AISI and SDI now speify steel thikness in terms of design thikness in lieu of gage thikness. Gage thiknesses, however, are still ommonly referred to in the metal dek industry. Table UN-1.1 shows ommon gages and orresponding unoated design and minimum steel thiknesses. Table UN-1.1 Gage No. Design Thikness Minimum Thikness 1 in. mm. in. mm Minimum thikness is 95% of the design thikness 1.2 Referene Codes, Standards, and Douments: 1

2 : A. Codes and Standards: The following douments or portions thereof are referened in this standard and shall be onsidered part of the requirements of this Standard. Where these douments onflit with this standard, the requirements of this Standard shall ontrol: 1. Amerian Conrete Institute (ACI) a. ACI , Building Code Requirements for Strutural Conrete 2. Amerian Iron and Steel Institute (AISI) a. AISI S w/s2-10, North Amerian Speifiation for the Design of Cold-Formed Steel Strutural Members, Inluding Supplement 2 (February 2010) b. AISI S905-08, Test Methods for Mehanially Fastened Cold-Formed Steel Connetions. AISI S907-08, Test Standard for Cantilever Test Method for Cold- Formed Steel Diaphragms d. AISI/AISC, Standard Definitions for Use in the Design of Steel Strutures, 2007 edition 3. Amerian Institute of Steel Constrution (AISC) a. ANSI/AISC , Speifiation for Strutural Steel Buildings 4. Amerian Soiety for Testing and Materials (ASTM) a. ASTM A615 / A615M - 09b Standard Speifiation for Deformed and Plain Carbon-Steel Bars for Conrete Reinforement b. ASTM A653 / A653M - 10 Standard Speifiation for Steel Sheet, Zin-Coated (Galvanized) or Zin-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Proess. ASTM A706 / A706M - 09b Standard Speifiation for Low-Alloy Steel Deformed and Plain Bars for Conrete Reinforement d. ASTM A820 / A820M 06, Standard Speifiation for Steel Fibers for Fiber-Reinfored Conrete e. ASTM A1008 / A1008M - 10, Standard Speifiation for Steel, Sheet, Cold-Rolled, Carbon, Strutural, High-Strength Low-Alloy, High- Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardenable f. ASTM A1064 / A1064M - 10 Standard Speifiation for Steel Wire and Welded Wire Reinforement, Plain and Deformed, for Conrete g. ASTM C1116 / C1116M - 10 Standard Speifiation for Fiber- Reinfored Conrete h. ASTM D7508 / D7508M - 10 Standard Speifiation for Polyolefin Chopped Strands for Use in Conrete 5. Amerian Soiety of Civil Engineers (ASCE) a. SEI/ASCE 7-10, Minimum Design Loads for Buildings and Other Strutures 6. Amerian Welding Soiety (AWS) a. AWS D1.1:2010, Strutural Welding Code-Steel b. AWS D1.3:2008, Strutural Welding Code-Sheet Steel 7. Steel Dek Institute (SDI) a. SDI-T-CD-2011, Test Standard for Composite Steel Dek-Slabs 2

3 B. Referene Douments: The following douments or portions thereof are referened in this standard and shall be onsidered part of the requirements of this Standard. Where these douments onflit with this standard, requirements of this Standard shall govern: 1. Steel Dek Institute (SDI) a. SDI-DDM, Diaphragm Design Manual, 3 rd Edition, inluding Appendies I through VI User Note: The following douments are referened within the user notes: 1. Amerian Assoiation of State Highway and Transportation Offiials (AASHTO) a. AASHTO LRFD Bridge Design Speifiations, Customary U.S. Units, 5th Edition, with 2010 Interim Revisions 2. Amerian Conrete Institute (ACI) a. ACI 215R-92, Considerations for Design of Conrete Strutures Subjeted to Fatigue Loading b. ACI 302.1R-04, Guide for Conrete Floor and Slab Constrution. ACI 224.1R-07, Causes, Evaluation, and Repair of Craks in Conrete Strutures d. ACI , Building Code Requirements for Strutural Conrete e. ACI 544 3R-08, Guide for the Speifiation, Proportioning and Prodution of Fiber Reinfored Conrete f. ACI Conrete Terminology, 3. Amerian Institute of Steel Constrution (AISC) a. AISC Design Guide No. 11, Floor Vibrations Due to Human Ativity, Amerian Iron and Steel Institute (AISI) a. AISI S w/s2-10, North Amerian Speifiation for the Design of Cold-Formed Steel Strutural Members, Inluding Supplement 2 (February 2010) b. AISI S907-08, Test Standard for Cantilever Test Method for Cold- Formed Steel Diaphragms 5. Amerian Soiety for Testing and Materials (ASTM) a. ASTM A653 / A653M - 10 Standard Speifiation for Steel Sheet, Zin-Coated (Galvanized) or Zin-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Proess b. ASTM A1008 / A1008M - 10, Standard Speifiation for Steel, Sheet, Cold-Rolled, Carbon, Strutural, High-Strength Low-Alloy, High- Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardenable. ASTM E119-10b,, Standard Test Methods for Fire Tests of Building Constrution and Materials 6. Conrete Reinforing Steel Institute (CRSI) a. CRSI Manual of Standard Pratie, 28 th Edition, Steel Dek Institute (SDI) a. SDI-CDD, Composite Dek Design Handbook, 2 nd Edition b. SDI-DDM, Diaphragm Design Manual, 3 rd Edition, inluding Appendies I through VI. SDI-MDCQ, Metal Dek and Conrete Quantities (SDI White Paper) d. SDI-MOC, Manual of Constrution with Steel Dek, 2 nd Edition 3

4 e. SDI Position Statement Use of Composite Steel Floor Dek in Parking Garages. 8. Underwriters Laboratories (UL) a. Fire Resistane Diretory 9. Wire Reinforing Institute (WRI) a. WWR-500-R-10, Manual of Standard Pratie-Strutural Welded Wire Reinforement 1.3 Constrution Douments: The onstrution douments shall desribe the omposite slabs that are to be onstruted and shall inlude not less than the following information: A. Loads 1. Composite slab loads as required by the appliable building ode. Where appliable, load information shall inlude onentrated loads. 2. Assumed onstrution phase loads. B. Strutural framing plans for all omposite slabs showing the size, loation and type of all dek supports. C. Dek and Dek Attahment 1. Depth, type (profile), and design thikness. 2. Dek material (inluding yield strength) and dek finish, 3. Dek attahment type, spaing, and details. D. Conrete and Reinforing 1. Speified onrete strength, f 2. Speified onrete density (and tolerane if required for fire rating assembly) 3. Speified strength or grade of reinforing steel or welded wire reinforement (if used) 4. Size, extent and loation of all reinforement (if used) 5. Slab thiknesses 6. Disontinuous fiber reinforement material, type and dosage (if used). User Note: The following is an example of a omposite slab as it ould be speified on the ontrat drawings: Composite slab shall onsist of 2 inh deep G-60 galvanized omposite steel dek, design thikness inh (20 gage), (Type XX by XX, In or approved equivalent) with 3 inh thik, 3000 psi, normal-weight onrete topping (total thikness = 5 inhes) reinfored with XXX. 2. Produts 2.1 Material: A. All sheet steel used for dek or aessories shall have a minimum speified yield stress that meets or exeeds 33 ksi (230 Mpa). 1 For the ase where the steel dek ats as a form, design yield and tensile stresses shall be determined in aordane with AISI S100, Setion A2. 2. For the ase where the steel dek ats as tensile reinforement for the omposite dek-slab, the steel shall onform to AISI S100, Setion A2. When the dutility of the steel measured over a two-inh (50 mm) gage length is 10% or greater, the maximum design yield stress shall not exeed the lesser of 50 ksi or Fy. When the dutility of the steel measured over a two-inh (50 mm) gage length is less than 10%, the maximum design yield stress shall not exeed the lesser of 50 ksi (345 Mpa) or 0.75 Fy. 4

5 When the dutility of the steel used for dek, measured over a two-inh (50 mm) gage length, is less than 10%, the ability of the steel to be formed without raking or splitting shall be demonstrated. B. Sheet steel for dek shall onform to AISI S100, Setion A2. Commentary: Most steel dek is manufatured from steel onforming to ASTM A1008 /A1008M, Strutural Sheet for unoated or unoated top/painted bottom dek or from ASTM A653 / A653M, Strutural Sheet for galvanized dek. In most ases the designer will hoose one finish or the other. However, both types of finish may be used on a projet, in whih ase the designer must indiate on the plans and projet speifiations the areas in whih eah is used. (Refer to Setion 2.3 of this standard). Stainless steel is not reommended due to the lak of available performane data. C. Sheet steel for aessories that arry defined loads shall onform to AISI S100, Setion A2. Sheet steel for non-strutural aessories that do not arry defined loads shall be permitted to be any steel that is adequate for the proposed appliation. D. Conrete and Reinforement: 1. Conrete plaed on steel dek shall onform to ACI 318, Chapters 3, 4 and 5, exept as modified by Setions 2.1.D.2 and 2.1.D The speified onrete ompressive strength shall not be less than 3000 psi (21 MPa). The maximum ompressive strength used to alulate the strength of the omposite dek-slab shall not exeed 6000 psi (42 MPa). User Note: Load tables and labeled fire resistant rated assemblies may require onrete ompressive strengths in exess of 3000 psi. The average ompressive strength of the onrete may exeed 6000 psi, but a maximum strength of 6000 psi is to be used in alulating the strength of the omposite dek-slab. 3. Admixtures ontaining hloride salts or other substanes that are orrosive or otherwise deleterious to the steel dek and embedded items shall not be permitted. 4. Steel Reinforing shall onform to the following: a. Deformed reinforing bars: ASTM A615 or ASTM A706. b. Welded wire reinforement: ASTM A Other deformed reinforing bars or welded wire reinforement as permitted by ACI 318, Setion Disontinuous fiber reinforement shall onform to the following: a. Steel fibers: ASTM A820. b. Marosyntheti fibers: ASTM D Tolerane of Delivered Material: A. The minimum unoated steel thikness as delivered to the job site shall not at any loation be less than 95% of the design thikness, however lesser thiknesses shall be permitted at bends, suh as orners, due to old-forming effets. User Note: The minimum delivered thikness is in aordane with AISI S100. B. Panel length shall equal the speified panel length, plus or minus ½ inh (13mm). C. Panel over width shall be no less than 3/8 inh (10 mm) less than the speified panel width, nor more than 3/4 inh (19 mm) greater than the speified width. 5

6 D. Panel amber and/or sweep shall not be greater than 1/4 inh in a 10 foot length (6 mm in 3 m). E. Panel end out of square shall not exeed 1/8 inh per foot of panel width (10 mm per m). 2.3 Finish: A. Galvanizing shall onform to ASTM A653 / A653M B. A shop oat of primer paint (bottom side only) shall be applied to steel sheet if speified by the designer. C. The finish on the steel dek shall be speified by the designer. Commentary: The finish on the steel omposite dek must be speified by the designer and be suitable for the environment to whih the dek is exposed within the finished struture. Beause the omposite dek is the positive bending reinforement for the slab, its servie life should at least be equal to the design servie live of the struture. Zin-Aluminum finishes are not reommended. When omposite dek with an unpainted top and painted bottom is used, the primer oat is intended to protet the steel for only a short period of exposure in ordinary atmospheri onditions and shall be onsidered an impermanent and provisional oating. In highly orrosive or hemial atmospheres or where reative materials ould be in ontat with the steel dek, speial are in speifying the finish should be used, whih ould inlude speialized oatings or materials. If speifying painted dek in areas that require spray-on fireproofing, the paint must be permitted by the appliable fire rated assembly. Not all paints are approved for fire rated assemblies. This requirement must be learly alled out in the ontrat douments. In general, there are three types of fire resistive assemblies; those ahieving the fire resistane by membrane protetion, diret applied protetion, or with an unproteted assembly. Of these three, only the systems that utilize diret applied protetion are onerned with the finish of the steel dek. In these systems, the finish of the steel dek an be the fator that governs the fire resistane rating that is ahieved. In assemblies with diret applied fire protetion the finish (paint) is ritial. In the Underwriters Laboratories Fire Resistane Diretory, some dek manufaturing ompanies have steel dek units that are lassified in some of the D700, D800, and D900-series onrete and steel floor units. These lassified dek units (Classified Steel Floor and Form Units) are shown as having a galvanized finish or a phosphatized/painted finish. These lassified dek units have been evaluated for use in these speifi designs and found aeptable. 2.4 Design: A. Dek as a form 1. Design by either Allowable Strength Design (ASD) or Load and Resistane Fator Design (LRFD) shall be permitted. The setion properties and allowable strength (ASD) or design strength (LRFD) for the steel dek shall be omputed in aordane with AISI S Dek shall be evaluated for strength under the following load ombinations: a. Allowable Stress Design w d + w dd + w l (Eq ) w d + w dd + P l (Eq ) 6

7 w dd + w dl (Eq ) Where: w d = dead weight of onrete w dd = dead weight of the steel dek w l = uniform onstrution live load (ombined with fluid onrete) not less than 20 psf (0.96 kpa) w dl = uniform onstrution live load (ombined with bare dek), not less than 50 psf (2.40 kpa) P l = onentrated onstrution live load per unit width of pounds on a 1 foot width (2.19 kn on a 1 meter width) User Note: The uniform onstrution live load of 20 psf is onsidered adequate for typial onstrution appliations that onsist of onrete transport and plaement by hose and onrete finishing using hand tools. The designer typially has little ontrol over means-and-methods of onstrution, and should bring to the attention of the onstrutor that bulk dumping of onrete using bukets, hutes, or handarts, or the use of heavier motorized finishing equipment suh as power sreeds, may require design of the dek as a form using uniform onstrution live loads, w l,of 50 psf or greater. Setion A1.3.1 requires that the designer inlude the assumed onstrution loads in the onstrution douments and it is suggested that the onstrutions douments require verifiation of adequay by the onstrutor. User Note: The designer should aount for additional loads attributable to onrete ponding due to defletions of the strutural system, inluding dek and support framing. See SDI-MDCQ for additional information. b. Load and Resistane Fator Design 1.6w d + 1.2w dd + 1.4w l (Eq ) 1.6w d + 1.2w dd + 1.4P l (Eq ) 1.2w dd + 1.4w dl (Eq ) Commentary: The load fator used for the dead weight of the onrete is 1.6 beause of delivering methods and an individual sheet an be subjeted to this load. The use of a load fator of 1.4 for onstrution load in LRFD design is alibrated to provide equivalent design results in ASD design. Refer to the ommentary of AISI S100 for additional information. 3. Cantilever spans shall be evaluated for strength under the following load ombinations: a. Allowable Strength Design: Equations and shall be applied to both the antilever span and the adjaent span. The onentrated onstrution live load (P l ) shall be applied at the end of the antilever. b. Load and Resistane Fator Design: Equations and shall be applied to both the antilever span and the adjaent span. The onentrated onstrution live load (P l ) shall be applied at the end of the antilever. 4. Speial loading onsiderations: 7

8 a. The speified onstrution live loads shall be inreased when required by onstrution operations. b. Loads shall be applied in a sequene that simulates the plaement of the onrete, in aordane with Appendix 1. Rational analysis shall be permitted to be used for developing shear and moment diagrams and alulating defletions for non-uniform spans. Commentary: The loading shown in Figure 1 of Appendix 1 is representative of the sequential loading of fresh onrete on the dek. The 150 pound per foot of width (2.19 kn per 1 m of width) load is the equivalent of distributing a 300 pound (1.33 kn) worker over a 2 foot (600 mm) width. Experiene has shown this to be a onservative distribution. Single span dek onditions have no redundany beause they are statially determinate, as opposed to multi-span onditions that are statially indeterminate. Beause of this lak of redundany, additional onsideration should be given to proper speifiation of onstrution live and dead loads. Allowable onstrution spans for single-span dek may be shorter than for multi-span appliations, and the designer must onsider this in loations where it is impossible to install the dek in a multi-span ondition, suh as between stair and elevator towers. Whenever possible, the dek should be designed as a multi-span system that does not require shoring during onrete plaement. The speified onstrution live loads reflet nominal loads from workers and tools and do not inlude loads of equipment suh as laser sreeds or power trowels nor additional onrete weight due to ponding. If antiipated onstrution ativities inlude these additional loads, they should be onsidered in the design. 5. Dek Defletion a. Calulated defletions of the dek as a form shall be based on the load of the onrete as determined by the design slab thikness and the selfweight of the steel dek, uniformly loaded on all spans, shall be limited to the lesser of 1/180 of the lear span or 3/4 inh (19 mm). Calulated defletions shall be relative to supporting members. b. The defletion of antilevered dek as a form, as determined by slab thikness and self-weight of the steel dek, shall not exeed a/90, where a is the antilever length, nor 3/4 inhes (19 mm). Commentary: The defletion alulations do not take into aount onstrution loads beause these are onsidered to be temporary loads. The dek is designed to always be in the elasti range, so removal of temporary loads will allow the dek to reover, unless onstrution overloads ause the stress in the dek to exeed the elasti limits of the dek. The supporting strutural steel also deflets under the loading of the onrete. The designer is urged to hek the defletion of the total system. Typial load tables are based on uniform slab thikness. If the designer wants to inlude additional onrete loading on the dek beause of frame defletion, the additional load should be shown on the design drawings or stated in the dek setion of the ontrat douments. 6. Minimum Bearing and Edge Distane: Minimum bearing lengths and fastener edge distanes shall be determined in aordane with AISI S100. 8

9 User Note: Figure 2 in Appendix 1 indiates support reations. The designer should hek the dek web rippling apaity based on available bearing length. 7. Diaphragm Shear Capaity: Diaphragm strength and stiffness shall be determined utilizing the bare steel dek apaity without onrete in aordane with: a. SDI-DDM b. Tests onduted in aordane with AISI S907. Other methods approved by the building offiial. Commentary: Unless otherwise required by the governing building ode, safety fators and resistane fators should be as shown in Table D5 of AISI S100 for bare steel dek diaphragms. When SDI-DDM is the basis of diaphragm design, fasteners and welds that do not have flexibility and strength properties listed in SDI-DDM Setion 4 an demonstrate flexibility and strength properties through testing in aordane with AISI S905 or other testing methods. Fastener or weld strength defined in AISI S100 or other methods an be used with the SDI-DDM method. It is always onservative to neglet the ontribution of sidelap onnetions to diaphragm strength and stiffness. Side lap fillet weld and top seam and side seam weld flexibility an be alulated in aordane with SDI-DDM Setion 4.4 and sidelap fillet weld and side seam weld strength an be alulated in aordane with AISI S Connetions: Dek shall be attahed to supports to resist loads and to provide strutural stability for the supporting member Connetions shall be designed in aordane with AISI S100 or strengths shall be determined by testing in aordane with AISI S905. Tests shall be representative of the design. When tests are used and the design allows either end laps or single thikness onditions, both onditions shall be tested. B. Dek and Conrete as a Composite Slab: 1. Strength: Strength of the omposite dek-slab shall be determined in aordane with one of the following methods a. Prequalified Setion Method as per Appendix 2. b. Shear Bond Method as per Appendix 3.. Full sale performane testing as per SDI-T-CD. d. Other methods approved by the building offiial. 2. Dek shall be evaluated for strength under the load ombinations required by the appliable building ode. In the absene of a building ode, the load ombinations presribed by ASCE 7 shall be used. 3. Load Determination: The superimposed load apaity shall be determined by deduting the weight of the slab and the dek from the total load apaity. Unless omposite dek-slabs are designed for ontinuity, slabs shall be assumed to at on simple spans. Commentary: Most published live load tables are based on simple span analysis of the omposite system; that is, a ontinuous slab is assumed to rak over eah support and to arry load as a series of simple spans. Commentary: By using the referene analysis tehniques or test results, the dek manufaturer determines the live loads that an be applied to the omposite dek-slab ombination. The results are usually published as uniform load tables. For most 9

10 appliations, the dek thikness and profile is seleted so that shoring is not required; the live load apaity of the omposite system is usually more than adequate for the superimposed live loads. In alulating the setion properties of the dek, AISI S100 may require that ompression zones in the dek be redued to an effetive width, but as tensile reinforement, the total area of the ross setion may be used. (See Appendix 3) Coatings other than those tested may be investigated, and if there is evidene that their performane is better than that of the tested produt, additional testing may not be required. 4. Conrete: Speified onrete ompressive strength (f ) shall omply with Setion 2.1 and shall not be less then 3000 psi (21 MPa), nor less than that required for fire resistane ratings or durability. Commentary: Load tables are generally alulated by using a onrete strength of 3000 psi (21 MPa). Composite slab apaities are not greatly affeted by variations in onrete ompressive strength; but if the strength falls below 3000 psi (21 MPa), it would be advisable to hek shear anhor design for omposite beam ation. a. Minimum Cover: The onrete thikness above the top of the steel dek shall not be less than 2 inhes (50 mm), nor that required by any appliable fire resistane rating requirements. Minimum onrete over for reinforement shall be in aordane with ACI Defletion: Defletion of the omposite slab shall be in aordane with the requirements of the appliable building ode. a. Cross setion properties shall be alulated in aordane with Appendix 4. b. Additional defletions resulting from onrete reep, where appliable, shall be alulated by multiplying the immediate elasti defletion due to the sustained load by the following fators: i. (1.0) for load duration of 3 months ii. (1.2) for load duration of 6 months iii. (1.4) for load duration of 1 year iv. (2.0) for load duration of 5 years. Commentary: Live load defletions are seldom a ontrolling design fator. A superimposed live load defletion of span/360 is typially onsidered to be aeptable. The defletion of the slab/dek ombination an be predited by using the average of the raked and unraked moments of inertia as determined by the transformed setion method of analysis. Refer to Appendix 4 of this standard or SDI-CDD. User Note: Limited information on reep defletions is available. This method is similar to the proedure for reinfored onrete slabs. Beause the steel dek initially arries the weight of the onrete, only the superimposed loads should be onsidered when reep defletions are a onern. User Note: Floor vibration performane is the result of the behavior of entire floor system, inluding the support framing. The designer should hek vibration performane using ommonly aepted methods, whih may inlude AISC Design Guide No

11 Speial Loads: The following loads shall be onsidered in the analysis and alulations for strength and defletion: a. Suspended Loads. b. Conentrated Loads. Moving Loads d. Cyli Loads 7. One-way Shear Strength: This setion shall be used to determine the one-way shear strength of the omposite dek-slab. φ V φ V n n Where: V V φ φ φ ' = v V + sv D v 4 f A (Eq a) (in-lb) = φ v V + φ sv D φ v f ' A (Eq b) (SI) = 2λ f A (Eq a) (in-lb) ' = 0.086λ f A (Eq b) (SI) ' V D = shear strength of the steel dek setion alulated in aordane with AISI S100, kips (kn) A = onrete area available to resist shear, in 2 (mm 2 ), see Figure 2-1. λ = 1.0 where onrete density exeeds 130 lbs/ft 3 (2100 kg/m 3 ); 0.75 where onrete density is equal to or less than 130 lbs/ft 3 (2100 kg/m 3 ). φ v = 0.75 φ s =

12 Figure 2-1 One-Way Shear Parameters 8. Punhing Shear Resistane: The ritial surfae for alulating punhing shear shall be perpendiular to the plane of the slab and loated outside of the periphery of the onentrated load or reation area. The fatored punhing shear resistane, V pr, shall be determined as follows: V V pr pr ( β) φv f' boh 4φv f' boh 0.043( β) φv f' boh 0.172φ v f' boh = (Eq a) (in-lb) = (Eq b) (SI) Where: b o = perimeter of ritial setion, in. (mm) h = thikness of onrete over above steel dek, in. (mm) β = ratio of long side to short side of onentrated load or reation area φ v = Conentrated Loads: Conentrated loads shall be permitted to be laterally distributed perpendiular to the dek ribs in aordane with this setion. 12

13 Alternate lateral load distributions based on rational analysis shall be permitted when allowed by the building offiial. a. Conentrated loads shall be distributed laterally (perpendiular to the ribs of the dek) over an effetive width, b e. The load distribution over the effetive width, b e, shall be uniform. b. The onrete above the top of steel dek shall be designed as a reinfored onrete slab in aordane with ACI 318, transverse to the dek ribs, to resist the weak axis moment, M wa, over a width of slab equal to W. Appropriate load fators as required by ACI 318 shall be applied to the weak axis moment. b m = b t + 2 t t (Eq ) b e = b m + (2)(1-x/L)x (t /h) for single span bending (Eq ) b e = b m + (4/3)(1-x/L)x (t /h) for ontinuous span bending when reinforing steel is provided in the onrete to develop negative bending. (Eq ) b e = b m + (1-x/L)x (t /h) for shear (Eq ) W = L/2 + b 3 L (Eq ) M wa = 12 P b e / (15W) in-lb per foot [ P b e / (15 W) N- mm per mm ] (Eq ) Where: b e = Effetive width of onentrated load, perpendiular to the dek ribs, in (mm) b m = Projeted width of onentrated load, perpendiular to the dek ribs, measured at top of steel dek, in (mm) b 2 = Width of bearing perpendiular to the dek ribs, in (mm) b 3 = Length of bearing parallel to the dek ribs, in (mm) h = Depth of omposite dek-slab, measured from bottom of steel dek to top of onrete slab, in (mm) L = Dek span length, measured from enters of supports, in (mm) M wa = Weak axis bending moment, perpendiular to dek ribs, of width, in.-lbs, (N-mm per mm of width) P = Magnitude of onentrated load, lbs (N) t = Thikness of onrete above top of steel dek, in (mm) t t = Thikness of rigid topping above strutural onrete (if any), in (mm) W = Effetive length of onentrated load, parallel to the dek ribs, in (mm) x = Distane from enter of onentrated load to nearest support, in (mm) 13

14 Figure Figure

15 User Note: Figures 2-2 and 2-3 illustrate the dimensions assoiated with this setion. Commentary: The designer should take into aount the sequene of loading. Suspended loads may inlude eilings, light fixtures, duts or other utilities. The designer should be informed of any loads to be applied after the omposite slab has been installed. Care should be used during the plaement of suspended loads on all types of hanger tabs or other hanging devies for the support of eilings so that an approximate uniform loading is maintained. The individual manufaturer should be onsulted for allowable loading on single hanger tabs. Improper use of hanger tabs or other hanging devies ould result in the overstressing of tabs and/or the overloading of the omposite dek-slab. Commentary: Composite floor dek is not reommended as the only onrete reinforement for use in appliations where the floor is loaded with repeated lift truk (forklift) or similar heavy wheeled traffi. (Lift truks are defined as small power operated vehiles that have devies for lifting and moving produt. The definition of lift truks does not inlude manually operated pallet jaks. ) Loading from lift truks inludes not only moving gravity loads, but also inludes vertial impat loading and in-plane loading effets from starting, stopping, and turning. The repetitive nature of this loading, inluding impat, fatigue, and in-plane effets an be more detrimental to the slab-dek performane than the gravity loads. Suspended floor slabs subjeted to lift truk traffi have speial design requirements to ensure the fatigue stress in the reinforement is low to keep the raks suffiiently tight and servieable to minimize rak spalling due to the hard wheel traffi. The design should only use the steel dek as a stay-in-plae form. Strutural onrete design reommendations ontained in ACI 215R and AASHTO-LRFD are suggested for guidane in the design of these slabs. Due onsideration for the stiffness of the supporting framing should be given by the designer. Composite floor dek has suessfully been used in appliations that are loaded by oasional sissor lift use, and in warehouses with industrial raks without lift truk traffi and in areas servied by pallet jaks. Proper analysis and design for moving and point loads must be performed. Commentary: For additional information regarding the use of omposite steel dek in parking struture appliations, refer to the SDI Position Statement Use of Composite Steel Floor Dek in Parking Garages. 10. Negative Reinforement: When the slab is designed for negative moments, the dek shall be designed to at in the negative moment region only as a permanent form. Conrete in negative moment regions shall be designed by the designer as a onventional reinfored onrete slab in aordane with ACI 318. Design moments and shears shall be permitted to be alulated by any aeptable method of analysis whih onsiders ontinuity. The oeffiient method of Chapter 8 of ACI 318 shall be onsidered to be an aeptable analysis method. Commentary: Composite steel dek does not funtion as ompression reinforing steel in areas of negative moment. If the designer desires a ontinuous slab, then negative bending reinforing should be designed using onventional reinfored onrete design tehniques in ompliane with ACI 318. The reinforement hosen for temperature and shrinkage reinforement most likely will not supply suffiient area of reinforement for negative bending over the supports. 15

16 Cantilevered Slabs: At antilevered slabs, the dek shall be onsidered to at only as a permanent form. The slab shall be designed by the designer for negative bending in aordane with ACI 318. Commentary: At antilevered slabs, the dek ats only as a permanent form. Composite steel dek does not funtion as ompression reinforing steel at antilevers. Negative bending reinforing at the antilever should be designed using onventional reinfored onrete design tehniques in ompliane with ACI 318. The reinforement hosen for temperature and shrinkage reinforing most likely will not supply suffiient area of reinforement for negative bending at the antilever. 12. Diaphragm Shear Capaity: Diaphragm strength and stiffness shall be determined in aordane with: a. SDI-DDM b. Tests onduted in aordane with AISI S907. Other methods approved by the building offiial. Commentary: Unless otherwise required by the governing building ode, when using the SDI-DDM method, the safety and resistane fators found in the SDI-DDM should be used, When SDI-DDM is the basis of diaphragm design, fasteners and welds that do not have flexibility and strength properties listed in SDI-DDM Setion 4 an demonstrate flexibility and strength properties through testing in aordane with AISI S905 or other testing methods. Fastener or weld strength defined in AISI S100 or other methods an be used with the SDI-DDM method. It is always onservative to neglet the ontribution of sidelap onnetions to diaphragm strength and stiffness. Side lap fillet weld and top seam and side seam weld flexibility an be alulated in aordane with SDI-DDM Setion 4.4 and sidelap fillet weld and side seam weld strength an be alulated in aordane with AISI S100. When strength is based on test, the safety and resistane fators should be determined in aordane with AISI S100 Chapter F, but should shall not be less ritial than those for onrete diaphragms ontained in ACI 318, Setion 9.3. The following statistial data may be used with AISI S100 for alulating the resistane fator: β o = 3.50 M m = 1.10 V m = 0.10 F m = 0.90 V f = 0.10 P m = 1.00 This statistial data is based on a onnetion limit state, and is differs from the data in the SDI T-CD standard for gravity loads. When using this data, the fator if safety should be alulated in aordane with AISI S100, Setion F. User Note: In instanes where the required diaphragm apaity exeeds what an be alulated using SDI-DDM, a designer an potentially develop additional apaity by designing the diaphragm as a reinfored onrete diaphragm in aordane with ACI 318. This design option as a onrete diaphragm is outside the sope of this standard. 13. Reinforement for Temperature and Shrinkage: 16

17 a. Reinforement for rak ontrol purposes other than to resist stresses from quantifiable strutural loadings shall be permitted to be provided by one of the following methods: 1. Welded wire reinforement or reinforing bars with a minimum area of times the area of the onrete above the dek (per foot or meter of width), but not be less than the area provided by 6 x 6 W1.4 x W1.4 (152 x 152 MW9 x MW9) welded wire reinforement. 2. Conrete speified in aordane with ASTM C1116, Type I, ontaining steel fibers meeting the riteria of ASTM A820, Type I, Type II, or Type V, at a dosage rate determined by the fiber manufaturer for the appliation, but not less than 25 lb/u yd (14.8 kg/u meter). 3. Conrete speified in aordane with ASTM C1116, Type III, ontaining marosyntheti fibers meeting the riteria of ASTM D7508 at a dosage rate determined by the fiber manufaturer for the appliation, but not less than 4 lb./u yd (2.4 kg/m 3 ). User Note: It is suggested that if fibers are used for this purpose, that the designer inlude quality ontrol provisions in aordane with ACI 544 3R in the projet speifiations. Commentary: Conrete floor slabs employing Portland ement will start to experiene a redution in volume as soon as they are plaed. Where shrinkage is restrained, raking will our in the floor. The use of the appropriate types and amount of reinforement for shrinkage and temperature movement ontrol is intended to result in a larger number of small raks in lieu of a fewer number of larger raks. Even with the best floor design and proper onstrution, it is unrealisti to expet rak free floors. Every owner should be advised by both the designer and ontrator that it is normal to expet some amount of raking and that suh ourrene does not neessarily reflet adversely on either the adequay of the floor s design or quality of the onstrution. Craking an be redued when the auses are understood and preventative steps are taken in the design phase. The major fators that the designer an ontrol onerning shrinkage and raking inlude ement type, aggregate type and gradation, water ontent, water/ement ratio, and reinforement. Most measures that an be taken to redue onrete shrinkage will also redue the raking tendeny. Drying shrinkage an be redued by using less water in the mixture and the largest pratial maximum-size aggregate. A lower water ontent an be ahieved by using a well-graded aggregate and lower initial temperature of the onrete. Designers are referred to ACI 302.1R and ACI for additional information. Although raking is inevitable, properly plaed reinforement used in adequate amounts will redue the width of individual raks. By distributing the shrinkage strains, the raks are distributed so that a larger number of narrow raks our instead of a few wide raks. Additional onsideration by the designer may be required to further limit the size and frequeny of raks. Additional provisions for 17

18 rak ontrol are frequently required where onrete is intended to be exposed, floors that will be subjeted to wheel traffi, and floors whih will reeive an inflexible floor overing material (suh as tile). Modifiations to fiber dosages will vary depending upon the speifi fiber manufaturers reommendations. As a general rule, redued rak widths an be ahieved by inreasing the amount of steel reinforement or by inreasing the fiber dosage and/or minimizing the shrinkage potential of the onrete. Beause omposite dek-slabs are typially designed as a series of simple spans, flexural raks may form over supports. Flexural raking of the onrete in negative moment regions of the slab (over beams and girders) is not typially objetionable unless the floor is to be left exposed or overed with inflexible floor overings. Flexural raking and rak widths an be minimized by one or more of the following: 1.) by paying strit attention to preventing overloads at dek midspan during onstrution, as this is a ommon soure of flexural raks; 2.) utilizing a stiffer steel dek; 3.) reduing the slab span. If flexural raks must be stritly ontrolled, onsideration should be given to designing the omposite dek-slab for negative moments over supports (both beams and girders) and providing appropriate reinforing steel at these supports. 14. Fire Resistane: The designer shall onsider required fire resistane ratings in the design of the omposite slab. Commentary: Fire rating requirements may ditate the onrete strength or density. Many fire rated assemblies that use omposite floor deks are available. In the Underwriters Laboratories Fire Resistane Diretory, the omposite dek onstrutions show hourly ratings for restrained and unrestrained assemblies. ASTM E119 provides information in Appendix X3 titled Guide for Determining Conditions of Restraint for Floor and Roof Assemblies and for Individual Beams, indiating that dek attahed to steel or onrete framing, and interior spans of wall supported dek may be onsidered to be restrained, while end spans of wall supported dek should be onsidered to be unrestrained. Designers should be aware that some fire rated assemblies set limits on load apaity and/or plae restritions on fastener type and spaing. 2.5 Aessories: A. Aessories for strutural appliations shall be of dimensions and thikness suitable for the appliation, and shall be designed in aordane with AISI S100 or AISC 360, as appliable. Commentary: For onveniene, minimum suggested pour stop thiknesses (gages) are shown in User Note Attahment 1. For appliations that exeed the sope of the attahment, alternate designs in aordane with AISI S100 and AISC 360 are aeptable. 3. Exeution 3.1 Installation/General: A. Temporary shoring, if required, shall be designed to resist the loads indiated in Setion 2.4.A.2. The shoring shall be designed and installed in aordane with 18

19 standards appliable to the speifi shoring system and shall be left in plae until the onrete attains 75% of its speified design strength. User Note: Typial pratie is to retain shoring in plae for a minimum of 7 days. B. Dek Support Attahment: Steel dek shall be anhored to strutural supports by ar spot welds, fillet welds, or mehanial fasteners. The average attahment spaing of dek at supports perpendiular to the span of the dek panel shall not exeed 12 inhes (300 mm) on enter, with the maximum attahment spaing not to exeed 18 inhes (460 mm), unless more frequent fastener spaing is required for diaphragm design. The dek shall be adequately attahed to the struture to prevent the dek from slipping off the supporting struture. User Note: When the side lap is a standing seam interlok, it may be permissible to only attah the female side, subjet to design requirements, when the female hem holds the male leg down. When the side lap is a nestable side lap a single fastener through both sheets of steel dek is aeptable to seure both sheets. C. Dek Sidelap Fastening: For dek with spans less than or equal to 5 feet (1.5 m), side lap fasteners shall not be required. unless required for diaphragm design. For dek with spans greater than 5 feet (1.5 m), side laps shall be fastened at intervals not to exeed 36 inhes (1 m) on enter, unless more frequent fastener spaing is required for diaphragm design, using one of the following methods: 1. Srews with a minimum diameter of inhes (4.83 mm) (#10 diameter) 2. Crimp or button punh 3. Ar spot welds 5/8 inh (16 mm) minimum visible diameter, minimum 1-1/2 inh (38 mm) long fillet weld, or other weld shown to be substantially equivalent through testing in aordane with AISI S905, or by alulation in aordane with AISI S100, or other equivalent method approved by the building offiial. 4. Other equivalent methods approved by the building offiial. User Note: The above side lap spaing is a minimum. Servie loads or diaphragm design may require loser spaing or larger side lap welds. Good metal-to-metal ontat is neessary for a good side lap weld. When welding, burn holes are to be expeted and are not a grounds for rejetion. The SDI does not reommend fillet welded or ar spot welded sidelaps for dek that is thinner than inh design thikness (20 gage) due to diffiulty in welding thinner material. D. Dek Perimeter Attahment Along Edges Between Supports: For dek with spans less than or equal to 5 feet (1.5 m), perimeter attahment shall not be required, unless required for diaphragm design. For dek with spans greater than 5 feet (1.5 m), perimeter edges of dek panels between span supports shall be fastened to supports at intervals not to exeed 36 inhes (1 m) on enter, unless more frequent fastener spaing is required for diaphragm design, using one of the following methods: 1. Srews with a minimum diameter of inhes (4.83 mm) (#10 diameter) 2. Ar spot welds with a minimum 5/8 inh (16 mm) minimum visible diameter, or minimum 1-1/2 inh (38 mm) long fillet weld. 3. Powder atuated or pneumatially driven fasteners. 19

20 User Note: This ondition is often referred to as parallel attahment to supports, referring to the support members running parallel or nearly parallel with the flutes of the dek panel. Number 10 srews may not be adequate at thiker edge supports and may frature due to driving torque resistane. A minimum of a Number 12 srew is reommended at parallel edge supports thiker than 14 gage ( inh) and a Number14 srew may be required for thiker and harder steels. E. Support at the perimeter of the floor shall be designed and speified by the designer. F. Cantilevers: 1. Side laps shall be attahed at the end of the antilever and at a maximum spaing of 12 inhes (300 mm) on enter from the antilevered end at eah support. 2. Eah dek orrugation shall be fastened at both the perimeter support and the first interior support. 3. The dek shall be ompletely attahed to the supports and at the side laps before any load is applied to the antilever. 4. Conrete shall not be plaed on the antilever before onrete is plaed on the adjaent span. G. Fastener edge distane shall be as required by the appliable fastener design standard. H. Dek bearing surfaes to be welded shall be brought into ontat as required by AWS D1.3, Setion User Note: Out of plane support flanges an reate knife-edge supports and air gaps between the dek and support. This makes welding more diffiult and allows distortion under srew or power atuated fastener washers or heads. Inherent toleranes of the supporting struture should be onsidered. 3.2 Welding A. All welding of dek shall be in aordane with AWS D1.3. Eah welder shall demonstrate the ability to produe satisfatory welds using a proedure in aordane with ANSI/AWS D1.3. User Note: SDI-MOC desribes a weld quality ontrol test proedure that an be used as a preliminary hek for welding mahine settings under ambient onditions. B. For onnetion of the dek to the supporting struture, weld washers shall be used with ar spot welds on all dek units with metal thikness less than inhes (22 gage) (0.71 mm). Weld washers shall be a minimum thikness of inhes (1.27 mm) and have a nominal 3/8 inh (10 mm) diameter hole. Weld washers shall not be used between supports along the sidelaps. C. Where weld washers are not required, a minimum visible 5/8 inh (16 mm) diameter ar spot weld or ar seam weld of equal perimeter shall be used. Weld metal shall penetrate all layers of dek material at end laps and shall have good fusion to the supporting members. D. When used, fillet welds to support struture shall be at least 1-1/2 inhes (38 mm) long. E. When steel headed stud anhors are installed to develop omposite ation between the beam or joist and the onrete slab, the steel headed steel anhor shall be permitted as a substitute for an ar spot weld to the supporting struture. Steel headed steel anhors shall be installed in aordane with AWS D Mehanial Fasteners 20

Composite Steel Floor Deck-Slabs

Composite Steel Floor Deck-Slabs AMERICAN NATIONAL STANDARDS / STEEL DECK C - 2017 Standard for Composite Steel Floor Dek-Slabs opyright 2017 steel dek institute 1. General AMERICAN NATIONAL STANDARDS / STEEL DECK 1.1 Sope: A. This Standard

More information

Steel. Members. in medium to. composite. provisions for. the available. b) strength of. design,

Steel. Members. in medium to. composite. provisions for. the available. b) strength of. design, Chapter 13 Steel Conrete Composite Strutural Members 13.1 General Provisions for Steel Conrete Composite Strutural Members This setion states the sope of the speifiation, summarizess referened speifiations,

More information

Camber Variability in Prestressed Concrete Bridge Beams

Camber Variability in Prestressed Concrete Bridge Beams CONCRETE BRIDGE TECHNOLOGY Camber Variability in Prestressed Conrete Bridge Beams by Dr. Maher Tadros, econstrut Beams ast with extra amber in storage yard at Conrete Tehnology Corporation; amber shown

More information

Suggested Changes to NZS3101:2006 with Amendments 1 and 2

Suggested Changes to NZS3101:2006 with Amendments 1 and 2 1 Suggested Changes to NZS3101:2006 with Amendments 1 and 2 Rihard Fenwik and Dene Cook Introdution NZS 3101: 2006 Conrete Strutures Standard is a design ode published by Standards New Zealand. Sine the

More information

Two-Way Flat Slab (Concrete Floor with Drop Panels) System Analysis and Design

Two-Way Flat Slab (Concrete Floor with Drop Panels) System Analysis and Design Two-Way Flat Slab (Conrete Floor with Drop Panels) System Analysis and Design Two-Way Flat Slab (Conrete Floor with Drop Panels) System Analysis and Design Design the onrete floor slab system shown below

More information

Two-Way Joist Concrete Slab Floor (Waffle Slab) System Analysis and Design

Two-Way Joist Concrete Slab Floor (Waffle Slab) System Analysis and Design Two-Way Joist Conrete Slab Floor (Waffle Slab) System Analysis and Design Version: May-18-017 Two-Way Joist Conrete Slab Floor (Waffle Slab) System Analysis and Design Design the onrete floor slab system

More information

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.1.

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.1. The following exerpt are pages from the North Amerian Produt Tehnial Guide, Volume 2: Anhor Fastening, Edition 16.1. Please refer to the publiation in its entirety for omplete details on this produt inluding

More information

Example 24.3 Flexural Strength of Prestressed Member Using Approximate Value for f ps

Example 24.3 Flexural Strength of Prestressed Member Using Approximate Value for f ps Example 24.3 Flexural Strength of Prestressed Member Using Approximate Value for f ps Calulate the nominal moment strength of the prestressed member shown. f = 5000 psi f pu = 270,000 psi (low-relaxation

More information

EXPERIMENTAL INVESTIGATION OF ECCENTRIC REINFORCED CONCRETE BEAM-COLUMN-SLAB CONNECTIONS UNDER EARTHQUAKE LOADING

EXPERIMENTAL INVESTIGATION OF ECCENTRIC REINFORCED CONCRETE BEAM-COLUMN-SLAB CONNECTIONS UNDER EARTHQUAKE LOADING 13 th World Conferene on Earthquake Engineering Vanouver, B.C., Canada August 1-6, 24 Paper No. 215 EXPERIMENTAL INVESTIGATION OF ECCENTRIC REINFORCED CONCRETE BEAM-COLUMN-SLAB CONNECTIONS UNDER EARTHQUAKE

More information

FINITE ELEMENT MODELLING OF STEEL-CONCRETE COMPOSITE BEAMS STRENGTHENED WITH PRESTRESSED CFRP PLATE

FINITE ELEMENT MODELLING OF STEEL-CONCRETE COMPOSITE BEAMS STRENGTHENED WITH PRESTRESSED CFRP PLATE FINITE ELEMENT MODELLING OF STEEL-CONCRETE COMPOSITE BEAMS STRENGTHENED WITH PRESTRESSED CFRP PLATE H.Y. Omran 1, P. Zangeneh 2, and R. EL-Haha 3 1 PhD student, Department of Civil Engineering, University

More information

Post-Tensioned Two-Way Slab

Post-Tensioned Two-Way Slab The Medial Oie Building Malvern, PA 13 Post-Tensioned Two-Way Slab Introdution The Filigree beam system reates a thin lightweight loor system that leaves plenty o open plenum spae or mehanial and eletrial

More information

30th Conference on OUR WORLD IN CONCRETE & STRUCTURES: August 2005, Singapore. Article Online Id:

30th Conference on OUR WORLD IN CONCRETE & STRUCTURES: August 2005, Singapore. Article Online Id: EXPERIMENTAL RESEARCH ON JOINTS OF PRESTRESSED CONCRETE BEAM AND COMPOSITE CONCRETE COLUMN WITH CORE OF CONCRETE FILLED STEEL TUBE UNDER LOW-CYCLIC REVERSED LOADING Deng Zhi-heng*, Guangxi University,

More information

Suspended ceiling with visible T-sections

Suspended ceiling with visible T-sections Suspended eiling with visible T-setions a E E E max. 300 mm a m Hanger spaing 1 Hanging system: Rihter System 11.2 D 2 E C 26 C Main setion spaing E A Suspended eiling with visible T-setions Produts Table

More information

R. W. Barnes, N. H. Burns, and M. E. Kreger Research Report

R. W. Barnes, N. H. Burns, and M. E. Kreger Research Report Tehnial Report Doumentation Page 1. Report No. 2. Government Aession No. 3. Reipient s Catalog No. FHWA/TX-02/1388-1 4. Title and Subtitle 5. Report Date Development Length of 0.6-Inh Prestressing Strand

More information

INVESTIGATION OF THE SIZE EFFECT IN SHEAR OF STEEL FIBER REINFORCED CONCRETE (SFRC) SLENDER BEAMS

INVESTIGATION OF THE SIZE EFFECT IN SHEAR OF STEEL FIBER REINFORCED CONCRETE (SFRC) SLENDER BEAMS High Performane Fiber Reinfored Cement Composites (HPFRCC7), INVESTIGATION OF THE SIZE EFFECT IN SHEAR OF STEEL FIBER REINFORCED CONCRETE (SFRC) SLENDER BEAMS M. Zarrinpour (1), J.-S. Cho (2) and S.-H.

More information

Two-Way Concrete Floor Slab with Beams Design and Detailing

Two-Way Concrete Floor Slab with Beams Design and Detailing Two-Way Conrete Floor Slab with Beams Design and Detailing Version: Apr-05-017 Two-Way Conrete Floor Slab with Beams Design and Detailing Design the slab system shown in Figure 1 for an intermediate floor

More information

KE double wall transport anchors

KE double wall transport anchors for better solutions... KE double wall transport anhors The safe transport anhor for double walls KE Ttransport anhors - Transport double walls seurely www.h-bau.de Contat Oslo Helsinki Mosow London Warsaw

More information

ENGINEERED DESIGN OF SIP PANELS USING NTA LISTING REPORT DATA

ENGINEERED DESIGN OF SIP PANELS USING NTA LISTING REPORT DATA ENGINEERED DESIGN OF SI ANELS USING NTA LISTING REORT DATA 1. SCOE 1.1. GENERAL This doument applies to strutural insulated panels (SIs), whih shall be deined as a strutural aing material with a oam ore.

More information

The influence of pallets on the behaviour and design of steel drive-in storage racks - Part II Design

The influence of pallets on the behaviour and design of steel drive-in storage racks - Part II Design University of Wollongong Researh Online Faulty of Engineering and Information Sienes - Papers: Part A Faulty of Engineering and Information Sienes 2013 The influene of pallets on the behaviour and design

More information

BBR VT CONA CMI BT. Internal Post-tensioning System with 02 to 61 Strands. European Technical Approval ETA 09/0286

BBR VT CONA CMI BT. Internal Post-tensioning System with 02 to 61 Strands. European Technical Approval ETA 09/0286 BBR VT with 02 to 61 Strands European Tehnial Approval ETA 09/0286 0432 BBR VT with 02 to 61 Strands BBR VT International Ltd Bahnstrasse 23, 8603 Shwerzenbah (Switzerland) www.bbrnetwork.om S P E C I

More information

Web buckling strength of beam-to-column connections, September 1970 (74-1) PB / AS

Web buckling strength of beam-to-column connections, September 1970 (74-1) PB / AS Lehigh University Lehigh Preserve Fritz Laboratory Reports Civil and Environmental Engineering 1970 Web bukling strength of beam-to-olumn onnetions, September 1970 (74-1) PB 234 621/ AS W. F. Chen I. J.

More information

SUBJECT: AASHTO LRFD Guide Specifications for Design of Concrete-Filled FRP Tubes for Flexural and Axial Members

SUBJECT: AASHTO LRFD Guide Specifications for Design of Concrete-Filled FRP Tubes for Flexural and Axial Members 2012 AASHTO BRIDGE COMMITTEE AGENDA ITEM: 43 SUBJECT: AASHTO LRFD Guide Speiiations or Design o Conrete-Filled FRP Tubes or Flexural and Axial Members TECHNICAL COMMITTEE: T-6 Fiber Reinored Polymer Composites

More information

Reinforced Concrete Design

Reinforced Concrete Design Reinored Conrete Design Notation: a = depth o the eetive ompression blok in a onrete beam A = name or area A g = gross area, equal to the total area ignoring an reinorement A s = area o steel reinorement

More information

ModuSec. Secure and efficient IT room solutions Composite Panel Systems Compared. Panel Systems are not all the same!

ModuSec. Secure and efficient IT room solutions Composite Panel Systems Compared. Panel Systems are not all the same! ModuSe Seure and effiient IT room solutions Composite Panel Systems Compared Panel Systems are not all the same! When it omes to aommodating ritial IT systems, the first issue to look at is the environment

More information

SECTION STEEL DECKING

SECTION STEEL DECKING SECTION 05 31 00 STEEL DECKING SPEC WRITER NOTE: 1. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. Refer to Section 05 36 00, COMPOSITE METAL DECKING for floor

More information

Rainwater Management Performance of Newly Constructed Residential Building Enclosures During August and September 2004

Rainwater Management Performance of Newly Constructed Residential Building Enclosures During August and September 2004 Rainwater Management Performane of Newly Construted Residential Building Enlosures During August and September 2004 Prepared for the Home Builders Assoiation of Metro Orlando and the Florida Home Builders

More information

The use of precast concrete sandwich panels has

The use of precast concrete sandwich panels has Load-arrying apaity of omposite preast onrete sandwih panels with diagonal fiber-reinfored-polymer bar onnetors Ehab Hamed The failure modes of omposite preast onrete sandwih panels made with diagonal

More information

PERFORMANCE OF DOUBLE-T PRESTRESSED CONCRETE BEAMS STRENGTHENED WITH STEEL REINFORCED POLYMER ABSTRACT

PERFORMANCE OF DOUBLE-T PRESTRESSED CONCRETE BEAMS STRENGTHENED WITH STEEL REINFORCED POLYMER ABSTRACT PERFORMANCE OF DOUBLE-T PRESTRESSED CONCRETE BEAMS STRENGTHENED WITH STEEL REINFORCED POLYMER Paolo Casadei 1, Antonio Nanni 2, Tarek Alkhrdaji 3 and Jay Thomas 4 ABSTRACT In the fall of 2002, a two-storey

More information

The Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers.

The Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers. SECTION 05 31 13 STEEL FLOOR DECKING PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the contract, including General and Supplementary Conditions and Division 01 - Specification

More information

SEISMIC RETROFIT USING CONTINUOUS FIBER SHEETS

SEISMIC RETROFIT USING CONTINUOUS FIBER SHEETS SEISMIC RETROFIT USING CONTINUOUS FIER SHEETS Yasuhiro MATSUZAKI 1, Katsuhiko NAKANO, Shigeru FUJII 3 And Hiroshi FUKUYAMA 4 SUMMARY The researh on seismi retrofit of RC members using ontinuous fiber sheets

More information

Indeterminate Prestressed Structures

Indeterminate Prestressed Structures Indeterminate Prestressed Strutures Introdution Use of ontinuous sstems results in redution of moments and stresses at midspans. Shallower members are used Stiffer than simpl supported members of equal

More information

TS Invisible (concealed) sub-frame

TS Invisible (concealed) sub-frame TS210-285 Invisile (onealed) raket-railfix on an aluminum su-frame This system offers large flexiility for installing Trespa Meteon panels, the use of adjustale rakets allow for preise joints and an optimal

More information

Pressure Vessels and Heat Exchangers

Pressure Vessels and Heat Exchangers With Pressure Vessel and Heat Exhanger expertise in design evaluation, development of tehnial purhase speifiations, rerating, and repair analysis and high temperature vessel design, you d think we an do

More information

Tapper Concrete Scew Anchor Type 410 & 304 Stainless Steel

Tapper Concrete Scew Anchor Type 410 & 304 Stainless Steel Conrete Sew Type 4 & 304 PRODUCT DESCRIPTION The fastening system is a family of srew anhors for light to meium uty appliations in onrete, masonry blok an brik base materials. The is fast an easy to install

More information

Comparison Study of Connector and Tubing Blow-Off Line

Comparison Study of Connector and Tubing Blow-Off Line PROCEEDINGS Comparison Study of Connetor and Tubing Blow-Off Line Pressures Jerry D. Leaf, Charles Dyson, Robert Emerson UCLA Medial Center, Department of Surgery, Division of Thorai Surgery Abstrat The

More information

Prediction of Temperature and Aging Effects on the Properties of Concrete

Prediction of Temperature and Aging Effects on the Properties of Concrete Predition of Temperature and Aging Effets on the Properties of Conrete Jin-Keun Kim 1* and Inyeop Chu 1 1 KAIST, Republi of Korea * E-mail: kimjinkeun@kaist.a.kr ABSTRACT For the sustainable onrete strutures,

More information

Accepted Manuscript. Factors affecting moment redistribution at ultimate in continuous beams prestressed with external CFRP tendons

Accepted Manuscript. Factors affecting moment redistribution at ultimate in continuous beams prestressed with external CFRP tendons Aepted Manusript Fators affeting moment redistribution at ultimate in ontinuous beams prestressed with external CFRP tendons Tiejiong Lou, Sergio M.R. Lopes, Adelino V. Lopes PII: S1359-8368(14)00205-4

More information

THE ENERGY DISSIPATION EFFECTS OF REDUNDANT MEMBERS IN SILOS UNDER EARTHQUAKES

THE ENERGY DISSIPATION EFFECTS OF REDUNDANT MEMBERS IN SILOS UNDER EARTHQUAKES 269 THE ENEGY DISSIPATION EFFECTS OF EDUNDANT MEMBES IN SILOS UNDE EATHQUAKES Li Zhiming 1 and Geng Shujiang 1 SUMMAY An analytial study is made the response to strong base motion reinfored onrete silo

More information

Article publié par le Laboratoire de Construction en Béton de l'epfl. Paper published by the Structural Concrete Laboratory of EPFL

Article publié par le Laboratoire de Construction en Béton de l'epfl. Paper published by the Structural Concrete Laboratory of EPFL Artile publié par le Laboratoire de Constrution en Béton de l'epfl Paper published by the Strutural Conrete Laboratory of EPFL Title: Effet of load distribution and variable depth on shear resistane of

More information

Beam-Column Connections. Joint shear strength - code-conforming joints - Joint damage in previous eq. φ = Force demands on joint

Beam-Column Connections. Joint shear strength - code-conforming joints - Joint damage in previous eq. φ = Force demands on joint Beam-Column Connetions Fore demands on joint T s1 = 1.2A s f y C 2 = T s2 V b1 V b2 Dawn Lehman John Stanton and Laura Lowes Uniersity of Washington, Seattle Jak Uniersity of California, Berkeley l M pr

More information

Concrete Frame Design Manual CSA A

Concrete Frame Design Manual CSA A Conrete Frame Design Manual CSA A23.3-04 Conrete Frame Design Manual CSA A23.3-04 For ETABS 2016 ISO ETA122815M24 Rev. 0 Proudly developed in the United States o Ameria Deember 2015 Copyright Copyright

More information

Structural vs Nonstructural Members. Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures

Structural vs Nonstructural Members. Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures Structural vs Nonstructural Members Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures Behavior of Cold-Formed Steel Members STEEL DESIGN SPECIFICATIONS Type of steel Specification

More information

The fracture of a Al bicycle crank arm.

The fracture of a Al bicycle crank arm. The frature of a Al biyle rank arm. Failure In hapters 6 and 7 we examined the elasti and plasti behaviour of materials. We learned how the motion of disloations makes it possible for the material to deform.

More information

Experimental and Theoretical Deflections of Hybrid Composite Sandwich Panel under Four-point Bending Load

Experimental and Theoretical Deflections of Hybrid Composite Sandwich Panel under Four-point Bending Load Civil Engineering Dimension, Vol. 19, No. 1, Marh 017, 9-5 ISSN 1410-950 print / ISSN 1979-570X online DOI: 10.9744/CED.19.1.9-5 Experimental and Theoretial Defletions of Hybrid Composite Sandwih Panel

More information

DIVISION: METALS SECTION: STEEL DECKING REPORT HOLDER: EPIC METALS CORPORATION 11 TALBOT AVENUE RANKIN, PENNSYLVANIA 15104

DIVISION: METALS SECTION: STEEL DECKING REPORT HOLDER: EPIC METALS CORPORATION 11 TALBOT AVENUE RANKIN, PENNSYLVANIA 15104 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2047 Reissued 07/207 This report is subject to renewal 07/209. DIVISION: 05 00 00

More information

Repair and strengthening of masonry walls with openings using FRP laminates

Repair and strengthening of masonry walls with openings using FRP laminates Repair and strengthening of masonry walls with openings using FRP laminates A Moussa*, Helwan University, gypt A M Aly, Helwan University, gypt 26th Conferene on OUR WORLD COCRT & STRUCTURS: 27-28 August

More information

DESIGNING WITH STEEL FORM DECK

DESIGNING WITH STEEL FORM DECK DESIGNING WITH STEEL FORM DECK All rights reserved 2003 P.O. Box 25 Fox River Grove, IL 60021 Phone: (847) 458-4647 Fax: (847) 458-4648 Form deck is a term used to describe deck that is most frequently

More information

Analysis of geopolymer concrete columns

Analysis of geopolymer concrete columns Analysis of geopolymer onrete olumns Prabir Kumar Sarker, Leturer, Department of Civil Engineering, Curtin University of Tehnology, Perth, Western Australia, Phone: +61 8 9266 7568, Fax: +61 8 9266 2681,

More information

GROUND WATER/SURFACE WATER INTERACTIONS AWRA SUMMER SPECULLTP CONF~NCR CZ-I PDG- ANALYSIS OF INFILTRATED STREAM WATER TO A PUMPING WELL

GROUND WATER/SURFACE WATER INTERACTIONS AWRA SUMMER SPECULLTP CONF~NCR CZ-I PDG- ANALYSIS OF INFILTRATED STREAM WATER TO A PUMPING WELL JULY 1-3 GROUND WATER/SURFACE WATER NTERACTONS AWRA SUMMER SPECULLTP CONF~NCR 22 32 CZ- PDG- ANALYSS OF NFLTRATED STREAM WATER TO A PUMPNG WELL Xunhong Chen' and Xi Chen' ABSTRACT: Pumping of groundwater

More information

WATER WITHIN LIGHTWEIGHT AGGREGATE CONCRETE AND ITS RELATION TO AUTOGENOUS SHRINKAGE

WATER WITHIN LIGHTWEIGHT AGGREGATE CONCRETE AND ITS RELATION TO AUTOGENOUS SHRINKAGE WATER WITHIN LIGHTWEIGHT AGGREGATE CONCRETE AND ITS RELATION TO AUTOGENOUS SHRINKAGE S.A. Kristiawan Department of Civil Eng.Sebelas Maret University, e-mail: sa_kristiawan@uns.a.id Senot Sangadji Department

More information

SHEAR RESISTANCE OF CONCRETE T-BEAMS PRESTRESSED WITH CFRP CABLES

SHEAR RESISTANCE OF CONCRETE T-BEAMS PRESTRESSED WITH CFRP CABLES SHEAR RESISTANCE OF CONCRETE T-BEAMS PRESTRESSED WITH CFRP CABLES Payam NABIPAY B.S, EIT University o Manitoba Department o Civil Engineering 15 Gillson st., Winnipeg, Manitoba, Canada umnabipa@.umanitoba.a

More information

DIVISION: METALS SECTION: METAL FASTENINGS SECTION: STEEL DECKING REPORT HOLDER: HILTI, INC.

DIVISION: METALS SECTION: METAL FASTENINGS SECTION: STEEL DECKING REPORT HOLDER: HILTI, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 43 6587 (56) 699 0543 www.icc es.org ESR 97 Reissued /7 This report is subject to renewal /8. DIVISION: 05 00 00 METALS SECTION:

More information

Experimental Investigation on Nanomaterial Concrete

Experimental Investigation on Nanomaterial Concrete International Journal of Civil & Environmental Engineering IJCEE-IJE Vol:13 No:03 15 Experimental Investigation on Nanomaterial Conrete Saloma 1, Amrinsyah Nasution 2, Iswandi Imran 3 and Mikrajuddin Abdullah

More information

Design of Corrugated Metal Box Culverts

Design of Corrugated Metal Box Culverts Transportation Researh Reord 18 33 Design of Corrugated Metal Box Culverts J. M. DUNCAN, R. B. SEED, and R. H. DRA WSKY ABSTRACT Corrugated metal box ulverts provide large ross-setional areas for water

More information

Originally Issued: 03/10/2017 Revised: 03/30/2019 Valid Through: 03/31/ Design

Originally Issued: 03/10/2017 Revised: 03/30/2019 Valid Through: 03/31/ Design Originally Issued: 03/10/2017 Revised: 03/30/2019 Valid Through: 03/31/2019 EVALUATION SUBJECT: STEEL DECK PANELS REPORT HOLDER NUCOR CORPORATION - VULCRAFT/VERCO GROUP VULCRAFT GROUP 7205 Gault Avenue

More information

The New SDI Diaphragm Design Manual

The New SDI Diaphragm Design Manual Missouri University of Science and Technology Scholars' Mine International Specialty Conference on Cold- Formed Steel Structures (2006) - 18th International Specialty Conference on Cold-Formed Steel Structures

More information

European Regulations For Multilayer Food Contact Materials. Dr. Hermann Onusseit Henkel KGaA Düsseldorf, Germany ABSTRACT

European Regulations For Multilayer Food Contact Materials. Dr. Hermann Onusseit Henkel KGaA Düsseldorf, Germany ABSTRACT European Regulations For Multilayer Food Contat Materials Dr. Hermann Onusseit Henkel KGaA Düsseldorf, Germany ABSTRACT Artiles and failities whih ome into ontat with food are subjet to speial demands.

More information

PROPERTIES OF SRP COMPOSITES AND THEIR EFFECT ON DESIGN PROCEDURES

PROPERTIES OF SRP COMPOSITES AND THEIR EFFECT ON DESIGN PROCEDURES PROPERTIES OF SRP COMPOSITES AND THEIR EFFECT ON DESIGN PROCEDURES Rafał Krzywoń PhD MsC Silesian University of Tehnology, Poland rafal.krzywon@polsl.pl Summary Desribed in the paper omposites are based

More information

Durability of bitumen mat used for increasing friction between concrete caisson and rock mound

Durability of bitumen mat used for increasing friction between concrete caisson and rock mound Duraility of itumen mat used for inreasing frition etween onrete aisson and rok mound Masakazu Mayama Hokkaido Institute of Tehnology, Sapporo, Japan Tadahiro Imoto Civil Engineering Researh Institute

More information

Performance Rating of Unitary Air-Conditioning & Air-Source Heat Pump Equipment

Performance Rating of Unitary Air-Conditioning & Air-Source Heat Pump Equipment ANSI/AHRI Standard 210/240 with Addenda 1 and 2 (formerly ARI Standard 210/240) 2008 Standard for Performane Rating of Unitary Air-Conditioning & Air-Soure Heat Pump Equipment Approved by ANSI in Deember

More information

Strength of Materials (Mechanics of Materials) (SI Units) Dr. Ashraf Alfeehan

Strength of Materials (Mechanics of Materials) (SI Units) Dr. Ashraf Alfeehan Strength of aterials (ehanis of aterials) (SI Units) Dr. Ashraf Alfeehan 217-218 ehanis of aterial I Tet Books ehanis of aterials, 1th edition (SI version), b: R. C. Hibbeler, 217 ehanis of aterials, 2nd

More information

Energy Saving Opportunities through Heat Recovery from Cement Processing Kilns: A Case Study

Energy Saving Opportunities through Heat Recovery from Cement Processing Kilns: A Case Study Energy Saving Opportunities through Heat Reovery from Cement Proessing Kilns: A Case Study I. I. AL-HINTI a, A. AL-GHANDOOR b, A. AL-NAJI, M. ABU-KHASHABEH, M. JOUDEH, M. AL-HATTAB a Department of Mehanial

More information

EXPERIMENTAL INVESTIGATION ON RECTANGULAR SRC COLUMNS WITH MULTI-SPIRAL CONFINEMENTS

EXPERIMENTAL INVESTIGATION ON RECTANGULAR SRC COLUMNS WITH MULTI-SPIRAL CONFINEMENTS 4th International Conferene on Earthquake Engineering Taipei, Taiwan Otober 12-13, 26 Paper No. 49 EXPERIMENTL INVESTIGTION ON RECTNGULR SRC COLUMNS WITH MULTI-SPIRL CONFINEMENTS C.C. Weng 1, Y.L. Yin

More information

Strength of Glass from Hertzian Line Contact

Strength of Glass from Hertzian Line Contact Strength of Glass from Hertzian Line Contat Wenrui Cai, Brian Cuerden, Robert E. Parks, James H. Burge College of Optial Sienes, University of Arizona, Tuson, AZ USA 85721 Phone: 52-626-486, 52-621-8182

More information

THE SITUATION WITH STEEL DECKS

THE SITUATION WITH STEEL DECKS THE SITUATION WITH STEEL DECKS Steel roof deck design can affect roof system selection and design by Mark S. Graham 32 www.professionalroofing.net MARCH 2017 teel roof decks commonly are encountered in

More information

LIGHTWEIGHT CONCRETE MATERIAL PROPERTIES FOR STRUCTURAL DESIGN. Henry G. Russell, Henry G. Russell, Inc., Glenview, IL

LIGHTWEIGHT CONCRETE MATERIAL PROPERTIES FOR STRUCTURAL DESIGN. Henry G. Russell, Henry G. Russell, Inc., Glenview, IL LIGHTWEIGHT CONCRETE MATERIAL PROPERTIES FOR STRUCTURAL DESIGN Henry G. Russell, Henry G. Russell, In., Glenview, IL ABSTRACT This paper ontains a ompilation and synthesis of researh relating to lightweight

More information

Finite Element Modeling of Cyclic Behavior of Shear Wall Structure Retrofitted using GFRP

Finite Element Modeling of Cyclic Behavior of Shear Wall Structure Retrofitted using GFRP SP-230 74 Finite Element Modeling of Cyli Behavior of Shear Wall Struture Retrofitted using GFRP by Z.J. Li, T. Balendra, K.H. Tan, and K.H. Kong Synopsis: In this paper, a non-linear 3-D finite element

More information

Strengthening of Reinforced Concrete Slab-Column Connection Subjected to Punching Shear with FRP Systems

Strengthening of Reinforced Concrete Slab-Column Connection Subjected to Punching Shear with FRP Systems IACSIT International Journal o Engineering and Tehnology, Vol. 5, No., Deember 2013 Strengning o Reinored Conrete Slab-Column Connetion Subjeted to Punhing Shear with FRP Systems G. I. Khaleel, I. G. Shaaban,

More information

Economic Assessment of Intensive Culture

Economic Assessment of Intensive Culture Reprodued from JOURNAL OF FORESTRY, Vol. 76, No. 11, November 1978, by the FOREST SERVICE, U.S. Department of Agriulture, for offiial use. About This File:,. lhis file was reated by sanning the printed

More information

Design Manual and Catalog of Steel Deck Products STEEL DECK INSTITUTE MEMBER

Design Manual and Catalog of Steel Deck Products STEEL DECK INSTITUTE MEMBER Design Manual and Catalog of Steel Deck Products s STEEL DECK INSTITUTE MEMBER Manufacturers of products History CMC Joist & Deck is a leading producer of steel deck, open-web steel joists, long span steel

More information

20 questions on genetically modified foods

20 questions on genetically modified foods Page 1 of 6 Searh All WHO This site only Home About WHO Countries Health topis Publiations Data and statistis Programmes and projets Food Safety Zoonoses Mirobiologial risks Chemial risks Biotehnology

More information

Experimental Study of a New Type Buckling-Restrained Brace. Abstract

Experimental Study of a New Type Buckling-Restrained Brace. Abstract Experimental Study of a New Type Bukling-Restrained Brae S. G. CHENG, X.X. KONG AND K.H. LUO Institute of Earthquake Engineering, China Aademy of Building Researh Abstrat The steel ore and unbonding agent

More information

Technical Data. Neutral 20. Single Pane Tinted Double Pane Double tinted Neutral 1/4" Neutral Dual 1/4" Neutral Dual 1/4" Neutral.

Technical Data. Neutral 20. Single Pane Tinted Double Pane Double tinted Neutral 1/4 Neutral Dual 1/4 Neutral Dual 1/4 Neutral. 20 (RE20NEARL) Redue air onditioning osts. Stay ooler by reduing exessive heat in warmer months. Redues glare and eye disomfort. Extend the life and vibrany in the fabri of furniture and arpets. Redues

More information

Keywords: Greenhouse; Thermal performance; Water pipes heating; Infrared radiation; Energy balance; Heating efficiency

Keywords: Greenhouse; Thermal performance; Water pipes heating; Infrared radiation; Energy balance; Heating efficiency International Symposium Greensys 7 "High Tehnology for Greenhouse system Management" Naples Italy, 4-6 Otober 7 Investigation of the Potential of Infrared-radiation (IR) to Redue Energy Consumption in

More information

Page 1 of 6 Searh All WHO This site only Home About WHO Countries Health topis Publiations Data and statistis Programmes and projets Food Safety Zoonoses Mirobiologial risks Chemial risks Biotehnology

More information

One-Way Wide Module Joist Concrete Floor Design

One-Way Wide Module Joist Concrete Floor Design One-Way Wide Module Joist Concrete Floor Design A 1 3 4 30'-0" 30'-0" 30'-0" 3' B 3' C 3' D 3' E 4" 4" (typ.) 3' F 0" 0" (typ.) Figure 1 One-Way Wide Module Joist Concrete Floor Framing System 1 Overview

More information

Effects of Electrode Composition, Flux Basicity, and Slag Depth on Grain-Boundary Cracking in Electroslag Weld Metals

Effects of Electrode Composition, Flux Basicity, and Slag Depth on Grain-Boundary Cracking in Electroslag Weld Metals Effets of omposition, Basiity, and Slag Depth on GrainBoundary raking in Eletroslag Weld Metals An aidi flux, a high slag depth, and highsilion eletrodes are found to help eliminate grainboundary raking

More information

WAER QUALITY CAPTURE VOLUME FOR STORMWATER BMP and LID DESIGNS

WAER QUALITY CAPTURE VOLUME FOR STORMWATER BMP and LID DESIGNS Guo, James C. Y. Urbonas, B. and MaKenzie K. (2012) Water Quality Capture Volume for LID and BMP Designs, HEENG- 1539, aepted for publiation on ASCE J of Hydrologi Engineering, Ot, 2012 WAER QUALITY CAPTURE

More information

Industry Standard Terms & Definitions Of The Steel Deck Institute

Industry Standard Terms & Definitions Of The Steel Deck Institute Industry Standard Terms & Definitions Of The Steel Deck Institute A specialized set of jargon to describe common terms used by manufacturers and other professionals associated with the usage of Steel Deck

More information

The American Institute

The American Institute Cynthia J. Lanz Cynthia J. Lanz is Director of Specifications at the American Institute of Steel Construction (AISC) in Chicago. The American Institute of Steel Construction (AISC) will welcome the new

More information

Optimizing the Allocation of Marketing Promotional Contacts

Optimizing the Allocation of Marketing Promotional Contacts Optimizing the Alloation of Marketing Promotional Contats Keith Hermiz, Ph.D., IBM Helene Miller, IBM Dhanesh Padmanabhan, Marketis Tehnologies Abstrat The typial marketing environment in the business-to-business

More information

CVEN 483. Structural System Overview

CVEN 483. Structural System Overview CVEN 483 Structural System Overview Dr. J. Bracci Fall 2001 Semester Presentation Overview 1. Building system primary function 2. Types of load 3. Building materials 4. Structural members 5. Structural

More information

Minimization of water and chemical usage in the cleaning in place process of a milk pasteurization plant

Minimization of water and chemical usage in the cleaning in place process of a milk pasteurization plant Songklanakarin J. Si. Tehnol. 33 (4), 431-440, Jul. - Aug. 2011 http://www.sjst.psu.a.th Original Artile Minimization of water and hemial usage in the leaning in plae proess of a milk pasteurization plant

More information

Architecture of an ERP System Supporting Project-Oriented Management

Architecture of an ERP System Supporting Project-Oriented Management Arhiteture of an ERP System Supporting Projet-Oriented Management Willy Piard and Grzegorz Wojiehowski Department of Information Tehnology The Poznań University of Eonomis ul. Mansfelda 4 60-854 Poznań,

More information

HIGH STRENGTH CONCRETE FOR SUSTAINABLE CONSTRUCTION

HIGH STRENGTH CONCRETE FOR SUSTAINABLE CONSTRUCTION 434 HIGH STRENGTH CONCRETE FOR SUSTAINABLE CONSTRUCTION Wu, D. 1, Sofi, M. 1 Mendis, P. 1 1 Department of Civil and Environmental Engineering, University of Melbourne, Vitoria, Australia. E-mail: d.wu11@ugrad.unimelb.edu.au

More information

June 1, 2012 PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS

June 1, 2012 PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS June 1, 2012 TO: PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS SUBJECT: Proposed Revisions to the Acceptance Criteria for Cold-formed Steel Framing Members, Subject AC46-0612-R1 (WM/DM) Dear

More information

Flexural Strength of RC Beams Strengthened with Prestressed CFRP Sheets Part II

Flexural Strength of RC Beams Strengthened with Prestressed CFRP Sheets Part II Flexural Strength o RC Beams Strengthened with Prestressed CFRP Sheets Part II by Piyong Yu, Pedro Frano Silva, and Antonio Nanni 1 1 1 1 1 1 1 1 Biography: Piyong Yu is a strutural Engineer with Matrix

More information

DENSIFICATION OF SELECTIVE LASER SINTERED METAL PARTS BY HOT ISOSTATIC PRESSING ABSTRACT INTRODUCTION

DENSIFICATION OF SELECTIVE LASER SINTERED METAL PARTS BY HOT ISOSTATIC PRESSING ABSTRACT INTRODUCTION DENSIFICATION OF SELECTIVE LASER SINTERED METAL PARTS BY HOT ISOSTATIC PRESSING Mukesh K. Agarwala, and David L. Bourell, Center for Materials Siene and Engineering, Joseph J. Beaman, Department ofmehanial

More information

The Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers.

The Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers. SECTION 05 31 33 - STEEL FORM DECKING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the contract, including General and Supplementary Conditions and Division 01 - Specification

More information

SAVANNAH TRIMS st STREET N., SUITE 4 LAKE PARK, FLORIDA

SAVANNAH TRIMS st STREET N., SUITE 4 LAKE PARK, FLORIDA M.O. R.O. F.S. A.F.F. STL ALUM HORIZ VERT ELEV. N.T.S. G.. ARH. P.S.F. REQ'D TYP. ABBREVIATIONS MASONRY OPENING ROUGH OPENING FRAME SIZE DAYLIGHT OPENING ABOVE FINISHED FLOOR STEEL ALUMINUM HORIZONTAL

More information

DESIGN CALCULATIONS INSTA-FOOTING LOAD BEARING CAPACITIES ON CONCRETE SLAB. January 14, 2017 Rev -

DESIGN CALCULATIONS INSTA-FOOTING LOAD BEARING CAPACITIES ON CONCRETE SLAB. January 14, 2017 Rev - DESIGN CALCULATIONS INSTA-FOOTING LOAD BEARING CAPACITIES ON CONCRETE SLAB January 14, 2017 Rev - Projection Name: Owner: Prepared by: Insta-Footing Design Calculations Insta-footing, LLC Richard Nolan,

More information

Structural Technical Report 1 Structural Concepts / Structural Existing Conditions Report

Structural Technical Report 1 Structural Concepts / Structural Existing Conditions Report Michael A. Troxell Structural Option Advisor: Professor Parfitt College of Business Administration Oct. 5, 2005 Structural Technical Report 1 Structural Concepts / Structural Existing Conditions Report

More information

DESIGN MANUAL FOR PURLIN AND CLADDING RAIL SYSTEMS

DESIGN MANUAL FOR PURLIN AND CLADDING RAIL SYSTEMS 11198 Purlin Manual Cover.qxd:11198 Purlin Manual Cover.qxd 2/4/12 16:30 Page 1 DESIGN MANUAL FOR PURLIN AND CLADDING RAIL SYSTEMS AYRSHIRE METAL PRODUCTS (Daventry) Ltd. Royal Oak Way, Daventry, Northamptonshire

More information

North Mountain IMS Medical Office Building

North Mountain IMS Medical Office Building North Mountain IMS Medical Office Building Phoenix, Arizona Michael Hopple Technical Assignment 1 October 5 th, 2007 AE 481W-Senior Thesis The Pennsylvania State University Faculty Adviser: Dr. Ali Memari,

More information

CURVATURE DUCTILITY OF REINFORCED CONCRETE BEAM

CURVATURE DUCTILITY OF REINFORCED CONCRETE BEAM CURVATURE DUCTILITY OF REINFORCED CONCRETE BEAM Monita Olivia, Parthasarathi Mandal ABSTRACT The aim o this paper is to examine the inluene o three variables on urvature dutility o reinored onrete beams.

More information

North Mountain IMS Medical Office Building

North Mountain IMS Medical Office Building North Mountain IMS Medical Office Building Phoenix, Arizona Michael Hopple Technical Assignment 2 October 29 th, 2007 AE 481W-Senior Thesis The Pennsylvania State University Faculty Adviser: Dr. Ali Memari,

More information

CALCULATION ON DEFORMATION RATIO OF SHEAR TO BENDING FOR

CALCULATION ON DEFORMATION RATIO OF SHEAR TO BENDING FOR CLCULTON ON DEFORMTON RTO OF SHER TO BENDNG FOR STEEL RENFORCED CONCRETE SPECL-SHPED COLUMNS Liu Yi, Xue Jianyang, Zao Hongtie, Cen Zongping 3 Candidate for P.D., Sool of Civil Engineering, Xi an University

More information

Vancouver Benches. Datasheet. Street Furniture. Benches & Chairs of Design, Strength,. Comfortable & Ecologic

Vancouver Benches. Datasheet. Street Furniture. Benches & Chairs of Design, Strength,. Comfortable & Ecologic 1/11 Vanouver Benhes Benhes & Chairs of Design, Strength,. Comfortable & Eologi Versions: Benh & Chair (5 or 6 boards) & Bakless Benh Suitable in three material versions, Pine (SFC) wood, Tropial (SFC)

More information

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel

More information

Pro-Con Structural Study for Alternative Floor Systems October 27, 2004

Pro-Con Structural Study for Alternative Floor Systems October 27, 2004 Ismail Al-Hadhrami Structural Option Faculty Consultant: Dr. Thomas Boothby Agricultural Hall and Annex East Lansing, MI Pro-Con Structural Study for Alternative Floor Systems October 27, 2004 Executive

More information