B. Provide equipment complying with this specification and manufactured by one of the following:

Size: px
Start display at page:

Download "B. Provide equipment complying with this specification and manufactured by one of the following:"

Transcription

1 SECTION PAINT SPRAY BOOTH PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Provide Paint Spray Booth, Prep Booth and Paint Mix Room, and associated ventilation equipment, complying with the requirements in this specification chapter. B. The following specifications sections shall apply: 1. Section Common Motor Requirements for Plumbing Equipment. 2. Section Facility Natural-Gas Piping. 3. Section Metal Ducts. 4. Section B Low-Voltage Electrical Power Conductors and Cables. 1.2 QUALITY ASSURANCE A. Equipment shall be produced by a manufacturer of established reputation with a minimum of five years experience supplying specified equipment. B. Provide equipment complying with this specification and manufactured by one of the following: 1. Global Finishing Solutions. C. Equipment supplied and installed shall comply with the following building codes and industry standards: 1. International Building Code. 2. International Fire Code. 3. NFPA-33: Standard for Spray Application Using Flammable of Combustible Materials. 4. NFPA-70: National Electrical Code. 5. NFPA-86: Standard for Ovens & Furnaces. 6. NFPA-91: Standard for Exhaust Systems for Air Conveying of Materials. 7. NFPA-101: Life Safety Code. 8. OSHA Safety & Health Standards (29 CFR ). 9. ASHRAE 90.1: Energy Standard for Buildings Except Low-Rise Residential Buildings. 10. All parts and equipment shall carry the appropriate UL and ETL Listings, where applicable. D. Provide a qualified manufacturer s representative at site to supervise work related to equipment installation, check out, and start up. E. Manufacturer s representative of the Paint Spray Booth system shall be responsible for the design and performance of the equipment to owner s satisfaction. PAINT SPRAY BOOTH

2 1.3 SUBMITTALS A. Product Data: Submit Product Data in accordance with Division 1 of these specifications. B. Operations and Maintenance Manual: 1. Submit Operations and Maintenance Manuals in accordance with Division 1- General Requirements of these specifications. 2. Provide complete parts, operating, and maintenance manual covering equipment at time of installation. 3. Schematic diagrams of electrical, plumbing, and mechanical ventilation, and cooling and heating air system. 4. Manufacturer s printed operating instructions. 5. Printed listing of periodic preventive maintenance items and recommended frequency to validate warranties. Failure to provide maintenance information will indicate that preventive maintenance is not a condition for validation of warranties. 1.4 WARRANTY A. Warranty work against defects in materials, functions and workmanship specified herein shall be good for 3 years from substantial completion. B. Warranty shall include materials and labor necessary to correct defects. C. Defects shall include, but not be limited to substandard operation; loose, damaged, and missing parts; and abnormal deterioration of finish. Defects shall not include damage due to neglect, misuse, or situations resulting from non-performance of a manufacturer s recommended preventive maintenance schedule. 1.5 PRODUCT DELIVERY, STORAGE, AND HANDLING A. Deliver equipment in manufacturer s containers, appropriately packaged and/or crated for protection during domestic shipment and storage in humid and/or dusty conditions. B. Label all containers on outside with item description(s) per title and Equipment Identifier of this specification. C. Provide equipment and materials specified complete in one shipment for each equipment item. PART 2 - PRODUCTS 2.1 SYSTEM DESCRIPTION A. General: The Paint Spray Booths equipment shall be dual-skin, downdraft, drive-in/back-out configuration, with high-performance airflow ceiling (HPAC), similar to Global Finishing Solutions, Ultra XD Equipment Series with BT Heater. Prep Booths be an excel workstation. Mix Room shall be a two sided Ultra XD Paint Mix Room. PAINT SPRAY BOOTH

3 B. Dimensions: 1. Exterior Dimensions: 14 5 W x 11 H x 30 5 L. 2. Internal Dimensions: 14 W x 9 H x 30 L. C. Construction: 1. High-performance airflow filter ceiling (HPAC). 2. Dual-skin insulated panels, made of rust-resistant, G-40, galvanized sheet metal Primed and coated on both sides with a baked-on polyester topcoat Inch galvanized steel H-channel columns construction; to connect wall panels without the use of nuts and/or bolts. 4. Floor Track Leveling. 5. Full 14-Ft wide, 2-Ft High plenum. D. Doors: 1. 3-slab entry door with (3) observation windows, 9-8 W x H. 2. Center door between booths. 3. Personnel service door with observation window, 2-8 x Weld free design, provide with high quality hardware, including fully-adjustable heavyduty handles, hinges and latches. Provide with durable hollow rubber seals. E. Ceiling: F. Floor: 1. High Performance Air flow Ceiling (HPAC), fully filtered. With integrated hip ceiling lights. 1. Floor shall be a single-row pit type system, along the center and includes the following parts from bottom to top: G. Lights: a. Full length concrete pit, 27-Ft. b. Diffusion tray. c. Wire-grid for filter support. d. Filter media. e. Heavy-duty steel grating. 1. (10) 4-tube, Class-I, Div.2, LED light fixtures, inside ceiling and accessible. 2. (4) 4-tube, side wall, Class-I, Div.2, LED Light Fixtures. 3. Include color-corrected light tubes. 4. ETL listed. 5. Provide interlock switch to disable painting operations when light access door is opened. H. Air Heating Equipment: 1. Basis of Design is GFS BT Side mounted, 15,000-CFM, 150,000-BTUH Input, Natural Gas. PAINT SPRAY BOOTH

4 3. Intake/Exhaust fan Motor HP: 15-HP DD / 7.5-HP BD. 4. Intake fan shall be reverse-incline, direct drive air-foil centrifugal, aluminum non-sparking construction. 5. Exhaust fan shall be tube axial. 6. Burner shall be direct-fire type made of corrosion-resistant aluminum. 7. Auto-Pressure Control: Include fans variable frequency drives and pressure transducer for auto-balancing. 8. Options: dual hi-limit switch, door safety interlock, and filter monitoring. 9. Gas Min Inlet Pressure: 11.3-iwc. 10. Gas Max Inlet Pressure: 5.0-psi. I. Advance Cure: 1. Provide cabin with integrated ADVANCE-CURE system to achieve faster and more even drying. J. Filters: 1. Booth Plenum: Diffusion Blanket Media. 2. Pit: GFS Wave Roll Media. 3. Air Heater Intake: Framed 5-Pocket. K. Controls: 1. Provide with automated controls LOGIC3 control panel, and integrate with DX cooling system control. 2. Include following features/modes: a. 3-programmable options to control time, and temperature, adjustable for any type of coating. b. SmartFlash feature to manage dry temperature between coats. c. Economy Mode energy saving feature. d. Built in self-diagnostic and alarms. PART 3 - EXECUTION 3.1 EXAMINATION A. Inspect delivered equipment for damage from shipping and exposure to weather. Compare delivered equipment with packing lists and specifications to assure receipt of all equipment items and specified accessories. B. Coordinate location of rough-in work and utility stub-outs to assure match with equipment to be installed. PAINT SPRAY BOOTH

5 3.2 INSTALLATION, GENERAL A. General Contractor shall provide final connection of equipment to all utilities, including disconnects, floor, piping and conduit structures, with labor services and incidentals necessary for complete and operational equipment installation. B. Manufacturer s Representative shall provide connections between equipment and roughed-in utilities and equipment connections. Installer is responsible for all system wiring and connections to mechanical and plumbing utilities for a complete operation of equipment after installation. C. General Contractor shall coordinate all equipment features which interface with building systems that are required beyond the roughed-in utilities. 3.3 ELECTRIC CONNECTIONS A. Electrical contractor shall furnish and install electrical power to equipment connection points at the direction of the equipment manufacturer representative. B. Coordinate with electrical plans and division 26 of the specifications. 3.4 PLUMBING CONNECTIONS A. Plumbing contractor shall furnish and install natural gas and compressed air connections to equipment at the direction of equipment manufacturer representative. B. Coordinate with plumbing plans and division 23 of the specifications. 3.5 INTAKE AND EXHAUST DUCTS A. Equipment supplier shall furnish exhaust and intake ducts, duct sizes as instructed by manufacturer. Ductwork shall be fabricated from 18-gage G90 galvanized steel. Include duct sections with required access and cleaning doors. B. Mechanical contractor shall install intake and exhaust duct on site. Mechanical contractor shall make connections to Paint Booth Equipment as instructed by equipment representative on site. Mechanical contractor shall provide all required cables, supports, anchors and clamps for complete and safe installation, and approved by equipment supplier, owner and AHJ. C. Maintain following clearances from building to air exhaust point above the roof: 1. At least 6-Ft from any exterior wall or roof. 2. At least 30-Ft away from the property line. 3. Terminate at higher elevation than all air intakes on the roof and at least 10-Ft away. 3.6 FIRE SUPPRESSION A. Fire suppression system shall be wet pipe sprinkler type which complies with NFPA 17. PAINT SPRAY BOOTH

6 3.7 CLEARANCES A. Provide code and service required clearances around and above Paint Spray Booth equipment, including, clearances to doors, heating and cooling equipment and filters. B. Any electrical and wiring devices which are installed within 3-Ft of Paint Spray Booth doors must be listed for Class-I, Div. 2. C. Provide code required explosion relief clearance above the Paint Spray Booth. D. Equipment representative shall examine and approve the construction documents and the physical area allocated for the paint spray booth before ordering or installing equipment to ensure all clearances shall be met. 3.8 IDENTIFICATION A. Manufacturer shall securely attach in a prominent location, on each major item of equipment, a non-corrosive nameplate showing manufacturer s name, address, model number, serial number, and pertinent utility or operating data. B. Label all parts of equipment as to its function. 3.9 CLEANING A. Touch-up damage to painted finishes. B. Wipe and clean equipment of any oil, grease and solvents, and make ready for use. C. Clean area around equipment installation and remove packing or installation debris from job site. D. Notify Architect or designated representative for acceptance inspection TESTING A. After final connections are made and prior to authorizing payment, specified equipment shall be tested for compliance with specification in the presence of the Architect or designated representative using acceptance procedures provided by the manufacturer. Testing report shall be submitted to the Architect or designated representative. B. Malfunctions during testing shall be corrected within five days and re-tested. Malfunctions during second testing shall be corrected within five days and re-tested. C. Inadequate performance: If equipment fails the third test, Owner may elect to have all installed equipment removed from site at no cost or obligation to the Owner. PAINT SPRAY BOOTH

7 3.11 DEMONSTRATION A. Training: Provide technical representative to provide training to Owner s maintenance personnel in operation and maintenance of specified equipment. B. Manufacturer shall provide Spare Parts Kit of the most critical parts which are applicable to the installed system. C. Manufacturer shall provide at least one complete set of spare filter and light tubes. END OF SECTION PAINT SPRAY BOOTH I:\Projects\ \ _0001\70_Specifications\0002\ docx

8 This Page Intentionally Blank

9

10

11

12

Re: ADDENDUM NO. 1 Project RFP for Design Build of SouthPort Vehicle Processing Facility

Re: ADDENDUM NO. 1 Project RFP for Design Build of SouthPort Vehicle Processing Facility Philadelphia Regional Port Authority 3460 North Delaware Ave. 2 nd Floor Philadelphia, PA 19134 May 24, 2018 To: All Bidders From: Kate Bailey Director of Procurement Re: ADDENDUM NO. 1 Project -18-059.1

More information

Truck and Large Equipment. Galvanized Spray Booths. Global Finishing Solutions

Truck and Large Equipment. Galvanized Spray Booths. Global Finishing Solutions Global Finishing Solutions Truck and Large Equipment Galvanized Spray Booths > Heavy-Duty Construction > Inside Accessible Energy Efficient Light Fixtures > and - Models > Expandable Modular Designs GFS

More information

SECTION AIR-TO-AIR ENERGY RECOVERY EQUIPMENT

SECTION AIR-TO-AIR ENERGY RECOVERY EQUIPMENT SECTION 23 72 00 AIR-TO-AIR ENERGY RECOVERY EQUIPMENT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

PIKES PEAK PARKING RESTORATION TABLE OF CONTENTS

PIKES PEAK PARKING RESTORATION TABLE OF CONTENTS 23 HEATING, VENTILATING AND AIR CONDITIONING TABLE OF CONTENTS TABLE OF CONTENTS DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING - Basic HVAC Requirements 238239.19 - Wall and Ceiling Unit Heaters

More information

SECTION EXHAUST FANS PART 1 GENERAL

SECTION EXHAUST FANS PART 1 GENERAL SECTION 15800 EXHAUST FANS PART 1 GENERAL 1.01 DESCRIPTION A. The Contractor shall furnish all labor, materials, accessories and all incidentals required to install wet well and control building ventilation

More information

PAINT BOOTHS GENERAL PURPOSE

PAINT BOOTHS GENERAL PURPOSE PAINT BOOTHS GENERAL PURPOSE 1 INDUSTRY-LEADING PRODUCTS With precise contamination control and premium angled ceiling hip lights, General Purpose Paint Booths from Global Finishing Solutions (GFS) enable

More information

ADDENDUM 2 - JULY 14, 2015

ADDENDUM 2 - JULY 14, 2015 7/9/2015 The Professional(s) of Record above has signed for the following specification sections: DIVISION 1 GENERAL REQUIREMENTS Section 01 10 00 Summary of Work Section 01 25 00 Substitution Procedures

More information

PAINT BOOTHS LARGE EQUIPMENT

PAINT BOOTHS LARGE EQUIPMENT PAINT BOOTHS LARGE EQUIPMENT 1 THE FINISHING TOUCH A flawless paint finish can make a product stand out from the rest. With precise contamination control and excellent lighting, Large Equipment Booths

More information

SECTION FUEL-FIRED UNIT HEATERS

SECTION FUEL-FIRED UNIT HEATERS SECTION 23 55 33 PART 1 - GENERAL 1.1 DESCRIPTION A. This Section includes gas-fired unit heaters. SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable

More information

SECTIONAL OVERHEAD DOORS SECTION SECTIONAL OVERHEAD DOORS PART 1 GENERAL

SECTIONAL OVERHEAD DOORS SECTION SECTIONAL OVERHEAD DOORS PART 1 GENERAL 13686.00 SECTIONAL OVERHEAD DOORS 083613-1 1.1 RELATED DOCUMENTS SECTION 083613 - SECTIONAL OVERHEAD DOORS PART 1 GENERAL A. Drawings and general provisions of Contract, including General and Supplementary

More information

HOLLOW METAL DOORS AND FRAMES SECTION HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL

HOLLOW METAL DOORS AND FRAMES SECTION HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 13686.00 HOLLOW METAL DOORS AND FRAMES 081113-1 SECTION 081113 - HOLLOW METAL DOORS AND FRAMES 1.1 RELATED DOCUMENTS: PART 1 - GENERAL A. Drawings and general provisions of Contract, including General

More information

SECTION Motor Operated Horizontal Sliding Sound Control Door

SECTION Motor Operated Horizontal Sliding Sound Control Door SECTION 08 34 73 Motor Operated Horizontal Sliding Sound Control Door PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including general and Supplementary Conditions

More information

L-SERIES: LTH3900 SPECIFICATIONS Stainless Steel Hollow Metal Sliding Fire Door System

L-SERIES: LTH3900 SPECIFICATIONS Stainless Steel Hollow Metal Sliding Fire Door System Version 5.22.13 L-SERIES: LTH3900 SPECIFICATIONS Stainless Steel Hollow Metal Sliding Fire Door System OPTIONS ARE LISTED IN BOLD, PLEASE MODIFY THESE AREAS AS NEEDED BASED ON YOUR PROJECT CONSULT MANUFACTURER

More information

SECTION LINEAR MOTION SLUDGE MIXERS

SECTION LINEAR MOTION SLUDGE MIXERS SECTION 11480 LINEAR MOTION SLUDGE MIXERS PART 1 -- GENERAL 1.01 THE REQUIREMENT A. The Contractor shall furnish, install, adjust, finish paint and test one (1) linear motion sludge mixer for mounting

More information

C. Samples: For each door face material, at least 3 by 5 inches (75 by 125 mm) in size, in specified finish.

C. Samples: For each door face material, at least 3 by 5 inches (75 by 125 mm) in size, in specified finish. SECTION 083113 - ACCESS DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION LOW-VOLTAGE TRANSFORMERS

SECTION LOW-VOLTAGE TRANSFORMERS PART 1 GENERAL 1.1 DESCRIPTION SECTION 26 22 00 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between // // if not applicable to project. Also, delete any other item or paragraph not

More information

Watercrest - Sand Hill - Columbia, SC TABLE OF CONTENTS PROCUREMENT AND CONTRACTING REQUIREMENTS

Watercrest - Sand Hill - Columbia, SC TABLE OF CONTENTS PROCUREMENT AND CONTRACTING REQUIREMENTS Watercrest - Sand Hill - Columbia, SC 00 0110-1 TABLE OF CONTENTS DIVISION 00 PROCUREMENT AND CONTRACTING REQUIREMENTS INTRODUCTORY INFORMATION Document 00 0101 Document 00 0110 Project Title Page CONTRACTING

More information

N-SERIES: NTH3500 SPECIFICATIONS Hollow Metal Sliding Door System

N-SERIES: NTH3500 SPECIFICATIONS Hollow Metal Sliding Door System Version 5.22.13 N-SERIES: NTH3500 SPECIFICATIONS Hollow Metal Sliding Door System OPTIONS ARE LISTED IN BOLD, PLEASE MODIFY THESE AREAS AS NEEDED BASED ON YOUR PROJECT CONSULT MANUFACTURER FOR ADDITONAL

More information

LTH3700, HOLLOW METAL SLIDING FIRE DOOR

LTH3700, HOLLOW METAL SLIDING FIRE DOOR LTH3700, HOLLOW METAL SLIDING FIRE DOOR Consult Manufacturer for additional options or modifications PART 1-GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

603 Summit Avenue, Suite 102 Greensboro, N.C Voice/FAX (336)

603 Summit Avenue, Suite 102 Greensboro, N.C Voice/FAX (336) Ricky L. Loman, AIA Architect 603 Summit Avenue, Suite 102 Greensboro, N.C. 27405-7700 Voice/FAX (336) 273-7999 ADDENDUM: Number 1 ISSUED: March 14, 2017 SUBJECT: New Agriculture & Equipment Storage Barn

More information

SECTION The specification section is organized by placing information in three standard parts:

SECTION The specification section is organized by placing information in three standard parts: SECTION 14244 LIMITED USE HYDRAULIC ELEVATOR ***** Since 1982 Liftavator, Inc. has provided limited use/limited application (LU/LA) elevators, residential elevators, hydraulic vertical platform wheelchair

More information

City of Westerville Guide to Commercial Inspections

City of Westerville Guide to Commercial Inspections City of Westerville Guide to Commercial Inspections FOOTINGS - After the excavation, with the form work and any required reinforcing steel in place. All footings shall have loose soil removed, reinforcing

More information

SECTION DOOR HARDWARE

SECTION DOOR HARDWARE SECTION 087100 -DOOR HARDWARE PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

N-SERIES: NTH2700 SPECIFICATIONS Tubular Composite Top Hung Sliding Door System

N-SERIES: NTH2700 SPECIFICATIONS Tubular Composite Top Hung Sliding Door System Version 5.22.13 N-SERIES: NTH2700 SPECIFICATIONS Tubular Composite Top Hung Sliding Door System OPTIONS ARE LISTED IN BOLD, PLEASE MODIFY THESE AREAS AS NEEDED BASED ON YOUR PROJECT CONSULT MANUFACTURER

More information

ANSI/ ASME HST Performance Standard For Overhead Electric Wire Rope Hoists

ANSI/ ASME HST Performance Standard For Overhead Electric Wire Rope Hoists SECTION 412213- BRIDGE CRANES Part 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

The fire resistance required for doors in this building is 1 (one) hour resistance in compliance with the below general specifications:

The fire resistance required for doors in this building is 1 (one) hour resistance in compliance with the below general specifications: Query No.1 ; we need more specs. about fire resistant doors Answer to Query No. 1: The fire resistance required for doors in this building is 1 (one) hour resistance in compliance with the below general

More information

F-SERIES: F SPECIFICATIONS Four-Fold Door Systems

F-SERIES: F SPECIFICATIONS Four-Fold Door Systems Version 5.22.13 F-SERIES: F100-600 SPECIFICATIONS Four-Fold Door Systems OPTIONS ARE IN BOLD, PLEASE MODIFY THESE AREAS AS NEEDED BASED ON YOUR PROJECT. CONSULT MANUFACTURER FOR ADDITIONAL OPTIONS OR MODIFICATIONS.

More information

SECTION CONVECTORS

SECTION CONVECTORS SECTION 23 82 33 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

1. Include construction details, materials, individual components and profiles, and finishes.

1. Include construction details, materials, individual components and profiles, and finishes. SECTION 08 31 13 - ACCESS DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings,and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Spray Booth Guideline

Spray Booth Guideline Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 2016 CODES PURPOSE The intent of this guideline is to provide the information necessary

More information

TABLE OF CONTENTS Public Safety Building

TABLE OF CONTENTS Public Safety Building DOCUMENT 00 01 10 - TABLE OF CONTENTS VOLUME I DIVISION 00 PROCUREMENT AND CONTRACTING REQUIREMENTS 00 01 10 Table of Contents 00 31 32 Geotechnical Data DIVISION 01 GENERAL REQUIREMENTS 01 10 00 Summary

More information

SECTION AIR TERMINAL UNITS

SECTION AIR TERMINAL UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Welded System

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Welded System SECTION 13096 RADIO FREQUENCY SHIELDING ENCLOSURE RF Welded System Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13096-1 RF WELDED SYSTEM PART 1 GENERAL 1.1 SECTION

More information

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

SECTION BASIC ELECTRICAL MATERIALS AND METHODS SECTION 26 05 05 BASIC ELECTRICAL MATERIALS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the limited scope construction materials and methods for application with electrical installations as follows:

More information

SECTION COOLING TOWER

SECTION COOLING TOWER PART 1 GENERAL 1.1 SECTION INCLUDES A. Mechanical induced draft Cooling Tower B. Controls C. Ladder and handrails 1.2 REFERENCES SECTION 23 65 00 COOLING TOWER A. ANSI/AFBMA 9 - Load Rating and Fatigue

More information

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including:

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including: Page 1 of 7 SECTION 083925 MECHANICAL ROOM FLOOD DOORS AND FRAMES **Note to Specifier** This specification contains component and configuration options. Where indicated, choose the appropriate choice for

More information

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION LIST OF FIGURES...

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION LIST OF FIGURES... DIVISION 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN Contents 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION 13 00 60 LIST OF FIGURES... 6 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN 1. General Requirements

More information

FF200, FOUR-FOLD DOORS CONSULT MANUFACTURER FOR ADDITIONAL OPTIONS OR MODIFICATIONS.

FF200, FOUR-FOLD DOORS CONSULT MANUFACTURER FOR ADDITIONAL OPTIONS OR MODIFICATIONS. FF200, FOUR-FOLD DOORS CONSULT MANUFACTURER FOR ADDITIONAL OPTIONS OR MODIFICATIONS. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

SECTION ENCLOSED BUS ASSEMBLIES

SECTION ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents DIVISION 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN Contents 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION 13 00 60 LIST OF FIGURES... 6 Page 1 of 6 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN 1. General

More information

F-SERIES: FF XT SPECIFICATIONS Exterior Swinging Four-Fold Door Systems

F-SERIES: FF XT SPECIFICATIONS Exterior Swinging Four-Fold Door Systems Version 5.22.13 F-SERIES: FF100-600XT SPECIFICATIONS Exterior Swinging Four-Fold Door Systems OPTIONS ARE LISTED IN BOLD, PLEASE MODIFY THESE AREAS AS NEEDED BASED ON YOUR PROJECT. CONSULT MANUFACTURER

More information

SECTION OVERHEAD COILING FIRE DOORS MODEL 662 OVERHEAD COILING COUNTER FIRE DOORS WITH INTEGRAL FRAME

SECTION OVERHEAD COILING FIRE DOORS MODEL 662 OVERHEAD COILING COUNTER FIRE DOORS WITH INTEGRAL FRAME SECTION 08331 OVERHEAD COILING FIRE DOORS MODEL 662 OVERHEAD COILING COUNTER FIRE DOORS WITH INTEGRAL FRAME Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES

More information

"SRMZ" ROOFTOP PACKAGED MULTIZONE UNITS Self Contained Single Package Units 17.5 to 43 Ton Cooling Capacities

SRMZ ROOFTOP PACKAGED MULTIZONE UNITS Self Contained Single Package Units 17.5 to 43 Ton Cooling Capacities "SRMZ" ROOFTOP PACKAGED MULTIZONE UNITS Self Contained Single Package Units 17.5 to 43 Ton Cooling Capacities Packaged Rooftop Multizone shall be Spinnaker Industries Inc. Model Series SRMZ. Units shall

More information

SECTION ENCLOSED BUS ASSEMBLIES

SECTION ENCLOSED BUS ASSEMBLIES SECTION 262500 ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Division 00 Procurement and Contracting Requirements

Division 00 Procurement and Contracting Requirements SECTION 00 01 10 TABLE OF CONTENTS Division SECTION NO. VOLUME ONE Title SECTION TITLE Division 00 Procurement and Contracting Requirements 00 11 00 Invitation to Bidders 00 21 00 Instructions to Bidders

More information

SECTION STEEL DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION STEEL DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 08110 - STEEL DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General, Supplementary, and Special Conditions and Division 1 Specification

More information

SERIES STB30 STEEL FIXED THERMAL BREAK DETENTION WINDOWS SECTION 08651

SERIES STB30 STEEL FIXED THERMAL BREAK DETENTION WINDOWS SECTION 08651 SERIES STB30 STEEL FIXED THERMAL BREAK DETENTION WINDOWS SECTION 08651 PART 1 GENERAL 1.1 DESCRIPTION A. Work Included: 1. Furnish all labor and materials to complete the fabrication of detention windows

More information

SECTION CRL70 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

SECTION CRL70 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS Page 1 of 6 SECTION 08 32 20 CRL70 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS [OR WOOD] PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,

More information

SECTION MODULAR GALVANIZED RF SHIELDING SYSTEM SPECIFICATIONS

SECTION MODULAR GALVANIZED RF SHIELDING SYSTEM SPECIFICATIONS SECTION 13096 MODULAR GALVANIZED RF SHIELDING SYSTEM SPECIFICATIONS Prepared by: NELCO 125 Chenoweth Lane, Ste. 206 Louisville, KY 40207 (502) 899-3726 13096-1 MODULAR GALVANIZED RF SHIELDING SYSTEM PART

More information

AMBICO Limited Section BLAST RESISTANT STEEL OVERHEAD DOOR ASSEMBLIES Page 1

AMBICO Limited Section BLAST RESISTANT STEEL OVERHEAD DOOR ASSEMBLIES Page 1 Page 1 This section includes Blast Resistant, Steel, Overhead Door Assemblies, with integral electric operators and accessories. This section includes proprietary, descriptive and performance type specification

More information

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding.

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding. ALLIANT ENERGY CENTER PAVILIONS Project No. 2013 027 SECTION 27 11 00 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

New Spray Booths Used Spray Booths New Commercial Spray Booths Paint Mixing Rooms Smart Repair Bays CV Conversions Extraction units Industrial Spray

New Spray Booths Used Spray Booths New Commercial Spray Booths Paint Mixing Rooms Smart Repair Bays CV Conversions Extraction units Industrial Spray New Spray Booths Used Spray Booths New Commercial Spray Booths Paint Mixing Rooms Smart Repair Bays CV Conversions Extraction units Industrial Spray Booths Emission and LEV testing for all makes of Spray

More information

SECTION HVAC AIR CLEANING DEVICES

SECTION HVAC AIR CLEANING DEVICES SECTION 23 40 00 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS INDIANA UNIVERSITY BIDDING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 (REVISED 2005) MINORITY,

More information

Project Manual Index of Specifications Shenandoah Schools Concession Building

Project Manual Index of Specifications Shenandoah Schools Concession Building INDEX OF SPECIFICATIONS Division 0..BIDDING AND CONTRACT REQUIREMENTS 00 11 13 Advertisement for Bids 00 21 13 Instructions to Bidders 00 41 00 Bid Forms 00 43 13 Bid Security Form 00 72 00 General Conditions

More information

A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein.

A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein. 16470 PANELBOARDS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 16 An optional keynote to

More information

SECTION AIR OUTLETS AND INLETS

SECTION AIR OUTLETS AND INLETS PART 1 - GENERAL 1.1 DESCRIPTION A. Roof Curbs SECTION 23 37 00 AIR OUTLETS AND INLETS SPEC WRITER NOTE: 1. Delete between //----// if not applicable to project. Also delete any other item or paragraph

More information

SECTION INSTALLATION OF OWNER-FURNISHED PRODUCTS

SECTION INSTALLATION OF OWNER-FURNISHED PRODUCTS SECTION 13 00 50 INSTALLATION OF PART 1 GENERAL 1.1 GENERAL A. Furnish and install all tools, supplies, materials, equipment, appurtenances, and labor necessary for the installation, testing, and placing

More information

Division 16 Sections for electrical service for elevators to and including disconnect and fused switches at machine room.

Division 16 Sections for electrical service for elevators to and including disconnect and fused switches at machine room. A+ ELEVATORS & LIFTS An A+ Connection Company Phone: 888-444-APLUS (2758) Fax: 888-444-9377 Email: info@aplusconnection.com Web: www.aplusconnection.com GEAR DRIVE An A+ Connection Company SECTION 14202

More information

SECTION PERSONNEL DUTY LOCKERS. 1. FPPL Series Police Personnel Duty Lockers, including the following:

SECTION PERSONNEL DUTY LOCKERS. 1. FPPL Series Police Personnel Duty Lockers, including the following: SECTION 10501 PERSONNEL DUTY LOCKERS PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 specifications

More information

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including:

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including: Page 1 of 7 SECTION 083925 MECHANICAL ROOM FLOOD DOORS AND FRAMES **Note to Specifier** This specification contains component and configuration options. Where indicated, choose the appropriate choice for

More information

SECTION LIGHTING. A. Section Basic Electrical Materials and Methods

SECTION LIGHTING. A. Section Basic Electrical Materials and Methods SECTION 16500 LIGHTING PART 1 GENERAL 1.01 SECTION INCLUDES A. Provide lighting fixtures of sizes, types and ratings as indicated; complete with, but not necessarily limited to, housings, lamps, lamp holders,

More information

A. Access doors and frames are part of an access door and frame allowance.

A. Access doors and frames are part of an access door and frame allowance. SECTION 08 31 13 ACCESS DOORS AND FRAMES PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Melhart Music Center Modular Music Practice Rooms - E3 Ready Specifications Section 13034

Melhart Music Center Modular Music Practice Rooms - E3 Ready Specifications Section 13034 Melhart Music Center Modular Music Practice Rooms - E3 Ready Specifications Section 13034 PART 1 - General 1.01 Summary A. Section includes labor, material, equipment, and other considerations required

More information

SECTION / STC 52 METAL SOUND CONTROL DOORS

SECTION / STC 52 METAL SOUND CONTROL DOORS SECTION 08 34 73 / 08 34 73.13 STC 52 METAL SOUND CONTROL DOORS PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including general and Supplementary Conditions

More information

SECTION GENERAL ELECTRICAL REQUIREMENTS PART 1- GENERAL

SECTION GENERAL ELECTRICAL REQUIREMENTS PART 1- GENERAL 1.01 DESCRIPTION SECTION 16000 GENERAL ELECTRICAL REQUIREMENTS PART 1- GENERAL A. This Section includes the general provisions applicable to electrical work and testing of the completed electrical systems.

More information

FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR

FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR Section 083713- Four Fold Doors- With Single Overhead Mounted Operator Part 1-General 1.1 Related Document: A. Drawing and general provisions of contract,

More information

SECTION METAL DOORS & FRAMES

SECTION METAL DOORS & FRAMES SECTION 08100 METAL DOORS & FRAMES PART 1 GENERAL 1.1 SCOPE Drawings and general provisions of the Contract, including General and Supplementary General Conditions and other Division 00 & 01 specification

More information

GUC LNG Facility Phase IIB Expansion 6/20/14 INSTRUMENTATION SPECIFICATION. A. This Section includes instrumentation for process piping systems.

GUC LNG Facility Phase IIB Expansion 6/20/14 INSTRUMENTATION SPECIFICATION. A. This Section includes instrumentation for process piping systems. INSTRUMENTATION SPECIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Section 70 Airport Transformer Vault and Vault Equipment (FAA L-109)

Section 70 Airport Transformer Vault and Vault Equipment (FAA L-109) Black text from standard FAA spec Strikeout text deletions from FAA standard spec Blue text additions to FAA standard spec Red text notes to the Engineer/won t appear in spec I. DESCRIPTION 1. This item

More information

Adjustable air blowers. External Spray Booths

Adjustable air blowers. External Spray Booths Haltec has an excellent reputation as a hands on company, looking after their customers and ensuring that they meet their unique individual requirements. We are based in Hednesford, Staffordshire although

More information

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Galvanized System

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Galvanized System SECTION 13096 RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Galvanized System Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13096-1 RF MODULAR GALVANIZED SYSTEM PART

More information

F International Fire Code

F International Fire Code 210500- COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 -GENERAL REQUIREMENTS AND EXECUTION REQUIREMENTS 1.1 CODE SECTIONS A. 2012 International Mechanical Code B. 20121nternational Building Code C. 2012

More information

1. Vertical reciprocating conveyor, Hydraulic straddle VRC.

1. Vertical reciprocating conveyor, Hydraulic straddle VRC. PART 1: GENERAL 1.01 Section Includes: 1. Vertical reciprocating conveyor, Hydraulic straddle VRC. a. Machine, controller, platform, structural steel hoist frame. b. Wire mesh enclosure and gates. Related

More information

Architect s Project Number of 5 Decentralized HVAC Equipment District Master Specs 2013 Edition

Architect s Project Number of 5 Decentralized HVAC Equipment District Master Specs 2013 Edition PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 23 81 00 DECENTRALIZED HVAC EQUIPMENT A. The other Contract Documents complement the requirements of this section. The General requirements apply to the work

More information

COMPLETE REVISION November Process Industry Practices Architectural. PIP ARS08111 Standard Steel Doors and Frames Supplier Specification

COMPLETE REVISION November Process Industry Practices Architectural. PIP ARS08111 Standard Steel Doors and Frames Supplier Specification November 2012 Process Industry Practices Architectural PIP ARS08111 Standard Steel Doors and Frames Supplier Specification PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost

More information

PIP ARS08111 Standard Steel Doors and Frames Supplier Specification

PIP ARS08111 Standard Steel Doors and Frames Supplier Specification May 2018 Architectural PIP ARS08111 Standard Steel Doors and Frames Supplier Specification PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities,

More information

SECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 08332 [08 33 13] COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) ** NOTE TO SPECIFIER ** Wayne Dalton; Coiling counter door products.. This section is based

More information

Price Fan Powered Terminal Units

Price Fan Powered Terminal Units Price Fan Powered Terminal Units Division 23 Heating, Ventilating, and Air Conditioning Section 23 3600 Air Terminal Units The following specification is for a defined application. Price would be pleased

More information

1. Vertical reciprocating conveyor, Hydraulic straddle VRC.

1. Vertical reciprocating conveyor, Hydraulic straddle VRC. PART 1: GENERAL 1.01 Section Includes: 1. Vertical reciprocating conveyor, Hydraulic straddle VRC. a. Machine, controller, platform, structural steel hoist frame. b. Wire mesh enclosure and gates. Related

More information

SPECIAL SPECIFICATION 8810 Communication Hub Enclosure

SPECIAL SPECIFICATION 8810 Communication Hub Enclosure 2004 Specifications CSJ 0914-00-301 & 0914-00-314 SPECIAL SPECIFICATION 8810 Communication Hub Enclosure 1. Description. Provide Communication Hub Enclosures of various types and sizes, as shown on the

More information

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including:

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including: Page 1 of 8 SECTION 083919 WATERTIGHT DOORS **Note to Specifier** This specification contains component and configuration options. Where indicated, choose the appropriate choice for your specific project

More information

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including:

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including: Page 1 of 8 SECTION 083921 PEDESTRIAN FLOOD DOORS AND FRAMES **Note to Specifier** This specification contains component and configuration options. Where indicated, choose the appropriate choice for your

More information

SECTION MOTOR CONTROL CENTER

SECTION MOTOR CONTROL CENTER SECTION 16445 MOTOR CONTROL CENTER PART 1 GENERAL 1.01 DESCRIPTION A. This section covers the contract item Motor Control Center (MCC). The contract item includes demolition and removal of existing MCC;

More information

SECTION EZ-SLIDE 80 AND 180 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

SECTION EZ-SLIDE 80 AND 180 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS Page 1 of 6 SECTION 08 32 20 EZ-SLIDE 80 AND 180 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,

More information

This guide can be used to prepare a specification for incorporating wall bracket jib cranes into a competitively bid construction project.

This guide can be used to prepare a specification for incorporating wall bracket jib cranes into a competitively bid construction project. SECTION 14654 WALL BRACKET JIB CRANE ***** Gorbel, Inc. manufacturers a broad range of material handling cranes including monorail, bridge, gantry, and jib cranes. Numerous work station and industrial

More information

COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100

COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100 COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100 Part 1 General 1.01 Work Included A. The work under this section shall include the furnishing of all items shown on the drawings and as specified,

More information

SECTION COPPER/ SOLDERED RF SYSTEM SPECIFICATIONS

SECTION COPPER/ SOLDERED RF SYSTEM SPECIFICATIONS SECTION 13096 COPPER/ SOLDERED RF SYSTEM SPECIFICATIONS Prepared by: NELCO 125 Chenoweth Lane, Ste. 206 Louisville, KY 40207 (502) 899-3726 13096-1 SECTION 13096 COPPER RADIO FREQUENCY SHIELDING ENCLOSURE

More information

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and

More information

Bus Facility

Bus Facility SECTION 32 31 13.53 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

AMBICO Limited Section BLAST RESISTANT STEEL OVERHEAD DOORS Page 1

AMBICO Limited Section BLAST RESISTANT STEEL OVERHEAD DOORS Page 1 Page 1 This section includes AMBICO steel blast resistant overhead door assemblies, with integral electric operators. This section includes proprietary, descriptive and performance type specification requirements.

More information

A. The work consists of furnishing a Chiller Noise Reduction System as listed in the specifications.

A. The work consists of furnishing a Chiller Noise Reduction System as listed in the specifications. SECTION 32 31 14 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 102239 - FOLDING PANEL PARTITIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SPRAY BOOTH REQUIREMENTS

SPRAY BOOTH REQUIREMENTS SPRAY BOOTH REQUIREMENTS Submittal Requirements: 4 sets of plans 2 sets of calculations 2 sets of manufacture specifications and/or cut sheets Plans shall be a minimum size of 11x17 Calculations shall

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION Section 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Invitation

More information

SPRAY BOOTH REQUIREMENTS

SPRAY BOOTH REQUIREMENTS SPRAY BOOTH REQUIREMENTS Submittal Requirements: 4 sets of plans 2 sets of calculations 2 sets of manufacture specifications and/or cut sheets Plans shall be a minimum size of 11x17 Calculations shall

More information

1.02 Related Sections A. Section Heating, Ventilation and Air Conditioning (HVAC). C. Section Pneumatic and Electric Control HVAC.

1.02 Related Sections A. Section Heating, Ventilation and Air Conditioning (HVAC). C. Section Pneumatic and Electric Control HVAC. PART 1: GENERAL 1.01 Section Includes A. Dual duct terminal units. B. Variable volume regulators. C. Integral damper motor operators. D. Integral controls. 1.02 Related Sections A. Section 23 00 00 Heating,

More information

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Pan System

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Pan System SECTION 13096 RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Pan System Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13096-1 RF MODULAR PAN SYSTEM PART 1 GENERAL 1.1

More information

Capital Projects Group Gas Fired Warm Air Furnace Specification

Capital Projects Group Gas Fired Warm Air Furnace Specification Capital Projects Group Gas Fired Warm Air Furnace Specification Specification 23 54 16 Revision 1 Date: September 2018 Gas Fired Warm Air Furnace Specification Specification 23 54 16 Publication Date:

More information

A. Hazardous Areas: Hazardous areas as defined by the NEC as Class I, Division 1, Group D, or Class I, Division 2, Group D hazardous are as follows:

A. Hazardous Areas: Hazardous areas as defined by the NEC as Class I, Division 1, Group D, or Class I, Division 2, Group D hazardous are as follows: SECTION 16050 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: General requirements for providing basic electrical materials and methods. B. Related Work Specified in Other Sections Includes: 1. Certain

More information