1 ADDENDUM NO. 1 Date: October 8, 2009 This addendum forms a part of the above-referenced Request for Proposal and modifies the original RFP documents issued September 17, Proposers shall acknowledge receipt of this Addendum in their RFP Cover Letter as indicated in Section IV, Proposal Instructions. Failure to do so may subject the Proposal to be disqualified. This Addendum consists of: PART 1 QUESTIONS AND ANSWERS The following are responses to all submitted questions. Q1. Please provide additional data on the new Co-Gen Plant at California State University Fullerton. A1. The Trigen Co-Generation Plant is scheduled to come on line around April/May The only potential capacity change is if a third cooling tower cell of equivalent size to the existing cells is added. Each existing cooling tower cell is approximately 7200 gpm and a sump of approximately 60,000 gallons. Two (2) absorption chillers of 1200 tons each will be added. Q2. Section 8.1 Cooling Tower Water Treatment The inhibitor specification is indicative of an alkaline (no ph control) type water treatment program. No specific corrosion inhibitor for mild steel is listed. However, the cycles of concentration (four cycles), the type of microbiocide (sodium hypochlorite), and references to acid, indicate that the intention of the specification is a ph controlled (acid feed) type program. What type of program is requested in specification (ph control or alkaline with no ph control)? If the program is (ph controlled) will the product specification be upgraded? Biocide 1 would be ineffective for alkaline type program. Biocide 2 (Glutaraldehyde) at use levels and given the system volume of 160,000 gallons would be very expensive to implement. Page 1 of 5
2 A2. The specification calls for a PBTC based corrosion inhibitor. Yes, you will still use acid. Hypo will work below a ph of 8.3 and you have been running at around 8.0. It works better as the ph drops. Glutaraldehyde is not cheap, we agree. Q3. Can other choices of an oxidizing biocide and non-oxidizing biocide 2 be proposed? A3. Proposers can propose as many alternate programs as they would like. They do need to bid the specification first. Q4. Section 8.2 Chilled TES Loop. The chilled (TES) water system is designed to be also an emergency source of water in an event of fire. This dual function of the chilled water system requires use of only non-hazardous chemical. Molybdate is required in the specification, however, molybdate is also a listed hazardous chemical in the State of California. Will molybdate be removed from the specification or should we propose chemicals that contain molybdate as an active ingredient? A4. If your chill water is also fire water, the treatment will need to be changed. Q5. Section 8.3 Boiler Water Treatment. Polymer minimum level of 100 ppm. Why polymer level required is 100 ppm? This level of polymer may cause severe foaming in the boiler water. Typically only ppm active polymer residuals are used. If this is a typo, will it be corrected? A PPM polymer in a boiler using a polymer program is a standard regime. Phosphate programs would be 50 PPM polymer. Q6. Section 5.1 Testing Program Requirements: This section calls out a Science Lab Center. Was that on the walk through? What are the specific equipment and systems requiring treatment for this location? A6. The Science Lab Center was discussed on the Job Walk. There are two (2) 9.5 hp boilers in the basement. Page 2 of 5
3 Q7. Section 8.1 Cooling Towers Water Treatment specifies that the cooling water inhibitor to contain molybdenum. Will a more environmentally friendly and lower cost substitute be allowed that provides the same control and monitoring benefits as molybdenum? This technology is proven used by more than 10,000 customers in the US and Worldwide. A7. Yes Q8. Section 8.2 Chilled TES Loop Systems Treatment specifies two different treatment approaches, HEDP and HPA. Would you accept an alternate technology (PSO) that has been proven in large TES systems to provide the same or improved corrosion protection as HEDP and or HPA? A8. Propose the specification and PSO as an alternate. Q b - Can you provide a list of the various sections required in the proposal? Would it be possible to provide the sections/descriptions as they should be listed on the Table of Contents? The order that they should be listed would be helpful. Where should the Program Notebook be located? Where should any proof statements, pictures be located? Do they have to be listed in the Table of Contents and in what format? ie as exhibits? A9. Per the instructions provided in Section IV, item 4.6 Proposal Format to include: a. Cover Letter (noting addenda received), b. Table of Contents, c. Exceptions, d. Worksheet Schedule of Values & Summary pages, e. Cost Proposal Sheet, f. Program Notebook. In addition you will also need to include: Exhibit C - Small Business Preference and Certification Request (if applicable), Exhibit D Disabled Veteran Business Enterprise (DVBE) Requirements (Mandatory), Exhibit E - Program Notebook Requirements Checklist/Questionnaire, Exhibit F - Client/System Reference List, Exhibit G - Reference Forms. Each of these sections should be indexed and tabbed. Index tabs with the appropriate title, are required. Proof statements and pictures are not required, but can be included as appendices. Emphasis should be on the completeness and clarity of content. Responses should emphasize the proposers capability to perform work of this type. Page 3 of 5
4 Q a - What are the hours of operation on the tower ie how many hours per day and how many days per year? A hours per day in the summer, 9 hours per day in the winter, approximately 270 to 300 days per year. Q a - What are the hours of operation of each boiler? Do some operate at different times than others? We are looking for hours per day and days per year. What percent of condensate is returned? What is the operating pressure of the boiler? Is there steam pressure reducing on the boiler? What is the distance of the steam lines? Can you verify the hardness of the make up to the boilers measured in ppm? We need this for both soft water and feed water. A hours per day, 365 days per year. No. Do not have an exact number. It is very little, only what comes from the strainers. 70 psi. Yes, DBH is down stream of boilers, MH is at the boilers. DBH is approximately 300 ft. MH is approximately 500 ft. In January 2009 monitoring data, the calcium hardness levels were reported at 0.3 PPM for soft water and 0.24 PPM for the boiler feed water. Q What percent of active azole and PBTC is expected in the Cooling Tower products? A12. The CSUF specifications ask that you maintain a minimum of 1.0 PPM free and available azole in the Cooling Tower system for copper corrosion protection and a minimum of 3.0 PPM phosphonate at all times. Page 4 of 5
5 Q What percent of active HEDP, azole and HPA is expected in the Chilled systems treatment? A13. The CSUF existing minimum range for HEDP is 30 PPM. Recommended HPA is at a minimum of 12 PPM. Chilled water system should have a free and available azole level at a minimum of 5 PPM. Q14. Should we fill out/sign the agreement and include with the proposal? A14. No. The agreement form is provided as a sample to Proposers. If the RFP is awarded, the winning firm will be required to enter into a binding agreement with California State University, Fullerton for the specified Water Treatment services described in the Request for Proposal. All other terms and conditions of the original RFP documents remain the same. - END OF ADDENDUM #1 - Page 5 of 5
Addendum #4. Addendum No. 4
Addendum #4 Purchasing Services 4202 East Fowler Avenue, SVC 1073 Tampa, Florida 33620 (813) 974-2481 Web Address: http://www.usf.edu/business-finance/purchasing/public-bids/index.aspx October 27, 2017
More informationEXHIBIT A UNIVERSITY OF NEVADA - LAS VEGAS WATER TREATMENT BEST PRACTICES
UNIVERSITY OF NEVADA - LAS VEGAS WATER TREATMENT BEST PRACTICES This document is designed to guide the UNIVERSITY OF NEVADA - LAS VEGAS HVAC systems through the difficult task of managing the water treatment
More informationTITLE: WATER TREATMENT PROGRAM FOR CHILLED WATER PLANTS THIS ADDENDUM IS FOR THE PURPOSE OF MAKING THE FOLLOWING CHANGES OR CLARIFICATIONS IN RED:
Procurement Department Bid Section Customer Center 1 st Floor, Room 002 21 W. Church Street Jacksonville, Florida 32202 May 17, 20 ADDENDUM NUMBER: ONE (1) TITLE: WATER TREATMENT PROGRAM FOR CHILLED WATER
More informationMetropolitan Washington Airports Authority PROCUREMENT AND CONTRACTS DEPT. AMENDMENT OF SOLICITATION
PROCUREMENT AND CONTRACTS DEPT. AMENDMENT OF SOLICITATION Metropolitan Washington Airports Authority Procurement and Contracts Dept., MA-29 2733 Crystal Drive Arlington, VA 22202 1A. AMENDMENT OF SOLICITATION
More informationPRODUCT PROGRAMMING GUIDELINES CHEMICAL GUIDELINES
CHEMICAL GUIDELINES INDEX : BOILER treatment program - Oxygen scavengers - Multi purpose - Deposit controllers - Return line treatment - ph controller /phosphate COOLING treatment program - Scale inhibition
More informationBRINGING WATER TREATMENT IN HOUSE - MONITORING AND CONTROL STRATEGIES AND IMPROVED RESULTS AT NRG PHOENIX
BRINGING WATER TREATMENT IN HOUSE - MONITORING AND CONTROL STRATEGIES AND IMPROVED RESULTS AT NRG PHOENIX MICHAEL FEHR, PH.D. FEHR SOLUTIONS, LLC AGENDA A VERY BRIEF HISTORY OF COOLING WATER TREATMENT
More informationCooling Tower Water Management Plan. 901 Fifth Avenue
2013 Cooling Tower Water Management Plan 901 Fifth Avenue Table of Contents I. INTRODUCTION II. GOAL III. SCOPE IV. RESPONSIBILITIES V. TIME PERIOD VI. PERFORMANCE METRIC VII. PROCEDURES AND STRATEGIES
More informationADDENDUM 2 TO REQUEST FOR PROPOSAL 673-FG UNLV FULL SERVICE WATER TREATMENT
ADDENDUM 2 TO REQUEST FOR PROPOSAL 673-FG UNLV FULL SERVICE WATER TREATMENT University of Nevada, Las Vegas Purchasing Department 4505 Maryland Parkway Las Vegas, Nevada 89154-1033 (702) 895-3521 Date
More informationCOOLING TOWER WATER TREATMENT
COOLING TOWER WATER TREATMENT 1 2 3 1 2 3 OXIDIZING NON-OXIDIZING Solid BCDMH used to control problems in the system caused by microorganisms. Solid DBNPA used to control problems in the system caused
More informationSulfuric Acid Plant Cooling Tower Improvements
Technical Paper Sulfuric Acid Plant Cooling Tower Improvements Ryan Barbour, Herb Quinones and Tom Refi GE Water & Process Technologies 4636 Somerton Road Trevose, PA 19053 Find a contact near you by visiting
More informationZero Blowdown Technology - ZBT Arizona Transportation Center
Zero Blowdown Technology - ZBT Arizona Transportation Center A major transportation center in Arizona was designed to be certified by the USGBC LEED green building program to its highest level, Platinum.
More informationHigher COC and ph Independent Operation of Cooling Water Systems
Higher COC and ph Independent Operation of Cooling Water Systems CONFER-NERTA 2016 S. M. Mahadik President Technical Vasu Chemicals 31/3/2015 Conventional Coal based Power Plants: Flue Gases Steam Turbine
More informationA. Submit manufacturer s data, qualifying documents, and shop drawings on the proposed water treatment system before starting any work.
15545 WATER TREATMENT ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 232516 An optional keynote to
More informationHVAC WATER TREATMENT 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. D. Section Plumbing (Potable) Water Treatment
232500 HVAC WATER TREATMENT PART 1 GENERAL 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS A. Section 230510 Chilled Water Systems B. Section 230520 Heat Generation C. Section 230530 Clean Steam
More informationReal World Experiences with a Plant- Based Alternative to Chemical Treatment in Cooling Water Systems
Real World Experiences with a Plant- Based Alternative to Chemical Treatment in Cooling Water Systems Steve Chewning, CWT, Southeastern Laboratories, Inc. September 2018 Companies adopting sustainable
More informationWater Conservation Technology for Recirculating Cooling Systems
Water Conservation Technology for Recirculating Cooling Systems Karen Golmer New England Water Innovation Network John Rowen Capture H2O, Inc. April 28, 2015, University of Connecticut, Hartford CT Game
More informationOptimizing Steam and Cooling Systems for Reliability and Sustainability. Presented By: Kevin Emery
Optimizing Steam and Cooling Systems for Reliability and Sustainability Presented By: Kevin Emery Kevine@chemtreat.com 804-317-2381 Optimizing Steam and Cooling Systems for Reliability and Sustainability
More informationCOC = ,000/ (CaH x TA) This discovery is the basis of our unique, patented HighCycle water management products.
Background HighCycle tm - Advanced Technology For Cooling Tower Blowdown Reduction A Safe, Simple, Economic, and Environmentally Responsible Technology for Reduction of Water Usage in Cooling Towers Drought
More informationBoiler/Cooling Water Processes and Parameters
Boiler/Cooling Water Processes and Parameters Outline Feedwater Internal Boiler Water Condensate Blowdown Cooling Water Process Water Feedwater Objectives of boiler feedwater treatment: Prevent introduction
More informationWastewater Characterization. Tenaska Westmoreland Generating Station
Wastewater Characterization Tenaska Westmoreland Generating Station Issued December 20, 2011 Rev 0 Revised October 23, 2012 Rev 1 Revised November 8, 2012 Rev 2 Prepared by GEWPT: R. Henry Weed, P.E. 1
More informationZero Discharge Treatment Method for Cooling Towers and Heat Exchangers with SP3, I-SOFT-OB, OXYDES & KATALOX LIGHT
Zero Discharge Treatment Method for Cooling Towers and Heat Exchangers with SP3, I-SOFT-OB, OXYDES & KATALOX LIGHT By Deepak Chopra Watch Water GmbH Fahrlachstraße 14 68165 Mannheim Germany May 2013 Web:
More informationIWC ZLD: New Silica Based Inhibitor Chemistry Permits Cost Effective Water Conservation for HVAC and Industrial Cooling Towers
IWC 07-11 ZLD: New Silica Based Inhibitor Chemistry Permits Cost Effective Water Conservation for HVAC and Industrial Cooling Towers Report by Dan Duke Water Conservation Technology International water-cti.com
More informationCooling Tower Treatment Chemicals
Cooling Tower Treatment 1) Scale & Corrosion Inhibitors 1. Cooling Tower Treatment Code Product Name 2048 Combined Scale Control / Anti-Foulant-cooling Systems 2202 Scale & Corrosion Inhibitor (Hard Water)
More informationOPTIDOSE 4210 Traceable Polymeric Acid Scale Inhibitor and Dispersant
Technical Data Sheet OPTIDOSE 4210 Traceable Polymeric Acid Scale Inhibitor and Dispersant Regional Product Availability Description Benefits North America OPTIDOSE 4210 traceable polymaleic acid polymer
More informationOFFICE OF PROCUREMENT COOLING TOWER REPLACEMENT, CT BUILDING RFP NO.: RFP OPENING DATE: APRIL 16, 3:00 PM ADDENDUM #4.
OFFICE OF PROCUREMENT COOLING TOWER REPLACEMENT, RFP NO.: 618-009 RFP OPENING DATE: APRIL 16, 2018 @ 3:00 PM ADDENDUM #4 April 9, 2018 THIS ADDENDUM IS TO PROVIDE ANSWERS TO THE FOLLOWING QUESTIONS: NOTE:
More informationElectro-Chemical UET Water Treatment System Achieves Sustainability Objectives for Scottsdale Fashion Square Mall.
Electro-Chemical UET Water Treatment System Achieves Sustainability Objectives for Scottsdale Fashion Square Mall. By George Chac, Melvin Mathew and Terry Waldo May, 28 Owned by Macerich (NYSE:MAC), Scottsdale
More informationhigh cycles cooling tower operation using a revolutionary alkaline treatment program Continuum* AEC (Alkyl Epoxy Carboxylate)
Water Technologies & Solutions technical paper high cycles cooling tower operation using a revolutionary alkaline treatment program Continuum* AEC (Alkyl Epoxy Carboxylate) Authors: Joseph Janeczko (SUEZ),
More informationB. System Design and Performance Requirements
15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes
More informationADVERTISEMENT FOR BIDS
ADVERTISEMENT FOR BIDS THE City of Craig, Colorado will receive sealed bids for CHEMICALS until 2:00 p.m., January 19, 2016, at the office of the City Clerk, 300 West Fourth Street, Craig, Colorado 81625,
More informationPRESENTED BY: BRAD SWEARINGEN JIM NONNENMANN, PE
IDEA CAMPUS ENERGY 2016 : THE CHANGING LANDSCAPE PRVN CONSULTANTS, INC. PRESENTED BY: BRAD SWEARINGEN JIM NONNENMANN, PE AGENDA Research Campus Utilities Overview Chilled Water Need and Project Goals Project
More informationIntegrating Standby Power and Steam Turbine Chillers for Better Resiliency at UNC Chapel Hill
Integrating Standby Power and Steam Turbine Chillers for Better Resiliency at UNC Chapel Hill IDEA 28 th Annual Campus Energy Conference Denver, Colorado Philip Barner, P.E. Director of Energy Services
More informationSection A: CUSTOMER INFORMATION. Customer Name Electric Account Number Rate Application Number. Facility Address City State Zip Code
New Equipment & Construction 2017 VFD Incentive Section A: CUSTOMER INFORMATION Customer Name Electric Account Number Rate Number Facility Address City State Zip Code Service Location Identification Email
More informationRICHMOND PUBLIC SCHOOLS DIVISION OF PURCHASES 2395 Hermitage Road, Vatex Building RICHMOND, VIRGINIA May 24, 2016 ADDENDUM NO.
RICHMOND PUBLIC SCHOOLS DIVISION OF PURCHASES 2395 Hermitage Road, Vatex Building RICHMOND, VIRGINIA 23220-1307 May 24, 2016 ADDENDUM NO. 1 Invitation No.: BID#16-6721-5 Dated: May 13, 2016 Opening Date:
More informationBIOBAN CWT Brand of 25% Aqueous TRIS(HYDROXYMETHYL)NITROMETHANE Cooling Water Treatment Microbicide EPA Reg. No
Product Information Brand of 25% Aqueous TRIS(HYDROXYMETHYL)NITROMETHANE Cooling Water Treatment Microbicide EPA Reg. No. 464-668 1 General BIOBAN CWT has been utilized successfully to control the growth
More informationPRODUCT SUMMARY. Water Treatment Chemicals. Aug 2016
PRODUCT SUMMARY Water Treatment Chemicals 1 Aug 2016 Man Chemical is a regional specialty chemical company that produces a broad range of advanced materials, additives and functional products, specialty
More informationIndustrial Waste Heat Recovery
Industrial Waste Heat Recovery Industrial Energy RoundTable Kathey Ferland Project Manager Texas Industries of the Future kferland@mail.utexas.edu Riyaz Papar, PE, CEM Director, Energy Assets & Optimization
More informationNACE CORROSION 2008 TEG 096X Symposia - Paper 1421
NACE CORROSION 2008 TEG 096X Symposia - Paper 1421 Electrochemical Studies with Coupled Multielectrode Array Sensors on Corrosion Inhibition of Copper and Affected Metals in the Presence of Ammonia and
More information9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax:
9707 Key West Avenue, Suite 100 Rockville, MD 20850 Phone: 301-740-1421 Fax: 301-990-9771 E-Mail: awt@awt.org Part of the recertification process is to obtain Continuing Education Units (CEUs). One way
More informationCOUNTY OF FRESNO ADDENDUM NUMBER: FOUR (4) RFP NUMBER: HVAC CHEMICAL TREATMENT SERVICES. July 23, 2014
COUNTY OF FRESNO ADDENDUM NUMBER: FOUR (4) RFP NUMBER: 910-5268 HVAC CHEMICAL TREATMENT SERVICES PURCHASING USE ssj IMPORTANT: SUBMIT PROPOSAL IN SEALED PACKAGE WITH PROPOSAL NUMBER, CLOSING DATE AND BUYER
More informationChilled Ammonia Process Update. Richard Rhudy, EPRI Sean Black, ALSTOM CO 2 Capture Network May 24, 2007 Lyon, France
Chilled Ammonia Process Update Richard Rhudy, EPRI Sean Black, ALSTOM CO 2 Capture Network May 24, 2007 Lyon, France Schematic of the Chilled Ammonia Process Exisiting FGD Existing Stack CO2 Flue Gas Wash
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-23 25 00 (November 2008) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 25 00 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS References
More informationIn Depth Feasibility Studies Aquifer Thermal Energy Storage (ATES) VAMC Chillicothe and Columbus, OH
In Depth Feasibility Studies Aquifer Thermal Energy Storage (ATES) VAMC Chillicothe and Columbus, OH 20 February 2014 Presented to by Mark A. Worthington, Underground Energy, LLC Project Team Outline Purposes
More informationAn Introduction to Water Sampling and Testing of Water Systems
An Introduction to Water Sampling and Testing of Water Systems J. Paul Guyer, P.E., R.A. Paul Guyer is a registered civil engineer, mechanical engineer, fire protection engineer and architect with 35 years
More informationPOTENTIAL ENERGY AND COST SAVINGS THROUGH PROPER TREATMENT OF HEATING AND COOLING SYSTEMS
POTENTIAL ENERGY AND COST SAVINGS THROUGH PROPER TREATMENT OF HEATING AND COOLING SYSTEMS A Webinar for Facility Managers and Operators at Institutional and Industrial Facilities October 16, 2018 Jeremy
More informationThe owner is Oral Roberts University, while management and leasing is handled by Trinity Corporate Real Estate Advisors, LLC.
CityPlex Towers is Oklahoma s largest mixed use office and medical complex comprising of approximately 2.2 million square feet. The structure is reinforced, poured in place concrete, built in 1980. The
More informationADDENDUM NO. 2 REQUEST FOR PROPOSAL NO. R DESIGN SERVICES FOR RENOVATIONS TO KREILING HALL
December 1, 2015 ADDENDUM NO. 2 Attention to Proposers: This constitutes Addendum No. 2 to the referenced Request for Proposals (RFP), and consists of this six (6) page cover letter, and a two (2) page
More informationSECTION HVAC WATER TREATMENT
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 25 00 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between //-----// if not applicable to project. Also delete any other item or paragraph
More informationESCO Industry Perspective
Opportunities Presented by the Utility Grid ESCO Industry Perspective Kevin Johnson Energy Systems Group August 10, 2016 Rhode Island Convention Center Providence, Rhode Island Agenda ESG Nation wide Utility
More information9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax:
9707 Key West Avenue, Suite 100 Rockville, MD 20850 Phone: 301-740-1421 Fax: 301-990-9771 E-Mail: awt@awt.org Part of the recertification process is to obtain Continuing Education Units (CEUs). One way
More informationOPERATIONAL UPDATE ON INNOVATIVE COOLING TOWER PRETREATMENT TECHNOLOGY
OPERATIONAL UPDATE ON INNOVATIVE COOLING TOWER PRETREATMENT TECHNOLOGY Presented By: Joel E. Bowdan III, P.E. PRESENTATION OUTLINE: Subject Introduction Amylin Project Background Cooling Tower Basics Typical
More informationVariable Frequency Drive Retrofit Opportunities. Michael Kuk CERx Solutions LLC
Variable Frequency Drive Retrofit Opportunities Michael Kuk CERx Solutions LLC Speaker Introduction» Founder / owner of CERx Solutions LLC» Veteran Owned Small Business Enterprise founded in 2013» 27+
More informationCase Study 3M Corporate Headquarters 2014 Distributed by:
Industrial Water Division Case Study 3M Corporate Headquarters 2014 Distributed by: Introduction Creative Water Solutions LLC and 3M conducted a 2 year trial of treatment at their corporate campus cooling
More informationPermanent Load Shifting Program
1. Program Description Permanent Load Shifting (PLS) can help reduce system peak load by storing energy produced during off-peak period and shifting electricity use from on-peak to off-peak periods on
More informationSPECIALIZED WATER TREATMENT
SPECIALIZED WATER TREATMENT One Resource for Water Treatment Technology The AQUATROL Division of MOMAR, Incorporated, formulates and manufactures a variety of technologically advanced products that effectively
More informationRequired Treatment of District Thermal Energy in LEED-NC version 2.2 and LEED for Schools
1 Required Treatment of District Thermal Energy in LEED-NC version 2.2 and LEED for Schools Version 1.0 May 28, 2008 Administrative All LEED-NC v2.2 or LEED for Schools projects that register with USGBC
More informationWhite Paper. A Reliable Alternative to Chemicals for Cooling Water Treatment. GWS-1107-D 10/31/11 Copyright 2011 All Rights Reserved
White Paper A Reliable Alternative to Chemicals for Cooling Water Treatment GWS-1107-D 10/31/11 Copyright 2011 All Rights Reserved Use Water for Efficient Cooling There are many problems associated with
More informationCleaning Techniques for Cooling Systems and Boilers
Cleaning Techniques for Cooling Systems and Boilers Cleaning Applications in Industrial Utility Systems Pre Operational Cleaning and Passivation Removal of Organic Buildup caused by leaks or biofilms Exchanger
More informationChilled Water Energy Savings Study
1 Chilled Water Energy Savings Study Pressure Dependent Valve Sizing and Valve Authority Pressure Independent Valves (Mechanical and Electronic) Chilled Water System Design MIT Beta Site Study-Correcting
More informationRFB Waco City Hall Chiller Replacement. Date: 3/20/2018 RFP No: Commodity: Waco City Hall Chiller Replacement
CITY OF WACO RFB 18-022 Waco City Hall Chiller Replacement Purchasing Services Post Office Box 20 Waco, Texas 602-20 Phone: 2 / 0-80 Fax: 2 / 0-8063 kaseyg@wacotx.gov www.waco-texas.com Date: 3//18 RFP
More informationCOUNTY OF ROCKLAND Department of General Services Purchasing Division
COUNTY OF ROCKLAND Department of General Services Purchasing Division Title: Contract Period: Water Treatment Services 9/9/13 through 9/8/14 with two additional one-year options, Extend thro ugh 9/8/15
More informationGreen FSRU for the future
Green FSRU for the future Presentation at GREEN4SEA Athens April 6 th 2016 Dr. John Kokarakis Vice President Technology & Business Development, Africa, S. Europe Hellenic, Black Sea & Middle East Zone
More informationCoach House: Hunziker Hall:
Number: Morristown, NJ From: Sergiu Pelau Sheet: 1 of 5 Date of Visit: 12/7/11 Coach House: 1. Central plant located in Hunziker Wing connecting piping is leaking a. Gas fired plant 10 year old b. Two
More informationCooling Tower Water Management
Cooling Tower Water Management Cooling tower water systems are subject to corrosion, scaling, deposition, and biological fouling; which increase operating costs due to downtime and equipment replacement,
More informationADDENDUM NO. 01. Include this signed and dated addendum to your proposal.
ADDENDUM NO. 01 To City of College Park RFP FIN 012716 - LEASE ADVERTISEMENT for LEASE for TAX-EXEMPT FINANCING Please note the following additions/changes to this bid. Include this signed and dated addendum
More informationCooling Tower Water Savings Stakeholder Meeting #1 - DRAFT California Statewide Utility Codes and Standards Program
1 Cooling Tower Water Savings Stakeholder Meeting #1 - DRAFT California Statewide Utility Codes and Standards Program Energy Solutions August 25, 2010 Cooling Tower Water Savings Agenda CALIFORNIA STATEWIDE
More informationAddendum 3 publishes and answers questions related to the Request for Qualifications ( RFQ ) issued on November 24, 2014:
www.dot.state.pa.us Date: December 18, 2014 Subject: Questions and Answers Regarding RFQ Solicitation: CNG Fueling for Transit Agencies Partnership Project SOQ Due Date: No later than 11:00 a.m. Eastern
More informationUndesirable impurities in boilers. Maximum permissible Cycles of concentration (NC)
Maximum permissible Cycles of concentration (NC) From the relationship BD/S = [L/S] / [NC - 1] calculated at material balance in boiler section, as long as L/S is related to system parameters and it is
More informationPuckorius & Associates, Inc.
REPORT TO CDG ENVIRONMENTAL, LLC. 205 WEBSTER STREET BETHLEHEM, PA 18015 Volume 1 of 1 SUBJECT: EFFICACY OF A 0.3% CHLORINE DIOXIDE SOLUTION (PRODUCT KNOWN AS CDG SOLUTION 3000) FOR ALGAE CONTROL IN AN
More informationNACE Paper No
NACE Paper No. 07626 Laboratory and Field Studies of Localized and General Corrosion Inhibiting Behaviors of Silica in Zero Liquid Discharge (High TDS Cooling Water) Using Real Time Corrosion Monitoring
More informationConstruction Engineering. Research Laboratory. Green Chemical Treatments for Heating and Cooling Systems ERDC/CERL TR-06-29
ERDC/CERL TR-06-29 Green Chemical Treatments for Heating and Cooling Systems Susan A. Drozdz and Vincent F. Hock September 2006 Construction Engineering Research Laboratory Approved for public release;
More informationOperation and Maintenance of Electrochlorination Plant
Operation and Maintenance of Electrochlorination Plant Introduction Sodium Hypochlorite is a powerful biocide and oxidizing agent that has been widely used in seawater cooling system to avoid the biofouling
More informationGreen Technologies to Minimize Cooling Tower Water Use
Green Technologies to Minimize Cooling Tower Water Use TAB0411 The environmental footprint of many facilities includes cooling towers, which consume large amounts of water, produce blowdown wastewater,
More informationLABARD AQUASOLVE INDIVIDUAL/ COMPACT TEST KIT
LABARD AQUASOLVE INDIVIDUAL/ COMPACT TEST KIT Labard Aquasolve presents India's first compact water testing kits. Aquasolve has completely eliminated the powder reagents from these kits which enhances
More informationEvaporative Condenser Passivation. Cameron Klein Strand Associates, Inc.
Evaporative Condenser Passivation Cameron Klein Strand Associates, Inc. Evaporative Condenser Wetted Surface Materials of Construction Galvanized Steel Protective zinc coating fused to a steel substrate
More informationBoiler Water Treatment
Boiler Water Treatment Preventive Solutions and Complete Treatment Programs Corrosion, scaling and deposition can reduce the operating efficiency of the boiler and all the systems connected to the water/steam
More informationProject Proposal Proposal for Investigation of Alternative Systems
Project Proposal Proposal for Investigation of Alternative Systems 01.15.2010 Defense Media Activity Building Fort George G. Meade Penn State University Architectural Engineering Faculty Advisor: Dr. Treado
More informationWaste Heat Management Options Industrial Process Heating Systems. Dr. Arvind C. Thekdi E3M, Inc.
Waste Heat Management Options Industrial Process Heating Systems By Dr. Arvind C. Thekdi E-mail: athekdi@e3minc.com E3M, Inc. August 20, 2009 Source of Waste Heat in Industries Waste heat is everywhere!
More informationCity of Frederick PURCHASING DEPT.
ADDENDUM #4 RFP #12-D CITY OF FREDERICK WWTP ENR UPGRADE March 12, 2012 TO: SUBJECT: REF: All Potential Proposers RFP #12-D, CITY OF FREDERICK WWTP ENR UPGRADE Revised Proposal Closing Date, Submitted
More information2018 Commercial Rebate Program
Black Hills Energy offers Colorado Commercial and Industrial electric customer rebates for some of the most commonly installed efficiency projects. Follow the checklist below to determine if you are eligible
More informationSPECIFICATIONS FOR TENDER # Repair/Modification to Two (2) Trane Cooling Towers Model BAC VLT550A S/N /5C A
SPECIFICATIONS FOR TENDER # 0171-1805 Repair/Modification to Two (2) Trane Cooling Towers Model BAC VLT550A S/N 72-3034/5C A CLOSING DATE: February 6 th, 2018 CLOSING TIME: 2:00 PM (Newfoundland Time)
More informationREQUEST FOR PROPOSALS FOR AN INTEGRATED PROJECT DELIVERY METHOD UTILIZING CONSTRUCTION MANAGEMENT/GENERAL CONTRACTING (CM/GC) SERVICES
STATE OF COLORADO OFFICE OF THE STATE ARCHITECT STATE BUILDINGS PROGRAM REQUEST FOR PROPOSALS FOR AN INTEGRATED PROJECT DELIVERY METHOD UTILIZING CONSTRUCTION MANAGEMENT/GENERAL CONTRACTING (CM/GC) SERVICES
More informationD E T E C T D E T E R M I N E D E L I V E R A NEW DIMENSION OF PERFORMANCE FOR PEOPLE, PLANET, PROFITS
D E T E C T D E T E R M I N E D E L I V E R A NEW DIMENSION OF PERFORMANCE FOR PEOPLE, PLANET, PROFITS 3D TRASAR TECHNOLOGY DETECTS CHANGING PROCESS PARAMETERS, DETERMINES CORRECT ACTIONS AND DELIVERS
More informationREQUEST FOR PROPOSALS DESAL ANTISCALANT/CLEAN-IN-PLACE CHEMICALS BID NO: ADDENDUM 1
REQUEST FOR PROPOSALS DESAL ANTISCALANT/CLEAN-IN-PLACE CHEMICALS BID NO: 18-18006 ADDENDUM 1 BIDS DUE: April 30, 2018 @ 3:00 PM Central Time To report suspected ethics violations impacting the San Antonio
More informationAN INTRODUCTION HARFST AND ASSOCIATES, INC.
Harfst and Associates, Inc. Water Management Consultants William F. Harfst AN INTRODUCTION TO HARFST AND ASSOCIATES, INC. William F. Harfst Consultant HARFST AND ASSOCIATES, INC. P.O. Box 276 Crystal Lake,
More informationOPTIDOSE 1000 Traceable Polymer A Tool for Maintaining Maximum Heat Transfer
OPTIDOSE 1000 Traceable Polymer A Tool for Maintaining Maximum Heat Transfer Description OPTIDOSE traceable polymer technology is a revolutionary method of tracking polymer levels in cooling water, boiler
More informationPURCHASING DEPARTMENT. Project # Addendum # # of pages Original Issue Date Request Doc # August 28, see text below
PURCHASING DEPARTMENT The bid listed below has had addenda issued. Documents are available over the Internet at http://www.norwalkct.org Adobe Acrobat reader is required to view this document. If you do
More informationFLORIDA DEPARTMENT OF TRANSPORTATION
FLORIDA DEPARTMENT OF TRANSPORTATION ADDENDUM NO. 2 DATE: December 28, 2011 RE: RFP NUMBER: RFP TITLE: ITS Equipment Replacement in Broward County OPENING OF TECHNICAL PROPOSAL DATE: January 5, 2012 Notice
More informationOPTIDOSE Traceable Polymer System OPTIDOSE Test Kits
OPTIDOSE Traceable Polymer System OPTIDOSE Test Kits Ever since polymers have been used as dispersants in cooling water treatment systems, there has been a need for a method of testing the polymer concentration.
More informationZero Liquid Discharge Cooling Tower Treatment at CSI
AIST 2007 Zero Liquid Discharge Cooling Tower Treatment at CSI Dan Duke & John Kubis Water & Enviro Tech Company, Mission Viejo CA Jeff Reed California Steel Industries, Fontana CA This technology is patent*
More informationMechanical Project Proposal
Mechanical Project Proposal Miller Children s Hospital Prepared for: Dr. James Freihaut Department of Architectural Engineering The Pennsylvania State University Prepared by: Stephen Haines December 18
More informationCombustion Turbine Inlet Cooling using Direct Evaporative Cooling
Combustion Turbine Inlet Cooling using Direct Evaporative Cooling By Pat Zeller, Munters Corporation Sponsored by: Turbine Inlet Cooling Association (TICA) August 22, 2012; 1 PM (U.S. Central Time) http://www.meetingzone.com/presenter/default.aspx?partcec=4147918
More informationGLIMPSES OF IMPROPER WATER CHEMISTRY IN A SUBCRITICAL PULVERIZED COAL FIRED BOILER AT A THERMAL POWER PLANT
GLIMPSES OF IMPROPER WATER CHEMISTRY IN A SUBCRITICAL PULVERIZED COAL FIRED BOILER AT A THERMAL POWER PLANT By K.K.Parthiban / Venus Energy Audit System & Sri Devi Boiler Equipment and Spares. Introduction
More information9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax:
9707 Key West Avenue, Suite 100 Rockville, MD 20850 Phone: 301-740-1421 Fax: 301-990-9771 E-Mail: awt@awt.org Part of the recertification process is to obtain Continuing Education Units (CEUs). One way
More information2.2 The Purposes and Advantages of a Central Utility Plant
2.2 The Purposes and Advantages of a Central Utility Plant The purpose of the Central Utility Plant (CUP) at NIST is to provide steam, chilled water, and compressed air for hot and cold water, warm and
More informationR & R IDENTIFICATION CO.
PRESSURE SENSITIVE HV FOR PIPE WITH OUTSIDE DIAMETER OF 6" AND OVER HOT WATER FOR PIPE WITH OUTSIDE DIAMETER OF 2-1/2" TO 6" COLD WATER FOR PIPE WITH OUTSIDE DIAMETER OF 1" TO 2-1/2" DOMESTIC DOMESTIC
More informationNortheast Middle School Cooling Tower Replacement Project
ADDENDUM 2 for Northeast Middle School Cooling Tower Replacement Project TO: FROM: SUBJECT: All Prospective Bidders John Quiocho, Project Manager, Engineered Designs, Inc. Addendum 2 for Northeast Middle
More informationEnvironment & Power Systems International. VOCGEN /CHP Feasibility Screening Data Form. Level 1 Feasibility Analysis
VOCGEN /CHP Feasibility Screening Data Form VOCGEN /CHP Gensets and Systems (VOCGEN /CHP) can provide significant economic benefits to certain users. Whether VOCGEN /CHP can be economically beneficial
More informationCooling Water Treatment
COOL-TREAT Cooling Water Treatment Water Treatment is used to: Optimize most water-based industrial processes Minimize Total Cost Of Operation (TCO) Reduce Risks of operation/production & failures Increase
More informationPREQUALIFICATION OF PROSPECTIVE BIDDERS
Subcontractor* Prequalification for Fullerton College Building 3000 HVAC Equipment Replacement North Orange Coast Community College District, Fullerton California BID #1819-09 PREQUALIFICATION OF PROSPECTIVE
More informationDCP Capacity Upgrade By Adding Thermal Ice Storage. Jelle Wagelmans Sales Manager EVAPCO Middle East DMCC
DCP Capacity Upgrade By Adding Thermal Ice Storage Jelle Wagelmans Sales Manager EVAPCO Middle East DMCC 1 Major Components of a District Cooling Plant 2 Major Components of a DCP Chillers Cooling Capacity
More information