PLAN SUBMITTAL REQUIREMENTS - ARCHITECTURAL
|
|
- Loreen Hampton
- 11 months ago
- Views:
Transcription
1 FIRE DEPARTMENT E Stockton Blvd. Elk Grove, CA (916) Fax (916) PLAN SUBMITTAL REQUIREMENTS - ARCHITECTURAL I Purpose To advise architects, engineers and contractors what minimum information is required for plan review approval. All required information listed below shall be on the plans. II Scope The following requirements shall apply to all new building, and building addition plans submitted to Cosumnes Fire Department. Not all requirements listed apply to every submittal. If questions arise, contact the area inspector to determine what information may not be required. III References 2013 California Building Code (CBC) 2013 California Fire Code (CFC) City of Elk Grove Fire Code Ordinance No County of Sacramento Fire Code Ordinance SCC City of Galt Code Chapter IV General A. All architectural plans are required to be stamped and wet-signed by the architect of record. Mechanical, electrical, structural sheets should also be stamped and wet-signed by the appropriate engineer. Copies of plans will not be accepted. B. Digital submittals shall be provided prior to project final. The digital drawings shall contain the floor plan of each floor and all external referenced ( XREF ) digital drawing support files. ed copies will not be accepted at this time. The submitted digital copy shall be labeled with the project name and address of the project. The submittal shall be submitted and comply with the following required data format: DWG (Applies to AUTOCAD drawing file format) Any AutoCad DWG version is accepted. Addresses for all subdivision lots shall be provided to the Fire Department within sixty (60) days of Fire Department signature of approval for such development plans. C. Plans will not be accepted for review until the plan review fee is paid in full. Fees include the initial review and resubmittals. D. The District s plan review turn around time is approximately 15 business days. E. Plans may be expedited for an additional minimum fee of $ (two hour minimum). Additional hours beyond the initial 2 will be assessed at $187.50/hr.
2 F. A minimum of two complete sets of plans shall be submitted each time plans are submitted or resubmitted. Projects located in the City of Galt require only a single set. G. Fire alarm and fire sprinkler plans may be deferred. H. The following require a separate submittal and additional plan review/inspection fees: 1. Fire sprinklers 2. Fire alarm 3. Perimeter gates and fences 4. Above ground storage tanks for hazardous materials (including fuels) 5. Rack storage (racks with top shelves at 8 feet or higher and exceeding 500 square feet of floor area) 6. High piled storage (greater than 12 feet and exceeding 500 square feet of floor area) 7. Civil Engineering and Improvement Plans 8. Spray booths 9. Commercial kitchen hood extinguishing systems. 10. Special suppression systems (I.E. FM 200 or CO2 systems) 11. Medical gas and vacuum systems. 12. LPG Tanks I. Cosumnes CSD Fire Department is not a Certified Unified Program Agency (CUPA) and therefore does not review the following submittals: 1. Underground storage tanks (unless installed in a concrete vault) Exception: Underground LPG Tanks IV Title Sheet shall include the following information: a. Address of project location b. Name, address, phone number of architect of record c. Location map showing the location of the project site in relation to major streets d. Sheet index e. Building analysis with the following info: 1. Occupancy of building (CBC Ch. 3). If building houses more than one occupancy type, list each occupancy. 2. Occupancy group of all adjacent suites not part of the scope of work. 3. Type of Construction. If project is an addition, note the construction type of the existing and the new building. 4. Square footage of new and existing construction 5. Number of stories - including number of basement stories. See CBC Ch. 2 for definitions of story, story, first, and basement. Plans shall be labeled according to these definitions. 6. Building height. 7. Indicate whether or not the building has the following: a. Fire alarm (indicate automatic or manual or both) b. Fire sprinklers (If any additional fire/life safety features such as standpipes, smoke control, or voice evacuation are provided, indicate so here) 8. If sprinklers are being used to substitute for 1-hr construction or increase the allowable number of stories, indicate so. 9. Scope of Work if the project is phased, indicate the scope of each phase. If the project is an addition or tenant improvement, indicate what construction is new, what existing building sections are to remain, and what existing building sections
3 are to be demolished. Provide sufficient information so that plan reviewer can determine what needs to be reviewed. f. List of applicable codes and the edition. V Site Plan shall include the following information: A. Building footprint, B. North direction arrow, C. Location of adjacent streets, D. Location of adjacent buildings (All adjacent buildings whether or not on the same lot and regardless of size shall be shown), E. If adjacent buildings are close enough to be affected by the assumed property line, show the construction type/rating of the exterior walls and the location/type of protection of exterior openings. F. Location of assumed property line around the entire building. This is required even if adjacent buildings are on the same lot and owned by the same person. G. Dimension lines showing the distance from each building to the assumed property line (NOT face of building to face of building). If side yards are used to increase maximum allowable area, provide dimension lines showing the length of side yards. For purposes of side yards, the entire width of a street may be used. H. Show area increase calculations on the plans. VI Architectural sheets shall provide the following info*: *Some information listed in this section is not necessary for small scale projects. However, when in doubt provide the information on the plans or contact the plan reviewer to confirm what information is required. A. Use of all rooms or areas B. Square footage of each room or area, C. Occupant load factor and analysis of each room (CBC ) D. Exit analysis that includes the following: 1. Occupant load of each room 2. Number of occupants exiting each exit 3. Exit width required for each exit 4. Exit width provided for each exit 5. For corridors and stairwells, provide the number of occupants exiting as well as the required and provided exit width. 6. Path of travel from each exterior exit to a public way. 7. Dimension lines showing maximum travel distance from the furthest occupied location to an exit E. Wall legend differentiate between rated and non-rated walls, new walls, existing to remain walls, and existing to be demolished walls. F. Rated walls shall be identified as rated corridor wall, occupancy separation wall, area separation wall, or horizontal exit wall as applicable. G. Detail/UL design number for all fire rated assemblies including, but not limited to, interior and exterior walls, floor/ceilings, roofs, shafts, head of walls, seismic separations, columns/beams, through penetrations, etc. Every rated wall detail shall have an associated head of wall detail. Wall details shall state whether the wall is full or partial height. (CBC Table (1) and US Gypsum assemblies are acceptable alternatives to UL) H. Where rated walls and non-rated walls intersect or where walls with different ratings intersect, provide a detail indicating how required fire ratings are maintained at each intersection. I. Door schedule that includes:
4 1. Door and frame construction (indicate presence of louvers or undercuts) 2. Door rating (CBC 715) 3. Door hardware type. If this info is in the specifications, please include specifications with submittal. 4. If panic hardware or fire exit hardware is to be installed, clearly state so. 5. Indicate if door is self closing or automatic closing via the fire alarm or an integral smoke detector J. Window schedule showing all locations requiring safety glazing. (CBC 2406) K. Location of Fire Control Room. L. Roof class. (Table ) M. Flame spread class for each area (CBC ) N. Show location of all hazardous materials storage and amounts. O. Notation of code requirement exceptions. Anytime an exception is utilized to eliminate a code requirement, indicate on plans the code section and exception number and state how the exception is being met. VII Mechanical Sheets shall provide the following information: A. Location of all rated walls. B. Location of all ducts, registers, fresh air intakes, fire dampers, and air flows in CFM. C. If door undercuts are utilized for air balance, indicate on plans. D. Clarify if dampers are smoke dampers, fire dampers, or combination smoke/fire dampers. E. Smoke, fire damper installation detail. F. Detail/UL design number for firestopping plumbing penetrations in rated assemblies (CBC 712.). G. CFM of all air handling units supplying air (CMC 609, NFPA 90). H. If automatic shutdown of air handling units is required, indicate whether shutdown is via main supply duct detectors or area detection (see CMC 609). VIII Electrical Sheets shall provide the following information: A. Location of all exit signs and the direction of arrows on the signs (CBC ) B. Location of all emergency illumination lights or lights connected to an emergency generator, including exterior lights requiring emergency illumination (CBC ) C. Detail and UL design number for firestopping all conduit penetrations in rated assemblies (CBC 712.) D. Location of fire alarm control panel. (This is always in the Fire Control Room) IX Plumbing Sheets shall provide the following information: A. Detail and UL design number for firestopping all penetrations in rated assemblies (CBC 712) B. Location of all natural gas pipes. X Landscape Sheets shall provide the following information: A. Location of all trees in relation to fire access lanes (CFC ) B. For trees shown extending over fire access lanes, a note indicating that the tree canopy will be greater than 13 ½ feet high shall be provided (CFC ) XI The following apply to Resubmittals
5 A. All changes shall be clouded and indicated with a delta that has a corresponding revision number and date. B. Plan review comments shall be addressed in a separate letter specifically addressing each plan review comment. C. Indicate how the plan review comment was addressed and on what sheet the change or correction was made D. All plan review comments must be addressed in order for plans to be approved. If there are any questions regarding code interpretation or the applicability of the code section cited, contact the area inspector to discuss the issue prior to resubmittal.
UNIVERSITY OF ARIZONA CONSTRUCTION AND RENOVATION PERMITTING PROCEDURE ADOPTED: JULY 2011
UNIVERSITY OF ARIZONA CONSTRUCTION AND RENOVATION PERMITTING PROCEDURE ADOPTED: JULY 2011 CONTENTS A. PURPOSE B. DESIGNATED RESPONSIBILITIES C. DEFINITIONS D. PROJECT SUBMITTAL PROCEDURE E. REQUIREMENTS
2014 Commercial Plan Submittal Checklist
City of Aurora Public Works Department AURORA PUBLIC SCHOOLS AND CHERRY CREEK PUBLIC SCHOOLS 2014 Commercial Plan Submittal Checklist Permit Center 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420
BUILDING CODES & DESIGN CRITERIA
BUILDING CODES & DESIGN CRITERIA Adopted Building Codes: 2006 International Building Code (IBC) 2006 International Residential Code (IRC) 2006 International Mechanical Code (IMC) 2006 International Plumbing
APPLICATION NUMBER:, TAX MAP KEY: STREET ADDRESS:, PRPOJECT: APPLICANT:, PHONE NO: MAILING ADDRESS:, FAX NO:
COUNTY OF KAUAI BUILDING DIVISION, DEPARTMENT OF PUBLIC WORKS 4444 RICE STREET, SUITE 175, LIHUE, HAWAII 96766 Telephone: (808) 241-6655 Fax Number: (808) 241-6806 BUILDING CODE COMMERCIAL CHECKLIST APPLICATION
2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES)
2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Reproduce the following data on the building plans sheet 1 or 2) Name of Project: Address:
Permit Requirements: Building Codes: The City of Clanton has adopted the following codes which are enforced by the Building Department:
Permit Requirements: Any owner, authorized agent, or contractor who desires to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install,
HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW
HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW 27 September 2007 prepared by: J. CHRIS EVANS ARCHITECT 3220 E. Terra Alta Blvd. No. 9 Tucson, Arizona 85716 520.319.8835 evansarch@hotmail.com
High Piled Combustible Storage Guideline
Moreno Valley High Piled Combustible Storage Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 5, 2017 Rev: 7-28-16 City of Moreno Valley Fire Department Page 1 of 19 High Piled Storage
CODE COMPLIANCE PLAN REVIEW PROCEDURES
CODE COMPLIANCE PLAN REVIEW PROCEDURES 1. All construction for state agencies on state-owned or state leased-purchased properties or facilities are to submit design documents for code compliance plan reviews
The Building Codes A.R.E. Building Design and Construction Exam Prep
Know Thy Codes! The Building Codes Building Codes The Code of Hammurabi 4000bc Developed 19 th and 20 th c. Codes define what you can and can t do Allowable area and height based on degree of danger Fire
Building Codes and Ordinances ARC 227
Building Codes and Ordinances ARC 227 Week 6 Fire Resistive Construction 03.02.10 Instructor: Rick Staub, AIA Email: staub@pointonearchitects.com Phone: 860-434-7707 Fire Resistive Construction Passive
TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit:
TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION 355-7575 Ext. 395 Needed to Obtain Permit: 1. Building Permit Application, and/or residential plumbing permit application, as applicable, to be
Chapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION
Chapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION Sections: 4-16-01 PURPOSE 4-16-02 APPLICABLE AREA 4-16-03 CONSTRUCTION AND OCCUPANCY 4-16-04 UPPER BUILDING AREA, HEIGHT, NUMBER OF STORIES
Building Code 8 th Edition
Massachusetts State Building Code 8 th Edition Kevin S. Hastings, P.E., LEED AP R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com RW R.W. Sullivan Engineering
What is a Won-Door FireGuard Door?
What is a Won-Door FireGuard Door?. A horizontal sliding accordion fire door that meets all IBC requirements for use in a means of egress and has fire ratings up to 3 hours. A Reference Guide to special
Code Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617)
Code Requirements for Existing Buildings R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS) was established in 1945 and currently
COMMERCIAL PLANS SUBMITTAL CHECKLIST For Commercial and Multi-family (3 or more units) Building Permit Applications
COMMERCIAL PLANS SUBMITTAL CHECKLIST For Commercial and Multi-family (3 or more units) Building Permit Applications Building Permit Application (3 rd Page MUST be signed & notarized by Owner!) Plans can
SECTION : FIRE WALL AND FIRE SUPPRESSION REGULATIONS FOR R1-Z, R-2, R-3 ZONING AND PDD CATEGORIES
SECTION 500.110: FIRE WALL AND FIRE SUPPRESSION REGULATIONS FOR R1-Z, R-2, R-3 ZONING AND PDD CATEGORIES A. Purpose. The intent of this regulation is to amend the current adopted edition of the International
2009 IBC Section 1024 Approved Luminous Egress Path Markings
2009 IBC Section 1024 Approved Luminous Egress Path Markings Where Required Buildings of Groups A (Assembly), B (Business), E (Education), I (Institutional), M (Mercantile) and R-1 (Residential transient
Bureau Policy for Tent Permit
Bureau Policy for Tent Permit Introduction: Occasionally we receive applications for erecting temporary or permanent tents at schools or commercial establishments. This policy is generated to give a general
ADMINISTRATIVE BULLETIN
City and County of San Francisco Department of Building Inspection Edwin M. Lee, Mayor Tom C. Hui, S.E., C.B.O., Director ADMINISTRATIVE BULLETIN NO. AB-032 DATE SUBJECT TITLE November 16, 2016 (Updated
Building Permit Submittal Requirements
CITY OF MONTE SERENO 18041 Saratoga-Los Gatos Road Monte Sereno, CA 95030 Phone (408) 354-7635 Fax (408) 395-7653 www.cityofmontesereno.org Building Permit Submittal Requirements NOTE: Submit three (3)
TOWAMENCIN TOWNSHIP BUILDING PERMIT PROCEDURES
TOWAMENCIN TOWNSHIP BUILDING PERMIT PROCEDURES NON-RESIDENTAL BUILDING PERMIT APPLICATION FORM PART I Location of Property Address, Zoning District, Parcel Number and Lot & Block must be provided on all
Q. Do residential and historical buildings that are going to be protected with sprinklers need to conduct an LSE?
TECHNICAL AND CODE INTERPRETATION QUESTIONS: Q. For evaluation and scoring purposes, the Rules distinguish between Residential and Commercial occupancies. In terms of the referenced sections of the Chicago
Protecting Penetrations in Fire Rated Construction
Protecting Penetrations in Fire Rated Construction NY State Fire Marshals and Inspectors Conference September 7 th Bruce E. Johnson UL Codes and Advisory Services UL and the UL logo are Trademarks of UL
Minnesota Health Care Engineers Association
Minnesota Health Care Engineers Association Life Safety Code Potpourri Friday, May 1, 2015 Presenter: Bob Dehler, P.E., Engineering Program Manager, Minnesota Department of Health Minnesota Department
BULLETIN. Permitting Tips (2/10/14)
BULLETIN Permitting Tips (2/10/14) This bulletin is to make you aware of issues that have been identified by the City or other retailers and suggest Tenant s architect and engineer pursue further as it
PLANS REVIEW CRITERIA - COMMERCIAL BUILDINGS
PLANS REVIEW CRITERIA - COMMERCIAL BUILDINGS NOTE: Building Code compliance is the obligation of design professionals and/or contractors. Plan review and inspection guidelines are to be used to ensure
RESIDENTIAL CONSTRUCTION New Dwellings and Additions
How to Obtain a Building Permit For RESIDENTIAL CONSTRUCTION New Dwellings and Additions MIAMI COUNTY, KANSAS CODE SERVICES DEPARTMENT 201 South Pearl Street, Suite 201 Paola, Kansas 66071-1777 Phone:
Comparison of the life safety elements of the 1997 UBC and the IBC 2000.
Comparison of the life safety elements of the 1997 UBC and the IBC 2000. Introduction The Building Performance Research Institute s mission is primarily one of education on building safety and performance.
Building Permit Application Instructions INFORMATION REQUIRED FOR ISSUANCE OF A BUILDING PERMIT
Building Permit Application Instructions NOTICE: Keep these instructions for your records. Please read and understand these instructions completely prior to completing and submitting your building permit
CODE 101 How To Read The California Building Code
CODE 101 How To Read The California Building Code Part 2 MA Continuing Education August 3, 2015 Instructor: Jay Hyde CSI, Member CALBO, Certified Interior Designer Architect Part 3 Occupancy Groups (Chapters
A/E Design Deliverable Checklist
A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic
CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA
CITY OF DANA POINT COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 33282 Golden Lantern, Suite 209 Dana Point, CA 92629 949 248-3594 www.danapoint.org B005 COM STRUCT 2016 CALIFORNIA CODES CODE CYCLE 01/01/2017
Legalization of Dwelling Units Installed Without a Permit SCREENING FORM No fee to file
City and County of San Francisco Department of Building Inspection Edwin M. Lee, Mayor Tom C. Hui, S.E., C.B.O., Director Legalization of Dwelling Units Installed Without a Permit SCREENING FORM No fee
CITY of COLDWATER. Requirements for Obtaining Building Permits City of Coldwater, Michigan
Requirements for Obtaining Building Permits City of Coldwater, Michigan Any owner, owner s builder, architect or agent who intends to construct, enlarge, alter, repair, move, demolish, or change the occupancy
Short title. This chapter may be cited as the "Kern County Building Code."
Chapter 17.08 BUILDING CODE Sections: 17.08.010 Short title. 17.08.020 Applicability. 17.08.030 Uniform Building CodeBAdopted. 17.08.040 Uniform Building CodeBProvisions not adopted. 17.08.050 Uniform
Telecommunication Spaces
Telecommunication Spaces October 19, 2016 Page 1 Revision History Telecommunication Spaces Standard Effective Date Email Version Contact Phone OIT-TS strevena@csustan.edu 1.0 Stan Trevena 209.667.3137
BUILDING PERMIT BASICS
Corey Bingham, Building Official 2930 Tongass Avenue, Ketchikan, AK 99901 Phone: 907.228.4727 Fax: 907.228.8721 Website: www.city.ketchikan.ak.us BUILDING PERMIT BASICS 1. When is a building permit required?
CITY OF CAMDENTON OFFICE OF THE BUILDING OFFICIAL Commercial Building & Architectural Review Permit Application
CITY OF CAMDENTON OFFICE OF THE BUILDING OFFICIAL Commercial Building & Architectural Review Permit Application DATE: / / PERMIT # REQUEST FOR: NEW BUILDING ADDITION REMODEL PLUMBING ONLY ELECTRIC ONLY
UNINCORPORATED JACKSON COUNTY BUILDING PERMITS
UNINCORPORATED JACKSON COUNTY BUILDING PERMITS May, 2014 Department of Public Works Planning and Environmental Health PREFACE The purpose of this manual is to provide an overview of the procedures to apply
780 CMR: 9 th Edition Massachusetts State Building Code. Presented to: BSA Codes Committee. DATE: January 20, 2016
780 CMR: 9 th Edition Massachusetts State Building Code Presented to: BSA Codes Committee DATE: January 20, 2016 This course is registered with AIA CES for continuing professional education. Credit(s)
BASEMENT FINISH CONSTRUCTION
BASEMENT FINISH CONSTRUCTION June 2017 A City of Rochester Hills Building Department Guide to Finishing a Basement Rochester Hills Building Department 1000 Rochester Hills Dr. 248-656-4615 Guidebooks/Basement
BUILDING PERMIT APPLICATION
TOWN OF LEICESTER 132 Main Street Post Office Box 197 Leicester, New York 14481 Phone: (585) 382-3231 FAX: (585) 382-9766 BUILDING PERMIT APPLICATION All Town of Leicester property owners are required
CHAPTER 8 CHANGE OF OCCUPANCY
CHAPTER 8 CHANGE OF OCCUPANCY SECTION 801 GENERAL 801.1 Rehabilitation with no change of occupancy classification. Any rehabilitation work undertaken in connection with a change of use that does not involve
RESIDENTIAL BUILDING PERMIT CHECKLIST FOR THE CITY OF SANTA ROSA
RESIDENTIAL BUILDING PERMIT CHECKLIST FOR THE CITY OF SANTA ROSA STARTING YOUR REBUILD RIGHT REBUILDING VERSION 1 Additional information regarding the Santa Rosa rebuilding effort available online: SRCity.org/rebuild
Last Updated March 15, 2016
CASS COUNTY, MISSOURI BUILDING CODES, ENVIRONMENTAL HEALTH AND ZONING DEPARTMENT 30508 S. West Outer Road, Harrisonville, MO 64701 P- (816) 380-8134 F- (816) 380-8130 Last Updated March 15, 2016 Information
Application Requirements for obtaining a Building Permit
CITY OF BIRMINGHAM Community Development Building Department 151 Martin Street, Birmingham, MI 48009 Application Requirements for obtaining a Building Permit Residential Structures Building Permit Application
TOWN OF PORT ROYAL BUILDING CODES DEPARTMENT Building Permit Submittal Requirements
TOWN OF PORT ROYAL BUILDING CODES DEPARTMENT Building Permit Submittal Requirements 700 Paris Ave. PO Drawer 9 Port Royal, SC 29935 Application for Permit - P O Drawer 9, Port Royal South Carolina Permit
c) Tiny houses that are not built and permitted per one of these two processes will be considered for PTEV on a case-by-case basis.
DRAFT 2.7 (9/26/16) Port Townsend EcoVillage Tiny House Requirements Please note that the following requirements are a work in progress, many of which are particular to the PT ecovillage. Once finalized,
Residential Building Permit Application
City of Twin Falls Building Department 324 Hansen Street East P.O. Box 1907 Twin Falls, ID 83303-1907 208-735-7238 208-736-2256 www.tfid.org PROJECT INFORMATION Project Residential Building Permit Application
BUILDING PERMIT APPLICATION PACKAGE
BUILDING PERMIT APPLICATION PACKAGE NOTICE TO BUILDING PERMIT APPLICANTS In addition to completed applications forms, the following documentation is required to accompany all building permit applications
WON-DOOR CORPORATION Won-Door FireGuard Applications
WON-DOOR CORPORATION Won-Door FireGuard Applications A Code Analysis WON-DOOR CORPORATION Won-Door FireGuard Applications A Code Analysis THE INTERNATIONAL BUILDING CODE is widely recognized in the United
CITY OF SELMA, TEXAS Inspection Guidelines: Residential
Selma, Texas, located in Bexar, Comal, and Guadalupe Counties Responsible party: Larry Verner, P.E. City Engineer Ph. (210) 651-7828 lverner@ci.selma.tx.us The Permits and Inspections Department welcomes
TOWN OF DEWITT PLANNING AND ZONING PERMIT REQUIREMENTS FOR DECKS
TOWN OF DEWITT PLANNING AND ZONING PERMIT REQUIREMENTS FOR DECKS 1) Copy of survey within ten years showing all structures, property lines and deck location drawn to scale. SURVEYS REDUCED IN SIZE ARE
Received by:* Date Received:* Zoning Approval:* Date:* PERMIT#:* *ZONING: *SETBACKS: FRONT ft/ SIDE ft/ REAR ft *FLOOD ZONE:
HENDRY COUNTY BUILDING, LICENSING & CODE ENFORCEMENT POST OFFICE BOX 2340 * 640 SOUTH MAIN STREET * LABELLE, FLORIDA 33975 * (863) 675-5245 * FAX: (863) 674-4194 1100 OLYMPIA ST CLEWISTON, FLORIDA 33440
RESIDENTIAL BUILDING PERMIT PROCEDURES
RESIDENTIAL BUILDING PERMIT PROCEDURES Community Development Dept. 9220 Bonita Beach Road, Ste. 111 Bonita Springs, FL 34135 (239) 444-6150 permitting@cityofbonitaspringscd.org THREE (3) SETS OF PLANS
FIRE AND SMOKE PROTECTION FEATURES
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated
Standard Plan Review - Project Submittal Checklist
Standard Plan Review - Project Submittal Checklist DATE: APPLICATION #: PROJECT ADDRESS: PROJECT MANAGER: RETURN TO PM WITH MISSING ITEMS 2 nd INTAKE APPOINTMENT The following information is required for
GENERAL PLAN REVIEW REQUIREMENTS
GENERAL PLAN REVIEW REQUIREMENTS Cover Letter A letter (or an authorized pre-printed form) authorizing CCIS to perform the Plan Review is required. CCIS performs plan reviews for the ICC International
PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION
PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION Permit No. 175 Beaver Drive, P.O. Box 486 DuBois, PA 15801 Phone: 814-375-1111 Fax: 814-375-1117 Toll Free: 855-PENNSAF LOCATION OF PROPOSED
Advanced Ventilation for Residential applications FBC Res 2010.
Advanced Ventilation for Residential applications FBC Res 2010. Course Description Review of the Residential Ventilation requirements in the Florida Building Code, Residential 2010. I. Introduction Dean
Chapter UNIFORM CODES FOR CONSTRUCTION BUILDING CODE
Chapter 23.12 UNIFORM CODES FOR CONSTRUCTION BUILDING CODE 23.12.010 Adoption of the 2010 California Building Code. Part 2. Title 24 of the California Code of Regulations. There is adopted and incorporated
Code Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617)
Code Requirements for Existing Buildings R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS) was established in 1945 and currently
SOLAR ENERGY SYSTEMS APPLICATION
For reasonable accommodations or alternative formats please contact 311 at 612-673-3000. People who are deaf or hard of hearing can use a relay service to call 311 at 612-673-3000. TTY users call 612-673-2157
TYP. SINGLE PLY ROOFING ROOF SHEETING BROAN VENT CAP #10 x 1" GASKETED SMS TYP. 4 SIDES 8" FRAMED CURB HVAC SYSTEMS "BASIS OF DESIGN" ROOF INSULATION R-19 WALL INSULATION R-13 LIGHTING EFFIECNCY PER STANDARDS
Code Inspections, Inc.
Permit Application will be automatically REJECTED if all highlighted areas are not filled out. All other areas of application pertaining to the project shall also be filled out. Code Inspections, Inc.
Jean Vaillancourt Fire Protection Specialist Hilti (Canada) Corp.
Cable Management Firestop Jean Vaillancourt Fire Protection Specialist Hilti (Canada) Corp. FIRESTOPPING KNOWLEDGE FOR BETTER SPECIFICATION AND DESIGN OF FIRE-RATED CONSTRUCTION Presentation Topics and
780 CMR CHAPTER 34 EXISTING BUILDINGS STRUCTURES
780 CMR CHAPTER 34 EXISTING BUILDINGS STRUCTURES SECTION 3401 GENERAL 3401.1 Scope. Chapter 34 of the International Building Code 2009 is deleted in its entirety. The provisions of the International Existing
AGREEMENT CONCERNING EXISTING AS BUILT CONSTRUCTION
AGREEMENT CONCERNING EXISTING AS BUILT CONSTRUCTION Building Permit Number: Date Received: By: I,, as owner of record of the above property, hereby request a permit for and final inspection of the installation
SITE PLAN AND ARCHITECTURAL REVIEW APPLICATION
SITE PLAN AND ARCHITECTURAL REVIEW APPLICATION CITY OF GENEVA, NEW YORK The purpose of the site plan and architectural review process is to secure compliance with the City s Zoning Ordinance and to promote
SPECIFICATION DIVISION 7 NUMBER SECTION DESCRIPTION DIVISION 07 THERMAL AND MOISTURE PROTECTION SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS
BuildingName The Description of the Project P00000000 0000 DOCUMENTS Title Page Table of Contents Instruction to Bidders Form of Proposal Equal Opportunity Statement Form of Guarantee Supplemental General
IBC FIRE SAFETY. Code Change No: FS1-07/08. Original Proposal SECTION 702 DEFINITIONS
DOCUMENTATION IBC FIRE SAFETY Code Change No: FS1-07/08 Sections: 702.1, 704.8.2, 706.7 Proponent: Philip Brazil, PE, Reid Middleton, Inc., representing himself SECTION 702 DEFINITIONS 702.1 Definitions.
WARWICK TOWNSHIP Dept. of Planning & Zoning
For Warwick Township Use Only WARWICK TOWNSHIP Dept. of Planning & Zoning 1733 Township Greene, Jamison, PA 18929 : (215) 343-6100 www.warwick-bucks.org Check #: Check Amount: Received by: BUILDING PERMIT
THE BUILDING PERMIT PROCESS
THE BUILDING PERMIT PROCESS How to use this diagram This is a graphic diagram of the Building Permit Process. Click on each step to find a detailed explanation of that part of the process. These are the
CITY OF CRANSTON RESIDENTIAL PERMIT PROCEDURE BASEMENT RENOVATION
CITY OF CRANSTON RESIDENTIAL PERMIT PROCEDURE BASEMENT RENOVATION WE WILL NOT ACCEPT ANY PLANS OR PAPERWORK TO START THE REVIEW PROCESS UNTIL ALL ITEMS BELOW ARE SUBMITTED TO US AT THE SAME TIME. PLANS
EXHIBIT DESIGN REGULATIONS
EXHIBIT DESIGN REGULATIONS May 19-22, 2018 McCormick Place Chicago, IL USA REGULATIONS & GUIDELINES TABLE OF CONTENTS STANDARD. 2 PERIMETER 3 PENINSULA 4 ISLAND 5 HANGING SIGNS. 5 CANOPIES & CEILINGS.
CONSTRUCTION TECHNOLOGY UPDATE
CONSTRUCTION TECHNOLOGY UPDATE No. 78, September 2011 Building Egress Using Photoluminescent Markings by Noureddine Benichou and Guylene Proulx The use of photoluminescent material systems in buildings
ARTICLE 987. PD 987. PD 987 was established by Ordinance No , passed by the Dallas City Council on June 14, (Ord.
ARTICLE 987. PD 987. SEC. 51P-987.101. LEGISLATIVE HISTORY. PD 987 was established by Ordinance No. 30512, passed by the Dallas City Council on June 14, 2017. SEC. 51P-987.102. PROPERTY LOCATION AND SIZE.
The following is required for a complete permit submittal for each unit.
P: (847)810-3502 OR (847)810-3503/3521, F: (847)615-4383 MULTI-FAMILY OR COMMERCIAL ADDITION OR ALTERATION PERMIT REQUIREMENTS The following is required for a complete permit submittal for each unit. MULTI-FAMILY
SIDEWALK & RAILING REPLACEMENT BOARD OF ED BUILDING
PROJECT: 25 E 5 S SALT LAKE CITY, UTAH 84111 CODE ANALYSIS APPLICABLE CODES 675 E. 5 S. Suite 4 DFCM PROJECT NUMBER: 182782 DFCM CONTRACT NUMBER: 18793 STRUCTURAL ENGINEER: REAVELEY ENGINEERS + ASSOCIATES
Considering Modular Buildings for Your Space Needs?
Considering Modular Buildings for Your Space Needs? Consider This Design of Space: What will you be using the building for? How many square feet of space per person is reasonable? Code Requirements*: (building
E d u c a t i o n a l S e m i n a r s f o r B u i l d i n g & R e s i d e n t i a l C o d e
I N D E X E d u c a t i o n a l S e m i n a r s f o r B u i l d i n g & R e s i d e n t i a l C o d e Title Course Number *Seminar Length (days) Pg. Class Scheduling Policies 8 International Building Code
INFORMATION SHEET. To demolish the entire building to the foundation will require a demolition permit (Form 6).
City and County of San Francisco Department of Building Inspection Edwin M. Lee, Mayor Tom C. Hui, S.E., C.B.O., Director INFORMATION SHEET NO. 5-04 DATE CATEGORY SUBJECT : June 22, 2015 Structural Demolition
CITY OF CHICAGO DEPARTMENT OF BUILDINGS
CITY OF CHICAGO DEPARTMENT OF BUILDINGS GUIDELINES FOR THE PREPARATION OF REQUESTS FOR QUALIFICATIONS FOR THE SELECTION OF CONSULTING FIRMS TO PERFORM LIFE SAFETY EVALUATIONS The Chicago Department of
COMMUNITY DEVELOPMENT
COMMUNITY DEVELOPMENT PERMITTING PROCEDURE FOR NEW SINGLE FAMILY & DUPLEX RESIDENCES, ADDITIONS, ALTERATIONS, SHEDS, UTILITY BUILDINGS, GAZEBOS, POLE- BARNS & DETACHED GARAGES (eff. 3/15/2012) Plans that
2007 Title 24 Accessibility Code Updates and ADA Issues
2007 Title 24 Accessibility Code Updates and ADA Issues C.A.S.H. Workshop June 2007 Introduction Update on ADA Certification of the California Building Code Overview of significant changes to accessibility
MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement
MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement Draft 11/17/08 Utility transformer issues began surfacing last year with questions of enforcement responsibilities due to utility
EARLY START PERMITS. Site cleaning, including removal of any existing asphalt, and/or concrete slab, Excavation work under the building footprint,
INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.106.4 Effective: 01-01-2017 DOCUMENT NO.: P/BC 2017-097 Revised: Previously Issued As: P/BC 2014-097 EARLY START PERMITS Los Angeles
Technical Facility Management FACILITY CONSULTING SERVICES. The Facility Audit Program
Technical Facility Management FACILITY CONSULTING SERVICES The Facility Audit Program TFM Audit Program - Schedule Customer: Dates of Visit: AREA TFM CUSTOMER SUBJECT Goals/Objectives Schedule Key Interviews
City of Jacksonville Development Guide Building Permits
City of Jacksonville TX City of Jacksonville Development Guide Building Permits A publication to help understand the Building Permit process in the City Jacksonville. Building Department 2011 J Revised
APPLICATION FOR PORCH / DECK PERMIT
Department of Neighborhood Services and Inspections 625 52nd Street, Room 100, Kenosha, WI 53140 Phone: 262.653.4263, Fax: 262.653.4254 APPLICATION FOR PORCH / DECK PERMIT Permit Fee: $60.00, Zoning Plan
2018 IBC Update. Based on the 2018 International Building Code, (IBC ) Goal. Objectives. Content
Based on the 2018 International Building Code, (IBC ) The International Building Code (IBC ), establishes minimum regulations for building safety. This handout will identify important changes in the IBC
2012 IBC Assembly Means of Egress. Based on the 2012 International Building Code
2012 IBC Assembly Means of Egress Based on the 2012 International Building Code Overview This seminar deals with those means of egress provisions of the IBC that are intended to address the concerns related
# 5 ) UN THREE CUPS YARD NORTH AMERICA CULTIVATION FACILITY SPECIAL USE PERMIT PUBLIC HEARING
# 5 ) UN-74-16 THREE CUPS YARD NORTH AMERICA CULTIVATION FACILITY SPECIAL USE PERMIT PUBLIC HEARING STAFF REPORT To: Planning Commission Meeting date: November 9, 2016 Item: UN-74-16 Prepared by: Marc
Applying the Building Code During Design
Applying the Building Code During Design A Step-By-Step Process AIA Learning Units The Salt Lake City CSI Chapter is a Registered Provider with The American Institute of Architects Continuing Education
Title: Building Construction for the Fire Service. Time: 3 hours. Teaching Materials: White board Building Construction for the Fire Service (PDF)
Title: Building Construction for the Fire Service Time: 3 hours Teaching Materials: White board Building Construction for the Fire Service (PDF) Motivation: With the evolution of newer building construction
COMMERCIAL PLAN REVIEW CHECKLIST
Bloomfield Township Building Division. P.O. Box 489 4200 Telegraph Road Phone (248) 433-7715 Fax: 433-7729 Inspection Line (248) 594-2818 Website: http//www.bloomfieldtwp.org COMMERCIAL PLAN REVIEW CHECKLIST
Community Development Department Planning Division 1600 First Street + P.O. Box 660 Napa, CA Napa (707)
Community Development Department Planning Division 1600 First Street + P.O. Box 660 Napa, CA 94559-0660 Napa (707) 257-9530 PLANNING COMMISSION STAFF REPORT MAY 19, 2016 AGENDA ITEM #7.B. 16-0063-DR; NAPA
Week of June 6, 2005
TAILGATE TRAINING ENGINEERING BUREAU Week of June 6, 2005 1. GENERAL Reviewed by: ƒ ORDINANCE 176673 Ordinance amending Division 85 of Article 1 of Chapter IX of the LAMC in its entirety to be in conformance