1 A Look into the The look and layout of the 2012 IECC changes Commercial Energy chapters 1-4 Commercial (CE) and chapters 1-4 Residential (RE) 2012 IECC 2011 Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 1

2 Commercial Changes from 2009 to 2012 C101.2 Scope In addition to the code applying to the commercial building, it now also applies to the building sites and associated systems and equipment. C101.3 Intent In addition to regulating the design and construction of the buildings for the effective use of energy, it now also states that it is to conserve energy over the useful life of each building Colorado Code Consulting, LLC 4 Chapter 2: New or Changed Definitions Building Any structure used or intended for supporting or sheltering any use or occupancy, including any mechanical systems, service water heating systems and electric power and lighting systems located on the building site and supporting the building Colorado Code Consulting, LLC 5 Chapter 2: New or Changed Definitions Building Commissioning A process that verifies and documents that the selected building systems have been designed, installed, and function according to the owner s project requirements and construction documents, and to minimum code requirements Colorado Code Consulting, LLC Colorado Code Consulting, LLC 2

3 Chapter 2: New or Changed Definitions Building Entrance Any door, set of doors, doorway, or other form of portal that is used to gain access to the building from the outside by the public. Building Site A contiguous area of land that is under the ownership or control of one entity Colorado Code Consulting, LLC 7 Chapter 2: New or Changed Definitions Continuous Air Barrier A combination of materials and assemblies that restrict or prevent the passage of air through the building thermal envelope 2011 Colorado Code Consulting, LLC 8 Chapter 2: New or Changed Definitions Dynamic Glazing Any fenestration product that has the fully reversible ability to change its performance properties, including U-factor, SHGC, or VT Colorado Code Consulting, LLC Colorado Code Consulting, LLC 3

4 Chapter 2: New or Changed Definitions Equipment Room A space that contains either electrical equipment, mechanical equipment, machinery, water pumps or hydraulic pumps that are a function of the building s services. Chapter 2: New or Changed Definitions Fenestration Field Fabricated A fenestration product whose frame is made at the construction site of standard dimensional lumber or other materials that were not previously cut, or otherwise formed with the specific intention of being used to fabricate a fenestration product or exterior door. Field fabricated does not include site-built fenestration. Site Built A fenestration designed to be made up of field-glazed or field-assembled units using specific factory cut or otherwise factory formed framing and glazing units. Examples of site-built fenestration include storefront systems, curtain walls, and atrium roof systems. Chapter 2: New or Changed Definitions General Lighting Lighting that provides a substantially uniform level of illumination throughout an area. General lighting shall not include decorative lighting or lighting that provides a dissimilar level of illumination to serve a specialized application or feature within such area Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 4

5 Chapter 2: New or Changed Definitions On-site Renewable Energy Energy derived from solar radiation, wind, waves, tides, landfill gas, biomass, or the internal heat of the earth. The energy system providing on-site renewable energy shall be located on the project site.. Chapter 2: New or Changed Definitions Skylights 2009 Glass or other transparent or translucent glazing material installed at a slope of 15 degrees or more from vertical 2012: Glass or other transparent or translucent glazing material installed at a slope of less than 60 degrees from horizontal. Glazing material in skylights, including unit skylights, solariums, sunroofs, roofs and sloped walls is included in this definition. Chapter 2: New or Changed Definitions Visible Transmittance The ratio of visible light entering the space through the fenestration product assembly to the incident visible light. Visible Transmittance includes the effects of glazing material and frame and is expressed as a number between 0 and Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 5

6 Chapter 3: General Requirements C Fenestration product rating. U Factors rated in accordance with NFRC 100 SHGC and VT rated in accordance with NFRC 200. (Products lacking labels shall be assigned a default from the tables) Chapter 4: Commercial Energy Efficiency The 2012 IECC references ASHRAE instead of 2007 Commercial Application Commercial buildings shall comply with one of the following: (Prescriptive)The requirements of Sections C402, C403, C404 and C405. In addition, commercial buildings shall comply with either Section C406.2, C406.3 or C406.4 (Performance) The requirements of Section C407, C402.4, C403.2, C404, C405.2, C405.3, C405.4, C405.6 and C The building energy cost shall be equal to or less than 85 percent of the standard reference design building. As an alternative the commercial building project shall comply with the requirements of ASHRAE/IESNA 90.1 in its entirety Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 6

7 Building Envelope Requirements (Prescriptive) C402.2 Specific insulation requirements New: Where 2 or more layers of continuous insulation board are used in a construction assembly, the continuous insulation boards shall be installed in accordance with Section C Also: If the manufacturer's install instructions don t address installation of 2 or more layers, the edge joints between each layer of continuous insulation boards shall be staggered Colorado Code Consulting, LLC 19 Specific insulation requirements (Prescriptive) Skylight curbs: Insulated to the level of roofs with insulation entirely above deck or R-5, whichever is less. Exception: Unit skylight curbs included as a component of an NFRC 100 rated assembly shall not be required to be insulated Colorado Code Consulting, LLC 20 C Roof Solar Reflectance and Transmittance Climate Zones 1, 2, or 3 Low sloped roofs (slopes less than 2 in 12) that are above a cooled space, shall comply with one or more of the options in Table C Exceptions apply for solar, PV, roof gardens, skylights, HVAC equipment on deck, etc 2011 Colorado Code Consulting, LLC Colorado Code Consulting, LLC 7

8 C Roof Solar Reflectance and Transmittance Area-weighted averages permitted Default values if materials don t have initial or three year values C Slabs on grade Just clarifies that the requirements for slabs in commercial buildings apply to a slab that is in contact with the ground, whether heated or unheated. Must comply with requirements of Table C402.2, which now has a requirement in Climate Zone 5 that didn t used to be there. Exception: slabs greater than 24 below grade. This exception was not in the 2009 for commercial. C Insulation of radiant heating systems Radiant panels, and associated U-bends and headers, designed for sensible heating of an indoor space through heat transfer from the thermally effective panel surfaces to the occupants or indoor space by thermal radiation and natural convection and the bottom surfaces of floor structures incorporating radiant heating shall be insulated with a minimum R Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 8

9 25 Fenestration (Mandatory) Requirements For fenestration, focus is often on U and SHGC, but there are also mandatory Air Leakage requirements. Max air infiltration rate depends on product type. Tested by independent lab, labeled by manufacturer Product Type Windows, skylights, sliding and swinging doors Skylights with weepage openings Curtainwall / storefront Commercial swinging entrance doors, revolving doors Max leakage 2012 IECC 0.2 cfm/ft 2 at 1.57 psf or 0.3 cfm/ft 2 at 6.24 psf 0.3 cfm/ft 2 at 1.57 psf or 0.5 cfm/ft 2 at 6.24 psf 0.06 cfm/ft 2 at 1.57 psf 1.0 cfm/ft2 at 1.57 psf Test method NFRC 400 or 101/I.S.2/A440 ASTM E 283 or NFRC 400 ASTM E 283, or 101/I.S.2/A440 or NFRC Fenestration (Prescriptive) C402.3 Vertical fenestration area (not including opaque doors and opaque spandrel panels) shall not exceed 30% of the gross above-grade wall area. (Was 40% in 2009 IECC) Skylights shall not exceed 3% of the gross roof area. (with daylighting controls this can be increased to 5% per C ) 2011 Colorado Code Consulting, LLC Colorado Code Consulting, LLC 9

10 Fenestration (Prescriptive) C402.3 Increases to 40% glazing allowed, CZ 1 through 6, provided: 1. No less than 50% of the conditioned floor area is within a daylight zone; 2. Automatic daylighting controls are installed in daylight zones; and 3. Visible transmittance of vertical fenestration is grater than or equal to 1.1 times SHGC. Exception: Fenestration that is outside the scope of NFRC 200 is not required to comply with item Colorado Code Consulting, LLC 28 VT Visible Transmittance Tinted products reduce the amount of visible light. This reduction in Visible Transmittance (VT) can lead to an increase in the amount of artificial lighting needs in buildings. To take advantage of potential savings from daylighting, the industry has seen growth in the use of spectrally selective glass. This type of glass has special properties that block or re-radiate the infrared energy from the sun, reducing solar gain, while maintaining higher levels of visible light transmittance Colorado Code Consulting, LLC Lower U-Factors for Most Zones Along With NEW Classifications Higher U-Factors for Zones 5-8 in most cases. Why? 2009 Colorado Code Consulting, LLC Colorado Code Consulting, LLC 10

11 C Minimum skylight fenestration area Enclosed spaces greater than 10,000 sq. ft., directly under a roof with ceiling heights greater than 15 feet, and used as specified occupancies, the total daylight zone under the skylights shall be not less than half the floor area and shall provide a minimum skylight area to daylight zone under skylights of either: Not less than 3% with a skylight VT of at least 0.40; or Provide a minimum skylight effective aperture of at least 1% determined in accordance with equation 4-1. Exception: Skylights above daylight zones of enclosed spaces are not required in 1. Buildings in climate zones Spaces where the designed general lighting power densities are less than 0.5 W/sq ft. 3. Areas where it is documented that the existing structures or natural objects block direct beam sunlight on at least half of the roof over the enclosed area for more than 1500 daytime hours per year between 8am and 4pm. 4. Spaces where the daylight zone under the rooftop monitors is greater than 50% of the enclosed space floor area. Lighting controls in daylight zones under skylights C All lighting in the daylight zone shall be controlled by multilevel lighting controls that comply with C (reduces lighting power in response to daylight available in the space) Same exceptions apply as in previous section where skylights are not required. C Haze Factor Certain occupancies are required to have a glazing material or diffuser with a measured haze factor greater than 90% when tested in accordance with ASTM D1003. Except skylights designed to exclude direct sunlight entering the occupied space by the use of fixed or automated baffles, or the geometry of skylight and light well. C Projection Factor Equation 4-2 PF = A/B where: PF = Projection factor (decimal). A = Distance measured horizontally from the furthest continuous extremity of any overhang, eave, or permanently attached shading device to the vertical surface of the glazing. B = Distance measured vertically from the bottom of the glazing to the underside of the overhang, eave, or permanently attached shading device. B A PF= A/B PF = 30 /84 PF = 0.36 Zone 5 SHGC - NR 2011 Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 11

12 C SHGC adjustment First, please note that there is a typo in the table the second line of the table should read: PF > 0.5 Second, in a sense, this section is an optional form of projection factor trade-off that is, it provides a reduction in stringency for SHGC (by increasing it) where there is significant projection factor (greater than or equal to 0.20). As a result, if a person does not want to calculate the projection factor, they can use the standard requirement in Table C402.3 (since that requirement is more stringent). > Example: Using the 0.40 SHGC requirement in CZ 5 to illustrate, that 0.40 becomes 0.44 for northern facing windows (0.40 * 1.1) and 0.48 for other orientations (0.40 * 1.2) if the projection factor is greater than or equal to 0.2 and less than Colorado Code Consulting, LLC 34 C SHGC adjustment Third, this modification in the SHGC requirement is specific to the requirement for each vertical fenestration product (not a weighted average). Under this provision, if a fenestration product has a projection factor greater than or equal to 0.2 and less than 0.5, then the SHGC requirement from Table C402.3 multiplied by 1.1 for northern oriented windows and 1.2 for all others. For products with projection factors equal to or greater than 0.5, the multipliers are 1.2 and 1.6. > 2011 Colorado Code Consulting, LLC 35 SHGC Credit for Permanent Shading Max allowable SHGC is determined using multiplier based on PF and direction the glazing faces. See Table C For example, a sunshade facing east, south, or west with 0.3 PF has a mutiplier of 1.2. Therefore, max SHGC in zones 4-6 is 1.2 x 0.40 = 0.48 There is currently a flaw in Table C that erroneously requires a lower SHGC on the north than on the other sides Colorado Code Consulting, LLC 12

13 C Dynamic Glazing Fenestration Compliance Overview of CMA Program, CMAST Definition: Any fenestration product that has the fully reversible ability to change its performance properties, including U-factor, SHGC, or VT For compliance with Section C , the SHGC for dynamic glazing shall be determined using the manufacturer s lowest-rated SHGC, and the VT/SHGC ratio shall be determined using the maximum VT and the maximum SHGC. Dynamic glazing shall be considered separately from other fenestration, and area-weighted averaging with other fenestration that is not dynamic glazing shall not be permitted Colorado Code Consulting, LLC 37 NFRC CMAST Program Component Modeling Approach (CMA) Software Tool (CMAST) A New Approach New concept: build virtual products and projects using predefined and certified components from online CMA database to issue projectspecific label certificates 2011 Colorado Code Consulting, LLC 38 U-FACTOR (thermal transmission) NFRC 100 SHGC (Solar Heat Gain) NFRC 200 VT (Visible Transmittance) NFRC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 13

14 Fenestration Labeling U-factors, SHGC, and VT must be determined in accordance with NFRC procedures by an independent lab Otherwise, use defaults in Table C NFRC label certificate is a good source, but manufacturer may submit own certificates or test reports as long as done by independent lab and states in accordance with NFRC 100 and 200. Generally, will not see NFRC labels on individual windows like in residential homes. More common to use a certificate listing multiple products on the building project. Fenestration Labeling NFRC label certificate shows U, SHGC, and VT at a hypothetical standard size. Real performance will be different, based on actual size of product and amount of glass vs. framing. NFRC and other test reports also provide supplemental info on U, SHGC, and VT at actual size. Especially useful for more accurate HVAC sizing C Air Barriers Continuous air barrier shall be provided throughout the building thermal envelope. Air barriers shall be permitted to be located on the inside or outside of the building envelope, located within the assemblies composing the envelope, or any combination thereof. Air barriers not required in climate zones 1-3. Air barrier construction: Shall be continuous for all assemblies that are the thermal envelope of the building and across the joints and assemblies Air barrier joints and seams shall be sealed, including sealing transitions in places and changes in materials. Air barrier penetrations shall be sealed 2011 Colorado Code Consulting, LLC Colorado Code Consulting, LLC 14

15 Prosoco R-Guard C Air Barriers Air barrier construction: Joints and seals shall be securely installed in or on the joint for its entire length so as not to dislodge, loosen or otherwise impair its ability to resist positive and negative pressure from wind, stack effect and mechanical ventilation. Recessed lighting fixtures shall comply with Section C Where similar objects are installed which penetrate the air barrier, provisions shall be made to maintain the integrity of the air barrier Colorado Code Consulting, LLC 43 C Air barrier compliance options A continuous air barrier for the opaque building envelope shall comply with Section C , C , OR C Option 1: C Materials New list of 15 items that are deemed to comply as an air barrier material provided that joints are sealed and materials are installed as air barriers in accordance with the manufacturer s instructions Colorado Code Consulting, LLC 44 C Air barrier materials Plywood - > 3/8 OSB - > 3/8 XPS - > 1/2 Polyiso-Foil - > 1/2 SPF CC - > 1 1/2 SPF OC - > 4 1/2 Gyp board - > 1/2 Cement board - > 1/2 Built up roofing membrane Modified bituminous roof membrane Fully adhered single-ply roof membrane Gypsum plaster > 5/8 Precast concrete Concrete block, grouted Sheet steel or aluminum 2011 Colorado Code Consulting, LLC Colorado Code Consulting, LLC 15

16 Option 2: Air barrier assemblies Assemblies of materials and components meeting specific air leakage requirements can comply. 2 items listed as deemed to comply provided joints are sealed Concrete masonry walls coated with one application either of block filler and two applications of a paint or sealer coating; A Portland cement/sand parge, stucco or plaster min ½ in thickness Colorado Code Consulting, LLC 46 Option 3: C Air barrier building test The completed building shall be tested and the air leakage rate of the building envelope shall not exceed 0.40 cfm/ft² at a pressure differential of 0.3 inches water gauge in accordance with ASTM E 779 or an equivalent method approved by the code official Colorado Code Consulting, LLC 47 C Air barrier penetrations Penetrations of the air barrier and paths of air leakage shall be caulked, gasketed or otherwise sealed in a manner compatible with the construction materials and locations.. Joints and seals shall be securely installed in or on the joint for its entire length so as not to dislodge, loosen or otherwise impair its ability to resist positive and negative pressure from wind, stack effect and mechanical ventilation Colorado Code Consulting, LLC Colorado Code Consulting, LLC 16

17 Air leakage in other building components C C New air leakage requirements for: Doors and access openings to shafts, chutes, stairways and elevator lobbies Air intakes, exhaust openings, stairways and shafts Outdoor air intakes and exhausts Certain exceptions exist for door openings that must comply with the IBC (Section 715), certain damper situations related to the building s fire alarm system, gravity dampers and dampers smaller than 24 in either dimension Colorado Code Consulting, LLC 49 Wording changed from stating that A door that separates conditioned space from the exterior shall be protected with an enclosed vestibule To All building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices. C Vestibules 2009 Colorado Code Consulting, LLC 50 C Vestibules Exception Doors not intended to be used by the public or intended soley for employee use New wording: The installation of one or more revolving doors in the building entrance shall not eliminate the requirement that a vestibule be provided on any doors adjacent to revolving doors Colorado Code Consulting, LLC Colorado Code Consulting, LLC 17

18 C403 Building Mechanical Systems New equations for calculating condenser water flow for certain water-cooled centrifugal chilling packages Changes to equipment efficiencies in 7 of the 9 tables New requirement for automatic start controls to be provided for each HVAC system. Demand control ventilation requirements changed to match the current IMC requirements. Energy recovery ventilation systems requirements re-written, including the exceptions. HVAC piping insulation table changed completely but still based on thickness of insulation instead of R-value Piping insulation protection is defined Economizer sections have been re-written and further clarified. New requirements for integrated economizer controls as well as static pressure sensor locations for VAV fans. C Calculation of heating and cooling loads Design loads shall be determined in accordance with the procedures described in ANSI/ASHRAE/ACCA Standard 183. The design loads shall account for the building envelope, lighting, ventilation and occupancy loads based on the project design. C Equipment and system sizing The output capacity of heating and cooling equipment and systems shall not exceed the loads calculated in accordance with Section C Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 18

19 C403.2.x Tables All tables have changed Efficiency values have changed New table for heat pump equipment Expands heat pump and room air conditioning table C Energy Recovery ventilation Simplifies this section, includes requirements if economizer used Adds table for ERVs Changes exceptions to climate zones instead of loads, HDD, temperatures C Protection of piping insulation Piping insulation exposed to weather shall be protected from damage, including that due to sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesives tape shall not be permitted Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 19

20 C Economizers C Economizers C Economizers Each cooling system that has a fan shall include either an air or water economizer. Exceptions: Economizers are not required for the systems listed below. Individual fan-cooling units with a supply capacity less than the minimum listed in Table C (1). Where more than 25 percent of the air designed to be supplied by the system is to spaces that are designed to be humidified above 35 F (1.7 C) dew-point temperature to satisfy process needs. Each cooling system that has a fan shall include either an air or water economizer. Exceptions Systems that serve residential spaces where the system capacity is less than five times the requirement listed in Table C (1). Systems expected to operate less than 20 hours per week. Where the use of outdoor air for cooling will affect supermarket open refrigerated casework systems. Where the cooling efficiency meets or exceeds the efficiency requirements in Table C (2). In 2009 IECC systems were > 54,000 Btu/h 2009 Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 20

21 C404 Service Water Heating Change to pipe insulation requirements that now include calculations instead of an R-value. Pool covers are now just vapor-retardant covers with no mention of the R-12 covers but the allowance to opt out of the requirements if you derive over 60% of the energy for heating from site-recovered energy has changed to 70%. C405 Mandatory Lighting Controls The description of lighting systems and controls has changed in C405.1 to include electrical energy consumption. In addition to the requirements for interior lighting controls, manual lighting controls have been added The exceptions have been expanded upon in C for when you don t have to provide light reduction controls C405 Mandatory Lighting Controls The entire section on automatic lighting shutoff and occupant override has been reformatted and renamed under Additional lighting controls and Automatic time switch control devices in C The requirements have stayed the same, they are just under different section titles Removed the requirement for holiday scheduling 2009 Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 21

22 C405 Mandatory Lighting Controls Added section C , which requires occupancy sensors be installed in all classrooms, conference/ meeting rooms, employee lunch and break rooms, private offices, restrooms, storage rooms and janitorial closets and other spaces 300 square feet or less enclosed by floor to ceiling height partitions, with an exception for public corridors, stairways, etc where it would endanger the safety or security of the occupants. C Daylight Zone Controls Daylight zones must be controlled independently of general area lighting Each daylight control zone shall not exceed 2500 sq. ft. Daylight zones under skylights more than 15 feet from the perimeter shall be controlled separately from daylight zones adjacent to vertical fenestration Manual and automatic daylighting controls shall be: be readily accessible Capable of automatically reducing the lighting power in response t available daylight by either continuous or stepped dimming controls C Specific application controls Display and accent light shall be controlled by a dedicated control, independent of controls for other lighting Lighting in cases used for display case purposes shall be controlled by a dedicated, independent control Hotel and motel sleeping units and guest suites shall have a master control device at the main room entry that controls permanently installed luminaires and switched receptacles 2011 Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 22

23 C Specific application controls C Interior Lighting Power C Interior Lighting Power Supplemental task lighting, including permanently installed under-shelf or undercabinet lighting, shall have a control device Lighting for nonvisual applications, such as plant growth and food warming, shall be controlled by dedicated, independent controls Lighting equipment that is for sale or demonstration in lighting education shall be by dedicated, independent controls Total interior lighting power allowance can now be determined by using the Building Area Method as was in the 2009 IECC, or by using the new table for calculating allowances using the Space-by-Space Method Notice in the footnotes of the new table that you are still allowed the additional interior lighting allowances for retail areas using this Space-by-Space method. For the Space-by-Space Method, the interior lighting power allowance is determined by multiplying the floor area of each space times the value for the space type in Table C405.2(2) that most closely represents the proposed use of the space, and then summing the lighting power allowances for all spaces. Tradeoffs among spaces are permitted. Total interior lighting power allowance can now be determined by using the Building Area Method as was in the 2009 IECC, or by using the new table for calculating allowances using the Space-by-Space Method Notice in the footnotes of the new table that you are still allowed the additional interior lighting allowances for retail areas using this Space-by-Space method. For the Space-by-Space Method, the interior lighting power allowance is determined by multiplying the floor area of each space times the value for the space type in Table C405.2(2) that most closely represents the proposed use of the space, and then summing the lighting power allowances for all spaces. Tradeoffs among spaces are permitted Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 23

24 C406 efficiency package options C406 efficiency package options C408 System commissioning NEW!!!!! Buildings shall comply with at least one of the following: Efficient HVAC Performance in accordance with Section C406.2 Efficient Lighting System in accordance with Section C406.3 On-Site Supply of Renewable Energy in accordance with C406.4 You have to choose one of these options in addition to all of the other requirements in Chapter C4 Either have higher efficiency HVAC equipment per the new tables Or an even further reduced lighting power density Or On-site renewable energy Colorado Code Consulting, LLC 70 NEW!!!!! Buildings shall comply with at least one of the following: Efficient HVAC Performance in accordance with Section C406.2 Efficient Lighting System in accordance with Section C406.3 On-Site Supply of Renewable Energy in accordance with C406.4 You have to choose one of these options in addition to all of the other requirements in Chapter C4 Either have higher efficiency HVAC equipment per the new tables Or an even further reduced lighting power density Or On-site renewable energy Colorado Code Consulting, LLC 71 NEW!!!! Prior to passing the final mechanical inspection, the registered design professional shall provide evidence of mechanical systems commissioning and completion in accordance with the provisions of this section. Registered Design Professional and Commissioning are supposed to be a defined terms but they forgot to add the definitions. Look for a future errata to be printed. C Acceptance of report: Buildings, or portions thereof, shall not pass the final mechanical inspection until such time as the code official has received a letter of transmittal from the building owner acknowledging that the building owner has received the preliminary commissioning report Colorado Code Consulting, LLC Colorado Code Consulting, LLC 24

25 C408 System Commissioning C Systems adjusting and balancing. HVAC systems shall be balanced in accordance with generally accepted engineering standards C Air systems balancing. Each supply air outlet and zone terminal device shall be equipped with means for air balancing C Hydronic systems balancing. Individual hydronic heating and cooling coils shall be equipped with means for balancing and measuring flow C408 System Commissioning C Preliminary commissioning report. A preliminary report of commissioning test procedures and results shall be completed and certified by the registered design professional or approved agency and provided to the building owner. C Final commissioning report. Final Commissioning Report shall be delivered to the building owner C408.3 Lighting system functional testing. Residential Energy 2011 Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 25

26 Residential Changes from 2009 to 2012 R101.2 Scope In addition to the code applying to the residential building, it now also applies to the building sites and associated systems and equipment. R101.3 Intent In addition to regulating the design and construction of the buildings for the effective use of energy, it now also states that it is to conserve energy over the useful life of each building. New or changed residential definitions Building thermal envelope: The basement walls, exterior walls, floor, roof, and any other building elements that enclose conditioned space or provides a boundary between conditioned space and exempt or unconditioned space. Whole House Ventilation System An exhaust system, supply system, or combination thereof that is designed to mechanically exchange indoor air with outdoor air when operating continuously or through a programmed intermittent schedule to satisfy the whole house ventilation rates. Residential Energy Efficiency Chapter 4 (RE) Certificate (Mandatory) A permanent certificate shall be completed and posted on or in the electrical distribution panel by the builder or registered design professional. It shall not cover or obstruct the visibility of the circuit directory label, service disconnect label or other required labels. The Certificate shall list: Predominant R-values of insulation installed in the thermal envelope R-Values of insulation on ducts outside conditioned space U-factors and SHGC for fenestration Results from any required duct system and building envelope air leakage testing done Types and efficiencies of heating, cooling and service water heating equipment If there is a gas-fired unvented room heater in the building If there is an electric furnace or baseboard electric heater in the building Building envelope air leakage testing 2011 Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 26

27 Insulation and Fenestration Requirements 2009 Colorado Code Consulting, LLC 79 Insulation and Fenestration Requirements Changes to Table R Climate Zone 5: Increased efficiency of windows from.35 U- value to.32 an skylights from.60 to.55; Increase ceiling insulation from R-38 to R49; Increased basement and crawl space R- value from 10/13 to 15/19. Climate Zone 6: Increased efficiency of windows from.35 U-value to.32 an skylights from.60 to.55; Increased Wood frame wall R-value from R20 or 13+5 to R20+5 or 13+10; Increased Mass wall R-value for insulation on interior from R19 to R20. Footnote changes: a: Instead of specifically calling out the compression of R19 batts and their labeled R- values, it changed to apply to all compressed insulations b: removed the exception for skylights in climate zones 1-3 where the SHGC didn t exceed.30 c: When adding the R-5 in 13+5 situations, it now specifies that the R-5 is continuous insulated sheathing. d-g remain unchanged h: In 13+5 situation the R-5 now is either continuous insulation or insulated siding and The structural sheathing issue in footnote h has changed to say that if structural sheathing covers 40% or less of the exterior, continuous insulation R-value shall be permitted to be reduced by no more than R-3 in the locations where structural sheathing is used to maintain a consistent total sheathing thickness Colorado Code Consulting, LLC 80 Building Thermal Envelope, Cont. Eave baffle R For air permeable insulations in vented attics, a baffle shall be installed adjacent to soffit and eave vents. The baffle shall maintain an opening equal or greater than the size of the vent, extend over the top of the insulation and be permitted to be any solid material Colorado Code Consulting, LLC Colorado Code Consulting, LLC 27

28 R402.4 Air Leakage R Building thermal envelope. The building thermal envelope shall comply with Sections R and R TESTING is not an option anymore. R Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate No longer 7 ACH (50) across the board Requirements to demonstrate compliance Whole-house pressure test Air Leakage Rate Climate Zone Testing may occur any time after creation of all building envelope penetrations Field verification of items listed in Table R Test Pressure 5 ACH Pascals 3 ACH Pascals R403.2 Ducts R Sealing (Mandatory). Ducts, air handlers, and filter boxes shall be sealed. Joints and seams shall comply with either the IMC or IRC, as applicable Duct testing is mandatory for ducts and air handlers located outside the thermal envelope but the duct tightness was ratcheted down. Rough-in test before air handler 4 cfm 100 ft2 Rough-in after air handler 4 cfm Post construction 4 cfm 2009 Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 28

29 Duct Sealing (Mandatory) R R Sealed air handler. Air handlers shall have a manufacturer s designation for an air leakage of no more than 2 percent of the design air flow rate when tested in accordance with ASHRAE 193 R Building Cavities (Mandatory) Building framing cavities shall not be used as ducts or plenums. (NEITHER SUPPLY NOR RETURN!) R403.4 Service hot water systems Pipe insulation protection requirements found in R R Hot water pipe insulation (Prescriptive): New laundry list of hot water piping that has to be insulated to a minimum of R-3. R403.4 Service hot water systems R Hot water pipe insulation (Prescriptive): All remaining piping shall be insulated to at least R-3 or meet the run length requirements of Table R Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 29

30 Whole House Mechanical Ventilation R403.5 (Mandatory) Ventilation Building to have ventilation meeting IRC or IMC or with other approved means Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating Whole-house mechanical ventilation system fans to meet efficacy in Table R Exception When fans are integral to tested and listed HVAC equipment, powered by electronically commutated motor 2009 Colorado Code Consulting, LLC 88 Whole House Mechanical Ventilation R403.5 (Mandatory) TABLE R MECHANICAL VENTILATION SYSTEM FAN EFFICACY AIR FLOW RATE AIR FLOW RATE MINIMUM EFFICACY FAN LOCATION MINIMUM MAXIMUM (CFM/WATT) (CFM) (CFM) Range hoods Any 2.8 cfm/watt Any In-line fan Any 2.8 cfm/watt Any Bathroom, utility room cfm/watt < 90 Bathroom, utility room cfm/watt Any 2011 Colorado Code Consulting, LLC 89 Whole House Mechanical Ventilation IRC 1507 (Mandatory) The whole-house ventilation system shall consist of one or more supply or exhaust fans, or a combination of such, and associated ducts and controls. Local exhaust or supply fans are permitted to serve as such a system. Outdoor air ducts connected to the return side of an air handler shall be considered to provide supply ventilation. The wholehouse mechanical ventilation system shall provide outdoor air at a continuous rate of not less than that determined in accordance with Table M (1). Exception: Is permitted to operate intermittently where the system has controls that enable operation for not less than 25-percent of each 4-hour segment and the ventilation rate prescribed in Table M (1) is multiplied by the factor determined in accordance with Table M (2) Colorado Code Consulting, LLC Colorado Code Consulting, LLC 30

31 Whole House Mechanical Ventilation IRC 1507 (Mandatory) Electrical Power and Lighting R404 (Mandatory) Simulated Performance Alternative R405 Changed from a minimum of 50% of the lamps in permanently installed lighting fixtures having to be high-efficacy lamps to a minimum of 75%. Low voltage lighting doesn t have to utilize high-efficiency lamps Fuel gas lighting systems shall not have continuously burning pilot lights. Table R (1) had changes to how glazing is looked at in the standard reference design Changes made to both standard reference design and proposed design for Air Exchange Rates Changes to the standard reference design as it relates to electric heating Changed the proposed design requirements for duct system efficiency 2011 Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 31

32 Colorado Code Consulting, LLC Shaunna Mozingo Colorado Code Consulting, LLC 4610 S Ulster Street, Suite 150 Denver, Colorado Ph smozingo@coloradocode.net 2011 Colorado Code Consulting, LLC Colorado Code Consulting, LLC Colorado Code Consulting, LLC 32

IECC Commercial Significant Changes Summary Tier I

IECC Commercial Significant Changes Summary Tier I 2009-2015 IECC Commercial Significant Changes Summary Tier I The first change is in the layout of the book. Instead of having Chapters 1-3 that applied to all projects and then having Chapter 4 Residential

More information

Boulder City NV Prepared by (Print Name) Signature Date

Boulder City NV Prepared by (Print Name) Signature Date City of Boulder City Community Development Department Building & Safety Division 401 California Avenue Boulder City, NV 89005-2600 702-293-9282 (Main Line) 702-293-9392 (Fax) 2009 International Energy

More information

A LOOK INTO THE 2015 IECC RESIDENTIAL PROVISIONS. Presented by: Shaunna Mozingo, Colorado Code Consulting

A LOOK INTO THE 2015 IECC RESIDENTIAL PROVISIONS. Presented by: Shaunna Mozingo, Colorado Code Consulting A LOOK INTO THE 2015 IECC RESIDENTIAL PROVISIONS Presented by: Shaunna Mozingo, Colorado Code Consulting WHAT CAN WE EXPECT TO SEE? Some consensus on enough is enough for now - No real roll backs, no real

More information

Instructions for the Residential Building Data Collection Checklist 2009 International Energy Conservation Code with 2011 Georgia Amendments

Instructions for the Residential Building Data Collection Checklist 2009 International Energy Conservation Code with 2011 Georgia Amendments Instructions for the Residential Building Data Collection Checklist 2009 International Energy Conservation Code with 2011 Georgia Amendments Use of these instructions with a residential data collection

More information

Hardin County Planning and Development Commission

Hardin County Planning and Development Commission Location by Climate Zone: Hardin County (per Table N1101.2), and the entire state of Kentucky is located in Climate Zone 4, the HDD is 4000 to 4999. Building Requirements; Building Thermal Envelope The

More information

Compliance Certificate

Compliance Certificate REScheck Software Version 4.6.4 Compliance Certificate Project RESIDENCE Energy Code: 2009 IECC Location: Perkasie, Pennsylvania Construction Type: Single-family Project Type: New Construction Conditioned

More information

Fenestration Components: Mechanical Summary. Water heater energy factor: Ef Fuel type: Gas Electric Other

Fenestration Components: Mechanical Summary. Water heater energy factor: Ef Fuel type: Gas Electric Other This information must be on the drawing documents not attached to plans. The following Compliance statements must be on the drawings: 2009 International Energy Conservation Code Statement of acknowledgement

More information

Michigan Energy Code Training and Implementation Program

Michigan Energy Code Training and Implementation Program Michigan Energy Code Training and Implementation Program 1.0 Hour Advanced Program Course Number 16202 Residential Energy Plan Review School of Planning, Design & Construction Michigan State University

More information

Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort

Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort Please add relevant logo here Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort Presented by: Peter J. Arsenault, FAIA, NCARB, LEED-AP Disclaimer: This presentation was developed by

More information

RESIDENTIAL ENERGY EFFICIENCY

RESIDENTIAL ENERGY EFFICIENCY CHAPTER 4 RESIDENTIAL ENERGY EFFICIENCY SECTION 401 GENERAL 401.1 Scope. This chapter applies to residential buildings. 401.2 Compliance. Projects shall comply with Sections 401, 402.4, 402.5, and 403.1,

More information

Single Family Residence Building Permits

Single Family Residence Building Permits Village of Northbrook Department of Building & Development Guide to: Designing, Documenting & Inspecting For Energy Code Compliance Single Family Residence Building Permits New Construction Additions Alterations

More information

Interpretation Variables and Common Areas of Confusion. Of the 2009 IECC

Interpretation Variables and Common Areas of Confusion. Of the 2009 IECC Interpretation Variables and Common Areas of Confusion Of the 2009 IECC 1. (Mandatory) provisions vs. (Prescriptive) provisions: The IECC contains flexibility by allowing different approaches to achieve

More information

2012 International Energy Conservation Code for Simple Commercial Buildings

2012 International Energy Conservation Code for Simple Commercial Buildings Compliance Guide 2012 International Energy Conservation Code for Simple Commercial Buildings Britt/Makela Group Ryan Meres, Institute for Market Transformation The Institute for Market Transformation (IMT),

More information

Energy Code Basics for Residential Buildings. Presented by Newport Ventures NEWPORT VENTURES

Energy Code Basics for Residential Buildings. Presented by Newport Ventures NEWPORT VENTURES Energy Code Basics for Residential Buildings Presented by Newport Ventures Course Overview / Introduction 1. Overview of definitions and compliance changes 2. Building envelope requirements including air

More information

THE GEORGIA ENERGY CODE: 2009 IECC + AMENDMENTS

THE GEORGIA ENERGY CODE: 2009 IECC + AMENDMENTS THE GEORGIA ENERGY CODE: 2009 IECC + AMENDMENTS For the Georgia Association of Home Inspectors Bourke Reeve ABOUT SOUTHFACE 1 EARTHCRAFT Regional Green Building Program HISTORY OF ENERGY CODES MEC 1992,

More information

November 10, 2015 Baltimore, MD. presented by

November 10, 2015 Baltimore, MD. presented by Baltimore, MD 2015 I code R values and best practices presented by Mark S. Graham Associate Executive Director, Technical Services National Roofing Contractors Association (NRCA) 1 IBC 2015: Ch. 15: Roofing

More information

APPROVED. Acceptable to the code official for compliance with the provisions of the applicable Code or referenced Standard.

APPROVED. Acceptable to the code official for compliance with the provisions of the applicable Code or referenced Standard. Chapter 1 101.1 Title. These regulations shall be known as the North Carolina Energy Conservation Code as approved by the North Carolina Building Code Council on March 11, 2008, to be effective January

More information

Michigan Energy Code Training and Implementation Program

Michigan Energy Code Training and Implementation Program Michigan Energy Code Training and Implementation Program 1.0 Hour Advanced Program Course Number 16201 Residential Energy Air Sealing School of Planning, Design & Construction Michigan State University

More information

Plan Check & Field Inspection Guide

Plan Check & Field Inspection Guide Plan Check & Field Inspection Guide 1992 MEC, 1993 MEC, and 1995 MEC Inside This Guide Plan Check Field Inspection Plan Check Building plans and specifications must be submitted with each building application

More information

2012 IECC Residential with State Adopted Changes

2012 IECC Residential with State Adopted Changes 2012 IECC Residential with State Adopted Changes Salt Lake County Townships 385-468-6694 801-381-1449 bursenbach@slco.org bursenbach@yahoo.com BUILDING TALK 1 2 The Family of I-Codes International Building

More information

Date Rater Verified. Rater Verified. Slab / Pre-Drywall / Thermal Inspection

Date Rater Verified. Rater Verified. Slab / Pre-Drywall / Thermal Inspection Slab on Grade & Basements: A capillary break is installed on top of all footings Slab / Pre-Drywall / Thermal Inspection A minimum of 4" of clean or washed gravel (0.5" diameter or greater) is placed over

More information

Chapter 2: Foundation

Chapter 2: Foundation Chapter 2: Foundation Crawlspace [V502.1.2] [V502.1.2] [V502.1.3] Vents. Vents in the crawlspace help keep floor insulation and floor framing dry. Crawlspace vents also reduce the potential for radon buildup

More information

Italcementi Center for Research and Innovation

Italcementi Center for Research and Innovation Italcementi Center for Research and Innovation Bergamo, Italy LEED-NC v2.1 EAc1 A. Project Narrative (Viridian) analyzed the energy use of the proposed Italcementi Center for Research and Innovation located

More information

780 CMR: 9 th Edition Massachusetts State Building Code. Presented to: BSA Codes Committee. DATE: January 20, 2016

780 CMR: 9 th Edition Massachusetts State Building Code. Presented to: BSA Codes Committee. DATE: January 20, 2016 780 CMR: 9 th Edition Massachusetts State Building Code Presented to: BSA Codes Committee DATE: January 20, 2016 This course is registered with AIA CES for continuing professional education. Credit(s)

More information

BUILDING ENERGY CODES UNIVERSITY

BUILDING ENERGY CODES UNIVERSITY BUILDING ENERGY CODES UNIVERSITY Changes to Residential Provisions of the 2012 International Energy Conservation Code Edited & Presented by Donald Vigneau AIA Additional Editing by Kevin Rose PNNL-SA-82108

More information

Recommended Amendments to the 2012 International Residential Code (IRC)

Recommended Amendments to the 2012 International Residential Code (IRC) Issue: Insulation Requirements by Components- Basement Wall R-value and U-value 2012 IECC Section: Table N1102.1.1 and Table N1102.1.3 Modify the Tables as shown below: (Delete data, add new data) CLIMATE

More information

Insulation, Fireblocking, Draftstopping and Crawl Space Requirements REVISION DATE: JANUARY 2017

Insulation, Fireblocking, Draftstopping and Crawl Space Requirements REVISION DATE: JANUARY 2017 City of Republic Community Development Department Insulation, Fireblocking, Draftstopping and Crawl Space Requirements REVISION DATE: JANUARY 2017 Insulation Requirements Insulation (2012 IRC Section R302.10.1):

More information

Rhode Island Commercial Codes FAQs

Rhode Island Commercial Codes FAQs Rhode Island Commercial Codes FAQs When does the new code go into effect? The new suite of building codes (including the new state energy conservation code, SBC-8) was adopted on July 1, 2013. A brief

More information

C H A P T E R 3. Completing the Residential Analysis Worksheet STEP 1: WINDOWS AND OTHER GLASS AREAS

C H A P T E R 3. Completing the Residential Analysis Worksheet STEP 1: WINDOWS AND OTHER GLASS AREAS C H A P T E R 3 Completing the Residential Analysis Worksheet The Residential Analysis Worksheet is designed to help the reader in making the preliminary calculations necessary to complete Forms 600A-04,

More information

Chapter 1: Compliance

Chapter 1: Compliance Chapter 1: Compliance [101] Who Must Comply? All new residential construction must comply with the Washington State Energy Code (WSEC). Exceptions. Exempt from envelope requirements but needing to comply

More information

SAN MIGUEL COUNTY & TOWN OF MOUNTAIN VILLAGE BUILDING DEPARTMENTS PRESCRIPTIVE ENERGY CODE & GREEN BUILDING STANDARD

SAN MIGUEL COUNTY & TOWN OF MOUNTAIN VILLAGE BUILDING DEPARTMENTS PRESCRIPTIVE ENERGY CODE & GREEN BUILDING STANDARD SAN MIGUEL COUNTY & TOWN OF MOUNTAIN VILLAGE BUILDING DEPARTMENTS PRESCRIPTIVE ENERGY CODE & GREEN BUILDING STANDARD The Prescriptive Energy Code & Green Building Standard requirements for San Miguel County

More information

Building Codes and Ordinances ARC 227

Building Codes and Ordinances ARC 227 Building Codes and Ordinances ARC 227 Week 6 Fire Resistive Construction 03.02.10 Instructor: Rick Staub, AIA Email: staub@pointonearchitects.com Phone: 860-434-7707 Fire Resistive Construction Passive

More information

1998 and 2000 International Energy Conservation Code Version 3.0 April 2000

1998 and 2000 International Energy Conservation Code Version 3.0 April 2000 1998 and 2000 International Energy Conservation Code Version 3.0 April 2000 MECcheck TM was developed by the Building Energy Standards Program at Pacific Northwest National Laboratory for use by the U.S.

More information

ASHRAE 62.2: What s New in 2016

ASHRAE 62.2: What s New in 2016 ASHRAE 62.2: What s New in 2016 Rick Karg 2016 Residential Energy Dynamics, LLC What We Will Talk About Overview of mechanics of 62.2-2016. Logic behind the Standard. Sizing local ventilation (exhaust-only).

More information

ORDINANCE NO. An ordinance amending Chapter 59, Dallas Energy Conservation Code, of the Dallas City

ORDINANCE NO. An ordinance amending Chapter 59, Dallas Energy Conservation Code, of the Dallas City 12-19-16 ORDINANCE NO. 3 0 32 5 An ordinance amending Chapter 59, Dallas Energy Conservation Code, of the Dallas City Code, as amended; adopting with certain changes the 2015 Edition of International Energy

More information

Spray Polyurethane Foam. Insulation and Air Barrier Requirements of the 2012 I-Codes. Spray Foam Coalition

Spray Polyurethane Foam. Insulation and Air Barrier Requirements of the 2012 I-Codes. Spray Foam Coalition Spray Polyurethane Foam Design Guidance Insulation and Air Barrier Requirements of the 2012 I-Codes Spray Foam Coalition about the collaboration the center for the polyurathanes industry (CPI) of the

More information

New Hampshire Residential Energy Code

New Hampshire Residential Energy Code CHAIRMAN STATE OF NEW HAMPSHIRE EXECUTIVE DIRECTOR Thomas B. Getz AND SECRETARY COMMISSIONERS Debra A. Howland Susan S. Geiger TDD Access: Relay NH Nancy Brockway 1-800-735-2964 Tel. (603) 271-2431 FAX

More information

Montana Homebuilder Brief: Residential Energy Code 1

Montana Homebuilder Brief: Residential Energy Code 1 1 Montana homebuyers appreciate the comfort and warmth of the energyefficient homes based on the energy code. All new houses in Montana must meet the minimum requirements of the 2012 International Energy

More information

Module number 6 provides an on-line, self-paced training seminar on energy efficiency and energy conservation for residential buildings.

Module number 6 provides an on-line, self-paced training seminar on energy efficiency and energy conservation for residential buildings. Module number 6 provides an on-line, self-paced training seminar on energy efficiency and energy conservation for residential buildings. 1 This chapter sets forth the requirements for energy efficiency

More information

2011 NORTHERN NEVADA ENERGY CODE AMENDMENTS

2011 NORTHERN NEVADA ENERGY CODE AMENDMENTS 2011 NORTHERN NEVADA ENERGY CODE AMENDMENTS 2009 INTERNATIONAL ENERGY CONSERVATION CODE Published by the Northern Nevada Chapter of the International Code Council: March 30, 2012 Carson City City of Sparks

More information

Senior Design Project for UNO. Design of the International Studies Building: An Environmental Analysis

Senior Design Project for UNO. Design of the International Studies Building: An Environmental Analysis Senior Design Project for UNO Design of the International Studies Building: An Environmental Analysis Design Intent Implement Passive & Active design strategies in order to make the building: More Energy

More information

General Residential Code Requirements

General Residential Code Requirements Residential building code review will be based on compliance with the requirements of the Louisiana State Uniform Construction code in accordance with ACT 12 of the 2005 First Extraordinary Session of

More information

ENERGY STAR Qualifying Criteria for Residential Windows, Doors, and Skylights Sold in Canada Version 3.0 October 1, 2010

ENERGY STAR Qualifying Criteria for Residential Windows, Doors, and Skylights Sold in Canada Version 3.0 October 1, 2010 ENERGY STAR Qualifying Criteria for Residential Windows, Doors, and Skylights Sold in Canada Below is the product criteria for ENERGY STAR qualified residential windows, doors, and skylights sold in Canada

More information

Thermal Bridging in Residential Construction

Thermal Bridging in Residential Construction PHRC Webinar Series Tuesday, May 12, 2015 @ 1pm Thermal Bridging in Residential Construction Brian Wolfgang Housing Systems Specialist Pennsylvania Housing Research Center 219 Sackett Building University

More information

Slab edge insulation is one of

Slab edge insulation is one of How to Properly Insulate a Slab Presented by: Mike Turns, Associate Director, PHRC Tuesday, April 10, 2012 1:00 PM www.enrg.psu.edu/phrc 4 Slab edge insulation is one of the most abused details in construction.

More information

KITCHEN REMODELS CITY OF MISSION VIEJO BUILDING SERVICES DIVISON 200 CIVIC CENTER, MISSION VIEJO, CA (949)

KITCHEN REMODELS CITY OF MISSION VIEJO BUILDING SERVICES DIVISON 200 CIVIC CENTER, MISSION VIEJO, CA (949) CITY OF MISSION VIEJO BUILDING SERVICES DIVISON 200 CIVIC CENTER, MISSION VIEJO, CA 92691 (949) 470-3054 KITCHEN REMODELS A permit is required for kitchen remodels that include removal and replacement

More information

The ASHRAE Energy Code: How it Will Affect Your Projects

The ASHRAE Energy Code: How it Will Affect Your Projects The ASHRAE 90.1-2010 Energy Code: How it Will Affect Your Projects Presenter Jeff Boldt, PE, LEED AP, HBDP KJWW Engineering Principal Director of Engineering Voting Member ASHRAE SSPC-90.1 Member SSPC

More information

Inspection of New One- and Two- Family Dwellings

Inspection of New One- and Two- Family Dwellings Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: permitservices@opkansas.org Inspection of New One- and Two- Family Dwellings Planning and Development

More information

2012 INTERNATIONAL CODES SIGNIFICANT CHANGES

2012 INTERNATIONAL CODES SIGNIFICANT CHANGES 2012 INTERNATIONAL CODES SIGNIFICANT CHANGES TIM PATE CHIEF BUILDING OFFICIAL CITY AND COUNTY OF BROOMFIELD 2012 IRC 1. Section R302.1 has been modified to allow reduced fire separation distances when

More information

CHAPTER 1: OVERVIEW OF ENERGY EFFICIENT CONSTRUCTION

CHAPTER 1: OVERVIEW OF ENERGY EFFICIENT CONSTRUCTION Chapter 1: Overview of Energy Efficient Construction 1 CHAPTER 1: OVERVIEW OF ENERGY EFFICIENT CONSTRUCTION Chapter 1 is a quick reference guide that discusses the key components and features of energy

More information

2015 IECC Residential Basic Principles Updates with State Amendments

2015 IECC Residential Basic Principles Updates with State Amendments 2 2015 IECC Residential Basic Principles Updates with State Amendments Funding for Energy Code Training Utah Office of Energy Development Building Talk Program U.S. Department of Energy energy codes.gov

More information

PREP + INSULATION. DISCLAIMER: These tools are for illustrative purposes only and

PREP + INSULATION. DISCLAIMER: These tools are for illustrative purposes only and PREP + INSULATION HOME ENERGY UPGRADES What every contractor needs to know. Copyright 2012 Advanced Energy. All Rights Reserved 103 HOME ENERGY UPGRADES Prep + Insulation Contents Air sealing is a challenging

More information

Florida HERO Program Residential Eligible Product List All Products

Florida HERO Program Residential Eligible Product List All Products All Products In addition to the HERO Product Eligibility Specifications listed below, it is the sole responsibility of the HERO Contractor and property owner (Project Stakeholders) to meet or exceed applicable

More information

Administrative Changes

Administrative Changes Revised 11/29/06 Knox County Residential Building Codes Significant Changes From The 1995 CABO One And Two Family Dwelling Code To The 2006 International Residential Code All one and two family dwellings

More information

Great Ocean Rd Ice Creamery

Great Ocean Rd Ice Creamery Great Ocean Rd Ice Creamery BCA Section J - JV3 Compliance Report Revision: 01 Job No: 2171 Date: 7 July 2015 ADP Consulting Pty Ltd Level 10, 10 Queens Rd, Melbourne Vic 3004 www.adpconsulting.com.au

More information

2012 CLEAResult All rights reserved. Residential Energy Efficiency

2012 CLEAResult All rights reserved. Residential Energy Efficiency Residential Energy Efficiency Presenter Bio Jaymar Davis, PE, CEM, CLEP, CMVP, CEA Sr. Field Engineering Manager 10 Years experience in energy efficiency Johnson Controls, Kohler Co. Certifications: Licensed

More information

California HERO Program Residential Eligible Product List All Products

California HERO Program Residential Eligible Product List All Products All Products In addition to the HERO Product Eligibility Specifications listed below, it is the sole responsibility of the HERO Contractor and property owner (Project Stakeholders) to meet or exceed applicable

More information

Air Barrier Requirements for Low-Slope Roof Assemblies Myths vs. Facts

Air Barrier Requirements for Low-Slope Roof Assemblies Myths vs. Facts Air Barrier Requirements for Low-Slope Roof Assemblies Myths vs. Facts Peter Kalinger Canadian Roofing Contractors Association Dr. B. Baskaran National Research Council of Canada 1 Air Leakage Controlling

More information

SUPPLEMENT FOR EDGE USER GUIDES V.2.0. Date of Publication: Refer to the EDGE website for the most recently published supplement

SUPPLEMENT FOR EDGE USER GUIDES V.2.0. Date of Publication: Refer to the EDGE website for the most recently published supplement SUPPLEMENT FOR EDGE USER GUIDES V.2.0 Date of Publication: 2017.04.19 Refer to the EDGE website for the most recently published supplement SUPPLEMENT FOR EDGE USER GUIDES VERSION 2.0 INTRODUCTION This

More information

CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8)

CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8) CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8) Builder or Installer Name Builder or Installer Contact Telephone Plan/Permit (Additions or Alterations) Number Compliance Method (Prescriptive)

More information

Advanced Ventilation for Residential applications FBC Res 2010.

Advanced Ventilation for Residential applications FBC Res 2010. Advanced Ventilation for Residential applications FBC Res 2010. Course Description Review of the Residential Ventilation requirements in the Florida Building Code, Residential 2010. I. Introduction Dean

More information

INTERIOR ENVIRONMENT

INTERIOR ENVIRONMENT CHAPTER 12 INTERIOR ENVIRONMENT > SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter shall govern ventilation, temperature control, lighting, yards and courts, sound transmission, room dimensions,

More information

NEW HOMES PROGRAM 2017 PROGRAM GUIDE

NEW HOMES PROGRAM 2017 PROGRAM GUIDE NEW HOMES PROGRAM 2017 PROGRAM GUIDE Focus on Energy, Wisconsin utilities statewide program for energy efficiency and renewable energy, helps eligible residents and businesses save energy and money while

More information

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal The following documentation provides an example submittal for the LEED-NC v2.1 Energy & Atmosphere Credit 1 (EAc1). This sample EAc1 submittal

More information

Green Building Guideline of Jordan

Green Building Guideline of Jordan Green Building Guideline of Jordan T. Awadallah 1*, S. Habet 1, A. Mahasneh 1, H. Adas 2 1 Royal Scintific Society, Amman, Jordan 2 National Energy Research Center, Amman, Jordan * Corresponding author.

More information

California Building Envelope Solutions

California Building Envelope Solutions California Building Envelope Solutions Attics & Walls October 2017 What s New in 2016 Title 24 Attics High Performance Attic New prescriptive requirements Roof deck insulation in many CZs Walls High Performance

More information

INTERIOR ENVIRONMENT

INTERIOR ENVIRONMENT CHAPTER 12 INTERIOR ENVIRONMENT SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter shall govern ventilation, temperature control, lighting, yards and courts, sound transmission, room dimensions,

More information

One and Two Family Additions

One and Two Family Additions One and Two Family Additions An addition to a house, duplex, garage, or an accessory structure requires a building permit prior to performing any construction. Building Department & Permit Office Mon-Fri

More information

HERO Program Residential Eligible Product List California Residential Eligible Products... 2

HERO Program Residential Eligible Product List California Residential Eligible Products... 2 HERO Program Residential Eligible Product List California Residential Eligible Products... 2 Renewable and Alternative Energy... 2 Alternative Energy... 2 Solar Electric... 3 Solar Thermal... 3 Energy

More information

The Role of Control Layers in Building Enclosure Design

The Role of Control Layers in Building Enclosure Design The Role of Control Layers in Building Enclosure Design COLIN SHANE M.ENG., P.ENG. ASSOCIATE, SENIOR PROJECT MANAGER OCTOBER 13, 2016 Disclaimer: This presentation was developed by a third party and is

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma LEED Green Building Certification The purpose of the LEED Green Building Rating is to provide a national standard that aims to improve environmental, health and economic performance of buildings using

More information

A/E Design Deliverable Checklist

A/E Design Deliverable Checklist A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic

More information

Green Remodeling Illustrations GREEN REMODELING ILLUSTRATIONS GREEN BUILDING GUIDELINES FOR HOME REMODELING

Green Remodeling Illustrations GREEN REMODELING ILLUSTRATIONS GREEN BUILDING GUIDELINES FOR HOME REMODELING Green Remodeling Illustrations GREEN REMODELING ILLUSTRATIONS GREEN BUILDING GUIDELINES FOR HOME REMODELING WWW.STOPWASTE.ORG New Addition Consider the following green remodeling options in a new addition.

More information

1. When using the REScheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

1. When using the REScheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is. Energy Conservation Code Residential Building CHAPTER 4 WORKSHEET 1. When using the REScheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is _

More information

Radon Vent Pipe System. Labeling Performance Indicators

Radon Vent Pipe System. Labeling Performance Indicators Section 6 Radon Vent Pipe Labeling Performance Indicators Radon Vent Pipe System Connected after sub-grade system installed Pipe cannot be trapped Provide space in chases Support at each floor level Discharge

More information

Part IV Energy Conservation

Part IV Energy Conservation OUBCC / Oklahoma version of the 2015 IRC Chapter 11 - AKA the Oklahoma Residential Energy Code Part IV Energy Conservation CHAPTER 11 ENERGY EFFICIENCY N1101.1 Scope. This chapter regulates the energy

More information

Green Building Guideline of Jordan

Green Building Guideline of Jordan Green Building Guideline of Jordan T. Awadallah 1*, S. Habet 1, A. Mahasneh 1, H. Adas 2 1 Royal Scientific Society, Amman, Jordan 2 National Energy Research Center, Amman, Jordan * Corresponding author.

More information

Energy Trigger (A Existing Building Upgrade Mechanism Model)

Energy Trigger (A Existing Building Upgrade Mechanism Model) Trigger (A-11.2.1.2 Existing Building Upgrade Mechanism Model) Applicability All Building Permit applications for projects related to existing buildings are required to follow the energy upgrade trigger

More information

Ontario s Building Code

Ontario s Building Code Ministry of Municipal Affairs and Housing Ontario s Building Code ONTARIO ONLY PROPOSED CHANGE TO THE 2006 BUILDING CODE CHANGE NUMBER E-B-12-03-05 CODE REFERENCE Div. B 12.3.4.1. 12.3.4.2. DESCRIPTION

More information

RESIDENTIAL BUILDING REQUIREMENTS

RESIDENTIAL BUILDING REQUIREMENTS RESIDENTIAL BUILDING REQUIREMENTS Residential Building Requirements This is an informational booklet with some of the general residential construction requirements taken from the codes adopted by Campbell

More information

Phase Two Change Proposal for the Next Edition of the Building Code: 2-CC-B POTENTIAL CHANGE TO ONTARIO S BUILDING CODE:

Phase Two Change Proposal for the Next Edition of the Building Code: 2-CC-B POTENTIAL CHANGE TO ONTARIO S BUILDING CODE: Phase Two Change Proposal for the Next Edition of the Building Code: 2-CC-B-12-02-05 POTENTIAL CHANGE TO ONTARIO S BUILDING CODE: SUMMER AND FALL 2017 CONSULTATION Ministry of Municipal Affairs PROPOSED

More information

Compliance to the IgCC. September 29, 2011

Compliance to the IgCC. September 29, 2011 Bringing Outcome-Based Compliance to the IgCC September 29, 2011 Outcome-Based Codes: Any code requirement or code enforcement mechanism based on actual outcomes in buildings after they have been occupied.

More information

March 11, 2004 Prepared for: Cool Metal Roofing Coalition Gregory L. Crawford, Executive Director

March 11, 2004 Prepared for: Cool Metal Roofing Coalition Gregory L. Crawford, Executive Director Report An Analysis of Metal Roofing Compliance Options for California s Title 24 2005 Energy Standard March 11, 2004 Prepared for: Cool Metal Roofing Coalition Gregory L. Crawford, Executive Director Architectural

More information

2012 IRC Sections R303 R310 Building Planning II

2012 IRC Sections R303 R310 Building Planning II Study Session 3 2012 IRC Sections R303 R310 Building Planning II OBJECTIVE: To develop an understanding of the health and safety criteria of the code, including light and ventilation; minimum room areas

More information

Airspace R-Values. Educational Overview. Revised 12/6/2016

Airspace R-Values. Educational Overview. Revised 12/6/2016 Airspace R-Values Educational Overview Revised 12/6/2016 Introduction Airspaces contained within building envelope assemblies are known to contribute to thermal performance. But, the actual R-value for

More information

FLORIDA BUILDING CODE, Energy Conservation

FLORIDA BUILDING CODE, Energy Conservation FLORIDA BUILDING CODE, Energy Conservation Although Florida s energy code has been in effect statewide since 1979, it is now based on the International Energy Conservation Code (IECC). It is a minimum

More information

Page 1. ASHRAE STANDARD Section. COMMENTS This is opinion and not comprehensive.

Page 1. ASHRAE STANDARD Section. COMMENTS This is opinion and not comprehensive. OVERVIEW. 1 PURPOSE. The purpose of this standard is to provide minimum requirements for the energyefficient design of buildings except low rise residential buildings. COMPARISON BETWEEN THE 2009 ICC INTERNATIONAL

More information

2012 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs

2012 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs Class Outline Inspection of Fire-resistance-Rated Floors, Ceilings and Roofs Based on 2012 International Building Code (IBC) Introduction Determining fire resistance Test standards Definitions Alternate

More information

Fenestration Energy Performance:

Fenestration Energy Performance: number 9 Builder Insight Fenestration Energy Performance: A Roadmap for Understanding Requirements for Residential Buildings in British Columbia Overview Energy performance requirements for windows, doors

More information

2015 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs

2015 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs Class Outline Inspection of Fire-Resistance-Rated Floors, Ceilings and Roofs Based on 2015 International Building Code, (IBC ) Introduction Determining fire resistance Test standards Definitions Alternate

More information

E d u c a t i o n a l S e m i n a r s f o r B u i l d i n g & R e s i d e n t i a l C o d e

E d u c a t i o n a l S e m i n a r s f o r B u i l d i n g & R e s i d e n t i a l C o d e I N D E X E d u c a t i o n a l S e m i n a r s f o r B u i l d i n g & R e s i d e n t i a l C o d e Title Course Number *Seminar Length (days) Pg. Class Scheduling Policies 8 International Building Code

More information

Zero Carbon Building Energy Modelling Guidelines. October 31, 2017

Zero Carbon Building Energy Modelling Guidelines. October 31, 2017 Zero Carbon Building Energy Modelling Guidelines October 31, 2017 Contents 1. INTRODUCTION... 3 1.1 DEFINITIONS... 4 2. CALCULATING TEDI... 5 2.1 INTERNAL HEAT GAINS... 6 2.2 CALCULATING BUILDING ENVELOPE

More information

CITY OF ORANGE BUILDING DIVISION 2016 Green Building Code Requirements For Residential Construction

CITY OF ORANGE BUILDING DIVISION 2016 Green Building Code Requirements For Residential Construction CITY OF ORANGE BUILDING DIVISION 2016 Green Building Code Requirements For Residential Construction In order to facilitate sustainable construction practices, all new projects* must comply with the State

More information

Is Yours? Homes Across Missouri are Being Built to the Latest National Energy Efficiency Standards

Is Yours? Homes Across Missouri are Being Built to the Latest National Energy Efficiency Standards Homes Across Missouri are Being Built to the Latest National Energy Efficiency Standards Is Yours? A home buyers guide to the energy efficiency requirements of the 2012 International Energy Conservation

More information

2003 International Residential Building Code

2003 International Residential Building Code 2003 International Residential Building Code Section R305 Ceiling Height Habitable rooms, hallways, corridors, bathrooms, toilet rooms, laundry rooms and basements shall have a ceiling height of not less

More information

Vermont Residential Building Energy Code. Handbook

Vermont Residential Building Energy Code. Handbook Vermont Residential Building Energy Code Handbook A Guide to Complying with Vermont s Residential Building Energy Standards (Act 20, 1997 & Act 45, 2009) Edition 3.0 October 2011 Effective October 1, 2011

More information

Applying the Building Code During Design

Applying the Building Code During Design Applying the Building Code During Design A Step-By-Step Process AIA Learning Units The Salt Lake City CSI Chapter is a Registered Provider with The American Institute of Architects Continuing Education

More information

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION CHAPTER 26 PLASTIC SECTION BC 2601 GENERAL 2601.1 Scope. These provisions shall govern the materials, design, application, construction and installation of foam plastic, foam plastic insulation, plastic

More information

Oregon High Performance Home Requirements

Oregon High Performance Home Requirements Oregon High Performance Home Requirements A Business Energy Tax Credit for Homebuilders Homebuilders who construct homes to the Oregon High Performance Home (HPH) standard are now eligible for the Business

More information

ESR-2072 Reissued September 1, 2013 This report is subject to renewal September 1, 2015.

ESR-2072 Reissued September 1, 2013 This report is subject to renewal September 1, 2015. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-2072 Reissued September 1, 2013 This report is subject to renewal September 1, 2015. A Subsidiary of the International Code Council

More information