SUBMITTALS Descriptive literature: Submit manufacturer's application instructions and technical data sheets or catalog cuts on materials.

Size: px
Start display at page:

Download "SUBMITTALS Descriptive literature: Submit manufacturer's application instructions and technical data sheets or catalog cuts on materials."

Transcription

1 PART I GENERAL APPLICABLE PUBLICATIONS The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only. 1. American Society for Testing and Materials Publication (ASTM) 2. ENERGY STAR guidelines for energy efficiency (Roof Coatings) 3. CRRC Cool Roof Rating Council 4. California Building Standards Code - Title 24 QUALITY CONTROL 1. Contractor shall be an approved applicator by Tropical Roofing Products who has a general knowledge and understanding of standard roofing practices as defined by the NRCA and knowledge of the Tropical Roofing Products materials to be used herein this specification. 2. Prior to starting the application of the roofing system, there will be a project conference with the owner's representative to assure a clear understanding of the specifications. The conference shall be attended by the Contractor and by Tropical Roofing Products representative. 3. For all warranties, a licensed contractor, authorized by Tropical Roofing Products as an approved applicator with proven business stability should be used to ensure proper installation. SUBMITTALS Descriptive literature: Submit manufacturer's application instructions and technical data sheets or catalog cuts on materials. DELIVERY, STORAGE AND HANDLING 1. Store and handle Tropical Roofing Products materials in a manner that will ensure there is no possibility of contamination. 2. Store materials in a dry, well ventilated, weather tight location at temperatures between 50ºF -80ºF until the materials are applied. 3. Keep product lids tightly closed on all containers when not in use. 4. Take all necessary precautions to ensure that damage and overspray will not occur. Tropical Roofing Products is not responsible for damages caused by the overspray of its products. PROJECT CONDITIONS 1. All warranties require wet substrate components of the existing roof to be replaced. A moisture scan is recommended to validate that the underlying roof system insulation is moisture free. 2. Apply a 12 x 12 test patch of the acrylic coating system prior to full roof surface installation to ensure adequate adhesion. Air intake, vents, blowers, air conditioning units and evaporative coolers shall be shut down for the duration of the project. 3. Do not begin work if temperature fall below 50ºF. APPLICATION REQUIREMENTS/100 SQ. FEET OF SURFACE* System Component Gallon(s) Dry Mils 1. #911 Eternalastic White (1 st Top Coat) #911 Eternalastic White (2 nd Top Coat) SYSTEM WET/DRY MILS & WEIGHT* 1. Total System Dry Weight (approximate) 20 lbs. 2. Total System Wet/Dry Mills (approximate) 50/25 mils SYSTEM COMPONENT PERFORMANCE & TEST METHODS # 911 CRRC ID SRI ASTM D6083 UL Class A Title 24 Compliant Solids By Vol. 52% *Note: dry film values shown are approximations and can vary depending on surface conditions. 6 mils of DFT added for fabric.

2 PART II PRODUCTS DESCRIPTION OF THIS RESTORATION SYSTEM A highly reflective Fluid Applied All Acrylic Restoration Coating System used to restore existing or new TPO/PVC. This restorations system is reinforced with heavy duty polyester fabric to extend the life of the existing substrate. This restoration system is applied directly over the existing substrates eliminating the need for roof tear offs. This restoration system will significantly reduce roof temperatures and energy costs. When used in this specification over a new or existing TPO/PVC membrane, a seamless, monolithic roof system is achieved. MATERIALS 1. Eternalastic Elastomeric Roof Coating #911: #911 is a professional grade 100% acrylic Elastomeric coating that exhibits maximum flexibility in cold climates and meets ASTM D In addition, #911 is Energy Star Approved, California Title 24 compliant, UL classified, and Miami-Dade County Approved, #911 will dramatically reduce roof temperatures while protecting the underlying roof membrane. 2. Fibered Eternamastic Elastomeric Roof Mastic #951: #951 is a fiber-fortified, tough, durable, white elastic compound of high-grade raw materials. Easy to apply by brush, this fiber reinforced, viscous mastic is an integral part of waterproofing roofing surfaces. The #951 is a superior choice in maintenance and re-roofing situations. #951 should be used at laps, cracks, seams, directional wall changes, screw heads, or any place a roof intrusion is made. 3. SEBS Elastomeric Flashing Mastic #975: #975 is a single component block copolymer Elastomeric mastic that forms a durable elastomeric flashing membrane. It has exceptional elongation properties, cold weather pliability, excellent weather and water resistance, good chemical resistance, and is highly reflective. It works great to patch and repair properly prepared existing EPDM, APP, SBS, BUR, PVC, Fiberglass, Concrete, and Wood. #975 forms an excellent sealant for horizontal and vertical seams and joints in a metal roofing system as well as drains and ponding susceptible areas. 4. ETERNALASTIC EPDM RINSEABLE PRIMER #990: is a rinseable, low viscosity, spray-able liquid used as a pretreatment of black EPDM rubber roof (Single-Ply) membrane prior to power washing and application of silicone coating. EPDM rinseable primer will significantly improves the adhesion of coating. 5. Polyester Fabric #932: #932 polyester fabric is non-woven, spun bonded 100% that covers 10 squares per roll, firm or soft. Tropical Roofing Products #932 is available in variable widths and must be used in conjunction with #951 fibered Eternamastic at all seams, penetrations, joints or transitions that are subjected to high shear. PART III - EXECUTION PREPARATION 1. Preparation of the roof substrate is the responsibility of the installer, who shall address and correct all of the conditions listed in this section. Examine substrates to receive new roofing. Do not proceed with the installation unsatisfactory conditions have been corrected in a manner acceptable to Tropical Roofing Products. 2. If the TPO/PVC substrate roof is newly installed, do not coat with the acrylic System for a minimum of 30 days to allow for full cure. 3. Thoroughly inspect the TPO/PVC substrate for delamination & defects (holes & other openings tears, cuts, and open or partially opened seams). If the defects are larger than 1/8, repair before coating application (refer to flashing section). 4. Apply a 12 x 12 test patch of the acrylic coating system prior to full roof surface installation to ensure adequate adhesion. Please refer to test patch application instructions. 5. Surface must be clean, dry and free of dust and dirt. 6. Examine roof surface for excessive ponding. Small incidental areas of ponded water will not impact the performance of this coating system; however in accordance with industry standards, the roofing assembly should be designed to prevent ponding of water on the roof for prolonged periods (longer than 48 hours). If necessary, tapered edge strips, crickets, or saddles are to be installed where periodic ponding may occur. 7. Treatment of Ponding Water Areas: Installer is to mechanically eliminate all ponding water areas on the roof prior to application of Tropical Roofing Products materials. The National Roofing Contractors Association (NRCA) considers ponding water on any roof undesirable and recommends that all roof systems be designed and built to ensure positive drainage. (See the NRCA Roofing and Waterproofing Manual). APPLICATION FLASHING APPLICATION 1. After completion of substrate preparation, all flashing details, penetrations and curbs shall be flashed with #951 fibered Eternamastic and shall be feathered at the edges in order for the water to flow over the various flashing details. 2. Base Flashings: Install the base flashing over the cant strip using 6 or 12 of #932 polyester fabric as needed. Saturate into a full coat of 3 gallons per 100 sq. ft. (per ply) of #911 to achieve full saturation. Terminate at least 2 above the cant and extend at least 2 onto the deck.

3 3. Wall Flashings: Install the wall flashing using one full ply of #932 polyester fabric set into a full coat of 3 gallons per 100 sq. ft. (per ply) of #911, achieving full saturation. #932 polyester fabric shall extend over cant strip onto deck and continue up wall to terminate as necessary-- under counter flashing, reglets or wall cap flashing. Wall flashing shall extend out onto the deck at least 2 beyond the termination of the base flashing. 4. Edge Flashings: Replace gravel stops and metal edge where necessary. Where gravel stop is replaced, replace with low or no rise metal edge. Metal edge shall be nailed at 4" on center Strip-in the metal with #932 polyester fabric and #951 fibered Eternamastic ensuring all the nails are completely covered. Where edge flashing is left in place, cut back roofing 2 from rise and strip-in with #932 polyester fabric and #951 fibered Eternamastic providing positive attachment of the metal edge to the new coating system. 5. Roof Drains: Remove clamping ring and clean all existing build-up from around the drains and sumps. Apply #951 fibered Eternamastic or #975 SEBS Elastomeric mastic in a three-course fashion across the entire drain/sump area. Extend the application into the drain bowl from center of drain onto the deck 6 beyond drain sump. Allow to cure. Replace clamping ring. The base coat application shall be applied overlapping onto the reinforced #951 fibered Eternamastic or #975 SEBS Elastomeric mastic and cut around the clamping ring. 6. Curb Flashings: All curb flashings shall be flashed with at least a 2 wide x 1/16 thick of #951 fibered Eternamastic. 7. Fasteners: Encapsulate all fasteners using #951 fibered Eternamastic with #932 polyester fabric, which shall be cut around all fasteners so fabric lies flat. 8. Penetrations: #951 fibered Eternamastic along with #932 polyester fabric shall be applied around the base of the penetration, extending at least 4 onto the vertical and 4 onto the base. Embed a 6 width of #932 polyester fabric using additional #951 fibered Eternamastic as necessary to accommodate the shape of the penetration. 9. Skylights & Curbed AC Units: Curb skylights shall be treated in the same fashion as curb flashings. The perimeter shall be flashed with a 4 of #932 polyester fabric along with #951 fibered Eternamastic. The 4 #932 polyester fabric is divided 2 evenly between the vertical and the roof surface. All exposed skylight fasteners shall be encapsulated with #951 fibered Eternamastic. 10. Seams: All seams and areas around roof protrusions (vents, scuttle hatches, etc.) are to be treated with #951 fibered Eternamastic along with #932 reinforcing fabric to achieve watertight seals in a three-course fashion (refer to flashing section for details). 11. Pitch Pans: Pitch pans shall be sealed using #951 fibered Eternamastic with #932 reinforcing fabric in a three-course fashion (refer to flashing section for details). 12. Condensation Lines: Condensation lines shall be installed from HVAC units to gutters as part of the overall drainage system. The type of piping used for condensation lines may vary depending on local building codes. 13. Inspect Preliminary Work / Flashing Details for problem areas (e.g., gaps, cracks, fish mouths, air pockets, etc.) #990 RINSEABLE PRIMER (EPDM ONLY) SUBSTRATE APPLICATION 1. Apply #990 Eternalastic rinseable primer at a rate of 1 gallon per 500 sq. ft. 2. #990 Eternalastic rinseable primer should be applied with a conventional compressive air sprayer/hudson sprayer. 3. The EPDM surface must next be pressure washed with water at a rate of max 2500 psi to remove remaining debris. 4. #990 Eternalastic rinseable primer is mandatory for maximum adhesion. Any residue of the #990 Eternalastic rinseable primer left on the EPDM will also have disastrous adhesion results. Therefore, a complete second rinse with water is essential. PIPE FLASHINGS & PENETRATIONS SURFACE TREATMENT After the base coat is cured and prior to the application of the top coat: 1. Apply #951 fibered Eternamastic and #932 polyester fabric in a three course fashion to all pipe flashings, cones, exposed metal joints and flanges. 2. Apply #951 fibered Eternamastic to all corners at curbs and skylight flashings or any area that has been previously repaired with roofing mastic.

4 PONDED AREAS & DRAINS APPLICATION After the base coat is cured and prior to the application of the top coat: 1. All areas around drains and scuppers shall be treated with a second layer of #932 polyester fabric saturated in the #911 Eternalastic coating. 2. Waterways and any locations where water ponds for more than 48 hours shall be treated with a second layer of #932 polyester fabric embedded in the #911 Eternalastic coating. The #932 polyester fabric shall extend 12 beyond the designated ponding area or as necessary to extend beyond the drain sump. In this area, saturate the #932 polyester fabric into a 3 gallon per 100 sq. ft. application of #911 and brush lightly to achieve full saturation without wrinkles or voids. TOP COAT APPLICATION 1. A visual inspection of the entire base coat should be performed to confirm an acceptable surface / substrate to accept the top coat. Any deficiencies must be repaired prior to application of the top coat. 2. Apply the first layer of top coat with #911 Eternalastic at an application rate of 1.5 gallon per 100 sq. ft. to achieve required DFT of 12.5 mils or 24 of mils wet. 3. The top coat shall completely cover the base coat including expansion joint covers, parapets and flashings. 4. Allow a minimum of 12 hours drying time prior to any foot traffic or inspections. (Weather dependent). 5. Apply second layer of the top coat with #911 Eternalastic perpendicular from the first in a cross hatch manner at an application rate of 1.5 gallon per 100 sq. ft. to achieve required DFT of 12.5 mils or 24 of mils wet. 6. The minimum DFT of the entire top coat must be 25 mils. 7. Allow a minimum of hours drying time before allowing any foot traffic or inspections. 8. After curing, inspect for defects and repair as necessary. 9. Pay special attention not to overspray, which can texture or discolor adjoining finished sections. 10. Note: Total minimum Restoration System Dry Film Thickness for the entire restoration system shall be 25 mils nominally. INSTALLATION OF WALKWAYS (OPTIONAL): In high-traffic areas and around mechanical equipment, walkways should be installed to protect the coating system from damage. FIELD QUALITY CONTROL 1. Maintain Job Progress Report / Daily Log of work completed as required to assure installation is in accordance with manufacturer requirements. 2. Provide on-the-job inspections, technical assistance and material application guidance as may be necessary to complete roofing material application in accordance with Tropical Roofing Products warranty requirements. JOB COMPLETION 1. Inspect completed coating system and correct all defects to meet the specification and/or warranty requirements. 2. Transparent or Thin Areas: If areas appear to be undercoated, recoating may be needed to ensure final thickness to meet the Tropical Roofing Products specifications Total Dry Mils. 3. Delamination: Verify that all coated areas appear to be fully adhered to the substrate. A visual inspection looking for typical signs of poor adhesion such as flaking, blistering etc. should be made. Re-priming and/or recoating will be required if such areas are apparent. 4. Pin Holing: Certain job or site conditions may result in pin holing or out gassing during curing or cause pin holes in the substrate. Again, a visual inspection looking for typical signs of out gassing such as excessive pockmarks, pinholes etc. should be done. 5. Delaminating: Delamination is caused when water-based coatings freeze, or solvent entrapment in solvent based coatings occurs. The coating surface may exhibit extreme wrinkles, small blisters and may have loss of adhesion. These areas will not self-heal and must be removed, power washed and a new coating must be applied. 6. Texture Finish: Heavy patterns, blistering, skinning, etc. may appear in the final finish. These may indicate that the coat is too thick, a build-up has occurred or another application problem. Check with Tropical Roofing Products Technical Representative for remedial advice. 7. A Tropical Roofing Products Technical Representative will inspect the finished system and notify the contractor with any defects in the application. 8. Restrict construction traffic and equipment movement on the completed coating system to only essential personnel. Provide appropriate protection against traffic and construction activities on completed roofs. Damage to the roof by other trades shall not be the responsibility of Tropical Roofing Products.

5 HOUSEKEEPING ITEMS 1. Contractor shall take photographs of representative roof areas, including detail work before work commences, after the surface has been properly prepared, after all flashing and detail work has been performed, and after the application of the #911 Eternalastic coating membrane. 2. Installer shall provide the following support for on-site inspections by a representative from Tropical Roofing Products (list is not comprehensive): a. Representative from the contractor's company who has authority to make binding decisions. b. Required means to access all areas of the treated roof. c. Previous photographs of the roof. 3. Access must be granted to all areas of the restored roof system. 4. Installer shall take special care when moving spray hoses and other equipment on the roof in order to prevent damage to the flashing work and encapsulated fastener heads. Also, all spray equipment shall remain on the ground for the duration of the job. 5. If there will be an extended period of time (6 months or greater) between application of base and finish coats, the use of #911 Eternalastic (white) for the base coat (versus gray) is recommended. The base coat shall be thoroughly cleaned before applying the finish coat. REPAIRS 1. In the event that the #911 Eternalastic membrane is damaged or punctured, repairs are to be performed using #951 fibered Eternamastic along with #932 polyester fabric (where necessary) as follows: a. Damaged areas are to be cut, cleaned and dried. b. Apply #951 fibered Eternamastic, and feather out onto the existing #911 Eternalastic membrane with a minimum of 2-4 inches beyond the existing coating. c. If a new penetration area has been cut, embed #932 polyester fabric into the #951 fibered Eternamastic according to standard Tropical Roofing Products specifications. CLEAN UP 1. Remove masking and protection tapes. 2. The HVAC vents and units can be opened and restarted once the spray operation is complete. 3. Remove all roof related trash and debris from jobsite. 4. Dispose of containers in accordance with local regulations. 5. For application questions, please contact Tropical Roofing Products at ENGINEERING Tropical Roofing Products does not practice Engineering or Architecture. Any review of the building s construction or inspection of roof plans or inspection of the building s structural roof deck by Tropical Roofing Products representatives shall not constitute any warranty by Tropical Roofing Products of such plans, specifications or construction. Any roof inspections are solely for the benefit of Tropical Roofing Products. MAINTENANCE To maintain your warranty coverage and in order to ensure that your roof will continue to perform to its fullest during the entire time of the warranty, always adhere to Tropical Roofing Products Care and Maintenance program and guidelines. IMPORTANT: The applicators strict adherence to this specification is the only way Tropical can ensure that this product will perform as intended. Accordingly, any changes made to specifications must be reviewed, approved in writing and signed by Tropical Roofing Products Director of Manufacturing & Technical Services prior to application. End of Section; Copyright 2016

DESIGN GUIDELINE FLUID-APPLIED WATERPROOFING

DESIGN GUIDELINE FLUID-APPLIED WATERPROOFING DESIGN GUIDELINE FLUID-APPLIED WATERPROOFING (TO RESTORE EPDM MEMBRANES) PART 1 GENERAL 1.01 DESCRIPTION A. The scope of this design guideline is to describe the installation of the ALDOCOAT Silicone reflective

More information

TOPCOAT Restoration Specifications Fiberglass & MB Granulated Cap Sheets

TOPCOAT Restoration Specifications Fiberglass & MB Granulated Cap Sheets TOPCOAT Restoration Specifications Fiberglass & MB Granulated Cap Sheets Updated: 1/11 Quality You Can Trust From North America s Largest Roofing Manufacturer! www.gaf.com TOPCOAT Restoration Specifications

More information

FireShield System Specifications Mineral Surface Cap, Mop Granule and Torch Granule APP Cap Sheets

FireShield System Specifications Mineral Surface Cap, Mop Granule and Torch Granule APP Cap Sheets FireShield System Specifications Mineral Surface Cap, Mop Granule and Torch Granule APP Cap Sheets Updated: 1/11 Quality You Can Trust From North America s Largest Roofing Manufacturer! www.gaf.com FireShield

More information

GE SCM3500 High Solids Silicone Roof Coating

GE SCM3500 High Solids Silicone Roof Coating GE SCM3500 High Solids Silicone Roof Coating Installation Guide Specification For GRANULATED or SMOOTH MODIFIED BITUMEN / BUR (20 Year Warranty) Warranty PART 1 GENERAL 1.01 SUMMARY A. This specification

More information

Guideline Specification ACRYMAX ARS-1-C Reinforced Composite Elastomeric Membrane System for Concrete Roofs Fluid-Applied Roofing

Guideline Specification ACRYMAX ARS-1-C Reinforced Composite Elastomeric Membrane System for Concrete Roofs Fluid-Applied Roofing 221 Brooke Street Media, PA 19063 610-566-7470 Fax 610-891-0834 Website www.acrymax.com e-mail info@acrymax.com This document is intended to provide guidelines for the proper specification and application

More information

TOPCOAT Restoration Specifications Structural Concrete

TOPCOAT Restoration Specifications Structural Concrete TOPCOAT Restoration Specifications Structural Concrete Updated: 1/11 Quality You Can Trust From North America s Largest Roofing Manufacturer! www.gaf.com TOPCOAT Restoration Specifications Structural Concrete

More information

TOPCOAT System Specifications Corrugated Transite Panels

TOPCOAT System Specifications Corrugated Transite Panels TOPCOAT System Specifications Corrugated Transite Panels Updated: 1/11 Quality You Can Trust From North America s Largest Roofing Manufacturer! www.gaf.com TOPCOAT System Specifications Corrugated Transite

More information

Acry-Tek 4200 / SPF Recoat System

Acry-Tek 4200 / SPF Recoat System WARRANTY SPECIFICATION Acry-Tek 4200 / SPF Recoat System MASTER GUIDE SPECIFICATIONS This MASTER GUIDE-SPEC is a brief outline of Coating & Foam Solutions, LLC.(CFS) roofing requirements and is intended

More information

DURA 500 THERMOPLASTIC FLAT ROOF COATING SYSTEM BY SUPERIOR POLYMERS INC.

DURA 500 THERMOPLASTIC FLAT ROOF COATING SYSTEM BY SUPERIOR POLYMERS INC. SPECIFICATION GUIDELINE FOR SMOOTH ROOF SUBSTRATES INCLUDING MODIFIED BITUMEN, SMOOTH ASPHALT, EPDM, TPO, AND PLYWOOD. Part 1 General Information For the purpose of clarification in this document, the

More information

SECTION ALPHAGUARD RESTORATION 20 YEAR WARRANTY SYSTEM. f. Conditions and Division 01 Specification Sections, apply to this Section.

SECTION ALPHAGUARD RESTORATION 20 YEAR WARRANTY SYSTEM. f. Conditions and Division 01 Specification Sections, apply to this Section. SECTION 07015 ALPHAGUARD RESTORATION 20 YEAR WARRANTY SYSTEM PART I.1 GENERAL A. RELATED DOCUMENTS 1. The attached are components of this section: a. General Conditions b. Supplemental Conditions c. Statement

More information

SECTION mil thickness COLD FLUID-APPLIED WATERPROOFING

SECTION mil thickness COLD FLUID-APPLIED WATERPROOFING SECTION 07 14 16 CCW-MIRASEAL @ 120 mil thickness COLD FLUID-APPLIED WATERPROOFING PART 1 - GENERAL 1.1 SECTION INCLUDES: Installation of waterproofing membrane on surfaces indicated on drawings, consisting

More information

ROOF SUBSTRATE PREP MANUAL

ROOF SUBSTRATE PREP MANUAL ROOF SUBSTRATE PREP MANUAL ALDOCOAT Liquid Applied Roof Restoration Systems AFTER BEFORE JULY 2016 1604 N. Main St. Kannapolis, NC 28081 (800) 474-6019 www.aldoproducts.com ROOF SUBSTRATE PREPARATION Preparation

More information

GEOGARD LO Base Coat / GEOGARD Finish Coat

GEOGARD LO Base Coat / GEOGARD Finish Coat GENERAL GUIDELINE SPECIFICATION LO Base Coat / Finish Coat WATERPROOFING SYSTEM FOR MODIFIED BITUMEN ROOFS PART 1 General 1.01 General A. This document is intended to provide only general guidelines regarding

More information

System Specifications

System Specifications 100% Silicone Roof Coating System for Existing, Aged, Smooth and Granulated Modified Bitumen Membrane Systems TABLE OF CONTENTS PART 1 GENERAL Page 1.1 Scope of Work... 1 1.2 Related Sections... 1 1.3

More information

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 075423 - THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Division 00 Bidding Requirements and other Division

More information

1. Rubberized asphalt waterproofing membrane, reinforced. 2. Molded sheet drainage panels. 3. Insulation. 4. Plaza deck pavers.

1. Rubberized asphalt waterproofing membrane, reinforced. 2. Molded sheet drainage panels. 3. Insulation. 4. Plaza deck pavers. SECTION 071413 HOT FLUID APPLIED RUBBERIZED ASPHALT WATERPROOFING PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Rubberized asphalt waterproofing membrane, reinforced. 2. Molded sheet drainage panels.

More information

MAKE ROOFS LAST LONGER

MAKE ROOFS LAST LONGER MAKE ROOFS LAST LONGER Roof Coatings & Roof Repair Single-Ply Metal Asphalt HIGHEST PERFORMING SYSTEMS. LOWEST APPLIED COST. METAL ROOF RESTORATION Metal Restoration Quick Guide Acrylic Polyurethane High

More information

SECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING

SECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING P.O. Box 599 - Mars, PA 16046 800-321-3337 SECTION 07555 COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including

More information

Colphene BSW Training and Application Guide. Colphene BSW Waterproofing Membrane. 1. Prepare substrate

Colphene BSW Training and Application Guide. Colphene BSW Waterproofing Membrane. 1. Prepare substrate Colphene BSW Training and Application Guide Colphene BSW Waterproofing Membrane. 1. Prepare substrate Substrate must be structurally sound. Surface must be free of voids, spalled areas, loose aggregate,

More information

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. SECTION 070150.76 REHABILITATION OF SINGLE PLY MEMBRANES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply

More information

SCOPE OF WORK PROJECT IDENTIFICATION

SCOPE OF WORK PROJECT IDENTIFICATION PROJECT IDENTIFICATION SCOPE OF WORK PROJECT NAME: Wickenburg High School PROJECT: Gym Roof 1 SITE ADDRESS: 1090 S. Vulture Mine Rd. Wickenburg AZ 85390 City State ZIP Code SCOPE OF WORK SUMMARY: 1. Extend

More information

Application Specification:

Application Specification: Application Specification: GW-15-UBU-HD April 2014 Supersedes 5/13 PART 1 - GENERAL 1.1 SUMMARY Division 07 18 16: GACOFLEX POLYURETHANE ELASTOMERIC COATING SYSTEM FOR VEHICULAR TRAFFIC DECKS AND RAMPS

More information

Pacific Polymers Elasto-Deck BT Guide Specification

Pacific Polymers Elasto-Deck BT Guide Specification 1 07141-1 August 2016 Pacific Polymers Elasto-Deck BT Guide Specification SECTION 07141 FLUID APPLIED WATERPROOFING 2 07141-2 August 2016 Pacific Polymers Elasto-Deck BT Guide Specification SECTION 07141

More information

GenFlex EZ TPO Peel & Stick SA (HW) APPLICATION GUIDE

GenFlex EZ TPO Peel & Stick SA (HW) APPLICATION GUIDE GenFlex EZ TPO Peel & Stick SA (HW) APPLICATION GUIDE I. MEMBRANE APPLICATION... 2 A. MEMBRANE... 2 II. MEMBRANE ATTACHMENT... 2 III. SEAMING... 3 A. SEAMING FOR GENFLEX EZ TPO PEEL & STICK SA (HW)...

More information

SECTION MODIFIED BITUMINOUS SHEET WATERPROOFING

SECTION MODIFIED BITUMINOUS SHEET WATERPROOFING SECTION 07 13 52 MODIFIED BITUMINOUS SHEET WATERPROOFING SPEC WRITER NOTE: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

FLUID APPLIED WATERPROOFING

FLUID APPLIED WATERPROOFING SECTION 07120 FLUID APPLIED WATERPROOFING PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 03300 - Cast-In-Place Concrete. 2. 09200 - Metal Studs, Metal Lath, Suspension Ceilings, Plaster, and Stucco.

More information

SECTION CO-POLYMER ELASTOMERIC COOL-ROOF COATING

SECTION CO-POLYMER ELASTOMERIC COOL-ROOF COATING SECTION 076000 - CO-POLYMER ELASTOMERIC COOL- PART 1 - GENERAL 1.1 SUMMARY OF WORK A. Contractor is to supply the necessary labor, materials, and equipment to coat existing roof system (approximately 390

More information

FIRESTONE ULTRAPLY TPO SA APPLICATION GUIDE

FIRESTONE ULTRAPLY TPO SA APPLICATION GUIDE FIRESTONE ULTRAPLY TPO SA APPLICATION GUIDE I. MEMBRANE APPLICATION... 2 A. MEMBRANE... 2 II. MEMBRANE ATTACHMENT... 2 III. SEAMING... 3 A. SEAMING FOR FIRESTONE ULTRAPLY TPO SA... 3 B. T-JOINT AREAS...

More information

RUBBERGARD EPDM SA APPLICATION GUIDE

RUBBERGARD EPDM SA APPLICATION GUIDE RUBBERGARD EPDM SA APPLICATION GUIDE I. MEMBRANE APPLICATION... 2 A. MEMBRANE... 2 II. MEMBRANE ATTACHMENT... 2 A. MEMBRANE PREPARATION... 2 B. MEMBRANE APPLICATION... 2 III. SEAMING... 3 VI. MEMBRANE

More information

TOPCOAT Product Catalog

TOPCOAT Product Catalog TOPCOAT Product Catalog (TOPGN235) Updated: 7/14 gaf.com TOPCOAT L I Q U I D-APPL IED R O O F I N G gaf.com Energy-Saving Liquid-Applied Roofing Solutions! FEWER COATS FEWER GALLONS FEWER LABOR HOURS BIGGER

More information

1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards

1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards SECTION 07185 TRAFFIC MEMBRANE PART 1 GENERAL 1.1 SECTION INCLUDES A. Traffic membrane, consisting of welded seam PVC waterproofing, over f following surfaces: 1. Decks, balconies, and sun porches 2. Walkways,

More information

LEGACY REPORT DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FLUID APPLIED ROOFING REPORT HOLDER: METACRYLICS

LEGACY REPORT DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FLUID APPLIED ROOFING REPORT HOLDER: METACRYLICS 0 Most Widely Accepted and Trusted ICC ES Legacy Report ICC ES 000 (800) 6587 (56) 699 05 www.icc es.org ER 785 Reissued 09/017 This report is subject to renewal 09/0. DIVISION: 07 00 00THERMAL AND MOISTURE

More information

FLUID APPLIED ROOFING - HYPALON ROOF RESTORATION

FLUID APPLIED ROOFING - HYPALON ROOF RESTORATION The enclosed specifications are designed to summarize the activities and responsibilities of all the principal parties to a roofing project. Oftentimes, the guide specification will function as the primary

More information

PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960

PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960 STUC-O-FLEX PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960 PART 1 - GENERAL 1.01 DESCRIPTION Provide all labor, materials and equipment necessary

More information

Henry #1 CHOICE OF PROFESSIONALS

Henry #1 CHOICE OF PROFESSIONALS Henry #1 CHOICE OF PROFESSIONALS GUIDE SPECIFICATION HENRY SPECIFICATION H-MR EXISTING ROOF MONOLITHIC MAINTENANCE COOL ROOF REFLECTIVE GUIDE SPEC H-M R The enclosed guide specification, general requirements

More information

LAKEWOOD HIGH SCHOOL RECOAT/REROOF PROJECT 100% OWNER REVIEW

LAKEWOOD HIGH SCHOOL RECOAT/REROOF PROJECT 100% OWNER REVIEW SECTION 07106-1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Outline NBS Specification. Protec System to PVC Single Ply (Waterproofing Only)

Outline NBS Specification. Protec System to PVC Single Ply (Waterproofing Only) Outline NBS Specification Protec System to PVC Single Ply (Waterproofing Only) This document is a guide to assist in the production of tender documents only and is not project specific. A site survey is

More information

Roof Replacement. Notes: T-1 (Title Sheet) Roof Key Plan Russell House Student Union 1400 Greene Street Columbia, South Carolina 29208

Roof Replacement. Notes: T-1 (Title Sheet) Roof Key Plan Russell House Student Union 1400 Greene Street Columbia, South Carolina 29208 Notes: Drawing Index T-1 Title R-1 Roof Plan - Existing Conditions R-2 Roof Plan - New D-1 Roof Details D-2 Roof Details D-3 Roof Details M-1 Mechanical - Roof Plan M-2 Mechanical - Details Roof Key Plan

More information

CITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO

CITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO SECTION 07220 - ROOF INSULATION PART 1 - GENERAL 1.01 DESCRIPTION A. Work included: The Roofing Contractor will provide all polyisocyanurate insulation and high density wood fiber roof insulation (tapered

More information

Elastomeric Protected Membrane Roofing Fluid-Applied Protected Membrane Roofing. Restoration Coating System (RCS) over Cap Sheet

Elastomeric Protected Membrane Roofing Fluid-Applied Protected Membrane Roofing. Restoration Coating System (RCS) over Cap Sheet 07 55 53 Elastomeric Protected Membrane Roofing 07 55 56 Fluid-Applied Protected Membrane Roofing Restoration Coating System (RCS) over Cap Sheet PART 1 - GENERAL 1.1 SUMMARY A. This specification covers

More information

Section COATING RESTORATION

Section COATING RESTORATION Sto Corp. 3800 Camp Creek Parkway Building 1400, Suite 120 Atlanta, GA 30331 Tel: 404-346-3666 Toll Free: 1-800-221-2397 Fax: 404-346-3119 www.stocorp.com 80658R StoColor Texture - Coarse Textured Acrylic-Based,

More information

1.1 SECTION INCLUDES Verify Scope, including identification of plies and type of coating.

1.1 SECTION INCLUDES Verify Scope, including identification of plies and type of coating. SECTION 07 51 00 - BUILT-UP ASPHALT ROOFING PART 1: GENERAL Requestor Note: Requestor to verify project requirements related to roof deck, drainage, fire resistance, wind uplift, insulation, surfacing,

More information

MANUFACTURER S (SHORT FORM) SPECIFICATION / SECTION

MANUFACTURER S (SHORT FORM) SPECIFICATION / SECTION STUC-O-FLEX - ELASTOMERIC ACRYLIC FINISH APPLICATION TO PORTLAND CEMENT PLASTER / CONCRETE RENDER MANUFACTURER S (SHORT FORM) SPECIFICATION / SECTION 09220-09 24 00 PART 1-GENERAL SCOPE: Manufacturer's

More information

MasterSeal HLM Liquid cold-applied elastomeric waterproofing membrane system

MasterSeal HLM Liquid cold-applied elastomeric waterproofing membrane system Liquid cold-applied elastomeric waterproofing membrane system DESCRIPTION MasterSeal HLM 5000 is a one-component, moisture-curing, bitumen-modified polyurethane elastomeric waterproofing membrane for exterior

More information

1.2 DEFINITIONS, REFERENCES, AND OVERALL STANDARDS Follow 07500

1.2 DEFINITIONS, REFERENCES, AND OVERALL STANDARDS Follow 07500 07721 ROOF ASSEMBLY SUPPORTS FOR ROOFTOP EQUIPMENT ****************************************** SPECIFIER: All roof-related items above or outside the structural roof deck, including such work as blocking,

More information

AVM System 500. Aussie Membrane 500

AVM System 500. Aussie Membrane 500 Generic Spec TECH DATA SHEET Sections - 071000 / 071400 / 071416 ICC ESR-2503 L.A. RR#: 25550 Heavy Duty Below Grade Bituminous Waterproofing Membrane Sections 071000 / 071400 / 071416 Fluid Applied Waterproofing

More information

ITEM 458 WATERPROOFING FOR STRUCTURES

ITEM 458 WATERPROOFING FOR STRUCTURES ITEM 458 WATERPROOFING FOR STRUCTURES 458.1. Description. This Item shall govern for the furnishing and placing of waterproofing on concrete and steel bridge decks of railroad structures and on other structures

More information

DUKE UNIVERSITY CONSTRUCTION STANDARDS

DUKE UNIVERSITY CONSTRUCTION STANDARDS 1 07 40 00 Roofing 1. General Several factors repeatedly show up during the inspection of roofs that have failed prematurely. They include inappropriate use of materials, poor drainage systems, poor details

More information

SECTION MANUFACTURED ROOF EXPANSION JOINTS

SECTION MANUFACTURED ROOF EXPANSION JOINTS SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Instruction Guide APPLICATION OF CIM TO CONCRETE

Instruction Guide APPLICATION OF CIM TO CONCRETE 23 Elm St., Peterborough, NH 03458 Tel: (800) 543-3458 (603) 924-9481 Fax: (603) 924-9482 Web site: Instruction Guide APPLICATION OF CIM TO CONCRETE 1.0 DESCRIPTION This guide covers the installation of

More information

Product Data Sheet Waterproofing Membrane for Ponds and Water Features Description Uses Suitable Surfaces Additional Uses Specification

Product Data Sheet Waterproofing Membrane for Ponds and Water Features Description Uses Suitable Surfaces Additional Uses Specification Product Data Sheet Pondseal Waterproofing Membrane for Ponds and Water Features Description Pondseal is a polyurethane / acrylic co-polymer, water based coating which when fully cured, forms an impervious,

More information

Index. Roofing. Metal Roofing Systems/Cold Process Systems. Dampproofing. Waterproofing. Sealants, Caulking, Flooring. Fabrics. Guide Specifications

Index. Roofing. Metal Roofing Systems/Cold Process Systems. Dampproofing. Waterproofing. Sealants, Caulking, Flooring. Fabrics. Guide Specifications Index Roofing 4 Metal Roofing Systems/Cold Process Systems Dampproofing Waterproofing Sealants, Caulking, Flooring Fabrics Guide Specifications Miscellaneous 68 92 120 128 141 147 167 1 Product Index ROOFING

More information

E. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage.

E. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage. DELTA -DRAIN Section 07 10 00 Dampproofing and Waterproofing PART 1 GENERAL 1.1 SECTION INCLUDES A. Below grade drainage sheets. B. Plaza deck and planter drainage sheets. 1.2 RELATED SECTIONS A. Section

More information

RENEW ELASTOMERIC ACRYLIC COATING (PAINT GRADE) MANUFACTURERS SPECIFICATION / SECTION

RENEW ELASTOMERIC ACRYLIC COATING (PAINT GRADE) MANUFACTURERS SPECIFICATION / SECTION STUC-O-FLEX RENEW ELASTOMERIC ACRYLIC COATING (PAINT GRADE) MANUFACTURERS SPECIFICATION / SECTION 09 97 23 PART 1-GENERAL 1.00 SCOPE: Manufacturer's specifications containing the requirements necessary

More information

A. Product Data: Submit manufacturer s product data, with complete general and specific installation instructions, recommendations, and limitations.

A. Product Data: Submit manufacturer s product data, with complete general and specific installation instructions, recommendations, and limitations. SECTION 071700 - BENTONITE WATERPROOFING PART 1 - GENERAL 1.1 WORK SUMMARY A. The work of this section includes, but is not limited to the furnishing and installing the following materials, per project

More information

SBS Hot-Mopped & Cold Adhesive Roofing (COMGN289) Updated: 1/17

SBS Hot-Mopped & Cold Adhesive Roofing (COMGN289) Updated: 1/17 SBS Hot-Mopped & Cold Adhesive Roofing (COMGN89) Updated: /7 TM TM GAF ROOF GUARANTEE PROGRAM GAF offers an extensive selection of roof guarantees to meet the needs of most building owners. The following

More information

SECTION RESILIENT SHEET FLOORING

SECTION RESILIENT SHEET FLOORING SECTION 09 65 16 RESILIENT SHEET FLOORING SPEC WRITER NOTE: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1.

More information

2016 Capital Improvement Project REHABILITATION OF METAL ROOFING SECTION REHABILITATION OF METAL ROOFING PART 1 - GENERAL

2016 Capital Improvement Project REHABILITATION OF METAL ROOFING SECTION REHABILITATION OF METAL ROOFING PART 1 - GENERAL 13414.01 REHABILITATION OF METAL ROOFING 070151-1 SECTION 070151 REHABILITATION OF METAL ROOFING 1.1 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of the Contract, including General

More information

HALIFAX HUMANE SOCIETY BOARDING AND GROOMING FACILITY SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS

HALIFAX HUMANE SOCIETY BOARDING AND GROOMING FACILITY SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS SECTION 075216 - PART 1 - GENERAL 1.1 SUMMARY A. Section includes styrene-butadiene-styrene (SBS) modified bituminous membrane roofing. 1.2 DEFINITIONS A. Hot Roofing Asphalt: Roofing asphalt heated to

More information

8245 Remmet Ave Canoga Park, CA (888) Installation Instructions - AVM System 700 Under Tile Waterproofing and Anti-Fracture Membrane

8245 Remmet Ave Canoga Park, CA (888) Installation Instructions - AVM System 700 Under Tile Waterproofing and Anti-Fracture Membrane 8245 Remmet Ave Canoga Park, CA. 91304 (888) 414-1041 Division 7-Moisture Protection Page 1 Table of Contents General... 2 Approvals... 2 Applicator... 2 Product Delivery, Storage and Handling... 2 Limitations...

More information

To ensure warranty eligibility, each job must be approved by American WeatherStar before it begins.

To ensure warranty eligibility, each job must be approved by American WeatherStar before it begins. SPRAY POLURETHANE FOAM & COATINGover metal roof deck SPF To ensure warranty eligibility, each job must be approved by American WeatherStar before it begins. PART 1 GENERAL 1.01 DESCRIPTION A. The intention

More information

TEX COTE 600 TEXTURED COATING MASONRY PROTECTIVE COATING

TEX COTE 600 TEXTURED COATING MASONRY PROTECTIVE COATING SECTION 09960 - TEXTURED COATINGS Coating System Submittals Guide Specification TEX COTE 600 TEXTURED COATING MASONRY PROTECTIVE COATING (SPLIT FACE OR SAND FINISH BLOCK) 1. TEX COTE 600, Textured Coating

More information

***********************************************************************************

*********************************************************************************** AQUAFIN-2K/M Two-Component Cement-based Acrylic-based Waterproofing GUIDE AQUAFIN, Inc. SPECIFICATION PART 1 - GENERAL 1.1 SECTION INCLUDES SECTION 07 16 14 ACRYLIC MODIFIED (FLEXIBLE) CEMENTITIOUS WATERPROOFING

More information

General Applications Before applying, mix the pre-measured catalyst* into Liquid Roof by following label directions.

General Applications Before applying, mix the pre-measured catalyst* into Liquid Roof by following label directions. General Applications Before applying, mix the pre-measured catalyst* into Liquid Roof by following label directions. Surface Preparation: Surface to be coated should be clean, dry and structurally sound.

More information

SECTION WINDOW FILM. Display hidden notes to specifier. (Don't know how? Click Here) Copyright ARCAT, Inc. - All rights reserved

SECTION WINDOW FILM. Display hidden notes to specifier. (Don't know how? Click Here) Copyright ARCAT, Inc. - All rights reserved SECTION 08 87 13 WINDOW FILM Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2008-2010 ARCAT, Inc. - All rights reserved PART 1 GENERAL 1.1 SECTION INCLUDES A. Safety and Security

More information

SECTION SELF-ADHERING SHEET WATERPROOFING

SECTION SELF-ADHERING SHEET WATERPROOFING SECTION 07 13 26 SELF-ADHERING SHEET WATERPROOFING This guide specification has been prepared by Polyguard Products Inc., in printed and electronic media, as an aid to specifiers in preparing written construction

More information

ARCHITECTURAL GUIDE SPECIFICATIONS - DESCRIPTIVE

ARCHITECTURAL GUIDE SPECIFICATIONS - DESCRIPTIVE ARCHITECTURAL GUIDE SPECIFICATIONS - DESCRIPTIVE MANNINGTON COLORFIELDS SHEET RUBBER FLOORING Section 09 65 16 Sheet rubber Flooring (Thermoset Rubber) Created May 2012 Mannington Mills, Inc. P. O. Box

More information

TUFF-TAC TM BRIDGE MEMBRANE INSTALLATION GUIDE

TUFF-TAC TM BRIDGE MEMBRANE INSTALLATION GUIDE 5 pages TUFF-TAC TM BRIDGE MEMBRANE INSTALLATION GUIDE The following will describe the proper procedure to use when installing Tuff-Tac TM bridge deck membrane. The guide will cover recommended tools to

More information

TTR SYSTEMS ROOF SPECIFICATION

TTR SYSTEMS ROOF SPECIFICATION SECTION 07 53 24 EPDM roofing membrane applied over spray applied polyurethane foam TTR SYSTEMS ROOF SPECIFICATION This specification has been numbered, organized and formatted in accordance with the Master

More information

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO SECTION 07 53 23 - ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions ofthe Contract, including General and Supplementary Conditions

More information

SECTION PVC SINGLE PLY ROOFING

SECTION PVC SINGLE PLY ROOFING SECTION 07 54 23 PVC SINGLE PLY ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Attached GENERAL CONDITIONS, GENERAL NOTES, INSTRUCTIONS TO BIDDERS, AND BID FORM are components of this section. B. Section

More information

May 8, 2017 ADDENDUM #1. IFB Resin Floor System For Highway Department Central District Building

May 8, 2017 ADDENDUM #1. IFB Resin Floor System For Highway Department Central District Building May 8, 2017 ADDENDUM #1 IFB 17-082 Resin Floor System For Highway Department Central District Building Addendum #1 is being issued to offer an alternate resin flooring system. 096700 FLUID-APPLIED FLOORING

More information

MULE-HIDE PRODUCTS CO., INC. MULE-HIDE SELF-ADHERING TPO ROOFING SYSTEM

MULE-HIDE PRODUCTS CO., INC. MULE-HIDE SELF-ADHERING TPO ROOFING SYSTEM MULE-HIDE PRODUCTS CO., INC. MULE-HIDE SELF-ADHERING TPO ROOFING SYSTEM 07500/MUL PART 1 - GENERAL 1.01 Description A. Scope: 1. Thermoplastic Self Adhering Single Ply Roofing 2. Insulation B. Related

More information

Standard specification for the application of Danosa Two-Layer waterproof roofing membrane to plywood & concrete surfaces.

Standard specification for the application of Danosa Two-Layer waterproof roofing membrane to plywood & concrete surfaces. Standard specification for the application of Danosa Two-Layer waterproof roofing membrane to plywood & concrete surfaces. BRANZ Appraised No. 678 Ref: P3200 Rev 1 February 2016 Page 1 of 5 1.0 PREAMBLE:

More information

POLYGLASS U.S.A., INC. CORPORATE HEADQUARTERS

POLYGLASS U.S.A., INC. CORPORATE HEADQUARTERS White Reflective Membranes and Coatings www.polyglass.us KOOL ROOF SOLUTIONS White Reflective Membranes and Coatings TABLE OF CONTENTS Table Of Contents 3... Introduction 4... CURE Technology 5...ADESO

More information

ARCHITECTURAL GUIDE SPECIFICATION REROOFING OVER EXISTING BUR C-EPDM SYSTEM 2001 FOR STEEL AND WOOD DECKS

ARCHITECTURAL GUIDE SPECIFICATION REROOFING OVER EXISTING BUR C-EPDM SYSTEM 2001 FOR STEEL AND WOOD DECKS ARCHITECTURAL GUIDE SPECIFICATION REROOFING OVER EXISTING BUR C-EPDM SYSTEM 2001 FOR STEEL AND WOOD DECKS RESTRICTIONS - This specification is not applicable for 1) roof slopes in excess of one (1) inch

More information

SECTION Pedestrian Traffic Coatings{PRIVATE } 1.1 SUMMARY (Specification writer shall add, delete or amend, as deemed necessary)

SECTION Pedestrian Traffic Coatings{PRIVATE } 1.1 SUMMARY (Specification writer shall add, delete or amend, as deemed necessary) Guide Specification MiraFlex II For Plywood Decks Pedestrian Deck and Waterproofing System (Specification writer shall choose the most appropriate section that applies to a given scope of work, including

More information

GigaCrete Specification PlasterMax. PlasterMax : Fire Rated Plaster for Direct Application over Cement Masonry Units (CMU) Interior Walls

GigaCrete Specification PlasterMax. PlasterMax : Fire Rated Plaster for Direct Application over Cement Masonry Units (CMU) Interior Walls GigaCrete Inc. 6775 Speedway Blvd. Suite M105 Las Vegas, NV 89115 Ph (702) 643-6363 Fax (702) 643 1453 www.gigacrete.com GigaCrete Specification PlasterMax PlasterMax : Fire Rated Plaster for Direct Application

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS REPORT HOLDER: PAREX USA, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS REPORT HOLDER: PAREX USA, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2045 Reissued 01/2017 This report is subject to renewal 01/2019. DIVISION: 07 00

More information

SECTION WINDOW FILM. Display hidden notes to specifier. (Don't know how? Click Here) Copyright ARCAT, Inc. - All rights reserved

SECTION WINDOW FILM. Display hidden notes to specifier. (Don't know how? Click Here) Copyright ARCAT, Inc. - All rights reserved SECTION 08 87 13 WINDOW FILM Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2008-2010 ARCAT, Inc. - All rights reserved PART 1 GENERAL 1.1 SECTION INCLUDES A. Safety and Security

More information

SECTION EPOXY FLOORING SYSTEMS

SECTION EPOXY FLOORING SYSTEMS SECTION 09800 EPOXY FLOORING SYSTEMS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Air and Vapor Barrier 3015

Air and Vapor Barrier 3015 Air and Vapor Barrier 3015 Technical Data March 2017 Product Description 3M Air and Vapor Barrier 3015 is an air, moisture and water impermeable membrane with an aggressive, high-tack acrylic pressure

More information

Tensile ASTM D1970 MD = 939 psi / CD = 1252 psi Self Sealability / water penetration resistance around nails. ASTM D1970 Section 7.

Tensile ASTM D1970 MD = 939 psi / CD = 1252 psi Self Sealability / water penetration resistance around nails. ASTM D1970 Section 7. TECHNICAL DATA SHEET Protecto Universal Primer Free Membrane Self-adhered Flashing / Air Barrier / Vapor Retarder Thru-Wall Flashing / Below Grade Waterproofing Membrane with Super Stick technology TECHNICAL

More information

A. Source Limitations: Obtain each type of building insulation through one source.

A. Source Limitations: Obtain each type of building insulation through one source. SECTION 07210 - BUILDING INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

ARCHITECTURAL SPECIFICATIONS LOOSE LAID & BALLAST SYSTEM

ARCHITECTURAL SPECIFICATIONS LOOSE LAID & BALLAST SYSTEM 57460 Dewitt Street Elkhart, Indiana 46517-1078 Phone (574) 293-9096 Fax (574) 294-3450 800-628-2957 Web site: www.roofingproductsint.com ARCHITECTURAL SPECIFICATIONS LOOSE LAID & BALLAST SYSTEM B1.00

More information

Repair Maintenance Hangar Phase II August 2010

Repair Maintenance Hangar Phase II August 2010 SECTION 08800 GLASS AND GLAZING PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Monolithic glass. 2. Insulating glass. 3. Mirror glass. 4. Glazing accessories. B. Types of work in this section include

More information

INTRODUCTION. Inspection Procedures oinitial Inspection Report. Visual Inspection Physical Sampling (Core and Slit Samples)

INTRODUCTION. Inspection Procedures oinitial Inspection Report. Visual Inspection Physical Sampling (Core and Slit Samples) INTRODUCTION Inspection Procedures oinitial Inspection Report Visual Inspection Physical Sampling (Core and Slit Samples) ROOF INSPECTION PROCEDURES Occurs upon project completion Includes visual observation

More information

CITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO

CITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO SECTION 01010 - SCOPE OF WORK PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General provisions of Contract, General Conditions and Technical Specification Sections, apply to this Section. 1.02 PROJECT DESCRIPTION

More information

4411N 4411G 4412N 4412G

4411N 4411G 4412N 4412G Extreme Sealing Tape Technical Data October, 2011 Product Description 3M Extreme Sealing Tape is a family of single coated, pressure sensitive adhesive tapes designed for difficult sealing applications.

More information

WATERPROOFING TAMKOWATERPROOFING.COM

WATERPROOFING TAMKOWATERPROOFING.COM WATERPROOFING TAMKOWATERPROOFING.COM DIVISION 7 Powerful Water Control Using the same SBS-modified technology we pioneered in the 1970s, TAMKO continues to raise the standard in waterproofing to help you

More information

ELASTOFLEX ELASTOMERIC TEXTURED ACRYLIC WALL COATING SPECIFICATION

ELASTOFLEX ELASTOMERIC TEXTURED ACRYLIC WALL COATING SPECIFICATION ELASTOFLEX ELASTOMERIC TEXTURED ACRYLIC WALL COATING SPECIFICATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions,

More information

WATERPROOFING. MiraPLYTM. -H with SeamLOCKSM. Technology SCIENCE. SERVICE. SOLUTIONS. Description. Typical Properties.

WATERPROOFING. MiraPLYTM. -H with SeamLOCKSM. Technology SCIENCE. SERVICE. SOLUTIONS. Description. Typical Properties. MiraPLYTM -H with SeamLOCKSM Technology Description MiraPLY-H with SeamLOCK Technology is a nominal, 70-mil horizontal grade, self-adhering, blindside waterproofi ng membrane. The dual laminate membrane

More information

QUALITY COATING & REPAIR PRODUCTS

QUALITY COATING & REPAIR PRODUCTS 2011 Agricultural Product Catalog QUALITY COATING & REPAIR PRODUCTS Roof & Foundation Barn & Fence Driveway Concrete The Farm Pride Seal of Approval signifies a dedicated commitment to product quality

More information

PRODUCT SPECIFICATIONS

PRODUCT SPECIFICATIONS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: High density cast resin architectural products, including columns, panels, caps, bases, trim elements and balustrade systems. Specifier Note: Article below

More information

ARDEX GUIDE SPECIFICATION ARDEX CD Concrete Dressing and ARDEX CD FINE Concrete Dressing Polymer-Modified, Portland Cement-Based, Resurfacing Compound

ARDEX GUIDE SPECIFICATION ARDEX CD Concrete Dressing and ARDEX CD FINE Concrete Dressing Polymer-Modified, Portland Cement-Based, Resurfacing Compound ARDEX GUIDE SPECIFICATION ARDEX CD Concrete Dressing and ARDEX CD FINE Concrete Dressing Polymer-Modified, Portland Cement-Based, Resurfacing Compound SECTION 03 01 30 MAINTENANCE OF CAST-IN-PLACE CONCRETE

More information

ROOFING CONTRACTORS GENERAL TRADE KNOWLEDGE EXAMINATION CONTENT INFORMATION

ROOFING CONTRACTORS GENERAL TRADE KNOWLEDGE EXAMINATION CONTENT INFORMATION ROOFING CONTRACTORS GENERAL TRADE KNOWLEDGE EXAMINATION CONTENT INFORMATION Revised September 14 The General Trade Knowledge portion of the examination is administered daily in Computer Based Testing (CBT)

More information

Rubber Roofing Pocket Application Guide

Rubber Roofing Pocket Application Guide Rubber Roofing Pocket Application Guide Table of Contents Page 2.......................... General Information Page 2........................ Cautions and Warnings Page 3.......................... Recommended

More information

SECTION WINDOW FILM. Display hidden notes to specifier. (Don't know how? Click Here) Copyright ARCAT, Inc. - All rights reserved

SECTION WINDOW FILM. Display hidden notes to specifier. (Don't know how? Click Here) Copyright ARCAT, Inc. - All rights reserved SECTION 08 87 13 WINDOW FILM Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2008-2010 ARCAT, Inc. - All rights reserved PART 1 GENERAL 1.1 SECTION INCLUDES A. Safety and Security

More information

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1 Louis Armstrong New Orleans International Airport NOAB Project # 8910-01233 PART 1 - GENERAL SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS 1.1 RELATED DOCUMENTS A. Drawings and general provisions

More information

ROOF BALLAST MATERIALS ARCHITECTURAL CONCRETE PAVING SLABS SRS LEVELING BLOCK SYSTEM INSTALLATION PART GENERAL 1.

ROOF BALLAST MATERIALS ARCHITECTURAL CONCRETE PAVING SLABS SRS LEVELING BLOCK SYSTEM INSTALLATION PART GENERAL 1. 07555 - ROOF BALLAST MATERIALS ARCHITECTURAL CONCRETE PAVING SLABS SRS LEVELING BLOCK SYSTEM INSTALLATION PART 1.00 - GENERAL 1.01 SUMMARY: A. The work of this section consists of furnishing and installing

More information