END OF SECTION P:\09PROJECTS\09096HYA-MIA\WP\SPECS\CITY OF MIAMI SPECS\DIV 15\15936-AIR INLETS AND OUTLETS.DOCX

Size: px
Start display at page:

Download "END OF SECTION P:\09PROJECTS\09096HYA-MIA\WP\SPECS\CITY OF MIAMI SPECS\DIV 15\15936-AIR INLETS AND OUTLETS.DOCX"

Transcription

1 4. Install louver assembly to ensure moisture shed from flashings. 5. Secure louver frames in openings with concealed fasteners. 6. Install perimeter sealant around louver. 7. Contractor shall maintain minimum distances from air intakes to plumbing vents and/or exhaust openings as specified in International Mechanical code and local codes having jurisdiction. END OF SECTION P:\09PROJECTS\09096HYA-MIA\WP\SPECS\CITY OF MIAMI SPECS\DIV 15\15936-AIR INLETS AND OUTLETS.DOCX Air Inlets and Outlets Central Chilled Water Plant and Cooling Tower Design Section

2 SECTION METERS AND GAUGES FOR HVAC AND PLUMBING PART 1 - GENERAL 1.1 SCOPE OF WORK A. Included in this section are: 1. Thermometers for Pipes 2. Thermometers for Ducts 3. Pressure Gauges for Pipes 4. Test Plugs for Pipes 1.2 CODES AND STANDARDS (USE LATEST ADDITION) A. American Recovery and Reinvestment Act (ARRA) of 2009 Section 1605 Required Use of American Iron, Steel, and Manufactured Goods (applies to BASE BID A only) B. American Society of Mechanical Engineers (ASME) 1.3 SUBMITTALS 1. ASME B Pressure Gauges and Gauge Attachments 2. ASME B Thermometers, Direct Reading and Remote Reading 3. ASME B40.3 Bimetallic Actuated Thermometers A. Product Data: For each type of product indicated provide manufacturer s literature. B. Provide certificate indicating compliance with ARRA See Exhibit for sample certificate. This applies to Base Bid A only. C. Shop Drawings: Schedule for instrumentation indicating manufacturer s number, scale range, and location for each. D. Operations and Maintenance Data: Submit under provisions of Division 1. Accurately record location of all instrumentation. PART 2 - PRODUCTS 2.1 LIQUID-IN-GLASS THERMOMETERS FOR PIPES A. Acceptable Manufacturers 1. Ashcroft Inc. 2. H.O. Trerice Company 3. Miljoco Corporation 4. Weiss Instruments, Inc. B. Direct reading liquid-in-glass thermometer complying with ASME B Case: Die-cast aluminum, 9 long 2. Tube: Red or blue colored spirit (organic) filled, lens front 3. Tube Background: Aluminum white with permanently etched scale calibration in degrees Fahrenheit 4. Window: Clear acrylic or glass; provide glass for steam and condensate applications 5. Connector: Adjustable angle joint with positive locking device 6. Stem: Brass of length to suit installation Meters and Gauges for HVAC & Plumbing Central Chilled Water Plant and Cooling Tower Design Section

3 7. Accuracy: ±1 scale division 8. Thermowells: Brass, pressure-tight, socket-type fitting made for insertion into piping and of type, diameter, and length required to hold thermometer clear of any pipe insulation. 9. Basis of Design: H.O. Trerice Company Model AX BIMETALLIC-ACTUATED DIAL THERMOMETERS FOR DUCTS A. Acceptable Manufacturers 1. Ashcroft Inc. 2. H.O. Trerice Co. 3. Miljoco Corporation 4. Weiss Instruments, Inc. B. Direct mounting, bimetallic actuated dial thermometer complying with ASME B Case: 5 diameter dial in stainless steel 2. Element: Bimetallic helix actuated with silicone fluid damping 3. Dial and Pointer: White dialface calibrated in degrees F with black markings and black pointer 4. Window: Hermetically sealed glass lens 5. Connector: Adjustable angle with front recalibration 6. Stem: Stainless steel stem of length to suit installation with zinc plated steel mounting flange for fastening to sheet metal duct 7. Accuracy: ±1% of full scale 8. Basis of Design: H.O. Trerice Company Model B PRESSURE GAUGES FOR PIPES A. Acceptable Manufacturers 1. Ashcroft Inc. 2. H.O. Trerice Co. 3. Miljoco Corporation 4. Weiss Instruments, Inc. B. Dial type pressure gauge complying with ASME B Case: 4½ diameter black aluminum 2. Pressure Element Assembly: Bronze bourdon tube 3. Pressure Connection: Brass socket 4. Movement: Rotary stainless steel 5. Dial: Aluminum with permanently etched black scale calibrated in psi on white background 6. Window: Clear glass 7. Accuracy: ±0.5% percent of full scale 8. Basis of Design: H.O. Trerice Company Model 500XB C. Pressure Gauge Accessories 1. Valves a. ¼ NPT brass needle valve for a maximum pressure of 2,000 psig b. Basis of Design: H.O. Trerice Company Series Impulse Dampeners a. Brass with ¼ NPT connection Meters and Gauges for HVAC and Plumbing Section Central Chilled Water Plant and Cooling Tower Design October 14, 2011 G/BA #09096

4 b. Basis of Design: H.O. Trerice Company Series Coil Syphons 2.4 TEST PLUGS FOR PIPES a. Seamless brass, schedule 40, ¼ NPT connections b. H.O. Trerice Company Series 885 A. Acceptable Manufacturers 1. Petersen Products Co. 2. Sisco Manufacturing Company, Inc. 3. H.O. Trerice Company 4. Watts Water Technologies B. Test Plug (for uninsulated pipe) 1. ¼ by 1½ long brass fitting for receiving ⅛ outside diameter pressure or temperature probe a. Core inserts: Two self-sealing rubber valve cores with a color coded cap strap with gasket (1) Neoprene (maximum 200F) at 500 psi (2) Nordel (maximum 275F) at 500 psi b. Minimum Pressure and Temperature Rating: 1000 psi at 140F c. Basis of Design: Model 100 (neoprene core) or Model 110 (Nordel core) manufactured by Petersen Products Co. C. Test Plug (for insulated pipe) 1. ¼ by 3 long brass fitting for receiving ⅛ outside diameter pressure or temperature probe a. Core Inserts: Two self-sealing rubber valve cores with a color coded cap strap with gasket (1) Neoprene (maximum 200F) at 500 psi (2) Nordel (maximum 275F) at 500 psi b. Minimum Pressure and Temperature Rating: 1,000 psi at 140F c. Basis of Design: Model 100XL (neoprene core) or Model 110XL (Nordel core) manufactured by Petersen Products Co. 2.5 HYDRONIC INDICATION SYSTEM (COMPOUND PRESSURE GAUGE AND TRUMPET VALVE) A. Acceptable Manufacturers: 1. Flow Conditioning Corp. B. Hydronic indication systems shall consist of hydronic indicator (compound gauge) and four-port trumpet valve model TV-4 by Flow Conditioning Corp. 1. Hydronic indicator shall have 1% accuracy. Steel case shall be 4-1/2", stem mounted with screwed ring and crystal. Indicator shall have re-calibrator, compound scale calibrated in psi and feet from full vacuum to selected pressure and quick set dial for pressure comparison. Maximum indicator pressure shall exceed pump working pressure by minimum 50 psi. Meters and Gauges for HVAC & Plumbing Central Chilled Water Plant and Cooling Tower Design Section

5 2. Trumpet valve shall have spring return push button manifold of rugged brass construction with ports for connection to system at indicated points and with test connection for gauge calibration. PART 3 - EXECUTION 3.1 APPLICATIONS A. Pressure Gauges 1. Provide pressure gauges in locations indicated on drawings with a scale range of those shown below such that the range is between 1 ½ and 2 times two times the operating pressure of the system. B. Thermometers 3.2 INSTALLATION a psi b psi c psi d psi e psi f psi g psi h psi C. Install liquid-in-glass thermometers in all chilled water, hot water, condenser water, steam and condensate piping applications in locations shown on drawings and with ranges as shown in the following table: System Range (degrees F) Heating hot water 30F to 240F with 2F scale divisions Chilled water 0F to 100F with 1F scale divisions Condenser water 0F to 160F with 2F scale divisions. D. Install bimetallic-actuated dial thermometers with range of -40F to 110F with 2F scale divisions in air ducts in the following locations: 1. Outside air intake ducts or plenums 2. Return air ducts 3. Mixed air ducts or plenums A. Install in accordance with manufacturer s instructions. B. Install gauges and thermometers in locations where they are easily read from normal operating level. C. Thermometers for Pipes 1. Install direct-mounting thermometers and adjust vertical and tilted positions. 2. Install thermometers in piping systems in thermowells with socket extending to center of pipe or a minimum of 2 into fluid for piping less than 4. Enlarge pipes smaller than 2½ for installation of thermowells. D. Thermometers for Ducts 1. Install direct-mounting thermometers and adjust vertical and tilted positions. Meters and Gauges for HVAC and Plumbing Section Central Chilled Water Plant and Cooling Tower Design October 14, 2011 G/BA #09096

6 2. Install thermometers in air duct systems on flanges and attach to duct with screws. E. Pressure Gauges for Pipes 1. Install direct-mounting pressure gauges in piping tees with pressure gauge located on pipe at most readable position. 2. Provide needle valve and impulse dampener for each pressure gauge installed in pipe carrying all fluids except steam. 3. Provide needle valve and coil siphon fitting for each pressure gauge installed in pipe carrying steam. F. Install test plugs in tees in piping where indicated. G. Hydronic Indication System for Pumps 1. Install hydronic indication system on pumps as indicated on drawings. 2. Hydronic indication system shall be reliably and permanently attached to piping with heavy bracket at convenient height. Connect the system to the following ports: a. Upstream of strainer/suction diffuser b. Downstream of strainer/suction diffuser (pump inlet). c. Pump discharge d. Downstream of discharge isolation valve END OF SECTION P:\09PROJECTS\09096HYA-MIA\WP\SPECS\CITY OF MIAMI SPECS\DIV 15\15980-METERS AND GAUGES FOR HVAC & PLUMBING.DOCX Meters and Gauges for HVAC & Plumbing Central Chilled Water Plant and Cooling Tower Design Section

7 SECTION REFRIGERANT DETECTION SYSTEM PART 1 - GENERAL 1.1 SCOPE OF WORK A. Systems addressed in this section include the following: 1. Refrigerant detection system. B. Products/Materials provided by others: 1.2 DEFINITIONS Not applicable. 1. Control wiring. 2. Power wiring. 1.3 CODES AND STANDARDS A. American Recovery and Reinvestment Act (ARRA) of 2009 Section 1605 Required Use of American Iron, Steel, and Manufactured Goods (applies to BASE BID A only) B. ANSI/ASHRAE Standard Safety Standard for Refrigeration Systems. 1.4 QUALITY ASSURANCE Not applicable. 1.5 SUBMITTALS A. Product Data: 1. Provide manufacturer s detailed product literature and illustrations for all components. 2. Provide cross-sensitivity response data to other refrigerants as well as cleaning agents and solvents typically found in chiller equipment rooms. B. Provide certificate indicating compliance with ARRA See Exhibit for sample certificate. This applies to Base Bid A only. C. Provide manufacturer s installation instructions with Product Data. 1.6 DELIVERY, STORAGE AND HANDLING Not applicable. 1.7 SPARE PARTS A. Provide one (1) extra set of end-of-line filters and zero filter. 1.8 WARRANTY A. Provide one year parts and service warranty. 1.9 MAINTENANCE Not applicable. PART 2 - PRODUCTS 2.1 REFRIGERANT DETECTION SYSTEM Refrigerant Detection System Central Chilled Water Plant and Cooling Tower Design Section

8 A. Acceptable Manufacturers: 1. Mine Safety Appliances (MSA) Chillgard 2. O-I Analytical SAM 3. Bacharach HGM 4. Vulcain VA-SQN 5. Thermal Gas Systems Haloguard IR B. Refrigerant gas detection system supplier and installer shall be familiar with standard practices of safety and installation for refrigerant vapor detection systems and shall provide these systems as a normal course of business. C. System shall meet or exceed the latest ASHRAE Standard 15 requirements and EPA Standard 608 CFR. System shall incorporate all latest revisions to bring up to current standards. D. System shall utilize multi-point monitoring with sequential sampling. 1. System shall be capable of detecting the presence of any CFC, HCFC, HFC, or ammonia refrigerant, regardless of which particular refrigerants are selected (e.g., R-11, R-12, R-22, R-123, R-134a, etc.). 2. Oxygen deficiency monitoring is not acceptable 3. System shall be capable of indicating, alarming, initiating purge/vent, and shutting down equipment as specified below and in governing regulations. E. Control Panel and Equipment 1. Analyzer: a. Shall be microprocessor-based and employ photoacoustic infrared or pyroelectric infrared sensor technology. b. Electrochemical sensing technology employing depletion sensors and short term life sensors which deplete, poison, or consume as a normal part of their operation or storage shelf life shall not be acceptable. c. Analyzer shall respond to the target refrigerant only and will not sense, display, or false alarm to any interfering gases, including other refrigerants. d. The analyzer and sensor combination shall be compound-specific, and/or capable of monitoring multiple compounds and be calibrated for specific refrigerant R-11, R-12, R-22, R-123, R-134a or other as required by the installed refrigerants. e. Refrigerant selection for each channel of multiple-channel analyzers shall be independently selectable. f. Unit can be switched to monitor, at a future date, a different refrigerant type by changing one part and recalibrating (e.g., CFC-11 to HCFC-123, etc.). g. Accuracy shall be ±1 part per million (ppm) in the range of 0-50 ppm, and ±10% of reading in the range of ppm. Accuracy shall include the effects of all errors including, but not limited to, linearity, stability, sensitivity, temperature effects, and humidity effects. (1) Submit calculations and supporting data indicating compliance with this requirement. h. Minimum concentration sensed shall be no greater than 5 ppm. Refrigerant Detection System Section Central Chilled Water Plant and Cooling Tower Design October 14, 2011 G/BA #09096

9 i. Auto-zero calibration shall be initiated at one hour intervals (adjustable), or manually, with air from an uncontaminated air source. j. Analysis response time shall be 70 seconds to a 90% step change in concentration when sequencer is switched to the sample. k. No field calibration shall be required for start-up or during the first year of operation. 2. Display: a. Provide alphanumeric green backlit LCD display, ½ figures, lowenergy level type, easily visible across darkened mechanical room. b. Display shall automatically scroll concentration levels for each sample point and alternately display any alarm or malfunction messages without operator-initiated keypad intervention. c. Alarm display shall alternately annunciate and define each alarm by sample point zone and alarm level. 3. Diagnostics: a. Provide self-diagnostics with on-board malfunction data log and a malfunction contact for remote annunciation at the building automation system (BAS). b. Display flow loss of sample, ZERO line, and electrical malfunction. 4. Sequential Sampling System: a. Multi-point sequential sampling system shall be integrated into analyzer enclosure. b. Microprocessor shall sequentially control required flow valves and coordinate signals to monitor from remote sampling locations. c. Built-in sample pump for continuous sample draw with differential pressure flow switch for low flow indication. d. Sample draw line capability shall be not less than 500 feet excluding exhaust tubing. e. Each point shall have adjustable sampling time for various tubing lengths and adjustable levels of alarm. f. The monitor shall have add-on sample point expansion modules available for present configuration and for future expansion. Expansion modules for future expansion are to be provided. g. Provide the number of sampling points as shown on the Drawings. h. The maximum recycle time (i.e., time when sequencer begins sampling of point #1, until it begins sampling of point #1 in the next cycle) shall be as follows, based on eight channels: 5. Enclosure: 50-foot sample tube length, each point 100-foot sample tube length, each point Less than 4 minutes Less than 6 minutes (1) Submit calculations and supporting data indicating compliance with this requirement. (2) Multiple refrigerant detection systems may be provided in order to meet the maximum recycle time at no additional cost to Owner. Refrigerant Detection System Central Chilled Water Plant and Cooling Tower Design Section

10 a. Wall-mounted enclosure with no external keypads for tampering. b. Power supply shall have multiple-tap isolating transformer, on/off switch, and circuit breaker, and shall require no more than 75 watts (main unit and expansion units combined). 6. Alarms and Other Outputs: a. Dry alarm contacts: (1) Provide three independent dry alarm contacts, each rated for 5 amp., 120 VAC. (2) Contacts shall be field-selectable as follows: (a) Normally open (NO) or normally closed (NC) (b) Latched (manual reset) / Non-latched (auto reset) b. Provide three independently-adjustable levels of alarm for each sampling point. c. Provide a separate 4-20 ma DC analog output for each sampling point representing the refrigerant levels in parts per million (ppm). Multiplexing may be used in lieu of independent outputs when five (5) or more sample points are provided by the same system. d. Provide an RS-485 output to communicate all refrigerant levels to a building automation system (BAS) for centralized facility data logging and trending. F. Strobe Light and Alarm Horn: 1. Strobe Light: 15 candela strobe light or rotating beacon. 2. Alarm Horn: minimum of 72 dba at 10 feet. 3. Shall be UL or CSA listed. 4. Where located outdoors, unit shall be weatherproof and listed for outdoor use over a temperature range of -30F to 150F for all humidity levels. G. Description of Operation: 1. The three independent dry alarm contacts shall represent low, medium, and high alarm levels. 2. The low alarm shall be triggered whenever the gas concentration in any of the sampling points exceeds its respective low alarm level setpoint. a. The low alarm shall be an early leak warning alarm. b. Setpoint shall be set at 10 ppm, regardless of refrigerant type, to prevent eventual refrigerant loss. 3. The medium alarm shall be triggered whenever the gas concentration in any of the sampling points exceeds its respective medium alarm level setpoint. a. The medium alarm shall be a spill alarm. b. Shall energize the strobe light(s) and activates the exhaust fan in purge mode. c. Shall be manually reset at the monitor reset button. d. Setpoint shall be set at 25 ppm for R-123 and 300 ppm for all other refrigerants. 4. The high alarm shall be triggered whenever the gas concentration in any of the sampling points exceeds its respective high alarm level setpoint. Refrigerant Detection System Section Central Chilled Water Plant and Cooling Tower Design October 14, 2011 G/BA #09096

11 a. The high alarm shall be an evacuate alarm. b. Shall energize the strobe light(s) and the alarm horn(s), activates the exhaust fan in purge mode. c. Program alarm horn audio to be a different sound than other life safety alarm systems (e.g., fire alarm). d. Shall be manually reset at the monitor reset button. e. Setpoint shall be set at 50 ppm for R-123 and 500 ppm for all other refrigerants. H. Maintenance and Calibration: 1. No calibration shall be required for a period of one year from date of shipment. 2. Zero filter and end-of-line filters shall be included with initial system. 3. Systems which frequently generate nuisance alarms, do not meet recycle times, or which require frequent calibration or sensor replacement during the first two operating years will be replaced in their entirety by Contractor at no additional cost to Owner. PART 3 - EXECUTION 3.1 INSTALLATION A. Install in accordance with manufacturer s instructions. 3.2 SAMPLE TUBING A. Shall be ¼ O.D. seamless Type ACR (hard or annealed) complying with ASTM-B280 or seamless Type K, L or M (drawn or annealed) in accordance with ASTM-B88. B. Shall be installed in good workmanship manner and shall be field assembled with compression fittings. Soldered or brazed connections are not acceptable because of foreign gases, masses, and compounds introduced. C. Poly or other absorbing and leaching tubing is not acceptable as it corrupts actual sampled air. D. All bends shall have a minimum bend radius of not less than 5. E. Install in accordance with latest ASHRAE Standards and local building codes. Support at intervals no greater than 6 feet and at all bends. 3.3 LOCATION AND TERMINATION A. Tubing shall be field assembled with compression fittings and shall terminate 12 to 18 above floor level with 0.1 micron particulate/coalescent filters furnished by the monitor manufacturer. B. Locate sensing terminations downwind of the device to be monitored, in the direction of convection airflow, and where shown on the Drawings. Run in areas not subject to damage. C. Identify all sample tubing, both ends, with stamped (non-ferrous) metal tags labeling by both zone and chiller monitored. D. Control wiring shall be provided by the control contractor; power wiring by the electric contractor. 3.4 COMMISSIONING AND START-UP A. Unit must be factory calibrated. No field calibration is acceptable at time of installation. Refrigerant Detection System Central Chilled Water Plant and Cooling Tower Design Section

12 B. Conduct the complete installation and start-up in accordance with the manufacturer=s recommendations. Become familiar with the manufacturer s complete instruction book. 3.5 TRAINING A. Provide a minimum of one hour of instruction to Owner s authorized operating personnel in the proper operation and maintenance of the system. B. If monitor requires key strokes and/or programming to query information in normal daily operation, conduct additional programming instruction to Owner s satisfaction at no additional cost to Owner. C. Provide three hard copies of operating and maintenance instructions to Owner s designated representative. END OF SECTION P:\09PROJECTS\09096HYA-MIA\WP\SPECS\CITY OF MIAMI SPECS\DIV 15\15981-REFRIGERANT DETECTION SYSTEM.DOCX Refrigerant Detection System Section Central Chilled Water Plant and Cooling Tower Design October 14, 2011 G/BA #09096

13 SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 SCOPE OF WORK A. This Section includes TAB to produce design objectives for the following: 1.2 DEFINITIONS 1. Air Systems: a. Constant-volume air systems. 2. Hydronic Piping Systems: a. Variable-flow systems. b. Primary-secondary systems. 3. HVAC equipment quantitative-performance settings. 4. Verifying that automatic control devices are functioning properly. 5. Reporting results of activities and procedures specified in this Section. A. Adjust: To regulate fluid flow rate and air patterns at the terminal equipment, such as to reduce fan speed or adjust a damper. B. Balance: To proportion flows within the distribution system, including submains, branches, and terminals, according to indicated quantities. C. Barrier or Boundary: Construction, either vertical or horizontal, such as walls, floors, and ceilings that are designed and constructed to restrict the movement of airflow, smoke, odors, and other pollutants. D. Draft: A current of air, when referring to localized effect caused by one or more factors of high air velocity, low ambient temperature, or direction of airflow, whereby more heat is withdrawn from a person s skin than is normally dissipated. E. NC: Noise criteria. F. Procedure: An approach to and execution of a sequence of work operations to yield repeatable results. G. RC: Room criteria. H. Report Forms: Test data sheets for recording test data in logical order. I. Stair Pressurization System: A type of smoke-control system that is intended to positively pressurize stair towers with outdoor air by using fans to keep smoke from contaminating the stair towers during an alarm condition. J. Static Head: The pressure due to the weight of the fluid above the point of measurement. In a closed system, static head is equal on both sides of the pump. K. Suction Head: The height of fluid surface above the centerline of the pump on the suction side. L. System Effect: A phenomenon that can create undesired or unpredicted conditions that cause reduced capacities in all or part of a system. Testing, Adjusting and Balancing for HVAC Central Chilled Water Plant and Cooling Tower Design Section

14 M. System Effect Factors: Allowances used to calculate a reduction of the performance ratings of a fan when installed under conditions different from those presented when the fan was performance tested. N. TAB: Testing, adjusting, and balancing. O. Terminal: A point where the controlled medium, such as fluid or energy, enters or leaves the distribution system. P. Test: A procedure to determine quantitative performance of systems or equipment. Q. Testing, Adjusting, and Balancing (TAB) Firm: The entity responsible for performing and reporting TAB procedures. 1.3 REFERENCES A. American Recovery and Reinvestment Act of 2009 (applies to Base Bid A only) 1. Section 1512 Reporting and Registration Requirements 2. Section Required Use of American Iron, Steel, and Manufactured Goods 3. Section 1606 Wage Rate Requirements B. Davis- Bacon Act applicable sections (applies to both Base Bids) 1.4 SUBMITTALS A. Certified TAB Reports: Submit two copies of reports prepared, as specified in this Section, on approved forms certified by TAB firm. B. Warranties specified in this Section. 1.5 QUALITY ASSURANCE A. TAB Firm Qualifications: Engage a TAB firm certified by AABC, NEBB, or TABB. B. Certification of TAB Reports: Certify TAB field data reports. This certification includes the following: 1. Review field data reports to validate accuracy of data and to prepare certified TAB reports. 2. Certify that TAB team complied with approved TAB plan and the procedures specified and referenced in this Specification. C. TAB Report Forms: Use standard forms from AABC, NEBB or TABB/SMACNA. D. Instrumentation Type, Quantity, and Accuracy: As described in AABC s National Standards for Total System Balance, NEBB s Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems, Section II, Required Instrumentation for NEBB Certification, or the TABB Instrument List. E. Instrumentation Calibration: Calibrate instruments at least every six months or more frequently if required by instrument manufacturer. 1.6 COORDINATION 1. Keep an updated record of instrument calibration that indicates date of calibration and the name of party performing instrument calibration. A. Coordinate the efforts of factory-authorized service representatives for systems and equipment, HVAC controls installers, and other mechanics to operate HVAC systems and equipment to support and assist TAB activities. B. Notice: Provide seven days advance notice for each test. Include scheduled test dates and times. Testing, Adjusting and Balancing for HVAC Section Central Chilled Water Plant and Cooling Tower Design October 14, 2011 G/BA #09096

15 C. Perform TAB after leakage and pressure tests on air and water distribution systems have been satisfactorily completed. 1.7 WARRANTY A. Provide one of the following performance guarantees: 1. AABC National Project Performance Guarantee 2. NEBB Certificate of Conformance Certification 3. TABB Quality Assurance Program Guarantee B. Guarantee shall include the following provisions: 1. The certified TAB firm has tested and balanced systems according to the Contract Documents. 2. Systems are balanced to optimum performance capabilities within design and installation limits. PART 2 - PRODUCTS 2.1 NOT USED PART 3 - EXECUTION 3.1 EXAMINATION A. Examine the Contract Documents to become familiar with Project requirements and to discover conditions in systems designs that may preclude proper TAB of systems and equipment. 1. Contract Documents are defined in the General and Supplementary Conditions of Contract. 2. Verify that balancing devices, such as test ports, gage cocks, thermometer wells, flow-control devices, balancing valves and fittings, and manual volume dampers, are required by the Contract Documents. Verify that quantities and locations of these balancing devices are accessible and appropriate for effective balancing and for efficient system and equipment operation. B. Examine approved submittal data of HVAC systems and equipment. C. Examine Project Record Documents described in Section Project Closeout. D. Examine design data, including HVAC system descriptions, statements of design assumptions for environmental conditions and systems output, and statements of philosophies and assumptions about HVAC system and equipment controls. E. Examine equipment performance data including fan and pump curves. Relate performance data to Project conditions and requirements, including system effects that can create undesired or unpredicted conditions that cause reduced capacities in all or part of a system. Calculate system effect factors to reduce performance ratings of HVAC equipment when installed under conditions different from those presented when the equipment was performance tested at the factory. To calculate system effects for air systems, use tables and charts found in AMCA 201, Fans and Systems, Sections 7 through 10; or in SMACNA s HVAC Systems--Duct Design, Sections 5 and 6. Compare this data with the design data and installed conditions. Testing, Adjusting and Balancing for HVAC Central Chilled Water Plant and Cooling Tower Design Section

16 F. Examine system and equipment installations to verify that they are complete and that testing, cleaning, adjusting, and commissioning specified in individual Sections have been performed. G. Examine system and equipment test reports. H. Examine HVAC system and equipment installations to verify that indicated balancing devices, such as test ports, gage cocks, thermometer wells, flow-control devices, balancing valves and fittings, and manual volume dampers, are properly installed, and that their locations are accessible and appropriate for effective balancing and for efficient system and equipment operation. I. Examine systems for functional deficiencies that cannot be corrected by adjusting and balancing. J. Examine HVAC equipment to ensure that clean filters have been installed, bearings are greased, belts are aligned and tight, and equipment with functioning controls is ready for operation. K. Examine strainers for clean screens and proper perforations. L. Examine heat-transfer coils for correct piping connections and for clean and straight fins. M. Examine system pumps to ensure absence of entrained air in the suction piping. N. Examine equipment for installation and for properly operating safety interlocks and controls. O. Examine automatic temperature system components to verify the following: 1. Dampers, valves, and other controlled devices are operated by the intended controller. 2. Dampers and valves are in the position indicated by the controller. 3. Integrity of valves and dampers for free and full operation and for tightness of fully closed and fully open positions. 4. Automatic modulating and shutoff valves, including two-way valves and threeway mixing and diverting valves, are properly connected. 5. Thermostats and humidistats are located to avoid adverse effects of sunlight, drafts, and cold walls. 6. Sensors are located to sense only the intended conditions. 7. Sequence of operation for control modes is according to the Contract Documents. 8. Controller set points are set at indicated values. 9. Interlocked systems are operating. P. Report deficiencies discovered before and during performance of TAB procedures. Observe and record system reactions to changes in conditions. Record default set points if different from indicated values. 3.2 PREPARATION A. Prepare a TAB plan that includes strategies and step-by-step procedures. B. Complete system readiness checks and prepare system readiness reports. Verify the following: 1. Permanent electrical power wiring is complete. 2. Hydronic systems are filled, clean, and free of air. 3. Automatic temperature-control systems are operational. 4. Equipment and duct access doors are securely closed. Testing, Adjusting and Balancing for HVAC Section Central Chilled Water Plant and Cooling Tower Design October 14, 2011 G/BA #09096

17 5. Balance, smoke, and fire dampers are open. 6. Isolating and balancing valves are open and control valves are operational. 7. Ceilings are installed in critical areas where air-pattern adjustments are required and access to balancing devices is provided. 8. Windows and doors can be closed so indicated conditions for system operations can be met. 3.3 GENERAL PROCEDURES FOR TESTING AND BALANCING A. Perform testing and balancing procedures on each system according to the procedures contained in AABC s National Standards for Total System Balance, NEBB s Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems, or SMACNA s HVAC Systems - Testing, Adjusting, and Balancing and this Section. B. Cut insulation, ducts, pipes, and equipment cabinets for installation of test probes to the minimum extent necessary to allow adequate performance of procedures. After testing and balancing, close probe holes and patch insulation with new materials identical to those removed. Restore vapor barrier and finish according to insulation Specifications for this Project. C. Mark equipment and balancing device settings with paint or other suitable, permanent identification material, including damper-control positions, valve position indicators, fan-speed-control levers, and similar controls and devices, to show final settings. D. Take and report testing and balancing measurements in inch-pound (IP) units. 3.4 GENERAL PROCEDURES FOR BALANCING AIR SYSTEMS A. Prepare test reports for both fans and outlets. Obtain manufacturer s outlet factors and recommended testing procedures. Crosscheck the summation of required outlet volumes with required fan volumes. B. Determine the best locations in main and branch ducts for accurate duct airflow measurements. C. Check airflow patterns from the outside-air louvers and dampers and the return- and exhaust-air dampers, through the supply-fan discharge and mixing dampers. D. Locate start-stop and disconnect switches, electrical interlocks, and motor starters. E. Verify that motor starters are equipped with properly sized thermal protection. F. Check dampers for proper position to achieve desired airflow path. G. Check for airflow blockages. H. Check condensate drains for proper connections and functioning. I. Check for proper sealing of air-handling unit components. J. Check for proper sealing of air duct system. 3.5 PROCEDURES FOR CONSTANT-VOLUME AIR SYSTEMS A. Adjust fans to deliver total indicated airflows within the maximum allowable fan speed listed by fan manufacturer. 1. Measure fan static pressures to determine actual static pressure as follows: a. Measure outlet static pressure as far downstream from the fan as practicable and upstream from restrictions in ducts such as elbows and transitions. Testing, Adjusting and Balancing for HVAC Central Chilled Water Plant and Cooling Tower Design Section

18 b. Measure static pressure directly at the fan outlet or through the flexible connection. c. Measure inlet static pressure of single-inlet fans in the inlet duct as near the fan as possible, upstream from flexible connection and downstream from duct restrictions. d. Measure inlet static pressure of double-inlet fans through the wall of the plenum that houses the fan. 2. Measure static pressure across each component that makes up an air-handling unit, rooftop unit, and other air-handling and -treating equipment. a. Simulate dirty filter operation and record the point at which maintenance personnel must change filters. 3. Measure static pressures entering and leaving other devices such as sound traps, heat recovery equipment, and air washers, under final balanced conditions. 4. Compare design data with installed conditions to determine variations in design static pressures versus actual static pressures. Compare actual system effect factors with calculated system effect factors to identify where variations occur. Recommend corrective action to align design and actual conditions. 5. Obtain approval from Engineer for adjustment of fan speed higher or lower than indicated speed. Make required adjustments to pulley sizes, motor sizes, and electrical connections to accommodate fan-speed changes. 6. Do not make fan-speed adjustments that result in motor overload. Consult equipment manufacturers about fan-speed safety factors. Modulate dampers and measure fan-motor amperage to ensure that no overload will occur. Measure amperage in full cooling, full heating, economizer, and any other operating modes to determine the maximum required brake horsepower. 7. Make required adjustments to vane axial fan blade pitch angle to achieve required airflow. 8. Provide sheaves, pulleys and belts required for adjustment of fan speed. B. Adjust volume dampers for main duct, submain ducts, and major branch ducts to indicated airflows within specified tolerances. 1. Measure static pressure at a point downstream from the balancing damper and adjust volume dampers until the proper static pressure is achieved. a. Where sufficient space in submain and branch ducts is unavailable for Pitot-tube traverse measurements, measure airflow at terminal outlets and inlets and calculate the total airflow for that zone. 2. Remeasure each submain and branch duct after all have been adjusted. Continue to adjust submain and branch ducts to indicated airflows within specified tolerances. C. Measure terminal outlets and inlets without making adjustments. 1. Measure terminal outlets using a direct-reading hood or outlet manufacturer s written instructions and calculating factors. D. Adjust terminal outlets and inlets for each space to indicated airflows within specified tolerances of indicated values. Make adjustments using volume dampers rather than extractors and the dampers at air terminals. Testing, Adjusting and Balancing for HVAC Section Central Chilled Water Plant and Cooling Tower Design October 14, 2011 G/BA #09096

19 1. Adjust each outlet in same room or space to within specified tolerances of indicated quantities without generating noise levels above the limitations prescribed by the Contract Documents. 2. Adjust patterns of adjustable outlets for proper distribution without drafts. 3.6 GENERAL PROCEDURES FOR HYDRONIC SYSTEMS A. Prepare test reports with pertinent design data and number in sequence starting at pump to end of system. Check the sum of branch-circuit flows against approved pump flow rate. Correct variations that exceed plus or minus 5 percent. B. Prepare schematic diagrams of systems as-built piping layouts. C. Prepare hydronic systems for testing and balancing according to the following, in addition to the general preparation procedures specified above: 1. Open all manual valves for maximum flow. 2. Check expansion tank liquid level. 3. Check makeup-water-station pressure gage for adequate pressure for highest vent. 4. Check flow-control valves for specified sequence of operation and set at indicated flow. 5. Set differential-pressure control valves at the specified differential pressure. Do not set at fully closed position when pump is positive-displacement type unless several terminal valves are kept open. 6. Set system controls so automatic valves are wide open to heat exchangers. 7. Check pump-motor load. If motor is overloaded, throttle main flow-balancing device so motor nameplate rating is not exceeded. 8. Check air vents for a forceful liquid flow exiting from vents when manually operated. 3.7 PROCEDURES FOR HYDRONIC SYSTEMS A. Measure water flow at pumps. Use the following procedures, except for positivedisplacement pumps: 1. Verify impeller size by operating the pump with the discharge valve closed. Read pressure differential across the pump. Convert pressure to head and correct for differences in gage heights. Note the point on manufacturer s pump curve at zero flow and verify that the pump has the intended impeller size. 2. Check system resistance. With all valves open, read pressure differential across the pump and mark pump manufacturer s head-capacity curve. Adjust pump discharge valve until indicated water flow is achieved. 3. Verify pump-motor brake horsepower. Calculate the intended brake horsepower for the system based on pump manufacturer s performance data. Compare calculated brake horsepower with nameplate data on the pump motor. Report conditions where actual amperage exceeds motor nameplate amperage. 4. Report flow rates that are not within plus or minus 5 percent of design. B. Set calibrated balancing valves, if installed, at calculated presettings. C. Measure flow at all stations and adjust, where necessary, to obtain first balance. 1. System components that have Cv rating or an accurately cataloged flowpressure-drop relationship may be used as a flow-indicating device. Testing, Adjusting and Balancing for HVAC Central Chilled Water Plant and Cooling Tower Design Section

20 D. Measure flow at main balancing station and set main balancing device to achieve flow that is 5 percent greater than indicated flow. E. Adjust balancing stations to within specified tolerances of indicated flow rate as follows: 1. Determine the balancing station with the highest percentage over indicated flow. 2. Adjust each station in turn, beginning with the station with the highest percentage over indicated flow and proceeding to the station with the lowest percentage over indicated flow. 3. Record settings and mark balancing devices. F. Measure pump flow rate and make final measurements of pump amperage, voltage, rpm, pump heads, and systems pressures and temperatures including outdoor-air temperature. G. Measure the differential-pressure control valve settings existing at the conclusions of balancing. H. When the balanced pump discharge valve position is greater than 45 percent closed, the pump impeller shall be trimmed or replaced. Calculate the required impeller size and notify the Engineer and Contractor. The Contractor shall furnish and install the new impeller. Once the new impeller is installed, measure pump flow rate and set discharge valve to achieve flow that is 5 percent greater than indicated flow. Make final measurements of pump flow, shutoff head, suction and discharge pressures, rpm, voltage and amperage. 3.8 PROCEDURES FOR VARIABLE-FLOW HYDRONIC SYSTEMS A. Balance systems with automatic two- and three-way control valves by setting systems at maximum flow through heat-exchange terminals and proceed as specified above for hydronic systems. B. Once the full flow condition is balanced and the system differential pressure setpoint is established, to control the variable speed pumps, observe the flow on the circuit with the greatest resistance as the other circuits are closed one at a time. The flow in the observed circuit should remain equal to, or greater than, the previously set flow. 3.9 PROCEDURES FOR PRIMARY-SECONDARY-FLOW HYDRONIC SYSTEMS A. Balance the primary system crossover flow first, then balance the secondary system PROCEDURES FOR HEAT EXCHANGERS A. Measure water flow through all circuits. B. Adjust water flow to within specified tolerances. C. Measure inlet and outlet water temperatures. D. Check the setting and operation of safety and relief valves. Record settings PROCEDURES FOR MOTORS A. Motors, ½ HP and Larger: Test at final balanced conditions and record the following data: 1. Manufacturer, model, and serial numbers. 2. Motor horsepower rating. 3. Motor rpm. 4. Efficiency rating. 5. Nameplate and measured voltage, each phase. Testing, Adjusting and Balancing for HVAC Section Central Chilled Water Plant and Cooling Tower Design October 14, 2011 G/BA #09096

21 6. Nameplate and measured amperage, each phase. 7. Starter thermal-protection-element rating. B. Motors Driven by Variable-Frequency Controllers: Test for proper operation at speeds varying from minimum to maximum. Test the manual bypass for the controller to prove proper operation. Record observations, including controller manufacturer, model and serial numbers, and nameplate data PROCEDURES FOR CHILLERS A. Balance water flow through each evaporator and condenser to within specified tolerances of indicated flow with all pumps operating. With only one chiller operating in a multiple chiller installation, do not exceed the flow for the maximum tube velocity recommended by the chiller manufacturer. Measure and record the following data with each chiller operating at design conditions: 1. Evaporator-water entering and leaving temperatures, pressure drop, and water flow. 2. If water-cooled chillers, condenser-water entering and leaving temperatures, pressure drop, and water flow. 3. Evaporator and condenser refrigerant temperatures and pressures, using instruments furnished by chiller manufacturer. 4. Power factor if factory-installed instrumentation is furnished for measuring kilowatt. 5. Kilowatt input if factory-installed instrumentation is furnished for measuring kilowatt. 6. Capacity: Calculate in tons of cooling. 7. If air-cooled chillers, verify condenser-fan rotation and record fan and motor data including number of fans and entering- and leaving-air temperatures PROCEDURES FOR COOLING TOWERS A. Shut off makeup water for the duration of the test, and verify that makeup and blowdown systems are fully operational after tests and before leaving the equipment. Perform the following tests and record the results: 1. Measure condenser-water flow to each cell of the cooling tower. 2. Measure entering- and leaving-water temperatures. 3. Measure wet- and dry-bulb temperatures of entering air. 4. Measure wet- and dry-bulb temperatures of leaving air. 5. Measure condenser-water flow rate recirculating through the cooling tower. 6. Measure cooling tower pump discharge pressure. 7. Adjust water level and feed rate of makeup-water system PROCEDURES FOR HEAT-TRANSFER COILS A. Water Coils: Measure the following data for each coil: 1. Entering- and leaving-water temperature. 2. Water flow rate. 3. Water pressure drop. 4. Dry-bulb temperature of entering and leaving air. 5. Wet-bulb temperature of entering and leaving air for cooling coils. 6. Airflow. 7. Air pressure drop. Testing, Adjusting and Balancing for HVAC Central Chilled Water Plant and Cooling Tower Design Section

22 3.15 TEMPERATURE-CONTROL VERIFICATION A. Verify that controllers are calibrated and commissioned. B. Check transmitter and controller locations and note conditions that would adversely affect control functions. C. Record controller settings and note variances between set points and actual measurements. D. Check the operation of limiting controllers (i.e., high- and low-temperature controllers). E. Check free travel and proper operation of control devices such as damper and valve operators. F. Check the sequence of operation of control devices. Note air pressures and device positions and correlate with airflow and water flow measurements. Note the speed of response to input changes. G. Check the interaction of electrically operated switch transducers. H. Check the interaction of interlock and lockout systems. I. Check main control supply-air pressure and observe compressor and dryer operations. J. Record voltages of power supply and controller output. Determine whether the system operates on a grounded or ungrounded power supply. K. Note operation of electric actuators using spring return for proper fail-safe operations TOLERANCES A. Adjust main ducts in air handling systems to ± 5% of design parameters for supply and exhaust/return systems. Adjust individual terminals and branches to ± 7.5% of design conditions for supply and exhaust/return systems. For applications where differential pressures must be maintained, use the following criteria: Positively pressurized spaces Supply air... 0 to +10% Exhaust air... 0 to -10% Return air... 0 to -10% Negatively pressurized spaces Supply air... 0 to -10% Exhaust air... 0 to +10% Return air... 0 to +10% B. Please note that differentials between supply and exhaust/return airflows, as indicated in the drawings, indicate those spaces with a requirement for differential pressure to be maintained. C. Adjust hydronic systems to ± 5% of design parameters REPORTING A. Initial Construction-Phase Report: Based on examination of the Contract Documents as specified in Examination Article, prepare a report on the adequacy of design for systems balancing devices. Recommend changes and additions to systems balancing devices to facilitate proper performance measuring and balancing. Recommend changes and additions to HVAC systems and general construction to allow access for performance measuring and balancing devices. Testing, Adjusting and Balancing for HVAC Section Central Chilled Water Plant and Cooling Tower Design October 14, 2011 G/BA #09096

23 B. Status Reports: As Work progresses, prepare reports to describe completed procedures, procedures in progress, and scheduled procedures. Include a list of deficiencies and problems found in systems being tested and balanced. Prepare a separate report for each system and each building floor for systems serving multiple floors FINAL REPORT A. General: Typewritten, or computer printout in letter-quality font, on standard bond paper, in three-ring binder, tabulated and divided into sections by tested and balanced systems. B. Include a certification sheet in front of binder signed and sealed by the certified testing and balancing engineer. 1. Include a list of instruments used for procedures, along with proof of calibration. C. Final Report Contents: In addition to certified field report data, include the following: 1. Pump curves. 2. Fan curves. 3. Manufacturers test data. 4. Field test reports prepared by system and equipment installers. 5. Other information relative to equipment performance, but do not include Shop Drawings and Product Data. D. General Report Data: In addition to form titles and entries, include the following data in the final report, as applicable: 1. Title page. 2. Name and address of TAB firm. 3. Project name. 4. Project location. 5. Architect s name and address. 6. Engineer s name and address. 7. Contractor s name and address. 8. Report date. 9. Signature of TAB firm who certifies the report. 10. Table of Contents with the total number of pages defined for each section of the report. Number each page in the report. 11. Summary of contents including the following: a. Indicated versus final performance. b. Notable characteristics of systems. c. Description of system operation sequence if it varies from the Contract Documents. 12. Nomenclature sheets for each item of equipment. 13. Data for terminal units, including manufacturer, type size, and fittings. 14. Notes to explain why certain final data in the body of reports varies from indicated values. 15. Test conditions for fans and pump performance forms including the following: a. Settings for outside-, return-, and exhaust-air dampers. b. Conditions of filters. c. Cooling coil, wet- and dry-bulb conditions. d. Face and bypass damper settings at coils. Testing, Adjusting and Balancing for HVAC Central Chilled Water Plant and Cooling Tower Design Section

B. ASHRAE 1991 HVAC Applications Handbook: Chapter 34--Testing, Adjusting and Balancing.

B. ASHRAE 1991 HVAC Applications Handbook: Chapter 34--Testing, Adjusting and Balancing. PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 230593 TESTING, ADJUSTING, AND BALANCING A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION COOLING TOWER

SECTION COOLING TOWER PART 1 GENERAL 1.1 SECTION INCLUDES A. Mechanical induced draft Cooling Tower B. Controls C. Ladder and handrails 1.2 REFERENCES SECTION 23 65 00 COOLING TOWER A. ANSI/AFBMA 9 - Load Rating and Fatigue

More information

SECTION ROTARY SCREW WATER CHILLERS

SECTION ROTARY SCREW WATER CHILLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

B. System Design and Performance Requirements

B. System Design and Performance Requirements 15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

PROJECT TITLE PROJECT NO.: CONTRACT TITLE UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

PROJECT TITLE PROJECT NO.: CONTRACT TITLE UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA PRE-START-UP/START-UP CHECKLIST CHILLED WATER SYSTEM NOTE: University s Representative must be notified and scheduled to witness test prior to any start up of equipment. A. Chilled Water Pumps 1. Submittal

More information

Series Sump and Sewage Systems

Series Sump and Sewage Systems Series 000 Sump and Sewage Systems file no: 0. date: may 17, 13 supersedes: 0. date: march 29, 13 Series 000 Sump Series 0 & 2 Armstrong offers a complete range of high performance, easily maintained Column

More information

SECTION HVAC INSTRUMENTATION AND CONTROLS INSTALLATION. (Applicable to IUPUI Only)

SECTION HVAC INSTRUMENTATION AND CONTROLS INSTALLATION. (Applicable to IUPUI Only) SECTION 15957 (Applicable to IUPUI Only) I. GENERAL A. NOTES 1. The University has a pre-purchase agreement (PPA) with Johnson Controls (JCI) and Siemens Building Technologies (SBT). The University will

More information

2. Water Pressure Booster Systems. 3. Duplex Pedestal Type Sump Pumps.

2. Water Pressure Booster Systems. 3. Duplex Pedestal Type Sump Pumps. PART 1: GENERAL 1.01 Purpose: A. The design guidelines contained herein includes the requirements for pumps utilized for plumbing systems at Texas State University. It is the intention of this document

More information

SECTION INFLUENT EQUALIZATION TANK PUMPS

SECTION INFLUENT EQUALIZATION TANK PUMPS PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall furnish and install all materials, labor and equipment to put into service the Influent Equalization Pumps in accordance with the Contract Drawings

More information

Price Single Duct Terminal Units

Price Single Duct Terminal Units Price Single Duct Terminal Units Division 23 Heating, Ventilating, and Air Conditioning Section 23 36 00 Air Terminal Units The following specification is for a defined application. Price would be pleased

More information

SECTION AIR DUCT CLEANING

SECTION AIR DUCT CLEANING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

SECTION COMMON MOTOR REQUIREMENTS FORHVAC EQUIPMENT

SECTION COMMON MOTOR REQUIREMENTS FORHVAC EQUIPMENT SECTION 230513- COMMON MOTOR REQUIREMENTS FORHVAC EQUIPMENT PART I - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION PACKAGE BOOSTER PUMP STATIONS

SECTION PACKAGE BOOSTER PUMP STATIONS SECTION 331223 PACKAGE BOOSTER PUMP STATIONS Scope: The Contractor shall install a pump station at two locations to be determined by the Owner. These pump stations shall be designed to deliver flow to

More information

1.02 Related Sections A. Section Heating, Ventilation and Air Conditioning (HVAC). C. Section Pneumatic and Electric Control HVAC.

1.02 Related Sections A. Section Heating, Ventilation and Air Conditioning (HVAC). C. Section Pneumatic and Electric Control HVAC. PART 1: GENERAL 1.01 Section Includes A. Dual duct terminal units. B. Variable volume regulators. C. Integral damper motor operators. D. Integral controls. 1.02 Related Sections A. Section 23 00 00 Heating,

More information

C. ASSE 1013 Performance Requirements for Reduced Pressure Principle Backflow Preventers.

C. ASSE 1013 Performance Requirements for Reduced Pressure Principle Backflow Preventers. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

A. This Section includes ceiling- and wall-mounted diffusers, registers, grilles and louvers.

A. This Section includes ceiling- and wall-mounted diffusers, registers, grilles and louvers. SECTION 23 37 13 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION SANITARY WASTE INTERCEPTORS

SECTION SANITARY WASTE INTERCEPTORS SECTION 22 13 23 SANITARY WASTE INTERCEPTORS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

Fiberglass Cooling Towers

Fiberglass Cooling Towers Fiberglass Cooling Towers Available in sizes from 100 to 240 tons. FC Series 700 Fiberglass Cooling Tower Available in sizes from 170 to 240 tons. No other fiberglass cooling tower comes with as many high-quality

More information

SECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 08332 [08 33 13] COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Metal Counter

More information

SECTION SLUDGE HOLDING TANK DECANTER PUMP

SECTION SLUDGE HOLDING TANK DECANTER PUMP PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall furnish and install all materials, labor and equipment to put into service the Sludge Holding Tank Decanter Pumping System in accordance with the

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

SUPERSTEAM USG LINE UNFIRED STEAM GENERATOR. Humidification. Sterilization. Pharmaceutical

SUPERSTEAM USG LINE UNFIRED STEAM GENERATOR. Humidification. Sterilization. Pharmaceutical SUPERSTEAM USG LINE UNFIRED STEAM GENERATOR. Humidification. Sterilization. Pharmaceutical Basic USG Package Includes: ASME Code Constructed and National Board Registered Vessel Fiberglass Insulation 20

More information

ACBC Floor Mounted Active Beam

ACBC Floor Mounted Active Beam Floor Mounted Active Beam The Price Floor Mounted Active Beam,, is designed for occupant comfort. It provides high cooling and heating capacities while simultaneously supplying ventilation air from a DOAS

More information

YARWAY HANCOCK CONTINUOUS BLOWDOWN GLOBE VALVE SERIES 5505

YARWAY HANCOCK CONTINUOUS BLOWDOWN GLOBE VALVE SERIES 5505 Advanced construction features of this high pressure drop angle globe valve provide quality and long service life. FEATURES GENERAL APPLICATION In addition to continuous blowdown service, the Yarway high

More information

Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619

Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619 AABC Commissioning Group AIA Provider Number 50111116 Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619 Jim Hall, PE, TBE, CxA Systems Management & Balancing,

More information

Field Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE

Field Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE Field Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE The purpose of this article is to discuss the measuring and reporting of temperatures at heat transfer equipment during the Testing

More information

OAKDALE CHILLED WATER PLANT CAPACITY UPGRADES UI PROJECT INSTALL CHILLERS SECTION COMMISSIONING

OAKDALE CHILLED WATER PLANT CAPACITY UPGRADES UI PROJECT INSTALL CHILLERS SECTION COMMISSIONING PART I GENERAL 1.01 SECTION INCLUDES A. Commissioning objectives. B. Roles and responsibilities. C. Test Equipment. D. Systems to be commissioned. E. Construction Checklist requirements. SECTION 01 91

More information

MASTER. Water Conditioning Corp. OPERATION MANUAL. PURO PRO 1200 SCP Series Modular Reverse Osmosis System. January 2012 Version

MASTER. Water Conditioning Corp. OPERATION MANUAL. PURO PRO 1200 SCP Series Modular Reverse Osmosis System.  January 2012 Version MASTER Water Conditioning Corp. www.masterwater.com OPERATION MANUAL PURO PRO 1200 SCP Series Modular Reverse Osmosis System January 2012 Version Table of Contents Model Number... 1 Shipping Description

More information

St. Monica Food Pantry Testing, Adjusting, & Balancing for HVAC sys-tek No

St. Monica Food Pantry Testing, Adjusting, & Balancing for HVAC sys-tek No St. Monica Food Pantry 23 0593-1 HVAC WORK DIVISION 23 SECTION 230593 TESTING, ADJUSTING, & BALANCING FOR HVAC PART 1. GENERAL 1.1 DESCRIPTION OF WORK A. Air balancing of dedicated outside air systems

More information

VPL-3200B Residential Vertical Platform Lift Technical Specifications

VPL-3200B Residential Vertical Platform Lift Technical Specifications Page 1 of 5 VPL-3200B Residential Vertical Platform Lift Technical Specifications MODEL NUMBER: VPL-3200B Series: Models VPL-3210B, VPL-3212B and VPL-3214B (DC-powered units) U.S. F.D.A. CLASSIFICATION:

More information

Pioneer Forced Draft Cooling Tower Specifications

Pioneer Forced Draft Cooling Tower Specifications Delta Cooling Towers, Inc. 41 Pine Street P.O. Box 315 Rockaway, New Jersey 07866-0315 Telephone 973.586.2201 Fax 973.586.2243 www.deltacooling.com sales@deltacooling.com Pioneer Forced Draft Cooling Tower

More information

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Welded System

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Welded System SECTION 13096 RADIO FREQUENCY SHIELDING ENCLOSURE RF Welded System Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13096-1 RF WELDED SYSTEM PART 1 GENERAL 1.1 SECTION

More information

SECTION ACOUSTICAL PANEL CEILINGS

SECTION ACOUSTICAL PANEL CEILINGS SECTION 095113 ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

The following document can be provided to an Engineer, Contractor, or Owner to allow them to

The following document can be provided to an Engineer, Contractor, or Owner to allow them to MESAN series MXL Engineering Guide Specifications The following document can be provided to an Engineer, Contractor, or Owner to allow them to properly specify MESAN s MXL series Cooling Towers. 15XXX-

More information

SPECIFICATIONS - DETAILED PROVISIONS Section Horizontal Centrifugal Water Pumps C O N T E N T S

SPECIFICATIONS - DETAILED PROVISIONS Section Horizontal Centrifugal Water Pumps C O N T E N T S SPECIFICATIONS - DETAILED PROVISIONS Section 11931 - Horizontal Centrifugal Water Pumps C O N T E N T S PART 1 - GENERAL... 1 1.01 PUMP - GENERAL... 1 1.02 CERTIFIED PUMP CURVES... 1 1.03 NPSH REQUIREMENTS...

More information

YORK BULKHEAD MOUNTED CHILLED BEAMS ENGINEERING GUIDE

YORK BULKHEAD MOUNTED CHILLED BEAMS ENGINEERING GUIDE YORK BULKHEAD MOUNTED CHILLED BEAMS ENGINEERING GUIDE Contents YORK Bulkhead Active Chilled Beams 3 CB-ABB-YK / CB-ABC-YK Performance Data 5 CB-ABB-YK Dimensions 10 CB-ABC-YK Dimensions 11 Specifications

More information

B. Shop Drawings: For air terminal units. Include plans, elevations, sections, details, and attachments to other work.

B. Shop Drawings: For air terminal units. Include plans, elevations, sections, details, and attachments to other work. SECTION 233600 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fan-powered air terminal units. 2. Shutoff, single-duct air terminal units. 1.2 PERFORMANCE REQUIREMENTS A. Structural Performance:

More information

ARRANGEMENT AND WORKING OF MULTIPORT FLOW SELECTOR VALVE IN PRODUCTION MANIFOLD:

ARRANGEMENT AND WORKING OF MULTIPORT FLOW SELECTOR VALVE IN PRODUCTION MANIFOLD: GENERAL DESCRIPTION Crude oil well test manifold to be provide as Multiport Flow Selector (MPFS) technology. It provides a cost effective method for selecting and diverting well fluids from an individual

More information

SUGGESTED SPECIFICATIONS Pump Frames through 64132

SUGGESTED SPECIFICATIONS Pump Frames through 64132 TYPE HBB - HORIZONTAL SOLIDS-HANDLING WASTEWATER PUMPS Pump Frames 44081 through 64132 GENERAL Furnish and install Horizontal Flexible Coupled Dry Pit Pumping Units complete with all accessories and appurtenances

More information

SECTION HVAC GRAVITY VENTILATORS

SECTION HVAC GRAVITY VENTILATORS SECTION 23 37 23 HVAC GRAVITY VENTILATORS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Essex County College - West Essex Campus Addition And Renovations Dib # / SECTION DOMESTIC WATER PIPING SPECIALTIES

Essex County College - West Essex Campus Addition And Renovations Dib # / SECTION DOMESTIC WATER PIPING SPECIALTIES Essex County College - West Essex Campus Addition And Renovations Dib # 54292 / 11-14 SECTION 221119 - DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions

More information

SECTION CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION

SECTION CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION SECTION 22 11 16.13 CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION PART 1: GENERAL 1.01 SUMMARY A. This Section includes water-distribution backflow prevention products and installation specifications.

More information

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST ENVELOPE REQUIREMENTS Project: Date: Instructions RECOMMENDED: List performance values, note exceptions that were applied, or provide other

More information

HYDROMATIC W/D/V-A1 SUBMERSIBLE SUMP/EFFLUENT

HYDROMATIC W/D/V-A1 SUBMERSIBLE SUMP/EFFLUENT PERFORMANCE DATA Wholesale Products Page: 6570-1 RPM: 1550 Discharge: 1 ½ Solids: ½ V-A1 W-A1 D-A1 Head, meters 8 4 Head, feet 30 20 10.3 HP 0 0 Capacity, US GPM 0 10 20 30 40 50 60 liters/second 0.0 1.0

More information

CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH

CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH Rev. 1.3 HVAC Guide Specifications Chilled and Hot Water Universal Mount Fan Coil 2-Pipe Nominal Size: 60,000

More information

SECTION OVERHEAD COILING FIRE DOORS MODEL 662 OVERHEAD COILING COUNTER FIRE DOORS WITH INTEGRAL FRAME

SECTION OVERHEAD COILING FIRE DOORS MODEL 662 OVERHEAD COILING COUNTER FIRE DOORS WITH INTEGRAL FRAME SECTION 08331 OVERHEAD COILING FIRE DOORS MODEL 662 OVERHEAD COILING COUNTER FIRE DOORS WITH INTEGRAL FRAME Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES

More information

NEBBinar: Managing Building Performance through Commissioning. March 28, 2013

NEBBinar: Managing Building Performance through Commissioning. March 28, 2013 NEBBinar: Managing Building Performance through Commissioning March 28, 2013 0 Moderator Jim Huber, NEBB Vice President and President of Complete Commissioning Jim Huber is the President of Complete Commissioning.

More information

SECTION 1000 ENGINEERING SPECIFICATION: AIR STRIPPER (REMOVABLE TRAY)

SECTION 1000 ENGINEERING SPECIFICATION: AIR STRIPPER (REMOVABLE TRAY) SECTION 1000 ENGINEERING SPECIFICATION: AIR STRIPPER (REMOVABLE TRAY) PART 1 GENERAL 1.1 SCOPE 1.1.1 The manufacturer shall furnish a low profile, multi-tray Air Stripper for removal of volatile organic

More information

ASI MODEL DM 100 SERIES DILUTING MODULES

ASI MODEL DM 100 SERIES DILUTING MODULES ASI MODEL DM 100 SERIES DILUTING MODULES The ASI Model DM 100 Series Diluting Modules have been developed to meet the requirements of some of our more specialized applications, where our standard in situ

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519 METAL CLAD CABLE - MC-PLUS Neutral

More information

SECTION MODULAR GALVANIZED RF SHIELDING SYSTEM SPECIFICATIONS

SECTION MODULAR GALVANIZED RF SHIELDING SYSTEM SPECIFICATIONS SECTION 13096 MODULAR GALVANIZED RF SHIELDING SYSTEM SPECIFICATIONS Prepared by: NELCO 125 Chenoweth Lane, Ste. 206 Louisville, KY 40207 (502) 899-3726 13096-1 MODULAR GALVANIZED RF SHIELDING SYSTEM PART

More information

SK75/100. Performance Data TOTAL HEAD IN FEET HEAD-METERS 6 SK100 SK Liters/Second Capacity-U.S. G.P.M.

SK75/100. Performance Data TOTAL HEAD IN FEET HEAD-METERS 6 SK100 SK Liters/Second Capacity-U.S. G.P.M. Performance SK75/100 RPM: 1750 Discharge: 2" Solids: 2" Wholesale Products Page: 6300-1 Section: Performance 12 40 9 30 HEAD-METERS 6 3 TOTAL HEAD IN FEET 20 10 SK75 SK100 0 0 Capacity-U.S. G.P.M. 20 40

More information

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466 BUSWAY LOW VOLTAGE (POW-R-WAY III) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 12 2113 - LOUVER BLINDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION AIR FILTERS

SECTION AIR FILTERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

AS950 ALL-WEATHER REFRIGERATED SAMPLER

AS950 ALL-WEATHER REFRIGERATED SAMPLER AS950 ALL-WEATHER REFRIGERATED SAMPLER Applications Wastewater Collection systems Industrial pretreatment Environmental monitoring Stormwater Sampling has never been this easy. Hach's AS950 sampler controller

More information

ACBC Floor Mounted Active Beam

ACBC Floor Mounted Active Beam Floor Mounted Active Beam The Price Floor Mounted Active Beam,, is designed for occupant comfort. It provides high cooling and heating capacities while simultaneously supplying ventilation air from a DOAS

More information

A. This Section includes ceilings consisting of acoustical panels and exposed suspension systems.

A. This Section includes ceilings consisting of acoustical panels and exposed suspension systems. SECTION 09 51 13 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

University of Delaware

University of Delaware University Contact: Energy & Engineering Group (302) 831-1744 SECTION 22 40 00_PLUMBING FIXTURES PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Water closets. 2. Urinals. 3. Lavatories. 4. Sinks. 5.

More information

SECTION VALVES, HANGERS, AND SPECIALTIES

SECTION VALVES, HANGERS, AND SPECIALTIES SECTION 15515 VALVES, HANGERS, AND SPECIALTIES PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15090 - Supports, Anchors, and Seals. 2. 15410 - Piping (Plumbing). 3. 15510 - Piping (HVAC). 4. 15540

More information

A. This Section includes the following types of dry-type transformers rated 600 V and less, with capacities up to 1000 kva:

A. This Section includes the following types of dry-type transformers rated 600 V and less, with capacities up to 1000 kva: SECTION 16461 - LOW-VOLTAGE TRANSFORMERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

MASTER. Water Conditioning Corp. OPERATION MANUAL. PURO PRO 1200 SC Series Modular Reverse Osmosis System. January 2012 Version

MASTER. Water Conditioning Corp. OPERATION MANUAL. PURO PRO 1200 SC Series Modular Reverse Osmosis System.  January 2012 Version MASTER Water Conditioning Corp. www.masterwater.com OPERATION MANUAL PURO PRO 1200 SC Series Modular Reverse Osmosis System January 2012 Version Table of Contents Model Number... 1 Shipping Description

More information

SECTION VIBRATION AND SEISMIC CONTROL FOR PLUMBING

SECTION VIBRATION AND SEISMIC CONTROL FOR PLUMBING SECTION 22 05 48 VIBRATION AND SEISMIC CONTROL FOR PLUMBING PART 1 - GENERAL 1.1 SUMMARY A. Section includes inertia bases, vibration isolation, acoustic housings, and for plumbing equipment. 1.2 PERFORMANCE

More information

SECTION SWIMMING POOLS STAINLESS, FULL TILE, OR TILE TRIM

SECTION SWIMMING POOLS STAINLESS, FULL TILE, OR TILE TRIM SECTION 13 1100 SWIMMING POOLS STAINLESS, FULL TILE, OR TILE TRIM This section includes editing notes to assist the user in editing the section to suit project requirements. These notes are included as

More information

MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 9,000 BTUH. Rev. 1.3

MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 9,000 BTUH. Rev. 1.3 MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil Heat / Cool Fan Coil 9,000 BTUH Rev. 1.3 HVAC Guide Specifications Chilled and Hot Water Hi-Wall Fan Coil 2-Pipe Nominal Size: 9,000 BTUH Multiaqua Model

More information

A. This Section includes exterior piping for vertical, direct-buried, ground-loop, heat-pump systems that operate between 23 and 104 deg F.

A. This Section includes exterior piping for vertical, direct-buried, ground-loop, heat-pump systems that operate between 23 and 104 deg F. SECTION 23 21 16 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS SECTION 08 32 20 CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS Page 1 of 6 USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,

More information

DARTMOUTH COLLEGE DESIGN September 15, 2004 &CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN September 15, 2004 &CONSTRUCTION GUIDELINES PART 1 DESIGN DIRECTIVE 1.1 RELATED DOCUMENTS SECTION 15240 SEISMIC RESTRAINT AND VIBRATION CONTROL A. This section shall be considered as a part of each DC Standards, Part 15. 1.2 QUALITY ASSURANCE A.

More information

2012 Fiscal Impact International Mechanical Code

2012 Fiscal Impact International Mechanical Code 2012 Section No. 306.5 Item 2 2012 Code Information - bold text = new text found in 2012 strike out = text deleted and not found in the 2012 Equipment and appliances on roofs or elevated structures: Item

More information

A. This Section includes acoustical panel ceilings installed with exposed suspension systems.

A. This Section includes acoustical panel ceilings installed with exposed suspension systems. SECTION 09511 ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

1. Vertical reciprocating conveyor, Hydraulic straddle VRC.

1. Vertical reciprocating conveyor, Hydraulic straddle VRC. PART 1: GENERAL 1.01 Section Includes: 1. Vertical reciprocating conveyor, Hydraulic straddle VRC. a. Machine, controller, platform, structural steel hoist frame. b. Wire mesh enclosure and gates. Related

More information

Shur-Shot X-Proof Hydrogen Fluoride Alarm Operations Manual

Shur-Shot X-Proof Hydrogen Fluoride Alarm Operations Manual Shur-Shot X-Proof Hydrogen Fluoride Alarm Operations Manual P/N 1000006053 Rev E $7%$QDO\WLFV// //& 733 Dairy Rd. Parkton, Md. 21120 www.atbanalytics.com (410) 733-6365 Table of Contents Chapter 1: Getting

More information

MSC Guidelines for Review of Ventilation System Plans

MSC Guidelines for Review of Ventilation System Plans K. B. FERRIE, CDR, Chief, Hull Division Purpose: This Plan Review Guideline (PRG) explains the requirements for seeking plan approval of ventilation systems from the Marine Safety Center (MSC) for most

More information

DESIGN BASIS FOR AIR CONDITIONING AND VENTILATION SYSTEM FOR SUBSTATION AND CONTROL BUILDING HINDUSTAN PETROLEUM CORPORATION LTD.

DESIGN BASIS FOR AIR CONDITIONING AND VENTILATION SYSTEM FOR SUBSTATION AND CONTROL BUILDING HINDUSTAN PETROLEUM CORPORATION LTD. CONDITIONING AND VENTILATION FOR SUBSTATION AND CONTROL BUILDING HINDUSTAN PETROLEUM CORPORATION LTD. VISAKH REFINERY DHT PROJECT TEIL JOB NO.: 6261 DOCUMENT NO.: 6261-HVAC-PKG-300 TEIL SPECIFICATION NO.:---

More information

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

B. Provide liquid-filled secondary substation transformers as indicated on drawings. SECTION 26 12 13 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 26 05 00. B. Provide liquid-filled secondary substation transformers as indicated on drawings. 1.02 RELATED

More information

SUGGESTED SPECIFICATIONS

SUGGESTED SPECIFICATIONS SOLIDS-HANDLING SUBMERSIBLE DRY-PIT PUMPS PART 1 GENERAL 1.1 DESCRIPTION Work Included: Under this section, the contractor shall provide all labor, equipment and material necessary to furnish, install,

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 71 19 (January 2008) Change 1-08/15 ---------------------------- Preparing Activity: USACE Superseding UFGS-23 71 19 (July 2007) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Using the PPM2 Portable Trace Moisture Transmitter

Using the PPM2 Portable Trace Moisture Transmitter APPLICATION NOTE 2016_0106 PPM2 Using the PPM2 Portable Transmitter The Model PPM2 Portable analyzer is a compact, cost effective, analyzer specifically designed to continuously measure low levels of moisture

More information

SYSTEM 1E LIQUID CHEMICAL STERILANT PROCESSING SYSTEM

SYSTEM 1E LIQUID CHEMICAL STERILANT PROCESSING SYSTEM SYSTEM 1E LIQUID CHEMICAL STERILANT PROCESSING SYSTEM APPLICATION For rapid, safe, standardized low-temperature liquid chemical sterilization of heat-sensitive critical and semi-critical devices. DESCRIPTION

More information

SECTION FACILITY POTABLE WATER DISTIBUTION

SECTION FACILITY POTABLE WATER DISTIBUTION PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 22 11 00 FACILITY POTABLE WATER DISTIBUTION A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 23 74 13 PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

TM Series Cooling Tower Specification

TM Series Cooling Tower Specification 1.0 Cooling Tower TM Series Cooling Tower Specification 1.1 General: Furnish and install factory-assembled, induced draft, counterflow cooling tower(s) with vertical air discharge conforming in all aspects

More information

Design and Construction Standards SECTION POTABLE WATER SYSTEMS

Design and Construction Standards SECTION POTABLE WATER SYSTEMS SECTION 15410 POTABLE WATER SYSTEMS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections,

More information

Water Quality Specification for Power Supplies

Water Quality Specification for Power Supplies Technical Note #6 Water Quality Specification for Power Supplies Introduction The cooling water for Alpha Scientific Power Supplies must meet certain minimum specifications in regard to quality and flow

More information

Banyan Air Service November 18, 2011 AVE Aviation and Commerce Center Building 1 Miami, FL

Banyan Air Service November 18, 2011 AVE Aviation and Commerce Center Building 1 Miami, FL SECTION 01815 - HVAC COMMISSIONING REQUIREMENTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

Lubricated Rotary Screw Air Compressors. Constant Speed Drives and Variable Speed Drives kw hp

Lubricated Rotary Screw Air Compressors. Constant Speed Drives and Variable Speed Drives kw hp Lubricated Rotary Screw Air Compressors Constant Speed Drives and Variable Speed Drives 18 30 kw 25 40 hp About Sullair For more than 50 years, Sullair has been on the leading edge of compressed air solutions.

More information

Stainless Steel Aeration Equipment Specification

Stainless Steel Aeration Equipment Specification Section 15 Stainless Steel Aeration Equipment Specification Part 1 - General 1.01 Description A. Scope of Work 1. Furnish, install and test aeration system including air mains, drop pipes, valves, expansion

More information

SECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM

SECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM Page 1 of 6 SECTION 08 32 20 LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS SLIDING DOORS. SECTION INCLUDES OVERHEAD SLIDING TUBE ASSEMBLY, MOUNTING

More information

Noise Control. Commercial, Industrial, and Environmental Products and Solutions.

Noise Control. Commercial, Industrial, and Environmental Products and Solutions. Noise Control Commercial, Industrial, and Environmental Products and Solutions www.kineticsnoise.com Commercial Duct Silencers Kinetics Noise Control offers the design and engineering assistance to integrate

More information

ANSI/ ASME HST Performance Standard For Overhead Electric Wire Rope Hoists

ANSI/ ASME HST Performance Standard For Overhead Electric Wire Rope Hoists SECTION 412213- BRIDGE CRANES Part 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

MERIGAUGE MODEL 3900 OPERATING INSTRUCTIONS

MERIGAUGE MODEL 3900 OPERATING INSTRUCTIONS 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com MERIGAUGE MODEL 3900 OPERATING INSTRUCTIONS Meriam Instrument s MERIGAUGE Model

More information

FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR

FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR Section 083713- Four Fold Doors- With Single Overhead Mounted Operator Part 1-General 1.1 Related Document: A. Drawing and general provisions of contract,

More information

Florida Department of Agriculture and Consumer Services

Florida Department of Agriculture and Consumer Services Florida Department of Agriculture and Consumer Services FOOD SAFETY BSL-3 HVAC IMPROVEMENTS Doyle Conner Laboratory Complex Tallahassee, Florida Project Technical Specifications Construction Documents

More information

HYDROMATIC SKV50 SEWAGE EJECTOR PERFORMANCE DATA SKV50. Wholesale Products Page: RPM: 1650 Discharge: 2 Solids: 2.

HYDROMATIC SKV50 SEWAGE EJECTOR PERFORMANCE DATA SKV50. Wholesale Products Page: RPM: 1650 Discharge: 2 Solids: 2. PERFORMANCE DATA Wholesale Products Page: 6280-1 RPM: 1650 Discharge: 2 Solids: 2 12 40 9 30 HEAD-METERS 6 HEAD-FEET 20 3 10 0 0 Capacity - U.S. G.P.M. 0 30 60 90 120 150 180 Liters/Second 0 2 4 6 8 10

More information

Unit Substation Transformer Construction Checklist (under 500 kva)

Unit Substation Transformer Construction Checklist (under 500 kva) Unit Substation Transformer Checklist (under 500 kva) Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

CITY OF LOS ANGELES LARUCP PLUMBING/MECHANICAL PLAN CHECK LIST

CITY OF LOS ANGELES LARUCP PLUMBING/MECHANICAL PLAN CHECK LIST CITY OF LOS ANGELES LARUCP PLUMBING/MECHANICAL PLAN CHECK LIST Plan Check No. Plan Check Expiration Date Job Address: Square Footage Use Zone Fire Zone Occ. Group Type of Construction No. of Stories Applicant

More information

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below)

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE APPENDIX C - ALTERNATE PLUMBING SYSTEMS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency authority

More information

Section BUILDINGS, SHELTERS, ENCLOSURES

Section BUILDINGS, SHELTERS, ENCLOSURES Section 13121 BUILDINGS, SHELTERS, ENCLOSURES Part 1 GENERAL 1.1 SECTION INCLUDES 1.2 A. Pre-engineered buildings. B. Pre-engineered shelters. C. Pre-engineered enclosures. D. Electrical wiring and devices

More information