Appreciating the Nuances of Structural Defect Issues and Related Legislation
|
|
- Evelyn Wheeler
- 6 years ago
- Views:
Transcription
1 Appreciating the Nuances of Structural Defect Issues and Related Legislation PRESENTED BY John P. Gill, Esq Hughes Gill Cochrane Tinetti, PC Mike Mastropietro OCBS, Inc. Roy Helsing The Helsing Group, Inc. 1
2 Learning Objectives REVIEW the inspection, reporting, and repair obligations required by pending legislation UNDERSTAND the impact on managers and associations IDENTIFY the hidden challenges facing condominium associations LEARN strategies to help clients identify and implement their legal obligations RECOGNIZE the limits of the manager role and learn how to partner with others effectively to get the job done SB 721 Two-Year Bill Background What prompted this bill? Substance off the bill in current form Impact on managers and associations Destructive testing What does it really mean? Berkeley Balcony Collapse Library Gardens Apartments construction completed in 2006 June 16, 2015: 5th floor balcony collapsed 13 people fell 40 feet 6 died and 7 injured 2
3 Independent Investigation CSLB investigated causes of collapse:... imposed load of the (13) students was well within the design limits of the balcony structure Dry rot along the top of the joists suggests long-term moisture saturation... of OSB Oriented Strand Board in direct contact with the joists Additional locations of water damage and dry rot were found to the wall OSB sheathing and the face of the doubled deck joists along the deck edge to wall interface Independent Investigation (continued) Contributing factors to the balcony failures: Failure to use pressure-treated structural support joists Substitution of OSB sheathing for plywood Failure to provide the specified membrane protection which could have protected the OSB sheathing from moisture saturation Independent Investigation (continued) Balcony deck-to-wall sheet metal flashing was not lapped over membrane or lath paper, resulting in extensive damage and dry rot to building wall OSB sheathing 3
4 Berkeley Inspection Ordinance On July 14, 2015, 28 days after the balcony collapse, Berkeley City Council approved an emergency ordinance mandating inspections every five years of all balconies and other weather-exposed structures in all multi-unit buildings. SB 721 Follows Berkeley Ordinance Introduced in 2017 legislative session Supported by Consumer Attorneys of California (state trial lawyers organization) Create Civil Code 4776 to apply to condominium CIDs Bill specifically excludes planned developments and an individual condominium owner s separate interest SB 721 Inspection Requirements As currently drafted, SB 721 would require: Inspection at least once every six years of the load-bearing components and associated waterproofing elements of exterior elevated elements 4
5 SB 721 Inspection Requirements (continued) As currently drafted, SB 721 would require: Inspections by a licensed architect, civil or structural engineer, or an individual certified as a building inspector or building official from a recognized state, national or international association, as determined by the local jurisdiction SB 721 Inspection Requirements (continued) Exterior elevated element means common area and exclusive use common area balconies, decks, porches, stairways, walkways, entry structures, and their supports and railings that extend beyond exterior walls of the building, have a walking surface elevated more than 6 feet above ground level, are designed for human occupancy or use, and rely in at least substantial part on wood or wood-based products for structural support or stability of the exterior elevated element SB 721 Inspection Requirements (continued) Associated waterproofing elements include flashings, membranes, coatings, and sealants that protect the load-bearing components of exterior elevated elements from exposure to water and the elements 5
6 SB 721 Inspection Requirements (continued) Load-bearing components are components that extend beyond the exterior walls of the building to deliver structural loads from the exterior elevated element to the building SB 721 Inspection Requirements (continued) Must determine that exterior elevated elements and their associated waterproofing elements are in a generally safe condition, adequate working order, and free from any hazardous condition caused by fungus, deterioration, decay, or improper alteration to the extent that the life, limb, health, property, safety, or welfare of the public or the occupants is not endangered Minimum Inspection Requirements Identify each exterior elevated element that, if found to be defective, decayed, or deteriorated to the extent that it does not meet its load requirements, would... constitute a threat to the health or safety of the occupants 6
7 Minimum Inspection Requirements (continued) Assess the load-bearing components and associated waterproofing elements of the exterior elevated elements using methods allowing for the evaluation of their performance by direct visual examination or comparable means of evaluating their performance (destructive testing) A sample of at least 15 percent of each type of exterior elevated element shall be inspected Minimum Inspection Requirements (continued) Inspector s assessment must address: Current condition of the exterior elevated elements Expectations of future performance and projected service life (for purposes of reserve study funding) Recommendations for further inspection Recommendations for repair or replacement Additional Reporting Requirements Association s initial inspection must be completed by January 1, 2024, and every six years thereafter Following initial report, inspector must submit a final report indicating that any required repairs have been completed 7
8 Repair Obligations An exterior elevated element found to be in need of repair or replacement by the inspector shall be corrected by the association Association shall have access easement through separate interests as necessary to accomplish inspections and any necessary repairs Repair Obligations (continued) Repair and replacement work by qualified and licensed contractor must comply with: Inspector s recommendations, or alternative recommendations by another licensed professional Applicable manufacturer s specifications The California Building Standards Code, consistent with Health & Safety Code 17922(d) Repair Timeline Immediate threat requires immediate corrective action If no immediate safety threat, association must apply for a permit within 120 days of receipt of the inspection report After permit approval, association has 180 days to make repairs 8
9 Effect on Levy of Association Assessments All costs associated with inspections and repairs (including non-threatening conditions) are considered an emergency situation per Civil Code 5610(b) Section 5610(b) permits an emergency assessment without a member vote Association/Management Responsibility Board of Directors shall cause inspections and testing to be completed Association is responsible for compliance Nothing required herein shall be the responsibility of the association s managing agent or its employees Manager Considerations Educating board members Scope of site visits Do NOT assume the role of expert Develop system for receiving member reports and relaying concerns to board Authority to contact construction professionals Avoid assurances of safety 9
10 Effect on Budgets Assemble inspection and testing team early Inspector General contractor Structural engineer Logistics of inspections and testing Member communication Access to unit interiors Project manager retention Developer Considerations Implications of SB 800 Builders may begin to re-map condominiums to include balconies within units 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 Risks and Challenges What does determine mean? Is testing of 15% of exterior elevated elements enough to determine the condition of all such elements? What does 15% mean? Risks and Challenges Budget considerations Board and member education considerations Risks of noncompliance Manager liability avoidance 18
19 Questions? Thank you! 19
CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE 01. GENERAL ADMINISTRATION 6% Project Administration 1%
CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE EXAM ID: I1 80 multiple-choice questions 3-1/2-hour time limit Open book 01. GENERAL ADMINISTRATION 6% 0101. Project Administration 1% Verify that
More informationAMERICAN SOCIETY OF HOME INSPECTORS AUXILIARY STANDARD OF PROFESSIONAL PRACTICE FOR RESIDENTIAL DECK INSPECTIONS DRAFT
AMERICAN SOCIETY OF HOME INSPECTORS AUXILIARY STANDARD OF PROFESSIONAL PRACTICE FOR RESIDENTIAL DECK INSPECTIONS 1. PURPOSE OF THIS STANDARD 1.1 The purpose of this Auxiliary Standard of Professional Practice
More informationDefining Failures in Residential Construction
PHRC Webinar Series Tuesday, January 12, 2016 @ 1pm Defining Failures in Residential Construction Brian Wolfgang Housing Systems Specialist Pennsylvania Housing Research Center 219 Sackett Building University
More informationCity of Hughson Building Safety Division 7018 Pine Street Hughson, CA (209)
City of Hughson Building Safety Division 7018 Pine Street Hughson, CA 95326 (209) 883-4054 RESIDENTIAL ATTACHED PATIO COVERS Patio covers are one story roofed structures not more than 12 feet above grade,
More informationExterior Stucco and Siding Installation
Exterior Stucco and Siding Installation CITY OF NEWARK, CALIFORNIA BUILDING INSPECTION DIVISION 37101 Newark Boulevard, Newark, CA 94560-3796 510-578-4261 Fax 510-578-4307 e-mail: building.inspection@newark.org
More informationSCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC Permit Requirements
SCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC. 320-226.5189 www.101developmentresources.com While every attempt has been made to insure the correctness of this handout, no guarantees are made to its accuracy
More information1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards
SECTION 07185 TRAFFIC MEMBRANE PART 1 GENERAL 1.1 SECTION INCLUDES A. Traffic membrane, consisting of welded seam PVC waterproofing, over f following surfaces: 1. Decks, balconies, and sun porches 2. Walkways,
More informationTOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ FAX
TOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ 08014 856-467-3626--- FAX 856-467-9260 Application for Certificate of Occupancy for Change of Occupancy Pursuant to Chapter 119 of the Township
More informationWILDLAND URBAN INTERFACE (WUI) PRODUCTS
CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL WILDLAND URBAN INTERFACE (WUI) PRODUCTS Published by CAL-FIRE WILDLAND FIRE PREVENTION ENGINEERING Revised 12/17/07
More informationSECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS
SECTION 075423 - THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Division 00 Bidding Requirements and other Division
More informationCOMMERCIAL WINDSTORM MITIGATION INSPECTION REPORT
Insurance Appraisals - Reserve Studies - Windstorm Mitigation Reports COMMERCIAL WINDSTORM MITIGATION INSPECTION REPORT Prepared for Harbour Hill Condominium Apartment Association, Inc. This report contains
More informationCITY OF CHICAGO DEPARTMENT OF BUILDINGS
CITY OF CHICAGO DEPARTMENT OF BUILDINGS GUIDELINES FOR THE PREPARATION OF REQUESTS FOR QUALIFICATIONS FOR THE SELECTION OF CONSULTING FIRMS TO PERFORM LIFE SAFETY EVALUATIONS The Chicago Department of
More informationCode Compliance Research Report CCRR-0194
Code Compliance Research Report CCRR-0194 Issued: 09-16-2013 Renewal Due: 09-16-2018 Revised: 10-12-2017 DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES Section: 06 05 23 Wood, Plastic, and Composite
More informationSupplemental Plan Check List for Unreinforced Masonry (URM) Retrofit
Supplemental Plan Check List for Unreinforced Masonry (URM) Retrofit Plan Check/PCIS App #: Job Address: P.C. Engineer: Phone: (E -mail: first name.last name@ lacity.org) For instructions and other information,
More informationSTRUCTURAL CONDITION ASSESSMENT
STRUCTURAL CONDITION ASSESSMENT ALLEN JAY ROCK GYM 1201 FAIRFIELD ROAD HIGH POINT, NC Prepared for: Prepared by: Guilford County Schools 617 West Market Street Greensboro, NC Adrian S. Durham, PE, SE,
More informationInterNACHI. Advanced Inspection of Crawlspaces for home inspectors
CRAWLSPACE INACCESSIBLE Crawlspace conditions which in the Inspector s opinion posed a personal safety hazard limited examination of the crawlspace to only those home systems and their components visible
More informationCode Compliance Research Report CCRR-0185
Code Compliance Research Report CCRR-0185 Issue Date: 12-09-2016 Renewal Date: 12-10-2017 Revision Date: 04-20-2017 DIVISION: 06 00 00 WOOD, PLASTICS, AND COMPOSITES Section: 06 50 00 Structural Plastics
More informationAn Applicants Guide to Residential Building Permits City of Galt Building Department
An Applicants Guide to Residential Building Permits City of Galt Building Department Service Assistance Telephone Numbers City of Galt Administration... 209-366-7100 Building Department... 209-366-7200
More informationSECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.
SECTION 06 12 00 STRUCTURAL INSULATED PANELS ------------------------------------------------------------------------------------------------------------ PART 1- GENERAL ----------------------------- 1.1
More informationCLAY TOWNSHIP BUILDING DEPARTMENT
CLAY TOWNSHIP BUILDING DEPARTMENT 4710 PTE. TREMBLE RD. P. O. BOX 429 ALGONAC, MI 48001 (810) 794-9320 FAX: (810) 794-1964 APPLICATON FOR BUILDING PERMIT AND PLAN EXAMINATION THE DEPARTMENT WILL NOT DISCRIMINATE
More informationINSPECTION TYPE EIFS system, Visual, Tramex & Delmhorst probe moisture readings
FINEGAN INSPECTION SERVICES, INC. 27 Laurelwood Drive Milford Ohio, 45150 513 683-0733 RESIDENCE LOCATION INSPECTION TYPE EIFS system, Visual, Tramex & Delmhorst probe moisture readings OVERVIEW The report
More informationA.ENVELOPE AIR SEALING
(Page 1 of 4) Note: The Energy Efficiency Standards Section 110.7 requires that all joints, penetrations and other openings in the building envelope that are potential sources of air leakage shall be caulked,
More informationNatureWood Construction Product Specification Guide
NatureWood Construction Product Specification Guide PRESERVATIVE TREATMENT Koppers Inc. Koppers Performance Chemicals PO Drawer O 1016 Everee Inn Road Griffin, GA 30224-0249 Phone: (800) 241-0240 Phone:
More informationFOR THE SELF-CERTIFICATION PERMIT PROGRAM ISSUED BY THE DEPARTMENT OF BUILDINGS
FOR THE SELF-CERTIFICATION PERMIT PROGRAM ISSUED BY THE DEPARTMENT OF BUILDINGS CONTENTS Overview... 2 Part I: General Provisions... 2 A. Definitions... 2 B. Scope and Effect... 4 Part II: General Self-Certification
More informationSTRUCTURAL ASSESSMENT OBSERVATION REPORT
Consulting Engineers THORSON BAKER & Associates, Inc. 3030 West Streetsboro Road (330) 659-6688 phone Richfield, Ohio 44286 (330) 659-6675 fax www.thorsonbaker.com STRUCTURAL ASSESSMENT OBSERVATION REPORT
More informationPlan Check No. Checked by: An Appointment Is Required for Verification
SUPPLEMENTAL CORRECTION SHEET UNREINFORCED MASONRY (URM) RETROFIT ( 2002 LABC ) Plan Check No. Checked by: Permit Appl. # An Appointment Is Required for Verification Job Address: For appt. call: APPLICATION
More informationHIDDEN HOLES IN WOOD FRAMED BALCONY WATERPROOFING
HIDDEN HOLES IN WOOD FRAMED BALCONY WATERPROOFING ROCCO ROMERO, RA WISS, JANNEY, ELSTNER ASSOCIATES, INC. 960 South Harney St., Seattle, Washington 98108 Phone: 206-622-1441 Fax: 206-622-0701 E-mail: rromero@wje.com
More informationBeginning of the Course
Beginning of the Course Topics we will Cover What is Stucco? What does InterNACHI require? How to Identify Stucco Type. Primary Concerns Related to Stucco. How to Inspect during a Home Inspection. What
More informationHILLSBOROUGH TOWNSHIP CODE ENFORCEMENT
HILLSBOROUGH TOWNSHIP CODE ENFORCEMENT SAMPLE GUIDE FOR RESIDENTIAL DECKS revised 7 16 Call before you dig! 1 800 272 1000 New Jersey One Call. Utility Mark Out. THIS GENERIC GUIDE IS NOT ALL INCLUSIVE
More informationContinuing Certificate of Occupancy Pre-Inspection Checklist
Pre-Inspection Checklist INTRODUCTION: This pre-inspection checklist has been produced to assist you in preparing for a Continuing Certificate of Occupancy (CCO) inspection. The inspection criteria and
More informationATI Evaluation Service A Division of Architectural Testing Certification Services
ATI Evaluation Service A Division of Architectural Testing Certification Services Subject to Renewal: 04/08/2014 Issued: 04/08/2013 Visit www.ati-es.com for current status Revision: 11/11/2013 Page 1 of
More informationFast Track Re-Roof Permit Checklist
Fast Track Re-Roof Permit Checklist ADDRESS I will abide by attached City Re-Roofing Building Permit Required Guidelines, including applicable Siding and Roofing Match and Smoke Detector requirements.
More informationCERTIFICATE of OCCUPANCY APPLICATION RESIDENTIAL
24 hour inspection line 737.793.1656 Date CERTIFICATE of OCCUPANCY APPLICATION RESIDENTIAL 1. Building Information Property address Property ID Type of Housing (please circle): OWNER OCCUPIED RENTAL HOME
More informationATI Evaluation Service A Division of Architectural Testing Certification Services
ATI Evaluation Service A Division of Architectural Testing Certification Services Subject to Renewal: 05/16/2016 Issued: 06/29/2015 Visit www.ati-es.com for current status Page 1 of 9 CPG Building Products
More information2016 CALGREEN RESIDENTIAL CHECKLIST MANDATORY ITEMS City of San Carlos - Building Division 600 Elm Street, San Carlos, CA Phone:
2016 CALGREEN RESIDENTIAL CHECKLIST MANDATORY ITEMS City of San Carlos - Building Division 600 Elm Street, San Carlos, CA 94070 Phone: 650-802-4261 PURPOSE: The residential provisions of the 2016 CalGreen
More informationJob Site Address. Lot/Parcel# Permit To: New Addition Alter/Remodel Code Compliance
Davison Township Building Permit Application Commercial/Residential Building Department: 1280 N Irish Rd Davison 48423 Ph: 810-653-4156 Fax: 810-658-3435 Scheduling: 810-653-4156 Job Site Address Lot/Parcel#_
More informationCode Compliance Research Report CCRR-0137
Code Compliance Research Report CCRR-0137 Issue Date: 06-14-2017 Renewal Date: 05-20-2018 DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSTES Section: 06 50 00 Structural Plastics Section: 06 53 00 Plastic
More informationBULLETIN FROM THE FIRST COAST CHAPTER ICC~BOAF
FIRST COAST CHAPTER INTERNATIONAL CODE COUNCIL (ICC) AND BUILDING OFFICIALS ASSOCIATION OF FLORIDA, INC. (BOAF) SERVING BAKER, BRADFORD, CLAY, DUVAL, NASSAU, PUTNAM, ST. JOHNS & UNION COUNTIES BULLETIN
More informationA. Submit product data sheets and literature verifying physical properties of materials.
I. GENERAL ACRYSHIELD ROOF MANAGEMENT SYSTEM Installation Guide Specification For Preserving EPDM Roofs 07500 Saving Money, Safeguarding the Environment One Roof at a Time. 1.01 SUMMARY A. Provide labor,
More informationATI Evaluation Service A Division of Architectural Testing Certification Services
ATI Evaluation Service A Division of Architectural Testing Certification Services PCA-125 Subject to Renewal: 05/16/2018 Issued: 05/24/2017 Visit www.ati-es.com for current status Page 1 of 9 CPG Building
More informationIn Depth Home Inspection LLC Report # Doe STRUCTURAL PESTS & DRY ROT INSPECTION REPORT
ADDRESS OF 123 Main Ave NE DATE OF INSPECTION PROPERTY Salem OR 97301 Feb 1, 2010 INSPECTED Inspection ordered by John and Jane Doe Report sent to John and Jane Doe Owner's Name & Address John and Jane
More informationReliant Holdings Ltd Safety Management System
Preparation: Safety Mgr Authority: President Issuing Dept: Safety Page: Page 1 of 7 Purpose The purpose of this program is to prevent injuries due to falls from elevated work areas and ensure employees
More informationA. Meet at Project site <insert number> days before starting installation.
SECTION 074643 - COMPOSITION SIDING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Engineered wood cladding. 2. Soffit panels. 3. Trim and fascia. 4. Sealant. 5. Weather barrier. 6. Flashing. 1.2
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 01 4000 - QUALITY REQUIREMENTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More informationBig Ox Energy Siouxland, LLC. Safety Management System. Authority: President
Issuing Dept: Safety Page: Page 1 of 5 Purpose The purpose of this program is to provide guidelines to Big Ox Energy - Siouxland LLC employees in the safe use of scaffolding, and to reduce the risk of
More informationTHE CONSTRUCTION SUPERVISOR
City of Aurora Building Inspections 15151 E Alameda Pkwy Aurora, CO 80012 (303) 739-7420 THE CONSTRUCTION SUPERVISOR When a building permit has been issued for any construction within the City, the Supervisor
More informationFORENSIC TILE CONSULTANTS
Page 1 FORENSIC TILE CONSULTANTS GREGORY I. MOWAT FCSI CDT CTC CFC 9541 Vervain Street San Diego, CA 92129-3523 Telephone (858) 484-8118 Fax (858) 484-8302 www.forensictileconsultants.com E- mail tile4n6@aol.com
More informationAsbestos Consulting Radon Measurements Lead Assessments Indoor Air Quality Testing Mold Investigations. Project Number: Page 1 of 22
Page 1 of 22 Asbestos Survey Project Summary Pursuant to your request; Environmental, Inc., has performed an Asbestos Building Survey on 8/13/2014 and limited to the above referenced location. The Interior/Exterior/Roof
More informationDricon FRT Wood Specification
PART 1 GENERAL Dricon FRT Wood Specification 1.01 SUMMARY A. Section includes: Fire retardant treatment for wood, including framing, decking, sheathing and other wood construction, not exposed to weather.
More informationQuality Inspection 8618 London Heights San Antonio, TX Phone: (210)
Quality Inspection 8618 London Heights San Antonio, TX 78254 Phone: (210) 240-0476 PRE DRYWALL INSPECTION REPORT Prepared For: DELETED (Name of Client) Concerning: DELETED, San Antonio, TX 78258 (Address
More informationTile on Existing. Viewpoint
Viewpoint Tile on Existing Exterior Reinforced Concrete BalconieS By Steven C. Turner Exterior reinforced concrete balconies are often covered by tile set in mortar beds with grouted joints. These installations
More informationPENNSAFE BUILDING INSPECTION SERVICES LLC Deck and Roof Cross Section Submittal
PENNSAFE BUILDING INSPECTION SERVICES LLC Deck and Roof Cross Section Submittal Roof Size: Width: Length: Roof Type: Gable: Hip: Shed: Roof Pitch: (check one) Trusses: Rafters: Spacing of Trusses or Rafters:
More informationTriton DCI Decoupling Mat
1 Triton DCI Decoupling Mat Advanced Decoupling Mat with Superior Performance Lightweight waterproof underlayment Mortar Lock Mesh system for one pass mortar application, provides enhanced adhesion between
More informationCS-100 Guide Specifications
MANUFACTURER CUSTOM-BILT METALS 1333 Corporate Drive, Suite 103 Irving, Texas 75038-2520 (800) 826-7813 or info@custombiltmetals.com www.custombiltmetals.com CS-100 Guide Specifications This Guide Specification
More informationBULLETIN 34: BUILDING ENVELOPE SERVICES APPROPRIATE PROFESSIONAL PRACTICE
200-4010 Regent Street Burnaby BC V5C 6N2 Canada Telephone: (604) 430-8035 Toll Free Canada-wide: 1-888-430-8035 Facsimile: (604) 430-8085 BULLETIN 34: BUILDING ENVELOPE SERVICES APPROPRIATE PROFESSIONAL
More informationPENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION
PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION Permit No. 175 Beaver Drive, P.O. Box 486 DuBois, PA 15801 Phone: 814-375-1111 Fax: 814-375-1117 Toll Free: 855-PENNSAF LOCATION OF PROPOSED
More informationSPECIAL INSPECTION AND OBSERVATION PROGRAM CITY OF CONCORD BUILDING DIVISION. Project Address:
SPECIAL INSPECTION AND OBSERVATION PROGRAM CITY OF CONCORD BUILDING DIVISION Permit Application #: Project Address: Purpose: To meet the requirements of CBC Section 1704.3 this form may be used as a statement
More informationTOWN OF DEWITT PLANNING AND ZONING PERMIT REQUIREMENTS FOR DECKS
TOWN OF DEWITT PLANNING AND ZONING PERMIT REQUIREMENTS FOR DECKS 1) Copy of survey within ten years showing all structures, property lines and deck location drawn to scale. SURVEYS REDUCED IN SIZE ARE
More informationSupplemental Concrete Tilt Up Retrofit Plan Check Correction Sheet (2014 LABC)
Supplemental Concrete Tilt Up Retrofit Plan Check Correction Sheet (2014 LABC) Plan Check Submittal Date: Plan Check / PCIS App #: Job Address: Applicant: P.C. Engineer: (Print first / last name) Phone:
More informationThe Inspection Process. Waxhaw N.C.
The Inspection Process In Waxhaw N.C. This information is provided by the Waxhaw Enforcement Division to assist you in the progression of your project. Nothing in this document should be considered "Code"
More informationTechnical Guideline for. Section 8. Inspection and Approval of Construction
Technical Guideline for Section 8. Inspection and Approval of Construction Ontario Regulation 22/04 Electrical Distribution Safety January 12, 2005 Technical Guideline Section 8 General Legal Disclaimer
More informationChapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION
Chapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION Sections: 4-16-01 PURPOSE 4-16-02 APPLICABLE AREA 4-16-03 CONSTRUCTION AND OCCUPANCY 4-16-04 UPPER BUILDING AREA, HEIGHT, NUMBER OF STORIES
More informationRESPONSIBILITIES IN THE DESIGN PROCESS INVOLVING METAL PLATE CONNECTED WOOD TRUSSES
CHAPTER 2 RESPONSIBILITIES IN THE DESIGN PROCESS INVOLVING METAL PLATE CONNECTED WOOD TRUSSES 2.1 PURPOSE The purpose of this chapter is as follows: 2.1.1 To define and draw attention to the typical duties
More informationPete Fowler CONSTRUCTION Services, Inc. SB 800: California s Builders Right to Repair Bill. Outline - Level 2. Introduction.
Pete Fowler CONSTRUCTION Services, Inc. Introduction SB 800: California s Builders Right to Repair Bill Outline - Level 2 Anyone involved with construction, selling, financing, inspecting, or litigating
More informationLouis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1
Louis Armstrong New Orleans International Airport NOAB Project # 8910-01233 PART 1 - GENERAL SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS 1.1 RELATED DOCUMENTS A. Drawings and general provisions
More informationPole Barns. Why Do I need a Permit? D ID Y OU K N OW? What you need to apply for a building permit: Tips on hiring contractors.
Building Guides for Homeowners Pole Barns What you need to apply for a building permit: Site Plan / Footing Detail Page 2 Floor Plan / Truss Details Page 3 Construction Details Pgs 4-5 Permit Application
More informationGHD Materials Technology
GHD Materials Technology Materials Technology Material Technology defined Asset owners and managers need durable structures to meet client expectations and manage the potentially significant economic and
More informationSECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof
SECTION 07550 MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof This section is based on the products of MFM Building Products Corp., which is located at: 525 Orange St. P. O. Box 340 Coshocton, OH 43812
More informationTOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit:
TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION 355-7575 Ext. 395 Needed to Obtain Permit: 1. Building Permit Application, and/or residential plumbing permit application, as applicable, to be
More informationFACT SHEET #2 DECK INFORMATION
Borough of Doylestown Building and Zoning Department 57 West Court Street, Doylestown, PA 18901 215.345.4140 FACT SHEET #2 DECK INFORMATION BACKGROUND The provisions of the PAUCC. ICC Property Maintenance
More informationChapter UNIFORM CODES FOR CONSTRUCTION BUILDING CODE
Chapter 23.12 UNIFORM CODES FOR CONSTRUCTION BUILDING CODE 23.12.010 Adoption of the 2010 California Building Code. Part 2. Title 24 of the California Code of Regulations. There is adopted and incorporated
More informationOne and Two Family Additions
One and Two Family Additions An addition to a house, duplex, garage, or an accessory structure requires a building permit prior to performing any construction. Building Department & Permit Office Mon-Fri
More informationNarrow Modular Pavers (NMP) for Sand-Set Installations
The following specification refers to the Stepstone, Inc. product known as: Narrow Modular Pavers (NMP) for Sand-Set Installations Narrow Modular Pavers are part of the California Architectural Paver line
More informationRIVERS EDGE CONDOMINIUM ASSOCIATION MAINTENANCE RESPONSIBILITIES
RIVERS EDGE CONDOMINIUM ASSOCIATION MAINTENANCE RESPONSIBILITIES This Policy Document outlines the separation of responsibilities between the Rivers Edge Condominium Association (RECA) and the Unit Owners
More informationCITY OF CARLISLE APPLICATION FOR BUILDING PERMIT
CITY OF CARLISLE APPLICATION FOR BUILDING PERMIT CITY OF CARLISLE APPLICATION FOR BUILDING PERMIT Please fill out the form below Please print Name: Phone Number: Address: City: State: Address of building
More informationSupported Scaffold Inspections
Supported Scaffold Inspections May 2016 Inspect scaffolds and scaffold parts daily, before each work shift, and after any event that may have caused damage. Check to see if power lines near scaffolds are
More informationSECTION 07530CP EPDM MEMBRANE ROOFING
PART 1 GENERAL 1.1 SUMMARY SECTION 07530CP EPDM MEMBRANE ROOFING A. Section includes: 1. Adhered membrane roofing and flashing 2. Mechanically fastened roof insulation 3. Walkway pads 1.2 ARCHITECTURAL
More informationSPECIFICATION GUIDELINE
Environmental StoneWorks specification guideline should be used to assist design professionals in the preparation of projects. Edit and delete items that may not be applicable. Verify all referenced section
More informationQuestions and Answers about Madison Crescent and Noise Issues
Questions and Answers about Madison Crescent and Noise Issues Question: What codes were applicable to our condos when they were built? Answer: The Virginia Uniform Statewide Building Code (VUSBC) - The
More informationSECTION PREPARATION FOR RE-ROOFING
SECTION 07 01 50.19 PREPARATION FOR RE-ROOFING SPEC WRITER NOTES: 1. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. Edit Summary article below after establishing
More informationINSULATION RETROFIT DESIGN ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT
INSULATION RETROFIT DESIGN ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT MAY 2009 prepared by N. A. JACOBSEN, P.Eng. CIVIL ENGINEERING CONSULTANT Whitehorse, Yukon ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT MAY
More information2016 Capital Improvement Project REHABILITATION OF METAL ROOFING SECTION REHABILITATION OF METAL ROOFING PART 1 - GENERAL
13414.01 REHABILITATION OF METAL ROOFING 070151-1 SECTION 070151 REHABILITATION OF METAL ROOFING 1.1 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of the Contract, including General
More informationCity of of Dauphin WOOD DECKS. Zoning and construction requirements for non-sheltered wood decks for residential dwellings.
City of of Dauphin WOOD DECKS Zoning and construction requirements for non-sheltered wood decks for residential dwellings. General Information.3-6 Zoning..7 Foundations..8-10 Structural 11-14 Design..15-18
More informationSpecifications for Electrical Underground Distribution Systems from Overhead Transformation, Apartments & Condominiums
Specifications for Electrical Underground Distribution Systems from Overhead Transformation, Apartments & Condominiums Specification DDS-3 OH Revision 10, March 2010 ONCOR ELECTRIC DELIVERY COMPANY SPECIFICATIONS
More informationBituminous Sheet Flat Roofs: Their repair and maintenance
Bituminous Sheet Flat Roofs: Their repair and maintenance Flat roof covered in sheets of bituminous felt Introduction Whilst flat roofs are often regarded as inferior to their pitched counterparts and
More informationRAY-CORE Structural Insulated Roof and Wall Panels
SUBMITTAL 20180101 RAY-CORE Structural Insulated Roof and Wall Panels Closed Cell Polyurethane Foam Insulation Douglas Fir Studs STANDARD FEATURES Insulation, Framing and Wrap in a 4 wide panel Available
More informationAttachment of Residential Deck Ledger to Metal Plate Connected Wood Truss Floor Systems
to Metal Plate Connected Wood Truss Floor Systems Structural Building Components Association (SBCA) February 17, 2015 Revised August 15, 2017 SBCA is an APPROVED SOURCE This research report is based on
More informationSIKALASTIC-152 EXTERIOR WATERPROOFING MEMBRANE. Product. Scope. Appraisal No. 811 [2013] Appraisal No. 811 (2013) Amended 28 August 2017
SIKALASTIC-152 EXTERIOR WATERPROOFING MEMBRANE Amended 28 August 2017 BRANZ Appraisals Technical Assessments of products for building and construction. Sika (NZ) Ltd PO Box 19 192 Avondale Auckland 1746
More informationDECK INFORMATION SHEET
Community Development Department 925 Burlington Avenue Lisle, Illinois 60532 630-271-4150 DECK INFORMATION SHEET The Village of Lisle requires a permit to build, repair or replace a deck. Decks are permitted
More informationBECx Design Phase Specification Review Workshop. Design Phase. Construction Risk Management. Building Enclosure Coordination Process
BECx Design Phase Specification Review Workshop Building Enclosure Commissioning: Train the Trainer Iowa State University, Ames Iowa May 10 12, 2016 Presented by William R. Nash Design Phase Pre Design
More informationINDUSTRIALIZED HOUSING AND BUILDINGS Administrative Rules of the Texas Department of Licensing and Regulation 16 Texas Administrative Code, Chapter 70
INDUSTRIALIZED HOUSING AND BUILDINGS Administrative Rules of the Texas Department of Licensing and Regulation 16 Texas Administrative Code, Chapter 70 TABLE OF CONTENTS 70.1. Authority... 1 70.10. Definitions...
More informationCode Compliance Research Report CCRR-0101
Code Compliance Research Report CCRR-0101 Issue Date: 07-31-2017 Renewal Date: 05-19-2018 DIVISION: 06 00 00 WOOD, PLASTICS, AND COMPOSITES Section: 06 50 00 Structural Plastics Section: 06 53 00 Plastic
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 01 8113.53 - SUSTAINABLE DESIGN REQUIREMENTS - GREEN GLOBES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationThe Loss Mitigation Grant Program Grants for Home Retrofits using Wind Resistive Devices Saturday June 2, 2007
The Loss Mitigation Grant Program Grants for Home Retrofits using Wind Resistive Devices Saturday June 2, 2007 OUTLINE Introduction to the Loss Mitigation Grant Program Hurricane Probabilities in Hawaii
More informationPost Remediation Warranty
Post Remediation Warranty This warranty is provided by: Manufacturer: Anabec, Inc. 9393 Main Street PO Box 433 Clarence, NY 14031 716-759-1674 info@anabec.com & Qualified Contractor (Contractor): Presented
More informationHealthy Homes Provisions of Lansing, Michigan Ordinances Extracted from by National Center for Healthy Housing
TITLE 6. HOUSING CHAPTER 1460. HOUSING AND PREMISES CODE Selected Provisions Related to Healthy Homes 1460.02. Applicability. (h) Historic Buildings. The provisions of this Code shall not be mandatory
More informationATI Evaluation Service A Division of Architectural Testing Certification Services
ATI Evaluation Service A Division of Architectural Testing Certification Services PCA-125 Subject to Renewal: 02/21/2018 Issued: 02/28/2017 Visit www.ati-es.com for current status Page 1 of 7 Trex Company,
More informationAttachment 1 Findings and Conditions
2451 Ridge Road Use Permit #04-10000066 Attachment 1 Findings and Conditions APRIL 10, 2008 CEQA FINDINGS 1. The project is categorically exempt from the provisions of the California Environmental Quality
More informationBison Innovative Products 1975 W. 13 th Ave. Phone February 2012 P.O. Box Toll Free Denver, CO Fax
Bison Innovative Products 1975 W. 13 th Ave. Phone 303-892-0400 February 2012 P.O. Box 40246 Toll Free 800-333-4234 Denver, CO 80204 Fax 303-825-5988 www.bisonip.com info@bisonip.com SECTION 02870 SITE
More informationSpecial Inspection Program Guide. City of Novi Community Development Building Division
Special Inspection Program Guide Based on the Michigan Building Code 2015 City of Novi Community Development Building Division TABLE OF CONTENTS PAGE NO. INTRODUCTION...1 GUIDELINES FOR THE SPECIAL INSPECTION
More information