HIDDEN HOLES IN WOOD FRAMED BALCONY WATERPROOFING

Size: px
Start display at page:

Download "HIDDEN HOLES IN WOOD FRAMED BALCONY WATERPROOFING"

Transcription

1 HIDDEN HOLES IN WOOD FRAMED BALCONY WATERPROOFING ROCCO ROMERO, RA WISS, JANNEY, ELSTNER ASSOCIATES, INC. 960 South Harney St., Seattle, Washington Phone: Fax: S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y N O V E M B E R R O M E R O 3 5

2 ABSTRACT Balconies are a standard component of many multistory apartment and condominium buildings and provide a means to extend the living space to the outdoors. However, inadequately detailed deck to wall interfaces and railing post penetrations often cause water intrusion into the tenant spaces of the building and substantial distress to the balcony structure. When designing balcony waterproofing assemblies, supplemental sheet metal flashing components integrated with both the waterproofing membrane and the weatherresistive barrier of the cladding system should be considered to provide long term waterproof performance. Several case studies of balcony repair projects will be presented, assessing the as built construction, subsequent water intrusion, resulting distress, and investigation and repair methodology. SPEAKER ROCCO ROMERO, RA WISS, JANNEY, ELSTNER ASSOCIATES, INC. Rocco C. Romero is a registered architect with over 20 years of experience in the forensic investigation of hundreds of building envelope and façade systems and specializes in investigation, assessment, and repair design for roofing, waterproofing, and cladding systems in both contemporary and vintage structures. He provides consulting services to owners, architects, and general contractors related to the design and constructibility of new and retrofit building envelope systems. Romero also provides litigation and expert witness support services for existing buildings. 3 6 R O M E R O S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y N O V E M B E R

3 HIDDEN HOLES IN WOOD FRAMED BALCONY WATERPROOFING Balconies offer an important benefit of living in a multistory apartment and condominium building by extending usable living space to the outdoors. In some cases, exterior elevated walkways act as corridors to provide access for residents to their units and include stairways that are also exposed to the elements. The desirable exterior exposure of balconies and corridors also creates a challenge in controlling water leakage. Poorly detailed and constructed transitions, interfaces, and penetrations often lead to water intrusion into the occupied tenant spaces of the building and may also result in substantial distress to the building s exterior walls and structure. In wood framed balcony and exterior elevated walkway construction, detailing at transitions, interfaces, and penetrations is often the most challenging and critical aspect of waterproofing system design. In particular, inadequate attention to the design of wall flashing, guardrail wall and exterior wall integration, railing post anchorage, and deck slope for proper drainage can lead to severe deterioration of the supporting structure. Remedies to mitigate problems often require removal of both exterior and interior building components, including cladding, architectural paving, door thresholds, soffits, ceilings, and interior finishes and can be difficult and expensive but are often necessary to gain access to inspect and repair leaking assemblies. When designing wood framed balcony and exterior elevated walkway waterproofing assemblies, proper detailing of supplemental sheet metal flashing components integrated with both the waterproofing membrane and adjacent cladding systems is essential to successful long term performance of waterproofing systems. Design should include systems that shed water and, most important, can be adapted to unique conditions. implemented in a balcony or exterior elevated walkway waterproofing design. In wooddeck construction, the components usually consist of (from bottom to top) balcony post or wall supports, wood joists and framing, exterior grade plywood or oriented strand board deck substrate, and waterproofing membrane or deck coating, with a railing system/guard wall incorporated at the perimeter edge. In some cases, a wall partition bisects a deck to segregate the deck into individual semiprivate areas. On larger decks or decks with raised perimeter curbs, drains can be incorporated into the waterproofing assembly. In many cases, however, the deck slopes to drain away from the building to the outer edge of the deck. At the underside of the decks, a vented soffit typically encloses the exterior joist cavities. Figure 1 Where decks are constructed over occupied living areas, insulation is usually installed in the joist cavities. Exposed pedestrian traffic bearing membranes generally consist of a multilayered, fluid applied deck coating system or single ply waterproofing membrane system. In some cases, fluid applied multilayered elastomeric systems have fabric reinforcing that can be used to prestrip deck board joints and also to reinforce the coating transition to the horizontal leg of supplemental sheet metal flashings. Aggregate (i.e., silica) is typically broadcast in the top coat to provide a level of slip resistance to the membrane surface. Fluid applied membranes are spread directly on the deck substrate with squeegees and trowels or sprayapplied to create a monolithic, seamless application. Flexible, single ply membranes are often referred to as vinyl membranes. They are composed of polyvinyl chloride (PVC), which consists of carbon, hydrogen, and chlorine. PVC single ply membranes are defined as a thermoplastic, which essentially means that the material can change BACKGROUND The goals of any waterproofing system are to minimize water leakage, manage the flow of water, and provide some level of redundancy within the system. Numerous approaches and membrane options can be Figure 2 S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y N O V E M B E R R O M E R O 3 7

4 Figure 3 from a solid state to a semisolid state with the application of adequate heat, enabling the membrane to be overlapped and fused through heat welding to create a watertight seam. At the overlapped seam that is to be heat welded, the process locally turns the membrane from a solid state into a semisolid state, thus fusing the membrane together. Once heat is removed, the membrane rapidly cools, returning to a solid state, and is thus fused. The membrane is then typically adhered to the deck with proprietary adhesives. leakage, a single ply membrane had laps located transverse and sometimes parallel to the slope of the deck. It was readily determined that in an apparent attempt to protect the seams from foot traffic, metal cover strips (similar to termination bars) were fastened through the horizontal surface of the membrane (Figure 3) into the plywood substrate, resulting in membrane penetrations at approximately 6 in on center intervals. It was at these penetrations that leakage was occurring. Railing Base Plate Anchor Penetrations In other cases, the sources of the water leakage are not as obvious. When railings are located at the deck perimeter, the base plates for the railing systems are often attached through the membrane and horizontal deck into the framing below. Because decks are often sloped for drainage to the outside edge (opposite the main exterior building wall), the railing anchors are located in the direct path of water flow. In addition, railing base plates installed on a sloped deck are usually not fabricated to accommodate the slope of the deck; thus the base plates require shimming, resulting in an additional gap between the base plate and membrane where water can enter the anchor bolt holes. Anchors can be installed with plastic caps, sealing washers, and sealant to cover the exposed anchor head; however, due to the anchor penetrations through the deck, the interface between the railing base plate and deck waterproofing is most critical. Although a sealant fillet bead is often applied at this juncture, water that infiltrates past this single line of defense enters under the railing base plate and can leak into the deck construction at the anchor bolts. Leakage Investigation When the integrity of the waterproofing membrane system is compromised, there can be obvious signs of water intrusion and deterioration of the deck structure, such as water stains on soffits directly below the deck and soft spots on the walking area of the deck surface. However, substantial damage to the structure is sometimes hidden beneath the cladding (Figures 1 and 2). When conducting a leakage investigation, sources of water leakage in the membrane are sometimes obvious but more often, are not. As an example of a more obvious source of water Figure R O M E R O S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y N O V E M B E R

5 Figure 5 Figure 6 Guardrail Walls Where guardrail walls are present, investigating from the top to bottom is the preferred approach when trying to find the source of water leakage. Guardrail walls are often used in conjunction with perimeter railing systems to provide a level of privacy at adjoining decks. Water leakage can often be traced to the interface of these walls with the main exterior building wall. Wood caps and sheet metal copings that do not incorporate sheet metal saddles properly integrated with the weather resistive barrier of the adjacent building cladding leave a gap at the transition to the main building wall that can be a source of water intrusion. If water enters the guardrail wall assembly and infiltrates past the weather resistive barrier to the underlying sheathing layer, this infiltrating water can pass behind the base of wall membrane flashing, resulting in leakage. By starting at the top and removing the guardrail wall cap and cladding, water stain patterns or sheathing deterioration can be revealed that can help determine the source(s) of water infiltration. Base of wall flashings are often covered by the subsequent cladding of the guardrail walls. Removal of the cladding and weatherresistive barrier (building paper) can provide initial indications to the origins of the water intrusion source. For instance, water stains on sheathing that originate near the base of the wall are signs of failed flashing (Figure 4) as depicted by water wicking upward at the sheathing. Sheet metal deck to wall transition flashings are commonly used in fluidapplied elastomeric membrane applications. Where gaps or discontinuities occur in transitions between flashing components (Figures 5 and 6), water intrusion can occur. These discontinuities are often the result of lack of coordination in work performed by different trades, such as the waterproofing subcontractor installing the membrane flashing on the outside edge of the deck and the siding subcontractor installing the drip flashing at the adjacent wood fascia trim. Coordination of the installation and sequencing of work are important components of quality control and are critical to a complete and successful membrane system. At sheet metal base of wall flashings, the metal work should be installed in sequence, following the slope of the deck from the low point to high point. Laps should be installed in a shingled manner so that the flow of water sheds over the laps. The waterproofing membrane should be installed prior to the cladding so that the membrane can be continuously applied vertically onto the sheet metal base of wall flashing, providing an additional seal at the sheet metal laps. Failure to follow this sequence can result in gaps at the flashing laps (Figures 7 and 8) and subsequent water leakage. S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y N O V E M B E R R O M E R O 3 9

6 Figure 7 Figure 8 Door Thresholds Doorways that provide access to balconies and exterior elevated walkways are a unique challenge to waterproofing membrane installations. At these locations, deck surfaces should always slope away from door thresholds. Door thresholds that are at the same elevation as the deck surface are prone to water entry from wind driven rain, as the only barrier to inhibit water entry is the weather stripping at the bottom of the door. While thresholds provide a termination point that separates the waterproofing from interior floor finishes, threshold anchors that penetrate the waterproofing membrane are direct paths for leakage into the wood deck construction. In addition, adjacent base of wall flashings often terminate at the jambs of the doorway s rough framed opening, often without supplemental flashing to make the doorway threshold waterproof. Good design practice is to have the interior subfloor slightly higher than the surface of the exterior deck to create a change in elevation plane that helps obstruct the flow of wind blown water into the interior. This practice, in combination with a fully soldered and flanged sheet metal door pan that is integrated with the adjacent sheet metal base of wall flashings, helps provide a continuous substrate for waterproofing application. The elevation change of the interior floor height at thresholds should conform to applicable local codes, ordinances, and federal accessibility guidelines. Covered Membranes Concrete Wearing Course Elevated exterior walkways that provide egress to individual apartment units are often designed with a concrete wearing course (topping) placed over a membrane as a part of the fire rated construction. This sandwich, or covered type of membrane installation, in which the membrane is installed between the deck and the concrete topping, can use numerous types of proprietary membrane systems, including selfadhering preformed sheets and hot or coldfluid applied rubberized asphalt membranes with integral fabric reinforcing. While these types of membranes are not designed for exposure to ultraviolet light or foot traffic, they can provide long term service if properly designed and installed. Membrane systems that are intended solely for roofing applications should not be used for decks and walkways. Drainage composites can be used for water management and for facilitating drainage of water in covered membrane systems, as they create a space between the underside of the topping and the membrane and help expedite drainage of the membrane surface. Heavy organic growth at concrete topping construction joints is usually an indication that water is not draining freely from the underlying membrane layer. Accumulation of water at the membrane level can result in freeze thaw deterioration of the concrete topping in some northern climates. At the outside edges of the walkway, L shaped galvanized metal edge strips are sometimes used as a permanent border of the deck construction to aid in the initial placement of the concrete wearing course (Figure 9). Problems can arise, however, when these edge strips are incorporated as part of the waterproofing membrane system. In a covered membrane application, the membrane cannot be exposed at the outside edge of the deck construction where the membrane terminates. If the waterproofing membrane is sealed to the top of the horizontal leg of the edge metal, water cannot readily exit the waterproofing membrane layer and can result in corrosion of the edge metal. Although a properly installed membrane can withstand the hydrostatic pressure of the trapped water, water can infiltrate underneath the membrane if the membrane is not well bonded to the metal flashing, causing localized water leakage Figure R O M E R O S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y N O V E M B E R

7 Figure 10 and deterioration of the deck construction (Figure 10). In addition, long term membrane bond to the edge metal can be affected by the corrosion on the edge metal. Sheet metal inside and outside corner flashings are most critical in a covered waterproofing application. Unlike an exposed membrane system, where there is access to the flashing to trace leaks and perform repairs, investigating and repairing leaks in a covered system can be difficult and expensive. Partial removal of the concrete wearing course presents other issues, such as causing additional damage to the existing membrane, difficulty in installing proper tie ins for the repaired area to the existing membrane, and matching the texture and color of repairs to the existing con crete finish. Therefore, if the area to be repaired is a walkway or small to midsize balcony deck, the economical decision is usually to remove and replace the entire waterproofing membrane system and concrete topping. At corners where the application of sheet metal flashing components requires them to be cut and pieced together, laps and discontinuities must be completely sealed. Sheet metal flashing at corners are often poorly field fabricated, creating holes at the apex of the cuts (Figures 11 and 12). Discontinuities in the sheet metal flashing, coupled with unsealed laps, can result in water intrusion under the membrane, contributing to the decay and deterioration of the deck structure. Challenges of Proper Flashing Integration Successful long term performance of a membrane system is the result of proper design of the waterproofing system, including the selection of appropriate and compatible materials and flashing, the skillful implementation by the applicator to achieve a quality installation, and maintenance to the system where applicable. While the field of the membrane is generally predictable and well detailed by the membrane manufacturer, the transition of the membrane at terminations and transitions can be unique and should be tailored to each project. In order for the designer, contractor, and owner to understand and develop realistic project expectations, details should be prepared that illustrate the profiles of the specific flashing components that are anticipated. Schematic plans of balconies and walkways where specific flashings are required should be part of the contract documents, followed by shop drawing submittals prepared by the contractor for each flashing type and condition. Mock-ups Field mock ups are essential and should be a part of all membrane installations. It should be understood that field conditions will likely require that components be altered to provide a better fit and to ensure watertightness; thus, modifications to field mock ups are useful in refining details prior to overall installation. Field mock ups are an important part of the construction process and provide an opportunity to resolve unforeseen conditions prior to fabrication of flashing components for the whole project. Mock ups should be installed in the field on actual decks that will be waterproofed and the work performed by the actual trades and specific personnel who will be performing the work, as well as sequenced with the adjacent cladding construction. The reviewed and accepted mockups help establish the quality of construction required for the project and define the expectations of all parties. Deck Slope Adequate slope of walkways and decks at the membrane layer is important to the success of a waterproofing membrane system. Where decks slope in one direction to Figure 11 Figure 12 S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y N O V E M B E R R O M E R O 4 1

8 Figure 14 Figure 13 the metal work is required. Elastomeric membranes bond well to galvanized sheet metal if the surface is properly cleaned, free from oily residue, and primed as required by the mem brane manufacturer. Prefinished sheet metal should be avoided if soldering is required. Stainless steel should also be avoided, as elastomeric membranes do not bond as well to stainless steel. In single ply PVC membrane installations, PVCcoated sheet metal is the optimum choice for flashing material to be incorporated into the membrane design. When heated to a specific temperature range, the single ply PVC membrane can be heat welded and fused to the PVC coated sheet metal. PVCcoated sheet metal can be provided as a part of the membrane system by the membrane manufacturer. Since dimensions in deck construction can differ slightly from deck to deck, all conditions requiring flashing should be measured by the contractor in the field prior to fabrication. the outside edge for drainage, slope at the membrane level should range between 1/8 in to 1/4 in per ft minimum or as required by local codes. In general, the more slope the better, and the design should accommodate for frame shrinkage as well. An additional design consideration is that floor joists are often cantilevered from the floor framing within the building interior; thus, if the decks are constructed with a low slope, the slope is often substantially diminished once the gypsum flooring is placed at the building interior. The weight of the gypsum flooring can cause the interior floor joists to deflect, causing the outer ends of the joists at the balconies to slightly rise upward. Therefore, adding additional deck slope during the original design and construction process should be considered to help accommodate for this condition. Metal Flashing Selection and Fabrication In wood framed construction, sheet metal flashings should be considered at all transitions to provide a continuous substrate for membrane application and adhesion. The metal flashing material will vary, depending on the type of membrane that is to be applied. Galvanized flashing is a serviceable choice for fluid applied elastomeric membrane applications where soldering of Door Pans Where doors access the decks, the doorway thresholds should be above the deck surface as much as allowed by governing codes. Waterproofing membrane installations should incorporate sheet metal door Figure 15 pans that are integrated with the waterproofing membrane and adjacent sheet metal flashing components (Figures 13 and 14). Where the door sets in the horizontal portion of the door pan, the pan should not be penetrated by threshold fasteners, as this defeats the purpose of installing a supplemental, watertight flashing component. Side laps in adjacent sheet metal flashing components must be adequately sealed with several beads of sealant that are transverse to the laps to make the flashing watertight prior to application of the waterproofing membrane. Sealant used in metal work that may be in contact with the waterproofing membrane must be compatible with the membrane. Flashing Coordination Outside edge flashings should not inhibit the flow of water draining from the deck. If the deck is sloped for drainage to the outside edge of the deck, the exterior 4 2 R O M E R O S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y N O V E M B E R

9 Figure 16 edge of the wood deck should be sufficiently planed so that the installed metal drip flashing is slightly recessed and the membrane application does not build up at the transition to the deck edge metal and inhibit drainage (Figure 15). If this condition is not sufficiently addressed, water may collect on the membrane at the deck edge. Sheet metal flashings should always be installed in shingle fashion, in a manner that sheds the flow of water so that it is not directed into laps. Base of wall flashing should be installed to a height of 6 in minimum, with laps sealed with several beads of sealant applied transverse to the lap. The flashing should be installed well in advance of the installation of the weather resistive barrier on the building walls (Figure 16). This sequencing allows the waterproofing membrane to be applied onto the vertical portion of the metal flashing, thus providing a redundant seal at the flashing laps. This sequencing can be tricky, as it requires coordination of the work of other trades that are likely on site performing work at the same time. Transition Components Deficiencies in transition components are one of the main sources of water intrusion in wood deck waterproofing systems. Base of wall flashing at inside and outside corners, post boots, and outside edge deck terminations at walls are critical components that are also complex; these components must be designed to integrate with adjacent metal flashing as well as to provide flanges for proper integration with the building s weather resistive barrier. To provide better long term performance, these flashings should be constructed as one component pieces, with all seams soldered watertight. Since these components are usually complex, they require fabrication from several sheet metal pieces that are tabbed together and soldered watertight at the seams. Though fabricated from several pieces, the result is a one component, complex flashing segment. Careful field measurement of as built conditions is required prior to fabrication so that the pieces fit together well in the field. At the outside edge of balconies, onecomponent sheet metal flashings (Figure 17) provide a watertight transition at this critical area. At deck to wall transitions on outside building corners, flanges should be provided for integration with the waterproofing membrane and for integration with the weather resistive barrier on the building wall (Figure 18). This detail helps create a watertight transition at the corner, which is otherwise susceptible to leakage. At post locations that penetrate through deck framing to support upper decks, boot flashings should be fabricated and installed as separate one component sheet metal Figure 18 Figure 17 S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y N O V E M B E R R O M E R O 4 3

10 Figure 20 Figure 19a Figure 19b flashings that fit together around the base of the post (Figure 19). As a part of proper installation sequencing, the post should be wrapped with a weather resistive barrier that laps over the vertical leg of the sheet metal boot flashing and the post subsequently clad with wood siding. This detailing allows the membrane to have a consistent substrate at the horizontal to vertical transition. In addition, if water enters the post cladding, the weather resistive barrier will direct the water over the metal boot flashing and safely onto the surface of the deck waterproofing membrane. Vertical-Mounted Railing Base Plates Although railings are a necessary part of balcony and walkway construction, design of railing attachments is sometimes overlooked and left to chance. Railing attachment is often not detailed in the construction documents, and it is left up to the fabricator/contractor to decide the preferred method of installation. Thus, a wellinstalled waterproofing membrane might be penetrated by railing base plate anchors at a critical location where the slope of the balcony directs water for drainage. Railing base plate attachment through the waterproof membrane at the horizontal deck surface should be avoided since it is difficult to make the anchor penetrations watertight. Even if watertight initially, sealants used at the base plates will require routine maintenance. A more serviceable approach to railing attachment is to design the deck for railing post anchorage at the vertical edge of the deck (Figure 20). Anchorage of the railing at this location does not compromise the integrity of the waterproofing membrane system. Unlike the horizontal base plate application where anchor bolts are subject to water directed by the slope of the deck, drip flashing can be installed directly above vertically oriented railing base plate connections to help direct water away from the anchor bolts. In repair projects, it is typically not economically feasible to modify existing railing posts and retrofit them with new vertically oriented base plates; thus, new railings are required. Additional framing and blocking is generally also required at the deck perimeter if the railings were not originally designed for anchorage through the fascia. CONCLUSIONS The successful performance of a wooddeck waterproofing membrane system is the result of proper waterproofing system selection, membrane and flashing design, installation of interface components, and coordination with the work of other building trades. In order for the designer, contractor, and owner to understand and develop realistic project expectations, details should be developed that illustrate the profiles of the specific flashing components that are anticipated. Mock ups are essential and should be installed in the field on decks that will be waterproofed, with the work performed by the specific personnel that will be performing the work on the project and properly sequenced with the adjacent cladding construction. The reviewed and accepted mockups help provide the required learning curve and establish the quality of construction required for the project, which subsequently defines the expectations of all parties. REFERENCES Thermoplastic Subcommittee of SPRI, The ABCs of PVC Roof Membranes, Roofing, Siding, Insulation, January R O M E R O S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y N O V E M B E R

WeatherSmart Air Barrier Installation Guide

WeatherSmart Air Barrier Installation Guide WeatherSmart Air Barrier Installation Guide 1 The intent of this document is to provide a guide for the installation of WeatherSmart as both a Weather Resistive Barrier (W.R.B.) and an Air Barrier Material

More information

INSTALLING WATER-RESISTIVE BARRIERS & FLASHING

INSTALLING WATER-RESISTIVE BARRIERS & FLASHING INSTALLING WATER-RESISTIVE BARRIERS & FLASHING IN A TWO-LAYER STUCCO APPLICATION Fortifiber Building Systems Group provides this guide to assist installers by demonstrating a two-layer installation of

More information

Architectural Wall Products Guide Specifications

Architectural Wall Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Wall Products Guide Specifications FORMED METAL WALL PANELS This Guide Specification is

More information

The better way to build TM. Installation Manual NAILBASE PANELS

The better way to build TM. Installation Manual NAILBASE PANELS The better way to build TM Installation Manual PANELS November 2018 SIPs Installation Manual Table of Contents Topics General Requirements................................... 3 Materials..............................................

More information

SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE:

SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE: IRC CODE UPDATES TO: RESIDENTIAL BUILDING CONTRACTORS FROM: GARY STABER, BUILDING OFFICIAL SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE: 6/1/2003 INTERNATIONAL RESIDENTIAL CODE (IRC) APPLICABILITY:

More information

University of New Hampshire Scholars' Repository

University of New Hampshire Scholars' Repository University of New Hampshire University of New Hampshire Scholars' Repository Division 07 Thermal and Moisture Protection Chapter 5 Technical Construction and Renovation Standards 1-25-2013 075423 - TPO

More information

SECTION 07530CP EPDM MEMBRANE ROOFING

SECTION 07530CP EPDM MEMBRANE ROOFING PART 1 GENERAL 1.1 SUMMARY SECTION 07530CP EPDM MEMBRANE ROOFING A. Section includes: 1. Adhered membrane roofing and flashing 2. Mechanically fastened roof insulation 3. Walkway pads 1.2 ARCHITECTURAL

More information

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 075423 - THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Division 00 Bidding Requirements and other Division

More information

Exterior Elevated Elements Inspection Guidelines

Exterior Elevated Elements Inspection Guidelines Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code

More information

Architectural Roof Products Guide Specifications

Architectural Roof Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Roof Products Guide Specifications FORMED METAL ROOF AND WALL PANELS This Guide Specification

More information

Architectural Roof and Wall Products Guide Specifications

Architectural Roof and Wall Products Guide Specifications Architectural Roof and Wall Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL WALL PANELS This Guide Specification

More information

Architectural Roof Products Guide Specifications

Architectural Roof Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Roof Products Guide Specifications FORMED METAL ROOF AND WALL PANELS This Guide Specification

More information

Architectural Roof and Wall Products Guide Specifications

Architectural Roof and Wall Products Guide Specifications Architectural Roof and Wall Products Guide Specifications 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL ROOF AND WALL PANELS This Guide Specification is to be used

More information

Building Enclosure Detailing for Balconies

Building Enclosure Detailing for Balconies Building Enclosure Detailing for Balconies COLIN SHANE M.ENG., P.ENG., P.E. ASSOCIATE, SENIOR PROJECT MANAGER RDH BUILDING SCIENCE INC. AUGUST 2016 Disclaimer: This presentation was developed by a third

More information

Insulation. First Revison October DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS

Insulation. First Revison October DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS Insulation First Revison October 2016 DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS 1. General Information This Guide describes the use of Kingspan GreenGuard DC14 Drainage

More information

Stucco Detailing for Buildings With Unique Geometry

Stucco Detailing for Buildings With Unique Geometry Stucco Detailing for Buildings With Unique Geometry Richard W. Mosco, AIA Wiss, Janney, Elstner Associates, Inc. 225 south lake ave., Pasadena, Ca 91101 Phone: 626-696-4650 626-696-4699 e-mail: rmosco@wje.com

More information

Architectural Roof and Wall Products Guide Specifications

Architectural Roof and Wall Products Guide Specifications Architectural Roof and Wall Products Guide Specifications 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL ROOF AND WALL PANELS This Guide Specification is to be used

More information

Item 2.3 Unit pricing GC to provide a square foot unit cost for material and labor to replace plywood decking beneath new concrete walkway slab.

Item 2.3 Unit pricing GC to provide a square foot unit cost for material and labor to replace plywood decking beneath new concrete walkway slab. Willow Glen Housing Repairs Project #9-59 Addendum Item. Change to bid date The bid date will be extended to March 8, 09, :00pm at the Housing Authority of Columbus Central Office,000 Wynnton Road Columbus,

More information

OREGON ROOF CONSULTING - ROOF INSPECTION FORM

OREGON ROOF CONSULTING - ROOF INSPECTION FORM Oregon CCB: 199121 PO Box 220190, Milwaukie, OR 97222 Washington License: OREGORC871MR OREGON ROOF CONSULTING - ROOF INSPECTION FORM General Roof Conditions: NA = Not Applicable Debris on Roof Physical

More information

SRP-AirOutshield UV Issued:

SRP-AirOutshield UV Issued: SECTION 07276: SRP-AirOutshield UV Ultra Violet (UV) resistant, Vapour Permeable Air Barrier Underlayment and Sheathing Membrane Guide Specification This specification is a guide only and may need editing

More information

R E S I D E N T I A L B U I L D E R S R E F E R E N C E G U I D E

R E S I D E N T I A L B U I L D E R S R E F E R E N C E G U I D E DRYVIT SYSTEMS CANADA DSC504 R E S I D E N T I A L B U I L D E R S R E F E R E N C E G U I D E BUILDING SUCCESSFULLY WITH DRYVIT OUTSULATION RESIDENTIAL SYSTEMS INTRODUCTION Building Successfully with

More information

1. Rubberized asphalt waterproofing membrane, reinforced. 2. Molded sheet drainage panels. 3. Insulation. 4. Plaza deck pavers.

1. Rubberized asphalt waterproofing membrane, reinforced. 2. Molded sheet drainage panels. 3. Insulation. 4. Plaza deck pavers. SECTION 071413 HOT FLUID APPLIED RUBBERIZED ASPHALT WATERPROOFING PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Rubberized asphalt waterproofing membrane, reinforced. 2. Molded sheet drainage panels.

More information

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS DAVIS, CALIFORNIA

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS DAVIS, CALIFORNIA The following standard specification is intended to be edited according to the specifics of the project. Brackets [ ] and areas shaded in gray [e.g. format] indicate requirements that are optional depending

More information

SSL-175. Specifications

SSL-175. Specifications SSL-175 Specifications Everlast Metals 10 Enterprise Court Lebanon, PA 17042 Phone: (717) 270-6554 Fax: (717) 270-6569 www.everlastmetals.com 7410 Preformed Metal Roofing PART 1: GENERAL 1.01 SECTION INCLUDES

More information

Perm-A-Barrier VPS (Vapor Permeable Sheet)

Perm-A-Barrier VPS (Vapor Permeable Sheet) VPS (Vapor Permeable Sheet) Self-adhering vapor permeable air barrier membrane Product Description VPS (Vapor Permeable Sheet) is a vapor permeable air barrier membrane consisting of a proprietary breathable

More information

Revised January buildingscience.com. Water Management Details. Housewraps/Flashings/Windows buildingscience.com

Revised January buildingscience.com. Water Management Details. Housewraps/Flashings/Windows buildingscience.com Revised January 2007 Housewraps/Flashings/Windows BSP-020: for Residential Buildings Table of Contents Introduction... 4 Water Management Concept...4 Risk Factors... 4 Building Paper/Housewraps as the

More information

2002 Advanced Building Products, Inc., P.O. Box 98, Springvale, Maine TEL: ; FAX: ; WEBSITE:

2002 Advanced Building Products, Inc., P.O. Box 98, Springvale, Maine TEL: ; FAX: ; WEBSITE: SECTION 07651 FLEXIBLE COPPER SHEET FLASHINGS Advanced Building Products, Inc. manufacturer many types of flexible copper sheet flashings. Due to their ductility, high tensile strength, and resistance

More information

SECTION ROOF SPECIALTIES

SECTION ROOF SPECIALTIES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 71 00 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information

Corium Brick Rainscreen System Specifications

Corium Brick Rainscreen System Specifications CORIUM BRICK RAINSCREEN SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Work Included: The Work of this Section shall include but not be limited to the following: 1. Corium brick plates 2. Galvanized and coated

More information

Building Enclosure Detailing for Balconies

Building Enclosure Detailing for Balconies Building Enclosure Detailing for Balconies COLIN SHANE M.ENG., P.ENG., P.E. PRINCIPAL, SENIOR PROJECT MANAGER RDH BUILDING SCIENCE INC. JUNE 2017 Disclaimer: This presentation was developed by a third

More information

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07 4243 - PART 1 GENERAL 1.01 SECTION INCLUDES A. Composite wall panel system consisting of aluminum-faced composite panels in a rainscreen application as part of the assembly described below.

More information

Commercial Flashing Details

Commercial Flashing Details This technical note illustrates many of the most common flashing details for commercial buildings. The purpose for flashing is to direct moisture to the exterior and in so doing, prevent moisture from

More information

DIVISION 7 - THERMAL AND MOISTURE PROTECTION

DIVISION 7 - THERMAL AND MOISTURE PROTECTION 07100 WATERPROOFING 07150 DAMPPROOFING 07175 Water Repellent Coatings 07190 VAPOR AND AIR RETARDERS 07192 Vapor Retarders 07200 INSULATION 07240 Exterior Insulation and Finish Systems 07250 FIREPROOFING

More information

Pebbletex Wall System Class PB Exterior Insulation and Finish System providing a primary moisture barrier. Typical Details

Pebbletex Wall System Class PB Exterior Insulation and Finish System providing a primary moisture barrier. Typical Details Pebbletex Wall System Class PB Exterior Insulation and Finish System providing a primary moisture barrier Typical Details (THIS PAGE INTENTIONALLY LEFT BLANK Pebbletex Wall System Class PB Exterior Insulation

More information

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1 Louis Armstrong New Orleans International Airport NOAB Project # 8910-01233 PART 1 - GENERAL SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS 1.1 RELATED DOCUMENTS A. Drawings and general provisions

More information

A. Section includes fluid applied, vapor permeable membrane air barriers.

A. Section includes fluid applied, vapor permeable membrane air barriers. Master Construction Specifications Insert Project Name SECTION 072726 FLUID APPLIED MEMBRANE AIR BARRIERS PART 1 GENERAL 1.1 SUMMARY A. Section includes fluid applied, vapor permeable membrane air barriers.

More information

Magnum Board Coatings

Magnum Board Coatings Master Wall Mesh and Base Coat Plastic Control Joint Accessory, Plastic Components 22027-16 or equal. See notes for placement recommendations Notes: Control joints are required and should be located by

More information

Carroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines Detached Garage

Carroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines Detached Garage Carroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines Detached Garage The following list of code requirements is intended to assist you in complying with the Code of Public

More information

SUMMER VILLAGE CONDITIONS ASSESSMENT ENVELOPE BUILDING

SUMMER VILLAGE CONDITIONS ASSESSMENT ENVELOPE BUILDING SUMMER VILLAGE BUILDING ENVELOPE CONDITIONS ASSESSMENT PREPARED FOR: Summer Village Townhomes c/o Kim Patterson Parker Brown Real Estate 187 W Main Street Lehi, UT 84043 PROJECT NUMBER: 15-144 REPORT DATE:

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 092216 - NON-STRUCTURAL METAL FRAMING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

DIVISION 07 THERMAL AND MOISTURE PROTECTION ROOFING

DIVISION 07 THERMAL AND MOISTURE PROTECTION ROOFING 07 00 00 PART 1 - GENERAL 1.01 DESIGN CRITERIA A. Preferred roofing types include Membrane, Metal, and Composition Shingles. 1. Membrane roofing is preferred for flat roof decks. 2. Use of asphalt-based

More information

SC-01 Cross-Section. Cement Board Substrate Master Wall Mesh and Base Coat Superior Finish

SC-01 Cross-Section. Cement Board Substrate Master Wall Mesh and Base Coat Superior Finish Master Wall Mesh and Base Coat Plastic Control Joint Accessory, Plastic Components 22027-16 or equal. See notes for placement recommendations Notes: Control joints are required and should be located by

More information

DL-200. Specifications

DL-200. Specifications DL-200 Specifications Everlast Metals 10 Enterprise Court Lebanon, PA 17042 Phone: (717) 270-6554 Fax: (717) 270-6569 www.everlastmetals.com 7410 Structural Preformed Metal Roofing PART 1: GENERAL 1.01

More information

1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards

1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards SECTION 07185 TRAFFIC MEMBRANE PART 1 GENERAL 1.1 SECTION INCLUDES A. Traffic membrane, consisting of welded seam PVC waterproofing, over f following surfaces: 1. Decks, balconies, and sun porches 2. Walkways,

More information

FUNCTIONAL REQUIREMENTS

FUNCTIONAL REQUIREMENTS FUNCTIONAL REQUIREMENTS FUNCTIONAL REQUIREMENTS 7.6 BALCONIES Workmanship i. All workmanship must be within the tolerances defined in Chapter 1 of this manual. ii. All work is to be carried out by a technically

More information

BUILDING SUCCESSFULLY WITH DRYVIT RESIDENTIAL SYSTEMS.

BUILDING SUCCESSFULLY WITH DRYVIT RESIDENTIAL SYSTEMS. BUILDING SUCCESSFULLY WITH DRYVIT RESIDENTIAL SYSTEMS. DS504 THE FOLLOWING IS A LIST OF MAJOR CONSIDERATIONS THAT WILL HELP ENSURE A QUALITY DRYVIT INSTALLATION. SUBSTRATES (INSPECTION/WALK-AROUND) Prior

More information

EverGuard Plaza Deck Roofing For Above-Grade Plaza Deck Applications

EverGuard Plaza Deck Roofing For Above-Grade Plaza Deck Applications EverGuard Plaza Deck Roofing For Above-Grade Plaza Deck Applications Specifications Updated: 12/07 Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer PLAZA DECK ROOFING

More information

Distances are not shown to scale. Existing porch. Community. Building. Distances are not shown to scale

Distances are not shown to scale. Existing porch. Community. Building. Distances are not shown to scale patio and deck 00 Building Two story Four-plex Entrance 0 0 00 Building Single Story Duplex 0 patio Contact Information: Owner: Housing Authority of Yamhill County, NE Dunn Place, McMinnville, OR 9. Contact:

More information

Stone and Masonry Veneer

Stone and Masonry Veneer Stone and Masonry Veneer R703.7 Stone and masonry veneer, general. Stone and masonry veneer shall be installed in accordance with this chapter, Table R703.4 and Figure R703.7. These veneers installed over

More information

Forensics Engineering 8th Congress Forging Forensic Frontiers November 29 December 2, 2018, Austin, TX

Forensics Engineering 8th Congress Forging Forensic Frontiers November 29 December 2, 2018, Austin, TX This paper was published at the Forensic Engineering 8th Congress, held November 29-December 2, 2018 in Austin, TX. The published version of this paper is available for purchase and download at: https://ascelibrary.org/doi/book/10.1061/9780784482018

More information

PROTECTO DECK INSTALLATION INSTRUCTIONS

PROTECTO DECK INSTALLATION INSTRUCTIONS PROTECTO DECK INSTALLATION INSTRUCTIONS THE FOLLOWING MATERIALS ARE NEEDED TO COMPLETE THE PROTECTO DECK SYSTEM. Protecto Deck Protecto Deck is a cold applied, nominal 70 mil, self-adhering primary waterproofing

More information

Perimeter Relief and Control Joints in Fire-Rated Gypsum Board

Perimeter Relief and Control Joints in Fire-Rated Gypsum Board Perimeter Relief and Control Joints in Fire-Rated Gypsum Board In multi-family residential construction, involving fire-rated assemblies stress relief in the firerated assemblies is important, but often

More information

AcroWall-ES System. Class PB Exterior Insulation and Finish System providing a primary moisture barrier. Typical Details

AcroWall-ES System. Class PB Exterior Insulation and Finish System providing a primary moisture barrier. Typical Details Typical Details AcroWall-ES System Class PB Exterior Insulation and Finish System providing a primary moisture barrier 1. Typical AcroWall-ES System Application 2. Typical Aesthetic Reveal 3. Typical Window

More information

Tuscaloosa Police Station

Tuscaloosa Police Station Tuscaloosa Police Station 3801 Trevor S Phillips Ave Tuscaloosa, AL 35401 Core Cut: Spray Foam Roof- ½ thick +- Single Ply Membrane Tapered EPS Insulation 2-6 Metal Deck PART 1 GENERAL 1.1 SCOPE OF WORK

More information

Aqua Coast Engineering

Aqua Coast Engineering Aqua Coast Engineering Ltd. P.O. Box 1367 Station A Delta, B.C. V4M 3Y8 Tel: (604)948-0958 Fax: 604)948-0959 September 1, 2011 Matthew Cheng File#:11145 Matthew Cheng Architect Inc. Fax: 604-731-3908 Unit

More information

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1 FIRESTOP JOINT SPRAY CFS-SP WB SILICONE JOINT SPRAY CFS-SP SIL F-RATING 2-HR. 2-HR. T-RATING -HR. -HR. APPLICATION THICKNESS PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table /8" WET FILM (/6"

More information

DIVISION 7 THERMAL AND MOISTURE PROTECTION

DIVISION 7 THERMAL AND MOISTURE PROTECTION DIVISION 7 THERMAL AND MOISTURE PROTECTION UCSC Campus Standards Handbook Waterproofing Standards 07100 1 SECTION 07100: WATERPROOFING STANDARDS A. Guarantee 1. Provide a guarantee on Contractor's letterhead

More information

PROPERTY PRESERVATION AND CAPITAL PLANNING

PROPERTY PRESERVATION AND CAPITAL PLANNING PROPERTY PRESERVATION AND CAPITAL PLANNING Overview What am I looking for Remaining Useful Life Estimating Planning TERMINOLOGY Shake Siding Service Head Barge Board Soffit / Overhang Belly Band Knee Brace

More information

Light-Metal Roof Edge, Raised

Light-Metal Roof Edge, Raised NAIL WOOD CANT TO BLOCKING 2 ROWS STAGGERED EACH ROW 24 O.C. 1/2 MIN. 10 0 MAX. FASTEN 18 O.C. WITH NEOPRENE GASKETED FASTENERS 3-1/2 MIN. 4 6 JOINT COVER PLATE SET IN TWO BEADS OF SEALANT 4 MIN. SPECIFIED

More information

KARRIER PANEL - BRICK

KARRIER PANEL - BRICK KPH-DS-01-BRICK KPH-PJ-01-BRICK KPH-PJ-02-BRICK KPH-PJ-03-BRICK KPH-BS-01-BRICK KPH-BS-02-BRICK KPH-BS-03-BRICK KPH-OC-01-BRICK KPH-FO-01-BRICK KPH-FO-02-BRICK KPH-FO-03-BRICK KPH-FO-04-BRICK KPH-FO-05-BRICK

More information

SECTION SELF-ADHERED WATER-RESISTIVE ROOF UNDERLAYMENT

SECTION SELF-ADHERED WATER-RESISTIVE ROOF UNDERLAYMENT SECTION 07 30 05.01 SELF-ADHERED WATER-RESISTIVE ROOF UNDERLAYMENT SPEC WRITERS NOTE: This specification includes materials and installation procedures for SlopeShield SA Self-Adhered Water-Resistive Vapor

More information

SECTION EXPANSION CONTROL

SECTION EXPANSION CONTROL SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Detail Booklet StoTherm ci XPS

Detail Booklet StoTherm ci XPS Detail Booklet Series 53sxx Steel Frame Construction February 2017 professional, general contractor or builder They should be installed in accordance with those specifications and Sto s instructions Sto

More information

SECTION EXPANSION CONTROL

SECTION EXPANSION CONTROL SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION TURBINE VENTILATORS

SECTION TURBINE VENTILATORS SECTION 07 72 00 TURBINE VENTILATORS **This is a CSI Three-Part Specification using CSI MasterFormat 2004-2010 Section Numbers and Titles. This specification must be edited to suit your particular project.

More information

ARCHITECTURAL WALL PANELS APPLIED OVER A SHEATHED STUDWALL BY MEANS OF A FIELD ASSEMBLED RAINSCREEN SYSTEM

ARCHITECTURAL WALL PANELS APPLIED OVER A SHEATHED STUDWALL BY MEANS OF A FIELD ASSEMBLED RAINSCREEN SYSTEM RAINSCREEN (H&J) SYSTEM INSTALLATION DATA & DETAILS Omnis Panels, Inc. Architectural Building Panels 22 East Chicago Avenue Suite 210 Naperville, Illinois 60540 (800) 450-6099 (630) 355-4040 Fax: (630)

More information

ARCHITECTURAL WALL PANELS APPLIED OVER A SHEATHED STUDWALL BY MEANS OF A FIELD ASSEMBLED RAINSCREEN SYSTEM

ARCHITECTURAL WALL PANELS APPLIED OVER A SHEATHED STUDWALL BY MEANS OF A FIELD ASSEMBLED RAINSCREEN SYSTEM RAINSCREEN (H&J) SYSTEM INSTALLATION DATA & DETAILS Omnis Panels, Inc. Architectural Building Panels 22 East Chicago Avenue Suite 210 Naperville, Illinois 60540 (800) 450-6099 (630) 355-4040 Fax: (630)

More information

Structural Inspection

Structural Inspection General: Background: An inspection and structural analysis have been performed for the purpose of evaluating the buildings structural systems and components. A full set of structural drawings was utilized

More information

SECTION EXPANSION CONTROL

SECTION EXPANSION CONTROL SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

ROOF REPLACEMENT AND ALTERATIONS TO WOODSTOCK Barrett Architecture, PC WASTE WATER TREATMENT FACILITY - Woodstock, VT February 28, 2019 SECTION

ROOF REPLACEMENT AND ALTERATIONS TO WOODSTOCK Barrett Architecture, PC WASTE WATER TREATMENT FACILITY - Woodstock, VT February 28, 2019 SECTION SECTION 075400 PART 1 - GENERAL 1.1 GENERAL PROVISIONS A. Attention is directed to the CONTRACT AND GENERAL CONDITIONS and all Sections within DIVISION 01 - GENERAL REQUIREMENTS which are hereby made a

More information

TYPICAL ROOF CONDITION LAYOUT

TYPICAL ROOF CONDITION LAYOUT FIXED POINTS TYPICAL ROOF CONDITION LAYOUT 15 17 9 16 29 12 14 11 3 7 35 20 6 23 30 31 24 13 18 Typical Roof Condition Layout... 1 Low Eave Isometric View - Fixed/ Floating... 2 Low Eave Section - Fixed/

More information

Building Envelope Solutions, Inc. Identifying solutions for better building performance

Building Envelope Solutions, Inc. Identifying solutions for better building performance Building Envelope Solutions, Inc. Identifying solutions for better building performance SUPERGREEN LAM TM (Liquid-applied Membrane) Background of the development of SUPERGREEN LAM TM : Spray-applied polyurethane

More information

DuPont Tyvek Air Barrier Installation Guidelines. Canadian Version. Version 2

DuPont Tyvek Air Barrier Installation Guidelines. Canadian Version. Version 2 DuPont Tyvek Air Barrier Installation Guidelines Helping you get the job done right Canadian Version Version 2 Table of Contents Applicable Products...2 Required Materials...2 Code Requirements...3 General

More information

SECTION EXPANSION CONTROL

SECTION EXPANSION CONTROL SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

ROOFING EPDM ELASTOMERIC SHEET ROOFING FULLY ADHERED- CONVENTIONAL

ROOFING EPDM ELASTOMERIC SHEET ROOFING FULLY ADHERED- CONVENTIONAL ROOFING EPDM ELASTOMERIC SHEET ROOFING FULLY ADHERED- CONVENTIONAL PART 1 GENERAL 1.1 SECTION INCLUDES A. Insulation, membrane roofing, base flashings roofing membrane accessories joints, and counter flashings.

More information

Tile on Existing. Viewpoint

Tile on Existing. Viewpoint Viewpoint Tile on Existing Exterior Reinforced Concrete BalconieS By Steven C. Turner Exterior reinforced concrete balconies are often covered by tile set in mortar beds with grouted joints. These installations

More information

STRATUM GUARD I AND II An Exterior Insulation and Finish System with Drainage DSC106C. Stratum Guard I and II System Installation Details

STRATUM GUARD I AND II An Exterior Insulation and Finish System with Drainage DSC106C. Stratum Guard I and II System Installation Details STRATUM GUARD I AND II An Exterior Insulation and Finish System with Drainage DSC106C Stratum Guard I and II System Installation Details Stratum Guard I and II DETAIL Table of Contents NOTE SG.0.0.01 SG.0.0.02

More information

Gensler 2014/06/16 Hertz Global Headquarters ISSUE FOR BUILDING PERMIT Estero, Florida SECTION

Gensler 2014/06/16 Hertz Global Headquarters ISSUE FOR BUILDING PERMIT Estero, Florida SECTION SECTION 072700 VAPOR PERMEABLE AIR BARRIER LIQUID MEMBRANE PART 1 GENERAL 1.1 GENERAL REQUIREMENTS A. The Work of this Section, as shown or specified, shall be in accordance with the requirements of the

More information

A. This Section provides information regarding vapor permeable roof underlayment for the exterior roof.

A. This Section provides information regarding vapor permeable roof underlayment for the exterior roof. DELTA -VENT S Vapor Permeable (Breathable) Roof Underlayment Division 7 Thermal and Moisture Protection PART 1 GENERAL 1.1 SUMMARY A. This Section provides information regarding vapor permeable roof underlayment

More information

SECTION HANDRAILS AND RAILINGS. A. Section Metal Fabrications: Associated metal supports.

SECTION HANDRAILS AND RAILINGS. A. Section Metal Fabrications: Associated metal supports. SECTION 05520 HANDRAILS AND RAILINGS PART 1 GENERAL 1.1 SECTION INCLUDES A. Handrails and guardrails B. Guardrails for hatches and openings. C. Safety barriers. D. Roof edge protection. 1.2 RELATED SECTIONS

More information

SPECIFICATIONS FOR AluSystems Aluminum Composite Panels Series 20 Dry Joint 1.00 GENERAL 1.01 RANGE OF WORK Section includes: Laminated panels and attachment systems for use as exterior cladding. A. Provide

More information

Guide Specification for the OSI QUAD Window and Door Flashing System

Guide Specification for the OSI QUAD Window and Door Flashing System Henkel Corporation 26235 First Avenue Westlake, OH 1-866-591-2178 www.ositough.com Guide Specification for the OSI QUAD Window and Door Flashing System Specifier Note: The purpose of this guide specification

More information

SRP-AirOutshield ROOF Issued:

SRP-AirOutshield ROOF Issued: SECTION 07276: Breathable Underlayment Guide Specification This specification is a guide only and may need editing for the specific intended application. It is the responsibility of the design professional

More information

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION METAL ROOF PANELS

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION METAL ROOF PANELS OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 SECTION INCLUDES A. Structural roofing system of preformed steel panels. B. Fastening system. C. Factory finishing. D. Accessories and miscellaneous components.

More information

A. Meet at Project site <insert number> days before starting installation.

A. Meet at Project site <insert number> days before starting installation. SECTION 074643 - COMPOSITION SIDING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Engineered wood cladding. 2. Soffit panels. 3. Trim and fascia. 4. Sealant. 5. Weather barrier. 6. Flashing. 1.2

More information

National Master Specification (NMS) Section Publisher: Spex.ca Page 1. Approved: RELATED REQUIREMENTS.1 Section [ ].

National Master Specification (NMS) Section Publisher: Spex.ca Page 1. Approved: RELATED REQUIREMENTS.1 Section [ ]. National Master Specification (NMS) Section 07 21 16 BLANKET INSULATION Publisher: Spex.ca Page 1 Approved: 2014-12-31 Part 1 General 1.1 RELATED REQUIREMENTS.1 Section [ ]. 1.2 REFERENCES.1 CSA Group.1

More information

DIVISION 5 METALS SECTION COLD-FORMED METAL FRAMING

DIVISION 5 METALS SECTION COLD-FORMED METAL FRAMING DIVISION 5 METALS SECTION 05 40 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

B.01. Lincoln Property Company 100 Lowell Road North Reading, MA 01864

B.01. Lincoln Property Company 100 Lowell Road North Reading, MA 01864 7 Specific Notes - Type B Repairs Detail Step. SHADED AREAS INDICATE MATERIALS TO BE REMOVED.. REMOVE EXISTING PVC RAILINGS AND STORE FOR RE-INSTALLATION UPON COMPLETION OF THE WORK 6" Min.. REMOVE X VERTICAL

More information

PERM-A-BARRIER VPS. Product Description. Product Data Sheets. Self-adhering vapor permeable air and water barrier membrane

PERM-A-BARRIER VPS. Product Description. Product Data Sheets. Self-adhering vapor permeable air and water barrier membrane PERM-A-BARRIER VPS Self-adhering vapor permeable air and water barrier membrane Product Description GCP Applied Technologies ( GCP ) PERM-A-BARRIER VPS (Vapor Permeable Sheet) membrane is a vapor permeable

More information

1.2 DEFINITIONS, REFERENCES, AND OVERALL STANDARDS Follow 07500

1.2 DEFINITIONS, REFERENCES, AND OVERALL STANDARDS Follow 07500 07721 ROOF ASSEMBLY SUPPORTS FOR ROOFTOP EQUIPMENT ****************************************** SPECIFIER: All roof-related items above or outside the structural roof deck, including such work as blocking,

More information

WARRANTY PROVIDER ACCEPTED A REFERENCE GUIDE OF TYPICAL RAINSCREEN WALL AND WINDOW DETAILS

WARRANTY PROVIDER ACCEPTED A REFERENCE GUIDE OF TYPICAL RAINSCREEN WALL AND WINDOW DETAILS WARRANTY PROVIDER ACCEPTED A REFERENCE GUIDE OF TYPICAL RAINSCREEN WALL AND WINDOW DETAILS Per: 2006 B.C.B.C. Part 9 DISCLAIMER: THE INFORMATION CONTAINED IN THIS DOCUMENT REPRESENTS CURRENT WOOD FRAME

More information

SECTION ROOF MOUNTED ATTIC EXHAUST VENT

SECTION ROOF MOUNTED ATTIC EXHAUST VENT SECTION 07 72 00 ROOF MOUNTED ATTIC EXHAUST VENT **This is a CSI Three-Part Specification using CSI MasterFormat 2004-2010 Section Numbers and Titles. This specification must be edited to suit your particular

More information

DuPont Tyvek Wall Underlay Install Guide

DuPont Tyvek Wall Underlay Install Guide DuPont Tyvek Wall Underlay Install Guide (For Residential & Light Commercial Buildings) Acceptable Solution to NZBC E2/AS1 New Zealand As at 1/4/15 Version 2 Subject to change without notice DuPont Tyvek

More information

CTIOA REPORT

CTIOA REPORT CERAMIC TILE INSTITUTE OF AMERICA, INC. 12061 Jefferson Blvd., Culver City, CA 90230-6219 CTIOA REPORT 2003-4-17 SUBJECT: FLASHING DETAILS EXTERIOR TILE DECK CONSTRUCTION By Mark Marsch Preface Having

More information

DESIGN TIPS TECHNICAL BULLETIN #47 FLASHING, WEEP HOLES AND RELATED ANCHORAGE [1 of 8]

DESIGN TIPS TECHNICAL BULLETIN #47 FLASHING, WEEP HOLES AND RELATED ANCHORAGE [1 of 8] FLASHING, WEEP HOLES AND RELATED ANCHORAGE [1 of 8] Proper flashing and weep holes are essential elements in exterior masonry walls. Together, they provide a means to control moisture in a wall. If not

More information

G October 2018

G October 2018 G-14-18 October 2018 The information contained in this supplement serves as a criteria for Specifiers and Authorized Applicators regarding the design and installation of Carlisle Roofing Systems and use

More information

SECTION PREFORMED CLADDING. A. Part A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION PREFORMED CLADDING. A. Part A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 074213 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. Part A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

Ice Rink Renovation & New Clubhouse

Ice Rink Renovation & New Clubhouse SECTION 074243- METAL COMPOSITE MATERIAL WALL PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

PLYWOOD FLOATING FLOOR

PLYWOOD FLOATING FLOOR PLYWOOD FLOATING FLOOR Read First These suggestions represent generally accepted procedures for successful installation of Enka Building Products. These instructions may be followed, modified, or rejected

More information

DIVISION 07 - THERMAL & MOISTURE PROTECTION

DIVISION 07 - THERMAL & MOISTURE PROTECTION DIVISION 07 - THERMAL & MOISTURE PROTECTION DESIGN CRITERIA General Design Requirements: 1. When designing roof access ladders and stairways to roof shall not be alternating tread type. 2. Provide 18 gauge

More information