1 ROOF INSPECTION AND ANALYSIS PROCEDURE QUINLAN ASSOCIATES, LLC.
2 INSPECTION AND ANALYSIS PROCEDURE CONDUCTED ON: QUINLAN ASSOCIATES, LLC. INSPECTION CONDUCTED FOR: MS. CHERYL QUINLAN QUINLAN ASSOCIATES, LLC. 16W421 S. FRONTAGE ROAD WILLOWBROOK, ILLINOIS INSPECTION CONDUCTED BY: RRK ASSOCIATES, LTD. COMMERCIAL / INDUSTRIAL ROOF CONSULTANTS 900 TRI-STATE PARKWAY, SUITE 800 GURNEE, ILLINOIS MR. GARY AWE TEL (847) FAX (847) INSPECTION DATE: OCTOBER 22 ND, 2013 REPORT DATE: OCTOBER 24 TH, 2013
3 OBJECTIVE OF THE ROOF INSPECTION AND ANALYSIS Per your request and authorization, a roof inspection and analysis procedure was conducted on the commercial/industrial property located at 166 Shore Drive in Burr Ridge, Illinois. The inspection and analysis procedure was conducted under the direction of Quinlan Associates, LLC. The purpose of the roof inspection and analysis was to examine the existing roof membrane assemblies and related components to determine the general condition and provide recommendations and budget estimates for the necessary repairs and/or roof replacement. The inspection was conducted on Tuesday, October 22 nd, FINDING OF THE ROOF INSPECTION AND ANALYSIS Building Specifics The subject property is a single-story, office facility. The subject property totals approximately 15,500 square feet divided across two roof areas over two elevations. Roof Specifics The roofing assemblies present on the West and central roof sections consist of granule surfaced modified bitumen roofing assembly installed over 1 perlite insulation. The perimeter and penetration flashings consist of matching granule surfaced modified bitumen membrane. Roof penetrations were typical of commercial/industrial construction, consisting of plumbing stacks, pipe penetrations, various vent assemblies, skylight and HVAC curbs. Drainage of the roof planes was fair, sloping from the perimeter to internal roof drain assemblies located throughout the field of the roof. The perimeter of the building consists of a metal gravel stop detail. The required roof repairs/preventative maintenance issues noted during our inspection of this building consist of the following: Clear all debris and loose granules from throughout the roofing assembly to allow for proper drainage. Monitor the low areas of standing water noted throughout the field location for premature deterioration of the field membrane at these locations. Properly trim the trees away from the roof surface along the Northwest building exterior location to ensure that physical damage doesn t occur to the field membrane at this location. Monitor the minor granule loss noted along the middle of the West perimeter field membrane location. If this condition worsens, corrective action will be required to ensure protection from UV sunlight.
4 Replace the deteriorated wood blocking noted at the RTU gas line support locations. Ensure that the new treated wood blocks are properly set atop a slip sheet and secure the gas line to the support block locations. Properly reinstall the roof drain strainer along the lower West roof section location. Reinstall the missing service panel noted along the West roof section at the RTU location to ensure a watertight installation. Monitor the single wire penetrations noted through the side of the RTU curb adapter location for future sealant maintenance issues. Along the middle field it was noted that the RTU condensation line is draining directly onto the field membrane. This condition as noted has resulted in premature deterioration to occur to the field membrane at this location. Install a matching granule surfaced sacrificial ply of membrane at this location to ensure protection from UV sunlight. The area affected is approximately 3 x8. There is rust noted along the duct lift location in the middle field. These areas should be wire brushed clean then primed and painted with a matching rust inhibiting paint. Install a matching granule surfaced modified bitumen target patch along the side of the RTU curb locations where the membrane has been over-torched. No roof warranties were provided at the time of our inspection. Any warranties that exist will need to be transferred to the new property owner upon acquisition of the building. CONCLUSIONS AND RECOMMENDATIONS OF THE ROOF INSPECTION Based upon our inspection and analysis, the granule surfaced modified bitumen roofing assembly is considered to be in fair condition at this time with a remaining useful service life of 7-9 years. The cost to conduct the immediate roof repairs is estimated at $2, A roof recover procedure can be conducted for an approximate cost of $4.50 per square foot resulting in a budget of $70, for the 15,500 square feet of roof area around 2020 based upon current industry pricing. Projected Budget Immediate Roof Repairs (2013): $2, Annual Maintenance Budget (2014): $1, Annual Maintenance Budget (2015): $2, Annual Maintenance Budget (2016): $2, Annual Maintenance Budget (2017): $3,500.00
5 Annual Maintenance Budget (2018): $5, Annual Maintenance Budget (2019): $7, Roof Replacement (2020): $70, If you have any questions regarding our inspection or analysis of this building, please contact our office for clarification. Report Prepared By: Gary Awe RRK ASSOCIATES, LTD. COMMERCIAL /INDUSTRIAL ROOF CONSULTANTS Attachments: Photographic exhibits Roof Plan
6 PHOTOGRAPH #1 OVERVIEW OF THE ROOFING ASSEMBLIES ON THE SUBJECT PROPERTY LOCATED AT IN BURR RIDGE, ILLINOIS PHOTOGRAPH #2 VIEW OF THE TYPICAL PERIMETER GRAVEL STOP INSTALLATION.
7 PHOTOGRAPH #3 MONITOR THE LOW AREAS OF STANDING WATER NOTED THROUGHOUT THE FIELD LOCATION FOR PREMATURE DETERIORATION OF THE FIELD MEMBRANE AT THESE LOCATIONS. PHOTOGRAPH #4 PROPERLY TRIM THE TREES AWAY FROM THE ROOF SURFACE ALONG THE NORTHWEST BUILDING EXTERIOR LOCATION TO ENSURE THAT PHYSICAL DAMAGE DOESN T OCCUR TO THE FIELD MEMBRANE AT THIS LOCATION.
8 PHOTOGRAPH #5 MONITOR THE MINOR GRANULE LOSS NOTED ALONG THE MIDDLE OF THE WEST PERIMETER FIELD MEMBRANE LOCATION. IF THIS CONDITION WORSENS, CORRECTIVE ACTION WILL BE REQUIRED TO ENSURE PROTECTION FROM UV SUNLIGHT. PHOTOGRAPH #6 REPLACE THE DETERIORATED WOOD BLOCKING NOTED AT THE RTU GAS LINE SUPPORT LOCATIONS. ENSURE THAT THE NEW TREATED WOOD BLOCKS ARE PROPERLY SET ATOP A SLIP SHEET AND SECURE THE GAS LINE TO THE SUPPORT BLOCK LOCATIONS.
9 PHOTOGRAPH #7 PROPERLY REINSTALL THE ROOF DRAIN STRAINER ALONG THE LOWER WEST ROOF SECTION LOCATION. PHOTOGRAPH #8 VIEW OF THE ELEVATION CHANGE NOTED ALONG THE WEST FIELD LOCATION.
10 PHOTOGRAPH #9 REINSTALL THE MISSING SERVICE PANEL NOTED ALONG THE WEST ROOF SECTION AT THE RTU LOCATION TO ENSURE A WATERTIGHT INSTALLATION. PHOTOGRAPH #10 MONITOR THE SINGLE WIRE PENETRATIONS NOTED THROUGH THE SIDE OF THE RTU CURB ADAPTER LOCATION FOR FUTURE SEALANT MAINTENANCE ISSUES.
11 PHOTOGRAPH #11 ALONG THE MIDDLE FIELD IT WAS NOTED THAT THE RTU CONDENSATION LINE IS DRAINING DIRECTLY ONTO THE FIELD MEMBRANE. THIS CONDITION AS NOTED HAS RESULTED IN PREMATURE DETERIORATION TO OCCUR TO THE FIELD MEMBRANE AT THIS LOCATION. INSTALL A MATCHING GRANULE SURFACED SACRIFICIAL PLY OF MEMBRANE AT THIS LOCATION TO ENSURE PROTECTION FROM UV SUNLIGHT. THE AREA AFFECTED IS APPROXIMATELY 3 X8. PHOTOGRAPH #12 THERE IS RUST NOTED ALONG THE DUCT LIFT LOCATION IN THE MIDDLE FIELD. THESE AREAS SHOULD BE WIRE BRUSHED CLEAN THEN PRIMED AND PAINTED WITH A MATCHING RUST INHIBITING PAINT.
12 PHOTOGRAPH #13 CLEAR ALL DEBRIS AND LOOSE GRANULES FROM THROUGHOUT THE ROOFING ASSEMBLY TO ALLOW FOR PROPER DRAINAGE. PHOTOGRAPH #14 INSTALL A MATCHING GRANULE SURFACED MODIFIED BITUMEN TARGET PATCH ALONG THE SIDE OF THE RTU CURB LOCATIONS WHERE THE MEMBRANE HAS BEEN OVER- TORCHED.
13
Architectural Inspection Low Slope Roofing
0521 Low Slope Roofing All components of the roof system including insulation The roofing on the original building is an Inverted Roof Membrane Assembly (IRMA). It consists of a rubber membrane over ¾
More informationLithia Dodge East 5500 L St. Omaha, NE
Lithia Dodge East 5500 L St. Omaha, NE Perimeter Photos Failed Joints at North Rear Wall Control Joints Look Good Inadequate Downspout Elbows Erosion Along Wall Minor Efflorescence Roof Section Photos
More informationROOF OWNER'S OPERATION AND MAINTENANCE MANUAL
ROOF OWNER'S OPERATION AND MAINTENANCE MANUAL Table of Contents Section Title Page Section 1.0 General Maintenance Statement 2 Section 2.0 Safety 2 Section 3.0 Inspections 2-4 Section 4.0 Repairs 4 Section
More informationMOISTURE MANAGEMENT. Providing roofing and waterproofing solutions. Zionsville High School Roof Asset Management Plan
MOISTURE MANAGEMENT Providing roofing and waterproofing solutions. Zionsville High School Roof Asset Management Plan Executive Summary Moisture Management conducted a detailed investigation of 34 roof
More informationREROOFING ANALYSIS OF K-12 BUILDING. Unified School District 306 Gypsum, Kansas
REROOFING ANALYSIS OF K-12 BUILDING Unified School District 306 Gypsum, Kansas Reroofing Analysis of K-12 Building Unified School District 306 Gypsum, Kansas September 12, 2017 P1711 Introduction This
More informationURETHANE. Asphalt Restoration Aged BUR and Modified Bitumen Sample Design Guideline
1 DG0001-J 05/2017 Asphalt Restoration Aged BUR and Modified Bitumen Sample Design Guideline URETHANE ITW POLYMERS SEALANTS NORTH AMERICA, INC. 111 S. Nursery Road. Irving, TX 75060 Tel: 972-438-9111 Fax:
More informationArchitectural Inspection Pitched Roofing
Architectural Inspection Pitched Roofing 0511 Pitched Roofing All components of the roof system including insulation Description of the building system Three types of pitched roofing are found at the Gastineau
More informationKings Welding Works. Mr. Adam LaDuke Kings Welding Works 10111Capital Road Oak Park, Michigan 48237
Mr. Adam LaDuke Kings Welding Works 10111Capital Road Oak Park, Michigan 48237 Jacqueline Walters LaDuke Roofing and 13000 Northend Ave Oak Park Michigan 48237 (248) 414-6600 (248) 414-6604 Kings Welding
More informationADDENDUM # 2. - Page 1 of 2
2013-03-20 REQUEST FOR TENDER AFRICA RESTAURANT ROOF REPLACEMENT RFT # 11 (2013-03) ADDENDUM # 2 - Page 1 of 2 This addendum shall be incorporated into, and form part of RFT # 11 (2013-03) and take precedence
More informationHANSON MIDDLE SCHOOL
ROOF ASSESSMENT REPORT HANSON MIDDLE SCHOOL NOVEMBER 08, 2010 PREPARED FOR: FACILITIES DEPARTMENT WHITMAN HANSON REGIONAL SCHOOL DISTRICT 1. Purpose This Roofing Assessment Report provides a summary of
More informationPrepared By. Accent Building Sciences Inc. For
ROOF LEAK INVESTIGATION & CONDITION ASSESSMENT REPORT For Toronto, Ontario Prepared By Accent Building Sciences Inc. For Client# 40105 Date: November 11, 2003 November 2003 Roof Leak Investigations & Condition
More informationACRYLIC Elastek #127 Solar One Plus
1 EL0003-N 01/2018 Asphalt Restoration New or Aged BUR and Modified Bitumen Sample Design Guideline ACRYLIC Elastek #127 Solar One Plus ITW POLYMERS SEALANTS NORTH AMERICA, INC. 111 S. Nursery Road. Irving,
More informationACRYLIC. AGED (PVC, CPE, CPA) SINGLE-PLY (Thermoplastic) Membrane Restoration Sample Design Guideline
1 DG0013-J 04/2017 AGED (PVC, CPE, CPA) SINGLE-PLY (Thermoplastic) Membrane Restoration Sample Design Guideline ACRYLIC ITW POLYMERS SEALANTS NORTH AMERICA, INC. 111 S. Nursery Road. Irving, TX 75060 Tel:
More informationIRS I ndustrial R oofing S ervices, Inc.
IRS I ndustrial R oofing S ervices, Inc. 13000 West Silver Spring Drive Butler, Wisconsin 53007 Phone: (262) 432-0500 Fax: (262) 432-0504 www.irsroof.com Duke Realty Corporation Visual Roof Survey Report
More informationACRYLIC Elastek #127 Solar One Plus
1 EL0017-L 01/2018 AGED (EPDM, TPO, CSPE-HYPALON, PIB) SINGLE-PLY (THERMOSET) MEMBRANE RESTORATION SYSTEM APPLICATION SAMPLE DESIGN GUIDELINE ACRYLIC Elastek #127 Solar One Plus ITW POLYMERS SEALANTS NORTH
More informationMAINTENANCE INSPECTION GUIDE
MAINTENANCE INSPECTION GUIDE A QUICK AND EASY REFERENCE FOR BUILDING OWNERS O OBSERVE The leading cause of premature roofing system failure is the lack of a maintenance program. Periodic inspections and
More informationSMOOTH SURFACED BUILT-UP ROOFS WITH ARC SEBS REFLECTIVE ROOF COATINGS
1.0 SCOPE SPECIFICATION FOR COATING SMOOTH SURFACED BUILT-UP ROOFS WITH ARC SEBS REFLECTIVE ROOF COATINGS The intention of this specification is to outline the procedures for the application of ARC SEBS
More informationCITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO
SECTION 01010 - SCOPE OF WORK PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General provisions of Contract, General Conditions and Technical Specification Sections, apply to this Section. 1.02 PROJECT DESCRIPTION
More informationSummary of Existing Conditions: Point Pleasant Borough High School
On behalf of Spiezle Architectural Group, Inc., we thank you for allowing us the opportunity to provide our services as a Roofing Consultant and issue a District-wide roof evaluation report. As discussed,
More informationRCi. roof consultants, inc. Thank you for your interest in Roof Consultants, Inc.
Thank you for your interest in Roof Consultants, Inc. We have been providing quality services for building owners and managers for over 30 years and have over 100 years of combined experience in the roofing
More informationSECTION TOPSHIELD GUIDE SPECIFICATION SMOOTH AND GRANULE SURFACE ROOF RESTORATION TS-AC yr
SECTION 07 56 00 TOPSHIELD GUIDE SPECIFICATION SMOOTH AND GRANULE SURFACE ROOF RESTORATION TS-AC-70-483-70 15yr PART I GENERAL 1.01 RELATED DOCUMENTS A. Requirements of Division 1 General Requirements
More informationERSYSTEM ONESTEP PLUS
1 DG0047-A 05/2017 AGED (EPDM, TPO, CSPE-HYPALON, PIB) SINGLE-PLY (THERMOSET) MEMBRANE RESTORATION SYSTEM APPLICATION SAMPLE DESIGN GUIDELINE ERSYSTEM ONESTEP PLUS ITW POLYMERS SEALANTS NORTH AMERICA,
More informationOREGON ROOF CONSULTING - ROOF INSPECTION FORM
Oregon CCB: 199121 PO Box 220190, Milwaukie, OR 97222 Washington License: OREGORC871MR OREGON ROOF CONSULTING - ROOF INSPECTION FORM General Roof Conditions: NA = Not Applicable Debris on Roof Physical
More information838 Coatings System Specification Single-Ply Restoration (838 SPR)
838 Coatings System Specification Single-Ply Restoration (838 SPR) PART 1 General 1.01 System Description The 838 Single-Ply Restoration System (838 SPR) can be applied to a variety of single-ply manufactures.
More informationRoof Replacement. Notes: T-1 (Title Sheet) Roof Key Plan Russell House Student Union 1400 Greene Street Columbia, South Carolina 29208
Notes: Drawing Index T-1 Title R-1 Roof Plan - Existing Conditions R-2 Roof Plan - New D-1 Roof Details D-2 Roof Details D-3 Roof Details M-1 Mechanical - Roof Plan M-2 Mechanical - Details Roof Key Plan
More informationROOF SUBSTRATE PREP MANUAL
ROOF SUBSTRATE PREP MANUAL ALDOCOAT Liquid Applied Roof Restoration Systems AFTER BEFORE JULY 2016 1604 N. Main St. Kannapolis, NC 28081 (800) 474-6019 www.aldoproducts.com ROOF SUBSTRATE PREPARATION Preparation
More informationREPORT OF ROOF CONDITION STUDY. YOUR FACILITY Your Facilities Location. Date YOUR FACILITY S IDENTIFICATION. Prepared for Your Company
REPORT OF ROOF CONDITION STUDY YOUR FACILITY Your Facilities Location YOUR FACILITY S IDENTIFICATION Date Prepared for Your Company 1114 Grindstone, Union, Kentucky 41091 (859) 657-6677 [Report Date] [Client]
More informationAPPLICATION GUIDELINE
PROVEN ACRYLIC ROOFING SYSTEMdesigned to restore & protect metal roofs METAL To ensure warranty eligibility, each job must be approved by American WeatherStar before it begins. PART 1 GENERAL 1.01 DESCRIPTION
More informationProject Number BID NO. CAG 18 2 ROOF REPLACEMENT FOR HARFORD COUNTY PUBLIC SCHOOLS NORTH HARFORD ELEMENTARY. Addendum # 2
Project Number.0 BID NO. CAG ROOF REPLACEMENT FOR HARFO COUNTY PUBLIC SCHOOLS NORTH HARFO ELEMENTARY Addendum # This addendum is to be attached to the North Harford Elementary School Roof Replacement bid
More informationDESIGN GUIDELINE FLUID-APPLIED WATERPROOFING
DESIGN GUIDELINE FLUID-APPLIED WATERPROOFING (TO RESTORE METAL ROOF SYSTEMS) PART 1 GENERAL 1.01 DESCRIPTION A. This design guideline is to describe the installation of the ALDOCOAT acrylic reflective
More informationAcrylic/Urethane. Metal Roof Restoration Sample Design Guideline
1 DG0009-I 04/2017 Metal Roof Restoration Sample Design Guideline Acrylic/Urethane ITW POLYMERS SEALANTS NORTH AMERICA, INC. 111 S. Nursery Road. Irving, TX 75060 Tel: 972-438-9111 Fax: 972-554-3939 www.itwsealants.com
More informationSOLAR COATING SYSTEMS SYSTEM EMULSION /ACRYLIC. Specification for Built-Up Roofing MULSION/A 1.01 SUMMARY
SOLAR COATING SYSTEMS 2-PLY EMULSION MULSION/A /ACRYLIC SYSTEM Specification for Built-Up Roofing 07590 PART 1. GENERAL 1.01 SUMMARY Name Address City, State, zip A. Furnish and install a seamless, reinforced
More informationMoisture and Mold Control
Moisture and Mold Control Introduction The key to mold control is moisture control, according to the EPA (U.S. Environmental Protection Agency). Mold spores are all around us in the air, they float through
More informationSCOPE OF WORK PROJECT IDENTIFICATION
PROJECT IDENTIFICATION SCOPE OF WORK PROJECT NAME: Wickenburg High School PROJECT: Gym Roof 1 SITE ADDRESS: 1090 S. Vulture Mine Rd. Wickenburg AZ 85390 City State ZIP Code SCOPE OF WORK SUMMARY: 1. Extend
More informationURETHANE. CONCRETE ROOF WATERPROOFING SYSTEM Sample Design Guideline
1 DG0049-A 052017 CONCRETE ROOF WATERPROOFING SYSTEM Sample Design Guideline URETHANE ITW POLYMERS SEALANTS NORTH AMERICA, INC. 111 S. Nursery Road. Irving, TX 75060 Tel: 972-438-9111 Fax: 972-554-3939
More informationSITE AND BUILDING INSPECTION CHECKLIST
PARISH BUILDING Page 1 of 6 SITE AND GROUNDS DATE INIT COMMENTS DATE INIT COMMENTS Ramps & Provisions for Handicap Designated parking spaces for Handicap Has soil dropped or heaved Is there standing water
More informationADDENDA #3- RFP Sylvania CC building Re-Roof Progressive Design Build for Sylvania Campus CC Building Re-Roof Services
ADDENDA #3- RFP Sylvania CC building Re-Roof Progressive Design Build for Sylvania Campus CC Building Re-Roof Services Addenda Dated: 01/16/2018 PURPOSE: The purpose of this Addenda #3 is to provide a
More informationRoof Inspection Report
Roof Inspection Report Lewis & Clark Middle School Bellevue, NE Roof Inspection Report Prepared for: Prepared by: Mr. Greg Boettger Roofing Solutions, Inc. Bellevue Schools 6728 W. 153 rd Street & Overland
More informationSECTION METAL ROOF AND SOFFIT PANELS
Metal Panel Systems, Inc. 11506 Reading Road Cincinnati, Ohio 45241-2512 Telephone: 800-554-6126 or 513-554-6120 Fax: 513-554-6121 www.metalpanelsystems.com info@metalpanelsystems.com Specifications for
More informationRECEIVE A RADICAL COMPREHENSIVE COMMERCIAL ROOF INSPECTION & DETAILED REPORT
RECEIVE A RADICAL COMPREHENSIVE COMMERCIAL ROOF INSPECTION & DETAILED REPORT Keeping moisture out of buildings since 1987 If you want something to perform, you have to maintain it. After all, you wouldn
More informationCERVANTES COMMUNITY CENTER RE-ROOFING NEW MEXICO STATE UNIVERSITY
420 CENTER DR,, NM 95% CD SUBMITTAL DRAWING INDEX TITLE SHEET T1.1 PROJECT DATA, VICINITY MAP, INDEX ARCHITECTURAL DEMOLITION FLOOR, CEILING & ROOF PLANS FLOOR & CEILING PLAN & ROOF PLAN MECHANICAL M1.0
More informationMAGNUM. I N S P E C T I O N S Inc. ROOF Walked on roof, crawled attic where accessible.
NAME: DATE: October 6, 2006 METHOD OF INSPECTION: ROOF Walked on roof, crawled attic where accessible. ADDRESS: MAIN ROOF COVERING SECONDARY ROOF COVERING Cement Tile: Strip Shingle: XX Tar and Gravel:
More informationCARLISLE OWNER S MANUAL
CARLISLE OWNER S MANUAL Table of Contents Revisions and Alterations Procedure.................................................. Care and Maintenance Information...................................................
More informationSOLAR COATING SYSTEMS ACRYLIC RENOVATION ROOF 4.5. Specification for Built-Up Roofing SUMMARY
SOLAR COATING SYSTEMS ACRYLIC ROOF RENOVATION 4.5 Specification for Built-Up Roofing 07590 PART 1. GENERAL 1.01 SUMMARY NAME ADDRESS A. Furnish and install a seamless, waterproof spray applied elastomeric
More informationTuscaloosa Police Station
Tuscaloosa Police Station 3801 Trevor S Phillips Ave Tuscaloosa, AL 35401 Core Cut: Spray Foam Roof- ½ thick +- Single Ply Membrane Tapered EPS Insulation 2-6 Metal Deck PART 1 GENERAL 1.1 SCOPE OF WORK
More informationRoof Inspection Report
Roof Inspection Report Bellevue Elementary Papillion, NE Roof Inspection Report Prepared for: Prepared by: Mr. Greg Boettger Roofing Solutions, Inc. Bellevue Schools 6728 W. 153 rd Street & Overland Park,
More informationSUMMARY 1234 Main St.Loudon TN Buyer Name 08/28/2018 9:00AM
SUMMARY 1234 Main St.Loudon TN 37774 Buyer Name 08/28/2018 9:00AM Dusty Jameson TN Home Inspector License #00123, TN WDI License #104158 Inspector Cluseau's Home Inspection Service 865-691-6158 dustyjameson@gmail.com
More informationLiquid Membrane Systems Product Guide
Liquid Membrane Systems Product Guide About Armour Proof Coatings Primers, Sealers / Mastics Armour Proof Coatings uses over 3 decades of technology and 5 decades of roofing expertise to provide a solution
More informationDESIGN GUIDELINE FLUID-APPLIED WATERPROOFING
DESIGN GUIDELINE FLUID-APPLIED WATERPROOFING (TO RESTORE SMOOTH MODIFIED BITUMEN/BUR ROOF SYSTEMS) PART 1 GENERAL 1.01 DESCRIPTION A. The scope of this design guideline is to describe the installation
More informationROOF REPORT 3130 TCHULAHOMA
ROOF REPORT 3130 TCHULAHOMA MEMPHIS, TENNESSEE BUILDING OWNER: Memphis Shelby County Airport Authority BUILDING MANAGER: MSCAA SURVEY DATE: 6/12/17 BUILDING CONSTRUCTION COMPLETED: 1985 ROOF AREA (SF):
More informationReflectiClean Acrylic/Urethane
1 DG0009-J 08/2015 Metal Roof Restoration Sample Design Guidelines ReflectiClean Acrylic/Urethane ITW POLYMERS SEALANTS NORTH AMERICA, INC. 111 S. Nursery Road. Irving, TX 75060 Tel: 972-438-9111 Fax:
More informationERSYSTEMS OneStep Plus
1 DG0045-C 052017 CONCRETE ROOF WATERPROOFING SYSTEM Sample Design Guideline ERSYSTEMS OneStep Plus ITW POLYMERS SEALANTS NORTH AMERICA, INC. 111 S. Nursery Road. Irving, TX 75060 Tel: 972-438-9111 Fax:
More informationRoof Systems ROOFS. Inspections
ROOFS Roof Systems Since your roof is overhead, not easily accessible and tends to be out of sight, out of mind, it is particularly necessary to develop and follow a strategy and program for its inspection
More informationMargaret Batts Tobin Laboratory
Roof Evaluation of Margaret Batts Tobin Laboratory The University of Texas At San Antonio Performed for UTSA Zero/Six Consulting, LLC 8423 Stewart Road Galveston, Texas 77554 409 740 0090 voice Table of
More informationPOLYURETHANE FOAM SAMPLE DESIGN GUIDELINES URETHANE
1 DG0034-H 05/2017 POLYURETHANE FOAM SAMPLE DESIGN GUIDELINES URETHANE ITW POLYMERS SEALANTS NORTH AMERICA, INC. 111 S. Nursery Road. Irving, TX 75060 Tel: 972-438-9111 Fax: 972-554-3939 www.itwsealants.com
More informationSubject: Amphitheater School District Reroofing Projects Amphi High School, Building 900 Roof Evaluation SCI Project Number:
27 June 2016 Mr. Shane Chism, AIA Breckenridge Group 4625 E. Fort Lowell Road Tucson, Arizona 85712 Subject: Amphitheater School District Reroofing Projects Amphi High School, Building 900 Roof Evaluation
More informationG October 2018
G-13-18 VacuSeal TM Vent Secured Roofing Systems October 2018 The information contained in this supplement serves as a criteria for Specifiers and Authorized Applicators regarding the design and installation
More informationOREGON CONVENTION CENTER CHILLER PLANT RE-DESIGN CD SET
SECTION 07 54 19 - POLYVINYL-CHLORIDE (PVC) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division
More informationCMP WellRoof Brochure
CMP WellRoof Brochure (COMGN183) Updated: 3/16 I M YOUR GAF CMP Certified Maintenance Professional CONTRACTOR Your Very Best Choice For Your Commercial Roofing Maintenance Program FACT * Studies have shown
More informationRoof Inspection Report
Roof Inspection Report Arts Center Lawrence, KS Roof Inspection Report Prepared for: Prepared by: City of Lawrence Roofing Solutions, Inc. Mr. Jason Stowe 6728 W. 153 rd Street PO Box 708 Overland Park,
More informationRoof Inspection Report
Roof Inspection Report Bellevue School Transport Bellevue, NE Roof Inspection Report Prepared for: Prepared by: Mr. Greg Boettger Roofing Solutions, Inc. Bellevue Schools 6728 W. 153 rd Street & Overland
More informationCounty of Santa Barbara, California Facility Condition Assessment 2014
Project No.: P05000.001 Building Number: P05000 Lompoc VMB Grounds Project Description: Overlay, Seal Coat and Restripe Parking Lots Background: The asphalt paving comprises approximately 135,600 square
More informationField Planning and Data Collection Practices for Conducting Detailed Natural Hazard Vulnerability Assessments of Campus Structures
University of New Orleans ScholarWorks@UNO DRU Workshop 2013 Presentations Disaster Resistant University Workshop: Linking Mitigation and Resilience Conferences and Workshops 3-1-2013 Field Planning and
More informationG October 2018
G-14-18 October 2018 The information contained in this supplement serves as a criteria for Specifiers and Authorized Applicators regarding the design and installation of Carlisle Roofing Systems and use
More informationPOLYURETHANE FOAM SAMPLE DESIGN GUIDELINE ACRYLIC
1 DG0030-J 04/2017 POLYURETHANE FOAM SAMPLE DESIGN GUIDELINE ACRYLIC ITW POLYMERS SEALANTS NORTH AMERICA, INC. 111 S. Nursery Road. Irving, TX 75060 Tel: 972-438-9111 Fax: 972-554-3939 www.itwsealants.com
More informationDOCUMENT ADDENDUM NO. 1
DOCUMENT 00 91 01 ADDENDUM NO. 1 1. GENERAL This document includes requirements that clarify or supersede portions of the bid and/or contract requirements for the project. This Addendum is a Contract Document.
More informationROOFING SYSTEM WARRANTY. System Warranty Revisions & Alterations Procedure Care & Maintenance Instructions
ROOFING SYSTEM WARRANTY System Warranty Revisions & Alterations Procedure Care & Maintenance Instructions WARRANTY REVISIONS AND ALTERATIONS PROCEDURES Versico recommends periodic roof system evaluations
More informationA. Submit product data sheets and literature verifying fire ratings and physical properties of materials.
I. GENERAL ACRYSHIELD ROOF MANAGEMENT SYSTEM Installation Guide Specification For Preserving BUR & Mod Bit Roofs 07560 Saving Money, Safeguarding the Environment One Roof at a Time. 1.01 SUMMARY A. Provide
More informationDESIGN GUIDELINE FLUID-APPLIED WATERPROOFING
DESIGN GUIDELINE FLUID-APPLIED WATERPROOFING (TO RESTORE EPDM MEMBRANES) PART 1 GENERAL 1.01 DESCRIPTION A. The scope of this design guideline is to describe the installation of the ALDOCOAT Silicone reflective
More informationTELEPHONE: (215) Addendum No. 1
THE SCHOOL DISTRICT OF PHILADLPHIA SCHOOL REFORM COMMISSION Office of Capital Programs 440 North Broad Street, 3 rd Floor - Suite 371 Philadelphia, PA 19130 TELEPHONE: (215) 400-4730 Addendum No. 1 Subject:
More informationDESIGN GUIDELINE FLUID-APPLIED WATERPROOFING
DESIGN GUIDELINE FLUID-APPLIED WATERPROOFING (TO RESTORE SMOOTH MODIFIED BITUMEN/BUR) PART 1 GENERAL 1.01 DESCRIPTION A. The scope of this design guideline is to describe the installation of the ALDOCOAT
More informationLight-Metal Roof Edge, Raised
NAIL WOOD CANT TO BLOCKING 2 ROWS STAGGERED EACH ROW 24 O.C. 1/2 MIN. 10 0 MAX. FASTEN 18 O.C. WITH NEOPRENE GASKETED FASTENERS 3-1/2 MIN. 4 6 JOINT COVER PLATE SET IN TWO BEADS OF SEALANT 4 MIN. SPECIFIED
More informationSUMMARY 792 Youngfield Ct., Lakewood CO Frank Oz January 13, 2018
SUMMARY 792 Youngfield Ct., Lakewood CO 80228 Frank Oz January 13, 2018 Christopher Grabbe internachi Certified Professional Inspector FirePower Inspections 7204645889 info@firepowerinspections.com 2.1.1
More informationMaintaining Building Envelope Integrity. Is Your Leak REALLY a Roof Leak?
Maintaining Building Envelope Integrity Is Your Leak REALLY a Roof Leak? Learning Objectives: At the end of the program, participants will be able to: Recognize what is, and what is not, a roof leak. Identify
More informationERSYSTEMS ONESTEP PLUS
1 DG0032-G 04/2017 POLYURETHANE FOAM-AGED SAMPLE DESIGN GUIDELINE ERSYSTEMS ONESTEP PLUS ITW POLYMERS SEALANTS NORTH AMERICA, INC. 111 S. Nursery Road. Irving, TX 75060 Tel: 972-438-9111 Fax: 972-554-3939
More informationSchedule A Development Permit No Issued this 18 day of April, 2018
Schedule A Development Permit No. 001610 Issued this 18 day of April, 2018 N No. Revision/Issue Date MM/DD/YY 1 ISSUED FOR TENDER 10/26/17 LEGEND: WORK AREA VILLAGE STROLL VILLAGE GREEN SOUTH WING 1 0
More informationASHLEY AVE. PARKING GARAGE CHILLER TOWER ROOF REPAIRS
NORTH CHILLER TOWER ROOF R-00 COVER SHEET R-0 ROOF PLAN DRAWING INDEX VICINITY MAP SITE MAP ASHLEY AVE. PARKING GARAGE CHILLER TOWER ROOF REPAIRS 58 ASHLEY AVE. CHARLESTON, SC 90 STATE PROJECT NO. H5-D5
More informationSECTION B. Product Data: Provide manufacturer's standard details and installation instructions.
SECTION 07710 MANUFACTURED ROOF SPECIALTIES PART 1 GENERAL 1.1 SECTION INCLUDES A. Roof drains for new roofing. B. Roof drains for reroofing. C. Roof drains for retrofitting into existing roof drains.
More informationAqua Coast Engineering
Aqua Coast Engineering Ltd. P.O. Box 1367 Station A Delta, B.C. V4M 3Y8 Tel: (604)948-0958 Fax: 604)948-0959 September 1, 2011 Matthew Cheng File#:11145 Matthew Cheng Architect Inc. Fax: 604-731-3908 Unit
More informationDUKE UNIVERSITY CONSTRUCTION STANDARDS
1 07 40 00 Roofing 1. General Several factors repeatedly show up during the inspection of roofs that have failed prematurely. They include inappropriate use of materials, poor drainage systems, poor details
More informationFundamentals of Insulated Panel Installation. MBCEA 2016 Clearwater, FL
Fundamentals of Insulated Panel Installation MBCEA 2016 Clearwater, FL Fundamentals of Insulated Panel Installation Industrial Roof & Walls Not Architectural Not Cold Storage Topics Preparation Installation
More informationDistributed by: BEST MATERIALS Ph: , Fax:
ChemCurbs can eliminate the number one cause of roof leaks. Properly Installed ChemCurb Penetration Seals fillers shrink and then leak, allowing water to penetrate and enter the building. These pitchpans
More informationOutline NBS Specification. Protec System to Felt (Waterproofing Only)
Outline NBS Specification Protec System to Felt (Waterproofing Only) This document is a guide to assist in the production of tender documents only and is not project specific. A site survey is always recommended.
More information1.2 DEFINITIONS, REFERENCES, AND OVERALL STANDARDS Follow 07500
07721 ROOF ASSEMBLY SUPPORTS FOR ROOFTOP EQUIPMENT ****************************************** SPECIFIER: All roof-related items above or outside the structural roof deck, including such work as blocking,
More informationCoating over Metal Roof: 5-Year System
Coating over Metal Roof: 5-Year System Acrylic White 1.5 gallons/sq 1.5 x SQs = Gallons Acrylic Gel Always consult your Metacrylics rep or contact Metacrylics for full system specifications. 1. Wire brush
More informationASTEC Re-Ply Roof System for ASPHALT & MODIFIED BITUMEN ROOFS
ASTEC Re-Ply Roof System for ASPHALT & MODIFIED BITUMEN ROOFS Re-Ply Roofing Systems Application Specification # AC - 2010-A & MB PART I GENERAL 1.01 DESCRIPTION A. This guideline specification includes
More informationOwners of Strata #2720 c/o
667 Beaver Lake Rd. (250) 479-8050 Victoria BC V8Z-5N9 June 29, 2009 Owners of Strata #2720 c/o Roger Taylor #417 545 Manchester Rd. Victoria, BC Attention: Roger Taylor Dear: Owners of Strata #2720, Re:
More information2017 FRENGER FOOD COURT ROOFING PROJECT
For: Facilities and Services, NMSU Main Campus, New Mexico State University, Las Cruces, NM : 10/18/2017 - SD & DD REVIEW PACKAGE - NOT FOR CONSTRUCTION CONSULTANTS: ARCHITECT: PROJECT SITE: PROJECT LOCATION:
More informationINSPECTION TIMING CHECKLIST FOR RESIDENTIAL FRAME BUILDING PRIOR TO INSPECTION REQUEST
Village of Vernon Hills Community Development Department - Building Division 290 Evergreen Drive, Vernon Hills, IL 60061 Phone 847-367-3704 - Fax 847-367-2541 - http://www.vernonhills.org INSPECTION TIMING
More informationMAKE ROOFS LAST LONGER
MAKE ROOFS LAST LONGER Roof Coatings & Roof Repair Single-Ply Metal Asphalt HIGHEST PERFORMING SYSTEMS. LOWEST APPLIED COST. METAL ROOF RESTORATION Metal Restoration Quick Guide Acrylic Polyurethane High
More informationAsphaltic Accessories Brochure
Asphaltic Accessories Brochure Updated: 5/12 www.gaf.com A sphaltic ccessories www.gaf.com M-WeLd Pre-FLashed accessories M-Weld accessories complement GAF asphaltic roofing systems. They are available
More informationCommercial Roof Cover Maintenance and Repair Risk Engineering Your Business Insurance Specialists
Commercial Roof Cover Maintenance and Repair Risk Engineering Your Business Insurance Specialists With information provided by the Insurance Institute for Business & Home Safety Protection from the top
More informationADDENDA #5- RFP Sylvania CC building Re-Roof Progressive Design Build for Sylvania Campus CC Building Re-Roof Services
ADDENDA #5- RFP Sylvania CC building Re-Roof Progressive Design Build for Sylvania Campus CC Building Re-Roof Services Addenda Dated: 01/16/2018 PURPOSE: The purpose of this Addenda #5 is to provide a
More informationCHECKLIST Inspecting a Garage
CHECKLIST Inspecting a Garage By Ben Gromicko This section deals with the details of the garage or carport inspection that may be performed. At the end of this section, you shall be able to: describe the
More informationRe-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY
Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded
More informationNational Property Inspections
Monday, August 22, 2011 Inspector Joe Smith 548-254-3658 Page 1 of 33 GENERAL INFORMATION GENERAL CONDITIONS AT TIME OF INSPECTION : No Property Occupied : Property Faces : North South East þ West Year(s)
More informationRoof Replacement. Notes: T-1 (Title Page) 709 Bull Street Columbia, South Carolina. University of South Carolina. Callcott Social Science
Notes: Drawing Index T-1 Title R-1 Roof Plan - Existing Conditions R-2 Roof Plan - New D-1 Roof Details D-2 Roof Details S1.0 Safety Anchor Plan Building 709 Bull Street Columbia, 1 10/13 T-1 (Title Page)
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 077200 - ROOF ACCESSORIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationRoof Inspection Report
Roof Inspection Report Lied Activity Center Bellevue, NE Roof Inspection Report Prepared for: Prepared by: Mr. Greg Boettger Roofing Solutions, Inc. Bellevue Schools 6728 W. 153 rd Street & Overland Park,
More informationA. Submit product data sheets and literature verifying physical properties of materials.
I. GENERAL ACRYSHIELD ROOF MANAGEMENT SYSTEM Installation Guide Specification For Preserving EPDM Roofs 07500 Saving Money, Safeguarding the Environment One Roof at a Time. 1.01 SUMMARY A. Provide labor,
More information