GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: FQP PILE CONSTRUCTION

Size: px
Start display at page:

Download "GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: FQP PILE CONSTRUCTION"

Transcription

1 GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: FQP PILE CONSTRUCTION /C/FQP PILE/R0 DT. 15/03/2008

2 SECTION : Foundation Materials 1. CHECKING OF FOUNDATION MATERIALS A) CEMENT i) Fitness One sample IS:456, IS:4031, IS:269, Manufacturer/ Review of B ii) Compressive Strength per lot of IS:8112, IS:12269 / manufacturers iii) Initial & final setting time 100 MT or part IS:1489 & approved lab test certificates iv) Soundness thereof from specification. (MTCs) and v) Heat of Hydration for low each source laboratory test heat cement (Not Applicable for MTC's and results by for OPC & PPC) one sample per lot of 200 MT or part thereof from each source for site testing. vi) Chemical Composition of One sample per IS:456, IS:4031, IS:269 Manufacturer Review of B Cement lot of 100 MT IS:8112, IS:12269 manufacturers or part thereof IS:1489 & test certificates from each specification. by source for MTCs. B) COARSE AGGREGATES i) Determination of Particle One sample IS:383, IS:2386 Each source to be B size (Sieve Analysis) per lot of and approved lab. ii) Flakiness Index 200 cubic meter specification. Review and iii) Crushing Value or part thereof acceptance of iv) Specific Gravity* from each test result by v) Bulk Density* source for each vi) Absorption Value* size vii) Moisture Content* viii) ix) Soundness of Aggregate** Presence of deleterious materials * Applicable to design mix concretes only. ** Applicable to concrete work subject to frost action. PAGE-1

3 Section : Foundation Materials C. FINE AGGREGATE i) Gradation : Determination One sample IS:383, IS;4031, IS:2386, Each source to B of Particle size per lot of 200 IS:236, IS:456 and approved lab be approved by (Sieve Analysis) cubic meter or specification. ii) Specificy Gravity and density* part thereof Review and iii) Moisture content* from each acceptance of iv) Absorption Value* source test result by v) Bulking* vi) vii) Silt Content Test Presence of deleterious materials D) WATER i) Cleanliness 100% IS:456, IS:3205 and Contractor Each source C (Visual ) specification. to be approved The water used for mixing by concrete shall be fresh, clean and free from oil, acids and alkalies, organic materials, or other deleterious materials ii) Suitablity of water for One sample per specificaiton Contractor Certification B RCC work source Potable water is generally regarding suitably for concreting. potability of water by contractor and approval by RCC work iii) P.H Value One sample per IS : 456, IS : 3025 and Approval by B source specification approved lab Min. 6 Contactor Max. 8 * Applicable to design mix concretes only. ** Applicable to concrete work subject to frost action. PAGE-2

4 Section : Foundation Materials E. REINFORCEMENT STEEL i) Identication & size Random IS:432, IS:1139, IS:1786 & Contractor Approval by B specification ii) Chemical Analysis Test One sample per IS:432, IS:1139, IS:1786 & Manufacturer Review of B heat specification manufacturers test certifcates by iii) Tensile Test One sample per IS:432, IS:1139, IS:1786 & Manufacturer Review of B iv) Yield Stress/ proof stress lot of 40 MT specification manufacturers v) Percentage Elongation or part thereof test certifcates for each size as well as lab by of steel confirming to IS:1139 and 5 MT or part thereof for HDS wire for each size of steel as per IS:432. For steel as per IS:1786 under 10 mm 1 sample for each 25 MT or part thereof. 10mm - 16 mm 1 sample for each 35 MT or part thereof. Over 16 mm 1 sample for each 45 MT or prt thereof. vi) Bend/ Rebend Test One sample per IS:432, IS:1139, IS:1786 Manufacturers Review of B lot of 20 MT or specification manufacturers part thereof for Approved lab test certificates as well as lab PAGE-3

5 Section : Foundation Materials each size of steel as per IS:432/ IS:1139. For steel as per IS:1786 under 10mm. 1 sample for each 25 MT or part thereof. 10 mm - 16mm. 1sample for each 35 MT or part thereof. Over 16 mm. 1 sample for each 45 MT or part thereof. test result by vii) Reverse Bend Test or HDS wire One sample per IS:432 Manufacturer/ Review of B lot of 5 MT specification manufacturers or part thereof approved lab. test certificates for each size. as well as lab test result by. PAGE-4

6 Section : Foundation ] 2. FOUNDATION A) EARTHWORK (EXCAVATION) i) Initial ground level, depth of Each pipe approved Joint Approval by B xcavation, final bed level. drawings/ specification Inspection by & Contractor ii) Dimension of Excavated PIT Each pile approved Joint Approval by B drawings/specification Inspection by & Contractor iii) Side slopes during excavation Each pile As per Site working Joint Approval by C final bed level condition Inspection by & Contractor iv) Nature of soil/rock Each pile specification -do- -do- B B. STUB & TEMPLATE (Applicable only if it is in the scope of pile foundation contractor) i) Identification & Assembly 100% on approved Joint Approval/ B each location drawings/specifications Inspection by clearance & contractor ii) Template level, width & 100% on approved Joint Approval/ B diagonal each location drawings/specifications Inspection clearance by and contractor iii) Tightening of all bolts & 100% on approved Joint Approval/ C nuts of template, stub & cleats each location drawings/specifications Inspection by clearance by & by contractor PAGE-5

7 Section : FOUNDATION iv) Stub setting 100% on approved Joint Approval/ B each location drawings/specifications Inspection by clearance by b y C) P.C.C. Padding For all locations IS:456 and Joint Approval by B approved foundation Inspection by drawings & specification D) STAGING FOR RAISED CHIMNEY i) durability, strength & 100% Joint Approval by B soundness of staging, joints specification Inspection by adequacy of its joints & specific levels E) SHUTTERING (Formwork) i) for materials, 100% Joint Approval by C breakage or damage specification/approved Inspection by drawings ii) for plumb alignment, 100% before Joint Approval by B parallelism, squareness and casting specification/approved Inspection by equidistance from stub. drawings iii) Dimensional check 100% before Joint Approval by B casting specification/approved Inspection by drawings iv) for level & height 100% before Joint Approval by B casting specification/approved Inspection by drawings v) for rigidity of frame/ 100% Joint Approval by C tightness specification/approved Inspection by drawings PAGE-6

8 Section : Foundation vi) Cleaning and oiling 100% Joint Approval by C approved specification / Inspection by drawings and contractor vii) Diagonal bracing if required 100% Joint Approval by C as per drawings /site approved specification / Inspection by conditions drawings viii) ing of joints to avoid 100% Joint Approval by C undue loss of cement specification/approved Inspection by slurry drawings F. PLACEMENT OF REINFORCEMENT STEEL i) the steel bars for 100% IS:456 and Joint Approval by C rust, cracks, surface flaws, Specification/approved Inspection by laminate etc. (Visual check) drawings ii) as per the bar bending For all IS:456 and Joint Approval by B schedule before placement locations Specification/approved Inspection by of concrete drawings iii) cutting tolerance for For all IS:456 and Joint Approval by B bars as per check list/ locations Specification/approved Inspection by drawings. drawings whether all the bent bars and lap lengths are as per approved bar bending schedule iv) whether all joints 100% IS:456 and Joint Approval by C & crossing of bars are tied Specification/approved Inspection by properly with right guage drawings & annealed wire as per specification PAGE-7

9 Section : Foundation v) for proper cover 100% IS:456 and Joint Approval by C distance, spacing of bars, Specification/approved Inspection by spacers & chairs after the drawings reinforcement cage has been put inside the formwork. vi) whether lapping of 100% IS:456 and Joint Approval by B bars are tied properly with Specification/approved Inspection by right guage and annealed drawings wire as per specification. G. PILE FOUNDATION (additional Tests) i) ing of centre line of Each pile group IS:2911 & Joint list to be B pile group approved pile foundation Inspection by prepared and drawings/specification. signed jointly ii) pile location Each pile IS:2911 & Joint list to be B approved pile foundation Inspection by prepared and drawings/specification. signed jointly iii) Temporary casing tube & Each pile IS:2911 & Joint Verticality of the B permanent liner also check approved pile foundation Inspection by tube to be thickness of liner material drawings/specification. checked (if applicable) iv) Bentonite slurry Each pile IS:2911 & Joint Records to be B (if applicable) approved pile foundation Inspection by kept by drawings/specification. for specific gravity of slurry v) Pile depth, level, size and Each pile IS:2911 & Joint Approval by A alignment approved pile foundation Inspection by drawings/specification. PAGE-8

10 Section : Foundation vi) Chipping of pile head Each pile IS:2911 & Joint Before concreting B approved pile foundation Inspection by pile cap, pile head drawings/specification. to be chipped off for concreting vii) Standard Penetration Test As per IS:2911 & Joint Records to be B approved pile foundation Inspection by kept by BOQ/ drawings/specification.. specification Approval by viii) Pile load testing As per IS:2911 & Joint Records to be B approved pile foundation Inspection by kept by BOQ/ drawings/specification.. specification Approval by ix) Anchor bolts if applicable a) Level,, centre to centre 100% on each Joint list to be B distance of bolts location approved pile foundation Inspection by prepared and drawings/specification. signed jointly b) Visual check for galvanising 100% on each Joint list to be B location approved pile foundation Inspection by prepared and drawings/specification. signed jointly 3) CONCRETING A) BATCHING, MIXING & 100% IS:456 and Joint Approval by B PLACING OF CONRETE approved drawings and Inspection by AND COMPACTING specifications. B) FIXING OF CHIMNEY 100% IS:456 and Joint Approval by C COLUMN approved drawings and Inspection by for Width/length, specifications. squareness, parallelism & equidistance from stub PAGE-9

11 Section : Foundation C) PLACING CONCRETE, 100% IS:456 and Joint Min. gap between C POKING AND approved drawings and Inspection by boxes and reinfor- COMPACTING specification. cement bars should be maintained. Approval by D) CONCRETE TESTING i) Slump Test One sample per IS:456, IS:516, IS:1199 Contractor Approval by B location and specification. ii) for quantities for 100% on all IS:456, IS:516, IS:1199 Contractor list to be B cement, fine aggregate, locations and prepared and coarse aggregate and water specification. signed jointly while batching E) CHECK FINISHING, 100% IS:456, IS:516, IS:1199 Contractor Approval by B DIMENSIONAL and CONFORMITY AND specification WORKMANSHIP BEFORE & AFTER BOX REMOVAL F) BACKFILLING 100% Contractor Approval by C i) for thickness of specification layer & watering ii) for compaction/ ramming G) COPING 100% on all Contractor Approval by B location Specification H) CURING 100% on all Contractor Approval by C location Specification I) EARTHING 100% IS:5613 and Contractor Approval by B (Pipe or counter poise type) Specification PAGE-10

12 Section : Foundation J) CONCRETE CUBE TESTING i) Compressive Strength a) One sample IS:1199, IS:456, IS:516 Approval by A for each and approved lab locations (One Specification Cubes must be sample consists tested within a of min. 3 test week after 28 cubes for 28 days curing days strength) period and test b) For pile results should be foundation one approved before sample for tower erection. each pile. ii) Compressive Strength for One sample for IS:1199, IS:456, IS:516 - DO - A concrete of pile cap, beams, every 20 Cum and approved lab chimney etc. of concrete or Specification part thereof for each days of concreting PAGE-11

13 Section : GENERAL GUIDELINES FOR IMPLEMENTATION 1. Details of categories of check codes A, B & C including accepting and deviation dispositioning authorities are indicated at Annexure-I. 2. specification shall mean technical specification, approved drawings/data sheets and A/T provisions applicable for the specific contract. 3. Acceptance criteria and permissible limits for certain tests are indicated at Annexure-II. For balance tests, site to verify the same with respect to specification, relevant Indian Standards and/or prevalent code of practice. 4. It is clarified that the tests indicated at column 2 of this FQP i.e. against column "Component operation & Description of Test," are only generally required to be conducted. However, reserves the right to carry-out any additional tests at any stage if the situation so warrants. 5. site representative shall witness all the tests conducted by the contractor as mentioned in this FQP. However, in case of tests conducted in the approved lab, it is preferred to witness the tests in the lab itself, if possible. 6. Head of Construction Division shall approve testing laboratory before accepting the test results from the lab. 7. Head of Construction Division shall approve the sources for cement, coarse aggregate, fine aggregate & water before actual utilisation. 8. All the testing & measuring equipments used by the contractor for testing are required to be calibrated. A copy of valid calibration report shall be retained by as records. 9. Classification of foundations shall be approved by based on the Joint Inspection Report & soil investigation reports. 10. Curing of concrete work should be continued for a minimum period of 10 days. 11. Zone-IV fine aggregate shall not be used for concreting work. PAGE-12

14 Section : GENERAL GUIDELINES FOR IMPLEMENTATION 12. CEMENT 12.1 In case supply of cement is in the scope of the contractor, the same shall be procured from sources approved by site and got tested at site on sample basis for specified acceptance tests as specified in this FQP at a reputed Third Party Lab approved by site The samples of cement for site testing shall be taken within three weeks of the delivery and all the tests shall be commenced within one week of sampling. 13. REINFORCEMENT STEEL 13.1 In case supply of reinforcement steel is in the scope of the contractor, the same shall be procured from the main producers i.e. SAIL, TISCO, IISCO or Rashtriya Ispat Nigam or the rerollers approved by main producers. The reinforcement steel shall be got tested at site on sample basis for specified acceptance tests as specified in this FQP at a reputed Third Party Lab approved by site The results of the testing of cement and reinforcement steel referred to in 13.1 and 14.1 above shall be got approved from site before cement and reinforcement steel are put to use. However, in exceptional cases due to exigencies of work., site may authorise the contractor to use Cement and Reinforcement Steel even before the test results are received. However, in all such cases, if the test results subsequently received are found to be not complying with the specified acceptance criteria, the contractor shall have to dismantle and recast all such foundations cast with such non-conforming materials at his own cost. Confirmation to this effect shall be obtained from the contractor by the Project authorities beforehand in all such cases. PAGE-13

15 ANNEXURE - I ACCEPTING AND DEVIATION DISPOSITIONG AUTHORITIES FOR DIFFERENT CATEGORIES OF CHECKS AS ENVISAGED IN FIELD QUALITY PLAN C ATEGORY TYPE OF 100% COUNTER CHECK/ ACCEPTING AUTHORITY, DEVIATION C H E C K CHECKING/ S U RVEILLANCE IF TEST RESULTS DISPOSITIONING WITNESSING BY CHECK BY ARE WITHIN AUTHORITY PERMISSIBLE LIMITS À' CRITICAL CONSTRUCTION CONSTRUCTION EE CONST. DN. SE(CIVIL) S/DN. DN. B' MAJOR CONSTRUCTION CONSTRUCTION EE CONST. DN. SE(CIVIL) S/DN. DN. `C' MINOR CONTRACTO R S CONSTRUCTION CONSTRUCTION DN. EE CONST. DN. RESENTATIVE S/DN. PAGE-14

16 ANNEXURE - II ACCEPTANCE CRITERIA AND PERMISSIBLE LIMITS FOR FOUNDATION MATERIALS & CONCRETE A) CEMENT : Description of the 33 Grade OPC 43 Grade PPC as per Low Heat tests as per IS:269 cement as IS:1489 Cement per IS:8112 (i) Fineness (Min.) 225 m 2 /kg 225 m 2 /kg 300 m 2 /kg 225 m 2 /kg (i) (ii) (iv) Compressive Strength (Min.) hours 160 kgf/cm 2 23 MPa 16 MPa 100 kgf/cm hours 220 kgf/cm 2 33 MPa 22 MPa 160 kgf/cm hours - 43 MPa 33 MPa 350 kgf/cm 2 Initial Setting Time (Minimum) 30 Minutes 30 Minutes 30 Minutes 30 Minutes Final Setting Time (Maximum) 600 Minutes 600 Minutes 600 Minutes 600 Minutes (v) Soundness Maximu m Maximu m Maximu m Maximu m (Le chatelier Method) 10mm 10mm 10mm 10mm expansion expansion expansion expansion (vi) Heat of hydration -- - Max. 65 cal/ (Max.) gm for 7 days & max. 75 cal/gm for 28 days (vi) Chemical Composition As per IS As per IS As per IS As per IS B) C OARSE AG G R E G ATE : (i) Sieve Analysis IS SIEVE DESIGNATION PERCENTAGE PASSING FOR GRADED AG G R E G ATE OF NOMINAL SIZE 40 mm 20 mm 40 mm 95 to mm 30 to to mm 10 to to mm 0 to 5 0 to 10 PAGE 1 OF 3 PAGE-15

17 ANNEXURE - II (i) Flakiness Index Not to exceed 25%. (ii) Crushing Value Not to exceed 45%. (iv) Soundness of aggregate Loss of weight after 5 cycle not to exceed 12% when tested with applicable for concrete works Sodium sulphate and 18% when tested with magnesium sulphate. subject to froast action (v) Deleterious material Not to exceed 5% of the weight of aggregate. (C) FINE AGGREGATE (i) Sieve Analysis Shall confirm to Zone I, Zone II or Zone III. IS Sieve designation Percentage Passing for Grading Grading Grading Grading Zone-I Zone-II Zone-III Zone-IV 10 mm mm mm mm Micron Micron Micron (i) For guidance of adjusting the quantity in mix of concrete, the following table may be used. Moisture Content % Bulking % by volume (ii) Silt content Test : Shall not exceed 8%. (iv) Deleterious Materials : Total deleterious material shall not be more than 5% by weight. (D) REINFORCEMENT STEEL : As per relevant Indian Standards PAGE-16 PAGE 2 OF 3

18 ANNEXURE - II (E) CONCRETE CUBE TEST For nominal (volumetric) concrete mixes, compressive strength for 1:1½:3 (cement : sand : Coarse aggregate) concrete shall be 265 kg/cm 2 for 28 days and for 1:2:4 nominal mix, it shall be 210kg/cm 2. (F) ACCEPTANCE CRITERIA BASED ON 28 DAYS COMPRESSIVE STRENGTH FOR NOMINAL MIX CONCRETE a) The average of the strength of three specimen be accepted as the compressive strength of the concrete, provided the strength of any individual cube shall neither be less than 70% nor higher than 130% of the specified strength. b) If the actual average strength of accepted sample exceeds specified strength by more than 30%, the Engineer-in-charge, if he so desires, may further investigate the matter. However, if the strength of any individual cube exceeds more than 30% of specified strength, it will be restricted to 30% only for computation of strength. c) If the actual average strength of accepted sample is equal to or higher than specified strength upto 30%, then strength of the concrete shall be considered in order and the concrete shall be accepted at ful rates. d) If the actual average strength of accepted sample is less than specified strength but not less than 70% of the specified strength, the concrete may be accepted at reduced rate at the discretion of Engineer-in-Charge. e) If the actual average strength of accepted sample is less than 70% of specified strength, the Engineerin-Charge shall reject the defective portion of work represented by sample and nothing shall be paid for the rejected work. Remedial measures necessary to retain the structure shall be taken at the risk and cost of contractor. If, however, the Engineer-in-Charge so desires, he may order additional tests to be carried out to ascertain if the structure can be retained. All the charges in connection with these additional tests shall be borne by the Contractor. (G) ACCEPTANCE CRITERIA FOR DESIGN MIX CONCRETE SHALL BE AS PER IS:456 PAGE 3 OF 3 PAGE-17

SPECIFICATION FOR REINFORCED SOIL WALL

SPECIFICATION FOR REINFORCED SOIL WALL SPECIFICATION FOR REINFORCED SOIL WALL 1.0 EXTENT OF WORK The work shall consist of Reinforced Soil walls built in accordance with this specification and in conformity with the lines, levels and details

More information

Pradhan Mantri Gram Sadak Yojana. Quality Control Register Part 1 FOR CC WORK

Pradhan Mantri Gram Sadak Yojana. Quality Control Register Part 1 FOR CC WORK Pradhan Mantri Gram Sadak Yojana Quality Control Register Part 1 FOR CC WORK Record of Tests State : Madhya Pradesh District : Programme Implementation Unit : Package Number MP- Name of Road Register From

More information

PROGRESS REPORT CGEWHO CHENNAI PHASE-III PROJECT

PROGRESS REPORT CGEWHO CHENNAI PHASE-III PROJECT 30.09.2018 A1 BLOCK Earth work excavation for Pile Cap works 75% completed. Plain Cement Concrete (PCC) For Pile Cap work 50% completed. Pile Chipping Work 50% Completed. A2 BLOCK Earth work excavation

More information

STANDARD SPECIFICATION FOR TANK PADS

STANDARD SPECIFICATION FOR TANK PADS STANDARD SPECIFICATION FOR TANK PADS STANDARD SPECIFICATION FOR TANK PADS 0.0 SCOPE The specification describes the technical requirements for the materials and construction of tank pads of murrum fill

More information

Drainage, Road Drainage and Collection Pit A - EXCAVATION:

Drainage, Road Drainage and Collection Pit A - EXCAVATION: 57 Drainage, Road Drainage and Collection Pit SCHEDULE OF QUANTITY Sl.N o. 1 Particulars Qty Unit Rate Amount A - EXCAVATION: Earth work in EXCAVATION IN FOUNDATION TRENCHES IN ALL KIND OF SOIL including

More information

Raicon Labs Pvt. Ltd., Plot No. 140, HSIIDC, Rai Industrial Area, Sonepat, Haryana. Discipline Mechanical Testing Issue Date

Raicon Labs Pvt. Ltd., Plot No. 140, HSIIDC, Rai Industrial Area, Sonepat, Haryana. Discipline Mechanical Testing Issue Date Last Amended on - Page 1 of 9 I. BUILDING MATERIALS 1. Cement Fineness by Blain Air Permeability IS 4031 (Part 2): 1999 (RA 2013) 100 m 2/ kg to 500 m 2/ kg Consistency IS 4031 (Part 4): 1988 (RA 2014)

More information

PROGRESS REPORT CGEWHO CHENNAI PHASE-III PROJECT

PROGRESS REPORT CGEWHO CHENNAI PHASE-III PROJECT 30.06.2018 A1 BLOCK Earth work excavation for Pile Cap works on progress. A2 BLOCK Earth work excavation for Pile Cap works on progress. B1 BLOCK Pile cap casting 100% completed. Columns up to stilt 100%

More information

SECTION CAST-IN-PLACE CONCRETE

SECTION CAST-IN-PLACE CONCRETE SECTION 03300 CAST-IN-PLACE CONCRETE PART 1 GENERAL 1.01 SECTION INCLUDES A. The Contractor shall furnish all work and materials, including cement, sand and coarse aggregate, water, admixtures, curing

More information

REINFORCED CONCRETE MASONRY SECTION

REINFORCED CONCRETE MASONRY SECTION SECTION 04 22 02 - REINFORCED CONCRETE MASONRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Checklist for Ready Mix Concrete Supply of Concrete (RMC)

Checklist for Ready Mix Concrete Supply of Concrete (RMC) C.A.01/CIDCO/SE(KHR)/EE(KHR-I)/2010 11 Pg. 568 Checklist for Ready Mix Concrete Supply of Concrete (RMC) Name of Work : C.A. : Name of Contractor/Client : 1. Name of RMC manufacturer with plant address

More information

CONCRETE WORK CONCRETE WORK. Underground Electric Distribution Standards I. SCOPE APPLICABLE STANDARDS

CONCRETE WORK CONCRETE WORK. Underground Electric Distribution Standards I. SCOPE APPLICABLE STANDARDS Underground Electric Distribution Standards I. SCOPE This section includes the standards for concrete, reinforcing steel, formwork, concrete placement, curing, and construction joints. Concrete work for

More information

CHAPTER 16 - GANTRIES

CHAPTER 16 - GANTRIES CHAPTER 16 - GANTRIES DS Temple 16.1 SCOPE This section covers the inspection of Sign Gantries as specified in the applicable chapter of the Specifications. It also covers the special attention which must

More information

Bhumi Research Centre (Civil Engineering Testing Laboratory), 2/1362, 'Bhumi House', Sagrampura, Ring Road, Surat, Gujarat

Bhumi Research Centre (Civil Engineering Testing Laboratory), 2/1362, 'Bhumi House', Sagrampura, Ring Road, Surat, Gujarat Bhumi Research Centre (Civil Engineering Testing ), Last Amended on - Page 1 of 6 AT LABORATORY I. SOIL & ROCK 1. Soil Grain Size Analysis IS 2720 (Part 4): 1985 Rev. 2, (RA 2007) Hydrometer Analysis IS

More information

SPECIAL SPECIFICATION 4491 Type CAC Concrete

SPECIAL SPECIFICATION 4491 Type CAC Concrete 2004 Specifications SPECIAL SPECIFICATION 4491 Type CAC Concrete 1. Description. Remove unsound concrete and replace with Type CAC, calcium aluminate concrete for ultra high early strength concrete repairs.

More information

Geotech Services, X-18, MIDC, Hingna, Nagpur, Maharashtra. Discipline Mechanical Testing Issue Date

Geotech Services, X-18, MIDC, Hingna, Nagpur, Maharashtra. Discipline Mechanical Testing Issue Date Last Amended on 11.01.2014 Page 1 of 14 I. BUILDING MATERIALS 1. Soil / Rock Plate Load Test IS 1888 1982 (Reaffirmed-2007) Cyclic Plate Load Test IS 5249 1992 Clause 6 (Reaffirmed-2010) Load Test On In-Situ

More information

Quality Control Register Part 1 (Building Work)

Quality Control Register Part 1 (Building Work) KARNATAKA RURAL INFRASTRUCTURE DEVELOPMENT LIMITED (FORMERLY KARNATAKA LAND ARMY CORPORATION LIMITED) GRAMEENABHIVRUDDHI BHAVANA, 4th & 5th FLOOR, ANAND RAO CIRCLE BANGALORE-9 Quality Control Register

More information

ITEM 432 RIPRAP. Dry Riprap is defined as Stone Riprap of the required type with voids filled only with spalls or small stones.

ITEM 432 RIPRAP. Dry Riprap is defined as Stone Riprap of the required type with voids filled only with spalls or small stones. ITEM 432 RIPRAP 432.1. Description. This Item shall govern for the furnishing and placing of riprap of the type and details shown on the plans and in accordance with this Item. 432.2. General. Riprap furnished

More information

1. Cast-in-place concrete is specified in Section

1. Cast-in-place concrete is specified in Section SECTION 03 38 00 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section describes the requirements for furnishing and installing post-tensioned slabs, jacks, jacking and anchors at Parking Structure, and record

More information

Stanford University Facilities Design Guidelines SECTION ASPHALT UNIT PAVING. A. ASTM C-33 Standard Specification for Concrete Aggregates.

Stanford University Facilities Design Guidelines SECTION ASPHALT UNIT PAVING. A. ASTM C-33 Standard Specification for Concrete Aggregates. SECTION 32 14 23 ASPHALT UNIT PAVING PART 1 GENERAL 1.1 DESCRIPTION Work Included: All labor, materials, appliances, tools, equipment, facilities, transportation, and services for and incidental to performing

More information

SOR FOR PILE FOUNDATION WORKS FOR TANKAGE & ENGINEERING STORE

SOR FOR PILE FOUNDATION WORKS FOR TANKAGE & ENGINEERING STORE SOR FOR PILE FOUNDATION WORKS FOR TANKAGE & ENGINEERING STORE S.NO Description Unit Total Qty EARTH WORK EXCAVATION : Earthwork in excavation at all depths for foundation, pile cap,drain, ramp,pits, etc.,

More information

MagnumStone Specifications Gravity

MagnumStone Specifications Gravity MagnumStone Specifications Gravity SPECIFICATION FOR MAGNUMSTONE GRAVITY MECHANICALLY STABILIZED EARTH SYSTEM PART 1: GENERAL.01Description The work consists of supplying and installing all aspects of

More information

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF SUB STATION STRUCTURE (LIGHTENING MAST) GETCO/E/TS-STR 2301/R1 Dt. 010208

More information

ITEM 416 DRILLED SHAFT FOUNDATIONS Materials. All materials shall conform to the requirements of the pertinent items as follows:

ITEM 416 DRILLED SHAFT FOUNDATIONS Materials. All materials shall conform to the requirements of the pertinent items as follows: ITEM 416 DRILLED SHAFT FOUNDATIONS 416.1. Description. This Item shall govern for the construction of foundations consisting of reinforced concrete drilled shafts and/or nonreinforced concrete drilled

More information

Main Roads Standard Specification

Main Roads Standard Specification Main Roads MRS. Manufacture of Precast Concrete Culverts December 7 COPYRIGHT State of Queensland (Department of Main Roads) 7 Copyright protects this publication. Except for the purposes permitted by

More information

PILING PART-VI CONSTRUCTION AND INSTALLATION OF RCC BORED CAST IN-SITU PILES

PILING PART-VI CONSTRUCTION AND INSTALLATION OF RCC BORED CAST IN-SITU PILES Page 1 of 8 PILING PART-VI OF RCC BORED CAST IN-SITU PILES REV. NO. PRAPARED APPROVED DATE 00 Marina P Mishra COPYRIGHT AND CONFIDENTAL The information on this document is the property of BHARAT HEVY ELECTRICAL

More information

TECHNICAL SPECIFICATION FOR PRESTRESSED CEMENT CONCRETE POLES ( F.O.S. 2.5) FOR 11 KV AND LT LINES ( REC SPECIFICATION NO.

TECHNICAL SPECIFICATION FOR PRESTRESSED CEMENT CONCRETE POLES ( F.O.S. 2.5) FOR 11 KV AND LT LINES ( REC SPECIFICATION NO. TECHNICAL SPECIFICATION FOR PRESTRESSED CEMENT CONCRETE POLES ( F.O.S. 2.5) FOR 11 KV AND LT LINES ( REC SPECIFICATION NO. 15 / 1979) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7

More information

BRICKWORK 3.5 BRICKWORK 1 GENERAL

BRICKWORK 3.5 BRICKWORK 1 GENERAL BRICKWORK 1 GENERAL 1.1 INSPECTION Notice Give sufficient notice so that inspection may be made of the following: - Set out of brickwork to lintels, arches and other architectural features. - Damp-proof

More information

CHAPTER 13 - MECHANICALLY STABILIZED EARTH WALLS AND PATENTED EARTH RETAINING SYSTEMS

CHAPTER 13 - MECHANICALLY STABILIZED EARTH WALLS AND PATENTED EARTH RETAINING SYSTEMS CHAPTER 13 - MECHANICALLY STABILIZED EARTH WALLS AND PATENTED EARTH RETAINING SYSTEMS DS Temple 13.1 SCOPE This section covers the inspection of mechanically stabilized earth walls and other patented earth

More information

CHECKLIST FOR READY MIX CONCRETE SUPPLY OF CONCRETE (RMC)

CHECKLIST FOR READY MIX CONCRETE SUPPLY OF CONCRETE (RMC) Sl.Pg. 450 CHECKLIST FOR READY MIX CONCRETE SUPPLY OF CONCRETE (RMC) Name of Work : C.A. : Name of Contractor/Client : 1. Name of RMC manufacturer with plant address & telephone nos. 2. Name of Plant In

More information

INDEX FOR SPECIFICATIONS FOR JACKING CULVERTS THROUGH EMBANKMENTS SCOPE... 2

INDEX FOR SPECIFICATIONS FOR JACKING CULVERTS THROUGH EMBANKMENTS SCOPE... 2 INDEX FOR SPECIFICATIONS FOR JACKING CULVERTS THROUGH EMBANKMENTS 410. 1 SCOPE... 2 410. 2 DEFINITIONS 2.1 Tunneling and Jacking... 2 2.2 Tunneling... 2 2.3 Jacking... 2 410. 3 MATERIALS 3.1 General...

More information

CONCRETE REINFORCEMENT. 1. Supplementary Conditions, General Conditions, General Requirements, shall govern Work of this Section.

CONCRETE REINFORCEMENT. 1. Supplementary Conditions, General Conditions, General Requirements, shall govern Work of this Section. CITY OF BRAMPTON LANDSCAPE SPECIFICATIONS SECTION 03200-1 PART 1 GENERAL 1.1 General Requirements 1. Supplementary Conditions, General Conditions, General Requirements, shall govern Work of this Section.

More information

Discipline Mechanical Testing Issue Date Certificate Number T-2522 Valid Until Last Amended on - Page 1 of 13

Discipline Mechanical Testing Issue Date Certificate Number T-2522 Valid Until Last Amended on - Page 1 of 13 Bureau Veritas (India) Pvt. Ltd. - Construction Services, Last Amended on - Page 1 of 13 I. MECHANICAL PROPERTIES OF MATERIALS 1. Steel Reinforcement Weight/meter IS 1786: 2008 (RA 2013) 0.1 kg to 20 kg

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR QUALITY CONTROL AND ACCEPTANCE OF STRUCTURAL PRECAST CONCRETE

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR QUALITY CONTROL AND ACCEPTANCE OF STRUCTURAL PRECAST CONCRETE MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR QUALITY CONTROL AND ACCEPTANCE OF STRUCTURAL PRECAST CONCRETE STR:MJF 1 of 8 APPR:JFS:POJ:01-04-19 FHWA:APPR:01-10-19 a. Description. The Contractor

More information

Mechanical Properties of Glass Fiber Reinforced Concrete

Mechanical Properties of Glass Fiber Reinforced Concrete Mechanical Properties of Glass Fiber Reinforced Concrete T. Sai Kiran 1, Dr. K. Srinivasa Rao 2 1 PG Scholar, Department of Civil Engineering, Andhra University, Visakhapatnam, Andhra Pradesh, India 2

More information

ITEM 431 PNEUMATICALLY PLACED CONCRETE. All material shall conform to the pertinent requirements of the following items:

ITEM 431 PNEUMATICALLY PLACED CONCRETE. All material shall conform to the pertinent requirements of the following items: ITEM 431 PNEUMATICALLY PLACED CONCRETE 431.1. Description. This Item shall govern for furnishing and placing of "Pneumatically Placed Concrete" for encasement of designated structural steel members, the

More information

CONSTRUCTION SPECIFICATION

CONSTRUCTION SPECIFICATION CAPRICORN MUNICIPAL DEVELOPMENT GUIDELINES GENERAL C220 CONSTRUCTION SPECIFICATION CAPRICORN MUNICIPAL DEVELOPMENT GUIDELINES C220 ISSUE: NO:3 July 2018 TABLE OF CONTENTS CLAUSE CONTENTS PAGE GENERAL...

More information

SPECIFICATION FOR ROAD SAFETY HARDWARE SYSTEMS APPENDIX D: SLIP FORMED CONCRETE BARRIERS

SPECIFICATION FOR ROAD SAFETY HARDWARE SYSTEMS APPENDIX D: SLIP FORMED CONCRETE BARRIERS SPECIFICATION FOR ROAD SAFETY HARDWARE SYSTEMS APPENDIX D: SLIP FORMED CONCRETE BARRIERS 1 GENERAL All slip formed concrete barrier shall be formed using the F-shape profile detailed in Specification M23

More information

Estimate FOR THE SEPTIC TANK

Estimate FOR THE SEPTIC TANK Estimate FOR THE SEPTIC TANK S.NO ITEM DESCRIPTION. 1 Excavation in soil,soft & hard murum... Qty UNIT Rate Excavation for footing, machine foundation, plinth beams, wall footing, gutters,brick wall, tanks

More information

COMPARATIVE STUDY OF BEAMS BY USING DIFFERENT TYPES OF RETROFITING TECHNIQUES

COMPARATIVE STUDY OF BEAMS BY USING DIFFERENT TYPES OF RETROFITING TECHNIQUES International Journal of Civil Engineering and Technology (IJCIET) Volume 10, Issue 04, April 2019, pp. 864 870, Article ID: IJCIET_10_04_091 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijciet&vtype=10&itype=4

More information

UPRR INDUSTRIAL LEAD BRIDGE T-WALL RETAINING WALL SYSTEM 5.0 x 7.5 UNITS DESIGN UNIT 018 WORK PACKAGE 04

UPRR INDUSTRIAL LEAD BRIDGE T-WALL RETAINING WALL SYSTEM 5.0 x 7.5 UNITS DESIGN UNIT 018 WORK PACKAGE 04 UPRR INDUSTRIAL LEAD BRIDGE T-WALL RETAINING WALL SYSTEM 5.0 x 7.5 UNITS DESIGN UNIT 018 WORK PACKAGE 04 1. Description This work shall consist of the design, manufacture and construction of a T-WALL structure

More information

EXAMPLE STATEMENT OF SPECIAL INSPECTIONS (SSI)

EXAMPLE STATEMENT OF SPECIAL INSPECTIONS (SSI) EXAMPLE STATEMENT OF SPECIAL INSPECTIONS (SSI) For this example let s consider a single-story retail shell building. The main structural walls consist of CMU construction with the front of the building

More information

City of Brandon Division 2 Standard Construction Specifications Section January 2009 (Revision 3) Page 1 of 6 READY MIXED CONCRETE

City of Brandon Division 2 Standard Construction Specifications Section January 2009 (Revision 3) Page 1 of 6 READY MIXED CONCRETE January 2009 (Revision 3) Page 1 of 6 PART 1 GENERAL 1.01 OTHER CONTRACT DOCUMENTS 1.02 DESCRIPTION OF WORK 1.03 RELATED WORK 1.04 CLASSIFICATION OF THE WORK The General Conditions of the Contract, General

More information

SECTION 1 TERMS, DEFINITIONS, ABBREVIATIONS, UNITS OF MEASURE, AND SYMBOLS 1-3 ABBREVIATIONS Common Usage.

SECTION 1 TERMS, DEFINITIONS, ABBREVIATIONS, UNITS OF MEASURE, AND SYMBOLS 1-3 ABBREVIATIONS Common Usage. SECTION 1 TERMS, DEFINITIONS, ABBREVIATIONS, UNITS OF MEASURE, AND SYMBOLS 1-3 ABBREVIATIONS. 1-3.2 Common Usage. Abbreviations Word or Words PAV.Pressure Aging Vessel PCC..Portland Cement Concrete PE.Polyethylene

More information

SECTION MORTAR

SECTION MORTAR PART l - SCOPE SECTION 04100 - MORTAR A. This Section includes all labor, materials, equipment, and related items required for the work of mortar as shown on the Drawings and specified herein. The work

More information

CONSTRUCTION SPECIFICATION FOR FOOTINGS AND PADS FOR ELECTRICAL EQUIPMENT

CONSTRUCTION SPECIFICATION FOR FOOTINGS AND PADS FOR ELECTRICAL EQUIPMENT ONTARIO PROVINCIAL STANDARD SPECIFICATION OPSS.MUNI 616 APRIL 2018 CONSTRUCTION SPECIFICATION FOR FOOTINGS AND PADS FOR ELECTRICAL EQUIPMENT TABLE OF CONTENTS 616.01 SCOPE 616.02 REFERENCES 616.03 DEFINITIONS

More information

SECTION REINFORCING STEEL

SECTION REINFORCING STEEL SECTION REINFORCING STEEL 1. DESCRIPTION This specification shall govern the furnishing and placing of reinforcing steel, deformed and smooth, of the size and quantity designated on the plans and in accordance

More information

Division 03 Concrete Section includes various guidelines for general concrete use, curing, forming, reinforcing, finishing and concrete accessories.

Division 03 Concrete Section includes various guidelines for general concrete use, curing, forming, reinforcing, finishing and concrete accessories. Section includes various guidelines for general concrete use, curing, forming, reinforcing, finishing and concrete accessories. This design guideline is written to the designer of record (DOR). This guideline

More information

STANDARD SPECIFICATION FOR CRIBLOCK CONCRETE CRIBWALL

STANDARD SPECIFICATION FOR CRIBLOCK CONCRETE CRIBWALL STANDARD SPECIFICATION FOR CRIBLOCK CONCRETE CRIBWALL 1. SCOPE 2. DESIGN 3. MATERIALS 4. CONSTRUCTION 5. METHOD OF MEASUREMENT AND PAYMENT SCOPE This Specification sets out requirements for the design,

More information

CHAPTER 3 BEHAVIOUR OF FERROCEMENT HOLLOW SLABS

CHAPTER 3 BEHAVIOUR OF FERROCEMENT HOLLOW SLABS 30 CHAPTER 3 BEHAVIOUR OF FERROCEMENT HOLLOW SLABS 3.1 INTRODUCTION There are numerous similarities between ferrocement and reinforced concrete. Both use similar matrix and reinforcement materials. They

More information

ADDENDUM January 2018 Updates for the 13 th Edition NPCA QC Manual QCM-001, Rev. 0,

ADDENDUM January 2018 Updates for the 13 th Edition NPCA QC Manual QCM-001, Rev. 0, ADDENDUM January 2018 Updates for the 13 th Edition NPCA QC Manual QCM-001, Rev. 0, 1-1-18 The NPCA Quality Assurance Committee has again raised the bar on quality for NPCA Plant Certification. The format

More information

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 PROFESSIONAL SERVICE INDUSTRIES, INC. 3011 South Huson Street, Suite A Tacoma, WA 98409 Eric Allen Phone: 253 589 1804 Valid To: December 31, 2019 Certificate

More information

The durability of normal strength concrete: an experimental study

The durability of normal strength concrete: an experimental study Materials Characterisation VII 195 The durability of normal strength concrete: an experimental study V. Patel & N. Shah Civil Engineering Department, Charotar University of Science and Technology, India

More information

ITEM 461 STRUCTURAL PLATE STRUCTURES. Galvanized steel plates shall conform to AASHTO M167 and aluminum plates shall conform to AASHTO M219.

ITEM 461 STRUCTURAL PLATE STRUCTURES. Galvanized steel plates shall conform to AASHTO M167 and aluminum plates shall conform to AASHTO M219. ITEM 461 STRUCTURAL PLATE STRUCTURES 461.1. Description. This Item shall govern for the furnishing and installing of structural plate pipes, pipe arches, arches, underpasses, box culverts and special shapes

More information

SECTION UNIT MASONRY

SECTION UNIT MASONRY SECTION 04200 UNIT MASONRY PART 1 GENERAL 1.01 SUMMARY A. Furnish labor, materials, and equipment and perform functions required in the installation and maintenance of the work covered by this Section.

More information

SECTION PERMEABLE INTERLOCKING CONCRETE UNIT PAVEMENT

SECTION PERMEABLE INTERLOCKING CONCRETE UNIT PAVEMENT SECTION 32 14 13 19 PERMEABLE INTERLOCKING CONCRETE UNIT PAVEMENT SECTION 32 14 13 19 PERMEABLE INTERLOCKING CONCRETE UNIT PAVEMENT PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Permeable Articulating

More information

SECTION INTERLOCKING PRECAST CONCRETE UNIT PAVERS

SECTION INTERLOCKING PRECAST CONCRETE UNIT PAVERS SECTION 321413.13 INTERLOCKING PRECAST CONCRETE UNIT PAVERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Interlocking concrete paver units. 2. Sand setting bed. 3. Sand joint

More information

CONCRETE SEGMENTAL FREESTANDING WALL SYSTEM

CONCRETE SEGMENTAL FREESTANDING WALL SYSTEM CONCRETE SEGMENTAL FREESTANDING WALL SYSTEM PART 1: GENERAL SPECIFICATIONS 1.01 Work Included A. Work shall consist of furnishing and constructing a Lakeland TM unit segmental freestanding wall in accordance

More information

TABLE OF CONTENTS

TABLE OF CONTENTS DIVISION 33: SEWER AND SEPTIC SYSTEMS 33 3633 UTILITY SEPTIC TANK DRAINAGE FIELD TABLE OF CONTENTS 33 0000-1 SECTION 33 3633-- UTILITY SEPTIC TANK DRAINAGE FIELD PART 1 - GENERAL 1.1 SUMMARY A. Includes

More information

Report of Special Inspections

Report of Special Inspections Project: Project Location: Report of Special Inspections Central Carolina Technical College Advanced Manufacturing Technology Training Center Sumter, South Carolina Permit Number: Owner/Address: 853 Broad

More information

Concrete Mix Design. Introduction

Concrete Mix Design. Introduction Concrete Mix Design Introduction The process of selecting suitable ingredients of concrete and determining their relative amounts with the objective of producing a concrete of the required, strength, durability,

More information

Trial Mix Details. Physical requirements verification for Super-plasticizers

Trial Mix Details. Physical requirements verification for Super-plasticizers Trial Mix Details Physical requirements verification for Super-plasticizers ASTM C 494 & IS 9103 Water reduction efficiency Strength Setting Time Air Content Bleeding Could be suggested - Slump retention

More information

1993 SPECIFICATIONS CSJ SPECIAL SPECIFICATION ITEM 4110 CONCRETE ENCASED DUCT BANK

1993 SPECIFICATIONS CSJ SPECIAL SPECIFICATION ITEM 4110 CONCRETE ENCASED DUCT BANK 1993 SPECIFICATIONS CSJ 581-1-95 SPECIAL SPECIFICATION ITEM 4110 CONCRETE ENCASED DUCT BANK 1. DESCRIPTION. This Item shall govern for the furnishing and installation of all materials and equipment for

More information

The Role of the Resident Engineer. Liam Geoghegan MSc

The Role of the Resident Engineer. Liam Geoghegan MSc The Role of the Resident Engineer Liam Geoghegan MSc Inroduction Liam Geoghegan, RPS Consulting Engineers Experience in Road Construction Projects since 1991 I have worked for Local Authorities, Consulting

More information

SPECIAL SPECIFICATION 4653 Polypropylene Pipe

SPECIAL SPECIFICATION 4653 Polypropylene Pipe 2004 Specifications CSJ 2158-01-013, Etc. SPECIAL SPECIFICATION 4653 Polypropylene Pipe 1. Description. Furnish and install polypropylene pipe for constructing polypropylene pipe culverts or polypropylene

More information

Description. This work shall consist of furnishing materials and placement of modular block wall constructed in accordance with

Description. This work shall consist of furnishing materials and placement of modular block wall constructed in accordance with MODULAR CONCRETE BLOCK RETAINING WALL WITH GROUND REINFORCING The Standard Specifications are revised as follows: 732-R-310r 1of 11 Rev. 12-03-03 SECTION 105, AFTER LINE 48, INSERT AS FOLLOWS: When constructing

More information

Reinforced Earth wall Construction Manual

Reinforced Earth wall Construction Manual COVER PAGE CT-PE-W02 Rev: 5 Reinforced Earth wall Construction Manual Concrete Facing Reinforced Earth Malaysia Sdn Bhd 80-1, Jalan 8/62A Bandar Menjalara 52200 Kuala Lumpur Tel : 03-62746162, Fax : 03-62747212

More information

SPECIFICATION 1035 M

SPECIFICATION 1035 M MAY 1984 SPECIFICATION 1035 M SPECIFICATIONS FOR UNDERWATER CONCRETE 1035. 1. DESCRIPTION The work will consist of the mixing of concrete in accordance with the "Specifications for Reinforced Concrete",

More information

SPECIFICATION OF NEOPRENE RUBBER SEALS

SPECIFICATION OF NEOPRENE RUBBER SEALS SPECIFICATION OF NEOPRENE RUBBER SEALS 1.0 SCOPE This specification establishes the requirements for the manufacture, inspection, testing, packing, guarantee & supply of Neoprene Rubber Seals for Fuelling

More information

1. Cast-in place structural concrete including footers, foundations, and other non-slab applications. 2. Formwork 3. Reinforcement

1. Cast-in place structural concrete including footers, foundations, and other non-slab applications. 2. Formwork 3. Reinforcement SECTION 03 31 00 - CAST-IN-PLACE STRUCTURAL CONCRETE PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Cast-in place structural concrete including footers, foundations, and other non-slab applications.

More information

CIVIL WORKS Mahesh G. Nair

CIVIL WORKS Mahesh G. Nair MEASUREMENT BOOK SUNIL Date Work Order Contractor : : EARTH WORKS CIVIL WORKS Mahesh G. Nair GROUND FLOOR 1 EARTH WORKS EXCAVATION : Earth work excavation for foundation trenches in all classes of soil

More information

CF50/100 KW TURBINE ACCESS ROAD, CRANE PLATFORM, CONCRETE, AND LIFTING SPECIFICATIONS C&F GREEN ENERGY REVISION PREPARED BY APPROVED BY DATE

CF50/100 KW TURBINE ACCESS ROAD, CRANE PLATFORM, CONCRETE, AND LIFTING SPECIFICATIONS C&F GREEN ENERGY REVISION PREPARED BY APPROVED BY DATE CF50/100 KW TURBINE ACCESS ROAD, CRANE PLATFORM, CONCRETE, AND LIFTING SPECIFICATIONS C&F GREEN ENERGY REVISION PREPARED BY APPROVED BY DATE 001 First Draft W Hession 12.02.2014 Introduction This document

More information

Concrete works in Highway Engineering

Concrete works in Highway Engineering Concrete works in Highway Engineering INTRODUCTION TO CONCRETE Concrete has been used as a construction material in largest quantity for several decades due to its excellent engineering properties and

More information

NATIONAL INSTITUTE OF ANIMAL BIOTECHNOLOGY (NIAB), HYDERABAD

NATIONAL INSTITUTE OF ANIMAL BIOTECHNOLOGY (NIAB), HYDERABAD NATIONAL INSTITUTE OF ANIMAL BIOTECHNOLOGY (NIAB), HYDERABAD TENDER FOR Construction of Stone Masonry Compound Wall for NIAB Campus at Survey No.37, Serlingampally, Hyderabad VOLUME V January 2013 HSCC

More information

MATERIAL SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS

MATERIAL SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 1821 APRIL 2004 MATERIAL SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS TABLE OF CONTENTS 1821.01 SCOPE 1821.02 REFERENCES

More information

International Journal of Engineering Science Invention Research & Development; Vol. I Issue XI May e-issn:

International Journal of Engineering Science Invention Research & Development; Vol. I Issue XI May e-issn: Overview of Utilization of fly ash as cementitious material R.A.Khan 1,M.U.Siddiiqui 2,M.W.Baig 3 1,2 Lecturer, Department of Civil Engineering, Integral University,Campus Shahjahanpur, U.P.(India) 3 In-charge,

More information

CONCRETE SEGMENTAL RETAINING WALL SYSTEM

CONCRETE SEGMENTAL RETAINING WALL SYSTEM CONCRETE SEGMENTAL RETAINING WALL SYSTEM PART 1: GENERAL SPECIFICATIONS 1.01 Work Included A. Work shall consist of furnishing and constructing a Rockwood Classic 8, Classic 6 and Legend unit segmental

More information

Section REINFORCING STEEL

Section REINFORCING STEEL Section 03210 PART 1 GENERAL 1.01 SUMMARY This Section includes the furnishing and subsequent placing of reinforcing steel, deformed and smooth, chairs, ties, splicing devices, and other reinforcing accessory

More information

National Test House (N.W.R.), E-763, Road No. 9F-1, VKI Area, Jaipur, Rajasthan. Discipline Mechanical Testing Issue Date

National Test House (N.W.R.), E-763, Road No. 9F-1, VKI Area, Jaipur, Rajasthan. Discipline Mechanical Testing Issue Date Last Amended on - Page 1 of 12 I. MECHANICAL PROPERTIES OF MATERIALS 1. Ferrous & Non Ferrous Tensile Test Tensile strength/breaking strength/load Proof load % Elongation % Reduction in Area Yield Stress

More information

What s in the Mix. Aim of this presentation Overview of mix design Overview of constituents Cement Aggregates Coarse Fine.

What s in the Mix. Aim of this presentation Overview of mix design Overview of constituents Cement Aggregates Coarse Fine. What s in The Mix What s in the Mix Aim of this presentation Overview of mix design Overview of constituents Cement Aggregates Coarse Fine Water SCM s Aim of a Mix Design Mix Design is a Scientific Art

More information

IS : Dr. S. RAVIRAJ

IS : Dr. S. RAVIRAJ CONCRETE MIX PROPORTIONING IS 10262 : 2009 Dr. S. RAVIRAJ Professor of Civil Engineering JSS Science and Technology University S.J. College of Engineering Mysuru 570 006 ravirajs@sjce.ac.in 1 Introduction

More information

Laboratory Certification For. Build Afghanistan Engineering Services (BAES) Laboratory

Laboratory Certification For. Build Afghanistan Engineering Services (BAES) Laboratory Laboratory Certification For Build Afghanistan Engineering Services (BAES) Laboratory Lab ID: LCP-017 Issue date: Oct 5, 2016 Expiry date: April 4, 2017 This Extension letter confirms the completion of

More information

Management of Design and Construction for Civil Works under EPC contract in one Oversea Wind Farm Project

Management of Design and Construction for Civil Works under EPC contract in one Oversea Wind Farm Project ORIGINAL ARTICLE Management of Design and Construction for Civil Works under EPC contract in one Oversea Wind Farm Project Wu Zheng Power China Chengdu Engineering Corporation LTD, Chengdu 610072 Abstract:

More information

FOR BUILDING WORKS PART-I WORK INFORMATION - (TO BE FILLED-UP BY PROJECT) Work is

FOR BUILDING WORKS PART-I WORK INFORMATION - (TO BE FILLED-UP BY PROJECT) Work is KARNATAKA RURAL INFRASTRUCTURE DEVELOPMENT LIMITED (FORMERLY KARNATAKA LAND ARMY CORPORATION LIMITED) "GRAMEENABHIVRUDDHI BHAVAN", 4TH & 5TH FLOOR, ANANDA RAO CIRCLE, BANGALORE 560 009 Annexure - 1 Format

More information

Technical Specifications of 8 M and 9 M PCC Poles (F.O.S.-2.5) with working load 200 Kg.

Technical Specifications of 8 M and 9 M PCC Poles (F.O.S.-2.5) with working load 200 Kg. DAKSHIN HARYANA BIJLI VITRAN NIGAM LIMITED Specification No. S-95/DD-177 Technical Specifications of 8 M and 9 M PCC Poles (F.O.S.-2.5) with working load 200 Kg. Chief Engineer/P&D, DHBVN, Hisar. Issue

More information

The hardening is caused by chemical action between water and the cement due to which concrete grows stronger with age.

The hardening is caused by chemical action between water and the cement due to which concrete grows stronger with age. CONCRETE MIX DESIGN INTRODUCTION Concrete is obtained by mixing cement, fine aggregate, coarse aggregate, water and admixtures in required proportions. The mixture when placed in forms and allowed to cure

More information

EFFECT ON MECHANICAL PROPERTIES OF CONCRETE USING NYLON FIBERS

EFFECT ON MECHANICAL PROPERTIES OF CONCRETE USING NYLON FIBERS EFFECT ON MECHANICAL PROPERTIES OF CONCRETE USING NYLON FIBERS Nitin 1, Dr. S.K. Verma 2 1 PG student, Dept. of Civil Engineering (Structures), PEC University of technology, Chandigarh, India. 2 Associate

More information

SECTION PRECAST CONCRETE COVER SYSTEM

SECTION PRECAST CONCRETE COVER SYSTEM SECTION 13500 PRECAST CONCRETE COVER SYSTEM PART 1 GENERAL 1.1 SYSTEM DESCRIPTION A. Design Criteria: 1. Precast manufacturer shall be responsible for structural design of individual precast components,

More information

REINFORCED CONCRETE CULVERT STORM DRAIN AND SEWER PIPE FIELD SECTION 1026

REINFORCED CONCRETE CULVERT STORM DRAIN AND SEWER PIPE FIELD SECTION 1026 (Page 1 of 8) REINFORCED CONCRETE CULVERT STORM DRAIN AND SEWER PIPE FIELD SECTION 1026 1026.1 SCOPE. To establish procedures for the inspection of reinforced concrete pipe and the approval of modified

More information

Pennoni Associates, Inc.

Pennoni Associates, Inc. in Bethlehem, Pennsylvania, USA has demonstrated proficiency for the testing of construction materials and has conformed to the requirements established in AASHTO R 18 and the AASHTO Accreditation policies

More information

Tex-426-A, Estimating Concrete Strength by the Maturity Method

Tex-426-A, Estimating Concrete Strength by the Maturity Method Maturity Method Contents: Section 1 Overview...2 Section 2 Apparatus...3 Section 3 Procedures...4 Section 4 Forms...8 Texas Department of Transportation 1 08/02 01/10 Section 1 Overview Section 1 Overview

More information

A Case Study on Strength Properties of Partially Replaced Recycled Aggregate and Steel Fibers to a Nominal Concrete

A Case Study on Strength Properties of Partially Replaced Recycled Aggregate and Steel Fibers to a Nominal Concrete ISSN 2278 0211 (Online) A Case Study on Strength Properties of Partially Replaced Recycled Aggregate and Steel Fibers to a Nominal Concrete A. R. Pradeep Assistant Professor, Department of Civil Engineering,

More information

Concrete. Chapter 10 Properties of Fresh Concrete. Materials of Construction-Concrete 1. Wikipedia.org

Concrete. Chapter 10 Properties of Fresh Concrete. Materials of Construction-Concrete 1. Wikipedia.org Wikipedia.org Concrete Chapter 10 Properties of Fresh Concrete Materials of Construction-Concrete 1 What is Concrete? Concrete is a composite material that consists of a cement paste within which various

More information

SECTION 44 SHOTCRETE, CAST CONCRETE CHANNEL LINING, AND GROUTED COBBLE TABLE OF CONTENTS

SECTION 44 SHOTCRETE, CAST CONCRETE CHANNEL LINING, AND GROUTED COBBLE TABLE OF CONTENTS SECTION 44 SHOTCRETE, CAST CONCRETE CHANNEL LINING, AND GROUTED COBBLE TABLE OF CONTENTS Section Page 44-1 SHOTCRETE... 44.1 44-1.01 Description... 44.1 44-1.02 Materials... 44.1 44-1.03 Proportions...

More information

Conditions of the Contract and Division 1 General Requirements are a part of this section.

Conditions of the Contract and Division 1 General Requirements are a part of this section. NOTES TO SPECIFIER General notes about the specifications and the reasons for them are listed here in general statements. Use this as a guide when choosing the correct selection of statements that apply

More information

Section CONCRETE SIDEWALKS. 1. Payment for concrete sidewalks is on square foot basis.

Section CONCRETE SIDEWALKS. 1. Payment for concrete sidewalks is on square foot basis. PART 1 GENERAL 1.01 SUMMARY A. This Section includes the following: Section 02775 1. Reinforced concrete sidewalks. 2. Wheelchair Ramps. 1.02 MEASUREMENT AND PAYMENT A. Unit Prices. 1. Payment for concrete

More information

THRESHOLD INSPECTION SPECIAL INSPECTION PLAN. Evangel Temple Addition

THRESHOLD INSPECTION SPECIAL INSPECTION PLAN. Evangel Temple Addition Page 1 of 11 THRESHOLD INSPECTION SPECIAL INSPECTION PLAN PROJECT: Addition OWNER: ARCHITECT: Brennfoerder Architectural Services STRUCTURAL ENGR: Tappana Ondrick Structural Engineers DATE: Sept. 4, 2018

More information

Construction Specification for Utility Adjustments

Construction Specification for Utility Adjustments Engineering & Construction Services Division Standard Specifications for Road Works TS 4.50 September 2017 for Utility Adjustments Table of Contents TS 4.50.01 SCOPE... 2 TS 4.50.02 REFERENCES... 2 TS

More information

UNIT 9 INSPECTION AND QUALITY CONTROL

UNIT 9 INSPECTION AND QUALITY CONTROL UNIT 9 INSPECTION AND QUALITY CONTROL Inspection and Quality Control Structure 9.1 Introduction Objectives 9.2 Need for Inspection and Quality Control 9.3 Principles of Inspection 9.4 Major Items in Construction

More information

SECTION 44 SHOTCRETE, CAST CONCRETE CHANNEL LINING, AND GROUTED COBBLE TABLE OF CONTENTS

SECTION 44 SHOTCRETE, CAST CONCRETE CHANNEL LINING, AND GROUTED COBBLE TABLE OF CONTENTS SECTION 44 SHOTCRETE, CAST CONCRETE CHANNEL LINING, AND GROUTED COBBLE TABLE OF CONTENTS Section Page 44-1 SHOTCRETE 44-1 44-1.01 Description 44-1 44-1.02 Materials 44-1 44-1.03 Proportions 44-1 44-1.04

More information

Foundation Specifications

Foundation Specifications Installation Instructions Bulletin 7581438 Revision C Foundation Specifications for 6.5-Meter Modular Earth Station Antennas Introduction This document specifies typical foundation characteristics, designs,

More information