1 INNOVATIVE LIFE-CYCLE CONCEPTS FOR MEDIUM-VOLTAGE SWITCHGEAR ON BROWN COAL SURFACE MINING DEVICES Dr. S. Ruhland, Dr. U. Riedl ALSTOM Sachsenwerk GmbH, Germany The requirements for medium voltage switchgear in brown coal surface mining networks are different from those in the networks of utilities. The main differences are the mobile power consumers in the mine such as mobile transformer stations, power shovels or winding bridges with dimensions of more then 400 meters in length and 50 meters in height. As the power consumption of such a unit is about 30 MW, the distribution network of such a device has a rated voltage of 36 kv respective 7,2 kv. The severe environmental conditions have a major influence to the design, the installation and the operation of the switchgear. Therefore it is evident to think about the full life cycle of these installations. DESIGN AND INDUSTRIAL PHASE The main aspects for the design of distribution equipment for brown coal surface mining are the electrical and mechanical requirements due to the environmental situation. The electrical situation is a network with high probability of faults. The faults can come from the mining process itself (e.g. earth faults coming from damages of cables or lightning impact of the extended metal structures) or from the mechanical movement of the mining devices (permanent vibration and shocks). The switchgear design has to withstand the resulting stresses such as overvoltages and mechanical vibration, therefore it is important to choose the correct materials with minor influence to the environment and with good possibility for the later recycling process, but with high withstand capabilities. The design has to pass several acceptance tests such as vibration tests with accelerations up to 1 g and shock tests with amplitudes up to 5 g. During the tests all mechanical and electrical interlocks have to work safely. The insulation system and the tightness in the case of gas insulated switchgear have to be proven as well to ensure the function during the whole lifetime. All the results and measures taken to fulfil the requirements have to be secured during the assembling process in the factory and have to be documented in the routine test reports. INSTALLATION AND SERVICE PHASE The on site installation is one of the most important milestones during the lifetime of a switchgear. In this period it has to be ensured, that the product attribute s are not influenced by the erection work. Measures have to developed to guarantee e.g. the integrity of the insulation system. That means partial discharge measurements have to be performed on site under a severe electromagnetic environment with disturbance levels. Other points that are important during the service phase are: no maintenance on the active part of the switchgear no maintenance/refilling on the gas system (in the case of GIS) maintenance free mechanical drives choice of resistant lubrication systems easy adaptation of the switchgear to the needs in the network (ratings) zero emission during the normal operation low emission in the improbable case of an internal arc END OF LIFE PHASE In spite of the high lifetime of distribution equipment the disposal at the end of the lifetime has to be considered at the beginning of the development. The usage of environmental friendly materials will reduce the disposal costs and will fulfil strong ecological requirements. Further on the requirements from the client side and from the disposal companies regarding the data of amounts of different materials (kind and amount of metals, plastics..) have to be taken into account during the development phase. A common view on the full lifetime cycle (design, service and disposal) of a medium voltage switchgear has to be developed to tackle the increasing number of ecological requirements in future.

2 INNOVATIVE LIFE-CYCLE CONCEPTS FOR MEDIUM-VOLTAGE SWITCHGEAR ON BROWN COAL SURFACE MINING DEVICES Dr. S. Ruhland, Dr. U. Riedl ALSTOM Sachsenwerk GmbH, Germany INTRODUCTION Using medium-voltage switchgear for brown coal surface mining as an example, we will show the principles according to which particular requirements and installation conditions are taken into consideration for all life phases of a product. ALSTOM concerning design, installation and operation. To this effect, the complete life-cycle of the switchgear was taken into consideration from the start. The following steps are defined as life phases: development, production, local assembly and operation, and disposal. Lignite mining and processing in Lusatia on an industrial scale dates back to the end of the 19 th century. There are lignite fields totalling 13 billion tons in Lusatia, 2.6 billion tons of which, which can be extracted in an economically efficient fashion, taking into account present ecological and social compatibility aspects, are scheduled or planned for mining. In this open cast mining, the lignite stratum to be extracted reaches a thickness of 8 to 12 meters. A typical feature of lignite open cast mining in Lusatia are the big overburden conveyor gantries. They are used to extract the majority of the 60 to 80 m high capping deposited on the stratum. The maximum energy demand of open-cast mining is 60 to 80 MW, depending on the actual extraction technology and utilisation of power. The largest individual energy consumers are the conveyor gantry units F60 with a maximum power utilisation of 25 to 30 MW and an overburden extraction capacity of 90 to 110 million m³ per year. Other main consumers are overburden and lignite conveyor belt systems of max. 15 to 20 MW per operated mining complex. Due to the continuous development of open cast mining with an annual coal advance of 250 to 400 meters, all main consumers, such as conveyor gantries, excavators and conveyor belt systems, are in constant motion. The unfavourable ambient conditions (dust immission, humid climates, vibrations) were of considerable importance for the choice of systems by the operating company, and important for PICTURE 1 Overburden conveyor gantry in lignite open cast mining TECHNICAL IMPLEMENTATION The profiles requested in the table 1 can be covered with the gas-insulated GMA and WSA switchgear series. Moreover, control of the additional mechanical strains imposed on the panels as regards the stability of the drive mechanism, the sealing function parts of the gas compartment and the stable behaviour regarding partial discharge (PD) had to be ensured as well as the condition that operating safety had to be guaranteed in the presence of dust immission and high, alternating air humidity values (condensation hazard). Besides, an internal specification from the manufacturer requires an environmentally compatible design (selection of materials, recycling-oriented design, use of environmentally compatible plastics) and the presence of a disposal concept for switchgear at the end of its service life which includes considerations of

3 ecological regeneration and re-use of the insulating gas sulphur hexafluoride SF 6. TABLE 1 Requirement criterion Technical requirements Service voltage 6 kv Service voltage 30 kv Rated voltage U r 12 kv 36 kv Rated short-circuit 20 ka 16 ka current I k Rated short-circuit 1 second 1 second duration t k Rated (service) current I r for circuit-breaker switchgear for switch-disconnector units Rated insulation level U p U d Insulation level when the insulating gas pressure is reduced to ambient pressure U p 1250 A 630 A 75 kv 28 kv 1250 A 630 A 170 kv 70 kv U d 75 kv 28 kv 145 kv 70 kv Insulation fluid of electrically active part 100% SF 6, no solid insulation 100% SF 6, no solid insulation Leakage rate <<1% p.a. <<1% p.a. Partial discharge (PD) behaviour of overall insulation system: PD intensity at 1.1 U r PD extinction voltage Mechanical endurance: Circuit-breaker mechanism Switch disconnector mechanism Disconnector/Earthing switch Integrated voltage detection system Proof of resistance to vibration strain Vibration Shock Resistance to external environmental influences (dust, humidity, etc.) Proof of staff level safety in case of internal faults Freely configurable interface to BUS systems (Interbus, Profibus etc.) < 15 pc < 15 pc > 0.9 U r > 0.9 U r > > 1000 > 1000 acc. to IEC g 5.0 g IP65 DIN EN 60298, Criteria 1-6 Possible for 100% of internal E/A signals > > 1000 acc. to IEC g 5.0 g IP65 DIN EN 60298, Criteria 1-6 Possible for 100% of internal E/A signals Due to different design characteristics, it was not possible to perform generally valid tests on the GMA and WSA switchgear to confirm the suitability of the types in question, but the inspections had to be adapted to the particularities in question. PICTURE 2 Gas insulated single busbar switchgear type WSA SIGNIFICANCE FOR THE DESIGN PHASE AND FOR THE PRODUCTION PHASE The customer's specific main task profile consisted of the critical ambient conditions of lignite mining. Before the vibration tests were performed in external, independent testing laboratories, the test objects were subjected to the following examinations: Partial discharge measurement Leakage test (test of all single components e.g. electrical and mechanical bushings under thermal cycling conditions -40 C/+105 C, to subject the systems to high mechanical strain; the measurements were performed integrally using highresolution infrared (IR) spectroscopy). After production, each switchgear unit was subjected to an integral test using sensitive IR spectroscopy (exception BB area of the WS switchgear which had been tested over the entire sealing area using a gas sensitive detector after local assembly) Functional inspection of the mechanical drives (in the design phase, the lubricant system was given special consideration as

4 regards stability to moisture and abrasive dusts with partially corrosive action) Determination of the mechanical characteristic data of the drive mechanisms (speeds etc.). Sequence of external inspections following internal inspections: Sweep sine test according to IEC in all three axes Shock test according to IEC in all three axes TABLE 2 Vibration test parameters Type of test Parameter Testing value Vibration Shock Frequency Stroke/ acceleration Frequency change Testing time Shock form Peak acceleration Shock duration Number of shocks Hz 5-58 Hz Hz 1 oct/min 10 cycles half-sine 5 g 11 ms 3 per direction ± mm 0.5 g per axis 6 per axis PICTURE 3 WSA during the vibration test During the tests performed at the Technical University of Berlin and the at the laboratories of the Navy of the armed forces all the functions were controlled. That means manual and electrical operation of the circuit breaker and the disconnectors respective the three position switch, observation of the change of the electrical position indication and check of the gas density control system. After the tests all dielectrical values, power withstand voltage, lightning impulse withstand voltage and partial discharge, could be demonstrated. The materials used for insulation, i.e. duroplastics and thermoplastics, and elastomers (sealing materials) satisfy the requirements to a large extent. Specific accelerated tests under enhanced mechanical strain also allow for conclusions on positive long-term behaviour. The corrosion protection system (painting, electroplating, zinc-plating) also ensures protection over the expected service life. For the painting a combination of a cathodic dip paint and a powder coating with an excellent withstand against moisture and corrosive immissions is used (proofed in time-lapsed tests with salt fog and sulphur-dioxide). The electroplating and hot dip zinc-plating surfaces are optimised with additives (electroplating) and with additional treatment of the protection-layer (hot dip zinc-plating). Graph 1 Measured accelerations during the vibration test All results of the electrical and mechanical parameters determined in type tests are taken over

5 in the routine tests in the production lines, verified there and documented accordingly. SIGNIFICANCE FOR LOCAL ASSEMBLY AND SWITCHGEAR OPERATION Zero fault installation - even under the most difficult installation conditions at the operating company s - is of paramount importance during local assembly. All the relevant systems are checked after assembly work. The on-site partial discharge measurements were particularly sophisticated, as there were powerful interference signals from surrounding electro-technical systems already installed during the testing phase. After installation, all switchgear stations were tested for leakage using mobile analysers, unless this had already been done prior to delivery. for the sealing elastomer systems to support zero leakage condition Zero emission of gas system (only the technically inevitable and extremely low gas losses due to material permeation were detected in the type tests) Low gas emission in the improbable case of an accidental arc (arc resistance of gas compartment, low plastics portion, high recombination capacity of the thermally decomposed insulating gas sulphur hexafluoride) SIGNIFICANCE FOR THE END-OF-LIFE PHASE The preparations for low-cost and ecologically justifiable disposal of the switchgear must be made as early as in the design phase. This step follows the latest state of disposal technology, in spite of the expected long service lives of 30 to 40 years. The use of a maximum recyclable metal portion provides optimum prerequisites to this effect. The metal portion of the GMA and WSA switchgear series amounts to approx. 90 % of the weight, i.e. a very high portion for an electrotechnical mediumvoltage product. The remaining portion consists of the insulating materials duroplastics and increasingly of recyclable thermoplastics), of elastomers (sealing materials), and to a very low extent of special materials and materials such as sulphur hexafluoride (insulating gas), mineral molecular sieves (desiccant in the gas compartment) and ceramics (insulating elements for vacuum interrupter chambers). PICTURE 4 Gasinsulated switchgear type GMA The following aspects were taken into consideration for the operating phase as early as in the design and engineering stage: Zero maintenance in the high-voltage section of the switchgear; this is ensured due to systematic enclosure (gas enclosure without solid insulation) Zero maintenance drive mechanisms over a period of several years, obtained by the specific lubricant and corrosion protection systems and by the selection of the metallic materials Use of a chemically stable lubricant system for the mechanical components, for the movable and fixed contact areas in the gas section and TABLE 3 Materials for the type GMA (average weight values) Steel 150 kg 57 % Stainless steel 70 kg 27 % Copper, aluminium, brass 25 kg 9 % Duroplastics 6 kg 2 % Thermoplastics 7 kg 3 % Other (ceramic, gas, desiccant) 5 kg 2 % The insulating materials have been designed so that the absolute plastics content is reduced even more by reinforcing materials, such as glass fibre. Moreover, all insulating components, if they are adjusted for self-extinguishing action, do not contain any halogen-type flame-retardants. There are effective recycling concepts and proposals for all materials. This is particularly

6 relevant for the insulating gas sulphur hexafluoride which can be recovered effectively, and is recycled after regeneration. To inform customers and disposal companies alike about the type, quantity and installation condition of various materials and the individual channels of disposal, Data Sheets for Materials and Disposal have been prepared for the various switchgear models to inform and instruct about handling after the end of service life. SUMMARY The switchgear project performed together with the operating company demonstrated the great importance of precise determination of a task profile, not only as regards the electro-technical design, but also material and concept selection for operation under extremely difficult ambient conditions. INITIAL OPERATING EXPERIENCE Due to extensions of GMA switchgear and the comments made by a customer, initial information became available after two years about the extent to which switchgear stations prove their functions under the difficult ambient conditions described above. The total period of operation is short compared with the total service life, but further long-term forecasts can be made thanks to certain assessment methods. Compared to the initial values, no increases of partial discharge values were found. The perfect gas tightness of the gas tanks was maintained; gas measurements did not show any leakage and also no change in the dew-point of the gas compartments. The inspection of the mechanical drives showed partially loose screws in one panel, coming from the permanent vibrations of the mining devices. As a precaution the screws in all panels were additional fitted by self securing nuts to avoid any repetition of this. Further the closing/opening coils were replaced in the drive area. However, this was due to the fact that the low-voltage magnets used for closing/opening were actually designed as undervoltage releases, and used at an even higher voltage than the permitted service voltage. PICTURE 5 Transportation of brown coal to the power station When implementing the assembly, testing and installation conditions defined in the development stage, the customer disposes of a switchgear ensuring safe and environmentally responsible operation. In case of malfunctions (power supply faults), operating safety and environmentally compatible behaviour are still ensured. Disposal of the product is due at the end of every service phase. Using environmentally friendly materials and taking account of the aspects of the future regulations on electrical scrap, the operator can rest assured that he has an optimally economical and ecological solution. No corrosion on metals was found, nor soiling in the drive and control section which was due to a sufficiently dimensioned degree of protection. Further dates for regular assessment were agreed upon with the customer, to obtain feedback as to the extent to which the concept of the two variants of gas-insulated medium-voltage switchgear afforded long-term safe operation.

Gas-insulated medium-voltage switchgear. for wind parks. Answers for energy.

Gas-insulated medium-voltage switchgear. for wind parks. Answers for energy. Gas-insulated medium-voltage switchgear for wind parks Answers for energy. Switchgear for wind turbines: 8DH10 up to 24 kv, up to 20 ka, up to 1,250 A up to 17.5 kv, up to 25 ka, up to 1,250 A Best performance

More information

Gas-insulated medium-voltage switchgear. for marine and offshore applications. Answers for energy.

Gas-insulated medium-voltage switchgear. for marine and offshore applications. Answers for energy. Gas-insulated medium-voltage switchgear for marine and offshore applications Answers for energy. 8DH10 switchgear up to 24 kv, up to 20 ka, up to 1,250 A up to 17.5 kv, up to 25 ka, up to 1,250 A Full

More information

Totally Integrated Power NXAIR. Flexible in Application, Consistent in Safety. Air-Insulated Medium-Voltage Switchgear NXAIR.

Totally Integrated Power NXAIR. Flexible in Application, Consistent in Safety. Air-Insulated Medium-Voltage Switchgear NXAIR. Totally Integrated Power NXAIR Flexible in Application, Consistent in Safety Air-Insulated Medium-Voltage Switchgear NXAIR www.siemens.com/nxair Totally Integrated Power (TIP) We bring power to the point

More information

Air-Insulated Medium-Voltage Switchgear NXAIR Totally Integrated Power NXAIR siemens.com/nxair

Air-Insulated Medium-Voltage Switchgear NXAIR Totally Integrated Power NXAIR siemens.com/nxair Flexible in Application, Consistent in Safety Air-Insulated Medium-Voltage Switchgear NXAIR Totally Integrated Power NXAIR siemens.com/nxair Totally Integrated Power (TIP) We bring power to the point Our

More information

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH SPECIFICATIONS FOR LOAD BREAK SWITCH This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE CODES

More information

sivacon Safety Embedded in Supreme Design: The Power Distribution Board, that sets new standards.

sivacon Safety Embedded in Supreme Design: The Power Distribution Board, that sets new standards. Safety Embedded in Supreme Design: The Power Distribution Board, that sets new standards. sivacon Everything. Perfect. With Low-Voltage Power Distribution by Siemens. SIVACON S4 the attractive power distribution

More information

Siemens Controls. The power distribution board that sets new standards. SIVACON S4 safe, cost-efficient and flexible SIVACON

Siemens Controls. The power distribution board that sets new standards. SIVACON S4 safe, cost-efficient and flexible SIVACON SIVACON The power distribution board that sets new standards SIVACON S4 safe, cost-efficient and flexible Siemens Controls Answers for infrastructure. Contents We support you with system 04 05 Maximum

More information

37-SDMS-01 REV. 03 SPECIFICATIONS FOR

37-SDMS-01 REV. 03 SPECIFICATIONS FOR 37-SDMS-01 REV. 03 SPECIFICATIONS FOR LOW VOLTAGE MOLDED CASE CIRCUIT BREAKERS FOR SERVICE CONNECTIONS This specification is property of SEC and subject to change or modification without any notice CLAUSE

More information

SGC switchgears compatible with real service conditions : Solutions that address on-site conditions Pieter Himpens

SGC switchgears compatible with real service conditions : Solutions that address on-site conditions Pieter Himpens SGC switchgears compatible with real service conditions : Solutions that address on-site conditions Pieter Himpens Pieter.Himpens@switchgearcompany.eu Frederik Delobelle Frederik.Delobelle@switchgearcompany.eu

More information

NPS/002/017 Technical Specification for 66 kv and 132 kv Cable Accessories

NPS/002/017 Technical Specification for 66 kv and 132 kv Cable Accessories Version:- 4.0 Date of Issue:- October 2016 Page 1 of 21 NPS/002/017 Technical Specification for 66 kv and 132 kv Cable Accessories 1. Purpose The purpose of this document is to detail the technical requirements

More information

Technical Specification for LV ABC Fuse Switch Disconnectors

Technical Specification for LV ABC Fuse Switch Disconnectors Ergon Energy Corporation Limited Technical Specification for LV ABC Fuse ETS-06-02-02 Check this is the latest Process Zone version before use. Specification ETS 06-02-02 Ver 3 Contents 1. Purpose and

More information

Also includes - Auxiliary Contacts & Shunt Trip - RCCB and - Distribution Boards

Also includes - Auxiliary Contacts & Shunt Trip - RCCB and - Distribution Boards As power distribution needs play a pivotal role in all the significant sectors namely Commercial, Industrial and Residential, improved Breaker performance through better electrical safety, higher operational

More information

SIS Solid Insulation System

SIS Solid Insulation System SIS Solid Insulation System Quality Security Progress Mühlberg 1 D 97514 Oberaurach-Kirchaich Germany Phone: +49 (0) 9549 / 89-0 Fax: +49 (0) 9549 / 89-11 E-mail: info@mwb-messwandler.de Parents companies:

More information

Power IT Compact Secondary Substations, CSS. Technical catalogue for sheet steel substations

Power IT Compact Secondary Substations, CSS. Technical catalogue for sheet steel substations Power IT Compact Secondary Substations, CSS Technical catalogue for sheet steel substations The New Standard for Individual Solutions The new CSS substations represent a unique concept, which is introducing

More information

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA 094: 2000 CEB STANDARD MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA Specification for MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEB Standard

More information

660 Volts 630 & 800AMP

660 Volts 630 & 800AMP Ergon Energy Corporation Limited Technical Specification for Switch- Disconnectors and Fuse-Switch- Disconnectors 660 Volts 630 & 800AMP ETS-06-02-01 Check this is the latest Process Zone version before

More information

The switchboard with a lot more. sivacon

The switchboard with a lot more. sivacon The switchboard with a lot more sivacon With integrated diagnostic function 4 for communications and more With integrated savings bank 5 for cost-effectiveness and more With amazing versatility 6 for flexibility

More information

Alvin.Xu, ABB Xiamen Switchgear Co,Ltd, Green & Energy saving concept of ABB MV apparatus For a better tomorrow.

Alvin.Xu, ABB Xiamen Switchgear Co,Ltd, Green & Energy saving concept of ABB MV apparatus For a better tomorrow. Alvin.Xu, ABB Xiamen Switchgear Co,Ltd, 2014-11 Green & Energy saving concept of ABB MV apparatus For a better tomorrow Slide 1 VD4 vacuum circuit-breaker in China Inheritance and innovation Y1992 Y2003

More information

New designed XLPE-insulated cables substituting paper-insulated pipe type cables

New designed XLPE-insulated cables substituting paper-insulated pipe type cables MODERN CABLE SYSTEMS IN STEEL PIPES New designed XLPE-insulated cables substituting paper-insulated pipe type cables Volker AUE, Nexans Deutschland Industries, Germany, Volker.Aue@nexans.com Wilfried ROSEBROCK,

More information

TABLE OF CONTENTS. FOREWORD... Error! Bookmark not defined. INTRODUCTION SCOPE NORMATIVE REFERENCES DRAWING...4

TABLE OF CONTENTS. FOREWORD... Error! Bookmark not defined. INTRODUCTION SCOPE NORMATIVE REFERENCES DRAWING...4 TITLE SPECIFICATION FOR FREE- STANDING 11 DATE: AUGUST 2006 PAGE: 1 OF 15 TABLE OF CONTENTS Page FOREWORD... Error! Bookmark not defined. INTRODUCTION...3 1 SCOPE...3 2 NORMATIVE S...3 3 DRAWING...4 4

More information

Prefabrication & Distribution A Global Solution GRC. Prefabricated Substation PARS TABLEAU

Prefabrication & Distribution A Global Solution GRC. Prefabricated Substation PARS TABLEAU Prefabrication & Distribution A Global Solution GRC Prefabricated Substation GRC We create tailor-made solutions adapted to your needs Because the methods, regulations, and needs are different in each

More information

093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA

093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA 093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA Specification for MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEB Standard 093 : 2000 CEYLON

More information

APDRP SCHEME, WESCO. Technical Specification for 33KV Air Break Switch PART 1: SCOPE AND CONDITIONS

APDRP SCHEME, WESCO. Technical Specification for 33KV Air Break Switch PART 1: SCOPE AND CONDITIONS PART 1: SCOPE AND CONDITIONS 1. SCOPE This specification covers the design, engineering, manufacture, testing, supply, delivery, off-loading and performance requirements of 33kV, 200 amp, triple pole Gang

More information

33-SDMS-02 SPECIFICATIONS FOR

33-SDMS-02 SPECIFICATIONS FOR SPECIFICATIONS FOR MV AUTOMATIC LINE SECTIONLIZER UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS SECTION T I T L E PAGE NO.

More information

The complete guide to transformers and packaged substations

The complete guide to transformers and packaged substations LAND LOGICAL POWER The complete guide to transformers and packaged substations Contents Land Logical Power transformers An introduction to the complete range of Land Logical Power transformers and package

More information

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv)

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv) Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators

More information

SUBJECT INTRODUCTION. EE ELECTRICAL MATERIAL SCIENCE SF6 and Vacuum Circuit Breaker

SUBJECT INTRODUCTION. EE ELECTRICAL MATERIAL SCIENCE SF6 and Vacuum Circuit Breaker SUBJECT INTRODUCTION EE 09506 ELECTRICAL MATERIAL SCIENCE EE04 CLASS 704: 1: POWER MODULE SYSTEM 1 III SF6 and Vacuum Circuit Breaker Module I Circuit Breakers : Principles of operation, different types

More information

Technical Specification for 12kV, 24kV and 36kV Disconnector (Isolators)

Technical Specification for 12kV, 24kV and 36kV Disconnector (Isolators) Ergon Energy Corporation Limited Technical Specification for 12kV, 24kV and 36kV Disconnector (Isolators) ETS06-05-01 Specification ETS06-05-01 Ver 4 Contents 1. Purpose and Scope... 1 2. References...

More information

SERIES 800 / 810 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTER ASSEMBLIES

SERIES 800 / 810 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTER ASSEMBLIES SERIES 800 / 810 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTER ASSEMBLIES MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT PADMOUNTED SWITCHGEAR WITH VACUUM LOAD INTERRUPTING

More information

SPECIFICATIONS FOR Gas-to-Cable termination

SPECIFICATIONS FOR Gas-to-Cable termination Product GSM-145 1.0 APPLICATION: Gas-to-cable termination is a part of high voltage gas insulated indoor switchgear equipment. The component is intended for a high voltage system of 132 kv (AC), 50 Hz.

More information

Metal-enclosed single busbar, Solid and Air-Insulated switchgear

Metal-enclosed single busbar, Solid and Air-Insulated switchgear Metal-enclosed single busbar, Solid and Air-Insulated switchgear IEC Medium Voltage Switchgear up to 24 kv Xiria E Extendable switchgear for distribution substations and commercial / industrial applications

More information

Insulated enclosure, +knockouts, RAL7032, HxWxD=500x375x225mm

Insulated enclosure, +knockouts, RAL7032, HxWxD=500x375x225mm DATASHEET - CI45E-200-RAL7032 Delivery program Insulated enclosure, +knockouts, RAL7032, HxWxD=500x375x225mm Part no. CI45E-200-RAL7032 Catalog No. 090160 EL-Nummer (Norway) 2502339 Dimensions mm Product

More information

Type THP Serial No Rated voltage 145 kv Rated normal current 2500 A Rated short-circuit current 40 ka Rated frequency 50/60 Hz

Type THP Serial No Rated voltage 145 kv Rated normal current 2500 A Rated short-circuit current 40 ka Rated frequency 50/60 Hz Object One compact switchgear assembly comprising a three-pole SF 6 circuit-breaker and a three-position disconnector/earthing switch, the circuit-breaker incorporating one interrupter per pole in single-pole

More information

TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1

TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1 I NDEPENDE N T POWER TR ANSM ISSION OP ER AT O R S.A. TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1 STRING INSULATOR

More information

Power evolution INNOVATION

Power evolution INNOVATION Power evolution INNOVATION simple ideas for great projects 1 3 2 9 1 2 3 Study of the cubicle lay-out in low voltage so as to suggest the most appropriate solution to the customer. FAST-ONE Study of the

More information

SELECTION GUIDE Appearance Sensing distance Operation Mode Connector Shape example (M8) Outer diameter (Ferrous material only) Wiring Output Output no

SELECTION GUIDE Appearance Sensing distance Operation Mode Connector Shape example (M8) Outer diameter (Ferrous material only) Wiring Output Output no Stainless Steel Sensing Face Proximity Switch Model FL7S The FL7S is a proximity switch having a stainless steel sensing face and housing, and is specially designed for welding applications on the automobile

More information

Environmental Pollution Caused by Electrical Power Devices

Environmental Pollution Caused by Electrical Power Devices Environmental Pollution Caused by Electrical Power Devices JOŽE PIHLER Power Engineering Laboratory University of Maribor, Faculty of Electrical Engineering and Computer Sciences Smetanova 17 SLOVENIA

More information

Technical Specification for. Insulators. Part 1. Insulators for High and Extra-High Voltage Overhead Lines

Technical Specification for. Insulators. Part 1. Insulators for High and Extra-High Voltage Overhead Lines Page: 1 / 18 for Insulators Part 1 Insulators for High and Extra-High Voltage Overhead Lines 1.2 Cap-and-pin insulators made of pre-stressed glass This technical specification is valid for the business

More information

Design Objective

Design Objective Design Objective 108-115096 Low profile 5A battery connector 2015.03.03 REV:A 1.0 Scope: 1.1 Content: This specification covers the requirements for product performance, test methods and quality assurance

More information

9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA

9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA 9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA Technical specification for 9KV/18KV 5KA Metal oxide Lightning Arrestors without Gap. ----------------------------------------------------------------------------------------------------------------

More information

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008 Revisions Notes Changed note Date 1 (A) Changed template 09 / 07 / 2008 2 Changed template. Clause 12.5.4.1 hot-rolled steel added. Clause 12.5.4.2, 12.5.2.4, 12.5.3.4, 12.5.4.4, 12.5.5.4, 12.5.6.4, 12.5.7.4

More information

Addendum - 2 for 11KV VCB Panel Specifications GETCO / E / TS HTPB 5401 / R1 Dt and GETCO / E / TS HTPB 5402 / R1 Dt

Addendum - 2 for 11KV VCB Panel Specifications GETCO / E / TS HTPB 5401 / R1 Dt and GETCO / E / TS HTPB 5402 / R1 Dt Addendum - 2 for 11KV VCB Panel Specifications GETCO / E / TS HTPB 5401 / R1 Dt. 25.01.12 and GETCO / E / TS HTPB 5402 / R1 Dt. 27.01.2012 Part - A 11KV Common Standard Busbar Configuration with Integrated

More information

THE NEXT GENERATION OF VACUUM INTERRUPTERS; USING A DESIGN FOR THE ENVIRONMENT APPROACH

THE NEXT GENERATION OF VACUUM INTERRUPTERS; USING A DESIGN FOR THE ENVIRONMENT APPROACH THE NEXT GENERATION OF VACUUM INTERRUPTERS; USING A DESIGN FOR THE ENVIRONMENT APPROACH Leslie T. Falkingham Alstom T&D UK leslie.falkingham@tde.alstom.com Martin Schlaug Alstom T&D - France martin.schlaug@tde.alstom.com

More information

Product Environmental Profile Premset 15 kv D02N, D06H and I06T functional units

Product Environmental Profile Premset 15 kv D02N, D06H and I06T functional units Medium Voltage Distribution Product Environmental Profile Premset 1 kv D02N, D06H and I06T functional units PE904 D02N D06H I06T Product Environmental Profile - PEP Product overview Premset 1 kv D02N and

More information

Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008

Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008 Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008 (Above 1000V and up to 38kV for Surface Mining) Key Components of Specification:

More information

Bulkhead Feed-throughs

Bulkhead Feed-throughs 38999 series III Bulkhead Feed-throughs Connectors and interconnect systems for harsh environments The company designs, manufactures and markets high performance interconnect solutions for severe environments

More information

SECTION SECONDARY UNIT SUBSTATIONS

SECTION SECONDARY UNIT SUBSTATIONS SECTION 26 12 16 SECONDARY UNIT SUBSTATIONS PART 1 GENERAL 1.1 SUMMARY This section describes metal-clad, indoor or outdoor, secondary unit substations with integral primary fused disconnect switches,

More information

Seismic-Resistant Switchboards Conforming to New Regulatory Standards Concerning Commercial Nuclear Reactors

Seismic-Resistant Switchboards Conforming to New Regulatory Standards Concerning Commercial Nuclear Reactors Seismic-Resistant Switchboards Conforming to New Regulatory Standards Concerning Commercial Nuclear Reactors KONNO, Masayuki * FUJIMOTO, Yoshio NAGASAWA, Takenori A B S T R A C T Nuclear power plants and

More information

15 15A 20 20A 30 30A 40 40A 60 60A VAC VAC VDC 24VAC VAC. 1 Single-phase. SRH VAC Zero cross turn-on

15 15A 20 20A 30 30A 40 40A 60 60A VAC VAC VDC 24VAC VAC. 1 Single-phase. SRH VAC Zero cross turn-on Features DIN rail mount or panel mount installation Dielectric strength: 4000 VAC High heat dissipation efficiency with ceramic PCB and integrated heatsink, random turn-on models available Input Indicator

More information

CCC Services for oil-filled- and XLPE-Cable Systems

CCC Services for oil-filled- and XLPE-Cable Systems sc CCC Services for oil-filled- and XLPE-Cable Systems Service Programme for Cable Systems As a supplier of MV- and HV-cable systems with several decades of experience, CCC GmbH Berlin offers the full

More information

1995 Metric CSJ SPECIAL SPECIFICATION ITEM Fiber Optic Dynamic Lane Control Sign

1995 Metric CSJ SPECIAL SPECIFICATION ITEM Fiber Optic Dynamic Lane Control Sign 1995 Metric CSJ 0353-03-077 SPECIAL SPECIFICATION ITEM 6143 Fiber Optic Dynamic Lane Control Sign 1.0 Description This Item shall govern for the furnishing and installation of Fiber Optic Dynamic Lane

More information

ROLINX Laminated Busbar. Design Rules Version 01 (12/2015)

ROLINX Laminated Busbar. Design Rules Version 01 (12/2015) ROLINX Laminated Busbar Design Rules Version 01 (12/2015) Content 1. Introduction... 03 7. Features... 13 2. Configuration...03 8. Thermal parameters... 14 3. Products... 04 9. General parameters... 14

More information

With uncoated stainless steel rope electrode and coated dynamic anchorage for level measurement of bulk-solid materials in higher silos.

With uncoated stainless steel rope electrode and coated dynamic anchorage for level measurement of bulk-solid materials in higher silos. průmyslová elektronika Capacitive level meters CLM 36 For continuous level measurement of liquid and bulk-solid materials Direct mounting into containers, silos, vessels, basins, reservoirs, etc Easy and

More information

PTC thermistors for degaussing

PTC thermistors for degaussing PTC thermistors for degaussing Series/Type: B59*** Date: March 2006 EPCOS AG 2006. Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained therein

More information

UHS 10kA Arrester. Certified Test Report IEC

UHS 10kA Arrester. Certified Test Report IEC CP No.: CP0606 Page 1 of 10 UHS 10kA Arrester Certified Test Report IEC 60099-4 2004 CERTIFICATION Statements made and data shown are, to the best of our knowledge and belief, correct and within the usual

More information

UNS 5kA Arrester. Certified Test Report IEC

UNS 5kA Arrester. Certified Test Report IEC CP No.: CP0504 Page 1 of 10 UNS 5kA Arrester Certified Test Report IEC 60099-4 2004 CERTIFICATION Statements made and data shown are, to the best of our knowledge and belief, correct and within the usual

More information

Gas-insulated medium-voltage switchgear 8DJH 36 siemens.com/8djh36

Gas-insulated medium-voltage switchgear 8DJH 36 siemens.com/8djh36 Compact and versatile Gas-insulated medium-voltage switchgear 8DJH 36 siemens.com/8djh36 We bring power to the point Left: Munich is one of the growth drivers in Germany. Urban centers offer chances for

More information

SECTION 1 SCOPE, SPECIFIC TECHNICAL REQUIREMENTS AND QUANTITIES

SECTION 1 SCOPE, SPECIFIC TECHNICAL REQUIREMENTS AND QUANTITIES Bihar State Electricity Board Bharat Heavy Electricals Ltd. 220 /132 kv Pusauli Substation & Dehri Extension Doc. No. TB-357-316-001, Rev 00 Technical Specification of 245kV & 145 kv Circuit Breaker SECTION

More information

An Insight into Design, Development & Testing of Insulation Piercing Connectors for LV Application

An Insight into Design, Development & Testing of Insulation Piercing Connectors for LV Application An Insight into Design, Development & Testing of Insulation Piercing Connectors for LV Application Introduction Designed for Indoor and outdoor applications Non-tension tap and splice applications Used

More information

DRAFT. GUIDELINES FOR Usage of AIR INSULATED SUBSTATION (AIS) or GAS INSULATED SUBSTATION(GIS)

DRAFT. GUIDELINES FOR Usage of AIR INSULATED SUBSTATION (AIS) or GAS INSULATED SUBSTATION(GIS) DRAFT GUIDELINES FOR Usage of AIR INSULATED SUBSTATION (AIS) or GAS INSULATED SUBSTATION(GIS) CENTRAL ELECTRICITY AUTHORITY 2018 1. Introduction Substations are an important part of the electrical distributions.

More information

42-SDMS-03 SPECIFICATIONS FOR

42-SDMS-03 SPECIFICATIONS FOR SPECIFICATIONS FOR INSIDE ROOM FIBER GLASS REINFORCED POLYESTER METER BOXES This specification is property of SEC and subject to change or modification without any notice CONTENTS Clauses: Page No. 1 SCOPE

More information

PTC thermistors for degaussing

PTC thermistors for degaussing PTC thermistors for degaussing Series/Type: B59*** Date: March 2006 EPCOS AG 2006. Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained therein

More information

31-SDMS-03 REV. 01 SPECIFICATIONS FOR

31-SDMS-03 REV. 01 SPECIFICATIONS FOR 31-SDMS-03 REV. 01 SPECIFICATIONS FOR LOW VOLTAGE CABINET FOR POLE MOUNTED TRANSFORMER This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Description

More information

PCN Change at Rast connector of EPCOS NTC thermistors

PCN Change at Rast connector of EPCOS NTC thermistors October 12, 2018 PCN Change at Rast connector of EPCOS NTC thermistors To further improve the EPCOS NTC thermistor series B57276K* and B57276Z* several changes at the Rast connectors of these sensors will

More information

NPS/001/003 Technical Specification for 11kV, 20kV and 33kV Overhead Line Air Break Switch-Disconnectors

NPS/001/003 Technical Specification for 11kV, 20kV and 33kV Overhead Line Air Break Switch-Disconnectors Document reference NPS/001/003 Document Type: Section Level Version:- 4.0 Date of Issue:- November 2015 Page 1 of 24 NPS/001/003 Technical Specification for 11kV, 20kV and 33kV Overhead Line Air Break

More information

High Speed... Rapid Temperature Change Rates with VTS & VCS Stress Screening Systems

High Speed... Rapid Temperature Change Rates with VTS & VCS Stress Screening Systems High Speed... Rapid Temperature Change Rates with VTS & VCS Stress Screening Systems Tested for absolute reliability... The testing of individual components ensures the reliability of your final product.

More information

Testing and Optimization

Testing and Optimization Testing and Optimization Company The EGELHOF Group Into the future with the right climate. As professionals in the sector of controls, the EGELHOF group has developed and produced expansion valves and

More information

www.eaton.eu\busbars Power Xpert XP2 Aluminium Eaton Power Xpert XP2 is a 1000 Volt totally encased, non-ventilated, low impedance sandwich construction. The range is available from 800A - 5000A with multiple

More information

NPS/003/001 Technical Specification for 33kV, 66kV and 132kV Voltage Transformers

NPS/003/001 Technical Specification for 33kV, 66kV and 132kV Voltage Transformers Version:- 5.0 Date of Issue:- February 2015 Page 1 of 25 NPS/003/001 Technical Specification for 33kV, 66kV and 132kV Voltage Transformers 1. Purpose This purpose of this document is to specify the technical

More information

Surge arrester 3EB4. with polymeric composite housing for operating aboard traction units

Surge arrester 3EB4. with polymeric composite housing for operating aboard traction units Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-33 77 19.00 40 (August 2016) --------------------------------- Preparing Activity: NASA Superseding UFGS-33 77 19.00 40 (August 2013) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Corrosion Chambers with Recirculating Air and Alternating Climate Control Salt Event SC/UKWT

Corrosion Chambers with Recirculating Air and Alternating Climate Control Salt Event SC/UKWT Corrosion Chambers with Recirculating Air and Alternating Climate Control Salt Event SC/UKWT Illustration is similar, contains options www.weiss-technik.com Test whatever you like. From boot to bonnet

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 220, 132 & 66 COMPOSITE SOLIDCORE STATION POST INSULATORS GETCO/E/2,1,6

More information

Surge arrester 3EQ3. contents to others without expressed authorization is prohibited. Offenders will be held liable

Surge arrester 3EQ3. contents to others without expressed authorization is prohibited. Offenders will be held liable Surge arrester 3EQ3 Operating instructions Order-No.: 928 00018 176a The copying, distribution and utilization of this document as well as the communication of its contents to others without expressed

More information

Focus on Wind Turbines LINAK.COM/TECHLINE WIND-AUTOMATION.COM

Focus on Wind Turbines LINAK.COM/TECHLINE WIND-AUTOMATION.COM Focus on Wind Turbines LINAK.COM/TECHLINE WIND-AUTOMATION.COM 2 Improving energy efficiency Global warming and the drive to minimise greenhouse gas emissions has put the focus on how to make the most of

More information

Amphenol Amphenol Taiwan Corporation Sheet 1 of 7

Amphenol Amphenol Taiwan Corporation Sheet 1 of 7 Amphenol Amphenol Taiwan Corporation Sheet 1 of 7 Title: Part Number: Description: Micro SD Card Connectors Product Specification GTFP08 SERIES Micro SD Card Connectors push-push type Revisions Control

More information

Surge arrester 3EB1. with polymeric composite housing for operating aboard traction units

Surge arrester 3EB1. with polymeric composite housing for operating aboard traction units Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders

More information

PowerEnergy MCC. Designed by the specialist for accidental arc fault protection!

PowerEnergy MCC. Designed by the specialist for accidental arc fault protection! PowerEnergy MCC Designed by the specialist for accidental arc fault protection! Safe power package up to 4000A The reliable supply of electrical energy increases the need for even safer and more efficient

More information

Power IT Compact Secondary Substations, CSS. Technical Brochure

Power IT Compact Secondary Substations, CSS. Technical Brochure Power IT Compact Secondary Substations, CSS Technical Brochure Substations from ABB Content Definitions In accordance with the EN 61330 standard, Prefabricated Secondary Substations are defined as substations

More information

CEG-200. Industrial X-Ray Tube

CEG-200. Industrial X-Ray Tube Industrial X-Ray Tube PRODUCT DESCRIPTION Maximum X-ray intensity is achieved by use of a beryllium window which is the only element of inherent filtration. The cathode operates at ground potential eliminating

More information

A SUBSTATION CONCEPT FOR CHANGEABLE LOAD CONDITIONS

A SUBSTATION CONCEPT FOR CHANGEABLE LOAD CONDITIONS A SUBSTATION CONCEPT FOR CHANGEABLE LOAD CONDITIONS Willy LORD SwedPower AB Sweden willy.lord@swedpower.com Lennart AHNLUND Vattenfall Eldistribution AB Sweden B. WALLBING-LÖVGREN Vattenfall Eldistribution

More information

It is standard practice and all manufacturers to abide by this. It is standard practice and all manufacturers to abide by this.

It is standard practice and all manufacturers to abide by this. It is standard practice and all manufacturers to abide by this. 1 162 General 2 162 General We recommend to specify door handle to singe shot latch type, bolted construction of Door shall not be acceptable. Closing and Tripping Coils shall be rated for continuous supply,

More information

Data sheet HYGROPHIL H 4230 process hygrometer

Data sheet HYGROPHIL H 4230 process hygrometer Data sheet HYGROPHIL H 4230 process hygrometer Continuous humidity measurement in industrial processes. HYGROPHIL H For very high demands in terms of being resistant to corrosion and dirt. Particularly

More information

Technical Specification for Helical Fittings for Overhead Power Lines

Technical Specification for Helical Fittings for Overhead Power Lines Ergon Energy Corporation Limited Technical Specification for Helical Fittings for Overhead Power Lines ETS01-09-03 Specification ETS01-09-03 Ver 3 Contents 1. Purpose and Scope... 4 2. References... 4

More information

ENGINEERING SPECIFICATION EE SPEC

ENGINEERING SPECIFICATION EE SPEC /. Company Directive ENGINEERING SPECIFICATION EE SPEC : 84/1 Relating to Surge Arresters EE SPEC : 84/1 20 December 2013-1 of 7 - IMPLEMENTATION PLAN Introduction This document defines the surge arresters

More information

Titre / Title HIGH RELIABILITY RF COAXIAL LOADS AND ATTENUATORS GENERIC SPECIFICATION

Titre / Title HIGH RELIABILITY RF COAXIAL LOADS AND ATTENUATORS GENERIC SPECIFICATION Date: May 13 th, 2011 ISSUE: 3 C PAGE: 1 / 18 Titre / Title HIGH RELIABILITY RF COAXIAL LOADS AND ATTENUATORS GENERIC SPECIFICATION Rédigé par / Written by Responsabilité / Responsibility Date Signature

More information

JUNCTION BOX AND BAYMARSHALLING KIOSK

JUNCTION BOX AND BAYMARSHALLING KIOSK JUNCTION BOX AND BAYMARSHALLING KIOSK September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata

More information

NPS/001/008 Technical Specification for Gapless Metal Oxide Surge Arresters

NPS/001/008 Technical Specification for Gapless Metal Oxide Surge Arresters Version:- 5.0 Date of Issue:- October 2017 Page 1 of 18 NPS/001/008 Technical Specification for Gapless Metal Oxide Surge Arresters 1. Purpose The purpose of this document is to detail the technical requirements

More information

Plasma Cutting System

Plasma Cutting System Plasma System Hiocus i The All-Rounder for Marking and from 0.5 to mm with Highest Productivity Soft-Switch-Inverter made in Germany Productivity - quality - flexibility: decisive in the competition Since

More information

PFS Underground Buildings for Transformer Substations Up to 36 kv

PFS Underground Buildings for Transformer Substations Up to 36 kv Transformer Substations PFS Underground Buildings for Transformer Substations Up to 36 kv PFS Underground Transformer Substation Buildings description The PFS building is a monoblock concrete enclosure

More information

6C-001 High-Voltage Pin-Type Insulator

6C-001 High-Voltage Pin-Type Insulator DISCLAIMER: This translation may be used for reference purpose only. This English version is not an official translation of the original Japanese document. In cases where any differences occur between

More information

METAL DETECTORS METAL DETECTORS

METAL DETECTORS METAL DETECTORS METAL DETECTORS METAL DETECTORS Metal detectors are specialized electronic devices that detect and mark the presence of any kind of metal (magnetic and nonmagnetic) impurities during the production process.

More information

General Requirements. Technical Specifications for Insulators of Transmission Lines

General Requirements. Technical Specifications for Insulators of Transmission Lines Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Insulators of Transmission

More information

ABSORPTION FILTERS FAP SERIES

ABSORPTION FILTERS FAP SERIES ABSORPTION FILTERS FAP SERIES INSTRUCTION MANUAL Cod. M - 981216-01A ------ Absorption filters FAP ------ Instructions Manual ------ Pág. 1 de 6 ------ 1 INTRODUCTION Absorption filters are designed to

More information

General CIRCUIT BREAKER WITH SF6 GAS

General CIRCUIT BREAKER WITH SF6 GAS General ETK Type Circuit Breakers: SF6 gas is used as insulating and arc quenching medium within ETK type circuit breakers. ETK breakers are suitable for rapid reclosing. Main Components:» Three separate

More information

MEDIZINTECHNIK FÜR TIERÄRZTE

MEDIZINTECHNIK FÜR TIERÄRZTE GB Tabel of contents: Operation Instructions Electronic Platfoorm Balances MEDIZINTECHNIK FÜR TIERÄRZTE 1 Technical data 17 2 Fundamental information (general) 18 2.1 Intended use 18 2.2 Inappropriate

More information

Corrosion Alternating Test Chambers SaltEvent SC/KWT

Corrosion Alternating Test Chambers SaltEvent SC/KWT Corrosion Alternating Test Chambers SaltEvent SC/KWT Test whatever you like. From boot to bonnet in research, development and quality control, you won t want to take any chances. We ll support you. Corrosion

More information

Knowledge is Power /SAFEGUARDING ASSETS AND PERFORMANCE THROUGH ONLINE MEASUREMENTS

Knowledge is Power /SAFEGUARDING ASSETS AND PERFORMANCE THROUGH ONLINE MEASUREMENTS Knowledge is Power /SAFEGUARDING ASSETS AND PERFORMANCE THROUGH ONLINE MEASUREMENTS A Small Investment to Generate Measurable Benefits Sometimes, solving challenges is surprisingly easy and cost effective.

More information

LMK 382. Stainless Steel Probe. Ceramic Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % FSO.

LMK 382. Stainless Steel Probe. Ceramic Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % FSO. Ceramic Sensor accuracy according to IEC 60770: standard: 0.5 % FSO option: 0.5 % FSO Nominal pressure from 0... 40 cmh O up to 0... 00 mh O Output signals -wire: 4... 0 ma -wire: 0 0 V others on request

More information

XMP i. Precision Pressure Transmitter for the Process Industry with HART -Communication. Stainless Steel Sensor

XMP i. Precision Pressure Transmitter for the Process Industry with HART -Communication. Stainless Steel Sensor Precision Pressure Transmitter for the Process Industry with HART -Communication Stainless Steel Sensor accuracy according to IEC 0770: 0. % FSO Nominal pressure from 0... 00 mbar up to 0... 00 bar Output

More information