Environmental Pollution Caused by Electrical Power Devices

Size: px
Start display at page:

Download "Environmental Pollution Caused by Electrical Power Devices"

Transcription

1 Environmental Pollution Caused by Electrical Power Devices JOŽE PIHLER Power Engineering Laboratory University of Maribor, Faculty of Electrical Engineering and Computer Sciences Smetanova 17 SLOVENIA Abstract: - This paper deals with environmental pollution caused by the operation of electrical power devices. This pollution can occur either during normal operation or in the cases of failures or mistakes. Such environmental pollution can be reduced and, in some cases, fully prevented by the adequate awareness of individuals, responsible behaviour by the consumers and manufacturers of these devices, and by adequate legislation and standards by governments and professional associations. This paper presents some concrete proposals from the field of medium and high voltage power devices. Key-Words: - electrical power apparatus, devices, insulation media, arc-extinguishing medium, pollution, ecosystems 1 Introduction Electrical power apparatus are basic elements within any electrical power system. They exist in power plants, as 400, 220 or 110 kv transmission networks, connected to 110, 20 or 10 kv distribution networks through substations. The latter are through distribution substations connected to the low voltage electricity networks of consumers. In addition to the abovementioned, there are also many substations with electrical power devices within industrial and other electricity consumers` internal networks. Electrical power devices and apparatus consist of electricity-conducting parts, and insulation-parts, that separate the conducting from the earthed parts. The earthed-parts are those protective elements or housings that prevent people when handling their devices from coming into direct contact with the energised parts of electrical power devices. At the same time their role can also be to prevent failures, such as line to ground faults, throughout the grid or to other devices. The insulation parts can be made of solid, liquid or gaseous dielectric materials. Insulation materials can have an important impact on the functional operation of a device, for example as an arcextinguishing medium. This paper deals with the possibility of replacing electrical power devices` insulation material and thus reducing or preventing environmental pollution. Section 2 describes the impact of electrical power devices` operations on the environment. It presents the insulation, cooling, and arcextinguishing media. Section 3 deals with those methods that could prevent environmental pollution caused due to the operation of electrical power devices. Special emphasis is given to improving environmental impacts during the operation of power devices based on SF 6 gas. Practical possibilities are given especially within the medium of voltage devices and apparatus. Section 4 contains the conclusion. 2 Impacts of electrical power devices` operations on the environment Each electrical power device consists of individual elements, such as switches, fuses, surge arresters, insulation elements (insulators and bushings), switchgear, i.e. the housing where all these elements are mounted, conductors or bus bars connecting conductive parts and insulation medium. Electrical power devices can basically be divided into devices for indoor and outdoor usages. These devices are considerably different with regard to voltage-levels and insulation media. Low voltage devices of up to 1 kv are mainly air-insulated. Medium voltage devices up to 35 kv are air-insulated, as shown in Fig. 1, or are SF 6 insulated. Both low and medium voltage devices for indoor use are placed within areas that are either parts of other buildings or are individual buildings. For outdoor devices single-elements are used that have to comply with the requirements for outdoor usage, especially regarding atmospheric conditions. They ISBN:

2 are placed on various poles or on special constructions. High voltage devices above 110 kv are those devices that are air-insulated as individual elements, and are used outdoor. They can also be SF 6 gas-insulated and used indoors. Switchingoperative devices are needed for performing their principal task interruption of an electrical current the arc-extinguishing medium. The latter can be air, oil, or of various gases. Important elements of electrical power systems are also power transformers and measurement transformers. They also need insulation and cooling media, which can be either air, oil, or various gases. 2.1 Insulation, cooling, and arc-extinguishing media of electrical power devices Electrical devices can have harmful impacts on the environment in those cases of non-operational, normal operation, and malfunctioning. These harmful impacts can be caused by cooling, insulation, and arc-extinguishing media. An example is transformer oil. Conventional transformer oils were inflammable and poisonous. When leaking into the environment, they caused environmental pollution and became a danger to living creatures. Today's mineral synthetic oils, however do have significantly-improved characteristics. Switching devices at all voltage levels interrupt and re-connect electrical circuits. These chambers make sure that the electrical arc is extinguished at a predefined time, which ultimately interrupts an electric current. An essential role is played by the arc-extinguishing medium. There are several methods for extinguishing and various arcextinguishing media. In switch-disconnector and older circuit-breakers this is compressed air. In other switch-disconnectors an important role is played by arc-extinguishing chambers with solid insulation materials. These insulation materials were gasified and ultimately extinguished the electrical arc (Fig. 2). Fig. 2: Switch-disconnector with arc-extinguishing chambers made of solid dielectric materials. Fig. 1: Air-insulated metal-clad switchgear within insulation walls, and a low oil circuit-breaker. SF 6 gas was introduced, as an upgrade of these switch-disconnectors. During the development of circuit-breakers arc-extinguishing chambers firstly phase contained compressed air and transformer oil. In the first phase of development this chamber was a vessel in which the device was submerged. During the development continuation phases, the arcextinguishing chambers were separately, topped-up with oil for each phase. As a result of this development work a low-oil circuit-breaker appeared (apparatus shown in Fig. 1). The essential advantage of such a device is that it is less harmful to the environment due to its significantly-lower quantity of oil. In Europe such devices are still massively used, although they are no longer installed in new buildings. Vacuum circuit-breakers within the middle-voltage area and SF 6 circuitbreakers within medium voltage area followed on low-oil circuit-breakers in Europe. In America, and partly in the UK, these circuit-breakers were the successors of compressed-air circuit-breakers. During the first period of development in Europe low-oil circuit-breakers were deployed at the 110 kv voltage level in the high voltage area. Many of these circuit-breakers are still in operation. SF 6 circuit-breakers became the successors of these devices. Switchgears were, in the early-phases of their usage, almost exclusively air-insulated. In later years, manufacturers started to add various solid dielectric materials composed of duroplast or thermoplast materials as walls for separating ISBN:

3 individual switchgear elements, as shown in Fig. 1. The positive effect was to reduce sizes. On the other hand, the negative effect was ozone production during normal operations, respectively causing burning and fires in the event of failures. SF 6 gas was introduced during the 1990`s as an insulation medium in medium-voltage switchgears, which led to a significant reduction in the devices' sizes. The disadvantage of using SF 6 gas was the pollution of environment, and negative impact on living beings. When speaking about environmental pollution it is necessary to mention the so called electromagnetic pollution. This refers to the impact of electrical and magnetic fields on living beings. There have been many theoretical and practical discussions about this issue. The European Union itself and individual Member States have imposed legal obligations about the maximum permitted values of electrical field strengths and magnetic flux densities in new buildings. This area also includes the operation of electrical power networks, where partial discharges occur in the forms of visible and audible corona. These discharges appear due to the improperly-designed individual elements of devices and conductors. Due to high-frequencies they strongly affect the wellbeing's of nearby residents. Qualities of their lives are greatly reduced. In continuations, a short presentation of today`s most widely-used insulation and arc-extinguishing medium SF 6, is given SF 6 gas as an insulation and arcextinguishing medium Sulphur hexafluoride (SF 6 ) is an almost ideal gas for usage in high voltage switchgear equipment and metal-clad systems. It has excellent electrical (insulation and extinguishing of electric-arcs) and thermal properties. SF 6 gas is produced by a direct chemical reaction between molten sulphur and fluorine, which is produced by the electrolysis of HF acid. The properties of produced gas have to comply with the requirements of IEC [1], which defines the permitted levels of impurities. The annual worldwide production of this gas is between 4,000 and 8,000 tonnes. The main use of this gas is as a filling in switching-devices. The technical advantages of SF 6 insulated switching-devices are generally well-known: insensitivity to environmental impacts (dirt, moisture, access to animals, etc.), safety for people working with them, long-lifespans, very little maintenance needed, small sizes, etc. Pure SF 6 is a non-poisonous and inflammable gas without colour and odour. Its density at 20 C within an atmospheric pressure of MPa amounts to 6,135 kg/m 3. SF 6 has an approximately five-times higher density than air, which means that it tends to accumulate within lower-lying areas, such as cable canals or vessel-bottoms. If larger amounts of this gas accumulate with closed-areas, there is a danger of suffocation. The dielectric strength of SF 6, is under the same conditions, approximately 2.5-times higher than for air, which means that the sizes of the devices can be 2.5-times smaller. At a pressure of 300 kpa, SF 6 gas insulates better than oil. SF 6 gas has certain disadvantages, such as: As insulation medium it is sensitive to appearance of points with high electric field strength, therefore it is very important that surfaces are smooth and high quality processed; As arc-extinguishing medium it forms during the burning phase of electric arc some products that are for long time poisonous for living beings; SF 6 is a greenhouse gas and has the highest greenhouse potential of all greenhouse gases, amounting to 23,900 (which means that 1 kg of SF 6 has the same greenhouse effect as 23.9 tonnes of CO 2 ). In addition to this, SF 6 has a very long atmospheric lifetime, ranging from a few thousands to more than ten thousand years (the longest atmospheric lifetime has CF 4, which stays in the atmosphere for up to 50,000 years). Because of the abovementioned disadvantages and massive use in electrical power devices there have been some initiatives in the recent years to limit the use of SF 6, to prevent its leakage, to capture all SF 6 from decommissioned devices and to replace SF 6 with other gases having lower greenhouse potential. 3 Prevention of environmental pollution caused by electrical power devices Electrical power devices are the most important parts of electrical power systems. They have to operate reliably and continuously. The total prevention of environmental pollution due to their operation is impossible. Nevertheless, it is possible to reduce it and in some cases even to prevent harmful impacts on the environment. The most important thing is to be aware of this fact and to act towards achieving this objective. This is a difficult task in this global world that is dictated to by multinational companies that have only one objective: to maximise their profits. An important ISBN:

4 role in this should be played by governments, professional associations, and nongovernmental organisations (NGOs). A possibility positive action towards the prevention of environmental pollution is discussed below in the case of using harmful SF 6 gas as an insulation and arc-extinguishing medium. The focus of this discussion is on medium-voltage devices. In high-voltage devices for outdoor usage air-insulated devices represent an alternative to SF 6 -insulated ones. This is unfortunately impossible in densely populated areas. High-voltage SF 6 circuit-breakers still have no alternative. 3.1 Mitigation of environmental impacts during the operation of SF 6 -insulated electrical power devices Professional associations, civil, and NGOs in Europe, America and Japan share the same opinion about the harmful impact of SF 6 -gas on the environment. Nevertheless, each sees their own way of solving the problem. Some thoughts and facts are presented in the continuation Governmental level In Europe especially there are increased activities at the governmental level. These activities mostly comprise the adoption of legislation (directives and regulations [2], [3], [4]), the aims of which are to make manufacturers and buyers aware of certain facts regarding SF 6 gas. Some regulations already exist about the requirements for reducing the usage of SF 6 and how to achieve this goal. In some areas the use of SF 6 gas is already prohibited and there are sanctions prescribed for breaching these provisions. The area of usage within electrical power devices is not yet one of them. In the field of standardisation (national, European EN and international IEC) [1],[5],[6],[7] there are already have some valid documents standards that more or less-precisely define the use of SF 6, by giving instructions for the designing of devices using this gas, monitoring of the operations, and for decommissioning after the ends of their lifespans. As is evident from American Standards, at the moment they are in a phase of adopting adequate standards that define this area in detail. Nevertheless, they already have some IEC standards that are more or less recommendations, but give only mild warnings to manufacturers and buyers about the issue of using SF 6 gas [8] Research & Development organisations New devices are being developed and designed especially in the field of medium voltage devices, where gas as an insulation medium is replaced by solid dielectrics and by a vacuum in combination with dry air and with solid insulation materials as an arc-extinguishing medium. In Japan [9] they use a special kind of resin for the fixed and silicone for the moving parts, which has led to a reduction in size for 25 %. Japanese, and some European researchers, [10] studying the possibility of SF 6 gas usage by adding other gases, such as helium, nitrogen, hydrogen, etc., both as arc-extinguishing and insulation mediums. The best results regarding insulation properties are being achieved by helium (Fig. 3). Fig. 3: Dielectric strengths [V/m] of various mixtures of SF 6 and helium in the case of an electrical arc with an arc tube of 2.5 mm Manufacturers of switching-devices and apparatus Manufacturers of switching-devices and apparatus are divided into two groups. In the first group there are manufacturers who still produce mediumvoltage devices with SF 6 as insulation and an arcextinguishing medium, and take the position that there is no need to stop or reduce the usage of this technology. The other group consists of manufacturers who have never used this technology (Northern Europe) or are switching to other technologies, which is clearly the case in Japan and some other parts of the world. An interesting alternative to medium-voltage SF 6 devices is thus being offered by those producers who make dry-air and solid insulation materials as an insulation medium (Fig. 4). Their sizes are even smaller than in the case of SF 6 switchgear blocks Professional associations Professional associations (CAPIEL, EPA ) [11] channel their efforts into making ISBN:

5 manufacturers and buyers aware about the importance of careful and safe-handling regarding SF 6 gas, and the need to reduce unnecessary and adverse emissions of SF 6 gas into the environment. They also place a great emphasis on safely decommissioning these devices after the ends of their lifespans. Fig. 4: RMU switchgear-block with dry-air and solid insulation materials as an insulation medium Environmental associations Environmental Associations claim that the usage of materials such as SF 6 gas should be stopped immediately. 3.2 Mitigation of environmental impacts caused by electrical power devices by other insulation, cooling, and arc-extinguishing media The insulation and arc-extinguishing media of medium voltage circuit-breakers are, in most cases vacuum, as it has replaced the environmentallyproblematic transformer oil. Some manufacturers still manufacture SF 6 circuit-breakers. Even in switch-disconnectors that contained transformer-oil, it has been replaced arc-extinguishing chambers by vacuums. In switchgears, insulation-walls (Fig. 1) made of plastic materials have been replaced by metal-clad cells with metal walls. This is an essential advantage especially in the cases of failures. It is almost impossible for these materials to burn, since any short circuit fault turns into a line-to-ground fault (metal partition wall is earthed), and a protection system within a minimum possible time, switches the device off. Conventional transformer oils in power transformers have been replaced by modern mineral and synthetic oils that are much less harmful to the environment. 4 Conclusions This paper dealt with those harmful impacts to the environment that can be caused by the operation of electrical power devices and apparatus. An important conclusion is that these impacts can be mitigated or even prevented, although these devices keep operating reliably without interruptions. It is very important to take into consideration the research and development achievements of science and those researchers who work for the manufacturers of electrical power equipment. An important role in this can also be played by governments, which have to adopt adequate legislation to incentivise, and in some cases, even force manufacturers and users not to forget the environmental protection aspect of their business decisions. At medium-voltage levels, SF6 gas may be prohibited for use in switchgear. However, there are solutions to the full replacement of SF6 gas as insulation and as an arc-extinguishing medium. In high-voltage switchgear the amount of gas SF6 could be reduce by adding helium and nitrogen. Further improvement could also be achieved by preventing the release of SF6 gas during the operating of circuit-breakers. References: [1] IEC 60376:2005, Specification of technical grade sulphur hexafluoride for use in electrical equipment. [2] REGULATION (EC) No 842/2006 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 17 May 2006, on certain fluorinated greenhouse gases [3] COMMISSION REGULATION (EC) No 1494/2007 of 17 December 2007 establishing, pursuant to Regulation (EC) No 842/2006 of the European Parliament and of the Council, the form of labels and additional labelling requirements as regards products and equipment containing certain fluorinated greenhouse gases. [4] COMMISSION REGULATION (EC) No 1493/2007 of 17 December 2007 establishing, pursuant to Regulation (EC) No 842/2006 of the European Parliament and of the Council, the format for the report to be submitted by ISBN:

6 producers, importers and exporters of certain fluorinated greenhouse gases. [5] IEC/TR ( ) High-voltage switchgear and controlgear - Part 303: Use and handling of sulphur hexafluoride (SF 6 ). [6] IEC 60480: Guidelines for the checking and treatment of sulphur hexafluoride (SF6) taken from electrical equipment and specification for its re-use [7] IEC/TR ( ) Ed. 1.0 Bilingual High-voltage switchgear and controlgear - Part 303: Use and handling of sulphur hexafluoride (SF 6 ). [8] IEEE Std C , IEEE Standard for Gas-Insulated Substations, Sponsor Substations Committee of the IEEE Power Engineering Society Approved December 2, 1993 (Revision of IEEE Std C , includes IEEE Std C37.122a-1991). [9] J. Sato, O Sakaguchi, N. Kubota, New technology for medium voltage solid insulated switchgear, Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES, Vo. 3 pp , [10] Hiromi Odaka, Masayuki Taki, Hitoshi Mizoguchi, Satoru Yanabu, Discussion about an Application of CF3I gas as a substitute gas for SF 6 gas, ISSN: , vol. 126, no.5, pages: (2006), Japan. [11] CAPIEL - Co-ordinating Committee for the Associations of Manufacturers of Industrial Electrical Switchgear and Controlgear in the European Union. ISBN:

* 1 Engr. Muhammad Junaid, 2 Engr. Mehran Tahir, 3 Engr. Kamal Haider, * 4 Engr. Muhammad Aamir

* 1 Engr. Muhammad Junaid, 2 Engr. Mehran Tahir, 3 Engr. Kamal Haider, * 4 Engr. Muhammad Aamir International Journal of Engineering & Computer Science IJECS-IJENS Vol:13 No:03 16 HVAC Breakdown of R12, R12 Air Mixtures in Sphere gap Electrodes and Proposed Composite insulating Liquid to Reduce the

More information

Gas-insulated medium-voltage switchgear. for wind parks. Answers for energy.

Gas-insulated medium-voltage switchgear. for wind parks. Answers for energy. Gas-insulated medium-voltage switchgear for wind parks Answers for energy. Switchgear for wind turbines: 8DH10 up to 24 kv, up to 20 ka, up to 1,250 A up to 17.5 kv, up to 25 ka, up to 1,250 A Best performance

More information

INNOVATIVE LIFE-CYCLE CONCEPTS FOR MEDIUM-VOLTAGE SWITCHGEAR ON BROWN COAL SURFACE MINING DEVICES

INNOVATIVE LIFE-CYCLE CONCEPTS FOR MEDIUM-VOLTAGE SWITCHGEAR ON BROWN COAL SURFACE MINING DEVICES INNOVATIVE LIFE-CYCLE CONCEPTS FOR MEDIUM-VOLTAGE SWITCHGEAR ON BROWN COAL SURFACE MINING DEVICES Dr. S. Ruhland, Dr. U. Riedl ALSTOM Sachsenwerk GmbH, Germany The requirements for medium voltage switchgear

More information

Study Committee A3. High Voltage Equipment. Action Plan

Study Committee A3. High Voltage Equipment. Action Plan Study Committee A3 High Voltage Equipment Action Plan October 2011 CIGRE Study Committee A3 - High Voltage Equipment Action Plan 1 Content 1 Content...2 2 Purpose of the Action Plan...3 3 Activities of

More information

CCC Services for oil-filled- and XLPE-Cable Systems

CCC Services for oil-filled- and XLPE-Cable Systems sc CCC Services for oil-filled- and XLPE-Cable Systems Service Programme for Cable Systems As a supplier of MV- and HV-cable systems with several decades of experience, CCC GmbH Berlin offers the full

More information

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

B. Provide liquid-filled secondary substation transformers as indicated on drawings. SECTION 26 12 13 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 26 05 00. B. Provide liquid-filled secondary substation transformers as indicated on drawings. 1.02 RELATED

More information

Gas-insulated medium-voltage switchgear. for marine and offshore applications. Answers for energy.

Gas-insulated medium-voltage switchgear. for marine and offshore applications. Answers for energy. Gas-insulated medium-voltage switchgear for marine and offshore applications Answers for energy. 8DH10 switchgear up to 24 kv, up to 20 ka, up to 1,250 A up to 17.5 kv, up to 25 ka, up to 1,250 A Full

More information

Thermal Recovery Characteristics of a CO 2 Mixture Gas Circuit Breaker

Thermal Recovery Characteristics of a CO 2 Mixture Gas Circuit Breaker J Electr Eng Technol.2016; 11(?): 1921-718 http://dx.doi.org/10.5370/jeet.2016.11.3.1921 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 Thermal Recovery Characteristics of a CO 2 Mixture Gas Circuit Breaker

More information

Instruction guide Medium Voltage equipment on sites exposed to high humidity and/or heavy pollution. Recommendations for installation and use

Instruction guide Medium Voltage equipment on sites exposed to high humidity and/or heavy pollution. Recommendations for installation and use Medium Voltage equipment on sites exposed to high humidity and/or heavy pollution Recommendations for installation and use Contents Introduction 2 Use of MV equipment 2 Normal service conditions for indoor

More information

PRY-MOULD. High Voltage Accessories for Extruded Cables

PRY-MOULD. High Voltage Accessories for Extruded Cables PRY-MOULD High Voltage Accessories for Extruded Cables Linking the future As the worldwide leader in the cable industry, Prysmian Group believes in the effective, efficient and sustainable supply of energy

More information

A unique SF6 supply and recovery service from BOC

A unique SF6 supply and recovery service from BOC sulphur hexafluoride A unique SF6 supply and recovery service from BOC Sulphur hexafluoride (SF 6 ) a unique product SF 6 is a gas with unusual properties that make it ideal for a wide range of applications.

More information

DISTRIBUTION OPERATIONS AND MAINTENANCE

DISTRIBUTION OPERATIONS AND MAINTENANCE EB-00-0 Exhibit F Schedule Page of 0 DISTRIBUTION OPERATIONS AND MAINTENANCE PREVENTIVE MAINTENANCE Preventive Maintenance is intended to maintain or improve customer service reliability, extend equipment

More information

The complete guide to transformers and packaged substations

The complete guide to transformers and packaged substations LAND LOGICAL POWER The complete guide to transformers and packaged substations Contents Land Logical Power transformers An introduction to the complete range of Land Logical Power transformers and package

More information

Quantifying the Economic Benefits of Online Monitoring

Quantifying the Economic Benefits of Online Monitoring Quantifying the Economic Benefits of Online Monitoring Neil DAVIES Dr Paul BLACKMORE Ying Wang EA Technology UK EA Technology Australia EA Technology Australia Neil.Davies@ eatechnology.com Paul.Blackmore@

More information

Friday, May 29, Update on Testing Medium Voltage Cable and Switchgear Systems

Friday, May 29, Update on Testing Medium Voltage Cable and Switchgear Systems Update on Testing Medium Voltage Cable and Switchgear Systems Friday, May 29, 2015 Presented by: Ashley Harkness Ashley.Harkness@Emerson.com Electrical Reliability Services Value--- When we find the one

More information

NZQA registered unit standard version 3 Page 1 of 5. Demonstrate and apply advanced knowledge of power system engineering

NZQA registered unit standard version 3 Page 1 of 5. Demonstrate and apply advanced knowledge of power system engineering Page 1 of 5 Title Demonstrate and apply advanced knowledge of power system engineering Level 6 Credits 15 Purpose This unit standard covers knowledge of three-phase power systems with an emphasis on distribution

More information

12th HSBC SRI Conference February 2017

12th HSBC SRI Conference February 2017 12th HSBC SRI Conference 2017 February 2017 Cautionary statement This presentation contains certain statements that are neither reported financial results nor other historical information. These statements

More information

THE NEXT GENERATION OF VACUUM INTERRUPTERS; USING A DESIGN FOR THE ENVIRONMENT APPROACH

THE NEXT GENERATION OF VACUUM INTERRUPTERS; USING A DESIGN FOR THE ENVIRONMENT APPROACH THE NEXT GENERATION OF VACUUM INTERRUPTERS; USING A DESIGN FOR THE ENVIRONMENT APPROACH Leslie T. Falkingham Alstom T&D UK leslie.falkingham@tde.alstom.com Martin Schlaug Alstom T&D - France martin.schlaug@tde.alstom.com

More information

Alvin.Xu, ABB Xiamen Switchgear Co,Ltd, Green & Energy saving concept of ABB MV apparatus For a better tomorrow.

Alvin.Xu, ABB Xiamen Switchgear Co,Ltd, Green & Energy saving concept of ABB MV apparatus For a better tomorrow. Alvin.Xu, ABB Xiamen Switchgear Co,Ltd, 2014-11 Green & Energy saving concept of ABB MV apparatus For a better tomorrow Slide 1 VD4 vacuum circuit-breaker in China Inheritance and innovation Y1992 Y2003

More information

International Standard Corresponding Indian Standard Degree of Equivalence

International Standard Corresponding Indian Standard Degree of Equivalence BUREAU OF INDIAN STANDARDS DRAFT FOR COMMENTS ONLY Doc: ET 28 (6756) (Not to be reproduced without the permission of BIS or used as a STANDARD) Draft Indian Standard PHOTOVOLTAIC (PV) ARRAYS DESIGN REQUIREMENTS

More information

Research of Evaluation Index System of the Development and Construction of Two-type Transformer Substation

Research of Evaluation Index System of the Development and Construction of Two-type Transformer Substation Research of Evaluation Index System of the Development and Construction of Two-type Transformer Substation Dongxiao Niu, Hui Shi & Jianqing Li School of Economics and Management, North China Electric Power

More information

Introduction to Substation Design TADP 542

Introduction to Substation Design TADP 542 Introduction to Substation Design TADP 542 Design Principles- General Framework Instructor: Richard Snell Transmission & Distribution Program Module 2 Outline Presentation 1: General Framework Presentation

More information

R.K.Yadav/Automobile Engg Dept/New Polytechnic Kolhapur. Page 1

R.K.Yadav/Automobile Engg Dept/New Polytechnic Kolhapur. Page 1 Fuel : A fuel is defined as a substance (containing mostly carbon and hydrogen) which on burning with oxygen in atmospheric air, produces a large amount of heat. fuel. The amount of heat generated is known

More information

Design features - Polymer-housed arresters, PEXLIM

Design features - Polymer-housed arresters, PEXLIM features - Polymer-housed arresters, PEXLIM PEXLIM arresters, using the same ZnO blocks as the EXLIM arresters, match their electrical performance. Silicone as outer insulation material has been used for

More information

Operating Instructions Plasma generator PG31

Operating Instructions Plasma generator PG31 Operating Instructions Plasma generator PG31 BA-PG31_EN / F0298601 We are pleased that you decided on a brand device from relyon plasma GmbH and thank you for the trust you have placed in our company.

More information

Future Challenges for the Grid - Integration of environment friendly gasinsulated. B. Lutz, M. Kuschel, P. Glaubitz Siemens AG Germany

Future Challenges for the Grid - Integration of environment friendly gasinsulated. B. Lutz, M. Kuschel, P. Glaubitz Siemens AG Germany PS3 Advances in substation technology and reliability Future Challenges for the Grid - Integration of environment friendly gasinsulated substations B. Lutz, M. Kuschel, P. Glaubitz Siemens AG Germany SUMMARY

More information

ELECTRICAL INSPECTION BULLETIN (Effective )

ELECTRICAL INSPECTION BULLETIN (Effective ) ELECTRICAL INSPECTION BULLETIN (Effective 2009-02-01) Rule 36-000 Customer Owned High Voltage Installations With the increase in customer own high voltage equipment there appears to be confusion over which

More information

WC / Ag Contact Materials with Improved Homogeneity

WC / Ag Contact Materials with Improved Homogeneity 200 RM 20 R. Grill et al. WC / Ag Contact Materials with Improved Homogeneity Robert Grill 1, Peter Kläusler ², Frank E.-H. Mueller², Oswald Schrott³, Hans Hauser ³ 1 Plansee Aktiengesellschaft, A-6600

More information

Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008

Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008 Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008 (Above 1000V and up to 38kV for Surface Mining) Key Components of Specification:

More information

Investigation of leakage current flow through wooden poles structures on overhead distribution system

Investigation of leakage current flow through wooden poles structures on overhead distribution system Proceedings of the 7th WSEAS International Conference on Power Systems, Beijing, China, September 15-17, 2007 120 Investigation of leakage current flow through wooden poles structures on overhead distribution

More information

Environmental aspects of the use of Sulphur Hexafluoride

Environmental aspects of the use of Sulphur Hexafluoride Environmental aspects of the use of Sulphur Hexafluoride A H Powell ERA Report 2002-0002 ERA Project 86CC0640A Published Client : ERA Information Services ISBN : 0 7008 0752 7 ERA Report Checked by: Approved

More information

Surge arrester 3EB4. with polymeric composite housing for operating aboard traction units

Surge arrester 3EB4. with polymeric composite housing for operating aboard traction units Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders

More information

U.S. Emissions

U.S. Emissions PSEG Voluntary Greenhouse Gas Emissions Inventory 2000 2006 U.S. Emissions Public Service Enterprise Group (PSEG) 80 Park Plaza Newark, NJ 07102 www.pseg.com October 2007-1- Printed on Recycled Paper Table

More information

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Revised European F-Gas Regulation

Revised European F-Gas Regulation A BARBOUR GUIDE The Official BIFM Information Service Partner 01 Background Current Position Fluorinated Greenhouse Gases Fluorinated gases (F-gases) are a family of man-made gases used in a range of industrial

More information

SWITCHGEAR MONITORING SYSTEM-ASSISTANCE IN MAINTENANCE AND CALCULATION OF THE COSTS

SWITCHGEAR MONITORING SYSTEM-ASSISTANCE IN MAINTENANCE AND CALCULATION OF THE COSTS SWITCHGEAR MONITORING SYSTEM-ASSISTANCE IN MAINTENANCE AND CALCULATION OF THE COSTS Ana Mik Končar-Electrical Engineering Institute anamik@koncar-institut.hr Krešimir Meštrović Končar-Electrical Engineering

More information

4. POINTS ON SWITCH AND CIRCUIT BREAKER PLATFORM GROUNDING.

4. POINTS ON SWITCH AND CIRCUIT BREAKER PLATFORM GROUNDING. 4. POINTS ON SWITCH AND CIRCUIT BREAKER PLATFORM GROUNDING. 4.1 All equipment (i.e., switches, breakers, control cabinets, etc.) inside switchyards or substations which require operations by workers must

More information

A SUBSTATION CONCEPT FOR CHANGEABLE LOAD CONDITIONS

A SUBSTATION CONCEPT FOR CHANGEABLE LOAD CONDITIONS A SUBSTATION CONCEPT FOR CHANGEABLE LOAD CONDITIONS Willy LORD SwedPower AB Sweden willy.lord@swedpower.com Lennart AHNLUND Vattenfall Eldistribution AB Sweden B. WALLBING-LÖVGREN Vattenfall Eldistribution

More information

sion lines: tower foot resistance, current division between ground and aerial earth wires, division of earth currents at substations.

sion lines: tower foot resistance, current division between ground and aerial earth wires, division of earth currents at substations. EEP201 Fundamentals of Power System Earthing This module is currently under revision. and mesh potentials. sion lines: tower foot resistance, current division between ground and aerial earth wires, division

More information

AGREEMENT FOR CONNECTION TO [EASTERN /LONDON / SOUTH EASTERN] POWER NETWORKS PLC S DISTRIBUTION SYSTEM

AGREEMENT FOR CONNECTION TO [EASTERN /LONDON / SOUTH EASTERN] POWER NETWORKS PLC S DISTRIBUTION SYSTEM AGREEMENT FOR CONNECTION TO [EASTERN /LONDON / SOUTH EASTERN] POWER NETWORKS PLC S DISTRIBUTION SYSTEM BETWEEN AND (1) [Eastern / London / South Eastern] Power Networks plc Company Number [02366906 / 03929195

More information

IMPLEMENTATION RULES FOR COMPULSORY CERTIFICATION OF ELECTRICAL AND ELECTRONIC PRODUCTS

IMPLEMENTATION RULES FOR COMPULSORY CERTIFICATION OF ELECTRICAL AND ELECTRONIC PRODUCTS Ref. No. CNCA-01C-011: 2007 IMPLEMENTATION RULES FOR COMPULSORY CERTIFICATION OF ELECTRICAL AND ELECTRONIC PRODUCTS Low-voltage Electrical Apparatus---switch and control Equipment Announced on Aug. 1,

More information

roduct Scope: Substation

roduct Scope: Substation roduct Scope: Substation Three Phase or Single Phase, 50 or 60 Hz, 55ºC, 65ºC, 75ºC, 55ºC/65ºC, 55ºC/75ºC, 65ºC/75ºC Envirotemp FR3 fluid or Mineral Oil Three Phase: 300 12,000 kva Single Phase: 167 6,667

More information

A computer-aided, reliability-centered maintenance strategy for power networks

A computer-aided, reliability-centered maintenance strategy for power networks A computer-aided, reliability-centered maintenance strategy for power networks The assessment of the technical condition of substation equipment and its influence on the network is basic to a reliability-centered

More information

Transmission Interconnection Requirements. Table of Contents

Transmission Interconnection Requirements. Table of Contents Transmission Interconnection Requirements Table of Contents I. Introduction II. Interconnection Agreement III. Facility Requirements IV. Interconnection Initiation I. Introduction A. Purpose and Scope

More information

UNS 5kA Arrester. Certified Test Report IEC

UNS 5kA Arrester. Certified Test Report IEC CP No.: CP0504 Page 1 of 10 UNS 5kA Arrester Certified Test Report IEC 60099-4 2004 CERTIFICATION Statements made and data shown are, to the best of our knowledge and belief, correct and within the usual

More information

Main Steam & T/G Systems, Safety

Main Steam & T/G Systems, Safety Main Steam & T/G Systems, Safety Page 1 This steam generator, built for the Wolsong station in Korea, was manufactured in Canada by the Babcock and Wilcox company. In Wolsong 2,3, and 4 a joint venture

More information

High voltage gas-insulated switchgear and hybrid switchgear, PASS

High voltage gas-insulated switchgear and hybrid switchgear, PASS Factory portrait Savli, India High voltage gas-insulated switchgear and hybrid switchgear, PASS ABB is a leader in power and automation technologies that enable utility and industry customers to improve

More information

Medium voltage switchgear for a sustainable industry

Medium voltage switchgear for a sustainable industry Thought leadership White Paper On board with Eaton. Medium voltage switchgear for a sustainable industry Author name Bert ter Hedde, Marketing and business development manager, Eaton There are, of course,

More information

The switchboard with a lot more. sivacon

The switchboard with a lot more. sivacon The switchboard with a lot more sivacon With integrated diagnostic function 4 for communications and more With integrated savings bank 5 for cost-effectiveness and more With amazing versatility 6 for flexibility

More information

Superconducting. magnets. The heart of NMR

Superconducting. magnets. The heart of NMR MARTIN TOWNSEND OXFORD INSTRUMENTS SUPERCONDUCTIVITY Superconducting The achievements of Oxford Instruments Superconductivity as a world leader in the research and development of superconducting magnets

More information

Lightning Protection Practice for Large-Extended Photovoltaic Installations

Lightning Protection Practice for Large-Extended Photovoltaic Installations 202 International Conference on ightning Protection (ICP), Vienna, Austria ightning Protection Practice for arge-extended Photovoltaic Installations Dr. Nikolaos Kokkinos Research and Development Department

More information

This is a draft revision of the briefing, and any comments are welcome please them to Becky Slater on

This is a draft revision of the briefing, and any comments are welcome please  them to Becky Slater on January 2009 Briefing Pyrolysis, gasification and plasma This is a draft revision of the briefing, and any comments are welcome please email them to Becky Slater on becky.slater@foe.co.uk. Introduction

More information

NB: Unofficial translation, legally binding texts are those in Finnish and Swedish Ministry of the Environment, Finland. Climate Change Act 609/2015

NB: Unofficial translation, legally binding texts are those in Finnish and Swedish Ministry of the Environment, Finland. Climate Change Act 609/2015 NB: Unofficial translation, legally binding texts are those in Finnish and Swedish Ministry of the Environment, Finland Climate Change Act 609/2015 Section 1 Purpose and goals of the Act (1) The purpose

More information

Power IT Compact Secondary Substations, CSS. Technical Brochure

Power IT Compact Secondary Substations, CSS. Technical Brochure Power IT Compact Secondary Substations, CSS Technical Brochure Substations from ABB Content Definitions In accordance with the EN 61330 standard, Prefabricated Secondary Substations are defined as substations

More information

Brugg Cables High Voltage Accessories. Swiss solutions for independent applications.

Brugg Cables High Voltage Accessories. Swiss solutions for independent applications. Brugg Cables High Voltage Accessories. Swiss solutions for independent applications. Fact Book High Voltage Accessories Brugg Cables Business Unit High Voltage Accessories Dr. Ruben Vogelsang Head of Product

More information

37-SDMS-01 REV. 03 SPECIFICATIONS FOR

37-SDMS-01 REV. 03 SPECIFICATIONS FOR 37-SDMS-01 REV. 03 SPECIFICATIONS FOR LOW VOLTAGE MOLDED CASE CIRCUIT BREAKERS FOR SERVICE CONNECTIONS This specification is property of SEC and subject to change or modification without any notice CLAUSE

More information

Smart Grid Monitoring of Transformers by DGA. Michel Duval. CIGRE Thailand, Bangkok 2013

Smart Grid Monitoring of Transformers by DGA. Michel Duval. CIGRE Thailand, Bangkok 2013 Smart Grid Monitoring of Transformers by DGA Michel Duval CIGRE Thailand, Bangkok 2013 1 Electric Power 2 Power Transformers 3 Catastrophic Failures 4 Failures in Service - The failure rate of power transformers

More information

Specification for Prefabricated Glass Reinforced Plastic Enclosures

Specification for Prefabricated Glass Reinforced Plastic Enclosures 1. SCOPE This document outlines a technical specification for prefabricated Glass Reinforced Plastic (GRP) enclosures designed to house outdoor rated equipment in secondary substations installed on the

More information

Compact Substation Design. Kobus Coetzer TGOOD Africa

Compact Substation Design. Kobus Coetzer TGOOD Africa Compact Substation Design Kobus Coetzer TGOOD Africa 1. 2. 3. 4. TGOOD Electric Compact Substation Design Considerations Project Reference Agenda 1. TGOOD Electric Key Facts Sino German Joint Venture Leading

More information

NPS/002/017 Technical Specification for 66 kv and 132 kv Cable Accessories

NPS/002/017 Technical Specification for 66 kv and 132 kv Cable Accessories Version:- 4.0 Date of Issue:- October 2016 Page 1 of 21 NPS/002/017 Technical Specification for 66 kv and 132 kv Cable Accessories 1. Purpose The purpose of this document is to detail the technical requirements

More information

Electrical Networks Principles and Performance

Electrical Networks Principles and Performance Engineering Standard Electrical Networks Electrical Networks Principles and Performance Version: 1 Issued: January 2015 Owner: Chief Engineer Approved By: Paul O Halloran Chief Engineer PRINTOUT MAY NOT

More information

WELDING Topic and Contents Hours Marks

WELDING Topic and Contents Hours Marks Topic and Contents Hours Marks 3.1 Introduction 04 Marks Classification and selection of welding process. Working principle of Gas welding and types of flames. 3.2 Arc welding process 08 Marks Metal arc,

More information

L 328/28 Official Journal of the European Union DIRECTIVES

L 328/28 Official Journal of the European Union DIRECTIVES L 328/28 Official Journal of the European Union 6.12.2008 DIRECTIVES DIRECTIVE 2008/99/EC OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 19 November 2008 on the protection of the environment through

More information

Ontario ENGINEERING STANDARD SPECIFICATION 1/10 REV. ELECTRICAL DISTRIBUTION HIGH VOLTAGE SUBSTATION GROUNDING AND BONDING. Approved by.

Ontario ENGINEERING STANDARD SPECIFICATION 1/10 REV. ELECTRICAL DISTRIBUTION HIGH VOLTAGE SUBSTATION GROUNDING AND BONDING. Approved by. /0 Rev Description Revision by Approved by Issue Date YYYY/MM/DD New Format Replaces 5322-0.0. T.C. 206/02/09 T.C. 206/03/02 206/03/02 2/0.0 PURPOSE This specification describes the minimum requirements

More information

Envirotran COOPER POWER. Critical Load Transformer (CLT) Superior reliability and efficiency for the most demanding power applications SERIES

Envirotran COOPER POWER. Critical Load Transformer (CLT) Superior reliability and efficiency for the most demanding power applications SERIES Critical Load Transformers COOPER POWER SERIES Critical Load Transformer (CLT) Superior reliability and efficiency for the most demanding power applications Photo courtesy of DuPont Fabros Technology,

More information

DISTRIBUTION SYSTEM ASSET CONDITION ASSESSMENT UPDATE

DISTRIBUTION SYSTEM ASSET CONDITION ASSESSMENT UPDATE EB-0-0 Exhibit D Page of DISTRIBUTION SYSTEM ASSET CONDITION ASSESSMENT UPDATE 0 EXECUTIVE SUMMARY Background Over the past number of years, THESL has put considerable effort into its Asset Management

More information

Electrical Protection Methods and Devices SAMPLE. Learner Workbook Version 1. Training and Education Support Industry Skills Unit Meadowbank

Electrical Protection Methods and Devices SAMPLE. Learner Workbook Version 1. Training and Education Support Industry Skills Unit Meadowbank Electrical Protection Methods and Devices Learner Workbook Version 1 Training and Education Support Industry Skills Unit Meadowbank Product Code: 5635 Table of Contents Introduction... 5 1. Protection

More information

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL). 16450 GROUNDING ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 26 An optional keynote to the

More information

Clearances and conductor spacings and a safe access for a.c. switchyards

Clearances and conductor spacings and a safe access for a.c. switchyards Clearances and conductor spacings and a safe access for a.c. switchyards T R A N S P O W E R APPROVED S T A N D A R D Implementation date: March 2009 COPYRIGHT 2009 TRANSPOWER NEW ZEALAND LIMITED. ALL

More information

GEOS / ENST Problem set #Grid Due: Tues. May 18

GEOS / ENST Problem set #Grid Due: Tues. May 18 GEOS 24705 / ENST 24705 Problem set #Grid Due: Tues. May 18 Problem 1: Three-phase power transmission The standard means by which electricity is transmitted in the U.S. is as 3-phase AC power. Each of

More information

Understanding New IEC Mechanical Test Requirements of Arresters

Understanding New IEC Mechanical Test Requirements of Arresters Understanding New IEC Mechanical Test Requirements of Arresters ArresterFacts 007 Understanding New IEC Mechanical Test Requirements of Arresters New Cyclic Load Test (1000 cycles) 1 cycle every 2 seconds

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Updated format, division title, and removed references to other sections. - mgl44 A. Summary This section contains design criteria for the

More information

INFLUENCE OF HEAT SOURCE LOCATION ON AIR TEMPERATURES IN SEALED MV SWITCHGEAR

INFLUENCE OF HEAT SOURCE LOCATION ON AIR TEMPERATURES IN SEALED MV SWITCHGEAR INFLUENCE OF HEAT SOURCE LOCATION ON AIR TEMPERATURES IN SEALED MV SWITCHGEAR Elin FJELD Wilhelm RONDEEL Knut VAAGSAETHER Univ.Coll. of Southeast Norway USN Norway USN - Norway elin.fjeld@usn.no wilhelm.rondeel@usn.no

More information

Cost-Effective And Environmental Friendly Distribution Transformer

Cost-Effective And Environmental Friendly Distribution Transformer Cost-Effective And Environmental Friendly Distribution Transformer Manish Kumar Srivastava Abstract The scope of this paper is to focus on cost effective design, reliable and environment friendly distribution

More information

Thermocouples. Operating and Maintenance Manual English. Thermocouples

Thermocouples. Operating and Maintenance Manual English. Thermocouples Thermocouples Operating and Maintenance Manual English Seite 1 / 8 Operating and Maintenance Manual Thermocouples Table of Contents 1 General Information 3 2 Functionality 4 2.1 Thermo Lines and Compensating

More information

Engineering Standard- Design Electrical Networks MEST TRACTION SUBSTATIONS AND TIE STATIONS

Engineering Standard- Design Electrical Networks MEST TRACTION SUBSTATIONS AND TIE STATIONS Engineering Standard- Design Electrical Networks MEST 000002-01 Version: 1 Issued: May 2013 Owner: Chief Engineer Approved By: Norm Grady Chief Engineer PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET

More information

Special Report - Session 1 NETWORK COMPONENTS

Special Report - Session 1 NETWORK COMPONENTS Special Report - Session 1 NETWORK COMPONENTS Alain DOULET Chairman - France alain.doulet@erdfdistribution.fr Peter BRACHER Special Rapporteur - Switzerland peter.bracher@nexans.com Philippe PICOT Special

More information

FAQs: F-gases GENERAL POINTS

FAQs: F-gases GENERAL POINTS Regulation (EU) No 517/2014, also known as F-gas Regulation, entered into force Europe-wide on 1 January 2015. Our climate chambers use gases that are subject to this Regulation. This FAQ paper provides

More information

The Next Step In The World Of Transformers

The Next Step In The World Of Transformers The Next Step In The World Of Transformers Envirotran TM Transformers Set Higher Environmental, Fire Safety and Performance Standards Envirotran TM Transformers Advance the Evolution of Electrical Distribution

More information

SAFETY DATA SHEET Relevant identified uses of the substance or mixture and uses advised against

SAFETY DATA SHEET Relevant identified uses of the substance or mixture and uses advised against Page : 1 1 Identification of the substance/mixture and of the company/undertaking 1.1. Product identifier Trade name : FLUXOCORD 35 25 2D 1.2. Relevant identified uses of the substance or mixture and uses

More information

Version: 1.1 Date of Issue: March 2017 Page: 1 of 23

Version: 1.1 Date of Issue: March 2017 Page: 1 of 23 Version: 1.1 Date of Issue: March 2017 Page: 1 of 23 NPS/002/034 - Technical Specification for Metering Base Unit for Connection to Extra High Voltage Metering Circuit Breakers in accordance with COP2

More information

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number PART 1 GENERAL 01 02 03 04 SCOPE Furnish and install Manual Transfer Switches (MTS) and

More information

REPUBLIC OF LITHUANIA LAW ON ELECTRICITY 20 July, 2000, No. VIII 1881 as amended by 26 June, 2001, No. IX-408 Vilnius CHAPTER ONE GENERAL PROVISIONS

REPUBLIC OF LITHUANIA LAW ON ELECTRICITY 20 July, 2000, No. VIII 1881 as amended by 26 June, 2001, No. IX-408 Vilnius CHAPTER ONE GENERAL PROVISIONS Official translation REPUBLIC OF LITHUANIA LAW ON ELECTRICITY 20 July, 2000, No. VIII 1881 as amended by 26 June, 2001, No. IX-408 Vilnius CHAPTER ONE GENERAL PROVISIONS Article 1. Purpose of the Law This

More information

Seismic Considerations of Circuit Breakers

Seismic Considerations of Circuit Breakers Seismic Considerations of Circuit Breakers Willie Freeman, IEEE 693 Working Group ABB Inc, Mt. Pleasant PA, USA IEEE Tutorial - 2008 Abstract: The tutorial covers the seismic qualification of high voltage

More information

MOISTURE IN PAPER ASSESSMENT FROM CONTINUOUS MONITORING OF MOISTURE IN OIL. GE Energy

MOISTURE IN PAPER ASSESSMENT FROM CONTINUOUS MONITORING OF MOISTURE IN OIL. GE Energy MOISTURE IN PAPER ASSESSMENT FROM CONTINUOUS MONITORING OF MOISTURE IN OIL Jacques Aubin GE Energy Brian D Sparling Abstract Moisture content of solid insulation is a persistent concern for power transformer

More information

Information Document Protection System Information ID# R

Information Document Protection System Information ID# R Information Documents are for information purposes only and are intended to provide guidance. In the event of any discrepancy between the Information Document and the related authoritative document(s)

More information

UPS Electrical Design and. Installation. critica POWER SUPPLIES

UPS Electrical Design and. Installation. critica POWER SUPPLIES UPS Electrical Design and critica POWER SUPPLIES Installation Important considerations for the electrical design and installation of UPS systems in mission critical applications Where Critical Power applications

More information

GEK B Instructions. Test Cabinet. for Power/Vac Vacuum Circuit Breakers

GEK B Instructions. Test Cabinet. for Power/Vac Vacuum Circuit Breakers g GEK 105263B Instructions Test Cabinet for Power/Vac Vacuum Circuit Breakers Power/Vac Test Cabinet Table of Contents Section 1. Introduction 1-1 Safety... 3 1-2 Maintenance... 3 Section 2. Receiving,

More information

Electricity Supply to Africa and Developing Economies Challenges and Opportunities. Technology solutions and innovations for developing economies

Electricity Supply to Africa and Developing Economies Challenges and Opportunities. Technology solutions and innovations for developing economies Electricity Supply to Africa and Developing Economies Challenges and Opportunities Technology solutions and innovations for developing economies Employment of various strategies in Eskom to optimize the

More information

LA Engineering Academy

LA Engineering Academy Laxmi Associates Consultancy Third party Inspection RLA Testing& Commissioning AMC Project Management Training 323-324, Sunplaza1, GIDC Road, Makarpura, Vadodara-390010. lxassociates@gmail.com, www.laxmiassociates.in,

More information

Data Sheet 110kV TD123II dry type outdoor termination

Data Sheet 110kV TD123II dry type outdoor termination 3 Data Sheet 110kV TD123II dry type outdoor termination 1. Product Description: 3M 110kV TD123II dry type outdoor termination meets requirement of test and product according to IEC60840 and GB11017.3,

More information

OperatiOn and safety report Of MOchOvce and BOhunice v2 nuclear power plants

OperatiOn and safety report Of MOchOvce and BOhunice v2 nuclear power plants 2016 OperatiOn and safety report Of MOchOvce and BOhunice v2 nuclear power plants The company is certified according to three management systems: Certificate stn en iso 9001:2008 Quality management system

More information

NEC 2017 Code Changes Chapter 1 - General

NEC 2017 Code Changes Chapter 1 - General NEC 2017 Code Changes Chapter 1 - General Changes from the 2014 code are highlighted in yellow. ARTICLE 110 - Requirements for Electrical Installations Part I. General 110.1 Scope. This article covers

More information

C60 Standby UPS. 800VA Models. User & Installation Manual Xtreme Power Conversion Corporation. All rights reserved.

C60 Standby UPS. 800VA Models. User & Installation Manual Xtreme Power Conversion Corporation. All rights reserved. For more information, visit www.247technology.com/on-line-ups/c60-standby-ups C60 Standby UPS 800VA Models User & Installation Manual 2015. All rights reserved. (Rev 6/23/15) Table of Contents Package

More information

SURGE ARRESTERS kv in silicone shield

SURGE ARRESTERS kv in silicone shield SURGE ARRESTERS 10-24 kv in e shield The surge arresters 12 kv produced in Electotechnical Institute Division in Wroclaw (nominal discharge capability 10kA, 8/20µs) are presented on the picture. Advantages

More information

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES Guidelines effective March 5, 2007 NES is committed to providing safe, reliable electric service at a reasonable price for all of our customers. These guidelines offer direction for activities relating

More information

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators Version:- 3.1 Date of Issue:- June 2014 Page 1 of 13 NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators 1. Purpose This document is the technical specification for 33kV, 66kV

More information

ACS OTHER PRIMARY EQUIPMENT

ACS OTHER PRIMARY EQUIPMENT ACS OTHER PRIMARY EQUIPMENT Fleet Strategy Document 31/10/2013 Transpower New Zealand Limited 2013. All rights reserved. Page 1 of 70 C O P Y R I G H T 2013 T R A N S P O W E R N E W Z E A L A N D L I

More information

High Energy Arcing Faults (HEAF) and Their Impact on PRA for a Nuclear Power Plant Latest International Operating Experience and Research Activities

High Energy Arcing Faults (HEAF) and Their Impact on PRA for a Nuclear Power Plant Latest International Operating Experience and Research Activities High Energy Arcing Faults (HEAF) and Their Impact on PRA for a Nuclear Power Plant Latest International Operating Experience and Research Activities Marina Roewekamp GRS ggmbh, Germany Nicholas Melly,

More information