Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008

Size: px
Start display at page:

Download "Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008"

Transcription

1 Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008

2 (Above 1000V and up to 38kV for Surface Mining) Key Components of Specification: Scope Applicable Standards Service Conditions Ratings Construction Tests Quality Assurance System

3 Scope Scope of work Define what is required Example: This specification defines requirements of one (1) 69kV-25kV, 60Hz, 15 MVA mine-duty skid mounted portable substation with primary structure, transformer, neutral grounding resistor and secondary switchgear, close coupled to transformer.

4 Applicable Standards (For illustration only) IEE Std C Metal-Enclosed Interrupter Switchgear IEEE Std C AC HV Circuit breakers IEEE Std C37.22 MV Switches used in indoor Metal-Enclosed Switchgear NFPA 70E-2000, Electrical Safety Requirements for Employee Workplace IEEE Std , IEEE Guide for performing Arc-Flash Hazard Calculations NEC, National Electric Code

5 Types of Switchgear Assemblies Defined by IEEE Standards SWITCHGEAR ASSEMBLIES METAL-ENCLOSED POWER SWITCHGEAR METAL-ENCLOSED BUS C37.23 CONTROL SWITCHBOARDS C37.21 LOW-VOLTAGE POWER CIRCUIT BREAKER (LV) C METAL-CLAD (MC) C METAL-ENCLOSED INTERRUPTER (MEI) C GUIDE FOR TESTING MV ME SWITCHGEAR FOR INTERNAL ARCING FAULTS C NON-SEGREGATED PHASE SEGREGATED PHASE ISOLATED PHASE REQUIREMENTS AND GUIDE FOR CALCULATING LOSSES VERTICAL (OPEN OR ENCLOSED) DUAL DUPLEX CONTROL DESK BENCHBOARD DUPLEX BENCHBOARD FIXED RACK CABINET SWING RACK CABINET

6 Service Conditions Usual Service Conditions The equipment shall be designed for the following service conditions: 1. The temperature of the cooling air surrounding the enclosure of the switchgear is within the limits of -30 C and +40 C 2. The altitude of the installation does not exceed 1000 m (3300 ft) 3. The effect of solar radiation is not significant

7 Unusual Service Conditions Or you may list: 1. The equipment shall be suitable to operate within the limits of -30 C and +50 C (require either derating or select next higher ampacity rating) 2. The altitude of the installation does not exceed 1500 m (5000 ft), (require either de-rating or use higher insulation level 3. The effect of solar radiation shall be considered per IEEE Std C37.24

8 Load current-carrying capabilities at various ambients 552A 1104A

9 Altitude Correction Factors Switchgear that depends on air for an insulating and cooling medium will have a higher temperature rise and a lower dielectric withstand capability when operated at higher altitudes The following Table shows historical altitude correction factors for dielectric withstand voltage and continuous current Specifier may refer to Annex B of IEEE PC for additional guidance

10 Altitude Correction Factors

11 Effect of Solar Radiation is Normally Insignificant Monthly Normal Max Temp in US & Canada See IEEE Std C for Ref Station June July August Phoenix 39.7 C/103.5 F 41.1 C/106 F 39.8 C/103.6 F Las Vegas 37.9C/100.2F 41.1C/106F 39.6C/103.3F Sheridan 24.9C/76.8F 30.1C/86.2F 29.6C/85.3F Evansville 30.1C/86.2F 31.7C/89F 30.7C/87.3F Fairbanks 21.2C/70.2F 22.4C/72.3F 19.1C/66.4F Edmonton 20.9C/69.6F 22.5C/72.5F 21.8C/71.2F Temperature rise of about 15 C may be expected on the conducting parts due to solar radiation

12 Ratings Ratings of Switchgear Designations of Operating Limits under Specified Conditions 1. Rated maximum voltage 2. Rated power frequency 3. Rated insulation levels 4. Rated continuous current 5. Rated momentary withstand current 6. Rated short-time withstand current

13 Example 25kV Dual VCB House w/o NGR Ratings of Switchgear 1. Rated maximum voltage = 27kV rms 2. Rated power frequency = 60Hz 3. Rated insulation levels: Power frequency withstand voltage = 60kV rms; BIL = 125kV peak 4. Rated continuous current = 1200A 5. Rated momentary withstand current = 43kA peak(10 Cy) 6. Rated short-time withstand current = 16kA (2 s) Bkrs have SC interrupting rating, switches do not Switches do have fault close rating

14 Example Neutral Grounding Resistor Ratings of NGR kV L-L, 13.8kV L-N, 60 Hz C = Ohm 3. Current = 25A 4. Duty/Max Temperature rise = Extended/610 C 5. Finish = Mill galvanized 6. Enclosure type = Outdoor 7. IEEE Std , reaffirmed 1990

15 Neutral Ground Monitoring if applicable Specify 1. Neutral ground monitoring device 2. Sensing resistor 3. Current transformer

16 Rating of Simple 25kV Junction box

17 25kV Junction box Ratings of Switchgear 1. Rated maximum voltage = 27kV rms 2. Rated power frequency = 60Hz 3. Rated insulation levels: Power frequency withstand voltage = 60kV rms; BIL = 125kV peak 4. Rated continuous current = 600A 5. Rated momentary withstand current =??ka peak(10 Cy) 6. Rated short-time withstand current =??A (2 s)

18 Associated Major Components Ratings of major components should also be listed in specification 1. Vacuum circuit breakers 2. Disconnect switches (specify load-break or non load-break) 3. Instrument transformers (CT s, PT s & CPT s) 4. Lighting arresters (MCOV for grounded or ungrounded system) 5. Ground monitor 6. Metering, controls, relays and ground monitors 7. Power transformers and primary structures for portable substations

19 Construction Considerations for Rugged Mine Duty Switchgear Skid (shall be fabricated using the following structural members) Wide flange I-beams for cross members Heavy duty structural steel channels for runners Wide runners with 3/8 steel plates on bottom ¼ Thick steel deck and belly plates ¾ -1 Thick steel wear plates under runners 1 ½ X 10 X 30 steel towing eyes with 3 eye Towing eyes at 45 degree angle to facilitate lifting with slings 1 Diameter steel J-hooks for tying off the cables

20 Skid for Portable Substation (Partial view)

21 Skid for Portable Substation

22 Skid for Portable Substation

23 Construction Considerations for Rugged Mine Duty Switchgear Enclosure (shall be fabricated with) 11 Gauge steel with seam welded construction Stainless steel hinges and door hardware Galvanized steel slide-bolt latches with provisions for padlocking Double flange door construction with drip shield Nema 3-R construction with door stops and gaskets Viewing windows for disconnect switches Adequate cable termination height 3/8 Steel plates for blast protection of transformers

24 Construction Considerations for Mine Duty Switchgear Enclosure Finishes After the enclosure fabrication all welds and hard to reach areas shall be cleaned with steel wire brush and power grinder to remove any corrosion, weld splatter and scale All enclosures shall be cleaned with high pressure phosphatizing solution to clean and etch the surfaces Enclosure shall be painted with a minimum of mil high-solids primer and mil acrylic enamel top coat Electronic paint gauge may be used to assure uniform quality finish Exterior paint shall withstand 2000 hours of exposure to a 5% salt spray

25 Steel Fabrication Welds are cleaned with a steel wire brush Power grinder is used to remove any corrosion, scale and weld splatter

26 Steel Fabrication High pressure cleaning with phosphatizing solution, rinsing and air drying of sub-assemblies and assemblies

27 Construction Two-Coat Paint System Primer: Alkyd high-solids universal primer Finish Coat: Acrylic enamel, high-solids semi-gloss finish 2000 Hrs of salt spray withstand, resistant to chalking, peeling, and UVR

28 38kV Switch and Fuse Enclosure for Portable Sub

29 Blast Protection of transformers 11 Ga Seam welded construction 3/8 Steel Plates Optional top lifting structure for crane handling

30 Wiring Control and secondary wiring Wiring shall be rated for 600V, and 90 C, and shall be flame-retardant. Wire shall be type SIS as listed in the NEC. Wiring across a hinge shall be flexible to withstand repeated door movement without sustaining damage to wire strands or insulation Wire size shall be suitable for the maximum steady-state load Wire shall be No. 14 AWG and larger

31 Insulation Coordination When Cables are ran through neutral CT CT s are properly spaced and air gaps are sealed with RTV to eliminate corona

32 Production Tests Production tests made for quality control shall be performed to assure that product meets the design specifications and applicable standards 1. Power frequency (60Hz) dielectric tests 2. Mechanical operation tests (Functioning of operating mechanisms, interlocks, door locks etc) 3. Grounding of instrument transformer cases (Metal case design only) 4. Control wiring continuity check (Operational check) 5. Polarity verification (To ensure correct connections between instrument transformers and meters) 6. Request test data for power transformer if applicable

33 Final Inspection & Production Tests

34 Quality Assurance Vendor shall be certified to ISO-9001 Quality Management System Vendor shall provide MSHA certified field service technicians when required

35

36 MSHA Certified technicians

37 Questions?

38 Thank you

Power Zone Center. Your solution for power distribution and control systems

Power Zone Center. Your solution for power distribution and control systems Power Zone Center Your solution for power distribution and control systems The Strength of One Powerful When you need to install a new power distribution center in your facility, you need it done in fastest

More information

Power Electronics, Inc. Packaged Equipment Center Standard Construction and Design Features

Power Electronics, Inc. Packaged Equipment Center Standard Construction and Design Features DESIGN CRITERIA FOR STANDARD CONSTRUCTION: These standard design elements of the P.E.I. Power Equipment Center are utilized to meet the following design criteria per ASCE 7-05 as adopted by the IBC (International

More information

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC Van Dam Street Long Island City, NY ELECTRIC METER SHOP DEPARTMENT

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC Van Dam Street Long Island City, NY ELECTRIC METER SHOP DEPARTMENT CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 48-05 Van Dam Street Long Island City, NY 11101 ELECTRIC METER SHOP DEPARTMENT METER ENGINEERING SPECIFICATION MES-350 REVISION 3 June 2016 EFFECTIVE DATE

More information

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

B. Provide liquid-filled secondary substation transformers as indicated on drawings. SECTION 26 12 13 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 26 05 00. B. Provide liquid-filled secondary substation transformers as indicated on drawings. 1.02 RELATED

More information

OPERATING PROCEDURE NO. 310

OPERATING PROCEDURE NO. 310 OPERATING PROCEDURE NO. 310 Related Operating Procedures: 310A; 310B; 310C; 310D SUBJECT: Conditions of Service Issued: February 10, 2014 Revised: March 28, 2016 OBJECTIVE: To establish the rules, regulations

More information

Standard of Practice - Campus Electrical Distribution System

Standard of Practice - Campus Electrical Distribution System A26.3 Standard of Practice - Campus Electrical Distribution System NOTE: Significant revisions or additions to the previous standards are highlighted in italics. GENERAL Designers shall verify that all

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Medium Voltage Switchgear. Basis of Design.

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Medium Voltage Switchgear. Basis of Design. Basis of Design This section applies to the design and selection of medium voltage switchgear, primarily for use in substations. Design Criteria 13.8kV equipment shall be 15kV class, 4.16kV and 2.4kV equipment

More information

ELECTRICAL INSPECTION BULLETIN (Effective )

ELECTRICAL INSPECTION BULLETIN (Effective ) ELECTRICAL INSPECTION BULLETIN (Effective 2009-02-01) Rule 36-000 Customer Owned High Voltage Installations With the increase in customer own high voltage equipment there appears to be confusion over which

More information

UFGS (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 35 33.00 40 (August 2013) --------------------------------- Preparing Activity: NASA Superseding UFGS-26 35 33.00 40 (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

NEC 2017 Code Changes Chapter 1 - General

NEC 2017 Code Changes Chapter 1 - General NEC 2017 Code Changes Chapter 1 - General Changes from the 2014 code are highlighted in yellow. ARTICLE 110 - Requirements for Electrical Installations Part I. General 110.1 Scope. This article covers

More information

Specification for Prefabricated Glass Reinforced Plastic Enclosures

Specification for Prefabricated Glass Reinforced Plastic Enclosures 1. SCOPE This document outlines a technical specification for prefabricated Glass Reinforced Plastic (GRP) enclosures designed to house outdoor rated equipment in secondary substations installed on the

More information

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466 BUSWAY LOW VOLTAGE (POW-R-WAY III) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein

More information

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number PART 1 GENERAL 01 02 03 04 SCOPE Furnish and install Manual Transfer Switches (MTS) and

More information

Electrical Houses. Coordinated. Coordinated Electrical Houses Integrated Power Assemblies IPAs Contents

Electrical Houses. Coordinated. Coordinated Electrical Houses Integrated Power Assemblies IPAs Contents Sheet 001 Coordinated.0-1 Electrical Houses Contents General Description............................................0-2 Technical Data Layout Dimensions..............................0-6 Specifications

More information

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding.

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding. ALLIANT ENERGY CENTER PAVILIONS Project No. 2013 027 SECTION 27 11 00 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION LOW-VOLTAGE SWITCHGEAR

SECTION LOW-VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 00 LOW-VOLTAGE SWITCHGEAR SPEC WRITER NOTE: This specification is not for general use. Use Section 26 24 13, DISTRIBUTION SWITCHBOARDS for most applications.

More information

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph

More information

ELECTRIC METERING GENERAL

ELECTRIC METERING GENERAL 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 EQUIPMENT 5.0 METER REQUIREMENTS 6.0 METER FACILITIES 7.0 ELECTRICAL CONNECTIONS 2.0 SCOPE This guide covers general requirements and codes for

More information

Outdoor + Switchgear, Walk-in Equipment Buildings Low & Medium Voltage NEMA 3R

Outdoor + Switchgear, Walk-in Equipment Buildings Low & Medium Voltage NEMA 3R Outdoor + Switchgear, Walk-in Equipment Buildings Low & Medium Voltage NEMA 3R Product Brochure www.apt-power.com 433 N. 36 th Street PROVIDING A COMPREHENSIVE Lafayette, IN 47905 www.apt-power.com 433

More information

660 Volts 630 & 800AMP

660 Volts 630 & 800AMP Ergon Energy Corporation Limited Technical Specification for Switch- Disconnectors and Fuse-Switch- Disconnectors 660 Volts 630 & 800AMP ETS-06-02-01 Check this is the latest Process Zone version before

More information

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

A SUBSTATION CONCEPT FOR CHANGEABLE LOAD CONDITIONS

A SUBSTATION CONCEPT FOR CHANGEABLE LOAD CONDITIONS A SUBSTATION CONCEPT FOR CHANGEABLE LOAD CONDITIONS Willy LORD SwedPower AB Sweden willy.lord@swedpower.com Lennart AHNLUND Vattenfall Eldistribution AB Sweden B. WALLBING-LÖVGREN Vattenfall Eldistribution

More information

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL). 16450 GROUNDING ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 26 An optional keynote to the

More information

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6.2 OVERHEAD SERVICES Wiring of any premises for connection

More information

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING 2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING E3305.3: now reads The space equal to the width and depth of the panelboard and extending

More information

SERVICE ENTRANCES. OPPD S Electrical Service Designer (ESD) shall designate the Point Of Entrance.

SERVICE ENTRANCES. OPPD S Electrical Service Designer (ESD) shall designate the Point Of Entrance. SERVICE ENTRANCES 3.01 POINT OF ENTRANCE General Service The customer, or the customer s electrician, should provide OPPD with a site plan, load schedule, and voltage requirements when requesting service.

More information

INC Pre-Assembled Structures

INC Pre-Assembled Structures INC Pre-Assembled Structures Drop-In In-Place Noise Control Pre-Engineered Factory Finished High Performance Rugged Durability INC pre-assembled structures offer a high performance, cost-effective alternative

More information

A-Series Aluminum Gantry Crane

A-Series Aluminum Gantry Crane SPANCO PRODUCT SPECIFICATIONS 1 A-Series Aluminum Gantry Crane This guide can be used to prepare a bid specification for the incorporation of an A-Series Gantry Crane into a competitive bid project or

More information

The complete guide to transformers and packaged substations

The complete guide to transformers and packaged substations LAND LOGICAL POWER The complete guide to transformers and packaged substations Contents Land Logical Power transformers An introduction to the complete range of Land Logical Power transformers and package

More information

roduct Scope: Substation

roduct Scope: Substation roduct Scope: Substation Three Phase or Single Phase, 50 or 60 Hz, 55ºC, 65ºC, 75ºC, 55ºC/65ºC, 55ºC/75ºC, 65ºC/75ºC Envirotemp FR3 fluid or Mineral Oil Three Phase: 300 12,000 kva Single Phase: 167 6,667

More information

SECTION 1101 TRAFFIC SIGNALS AND APPURTENANCES END OF SECTION

SECTION 1101 TRAFFIC SIGNALS AND APPURTENANCES END OF SECTION SECTION 1101 SIGNALS AND APPURTENANCES PART 1 GENERAL 1.4 SUBMITTALS E. Submit warranty for all supplied material and workmanship for a period of two years from final acceptance. The warranty must state

More information

ANSI/ ASME HST Performance Standard For Overhead Electric Wire Rope Hoists

ANSI/ ASME HST Performance Standard For Overhead Electric Wire Rope Hoists SECTION 412213- BRIDGE CRANES Part 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 1.1. REFERENCE STANDARDS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 6/15/16 Updated division section from 16124 to 2605 - mgl44 13, removed references to other section 10/17/14

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 36 00.00 10 (October 2007) ---------------------------------- Preparing Activity: USACE Superseding UFGS-26 36 00.00 10 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

E-Series Steel Gantry Crane

E-Series Steel Gantry Crane SPANCO PRODUCT SPECIFICATIONS 1 E-Series Steel Gantry Crane This guide can be used to prepare a bid specification for the incorporation of an E-Series Gantry Crane into a competitive bid project or application.

More information

Permitting and Inspecting PV Systems. PV Codes and Standards 101. Photovoltaic System Basics

Permitting and Inspecting PV Systems. PV Codes and Standards 101. Photovoltaic System Basics Permitting and Inspecting PV Systems Presented by Bill Brooks, PE Brooks Engineering PV Codes and Standards 101 What are the applicable codes and standards for PV systems? Electrical codes - NEC Article

More information

SPECIFICATIONS - DETAILED PROVISIONS Section General Electrical Requirements C O N T E N T S

SPECIFICATIONS - DETAILED PROVISIONS Section General Electrical Requirements C O N T E N T S Revised 04/14/16 SPECIFICATIONS - DETAILED PROVISIONS Section 16010 - General Electrical Requirements C O N T E N T S PART 1 - GENERAL... 1 1.01 DESCRIPTION... 1 1.02 QUALITY ASSURANCE... 1 1.03 UTILITY

More information

DESIGN. DEVELOP. DELIVER. CAPABILITY STATEMENT

DESIGN. DEVELOP. DELIVER. CAPABILITY STATEMENT DESIGN. DEVELOP. DELIVER. CAPABILITY STATEMENT Mining & Industrial Switchgear Kiosk Substations Water Infrastructure Projects Project Management Slurry Management Systems Pumping Solutions Fire Protection

More information

REQUIREMENTS FOR INDOOR INSTALLATION OF PADMOUNTED TRANSFORMERS

REQUIREMENTS FOR INDOOR INSTALLATION OF PADMOUNTED TRANSFORMERS REQUIREMENTS FOR INDOOR INSTALLATION OF PADMOUNTED TRANSFORMERS Introduction An applicant applying for permanent electric service who opts to have the padmounted transformers installed inside his building

More information

SECTION MEDIUM VOLTAGE TRANSFORMERS

SECTION MEDIUM VOLTAGE TRANSFORMERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 5/12/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 5/12/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 5/12/10 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. Is it illegal to install a wet-niche luminaire face-up

More information

SECTION OUTLET, PULL, AND JUNCTION BOXES

SECTION OUTLET, PULL, AND JUNCTION BOXES SECTION 16131 OUTLET, PULL, AND JUNCTION BOXES PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 09900 - Painting. 2. 16112 - Raceways and Conduits. 1.02 SYSTEM DESCRIPTION A. Performance Requirements:

More information

CHAPTER 5 METERING REQUIREMENTS

CHAPTER 5 METERING REQUIREMENTS CHAPTER 5 METERING REQUIREMENTS CHAPTER 5 METERING REQUIREMENTS 5.1 General 1. All installations connected to, or intended to be connected to HK Electric s supply of electricity must comply with HK Electric

More information

Technical Specification for LV ABC Fuse Switch Disconnectors

Technical Specification for LV ABC Fuse Switch Disconnectors Ergon Energy Corporation Limited Technical Specification for LV ABC Fuse ETS-06-02-02 Check this is the latest Process Zone version before use. Specification ETS 06-02-02 Ver 3 Contents 1. Purpose and

More information

OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE. See Chapter 3, Section 3.01 for more information about point of entrance (POE).

OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE. See Chapter 3, Section 3.01 for more information about point of entrance (POE). 6.01 GENERAL OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE See Chapter 3, Section 3.01 for more information about point of entrance (POE). In all cases, the customer installs, owns, and maintains the

More information

A. Product Data shall be provided for each type of product indicated.

A. Product Data shall be provided for each type of product indicated. 32 31 13 CHAIN LINK FENCES AND GATES SECTION 1 GENERAL 1.1 SUMMARY This Section includes the following: 1. Chain Link Fences 2. Gates for Chain Link Fences. See electrical specifications for electrical

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Updated format, division title, and removed references to other sections. - mgl44 A. Summary This section contains design criteria for the

More information

Compact Substation Design. Kobus Coetzer TGOOD Africa

Compact Substation Design. Kobus Coetzer TGOOD Africa Compact Substation Design Kobus Coetzer TGOOD Africa 1. 2. 3. 4. TGOOD Electric Compact Substation Design Considerations Project Reference Agenda 1. TGOOD Electric Key Facts Sino German Joint Venture Leading

More information

Metering Requirements 750 Volts or Less

Metering Requirements 750 Volts or Less SECTION 1 - SCOPE 1.1 Toronto Hydro Requirements 1.2 Ontario Electrical Safety Code SECTION 2 - PURPOSE Metering Requirements 750 Volts or Less INDEX SECTION 3 - DEFINITIONS, PUBLICATIONS AND THE INTERNATIONAL

More information

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS SINGLE-PHASE PADMOUNTED TRANSFORMERS

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS SINGLE-PHASE PADMOUNTED TRANSFORMERS CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS SINGLE-PHASE PADMOUNTED TRANSFORMERS Original Issue 1/84 Revised 1/91 Revised 6/02 Revised 11/05 Revised 11/09 Revised 1/12 Revised 11/12 Revised 5/14 Revised

More information

SECTION AUTOMATIC TRANSFER SWITCH

SECTION AUTOMATIC TRANSFER SWITCH SECTION 26 36 23 AUTOMATIC TRANSFER SWITCH PART 1: GENERAL 1.01 SCOPE A. Furnish all labor, materials, equipment and appurtenances, install and test electrically operated, automatic transfer switch (ATS)

More information

PF-Series Gantry Crane

PF-Series Gantry Crane SPANCO PRODUCT SPECIFICATIONS 1 PF-Series Gantry Crane This guide can be used to prepare a bid specification for the incorporation of a PF-Series Gantry Crane into a competitive bid project or application.

More information

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES Guidelines effective March 5, 2007 NES is committed to providing safe, reliable electric service at a reasonable price for all of our customers. These guidelines offer direction for activities relating

More information

ELECTRICAL SAFE WORK PRACTICES

ELECTRICAL SAFE WORK PRACTICES ELECTRICAL SAFE WORK PRACTICES I. PURPOSE To establish minimum acceptable standards for AC and DC electrical safe work practices. The program includes requirements for the training of qualified and unqualified

More information

SECTION HEAT TRACING FOR PLUMBING PIPING

SECTION HEAT TRACING FOR PLUMBING PIPING SECTION 22 05 33 HEAT TRACING FOR PLUMBING PIPING PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between //----// if not applicable to project. Also delete any other item or paragraph not

More information

1.05 Power System Fault and Coordination Study with Arc Flash Calculations

1.05 Power System Fault and Coordination Study with Arc Flash Calculations PART 1: GENERAL 1.01 Underground Ducts and Manholes A. The work included in this section of the construction standards consists of the design requirements for the complete layout and installation of a

More information

SECTION CHAIN-LINK FENCES AND GATES 02821/1

SECTION CHAIN-LINK FENCES AND GATES 02821/1 SECTION 02821 - CHAIN-LINK FENCES AND GATES 02821/1 PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Chain-Link Fences: 2. Gates: horizontal slide or swing. 3. Fences installed where

More information

SECTION SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION

SECTION SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION SECTION 16-372 SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION 1. GENERAL SPECIFICATIONS The work of this Section includes furnishing all labor, equipment, materials (unless specifically identified as Owner-furnished)

More information

Series PV. Compact Switchgear Cabinets. Construction subject to change without notice Dimensions in mm

Series PV. Compact Switchgear Cabinets. Construction subject to change without notice Dimensions in mm Series PV Single layer design, thermal conductivity k = 5 W/m 2 K For wall mounting by hanging and standing installation Torsion resistant, self-supporting casing without joints, corrosion and seawater

More information

SINGLE SWING DOOR PAIRED SWING DOOR

SINGLE SWING DOOR PAIRED SWING DOOR Rev. 091416 SINGLE SWING DOOR PAIRED SWING DOOR Drawing No.: Revision: Date: If you need to contact Customer Service Please complete the following information and retain for future reference: Serial Number:

More information

Conductor Shield A combination of semi-conducting tape and extruded thermosetting semi-conducting material meeting UL 1309, IEEE 1580 and UL1072.

Conductor Shield A combination of semi-conducting tape and extruded thermosetting semi-conducting material meeting UL 1309, IEEE 1580 and UL1072. 37-105VFD MMV-VFD Power Cable Three : kv - 15kV 133% Level Rated 90 C s (3) Soft annealed flexible stranded tinned copper per IEEE 150 Table 11. Extruded thermosetting 90 C Ethylene Propylene Rubber (EPR),

More information

This guide can be used to prepare a specification for incorporating free standing jib cranes into a competitively bid construction project.

This guide can be used to prepare a specification for incorporating free standing jib cranes into a competitively bid construction project. SECTION 14651 FREE STANDING JIB CRANE ***** Gorbel, Inc. manufacturers a broad range of material handling cranes including monorail, bridge, gantry, and jib cranes. Numerous work station and industrial

More information

A. This section includes building wire and cable rated 600V and less Full Short Circuit Device, Coordination and Arc Fault Study

A. This section includes building wire and cable rated 600V and less Full Short Circuit Device, Coordination and Arc Fault Study PART 1: GENERAL 1.01 Underground Ducts and Manholes A. The work included in this section of the construction standards consists of the design requirements for the complete layout and installation of a

More information

NEPAL ELECTRICITY AUTHORITY (An Undertaking of Government of Nepal) Project Management Directorate

NEPAL ELECTRICITY AUTHORITY (An Undertaking of Government of Nepal) Project Management Directorate NEPAL ELECTRICITY AUTHORITY (An Undertaking of Government of Nepal) SAMUNDRATAR TRISHULI 3B HUB 132 KV TRANSMISSION LINE PROJECT BIDDING DOCUMENT FOR DESIGN, SUPPLY AND CONSTRUCTION OF 132/33 KV SUBSTATION

More information

Data Bus Connector and Terminator Requirements Document DB-1001-A. Revision C

Data Bus Connector and Terminator Requirements Document DB-1001-A. Revision C Data Bus Connector and Terminator Requirements Document DB-1001-A Revision C 2507 W. Geneva Dr. Tempe, Arizona 85282 Phone [602] 231-8616 FAX [602] 273-9135 www.phxlogistics.com TABLE OF CONTENTS 1. Introduction

More information

Switch Rack Assemblies

Switch Rack Assemblies Switch Rack Assemblies Applications: Free-standing switch rack assemblies are used: To provide a complete motor control center in one integrated package Outdoors and indoors In damp, wet or corrosive locations

More information

Section BUILDINGS, SHELTERS, ENCLOSURES

Section BUILDINGS, SHELTERS, ENCLOSURES Section 13121 BUILDINGS, SHELTERS, ENCLOSURES Part 1 GENERAL 1.1 SECTION INCLUDES 1.2 A. Pre-engineered buildings. B. Pre-engineered shelters. C. Pre-engineered enclosures. D. Electrical wiring and devices

More information

800 Series Aluminum Overhead Doors, by Northwest Door Section ALUMINUM SECTIONAL DOORS Digicon Information Inc.

800 Series Aluminum Overhead Doors, by Northwest Door Section ALUMINUM SECTIONAL DOORS Digicon Information Inc. Digicon Information Inc. Page 1 This section includes Model 800 aluminum insulated overhead sectional doors manufactured by Northwest Doors, with manual, chain or electric operation, with our without windows.

More information

METERING INSTALLATION

METERING INSTALLATION 4.01 METERING SPECIFICATIONS METERING INSTALLATION Metering specifications will be issued to the customer by OPPD. Metering specifications are required before any work is started on all new wiring or additions

More information

ARC STUD WELDING SYSTEMS

ARC STUD WELDING SYSTEMS ARC STUD WELDING SYSTEMS ARE complete stud welding systems which weld ARC studs using the ARC stud welding process. CONSIST OF the following items: An ARC stud welding power supply with built-in timer/control

More information

UNDERGROUND SERVICES SECONDARY

UNDERGROUND SERVICES SECONDARY Reference UNDERGROUND SERVICES SECONDARY Underground services secondary... U- 1 General requirements for underground service... U- 2 Name of parts for underground service... U- 3 Conduit layouts... U-

More information

Installation, Inspection and Maintenance of Dry Type Transformers

Installation, Inspection and Maintenance of Dry Type Transformers Dry Type TX 1 of 8 Installation, Inspection and Maintenance of Dry Type Page 1 of 8 Dry Type TX 2 of 8 Table Of Contents Page Number 1. General... 3 2. Installation... 3 3. Safety Inspections... 4 4. Safety

More information

B. Accept materials on site in original factory packaging, labeled with manufacturer s identification.

B. Accept materials on site in original factory packaging, labeled with manufacturer s identification. SECTION 26 05 02 - BASIC ELECTRICAL REQUIREMENTS PART 1 - GENERAL 1.1 SUMMARY A. Work Included: Furnish all labor, material, services and skilled supervision necessary for the construction, erection, installation,

More information

VPL-3200B Residential Vertical Platform Lift Technical Specifications

VPL-3200B Residential Vertical Platform Lift Technical Specifications Page 1 of 5 VPL-3200B Residential Vertical Platform Lift Technical Specifications MODEL NUMBER: VPL-3200B Series: Models VPL-3210B, VPL-3212B and VPL-3214B (DC-powered units) U.S. F.D.A. CLASSIFICATION:

More information

Unit Substation Transformer Construction Checklist (under 500 kva)

Unit Substation Transformer Construction Checklist (under 500 kva) Unit Substation Transformer Checklist (under 500 kva) Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

Air Cargo Heavy Duty Scissor Lift Premium High Capacity Dock Lift with Conveyor for Safe Transfer of Cargo between Trucks and Dock

Air Cargo Heavy Duty Scissor Lift Premium High Capacity Dock Lift with Conveyor for Safe Transfer of Cargo between Trucks and Dock Air Cargo Heavy Duty Scissor Lift Premium High Capacity Dock Lift with Conveyor for Safe Transfer of Cargo between Trucks and Dock Because of its premium features and ability to provide up to five times

More information

Electric Service Standards

Electric Service Standards V: 1 of 6 A. Padmounted Requirements Complete requirements are contained in FPL specifications given to Customers for individual projects. Typical pad mounted transformer requirements include, but are

More information

Shur-Shot X-Proof Hydrogen Fluoride Alarm Operations Manual

Shur-Shot X-Proof Hydrogen Fluoride Alarm Operations Manual Shur-Shot X-Proof Hydrogen Fluoride Alarm Operations Manual P/N 1000006053 Rev E $7%$QDO\WLFV// //& 733 Dairy Rd. Parkton, Md. 21120 www.atbanalytics.com (410) 733-6365 Table of Contents Chapter 1: Getting

More information

Low Voltage Switchgear Construction Checklist (under 500 kva)

Low Voltage Switchgear Construction Checklist (under 500 kva) Low Voltage Switchgear Checklist (under 500 kva) Project: Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

Inspection Guide for PV Systems in One- and Two- Family Dwellings (For Rooftop Photovoltaic Systems meeting the Standard Plan)

Inspection Guide for PV Systems in One- and Two- Family Dwellings (For Rooftop Photovoltaic Systems meeting the Standard Plan) TOOLKIT DOCUMENT #7 Inspection Guide for PV Systems in One- and Two- Family Dwellings (For Rooftop Photovoltaic Systems meeting the Standard Plan) This document has two sections. Neither section is all-inclusive

More information

FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR

FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR Section 083713- Four Fold Doors- With Single Overhead Mounted Operator Part 1-General 1.1 Related Document: A. Drawing and general provisions of contract,

More information

(Condensed from National Electric Code)

(Condensed from National Electric Code) WIRING, SPECIFICATIONS, INSPECTION, AND METER INSTALLATION PROCEDURES FOR RESIDENTIAL CUSTOMERS SERVED BY SOUTHWEST ARKANSAS ELECTRIC COOPERATIVE CORPORATION Effective April 1, 1974 Revised February 3,

More information

SECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 08332 [08 33 13] COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Metal Counter

More information

ELECTRICAL BULLETIN

ELECTRICAL BULLETIN PO Box 697 Halifax, Nova Scotia B3J 2T8 Labour and Advanced Education ELECTRICAL BULLETIN 2012-01 From: David MacLeod,C.E.I.,P.Eng. Pg 1 of 8 Provincial Chief Electrical Inspector Date : March 1, 2012

More information

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION LIST OF FIGURES...

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION LIST OF FIGURES... DIVISION 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN Contents 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION 13 00 60 LIST OF FIGURES... 6 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN 1. General Requirements

More information

1. Vertical reciprocating conveyor, Hydraulic straddle VRC.

1. Vertical reciprocating conveyor, Hydraulic straddle VRC. PART 1: GENERAL 1.01 Section Includes: 1. Vertical reciprocating conveyor, Hydraulic straddle VRC. a. Machine, controller, platform, structural steel hoist frame. b. Wire mesh enclosure and gates. Related

More information

Communications Page 1 of 9

Communications Page 1 of 9 Page 1 of 9 Last Update: April 23 rd, 2014 Introduction Design In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a

More information

SECTION SLUDGE HOLDING TANK DECANTER PUMP

SECTION SLUDGE HOLDING TANK DECANTER PUMP PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall furnish and install all materials, labor and equipment to put into service the Sludge Holding Tank Decanter Pumping System in accordance with the

More information

SECTION HIGH EFFICIENCY DISTRIBUTION TRANSFORMERS

SECTION HIGH EFFICIENCY DISTRIBUTION TRANSFORMERS SECTION 26 22 13 HIGH EFFICIENCY DISTRIBUTION TRANSFORMERS PART 1 GENERAL 1.1 WORK INCLUDED A. Dry-type, low-voltage, distribution transformers meeting US Department of Energy proposed Candidate Standard

More information

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS 1 Introduction 1.1 In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a utility. It should be assumed that all new

More information

Details of technical leaflets/write-up on various pieces of equipment.

Details of technical leaflets/write-up on various pieces of equipment. Details of technical leaflets/write-up on various pieces of equipment. (1) Insulator Designs: The insulators are provided in one, two, three, or four insulator designs per location and spaced to provide

More information

Customer Owned Meter Enclosures for Self-Contained Watthour Meters

Customer Owned Meter Enclosures for Self-Contained Watthour Meters Revision No. 4 Page 1 of 15 SPECIFICATION Page 2 of 15 RECORD OF SPECIFICATION APPROVALS: This Specification is approved for the inclusion of subject products on the Florida Meter Group s Approved Metering

More information

SECTION INFLUENT EQUALIZATION TANK PUMPS

SECTION INFLUENT EQUALIZATION TANK PUMPS PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall furnish and install all materials, labor and equipment to put into service the Influent Equalization Pumps in accordance with the Contract Drawings

More information

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Welded System

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Welded System SECTION 13096 RADIO FREQUENCY SHIELDING ENCLOSURE RF Welded System Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13096-1 RF WELDED SYSTEM PART 1 GENERAL 1.1 SECTION

More information

PIP PCEPA003 Process Analyzer System Field Installation Guidelines

PIP PCEPA003 Process Analyzer System Field Installation Guidelines January 2016 Process Control PIP PCEPA003 Process Analyzer System Field Installation Guidelines PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities,

More information

Electric Service Requirements. Residential Overhead. Engineering Specification T002. February

Electric Service Requirements. Residential Overhead. Engineering Specification T002. February Electric Service Requirements Residential Overhead Engineering Specification T002 February 2017 0362-16 ENG. SPEC. T002 REV. 3 RESIDENTIAL OVERHEAD INSTALLATIONS page 1 of 12 Table of Contents 1 GENERAL

More information

Installation and Operation Manual

Installation and Operation Manual Installation and Operation Manual Maintenance Bypass Panel Model: SU2030KMBP Tripp Lite follows a policy of continuous improvement. Product specifications are subject to change without notice. 1111 West

More information

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR PART 1 - GENERAL Section 26 05 15 SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR 1.1 Cable shall be 15 kv, shielded, three conductor with ground, stranded copper, with continuously welded and corrugated

More information

ADDENDUM. ADDENDUM # 1 DATE: February 16, 2017

ADDENDUM. ADDENDUM # 1 DATE: February 16, 2017 ADDENDUM ADDENDUM # 1 DATE: February 16, 2017 REFERENCE: Invitation for Bid No.: S-LB-17613 IFB Issue Date: January 30, 2017 Title: River Oaks Elementary School Renewal Architect/Engineer: Architecture

More information