Measuring Air Velocity - presented by Lonnie Glen, Kice Industries 2/28/2018. (and why it is important) Applications for Air

Size: px
Start display at page:

Download "Measuring Air Velocity - presented by Lonnie Glen, Kice Industries 2/28/2018. (and why it is important) Applications for Air"

Transcription

1 (and why it is important) Wednesday, February 28, 2018 Presented by Lonnie Glen, Kice Technical Sales and Quickship Manager Applications for Air Air Activated Processing Grinders Granulators Hammermills Aspirators Pneumatic Conveying Positive Pressure Vacuum (limited to non fluctuating loads) Dust Control Drying/Cooling Reasons to know how to measure air volumes To know if your equipment is operating efficiently Best operation for the least amount of power Sizing new equipment Dust Collection Aspiration Conveying Important to know when to replace equipment Blowers, Cyclone, Filters, Fans Record keeping Plant operations Government agencies 1

2 Measuring air to determine CFM and STATIC PRESSURE of a dust collection system 3.5 w.c. 1 w.c. 0.7 w.c. 0.5 w.c. 1.3 w.c. 2.5 w.c. 3 OD 5 OD 6 OD 7 OD 8 OD 4 w.c. 0.5 w.c. 3 OD 180 CFM 5 OD 520 CFM 6 OD 750 CFM 10 OD 2425 CFM 4 OD 325 CFM 4 OD 325 CFM 4 OD 325 CFM 12 OD 2425 CFM Sum total of CFM: 2,425 CFM Total of HIGHEST static pressure run of the system: 14 w.c. SP Common terms used in measuring air Pitot Tube Device used to measure static and velocity pressure Air Measuring Kit Tool set containing components to measure air, including Pitot tube, Magnehelic gauge(s), tubing, drill bits, charts, calculator, etc. Pressure Differential Gauge Magnehelic Gauge, Manometer, Spring Gauge, Analog, or Digital device/gauge use to measure pressure differential Velocity Speed of air, measured as Feet per Minute (FPM) Volumetric Air Flow Rate Amount of air typically being moved through the system, measured as Cubic Feet per Minute (CFM) Duct Velocity How fast the air, dust or product flies through the duct, measured in FPM Grain dust typically has minimum of 3400 FPM. Wheat typically conveys at 4200 FPM Typical Air Measuring Kit 2

3 Magnehelic Gauge High Pressure Connection Total Pressure Connection Pitot Tube Static Pressure Connection Static Pressure Port Total Pressure Port Low Pressure Connection Common terms used in measuring air Static Pressure Pressure used to overcome the resistance to flow or. The amount of resistance of friction (including the hood, ducting, product and all other components) And.the energy used to move the product from Point A to Point B Usually the longest, smallest diameter run, but not always Velocity Pressure Pressure required to accelerate the mass of air from rest to its existing velocity or.. Air traveling at a given velocity or. Way to calculate velocity Total Pressure Sum total of static and velocity pressures Area Measurement of the inside of a duct Measured in square feet Vector representation of SP, VP, and TP Pressure Inside of a Duct Reprinted from Industrial Ventilation: A Manual of Recommended Practice for Design, 27 th Edition, published by the American Conference of Governmental Industrial Hygienists TP total pressure = SP static pressure VP (velocity pressure) 3

4 Common Terms Air to Cloth Ratio Establishes design capacity of a baghouse filter Ratio between the total amount of CFM and total area of the filter bags 15,000 CFM / 1,555 sq ft of filter area = 9.65:1 Air to Cloth Ratio Rule of Thumb 7 10:1 for Elevator, Cleaning House, and General Suction 7:1 for Secondary Collectors and High Humidity Air Systems 5:1 for Filter/Receiver, Centro Vacs, and Bin Vents Can Velocity Velocity measured inside the filter (in the open space below the bags) Interstitial Velocity Velocity measured inside the filter (between the filter bags) Basic Formula to determine CFM Q = VA Q = ACFM (Volume of Air) V = Velocity (in feet per minute) A = Tube internal cross-section area (in square feet) Follow a few basic principles Obtain the Velocity of the Air Obtain the Area of the duct/tube/pipe at the point of measurement Multiply Velocity x Area to determine volumetric flow rate Why 5 + pipe diameters downstream of fitting? Air after an, fitting, damper, etc. becomes turbulent Allows air to become laminar or more even inside the tubing/ducting/pipe Makes measurements more accurate Reprinted from Publication (R2007) Air Systems, published by the Air Movement and Control Association International, Inc 4

5 Typical Air Measurement Reading Points OUTLET SP AND OPTIONAL VP READING OUTLET SP AND OPTIONAL VP READING INLET SP AND VP READING INLET SP AND VP READING OPTIONAL VP READING NOT GOOD LOCATIONS for Air Measurement Reading Points Right after Right after Turbulent flow Right after Right after Right after To short of straight run after Not good location; difficult to measure area LOCATIONS for Air Measurement Reading Points Not good location; right after Good location Good location Not good location; air too turbulent Not good location; air too turbulent 5

6 By the Book Method of Measuring Air for accurate air flow measurements Safety First Select location 10 pipe diameters, if possible, away from dampers, branches, s, etc. Drill 2 holes 90 degrees apart to allow insertion of Pitot tube Connect Pitot tube static and/or total pressure connections to gauge Need to record temperature and absolute pressure Traverse the tube, recording SP ( w.c.) and VP ( w.c.) readings at published insertion depths Take readings in both planes Calculate velocities using each VP reading Average the velocities to determine Average Velocity (V avg ) in FPM Calculate the Tube Area in square feet at the plane the measurements were taken Multiply Velocity by the Tube Area to get CFM Reality Method of Measuring Air for ESTIMATED STATIC PRESSURE Safety First Select location 5+ pipe diameters, if possible, away from dampers, branches, s, etc. Drill hole to allow insertion of Pitot tube Connect Pitot tube SP port to gauge or Put hose perpendicular to the flow over the hole If using Pitot tube, center the tube inside the duct Record the reading on the gauge Reality Method of Measuring Air for ESTIMATED air flow measurements Safety First Select location 5+ pipe diameters, if possible, away from dampers, branches, s, etc. Drill hole to allow insertion of Pitot tube Connect Pitot tube static and total pressure ports to gauge Record the VP at the center of the duct using the Pitot tube Convert Velocity Pressure (V p ) reading to Velocity (V) FPM Refer to chart for Velocity or calculate 4005 x VP (at STP) Multiply the velocity by.9 for 6 OD and smaller duct or by.95 for ducts 8 OD and larger to ESTIMATE Average Velocity (V avg ) Determine Tube Area in Square Feet In Feet: Area of circle = 3.14 x R 2 or.7854 x Diameter 2 In Inches: Area of circle = 3.14 x R 2 /144 or.7854 x Diameter 2 /144 (144 square inches = 1 square foot) Multiply Velocity by the Tube Area to get CFM 6

7 Measuring Static Pressure By the Book Low pressure connection is hooked up Usually the higher reading gauge Zero out gauge Hold gauge level Traverse readings across tube Measure in 2 planes Pitot Tube is into flow Reality Low pressure connection is hooked up Usually the higher reading gauge Zero out gauge Hold gauge level Take center reading Measure in 1 plane Pitot Tube is into flow Velocity Pressure TP (Total Pressure) SP (Static Pressure) = VP (Velocity Pressure) Velocity = 4005 x VP (at STP) Reprinted from Industrial Ventilation, A Manual of Recommended Practice, 22 nd Edition, published by the American Conference of Governmental Industrial Hygienists Measuring Velocity Pressure Reality Both connections hooked up Usually the lower reading gauge Zero out gauge Hold gauge level Measure in 1 plane Pitot Tube is into flow Read VP at center of duct By the Book Both connections hooked up Usually the lower reading gauge Zero out gauge Hold gauge level Measure in 2 planes Pitot Tube is into flow Traverse readings across tube 7

8 Finding Velocity Example 1: VP reading = 1.1 Velocity = 4200 FPM Example 2: VP reading = 1.75 Velocity = 5298 FPM Example 3: VP reading = 3.60 Velocity = 7599 FPM Calculation: Velocity = 4005 x VP (at STP) Reprinted from Industrial Ventilation, A Manual of Recommended Practice, 22 nd Edition, published by the American Conference of Governmental Industrial Hygienists Finding Volume (Q = V x A) Example 1: Tube = 12 OD and has sq ft area Velocity = 4200 FPM x.95 Average Velocity = 3990 FPM 3990 x = Volume of 3,134 CFM Example 2: Tube = 12 OD and has sq ft area Velocity = 5298 FPM x.95 Average Velocity = x = Volume of 3,953 CFM Example 3: Tube = 12 OD and has sq ft area Velocity = 7599 FPM x.95 Average Velocity = x = Volume of 5,670 CFM Reprinted from Industrial Ventilation, A Manual of Recommended Practice, 22 nd Edition, published by the American Conference of Governmental Industrial Hygienists Velocity readings based on Standard Air Typically, we calculate the Air Velocity from the Velocity Pressure. The calculations are correct for standard air conditions (air with a density of lbs. per cubic foot) and based on 70F ambient air temperature, at sea level and a barometric pressure of HG. Correction for actual conditions For conditions different that standard air we need to correct the velocity reading before we calculate to find the velocity and CFM. For this we need to know the Air Density. Typically we need to know the air temperature and elevation to make a correction to the Air Density. VP Calculation: Velocity (V) = x Air density 8

9 Air Density Calculation Calculation: Velocity (V) = 4005 x V = 4005 x of Velocity Pressure V = 4005 x of 1.0 V = 4005 x 1.0 V = 4005 FPM V (avg) = 4005 x.95 = CFM = V x A CFM = x.7854 CFM = 2988 VP Calculation: Velocity (V) = x Air density V = x of Velocity Pressure divided by the Air Density V = x of 1.0 / V = x V = x V = 4291 FPM V (avg) = 4291 x.95 = CFM = V x A CFM = x.7854 CFM = 3201 VP Assumption: 70F and 0 ASL Assumption: 120F and 1350 ASL Known Data compared to Calculated Data Issue/Problem 1: Sum total of air going to a dust collector is measured at 200% of original design. Result: Short bag lift, High air-tocloth ratio; dusting out at points, additional maintenance issues; line plugging? What changed? What was added? What was taken off line? Something open that is not supposed to be open Issue/Problem 2: Air leg no longer has the capacity it used to have. Result: Fan or Air Power Unit is unable to provide adequate static pressure and conveying line cannot handle the load. Allows you a starting point for checking. Fan belts loose or slipping? Motor over amping? Is it the fan rotation? Is the fan speed? Is it fan wear? Is there a choke point? Is there a leak point? Check the Airlock for leakage? Are filters dirty? Issue/Problem 3: Grinder or Mill is getting too hot. Result: Fan may not be providing enough CFM or static pressure to reduce heat at the mill. Allows you a starting point for checking. Has equipment been relocated? Fan belts loose or slipping? Motor over amping? Is it the feed rate? Is it the fan rotation? Is the fan speed? Is there a choke point? Is there a leak point? Check the Airlock for leakage. 9

10 Why is this information important in an Air System? Make system changes for adequate conveying velocity: For example, downstream duct area must roughly equal the sum of the area of the upstream ducts. A system tour can reveal duct branches that may have issues. Take proof of performance airflow and static pressure measurements: These will show whether you have adequate conveying velocity in all system branches at startup and provide a reference point to which you can go back if rebalancing is needed. Keep records of recent routine system measurements AND follow up when out of acceptable : Data history may show which parts of the system typically fail first (for example, plugged s, blinded filter media, or other component) for corrective action before major events. Assign trained personnel responsibility for the system: Allow your personnel the time, tools, and skills to take the data and complete follow up actions. General Good Practices Increase line size as needed to keep good velocity in the line back to the filter Reduces resistance & keeps dust in suspension. Use lockable dampers or slide gates on each connection point AND MARK FOR REFERENCE Use for balancing & lockout to keep from changes being made. Allow Free Air into the system Cannot pull against a dead head or sealed system & makes use of natural air currents. Seal any leaks in the system Will rob the dust collection system of suction to remove dust & many small leaks will add up. Purchase and learn to use an Air Measuring Kit Will let you measure resistance and static pressure, can use to rebalance a system, and gives you some known data to work with. Use care putting Pitot tube in conveying line or heavy dust line. May clog the small ports in the Pitot tube. Good design, Good volume, Good velocity Dust is in suspension because of correct velocities and velocities are correct to minimize wasting HP. 10

11 BAD design, Good volume, BAD velocity Dust is dropping out (in locations) but system is balanced (at end of system). Additions without rebalancing Dust is NOT in suspension throughout the line System is not balanced. Dust build up inside line until area small enough to carry dust at correct velocity. Air taking path of least resistance. Deductions without rebalancing Dust is in suspension (but at higher velocity) System is balanced (but not correct) May be picking up good product. System works but wasting energy (HP). Once you are done measuring the air Leaving the drilled hole open Usually not so large as to effect the system Can be a point where foreign material can enter Covering the drilled hole Closes a leak point Does not allow foreign material to enter Marking the drilled hole Air Measurement label/magnet Leaves info for next person Self tapping screw Rubber plug Dab of silicone/caulking Duct tape/hvac tape Air Measurement label/magnet 11

12 Closing Comments It is not difficult to take air measurement reading with the correct tools. It can help you in dealing with the manufacturer and minimize any downtime. The information the air readings provide can: Benefit product quality Benefit in product recovery Extend equipment life Save energy Reduce emissions Reduce housekeeping Keep the plant running and out of trouble Thank you for the opportunity to speak today Contact information: Lonnie Glen; / Ph:

NJ AIHA CIH Review Industrial Ventilation

NJ AIHA CIH Review Industrial Ventilation NJ AIHA CIH Review Industrial Ventilation Thomas Block, CIH MPH tblock@aps.rutgers.edu 848-445-2550 2016 American Industrial Hygiene Association, New Jersey Section, Inc. Course Objectives At the end of

More information

Honeywell Thermal Solutions. Engineering Guide

Honeywell Thermal Solutions. Engineering Guide Engineering Guide Honeywell Thermal Solutions Engineering Guide Copyright 2017 by Honeywell Thermal Solutions All Rights Reserved CONTENTS 1. Orifices & Flows Coefficients of Discharge for Various Types

More information

EPA Method 1 Field Procedures Example:

EPA Method 1 Field Procedures Example: EPA Method 1 Field Procedures Step Instruction 100 Is the stack or duct circular or square/rectangle? If square/rectangular go to step 170. 105 Determine the diameter of the stack from one of the following

More information

Operating characteristics of PNEUMATIC GRAIN CONVEYORS By R. W. KLEIS Bulletin 594 UNIVERSITY OF ILLINOIS AGRICULTURAL EXPERIMENT STATION Operating Characteristics of Pneumatic Grain Conveyors' By R. W.

More information

Industrial Ventilation System Monitoring & Maintenance

Industrial Ventilation System Monitoring & Maintenance Industrial Ventilation System Monitoring & Maintenance Gary Q. Johnson, P.E. Health & Environmental Safety Alliance VENT 2006 Chicago May 15, 2006 Ventilation Program Management Paradigm Shift: IV System

More information

Field Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE

Field Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE Field Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE The purpose of this article is to discuss the measuring and reporting of temperatures at heat transfer equipment during the Testing

More information

1.02 Related Sections A. Section Heating, Ventilation and Air Conditioning (HVAC). C. Section Pneumatic and Electric Control HVAC.

1.02 Related Sections A. Section Heating, Ventilation and Air Conditioning (HVAC). C. Section Pneumatic and Electric Control HVAC. PART 1: GENERAL 1.01 Section Includes A. Dual duct terminal units. B. Variable volume regulators. C. Integral damper motor operators. D. Integral controls. 1.02 Related Sections A. Section 23 00 00 Heating,

More information

Alabama Department of Environmental Management Air Division Planning Branch Emission Measurement Section

Alabama Department of Environmental Management Air Division Planning Branch Emission Measurement Section Alabama Department of Environmental Management Air Division Planning Branch Emission Measurement Section Particulate Sampling Guideline & Reporting Format Revision No. 6 December 2003 PARTICULATE SAMPLING

More information

Peerless Pump Company Handbook of Engineering Data

Peerless Pump Company Handbook of Engineering Data Peerless Pump Company Handbook of Engineering Data Brochure EM77 DEFINITION OF PUMP TERMS A.1 A line shaft vertical turbine pump is a vertical-shaft centrifugal or mixed-flow pump with rotating impeller

More information

Alnor HVAC Handbook. A Practical Guide to Performance Measurements in Mechanical Heating, Ventilating and Air Conditioning Systems

Alnor HVAC Handbook. A Practical Guide to Performance Measurements in Mechanical Heating, Ventilating and Air Conditioning Systems Alnor HVAC Handbook A Practical Guide to Performance Measurements in Mechanical Heating, Ventilating and Air Conditioning Systems P/N 2980562 Rev A. Copyright 2007 by TSI Incorporated All Rights Reserved

More information

Page - 1 INSTRUCTION MANUAL - DUCT DESIGN PROGRAM

Page - 1 INSTRUCTION MANUAL - DUCT DESIGN PROGRAM Page - 1 INSTRUCTION MANUAL - DUCT DESIGN PROGRAM The design of a system of ducts is a tedious job requiring repetitive computations and is ideally suited for computers. The requirement that the designer

More information

INDUSTRIAL ACCESSORIES COMPANY

INDUSTRIAL ACCESSORIES COMPANY INDUSTRIAL ACCESSORIES COMPANY Industrial Accessories Company is an industrial design/build and original equipment manufacturer of baghouses, flue gas desulfurization, heavy metal mitigating sorbent injection

More information

DETERMINATION OF CONCENTRATION AND MASS FLOW OF PARTICULATE MATTER IN FLUE GAS FOR STATIONARY SOURCE EMISSIONS

DETERMINATION OF CONCENTRATION AND MASS FLOW OF PARTICULATE MATTER IN FLUE GAS FOR STATIONARY SOURCE EMISSIONS MS 1596: 2003 DETERMINATION OF CONCENTRATION AND MASS FLOW OF PARTICULATE MATTER IN FLUE GAS FOR STATIONARY SOURCE EMISSIONS Presented BY: UiTM A&A Laboratory Malaysia s 1 st University Affiliated Environmental

More information

B. ASHRAE 1991 HVAC Applications Handbook: Chapter 34--Testing, Adjusting and Balancing.

B. ASHRAE 1991 HVAC Applications Handbook: Chapter 34--Testing, Adjusting and Balancing. PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 230593 TESTING, ADJUSTING, AND BALANCING A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Calculate the Costs of Piping System Elements

Calculate the Costs of Piping System Elements Calculate the Costs of Piping System Elements by Ray Hardee, Engineered Software, Inc. Last month s column described the process of creating an energy cost balance sheet for a piping system (see Figure

More information

Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619

Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619 AABC Commissioning Group AIA Provider Number 50111116 Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619 Jim Hall, PE, TBE, CxA Systems Management & Balancing,

More information

Radon Mitigation Technology

Radon Mitigation Technology Radon Mitigation Technology Field Exercise Package Includes: Description of Mentoring Program Mentor Selection Criteria Field Exercises Field Exercise Verification Form Course Evaluation This field exercise

More information

AALSO Summary of Formulas needed for Levels I, II and III.

AALSO Summary of Formulas needed for Levels I, II and III. AALSO Summary of Formulas needed for Levels I, II and III. The information provided below is used in the math portion of the proficiency exams. Please take time to review and learn how to use these formulas

More information

A Quick Check Method For The Design Of Pneumatic Conveying Systems

A Quick Check Method For The Design Of Pneumatic Conveying Systems A Quick Check Method For The Design Of Pneumatic Conveying Systems by Dr David Mills, Pneumatic Conveying Consultant, Old Wives Lees, England INTRODUCTION The design of pneumatic conveying systems is usually

More information

Airflow Measurement for HVAC Systems Comparing Technologies June 11, 2003

Airflow Measurement for HVAC Systems Comparing Technologies June 11, 2003 Airflow Measurement for HVAC Systems Comparing Technologies June 11, 2003 INTRODUCTION The proper selection of airflow measurement devices can be critical to the performance of today s state-of-the-art

More information

AALSO Proficiency Program Level I, II & III

AALSO Proficiency Program Level I, II & III AALSO Proficiency Program Level I, II & III Hello, and welcome to AALSO s 2010 Proficiency Program! AALSO offers a multi-level operator competency acknowledgment program based on test scores received from

More information

YORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM

YORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM YORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM YORK UNITIZED ENERGY RECOVERY VENTILATORS Regardless of building type or rating system, today s building must be as energy

More information

Comparison of Dry Sorbent Injection of Sodium Bicarbonate, Lime, and Carbon and Their Control of Dioxins/Furans, Mercury, Chlorides and Sulfur Dioxide

Comparison of Dry Sorbent Injection of Sodium Bicarbonate, Lime, and Carbon and Their Control of Dioxins/Furans, Mercury, Chlorides and Sulfur Dioxide Comparison of Dry Sorbent Injection of Sodium Bicarbonate, Lime, and and Their Control of Dioxins/Furans, Mercury, Chlorides and Sulfur Dioxide Acid Gas and Toxics Removal at WCA Hospital, Jamestown, NY

More information

SAMPLING AND ANALYTICAL PROCEDURES FOR DETERMINING EMISSIONS OF PARTICLES FROM COMBUSTION OF WASTES

SAMPLING AND ANALYTICAL PROCEDURES FOR DETERMINING EMISSIONS OF PARTICLES FROM COMBUSTION OF WASTES NEW JERSEY STATE DEPARTMENT OF ENVIRONMENTAL PROTECTION NEW JERSEY ADMINISTRATIVE CODE TITLE 7, CHAPTER 27B-1 AIR TEST METHOD 5 SAMPLING AND ANALYTICAL PROCEDURES FOR DETERMINING EMISSIONS OF PARTICLES

More information

Electric Furnace Off-Gas Cleaning Systems Installation at PT Inco ABSTRACT

Electric Furnace Off-Gas Cleaning Systems Installation at PT Inco ABSTRACT Electric Furnace Off-Gas Cleaning Systems Installation at PT Inco Paykan Safe and Matt Russell WorleyParsons Gas Cleaning, Irving, Texas USA ABSTRACT PT Inco is a ferronickel smelter in Soroako, Sulawesi,

More information

Reducing Maintenance and Saving Fuel with Ellison s Portable Steam Calorimeter

Reducing Maintenance and Saving Fuel with Ellison s Portable Steam Calorimeter 900 SERIES ELLISON STEAM CALORIMETER OPERATION AND MAINTENANCE MANUAL Reducing Maintenance and Saving Fuel with Ellison s Portable Steam Calorimeter Ellison's unique Calorimeter combines the advantages

More information

SP Standard Profile. Flanged to Duct Install Type THERMAL BREAKS OPPOSED ACTION PARALLEL ACTION. T.A. Morrison & Co. Inc.

SP Standard Profile. Flanged to Duct Install Type THERMAL BREAKS OPPOSED ACTION PARALLEL ACTION.  T.A. Morrison & Co. Inc. 1 SUBMITTAL DATA Series 9000 BF Thermally Insulated Damper with Thermally Broken Frames & Blades SP Standard Profile Flanged to Duct Install Type THERMAL BREAKS OPPOSED frame is 4 (101.6 mm) deep x 1 (25.4

More information

Filter Media 452 sq. ft. (42 sq. m) Accu-Rated Airflow 900 cfm (425 L/sec.) Sound Level Approximately 77 dba at 5 ft. (1.5 m)

Filter Media 452 sq. ft. (42 sq. m) Accu-Rated Airflow 900 cfm (425 L/sec.) Sound Level Approximately 77 dba at 5 ft. (1.5 m) FILTAIR Capture 5 Issued July 2016 Index No. AY/3.5 Welding Safety and Health Quick Specs Industrial Applications Heavy equipment manufacturing Fabrication Maintenance and repair operations Processes Stick

More information

INVENTION ON SAMPLING BY YUNEL

INVENTION ON SAMPLING BY YUNEL A NEW ERA IN SAMPLING INVENTION ON SAMPLING BY YUNEL NEW TECHNOLOGY ON SAMPLING SYSTEMS OVER CONVEYOR 'SAMPLING SYSTEM WITH SUPER SHOCK PRINCIPLE IS IN CHARGE OVER CONVEYOR BELTS IN A COAL MINE 2 In New

More information

Measuring Up. Tools for High Performance Building Performance. RESNET 2008 San Diego, CA February 20, 2008 Bill Spohn. Bill Spohn, testo, inc.

Measuring Up. Tools for High Performance Building Performance. RESNET 2008 San Diego, CA February 20, 2008 Bill Spohn. Bill Spohn, testo, inc. Measuring Up Tools for High Performance Building Performance RESNET 2008 San Diego, CA February 20, 2008 Bill Spohn Measuring up Building performance evaluation Observation and measurements. Principles

More information

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

For sale by Intercem. Example of a cement grinding plant with used / refurbished ball mill and partial new auxiliary equipment

For sale by Intercem. Example of a cement grinding plant with used / refurbished ball mill and partial new auxiliary equipment Used equipment For sale by Intercem 1 pre-owned clinker grinding plant with ball mill ø 3,2m x 10,6 m for approx. 40 t/h OPC at 3000 Blaine (I01032) Example of a cement grinding plant with used / refurbished

More information

Energy Effort of Air Distribution Systems

Energy Effort of Air Distribution Systems Energy Effort of Air Distribution Systems F. Kolarik Content Introduction Energy effort of air distribution systems Method of calculation Example Further investigations Introduction Increasing requirements

More information

METHOD 2 - DETERMINATION OF STACK GAS VELOCITY AND VOLUMETRIC FLOW RATE (TYPE S PITOT TUBE) NOTE: This method does not include all of the

METHOD 2 - DETERMINATION OF STACK GAS VELOCITY AND VOLUMETRIC FLOW RATE (TYPE S PITOT TUBE) NOTE: This method does not include all of the 214 METHOD 2 - DETERMINATION OF STACK GAS VELOCITY AND VOLUMETRIC FLOW RATE (TYPE S PITOT TUBE) NOTE: This method does not include all of the specifications (e.g., equipment and supplies) and procedures

More information

CROP PROCESSING ENGINEERING Cleaning and Sorting

CROP PROCESSING ENGINEERING Cleaning and Sorting CROP PROCESSING ENGINEERING Cleaning and Sorting Comparative commercial value of a farm product is a function of its grade factor. Grade factors (that apply in various combinations to all products produced

More information

Silica. Jim Gillespie, Hilti North America. Gary Hatcher, NiSource. Tina Weeks, Zachry Group

Silica. Jim Gillespie, Hilti North America. Gary Hatcher, NiSource. Tina Weeks, Zachry Group Silica Jim Gillespie, Hilti North America Gary Hatcher, NiSource Tina Weeks, Zachry Group Respirable Crystalline Silica EEI Contractor Meeting April 27, 2017 Introduction OSHA has issued a standard to

More information

HVAC Procedures and Forms Manual. Second Edition

HVAC Procedures and Forms Manual. Second Edition HVAC Procedures and Forms Manual Second Edition i This page intentionally left blank ii HVAC Procedures and Forms Manual Second Edition by Herb Wendes, P.E. THE FAIRMONT PRESS, INC. Lilburn, Georgia MARCEL

More information

Water Utility Science Water Math and Hydraulics 050. Name: Date:

Water Utility Science Water Math and Hydraulics 050. Name: Date: Water Utility Science Water Math and Hydraulics 050 Name: Date: Note: Please show all of your calculations for each problem no matter how simple the problem may seem. Please use the accompanying pieces

More information

Document Title: Doc No: FRM B4-59 Rev No: Page: Of: Thermal Insulation Program Certification Report

Document Title: Doc No: FRM B4-59 Rev No: Page: Of: Thermal Insulation Program Certification Report New 1 7 Number: 11026-001.01-KCR Issue Date: 2/25/2016 Revision Date: N/A Re-evaluation Date: 2/25/2019 Licensee EPA Organizational ID: 1020646 This is issued by Keystone Certifications, Inc. (KCI) and

More information

CertainTeed OPTIMA. Installation Instruction Manual

CertainTeed OPTIMA. Installation Instruction Manual CertainTeed OPTIMA Installation Instruction Manual TABLE OF CONTENTS OPTIMA System... 2 System Description... 2 Fabric Installation... 3-4 Insulation Installation... 4 Equipment and Blowing Machine Settings...

More information

Pulverized Coal Extractive Testing Methods Evaluation at the EPRI Coal Flow Loop

Pulverized Coal Extractive Testing Methods Evaluation at the EPRI Coal Flow Loop Pulverized Coal Extractive Testing Methods Evaluation at the EPRI Coal Flow Loop Robert Mudry, P.E. Matthew Fleming Airflow Sciences Corporation Livonia, Michigan Richard Brown Jose Sanchez The Electric

More information

Equipment for Engineering Education

Equipment for Engineering Education Equipment for Engineering Education Operating Instructions HM70.24 Boundary Layer Plate G.U.N.T. Gerätebau GmbH P.O. Box 25 D-2288 Barsbüttel Germany Phone (040) 670854-0 Fax (040) 670854-4 Table of Contents

More information

BAG FILTERS (BAGHOUSES)

BAG FILTERS (BAGHOUSES) BAG FILTERS (BAGHOUSES) Bag Filters (baghouses) have been our core product for over 30 years. With our own proprietary technology, our Bag Filters offer the highest particulate removal efficiency on the

More information

Emission Factors for Non-Atomized Application of Gel Coats used in the Open Molding of Composites

Emission Factors for Non-Atomized Application of Gel Coats used in the Open Molding of Composites Emission Factors for Non-Atomized Application of Gel Coats used in the Open Molding of Composites Robert A. Haberlein, Ph.D., QEP Engineering Environmental Annapolis, MD 21401 July 17, 2001 Introduction

More information

Portable Ventilator Product Catalog

Portable Ventilator Product Catalog Portable Ventilator Product Catalog WELCOME For more than 0 years, COPPUS portable ventilators and cooling products have been recognized as leaders in providing reliable, ventilation to meet the demands

More information

metals temperature limits.

metals temperature limits. 9:41 Page 39 Richard F. Storm, Stephen K. Storm and Sammy Tuzenew, Storm Technologies, Inc., US, consider how to conduct a comprehensive diagnostic test on a pulverised coal-fuelled boiler. T Tuning of

More information

High Efficiency Liquid-Solid Separators

High Efficiency Liquid-Solid Separators High Efficiency Liquid-Solid Separators Continuous Filtration with Zero Maintenance ehtx Features and Benefits: Filter performance rated to remove 98% of all solids 44 micron (325 mesh), 2.6 specific gravity,

More information

Types of Hydropower Facilities

Types of Hydropower Facilities Types of Hydropower Facilities 1 Impoundment Hydropower- uses a dam to store water. Water may be released either to meet changing electricity needs or to maintain a constant water level. 2 Run-of-River

More information

TYPES OF SEWAGE PUMPS. Solids Handling Pumps: Grinder Pumps: Effluent Pumps:

TYPES OF SEWAGE PUMPS. Solids Handling Pumps: Grinder Pumps: Effluent Pumps: Effluent Pumps: Effluent pumps are the pumps most often used in small on-site systems. They are designed to pump effluent, the effluent flowing out of a septic tank. This effluent is relatively clear liquid

More information

Page of ENGINEERING DATA - HOT WATER CAPACITIES, CALCULATIONS AND CORRECTION FACTORS Use the following two tables to determine

Page of ENGINEERING DATA - HOT WATER CAPACITIES, CALCULATIONS AND CORRECTION FACTORS Use the following two tables to determine ENGINEERING DATA - HOT WATER CAPACITIES, CALCULATIONS AND CORRECTION FACTORS Use the following two tables to determine The performances reflected in these tables are based on 1. Heating Capacity (MBH)

More information

CHAPTER 12 TRICKLING FILTER PLANTS

CHAPTER 12 TRICKLING FILTER PLANTS CHAPTER 12 TRICKLING FILTER PLANTS TM 5-814-3/AFM 88-11, Volume III 12-1. General considerations. Trickling filter plants have been justified by their low initial cost, low operating and maintenance costs,

More information

ROOF MOUNT KIT OWNERS MANUAL

ROOF MOUNT KIT OWNERS MANUAL ROOF MOUNT KIT OWNERS MANUAL Made in the USA by: Primus Wind Power, Inc. 938 Quail St. Lakewood, CO 80215 Phone: (303) 242-5820 www.primuswindpower.com AIR is a trademark of Primus Wind Power, Inc. ROOF

More information

Mill Inerting and Pulverizer/Mill Explosion Mitigation

Mill Inerting and Pulverizer/Mill Explosion Mitigation Mill Inerting and Pulverizer/Mill Explosion Mitigation Richard P. Storm richardstorm@innovativecombustion.com (205) 453-0236 Coal Mills are the Heart of a Coal Fired Plant Maximum capacity, reliability

More information

New Coal Handling Transfer Chute Technologies

New Coal Handling Transfer Chute Technologies New Coal Handling Transfer Chute Technologies Significantly Improve the Operation by Increasing Efficiencies, Reducing Maintenance, and Increasing Operating Margins INTRODUCTION The success of any bulk

More information

NEBBinar: Managing Building Performance through Commissioning. March 28, 2013

NEBBinar: Managing Building Performance through Commissioning. March 28, 2013 NEBBinar: Managing Building Performance through Commissioning March 28, 2013 0 Moderator Jim Huber, NEBB Vice President and President of Complete Commissioning Jim Huber is the President of Complete Commissioning.

More information

Joint Committee Issue Paper

Joint Committee Issue Paper NSF Standard(s) Impacted: Background: Provide a brief background statement indicating the cause and nature of concern, the impacts identified relevant to public health, public understanding, etc, and any

More information

All of Alaska in Zone 7 except for the following Boroughs in Zone 8: Northwest Arctic. Yukon-Koyukuk. North Slope ADD INSULATION TO ATTIC

All of Alaska in Zone 7 except for the following Boroughs in Zone 8: Northwest Arctic. Yukon-Koyukuk. North Slope ADD INSULATION TO ATTIC DO-IT YOURSELF ATTIC INSTALLATION INSTRUCTIONS GREENFIBER CELLULOSE FIBER INSULATION HOW TO INSTALL 1 Calculate How Much GreenFiber Insulation You Need First, determine the R-value recommended for your

More information

Pipeline Material, Orientation, and Bends

Pipeline Material, Orientation, and Bends 8 Pipeline Material, Orientation, and Bends 1 INTRODUCTION A major advantage that pneumatic conveying systems have over alternative mechanical conveying systems is in flexibility in continuous pipeline

More information

Environmental Systems and Services - Air Pollution Control. Jet III Pulse Jet Dust Collectors

Environmental Systems and Services - Air Pollution Control. Jet III Pulse Jet Dust Collectors nvironmental Systems and Services - Air Pollution Control Jet III Pulse Jet Dust Collectors Siemens Wheelabrator Jet III missions from cement kilns Ventilation for two 43-ton ladle metallurgy stations

More information

SPILL ESTIMATION. Not Just A Guess Anymore

SPILL ESTIMATION. Not Just A Guess Anymore SPILL ESTIMATION Not Just A Guess Anymore SPILL ESTIMATION Under current regulations accurate spill estimation has become critical to the operation and maintenance of a sanitary collection system Reporting

More information

HYDRAULIC DEMONSTRATION CHANNEL

HYDRAULIC DEMONSTRATION CHANNEL HYDRAULIC DEMONSTRATION CHANNEL PACKING LIST Pitot-Static Tube and Manometer Tube Flow Meters 1. 48 Long Differential Manometer 2. Clear Tubing 3. Pitot-static Tube Clamp 4. Pitot-static Tube 1. Venturi

More information

TEST REPORT SCOPE: EMISSIONS, EFFICIENCY AND OUTPUT FUEL: EPA TEST FUEL (CRIBS) TEST STANDARD: EPA MODEL: S245E WOOD STOVE

TEST REPORT SCOPE: EMISSIONS, EFFICIENCY AND OUTPUT FUEL: EPA TEST FUEL (CRIBS) TEST STANDARD: EPA MODEL: S245E WOOD STOVE TEST REPORT SCOPE: EMISSIONS, EFFICIENCY AND OUTPUT FUEL: EPA TEST FUEL (CRIBS) TEST STANDARD: EPA MODEL: S245E WOOD STOVE Notice to reader: Our S245E wood stove was tested as part of our 1.3 Series (S244)

More information

ters them into a hammermill at a constant feedrate. The hammermill reduces the kernels to a powder that has the consistency of cornmeal. This discharg

ters them into a hammermill at a constant feedrate. The hammermill reduces the kernels to a powder that has the consistency of cornmeal. This discharg Ethanol research center toasts new production line Case history The National Corn-to-Ethanol Research Center (NCERC), Edwardsville, Ill., operates a full-scale ethanol pilot plant facility on the campus

More information

Dust Recovery Collector Systems. University of Iowa Iowa City, IA. Considerations for NAAQS & NFPA Compliance

Dust Recovery Collector Systems. University of Iowa Iowa City, IA. Considerations for NAAQS & NFPA Compliance Prepared by: Sebesta Blomberg Contact: Mike Svensk, PE 2381 Rosegate St. Paul, MN 55113 Main: 651-634-0775 Fax: 651-634-7400 email: msvensk@sebesta.com Dust Recovery Collector Systems Considerations for

More information

Steven L. Alderman, Michael S. Parsons, and Charles A. Waggoner. Institute for Clean Energy Technology, Mississippi State University

Steven L. Alderman, Michael S. Parsons, and Charles A. Waggoner. Institute for Clean Energy Technology, Mississippi State University The Effects of Media Velocity and Particle Size Distribution on Most Penetrating Particle Size and Filter Loading Capacity of 12 x12 x11.5 AG 1 HEPA Filters Steven L. Alderman, Michael S. Parsons, and

More information

Flow Meter Calibration

Flow Meter Calibration fluid mechanics H4 A compact unit that compares and shows the accuracy, losses and use of fundamental flow meters Key Features Unique quick-change flow meter adaptors and pressure connections Four tube

More information

289 Series Spring-Loaded Relief Valves

289 Series Spring-Loaded Relief Valves 8/9 289 Series Spring-Loaded Relief Valves W187-2 W187-2 W21-1 W29-2 1-INCH TYPE 289H AND 289HH 2-INCH TYPE 289H Figure 1. Type 289H and 289HH Relief Valves The 289 Series relief valve is a throttling

More information

A Guide to Understanding Ventilation Systems.

A Guide to Understanding Ventilation Systems. A Guide to Understanding Ventilation Systems. Control of Substances Hazardous to Health Regulations 2002 A Guide to Understanding Ventilation Systems A guide to understanding ventilation systems. This

More information

CEA Guidelines for Ash Handling Plants

CEA Guidelines for Ash Handling Plants By K. P. Shah Email: kpshah123[at]gmail.com (Please replace [at] with @) Committed to improve the Quality of Life Selected information on ash handling plants from standard design criteria / guidelines

More information

Screening, Definition: The unit involved is called a screen.

Screening, Definition: The unit involved is called a screen. Screening, Definition: Screening is a unit operation that separates materials in and/or on water (found in different sizes) from water and from entering water treatment facilities and mains. The unit involved

More information

TEST REPORT. EVALUATION CENTER Intertek Testing Services NA Inc Murphy Drive Middleton, WI 53562

TEST REPORT. EVALUATION CENTER Intertek Testing Services NA Inc Murphy Drive Middleton, WI 53562 TEST REPORT REPORT NUMBER: 102741836MID-001bR2 REPORT DATE: October 24, 2016 REVISED REPORT DATE: August 7, 2017 REVISED REPORT DATE: August 11, 2017 REVISED REPORT DATE: September 6, 2017 EVALUATION CENTER

More information

ABSTRACT I. INTRODUCTION II. METHODS AND MATERIAL

ABSTRACT I. INTRODUCTION II. METHODS AND MATERIAL 2017 IJSRSET Volume 3 Issue 2 Print ISSN: 2395-1990 Online ISSN : 2394-4099 Themed Section: Engineering and Technology Chiller and AHU Design for A commercial Usage S M Azfar Hashmi, Mirza Muneer Baig,

More information

Southwest Clean Air Agency NE 99 th St, Suite 1294, Vancouver, WA 98682

Southwest Clean Air Agency NE 99 th St, Suite 1294, Vancouver, WA 98682 Source Test Guidance Test plans are required to be submitted to SWCAA prior to testing. Generally the plans must be submitted 2 weeks prior to testing but may be different based on individual facility

More information

Installation Guide D-Shape

Installation Guide D-Shape Installation Guide D-Shape Thank you for selecting a DuctSox ventilation system. This guide should be helpful for installing Surface Mount Suspension Systems. Sections of fabric will be labeled, assembled,

More information

OPERATION, MAINTENANCE AND PARTS MANUAL

OPERATION, MAINTENANCE AND PARTS MANUAL OPERATION, MAINTENANCE AND PARTS MANUAL MODEL: LOVA SERIES 4 REED, provides this manual for the guidance of all owners, operators and servicing personnel in order to obtain the longest possible trouble-free

More information

Module 9 : Sewage And Storm water Pumping Stations. Lecture 11 : Sewage And Storm water Pumping Stations

Module 9 : Sewage And Storm water Pumping Stations. Lecture 11 : Sewage And Storm water Pumping Stations 1 P age Module 9 : Sewage And Storm water Pumping Stations Lecture 11 : Sewage And Storm water Pumping Stations 2 P age 9.1 Introduction There are certain locations where it is possible to convey sewage

More information

DURA-LIFE BAG FILTERS

DURA-LIFE BAG FILTERS MAKE A CHANGE TO THE BETTER Can t think of a good reason to change your brand of bag filters? Donaldson Torit just provided the reason Dura-Life bag filters that outlast, outperform and outvalue standard

More information

Agilent InfinityLab Preparative Flow Cells for MWD & DAD

Agilent InfinityLab Preparative Flow Cells for MWD & DAD Agilent InfinityLab Preparative Flow Cells for MWD & DAD Technical Note This technical note describes the preparative flow cells for the Agilent 1260 Infinity II DAD WR (G7115A) and Agilent 1260 Infinity

More information

air classification UCX air classifier series

air classification UCX air classifier series UCX air classifier series The process of air classification is of critical importance for many grinding operations. Generally the overall energy consumption for grinding can be reduced drastically provided

More information

763.389.9475 www.erdmanautomation.com The Erdman 3M VHB Structural Glazing Tape Applicator, Frame Assembly & Glass Lay-in System Erdman 3M VHB Structural Glazing Tape Applicator, Frame Assembly and Glass

More information

SUB-SLAB DEPRESSURIZATION SYSTEM DESIGN AND INSTALLATION

SUB-SLAB DEPRESSURIZATION SYSTEM DESIGN AND INSTALLATION SUB-SLAB DEPRESSURIZATION SYSTEM DESIGN AND INSTALLATION Prepared for: 1500 East Bannister Road, Room 2101 Kansas City, Missouri, 64131-3088 Prepared by: 6750 Antioch Road, Suite 305 Merriam, Kansas 66204

More information

Utility Flow Metering for Steam and Heated/Chilled Water: A Tutorial. Richard Gruskos Flow Products Manager Kessler Ellis Products

Utility Flow Metering for Steam and Heated/Chilled Water: A Tutorial. Richard Gruskos Flow Products Manager Kessler Ellis Products Utility Flow Metering for Steam and Heated/Chilled Water: A Tutorial Richard Gruskos Flow Products Manager Kessler Ellis Products Review Flow Metering Principles: Flow Meters and Flow Computers Utility

More information

CHAPTER 6 : GAS SAMPLING SYSTEMS

CHAPTER 6 : GAS SAMPLING SYSTEMS CHAPTER 6 : GAS SAMPLING SYSTEMS 1 Scope : 1.1 This Chapter describes two types of gas sampling systems in paragraphs 2.1 and 2.2 meeting the requirements specified in para 4.2 of Chapter 3 of this Part.

More information

Water Quality Specification for Power Supplies

Water Quality Specification for Power Supplies Technical Note #6 Water Quality Specification for Power Supplies Introduction The cooling water for Alpha Scientific Power Supplies must meet certain minimum specifications in regard to quality and flow

More information

TruTech Technical Training

TruTech Technical Training TruTech Technical Training Understanding Equipment Operation The rest of the story. Part IV Going where no technician has gone before There are no theories in HVAC/R! Air conditioning is made of scientific

More information

Applications of AIRMaster+ in Real Industrial Facilities

Applications of AIRMaster+ in Real Industrial Facilities Applications of AIRMaster+ in Real Industrial Facilities Satyen Moray, Energy & Resource Solutions, Inc. Mark D Antonio, Energy & Resource Solutions, Inc. Yogesh Patil, Energy & Resource Solutions, Inc.

More information

Report Prepared by John Meeker ScD, CIH Edited by Pam Susi, MSPH, CIH March 1, 2013 LEV-E-W1-Trion

Report Prepared by John Meeker ScD, CIH Edited by Pam Susi, MSPH, CIH March 1, 2013 LEV-E-W1-Trion Welding Fume Local Exhaust Ventilation (LEV)Evaluation: the Trion AirBoss One-Man Portable LEV System Conducted between August 28-30, 2012 at Pipefitters Local 597 Training Center, Mokena, IL Report Prepared

More information

CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH

CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH Rev. 1.3 HVAC Guide Specifications Chilled and Hot Water Universal Mount Fan Coil 2-Pipe Nominal Size: 60,000

More information

92831 TEL: (714) FAX:

92831 TEL: (714) FAX: Document No. 1800-59 MicroVac Portable Cleanroom Vacuum Cleaner Copyright 2010 Terra Universal Inc. All rights reserved. Revised October 2010 Terra Universal, Inc. TerraUniversal.com 800 S. Raymond Ave.

More information

TOTAL SUSPENDED SOLIDS REMOVAL TEST OF A HIGH DENSITY POLYETHYLENE WATER QUALITY UNIT. By James T. Mailloux Dean K. White

TOTAL SUSPENDED SOLIDS REMOVAL TEST OF A HIGH DENSITY POLYETHYLENE WATER QUALITY UNIT. By James T. Mailloux Dean K. White TOTAL SUSPENDED SOLIDS REMOVAL TEST OF A HIGH DENSITY POLYETHYLENE WATER QUALITY UNIT By James T. Mailloux Dean K. White Submitted to ADVANCED DRAINAGE SYSTEMS 250-04/H1098F September 2004 TOTAL SUSPENDED

More information

Liquid Stream Fundamentals: Grit Removal

Liquid Stream Fundamentals: Grit Removal FACT SHEET Liquid Stream Fundamentals: Grit Removal Grit removal is an essential component of the wastewater treatment process. Not only does the removal of grit help protect downstream equipment from

More information

Introduction. Disclaimer. Table of contents

Introduction. Disclaimer. Table of contents Updated July 18, 2012 Introduction The Cambridge Elevating Limited-Use / Limited-Application Elevator is designed to service schools, libraries, low rise, low occupancy commercial buildings, churches and

More information

DESIGNING COMMERCIAL SUB-SLAB DEPRESSURIZATION SYSTEMS

DESIGNING COMMERCIAL SUB-SLAB DEPRESSURIZATION SYSTEMS DESIGNING COMMERCIAL SUB-SLAB DEPRESSURIZATION SYSTEMS Presented at the 2002 - AARST - 12 th Annual International Radon Symposium in Reno, Nevada Bill Brodhead WPB Enterprises, Inc., 2844 Slifer Valley

More information

W ater T alk. Field Corrosion Testing using Coupons

W ater T alk. Field Corrosion Testing using Coupons W ater T alk Field Corrosion Testing using Coupons Volume 12, Issue 1 April 2012 Most Cooling Water systems are continuously in use. Therefore it is rare to have access to inspect the actual system to

More information

Imagineering Air-Driven Solutions.

Imagineering Air-Driven Solutions. Imagineering Air-Driven Solutions. Pneumatic Conveying Systems Air-driven solutions. Corporate Profile VAC-U-MAX specializes in design and manufacture of pneumatic systems and support equipment for conveying,

More information

Slurry sampling. Benefits. Outotec slurry sampling

Slurry sampling. Benefits. Outotec slurry sampling Slurry sampling Outotec slurry sampling Sampling from process streams and delivery to analyzer is crucial in process monitoring. Information on the process pipe, flow rates and the amount of sample required,

More information

DRY HYDRATED LIME INJECTION FOR COAL-FIRED BOILER FLUE GAS DESULFURIZATION (FGD) FOREWORD

DRY HYDRATED LIME INJECTION FOR COAL-FIRED BOILER FLUE GAS DESULFURIZATION (FGD) FOREWORD FOREWORD When coal is oxidized (burned) as fuel, the elemental sulfur it contains is converted to SO 2. Some of this SO 2 is converted to SO 3 when oxygen leftover from the combustion process causes further

More information

BLOWER COILS COMMERCIAL

BLOWER COILS COMMERCIAL BLOWER COILS COMMERCIAL 2 THRU 5 TONS SPLIT SYSTEM EBP / EBX / EBXX Series FEATURES Representative photo only, some models may vary in appearance. Listed By Underwriters Laboratories Grooved copper tubing

More information

Pulverizer Plant O&M Aspects

Pulverizer Plant O&M Aspects Pulverizer Plant O&M Aspects Dr. T K Ray NTPC Limited E-mail: rayt3@asme.org Contents Coal characteristics, fineness, combustion interrelationship Mill operational issues Constructional features and maintenance

More information

SECTION AIR FILTERS

SECTION AIR FILTERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information