Silicone Dielectric Fluids Fredi Jakob, Karl Jakob, Nicholas Perjanik Analytical ChemTech International, Inc.

Size: px
Start display at page:

Download "Silicone Dielectric Fluids Fredi Jakob, Karl Jakob, Nicholas Perjanik Analytical ChemTech International, Inc."

Transcription

1 Silicone Dielectric Fluids Fredi Jakob, Karl Jakob, Nicholas Perjanik Analytical ChemTech International, Inc. I. Introduction Mineral oil based dielectric fluids have been used more extensively than other dielectric fluids in electrical equipment because of their wide availability, low cost and excellent physical and electrical properties. Their only shortcoming is their relatively low flash and fire points. Polychlorinated bi-phenyls, PCB s, known generically as Askarels, were developed as alternative dielectric fluids. PCB s have excellent dielectric properties and they are far less flammable than mineral oils. Government agencies, at one time, mandated the use of PCB s whenever there was a safety concern related to fluid flammability. Unfortunately PCB s turned out to be an environmentally hazardous material. Federal regulations subsequently mandated elimination of PCB s. This regulation lead to a search for replacement dielectric fluids that are not as flammable as mineral oil. Two major types of fluids were developed. The first is a less flammable hydrocarbon fluid, which could be either a natural or synthetic blend of hydrocarbons. This type of hydrocarbon fluid is often designated as a high molecular weight hydrocarbon, HMWH. The second type of less flammable fluid type, which was first introduced in 1974, is a synthetic silicone based polymer. It has been estimated that as of 1993 over 100,000 transformers have been filled with silicone fluids and more than 25,000 have been filled with HMWH 1. The flash and fire points of these alternative fluids are compared with both mineral oil and Askarels in Table 1. 1

2 Table 1. Flash and Fire Points of Dielectric Fluids 1 Dielectric Fluid Askarel Mineral Oil HMWH Silicone Flash Point o C Fire Point o C None The large difference between the flash and fire points of silicone fluid, 43 0 C, compared to a difference of only 15 0 C for mineral oil is a significant safety factor. This difference is due to the low volatility of silicone fluids which results in very little vapor production when the fluid is heated. Complete combustion of silicone fluid results in the production of primarily silica, SiO 2, water and carbon dioxide. In the case of a fire the amorphous crust of silica that forms on the fluid surface reduces the heat flux to the burning fluid which in turn reduces the combustion rate. A primary fire concern is the heat release rate of a burning dielectric fluid. The greater the heat release rate the greater the danger of a transformer fire spreading to adjacent structures. Figure 1. Shows the heat release data for several types of dielectric fluids. 2

3 1600 Heat Release Rate (kw/m^2) Radiative Convective Total 0 Mineral Oil HMW Hydrocarbon Silicone Figure 1. Heat Release Data for Dielectric Fluids 1 II. Physical and Chemical Properties of Silicone Dielectric Fluids 2. Silicone fluids are synthetic linear polymers having the molecular structure shown in Figure H 3 C H 3 C H 3 C Si R O Si O Si R n CH 3 CH 3 CH 3 Figure 2. Molecular Structure of Synthetic Silicone Fluids 3

4 The organic groups, shown as R, can be virtually of any type and the R groups attached to any one silicon atom can be the same or different. The polymer terminating groups are generally trimethyls. The average value of n and the molecular weight of the attached organic groups determines the molecular weight of the polymer. Critical physical properties of the silicon fluid such as viscosity, volatility and thermal conductivity are determined by the molecular weight. Increased molecular weight results in increased viscosity, lower volatility and lower thermal conductivity. Silicone polymers in which both of the organic groups are methyl groups, CH 3, are called Polydimethysiloxanes (PDMS). The value of n in these fluids can vary from 0 to over Despite this very large range of molecular weights the PDMS fluids do not solidify over a wide range of temperatures. Viscosity increases from 0.65 to 2,500,000 centistokes as n goes from 0 to This wide range of viscosities allows the PDMS fluids to be used in a variety of applications such as dielectric fluids, anti-foam agents and heat- transfer fluids. These low toxicity silicone fluids are thermally and chemically stable and are also used, at low concentrations, in cosmetics, auto polishes and paints. A typical PDMS fluid, for use in transformers, in which all of the R groups are methyl groups has a viscosity of 50 centistokes. Table 2 provides comparative data for the three types of dielectric fluids discussed above. Values listed are based on the pertinent IEEE acceptance guides for each fluid 2. 4

5 Table 2. Physical and Chemical Characteristics of Dielectric Fluids,as Supplied 2 Property ASTM Method Mineral Oil HMWH Fluids Silicon Fluid Dielectric Strength (kv) D Dissipation Factor (Power Factor) 25 o C 100 o C D Pour Point o C D Specific Gravity 25 o C D Interfacial Tension (dyne/cm) 25 o C D Viscosity 0 o C 25 o C 40 o C 100 o C D-445 D max max. 3.0 max. 2,200-2, Moisture Content, ppm max. D Flash Point o C D (note) 268 (note) Fire Point o C D (note) 371 (note) III. Maintenance of Silicone Fluids Dielectric fluids used in electrical equipment have three essential functions. They must be good insulators, provide thermal conduction and quench arcs. These essential functions must be maintained throughout the life of the fluid. Fluids used in transformers are all relatively stable and should last indefinitely in an ideal environment. In practice, dielectric fluids are subjected to thermal and electrical stresses that may alter the composition of the fluid. Undesirable materials may enter and mix with the fluids. Impurities, such as moisture and oxygen, can enter the equipment from the surrounding atmosphere or they can originate from materials, such as paper insulation and coatings, used in the construction of the equipment. Impurities interact chemically or physically with the 5

6 insulating fluids and alter their properties. Moisture from the atmosphere, or cellulose particles, from the paper insulation, dissolve or disperse in the fluid and reduce its insulating quality. Oxygen reacts chemically with mineral oil and can produce acid and sludge. Fortunately silicone fluids are more oxidation resistant than oil and acid formation is not a significant problem. The ASTM has developed a series of diagnostic tests for determination of the characteristics, physical properties, purity and functionality of insulating fluids. These ASTM methods were developed for evaluation of mineral oils but they are applicable, with minor modifications, to the evaluation of silicone fluids. The ASTM test methods that are recommended for maintenance testing of silicone fluids are listed in Table 3. 6

7 Table 3. Recommended Maintenance Tests for Silicone Transformer Fluid 3 Minimum Testing Test Procedure Acceptable result Unacceptable result may indicate Visual Inspection Crystal clear-free of particles Particulates, free water, color change Dielectric Breakdown ASTM D-877 >35 kv for fresh liquid >25 kv in transformer Particulates or water present Additional Recommended Testing Water Content ASTM D- 1533B Volume Resistivity ASTM D < 100 Excess water present > 1 x Water or contamination present Interfacial Tension ASTM D Contamination present Power Factor ASTM D-924 < 0-1% Polar/ionic contamination Viscosity ASTM D cst Degradation or contamination Fire Point ASTM D-92 > 340 o C Contamination by volatile material Acid Number BCP ASTM D-974 ASTM D Degradation of cellulose insulation or contamination Most of the ASTM methods listed in this table have been developed for the evaluation of mineral oils and can be used without modification for the evaluation of silicone fluids. For example, ASTM D-877 used to measure dielectric breakdown potential requires slight modification. This method calls for five consecutive measurements on the same oil sample. When it is applied to silicone fluids only one breakdown test can be made with each filling of the test cup because of the 7

8 buildup of arc decomposition products. The five dielectric breakdown measurements are therefore performed on five aliquots of the same sample.. IV. Fault Detection in Silicone Filled Transformers Dissolved gas analysis, DGA, has been universally accepted as a diagnostic tool for the detection of incipient faults in mineral oil filled transformers, load tap changers and other oil insulated equipment. Application of the DGA method to silicone fluid filled electrical equipment has generated much interest. The development of the DGA method for silicone fluids parallels that for application of DGA to mineral oil filled transformers. Griffin 4 completed extensive laboratory studies on the degradation of silicone fluids subjected to thermal and electrical stresses. He studied the conditions that are associated with the common fault conditions viz. overheating, corona or partial discharge and arcing. The low molecular weight gases that were found are identical to those that are normally reported, with DGA, for mineral oils: hydrogen, carbon monoxide, carbon dioxide, methane, ethane, ethylene and acetylene. The concentration of each of these fault gases depends on many parameters including temperature, fault energy, fault characteristics, oxygen level and the presence of metal catalysts such as copper. Several fault gas patterns were reported by Griffin. Thermal faults produce mainly methane with small amounts of hydrogen, carbon monoxide, ethylene and ethane. Corona produce mainly hydrogen and methane. Arcing results in the production of hydrogen, methane, carbon monoxide and acetylene. The ratio of hydrogen to acetylene is much higher in silicon fluids than it is in mineral oils subjected to the same arcing conditions. In addition to variations in the dissolved gas concentrations, the concentration of the gases above the fluid will also vary. The Ostwald equilibrium solubility of fault gases in mineral oil is 8

9 different than it is in silicon fluids. This difference in solubility, which is tabulated in Table 4, will lead to different equilibrium concentrations of fault gases in the transformer fluid and gas blanket. Remember that these are equilibrium values that provide limiting concentration ratios and they may not be applicable to the dynamic environment inside of an operating transformer. Table 4. Ostwald Solubility Coefficients 5 GAS Silicone Fluid Mineral Oil Hydrogen (H 2 ) Nitrogen (N 2 ) Carbon Monoxide (CO) Oxygen (O 2 ) Methane (CH 4 ) Carbon Dioxide (CO 2 ) Acetylene (C 2 H 2 ) Ethylene (C 2 H 4 ) Ethane (C 2 H 6 ) Interpretation of DGA data is empirical in nature and the most widely used empirical methods, for mineral oil filled transformers, are based on the identification of key gases and various gas concentration ratios. Threshold concentrations for each of the key gases and for the 9

10 total fault gas concentration must also be empirically established. Correlation of key gases and investigated faults are essential to the development of these methods. At this time the data available for mineral oil filled transformers is far greater than that available for silicone filled units. General guidelines for the interpretation of gases generated in silicone immersed transformers have been developed by IEEE 5. The gases associated with fault types are essentially the same as those observed by Griffin in his laboratory studies. Cellulose decomposition results in the production of both carbon monoxide and carbon dioxide in a concentration ratio that is temperature dependent. The presence of carbon oxides, in the absence of hydrocarbons, is a significant indication of cellulose decomposition. Determination of dissolved furanic compounds in insulating fluid, according to ASTM D-5837, is recommended as a confirmatory test to assess the extent of cellulose degradation. IEEE guidelines recommend the establishment of base line data when the transformer is first placed in service. A weekly or monthly DGA analysis is recommended when a new transformer is initially placed in service. The rate of gas generation is a key parameter to indicate the severity of an incipient fault. At this time no specific gas generation rates have been presented in the IEEE guidelines but the presence of any amount of acetylene is considered extremely serious. For existing units, where no base line data is available, IEEE recommends a set of threshold concentrations based on collective laboratory experience 5. These flag points are summarized in Table 5. If any of the individual fault gases or the total dissolved combustible gas, TDCG, exceeds the flag points one should take additional samples to assess gas generation rate and the severity of the fault. 10

11 Table 5. IEEE Dissolved Gas Threshold Levels in ppm vol 5 GAS H 2 CH 4 C 2 H 2 C 2 H 4 C 2 H 6 CO CO 2 TDCG Threshold Level The second stage in the interpretive process involves interpretation of the fault gas data. Current IEEE recommended interpretation rules are summarized in Table 6. As more silicone DGA data becomes available these rules may be modified or expanded. Table 6. Key Gas Interpretation Fault Type Key Gas(es) Additional Gases Notes Thermal-Fluid CO(principal), CO 2, CH 4 H 2 and C 2 H 6 1 Thermal-Cellulose CO(principal) and CO Corona H 2 (principal) and CH 4 CO, C 2 H 2, C 2 H 4, C 2 H Arcing H 2 (principal) and C 2 H 2 CH 4, C 2 H 4, CO, CO Oxygen must be present to form CO and CO 2. Methane, CH 4, is favored with low oxygen levels. 2. The ratio C 2 H 2 /H 2 increases with increasing arc energy. Ratio methods similar to the widely accepted Rogers Ratio method are not yet available in the IEEE guide. Ratios that may be significant might include hydrogen/acetylene and carbon 11

12 dioxide/carbon monoxide. Case histories for DGA applied to silicone fluids are limited. It is interesting to take a case history which is presented in the IEEE guideline 5, and analyze the data with the DTK plus software package. The silicone filled 3500 KVA transformer in question was initially tested after being in service for three years. None of the individual fault gases or the total dissolved gases exceeded the IEEE concentration threshold levels, given in Table 5. The transformer was therefore considered to be operating normally. Thirteen months later every key fault gas and the TDCG exceeded the IEEE threshold values. Inspection revealed arcing in one of the windings. This wind was rewound and a catastrophic failure was avoided. Appendix A shows the plots and report generated with DTK plus for this interesting case history. The procedures for sampling silicone fluid filled transformers are identical to those employed for mineral oil filled units. The sampling procedures are documented in ASTM D The determination of the fault gases, and oxygen and nitrogen in the oil sample is conducted according to ASTM D The gases that are separated and quantified by this ASTM method include nitrogen, oxygen, hydrogen, carbon monoxide, carbon dioxide, methane, ethane, ethylene and acetylene. V. Conclusion Silicone fluids are a viable alternative to polychlorinated biphenyls. Their high flash and flame points make them an attractive choice when safety considerations mandate a less flammable dielectric fluid. These fluids are non-toxic and generate only one toxic substance, carbon monoxide, when they are ignited. Silicone fluids are oxidation resistant and thus acid buildup, which is a problem with mineral oils, is not a significant problem with silicone fluids. 12

13 Silicone fluids have higher viscosities than transformer grade mineral oils and thus their overall heat transfer rates are lower than that of mineral oils. In the worst case scenario the rated temperature rise will be achieved with 90 percent of the name plate rating. Thus, transformers that will be run at nameplate rating would not be suitable candidates for retrofilling with silicone fluids. VI. References 1. Goudie, J.L., "Less Flammable Transformer Liquids Gain Acceptance", CEE News, Feb IEEE C , "IEEE Guide for Acceptance of Silicone Fluids and its Maintenance in Transformers". IEEE C , "IEEE Guide for Acceptance and Maintenance of Less Flammable Hydrocarbon Fluid in Transformers". IEEE C , "IEEE Guide for Acceptance and Maintenance of Insulating Oil in Equipment Annual Book of ASTM Standards, Vol , "Standard Test Methods for Silicone Fluids Used for Electrical Insulation", Designation: D , American Society for Testing and Materials, Philadelphia, PA Griffin, P.J., "Analysis for Combustible Gases in Transformer Silicone Fluids," Minutes of the Fifty-Second Annual International Conference of Doble Clients, 1987, Section IEEE Trial-Use Guide for the Interpretation of Gases Generated in Silicone-Immersed Transformers," IEEE Draft P1258, IEEE, NY, NY September

Visit our website:

Visit our website: Lab Services ISO/IEC 17025:2005 Lab Services Lab Services MORGAN SCHAFFER, located in Montreal, Canada pioneered Dissolved Gas Analysis (DGA) in America. Almost 50 years of experience in transformer oil

More information

Oil Diagnostics - Test Information

Oil Diagnostics - Test Information Oil Diagnostics - Test Information For both financial and operational reasons it is very important that transformers are managed efficiently. Optimising the future management of large transformers on networks

More information

Power Transformers. Dissolved Gas Analysis Siemens Energy, Inc. All Rights Reserved

Power Transformers. Dissolved Gas Analysis Siemens Energy, Inc. All Rights Reserved Power Transformers Dissolved Gas Analysis 2008 Siemens Energy, Inc. All Rights Reserved Application ü DGA allows to detect the presence and severity of faults: Air leaks Hot metal faults Arcing and partial

More information

INTELLIGENT DIAGNOSTIC METHOD FOR PREDICTION OF INTERNAL CONDITION OF TRANSFORMER USING FUZZY LOGIC

INTELLIGENT DIAGNOSTIC METHOD FOR PREDICTION OF INTERNAL CONDITION OF TRANSFORMER USING FUZZY LOGIC INTELLIGENT DIAGNOSTIC METHOD FOR PREDICTION OF INTERNAL CONDITION OF TRANSFORMER USING FUZZY LOGIC by LAXMANRAO ALUR KARNATAKA POWER CORPORATION LTD.,INDIA alur.laxman@gmail.com 1 INDEX INTRODUCTION DISSOLVED

More information

TOGA Electrical Insulating Fluid Analysis. Improving performance and protecting assets.

TOGA Electrical Insulating Fluid Analysis. Improving performance and protecting assets. TOGA Electrical Insulating Fluid Analysis Improving performance and protecting assets. It happens all the time - transformers fail unexpectedly, and there are often no external visual clues on what caused

More information

Prediction of the Characteristics of Transformer Oil under Different Operation Conditions

Prediction of the Characteristics of Transformer Oil under Different Operation Conditions Prediction of the Characteristics of Transformer Oil under Different Operation Conditions EL-Sayed M. M. EL-Refaie, Mohamed R. Salem, and Wael A. Ahmed Digital Open Science Index, Electrical and Computer

More information

TOGA PRESENTATION REVIEW OF CASE STUDIES. Paul Boman,

TOGA PRESENTATION REVIEW OF CASE STUDIES. Paul Boman, TOGA PRESENTATION REVIEW OF CASE STUDIES Paul Boman, paul_boman@hsb.com October 8, 2014 HSB s TOGA History TOGA Transformer Oil Gas Analyst Registered trademark of Hartford Steam Boiler Inspection and

More information

Superior client serv ice. Electrical confidence. CARGILL LIMITED Transformer Oil Sampling and Analysis. June 7, 2016 File: C

Superior client serv ice. Electrical confidence. CARGILL LIMITED Transformer Oil Sampling and Analysis. June 7, 2016 File: C Superior client serv ice. Electrical confidence. CARGILL LIMITED 6 Transformer Oil Sampling and Analysis June 7, 6 File: C- Project Manager: George Shehata, P.Eng. info@magnaiv.com www.magnaiv.com Engineering

More information

TRANSFORMER OIL ANALYSIS

TRANSFORMER OIL ANALYSIS A member of the Set Point group I S S U E 3 6 TRANSFORMER OIL ANALYSIS By Neil Robinson, B.Sc. Hons. A basic introduction to an essential part of a cost-efficient maintenance programme It is well known

More information

ICM Project Station Infrastructure and Equipment

ICM Project Station Infrastructure and Equipment EB 0 00 ( pages) ICM Project Station Infrastructure and Equipment Stations Power Transformers Segment (THESL) EB 0 00 I EXECUTIVE SUMMARY. Project Description This segment consists of replacing power transformers

More information

Online Condition Monitoring of Transformer

Online Condition Monitoring of Transformer Online Condition Monitoring of Transformer ---------------------------------------------------- Heart of any power system An essential Part of a Cost efficient maintenance Program. It is well known that

More information

Dissolved Gas Analysis of Transformer Oils: Effects of electric arc

Dissolved Gas Analysis of Transformer Oils: Effects of electric arc Proceedings of the 6th WSEAS International Conference on Power Systems, Lisbon, Portugal, September 22-24, 26 376 Dissolved Gas Analysis of Transformer Oils: Effects of electric arc SUWARNO School of Electrical

More information

FORECASTING THE NATURE OF POWER TRANSFORMER INSULATION OIL USING CHEMICAL PROPERTIES OF DISSOLVED GASES

FORECASTING THE NATURE OF POWER TRANSFORMER INSULATION OIL USING CHEMICAL PROPERTIES OF DISSOLVED GASES Int. J. Chem. Sci.: 13(4), 2015, 1777-1786 ISSN 0972-768X www.sadgurupublications.com FORECASTING THE NATURE OF POWER TRANSFORMER INSULATION OIL USING CHEMICAL PROPERTIES OF DISSOLVED GASES K. IYSWARYA

More information

TECHNICAL PAPER PRESENTATION

TECHNICAL PAPER PRESENTATION 1 W E L C O M E T O A C O M E T 2 1 7 TECHNICAL PAPER PRESENTATION 2 Analytics for Dissolved Gas Analysis BY RANDY COX A B O U T T H E A U T H O R Randy Cox is the Domain Expertise Manager for GE Grid

More information

DGA - Method in the Past and for the Future

DGA - Method in the Past and for the Future DGA - Method in the Past and for the Future IVANKA ATANASOVA-HÖHLEIN Höhlein, Folie 1 Höhlein, Folie 2 -1970 Doerenburg introduced the differentiation between electrical and thermal failure mode and introduced

More information

IEEE Transformer Committee Atlanta Arturo Núñez MISTRAS Group, Inc. (dba Physical Acoustics Corporation)

IEEE Transformer Committee Atlanta Arturo Núñez MISTRAS Group, Inc. (dba Physical Acoustics Corporation) IEEE Transformer Committee Atlanta 2016 Arturo Núñez MISTRAS Group, Inc. (dba Physical Acoustics Corporation) A A A A A A A A A AE Sensor ACOUSTIC EMISSIONS INSTALLATION AE SENSORS HFCT Other info: DGA

More information

ANSI/IEEE Standard C57.12"Standard Guide for Loading Mineral Oil Insulated Transformers"

ANSI/IEEE Standard C57.12Standard Guide for Loading Mineral Oil Insulated Transformers References: ANSI/IEEE Standard C57.12"Standard Guide for Loading Mineral Oil Insulated Transformers" IEEE Project P1276 "IEEE Guide for the Application of High Temperature Insulation Materials in Liquid

More information

Presentation to: Western Mining Electric Association

Presentation to: Western Mining Electric Association Presentation to: Western Mining Electric Association World s Largest Database of Test Records 4,000,000 Customer Transformer Test Records. World s Leading Reclaimer of Transformer Oil Over 1 Billion Gallons

More information

The effectiveness of oil analysis for failure prediction of power transformers

The effectiveness of oil analysis for failure prediction of power transformers The effectiveness of oil analysis for failure prediction of power transformers by Krige Visser and Yashin Brihmohan, University of Pretoria The availability of an electricity network is of utmost importance

More information

FAILURE ANALYSIS OF POWER TRANSFORMERS BY DGA, OIL TESTS AND MARKOV APPROACH

FAILURE ANALYSIS OF POWER TRANSFORMERS BY DGA, OIL TESTS AND MARKOV APPROACH FAILURE ALYSIS OF POWER TRANSFORMERS BY DGA, OIL TESTS AND MARKOV APPROACH Mohammed Abdul Rahman Uzair Research Scholar, Department of EEE, GITAM University, Hyderabad, Telangana, INDIA Dr. Basavaraja

More information

Excellent Insulation and Cooling of Power Transformer Oil 25#&45# Brand Transformer Oil Specification

Excellent Insulation and Cooling of Power Transformer Oil 25#&45# Brand Transformer Oil Specification Excellent Insulation and Cooling of Power Transformer Oil 25#&45# Brand Transformer Oil Specification 1 1. Description The chemical composition of transformer oil is made up of moderate low viscosity and

More information

Lecture No. (7) Rubber Fillers

Lecture No. (7) Rubber Fillers Lecture No. (7) Rubber Fillers Introduction of Rubber Fillers Rubbers in general are seldom used in their only form because of they are too weak to fulfill practical requirements for many applications

More information

CHAPTER 6 ENHANCEMENT OF CRITICAL CHARACTERISTICS OF TRANSFORMER OIL USING NANOMATERIALS

CHAPTER 6 ENHANCEMENT OF CRITICAL CHARACTERISTICS OF TRANSFORMER OIL USING NANOMATERIALS 120 CHAPTER 6 ENHANCEMENT OF CRITICAL CHARACTERISTICS OF TRANSFORMER OIL USING NANOMATERIALS 6.1 INTRODUCTION Transformer oil is typically a highly refined mineral oil that is stable at high temperature

More information

oil standards TRUE NORTH AND ATLANTIS

oil standards TRUE NORTH AND ATLANTIS oil standards TRUE NORTH AND ATLANTIS Accuracy Matters Accurate lab data is critical to sound decision making. Running certified oil standards is the ideal way to ensure the accuracy of your DGA results.

More information

Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter. Ian.A.R. Gray

Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter. Ian.A.R. Gray Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter Ian.A.R. Gray Largest aluminium smelter in the Southern hemisphere South Africa's major producer of primary aluminium It

More information

Study on Thermal Ageing Characteristics of Silicone Rubber and Pressboard in Mineral Oil

Study on Thermal Ageing Characteristics of Silicone Rubber and Pressboard in Mineral Oil Study on Thermal Ageing Characteristics of Silicone Rubber and Pressboard in Mineral Oil M.Sc. Smitha Karambar, Prof. Dr.-Ing. Stefan Tenbohlen University of Stuttgart, Institute of Power Transmission

More information

Pyrometallurgy of iron is still the most important pyrometallurgical process economically.

Pyrometallurgy of iron is still the most important pyrometallurgical process economically. 1 Pyrometallurgy of iron is still the most important pyrometallurgical process economically. Prehistorically, iron was prepared by simply heating it with charcoal in a fired clay pot. Coke is coal that

More information

Available online at ScienceDirect. Study on Dissolved Gas Due Tue Thermally Degraded Insulating Paper in Transformer Oil

Available online at   ScienceDirect. Study on Dissolved Gas Due Tue Thermally Degraded Insulating Paper in Transformer Oil Available online at www.sciencedirect.com ScienceDirect Procedia Technology 11 ( 2013 ) 257 262 The 4th International Conference on Electrical Engineering and Informatics (ICEEI 2013) Study on Dissolved

More information

Condition Assessment of Power Transformer Using Dissolved Gas Analysis

Condition Assessment of Power Transformer Using Dissolved Gas Analysis Condition Assessment of Power Transformer Using Dissolved Gas Analysis Jagdeep Singh, Kulraj Kaur, Priyam Kumari, Ankit Kumar Swami School of Electrical and Electronics Engineering, Lovely Professional

More information

The Next Step In The World Of Transformers

The Next Step In The World Of Transformers The Next Step In The World Of Transformers Envirotran TM Transformers Set Higher Environmental, Fire Safety and Performance Standards Envirotran TM Transformers Advance the Evolution of Electrical Distribution

More information

DGA Method-Based ANFIS Expert System for Diagnosing Faults and Assessing Quality of Power Transformer Insulation Oil

DGA Method-Based ANFIS Expert System for Diagnosing Faults and Assessing Quality of Power Transformer Insulation Oil Modern Applied Science; Vol. 10, No. 1; 2016 ISSN 1913-1844 E-ISSN 1913-1852 Published by Canadian Center of Science and Education DGA Method-Based ANFIS Expert System for Diagnosing Faults and Assessing

More information

PS 2000 Hot Melt November 3, 2015 ***SAFETY DATA SHEET *** Page 1 of 5

PS 2000 Hot Melt November 3, 2015 ***SAFETY DATA SHEET *** Page 1 of 5 Page 1 of 5 1. PRODUCT & COMPANY IDENTIFICATION Product Name: PS 2000 Product Type: Hot Melt Adhesive Company Address: The Gluefast Company, Inc. 3535 Route 66, Bldg. #1 Neptune, NJ 07753 USA Phone 732-918-4600

More information

Dissolved Gas Analysis for transformer. health. management. Precise DGA measurements are required to look for transformer condition changes COLUMN

Dissolved Gas Analysis for transformer. health. management. Precise DGA measurements are required to look for transformer condition changes COLUMN COLUMN Precise DGA measurements are required to look for transformer condition changes ABSTRACT Complex studies have led to the development of powerful methods to assess the health of the insulation system,

More information

Transformer Life Extension. CJC V30 Transformer Oil Vacuum Filtration Unit and Ion Exchange Filtration Units

Transformer Life Extension. CJC V30 Transformer Oil Vacuum Filtration Unit and Ion Exchange Filtration Units Transformer Life Extension CJC V30 Transformer Oil Vacuum Filtration Unit and Ion Exchange Filtration Units Agenda Examples of V30 installations Background info Theory Field results Added safety Conclusion

More information

Software Implementation of Duval Triangle Technique for DGA in Power Transformers

Software Implementation of Duval Triangle Technique for DGA in Power Transformers International Journal of Electrical Engineering. ISSN 0974-2158 Volume 4, Number 5 (2011), pp. 529-540 International Research Publication House http://www.irphouse.com Software Implementation of Duval

More information

Capabilities of the Doble Materials Laboratories

Capabilities of the Doble Materials Laboratories Capabilities of the Doble Materials Laboratories Introduction The Doble Engineering Company has been providing laboratory services to the electric power industry since the 1930 s. We have continually evolved

More information

Anil Kumar*, Ajay Rathore** Ashish Patra ***

Anil Kumar*, Ajay Rathore** Ashish Patra *** Analysis of Power Transformer using fuzzy expert and neural network system Anil Kumar*, Ajay Rathore** Ashish Patra *** Electrical Department MITS Gwalior (MP)INDIA474002 Abstract- Power transformers being

More information

Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter. Ian Gray Transformer Chemistry Services

Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter. Ian Gray Transformer Chemistry Services Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter By Ian Gray Transformer Chemistry Services 1 Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter

More information

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING UNIT 1: BREAKDOWN IN LIQUIDS 1.) Introduction: The liquid dielectrics due to their inherent properties appear as though they would be more useful as insulating materials than either solids or gases. The

More information

Residual Life assessment with DGA, Furan content in transformer oil and Degree of polymerization of solid insulation

Residual Life assessment with DGA, Furan content in transformer oil and Degree of polymerization of solid insulation International Journal of Scientific and Research Publications, Volume 6, Issue 7, July 2016 230 Residual Life assessment with DGA, Furan content in transformer oil and Degree of polymerization of solid

More information

Condition Assessment of High Voltage Power Transformer Using Dissolved Gas Analysis

Condition Assessment of High Voltage Power Transformer Using Dissolved Gas Analysis ISSN 348-7X September 5 Condition Assessment of High Voltage Power Transformer Using Dissolved Gas Analysis Jugasri Joy Sarma M.E. Scholar, EE Department, Assam Engineering College, Guwahati, India Dr.

More information

PROGRESS IN PAPER DEGRADATION ASSESSMENT IN SERVICE-AGED TRANSFORMERS

PROGRESS IN PAPER DEGRADATION ASSESSMENT IN SERVICE-AGED TRANSFORMERS PROGRESS IN PAPER DEGRADATION ASSESSMENT IN SERVICE-AGED TRANSFORMERS H. Ding, R. Heywood, J. Lapworth, S. Ryder and A. Wilson Presenter: Dr Hongzhi Ding Doble PowerTest Ltd UK INSUCON - 17 th May 2017

More information

DOW CORNING CORPORATION Material Safety Data Sheet DOW CORNING(R) 200 FLUID, 60,000 CST.

DOW CORNING CORPORATION Material Safety Data Sheet DOW CORNING(R) 200 FLUID, 60,000 CST. Page: 1 of 7 1. PRODUCT AND COMPANY IDENTIFICATION MSDS No.: 01013394 SUPPLIER: Dow Corning Corporation South Saginaw Road Midland, Michigan 48686 MANUFACTURER: Dow Corning Corporation South Saginaw Road

More information

Oil Regeneration in 132kV and 33kV Transformers 6 December 2017

Oil Regeneration in 132kV and 33kV Transformers 6 December 2017 1 Oil Regeneration in 132kV and 33kV Transformers 6 December 2017 Paul Marshall Innovation Project Manager Agenda Introduction Research IFI oil regeneration project Oil regeneration results Oil regeneration

More information

An Overview of Online Oil Monitoring Technologies

An Overview of Online Oil Monitoring Technologies An Overview of Online Oil Monitoring Technologies Tim Cargol Weidmann-ACTI, Inc. 71 Bishop St., Framingham, MA 01702, USA tcargol@weidmann-acti.com Abstract Several new and exciting oil monitoring technologies

More information

CIGRE 16 BRUGGE Partial Discharge and Dissolved Gas Analysis In bio-degradable transformer oil. The University of New South Wales Australia

CIGRE 16 BRUGGE Partial Discharge and Dissolved Gas Analysis In bio-degradable transformer oil. The University of New South Wales Australia CIGRE 16 BRUGGE 2007 Partial Discharge and Dissolved Gas Analysis In bio-degradable transformer oil D. IMAMOVIC *, K.X. LAI, N.A. MUHAMAD, B.T. PHUNG and T.R. BLACKBURN # The University of New South Wales

More information

The following table summarizes the average test results for the three tests conducted by ORTECH and the corresponding emission criteria:

The following table summarizes the average test results for the three tests conducted by ORTECH and the corresponding emission criteria: EXECUTIVE SUMMARY ORTECH Environmental (ORTECH) was requested by Clean Harbors to conduct a comprehensive emission testing program at the incineration facility located at 4090 Telfer Road in Corunna, Ontario.

More information

EMERGENCY OVERVIEW Dust may cause eye and respiratory irritation. Dust particles may cause abrasive injury to the eyes.

EMERGENCY OVERVIEW Dust may cause eye and respiratory irritation. Dust particles may cause abrasive injury to the eyes. Safety Data Sheet Date Issued - 06/8/2018 SDS Number - PB-03 1. PRODUCT AND COMPANY IDENTIFICATION PRODUCT DESCRIPTION: GENERAL USE: Material removal, surface finishing MANUFACTURER ADDRESS: Osborn 2350

More information

PS 1823 Hot Melt November 3, 2015 ***SAFETY DATA SHEET *** Page 1 of 5

PS 1823 Hot Melt November 3, 2015 ***SAFETY DATA SHEET *** Page 1 of 5 Page 1 of 5 1. PRODUCT & COMPANY IDENTIFICATION Product Name: PS 1823 Product Type: Hot Melt Adhesive Company Address: The Gluefast Company, Inc. 3535 Route 66, Bldg. #1 Neptune, NJ 07753 USA Phone 732-918-4600

More information

EU Health and Safety Data Sheet

EU Health and Safety Data Sheet EU Health and Safety Data Sheet Buffler 20 CTP Safety Data Sheet in accordance with 1907/2006 EC 1. Name of material / preparation and company Name of material / preparation: Name of company / Manufacturer:

More information

INSPIRED SCIENCES, LLC

INSPIRED SCIENCES, LLC INSPIRED SCIENCES, LLC Material HEATER PAD Previous revision date Oct 27, 2010 SECTION 1 -- PRODUCT AND COMPANY IDENTIFICATION File designation Manufacture s Name and issuing location Forever Young International,

More information

Online dissolved gas analysis sensor

Online dissolved gas analysis sensor GAS Guard 8 Online dissolved gas analysis sensor Answers for energy. Dissolved Gas Analysis (DGA) Dissolved gas analysis is the single-most comprehensive tool for transformer condition assessment. The

More information

POLYMER DYNAMIX MATERIAL SAFETY DATA SHEET

POLYMER DYNAMIX MATERIAL SAFETY DATA SHEET POLYMER DYNAMIX MATERIAL SAFETY DATA SHEET Product Name: EverGlide MB350 and MB450 Section 1: Chemical Product and Company Identification Polymer Dynamix, L.L.C. Phone: 908-668-0300 238 St. Nicholas Ave.

More information

Transformer Monitoring

Transformer Monitoring 100x 100x Offshore 100x-3/-2/-1 Load Voltage kv ma Load Current Ambient Oil Position Top Oil Bottom Oil MS-7 X1 X2 X3 H3 H1 Bushing Monitor ZVCM-1001 Transformer Monitoring Overview of modular system components

More information

Material Safety Data Sheet High Impact Polystyrene

Material Safety Data Sheet High Impact Polystyrene Material Safety Data Sheet Section 1. Chemical product and company identification Identification Product Name: (general purpose) 9003-53-6 100% Company Identification: (INDIA) Veritas House, 70 Mint Road,

More information

DOW CORNING CORPORATION Material Safety Data Sheet DOW CORNING 200(R) FLUID, 350 CST.

DOW CORNING CORPORATION Material Safety Data Sheet DOW CORNING 200(R) FLUID, 350 CST. Page: 1 of 7 1. IDENTIFICATION OF THE SUBSTANCE AND OF THE COMPANY MSDS No.: 01013211 SUPPLIER: Dow Corning Canada Inc. 15-6400 Millcreek Drive, Suite 416 Mississauga, ON, Canada L5N 3E7 MANUFACTURER:

More information

Inside View Features and Specifications Software Version 3.0

Inside View Features and Specifications Software Version 3.0 Inside View Features and Specifications Software Version 3.0 page 1 / 15 Introduction Inside View is a software system that was conceived and designed to identify warning events rapidly from large amounts

More information

Name: Organic chemistry. Class: Foundation revision questions. Date: 67 minutes. Time: 67 marks. Marks: Comments: Page 1 of 27

Name: Organic chemistry. Class: Foundation revision questions. Date: 67 minutes. Time: 67 marks. Marks: Comments: Page 1 of 27 Organic chemistry Foundation revision questions Name: Class: Date: Time: 67 minutes Marks: 67 marks Comments: Page of 27 Barbecues are heated by burning charcoal or burning hydrocarbons. (a) Use the Chemistry

More information

Safety Data Sheet. Expanded Polystyrene

Safety Data Sheet. Expanded Polystyrene Safety Data Sheet Expanded Polystyrene Section 1 - CHEMICAL PRODUCT/COMPANY IDENTIFICATION Material Identification CAS Number: 9003-53-6 CAS Name: Polystyrene Product Use: Foamed polystyrene. Packaging,

More information

MATERIAL SAFETY DATA SHEET

MATERIAL SAFETY DATA SHEET 5/12/2 004 SECTION 1: PRODUCT IDENTIFICATION Product ill: Chemical Description: Treated Duster 100% Rayon wiacrylic Binder and Mineral Oil Additions SECTION II: COMPOSITION, INFORMATION ON INGREDIENTS

More information

This product is not classified as hazardous material according to the established norms and regulations.

This product is not classified as hazardous material according to the established norms and regulations. 1. IDENTIFICATION OF THE SUBSTANCE / COMPANY INFORMATION TRADE NAME CHEMICAL NAME Low Density Polyethylene MANUFACTURER Saudi Ethylene & Polyethylene Company (SEPC) 2. HAZARD IDENTIFICATION This product

More information

CHEMOLUBE H WATER-GLYCOL FIRE RESISTANT FLUIDS PRODUCT DESCRIPTION

CHEMOLUBE H WATER-GLYCOL FIRE RESISTANT FLUIDS PRODUCT DESCRIPTION CHEMOLUBE H WATER-GLYCOL FIRE RESISTANT FLUIDS PRODUCT DESCRIPTION CHEMOLUBE H fluids are specially formulated, water-glycol based products designed for industrial application. CHEMOLUBE H fluids at the

More information

PRODUCT S VOLUNTARY DATA SHEET

PRODUCT S VOLUNTARY DATA SHEET PRODUCT S VOLUNTARY DATA SHEET Security Data Sheets are documents with a legal defined application range, that must follow certain requirements regarding their format and their content ((Annex II of the

More information

Questions Q1. (b) Molecules of two compounds W and X are shown. (i) Compound W is an alkane. Explain what is meant by the term alkane.

Questions Q1. (b) Molecules of two compounds W and X are shown. (i) Compound W is an alkane. Explain what is meant by the term alkane. Questions Q1. (a) Crude oil is separated into useful fractions by fractional distillation. Diesel oil and kerosene are two of these fractions. Draw one straight line from each of these fractions to a use

More information

ISOVOLTINE Transformer oils

ISOVOLTINE Transformer oils ISOVOLTINE Transformer oils ISOVOLTINE TRANSFORMER OIL Safety and longevity In operation, a transformer reaches very high temperatures. It requires a lubricant to prevent overheating and break down. Each

More information

CONDITION-BASED ASSESSMENT OF ON-LOAD TAP CHANGERS

CONDITION-BASED ASSESSMENT OF ON-LOAD TAP CHANGERS ISSUE 66 CONDITION-BASED ASSESSMENT OF ON-LOAD TAP CHANGERS By I.A.R. Gray transformer division manager, WearCheck Condition Monitoring Specialists I.A.R. Gray transformer division manager, WearCheck INTRODUCTION

More information

Transformer Program. Trevor Foster Electrical Engineering, Manager Calpine Corporation April 16 17, 2013

Transformer Program. Trevor Foster Electrical Engineering, Manager Calpine Corporation April 16 17, 2013 Transformer Program Trevor Foster Electrical Engineering, Manager Calpine Corporation April 16 17, 2013 Overview of Calpine Established in 1984 One of the largest Independent power producers in the U.S.,

More information

Weidmann Electrical Technology. Presenter Thomas A. Prevost, Weidmann-ACTI

Weidmann Electrical Technology. Presenter Thomas A. Prevost, Weidmann-ACTI Estimation of Insulation Life Based on a Dual Temperature Aging Model Weidmann-ACTI Inc. Fifth Annual Technical Conference Albuquerque, NM Nov. 13-15, 2006 Thomas A. Prevost, Hans Peter Gasser Weidmann

More information

MATERIAL SAFETY DATA SHEET: RED STICKY WAX SS-66

MATERIAL SAFETY DATA SHEET: RED STICKY WAX SS-66 SECTION 1: CHEMICAL PRODUCT & COMPANY INFORMATION APPLICABLE PART #: PZ66000, PA66000 IDENTITY: Red Sticky Wax SS-66 SUPPLIER: Universal Photonics, Inc. FOR INFORMATION CALL 85 Jetson Lane CUSTOMER SERVICE

More information

MATERIAL SAFETY DATA SHEET

MATERIAL SAFETY DATA SHEET MATERIAL SAFETY DATA SHEET 1. CHEMICAL PRODUCT AND COMPANY INFORMATION Product Type: C4001 POLYPROPYLENE Product Name: 31S35V-X0316, 52T30V, CP-, D-, F-,FF-, FP-, FPT-, FT-, HR-, JH-, L, NW, X-, ZS- This

More information

Technick Products MATERIAL SAFETY DATA SHEET

Technick Products MATERIAL SAFETY DATA SHEET Technick Products MATERIAL SAFETY DATA SHEET Product Name: Tech-Lube KP-500 Section 1: Chemical Product and Company Identification Technick Products Inc. Phone: 908-791-0400 238 St. Nicholas Ave. Fax:

More information

1) ABSORPTION The removal of one or more selected components from a gas mixture by absorption is probably the most important operation in the control

1) ABSORPTION The removal of one or more selected components from a gas mixture by absorption is probably the most important operation in the control 1) ABSORPTION The removal of one or more selected components from a gas mixture by absorption is probably the most important operation in the control of gaseous pollutant emissions. Absorption is a process

More information

Makrolon SL Safety Data Sheet

Makrolon SL Safety Data Sheet 1. Identification TRANSPORTATION EMERGENCY CALL CHEMTREC: (800) 424-9300 INTERNATIONAL: (703) 527-3887 NON-TRANSPORTATION Emergency Phone: Call Chemtrec Information Phone: (844) 646-0545 Product Name:

More information

MATERIAL SAFETY DATA SHEET

MATERIAL SAFETY DATA SHEET MATERIAL SAFETY DATA SHEET 1. IDENTIFICATION OF THE MATERIAL AND SUPPLIER 1.1 Product Details: Product name: Chemical name of main ingredient: Recommended Use: AQUATAIN AMF Silicone Fluid (Polydimethylsiloxane)

More information

Material Safety Data Sheet

Material Safety Data Sheet Material Safety Data Sheet Nylon 66. Identification of the Substance / Preparation & Company. Commercial Product Name: PA 66 Use: Company: Polymer Plastim Ltd. Unit 100, Ashville Business Park Commerce

More information

Hexylene Glycol (HG)

Hexylene Glycol (HG) 16717 Jacintoport Blvd. Houston, TX 77015-6544 Phone: 281-452-5951 Fax: 281-457-1128 Technical Data & Safety Bulletin Hexylene Glycol (HG) PRODUCT OVERVIEW Hexylene Glycol (HG) is an organic compound with

More information

PT. PACIFIC LUBRITAMA INDONESIA ISO 9001: 2008 Certificate No. JKT

PT. PACIFIC LUBRITAMA INDONESIA ISO 9001: 2008 Certificate No. JKT MATERIAL SAFETY DATA SHEET 1. PRODUCT IDENTIFICATION AND COMPANY Product Name Product Type Company SN 150 N Base oil (Group2) PT. PACIFIC LUBRITAMA INDONESIA Jl. Raya Bojonegara KM 6, Desa Bojonegar Serang

More information

Smart Grid Monitoring of Transformers by DGA. Michel Duval. CIGRE Thailand, Bangkok 2013

Smart Grid Monitoring of Transformers by DGA. Michel Duval. CIGRE Thailand, Bangkok 2013 Smart Grid Monitoring of Transformers by DGA Michel Duval CIGRE Thailand, Bangkok 2013 1 Electric Power 2 Power Transformers 3 Catastrophic Failures 4 Failures in Service - The failure rate of power transformers

More information

DOW CORNING CORPORATION Material Safety Data Sheet

DOW CORNING CORPORATION Material Safety Data Sheet Page: 1 of 8 1. PRODUCT AND COMPANY IDENTIFICATION Dow Corning Corporation South Saginaw Road Midland, Michigan 48686 24 Hour Emergency Telephone: Customer Service: Product Disposal Information: CHEMTREC:

More information

MATERIAL SAFETY DATA SHEET

MATERIAL SAFETY DATA SHEET MATERIAL SAFETY DATA SHEET Product: Monofilament produced from nylon resin blend 1. CHEMICAL PRODUCT AND COMPANY IDENTIFICATION PRODUCT NAMES: 3314, BCCL-58, BCCL-58B, BCCL-301, BCCL-308, HT-38PT, HT-38RF,

More information

Quality assessment of 11 KV transformer by internal dissolved gas analysis using CFD

Quality assessment of 11 KV transformer by internal dissolved gas analysis using CFD INTERNATIONAL JOURNAL OF INNOVATIVE RESEARCH IN ELECTRICAL, ELECTRONICS, INSTRUENTATION AND CONTROL ENGINEERING Quality assessment of 11 KV transformer by internal dissolved gas analysis using CFD ithu

More information

Product No: BiologiQ AG201090, AG202080, AG203070, AG204060, AG Revision Date: 08 December 2016

Product No: BiologiQ AG201090, AG202080, AG203070, AG204060, AG Revision Date: 08 December 2016 SECTION 1. PRODUCT AND COMPANY IDENTIFICATION Product Name Common Names BiologiQ AG Eco Starch Polymer Resin BiologiQ Starch Resin BiologiQ Eco Starch Resin Product Use Manufacturer BiologiQ ESR Resin

More information

How can hydrocarbons be broken down into smaller molecules? What is an alkane? Give an example and draw it

How can hydrocarbons be broken down into smaller molecules? What is an alkane? Give an example and draw it How can hydrocarbons be broken down into smaller molecules? What is an alkane? Give an example and draw it What kind of reaction happens when large hydrocarbons are broken down? What is the general formula

More information

Remnant Life Estimation of Power Transformers Based on Chemical Diagnostic Parameters Using Adaptive Neuro- Fuzzy Inference System

Remnant Life Estimation of Power Transformers Based on Chemical Diagnostic Parameters Using Adaptive Neuro- Fuzzy Inference System Faculty of Science and Engineering Department of Electrical and Computer Engineering Remnant Life Estimation of Power Transformers Based on Chemical Diagnostic Parameters Using Adaptive Neuro- Fuzzy Inference

More information

Dr B Pahlavanpour Senior Techncal Co-ordinator Nynas Naphthenics LTD UK

Dr B Pahlavanpour Senior Techncal Co-ordinator Nynas Naphthenics LTD UK Dr B Pahlavanpour Senior Techncal Co-ordinator Nynas Naphthenics LTD UK IEC specification and maintenance guide for mineral insulating oil Dr B Pahlavanpour Nynas Naphthenics Ltd UK Three Important oil

More information

CHAPTER 3 BENEFITS OF BETTER BURNING

CHAPTER 3 BENEFITS OF BETTER BURNING Combustion Fundamentals CHAPTER 3 BENEFITS OF BETTER BURNING As every stationary engineer knows, conventional fuels are made up of two elements: carbon and hydrogen, which combine with oxygen, in a process

More information

ENGINEERING SPECIFICATION

ENGINEERING SPECIFICATION ENGINEERING SPECIFICATION No. Page 1 CATEGORY: TRANSFORMERS DATE: 11/16/2006 Subject: TABLE OF CONTENTS PURPOSE...2 SCOPE...2 REFERENCES...2 DEFINITIONS...2 SPECIFICATION...2 General... 2 High Voltage

More information

DOW CORNING CORPORATION Material Safety Data Sheet

DOW CORNING CORPORATION Material Safety Data Sheet Page: 1 of 8 1. PRODUCT AND COMPANY IDENTIFICATION Dow Corning Corporation South Saginaw Road Midland, Michigan 48686 24 Hour Emergency Telephone: Customer Service: Product Disposal Information: CHEMTREC:

More information

DAXIN LUBES MATERIAL SAFETY DATA SHEET. Power Diesel Engine Oil 15W-40 CI-4 Plus. Prolonged or repeated contact may irritate skin

DAXIN LUBES MATERIAL SAFETY DATA SHEET. Power Diesel Engine Oil 15W-40 CI-4 Plus. Prolonged or repeated contact may irritate skin 1. Product Identification and Company Product Name Company Power Diesel Engine Oil 15W-40 CI-4 Plus Niugini Oil Company P.O. Box 3722 Lae 411, Morobe Province Papua New Guinea. 2. Composition Mineral Oil

More information

CHAPTER 4: Oxidation. Chapter 4 1. Oxidation of silicon is an important process in VLSI. The typical roles of SiO 2 are:

CHAPTER 4: Oxidation. Chapter 4 1. Oxidation of silicon is an important process in VLSI. The typical roles of SiO 2 are: Chapter 4 1 CHAPTER 4: Oxidation Oxidation of silicon is an important process in VLSI. The typical roles of SiO 2 are: 1. mask against implant or diffusion of dopant into silicon 2. surface passivation

More information

MATERIAL SAFETY DATA SHEET

MATERIAL SAFETY DATA SHEET MATERIAL SAFETY DATA SHEET 1. CHEMICAL PRODUCT AND COMPANY INFORMATION Product Type: C4001 POLYPROPYLENE Product Name: 31S1A CS448, 31S35V-X0316, 51S12A, 51S12A-CS439, 52T30V, CP-, D-, F-,FF-, FP-, FPT-,

More information

Silicone Conformal Coating 422B Technical Data Sheet 422B-Aerosol

Silicone Conformal Coating 422B Technical Data Sheet 422B-Aerosol Description The 422B Silicone Conformal Coating is a UL recognized, clear, and flexible coating that is ideal for protecting electronic circuits in high temperature environments or applications requiring

More information

Transformers are the heart of an

Transformers are the heart of an 98 Technical Article Reliability of Electrical Systems: From Testing to Monitoring Specific data from a fault gas monitor study will be presented, as well as a test case that focuses on the relationship

More information

Revision Date: July 1, 2015 Version No.: 1 SECTION 1 IDENTIFICATION OF THE SUBSTANCE / MIXTURE AND OF THE COMPANY / UNDERTAKING

Revision Date: July 1, 2015 Version No.: 1 SECTION 1 IDENTIFICATION OF THE SUBSTANCE / MIXTURE AND OF THE COMPANY / UNDERTAKING SECTION 1 IDENTIFICATION OF THE SUBSTANCE / MIXTURE AND OF THE COMPANY / UNDERTAKING 1.1 Product Identifier Product Name JEESILC PDS-100 1.2 Relevant Identified Uses of the Substance or Mixture and Uses

More information

Methoxy-nonafluorobutane 1

Methoxy-nonafluorobutane 1 3 Novec Engineered Fluid HFE-7100 for Heat Transfer Application A New Engineered Fluid with Unique Heat Transfer Properties Information 3M Novec Engineered Fluid HFE-7100 is a clear, colorless, nonflammable

More information

1. IDENTIFICATION OF THE SUBSTANCE / COMPANY INFORMATION. Saudi Ethylene & Polyethylene Company (SEPC)

1. IDENTIFICATION OF THE SUBSTANCE / COMPANY INFORMATION. Saudi Ethylene & Polyethylene Company (SEPC) 1. IDENTIFICATION OF THE SUBSTANCE / COMPANY INFORMATION TRADE NAME CHEMICAL NAME MANUFACTURER SUPPLIER Low Density Polyethylene Saudi Ethylene & Polyethylene Company (SEPC) TASNEE Business Gate Building

More information

***SAFETY DATA SHEET *** 1. CHEMICAL PRODUCT AND COMPANY IDENTIFICATION

***SAFETY DATA SHEET *** 1. CHEMICAL PRODUCT AND COMPANY IDENTIFICATION 1. CHEMICAL PRODUCT AND COMPANY IDENTIFICATION PRODUCT NUMBER... 11345 PRODUCT NAME...... VitaMent an orange flavored vitamin, high-potency... vitamin and mineral supplement 60/10 gram packets Medtrition,

More information

PRODUCT S VOLUNTARY DATA SHEET

PRODUCT S VOLUNTARY DATA SHEET PRODUCT S VOLUNTARY DATA SHEET Security Data Sheets are documents with a legal defined application range, that must follow certain requirements regarding their format and their content ((Annex II of the

More information

DOW CORNING CORPORATION Material Safety Data Sheet

DOW CORNING CORPORATION Material Safety Data Sheet Page: 1 of 7 1. IDENTIFICATION OF THE SUBSTANCE AND OF THE COMPANY Dow Corning Corporation South Saginaw Road Midland, Michigan 48686 24 Hour Emergency Telephone: Customer Service: Product Disposal Information:

More information