Superior client serv ice. Electrical confidence. CARGILL LIMITED Transformer Oil Sampling and Analysis. June 7, 2016 File: C

Size: px
Start display at page:

Download "Superior client serv ice. Electrical confidence. CARGILL LIMITED Transformer Oil Sampling and Analysis. June 7, 2016 File: C"

Transcription

1 Superior client serv ice. Electrical confidence. CARGILL LIMITED 6 Transformer Oil Sampling and Analysis June 7, 6 File: C- Project Manager: George Shehata, P.Eng. info@magnaiv.com Engineering & Technical Field Services Canada United States Chile

2 Superior client service. Electrical confidence. Parsons Road SW Edmonton, AB T6X X p f tf File: C- June 8, 6 CARGILL LIMITED 8 LOW LEVEL ROAD NORTH VANCOUVER, BC V7L A7 Attention: Dear Sir: Mr. Ron Ludwig Supervisor, Electrical Via: fax mail Re: Oil Sampling and Analysis North Vancouver Facility We are pleased to submit the insulating fluid report and test sheets for the three () transformers and one () OCB located at the North Vancouver facility. The transformer sampling was performed by James Powell on June 7, 6 in accordance with ASTM D9 and D6 standards. The laboratory testing was completed by The Chemlab of Calgary. Review of results and analysis was provided by the undersigned. Based on the analysis of the laboratory results, all equipment is in good condition and suitable for continued service. Once again, both the East and West transformers are showing elevated Ethylene indicating higher temperature internal heating however, since there has been no significant generation and all other dissolved gases and standard fluid quality tests are within IEEE acceptable limits for in-service equipment, the units are of no immediate concern. Annual sampling is highly recommended to monitor any further generation. The Sub transformer is filled with Natural Ester (FR) it appears there is elevated Ethane however, the limits indicated are for mineral oil only. Natural ester generates Ethane under normal operation (test limit is 4PPM) therefore the current value is within acceptable limits. In addition, the interfacial tension appears low however, the test limit is 8 for Natural ester. As such all values meet the recommended test limits for natural ester. The OCB is showing all dissolved gases and tested fluid quality properties to be within acceptable limits. All equipment is classified as category Type. Equipment in this category shows acceptable test results, with some showing minor elevated gas levels. Close observation of dissolved gases in the oil, along with the fluid quality properties, provides the most valuable information about your equipment health. All units are recommended for annual resampling with electrical tests performed at year intervals. This testing schedule will allow us to maintain a comprehensive trend of all properties, and provide accurate analysis on the condition and operational reliability of your equipment. Please see Section. Summary of Results and Deficiencies for a complete breakdown. info@magnaiv.com Engineering & Technical Field Services Canada United States Chile

3 We trust this report meets with your approval and requirements. Should you need further information or assistance, please do not hesitate to contact us. Thank you for retaining the services of Magna IV Engineering. We look forward to being of service to you again in the future. Yours Truly, MAGNA IV ENGINEERING Stephanie Parsons Oil Analysis Project Manager Pa ge

4 INDEX.. SCOPE OF WORK..... SUMMARY OF TESTS SUMMARY OF RESULTS AND DEFICIENCIES TEST RESULTS Pa ge

5 .. SCOPE OF WORK As per Magna IV Engineering s standard practices for transformer oil sampling, our scope of work consisted of: Providing Transformer Inspection Recording Nameplate Data Reading and resetting Gauges Providing Inspection Report Procurement of oil samples in accordance with ASTM D9 & D6 - obtain one syringe for gas-in-oil analysis & moisture content - obtain bottle sample for fluid quality tests The Chemlab of Calgary performs all analytical tests, consisting of: Gas Analysis (DGA) D-6 Moisture Content D-B Interfacial Tension D-97 Acid Number D-974 Color Number D- Visual Examination D-4 Dielectric Breakdown mm The Chemlab is responsible for proper disposal of samples. Analysis of Laboratory results by Magna IV Engineering. Tools utilized: Duval Triangle GA Key Gas Method DGA Rogers Ratio Method DGA Cellulose DGA IEEE/ANSI Specific History and Trending (Generation vs. Time) Document, interpret and evaluate results, and recommend corrective or follow up action. Prepare traditional summary sheets and lifetime trending graphs. Prepare report detailing findings, recommendations and corrective action as required. Pa ge

6 .. SUMMARY OF TESTS For your reference and confirmation of the specific tests performed and their analytical value, we provide the following highlight information. All transformer tests were performed as per the latest ASTM standards. Specific tests performed include: ASTM D86 - Liquid Dielectric Test The dielectric breakdown voltage of an insulating liquid is important as a measure of the liquid s ability to withstand electric stress without failure. It serves to indicate the presence of contaminating agents, such as water, dirt, moisture, cellulosic fibers or conducting particles in the liquid, one or more of which may be present in significant concentrations when low dielectric breakdown values are found by test. However, a high dielectric breakdown voltage does not indicate that the concentrations of contaminants that are present in the liquid between the electrodes are not large enough to negatively affect the average breakdown voltage of the liquid when tested by this method. ASTM D97 - Interfacial Tension This method has been shown by practice to give a reliable indication of the presence of hydrophilic compounds. When certain contaminants such as soaps, paints varnishes and oxidation products are present in the oil, the film strength of the oil is weakened, thus requiring less force to rupture. For oils in service, a decreasing value indicates the accumulation of contaminants and oxidation products, which may attack the insulation and interfere with the cooling of transformer windings. ASTM D - Moisture Content The electrical characteristics of an insulating liquid are deleteriously affected by its water content. A high water content may make a dielectric liquid unsuitable for some applications because a deterioration in properties such as dielectric breakdown voltage may occur. This test is suitable for use in acceptance specifications, in control of processing and in evaluating the condition of dielectric liquids in service. ASTM D974 - Neutralization Number The acid number of an oil is a measure of the amount of acidic materials present. As oils age in service the acidity, and therefore the acid number, increases. A used oil having a high acid number indicates the oil is either oxidized or contaminated with materials such as varnish, paint or other foreign matter. This test serves as an indicator of the potential of the oil to form sludge. ASTM D Color Number The color of a new oil is generally accepted as an index of the degree of refinement. For oils in service, an increasing or high color number is an indication of contamination, deterioration or both. 6 Pa ge

7 ASTM D6 - Dissolved Gas Analysis Gas analysis is based upon the fact that both electrical insulating oil and cellulosic insulation break down under abnormal thermal or electrical stress. The results of these stresses are both volatile and non-volatile gases, known as fault gases. Gas analysis is the technique that identifies fault gases, relates their quantity, generation rate and relevant ratios to type and severity of fault. Typical fault gases analyzed are: Hydrogen Methane Ethane Ethylene Acetylene Carbon Monoxide Carbon Dioxide H CH4 CH6 CH4 CH CO CO Typical types of transformer problems that can be detected are: thermal degradation - low temperature - high temperature (hot spot) arcing partial discharges degradation of paper insulation Increased frequency or periodic testing will significantly increase the value and accuracy of fault gas analysis. 7 Pa ge

8 .. SUMMARY OF RESULTS AND DEFICIENCIES Transformers typically can be broken down into the following categories: Type Type Type Type 4 Transformers in this category show acceptable test results, with a few transformers showing signs of minor non-serious overheating (re-test recommended in one year). Variations of Type transformers may exist pending past records and age of units. This category covers any transformer showing test results where some concern is evident (re-test recommended in six months). Transformers in this category show signs of serious fault gas concentrations or very poor chemical properties (prompt re-tests or further investigations are required). Mechanical deficiencies (corrective action to be taken as soon as possible or as recommended). Please refer to the test sheets ( pages) for a detailed breakdown of results and recommendations. Following is the Summary of Results and Deficiencies. Transformer Identification / Serial Number Year Manufactured Analysis Type Recommended Retest Comments East TX 969 West TX 968 Sub 94 6OCB Year 967 Year Year 967 Year Slight elevation in Ethylene higher temperature internal heating no immediate concern. All other dissolved gases and tested fluid properties within acceptable limits. Annual sampling highly recommended to monitor any further generation. Check loading conditions and cooling means. No major deficiencies noted. Slight elevation in Ethylene higher temperature internal heating no immediate concern. All other dissolved gases and tested fluid properties within acceptable limits. Annual sampling highly recommended to monitor any further generation. Check loading conditions and cooling means. No major deficiencies noted. All dissolved gases and standard fluid quality properties within acceptable limits for Natural Ester Insulating fluid. Annual sampling should be maintained. No major deficiencies noted. All dissolved gases and standard fluid quality properties within acceptable limits showing no significant change. Annual sampling should be maintained. No major deficiencies noted. 8 Pa ge

9 4.. TEST RESULTS Following is a copy of all individual test results. We recommend you review the results and graphs at your convenience to better understand our analysis and the condition of your equipment. Each piece of equipment consists of the following 4 pages of documentation: Page Transformer nameplate, identification name, oil and gas results and any notable comments and deficiencies. Pages & Graphs for all generated gases and chemical analysis tests. This provides a more visual idea of determining the trending of these gases. All limits are based upon standards widely accepted throughout the industry. Page 4 Inspection sheet, nameplate data, gauge recordings. 9 Pa ge

10 Cargill Terminal East - TX S/N: 969 Oil & Gas Results C-

11 Fluid Test Report Maintenance Serial Number: 969 kva Rating: 4 Cargill Limited Cargill Terminal Nameplate Information kv Rating: 7./.7 Apparatus Type: TRN Manufacturer: WESTINGHOUSE Designation: Fluid Type: Year Manufactured: 967 Fluid Capacity (G): 7 East - TX OIL Sample Date: Job Number: Jun-7-6 C- Jun-- C-7 Dissolved Gas Analysis D6-C Limits Expressed in PPM Hydrogen (H₂) 4 Methane (CH₄) Ethane (C₂H₆) 6... Ethylene (C₂H₄) Acetylene (C₂H₂)... Carbon Monoxide (CO) Carbon Dioxide (CO₂) 78 7 Oxygen (O₂) 9 7 Nitrogen (N₂) Total Dissolved Combustible Gas 8 6 Total Gas Content (%)..66 Fluid Quality Analysis Limits Voltage Class >69kV - <kv Moisture Content D (ppm) 6 7 Interfacial Tension D97 (mn/m)..8.4 Acid Number D974 (mg KOH/g)..8. Color Number D (Relative). L.. Visual Examination D4 (Relative) CLEAR CLEAR CLEAR Dielectric mm D86 (kv) 8 4 Dielectric Breakdown D877 (kv) 6 Power C D94 (%). Power C D94 (%). Additional Fluid Quality Tests PCB D49 (ppm) Specific Gravity D4 (Relative) Oxidation Inhibitor D668 (%) Notes: Limits Magna IV Engineering Serial Number: 969 Page of

12 Fluid Test Report Maintenance Cargill Limited Cargill Terminal Historic Graphs and Diagnostic Charts Total Gas Content (%) (All Gases) Key Gas Comparison (ppm) CO - H - Meth - Eth - Ethy - Ace Combustible Gases.... Methane (CH4).... Ethane (CH6) Ethylene (CH4) Acetylene (CH) 6 4 Hydrogen (H) Carbon Monoxide (CO) Non-Combustible Gases Carbon Dioxide (CO) Thousands Nitrogen (N) Thousands Oxygen (O) Magna IV Engineering Serial Number: 969 Page of

13 Fluid Test Report Maintenance Cargill Limited Cargill Terminal Fluid Analysis Moisture Content (Should be <Limit) Interfacial Tension (Should be >Limit).6.4 Acid Number (Should <Limit) mn/m mg KOH/g Color Number (Should be <Limit) Dielectric Breakdown D877 (Should be >Limit) kv 4 4 Dielectric Breakdown D86 (Should be >Limit) Actual Values Acceptable Limits Magna IV Engineering Serial Number: 969 Page of

14 PREPARED FOR CARGILL DESCRIPTION YES NO DESCRIPTION OK FAIL COMMENTS BREATHERS HV BUSHINGS ACCESSIBLE HV BUSHING CONDITION LV BUSHINGS ACCESSIBLE RADIATORS INSTALLED CONSERVATOR TANK GROUNDING ( LOCATIONS) PHYSICAL DAMAGE NITROGEN ADDED RELIEF VALVE INSTALLED OIL FILLED EQUIPMENT INSPECTION SHEET WO# C- TAG # EAST TX DATE June 7, 6 SITE CARGILL TERMINAL TEST BY JMP AREA MAIN SUB STANDARD MAINTENANCE APPROVED BY TYPE ONAN SEC VOLTS 7 %IMPED SO# 969 AMPS WEIGHT YEAR 967 CAPACITY LTRS 7 GALS TEMP RISE OIL TYPE MINERAL SYSTEM BREATHING DATE OF LAST OIL CHANGE (IF KNOWN) CRITERIA YES NO CRITERIA ADEQUATE CLEARANCE TANK PRESSURE (Min:- Psi (-6.89 kpa)) SILICA DESICANT CONDITION PCB CONTAMINATED LOW OIL LEVEL (GAUGE@ LOW) LV BUSHING CONDITION RADIATOR CONDITION OIL LEAKS (WHERE) DIRT ACCUMULATION NAMEPLATE DATA PRE-SAMPLING CHECKLIST INSPECTIONS UNKNOWN YES NO.7% COMMENTS.7 PPM PROPER LEVEL BLUE DUSTY DUSTY N/A OK CORROSION / RUST ACCUMULATION PAINT IS GOOD CANF-E6 EQUIPMENT TX KVA 4 # OF TAPS MANUF. WESTINGHOUSE PRI VOLTS 7KV TAP FOUND/LEFT / DUSTY GAUGE READING DRAGHAND OIL TEMP WINDING TEMP STRAW WHITE STRAW YELLOW LEMON YELLOW Sampler: PSI PO# for Sampling Lab: REPORT RUSH: DGA D6C Dielectric.mm D86 Oxidation Inhibitor D668 NOTES: Moisture in Oil DB Dielectric.mm D86 Furfurals (paper degradation). NO WINDING TEMP GAUGE Interfacial Tension D97 Power Factor C D94 Metals D6ICP TRANSFORMER IS IN A VAULT Acid Number D974 Power Factor C D94 Viscosity D88 Color/Visual D, D4 Specific Gravity D98 Other: Dielectric.mm D877 4 C N/A JMP PCB C SAMPLE COLOR ORANGE REDDISH ORANGE BROWN Syringe #: Tests Required (Internal Purposes Only) GAUGE DOCUMENTATION RESET NO YES / NO BLACK OTHER: GAUGE OIL LEVEL PRESSURE SAMPLE DATA SAMPLE POINT SEDIMENT AMB. TEMP HUMIDITY READING SEE DIAGRAM AT RIGHT KPA BOTTOM VALVE DM NO 7. C East Tx Oil Filled Equipment Inspection Page of 78 % NO

15 Cargill Terminal West - TX S/N: 968 Oil & Gas Results C-

16 Fluid Test Report Maintenance Serial Number: 968 kva Rating: 4 Cargill Limited Cargill Terminal Nameplate Information kv Rating: 7./.7 Apparatus Type: TRN Manufacturer: WESTINGHOUSE Designation: Fluid Type: Year Manufactured: 967 Fluid Capacity (G): 7 West - TX OIL Sample Date: Job Number: Jun-7-6 C- Jun-- C-7 Dissolved Gas Analysis D6-C Limits Expressed in PPM Hydrogen (H₂) 7 8 Methane (CH₄) Ethane (C₂H₆) Ethylene (C₂H₄) Acetylene (C₂H₂)... Carbon Monoxide (CO) Carbon Dioxide (CO₂) Oxygen (O₂) 8 4 Nitrogen (N₂) Total Dissolved Combustible Gas Total Gas Content (%) Fluid Quality Analysis Limits Voltage Class >69kV - <kv Moisture Content D (ppm) 7 Interfacial Tension D97 (mn/m)...8 Acid Number D974 (mg KOH/g)..4.4 Color Number D (Relative). L. Visual Examination D4 (Relative) CLEAR CLEAR CLEAR Dielectric mm D86 (kv) Dielectric Breakdown D877 (kv) 6 Power C D94 (%). Power C D94 (%). Additional Fluid Quality Tests PCB D49 (ppm) Specific Gravity D4 (Relative) Oxidation Inhibitor D668 (%) Notes: Limits Magna IV Engineering Serial Number: 968 Page of

17 Fluid Test Report Maintenance Cargill Limited Cargill Terminal Historic Graphs and Diagnostic Charts Total Gas Content (%) (All Gases) Key Gas Comparison (ppm) CO - H - Meth - Eth - Ethy - Ace Combustible Gases 6 4 Methane (CH4) 4 Ethane (CH6) Ethylene (CH4) Acetylene (CH) Hydrogen (H) Carbon Monoxide (CO) Non-Combustible Gases 6 4 Carbon Dioxide (CO) Thousands Nitrogen (N) Thousands Oxygen (O) Magna IV Engineering Serial Number: 968 Page of

18 Fluid Test Report Maintenance Cargill Limited Cargill Terminal Fluid Analysis Moisture Content (Should be <Limit) Interfacial Tension (Should be >Limit).6.4 Acid Number (Should <Limit) mn/m mg KOH/g Color Number (Should be <Limit) Dielectric Breakdown D877 (Should be >Limit) kv 4 4 Dielectric Breakdown D86 (Should be >Limit) Actual Values Acceptable Limits Magna IV Engineering Serial Number: 968 Page of

19 PREPARED FOR CARGILL OIL FILLED EQUIPMENT INSPECTION SHEET WO# C- TAG # WEST TX DATE SITE CARGILL TERMINAL TEST BY AREA MAIN SUB STANDARD MAINTENANCE APPROVED BY NAMEPLATE DATA EQUIPMENT TX KVA 4 # OF TAPS NO CRITERIA YES PCB CONTAMINATED LOW OIL LEVEL (GAUGE@ LOW) CANF-E6 June 7, 6 JMP MANUF. WESTINGHOUSE PRI VOLTS 7KV TAP FOUND/LEFT / TYPE ONAN SEC VOLTS 7 %IMPED.7% SO# 968 AMPS WEIGHT YEAR 967 CAPACITY LTRS 7 GALS TEMP RISE OIL TYPE MINERAL SYSTEM BREATHING DATE OF LAST OIL CHANGE (IF KNOWN) UNKNOWN CRITERIA YES ADEQUATE CLEARANCE TANK PRESSURE (Min:- Psi (-6.89 kpa)) BREATHERS PRE-SAMPLING CHECKLIST INSPECTIONS DESCRIPTION YES NO DESCRIPTION OK LV BUSHINGS ACCESSIBLE RADIATORS INSTALLED CONSERVATOR TANK GROUNDING ( LOCATIONS) PHYSICAL DAMAGE NITROGEN ADDED RELIEF VALVE INSTALLED SILICA DESICANT CONDITION LV BUSHING CONDITION RADIATOR CONDITION OIL LEAKS (WHERE) DIRT ACCUMULATION HV BUSHINGS ACCESSIBLE HV BUSHING CONDITION COMMENTS 6 PPM PROPER LEVEL FAIL COMMENTS BLUE DUSTY DUSTY N/A OK CORROSION / RUST ACCUMULATION PAINT IS GOOD NO DUSTY GAUGE READING DRAGHAND OIL TEMP WINDING TEMP STRAW WHITE STRAW YELLOW LEMON YELLOW Sampler: PSI PO# for Sampling Lab: REPORT RUSH: DGA D6C Dielectric.mm D86 Oxidation Inhibitor D668 NOTES: Moisture in Oil DB Dielectric.mm D86 Furfurals (paper degradation). NO WINDING TEMP GAUGE Interfacial Tension D97 Power Factor C D94 Metals D6ICP TRANSFORMER IS IN VAULT. Acid Number D974 Power Factor C D94 Viscosity D88. IMPERIAL GALLONS Color/Visual D, D4 Specific Gravity D98 Other: Dielectric.mm D877 C N/A JMP SAMPLE COLOR ORANGE REDDISH ORANGE BROWN PCB 4 C Syringe #: RESET NO YES / NO BLACK OTHER: Tests Required (Internal Purposes Only) GAUGE DOCUMENTATION GAUGE OIL LEVEL PRESSURE SAMPLE DATA SAMPLE POINT SEDIMENT AMB. TEMP HUMIDITY READING SEE DIAGRAM AT RIGHT KPA BOTTOM VALVE 6. C 78 % CO West Tx Oil Filled Equipment Inspection Page of NO NO

20 Cargill Terminal Sub S/N: 94 Oil & Gas Results C-

21 Fluid Test Report Maintenance Serial Number: 94 kva Rating: Cargill Limited Cargill Terminal Nameplate Information kv Rating:.4/.7 Apparatus Type: TRN Manufacturer: COOPER Designation: Sub Fluid Type: ESTER Year Manufactured: Fluid Capacity (L): Sample Date: Job Number: Jun-7-6 C- Jun-- C-7 Dissolved Gas Analysis D6-C Limits Expressed in PPM Hydrogen (H₂) 6 6 Methane (CH₄) 6 6 Ethane (C₂H₆) Ethylene (C₂H₄) Acetylene (C₂H₂)... Carbon Monoxide (CO) 6 8 Carbon Dioxide (CO₂) Oxygen (O₂) 4 Nitrogen (N₂) Total Dissolved Combustible Gas Total Gas Content (%) Fluid Quality Analysis Limits Voltage Class 69kV Moisture Content D (ppm) Interfacial Tension D97 (mn/m)...9 Acid Number D974 (mg KOH/g)...4 Color Number D (Relative). Visual Examination D4 (Relative) CLEAR CLEAR CLEAR Dielectric mm D86 (kv) 7 47 Dielectric Breakdown D877 (kv) 6 Power C D94 (%). Power C D94 (%). Additional Fluid Quality Tests PCB D49 (ppm) Specific Gravity D4 (Relative) Oxidation Inhibitor D668 (%) Limits <. Notes: 7/6/6 : Limits based on Mineral Oil Insulating Fluid. All Results considered normal for Natural Ester Insulating Fluid. Magna IV Engineering Serial Number: 94 Page of

22 Fluid Test Report Maintenance Cargill Limited Cargill Terminal Historic Graphs and Diagnostic Charts Total Gas Content (%) (All Gases) Key Gas Comparison (ppm) CO - H - Meth - Eth - Ethy - Ace Combustible Gases Methane (CH4) Ethane (CH6) Ethylene (CH4) Acetylene (CH) 4 Hydrogen (H) 4 Carbon Monoxide (CO) Non-Combustible Gases Carbon Dioxide (CO) Thousands Nitrogen (N) Thousands... Oxygen (O) Magna IV Engineering Serial Number: 94 Page of

23 Fluid Test Report Maintenance Cargill Limited Cargill Terminal Fluid Analysis 4 Moisture Content (Should be <Limit) mn/m Interfacial Tension (Should be >Limit) mg KOH/g..... Acid Number (Should be <Limit) Color Number (Should be <Limit) Dielectric Breakdown D877 (Should be >Limit) kv 4 4 Dielectric Breakdown D86 (Should be >Limit) Actual Values Acceptable Limits Magna IV Engineering Serial Number: 94 Page of

24 PREPARED FOR CARGILL OIL FILLED EQUIPMENT INSPECTION SHEET WO# C- TAG # SUBSTATION DATE SITE CARGILL TERMINAL TEST BY AREA SUB STANDARD MAINTENANCE APPROVED BY NAMEPLATE DATA EQUIPMENT TX KVA # OF TAPS NO CRITERIA YES PCB CONTAMINATED LOW OIL LEVEL (GAUGE@ LOW) CANF-E6 June 7, 6 SB MANUF. COOPER PRI VOLTS.4Kv TAP FOUND/LEFT / TYPE ONAN SEC VOLTS 7 %IMPED SO# 94 AMPS WEIGHT YEAR CAPACITY LTRS GALS TEMP RISE OIL TYPE FR SYSTEM BREATHING DATE OF LAST OIL CHANGE (IF KNOWN) NEW TRANSFORMER CRITERIA YES ADEQUATE CLEARANCE TANK PRESSURE (Min:- Psi (-6.89 kpa)) BREATHERS PRE-SAMPLING CHECKLIST INSPECTIONS DESCRIPTION YES NO DESCRIPTION OK FAIL HV BUSHINGS ACCESSIBLE HV BUSHING CONDITION LV BUSHINGS ACCESSIBLE RADIATORS INSTALLED CONSERVATOR TANK GROUNDING ( LOCATIONS) PHYSICAL DAMAGE NITROGEN ADDED RELIEF VALVE INSTALLED SILICA DESICANT CONDITION NOT USED LV BUSHING CONDITION RADIATOR CONDITION OK OIL LEAKS (WHERE) DIRT ACCUMULATION COMMENTS UNKNOWN PROPER LEVEL COMMENTS CORROSION / RUST ACCUMULATION PAINT IS GOOD NO OK DUSTY GAUGE READING DRAGHAND OIL TEMP WINDING TEMP STRAW WHITE STRAW YELLOW LEMON YELLOW Sampler: PSI PO# for Sampling Lab: REPORT RUSH: DGA D6C Dielectric.mm D86 Oxidation Inhibitor D668 NOTES: Moisture in Oil DB Dielectric.mm D86 Furfurals (paper degradation). NO WINDING TEMP GAUGE Interfacial Tension D97 Power Factor C D94 Metals D6ICP TRANSFORMER IS IN A VAULT Acid Number D974 Power Factor C D94 Viscosity D88 Color/Visual D, D4 Specific Gravity D98 Other: Dielectric.mm D877 4 C N/A SB SAMPLE COLOR ORANGE REDDISH ORANGE BROWN PCB 4 C Syringe #: RESET NO YES / NO BLACK OTHER: Tests Required (Internal Purposes Only) GAUGE DOCUMENTATION GAUGE OIL LEVEL PRESSURE SAMPLE DATA READING SEE DIAGRAM AT RIGHT SAMPLE POINT SEDIMENT AMB. TEMP HUMIDITY KPA BOTTOM VALVE 6. C 4 % DS Substation Oil Filled Equipment Inspection Page of NO NO

25 Cargill Terminal 6OCB S/N: 6 Oil & Gas Results C- Nameplate Information

26 Fluid Test Report Maintenance Serial Number: 6 kva Rating: Cargill Limited Cargill Terminal Nameplate Information kv Rating: 7. Apparatus Type: OCB Manufacturer: GE Designation: Fluid Type: Year Manufactured: 967 Fluid Capacity (G): 7 6OCB OIL Sample Date: Job Number: Jun-7-6 C- Jun-- C-7 Dissolved Gas Analysis D6-C Limits Expressed in PPM Hydrogen (H₂) Methane (CH₄) Ethane (C₂H₆) 6... Ethylene (C₂H₄)..8.7 Acetylene (C₂H₂)... Carbon Monoxide (CO) Carbon Dioxide (CO₂) 6 8 Oxygen (O₂) 74 Nitrogen (N₂) 6 69 Total Dissolved Combustible Gas 7 4 Total Gas Content (%) Fluid Quality Analysis Moisture Content D (ppm) Limits Voltage Class >69kV - <kv Interfacial Tension D97 (mn/m)... Acid Number D974 (mg KOH/g)... Color Number D (Relative). L.. Visual Examination D4 (Relative) CLEAR CLEAR CLEAR Dielectric mm D86 (kv) 8 6 Dielectric Breakdown D877 (kv) 6 Power C D94 (%). Power C D94 (%). Additional Fluid Quality Tests PCB D49 (ppm) Specific Gravity D4 (Relative) Oxidation Inhibitor D668 (%) Limits <. Notes: : All results considered normal for OCB operation Magna IV Engineering Serial Number: 6 Page of

27 Fluid Test Report Maintenance Cargill Limited Cargill Terminal Historic Graphs and Diagnostic Charts Total Gas Content (%) (All Gases) Key Gas Comparison (ppm) CO - H - Meth - Eth - Ethy - Ace Combustible Gases Methane (CH4) Ethane (CH6) Ethylene (CH4) Acetylene (CH) Hydrogen (H) Carbon Monoxide (CO) Non-Combustible Gases 7 Carbon Dioxide (CO) Thousands 7 Nitrogen (N) Thousands Oxygen (O) Magna IV Engineering Serial Number: 6 Page of

28 Fluid Test Report Maintenance Cargill Limited Cargill Terminal Fluid Analysis Moisture Content (Should be <Limit) mn/m Interfacial Tension (Should be >Limit) mg KOH/g Acid Number (Should <Limit) Color Number (Should be <Limit) Dielectric Breakdown D877 (Should be >Limit) kv 4 Dielectric Breakdown D86 (Should be >Limit) Actual Values Acceptable Limits Magna IV Engineering Serial Number: 6 Page of

29 PREPARED FOR CARGILL OIL FILLED EQUIPMENT INSPECTION SHEET WO# C- TAG # 6 OCB DATE SITE CARGILL TERMINAL TEST BY AREA MAIN SUB STANDARD MAINTENANCE APPROVED BY NAMEPLATE DATA EQUIPMENT OCB KVA # OF TAPS NO CRITERIA YES PCB CONTAMINATED LOW OIL LEVEL (GAUGE@ LOW) CANF-E6 June 7, 6 JMP N/A MANUF. GE PRI VOLTS 7KV TAP FOUND/LEFT / TYPE WSO SEC VOLTS %IMPED N/A SO# 6 AMPS WEIGHT YEAR 967 CAPACITY LTRS 7 GALS TEMP RISE N/A OIL TYPE MINERAL SYSTEM BREATHING DATE OF LAST OIL CHANGE (IF KNOWN) UNKNOWN CRITERIA YES ADEQUATE CLEARANCE TANK PRESSURE (Min:- Psi (-6.89 kpa)) PRE-SAMPLING CHECKLIST INSPECTIONS DESCRIPTION YES NO DESCRIPTION OK BREATHERS HV BUSHINGS ACCESSIBLE LV BUSHINGS ACCESSIBLE LV BUSHING CONDITION RADIATORS INSTALLED CONSERVATOR TANK GROUNDING ( LOCATIONS) PHYSICAL DAMAGE NITROGEN ADDED RELIEF VALVE INSTALLED SILICA DESICANT CONDITION HV BUSHING CONDITION RADIATOR CONDITION OIL LEAKS (WHERE) DIRT ACCUMULATION COMMENTS <. PPM NO GAUGE FAIL COMMENTS NOT USED SOME CHIPS N/A N/A OK CORROSION / RUST ACCUMULATION PAINT IS POOR NO NONE VISIBLE GAUGE READING DRAGHAND OIL TEMP WINDING TEMP STRAW WHITE STRAW YELLOW LEMON YELLOW Sampler: PSI PO# for Sampling Lab: REPORT RUSH: DGA D6C Dielectric.mm D86 Oxidation Inhibitor D668 NOTES: Moisture in Oil DB Dielectric.mm D86 Furfurals (paper degradation) Interfacial Tension D97 Power Factor C D94 Metals D6ICP Acid Number D974 Power Factor C D94 Viscosity D88 Color/Visual D, D4 Specific Gravity D98 Other: Dielectric.mm D877 6 C JMP SAMPLE COLOR ORANGE REDDISH ORANGE BROWN PCB Syringe #: RESET YES / NO YES / NO BLACK OTHER: Tests Required (Internal Purposes Only) GAUGE DOCUMENTATION GAUGE OIL LEVEL PRESSURE SAMPLE DATA SAMPLE POINT SEDIMENT AMB. TEMP HUMIDITY READING SEE DIAGRAM AT RIGHT KPA BOTTOM VALVE YES / NO. C 78 % DS OCB Oil Filled Equipment Inspection Page of NO

Silicone Dielectric Fluids Fredi Jakob, Karl Jakob, Nicholas Perjanik Analytical ChemTech International, Inc.

Silicone Dielectric Fluids Fredi Jakob, Karl Jakob, Nicholas Perjanik Analytical ChemTech International, Inc. Silicone Dielectric Fluids Fredi Jakob, Karl Jakob, Nicholas Perjanik Analytical ChemTech International, Inc. I. Introduction Mineral oil based dielectric fluids have been used more extensively than other

More information

Presentation to: Western Mining Electric Association

Presentation to: Western Mining Electric Association Presentation to: Western Mining Electric Association World s Largest Database of Test Records 4,000,000 Customer Transformer Test Records. World s Leading Reclaimer of Transformer Oil Over 1 Billion Gallons

More information

Oil Diagnostics - Test Information

Oil Diagnostics - Test Information Oil Diagnostics - Test Information For both financial and operational reasons it is very important that transformers are managed efficiently. Optimising the future management of large transformers on networks

More information

TOGA PRESENTATION REVIEW OF CASE STUDIES. Paul Boman,

TOGA PRESENTATION REVIEW OF CASE STUDIES. Paul Boman, TOGA PRESENTATION REVIEW OF CASE STUDIES Paul Boman, paul_boman@hsb.com October 8, 2014 HSB s TOGA History TOGA Transformer Oil Gas Analyst Registered trademark of Hartford Steam Boiler Inspection and

More information

Dissolved Gas Analysis of Transformer Oils: Effects of electric arc

Dissolved Gas Analysis of Transformer Oils: Effects of electric arc Proceedings of the 6th WSEAS International Conference on Power Systems, Lisbon, Portugal, September 22-24, 26 376 Dissolved Gas Analysis of Transformer Oils: Effects of electric arc SUWARNO School of Electrical

More information

ANSI/IEEE Standard C57.12"Standard Guide for Loading Mineral Oil Insulated Transformers"

ANSI/IEEE Standard C57.12Standard Guide for Loading Mineral Oil Insulated Transformers References: ANSI/IEEE Standard C57.12"Standard Guide for Loading Mineral Oil Insulated Transformers" IEEE Project P1276 "IEEE Guide for the Application of High Temperature Insulation Materials in Liquid

More information

Dr B Pahlavanpour Senior Techncal Co-ordinator Nynas Naphthenics LTD UK

Dr B Pahlavanpour Senior Techncal Co-ordinator Nynas Naphthenics LTD UK Dr B Pahlavanpour Senior Techncal Co-ordinator Nynas Naphthenics LTD UK IEC specification and maintenance guide for mineral insulating oil Dr B Pahlavanpour Nynas Naphthenics Ltd UK Three Important oil

More information

roduct Scope: Substation

roduct Scope: Substation roduct Scope: Substation Three Phase or Single Phase, 50 or 60 Hz, 55ºC, 65ºC, 75ºC, 55ºC/65ºC, 55ºC/75ºC, 65ºC/75ºC Envirotemp FR3 fluid or Mineral Oil Three Phase: 300 12,000 kva Single Phase: 167 6,667

More information

Condition Assessment of Power Transformer Using Dissolved Gas Analysis

Condition Assessment of Power Transformer Using Dissolved Gas Analysis Condition Assessment of Power Transformer Using Dissolved Gas Analysis Jagdeep Singh, Kulraj Kaur, Priyam Kumari, Ankit Kumar Swami School of Electrical and Electronics Engineering, Lovely Professional

More information

The Next Step In The World Of Transformers

The Next Step In The World Of Transformers The Next Step In The World Of Transformers Envirotran TM Transformers Set Higher Environmental, Fire Safety and Performance Standards Envirotran TM Transformers Advance the Evolution of Electrical Distribution

More information

The effectiveness of oil analysis for failure prediction of power transformers

The effectiveness of oil analysis for failure prediction of power transformers The effectiveness of oil analysis for failure prediction of power transformers by Krige Visser and Yashin Brihmohan, University of Pretoria The availability of an electricity network is of utmost importance

More information

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

B. Provide liquid-filled secondary substation transformers as indicated on drawings. SECTION 26 12 13 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 26 05 00. B. Provide liquid-filled secondary substation transformers as indicated on drawings. 1.02 RELATED

More information

PROGRESS IN PAPER DEGRADATION ASSESSMENT IN SERVICE-AGED TRANSFORMERS

PROGRESS IN PAPER DEGRADATION ASSESSMENT IN SERVICE-AGED TRANSFORMERS PROGRESS IN PAPER DEGRADATION ASSESSMENT IN SERVICE-AGED TRANSFORMERS H. Ding, R. Heywood, J. Lapworth, S. Ryder and A. Wilson Presenter: Dr Hongzhi Ding Doble PowerTest Ltd UK INSUCON - 17 th May 2017

More information

GST001 MV/LV TRANSFORMERS LOCAL SECTION CELG D

GST001 MV/LV TRANSFORMERS LOCAL SECTION CELG D GST001 MV/LV TRANSFORMERS LOCAL SECTION CELG D In addition on what specified in the common part, the following requirements are prescribed: 3.1 LAWS Portaria INMETRO 378/2010 Requisitos de Avaliação da

More information

CIGRE 16 BRUGGE Partial Discharge and Dissolved Gas Analysis In bio-degradable transformer oil. The University of New South Wales Australia

CIGRE 16 BRUGGE Partial Discharge and Dissolved Gas Analysis In bio-degradable transformer oil. The University of New South Wales Australia CIGRE 16 BRUGGE 2007 Partial Discharge and Dissolved Gas Analysis In bio-degradable transformer oil D. IMAMOVIC *, K.X. LAI, N.A. MUHAMAD, B.T. PHUNG and T.R. BLACKBURN # The University of New South Wales

More information

Smart Grid Monitoring of Transformers by DGA. Michel Duval. CIGRE Thailand, Bangkok 2013

Smart Grid Monitoring of Transformers by DGA. Michel Duval. CIGRE Thailand, Bangkok 2013 Smart Grid Monitoring of Transformers by DGA Michel Duval CIGRE Thailand, Bangkok 2013 1 Electric Power 2 Power Transformers 3 Catastrophic Failures 4 Failures in Service - The failure rate of power transformers

More information

Inside View Features and Specifications Software Version 3.0

Inside View Features and Specifications Software Version 3.0 Inside View Features and Specifications Software Version 3.0 page 1 / 15 Introduction Inside View is a software system that was conceived and designed to identify warning events rapidly from large amounts

More information

An Overview of Online Oil Monitoring Technologies

An Overview of Online Oil Monitoring Technologies An Overview of Online Oil Monitoring Technologies Tim Cargol Weidmann-ACTI, Inc. 71 Bishop St., Framingham, MA 01702, USA tcargol@weidmann-acti.com Abstract Several new and exciting oil monitoring technologies

More information

ELECTRICAL INSPECTION BULLETIN (Effective )

ELECTRICAL INSPECTION BULLETIN (Effective ) ELECTRICAL INSPECTION BULLETIN (Effective 2009-02-01) Rule 36-000 Customer Owned High Voltage Installations With the increase in customer own high voltage equipment there appears to be confusion over which

More information

Hydrosol System Furnace Cooling Water Cleaning Case Study: North American Stainless

Hydrosol System Furnace Cooling Water Cleaning Case Study: North American Stainless Hydrosol System Furnace Cooling Water Cleaning Case Study: North American Stainless Prepared by: Shane M. Slack BSWE, MBA Hydrosol System, Inc. 4175 Karg Industrial Parkway Kent, Ohio 44240 shane@hydrosolsystem.com

More information

Transformer Monitoring

Transformer Monitoring 100x 100x Offshore 100x-3/-2/-1 Load Voltage kv ma Load Current Ambient Oil Position Top Oil Bottom Oil MS-7 X1 X2 X3 H3 H1 Bushing Monitor ZVCM-1001 Transformer Monitoring Overview of modular system components

More information

Transformer Life Extension. CJC V30 Transformer Oil Vacuum Filtration Unit and Ion Exchange Filtration Units

Transformer Life Extension. CJC V30 Transformer Oil Vacuum Filtration Unit and Ion Exchange Filtration Units Transformer Life Extension CJC V30 Transformer Oil Vacuum Filtration Unit and Ion Exchange Filtration Units Agenda Examples of V30 installations Background info Theory Field results Added safety Conclusion

More information

CASE STUDIES INVOLVING INSULATING LIQUIDS AND MATERIALS FROM THE DOBLE MATERIALS LABORATORIES

CASE STUDIES INVOLVING INSULATING LIQUIDS AND MATERIALS FROM THE DOBLE MATERIALS LABORATORIES CASE STUDIES INVOLVING INSULATING LIQUIDS AND MATERIALS FROM THE DOBLE MATERIALS LABORATORIES Lance R. Lewand and Paul J. Griffin Doble Engineering Company, USA ABSTRACT This paper discusses cases that

More information

Anil Kumar*, Ajay Rathore** Ashish Patra ***

Anil Kumar*, Ajay Rathore** Ashish Patra *** Analysis of Power Transformer using fuzzy expert and neural network system Anil Kumar*, Ajay Rathore** Ashish Patra *** Electrical Department MITS Gwalior (MP)INDIA474002 Abstract- Power transformers being

More information

Frequently Asked Questions. 3M Liquid-Filled Transformer Insulation

Frequently Asked Questions. 3M Liquid-Filled Transformer Insulation Frequently Asked Questions 3M Liquid-Filled Transformer Insulation Frequently Asked Questions What configurations are available for 3M Liquid-Filled Transformer Insulation (LFT Insulation) layer insulation?

More information

Pomona, CA May 24 25, 2016

Pomona, CA May 24 25, 2016 Pomona, CA May 24 25, 2016 Transformer Technology Seminar Modular approach on economic condition assessment for power transformer; data management, Fleet screening and risk ranking Siemens AG 2014 All

More information

MOISTURE IN PAPER ASSESSMENT FROM CONTINUOUS MONITORING OF MOISTURE IN OIL. GE Energy

MOISTURE IN PAPER ASSESSMENT FROM CONTINUOUS MONITORING OF MOISTURE IN OIL. GE Energy MOISTURE IN PAPER ASSESSMENT FROM CONTINUOUS MONITORING OF MOISTURE IN OIL Jacques Aubin GE Energy Brian D Sparling Abstract Moisture content of solid insulation is a persistent concern for power transformer

More information

Experience With Use of C LTC DGA Guide IEEE TRANSFORMER COMMITTEE MEETINGS

Experience With Use of C LTC DGA Guide IEEE TRANSFORMER COMMITTEE MEETINGS Experience With Use of C57.139 LTC DGA Guide IEEE TRANSFORMER COMMITTEE MEETINGS OCTOBER 23, 2011 JOHN PRUENTE DIR. ENG. TECHNICAL SUPPORT SPX Transformer Solutions, Inc. 2012 Outline of Presentation Background

More information

Unit Substation Transformer Construction Checklist (under 500 kva)

Unit Substation Transformer Construction Checklist (under 500 kva) Unit Substation Transformer Checklist (under 500 kva) Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

SUPPLY AND DELIVERY OF 200KVA EARTHING TRANSFORMER TENDER DOCUMENTS: SARAWAK ENERGY REF. NO. PLS PART I TENDER PROCEDURES

SUPPLY AND DELIVERY OF 200KVA EARTHING TRANSFORMER TENDER DOCUMENTS: SARAWAK ENERGY REF. NO. PLS PART I TENDER PROCEDURES SUPPLY AND DELIVERY OF 200KVA EARTHING TRANSFORMER TENDER DOCUMENTS: SARAWAK ENERGY REF. NO. PLS-160091 PART I TENDER PROCEDURES SECTION 1 INTRODUCTION This Introduction should be read in conjunction with

More information

WEIDMANN Electrical Technology. Presentation at. NETA Trade Show. March 15 th, 2016

WEIDMANN Electrical Technology. Presentation at. NETA Trade Show. March 15 th, 2016 WEIDMANN Electrical Technology Presentation at NETA Trade Show March 15 th, 2016 WEIDMANN DIAGNOSTIC SOLUTIONS INC. A Member of the WICOR Group ELECTRICAL TECHNOLOGY WICOR WORLDWIDE Company Overview INSULATION

More information

APEC 2016 Component Level Safety Certification in Systems- IEC /UL1577. MARK CANTRELL Senior Applications Engineer

APEC 2016 Component Level Safety Certification in Systems- IEC /UL1577. MARK CANTRELL Senior Applications Engineer APEC 2016 Component Level Safety Certification in Systems- IEC60747-17/UL1577 MARK CANTRELL Senior Applications Engineer 3/20/2016 Agenda What is safety isolation Isolation Concepts Regulatory Landscape

More information

Field experiences with the world s l argest natural e ster-filled transformer EVENTS LIQUID INSULATION ABSTRACT KEYWORDS

Field experiences with the world s l argest natural e ster-filled transformer EVENTS LIQUID INSULATION ABSTRACT KEYWORDS EVENTS LIQUID INSULATION ABSTRACT Electric utilities have a duty to supply electricity securely whilst being mindful of environmental needs and fire safety, especially in urban areas. Mineral oil in power

More information

Services SAMPLE SUMMARY REPORT DR. PUMP, LLC Isuzu Rodeo. Atlanta, GA 05/24/2007

Services SAMPLE SUMMARY REPORT DR. PUMP, LLC Isuzu Rodeo. Atlanta, GA 05/24/2007 SAMPLE SUMMARY REPORT 7 Portage Trail 8.48.R 7 E A L 5.6.7 Fax:.6.7 44. 57 Report Date: 5/4/7 Primay Contact: Dr. Lev Nelik, PhD 977 Four Oaks Drive 6-75 Secondary Contact: None Provided Voice: None Provided

More information

Health Index: the TERNA s Practical Approach for Transformers Fleet Management

Health Index: the TERNA s Practical Approach for Transformers Fleet Management 213 Electrical Insulation Conference, Ottowa, Onterio, Canada, 2 to 5 June 213 Health Index: the TERNA s Practical Approach for Transformers Fleet Management Fabio Scatiggio TERNA RETE ITALIA SpA Via delle

More information

Weidmann Electrical Technology. Presenter Thomas A. Prevost, Weidmann-ACTI

Weidmann Electrical Technology. Presenter Thomas A. Prevost, Weidmann-ACTI Estimation of Insulation Life Based on a Dual Temperature Aging Model Weidmann-ACTI Inc. Fifth Annual Technical Conference Albuquerque, NM Nov. 13-15, 2006 Thomas A. Prevost, Hans Peter Gasser Weidmann

More information

Premium Acrylic Conformal Coating 419D Technical Data Sheet 419D-Liquid

Premium Acrylic Conformal Coating 419D Technical Data Sheet 419D-Liquid Description Premium Acrylic Conformal Coating Our 419D Premium Acrylic Conformal Coating is a fast drying, xylene and toluene free product that provides an excellent finish. This one part coating is easy

More information

Friday, May 29, Update on Testing Medium Voltage Cable and Switchgear Systems

Friday, May 29, Update on Testing Medium Voltage Cable and Switchgear Systems Update on Testing Medium Voltage Cable and Switchgear Systems Friday, May 29, 2015 Presented by: Ashley Harkness Ashley.Harkness@Emerson.com Electrical Reliability Services Value--- When we find the one

More information

Acceptable values for receipt of shipments of new FR3 fluid. As-received new fluid property requirements 1.0

Acceptable values for receipt of shipments of new FR3 fluid. As-received new fluid property requirements 1.0 Dielectric Fluids Envirotemp FR3 Fluid Electrical Apparatus R2000 DESCRIPTION Envirotemp FR3 fluid is a renewable, bio-based natural ester dielectric coolant for use in distribution and power class transformers

More information

The complete guide to transformers and packaged substations

The complete guide to transformers and packaged substations LAND LOGICAL POWER The complete guide to transformers and packaged substations Contents Land Logical Power transformers An introduction to the complete range of Land Logical Power transformers and package

More information

IEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor

IEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor TABLE OF CONTENTS SECTION SUBJECT PAGE I. SCOPE...1 II. APPLICABLE DOCUMENTS...1 III. CONDUCTOR...2 IV. SEPARATOR...2 V. INSULATION...2 A. Physical Properties...2 B. Electrical Properties...3 C. Qualification

More information

Performance of Oil and Paper in Transformers Based on IEC and Dielectric Response Techniques*

Performance of Oil and Paper in Transformers Based on IEC and Dielectric Response Techniques* F E A T U R E A R T I C L E Performance of Oil and Paper in Transformers Based on IEC 61620 and Dielectric Response Techniques* Key words: oil paper insulation, transformer, polarization, conduction, aging

More information

VERSAFIT V2 AND V4 TUBING Polyolefin, Flexible, Heat-Shrinkable, Flame-Retardant

VERSAFIT V2 AND V4 TUBING Polyolefin, Flexible, Heat-Shrinkable, Flame-Retardant TE Connectivity 300 Constitution Drive Menlo Park, CA 94025 USA Raychem Tubing Specification This Issue: Date: Replaces: RW-3023 Issue 9 Nov 21, 2016 Issue 8 VERSAFIT V2 AND V4 TUBING Polyolefin, Flexible,

More information

Systems Commissioning Table of Contents

Systems Commissioning Table of Contents Systems Commissioning Table of Contents C NC NA I. General II. Commissioning III. Mechanical Systems A. Testing, Adjusting, and Balancing B. Piping IV. Electrical Systems A. Load Balancing B. Electrical

More information

Thermal Aging Study of Cellulosic Materials in Natural Ester Liquid for Hybrid Insulation Systems

Thermal Aging Study of Cellulosic Materials in Natural Ester Liquid for Hybrid Insulation Systems 21, rue d Artois, F-758 PARIS CIGRE 212 http : //www.cigre.org D1-111 Thermal Aging Study of Cellulosic Materials in Natural Ester Liquid for Hybrid Insulation Systems J-C DUART * L. C. BATES R. ASANO

More information

Transmission Owner Asset Management

Transmission Owner Asset Management Transmission Owner Asset Management Pieces of Asset Management New customers, load growth, repairs, maintenance, operational issues, etc. All the pieces make up the asset management plan for repair or

More information

Copper Odyssey. Chemical Reactions of Copper

Copper Odyssey. Chemical Reactions of Copper Name Lab Partner(s) Copper Odyssey Chemical Reactions of Copper Date Period Elemental copper metal will be converted into copper (II) ion and then brought through a series of compound conversions until

More information

The World s Most Versatile Filter System

The World s Most Versatile Filter System The World s Most Versatile Filter System Full-flow filtration systems By-pass filtration systems Water Based Fluids Process Fluids Heating oils Turbine oils Bioethanol Hippo Filter Biodiesel Kerosene Diesel

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement Draft 11/17/08 Utility transformer issues began surfacing last year with questions of enforcement responsibilities due to utility

More information

AEP 69-kV Oil-Insulated Transmission Line Removal Project

AEP 69-kV Oil-Insulated Transmission Line Removal Project AEP 69-kV Oil-Insulated Transmission Line Removal Project Michael Glueck, PE, American Electric Power Michelle Beckman, Burns & McDonnell Bill Halliburton, PG, Burns & McDonnell Woody McOmber, PE, Burns

More information

Premium Acrylic Conformal Coating 419D Technical Data Sheet 419D-Liquid

Premium Acrylic Conformal Coating 419D Technical Data Sheet 419D-Liquid Description Premium Acrylic Conformal Coating Our 419D Premium Acrylic Conformal Coating is an IPC-CC-830B and UL 94-V0 certified, fast drying, xylene and toluene free product that provides an excellent

More information

This Technical Note is to notify you that Tecvalco has changed the brand of glycol in the CWT Heater. This change took affect in April 2016.

This Technical Note is to notify you that Tecvalco has changed the brand of glycol in the CWT Heater. This change took affect in April 2016. UTILITY, MUNICIPAL, AND WHOLESALE SUPPLY May 5, 2016 Technical Note: CWT-20160505-001 Dear Customer, This Technical Note is to notify you that Tecvalco has changed the brand of glycol in the CWT Heater.

More information

TRANSFORMER S MOISTURE ASSESSMENT WITH ONLINE MONITORING

TRANSFORMER S MOISTURE ASSESSMENT WITH ONLINE MONITORING TRANSFORMER S MOISTURE ASSESSMENT WITH ONLINE MONITORING Senja LEIVO Vaisala Oyj Finland senja.leivo@vaisala.com Jukka LEPPÄNEN Vaisala Oyj Finland jukka.leppanen@vaisala.com ABSTRACT This paper discusses

More information

SERVICE ENTRANCES. OPPD S Electrical Service Designer (ESD) shall designate the Point Of Entrance.

SERVICE ENTRANCES. OPPD S Electrical Service Designer (ESD) shall designate the Point Of Entrance. SERVICE ENTRANCES 3.01 POINT OF ENTRANCE General Service The customer, or the customer s electrician, should provide OPPD with a site plan, load schedule, and voltage requirements when requesting service.

More information

Life Extension by Refurbishment of Transformers

Life Extension by Refurbishment of Transformers Life Extension by Refurbishment of Transformers C. JAYASENAN by and SHIRISH KANUNGO SIEMENS, India SIEMENS, India c.jayasenan@siemens.com Shirish.Kanungo@siemens.com 1 6th International Conference on Large

More information

Moisture equilibrium charts

Moisture equilibrium charts Moisture equilibrium charts For effective condition monitoring of natural ester fluid-filled green transformers 04/29/2016-5.18 pm Clean Grid Green transformer Power transformers Green transformers, which

More information

NOMEX TYPE 410 TECHNICAL DATA SHEET. Electrical properties. Please note: PERFORM WHEN THE HEAT S ON TYPICAL ELECTRICAL PROPERTIES

NOMEX TYPE 410 TECHNICAL DATA SHEET. Electrical properties. Please note: PERFORM WHEN THE HEAT S ON TYPICAL ELECTRICAL PROPERTIES NOMEX TYPE 41 NOMEX Type 41 is a calendered insulation paper which offers high inherent dielectric strength, mechanical toughness, flexibility and resilience. NOMEX Type 41 is the original form of NOMEX

More information

SODIUM SULPHITE BASED WATER TREATMENT PROGRAM FOR CLOSED CHILLED WATER SYSTEMS

SODIUM SULPHITE BASED WATER TREATMENT PROGRAM FOR CLOSED CHILLED WATER SYSTEMS SODIUM SULPHITE BASED WATER TREATMENT PROGRAM FOR CLOSED CHILLED WATER SYSTEMS Presented at ALBERTA Public Works, Supply & Services Property Management Operations Division Water Treatment Co-ordinators'

More information

Installation, Inspection and Maintenance of Dry Type Transformers

Installation, Inspection and Maintenance of Dry Type Transformers Dry Type TX 1 of 8 Installation, Inspection and Maintenance of Dry Type Page 1 of 8 Dry Type TX 2 of 8 Table Of Contents Page Number 1. General... 3 2. Installation... 3 3. Safety Inspections... 4 4. Safety

More information

page 1/5 material SaFetY Data SHeet

page 1/5 material SaFetY Data SHeet Material Safety Data Sheet according to 91/155/EEC, the standards and regulatory requirements of United States. Date of issue: 29/01/2008 1. SUBSTANCE/PREPARATION AND COMPANY IDENTIFICATION Product Name:

More information

Bachelor of Electrical Engineering (Industrial Power)

Bachelor of Electrical Engineering (Industrial Power) TRANSFORMER DISSOLVED GAS ANALYSIS USING DUVAL TRIANGLE METHOD VIA ANDROID Mohamad Hafiz Bin Abdul Wahid Bachelor of Electrical Engineering (Industrial Power) June 2014 " I hereby declare that I have read

More information

MATERIAL SAFETY DATA SHEET

MATERIAL SAFETY DATA SHEET MATERIAL SAFETY DATA SHEET MSDS# 1500 SECTION 1 QUADRANT EPP 2120 FAIRMONT AVENUE TELEPHONE NUMBERS: P.O. BOX 14235 PRODUCT INFORMATION(Quadrant EPP ) - READING, PA. 19612-4235 610-320-6600 TRANSPORTATION

More information

Main Steam & T/G Systems, Safety

Main Steam & T/G Systems, Safety Main Steam & T/G Systems, Safety Page 1 This steam generator, built for the Wolsong station in Korea, was manufactured in Canada by the Babcock and Wilcox company. In Wolsong 2,3, and 4 a joint venture

More information

Electricity Supply to Africa and Developing Economies Challenges and Opportunities. Technology solutions and innovations for developing economies

Electricity Supply to Africa and Developing Economies Challenges and Opportunities. Technology solutions and innovations for developing economies Electricity Supply to Africa and Developing Economies Challenges and Opportunities Technology solutions and innovations for developing economies Employment of various strategies in Eskom to optimize the

More information

Technical Data. SAPPHIRE Hi-Power Oils. Hydraulic, airline and compressor oils ISO VG 22, 32, 46, 68, 100. Product Overview

Technical Data. SAPPHIRE Hi-Power Oils. Hydraulic, airline and compressor oils ISO VG 22, 32, 46, 68, 100. Product Overview Technical Data SAPPHIRE Hi-Power Oils Hydraulic, airline and compressor oils ISO VG 22, 32, 46, 68, 100 Product Overview Directions for Storage and Use ROCOL SAPPHIRE Hi-Power oils are high performance,

More information

ETHYLENE PLANT DRY CRACKED GAS Product Code 54801

ETHYLENE PLANT DRY CRACKED GAS Product Code 54801 SS2100 WATER IN ETHYLENE PLANT DRY CRACKED GAS Product Code 54801 KEY FEATURES Extremely fast analysis time 1 second updates possible Non-contact laser and detector - Reliable Tunable Diode Laser lasts

More information

A2-00. GENERAL REPORT FOR SC A2 (Transformers)

A2-00. GENERAL REPORT FOR SC A2 (Transformers) CIGRE 2012 A2-00 GENERAL REPORT FOR SC A2 (Transformers) Chairman: Secretary: C. RAJOTTE (CA) P. PICHER (CA) Special Reporters: C.J. DUPONT (BR) (PS1) R. MERTENS (BE) (PS2) S. VOSS (DE) (PS3) Discussion

More information

FLAME RETARDANT POLYPROPYLENE SHEET

FLAME RETARDANT POLYPROPYLENE SHEET FORMEX TM GK/FORMEX PRODUCT DATA FLAME RETARDANT POLYPROPYLENE SHEET FRP Products 847 299 2222 FAX 847 390 8727 TEST METHOD FORMEX-10 FORMEX GK-10 FORMEX GK-17 FORMEX GK-30 FORMEX GK-40 COLOR NATURAL NATURAL/BLACK

More information

Polymer Tantalum Capacitors for Automotive Applications

Polymer Tantalum Capacitors for Automotive Applications CARTS International 2014 March 31-April 3, 2014 Introduction Polymer Tantalum Capacitors for Automotive Applications Jayson Young and Javaid Qazi Kemet Corporation PO Box 5928, Greenville SC 29606 Phone:

More information

Del-Monox Breathing Air Purifiers DM Series

Del-Monox Breathing Air Purifiers DM Series Del-Monox Breathing Air Purifiers DM Series Del-Monox Breathing Air Purifiers Time-Proven Reliability In 1966, Deltech introduced the industry s first engineered, contaminant removing system to convert

More information

Sprayon Liqui-Sol is your option for safety, storage and disposal. Preserve, Prevent and Protect your equipment safely with Sprayon s new and

Sprayon Liqui-Sol is your option for safety, storage and disposal. Preserve, Prevent and Protect your equipment safely with Sprayon s new and Sprayon Liqui-Sol is your option for safety, storage and disposal. Preserve, Prevent and Protect your equipment safely with Sprayon s new and improved Liqui-Sol MRO chemical program. Liqui-Sol eliminates

More information

Protection Effectiveness of Vapor Corrosion Inhibitor VpCI 619 for Corrosion Under Insulation at Elevated Temperatures

Protection Effectiveness of Vapor Corrosion Inhibitor VpCI 619 for Corrosion Under Insulation at Elevated Temperatures VpCI 619 Protection Effectiveness of Vapor Corrosion Inhibitor VpCI 619 for Corrosion Under Insulation at Elevated Temperatures For: CORTEC Corporation by Behzad Bavarian, California State University,

More information

Technical Note TN-114 rev 16 wy/wh.11-04

Technical Note TN-114 rev 16 wy/wh.11-04 Sensor Specifications And Cross-Sensitivities Technical Note TN-114 Note: All performance specifications are subject to change without notice and are based upon conditions at 68 o F (20 o C), 50% relative

More information

Seismic Considerations of Circuit Breakers

Seismic Considerations of Circuit Breakers Seismic Considerations of Circuit Breakers Willie Freeman, IEEE 693 Working Group ABB Inc, Mt. Pleasant PA, USA IEEE Tutorial - 2008 Abstract: The tutorial covers the seismic qualification of high voltage

More information

Distribution Transformer Failures In Port Harcourt

Distribution Transformer Failures In Port Harcourt Global Advanced Research Journal of Engineering, Technology and Innovation (ISSN: 2315-5124) Vol. 3(7) pp. 202-206, November, 2014 Available online http://garj.org/garjeti/index.htm Copyright 2014 Global

More information

Cellulosic Biomass Chemical Pretreatment Technologies

Cellulosic Biomass Chemical Pretreatment Technologies Life-changing Research and Development Cellulosic Biomass Chemical Pretreatment Technologies September 6, 2007 Keith Pauley Keith.Pauley@matricresearch.com 800-611-2296 Chemical and Environmental Technologies

More information

REVIEW OF THE ELECTRICAL AND THERMAL BEHAVIOUR OF ESTER-BASED DIELECTRIC LIQUIDS FOR EXTRA HIGH VOLTAGE APPLICATIONS

REVIEW OF THE ELECTRICAL AND THERMAL BEHAVIOUR OF ESTER-BASED DIELECTRIC LIQUIDS FOR EXTRA HIGH VOLTAGE APPLICATIONS REVIEW OF THE ELECTRICAL AND THERMAL BEHAVIOUR OF ESTER-BASED DIELECTRIC LIQUIDS FOR EXTRA HIGH VOLTAGE APPLICATIONS Mark Lashbrook, Dr Attila Gyore, Dr Russell Martin Products of M&I Materials Ltd. Agenda

More information

Why Fine Filtering for quench oil systems is a must!

Why Fine Filtering for quench oil systems is a must! Why Fine Filtering for quench oil systems is a must! Jimmy Pfaffenberger C.C. Jensen Inc., Newnan, GA USA jimmy@ccjensen.com, (770) 683-6810 Place author name(s) from company 2 here in Arial bold and italic,

More information

Black 1:1 Epoxy, Encapsulating & Potting Compound

Black 1:1 Epoxy, Encapsulating & Potting Compound Technical Data Sheet Black 1:1 Epoxy, Encapsulating & Potting Compound Description 832HD potting and encapsulating compound is a general purpose, hard, black, two-part epoxy that offers extreme environmental,

More information

A. This Section includes the following types of dry-type transformers rated 600 V and less, with capacities up to 1000 kva:

A. This Section includes the following types of dry-type transformers rated 600 V and less, with capacities up to 1000 kva: SECTION 16461 - LOW-VOLTAGE TRANSFORMERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Module-13. Corrosion and Degradation of materials

Module-13. Corrosion and Degradation of materials Module-13 Corrosion and Degradation of materials Contents 1) Corrosion of metals 2) Corrosion of ceramics 3) Degradation of polymers Deterioration of materials Conventional engineering materials are not

More information

Datasheet RS Pro RS Series Axial Carbon Resistor 1kΩ ±5% 2W ppm/ C RS Stock No:

Datasheet RS Pro RS Series Axial Carbon Resistor 1kΩ ±5% 2W ppm/ C RS Stock No: Datasheet RS Pro RS Series Axial Carbon Resistor 1kΩ ±5% 2W -500 +350ppm/ C RS Stock No: 707-8861 Product Details RS Pro axial carbon resistor with ±5% tolerance, provides 1 kω resistance and is power

More information

MATERIAL SAFETY DATA SHEET

MATERIAL SAFETY DATA SHEET MATERIAL SAFETY DATA SHEET BLACK WARRIOR ROOFING 1. Chemical Product and Company Identification Product Name: Asphalt Saturated Roll Roofing Products CAS#: Mixture/Not Assigned Generic Name: Asphalt Saturated

More information

Grid Solutions. ASSET PERFORMANCE MANAGEMENT for Electrical Substations

Grid Solutions. ASSET PERFORMANCE MANAGEMENT for Electrical Substations Grid Solutions ASSET PERFORMANCE MANAGEMENT for Electrical Substations Electrical equipment is a critical component of an asset portfolio. Beyond its financial value, it plays an even greater role in overall

More information

Combustion Control and Safety A comparison between Zirconium Oxide/Catalytic and Tunable Diode (TDL) Technologies Dr Stephen Firth / Rhys Jenkins

Combustion Control and Safety A comparison between Zirconium Oxide/Catalytic and Tunable Diode (TDL) Technologies Dr Stephen Firth / Rhys Jenkins Combustion Control and Safety A comparison between Zirconium Oxide/Catalytic and Tunable Diode (TDL) Technologies Dr Stephen Firth / Rhys Jenkins Agenda Introduction Combustion Theory / Practical Benefits

More information

PRELIMINARY. HTHA (Z1-Foil)

PRELIMINARY. HTHA (Z1-Foil) Ultra High Precision Z1-Foil Technology Chip Resistor for Hybrid Circuits with Aluminum Wire Bonding for High Temperature Applications up to +240 C, Long Term Stability of 0.05%, TCR to ± 1ppm/ C INTRODUCTION

More information

HTHA (Z1-Foil) Vishay Foil Resistors

HTHA (Z1-Foil) Vishay Foil Resistors Ultra High Precision Z1-Foil Technology Chip Resistor for Hybrid Circuits with Aluminum Wire Bonding for High Temperature Applications up to +240 C, Long Term Stability of 0.05%, TCR to ± 1ppm/ C INTRODUCTION

More information

PROJECT TITLE PROJECT NO.: CONTRACT TITLE UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

PROJECT TITLE PROJECT NO.: CONTRACT TITLE UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA PRE-START-UP/START-UP CHECKLIST CHILLED WATER SYSTEM NOTE: University s Representative must be notified and scheduled to witness test prior to any start up of equipment. A. Chilled Water Pumps 1. Submittal

More information

Environmentally Acceptable Lubricants (EALs): Choosing the right EAL type for your application

Environmentally Acceptable Lubricants (EALs): Choosing the right EAL type for your application Environmentally Acceptable Lubricants (EALs): Choosing the right EAL type for your application There is a wide range of performance levels among both readily biodegradable and petroleum based lubricants.

More information

Advice on Power Factor and Accuracy of Temperature Dependant Outputs

Advice on Power Factor and Accuracy of Temperature Dependant Outputs Advice on Power Factor and Accuracy of Temperature Dependant Outputs REPORT WP03749-EE-RP-0001 Rev. 1 3 September 2009 Advice on Power Factor and Accuracy of Temperature Dependant Outputs REPORT WP03749-EE-RP-0001

More information

DATA SHEET. EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0

DATA SHEET. EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0 DATA SHEET EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0 Unit 21 Priory Industrial Park Airspeed Road Christchurch Dorset BH23 4HD Tel: 01425 278011 Fax: 01425 278012 www.deltarubber.co.uk

More information

MATERIAL SAFETY DATA SHEET

MATERIAL SAFETY DATA SHEET Prepared: 29 Oct. 2009 Revised: 5 Jan. 2015 Page 1/5 Company Identification GS Battery Taiwan CO., LTD. NO.999 Chung Cheng N. Rd., Yongkang Dist., Tainan City 710, Taiwan Emergency contact:0800-612-011

More information

ROLINX Laminated Busbar. Design Rules Version 01 (12/2015)

ROLINX Laminated Busbar. Design Rules Version 01 (12/2015) ROLINX Laminated Busbar Design Rules Version 01 (12/2015) Content 1. Introduction... 03 7. Features... 13 2. Configuration...03 8. Thermal parameters... 14 3. Products... 04 9. General parameters... 14

More information

Maximum Rust Protection!

Maximum Rust Protection! ZERO-RUST Zero Rust is a direct-to-metal, phenolic modified alkyd rust and corrosion control coating, which controls rust and corrosion by putting down an impermeable barrier at the steel level. Its dielectric

More information

Asset Optimization and Condition-Based Maintenance (CBM) Improving Reliability and Quality

Asset Optimization and Condition-Based Maintenance (CBM) Improving Reliability and Quality Asset Optimization and Condition-Based Maintenance (CBM) Improving Reliability and Quality Ann Moore Business Development Executive Agenda Asset Management Issues and Trends Utility Use Cases PSE&G CMMS

More information

Thermally Conductive Epoxy Product No

Thermally Conductive Epoxy Product No PELCO T E C H N I C A L N O T E S DESCRIPTION Thermally Conductive Epoxy Product No. 16027 Product No. 16027 Thermally Conductive Epoxy, Encapsulating and Potting Compound, is an electric grade epoxy.

More information

// XPLORER-NS. Full range Total Nitrogen, Total Sulfur instrument for the modern Laboratory.

// XPLORER-NS. Full range Total Nitrogen, Total Sulfur instrument for the modern Laboratory. Configuration: XPLORER with ARCHIE and GLS* // XPLORER-NS Full range Total Nitrogen, Total Sulfur instrument for the modern Laboratory. TE Instruments has developed the XPLORER-NS, a Total Nitrogen and

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 6/15/16 Updated division section from 16124 to 2605 - mgl44 13, removed references to other section 10/17/14

More information

BRS VALUE RO/DI SYSTEM INSTRUCTIONS

BRS VALUE RO/DI SYSTEM INSTRUCTIONS BRS VALUE RO/DI SYSTEM INSTRUCTIONS 4 Stage Value V 4 Stage Value Plus 4 Stage Value Water Saver Plus V+ VWS+ Please ensure all parts are included and undamaged. If a part is found missing or damaged,

More information