Thermo-Mechanical Conductor & Dead-End Testing ACCC Drake

Size: px
Start display at page:

Download "Thermo-Mechanical Conductor & Dead-End Testing ACCC Drake"

Transcription

1 Introduction Thermo-Mechanical Conductor & Dead-End Testing ACCC Drake In early 2009, EPRI & EDF conducted a thermo-mechanical test on ACCC Drake size conductor and dead-ends at Kinectrics Lab. Based upon previous experience, a test protocol was developed wherein two conductor samples would each be terminated with ACCC dead-ends and wired in series so that the conductors could be thermally cycled from ambient lab temperature (~22 C) to 180 C, which is the ACCC conductor s maximum recommended (non-emergency) operating temperature. Following the completion of 500 thermal cycles, one-half of each conductor sample and two dead-end assemblies were pulled to failure. The remaining dead-ends and conductor samples were returned to EDF and CTC for post testing analysis. While the test protocol was initially developed to assess thermal aging of the ACCC composite core, thermocouple data that was gathered during the testing and post-testing analysis also provided valuable information about the performance of ACCC dead-end assemblies. Test Set Up Two conductor samples approximately 45 feet (14 meters) in length were terminated using conventional ACCC dead-ends (Figure 1). One conductor sample was tensioned to approximately 20% of its Rated Tensile Strength (RTS) of 41,100 pounds (~8,220 pounds) and held under constant tension during the thermal cycling. The other ACCC conductor sample was also terminated with ACCC dead-ends, but no tension was applied (Figure 2). Figure 1: ACCC Conductor & Dead-ends

2 Figure 2: Test Diagram The un-tensioned conductor sample was labeled dummy conductor. A jumper cable was attached to the south dead-ends so that electrical current could be applied to the conductors (wired in series) and the conductors could be heated equally as current was applied through the north dead-ends. Several thermocouples were placed at numerous locations in the dummy conductor and also at different locations in each dead-end and jumper terminal (Figure 3). Both conductor samples were placed in insulated boxes to improve thermal control (Figure 4). Figure 3: Thermocouple Locations in ACCC Dead-ends Test Protocol Figure 4: Insulated Boxes & Load Frame Two conductor samples and four dead-ends were initially subjected to 100 thermal cycles from ambient lab temperature of approximately 22 C (72 F) to 180 C (356 F). At the end of the first 100 thermal cycles, the tensioned conductor was pulled to 70% RTS, (~28,770 pounds) and held for 24 hours. This series was repeated five times, for a total of 500 thermal cycles and five 24 hour holds at 70% RTS.

3 Kinectrics Lab Results At the end of the thermo-mechanical sequence, the two conductor samples were cut in half leaving each dead-end in place. Lab grips, using potted resin, were then placed on one of the cut ends of each conductor sample (Figure 5). The two samples were then pulled to failure. The dummy conductor and its original ACCC dead-end pulled to failure at 101.6% RTS and the test conductor and its original dead-end pulled to failure at 102% RTS or roughly 42,000 pounds. These results demonstrated the ability of the ACCC conductor and dead-end assemblies to retain full strength after the thermomechanical and sustained load testing. Figure 5: Installing Lab Grips In addition to the mechanical results obtained by Kinectrics Lab during this testing, resistance and thermal data were also gathered on each of the dead-ends. This data showed that while some difference in resistance could be measured between the tensioned and un-tensioned test samples (Figure 6), the ACCC dead-ends and jumpers still operated >50% cooler than the conductor itself (Figure 7 & 8). Figure 6

4 Figure 7: Jumper & Dead-end Pad Temperatures (Conductor at 180 O C) Figure 8: Jumper Terminal & Dead-end Temperature (Conductor at 180 O C)

5 Figure 9: ACCC Conductor & Dead-end Assembly at Completion of Test ( sleeve thermocouple shown) During the final (500 th ) thermo-mechanical cycle when the ACCC conductor was at 180 C, the maximum temperature recorded at the tip of the dead-end (its entry point) was 120 C (Figures 8 & 9). The crimped area, where the electrical path occurs, increased in temperature from 45 C to 95 C over the course of the thermo-mechanical and high-tension sustained load test (Figures 3 & 8). The temperatures recorded were significantly cooler than ACSR or ACSS dead-end assemblies under similar elevated temperature conditions, primarily due to the added mass of the ACCC dead-ends compared to the smaller (less massive) ACSR and ACSS dead-ends (Figure 10). While some increase in resistance (and subsequent increase in temperature) is expected from any compression assembly over time, the minimal increase in resistance and temperature observed during this relatively severe test sequence confirmed robust connector design. Figure 10: ACCC & ACSR Drake Size Dead-end Housings (ACCC shown crimped)

6 Post Test Evaluation Following the thermo-mechanical testing at Kinectrics, the balance of the conductor samples were cut into several shorter lengths approximately one meter long (Figure 11). Half of these samples were shipped to EDF s lab in France and the other half were shipped to CTC s Lab in California along with several un-aged samples taken from the original reel of the ACCC Drake size conductor. Figure 11: Post Test Cut List CTC completed a series of Short Beam Shear Strength, Flexural Strength, and Tensile Strength tests of the aged and un-aged samples and compared the results (Figure 12). Figure 12: Post Test Evaluation Results (CTC)

7 Based on CTC s evaluation, it was found that the Short Beam Shear Strength increased from an average of 4,845 N (un-aged) to 4,970 (fully aged). The fully aged samples were taken from the tensioned conductor. The dummy conductor samples (that only saw thermal cycles but no tensile load) also showed slightly improved results compared to the un-aged samples (4,936 N). Data gathered from the post testing Flexural Strength test showed a slight decrease in flexural strength for the fully aged samples compared to the un-aged samples (2,317 N compared to 2,350 N). The dummy conductor showed a slight improvement (2,370 N). Tensile testing of the fully aged core samples and the dummy conductor core samples also showed a slight decrease in tensile strength after the earlier thermo-mechanical and high tension sustained load test protocol. The average strength of the un-aged core samples was 37,154 lbs (~108% RTS), while the average strength of the fully aged core samples was 35,905 lbs (~104% RTS). The dummy conductor core samples reached an average of 35,503 lbs (~103% RTS) at failure. Conclusions Based on the results of the thermo-mechanical and high-tension sustained load test performed at Kinectrics Lab, and the post test evaluation performed at CTC, both the ACCC conductor and ACCC dead-end assemblies exhibited excellent resistance to thermo-mechanical and sustained high tensile load fatigue. A copy of EDF s report is available from EPRI under the heading Specification for a Testing Procedure to Qualify Organic Matrix Core HTLS Conductors (Product ID # ). For Additional Information Please contact: Dave Bryant Vice President Technology CTC Cable Corporation 2026 McGaw Avenue Irvine, CA (949) dbryant@ctcglobal.com

TENSILE TEST SUMMARY- DRAKE ACCC/TW

TENSILE TEST SUMMARY- DRAKE ACCC/TW TENSILE TEST SUMMARY- DRAKE ACCC/TW MECHANICAL STRENGTH TESTING ABSTRACT In order to demonstrate the tension fittings (Deadends) will maintain the required strength of 95% conductor RBS (per referenced

More information

CTC Lisbon ACCC Conductor Stress-Strain, Clamp Slip, and Compression Fitting Tensile Tests, Modification 1 Lamifil Comments

CTC Lisbon ACCC Conductor Stress-Strain, Clamp Slip, and Compression Fitting Tensile Tests, Modification 1 Lamifil Comments CTC Lisbon ACCC Conductor Stress-Strain, Clamp Slip, and Compression Fitting Tensile Tests, Modification 1 Lamifil Comments This report, from NEETAC dated October 2009, has been intentionally modified

More information

477 kcmil, 3M Brand Composite Conductor Mechanical Properties, Volume 1 Tensile and Stress-Strain Tests

477 kcmil, 3M Brand Composite Conductor Mechanical Properties, Volume 1 Tensile and Stress-Strain Tests 477 kcmil, 3M Brand Composite Conductor Mechanical Properties, Volume 1 Tensile and Stress-Strain Tests Minnesota Mining and Manufacturing (3M) Company Purchase Order 0000227040 NEETRAC Project Number:

More information

ACCR. More Amps. More Confidence. Glenmar E. Cambri, REE Senior Applications Engineer

ACCR. More Amps. More Confidence. Glenmar E. Cambri, REE Senior Applications Engineer TM ACCR More Amps More Confidence Glenmar E. Cambri, REE Senior Applications Engineer What is 3M ACCR? A high voltage, overhead transmission conductor designed as a drop-in replacement for ACSR and other

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Updated format, division title, and removed references to other sections. - mgl44 A. Summary This section contains design criteria for the

More information

Merrimack and Suwannee ACSS/TW/HS285 Conductor Stress-Strain Tests. Southwire Company

Merrimack and Suwannee ACSS/TW/HS285 Conductor Stress-Strain Tests. Southwire Company Merrimack and Suwannee ACSS/TW/HS285 Conductor Stress-Strain Tests Southwire Company NEETRAC Project Number: 05-204 November, 2005 A Research Center of the Georgia Institute of Technology Requested by:

More information

OVERHEAD LINE INSTALLATION TRAINING

OVERHEAD LINE INSTALLATION TRAINING OVERHEAD LINE INSTALLATION TRAINING 2-day seminar, max. 12 participants OVERHEAD LINE INSTALLATION TRAINING The seminar offers instruction and practical tips on the installation, inspection and maintenance

More information

Engineering Data for Copper and Aluminum Conductor Electrical Cables

Engineering Data for Copper and Aluminum Conductor Electrical Cables 2018 Edition Engineering Data for Copper and Aluminum Conductor Electrical Cables THE OKONITE COMPANY Okonite Cables...A higher Standard! The Okonite Company, 2018 Okonite Cables Table of Contents SECTION

More information

How to Design a Singly Reinforced Concrete Beam

How to Design a Singly Reinforced Concrete Beam Time Required: 45 minutes Materials: -Engineering Paper -Calculator -Pencil -Straight Edge Design For Flexural Limit State How to Design a Singly Reinforced Concrete Beam Goal: ΦMn > Mu Strength Reduction

More information

Compounds. Table of Contents. or TABLE OF CONTENTS

Compounds. Table of Contents.  or TABLE OF CONTENTS Table of Contents Compounds TABLE OF CONTENTS Compounds Pictorial Index... 470 HiTemp Universal Compound (HiTUC)... 471 AFL No. 2 Electrical Joint Compound... 472 Alnox Electrical Joint Compound... 473

More information

North Mountain IMS Medical Office Building

North Mountain IMS Medical Office Building North Mountain IMS Medical Office Building Phoenix, Arizona Michael Hopple Technical Assignment 2 October 29 th, 2007 AE 481W-Senior Thesis The Pennsylvania State University Faculty Adviser: Dr. Ali Memari,

More information

Electric Service Standards

Electric Service Standards V: 1 of 6 A. Padmounted Requirements Complete requirements are contained in FPL specifications given to Customers for individual projects. Typical pad mounted transformer requirements include, but are

More information

TYPICAL PHYSICAL STRENGTH PROPERTIES OF PRO TILE

TYPICAL PHYSICAL STRENGTH PROPERTIES OF PRO TILE TYPICAL PHYSICAL STRENGTH PROPERTIES OF PRO TILE The following results of eight different tests show the typical physical strength properties of Pro Tile. IMPACT STRENGTH Date: September 19, 1983 cement

More information

CYCOM 2237 POLYIMIDE RESIN SYSTEM

CYCOM 2237 POLYIMIDE RESIN SYSTEM DESCRIPTION CYCOM 2237 is Cytec Engineered Materials version of PMR-5. It is formulated for high temperature applications where low void content is critical. CYCOM 2237 has the best overall balance of

More information

Small Terminals. TEST CURRENT (Amps) Fig 1. Tensile strength of YAD HYLUG after axial rotation stresses. TENSILE STRENGTH IN POUNDS

Small Terminals. TEST CURRENT (Amps) Fig 1. Tensile strength of YAD HYLUG after axial rotation stresses. TENSILE STRENGTH IN POUNDS B-2 Performance The terminals and splices in this catalog are approved, per MIL-T-7928 and/or UL 486, where indicated. Table 1 shows the performance requirements for terminals used in military and commercial

More information

Unit Price Labor. INSTALL 138KV DISCONNECT SWITCH WITH MOTOR OPERATOR AND AUXILIARY SWITCHES ON EXISTING STRUCTURE 1 ea.

Unit Price Labor. INSTALL 138KV DISCONNECT SWITCH WITH MOTOR OPERATOR AND AUXILIARY SWITCHES ON EXISTING STRUCTURE 1 ea. SUBSTATION B UPGRADE CONSTRUCTION MAJOR MATERIAL NOTES: Contractor to fill in line item column "Est. Qty." for items left blank. Construction Unit No. Description Est. Qty. Unit Labor 100 INSTALL 138KV

More information

A LIGHTWEIGHT SOLUTION FOR SHIELDING AND CONDUCTING

A LIGHTWEIGHT SOLUTION FOR SHIELDING AND CONDUCTING A LIGHTWEIGHT SOLUTION FOR SHIELDING AND CONDUCTING EMI Shielding ARACON fibers braided into a shield or sock offer superior performance against electromagnetic interference. Advantages include: More uniform

More information

Composite Production Systems Global Poly Linepipe

Composite Production Systems Global Poly Linepipe Headquarters 25 Bethridge Road Toronto, ON M9W 1M7 Canada Tel: +1 416 743 7111 Canada 3501 54 Avenue Southeast Calgary, AB T2C 0A9 Canada Tel: +1 403 503 0548 shawcor.com Shawcor Ltd. is a global energy

More information

Gage Series Stress Analysis Gages

Gage Series Stress Analysis Gages GAGE SERIES All Micro-Measurements strain gages incorporate precision foil grids mounted on organic backing materials. The strain-sensing alloys and backing materials cannot be arbitrarily combined in

More information

The University of Texas at Austin September 30, 2011

The University of Texas at Austin September 30, 2011 SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATIONS PART 1 - GENERAL 1.1 SUMMARY A. This section governs the products and execution requirements relating to furnishing and installing grounding and

More information

NON-LINEAR STRUCTURAL INTEGRITY ANALYSIS

NON-LINEAR STRUCTURAL INTEGRITY ANALYSIS NON-LINEAR STRUCTURAL INTEGRITY ANALYSIS AHMAD RAHIMIAN, PhD, PE, SE Dr. Ahmad Rahimian., PE, SE is President of Cantor Seinuk Structural Engineers in New York City. An expert in the behaviour of steel

More information

North Mountain IMS Medical Office Building

North Mountain IMS Medical Office Building North Mountain IMS Medical Office Building Phoenix, Arizona Michael Hopple Technical Assignment 1 October 5 th, 2007 AE 481W-Senior Thesis The Pennsylvania State University Faculty Adviser: Dr. Ali Memari,

More information

TEMPORARY PROTECTIVE GROUNDING EQUIPMENT

TEMPORARY PROTECTIVE GROUNDING EQUIPMENT TEMPORARY PROTECTIVE GROUNDING EQUIPMENT TEMPORARY PROTECTIVE GROUNDING EQUIPMENT NOTE: When ordeing assemblies of grounding products, please make sure all items included in the assembly are only from

More information

Design of a Horizontal Creep Testing Machine

Design of a Horizontal Creep Testing Machine The University of Akron IdeaExchange@UAkron Honors Research Projects The Dr. Gary B. and Pamela S. Williams Honors College Spring 2015 Design of a Horizontal Creep Testing Machine Michael Presby mjp80@zips.uakron.edu

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

THE FORENSIC MEDICAL CENTER

THE FORENSIC MEDICAL CENTER THE FORENSIC MEDICAL CENTER Image courtesy of Gaudreau, Inc. TECHNICAL REPORT #2 OCTOBER 26, 2007 KEENAN YOHE STRUCTURAL OPTION DR. MEMARI FACULTY ADVISOR EXECUTIVE SUMMARY Image courtesy of Gaudreau,

More information

Accelerated Aging Tests for MV Cables

Accelerated Aging Tests for MV Cables Accelerated Aging Tests for MV Cables Educational Session Fall ICC 2011 Denver, CO Acknowledgments: Rick Hartlein-NEETRAC Lauri Hiivala - Teksavvy Ram Ramachandran Dow Electrical & Telecommunications Dow

More information

Study Committee B2 Technical Advisory Group B2-AG-06

Study Committee B2 Technical Advisory Group B2-AG-06 Study Committee B2 Technical Advisory Group B2-AG-06 Cigré AG06 Seminar Bangkok Types and Uses of High Brian Wareing Brian Wareing.Tech Ltd Chester, UK Convenor Cigré AG06 WG48 Experience with the Mechanical

More information

Araldite LY 5052 Resin / Aradur 5052 Hardener

Araldite LY 5052 Resin / Aradur 5052 Hardener Araldite LY 5052 Resin / Aradur 5052 Hardener Product Description Araldite LY 5052 is a low-viscosity epoxy resin that is used with Aradur 5052, a mixture of polyamines, to form a cold curing epoxy system.

More information

Hg Umbilical Installation Guide

Hg Umbilical Installation Guide 0419-38002 Hg Umbilical Installation Guide GUIDELINES FOR THE INSTALLATION OF DEKORON UNITHERM MERCURY ANALYZER BUNDLES This bulletin provides the Field Engineer and Crafts with tips and techniques to

More information

SECTION INSULATED WIRE AND CABLE

SECTION INSULATED WIRE AND CABLE SECTION 16120 INSULATED WIRE AND CABLE PART 1 GENERAL 1.01 DESCRIPTION A. This section covers the contract item Insulated Wire and Cable, which includes the following items with accessories, and appurtenances:

More information

04.00 GENERAL SECONDARIES & SERVICES SECONDARY AND SERVICE CABLE SPLICES INSULATED SERVICE ENTRANCE COMPRESSION CONNECTORS 04.

04.00 GENERAL SECONDARIES & SERVICES SECONDARY AND SERVICE CABLE SPLICES INSULATED SERVICE ENTRANCE COMPRESSION CONNECTORS 04. 4. GENERAL SECONDARIES & SERVICES 4.- TIE COLOR CODING 4.-6 SECONDARY AND SERVICE CABLE SPLICES 4.- INSULATED SERVICE ENTRANCE COMPRESSION CONNECTORS 4.- 4. POLE ATTACHMENTS POLE ATTACHMENT DEVICES NEUTRAL

More information

Model: LoLander Series Truck Scale Model: LL FT Model: LL FT Installation, Set-Up and Operation Manual

Model: LoLander Series Truck Scale Model: LL FT Model: LL FT Installation, Set-Up and Operation Manual SCALE WORKS, INC. Model: LoLander Series Truck Scale Model: LL8035-10FT Model: LL8035-11FT Installation, Set-Up and Operation Manual Cambridge Scale Works, Inc. P.O. Box 670 Honey Brook, PA. 19344 (800)

More information

Wireless Maturity System Applications: Lowe Precast Waco, TX.

Wireless Maturity System Applications: Lowe Precast Waco, TX. Wireless Maturity System Applications: Lowe Precast Waco, TX. 1 Precast Concrete Plant Prior to implementing the Maturity System: Mix designs were created to drive strength in the small 4x8 test cylinders,

More information

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE ONTARIO PROVINCIAL STANDARD SPECIFICATION OPSS.PROV 604 NOVEMBER 2017 CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

3M Cold Shrink Silicone Rubber Connector Insulators 8440 Series

3M Cold Shrink Silicone Rubber Connector Insulators 8440 Series 3M Cold Shrink Silicone Rubber Connector Insulators 8440 Series Data Sheet May 2014 Product Description 3M Cold Shrink Connector Insulators 8440 Series are open-ended, silicone rubber, tubular sleeves.

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB #

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # SECTION 26 0529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Testing Overview (USA) INFRASTRUCTURE FOR LIFE

Testing Overview (USA) INFRASTRUCTURE FOR LIFE Testing Overview (USA) INFRASTRUCTURE FOR LIFE RS Technologies www.rstandard.com Email Toll Free Phone Fax info@grouprsi.com +1 877 219 8002 +1 403 219 8000 +1 403 219 8001 2421 37th Avenue NE, Suite 400

More information

XASeries. Shear Beam Load Cell

XASeries. Shear Beam Load Cell XASeries The XA Series is a high performance strain gage load cell constructed of alloy tool steel or stainless steel. This robust, rectangular shear beam is designed to accurately measure compression

More information

SECTION WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring.

SECTION WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring. SECTION 16120 WIRE AND CABLE PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 16112 - Raceways and Conduit. 2. 16155 - Motor Power and Control Wiring. 1.02 SYSTEM DESCRIPTION A. Performance Requirements:

More information

Single core conductor BETAtherm 145

Single core conductor BETAtherm 145 Internet: www.synflex.de Single core conductor BETAtherm 145 Description BETAtherm 145 is a flexible low-voltage cable with UL recognition consisting of a tinned copper stranded wire and insulated with

More information

Sabah Shawkat Cabinet of Structural Engineering 2017

Sabah Shawkat Cabinet of Structural Engineering 2017 3.1-1 Continuous beams Every building, whether it is large or small, must have a structural system capable of carrying all kinds of loads - vertical, horizontal, temperature, etc. In principle, the entire

More information

SECTION 4 - SECONDARY CONSTRUCTION OVERHEAD TABLE OF CONTENTS

SECTION 4 - SECONDARY CONSTRUCTION OVERHEAD TABLE OF CONTENTS 4. GENERAL SECONDARIES & SERVICES 4.- INDIVIDUAL PHASE SECONDARY OVERHEAD LINE EXTENSIONS 4.- SECONDARY AND SERVICE CABLE SPLICES 4.- INSULATED SERVICE ENTRANCE COMPRESSION CONNECTORS 4.- 4. POLE ATTACHMENTS

More information

Electrical Fasteners. Everything concerning cables

Electrical Fasteners. Everything concerning cables Electrical Fasteners Everything concerning cables «Bossard delivers everything concerning cables upon request in the fully-automatic logistics system.» EVERYTHING CONCERNING CABLES Electrical fasteners

More information

DIVISION 26 ELECTRICAL Electrical Power Conductors and Cables

DIVISION 26 ELECTRICAL Electrical Power Conductors and Cables PART 1 - GENERAL 1.01 DESIGN REQUIREMENTS A. Scope: Power Conductors and Cables in this section are defined as system voltages above 120V and less than 600V. B. System Voltages Three Phase and Single Phase:

More information

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL). 16450 GROUNDING ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 26 An optional keynote to the

More information

TECHNICAL DATA SHEET APC (PEKK-FC) PEKK-FC THERMOPLASTIC POLYMER PREPREG

TECHNICAL DATA SHEET APC (PEKK-FC) PEKK-FC THERMOPLASTIC POLYMER PREPREG Solvay s composites consist of a thermoplastic matrix of poly (ether-ketone-ketone) commonly referred to as PEKK-FC polymer with aligned, continuous unidirectional fiber reinforcement. The tapes are fully

More information

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11 Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11 Underground Residential Distribution (URD) Index General Discussion... 1-2 Description... 3-7 Drawings (Available

More information

1-800-ICE-BRIX

1-800-ICE-BRIX 1-800-ICE-BRIX www.polar-tech.com TEMPERATURE SAFE SHIPPING & PROTECTIVE PACKAGING PRODUCTS DISTRIBUTION AND MANUFACTURING LOCATIONS: CHICAGO/MIDWEST NYC/PHILA Dry ice snow makers are ergonomically engineered

More information

Calculation accuracy of high-temperature sag for ACSR in existing lines

Calculation accuracy of high-temperature sag for ACSR in existing lines Calculation accuracy of high-temperature sag for ACSR in existing lines D. Loudon, EFLA, Norway D.A. Douglass*, DPC, LLC, USA R.G. Stephen, ESKOM, South Africa G.C. Sibilant, EPRI/UKZN, USA Abstract According

More information

Originally Issued: 11/24/2010 Revised: 01/20/2017 Valid Through: 11/30/ Design

Originally Issued: 11/24/2010 Revised: 01/20/2017 Valid Through: 11/30/ Design EVALUATION SUBJECT: HRC 555 SERIES (XTENDER ) AND HRC 670 SERIES T-HEAD (HEADLOCK ) HEADED ENDS OF CONCRETE REINFORCEMENT REPORT HOLDER: Headed Reinforcement Corp. 11200 Condor Avenue Fountain Valley,

More information

System Level Effects on Solder Joint Reliability

System Level Effects on Solder Joint Reliability System Level Effects on Solder Joint Reliability Maxim Serebreni 2004 2010 Outline Thermo-mechanical Fatigue of solder interconnects Shear and tensile effects on Solder Fatigue Effect of Glass Style on

More information

appendix a. iso standards for adhesives and grouts

appendix a. iso standards for adhesives and grouts ISO installation material standards for mortars, adhesives, and grouts are more fully described in the following standards: 13007-1 Ceramic Tiles - Grouts and adhesives - Part 1: Terms, definitions and

More information

Evaluation of Aluminum Cable Presentation for IEEE OCS September 14, 2011 Breck Booker, Southwire

Evaluation of Aluminum Cable Presentation for IEEE OCS September 14, 2011 Breck Booker, Southwire Evaluation of Aluminum Cable Presentation for IEEE OCS September 14, 2011 Breck Booker, Southwire Today s Topics Brief Overview of Southwire In-depth Discussion on Aluminum Characteristics Discussion of

More information

Brief History. BetaTron Electronics Inc. was established in 1982 and has enjoyed 29 years in business in Albuquerque, NM.

Brief History. BetaTron Electronics Inc. was established in 1982 and has enjoyed 29 years in business in Albuquerque, NM. Brief History BetaTron Electronics Inc. was established in 1982 and has enjoyed 29 years in business in Albuquerque, NM. BetaTron has retained ISO 9001:2008 certification for 12 years. BetaTron is UL 508A

More information

CONTENTS INSTRUCTIONS. UK POWER NETWORKS LV JOINTING MANUAL I Version Section Index I Page 1

CONTENTS INSTRUCTIONS. UK POWER NETWORKS LV JOINTING MANUAL I Version Section Index I Page 1 CONTENTS 1 INTRODUCTION 2 JOINTING INSTRUCTIONS 2.1 Conductor Sizes 1 2.2 Comparison of Cable Ratings Based on Cable Type and Size 2 2.3 Jointers Tool Kit 3 2.4 New Harmonised Phase Colours 4 2.4.1 Single-Phase

More information

Wireless Freezer Manual Installation Guide

Wireless Freezer Manual Installation Guide Wireless Freezer Manual Installation Guide Doc # 152-11103-01 Revision DRAFT May 2009 Copyrights Copyright 2008 by. All rights reserved. The information in this document is subject to change without notice.

More information

Lightning exposure of Carbon Fiber Composites in wind turbine blades

Lightning exposure of Carbon Fiber Composites in wind turbine blades 105 24 th Nordic Insulation Symposium on Materials, Components and Diagnostics Lightning exposure of Carbon Fiber Composites in wind turbine blades Søren Find Madsen, Lisa Carloni Global-Lightning Protection

More information

CYCLIC PERFORMANCE OF RC BEAMS WITH WEB OPENINGS

CYCLIC PERFORMANCE OF RC BEAMS WITH WEB OPENINGS CYCLIC PERFORMANCE OF RC BEAMS WITH WEB OPENINGS Luis HERRERA 1 and Anne LEMNITZER 2 ABSTRACT The introduction of web openings in reinforced concrete beams enables the passage of utility services and avoids

More information

Welding Accessories

Welding Accessories Welding Accessories www.airliquide.ca 1-800-817-7697 Welding Accessories BLUESHIELD Welding Cables Blueshield Welding Cables: Excellent flexibility (stays flexible at -50 C) Abrasion resistant Oil, solvent

More information

AASHTOWare BrDR 6.8 Steel Tutorial STL6 Two Span Plate Girder Example

AASHTOWare BrDR 6.8 Steel Tutorial STL6 Two Span Plate Girder Example AASHTOWare BrDR 6.8 Steel Tutorial STL6 Two Span Plate Girder Example STL6 - Two Span Plate Girder Example (BrDR 6.5) 1'-6" 37'-0" 34'-0" 1'-6" 8 1/2" including 1/2" integral wearing surface FWS @ 25 psf

More information

CORROSION ENGINEERING SPECIFICATION FOR INSTALLATION SPECIFICATION FOR CONCRETE VESSELS DESIGNED TO RECEIVE BRICK OR MEMBRANE AND BRICK LINING

CORROSION ENGINEERING SPECIFICATION FOR INSTALLATION SPECIFICATION FOR CONCRETE VESSELS DESIGNED TO RECEIVE BRICK OR MEMBRANE AND BRICK LINING AN ERGONARMOR COMPANY TECHNICAL INFORMATION CES-301 03/00 SUPERSEDES 02/99 PAGE 1 OF 5 CORROSION ENGINEERING SPECIFICATION FOR INSTALLATION SPECIFICATION FOR CONCRETE VESSELS DESIGNED TO RECEIVE BRICK

More information

Detailed Requirements Document (DRD) Level 3 OLE Context Core and Specialisms

Detailed Requirements Document (DRD) Level 3 OLE Context Core and Specialisms Detailed Requirements Document (DRD) Level 3 OLE Context Core and Specialisms Overview Employers in the Rail Engineering Sector have developed this Detailed Requirements Document (DRD); the document is

More information

Serv. Low-Voltage Cable Insulated Conductors for Overhead and Underground Distribution

Serv. Low-Voltage Cable Insulated Conductors for Overhead and Underground Distribution Serv Low-Voltage Cable Insulated Conductors for Overhead and Underground Distribution General Cable offers a complete line of insulated cable designs and sizes to meet utility requirements for exceptional

More information

*** Supercedes: BECO E and COM , , & ***

*** Supercedes: BECO E and COM , , & *** 7/27/09 Page 1 of 9 R5 *** Supercedes: BECO E2.9-27.4 and COM 1-0696, 2-0196, & 5-0385 *** 1.0 Scope #2 AWG to 1000 KCMIL CONCENTRIC NEUTRAL JACKETED CABLES RATED 5-35 kv These Specifications cover single

More information

QuakeWrap s PileMedic System November 30, 2010

QuakeWrap s PileMedic System November 30, 2010 PileMedic for Repair and Strengthening of Columns & Underwater Piles How can we fix these piers in a day while maintaining traffic? Mo Ehsani, Ph.D., P.E., S.E. President, QuakeWrap, Inc., and Professor

More information

TECHNICAL ANALYSIS #2

TECHNICAL ANALYSIS #2 TECHNICAL ANALYSIS #2 Problem Civista is wired using copper conductors only. Copper is an expensive material that is some opinions, offers the same performance from a much cheaper aluminum alloy alternative.

More information

Mechanical Behavior of Glass Fiber Reinforced Polymer Pultruded Composite Gratings

Mechanical Behavior of Glass Fiber Reinforced Polymer Pultruded Composite Gratings Modern Mechanical Engineering, 213, 3, 142-146 Published Online November 213 (http://www.scirp.org/journal/mme) http://dx.doi.org/1.4236/mme.213.342 Mechanical Behavior of Glass Fiber Reinforced Polymer

More information

Details of technical leaflets/write-up on various pieces of equipment.

Details of technical leaflets/write-up on various pieces of equipment. Details of technical leaflets/write-up on various pieces of equipment. (1) Insulator Designs: The insulators are provided in one, two, three, or four insulator designs per location and spaced to provide

More information

THE BRACE CONNECTION THE BOLTED OPTION FIGURE 1 MODEL SHOWING THE BOILER AND THE STRUCTURAL SUPPORT SYSTEM (BOILER BUILDING)

THE BRACE CONNECTION THE BOLTED OPTION FIGURE 1 MODEL SHOWING THE BOILER AND THE STRUCTURAL SUPPORT SYSTEM (BOILER BUILDING) Comparative Study of Bolted versus Welded SCBF Connections Authors: Robert P. Krumpen III P.E., Bechtel Corporation, rpkrumpe@bechtel.com Dr. Peter J. Carrato P.E. S.E., Bechtel Corporation, pcarrato@bechtel.com

More information

ISO/TR TECHNICAL REPORT

ISO/TR TECHNICAL REPORT TECHNICAL REPORT ISO/TR 15655 First edition 2003-04-01 Fire resistance Tests for thermo-physical and mechanical properties of structural materials at elevated temperatures for fire engineering design Résistance

More information

Radiation Resistant Insulation Systems for the ITER Toroidal Field Coils

Radiation Resistant Insulation Systems for the ITER Toroidal Field Coils Radiation Resistant Insulation Systems for the ITER Toroidal Field Coils R. Prokopec 1), K. Humer 1), R. K. Maix 1), H. Fillunger 1), H. W. Weber 1), J. Knaster 2), F. Savary 2) 1) Vienna University of

More information

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING SECTION 16060 PART 1 GENERAL 1.01 DESCRIPTION A. Section includes requirements for an electrical grounding system, including electrodes, grounding rods, connectors, insulators, equipment grounding and

More information

TECHNICAL DATA NEAT RESIN MECHANICAL PROPERTIES

TECHNICAL DATA NEAT RESIN MECHANICAL PROPERTIES TYPICAL APPLICATIONS Marine Structures Dielectric Structures Aerospace Structures PRODUCT FORMS Unitape to 24 Inches Wide Fabric Prepreg to 50 Inches Wide TYPICAL CURE PARAMETERS (If Aerospace applications

More information

CHAPTER III METHODS AND MATERIALS

CHAPTER III METHODS AND MATERIALS CHAPTER III METHODS AND MATERIALS 3.1: Tensile Tests 3.1.1: Introduction The first phase of testing for the experimental program, was to conduct tensile tests of No. 4, No. 5, and No. 6 nominal diameter

More information

XXXXXXXXXXX Solar (XXX) Generation Interconnection

XXXXXXXXXXX Solar (XXX) Generation Interconnection Facility Study For XXXXXXXXXXX Solar (XXX) Generation Interconnection Prepared For: Randy Harlas, Substation Manager El Paso Electric Company El Paso, TX September 2010 Table of Contents 1. GENERAL...

More information

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases.

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases. SECTION 260529 - HANGERS AND SUPPORTS PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases. 1.2

More information

Technical Notes 24G - The Contemporary Bearing Wall - Detailing [Dec. 1968] (Reissued Feb. 1987) INTRODUCTION

Technical Notes 24G - The Contemporary Bearing Wall - Detailing [Dec. 1968] (Reissued Feb. 1987) INTRODUCTION Technical Notes 24G - The Contemporary Bearing Wall - Detailing [Dec. 1968] (Reissued Feb. 1987) INTRODUCTION The selection of a wall type and appropriate connection details is one of the most important

More information

FINITE ELEMENT ANALYSIS AND EXPERIMENTAL EVALUATION OF SUPERELASTIC NITINOL STENT

FINITE ELEMENT ANALYSIS AND EXPERIMENTAL EVALUATION OF SUPERELASTIC NITINOL STENT FINITE ELEMENT ANALYSIS AND EXPERIMENTAL EVALUATION OF SUPERELASTIC NITINOL STENT Xiao-Yan Gong*, Alan R. Pelton*, Tom W. Duerig*, Nuno Rebelo** and Ken Perry*** *Nitinol Devices & Components, 47533 Westinghouse

More information

TECHNICAL BULLETIN October 5, 2007

TECHNICAL BULLETIN October 5, 2007 INTRODUCTION Successful food service countertop design requires attention to detail and often requires technical expertise. Hot and cold food service countertops require special fabrication and installation

More information

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph

More information

Building Attachments and Services

Building Attachments and Services Part Four. Other Electrical Procedures CHAPTER 11 Building Attachments and Services All electrical energy supplied to power-consuming devices and appliances within a building must pass through the electrical

More information

Casing Connection Selection for Geothermal Applications Using Input From HPHT and Thermal Wells Testing Protocols. Mustaffa Merliahmad, Tenaris

Casing Connection Selection for Geothermal Applications Using Input From HPHT and Thermal Wells Testing Protocols. Mustaffa Merliahmad, Tenaris Casing Connection Selection for Geothermal Applications Using Input From HPHT and Thermal Wells Testing Protocols Mustaffa Merliahmad, Tenaris Agenda Geothermal Operation Connection Testing Connection

More information

Installation of CSST Gas Piping Systems

Installation of CSST Gas Piping Systems (What Inspectors Need To Know) May 2016 Conventional Arc-Resistant CSST Product Standard National Standard ANSI LC-1 Performance-based standard Listed system installed in accordance with manufacturer s

More information

AASHTOWare BrR 6.8 Steel Tutorial Steel Plate Girder Using LRFR Engine

AASHTOWare BrR 6.8 Steel Tutorial Steel Plate Girder Using LRFR Engine AASHTOWare BrR 6.8 Steel Tutorial Steel Plate Girder Using LRFR Engine STL6 - Two Span Plate Girder Example 1'-6" 37'-0" 34'-0" 1'-6" 8 1/2" including 1/2" integral wearing surface FWS @ 25 psf 3'-6" 3

More information

Presentation in support of

Presentation in support of Presentation in support of Proposed Acceptance Criteria For Continuous or Semi- Continuous Fiber-Reinforced Grid Connectors used in combination with Rigid Insulation in Concrete Sandwich Panel Construction

More information

Daytona Beach Pier Building Renovation Jun 2010

Daytona Beach Pier Building Renovation Jun 2010 SECTION 15060 - HANGERS AND SUPPORTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Trusted ICC ES. Conformity! Look. Evaluation. ICC-ES Evaluation

Trusted ICC ES. Conformity! Look. Evaluation. ICC-ES Evaluation 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg ESR 3288 Reissued 12/2017 This report is subject to renewal 12/2018. DIVISION: 03 00

More information

Would You Like Concrete With Little or No Shrinkage, Cracking, and Curling??? We Will Focus on:

Would You Like Concrete With Little or No Shrinkage, Cracking, and Curling??? We Will Focus on: Would You Like Concrete With Little or No Shrinkage, Cracking, and Curling??? We Will Focus on: Coarse Aggregates Admixtures Including Shrinkage Reducing and Shrinkage Compensating Admixtures Evaporation

More information

R. Prokopec, K. Humer, H. Fillunger, R. K. Maix, and H. W. Weber

R. Prokopec, K. Humer, H. Fillunger, R. K. Maix, and H. W. Weber PROPERTY CHANGES OF CYANATE ESTER / EPOXY INSULATION SYSTEMS CAUSED BY AN ITER-LIKE DOUBLE IMPREGNATION AND BY REACTOR IRRADIATION R. Prokopec, K. Humer, H. Fillunger, R. K. Maix, and H. W. Weber Atominstitut,

More information

DESIGN FOR PROGRESSIVE COLLAPSE 1

DESIGN FOR PROGRESSIVE COLLAPSE 1 Your Partner in Structural Concrete Design TN447_progressive_collapse_110713 DESIGN FOR PROGRESSIVE COLLAPSE 1 Bijan O Aalami 2 This Technical Note outlines the design of column-supported conventionally

More information

Low-profile, 11U high cabinets hold networking equipment, servers, and phone equipment.

Low-profile, 11U high cabinets hold networking equipment, servers, and phone equipment. RM140A-R3 RM140A-M-R3 RM145A-R3 RM145A-M-R3 Small Office/Home Office (SOHO) Cabinets Low-profile, 11U high cabinets hold networking equipment, servers, and phone equipment. Fit under most desktops in the

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less)

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less) SECTION 260523 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less) PART 1 - GENERAL 1.1 SUMMARY A. Related Documents: 1. Drawings and general provisions of the Subcontract apply

More information

WITH THE TITLE 24. replacement. story. stories, etc. R disconnects. to, PV. unit and any. supporting frame. conditions. greater than the main

WITH THE TITLE 24. replacement. story. stories, etc. R disconnects. to, PV. unit and any. supporting frame. conditions. greater than the main CITY OF CYPRESS Building Division 5275 Orange Avenue, Cypress, California 906300 714-229-6730 buildingpermits@ @ci.cypress.ca.us RESIDENTIAL PHOTOVOLTAIC SYSEMS ALL WORK SHALL REQUIRE COMPLIANCE WITH THE

More information

MAR 17 Rev B1

MAR 17 Rev B1 Product Specification 108-151010 01 MAR 17 Rev B1 DTM Series Connector System 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for the TE Connectivity (TE) DTM

More information

Aluminum Wiring. Facts and Figures

Aluminum Wiring. Facts and Figures Aluminum Wiring by Nick Gromicko and Kenton Shepard Between approximately 1965 and 1973, single-strand aluminum wiring was sometimes substituted for copper branch-circuit wiring in residential electrical

More information

Testing and Analysis

Testing and Analysis Testing and Analysis Fatigue and Failure Testing of Elastomers for Analysis By Kurt Miller, Introduction Elastomeric materials in engineering applications experience complicated strains and stresses. They

More information

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES CEB STANDARD 030-1 : 1996 Specification for RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES CEYLON ELECTRICITY BOARD SRI LANKA Specification for RESIN FILLING TYPE JOINTING KITS FOR

More information

NEUTRAL GROUNDING TRANSFORMERS INSTALLATION AND MAINTENANCE INSTRUCTIONS

NEUTRAL GROUNDING TRANSFORMERS INSTALLATION AND MAINTENANCE INSTRUCTIONS 1 Table of Contents SECTION 1 Unpacking... 3 1.1 Shipping... 3 1.2 Receiving... 3 SECTION 2 Installation... 3 SECTION 3 Inspection... 4 SECTION 4 Connection... 4 4.1 Neutral Lead... 5 4.2 Ground Lead...

More information