Executive Summary. ABSA Building October Project Brief. Introduction
|
|
- Jonah Mosley
- 6 years ago
- Views:
Transcription
1 Executive Summary ABSA Building October 2014 Project Brief The project brief requested that the professional team conduct a visual only, conditional assessment of the building condition, services and structural integrity of the ABSA Building. Recommendations with regard to the repairs, renovations and upgrading of the building are to be included in this assessment. Introduction The professional team, whom carry vast knowledge throughout all facets of the construction industry, have performed a high-level evaluation of the building, with the objective of achieving all targets set out in the clients Request for Proposal of April The building is located on the corner of Albertina Sisulu and Fraser Street, in the Central Business District of Johannesburg, Gauteng. The building has two sections, one lower portion on the western side which comprises of a ground floor, mezzanine and 5 floors above ground and a higher portion to the east which comprises of a ground floor, mezzanine and 11 floors above ground. The building has 2 basements but a singular entrance which only accommodates one car at a time. This building is partially occupied. The fire escape staircases are non-compliant to regulations and are currently a hazard to the occupants. Despite this fact, all levels will require renovation works which must comply with the latest National Building Regulations, SANS10400 and the B-Grade SAPOA grading. All Town Planning prescripts of the local authority must furthermore be conformed to. The building holds a gross building area of approximately m 2 with a Gross leasable Area of m 2 which results in an efficiency factor of 58%. As per the SANA the population is calculated on the basis of 1 person per 15m 2 which equates to occupancy of 460 people. However, should the Client opt for 10 m 2 per person, then the maximum occupancy would be 693 people. A table indicating the various occupancy allowable per floor has been included in the detailed Architectural assessment. The building condition assessment carried out, is detailed and documented herein accordingly under each specific building discipline. It must further be noted that the assessment conducted is of a visual nature and where required, advanced comprehensive testing is recommended. The professional team s findings are evaluated, but limited to: Best practice; Future usage of the building; Compliance to SANS 10400; Compliance to the OHS Act; Compliance to the factories act; Compliance to the Environmental ACT.
2 Architectural Detailed as-built drawings are furnished within Annexure A. External The building envelope on the street facing remains intact and appears to be in a fairly good condition. The fascade comprises of pre-cast concrete panels with window openings clad with marble stone on the ground and first floor level, followed by face brickwork on the levels above. The façade in the courtyard needs remedial works and gutters and downpipes replaced. Vegetation can be seen growing on the fascade cracks. Basement Level There are currently 2 basement parking levels of which the head restriction is 1.95m which is very low. No trucks allowed. There is only one entry/exit route to this parking which can only accommodate one car at a time. This is only wide enough for one vehicle at a time which could lead to congestions during peak times. There is apparent water penetration in the basement which would need further investigation and remedial works. Staircases from the basement are narrow and do not comply with the National Building Regulations. Ground Level There are currently 3 entrances to this building. The entrances is to host an additional disability friendly ramp in order to comply with SANS10400 universal access regulations; The lobby area requires a redesign to make more efficient use of the space, and additionally a complete fit out to this area is required. Levels - mezzanine, 1-11 Concrete staircases to be repaired on edges and an additional handrail installed. Finishes are poor and outdated. Level 2-6 appear to have undergone a recent refurbishment and appear to be in a fair condition. Glazing through the building to be replaced to energy efficient glazing. Ablutions are located on split levels and therefore do not cater for disable persons. The top two floors have been stripped and all rubble left behind. The banking hall appears in good condition but would a complete renovation should office space be introduced. The banking area has many safes and must be relocated if a new space planning layout is implemented. Some ablutions are leaking and water spread to passage. The offices on the levels above the banking hall are in a relatively good condition, with some remedial works where necessary.
3 Roof Levels All waterproofing requires advanced assessment, and replacement may be necessary, as per the Structural Engineers report. Full-bore outlets to be checked for blockages All gutters and downpipes to be replaced as it is not functional, rusted and inadequate. Structural The building has no links; however there is a possibility of joining this building to FNB Building and/or a bridge link across to Rand Water Building. The building has a combination of soft roof (corrugated sheeting), which has gutters and downpipes discharging onto concrete slab with screed to fall (with torch on waterproofing). Certain higher portions of roof are localised concrete roof slabs. The building has a substantial number of level differences via steps on the external pavement, without and disabled access ramps. The ablutions on the buildings are at mid stair landing heights, which is an issue from a disabled access perspective. The external fascade needs cleaning; however the internal fascade needs more remedial works. Windows will have to be replaced to comply with regulations. It is recommended that the slab systems are not populated with new air-conditioning plant as the slabs are not designed for such loadings. The concrete flat slabs will require replacement of the torch on waterproofing as it is showing signs of perishing and degradation. Some local areas show areas of local ponding which can be resolved by local screeding. The major issue with the concrete roof is the outlets from the various roofs are not being maintained. These outlets are extensively blocked with organic matter and rubbish. In general the existing slab system is in good condition; however there are many local details and local damage that needs to be repaired. The building is supported by concrete columns which are in good condition. Most of the columns require surface repainting to improve their appearance. The building shows no signs of settlement and hence foundations and bearing strata below are in good condition. Structural Floor loadings must be adhered to as per the Structural Engineers report. No masonry brickwork partitions are allowed unless verified by the Structural Engineer. Fire Existing fire hose reels and hydrants are installed with fire extinguishers in all areas of the building. The system is operational and within its service window. The statutory fire signage does not comply with SANS requirements and must be replaced.
4 The hose reels are fed by a hose connected in the fire hydrants. This does not comply with SANS. All hose reels are to have a separate valve and connection to the fire water mains installed. Some fire extinguishers are mounted too high for easy use by the office occupants. These need to be lowered to an accessible height. The fire water system is supplied with a twin booster connection at the main vehicle ramp. The pressure gauge on the booster indicates a good water supply to the building but this cannot be confirmed without a full flow test. The fire water system has no back up water supply, a hose reel pump and small storage tank should be installed to serve all hose reels in the building. There is currently a sprinkler system in the basements which is connected directly to the council supply main. Sprinkler heads to be tested and minor remedial works required. Smoke extraction to be tested and verified as compliant. External fire escapes have been locked with gates and also show signs of server rust and corrosion. These are hazardous and must be replaced. Fire rated walls to be erected to ensure fire exits and fire seal all penetrations. Smoke detection to be installed. HVAC The building is currently air-conditioned by the following types of systems: o Dunham Bush Rooftop DX Packaged units not in operation o Daikin R22 Heat Pump type VRV Systems not in operation o DX Split type units (various makes) some in operation, some beyond repair Ablutions are naturally ventilated. No mechanical extraction systems are installed. Basements are mechanically ventilated and seem intact. Recommendation to check all systems, and replace with new energy efficient system. Proposal to install a Chilled water system with distribution throughout the building. Wet Services The building has very little cold water storage located on the roof level. There is also a concrete water tank which is empty and does not seem operational. Pipes and fitting are intact and show signs of corrosion. Water reticulation is transferred to the water tank via municipal main supply and then fed through the building via gravity pressure. No booster pumps found. The sanitary ware is old and is in a poor condition. All the current fittings consume considerable amounts of water. There is only 1 geyser in the kitchen but is not operational. The drainage system is extremely rusted and is at the end of its lifespan. Electrical Services The switchgear and its cabling are in the basement in the transformer room. The switchgears are intact, well maintained but very old. The room is not well ventilated and very hot. There are 2 x 500kva transformers and in a good condition but very old. The room is not well ventilated and therefore very hot.
5 There is a 125kVA generator set in the basement and seems to be well maintained, however it seems very old. The change over panel is well maintained and must be checked. There is a very old UPS system (20kVA) and the batteries look old and dusty. DB board to be upgraded to modern technology and wiring to be replaced. Most plugs and light fitting are in working condition but seems to be very old. No energy efficient fittings have been used. System to be upgraded and replaced due to its age and to bring in line with SANS and SANS Electronic Services Life systems currently limited to fire detection system only. The system currently has faults on 3 loops on the panel. As this system does not comply with SANS 10139, the system will have to be replaced and upgraded for early detection. No zoning diagrams present. Entrances are secured by physical guards. The branch area has no detection visible. Floors 2 to roof level contain convention detectors, break glass units and strobes/sirens. Lift lobbies and fire escapes also contain break glass units and strobes/sirens. No fire brigade installed next to panel. Intruder detection is evident in the branch part of the office but is not operational as the head-end of the alarm system has been removed. Only a DSTV satellite dish installed on the roof. Town Planning The property identification is Erf 5151 Marshalls Town, and holds a building footprint extent of 1488 m 2. There is currently a 2.5m wide servitude for street purposes registered against this property and affects the boundaries on Fraser and Albertina Sisulu Street. The building is registered in the name of Gauteng Provincial Government and is held in terms of the Deed of Transfer No T /2005. A copy of the title deed is attached under the detailed town planning report. In addition to this, certain standard conditions are stipulated in the Title Deed concerning mineral rights and the enforcement of Town Planning regulations. Zoning to the building does not restrict the building plan approval process, and the dual possession of Site Development Plan approval in submission is not a prerequisite; The existing building complies with the 59 o height line and is presently zoned Business 1 in terms of the Johannesburg Town Planning Scheme, 1979.
6 Vertical Transport The status of the lifts to the building are as follows: Core 1 (Albertina Sisulu Road Entrance) : 3 Passenger lifts with one not being operational. Core 2 (Fraser Street Entrance) : 3 Passenger lifts and not in operation at the time of inspection. One lift from each core serviced the basement to the respective floors. The lifts and equipment are old and recommend replacing the lifts in excess of 30 years old and those not functional. Upgrade lift motor rooms and ensure that all lifts comply with SANS 10400, SANS 1543, SANS 1545 and SANS Heritage ABSA building is considered to be a Heritage building with Section 34 as it is over 60 years old and it has been designed by the prominent Architect Louw & Louw. This is the same Architect that designed the New Library Hotel. The building was constructed in 1950 and maintains Heritage significance. The key architectural elements are the marble fascade on the first 2 levels. This must be maintained and cleaned. Minor repairs are required and the detailed Heritage report stipulates the history and recommendations to refurbish this building. Recommendations provided herein, must fall in line with any other applicable legislation or regulations to meet acceptable office accommodation standards and an application process to the Heritage Council must be carried out prior to commencement with any remedial works. Environmental Heaps of building rubble, rubbish, electrical waste cables, broken florescent lighting, broken windows and birds are found on the top floors of the building. This is a health& safety risk for the current occupants as the floor can be accessed by anyone within the building. Various elements such as poor ventilation, outdated electrical infrastructure, inefficient layouts, penetrating water and damp could lead to negative and a poor working environment. The emergency escape routes are deteriorated, locked in all cases and not in accordance with the regulations, thus providing this building unsafe for its occupants during emergencies. Proposals for a green courtyard, energy efficient materials and services, water management solutions, rain water harvesting, etc. have been included in the detailed report.
7 Proposed Cost Estimate The estimated high level budget is as per the attached QS Report provided herein and is based on the proposed refurbishment work furnished by the professional team concluded at the end of October.
GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT WET SERVICES ABSA BUILDING
Report for Department of Infrastructure Development Wet Services Preliminary Report: ABSA Building October 2014 GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT WET SERVICES
More informationGAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT
GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT STRUCTURAL FOR CUSTOMS HOUSE JULY 2014 i P a g e Table of Contents 1. INTRODUCTION 3 1.1 Design Criteria and Specifications..
More informationGAUTENG DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
GAUTENG DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT HVAC FOR ABSA Building OCTOBER 2014 Report for Gauteng Department of Infrastructure Development HVAC Services Preliminary Report:
More informationGAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT WET SERVICES 78 FOX STREET BUILDING
Report for Department of Infrastructure Development Wet Services Preliminary Report: 78 Fox Street Building October 2014 GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT WET
More informationGAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT
GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT STRUCTURAL FOR CORNER HOUSE AUG 2014 i P a g e Table of Contents 1. INTRODUCTION... 3 1.1 Design Criteria and Specifications...
More informationSIMULATED OFFICE PROJECT 2008 TECHNICAL REPORT
SIMULATED OFFICE PROJECT 2008 TECHNICAL REPORT NEW FACILITY FOR ADULT BASIC EDUCATION AND VOCATIONAL TRAINING By Leigh Hartl Student Number: 207514952 A Report Submitted in Partial Fulfilment of the Requirements
More informationAdministration Building Needs Assessment
Town Hall Meeting with the Habersham County Board of Commissioners Administration Building Needs Assessment JUNE 13, 2016 Detailed Evaluation Performed in 2015 Engineering Evaluation Site/Civil Architectural
More informationTanaz Fashions Ltd. & Zayantex Ltd. L Usine Fashion Ltd (Unit 1)
Tanaz Fashions Ltd. & Zayantex Ltd. L Usine Fashion Ltd (Unit 1) 216, Sataish Road, Gazipura, Tongi, Gazipur, Bangladesh (23.921458N,90.386581E) 22 September 2013 1 2 Local concrete spalling caused by
More informationGAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT
GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT STRUCTURAL FOR 75 FOX STREET AUGUST 2014 i P a g e Table of Contents 1. INTRODUCTION 3 1.1 Design Criteria and Specifications..
More informationSPECIFICATION OUTLINE. 28 November 2017 REV 2
P a g e 1 ORIGIN PARK, RICHMOND PARK, MILNERTION N7 CAPE TOWN 28 November 2017 REV 2 1. EXTERIOR 1.1 MAIN BUILDING - Main Building design to warehousing building type class J2 as per SANS 10400. Goods
More informationSPACE TYPE: OUTSIDE PARKING (STRUCTURE)
SPACE TYPE: OUTSIDE PARKING (STRUCTURE) Construction Criteria The unit costs for Outside Parking (Structure) space types are based on the construction quality and design features in the following table.
More informationCONSTRUCTION DOCUMENTS CHECKLIST for the 2012 Michigan Building Code Including Building Permit Application Checklist
CONSTRUCTION DOCUMENTS CHECKLIST for the 2012 Michigan Building Code Including Building Permit Application Checklist This checklist is a convenient reference to the 2012 Michigan Building Code. The checklist
More informationUCC Permit Application Procedures
How do I apply for a permit? UCC Permit Application Procedures 1. Please complete the CodeMaster Pan Review Application 2. Please provide the scope of work description and/or construction documents/plans.
More information&02.1. Level 3 Alterations. Level 3 Alterations shall comply with Sections & and &
&01 GENERAL To be developed. All of the exceptions have to be coordinated. &02 SPECIAL USE AND OCCUPANCY &02.1. Level 3 Alterations. Level 3 Alterations shall comply with Sections &02.1.1 and &02.1.2.
More information4. Number of drawings required: ( ) Locations of nearest streets
CITY OF MANSFIELD BUREAU OF BUILDING AND CODES 30 NORTH DIAMOND STREET 3RD FLOOR MANSFIELD, OHIO 44902 Phone (419) 755-9688 Fax (419) 755-9453 www.ci.mansfield.oh.us COMMERCIAL BUILDING PLAN REQUIREMENTS
More informationThe Magna Standard January 2015
Version: 2 Effective Date: 22/03/17 The Magna Standard January 2015 A guide for residents We have designed The Magna Standard to make sure that we maintain and improve your home above the Decent Homes
More informationCity of Walnut Creek Development Review Services 1666 N. Main Street, Walnut Creek, CA (925) phone (925) fax
City of Walnut Creek Development Review Services 1666 N. Main Street, Walnut Creek, CA 94596 (925) 943-5834 phone (925) 256-3500 fax Issued August 3, 2011 Information Bulletin No. IB-002 Submittal Requirements
More information1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural %
BartelsRode Gymnasium 8/11/ Building Rating System Percent Site: 1.0 Total 0 13 77% Building: 2.1 Building Exterior Elements 0 8 8% 2.2 Accessibility 0 74 74% 2.3 Structural 0 76 76% 2.4 Building Envelope
More informationBuilding Permit Application
Building Permit Application Administrative Use Only PARENT PERMIT NUMBER (Required if part of another project) PERMITTEE: PERMITTEE ADDRESS: E-MAIL ADDRESS: ARCHITECT/ENGINEER: ARCHITECT/ENGINEER ADDRESS:
More informationEH Textiles Ltd EH Fabrics Ltd
EH Textiles Ltd EH Fabrics Ltd 221 225 Sataish Rd, Khortoil, Dhaka (23.9208N, 90.3880E) 31 October, 2013 1 2 Building Observations 3 Engineering Checks on columns required C2 perimeter columns drawings
More informationPiping system (steam, hot water, chilled water system) including pipe and duct insulation needs replacement.
NW Corridor Transit Planning Union Station Existing Conditions Technical Memorandum (Physical and Operational Assessments) Executive Summary Capitol Region Council of Governments Prepared in cooperation
More informationCTC MEETING #25 CHILD WINDOW SAFETY REPORT
CTC MEETING #25 CHILD WINDOW SAFETY REPORT The Child Window Safety SG has not met following the 2012 Final Action Hearing. Group B activities did not necessitate SG meetings as the activity will be limited
More informationAPPENDIX 3E HAZELWOOD HOTEL SPECIFICATIONS
APPENDIX 3E HAZELWOOD HOTEL SPECIFICATIONS 1. GENERAL 1.1 Refer to Section 2.1 of Schedule 3 [Design and Construction Specifications] regarding compliance with Schedule 3 and this Building Specification.
More informationSPRINGWOOD COMMUNITY & CULTURAL FACILITIES
SPRINGWOOD COMMUNITY & CULTURAL FACILITIES REPORT ON PROPOSED HYDRAULIC AND FIRE SERVICES Issue Date Revision Author Status A September 2011 Preliminary G. Barnes Current Prepared by: Prepared for: WARREN
More informationSCHEDULE OF CONDITION. Fulham, London SW6 FOR. Mr S Of XXXX Limited. Prepared by: INDEPENDENT CHARTERED SURVEYORS
SCHEDULE OF CONDITION Fulham, London SW6 FOR Mr S Of XXXX Limited Prepared by: INDEPENDENT CHARTERED SURVEYORS Marketing by: CONTENTS SCHEDULE OF CONDITION Elevations page 4 Internal Rooms page 12 GROUND
More informationVillage of Gurnee Construction Documents Submittal Requirements
Commercial New Construction 4 sets of complete plans Commercial Alterations 2 sets of complete plans Residential New Construction, Remodel and/or Addition 2 sets of complete plans DETAILED PLAN REQUIREMENTS
More informationPENNSAFE BUILDING INSPECTION SERVICES LLC NEW COMMERCIAL BUILDING UCC PLAN REVIEW HANDOUT AND CHECKLIST
PENNSAFE BUILDING INSPECTION SERVICES LLC NEW COMMERCIAL BUILDING UCC PLAN REVIEW HANDOUT AND CHECKLIST Every item below must be checked as completed (if applicable), or marked n/a (if not applicable),
More informationMondol Fabrics Ltd. Nayapara,kasimpur, Gazipur ( N, E0) 8th March 2014
Mondol Fabrics Ltd Nayapara,kasimpur, Gazipur (23.990028N, 90.317336E0) 8th March 2014 1 2 Observations 3 Column Stresses in Toilet Area North of Building Cursory calculations indicate that column size
More informationCHAPTER 34 EXISTING BUILDINGS
CHAPTER 34 EXISTING BUILDINGS SECTION 3401 GENERAL 3401.1 Scope. Provisions of this chapter shall govern the application of this code to existing buildings. Exception: Buildings and structures located
More informationRepair or replace section of driveway, approach, or sidewalk that are a trip hazard.
City of Gibraltar Pre-Sale Inspection Report Checklist FLATWORK: Repair or replace section of driveway, approach, or sidewalk that are a trip hazard. EXTERIOR PROPERTY: Fences/Sheds/Retaining walls: Repair,
More informationWest & North Yorkshire Chamber of Commerce. Serviced offices project, Bradford. Information for contractor Expressions of Interest
West & North Yorkshire Chamber of Commerce Serviced offices project, Bradford Information for contractor Expressions of Interest Background West & North Yorkshire Chamber of Commerce (the Chamber) plans
More informationNYC Department of Education
Building Assessment Survey 2017-2018 Asset: HS FOR MATH, SCI & ENGINEERING-M, 240 CONVENT AVENUE, New York, 10031 Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior 2017-12-20
More informationNewton Group CANADACAR SYSTEM. Basic Construction of the CANADACAR System. CANADACAR Module Format
Basic Construction of the CANADACAR System The CANADACAR System is a prefabricated, engineered and constructed freestanding parking garage structure that utilizes superior technology combining pre-cast
More informationAppendix J - Custom Uniformat for EDU Migration
Appendix J - Custom Uniformat for EDU Migration Nr. MTC Uniformat for VFA.facility Life (Years) Weight (1-100) Out of Scope Cost Y/N 1 A Substructure 150 N 2 A10 Foundations 150 N 3 A1010 Standard Foundations
More informationExhibit A Library Shell Construction
Exhibit A Library Shell Construction Library Component Building Requirements Approximately 15,000-17,000 square feet plus 900 square feet for mechanical room and additional space on roof for installation
More informationMills Elementary School Site Summary
1 Mills Elementary School Site Summary Address 6201 Davis Lane Austin, TX 78749 Number of Permanent Campus Facilities 1 Original Year of Construction 1998 Total Campus Building Area (combined) 81,368 SF
More informationAPPENDIX 3C DOMINION HOTEL SPECIFICATIONS
APPENDIX 3C DOMINION HOTEL SPECIFICATIONS 1. GENERAL 1.1 Refer to Section 2.1 of Schedule 3 [Design and Construction Specifications] regarding compliance with Schedule 3 and this Building Specification.
More informationAdministrative Offices
CUYAHOGA COUNTY PUBLIC LIBRARY EXISTING FACILITY ASSESSMENT December 2009 Administrative Offices 2111 Snow Road, Parma, Ohio 44134 Location Entry Site View of Staff Entrance ADM Administrative Offices
More informationCONTRACT DOCUMENTS REVIEW PACKAGE CHECKLIST
CONTRACT DOCUMENTS REVIEW PACKAGE CHECKLIST Check off each item that is included within the submitted Contract Documents Review Package. Provide a written explanation for any omissions. The following items,
More informationEastern Cape Development Corporation invites developers to submit proposal calls with concept, designs and funding. and Motor Town Land
REQUEST FOR PROPOSAL Eastern Cape Development Corporation invites developers to submit proposal calls with concept, designs and funding. RFP Reference Number Description Briefing Meeting Closing Date/Time
More information2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012
2012 Ontario Building Code Requirements for New Construction Bradford West Gwillimbury Building Division March 5, 2012 1 Ontario Building Code changes Applicable to permits applied for after December 31,
More informationPreliminary Inspection Plan Certification On Site Inspection. Ancillary Design... Ancillary Construction Inspecti... Testing Requirement
1 Commencement Setting Out Ground Location of existing below ground service Ground Location of site gas CSD Ground Location of site water mains CSD Ground Location of below ground drainage FFA Ground Location
More informationPreliminary Inspection Plan Certification On Site Inspection. Ancillary Design... Ancillary Construction Inspecti... Testing Requirement
1 Commencement Setting Out Ground Location of existing below ground service Ground Location of site gas CSD Ground Location of site water mains CSD Ground Location of below ground drainage FFA Ground Location
More informationHERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW
HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW 27 September 2007 prepared by: J. CHRIS EVANS ARCHITECT 3220 E. Terra Alta Blvd. No. 9 Tucson, Arizona 85716 520.319.8835 evansarch@hotmail.com
More informationInspection requests submitted by 2:30pm will be scheduled for the following business day unless otherwise requested.
Purpose 355 West Queens Road Single Family New Construction Required Inspection Stages Master Requirement GEN 110 Building Department: 604-990-2480, building@dnv.org, fax: 604-984-9683 The following procedure
More informationPERMIT APPLICATION CHECKLIST Municipal Address, Phone & Fax NONRESIDENTIAL
PERMIT APPLICATION CHECKLIST Municipal Address, Phone & Fax NONRESIDENTIAL Permit Application #: Date: mm/dd/yy Project Address Applicant s Name NOTE TO PERMIT APPLICANTS: All permit applications must
More informationLake Highlands North Recreation Center Summary
Lake Highlands North Recreation Center Summary Address Building Purpose 9940 White Rock Trail Dallas, TX 75238 Recreation Center Original Year of Construction 1971 Building Area 33,036 SF Inspection Date
More informationRESIDENTIAL BUILDING PERMIT GUIDE FOR MULTI-FAMILY DWELLINGS
RESIDENTIAL BUILDING PERMIT GUIDE FOR MULTI-FAMILY DWELLINGS New Construction, Addition, or Alteration All plans submitted must be prepared, sealed, and signed by a Registered Nebraska Design Professional
More informationCity of South Pasadena COMMUNITY IMPROVEMENT
City of South Pasadena COMMUNITY IMPROVEMENT Office Address: Mailing Address: 6940 Hibiscus Ave S 7047 Sunset Dr S South Pasadena, FL 33707 South Pasadena, FL 33707 *PHONE: (727) 343-4192 * FAX: (727)
More informationOPERATIONAL POLICY AND PROCEDURE
OPERATIONAL POLICY AND PROCEDURE Overv iew Building & Environment Asbestos Policy Cleaning Policy Passenger and Goods Lifts Ladders and Access Equipment Policy Sanitary Bins Policy Waste Management Policy
More informationPHILMONT WAREHOUSE BUILDING PRELIMINARY STRUCTURAL ASSESSMENT
PHILMONT WAREHOUSE BUILDING PRELIMINARY STRUCTURAL ASSESSMENT Prepared for: GATTER ARCHITECTS 111 MAIN ST. PHILMONT, NY 12565 Prepared by: TACONIC ENGINEERING, DPC PO BOX 272 CHATHAM, NY 12037 TACONIC
More informationA/E Design Deliverable Checklist
A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic
More informationEQUIVALENT INITIAL STRUCTURAL SAFETY ASSESSMENT
EQUIVALENT INITIAL STRUCTURAL SAFETY ASSESSMENT A-23, 24, 25, 26 BSCIC, Industrial Estate, Kalurghat, Chittagong The Alliance for Bangladesh Worker Safety Page 1/15 Introduction to the Report The following
More information(Old examination format for reference only)
The Institution of Structural Engineers Associate-Membership Examination 11 APRIL 2003 INSTRUCTIONS TO CANDIDATE 1. The examination comprises two sessions separated by a lunch break of 1 2 hour, during
More informationDAVIS ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1943 BUILDING AREA 71,100 SF CURRENT PROGRAM CAPACITY 507 ENROLLMENT 2008 227 WARD 7 PROPOSED PROGRAM CAPACITY 325 Site Plan DAVIS - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-
More informationLORD'S VIEW INDUSTRIAL PARK
P a g e 1 LORD'S VIEW INDUSTRIAL PARK APPLICATION: - BUILDING PLANS CHECKLIST APPROVAL PROCESS Contents 1 Property Information...Page 2 2 Owner/Title Holder...Page 2 3 Designer... Page 2 4 Scrutiny Fees...
More informationProperty Services Design Standard Volume 5 Hydraulic Systems Issue
Design Standard Volume 5 Issue 7 2015 August 2015 RMIT University Design Standards Volume Five August 2015 Version Control This document will be updated and re-issues to reflect approved change to content,
More informationBrent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan
Brief Building Overview: 200 Minuteman Park stands as a 200,000 square foot Class A office building in Andover, Massachusetts, worth roughly $15,000,000. Although the building has a large square footage,
More informationPRESCRIPTIVE COMPLIANCE METHOD
CHAPTER PRESCRIPTIVE COMPLIANCE METHOD 3 SECTION 301 GENERAL 301.2 Building materials. Building materials shall comply with the requirements of this section. 301.2.1 Existing materials. Materials already
More informationGeneral Building Information
Software Module s Description Page 1 General Building Information BUILDING AREA AND HEIGHT - This module designed to determine the height and area of buildings on the basis of occupancy group classification
More informationCOOLIDGE SENIOR HIGH SCHOOL
INITIAL YEAR BUILT 1940 BUILDING AREA 271,300 SF CURRENT PROGRAM CAPACITY 1240 ENROLLMENT 2008 652 WARD 4 PROPOSED PROGRAM CAPACITY 1100 Site Plan COOLIDGE - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationRENTAL INSPECTION CHECKLIST. Helpful Definitions: Egress: the free and unobstructed access to the exterior of a habitable space.
CITY OF MANASSAS DEPARTMENT OF COMMUNITY DEVELOPMENT DEVELOPMENT SERVICES DIVISION 9027 Center Street, Room 201, Manassas, VA 20110 P.O. Box 560 Manassas, VA 20108 Phone: 703-257-8278 Fax: 703-257-5831
More informationCOMMERCIAL TENANT IMPROVEMENT PERMIT APPLICATION
COMMERCIAL TENANT IMPROVEMENT PERMIT APPLICATION OFFICIAL USE ONLY Date: Permit #: Received by: For Staff Use Only: OFD ELEC Planning SITE LOCATION Site Address: Tax Parcel Number: TYPE OF WORK Building
More informationFACILITY DESIGN PLAN FOR HARDING HALL RENOVATION AND ADDITION SOUTH DAKOTA STATE UNIVERSITY DATE: March 29, 2017
FACILITY DESIGN PLAN FOR HARDING HALL RENOVATION AND ADDITION SOUTH DAKOTA STATE UNIVERSITY DATE: March 29, 2017 SDSU requests approval of this Facility Design Plan for renovation and addition to Harding
More informationCODE ANALYSIS REPORT SECOND FLOOR
CODE ANALYSIS REPORT SECOND FLOOR 384 DWIGHT STREET HOLYOKE, MA Prepared by Dietz & Company Architects, Inc. 17 Hampden Street Springfield, MA March 2014 INTRODUCTION The following report is a preliminary
More informationLeaseholder Information Booklet
Leaseholder Information Booklet This information booklet provides details about the lease on your home. It will give you information about: What your lease means Your rights and responsibilities, as well
More informationArea The University s responsibilities The Occupier s responsibilities External Area Bicycle sheds
Responsibilities of University and Occupier of University Buildings (Schools) Below lists the University s responsibilities and your responsibilities as the Occupier of University buildings Area The University
More informationArea The University s responsibilities The Occupier s responsibilities External Area Bicycle sheds
Responsibilities of University and Occupier of University Buildings (Schools) Below lists the University s responsibilities and your responsibilities as the Occupier of University buildings Area The University
More informationOverall Existing Conditions Summary
September 12, 2002 Overall Executive Summary: The multi-use project on 250 West Street is a 7-story building with space for offices, retail, storage and parking. The project is a small part of the development
More informationScope of Work. Invitation to Bid Interior Renovation Works for the United Nations University, Macau (Phase 1) (UNUCS-ITB/001/2015)
Scope of Work Invitation to Bid Interior Renovation Works for the United Nations University, Macau (Phase 1) (UNUCS-ITB/001/2015) 1. Technical Specifications 1.1 The United Nations University Computing
More informationBuilding Codes and Ordinances ARC 227
Building Codes and Ordinances ARC 227 Week 6 Fire Resistive Construction 03.02.10 Instructor: Rick Staub, AIA Email: staub@pointonearchitects.com Phone: 860-434-7707 Fire Resistive Construction Passive
More information1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural %
8/11/ Building Rating System Percent Site: 1.0 Total 0 163 82% Building: 2.1 Building Exterior Elements 0 82 82% 2.2 Accessibility 0 92 92% 2.3 Structural 0 91 91% 2.4 Building Envelope 0 84 84% 2. Interior
More informationSimcoe County District School Board. 5yr Condition Assessment 2006/07 to 2010/11. Hillcrest PS (Barrie), 9205
5yr Condition Assessment 2006/07 to 2010/11 Construction Year Area 1951 3,813 Page 1 of 25 1. Architectural / Structural & Site Exec Summary Hillcrest Public School is a two storey structure of masonry
More informationSite Bldg Fiscal Yr System Sub-System. Verde Valley Site site 2014/15 Parking Paving. Verde Valley Site site 2014/15 Sidewalks
Site Bldg Fiscal Yr System Sub-System Site site 2014/15 Parking Paving Site site 2014/15 Sidewalks Skill Center L 2015/16 Architectural Partitions Site Site 2015/16 Parking Striping Arc Center M 2014/15
More informationTEXAS A&M ENGINEERING
TEXAS A&M ENGINEERING 312 Jack K. Williams Administration Building I 3126 TAMU I College Station, Texas 77843-3126 M. Katherine Banks, Ph.D., P.E. Vice Chancellor and Dean of Engineering Director, Texas
More informationBuilding Consent COMMERCIAL
Building Consent COMMERCIAL About this checklist This checklist is required for all BC applications. The applicant should identify if, and where, information is shown on the plan drawings. This is to help
More informationDraft Feasibility Study for the Expansion of Southeast Library
DC public Library KH KEAST & HOOD METROPOLITAN E N G I N E E R I N G I N C S H A P I RO-O BRIEN Draft Feasibility Study for the Expansion of Southeast Library Draft Submission: November 4, 2016 1 OVERVIEW
More informationPLANS REVIEW CRITERIA - COMMERCIAL BUILDINGS
PLANS REVIEW CRITERIA - COMMERCIAL BUILDINGS NOTE: Building Code compliance is the obligation of design professionals and/or contractors. Plan review and inspection guidelines are to be used to ensure
More informationCONSTRUCTION DOCUMENTS NECESSARY FOR PLAN REVIEW
2012 International Residential Code 2012 International Building Code 2012 International Fire Code 2014 NFPA 70 National Electrical Code 2012 International Existing Building Code 2012 International Plumbing
More informationDr. Edward Livingston Trudeau Building. 118 Main Street, Saranac Lake, NY. Building Systems Report. June 24, 2018
G2 Gordon + Gordon Architecture. LLC Dr. Edward Livingston Trudeau Building 118 Main Street, Saranac Lake, NY Building Systems Report June 24, 2018 Harry Gordon, FAIA 164 Otter Slide Road Saranac Lake
More informationINFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS
INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS November 2018 Contents 1. Introduction... 1 2. Ontario Building Code and Second Dwelling Units... 1 3. How Do I Make My Secondary Dwelling Unit
More informationEQUIVALENT INITIAL FIRE SAFETY ASSESSMENT
EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory 191-192 Baizid Bostami Road, Nasirabad Industrial Area, Chittagong 24 May 2014 The Alliance for Bangladesh Worker Safety Page 1/13 24 May 2014 Introduction
More informationNOTE: For construction other than new commercial or additions (renovations), only those areas below describing the scope of work will be applicable.
Applicant s Name: New Commercial - Commercial Additions Renovations Permit Plan Submittal Check List Applicant s Phone Number (s): Project Address: Project Type: _New Commercial or Commercial Addition
More informationC. Type of Selective Demolition Work: Demolition requires the selective removal and subsequent off-site disposal of:
02070 - SELECTIVE DEMOLITION PART 1 - GENERAL 1.1 STIPULATIONS A. The specifications sections " General Conditions of the Construction Contract ", "Special Conditions", and "Division 1 - General Requirements"
More informationFORM NO. Certificate of Stability for Continued Use of School
FORM NO. Certificate of Stability for Continued Use of School 1. Name of the Building: 2. Address: 3. Phone No. /Email: 4. Name of the Occupier of the Premises: 5. Use of Occupancy: 6. No. of floors: I
More informationBuilding Inspection Report
Building Inspection Report Sample Commercial Inspection Report Inspection Date: Prepared For: Prepared By: Professional Property Inspection Consultants 4857 Winterset Drive Columbus, OH 43220 (614) 459-5941
More informationPaulsboro Public Schools
BOND REFERENDUM PRESENTATION January 27, 2015 713 Creek Road Bellmawr, NJ 08031 Telephone (856) 396-6200 Facsimile (856) 396-6205 Please visit us on the web at www.garrisonarch.com 1 05-12-14 AGENDA NJDOE
More informationUniform Construction Code
Uniform Construction Code When the UCC Requires Permits and Inspections (A Zoning Certificate may be required even though the project does not require a UCC Building Permit.) As a general rule, the UCC
More informationEQUIVALENT INITIAL STRUCTURAL SAFETY ASSESSMENT
EQUIVALENT INITIAL STRUCTURAL SAFETY ASSESSMENT Factory C.D.A Plot No. C-49, Sagarika Road, Pahartaly, Chittagong Chittagong 18 May 2014 The Alliance for Bangladesh Worker Safety Page 1/12 18 May 2014
More informationSOUTH DAKOTA BOARD OF REGENTS. Budget and Finance ******************************************************************************
SOUTH DAKOTA BOARD OF REGENTS Budget and Finance AGENDA ITEM: 7 I DATE: May 9-11, 2017 ****************************************************************************** SUBJECT: SDSU Harding Hall Renovation
More informationHUGHES STADIUM CONTROLLED MAINTENANCE THROUGH 2020 Description of Projects on Facilities Management List September 18, 2014
HUGHES STADIUM CONTROLLED MAINTENANCE THROUGH 2020 Description of Projects on Facilities Management List September 18, 2014 1. Upgrade Video Security and Surveillance Systems - Replace with New a. Existing
More informationCONCURRENT ADVERTISEMENT FOR SUBCONTRACTOR PREQUALIFICATION AND BIDS
CONCURRENT ADVERTISEMENT FOR SUBCONTRACTOR PREQUALIFICATION AND BIDS (August 28, 2018) PIERCE HALL IMPROVEMENTS PROJECT NO. 950511-950532 UNIVERSITY OF CALIFORNIA, RIVERSIDE PREQUALIFICATION PROCESS ALL
More informationTOWN OF HAGUE GUIDELINES FOR PERMIT APPLICATION
TOWN OF HAGUE GUIDELINES FOR PERMIT APPLICATION Town of Hague Building Inspector: Dale Wagner Home #: 306-225-2265 Cell #: 306-241-4741 Fill all part of the permit application including the date and signature.
More informationDeKalb County School District/Stadiums Avondale Stadium Final School Assessment Report May 20, 2016
DeKalb County School District/Stadiums Avondale Stadium Final School Assessment Report May 20, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 4 School Condition Summary
More informationFacility Assessment Report, Montgomery Independent School District
NATATORIUM CAMPUS DATA NATATORIUM 22628 Hwy 105 West, Montgomery TX 77356 Year Built 2009 Approx. Total Square Footage Grades Served 30,420 n/a Current Enrollment n/a Building Levels 1 1 MASTER PLAN 2
More informationColumbia County Health Care Center Added Amenities
Columbia County Health Care Center Added Amenities Columbia County Board Meeting on January 16th, 2013 Building Exterior Added Amenities 1. Upgraded nail-base roofing insulation to 3 thickness on Center
More informationMultiProof -design compliance with Building Code clauses
MultiProof -design compliance with Building Code clauses Applicants and designers should use this table as a starting point for MultiProof. It lists the Building Code clauses, summarises what you need
More informationHow to Prepare Your LSE Report
LSE Rule Category Required Documentation Information Comments / Applicable Code Sections/ 10.1 Building Height Provide the Building height in Feet Provide the number of stories above grade Helpful Hints
More information