REQUEST FOR ARCHITECTURAL & ENGINEERING DESIGN SERVICES HANSEN RESIDENCE HALL RENOVATION PROJECT

Size: px
Start display at page:

Download "REQUEST FOR ARCHITECTURAL & ENGINEERING DESIGN SERVICES HANSEN RESIDENCE HALL RENOVATION PROJECT"

Transcription

1 University of Wisconsin-Stevens Point REQUEST FOR ARCHITECTURAL & ENGINEERING DESIGN SERVICES HANSEN RESIDENCE HALL RENOVATION PROJECT DSF # 09A2V January, 2009

2 TABLE OF CONTENTS PAGE Project Scope & Description 3 Project Budget 4 Project Schedule 4 University of Wisconsin Contacts 4 Websites 4 General Requirements 5 Site and Utilities 5 Architectural 6 Heating Venting & Air Conditioning 6 Electrical 7 Health & Safety 8 User Description of Functions & Requirements 8 Resident Rooms 8 Common Areas 9 Hall Director Apartment 10 Appendix Hansen Standard Resident Room Floor Plan 11 Hansen Resident Room-Former Lounge Room Floor Plan 12 Hansen Basement Floor Plan 13 Hansen 1 st Floor Plan 14 Hansen 2 nd, 3 rd & 4 th Floors Floor Plan 15 Campus Map 16 2

3 Project Scope and Description This project will renovate Hansen Residence Hall in the south DeBot quadrant at UW-Stevens Point. The project will roughly duplicate similar renovation work completed on one separate residence hall in summer 2008 and a second scheduled for summer This project for the third hall will have construction begin May 24, Hansen hall comprises a total of 53,917 GSF and 270 total beds, will receive significant renovations with room lighting upgrades, updates to closet side panels where needed, replacement of existing resident room slide-by windows, replacement of resident room and lower level wood doors with new wood doors. The steam radiant heat system will be replaced with a four pipe system that will incorporate hot water and future air conditioning and will allow for individual room control within a pre-set range. Domestic hot-water tank storage will be replaced with an instantaneous steam conversion unit and if needed smaller tank storage. ADA modifications shall include: a) removal of bathtubs in private baths on floors 2-4 to accommodate shower areas for wheelchair restricted residents/guests on all floors, b) lower-level gender specific toilet rooms to be made fully accessible and converted to be non-gender specific, c) a 5-stop elevator installed, d) an exterior ramp to the lobby level, and e) resident and public access rooms door handle hardware upgraded to a graspable lever style. Eleven resident rooms on various floors will be made fully ADA accessible. A fire sprinkler system will be installed throughout. Masonry block walls in resident rooms and resident floor corridors will receive a thin-coat plaster finish and paint. All resident room ceilings to be re-painted and the floor corridor ceilings will have the tectum removed and the surface painted. Carpeting in the resident rooms, main corridors, front lobby and various lower level room will be replaced. Replacement of T-Center floor-tile shall occur on floors 1-4. The Hall Director apartment will be provided with a private exterior entrance and small patio. The building will be connected to an emergency generator installed in Steiner Hall. Existing telephone and data connections will be relocated to the new exterior wall panels. The fire alarm system will be upgraded to current standards of addressable devices, synchronized strobes and emergency broadcasting capabilities. The building emergency lighting and power circuits will be connected to an electrical generator to be installed in Steiner Hall in The campus presently manages thirteen four story residence halls with beds for approximately 3100 students with a GSF of just over 700,000. These residential buildings are of a traditional style with double loaded corridors and centrally located group bathroom facilities on each floor built primarily in the 1960's. A renovation of similar scope took place in Baldwin hall in 2008 and will take place in Steiner Hall beginning May Baldwin and Steiner halls are neighboring halls located south and east of Steiner in the South DeBot quadrant. Baldwin and Steiner are of same building structure and bed capacity as Hansen hall. Hansen hall received a major renovation in 1993 which concentrated primarily on common areas such as the bathrooms where gang showers were converted to private shower stalls and worn restroom fixtures were replaced. Recycling chutes were added and kitchenettes installed on each floor. Voice and data wiring was updated to Category 5E. All fire alarm systems were upgraded but do not provide the current standard of addressable devices, synchronized strobes, or emergency voice broadcast capability. 3

4 The renovations should comply with DSF Sustainability Standards, Act 141 and Executive Order 145 issued in April EO 145 relates to conserving Wisconsin and the creation of high performance green building standards and the energy conservation for state facilities and operations based on the LEED Green building Rating System for existing buildings. Project Budget Construction $4,168,000 Contingency (7%) 292,000 A/E Design & other fees (8.1%) 334,600 DSF Management (4%) 178,900 Percent for Art 12,500 Total $4,986,000 Project Schedule A/E Selection February 2009 Design Report Completion July 2009 BOR/SBC Authority to Construct August % Documents Submitted for Review November 2009 Bid Opening January 2010 Start Construction May 2010 Substantial Completion and Occupancy August 2010 Final Completion November 2010 University of Wisconsin Contacts Title Name Phone Number Address Agency Representative UW-System Admin Maura Donnelly mdonnelly@uwsa.edu Campus Representative UWSP Dir. Facilities Planning Carl Rasmussen crasmuss@uwsp.edu Pertinent Websites UW-Stevens Point UW-Stevens Point Residential Living UW System Capital Planning & Budget City of Stevens Point Wis. Division of State Facilities

5 General Requirements: Site and Utilities Soil Conditions Four soil borings were done as part of the original Hansen hall construction in 1966 and are available on page 2 of project drawings for project # Cross section results generally show very dense red and gray granite at an elevation ten to sixteen feet below surface covered by varying levels of medium to coarse firm brown sand, topped by a two feet of loose medium sand and then, six inches of organic topsoil. The soil borings generally showed ground water at one to two feet above the dense red and gray granite. Zoning Requirements University of Wisconsin facility projects are required to conform with local zoning. There is nothing in the proposed project which will trigger the need for a zoning review. WEPA To comply with the Wisconsin Environmental Policy Act (WEPA) a Type III Environmental Action is required. This is a campus responsibility and will not necessitate any action on the part of the A/E team. City Water The Stevens Point Water Department supplies Buildings and outdoor systems with domestic water at a pressure of 65 lb. Underground piping is cast iron with all services adequate and in good repair. A 4-inch lateral with a 3-inch meter currently services the building and enters from the West side. The A/E team will need to analyze the requirements for sprinklering thus upgrades may be needed. A 6-inch city water main runs parallel to the building approximately 150 feet away. The need for an upgrade to capacity needs to be verified by the A/E team. The city main line on Isadore is 6 inch. Primary Electric The campus primary electric and signal underground conduit system runs parallel to and just to the east of the Isadore Street right of way boundary. This conduit duct bank installed in 1965 contains (10) 4 PVC conduits encased in a concrete envelope. Four of these conduits are dedicated to the primary power delivery system. Two of these conduits contain 15KV feeder cables sized at 1/0 and 4/0. The building appears to have adequate capacity to add the elevator component to the project, however the A/E team will need to verify. Signal Six of the ten conduits in the campus duct bank are dedicated to signal system delivery. These conduits contain four 32-strand and one 16-strand fiber optic data cables installed in 1993 along with multi-pair telephone and other low voltage cables. This signal conduit system is of adequate capacity to carry any additional signal conductors required to support additional space. 5

6 Architectural The addition of the elevator core and the new entry ramp must fit with in the context of the existing building. Building Envelope The building envelope is basically secure and in good repair. Bricks show no need for tuckpointing, expansion joints are caulked, doors, windows, and frames are solid and roof access assemblies and penetrations are functional and holding. ADA The residence halls are not compliant with current ADA requirements. A complete ADA analysis is required for the project. The current entrance to the building is by way of ramp with a gradient that exceeds ADA requirements. Upon entering the building, only the first floor is accessible to any wheelchair bound occupants or guests. Occupancy During Construction The building will be vacant during the 2010 summer break to allow construction occupancy of the entire facility. However, it is possible to continue elevator installation after fall occupancy if the work is outside the main living areas. Heating, Venting and Air-Conditioning The intention of this upgrade is to replace steam heating system and controls with a new hot water heating system 4 pipe system that can provide air conditioning when connected to a future source of chilled water. Existing make-up air and toilet exhaust systems were installed in Building steam service, pressure reducing station, and condensate return pumps are in good condition. Since they were installed the make-up air units have had chronic problems with coil freezing and low temperature shut downs. This problem should be addressed by the project. Campus Automation System The campus automation system is a Johnson Controls Metasys Extended Architecture Network. All new controls should be DDC and should be served and monitored by the campus system through the existing building network connection. Resident rooms shall have independent control within a pre-set range. 6

7 Plumbing Domestic Plumbing Systems The 1993 renovation of the bathrooms included providing private shower stalls replacing bathroom fixtures and plumbing systems. Fire Protection System The entire building should be served by a wet sprinkler system with concealed piping to the greatest extent possible. Piping must be concealed in common areas. Each floor should be provided with individual control valves. Vandal proof (security type) heads should be used on resident floors. Sprinkler heads in the lower level common areas will be protected with sprinkler head guards. A stand pipe will be added to the common stairways. No fire pump is required. Electrical Transformer Rating Transformer rating is 1000 KVA. Telecommunications The telecommunications system was updated in all residence halls during the summer months of Two 5e data jacks were installed on each side of the side of the room for internet capabilities of each resident. These jacks will be relocated to the new exterior wall panel. This will involve pulling existing cabling back to the lower-level, core drilling the floors, and re-pulling and terminating the wiring in the wall panel. Lower-level wiring will be routed via cable-tray. Fire Alarm Central Reporting A centralized, smoke detector and fire alarm system, as manufactured by Simplex, Model 4002 was installed as part of a comprehensive campus project in 1995, DSF Project 93A79. This project provided solid state electronic zoned display panels with voice evacuation capability. It is operated with low voltage cable and includes smoke detectors, pull stations, speaker/strobes and strobe annunciating devices. The system reports events to the campus security department located in the George Stein Building. The existing control panel will be upgraded to accept addressable devices and initiating devices (i.e. smoke/heat detectors, pull stations) and perform Emergency Broadcasting from University Protective Services such that Protective Services can address one hall or all halls in case of emergency.. Strobes will be replaced with synchronized strobes. The new sprinkler system to include flow and tamper switch alarms integrated into the alarm system. Public Address System The front desk is equipped with a PA system that allows for communication to all floors. A speaker box is located in each wing for communication from the main PA system located behind front desk. No work will be done to the PA system. 7

8 Health and Safety Asbestos Wisconsin Asbestos and Lead Abatement Management System identify residence hall areas as asbestos free with the exception of fire doors. All accessible ACM floor tile, mastic and pipe elbows were abated during the 1993 bathroom renovation upgrade. According to the WALMS report last revision 4/24/2003 asbestos containing 12x12 white pinhole ceiling tile and mastic exists in rooms 002,006, 007, 012, 030, 036, 038, 039, 138, 139, 140, and CO04, CO101, M001 and ACM 0-5 fittings on fiberglass line and ACM tank insulation only exists in room 015. Since the revision of 4/24/2003 Residential Living has removed all ACM fire doors in Hansen Hall. Lead The campus is not aware of any exposed lead containing products within the residence halls. User Description of Functions & Requirements Resident Rooms Occupants 2/room 160 ASF/room Total Rooms 135 A). Activity The resident rooms are fundamentally used as sleeping accommodations for 2 residents of primarily freshman or sophomore age. The secondary function of a resident room is as a small living environment which is conducive to studying and reading. The rooms are furnished with 2 beds, 2 desks with attached lighted hutch and a 5 drawer dresser set under a wall mount 24 x 27 mirror. There are 2 mirror fixtures installed above each mirror that are currently in excess of 30 years old and require a great deal of repeated repair, replacements and modifications. The rooms are equipped with 2 telecommunication ports one on each side of the room along with duplex outlets located slightly above the dresser tops on each side of the room along with quad plexes at the back of the room behind the desks. Residents are able to bring in lofts and/or bunks to suit their preferred room arrangement along with additional personal furnishings including, but not limited to soft seating, microwaves, refrigerators, floor and table lamps, entertainment centers and etc. Residents are able to configure and arrange their rooms as necessary during their stay. B.) Special Equipment or Services Lighting Inadequate lighting remains to be an issue within the resident rooms. Residents request more lighting and more versatile lighting options to suit their living style. Install new over-the-mirror fixtures (2 per room) Install a ceiling mount fixture in each room Unify switching to door frame for mirror and ceiling fixtures Energy efficient fluorescent only Housing and lens to be durable for a high use environment Aesthetic value of housing/casing to have residential appeal Ease of maintenance and/or lamp replacement by one facility repair worker Electronic ballasts 20 year life expectancy for housing 8

9 Thin-coat block walls Concrete block is to be thin coated to provide a flush residential wall finish. All existing ceiling tectum panels are to be removed with ceiling thin coated and painted. Slight texture Painted surface Door Knobs All resident room door handles are to be replaced with lever style handles to make rooms more accessible and user friendly. Locks must be compatible with current lock systems Doors Due to maintenance issues with existing doors, all resident room and existing wood public access room doors are to be replaced with new wood doors. Windows Replacement of resident room windows will aid in more efficient temperature control of each resident room. 3 Panel glazing Outside slider panels Screens Common Areas A). Activity The common areas include all corridors T-Centers, public use rooms in lower level, lobby, study lounge and floor kitchens. These spaces are a vital element of the residence hall as they encourage and promote community and programming efforts within the hall. The room sizes, use and finish vary to meet the needs of the residents and staff. All spaces are identified as high use that requires maintenance friendly, durable and aesthetically pleasing finishes. Thin-coat block walls & ceilings Concrete block is to be thin coated to provide a flush residential wall finish. All existing ceiling tectum panels are to be removed with ceiling thin coated and painted. Slight texture Painted surface Door Knobs All public access door handles are to be replaced with lever style handles to make rooms more accessible and user friendly. Locks must be compatible with current lock systems Doors Due to maintenance issues with existing doors, all resident room and existing wood public access room doors are to be replaced with new fire rated wood doors. 9

10 Elevator In addition to use as a personal transport the elevator will also be utilized for delivering materials, supplies, furnishings and/or heavy equipment between the floors. The elevator will serve as a much needed transport of recycling bins between floors by staff. The bins contain broken glass, paper, cardboard and other recyclable material with weights averaging anywhere between lbs each. Elevator to have 5 stops Finish to match or coordinate exterior brick 6 8 person capacity Bathrooms: Bathtubs located in the private baths on floors 2-4 are to be removed so to provide an accessible shower stall to residents housed in fully accessible resident rooms located on each floor. Toilet rooms on the lower level to be made ADA compliant and non-gender specific for purposes of providing an accessible toilet room on all floors. T-Center Tiles: Vinyl floor tiles in T-centers on floors 1-4 to be removed and replaced with stone as neighboring halls. Current tiles are hazardous and problematic for maintenance. Hall Director Apartment Secondary Entrance & Patio: A secondary private apartment entrance with patio is to be added to the building exterior at the Hall Director Living room location. The entrance and patio are to coordinate with the building envelope and are to provide the Hall Director with privacy, security and adequate space for outdoor leisure. 10

11 HANSEN STANDARD RESIDENT ROOM 11

12 HANSEN FORMER LOUNGE RESIDENT ROOM 12

13 HANSEN BASEMENT PLAN Please Note: Dimensions provided are close approximations and are not to be considered as exact measurements. Ceiling Height: 7-9 approx. 13

14 HANSEN FIRST FLOOR PLAN Plan not to scale. Ceiling Height: 7-9 approx. 14

15 HANSEN 2 4 FLOOR PLAN Plan not to scale. Ceiling Height: 7-9 approx. 15

16 HANSEN UW-SP Campus Map 16

A/E Design Deliverable Checklist

A/E Design Deliverable Checklist A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic

More information

REQUEST FOR ARCHITECTURAL AND ENGINEERING DESIGN SERVICES DRUMLIN DINING HALL RENOVATION. University of Wisconsin-Whitewater.

REQUEST FOR ARCHITECTURAL AND ENGINEERING DESIGN SERVICES DRUMLIN DINING HALL RENOVATION. University of Wisconsin-Whitewater. REQUEST FOR ARCHITECTURAL AND ENGINEERING DESIGN SERVICES DRUMLIN DINING HALL RENOVATION University of Wisconsin-Whitewater March 2008 Project No. 08B21 TABLE OF CONTENTS PAGE Table of Contents... 2 Project

More information

A/E Design Deliverable Checklist

A/E Design Deliverable Checklist A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic

More information

Residential Outline Specifications

Residential Outline Specifications Residential Outline Specifications September 2014 1. General a. Site i. Direct elevator access from parkade to residential floors ii. Separate commercial elevator access from parkade to 10th Street NW

More information

FACILITY DESIGN PLAN FOR HARDING HALL RENOVATION AND ADDITION SOUTH DAKOTA STATE UNIVERSITY DATE: March 29, 2017

FACILITY DESIGN PLAN FOR HARDING HALL RENOVATION AND ADDITION SOUTH DAKOTA STATE UNIVERSITY DATE: March 29, 2017 FACILITY DESIGN PLAN FOR HARDING HALL RENOVATION AND ADDITION SOUTH DAKOTA STATE UNIVERSITY DATE: March 29, 2017 SDSU requests approval of this Facility Design Plan for renovation and addition to Harding

More information

Timberglen Recreation Center Summary

Timberglen Recreation Center Summary Timberglen Recreation Center Summary Address Building Purpose 3810 Timberglen Road Dallas, TX 75287 Recreation Center Original Year of Construction 2003 Building Area 15,000 SF Inspection Date August 2,

More information

APPLICATION FOR FINISHED BASEMENT PERMIT

APPLICATION FOR FINISHED BASEMENT PERMIT APPLICATION FOR FINISHED BASEMENT PERMIT REAL ESTATE TAX I.D. #: - - _ - _ 7607 W College Drive Ph: (708) 361-1804 Fax: (708) 923-7112 building@palosheights.org APPLICANTS: COMPLETE ALL ITEMS AND SUBMIT

More information

HILLSIDE ELEMENTARY SCHOOL. Overview: Livingston School District Hillside Elementary School

HILLSIDE ELEMENTARY SCHOOL. Overview: Livingston School District Hillside Elementary School HILLSIDE ELEMENTARY SCHOOL Overview: The is located at 98 Belmont Drive and consists of a two-story building which has had a number of additions added to it over the years, the latest of which was a two-story

More information

VILLAGE OF MARATHON CITY MARATHON COUNTY WISCONSIN

VILLAGE OF MARATHON CITY MARATHON COUNTY WISCONSIN VILLAGE OF MARATHON CITY MARATHON COUNTY WISCONSIN Instructions to Contractors The Village of Marathon City will be accepting proposals at the Marathon City Village Hall, 311 Walnut Street, PO Box 487

More information

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural %

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural % 8/11/ Building Rating System Percent Site: 1.0 Total 0 163 82% Building: 2.1 Building Exterior Elements 0 82 82% 2.2 Accessibility 0 92 92% 2.3 Structural 0 91 91% 2.4 Building Envelope 0 84 84% 2. Interior

More information

SANDTOWN CROSSING PROFESSIONAL OFFICE PARK Atlanta, GA

SANDTOWN CROSSING PROFESSIONAL OFFICE PARK Atlanta, GA Atlanta, GA LOCATED AT CAMP CREEK PARKWAY AND CAMPBELLTON ROAD For Sale or Lease Single units start at 1,176sf and can be combined to exact specification Custom Designed Medical and Professional finishes

More information

Evansville Public Schools. Facility Assessment Report January 28, 2 , General Building Data

Evansville Public Schools. Facility Assessment Report January 28, 2 , General Building Data Evansville Public Schools Facility Assessment Report January 28, 2, 2013 SGN/Wendel Architects, Design Tree Engineering and R.A. Morton Construction Managers were retained by the Evansville Public School

More information

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents DIVISION 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN Contents 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION 13 00 60 LIST OF FIGURES... 6 Page 1 of 6 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN 1. General

More information

Delta Gamma Sorority Renovation Budget Scope 3/7/2018

Delta Gamma Sorority Renovation Budget Scope 3/7/2018 Delta Gamma Sorority Renovation Budget Scope 3/7/2018 PROJECT: Barbara Cerni Delta Gamma Sorority Tallahassee, Fla. This scope is based on the 50% Construction Documents drawn by BKJ Architecture dated

More information

CONTRACT DOCUMENTS REVIEW PACKAGE CHECKLIST

CONTRACT DOCUMENTS REVIEW PACKAGE CHECKLIST CONTRACT DOCUMENTS REVIEW PACKAGE CHECKLIST Check off each item that is included within the submitted Contract Documents Review Package. Provide a written explanation for any omissions. The following items,

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION Section 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Invitation

More information

Deficiency ID Qty UoM Priority. Concrete Walks Are Damaged And Require Replacement ,000 SF 3

Deficiency ID Qty UoM Priority. Concrete Walks Are Damaged And Require Replacement ,000 SF 3 School and Site Level Deficiencies Site Concrete Walks Are Damaged And Require Replacement 5539 4,000 SF 3 Bus drop-off area does not have a canopy. 14005 250 LF 5 Paved Play Requires Recoating And Resurfacing

More information

Columbia County Health Care Center Added Amenities

Columbia County Health Care Center Added Amenities Columbia County Health Care Center Added Amenities Columbia County Board Meeting on January 16th, 2013 Building Exterior Added Amenities 1. Upgraded nail-base roofing insulation to 3 thickness on Center

More information

CITY OF ANDERSON BUILDING AND CODES 601 South Main Street

CITY OF ANDERSON BUILDING AND CODES 601 South Main Street CITY OF ANDERSON BUILDING AND CODES 601 South Main Street Plan Review Notes (STREET ADDRESS) ANDERSON, SC Plan Review Number: Building Plans prepared by: Plans Signed by: Project Name: Plans Received:

More information

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION LIST OF FIGURES...

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION LIST OF FIGURES... DIVISION 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN Contents 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION 13 00 60 LIST OF FIGURES... 6 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN 1. General Requirements

More information

PRESENTATION TO THE FARMINGTON CITY COUNCIL FOR THE PROPOSED FARMINGTON CIVIC CENTER EXPANSION SEPTEMBER 20, 2016

PRESENTATION TO THE FARMINGTON CITY COUNCIL FOR THE PROPOSED FARMINGTON CIVIC CENTER EXPANSION SEPTEMBER 20, 2016 PRESENTATION TO THE FARMINGTON CITY COUNCIL FOR THE PROPOSED FARMINGTON CIVIC CENTER EXPANSION SEPTEMBER 20, 2016 WORK LEGEND OVERALL WORK TO BOTH BUILDINGS 1 2 3 4 Existing corridors will receive new

More information

FRANKLIN VILLAGE APARTMENTS Building I Franklin Street Morristown, NJ Block: 3901 Lots: 4,5,6

FRANKLIN VILLAGE APARTMENTS Building I Franklin Street Morristown, NJ Block: 3901 Lots: 4,5,6 PROJECT MANUAL for: FRANKLIN VILLAGE APARTMENTS Building I Morristown, NJ 07960 Block: 3901 Lots: 4,5,6 Owner: Atlantic Health Investment Corp. 200 American Road Morris Plains, NJ 07950 Architect NETTA

More information

Inspection Report. Property Address:

Inspection Report. Property Address: Inspection Report provided by: Safe Side Home Inspection Inspector: Corey Stuart TN License # 778 434 Margaret Circle McMinnville, TN 37110 safesideinspection@blomand.net Property Address: 1234 Anywhere

More information

INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS

INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS November 2018 Contents 1. Introduction... 1 2. Ontario Building Code and Second Dwelling Units... 1 3. How Do I Make My Secondary Dwelling Unit

More information

SPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM)

SPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM) SPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM) Construction Criteria The unit costs for the Physical Fitness Center (Exercise Room) space type are based on the construction quality and design features in

More information

SOUTH DAKOTA BOARD OF REGENTS. Budget and Finance ******************************************************************************

SOUTH DAKOTA BOARD OF REGENTS. Budget and Finance ****************************************************************************** SOUTH DAKOTA BOARD OF REGENTS Budget and Finance AGENDA ITEM: 7 I DATE: May 9-11, 2017 ****************************************************************************** SUBJECT: SDSU Harding Hall Renovation

More information

1 data PIC location (with 2 ports) typically asf for multiple staff members

1 data PIC location (with 2 ports) typically asf for multiple staff members 1 Introduction 1.1 In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a utility. It should be assumed that all new

More information

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural %

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural % BartelsRode Gymnasium 8/11/ Building Rating System Percent Site: 1.0 Total 0 13 77% Building: 2.1 Building Exterior Elements 0 8 8% 2.2 Accessibility 0 74 74% 2.3 Structural 0 76 76% 2.4 Building Envelope

More information

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS INDIANA UNIVERSITY BIDDING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 (REVISED 2005) MINORITY,

More information

Funding Source. Ranking

Funding Source. Ranking Military Affairs Projects Summary ($ in thousands) Project Title Priority Ranking Funding Source Project Requests for State Funds 2016 2018 2020 West St. Paul 1 GO $ 4,500 $ 0 $ 0 St Cloud Facility Batch

More information

Franklin Hall Renovation TABLE OF Document Indiana University Bloomington

Franklin Hall Renovation TABLE OF Document Indiana University Bloomington VPS Project No. 2013022.00 Page 1 SPECIFICATIONS VOLUME I INTRODUCTORY INFORMATION Document 000010 - Table of Contents... 6 Document 000011 - Certification and Seals... 2 Document 000012 - Project Directory...

More information

Pembridge The Country Club Collection TOWNHOMES AT CRYSTAL SPRINGS

Pembridge The Country Club Collection TOWNHOMES AT CRYSTAL SPRINGS Pembridge The Country Club Collection TOWNHOMES AT CRYSTAL SPRINGS STANDARD FEATURES LIST Foundation Concrete walls 4 concrete floor slab Interior basement unfinished Standard nine foot foundation walls

More information

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets. ALLIANT ENERGY CENTER PAVILIONS Project No. 2013 027 SECTION 27 05 28 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities Division 1 Requirements Design and Construction Quality Campus Master Plans Texas Tech University System Operating and Building Maintenance Project Administration Historically Underutilized Business (HUB)

More information

Deficiency ID Qty UoM Priority. K Play Area Requires Impact Resistant Material Ea. 2

Deficiency ID Qty UoM Priority. K Play Area Requires Impact Resistant Material Ea. 2 School and Site Level Deficiencies Site K Play Area Requires Impact Resistant Material 1320 1 Ea. 2 Exterior Basketball Goals Are Damaged And Require Replacement 1322 1 Ea. 4 Bus drop-off area does not

More information

COMMERCIAL TENANT IMPROVEMENT PERMIT APPLICATION

COMMERCIAL TENANT IMPROVEMENT PERMIT APPLICATION COMMERCIAL TENANT IMPROVEMENT PERMIT APPLICATION OFFICIAL USE ONLY Date: Permit #: Received by: For Staff Use Only: OFD ELEC Planning SITE LOCATION Site Address: Tax Parcel Number: TYPE OF WORK Building

More information

FACILITY COMPONENTS - MIDDLE SCHOOL

FACILITY COMPONENTS - MIDDLE SCHOOL SITE AREAS Parking and Access - Buses 2.0 2.0 0.30 Parking and Access - Serv. / Delivery 3.0 1.0 0.22 Parking and Access - Staff 4.0 3.0 0.89 Parking and Access - Visitors 1.0 3.0 0.22 Four fewer stalls

More information

PROFESSIONAL DESIGN MANUAL INDEX

PROFESSIONAL DESIGN MANUAL INDEX PROFESSIONAL DESIGN MANUAL INDEX DIVISION A--GENERAL PROJECT REQUIREMENTS... A2-A15 A.1 INTRODUCTION... A-2 A.2 CODES COMPLIANCE (VERIFY CITY REQUIREMENTS)... A-5 A.3 SPECIAL SUBSURFACE AND LAND CONDITIONS...

More information

SANDTOWN CROSSING PROFESSIONAL OFFICE PARK Atlanta, GA

SANDTOWN CROSSING PROFESSIONAL OFFICE PARK Atlanta, GA Atlanta, GA LOCATED AT CAMP CREEK PARKWAY AND CAMPBELLTON ROAD For Sale or Lease Single units start at 1,176sf and can be combined to exact specification Custom Designed Medical and Professional finishes

More information

Whitley Shower Locker Toilet Facilities

Whitley Shower Locker Toilet Facilities Whitley Manufacturing Co., Inc. 201 W. First Street S. Whitley, IN 46787 Phone (260) 723-5131 Sales Fax (260) 723-6396 whitley@whitleyman.com Building Type Building Code Whitley Shower Locker Toilet Facilities

More information

Appendix J - Custom Uniformat for EDU Migration

Appendix J - Custom Uniformat for EDU Migration Appendix J - Custom Uniformat for EDU Migration Nr. MTC Uniformat for VFA.facility Life (Years) Weight (1-100) Out of Scope Cost Y/N 1 A Substructure 150 N 2 A10 Foundations 150 N 3 A1010 Standard Foundations

More information

Communications Page 1 of 9

Communications Page 1 of 9 Page 1 of 9 Last Update: April 23 rd, 2014 Introduction Design In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a

More information

Facilities Feasibility Study Frederick Douglass HS Condition Assessment

Facilities Feasibility Study Frederick Douglass HS Condition Assessment Summary of Findings The Frederick Douglass HS Facility located at 2301 Gwynns Falls Parkway in Baltimore, Maryland, was built in 1927. It comprises 194,249 gross square feet. The total current deficiencies

More information

TABLE OF CONTENTS. (Δ = Rev 06/08)

TABLE OF CONTENTS. (Δ = Rev 06/08) TABLE OF CONTENTS (Δ = Rev 06/08) INTRODUCTION REQUEST FOR REVISION FORMS TAB A TABLE OF CONTENTS TAB B PROCEDURES B-9 Record Drawings B-10 Variance Procedure B-11 Surface Water Procedures (New Section)

More information

Carter's Oshkosh (SIS) # The Center at Pearland Parkway - Pearland, TX Scope Of Work / Bid Qualifications

Carter's Oshkosh (SIS) # The Center at Pearland Parkway - Pearland, TX Scope Of Work / Bid Qualifications Carter's Oshkosh (SIS) #1185 - The Center at Pearland Parkway - Pearland, TX 77581 - Scope Of Work / Bid Qualifications Please fill out the blanks associated with your trade scope or work with the words

More information

Walnut Creek Mutual Seventy

Walnut Creek Mutual Seventy Appliances: Dishwashers, Refrigerators, Disposals, Ranges, Ovens, Vents, Hoods, Fireplaces, Washing Machines, Dryers, etc. All appliances are the owner s property; all maintenance and repair is the owner

More information

FRAMING INSPECTION GENERAL

FRAMING INSPECTION GENERAL FRAMING INSPECTION GENERAL 20 FRAMING INSPECTION GENERAL Tips Check habitable rooms for minimum light, ventilation and sanitation requirements. Check that stair framing meets headroom, width, and rise

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Notice to Bidders

More information

RAYMOND EDUCATION CAMPUS

RAYMOND EDUCATION CAMPUS INITIAL YEAR BUILT 1924 BUILDING AREA 73,600 SF CURRENT PROGRAM CAPACITY 479 ENROLLMENT 2008 302 WARD 1 PROPOSED PROGRAM CAPACITY 600 Site Plan RAYMOND - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

NARRATIVE REPORT 1.0 BUILDING INFORMATION 2.0 ASBESTOS SURVEY INFORMATION

NARRATIVE REPORT 1.0 BUILDING INFORMATION 2.0 ASBESTOS SURVEY INFORMATION NARRATIVE REPORT 1.0 BUILDING INFORMATION Bentson Bunker Fieldhouse was originally constructed in 1931; the building has had several renovations, notably, a 1976-1980 multi-phase renovation throughout

More information

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural %

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural % 8/11/ Building Rating System Percent Site: 1.0 Total 0 9 8 Building: 2.1 Building Exterior Elements 0 82 82% 2.2 Accessibility 0 82 82% 2.3 Structural 0 7 7% 2.4 Building Envelope 0 47 47% 2. Interior

More information

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS 1 Introduction 1.1 In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a utility. It should be assumed that all new

More information

Collins Middle School

Collins Middle School Contents Collins Middle School...2 General comments, campus capacity, and student demographics:...2 1.0 School Site...4 2.0 Building Systems and Components...5 3.0 Building Safety and Security...19 4.0

More information

COOLIDGE SENIOR HIGH SCHOOL

COOLIDGE SENIOR HIGH SCHOOL INITIAL YEAR BUILT 1940 BUILDING AREA 271,300 SF CURRENT PROGRAM CAPACITY 1240 ENROLLMENT 2008 652 WARD 4 PROPOSED PROGRAM CAPACITY 1100 Site Plan COOLIDGE - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

How to Prepare Your LSE Report

How to Prepare Your LSE Report LSE Rule Category Required Documentation Information Comments / Applicable Code Sections/ 10.1 Building Height Provide the Building height in Feet Provide the number of stories above grade Helpful Hints

More information

SUMMARY 1234 Main St.Loudon TN Buyer Name 08/28/2018 9:00AM

SUMMARY 1234 Main St.Loudon TN Buyer Name 08/28/2018 9:00AM SUMMARY 1234 Main St.Loudon TN 37774 Buyer Name 08/28/2018 9:00AM Dusty Jameson TN Home Inspector License #00123, TN WDI License #104158 Inspector Cluseau's Home Inspection Service 865-691-6158 dustyjameson@gmail.com

More information

BELLA PALERMO HOMEOWNERS ASSOCIATION MAINTENANCE MATRIX DIVISION OF MAINTENANCE AND REPAIR RESPONSIBILITY

BELLA PALERMO HOMEOWNERS ASSOCIATION MAINTENANCE MATRIX DIVISION OF MAINTENANCE AND REPAIR RESPONSIBILITY BELLA PALERMO HOMEOWNERS ASSOCIATION MAINTENANCE MATRIX DIVISION OF MAINTENANCE AND REPAIR RESPONSIBILITY The list below contains those building elements most commonly found in buildings found in a condominium

More information

TABLE OF CONTENTS. (Δ = Rev 11/15) Update #7

TABLE OF CONTENTS. (Δ = Rev 11/15) Update #7 TABLE OF CONTENTS ( = Rev 11/15) Update #7 INTRODUCTION REQUEST FOR REVISION FORMS TAB A TABLE OF CONTENTS TAB B PROCEDURES B-4 International Suite of Codes (New) B-9 Record Drawings B-10 Variance Procedure

More information

TOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ FAX

TOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ FAX TOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ 08014 856-467-3626--- FAX 856-467-9260 Application for Certificate of Occupancy for Change of Occupancy Pursuant to Chapter 119 of the Township

More information

TABLE OF CONTENTS. (Δ = Rev 04/17) Update #8

TABLE OF CONTENTS. (Δ = Rev 04/17) Update #8 TABLE OF CONTENTS ( = Rev 04/17) Update #8 INTRODUCTION REQUEST FOR REVISION FORMS TAB A TABLE OF CONTENTS TAB B PROCEDURES B-4 International Suite of Codes B-9 As-Builts and Record Drawings B-10 Variance

More information

REHABILITATION STANDARDS CHECKLIST

REHABILITATION STANDARDS CHECKLIST Project Name Date Built Date Last Rehabilitated (If applicable) EXTERIORS REHABILITATION STANDARDS CHECKLIST ROOF Age (Yrs) Poor Fair Good Excellent Roof /Pitch/Flat # of Layers Substrate Material Insulation

More information

TABLE OF CONTENTS Public Safety Building

TABLE OF CONTENTS Public Safety Building DOCUMENT 00 01 10 - TABLE OF CONTENTS VOLUME I DIVISION 00 PROCUREMENT AND CONTRACTING REQUIREMENTS 00 01 10 Table of Contents 00 31 32 Geotechnical Data DIVISION 01 GENERAL REQUIREMENTS 01 10 00 Summary

More information

Exhibit A Library Shell Construction

Exhibit A Library Shell Construction Exhibit A Library Shell Construction Library Component Building Requirements Approximately 15,000-17,000 square feet plus 900 square feet for mechanical room and additional space on roof for installation

More information

SECTION OUTLET, PULL, AND JUNCTION BOXES

SECTION OUTLET, PULL, AND JUNCTION BOXES SECTION 16131 OUTLET, PULL, AND JUNCTION BOXES PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 09900 - Painting. 2. 16112 - Raceways and Conduits. 1.02 SYSTEM DESCRIPTION A. Performance Requirements:

More information

CONCURRENT ADVERTISEMENT FOR SUBCONTRACTOR PREQUALIFICATION AND BIDS

CONCURRENT ADVERTISEMENT FOR SUBCONTRACTOR PREQUALIFICATION AND BIDS CONCURRENT ADVERTISEMENT FOR SUBCONTRACTOR PREQUALIFICATION AND BIDS (August 28, 2018) PIERCE HALL IMPROVEMENTS PROJECT NO. 950511-950532 UNIVERSITY OF CALIFORNIA, RIVERSIDE PREQUALIFICATION PROCESS ALL

More information

BELLA PALERMO HOMEOWNERS ASSOCIATION MAINTENANCE MATRIX DIVISION OF MAINTENANCE AND REPAIR RESPONSIBILITY

BELLA PALERMO HOMEOWNERS ASSOCIATION MAINTENANCE MATRIX DIVISION OF MAINTENANCE AND REPAIR RESPONSIBILITY BELLA PALERMO HOMEOWNERS ASSOCIATION MAINTENANCE MATRIX DIVISION OF MAINTENANCE AND REPAIR RESPONSIBILITY The list below contains those building elements most commonly found in buildings found in a condominium

More information

Work Write Up / Specification of Repairs HUD DIVISION 1. MASONRY HUD DIVISION 2. SIDING. Toll Free

Work Write Up / Specification of Repairs HUD DIVISION 1. MASONRY HUD DIVISION 2. SIDING. Toll Free / / Paperport 2000 official estimating report Work Write Up / Specification of Repairs Toll Free 1-877-932-7177 Clients Name. GREAT CLIENT Property Address. NUMBER ONE GOOD ROAD METRO, VA 20000 Primary

More information

The Compass ( 270 Lisgar Street, Brighton ) Features General Site Work 1. Construction Drawings 2. Building, Plumbing Electrical and Entrance Permits

The Compass ( 270 Lisgar Street, Brighton ) Features General Site Work 1. Construction Drawings 2. Building, Plumbing Electrical and Entrance Permits The Compass ( 270 Lisgar Street, Brighton ) Features General Site Work 1. Construction Drawings 2. Building, Plumbing Electrical and Entrance Permits 3. Development and Septic Fees 4. Tarion New Home Warranty

More information

Z & C Construction, Inc. Subdivision:

Z & C Construction, Inc. Subdivision: : Buyer(s): Address: Lot: Block: Model: Subdivision: A. Foundations Unfinished basement or crawlspace included per buyer selection (extra fees may apply) Engineered concrete foundation Perimeter drainage

More information

3. 21st Century Learning A. Districtwide Flexible Learning $600,000 Subtotal $600,000

3. 21st Century Learning A. Districtwide Flexible Learning $600,000 Subtotal $600,000 1. Safety and Security A. Additional Cameras District Wide $382,000 B. Interior Locks Upgrades $300,000 C. Tilden Entrance Upgrades $50,000 D. Door and Glass Improvements $500,000 E. Alert Systems $800,000

More information

Wallingford, CT. Project Manager: Karen Charest Ext. 233

Wallingford, CT. Project Manager: Karen Charest Ext. 233 Wallingford, CT Project Manager: Karen Charest 203-265-1821 Ext. 233 THE MARTHA 1 MODEL at Simpson Village Martha 1 Model Total The rendering and floor plans substantially represent the model depicted.

More information

HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW

HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW 27 September 2007 prepared by: J. CHRIS EVANS ARCHITECT 3220 E. Terra Alta Blvd. No. 9 Tucson, Arizona 85716 520.319.8835 evansarch@hotmail.com

More information

St. Jude Children s Hospital cgmp Facility Memphis, TN

St. Jude Children s Hospital cgmp Facility Memphis, TN St. Jude Children s Hospital cgmp Facility Memphis, TN CM Option Consultant TBD September 12, 2002 Overall Existing Conditions Summary Executive Summary This Overall Conditions Summary is a fairly comprehensive

More information

TRIPLEX BUILDING 3 TOWNHOUSE UNITS

TRIPLEX BUILDING 3 TOWNHOUSE UNITS 743 MAIN STREET TEWKSBURY, MA TRIPLEX BUILDING 3 TOWNHOUSE UNITS 2 BR, 2.5 BA page 2 FIVEPLEX BUILDING 5 TOWNHOUSE UNITS 2 BR, 2.5 BA page 3 MIXED BUILDING 2 GARDEN STYLE UNITS 2 BR, 2 BA page 4 3 COMMERCIAL

More information

Overbrook Theater / Fruenthal Foundation Art Center. 1.0 Total Points % 2.1 Building Exterior Elements %

Overbrook Theater / Fruenthal Foundation Art Center. 1.0 Total Points % 2.1 Building Exterior Elements % 8/13/ Building Rating System Percent Site: 1.0 Total 0 9 8 Building: 2.1 Building Exterior Elements 0 64 64% 2.2 Accessibility 0 66 66% 2.3 Structural 0 77 77% 2.4 Building Envelope 0 4 4% 2. Interior

More information

A UCC Building permit is not required for the exceptions listed below for COMMERCIAL application: (403.42): Building construction for the following:

A UCC Building permit is not required for the exceptions listed below for COMMERCIAL application: (403.42): Building construction for the following: New buildings or renovations to existing buildings for which an application for a permit was made to the Department or a municipality before April 9, 2004. New buildings or renovations to existing buildings

More information

TOWN OF HAGUE GUIDELINES FOR PERMIT APPLICATION

TOWN OF HAGUE GUIDELINES FOR PERMIT APPLICATION TOWN OF HAGUE GUIDELINES FOR PERMIT APPLICATION Town of Hague Building Inspector: Dale Wagner Home #: 306-225-2265 Cell #: 306-241-4741 Fill all part of the permit application including the date and signature.

More information

Dr. Edward Livingston Trudeau Building. 118 Main Street, Saranac Lake, NY. Building Systems Report. June 24, 2018

Dr. Edward Livingston Trudeau Building. 118 Main Street, Saranac Lake, NY. Building Systems Report. June 24, 2018 G2 Gordon + Gordon Architecture. LLC Dr. Edward Livingston Trudeau Building 118 Main Street, Saranac Lake, NY Building Systems Report June 24, 2018 Harry Gordon, FAIA 164 Otter Slide Road Saranac Lake

More information

HERITAGE MIDDLE SCHOOL. Overview: Livingston School District Heritage Middle School

HERITAGE MIDDLE SCHOOL. Overview: Livingston School District Heritage Middle School HERITAGE MIDDLE SCHOOL Overview: The is located at 20 Foxcroft Drive and consists of a three-story building with Three-Story Classroom and Multi-Purpose Room Additions completed in 2002. The building has

More information

UCC Permit Application Procedures

UCC Permit Application Procedures How do I apply for a permit? UCC Permit Application Procedures 1. Please complete the CodeMaster Pan Review Application 2. Please provide the scope of work description and/or construction documents/plans.

More information

FACILITY DESIGN PLAN FOR INDOOR PRACTICE AND HUMAN PERFORMANCE FACILITY SOUTH DAKOTA STATE UNIVERSITY

FACILITY DESIGN PLAN FOR INDOOR PRACTICE AND HUMAN PERFORMANCE FACILITY SOUTH DAKOTA STATE UNIVERSITY FACILITY DESIGN PLAN FOR INDOOR PRACTICE AND HUMAN PERFORMANCE FACILITY SOUTH DAKOTA STATE UNIVERSITY DATE: November 20, 2012 SDSU requests approval of this Facility Design Plan to continue planning the

More information

Lake Highlands North Recreation Center Summary

Lake Highlands North Recreation Center Summary Lake Highlands North Recreation Center Summary Address Building Purpose 9940 White Rock Trail Dallas, TX 75238 Recreation Center Original Year of Construction 1971 Building Area 33,036 SF Inspection Date

More information

NC State University Design and Construction Guidelines Division 00 Planning & Design Space Planning

NC State University Design and Construction Guidelines Division 00 Planning & Design Space Planning 1.0 Purpose A. These guidelines provide requirements for the Designer and Contractor to follow related to space planning. 2.0 General Requirements A. Single Occupant Toilet Room Each new or renovated building

More information

BUILDING CONDITION ASSESSMENT

BUILDING CONDITION ASSESSMENT BUILDING CONDITION ASSESSMENT 500 MacNab Street North, Hamilton ID. No.: EBE 16-0153 Prepared for Corporation By Effective Building Engineering Ltd.. Final Report: July 2016 Project No. 16-0153 Table of

More information

Asbestos Abatement: See Asbestos Survey and Specification. Abatement for seven (7) onebedroom units floors 7-13.

Asbestos Abatement: See Asbestos Survey and Specification. Abatement for seven (7) onebedroom units floors 7-13. Portage Trail 232/223(f) Refinance and 4% LIHTC Project 45 Cathedral Lane, Cuyahoga Falls, Ohio Scope of work January 19, 2016 Project Summary: Portage Trail is a 13 story 183 unit circular apartment building

More information

CM ASSIGNMENT OF TEMPORARY FACILITIES see included IU Project Site Requirements

CM ASSIGNMENT OF TEMPORARY FACILITIES see included IU Project Site Requirements SECTION A CM INSTRUCTIONS TO BIDDERS SECTION B BID CATEGORY DESCRIPTIONS & BID FORMS BC-07: Building HVAC and Plumbing BC-08: Building Electric BC-09: General Trades BC-10: Masonry BC-11: Precast Structural

More information

LUFacilities Policy Service Level Agreement v1.1

LUFacilities Policy Service Level Agreement v1.1 PURPOSE The Service Level Agreement (SLA) for University provides a detailed list of services offered by the LU Department. The SLA identifies which services are funded by the approved Lehigh University

More information

LASALLE - BACKUS EDUCATION CAMPUS

LASALLE - BACKUS EDUCATION CAMPUS INITIAL YEAR BUILT 1957 BUILDING AREA 63,000 SF CURRENT PROGRAM CAPACITY 406 ENROLLMENT 2008 349 WARD 4 PROPOSED PROGRAM CAPACITY 425 Site Plan LASALLE - BACKUS - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

SEATON ELEMENTARY SCHOOL

SEATON ELEMENTARY SCHOOL INITIAL YEAR BUILT 1969 BUILDING AREA 65,000 SF CURRENT PROGRAM CAPACITY 428 ENROLLMENT 2008 280 WARD 2 PROPOSED PROGRAM CAPACITY 325 Site Plan SEATON - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5

More information

Welcome Center, New Student Services, and Career and Employment Services

Welcome Center, New Student Services, and Career and Employment Services Architectural Program Welcome Center, New Student Services, and Career and Employment Services East Memorial Stadium Renovation May 2014 Prepared By Table of Contents Introduction.... 1 Competitive Market....

More information

CTC MEETING #25 CHILD WINDOW SAFETY REPORT

CTC MEETING #25 CHILD WINDOW SAFETY REPORT CTC MEETING #25 CHILD WINDOW SAFETY REPORT The Child Window Safety SG has not met following the 2012 Final Action Hearing. Group B activities did not necessitate SG meetings as the activity will be limited

More information

NARRATIVE REPORT 1.0 BUILDING INFORMATION 2.0 ASBESTOS SURVEY INFORMATION

NARRATIVE REPORT 1.0 BUILDING INFORMATION 2.0 ASBESTOS SURVEY INFORMATION NARRATIVE REPORT 1.0 BUILDING INFORMATION Putnam Hall was originally constructed in 1905; there appears to have been several renovations, notably, a 1982 renovation throughout the basement and a 1983 renovation

More information

Helms Builders, Inc.

Helms Builders, Inc. Helms Builders, Inc. President 9669 Fred Rd. Steve Helms Stanfield NC. 28163 Locust Town Center Lot #31, 261 Harrison Ln. Locust NC. Scope of Construction & General Conditions: Building Contract contingent

More information

RENTAL INSPECTION CHECKLIST. Helpful Definitions: Egress: the free and unobstructed access to the exterior of a habitable space.

RENTAL INSPECTION CHECKLIST. Helpful Definitions: Egress: the free and unobstructed access to the exterior of a habitable space. CITY OF MANASSAS DEPARTMENT OF COMMUNITY DEVELOPMENT DEVELOPMENT SERVICES DIVISION 9027 Center Street, Room 201, Manassas, VA 20110 P.O. Box 560 Manassas, VA 20108 Phone: 703-257-8278 Fax: 703-257-5831

More information

DESIGN DEVELOPMENT REVIEW PACKAGE CHECKLIST

DESIGN DEVELOPMENT REVIEW PACKAGE CHECKLIST DESIGN DEVELOPMENT REVIEW PACKAGE CHECKLIST Check off each item that is included within the submitted Design Development Review Package. Provide a written explanation for any omissions. The following items,

More information

Deferred Maintenance Plan

Deferred Maintenance Plan Deferred Maintenance Plan 2012-2015 1/5/2012 1 Table of Contents Title Page Introduction 3 Wallace Hall Deferred Maintenance 4 Wallace Hall Building Assessment 6 Wilson Hall Deferred Maintenance 7 Wilson

More information

QUINN COMMONS. Quinn Ln. SOLD

QUINN COMMONS. Quinn Ln. SOLD Quinn Ln. SOLD SOLD Specifications, square footage, renderings and floor plans are for illustration purposes only and are subject to change. Pictures are of similar Sage Built home. Prices may change without

More information

Home Inspection Report

Home Inspection Report Home Inspection Report Example Home Inspection Report. Page 1 of 17 Table of Contents Definitions 2 Company Information 2 General Information 2 Lots and Grounds 3 Exteriors 3 Garage/Carport 4 Roof 5 Attic

More information

S CHEDULE G - D OCUMENTS S UBMITTAL R EQUIREMENTS

S CHEDULE G - D OCUMENTS S UBMITTAL R EQUIREMENTS S CHEDULE G - D OCUMENTS S UBMITTAL R EQUIREMENTS This Attachment lists the items to be provided by the Architect in accordance with Owner/Architect Agreement. This list is not all-inclusive, nor is it

More information

DESIGN DEVELOPMENT PHASE

DESIGN DEVELOPMENT PHASE UNIVERSITY OF MICHIGAN DESIGN DELIVERABLES FEBRUARY 2012 As part of the deliverables for formal UM review at each of the major phases of design listed below, the Design Professional shall submit this "Design

More information