PMG LISTING CRITERIA FOR MULTILAYER PIPE AND FITTINGS ASSEMBLY FOR REFRIGERANT APPLICATIONS LC1036

Size: px
Start display at page:

Download "PMG LISTING CRITERIA FOR MULTILAYER PIPE AND FITTINGS ASSEMBLY FOR REFRIGERANT APPLICATIONS LC1036"

Transcription

1 (800) (562) A Subsidiary of the International Code Council PMG LISTING CRITERIA FOR MULTILAYER PIPE AND FITTINGS ASSEMBLY FOR REFRIGERANT APPLICATIONS LC1036 August 12, 2014 PREFACE Plumbing, mechanical and fuel gas (PMG) listings issued by ICC Evaluation Service, LLC (ICC-ES), are based upon performance features of the International Plumbing Code, International Mechanical Code, International Residential Code, Uniform Plumbing Code and Uniform Mechanical Code. Section of the International Plumbing Code reads as follows: Alternative materials, methods and equipment. The provisions of this code are not intended to prevent the installation of any material or to prohibit any method of construction not specifically prescribed by this code, provided that any such alternative has been approved. An alternative material or method of construction shall be approved where the code official finds that the proposed design is satisfactory and complies with the intent of the provisions of this code, and that the material, method or work offered is, for the purpose intended, at least the equivalent of that prescribed in this code in quality, strength, effectiveness, fire resistance, durability and safety. Similar provisions are contained in the Uniform Codes. ICC-ES may consider alternate listing criteria, provided the listing applicant submits valid data demonstrating that the alternate listing criteria are at least equivalent to the listing criteria set forth in this document, and otherwise demonstrate compliance with the performance features of the codes. Notwithstanding that a product, material, or type or method of construction meets the requirements of the criteria set forth in this document, or that it can be demonstrated that valid alternate criteria are equivalent to the criteria in this document and otherwise demonstrate compliance with the performance features of the codes, ICC-ES retains the right to refuse to issue or renew a listing, if the product, material, or type or method of construction is such that either unusual care with its installation or use must be exercised for satisfactory performance, or if malfunctioning is apt to cause unreasonable property damage or personal injury or sickness relative to the benefits to be achieved by the use of the product, material, o r type or method of construction. Listing criteria are developed solely for use by ICC-ES for purposes of issuing ICC-ES PMG listings. Copyright

2 1.0 INTRODUCTION 1.1 Purpose: The purpose of this listing criteria is to establish requirements for multilayer pipe and associated fittings to be recognized in an ICC Evaluation Service, Inc. (ICC-ES) listing. 1.2 Scope: This listing criteria defines test methods and performance requirements applicable to multiplayer pipe and fittings for refrigeration applications. 1.3 Codes and Referenced Standards: Note: Any standard referenced herein shall be the current edition of that standard. In instances where the applicable code references a different edition of a given standard, the applicant shall also provide documentation of conformance with the code referenced standard edition , 2012 and 2009 International Mechanical Code, Chapter 11, Refrigeration. International Code Council and 2009 Uniform Mechanical Code, Chapter 11, Refrigeration. International Association of Plumbing and Mechanical Officials ASME B31.5, Refrigeration Piping and Heat Transfer Components. ASME ASTM D380, Standard Test Methods for Rubber Hose. ASTM UL1995, Heating and Cooling Equipment. Underwriters Laboratories, Inc UL1963, Refrigerant Recovery/Recycling Equipment. Underwriters Laboratories, Inc UL 207, Refrigerant-Containing Components and Accessories, Nonelectrical. Underwriters Laboratories, Inc UL 746C, Polymeric Materials Use in Electrical Equipment Evaluations, Underwriters Laboratories, Inc ASHRAE Standard 15, Safety Standard for Refrigeration Systems. American Society of Heating, Refrigeration, and Air Conditioning Engineers. 2.0 BASIC INFORMATION 2.1 Product Description: Complete information shall be provided concerning material specifications, thickness, size and the manufacturing process. 2.2 Installation Instructions: Product shall be installed in accordance with the manufacturer's instructions and the requirements of the applicable codes and reference standards in Section 1.3. The installation instruction supplied by the manufacturer with each hose shall include provisions or tables stating the minimum bend radius for each nominal size of the hose. 2

3 2.3 Packaging and Identification: The piping shall be permanently and legibly marked with the manufacturer's name or trademark, and the model number. The product shall also bear the PMG listing mark. 3.0 GENERAL REQUIREMENTS 3.1 Design: Pipe and fittings shall comply with the applicable design conditions and criteria in either Chapter II of ASME B Material: The Pipe assembly shall be made of multilayers. Inner layer, reinforcement layer, and outer layer shall meet the minimum physical properties listed below: Inner Layer Inner layer of tubing shall be made of plastic material having a minimum tensile strength of 30 MPa and an elongation break of 150% and shall comply with the Refrigerant Exposure test in Section 4.6 of this listing criteria. Reinforcement Layer Reinforcement layer shall be made of braided polyester material and shall have a minimum tensile strength of 100 N and an elongation at break of 13%. Outer Layer Outer layer of tubing shall be made of rubber material having a minimum hardness of 63 ± 5, Shore A, a tensile strength of 12 MPa and an elongation at break of 500% and shall comply with the UV test in Section 4.2 of this listing criteria. 4.0 TEST METHOD AND PERFORMANCE REQUIREMENTS 4.1 General For the purpose of the test, five set of samples of pipe and fittings assembly of not less than 18 in long shall be tested. Sample A shall be tested to section 4.2 and 4.3. Sample B shall be tested to section 4.4. Sample C shall be tested to 4.5. Sample D shall be tested to 4.6. Sample E shall be tested to Ultraviolet Light Exposure Test Pipe and fittings assembly shall be exposed to 720 hours of twin enclosed carbon-arc (ASTM G151 and G153) or 1000 hours of xeon-arc (ASTM G151 and G155) as prescribed in clause 57 of UL 746C. 4.3 Pull Test After being exposed to UV light, sample A shall be subjected to the pull test to withstand a tensile force of not less than 500 lbs. 4.4 Permeation Test Pipe and Fitting assembly shall be tested in accordance with clause of UL1963, and shall not permit effusion of refrigerant at a rate greater than 8 lbs/ft 2 /yr. 3

4 4.5 Corrosion Test Five pipe and fittings assemblies shall be prepared for this test. The pipe and fittings assembly shall be tested with salt spray in accordance with ASTM B117 for a duration of not less than 360 hours. After corrosion test, samples shall be tested to section Refrigerant Exposure Test Six pipe and fittings assemblies shall be prepared for this test. The inner tube shall be exposed to the liquid phase of each refrigerant intended to be handled for 30 days at 176 F (80 C). After exposure, one sample shall be tested for delamination to section 4.9. Remaining samples shall be tested to section Thermal Cycling Test Five pipe and fittings assemblies shall be prepared for this test. Pipe and fittings assembly shall be tested in accordance with the thermal cycling test in Clause 58.8 of UL After thermal cycling, samples shall be tested to section Strength Test After Sample C, D and E have completed the test described in 4.5, 4.6, 4.7 respectively; they shall be connected together to be tested to either section or Burst Method: The pipe and fitting assembly shall withstand without failure (such as burst or visible leakage) a pressure equal to five times the refrigerant minimum design pressure in table 11.1 of UL 207, or a pressure equal to five times the design pressure marked on the component, whichever is higher. The burst test shall be performed in accordance with clause 13 of UL 207 at a temperature of not less than 68 F Fatigue Method: the Pipe and fittings when tested in accordance with the Fatigue Test in Clause 14 of UL 207 at the a temperature of not less than 68 F for shall maintain for 1 minute without rupture, burst or leak at the higher of: a) Two times the minimum upper pressure test values specified in Clause of UL 207; or b) One and one-half times the working pressure marked on the component Pressure test specification: Two samples shall be tested. Pressure shall be raised gradually and maintained for 1 minute to the higher of three times the a) Minimum design pressure specified in table 11.1 of UL207 b) Design pressure marked on the component 4

5 Cycle test specification: For the purpose of cyclic test to section 14.3 of UL 207, three samples shall be tested. Samples used for cyclic test may be different from the ones used in the pressure test described in If the pipe is marked for use with more than one refrigerant, the upper and lower cycle pressure test values shall be in accordance with Clause of UL Delaminate Test A 6 inch sample of tubing shall be cut from Sample E after it has been tested to 4.7. Sample shall be tested in accordance with ASTM D380, the hose shall not delaminate between any of the layers. 5.0 LISTING RECOGNITION CONDITIONS 5.1 Multilayer Hose and Fitting Systems: hose and fittings used in used in refrigeration applications shall have a working temperature range of -25 to 200 F (-32 to 93 C), a maximum design working pressure of at least 700 psi, and must be used only with refrigerants meeting the exposure test requirements of 4.5 and that operate within the limits attained in the Pressure Test requirements of 4.1. Mechanical joints shall not be used on annealed temper copper tube in sizes larger than 7/8-inch (22.2 mm) OD size per IMC and ¾" of an inch nominal size per UMC. 5.2 Field Inspection Approval: The listing shall state that prior to final approval by the inspector, verification of factory pre-assembled pipe and fittings connections or hose shall conducted to insure that the assembly was not cut or compromised after installation other than in accordance with manufacturer s installation instructions. If such changes are made to the assembly, this listing report shall be voided, and installation shall not be accepted by authority having jurisdiction. 5.3 Field Testing: Testing shall be conducted In accordance with Section of ASME B31.5. Testing medium for refrigeration piping shall be in accordance with Section of ASME B31.5. Pressure testing for secondary coolant piping shall be in accordance with Section of ASME B

PMG LISTING CRITERIA FOR PERT-AL-PERT PIPE AND FITTINGS FOR REFRIGERATION APPLICATIONS LC1039. Approved Date: November 2015 PREFACE

PMG LISTING CRITERIA FOR PERT-AL-PERT PIPE AND FITTINGS FOR REFRIGERATION APPLICATIONS LC1039. Approved Date: November 2015 PREFACE www.icc-es.org/pmg (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council PMG LISTING CRITERIA FOR PERT-AL-PERT PIPE AND FITTINGS FOR REFRIGERATION APPLICATIONS Approved Date: November

More information

PMG LISTING CRITERIA FOR STRUCTURAL ADHESIVE JOINING SYSTEMS FOR FITTINGS PREFACE

PMG LISTING CRITERIA FOR STRUCTURAL ADHESIVE JOINING SYSTEMS FOR FITTINGS PREFACE www.icc-es.org/pmg (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council PMG LISTING CRITERIA FOR STRUCTURAL ADHESIVE JOINING SYSTEMS FOR FITTINGS Approved March 2009 (Editorially

More information

PMG LISTING CRITERIA FOR PUSH-FIT FITTINGS FOR POTABLE WATER TUBE AND RADIANT HEATING SYSTEMS LC1009

PMG LISTING CRITERIA FOR PUSH-FIT FITTINGS FOR POTABLE WATER TUBE AND RADIANT HEATING SYSTEMS LC1009 www.icc-es.org/pmg (800) 42-6587 (562) 699-054 A Subsidiary of the International Code Council PMG LISTING CRITERIA FOR PUSH-FIT FITTINGS FOR POTABLE WATER TUBE AND RADIANT HEATING SYSTEMS Approved April

More information

PMG LISTING CRITERIA FOR PRESS-CONNECTION FITTINGS FOR POTABLE WATER TUBE AND RADIANT HEATING SYSTEMS PREFACE

PMG LISTING CRITERIA FOR PRESS-CONNECTION FITTINGS FOR POTABLE WATER TUBE AND RADIANT HEATING SYSTEMS PREFACE Title???? Page 1 of 1 www.icc-es.org/pmg (800) 42-6587 (562) 699-054 A Subsidiary of the International Code Council PMG LISTING CRITERIA FOR PRESS-CONNECTION FITTINGS FOR POTABLE WATER TUBE AND RADIANT

More information

The Rehabilitation of Existing Building Drains and Building Sewers by the

The Rehabilitation of Existing Building Drains and Building Sewers by the Inversion or Pulled-in-Place Method and Curing of Resin-impregnated Tube Page 1 of 7 www.icc-es.org/pmg (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council PROPOSED PMG LISTING

More information

ACCEPTANCE CRITERIA FOR THREADED HIGH-STRENGTH STEEL BARS FOR CONCRETE REINFORCEMENT PREFACE

ACCEPTANCE CRITERIA FOR THREADED HIGH-STRENGTH STEEL BARS FOR CONCRETE REINFORCEMENT PREFACE www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR THREADED HIGH-STRENGTH STEEL BARS FOR CONCRETE REINFORCEMENT AC237 Approved June 2009

More information

June 7, 2012 PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES

June 7, 2012 PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES June 7, 2012 TO: PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES SUBJECT: Revisions to the Acceptance Criteria for Metallic HVAC Duct Enclosure Assemblies, Subject AC179-0612-R1 (MB/CA) Dear Colleague:

More information

July 23, 2010 PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION

July 23, 2010 PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION July 23, 2010 TO: SUBJECT: PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION Revisions to the Acceptance Criteria for Reflective Foil Insulation, Subject AC02-0610-R1 (LS/RB) Dear Madam or Sir: In June

More information

June 1, 2017 PARTIES INTERESTED IN POST-TENSIONING ANCHORAGES AND COUPLERS OF PRESTRESSED CONCRETE

June 1, 2017 PARTIES INTERESTED IN POST-TENSIONING ANCHORAGES AND COUPLERS OF PRESTRESSED CONCRETE June 1, 2017 TO: PARTIES INTERESTED IN POST-TENSIONING ANCHORAGES AND COUPLERS OF PRESTRESSED CONCRETE SUBJECT: Proposed Revisions to the Acceptance Criteria for Post-Tensioning Anchorages and Couplers

More information

October 3, Section 1.2 Scope and Section 6.6 were revised to clarify interior and exterior construction types allowed.

October 3, Section 1.2 Scope and Section 6.6 were revised to clarify interior and exterior construction types allowed. October 3, 2016 TO: PARTIES INTERESTED IN EVALAUTION REPORTS ON FIBER- REINFORCED POLYMER (FRP) COMPOSITE COLUMNS USED AS AXIAL LOAD-BEARING AND NONLOAD-BEARING ARCHITECTURAL AND DECORATIVE COLUMNS SUBJECT:

More information

EVALUATION SUBJECT: THE UNICO SYSTEM SMALL- DUCT, HIGH-VELOCITY HEATING AND COOLING SYSTEMS

EVALUATION SUBJECT: THE UNICO SYSTEM SMALL- DUCT, HIGH-VELOCITY HEATING AND COOLING SYSTEMS ICC-ES Report PMG-1002 Reissued 08/2018 This report is subject to renewal 08/2019 EVALUATION SUBJECT: THE UNICO SYSTEM SMALL- DUCT, HIGH-VELOCITY HEATING AND COOLING SYSTEMS DIVISION: 23 00 00 HEATING,

More information

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) AC191 Approved May 2008 Effective June 1, 2008 Previously approved February 2008, October 2007,

More information

ACCEPTANCE CRITERIA FOR ROOF UNDERLAYMENT FOR USE IN SEVERE CLIMATE AREAS PREFACE

ACCEPTANCE CRITERIA FOR ROOF UNDERLAYMENT FOR USE IN SEVERE CLIMATE AREAS PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR ROOF UNDERLAYMENT FOR USE IN SEVERE CLIMATE AREAS AC48 Approved January 2000 Effective February 1, 2000 (Editorially revised

More information

June 1, 2012 PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS

June 1, 2012 PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS June 1, 2012 TO: PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS SUBJECT: Proposed Revisions to the Acceptance Criteria for Cold-formed Steel Framing Members, Subject AC46-0612-R1 (WM/DM) Dear

More information

June 22, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON COMPOSITE COLD-FORMED LIGHT GAGE STEEL AND CONCRETE MASONRY LINTELS

June 22, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON COMPOSITE COLD-FORMED LIGHT GAGE STEEL AND CONCRETE MASONRY LINTELS June 22, 2009 TO: SUBJECT: PARTIES INTERESTED IN EVALUATION REPORTS ON COMPOSITE COLD-FORMED LIGHT GAGE STEEL AND CONCRETE MASONRY LINTELS Acceptance Criteria for Composite Cold-formed Light Gage Steel

More information

EVALUATION SUBJECT: VIEGA LLC S PUREFLOW PLUMBING SYSTEM

EVALUATION SUBJECT: VIEGA LLC S PUREFLOW PLUMBING SYSTEM ICC-ES Report PMG-1038 Reissued 11/2018 This report is subject to renewal 11/2019 EVALUATION SUBJECT: VIEGA LLC S PUREFLOW PLUMBING SYSTEM DIVISION: 22 00 00 PLUMBING SECTION: 22 11 16 DOMESTIC WATER PIPING

More information

EVALUATION SUBJECT: WATTS RADIANTPEX, WATTS RADIANTPEX+, WATTS HEATINGPEX, AND RADIANTFLOW

EVALUATION SUBJECT: WATTS RADIANTPEX, WATTS RADIANTPEX+, WATTS HEATINGPEX, AND RADIANTFLOW ICC-ES Report PMG-1008 Reissued 12/2017 This report is subject to renewal 12/2018 EVALUATION SUBJECT: WATTS RADIANTPEX, WATTS RADIANTPEX+, WATTS HEATINGPEX, AND RADIANTFLOW DIVISION: 23 00 00 HEATING,

More information

ACCEPTANCE CRITERIA FOR METAL COMPOSITE MATERIAL (MCM) PREFACE

ACCEPTANCE CRITERIA FOR METAL COMPOSITE MATERIAL (MCM) PREFACE www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR METAL COMPOSITE MATERIAL (MCM) AC25 Approved October 2010 (Editorially revised August

More information

June 9, 2008 PARTIES INTERESTED IN EVALUATION REPORTS ON TERMITE- RESISTANT FOAM PLASTICS

June 9, 2008 PARTIES INTERESTED IN EVALUATION REPORTS ON TERMITE- RESISTANT FOAM PLASTICS ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect June 9, 2008 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON TERMITE- RESISTANT FOAM PLASTICS SUBJECT: Acceptance Criteria for Termite-resistant

More information

June 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION

June 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION June 1, 2010 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION SUBJECT: Proposed Revisions to the Acceptance Criteria for Reflective Foil Insulation, Subject AC02-0610-R1 (LS/RB)

More information

April 2, 2018 PARTIES INTERESTED IN CROSS LAMINATED TIMBER PANELS USED AS COMPONENTS IN FLOOR AND ROOF DECKS

April 2, 2018 PARTIES INTERESTED IN CROSS LAMINATED TIMBER PANELS USED AS COMPONENTS IN FLOOR AND ROOF DECKS April 2, 2018 TO: PARTIES INTERESTED IN CROSS LAMINATED TIMBER PANELS USED AS COMPONENTS IN FLOOR AND ROOF DECKS SUBJECT: Proposed Revisions to the ICC-ES Acceptance Criteria for Cross-laminated Timber

More information

December 3, 2012 PARTIES INTERESTED IN INTUMESCENT FIRE-RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS

December 3, 2012 PARTIES INTERESTED IN INTUMESCENT FIRE-RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS December 3, 2012 TO: PARTIES INTERESTED IN INTUMESCENT FIRE-RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS SUBJECT: Proposed Acceptance Criteria for Intumescent Fire-resistant Coatings

More information

ICC-ES Report. PMG-1009 Reissued 10/2017 This report is subject to renewal 10/2018 EPIPE EPOXY LINED PIPING SYSTEM ACE DURAFLO SYSTEMS, LLC

ICC-ES Report. PMG-1009 Reissued 10/2017 This report is subject to renewal 10/2018 EPIPE EPOXY LINED PIPING SYSTEM ACE DURAFLO SYSTEMS, LLC ICC-ES Report PMG-1009 Reissued 10/2017 This report is subject to renewal 10/2018 EVALUATION SUBJECT: EPIPE EPOXY LINED PIPING SYSTEM DIVISION: 22 00 00 PLUMBING SECTION: 22 11 16 DOMESTIC WATER PIPING

More information

ACCEPTANCE CRITERIA FOR POLYMER-BASED AND POLYMER-MODIFIED EXTERIOR AND INTERIOR WALL CLADDING

ACCEPTANCE CRITERIA FOR POLYMER-BASED AND POLYMER-MODIFIED EXTERIOR AND INTERIOR WALL CLADDING www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR POLYMER-BASED AND POLYMER-MODIFIED EXTERIOR AND INTERIOR WALL CLADDING AC92 Approved

More information

ACCEPTANCE CRITERIA FOR WATER-RESISTIVE BARRIERS PREFACE

ACCEPTANCE CRITERIA FOR WATER-RESISTIVE BARRIERS PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR WATER-RESISTIVE BARRIERS AC38 Approved June 2004 Effective July 1, 2004 Previously approved July 2000, September 1990 PREFACE

More information

EVALUATION SUBJECT: TEEL BQ POLYPROPYLENE (PP-RCT) PIPING SYSTEM

EVALUATION SUBJECT: TEEL BQ POLYPROPYLENE (PP-RCT) PIPING SYSTEM ICC-ES Report PMG-1452 Issued 01/2018 This report is subject to renewal 01/2019 EVALUATION SUBJECT: TEEL BQ POLYPROPYLENE (PP-RCT) PIPING SYSTEM DIVISION: 22 00 00 PLUMBING SECTION: 22 11 00 FACILITY WATER

More information

February 1, SUBJECT: Proposed Revisions to the Acceptance Criteria for Staples, Subject AC R1 (EL/JF)

February 1, SUBJECT: Proposed Revisions to the Acceptance Criteria for Staples, Subject AC R1 (EL/JF) February 1, 2018 TO: PARTIES INTERESTED IN STAPLES SUBJECT: Proposed Revisions to the Acceptance Criteria for Staples, Subject AC201-0218-R1 (EL/JF) Dear Colleague: We are seeking your comments on proposed

More information

EVALUATION SUBJECT: UPONOR/WIRSBO hepex TUBING, UPONOR AQUAPEX TUBING AND FITTINGS

EVALUATION SUBJECT: UPONOR/WIRSBO hepex TUBING, UPONOR AQUAPEX TUBING AND FITTINGS ICC-ES Report PMG-1012 Reissued 08/2017 This report is subject to renewal 08/2018 EVALUATION SUBJECT: UPONOR/WIRSBO hepex TUBING, UPONOR AQUAPEX TUBING AND FITTINGS DIVISION: 23 00 00 HEATING, VENTILATING

More information

EVALUATION SUBJECT: HAMMERHEAD CURED-IN- PLACE PIPE (CIPP) LINING SYSTEM DIVISION: PLUMBING SECTION: SANITARY WASTE AND VENT PIPING

EVALUATION SUBJECT: HAMMERHEAD CURED-IN- PLACE PIPE (CIPP) LINING SYSTEM DIVISION: PLUMBING SECTION: SANITARY WASTE AND VENT PIPING ICC-ES Report PMG-1273 Reissued 01/2018 This report is subject to renewal 01/2019 EVALUATION SUBJECT: HAMMERHEAD CURED-IN- PLACE PIPE (CIPP) LINING SYSTEM DIVISION: 22 00 00 PLUMBING SECTION: 22 13 16

More information

April 18, 2018 PARTIES INTERESTED IN ADHERED PORCELAIN TILE WALL CLADDING SYSTEM

April 18, 2018 PARTIES INTERESTED IN ADHERED PORCELAIN TILE WALL CLADDING SYSTEM April 18, 2018 TO: SUBJECT: PARTIES INTERESTED IN ADHERED PORCELAIN TILE WALL CLADDING SYSTEM Proposed Acceptance Criteria for Adhered Porcelain Tile Wall Cladding System, Subject (YM/DO) Hearing Information:

More information

EVALUATION SUBJECT: PERMA-LATERAL PULLED- IN-PLACE CURED-IN-PLACE PIPE LINING SYSTEM

EVALUATION SUBJECT: PERMA-LATERAL PULLED- IN-PLACE CURED-IN-PLACE PIPE LINING SYSTEM ICC-ES Report PMG-1074 Reissued 11/2017 This report is subject to renewal 11/2018 EVALUATION SUBJECT: PERMA-LATERAL PULLED- IN-PLACE CURED-IN-PLACE PIPE LINING SYSTEM DIVISION: 22 00 00 PLUMBING SECTION:

More information

EVALUATION SUBJECT: VIEGA LLC PROPRESSG AND MEGAPRESSG SYSTEM

EVALUATION SUBJECT: VIEGA LLC PROPRESSG AND MEGAPRESSG SYSTEM ICC-ES Report PMG-1036 Reissued 07/2018 This report is subject to renewal 07/2019 EVALUATION SUBJECT: VIEGA LLC PROPRESSG AND MEGAPRESSG SYSTEM DIVISION: 23 00 00 HEATING, VENTILATING AND AIR CONDITIONING

More information

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: PJ S REBAR INC.

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: PJ S REBAR INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 42 687 (62) 699 04 www.icc es.org ESR 82 Reissued 0/207 This report is subject to renewal 0/209. DIVISION: 0 00 00 CONCRETE

More information

February 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON ROOF UNDERLAYMENTS FOR USE IN SEVERE CLIMATE AREAS

February 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON ROOF UNDERLAYMENTS FOR USE IN SEVERE CLIMATE AREAS February 1, 2010 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON ROOF UNDERLAYMENTS FOR USE IN SEVERE CLIMATE AREAS SUBJECT: Proposed Revisions to the Acceptance Criteria for Roof Underlayments for Use

More information

ACCEPTANCE CRITERIA FOR EXPANSION BOLTS IN STRUCTURAL STEEL CONNECTIONS (BLIND-BOLTS) PREFACE

ACCEPTANCE CRITERIA FOR EXPANSION BOLTS IN STRUCTURAL STEEL CONNECTIONS (BLIND-BOLTS) PREFACE www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR EXPANSION BOLTS IN STRUCTURAL STEEL CONNECTIONS (BLIND-BOLTS) AC437 Approved October

More information

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR GLASS LAVATORIES, SINKS AND COUNTER TOPS IAPMO IGC

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR GLASS LAVATORIES, SINKS AND COUNTER TOPS IAPMO IGC INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR GLASS LAVATORIES, SINKS AND COUNTER TOPS IAPMO IGC 172-200810 1. PURPOSE 1.1 The purpose of this standard is to establish

More information

October 12, Yours very truly, Gary G. Nichols, P.E., SECB Vice President. GGN/md Enclosure Evaluation Committee

October 12, Yours very truly, Gary G. Nichols, P.E., SECB Vice President. GGN/md Enclosure Evaluation Committee October 12, 2010 TO: SUBJECT: PARTIES INTERESTED IN EVALUATION REPORTS ON STAY-IN-PLACE, FOAM PLASTIC INSULATING CONCRETE FORM (ICF) SYSTEMS FOR SOLID CONCRETE WALLS Revisions to the Acceptance Criteria

More information

EVALUATION SUBJECT: CURAFLO ENGINEERED FLOW LINING SYSTEMS DIVISION: PLUMBING SECTION: DOMESTIC WATER PIPING.

EVALUATION SUBJECT: CURAFLO ENGINEERED FLOW LINING SYSTEMS DIVISION: PLUMBING SECTION: DOMESTIC WATER PIPING. ICC-ES Report PMG-1057 Reissued 02/2018 This report is subject to renewal 02/2019 EVALUATION SUBJECT: CURAFLO ENGINEERED FLOW LINING SYSTEMS DIVISION: 22 00 00 PLUMBING SECTION: 22 11 16 DOMESTIC WATER

More information

June 1, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS

June 1, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS June 1, 2009 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS SUBJECT: Proposed Revisions to the Acceptance Criteria for Wood-based Studs, Subject AC202-0609-R1

More information

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3317 Reissued 07/2018 This report is subject to renewal 07/2020. SECTION: 03 15 00

More information

EVALUATION SUBJECT: AKDUCT AND AKDUCT PREMIER

EVALUATION SUBJECT: AKDUCT AND AKDUCT PREMIER ICC-ES Report PMG-1023 Reissued 10/2017 This report is subject to renewal 10/2018 EVALUATION SUBJECT: AKDUCT AND AKDUCT PREMIER DIVISION: 23 00 00 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION:

More information

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: SRL INDUSTRIES LTD.

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: SRL INDUSTRIES LTD. 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 42-6587 (562) 699-054 www.icc-es.org ESR-298 Reissued 0/2018 This report is subject to renewal 0/2019. DIVISION: 0 00 00 CONCRETE

More information

EVALUATION SUBJECT: AQUATECHNIK GAS PEX-AL-PEX PIPE AND FITTING SYSTEM

EVALUATION SUBJECT: AQUATECHNIK GAS PEX-AL-PEX PIPE AND FITTING SYSTEM ICC-ES Report PMG-1438 Issued 08/2017 This report is subject to renewal 08/2018 EVALUATION SUBJECT: AQUATECHNIK GAS PEX-AL-PEX PIPE AND FITTING SYSTEM DIVISION: 23 00 00 HEATING, VENTILATING AND AIR CONDITIONING

More information

EVALUATION SUBJECT: NIRON POLYPROPYLENE (PP-RCT) PIPING SYSTEM DIVISION: PLUMBING SECTION: DOMESTIC WATER PIPING

EVALUATION SUBJECT: NIRON POLYPROPYLENE (PP-RCT) PIPING SYSTEM DIVISION: PLUMBING SECTION: DOMESTIC WATER PIPING ICC-ES Report PMG-1244 Reissued 04/2017 This report is subject to renewal 04/2018 EVALUATION SUBJECT: NIRON POLYPROPYLENE (PP-RCT) PIPING SYSTEM DIVISION: 22 00 00 PLUMBING SECTION: 22 11 16 DOMESTIC WATER

More information

March 6, 2012 PARTIES INTERESTED IN THE DETERMINATION OF FORMALDEHYDE EMISSIONS OF COMPOSITE WOOD PRODUCTS

March 6, 2012 PARTIES INTERESTED IN THE DETERMINATION OF FORMALDEHYDE EMISSIONS OF COMPOSITE WOOD PRODUCTS March 6, 2012 TO: SUBJECT: PARTIES INTERESTED IN THE DETERMINATION OF FORMALDEHYDE EMISSIONS OF COMPOSITE WOOD PRODUCTS Revisions to the Environmental Criteria for Determination of Formaldehyde Emissions

More information

ENVIRONMENTAL CRITERIA FOR DETERMINATION OF SOURCE OF RECOVERY, EXTRACTION, HARVEST AND MANUFACTURE FOR MATERIALS OR PRODUCTS EC114

ENVIRONMENTAL CRITERIA FOR DETERMINATION OF SOURCE OF RECOVERY, EXTRACTION, HARVEST AND MANUFACTURE FOR MATERIALS OR PRODUCTS EC114 www.icc-es.org/ep 1-800-423-6587 (562) 699-0543 A Subsidiary of the International Code Council ENVIRONMENTAL CRITERIA FOR DETERMINATION OF SOURCE OF RECOVERY, EXTRACTION, HARVEST AND MANUFACTURE FOR OR

More information

EVALUATION SUBJECT: AQUAPEX PRESSURE RATED TUBING, PROPEX AND COMPRESSION TYPE FITTINGS

EVALUATION SUBJECT: AQUAPEX PRESSURE RATED TUBING, PROPEX AND COMPRESSION TYPE FITTINGS ICC-ES Report PMG-1006 Reissued 03/2018 This report is subject to renewal 03/2019 EVALUATION SUBJECT: AQUAPEX PRESSURE RATED TUBING, PROPEX AND COMPRESSION TYPE FITTINGS DIVISION: 22 00 00 PLUMBING SECTION:

More information

EVALUATION SUBJECT: SPEEDFIT TUBING AND FITTINGS DIVISION: PLUMBING SECTION: DOMESTIC WATER PIPING

EVALUATION SUBJECT: SPEEDFIT TUBING AND FITTINGS DIVISION: PLUMBING SECTION: DOMESTIC WATER PIPING ICC-ES Report PMG-1033 Reissued 05/2017 This report is subject to renewal 05/2018 EVALUATION SUBJECT: SPEEDFIT TUBING AND FITTINGS DIVISION: 22 00 00 PLUMBING SECTION: 22 11 16 DOMESTIC WATER PIPING DIVISION:

More information

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: PEIKKO GROUP, INC.

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: PEIKKO GROUP, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3902 Reissued 04/2017 This report is subject to renewal 04/2019. SECTION: 03 15 00

More information

August 1, Removed reference to the standard edition from Sections and

August 1, Removed reference to the standard edition from Sections and August 1, 2018 TO: PARTIES INTERESTED IN SPRAYED FIRE-RESISTANT MATERIALS (SFRMs), INTUMESCENT FIRE-RESISTANT COATINGS AND MASTIC FIRE-RESISTANT COATINGS USED TO PROTECT STRUCTURAL STEEL MEMBERS SUBJECT:

More information

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: TENDON SYSTEMS, LLC

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: TENDON SYSTEMS, LLC 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 42-6587 (562) 699-054 www.icc-es.org ESR-900 Issued 08/2017 This report is subject to renewal 08/2018. DIVISION: 0 00 00 CONCRETE

More information

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR RECLAIMED WATER CONSERVATION SYSTEM FOR FLUSHING TOILETS

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR RECLAIMED WATER CONSERVATION SYSTEM FOR FLUSHING TOILETS INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR RECLAIMED WATER CONSERVATION SYSTEM FOR FLUSHING TOILETS IAPMO IGC 207-2009a 1. PURPOSE 1.1 The purpose of this standard

More information

EVALUATION SUBJECT: AQUATECHNIK SAFETY -POL PEX- AL-PEX PIPE AND FITTING SYSTEM

EVALUATION SUBJECT: AQUATECHNIK SAFETY -POL PEX- AL-PEX PIPE AND FITTING SYSTEM ICC-ES Report PMG-1437 Reissued 08/2018 This report is subject to renewal 08/2019 EVALUATION SUBJECT: AQUATECHNIK SAFETY -POL PEX- AL-PEX PIPE AND FITTING SYSTEM DIVISION: 23 00 00 HEATING, VENTILATING

More information

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER:

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3902 Reissued 04/2017 This report is subject to renewal 04/2019. SECTION: 03 15 00

More information

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR LONGITUDINALLY WELDED HOT-DIP GALVANIZED STEEL PIPE AND FITTINGS FOR WASTEWATER SYSTEMS IGC 270-2008 1. PURPOSE 1.1

More information

ENVIRONMENTAL CRITERIA FOR DETERMINATION OF RECYCLED CONTENT OF MATERIALS EC101 PREFACE

ENVIRONMENTAL CRITERIA FOR DETERMINATION OF RECYCLED CONTENT OF MATERIALS EC101 PREFACE www.icc-es.org/save 1-800-423-6587 (562) 699-0543 A Subsidiary of the International Code Council ENVIRONMENTAL CRITERIA FOR DETERMINATION OF OF MATERIALS EC101 Effective date: March 1, 2012 Previously

More information

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: SAS STRESSTEEL INC. 100 NEW DUTCH LANE FAIRFIELD, NEW JERSEY 07004

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: SAS STRESSTEEL INC. 100 NEW DUTCH LANE FAIRFIELD, NEW JERSEY 07004 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1163 Reissued 12/2016 This report is subject to renewal 12/2017. DIVISION: 03 00

More information

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER AC51 Approved February 2008 Effective March 1, 2008 (Editorially

More information

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES REPORT HOLDER: NELSON STUD WELDING, INC WEST RIDGE ROAD ELYRIA, OHIO 44036

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES REPORT HOLDER: NELSON STUD WELDING, INC WEST RIDGE ROAD ELYRIA, OHIO 44036 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 42-687 (62) 699-04 www.icc-es.org ESR-2907 Reissued 2/207 This report is subject to renewal 2/208. DIVISION: 0 00 00 CONCRETE

More information

PMG-1039 Effective Date: April 1, 2014 This listing is subject to re-examination in one year.

PMG-1039 Effective Date: April 1, 2014 This listing is subject to re-examination in one year. ICC-ES PMG Listing PMG-1039 Effective Date: April 1, 2014 This listing is subject to re-examination in one year. www.icc-es-pmg.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code

More information

April 1, 2015 PARTIES INTERESTED IN FLEXIBLE FLASHING MATERIALS

April 1, 2015 PARTIES INTERESTED IN FLEXIBLE FLASHING MATERIALS April 1, 2015 TO: PARTIES INTERESTED IN FLEXIBLE FLASHING MATERIALS SUBJECT: Proposed Revisions to the Acceptance Criteria for Flexible Flashing Materials, Subject AC148-0415-R1 (ST/YM) Dear Colleague:

More information

The purpose of this memo is to respond to the comments received in response to the May 1, 2007, staff letter and the revised criteria.

The purpose of this memo is to respond to the comments received in response to the May 1, 2007, staff letter and the revised criteria. ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect #19 To: From: ICC-ES Evaluation Committee Brian Gerber, S.E., and Irni Yani Date: June 1, 2007 Subject: Revisions to the Proposed Acceptance Criteria

More information

December 1, 2014 PARTIES INTERESTED IN STRUCTURAL WOOD-BASED PRODUCTS

December 1, 2014 PARTIES INTERESTED IN STRUCTURAL WOOD-BASED PRODUCTS December 1, 2014 TO: PARTIES INTERESTED IN STRUCTURAL WOOD-BASED PRODUCTS SUBJECT: Proposed Revision to the ICC-ES Acceptance Criteria for Structural Wood-Based Products, Subject AC47-1214-R2-2 (JF/PC)

More information

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR HEADED AND MECHANICALLY ANCHORED DEFORMED REINFORCEMENT BARS IN TENSION EC 006-2014 (Adopted

More information

DIVISION: MASONRY SECTION: CONCRETE UNIT MASONRY REPORT HOLDER: 3B CONSTRUCTION SOLUTIONS, INC.

DIVISION: MASONRY SECTION: CONCRETE UNIT MASONRY REPORT HOLDER: 3B CONSTRUCTION SOLUTIONS, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3788 Reissued 11/2017 This report is subject to renewal 11/2018. DIVISION: 04 00

More information

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: AKRON PRODUCTS COMPANY

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: AKRON PRODUCTS COMPANY 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1767 Reissued 04/2018 This report is subject to renewal 04/2020. DIVISION: 05 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: FOUR SEASONS BUILDING PRODUCTS, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: FOUR SEASONS BUILDING PRODUCTS, LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2229 Reissued 05/2018 This report is subject to renewal 05/2019. DIVISION: 07 00

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: PLASTIC DECKING REPORT HOLDER: SILCA SYSTEM

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: PLASTIC DECKING REPORT HOLDER: SILCA SYSTEM 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3748 Reissued 05/2018 This report is subject to renewal 05/2019. DIVISION: 06 00

More information

December 1, 2011 PARTIES INTERESTED IN ALTERNATE DOWEL-TYPE THREADED FASTENERS

December 1, 2011 PARTIES INTERESTED IN ALTERNATE DOWEL-TYPE THREADED FASTENERS December 1, 2011 TO: PARTIES INTERESTED IN ALTERNATE DOWEL-TYPE THREADED S SUBJECT: Proposed Revisions to the Acceptance Criteria for Alternate Dowel-type Threaded Fasteners, Subject AC233-1211-R1 (EL/JS)

More information

UNI-BELL PVC PIPE ASSOCIATION UNI-B-15-10

UNI-BELL PVC PIPE ASSOCIATION UNI-B-15-10 UNI-BELL PVC PIPE ASSOCIATION UNI-B-15-10 RECOMMENDED STANDARD SPECIFICATION FOR POLYVINYL CHLORIDE (PVC) FABRICATED PRESSURE FITTINGS November 2010 UNI-BELL PVC PIPE ASSOCIATION 2711 LBJ Freeway, Suite

More information

ICBO Evaluation Service, Inc. A subsidiary corporation of the International Conference of Building Officials

ICBO Evaluation Service, Inc. A subsidiary corporation of the International Conference of Building Officials ICBO Evaluation Service, Inc. A subsidiary corporation of the International Conference of Building Officials 30 WORKMAN MILL ROAD WHITTIER, CALIFORNIA 9001-2299 (2) 99-03 FAX (2) 9-9 ACCEPTANCE CRITERIA

More information

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER PREFACE

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER AC51 Approved February 2008 Effective March 1, 2008 Previously approved October 2007, January 2001,

More information

February 1, 2018 PARTIES INTERESTED IN DECK BOARD SPAN RATINGS AND GUARDRAIL SYSTEMS (GUARDS AND HANDRAILS)

February 1, 2018 PARTIES INTERESTED IN DECK BOARD SPAN RATINGS AND GUARDRAIL SYSTEMS (GUARDS AND HANDRAILS) February 1, 2018 TO: SUBJECT: PARTIES INTERESTED IN DECK BOARD SPAN RATINGS AND GUARDRAIL SYSTEMS (GUARDS AND HANDRAILS) Proposed Revisions to the ICC-ES Acceptance Criteria for Deck Board Span Ratings

More information

Trusted ICC ES MILAN ITALY SYSTEMS. Look. Conformity! Evaluation. ICC-ES Evaluation

Trusted ICC ES MILAN ITALY SYSTEMS. Look. Conformity! Evaluation. ICC-ES Evaluation 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg ESR 3499 Reissued 02/2016 This report is subject to renewal 02/2018. DIVISION: 03 00

More information

EVALUATION SUBJECT: ENAMELED CAST IRON PLUMBING FIXTURES DIVISION: PLUMBING SECTION: PLUMBING EQUIPMENT PLUMBING FIXTURES

EVALUATION SUBJECT: ENAMELED CAST IRON PLUMBING FIXTURES DIVISION: PLUMBING SECTION: PLUMBING EQUIPMENT PLUMBING FIXTURES ICC-ES Report PMG-1378 Reissued 03/2017 This report is subject to renewal 03/2018 EVALUATION SUBJECT: ENAMELED CAST IRON PLUMBING FIXTURES DIVISION: 22 00 00 PLUMBING SECTION: 22 30 00 PLUMBING EQUIPMENT

More information

ACCEPTANCE CRITERIA FOR FASTENERS POWER-DRIVEN INTO CONCRETE, STEEL AND MASONRY ELEMENTS PREFACE

ACCEPTANCE CRITERIA FOR FASTENERS POWER-DRIVEN INTO CONCRETE, STEEL AND MASONRY ELEMENTS PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR FASTENERS POWER-DRIVEN INTO CONCRETE, STEEL AND MASONRY ELEMENTS AC70 Approved October 2006 Effective January 1, 2007 Previously

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PLASTICS REPORT HOLDER: HB&G BUILDING PRODUCTS, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PLASTICS REPORT HOLDER: HB&G BUILDING PRODUCTS, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1361 Reissued 08/2017 This report is subject to renewal 08/2019. DIVISION: 06 00

More information

Raychem Fluoroelastomer Tubing Flexible, Fluid Resistant, Heat-Shrinkable

Raychem Fluoroelastomer Tubing Flexible, Fluid Resistant, Heat-Shrinkable Tyco Electronics Corporation 300 Constitution Drive Menlo Park, CA 94025 USA Specification This Issue: Date: Replaces: RW-3037 Issue 2 July 26, 2006 Issue 1 Raychem Fluoroelastomer Tubing Flexible, Fluid

More information

REPORT HOLDER: UNITED DURALUME PRODUCTS, INC. EVALUATION SUBJECT: DURACOOL COMPOSITE STRUCTURAL INSULATED PANELS

REPORT HOLDER: UNITED DURALUME PRODUCTS, INC. EVALUATION SUBJECT: DURACOOL COMPOSITE STRUCTURAL INSULATED PANELS 0 ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org Most Widely Accepted and Trusted ESR 3779 Reissued 01/2017 Revised 10/2018 This report is subject to renewal 01/2019.

More information

October 1, SUBJECT: Proposed Revisions to the Acceptance Criteria for Walking Decks, Subject AC R1 (WU/CA).

October 1, SUBJECT: Proposed Revisions to the Acceptance Criteria for Walking Decks, Subject AC R1 (WU/CA). October 1, 2012 TO: PARTIES INTERESTED IN WALKING DECKS SUBJECT: Proposed Revisions to the Acceptance Criteria for Walking Decks, Subject AC39-1012-R1 (WU/CA). Dear Colleague: We are seeking your comments

More information

Trusted ICC ES. Conformity! Look. Evaluation. ICC-ES Evaluation

Trusted ICC ES. Conformity! Look. Evaluation. ICC-ES Evaluation 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg ESR 3288 Reissued 12/2017 This report is subject to renewal 12/2018. DIVISION: 03 00

More information

EVALUATION SUBJECT: IPEX AQUARISE CPVC HOT- AND COLD- POTABLE WATER DISTRIBUTION SYSTEM

EVALUATION SUBJECT: IPEX AQUARISE CPVC HOT- AND COLD- POTABLE WATER DISTRIBUTION SYSTEM ICC-ES Report PMG-1156 Reissued 08/2018 This report is subject to renewal 08/2019 EVALUATION SUBJECT: IPEX AQUARISE CPVC HOT- AND COLD- POTABLE WATER DISTRIBUTION SYSTEM DIVISION: 22 00 00 PLUMBING SECTION:

More information

DIVISION: CONCRETE SECTION: MAINTENANCE OF CONCRETE REPORT HOLDER: STRUCTURAL TECHNOLOGIES, LLC

DIVISION: CONCRETE SECTION: MAINTENANCE OF CONCRETE REPORT HOLDER: STRUCTURAL TECHNOLOGIES, LLC 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3606 Reissued 01/2018 This report is subject to renewal 01/2019. DIVISION: 03 00

More information

AC178. June (Effective July 1, 2003) Previously issued April 2001 PREFACE

AC178. June (Effective July 1, 2003) Previously issued April 2001 PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect INTERIM CRITERIA FOR INSPECTION AND VERIFICATION OF CONCRETE AND AC178 June 2003 (Effective July 1, 2003) Previously issued April 2001 PREFACE Legacy

More information

Engineering Specifications

Engineering Specifications VIEGA PUREFLOW SYSTEM PART 1 GENERAL 1.1 SUMMARY 1.1.1 This specification covers Branch & Main, Parallel Water Distribution Systems (ManaBloc), Cross-linked Polyethylene tubing and fittings using PureFlow

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: FCP, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: FCP, INC. 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2937 Reissued 05/2016 This report is subject to renewal 05/2018. DIVISION: 07 00 00 THERMAL

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: KWIK BOLT TZ MASONRY ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: KWIK BOLT TZ MASONRY ANCHORS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 4 687 (6) 699 04 www.icc es.org ESR 78 Reissued 07/018 This report is subject to renewal 07/019. DIVISION: 04 00 00 MASONRY

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: NCFI POLYURETHANES

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: NCFI POLYURETHANES 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3392 Reissued 06/2017 This report is subject to renewal 06/2018. DIVISION: 07 00

More information

CERTIFICATIONS AND LISTINGS

CERTIFICATIONS AND LISTINGS CERTIFICATIONS AND LISTINGS REHAU PEXa Tubing, Effective October 2017 TABLE OF CONTENTS Table 1: REHAU Certifications and Listings 1. REHAU PEX Tubing..................................4 2. Fire-rated Assembly

More information

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: MMFX TECHNOLOGIES A COMMERCIAL METALS COMPANY

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: MMFX TECHNOLOGIES A COMMERCIAL METALS COMPANY 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2107 Reissued 02/2018 This report is subject to renewal 01/2019. DIVISION: 03 00

More information

Installation Practice InnerSeal

Installation Practice InnerSeal Installation Practice InnerSeal Rehabilitation of a Full-Length Sewer Service Lateral using One-Piece Main and Lateral Cured-In-Place Liner Assembly Installed By Means Of Air Inversion 1. Intent This instruction

More information

Trusted ICC ES TEK USA, Evaluation. report, or as to any. ICC-ES Evaluation

Trusted ICC ES TEK USA, Evaluation. report, or as to any. ICC-ES Evaluation 0 ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg Most Widely Accepted and Trusted ESR 3105 Reissued 08/2017 Revised 10/2018 This report is subject to renewal 08/2019.

More information

THERMOFIT SCL TUBING Polyolefin, Selectively Crosslinked, Semirigid, Heat Shrinkable

THERMOFIT SCL TUBING Polyolefin, Selectively Crosslinked, Semirigid, Heat Shrinkable Tyco Electronics Corporation 300 Constitutional Drive Menlo Park, CA 94025 USA Specification This Issue: Date: Replaces: RT-1301 Issue 7 October 3, 2003 Issue 6 THERMOFIT SCL TUBING Polyolefin, Selectively

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER: 0 Most idely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-687 (62) 699-043 www.icc-es.org ESR-199 Reissued 0/2017 This report is subject to renewal 0/2019. DIVISION: 07 00 00 THERMAL AND MOISTURE

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 687 (6) 699 0 www.icc es.org ESR 8 Reissued 0/08 This report is subject to renewal 0/09. DIVISION: 0 00 00 MASONRY SECTION:

More information

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1530 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 03 00

More information

THERMOFIT AP2000 TUBING HEAT-SHRINKABLE CROSSLINKED MODIFIED POLYOLEFIN, ADHESIVE LINER

THERMOFIT AP2000 TUBING HEAT-SHRINKABLE CROSSLINKED MODIFIED POLYOLEFIN, ADHESIVE LINER Product Brand:Raychem 305 Constitution Drive, Menlo Park, CA 94025 SPECIFICATION: RW-1001 THIS ISSUE: ISSUE 3 DATE: April 11, 2003 REPLACES: ISSUE 2 THERMOFIT AP2000 TUBING HEAT-SHRINKABLE CROSSLINKED

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: BOSTITCH FASTENING SYSTEMS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: BOSTITCH FASTENING SYSTEMS 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2122 Reissued 03/2017 This report is subject to renewal 03/2018. DIVISION: 06 00 00 WOOD, PLASTICS

More information