Report. Laboratory for Acoustics Determination of the insertion loss or sound power insulation of Arma-Chek Sound Insulation
|
|
- Maryann Rodgers
- 6 years ago
- Views:
Transcription
1 Report Member ONRI ISO-9001: 2000 certified Laboratory for Acoustics Determination of the insertion loss or sound power insulation of Arma-Chek Sound Insulation Report number A E dd. 4 February 2005 Peutz bv Paletsingel 2, Postbus AR Zoetermeer Tel. (079) Fax (079) info@zoetermeer.peutz.nl Peutz bv Lindenlaan 41, Molenhoek Postbus 66, 6585 ZH Mook Tel. (024) Fax (024) info@mook.peutz.nl Principal: Armacell UK Ltd Mars Street Oldham OL9 6LY United Kingdom Report number: A E Date: 4 February 2005 Peutz GmbH Kolberger Strasse Düsseldorf Tel Fax dus@peutz.de Peutz S.A.R.L. 34 Rue de Paradis Paris Tel Fax peutz@club-internet.fr Peutz bv PO Box London W5 2ZA Tel Fax peutz.london@tiscali.co.uk Ref.: TS/YW/LvI/A E-RA All orders are accepted, carried out and charged in accordance with the 'Regeling van de verhouding tussen opdrachtgever en adviserend ingenieursbureau' (Regulations governing relations between clients and consulting engineers), RVOI KvK: BTW: NL B01.
2 Index page 1. INTRODUCTION 3 2. NORMS AND GUIDELINES 4 3. TESTED CONSTRUCTION 5 4. MEASUREMENTS Method Accuracy Restrictions due to the measurement set-up Classification according to table 1 of ISO Environmental conditions during the tests Results 8 A E-RA 2
3 1. INTRODUCTION At the request of ARMACELL UK Ltd sound insulation measurements (insertion loss, sound power insulation) have been carried out on Arma-Chek Sound Insulation in the Laboratory for Acoustics of Peutz bv, at Mook, The Netherlands (see figure 1) A E-RA 3
4 2. NORMS AND GUIDELINES The measurements have been carried out according to the Quality Manual of the Laboratory for Acoustics and to: ISO 15665:2003 Acoustics - Acoustic insulation for pipes, valves and flanges which norm refers to: ISO 3741:1999 NOTE: Acoustics - Determination of sound power levels of noise sources using sound pressure - Precision methods for reverberation rooms this international standard has been accepted within all EUcountries as European Norm EN ISO 3741:1999 A E-RA 4
5 3. TESTED CONSTRUCTION The description of the various constructions was taken from the data supplied by the principal. The masses have been checked by the staff of the laboratory. Several types of materials are combined in the variants tested. These materials are: Armafoam Sound 240 (called AFS in this report) 25 mm thick, with a density of 254 kg/m 3 (weighted) Class 0 (called CO in this report) 25 mm thick, with a density of 58 kg/m 3 (weighted) Arma-Chek R (called 2R in this report), 2.1 mm thick (measured); with a density of 1655 kg/m 3 (weighted) Armafoam barrier 10 kg/m 2 (called AFB10 in this report), 4.5 mm thick (measured); with a density of 2313 kg/m 3 (weighted) The materials have been put with no tension around the pipe and around each other. The joints between the AFS and CO have been glued together with no overlap, using Armaflex adhesive type 520. The joints between the 2R and the AFB10 have been glued together with an overlap, using Armaflex adhesive type 520. The layers of Arma-Chek R have been applied using a small overlap, the same adhesive has been used. Thickness ca. 106 mm total mass ca kg/m 2. The different materials have been applied to the test pipe in the following order : 1 x CO 2 x AFS 1 x AFB10 1 x CO 1 x 2R The results as presented here relate only to the tested items and laboratory conditions as described in this report. The laboratory can make no judgement about the representativity of the tested samples. A E-RA 5
6 4. MEASUREMENTS 4.1. Method The tests were conducted in accordance with the provisions of the test method ISO in the Laboratory for Acoustics of Peutz bv in Mook. A detailed description of the test set up has been given in the figure 2 of this report. A steel pipe (323 mm outer diameter; wall thickness 6.3 mm) is installed crossing the reverberation room, both ends of the pipe penetrating through the walls of the room. The penetrations have been sealed adequately. Noise is introduced in this pipe using a loudspeaker mounted in one end. The opposite end of the pipe is terminated by means of a closed anechoic termination. A microphone on a rotating boom is used in the reverberation room in order to measure the noise radiated from the pipe before and after insulation is applied to the pipe. A microphone is mounted inside the pipe in order to control the consistency of the noise source before and after insulation is applied to the pipe. The reverberation time of the room is also determined before and after insulation is applied to the pipe. From each set of measurements (sound pressure level and reverberation time) the sound power level L W radiated into the reverberation room is calculated according to ISO The reverberation room of Peutz has been accredited for this kind of measurements. The insertion loss D W caused by the cladding is now calculated as D W = L W,b - L W,c where: L W,b = the sound power level with the bare pipe L W,c = the sound power level with the cladded pipe 1 For this type of measurements the Laboratory for Acoustics has been accredited by the Dutch Council for Accreditation (RvA) as a test laboratory, registration number L334. A E-RA 6
7 4.2. Accuracy This norm relates to ISO 3741 and in there the next estimations regarding accuracy are mentioned: (reproduction of the table 1 of the ISO 3741) Table 1 Estimated upper values of the standard deviations of reproducibility 1 of sound power levels determined in accordance ISO 3741:1999 Band width midband frequencies [Hz] upper values of standard deviation of reproducibility [db] 1/3 octave 100 a to to to to /1 octave 125 a to A-weighted per Annex E 0.5 b a Recommendations for frequencies below 100 Hz: are given in Annex C b Applicable to a source which emits noise with a relatively flat spectrum in the frequency range 100 Hz to Hz 4.3. Restrictions due to the measurement set-up In the set-up as used the maximum measurable insertion loss is determined by the difference between (1): the sound pressure level in the reverberation room of the bare pipe and (2): the back-ground sound pressure level. This difference is determined and shown as the maximum measurable insertion loss in table 2 below. Table 2: maximum measurable insertion loss limited by the measurement set-up used octave band centre frequency, Hz D w Reproducibility R: when two tests are performed on identical test materials - in different laboratories - by different person(s) - under different environmental conditions - the probability will be 95% that the difference between the two test results will be less than or equal to R A E-RA 7
8 4.4. Classification according to table 1 of ISO In ISO a classification system is given in order to give a simple way to classify the material under test. It has to be mentioned that before comparison the octave-band insertion loss values have to be rounded to the nearest 0.5 db The table 1 of ISO is reproduced here partly, it is simplified for the nominal diameter of the used pipe (310.4 mm inner diameter, 323 mm outer diameter): Table 3: minimum insertion loss required for each class for a pipe diameter 300 D 650 mm octave band centre frequency, Hz Class minimum insertion loss A B C Environmental conditions during the tests Table 4: Environmental conditions during test room barometric pressure [kpa] Temperature [ C] relative humidity [%] Results The results of the measurements are given in the table 5 and in figure 3. A E-RA 8
9 Table 5: Measurement results VARIANT figure nr. frequency [Hz] INSERTION LOSS [db] values in () rounded to the nearest 0.5 db (see 4.4) 2 1/3 oct /1 oct (-2.5) (5.5) (17.5) (37.0) (54.5) (49.5) class (see 4.4) C (45.5) Measurements and calculations are made in 1/3 octave bands form 100 to Hz. From the final results the octave-band insertion loss has been calculated from 125 to 8000 Hz. From the rounded octave-band values the Class has been determined and stated. Mook, Th. Scheers Leader of the Laboratory ir. M.L.S Vercammen manager This report contains: 9 pages and 3 figures A E-RA 9
10 LABORATORY FOR ACOUSTICS PEUTZ bv Lindenlaan 41, NL-6584 AC MOLENHOEK (LB), THE NETHERLANDS Story OVERVIEW air supply silencer plenum silencer (E) (8) floor measurement of the reduction of transmitted impact noise (9) waste water level mm Ground level opening (A) (closed) w x h = 1.30 x 1.80 m plenum air supply installations (6) (5) (4) (A) reverberation room (B) (3) (C) (D) receiving room (2) sending room (1) sanitairy installations (7) suspended ceilings or raised floors workshop heating wc shower conference room analyses overhead door TEST OPENINGS (w x h in mm) (B) 1000 x 2200 (C) 1500 x 1250 (D) 4300 x 2800 (E) 4000 x m scale A E-RA figure 1
11 LABORATORY FOR ACOUSTICS Measurement set-up 8090 mm 5560 mm 0 X 0 Y anechoic termination 1 (A) pipe with insulation under test microphone sound source 5 (B) 6 7m revereration room (3) termination loudspeaker bare pipe in reverberation room A E-RA figure 2
12 LABORATORY FOR ACOUSTICS MEASUREMENT OF THE INSERTION LOSS DW ACCORDING TO ISO 15665:2003 principal: ARMACELL UK Ltd R; 2 mm CO; 25 mm AFB10; 4 mm AFS; 25 mm AFS; 25 mm CO; 25 mm STEEL; 10 mm db measured at: laboratory conditions signal: broad-band noise bandwidth: 1/3 octave 50 ISO 15665:2003 Class C2 40 insertion loss DW Insulat rel , mode 4 file: a1395 ##:292 1/3 oct. 1/1 oct k 2k 4k 8k Hz frequency /3 oct db /1 oct db publication is permitted for the entire page only Mook, A E-RA figure 3
Report. Draft. Laboratory for Acoustics
Report Member ONRI ISO-9001: 2000 certified Draft Laboratory for Acoustics Determination of the sound absorption (reverberation room method) of a suspended ceiling type Luxalon 80B and Derako Wooden Grills,
More informationEvidence of Performance Joint sound reduction of filling material
Evidence of Performance Test Report No. 13-002455-PR01 (PB Z6-K02-04-en-01) ift Rosenheim 13.09.2013 Client Soudal N. V. Everdongenlaan 18-20 2300 Turnhout Belgium Product Designation Thickness of sealant
More informationTesting Procedure: AS ISO
RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON
More informationKINETICS NOISE CONTROL TEST REPORT #AT001067
KINETICS NOISE CONTROL TEST REPORT #AT001067 KINETICS NOISE CONTROL PRODUCTS: o FLM- NEOPRENE PAD ACOUSTICAL RATINGS: o STC 69 o IIC 61 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA
More informationImportant Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA
Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure
More informationImportant Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA
Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure
More informationLABORATORY MEASUREMENTS OF THE SOUND REDUCTION INDEX ROCKWOOL ABLATIVE COATED BATTS
eport No. L/3132 Page 1 of 10 for ockwool UK Limited Pencoed Bridgend CF35 6NY Dated: 30 November 2009 LABOATOY MEASUEMENTS OF THE SOUND EDUCTION INDEX OF OCKWOOL ABLATIVE COATED BATTS eport Author: M
More information-Letter - Tables 1 and 2 - Figure 1 - Exhibits 1 through 6
213-93 May 29, 213 Mr. Doug Spear, Inc. 29 Rodd St. #2847 Midland, MI 48641 Subject: Sound Transmission Loss Results of Five Test Samples, Inc. Initial tests Pre-paid Dear Mr. Spear: At your request, (K&SE)
More informationANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS
ANSI/ASHRAE STANDARD 200-2015, METHODS OF TESTING CHILLED BEAMS NEMIC 2017 Agenda 1. Foreword 2. Purpose & Scope 3. Definitions 4. Instrumentation & Facilities 5. Test Methods 6. Reporting 7. Normative
More informationTEST REPORT NO
Istituto Giordano S.p.A. Via Rossini, 2-47814 Bellaria-lgea Marina (RN) - Italy Tel. +39 0541 343030 - Fax +39 0541 345540 istitutogiordano@giordano.it - www.giordano.it Cod. Fise./ Riva 00 549 540 409
More informationinter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE
Copyright SFA - InterNoise 2000 1 inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering 27-30 August 2000, Nice, FRANCE I-INCE Classification: 5.1 INCLUSION OF DAMPING
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Margate, FL. Sound Absorption CONDUCTED: 2015-09-15 Page 1 of 7 ON: Micro-Perforated Acoustical Aluminum Ceiling Tile with SoundTex - #MPA-1 TEST METHOD Riverbank Acoustical Laboratories is accredited
More informationKINETICS NOISE CONTROL TEST REPORT #AT001035
KINETICS NOISE CONTROL TEST REPORT #AT001035 KINETICS NOISE CONTROL PRODUCTS: o RIM I-2-16 ACOUSTICAL RATINGS: o STC 66 o IIC 63 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B-3140.1 KINETICS DRAWING
More informationACOUSTICAL DUCT & PIPE LAGGING INDUSTRIAL NOISE CONTROL PRODUCTS
23 07 13 ACOUSTICAL DUCT & PIPE LAGGING INDUSTRIAL NOISE CONTROL PRODUCTS ACOUSTICAL DUCT AND PIPE LAGGING Acoustical Lagging is wrapped around the outside of duct or pipe to reduce the radiated noise
More informationCONDUCTED: 26 November 2013 Page 1 of 6
FOR: Audimute Soundproofing Beachwood, OH Sound Absorption CONDUCTED: 26 November 2013 Page 1 of 6 ON: Audimute Isolé Plus External Barrier Sheet TEST METHOD The test method conformed explicitly with the
More informationPIP INSA1000 Acoustic Insulation Systems Specification
TECHNICAL REVISION April 2015 Insulation PIP INSA1000 Acoustic Insulation Systems Specification PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities,
More informationNEW! THE FLEXIBLE PROFESSIONAL INSULATION WITH REVOLUTIONARY CHARACTERISTICS. even easier to use
NEW! THE FLEXIBLE PROFESSIONAL INSULATION WITH even easier to use REVOLUTIONARY CHARACTERISTICS AF/ARMAFLEX the sustainable solution for use in air conditioning, refrigeration and process facilities The
More informationA Measurement Technique for Evaluating Insertion Loss of Cavity Fillers
A Measurement Technique for Evaluating Insertion Loss of Cavity Fillers Sachin K. Jain, Manasi Joshi, Paresh Shravage, N.V. Karanth NVH Laboratory, Automotive Research Association of India, Pune-411038
More informationNew Dutch Code of Practice NTR 5076 for equipment noise in dwellings and apartments
New Dutch Code of Practice NTR 5076 for equipment noise in dwellings and apartments Wim Beentjes MSC LBP Sight.BV PObox 1475 3430BL Nieuwegein, The Netherlands. Summary During the last decade there were
More informationslimlite Double Glazed Units BS EN 1279 Certificate Double Glazed Units
slimlite Double Glazed Units BS EN 1279 Certificate slimlite Double Glazed Units Timber Georgian Sash and Case with Super Slimlite Double Glazed Units with, 8mm or 10mm cavity will comply with Document
More informationCONDUCTED: 26 November 2013 Page 1 of 6
FOR: Audimute Soundproofing Beachwood, OH Sound Absorption CONDUCTED: 26 November 2013 Page 1 of 6 ON: Rigid eco-c-tex 2' x 2' Ice Cube Audimute Acoustic Coating TEST METHOD The test method conformed explicitly
More informationACOUSTIC FOLDING PARTITIONS PHONIC PROGRESS. designed for space
ACOUSTIC FOLDING PARTITIONS designed for space Parthos has been Europe's leading manufacturer of movable wall systems and folding doors, since 1968. The creation of space and freedom of design are the
More informationAnalysis Joint sound insulation of filler materials
Analysis Joint sound insulation of filler materials Testing Report 167 43780/Z2 Basis ift regulation SC-01 determination of joint sound insulation degree of 2002 Diagram Applicant Hanno-Werk GmbH & Co.
More informationinter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE
1 inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering 27-30 August 2000, Nice, FRANCE I-INCE Classification: 3.1 IN SITU METHODS FOR THE CHARACTERISATION OF ROAD
More informationTEST REPORT. Report Number : / Report Date : 27 / 07 / 2015
TEST REPORT Report Number : 060.416.1 / 2015 Report Date : 27 / 07 / 2015 Testing Reference Product Client : TS EN ISO 10140-2 Acoustics - Laboratory Measurement of Sound Insulation of Building Elements
More informationOptimizing Ceiling Systems and Lightweight Plenum Barriers
Optimizing Ceiling Systems and Lightweight Plenum Barriers Gary S. Madaras, ROCKFON, Chicago, Illinois Andrew E. Heuer, NGC Testing Services, Buffalo, New York Acoustics is one of the lowest scoring indoor
More informationMeasurement of the insertion loss of the pipe clamp FRSPlus for 4 sewer pipes
Prof. Dr.-Ing. H.M. Fischer Report Nr. FEB/FS-75/13 3e Measurement of the insertion loss of the pipe clamp FRSPlus for 4 sewer pipes Client: fischerwerke GmbH & Co. KG Weinhalde 14 18 72178 Waldachtal
More informationSolutions for industrial pipe work insulation
Solutions for industrial pipe work insulation Technical Insulation November 2006 Prefabricated insulation components for superior pipe work insulation Pipes are a crucial component in industrial processes.
More informationK-FLEX K-FONIK INDUSTRIAL
J a n u a r y 2 0 1 3 K-FLEX K-FONIK INDUSTRIAL Sound & Thermal Insulation design compliant with ISO 15665 www.kflexenergy.com Flexible Elastomeric Foam layer INSULATING PIPING WITH K-FLEX SHEETS > FIRST
More informationNoise Control. Commercial, Industrial, and Environmental Products and Solutions.
Noise Control Commercial, Industrial, and Environmental Products and Solutions www.kineticsnoise.com Commercial Duct Silencers Kinetics Noise Control offers the design and engineering assistance to integrate
More informationTROCELLEN TROSIL, TROSIL TECH
INSULATION TROCELLEN TROSIL, TROSIL TECH Superior acoustic insulation Acoustic insulation Trosil - Trosil Tech TROSIL Sound insulation of new generation, against impact sound, manufactured by TROCELLEN
More informationNEC Acostix. Sound Attenuation Calculations and Design Software. General Information
NEC Acostix Sound Attenuation Calculations and Design Software General Information NEC Acostix TM is an Excel-Based programmable sheets to help engineers and manufacturers design acoustic enclosures, rectangular
More informationROCKWOOL INSULATION & PROTECTION MATERIALS ROCKWOOL BLANKETS FACINGS TYPES APPLICATIONS
BLANKETS UNIPRO Rockwool Blanket conforming to ASTM C-553 and ASTM C-665 is a lightly bonded insulating material available with or without facing. These products can be faced on one side or both sides
More informationAchieving acoustical standards in the classroom Study of HVAC systems and classroom acoustics
Achieving acoustical standards in the classroom Study of HVAC systems and classroom acoustics Trane believes the facts and suggestions presented here to be accurate. However, final design and application
More informationFire protection, soundproofing and thermal insulation
ROMA INSULATION SYSTEMS Fire protection, soundproofing and thermal insulation Quick-assembly insulating panel, types FP, FV and FP Acoustic 02 ROMA quick-assembly insulating panel, types FP and FP+ Cladding
More informationFOR: CEMCO - California Expanded Metal Products Co. Sound Transmission Loss Test
FOR: CEMCO - California Expanded Metal Products Co. Sound Transmission Loss Test Industry, CA ON: Bare 1 Inch Thick USG LEVELROCK Brand CSD Floor Underlayment on USG LEVELROCK SRM-25 Sound Mat on CEMCO
More informationSWEDISH STANDARD SS
SWEDISH STANDARD SS 02 52 68 Approved 2001-06-21 Edition 1 Acoustics Sound classification of spaces in buildings Institutional premises, rooms for education, preschools and leisure-time centres, rooms
More informationSpecialists in Acoustic Flooring and House to Flat Conversions
Sound Solution Consultants Ltd Po Box 755 Capel St Mary Ipswich Suffolk IP9 2WF Tel No: 0845 5212096 Fax No: 0845 5212097 Email: mpconsultservice@aol.com Specialists in Acoustic Flooring and House to Flat
More informationPrediction of the acoustic performance of floor coverings on lightweight floors
Prediction of the acoustic performance of floor coverings on lightweight floors Catherine Guigou-Carter a CSTB, Center for Building Science and Technology 24 Rue Joseph Fourier 38 Saint Martin d Hères,
More informationRSIC-1 ACOUSTIC ASSEMBLY
RSIC-1 ACOUSTIC ASSEMBLY FLOOR/CEILING ASSEMBLY DIRECT FIX TO CONCRETE SLAB FCS3 DSWA FIIC 69 PAC INTERNATIONAL Inc. Toll Free 866-774-2100 Telephone 503-649-7700 CONSTRUCTION * Ceramic Tile * 1/4" James
More informationKinetics Noise Control
Kinetics Noise Control Acoustical Curtain Systems www.kineticsnoise.com Acoustical Curtain Systems Kinetics Noise Control s acoustical curtain systems are custom engineered to your application for acoustic
More informationEKVÜ seminar 11 mar 2016 Armacell/ Armaflex. Tallinn/ Estonia Petri Ojanen
EKVÜ seminar 11 mar 2016 Armacell/ Armaflex Tallinn/ Estonia Petri Ojanen Condensation Corrosionunderinsulation Installation conditions - Temperature -Moisture Condensationon top of Insulation Wall Thickness
More informationAcoustic Design Criteria
Apartment Acoustics Apartment Buildings Acoustic Design Criteria Building Code of Australia: - Intertenancy walls and floors - Corridor walls and doors - Floor impact isolation - Lift, stair and core walls
More informationApplied Noise Control. D. W. Herrin, Ph.D., P.E. University of Kentucky Department of Mechanical Engineering
D. W. Herrin, Ph.D., P.E. Department of Mechanical Engineering Outline of Topics 1. Introduction 2. Noise Control at Source 3. Noise Control of Transmission Path 4. Protection at Receiver 5. Summary 2
More informationPacifyre MK II Fire Sleeves
Pacifyre MK II Fire Sleeves Fire, smoke and sound barrier Fire resistant for 240 minutes Easy to install Wide range of applications Conforms to BS standards Easy self installation in accordance with the
More informationHILTI CP 674 Cavity Closure For Rainscreen / Cladding Systems
Data Sheet HILTI CP 674 Cavity Closure For Rainscreen / Cladding Systems The enclosed pages are taken from the Hilti Firestop Systems Manual Edition April 2011 Supported by additional standard details
More informationGIB Quiet Clip GIB CBI March Features and Benefits
CBI - 5113 March 2002 GIB Quiet Clip Features and Benefits No special flooring systems required Easy fit Installation Significantly improves low frequency sound transmission Significantly improves low
More informationmovable walls Space Optimal Solutions
Space Optimal Solutions www.movablewall.co.uk by dividing, we multiply Prestige-Space for every occasion From a large meeting room you then have several smaller ones at your disposal Your hotel instantly
More informationModuline. Acoustic Enclosure System. Rugged Noise Control Structures Using Acoustically Rated & Field Proven Demountable Components
Moduline Acoustic Enclosure System Rugged Noise Control Structures Using Acoustically Rated & Field Proven Demountable Components Lab certified acoustic ratings Broad range of performance levels 63 Hz
More informationThis page was. intentionally. left blank
CONSTRUCTION Measurement of Airborne Sound Insulation of 8 Wall Assemblies Measurement of Airborne and Impact Sound Insulation of 29 Floor Assemblies Nordic Engineered Wood Report No. A1-006070.10 July
More informationSection SoundPly LR M25 Acoustic Ceiling Panels
Section 095126 Acoustic Ceiling Panels PART 1 GENERAL 1.1 RELATED DOCUMENTS 1.2 SUMMARY A. Drawings and general conditions of the Contract, including General and Supplementary Conditions and Division 1
More informationProduct Data Sheet. Product: Benchmark Wall Liner System
APPLICATION The Benchmark Wall Liner system is to be used as an insulated composite wall panel under site applied fully supported or self-supported aluminium, copper, zinc and stainless steel cladding
More informationNoise-Foil Acoustic Metal Panels Sound Absorption Systems for Industry & Commerce
Noise-Foil Acoustic Metal Panels Sound Absorption Systems for Industry & Commerce Abuse resistant metal jacketed constructions Lab certified acoustic performances Suitable for interior and exterior installations
More informationU L - E U C E R T I F I C A T E
U L - U C R T I F I C A T Page 1/8 Date of Issue 15-07-02 Certificate Holder Manufacturer Certified Product Type Product Trade Name Trademark Rating/Classification ASTROFLAM FIRSALS LIMITD UNIT 8 TH IO
More informationThe effect of additional thermal lining on the acoustic performance of a wall
The effect of additional thermal lining on the acoustic performance of a wall J. Nurzynski Building Research Institute, Filtrowa Str. 1, 00-611 Warsaw, Poland j.nurzynski@itb.pl 5417 External thermal insulation
More informationPart E robustdetails. robustdetails. January 2017 Update Pack. Dear Colleague,
Part E Pack Dear Colleague, This is the first 2017 update to the Part E Robust Details Handbook. In this update pack, we have focussed on clarifying the situation on incorporating underfloor heating (UFH)
More informationAcoustical characterization of the underground chapels of the new Holy Trinity church in the Fatima shrine, Portugal
Acoustical characterization of the underground chapels of the new Holy Trinity church in the Fatima shrine, Portugal António P. O. Carvalho Lab. of Acoustics, Faculty of Engineering, University of Porto,
More informationJune Residential Refurbishment Separating walls
June 2010 Residential Refurbishment 3.6.1 Separating walls Residential refurbishment 3.0 Residential Refurbishment Separating Walls Contents Introduction find online page Solution optimiser and pathfinder
More informationCore. Thickness. Biological
LOUVRE DW Design Wall Series Benchmark Louvre forms part of the Design Wall Series. It is a secret fix system that can be laid horizontally or vertically giving the appearance of a Louvre Wall. Available
More informationLINK. By ITEMDesign Works Javier Cuñado.
By ITEMDesign Works Javier Cuñado WHAT IS? The new trends in office design suggest combining privacy with open and collaborative offices, where creativity and communication flow in a natural way. This
More informationVALIDATION REPORT No
Istituto Giordano S.p.A. Via Rossini, - 4784 Bellaria-Igea Marina (RN) - Italia Tel. +39 054 343030 - Fax +39 054 345540 istitutogiordano@giordano.it - www.giordano.it PEC: ist-giordano@legalmail.it Cod.
More informationWith a presence in over 50 countries, the company offers lighting solutions for every kind of environment, from offices to production lines to
EN 2 With a presence in over 50 countries, the company offers lighting solutions for every kind of environment, from offices to production lines to commercial areas. Constant research has led 3F Filippi
More informationAcoustics 08 Paris 3059
Innovative building systems to improve the acoustical quality in lightweight masonry constructions: Application of resilient joints at junctions - PART 2: Study cases modelled according to the standard
More informationEdition October May (always refer to the latest manual as set out on
LOXO PANEL INTER AND BLOCK TENANCY SYSTEMS WALLS TECHNICAL FIRE AND ACOUSTIC MANUAL REPORT PRODUCT DESCRIPTION AND BUILDING SYSTEM DETAILS Edition October May 2015 2014 (always refer to the latest manual
More informationGLAUNACH THE SILENCER HANDBOOK INSULATION SUPPLEMENTARY ACOUSTIC SHIELDING OF SILENCERS, PIPES & CO GLAUNACH GMBH ALL RIGHTS RESERVED -
GLAUNACH THE SILENCER HANDBOOK INSULATION SUPPLEMENTARY ACOUSTIC SHIELDING OF SILENCERS, PIPES & CO GLAUNACH GMBH 2010 - ALL RIGHTS RESERVED - Part VIII page 2 of 9 There are two main motivations for adding
More informationLARGO. Angle sound attenuator with recessed connection for rectangular ducts QUICK FACTS
Angle sound attenuator with recessed connection for rectangular ducts QUICK FACTS Remarkably space-saving rectangular sound attenuator Excellent aerodynamic characteristics Very low pressure drop acoustic
More informationDelivery efficiency of the Jaga Low H 2 O heat exchanger in a Tempo enclosure
Delivery efficiency of the Jaga Low H 2 O heat exchanger in a Tempo enclosure Determination of the delivery efficiency for a quality declaration for the ISSO database Delivery efficiency of the Jaga Low
More informationInsulated Panel System. QuadCore IND. Superior FIRE Protection. Unrivalled THERMAL Efficiency. ENHANCED Environmental Credentials
1 Superior FIRE Protection 2 Unrivalled THERMAL Efficiency 3 ENHANCED Environmental Credentials 4 Longest Performance GUARANTEE Insulated Panel System QuadCore IND Technical Information Projet / Usage
More informationOG-100 ICC-SRCC TM CERTIFIED SOLAR COLLECTOR # D
accredited and EPA recognized Certification Body, in accordance with the SRCC OG-100 Certification Program, as defined in SRCC OG-100, Operating Guidelines and Minimum Standards for Certifying Solar Collectors.
More informationNEW THE FLEXIBLE INSULATION WITH ANTIMICROBIAL PROTECTION
THE FLEXIBLE INSULATION WITH ANTIMICROBIAL PROTECTION NEW Microban technology System warranty years Supervised per formance: Euroclass (B/B L -s3, d0) l 0 ºC 0,033 W/(m K) µ.000 Microban + + antimicrobial
More informationSOUND INSULATION TESTING IN DWELLINGS
SOUND INSULATION TESTING IN DWELLINGS Chris Dilworth, AWN Consulting This Presentation Discusses the standards by which we judge sound insulation performance. Presents the results of sound insulation tests
More informationEvaluation VerteTek Coat of Silence
DLM Enterprises Noise Control, Acoustics and Testing 1515 Meadows Road, Suite B Geneva, IL 60134 Evaluation VerteTek Coat of Silence Acoustical Evaluation of One and Two Sided Applications of VerteTek
More informationNoise Reduction for 4WD Bus and Coach
Noise Reduction for 4WD Bus and Coach Engineering Test Report and Recommendations Megasorber soundproofing provides cost effective solutions by reducing (1) the low frequency noise structure-borne noise
More informationAcoustic design of industrial spaces. The reduction of noise levels and increase of production
Acoustic design of industrial spaces The reduction of noise levels and increase of production Contents. Introduction. Acoustic measurements Effect of acoustical treatment with suspended ceiling and wall
More informationwalraven.com BIS Pacifyre AWM III Fire Collar BIS Pacifyre IWM III Fire Strip
walraven.com BIS Pacifyre AWM III Fire Collar BIS Pacifyre IWM III Fire Strip Member of: BIS Pacifyre AWM III Fire Collar Product description Built-up fire collar for plastic (combustible) pipes and pipe
More informationThe uncertainty in sound insulation of an industrially prefabricated lightweight timber construction
The uncertainty in sound insulation of an industrially prefabricated lightweight timber construction Rikard ÖQVIST 1 1 Tyréns AB, Sweden ABSTRACT The variations in sound insulation are often large for
More informationRegupol CONSTRUCTION. Regupol BA. Heavy duty screed isolation. Regupol BA. Excellent impact performance.
CONSTRUCTION Regupol Heavy duty screed isolation Excellent impact performance www.berleburger.de CONSTRUCTION The properties heavy duty screed isolation Offers long term performance, with minimal creep,
More informationEffective Noise Barrier Design and Specification
Effective Noise Barrier Design and Specification Giles Parker Managing Director, Sound Barrier Solutions Ltd, Market Harborough, United Kingdom Chair CEN TC226/WG6/TG1 for Road Traffic Noise reducing Devices
More informationDIVISION 13 - SPECIAL CONSTRUCTION SECTION ACOUSTICAL PANEL ENCLOSURE
DIVISION 13 - SPECIAL CONSTRUCTION SECTION 13080 - ACOUSTICAL PANEL ENCLOSURE 1 GENERAL 1.01 SUMMARY A. ACOUSTIC ENCLOSURE CONSISTING OF WALLS, CEILING, STRUCTURAL FRAMING, CONNECTING MEMBERS, DOORS, WINDOWS,
More informationTechnical Assessment Body issuing the ETA: Kiwa Nederland B.V. Sinh Board
Member of Kiwa Nederland B.V. www.eota.eu Sir Winston Churchilllaan 273 NL-2288 EA Rijswijk Postbus 70 NL-2280 AB Rijswijk Tel.: +31 (0)88 998 44 00 Fax: +31 (0)88 998 44 20 E-mail: info@kiwa.nl European
More informationDesign Standards Brief Section 13 Acoustics
Property Services Design Standards Brief Section 13 Acoustics Issue 6 2009 Section 13 Acoustics 13 CONTENTS 13.1 INTRODUCTION...3 13.2 NOMENCLATURE...3 13.3 APPLICABLE STANDARDS...4 13.4 ARCHITECTURAL
More informationGypLyner UNIVERSAL Metal framed wall lining system
Metal framed wall lining system Pizza Express, York 30 Metal framed wall lining system wall lining system is a cost-effective, virtually independent metal frame drylining. It is a general purpose system
More informationTL: Transmission Loss ASTM E-90
Calculation of: STC (Sound Transmission Class), R W (European) as per ISO 717-1, MTC (Music/Machinery Transmission Class), OITC (Outdoor-Indoor Transmission Class) Note: This document is an extension/adaptation
More informationHILTI CP 601S Elastomeric Firestop Sealant
Data Sheet HILTI CP 601S Elastomeric Firestop Sealant The enclosed pages are taken from the Hilti Firestop Systems Manual Edition April 2011 Supported by additional standard details For Material Safety
More informationRecommendations for additional fire protection of structural elements
ANNEX 6 Recommendations for additional fire protection of structural elements 1 Scope This Annex contains a series of recommendations applicable to structural concrete structures which, for general fire
More informationÖsterreichisches Institut für Bautechnik Schenkenstrasse Vienna Austria T F
Authorised and notified according to Article 10 of the Council Directive 89/ 106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating
More informationCovering (Month/Year): January/2012 Submitted (date): 06/02/2012. Cotentin, Paris, France. van der Lelijstraat, Delft, the Netherlands
BEEM Up WP2 Monthly Update template, material for the official website Covering (Month/Year): January/2012 Submitted (date): 06/02/2012 Construction site: Brogården, Alingsås, Sweden Cotentin, Paris, France
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: PAC INTERNATIONAL, LLC
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: PAC INTERNATIONAL, LLC TYPE: Wall, Steel (0.018" / 25 ga), RSIC-V, STC 67 DATA FILE NO: E4748.01A STC 67 OITC 56 Test Specimen Identification: (Source
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 8/0 Sliding Patio Door Summary of Test Results ATI Data File No. Glazing (Nominal Dimensions) STC
More informationLTG Air Diffusers. Product Overview. Outstanding technique for highest demands. Unique in comfort, acoustics and design.
The Innovation Company LTG Incorporated Product Overview LTG Air Diffusers Outstanding technique for highest demands. Unique in comfort, acoustics and design. LTG Incorporated 1 LTG Air Technology Solutions
More informationP.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Determination of the fire resistance according to EN 1364-1:1999 and FprEN 1364-1:2014
More informationThe Optimization of a Wooden Floor Design Based on Validated Finite Element Models
The Optimization of a Wooden Floor Design Based on Validated Finite Element Models Jeffrey MAHN 1 ; Carl HOPKINS 2 ; Marios FILIPPOUPOLITIS 2 ; Ulrich SCHANDA 3 ; Raphael VÖLTL 3 ; Luboš KRAJČI 4 1 National
More informationFIRE PROTECTION. GTEC Shaftwall systems 244 GTEC Shaftwall Stairwell systems 248 GTEC Horizontal Shaftwall systems 249 GTEC Encasement systems 250
FIRE PROTECTION GTEC Shaftwall range uses a specially designed system to protect voids and shafts in buildings. It resists pressure changes and enables installation from one side of the shaft only. GTEC
More informationTI-LINE TILUX DURABASE. Borderless Shower Areas
TI-LINE TILUX DURABASE Borderless Shower Areas Borderless Shower Areas TI-LINE The patented linear drainage system that makes a perfect junction with walls. An overview of all the system s components along
More informationHILTI CP 657 Firestop Brick
Data Sheet HILTI CP 657 Firestop Brick The enclosed pages are taken from the Hilti Firestop Systems Manual Edition April 2011 Supported by additional standard details For Material Safety data sheets visit
More informationTHE FLEXIBLE INSULATION SYSTEM TO PREVENT CONDENSATION AND ENERGY LOSSES
THE FLEXIBLE INSULATION SYSTEM TO PREVENT CONDENSATION AND ENERGY LOSSES Reliable condensation control with closed-cell Armaflex structure High flexibility and ease of installation. Increases equipment
More informationTIMBER REFLECTIVE NOISE BARRIER - ACOUSTIC FENCING. Acoustic Barriers. Gramm Barrier Systems Registered in England and Wales No:
TIMBER REFLECTIVE NOISE BARRIER - ACOUSTIC FENCING Acoustic Barriers Gramm Barrier Systems Registered in England and Wales No: 05836133 We have put a lot of thought into our noise barrier range and have
More information