Instructions for use - tender specifications for UNIGLAS FACADE:

Size: px
Start display at page:

Download "Instructions for use - tender specifications for UNIGLAS FACADE:"

Transcription

1 Instructions for use - tender specifications for UNIGLAS FACADE: The performance limit is the glued laminated timber post and beam construction to be provided by the customer. The minimum timber quality of the construction must correspond to grade GL 24 for glued laminated timber. The minimum width of posts and beams is 60 mm. The structural design must prove that the beam has a maximum deflection of l/500 from the weight of the beam itself including the weight of the insulating glass. Contrary to DIN 18202: and DIN : , the installation inaccuracy (dimensions) of the post and beam construction is maximum ± 2 mm (=> maximum tolerance 4 mm) with regard to the reference point of a reference axis both in height and in the axes. The offset of the posts from the beams at the level of the insertion elements must not exceed ± 0.5 mm. The maximum sag of the beams must be limited to fmax l/500. Beam axis 2 Beam axis 1 h Nominal axis dimension ± 2 mm Beam axis 0 Post axis n b n Nominal axis dimension ± 2 mm Example of installation inaccuracies for nominal dimension transgression with the post (beam dimension h arises parallel to reference point = post axis 0 / beam axis 0): Other performance limits are lateral building connections, as well as connections to the base, eaves or attic, including insulation and cladding with flashings, as well as exterior sun protection. The glazing is not further specified. Any functional glazing from the corresponding proposal, the UNIGLAS product range or even panels, PV or solar thermal energy modules in insulating glass technology can be used here. Tenders for a window and/or glazed doors with turn-tilt function as an insert element are invited by way of example. Accordingly tenders are also invited for sliding sashes or lift-slide sashes as an insert element, as presented in the guiding notes.

2 UNIGLAS Tender Specifications for Special contractual conditions: Insulating glass elements The insulating glass elements used and integrated must bear the CE mark, as well as the Ü-mark for multipane insulating glass in Germany in accordance with Bauregelliste A, Part 1, Annex Glass Clear, transparent base glass with maximum colour neutrality must be used. Connecting rods Only connecting rods made of birch veneer plywood in accordance with EN 636 "S" with bonding class 3 in accordance with EN with a minimum thickness of 12 mm, surface 2 x ground on all sides (grain 120 and grain 180) maybe used. For TGC façades with buildings of a bracing function, the face veneer layer of the birch veneer plywood must always run along the rod axis i.e. parallel to the glass edge. Humidification of the connecting rods that exceeds an 18% moisture content of the timber must be avoided. Thick layer of varnish The connecting rod must have a thick layer of varnish consisting of a water-based, pigmented woodpreservative impregnation of "Aquawood TIG Weiß, nominal application quantity of 200 g/m², a waterbased intermediate coating of "Aquawood Spritz-Intermedio Jet', nominal application quantity of 125 to 150 g/m², as well as a water-based, pigmented top coat of "Adler Acryl-Spritzlack Q10 M" nominal application quantity of 250 bis 300 g/m² (250 bis 300 µm) according to the technical specification sheets of ADLER- WERK Lackfabrik, A-6130 Schwaz. However, the adhesion area must be completely free of any coating. Over-coats and subsequent removal by milling is not permitted. Wood screws For screwing the TGC element to the post and beam timber sub-structure, only anti-corrosion wood screws Ø 5 mm; length 70 mm with general technical approval or in accordance with DIN 1052 are permitted e.g. Würth Assy 3.0 wood screw 5.0 / 70 mm shaft mounted counter-sunk head, galvanised or yellow passivated: General technical approval Z Works certificates and tests The compliance of the "birch veneer plywood EN 636 "S"" connecting rod with bonding class 3 in accordance with EN 314-2, the surface treatment, adherence to timber moisture, if necessary to layer structure (for supporting buildings with a bracing function of the TGC element), the thick layer of varnish, as well as the layer thickness must be confirmed with the manufacturer of the bonding through works certificate "2.1" in accordance with DIN EN 10204: Only connecting rods from processing plants that have undergone an initial inspection by one of the "Supervisory and Certification Boards" listed according to trade in the Nando list and which voluntarily undergo regular external inspections by a corresponding institute may be used. Only insulating glass produced by manufacturers that undergo a voluntary third-party inspection performed by a test institute recognised by the GMI, KOMO or a corresponding Austrian body may be used. Evidence of the last two test reports must be submitted upon request. Page 2 of 7 Version: Sept. 2013

3 Glass dimensions and applicable standards EN 1991 For construction projects in Germany the necessary glass thickness, as well as evidence of the supporting bond for the SSG (structural sealant glazing), must comply with the TRLV, ETAG 002, the general technical approval for UNIGLAS FACADE and/or the requirements of approval for individual cases and the relevant applicable technical regulations of DIBt and/or in accordance with DIN and any relevant building standards. The established building regulations and standards in each respective federal state shall take precedence. In Austria, dimensioning observes ÖNORM B 3716 in conjunction with the relevant applicable national standards and legal provisions. For construction projects in other countries, the local established building regulations and standards shall apply. Within the jurisdiction of European standards, the actions in accordance with the corresponding national versions of EN 1991 must be applied. If the EN 1991 standards have not yet been implemented by building authorities, the corresponding national standards must be observed. The building height is m above sea level, in wind zone, inland, postcode/zip region: Dimensions of the building b x l x h in m Exterior walls are not permeable. DIN 1961 The general contractual terms and conditions for the execution of construction works (VOB/B) and the general technical contractual terms and conditions (VOB/C) shall apply in their latest versions. ÖNORM A 2060 and ÖNORM B 2110 The general provisions of a contract for services and construction ÖNORM B 2227 Glass works - work contract DIN 4108 The thermal transfer coefficient of the façade Ucw is specified in the performance description. DIN EN The calculated value of the evaluated sound insulation value R w,r according to Table 40 in DIN 4109/A1 version January 2001 for the façade element is requested in the performance description. EN 636 Plywood - Requirements DIN For roof glazing, laminated safety glass must be integrated in the lower pane by derogation from VOB/C DIN Page 3 of 7 Version: Sept. 2013

4 Regulations Technical regulations must be observed for the glazing design. The most important regulations are listed below and are valid in the corresponding current versions. - General technical approval for UNIGLAS FACADE and/or approval for individual cases for the object. - Manual for the design and manufacture of UNIGLAS for UNIGLAS FACADE - UNIGLAS glazing guidelines, latest version - Guidelines of the Institute of Window Technology, Rosenheim - Guidelines of the Institut des Glaserhandwerks für Verglasungstechnik und Fensterbau, Hadamar - Passive house suitable components of the Dr. W. Feist Passive House Institute, Darmstadt - Standards and technical regulations introduced by building authorities - Guidelines for assessing the visual quality of glass for the building industry, issued by the Technical Advisory Board of the Institut des Glaserhandwerks für Verglasungstechnik und Fensterbau, Hadamar and by the Technical Committee of the Bundesverband Flachglas e.v., Troisdorf *) - Pamphlet 006 of the Bundesverband Flachglas e.v. "Visual guidelines for systems in gaps between panes" issued by the Technical Committee of the Bundesverband Flachglas e.v., Troisdorf - Pamphlet 006 of the Bundesverband Flachglas e.v., "Guidelines for assessing the visual quality for systems in insulating glass units" issued by the Technical Committee of the Bundesverband Flachglas e.v., Troisdorf *) in Austria shall apply contrary to the "Guidelines for assessing the visual quality of glass for the building industry" ÖNORM B 3738 Plate glass in the building industry - Insulating glass - Requirements in visual quality Technical data - The technical data and functional values indicated are based on information from base glass manufacturers and were determined on the basis of each applicable product standard. - The functional values determined by test certificate refer to test pieces in the standard dimensions intended for the test. - Corresponding deviations from the declared values occur due to the reliable tolerances of incoming products. - Lighting and radiometric parameters must be determined in accordance with EN The thermal transfer coefficient Ug value must be calculated with a validated programme in accordance with EN 673. The validation must come from a notified body approved by the DIBt and/or one listed in the Nando list. Test certificates in accordance with EN 674 or 675 shall only be approved in justified, exceptional cases due to the insufficient comparability of values in accordance with EN Page 4 of 7 Version: Sept. 2013

5 Performance description Create a verifiable, static calculation of the TGC elements. In particular the glass thicknesses of the insulating glass elements must be determined and the supporting insulating glass bond for the loading conditions, wind suction and climate load, the bond of the connecting rod and the attachment of the TCG element to the substructure including the normal and shear stress must be verified. The submission of a structural analysis is also permitted by way of evidence. Corresponding component tests must be submitted for own weight deflection of the insulating glass, as well as for evidence of the emergency support in the event of failure of the static adhesive joint. Fixed sum EUR.. Determine the thermal transfer coefficients Ucw of the complete façade. Fixed sum EUR.. Manufacture, supply and install the TGC elements consisting of multi-pane insulating glass UNIGLAS. or similar with connecting rod adhered in the factory. The PP covers the supply and installation of the glass supports in accordance with static and component test (system section: SYS-010). Supplier of the TGC elements: partner company of UNIGLAS GmbH & Co. KG The insulating glass must be manufactured from 2 x ESG-H in accordance with the German Building Rules List (BRL). The middle pane of triple-glazed insulating glass made of ESG in accordance with EN or ESG-H, thickness of the individual panes according to static calculations, but at least 6 mm, thermotechnically improved edge bond made of stainless steel e.g. Chromatech Plus and/or Chromatech ultra black, SIKA IG-25 HM Plus or SIKA SG 500 silicon, height of the adhesive/sealant over the spacer bar according to static calculations, but at least 15 mm. The connecting rod must be checked for dust, damages and timber humidity and expertly glued to the insulating glass, which has been cleaned beforehand, using Ottocoll S 660, observing defined adhesive geometry, ensuring that there are no holes or bubbles and with the correct interlocking arrangement according to the workshop drawing supplied. The adhesive surface on the connecting rod must be free of varnish residue. Rods that do not meet requirements must be sorted out and may not be used. The adhesive geometry must correspond to the static calculation. The adhesion may not take place on the construction site. The adhesive joint must be fully hardened in according to manufacturer's specifications before installing the TGC element. The dimensional accuracy, planarity and parallelism of the glued laminated timber post and beam construction provided by the customer must be checked and the tolerances determined before installation. The timber construction must be masked with a compressible Duplocoll adhesive tape before inserting the elements to ensure air and driving rain impermeability and to serve as a vapour barrier. Longitudinal joints in the adhesive tape on the post must be avoided. The connection joint of the adhesive tape on the beam must be tight i.e. free of open joints. Any unplanned moisture penetration into the elements during installation must be avoided. The TGC element must be hoisted, aligned and screwed to the post and beam supporting structure. When screwing the TGC element to the supporting structure, it must be ensured that glass substrate and the thick layer of varnish on the connecting rod is not damaged. Technical data of the element and insulating glass: Ucw = W/m²K RW,R =. db Ug = W/m²K g =.. V =.... m² PP.. EUR / m² EUR Page 5 of 7 Version: Sept. 2013

6 As item..., but with supporting function of category The glass structure must consist of at least 1 pane of laminated safety glass (VSG). The glass type, thickness and structure shall comply with the static calculation in conjunction with the component analysis. When using annealed glass (TGV), TGV must be used with valid general technical approval. The PP includes mechanical safety devices in accordance with the system section SYS-020 in the number established in the corresponding category of the component test. The remaining performance corresponds with item.. Technical data of the element and insulating glass: Ucw = W/m²K RW,R =. db Ug = W/m²K g =.. V =.... m² PP.. EUR / m² EUR Allowance for the execution of a glazed corner version B in accordance with connection detail AND m PP.. EUR / m EUR Pre-positioning allowance for the execution of frame enamelling on the insulating glass for covering the edge seal. Only enamel colours that are compatible with the construction silicon and approved by building authorities in accordance with ETAG 002 (with positive verification of the adhesion and ductility behaviour of the construction silicon) may be used e.g. Ferro group B (zinc-boron-silicates), collection 140, general technical approval no. Z The adhesion and ductility behaviour must be established by an expert opinion from a notified institute... m PP.. EUR / m EUR Page 6 of 7 Version: Sept. 2013

7 Allowance for the supply and installation of an insert element in the form of a timber and metal window and/or glazed door. Timber-aluminium compound system, solid wood species.., Exterior frame flush-mount Frame and sash frame profile sharp-edged, sash opens inward, inside colour, Exterior surface powder-coated, colour (coating).., standard fittings according to tenderer specifications (please indicate product):... Fittings covered. Cover strips/cover profiles connecting joints' ', 4-sided, EPDM (APTK) sealing profile, as middle seal in the sash frame. Attachment to the post and beam construction using screwed connecting rod with interlocking according to a workshop drawing. Multi-pane insulating glass UNIGLAS. or similar, profiled glass holding bar, attached with wire pins, zinccoated, DIN Part 3. Joint permeability and driving rain permeability DIN stress group B, nominal value of the thermal transfer coefficient (referring to standard size 1.23 m x 1.48 m, frame proportion 30 % Design: Window, one-piece as turn-tilt sash, Carcass dimensions (W x H) '. X.. mm'. Design in accordance with connection details AND-105 / AND-110 Technical data of the element and insulating glass: Ucw = W/m²K RW,R =. db Ug = W/m²K g =.. V =.... Unit PP.. EUR / unit EUR Execution of the weather-seal joints with Ottoseal S 7. Joint width 20 mm. The joint must be backfilled with a closed-cell PE round cord Ottocord PE B2 to prevent three-point adhesion and to ensure ventilation of the joint. Other sealants may only be used with evidence of compatibility with the surfaces to be bonded and the insulating glass frame composite. The unit price includes the scheduled opening of the rebate base ventilation and drainage in the base, eaves and attic area... m PP.. EUR / m EUR Allowance for production, supply, screwing in and professional sealing of mechanical pane safety mechanism prescribed by building authorities (in Germany from a glazing height of 8.00 above the ground; in Austria generally) in accordance with system section SYS Unit PP.. EUR / unit EUR Page 7 of 7 Version: Sept. 2013

In accordance with DIN and DIN , this is a structure with the utility class GK 0.

In accordance with DIN and DIN , this is a structure with the utility class GK 0. Special preliminary remarks Application In accordance with DIN 68800-1 and DIN 68800-2, this is a structure with the utility class GK 0. Substructure Post-and-beam structure made of timber, consisting

More information

OTTO Professional Guide. Perfect assembling of timber glass-composite units

OTTO Professional Guide. Perfect assembling of timber glass-composite units Perfect assembling of timber glass-composite units 2 THE OTTO BUILDING WITH TIMBER-GLASS-COMPOSITE UNITS Photo credits: North German Centre for Sustainable Construction, Verden 9999868 HGV-Elemente perfekt

More information

OPTIWIN MOTURA. Technical Description. Synopsis:

OPTIWIN MOTURA. Technical Description. Synopsis: Technical Description OPTIWIN MOTURA Synopsis: 1. Product "OPTIWIN MOTURA" General Description... 2 2. Materials... 3 2.1. Wood... 3 2.2. Surface... 3 2.2.1. Inside... 3 2.2.2. Outer shell... 4 2.3. Glazing...

More information

Suitable for large-area facades, commercial properties, conservatories, extensions plus detached, semi-detached and terraced houses.

Suitable for large-area facades, commercial properties, conservatories, extensions plus detached, semi-detached and terraced houses. Timber-Glass-Composite elements (TGC) Architecture is based on three principles: Firmitas, Utilitas and Venustas. Vitruv, Roman architect Naturalness, energy efficiency and structural flexibility: uniglas

More information

cero by Solarlux cero by Solarlux cero opens rooms with extensive glass panels: impressive transparency dissolves the line between inside and outside. As a brand of Solarlux, the leading supplier in the

More information

Translation authorized by DIBt

Translation authorized by DIBt Date: Reference: 11.01.2012 I 38-1.70.3-1/12 Approval number: Z-70.3-175 Validity from: 11 January 2012 to: 11 January 2017 Applicant: seele sedak GmbH & Co. KG Einsteinring 1 86368 Gersthofen, Germany

More information

The TKI success kit. The excellently thought-out aluminium profi le system for windows, doors and façades.

The TKI success kit. The excellently thought-out aluminium profi le system for windows, doors and façades. The TKI success kit The excellently thought-out aluminium profi le system for windows, doors and façades. Presented by MKF Metallbaukontor Frankfurt GmbH More than 40 years of excellent system engineering

More information

PREFA Aluminiumprodukte GmbH Page 1 of 21

PREFA Aluminiumprodukte GmbH Page 1 of 21 Tender Specifications 120901 PREFA Shingles_2012 ---------------------------------------------------------------------------------- 01. Text GENERAL PRELIMINARY REMARKS Roof ----------------------------------------------------------------------------------

More information

Kingspan Day-Lite Klick

Kingspan Day-Lite Klick Insulated Panel Envelope Systems Roof Wall Façades Lighting Rooftop PV Coldstore Structural Products Cleanrooms UK & Ireland Kingspan Day-Lite Klick Installation Guide Page 2 Accessories Overview Designation

More information

More space, more light, a better quality of life: The high insulated folding sliding doors from Schweizer.

More space, more light, a better quality of life: The high insulated folding sliding doors from Schweizer. More space, more light, a better quality of life: The high insulated folding sliding doors from Schweizer. 2 An easy perspective: Folding sliding doors enable greater transparency. Whether for a modern

More information

RUUKKI FORMA DESIGN INSTRUCTION

RUUKKI FORMA DESIGN INSTRUCTION www.ruukki.com RUUKKI FORMA DESIGN INSTRUCTION 1. General Ruukki Forma is a complete façade system in which Ruukki energy panels form an energy efficient base structure and Ruukki cladding products finalize

More information

Sandwich panel SPA Product description

Sandwich panel SPA Product description Sandwich panel SPA Product description Ruukki offers a sandwich panel system that combines an attractive appearance with excellent thermal insulation and fire-resistance. The panels are of a lightweight,

More information

Product information Roof balcony CABRIO GDL

Product information Roof balcony CABRIO GDL Edition 2.0 01.04.2016 Product information Roof balcony CABRIO GDL Product description High quality natural pinewood coated with impregnation and layers of water-based acrylic white paint or clear lacquer

More information

Product information Vertical window element VFE

Product information Vertical window element VFE Edition 2.0 01.01.2017 Product information Vertical window element Product description High quality natural pinewood coated with impregnation and layers of water-based white paint or acrylic clear lacquer

More information

Product information Centre-pivot white-painted roof window GGL

Product information Centre-pivot white-painted roof window GGL Edition 2.0 13.09.2017 Product information Centre-pivot white-painted roof window Product description High quality natural pinewood coated with impregnation and layers of water-based acrylic white paint

More information

PVC-U: Innovations and product ranges

PVC-U: Innovations and product ranges PVC-U: Innovations and product ranges Be successful with Schüco 4 pillars of success 1 2 3 4 Product innovations Ranges Sales support Marketing Productivity gains Machinery and application technology Speed

More information

Code of practice for the use of triple thermal insulating glass units

Code of practice for the use of triple thermal insulating glass units Code of practice for the use of triple thermal insulating glass units Entwurfsfassung, Stand 07.03.2008 Code of practice for the use of triple thermal insulating glass units Contents 1.0 Introduction................

More information

COMP ONENT CATA LO GUE FOR INDUSTRIAL BUILDINGS

COMP ONENT CATA LO GUE FOR INDUSTRIAL BUILDINGS M a d e f o r b u i l d i n g b u i l t f o r l i v i n g COMP ONENT CATA LO GUE FOR INDUSTRIAL BUILDINGS I M P R i n t KLH Massivholz GmbH Publisher and responsible for the content: KLH Massivholz GmbH

More information

PREFA Aluminiumprodukte GmbH Page 1 of 25

PREFA Aluminiumprodukte GmbH Page 1 of 25 Tender Specifications 120901 PREFALZ Double Standing Seam_2012 ---------------------------------------------------------------------------------- 01. Text GENERAL PRELIMINARY REMARKS Roof ----------------------------------------------------------------------------------

More information

Product information Roof terrace GEL + VEA/VEB/VEC

Product information Roof terrace GEL + VEA/VEB/VEC Edition 1.0 01.07.2015 Product information Roof terrace GEL + VEA/VEB/VEC Product description High quality natural pinewood coated with impregnation and layers of water-based acrylic clear lacquer or white

More information

External Steel Stud and Top Hat Walls. Details SYSTEMS 176 NON-FIRE RATED SYSTEMS 176 FIRE RATED SYSTEMS 178 BRICK VENEER SYSTEMS 183 INSTALLATION 185

External Steel Stud and Top Hat Walls. Details SYSTEMS 176 NON-FIRE RATED SYSTEMS 176 FIRE RATED SYSTEMS 178 BRICK VENEER SYSTEMS 183 INSTALLATION 185 Details SYSTEMS 176 NON-FIRE RATED SYSTEMS 176 FIRE RATED SYSTEMS 178 BRICK VENEER SYSTEMS 183 INSTALLATION 185 GENERAL REQUIREMENTS 185 FRAMING 185 PLASTERBOARD LAYOUT 189 PLASTERBOARD FIXING 190 EXTERIOR

More information

Products PVC-ALU-WOOD

Products PVC-ALU-WOOD ducts PVC-ALU-WOOD Products PVC-ALU-WOOD Products PVC-ALU-WOOD Products PVC-ALU-WOOD Products PVC-ALU-WOOD Products PVC-A Products PVC-ALU-WOOD PVC PROFILES Ideal 4000 02 5 chamber system 70 mm depth Uw

More information

HALFEN HLB LOOP BOX Z-HLB-M50 13-E CONCRETE

HALFEN HLB LOOP BOX Z-HLB-M50 13-E CONCRETE HALFEN HLB LOOP BOX Z-HLB-M50 13-E CONCRETE Translation of the General Certificate of Approval Approval Office: German Institute for Construction Engineering (Deutsches Institut für Bautechnik DIBt) Kolonnenstrasse

More information

SECTION SECTIONAL OVERHEAD DOORS

SECTION SECTIONAL OVERHEAD DOORS SECTION 08360 SECTIONAL OVERHEAD DOORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Aluminum Doors B. Track and Framing 1.2 RELATED SECTIONS A. Section 04810 - Unit Masonry Assemblies: Prepared opening in masonry.

More information

Gold Bond BRAND Gypsum Sheathing

Gold Bond BRAND Gypsum Sheathing BRAND 09 06 29 16 00/NGC 43/NGC brand is a moisture-resistant sheathing installed on the outside of exterior framing as a substrate for exterior claddings. It is manufactured with a treated water-resistant

More information

SECTION 07530CP EPDM MEMBRANE ROOFING

SECTION 07530CP EPDM MEMBRANE ROOFING PART 1 GENERAL 1.1 SUMMARY SECTION 07530CP EPDM MEMBRANE ROOFING A. Section includes: 1. Adhered membrane roofing and flashing 2. Mechanically fastened roof insulation 3. Walkway pads 1.2 ARCHITECTURAL

More information

1.1.2 All window frames will be Kite marked to indicate compliance with these standards.

1.1.2 All window frames will be Kite marked to indicate compliance with these standards. PVC-u WINDOWS Specification 1.1 General Spcification 1.1.1 All products supplied will fully comply with current editions of all relevant British Standards and Codes of Practice, and in particular all profiles

More information

Curtain walls. NEW: forster thermfix vario HI Passiv House facades U f

Curtain walls. NEW: forster thermfix vario HI Passiv House facades U f Curtain walls NEW: forster thermfix vario HI Passiv House facades U f = 0.49 W/(m 2 K) Security: fire protection EI30 EI90 Burglar protection RC2 3 Bullet resistance FB4NS, in steel and stainless steel

More information

Hoesch isodach integral Technical information

Hoesch isodach integral Technical information Technical information A company of ThyssenKrupp Steel tk Contents Page General 3 Main dimensions and properties 4 Corrosion protection 5 Thermal protection / Insulating core 5 Fire protection 5 Information

More information

ifix INSTALLATION MANUAL PV flat roof installation system Version

ifix INSTALLATION MANUAL PV flat roof installation system Version ifix PV flat roof installation system INSTALLATION MANUAL Version 2012-09-06 ifix Installation Manual Version 2012-09-06 Seite 1 Table of contents Table of contents... 1 Special characteristics of ifix...

More information

(English translation prepared by CSTB - Original version in French language) TRIGON Opening Units Ouvrants TRIGON

(English translation prepared by CSTB - Original version in French language) TRIGON Opening Units Ouvrants TRIGON Centre Scientifique et Technique du Bâtiment 84 avenue Jean Jaurès Champs sur Marne FR-77447 Marne la Vallée Cedex 2 Tél.: (33) 01 64 68 82 82 Fax: (33) 01 60 05 70 37 Authorized and notified according

More information

SYSTEM S7-RHOMBOS INSTALLATION MANUAL

SYSTEM S7-RHOMBOS INSTALLATION MANUAL SYSTEM S7-RHOMBOS INSTALLATION MANUAL GENERAL INFORMATION GENERAL INFORMATION This assembly manual addresses all metal ceilings manufactured by durlum. The different sections describe the related/relevant

More information

WEEDOO - SA CONSTRUCTION TECHNOLOGY

WEEDOO - SA CONSTRUCTION TECHNOLOGY Advantages of Double Glazed upvc Windows & Doors WEEDOO SA Technical Support by Jason Jorgensen Advantages of upvc Windows and Doors Heat and Cold insulation Sound insulation Water tightness Dust proof

More information

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board. 1.2 RELATED WORK A. Installation of steel framing members for walls, partitions,

More information

OTTO Professional Guide 1. Bonded window systems for industry and trade

OTTO Professional Guide 1. Bonded window systems for industry and trade OTTO Professional Guide 1 Bonded window systems for industry and trade 2 Orientation 3 Preface 3 Bonded window systems 4 System requirements 5 OTTOCOLL S 81 6-7 Ideal for industry and trade Technical specifications

More information

Field Determination of Water Penetration of Windows using Blowerdoor and Infrared Camera

Field Determination of Water Penetration of Windows using Blowerdoor and Infrared Camera Field Determination of Water Penetration of Windows using Blowerdoor and Infrared Camera Walter Sebastian BMT Building Enviroment Consultants Ltd., Doktor Neergaards Vej 15, DK-2970 Hoersholm, Denmark

More information

KÖMMERLING CHEMISCHE FABRIK GMBH

KÖMMERLING CHEMISCHE FABRIK GMBH KÖMMERLING CHEMISCHE FABRIK GMBH Adhesives for the photovoltaic industry European Coatings CONFERENCE 22. & 23. November 2011, Berlin PRODUCTS Adhesives and sealants for Insulating glass Structural Glazing

More information

European Technical Assessment. ETA-11/0135 of Member of. General part

European Technical Assessment. ETA-11/0135 of Member of. General part INSTITU Schenkenstrasse 4 T +43 1 533 65 50 1010 Vienna Ι Austria F +43 1 533 64 23 www.oib.or.at Ι mail@oib.or.at Designated according to Article 29 of Regulation (EU) No 305/2011 Member of www.eota.eu

More information

A M E R I C A N A R C H I T E C T U R A L M A N U F A C T U R E R S A S S O C I A T I O N

A M E R I C A N A R C H I T E C T U R A L M A N U F A C T U R E R S A S S O C I A T I O N A M E R I C A N A R C H I T E C T U R A L AAMA 2410-13 Standard Practice for Installation of Windows with an Exterior Flush Fin Over an Existing Window Frame M A N U F A C T U R E R S A S S O C I A T I

More information

LUX Specifications. Section S - Preformed Steel Siding

LUX Specifications. Section S - Preformed Steel Siding Part 1 General.1 System-1: Installation over building paper or air barrier membrane, on exterior grade gypsum board or exterior grade wood sheathing. 1.2 RELATED SECTIONS.1 Section 01 11 00 Summary of

More information

SWING DOOR SPECIFICATION

SWING DOOR SPECIFICATION SWING DOOR A1 Work included: Furnish all necessary materials, labour and equipment for the complete installation of aluminum entrance doors, door frames and hardware as detailed on the drawings and specified

More information

Series - 1

Series - 1 SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word

More information

FACADE PROFILES FOR VERSATILE APPLICATIONS 01/16

FACADE PROFILES FOR VERSATILE APPLICATIONS 01/16 FACADE PROFILES FOR VERSATILE APPLICATIONS 01/16 EDGE FORMATION JOINT STRUCTURE CONNECTION STRUCTURE REVEAL FORMATION ROOF AND FACADE VENTILATION CUSTOM SOLUTIONS PRODUCT RANGE According to item number

More information

Data Sheet 3611 Englisch

Data Sheet 3611 Englisch Englisch ETICS Mineral Wool Lamella Insulation Board 3611 WDVS Steinlamellen-Dämmplatte 3611 MW-L 041 WAP, non-combustible, blunt edges, pre-coated on both sides Properties Nichtbrennbar (non-combustible),

More information

Façade System Trimoterm FTV INVISIO

Façade System Trimoterm FTV INVISIO Façade System Trimoterm FTV INVISIO Technical document No. 6/ Version / October 0 CONTENT.0 Technical description of the Facade system with Hidden Fixing - INVISIO []. General []. Panel profile []. Panel

More information

Note: Any verbiage written in red needs to be specified. All other options should be deleted

Note: Any verbiage written in red needs to be specified. All other options should be deleted Note: Any verbiage written in red needs to be specified. All other options should be deleted KYLER SCREENLINE BLIND SPECIFICATION PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions

More information

deceuninck 2500 chamfered series

deceuninck 2500 chamfered series deceuninck 2500 chamfered series 2500 chamfered windows casement internally glazed features Framing choice of two outer frame sizes (52mm and 70mm) choice of three transom/mullion sizes (68mm, 88mm and

More information

Advantages of upvc Windows & Doors. M. Hommernick 1

Advantages of upvc Windows & Doors. M. Hommernick 1 Advantages of upvc Windows & Doors M. Hommernick 1 Advantages of upvc Windows and Doors Heat and Cold insulation Sound insulation Water tightness M. Hommernick 2 Advantages of upvc Windows and Doors Dust

More information

AESTUVER fire-protection mastic For the AESTUVER expansion joint M

AESTUVER fire-protection mastic For the AESTUVER expansion joint M fermacell AESTUVER product data sheet For the AESTUVER expansion joint M Product is an elastic RTV-1 silicone combined with halogen-free fire retardants. Silicone is a versatile elastomer which is mainly

More information

Translation from German (14 pages in all) Translation of the German original version not revised by the Deutsches Institut für Bautechnik

Translation from German (14 pages in all) Translation of the German original version not revised by the Deutsches Institut für Bautechnik Translation from German (14 pages in all) Translation of the German original version not revised by the Deutsches Institut für Bautechnik National Deutsches Institut für Bautechnik 1 Technical ANSTALT

More information

SIKALASTIC-152 EXTERIOR WATERPROOFING MEMBRANE. Product. Scope. Appraisal No. 811 [2013] Appraisal No. 811 (2013) Amended 28 August 2017

SIKALASTIC-152 EXTERIOR WATERPROOFING MEMBRANE. Product. Scope. Appraisal No. 811 [2013] Appraisal No. 811 (2013) Amended 28 August 2017 SIKALASTIC-152 EXTERIOR WATERPROOFING MEMBRANE Amended 28 August 2017 BRANZ Appraisals Technical Assessments of products for building and construction. Sika (NZ) Ltd PO Box 19 192 Avondale Auckland 1746

More information

Signature Series 5 Lap SECTION ALUMINUM WINDOWS

Signature Series 5 Lap SECTION ALUMINUM WINDOWS Signature Series 5 Lap SECTION 08 51 13 ALUMINUM WINDOWS PART 1 GENERAL 1.01 SUMMARY A. Related Documents: Conditions of the Contract, Division 1 - General Requirements, and Drawings apply to Work of this

More information

4257M METALCRAFT INSULATED PANEL SYSTEMS

4257M METALCRAFT INSULATED PANEL SYSTEMS 4257M METALCRAFT INSULATED PANEL SYSTEMS 1. GENERAL This section relates to the fabrication, supply and installation of prepainted steel clad, insulating panels and cladding system for ambient controlled

More information

heroal D 92 UD Front door system

heroal D 92 UD Front door system heroal D 92 UD Front door system Door system Top-quality materials, technical solutions fine-tuned to the smallest detail and a wide variety of design options distinguish the efficient technology available

More information

VELUX America Inc. SPECIFICATION FOR MODEL QPF SELF-FLASHED FIXED SKYLIGHT SECTION UNIT SKYLIGHTS

VELUX America Inc. SPECIFICATION FOR MODEL QPF SELF-FLASHED FIXED SKYLIGHT SECTION UNIT SKYLIGHTS SECTION 08620 UNIT SKYLIGHTS PART 1 GENERAL 1.01 SECTION INCLUDES A. Performance and product component information for VELUX QPF selfflashed fixed skylight. B. Unit skylight mounted directly to roof decking.

More information

Repair Maintenance Hangar Phase II August 2010

Repair Maintenance Hangar Phase II August 2010 SECTION 08800 GLASS AND GLAZING PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Monolithic glass. 2. Insulating glass. 3. Mirror glass. 4. Glazing accessories. B. Types of work in this section include

More information

BF Bulletin 010 / ESG-H a controlled and externally monitored building product to the highest safety standard

BF Bulletin 010 / ESG-H a controlled and externally monitored building product to the highest safety standard ESG-H a controlled and externally monitored building product to the highest safety standard ESG-H a controlled and externally monitored building product to the highest safety standard 1.0 Introduction:

More information

PROJECT LOCATION SECTION COPPER METAL PLATE WALL PANELS

PROJECT LOCATION SECTION COPPER METAL PLATE WALL PANELS SECTION 07 4213.25 PART 1- GENERAL 1.01 SECTION INCLUDES A. Copper metal plate wall panels. 1.02 RELATED REQUIREMENTS A. Section 05 4000 Cold-Formed Metal Framing: Wall panel substrates support framing.

More information

Corium Brick Rainscreen System Specifications

Corium Brick Rainscreen System Specifications CORIUM BRICK RAINSCREEN SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Work Included: The Work of this Section shall include but not be limited to the following: 1. Corium brick plates 2. Galvanized and coated

More information

Österreichisches Institut für Bautechnik Schenkenstrasse Vienna Austria T F

Österreichisches Institut für Bautechnik Schenkenstrasse Vienna Austria T F Authorised and notified according to Article 10 of the Council Directive 89/ 106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating

More information

Bill of Quantities PANDOMO TerrazzoBasic PANDOMO BG/BW TerrazzoBasic two layers on separating sheet or insulation

Bill of Quantities PANDOMO TerrazzoBasic PANDOMO BG/BW TerrazzoBasic two layers on separating sheet or insulation Bill of Quantities PANDOMO TerrazzoBasic PANDOMO BG/BW TerrazzoBasic two layers on separating sheet or insulation General remarks Products used: The tenderer shall include with the offer technical data

More information

Data Sheet 3631 Englisch

Data Sheet 3631 Englisch Englisch Silicate Render KR Silikat-Putz Mineral decorative render, in scraped render structure, for exterior use Properties Decorative, easy structurable facade render silicate based with organic stabilizers

More information

ILKAclean Clean Room Systems

ILKAclean Clean Room Systems ILKAclean Clean Room Systems Systems for Ideas Cleanliness with System ILKAZELL Isoliertechnik GmbH Zwickau is your versatile expert when clean rooms are to meet unique demands. Thanks to the untiring

More information

GXi SLIDING WINDOW AND BALCONY DOOR

GXi SLIDING WINDOW AND BALCONY DOOR Uniclass L41305 EPIC CI/SfB (31.4) Xh4 GXi SLIDING WINDOW AND BALCONY DOOR An elegant, robust and high specification sliding window and balcony door. Intelligent engineering and innovative design features

More information

Revision 1 of EN Changes and news Klaus Berner 25. Oct. 2013

Revision 1 of EN Changes and news Klaus Berner 25. Oct. 2013 The European Association for Panels and Profiles Revision 1 of EN 14509 Changes and news Klaus Berner 25. Oct. 2013 EN 14509 valid version EN 14509:2006: valid version Date of applicability of the standard

More information

MAXIMUM VIEW Architect: Joël Claisse, Photographer: Geraldine Claisse The frameless sliding and fixed window system KELLER minimal windows captivates by slim profile geometry and flush-fitted floors,

More information

D Side lap. Side lap screw spacing < 500mm factory-installed seals on side lap. Decoupling tape > 60mm

D Side lap. Side lap screw spacing < 500mm factory-installed seals on side lap. Decoupling tape > 60mm 25 Side lap screw spacing < 500mm 333.3 15 42 Decoupling tape > 60mm 3 factory-installed seals on side lap Side lap D 201.1 SECTION VIEWS Type L Ridge profile Type R Ridge flashing FLOOR PLAN > 200 overlap

More information

Case Study. Stainless Steel Tilted Solar Roof: German Nautical Museum, Stralsund

Case Study. Stainless Steel Tilted Solar Roof: German Nautical Museum, Stralsund Case Study Stainless Steel Tilted Solar Roof: German Nautical Museum, Stralsund Stainless steel and the photovoltaic array Project concept The German Nautical Museum has an extensive collection of items

More information

Product information Additional window element GIU

Product information Additional window element GIU Edition 1.0 15.12.2014 Product information Additional window element Product description High quality moulded polyurethane with white lacquer finish Fixed window element (non opening) For installation

More information

SEALING & BONDING SIKA FIRE PROTECTION SOLUTIONS

SEALING & BONDING SIKA FIRE PROTECTION SOLUTIONS SIKA FIRE PROTECTION SOLUTIONS APPROVED AND RELIABLE: FOR JOINTS AND PENETRATIONS BENEFIT OF OUR SOLUTION Sika provides comprehensive solutions for fire resistant constructions such as tunnels, commercial

More information

S S 9000 GEALAN s new system platform SYSTEMATIC INNOVATION

S S 9000 GEALAN s new system platform SYSTEMATIC INNOVATION S 9000 GEALAN s new system platform + + Heat-insulating + + Flexible + + Solid + + Innovative + + Design-oriented + + RAL-tested S 9000 SYSTEMATIC INNOVATION Convincing arguments Entirely future-proof

More information

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM PART 1- GENERAL 1.1 SUMMARY A. Section Includes: SECTION 084523 - SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM 1. Flat factory prefabricated structural insulated translucent sandwich panels; with glazed endwalls.

More information

hüma PARKETTSYSTEM GmbH INSTALLATION GUIDE

hüma PARKETTSYSTEM GmbH INSTALLATION GUIDE hüma PARKETTSYSTEM GmbH INSTALLATION GUIDE www.huema.co.uk Content Content GENERAL INFORMATION... 4 INSTALLATION NOTES... 6 ACCLIMATISATION... 6 CHECK FOR FAULTS IN THE MATERIAL... 6 REQUIREMENTS FOR

More information

SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.

SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures. SECTION 06 12 00 STRUCTURAL INSULATED PANELS ------------------------------------------------------------------------------------------------------------ PART 1- GENERAL ----------------------------- 1.1

More information

European Technical Assessment ETA-07/0141 of 15/12/2014

European Technical Assessment ETA-07/0141 of 15/12/2014 ETA-Danmark A/S Göteborg Plads 1 DK-2150 Nordhavn Tel. +45 72 24 59 00 Fax +45 72 24 59 04 Internet www.etadanmark.dk Authorised and notified according toarticle 29 of the Regulation (EU) No 305/2011 of

More information

WINDOWS Highlights of Architecture 2014/15

WINDOWS Highlights of Architecture 2014/15 WINDOWS Highlights of Architecture 2014/15 CONTENT Design styles 6 WINDOWS Window overview 10 studio home pure home soft ambiente 14 0 48 62 EUROPE S No. 1 WINDOW BRAND Already more than 20 million window

More information

SECTION EXPANSION CONTROL

SECTION EXPANSION CONTROL SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Facades. Highest Security in Glass and Aluminium. Protecting Lives and Property. Worldwide.

Facades. Highest Security in Glass and Aluminium. Protecting Lives and Property. Worldwide. Facades Highest Security in Glass and Aluminium Facades Highest Security and individual Design Complete building envelope from SÄLZER: double glazed facade with windows, doors, glass roofs and panel inserts.

More information

Leak Tightness of Jointing. 1. Basic Principles

Leak Tightness of Jointing. 1. Basic Principles Leak Tightness of Jointing a) Fischer roof element low pressure box 28th November 2000 low pressure on corrugated side L = Rota tube L1/50-8623 n = 2 Pressure Airflow Airflow Brandenburg Technical University

More information

3275 & 3275U, 3285 & 3285U Vertical Sliding, Double-Hung Windows

3275 & 3275U, 3285 & 3285U Vertical Sliding, Double-Hung Windows 3275 & 3275U, 3285 & 3285U Vertical Sliding, Double-Hung Windows 3000 SERIES FIBERGLASS - Min 1 6 2 9 Max 4 0 7 0 - Min 3 0 2 9 Max 8 0 7 0 Double-Hung Double Double-Hung - Min 4 6 2 9 Max 12 0 7 0 Minimum

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 08 - OPENINGS. A. This Section includes fixed and operable aluminum-framed windows.

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 08 - OPENINGS. A. This Section includes fixed and operable aluminum-framed windows. SECTION 085113 - ALUMINUM WINDOWS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes fixed and operable aluminum-framed windows. 1.2 PERFORMANCE REQUIREMENTS A. General: Provide aluminum windows capable

More information

Series PV. Compact Switchgear Cabinets. Construction subject to change without notice Dimensions in mm

Series PV. Compact Switchgear Cabinets. Construction subject to change without notice Dimensions in mm Series PV Single layer design, thermal conductivity k = 5 W/m 2 K For wall mounting by hanging and standing installation Torsion resistant, self-supporting casing without joints, corrosion and seawater

More information

SECTION ALUMINUM STORM WINDOWS

SECTION ALUMINUM STORM WINDOWS PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 08 51 69.11 ALUMINUM STORM WINDOWS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Also delete any other item or paragraph not applicable

More information

GREENHOUSE ENGINEERING PREFABRICATED HOUSES

GREENHOUSE ENGINEERING PREFABRICATED HOUSES GREENHOUSE ENGINEERING PREFABRICATED HOUSES WOODEN HOUSES Prefabricated wooden houses are made of wooden bearing structure with mineral wool, with a vapor barrier. On the inside, construction is lining

More information

NOVABRIK MORTARLESS CONCRETE BRICK VENEER SPECIFICATION. MASTERFORMAT SECTION (Mortarless Concrete Brick Veneer)

NOVABRIK MORTARLESS CONCRETE BRICK VENEER SPECIFICATION. MASTERFORMAT SECTION (Mortarless Concrete Brick Veneer) NOVABRIK MORTARLESS CONCRETE BRICK VENEER SPECIFICATION MASTERFORMAT SECTION 04818 (Mortarless Concrete Brick Veneer) Spec_USA_En_18102005.doc 12/1/2005 Novabrik Page 2 Section 04818 NOVABRIK MORTARLESS

More information

Product Data Sheet. Product: Benchmark Wall Liner System

Product Data Sheet. Product: Benchmark Wall Liner System APPLICATION The Benchmark Wall Liner system is to be used as an insulated composite wall panel under site applied fully supported or self-supported aluminium, copper, zinc and stainless steel cladding

More information

Contents: 3. Benefits of CLT with regard to airtightness. 4. Technical aspects of airtightness. 5. Configurations and specific connections. 6.

Contents: 3. Benefits of CLT with regard to airtightness. 4. Technical aspects of airtightness. 5. Configurations and specific connections. 6. Contents: 1. Introduction 2. Relevance of airtightness/windtightness 3. Benefits of CLT with regard to airtightness 4. Technical aspects of airtightness 5. Configurations and specific connections 6. Summary

More information

Concepts. Products. Service. Partitions Lindner Logic

Concepts. Products. Service. Partitions Lindner Logic Concepts Products Service Partitions Lindner Logic Building new solutions. Lindner undertakes major projects worldwide in all areas of interior fit-out, insulation technology, industrial services and building

More information

Xtratherm Thin-R Thermal Liner (XT/TL Grade)

Xtratherm Thin-R Thermal Liner (XT/TL Grade) CERTIFICATE NO. 03/0183 DETAIL SHEET 4 Xtratherm Thin-R Thermal Liner (XT/TL Grade) PRODUCT DESCRIPTION: This Detail Sheet relates to Xtratherm Thin-R Thermal Liner, as defined in NSAI Agrément Certificate

More information

ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95

ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95 ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95 TEST PROCEDURE FOR STATIC UPLIFT RESISTANCE OF MECHANICALLY ATTACHED, CLIPPED, RIGID, ROOF SYSTEMS (For Methods of Mechanical Attachment Excluding Clips,

More information

Page 1. Energy Saving skylights. PolyCarbonate Panels

Page 1. Energy Saving skylights. PolyCarbonate Panels Page 1 Energy Saving skylights PolyCarbonate Panels Page 2 PRODUCT RANGE AKYVER is a light and impact resistant insulating Polycarbonate glazing. The 4, 6, 8 and10 mm depth sheets are available in twin

More information

Sectional garage doors. A product of ALPHA Deuren International BV

Sectional garage doors. A product of ALPHA Deuren International BV Sectional garage doors A product of ALPHA Deuren International BV Bau muster geprüft 1 All-in-one design Modern door concept high quality optimum performance extensive colour range perfect match for all

More information

SOLITEX EXTASANA ADHERO SELF-ADHESIVE UNDERLAY. Product. Scope. Appraisal No. 989 [2017] Appraisal No. 989 (2017) BRANZ Appraisals

SOLITEX EXTASANA ADHERO SELF-ADHESIVE UNDERLAY. Product. Scope. Appraisal No. 989 [2017] Appraisal No. 989 (2017) BRANZ Appraisals SOLITEX EXTASANA ADHERO SELF-ADHESIVE UNDERLAY BRANZ Appraisals Technical Assessments of products for building and construction. Product 1.1 is a self-adhesive, synthetic underlay for use over rigid wall

More information

TPS Thermo Plastic Spacer

TPS Thermo Plastic Spacer contact optimize your products www.bystronic-glass.com sales@bystronic-glass.com Errors and technical modifications reserved 09.10 TPS Thermo Plastic Spacer The most advanced solution for efficient and

More information

EasylationWall. External Wall Insulation System. bringing european innovation

EasylationWall. External Wall Insulation System. bringing european innovation EasylationWall External Wall Insulation System bringing european innovation EasylationWall... the new External Wall Insulation System using brick slips for stunning façades. EXTERNAL WALL INSULATION (EWI)

More information

CONTENTS. General Glazing Guidelines

CONTENTS. General Glazing Guidelines ECKELT I I Page 1 CONTENTS Introduction 3 Standards 4 Validity 5 Glass rebate 6 Rebate size 6 Use of sealants 9 Glazing block guidelines 10 Role of glazing blocks 10 Material of glazing blocks 11 Heavy

More information

wood EUROPEAN ARCHITECTURAL SUPPLY FINE WINDOWS FOR ALL SEASONS products Makrowin MW88 G2 21 Makrowin MW88 23 Makrowin MW78 25 Makrowin MW AluClad 27

wood EUROPEAN ARCHITECTURAL SUPPLY FINE WINDOWS FOR ALL SEASONS products Makrowin MW88 G2 21 Makrowin MW88 23 Makrowin MW78 25 Makrowin MW AluClad 27 wood products Makrowin MW88 G2 21 PHI Certified Triple-Pane Window Makrowin MW88 23 PH Performance Triple-Pane Window Makrowin MW78 25 Top Performance Double-Pane Window Makrowin MW AluClad 27 Premium

More information

Mounting System MCG 1.1 Membrane-Connected Glass. System description

Mounting System MCG 1.1 Membrane-Connected Glass. System description Mounting System MCG 1.1 Membrane-Connected Glass System description SUNOVA MCG 1.1 System Fields of application: Not suitable for: (please inquire for other SUNOVA systems) The SUNOVA MCG system is a lightweight

More information

American Architectural Manufacturers Association VOLUME 1 - WINDOWS AND DOORS

American Architectural Manufacturers Association VOLUME 1 - WINDOWS AND DOORS VOLUME 1 - WINDOWS AND DOORS Window and Door Selection Guide PART 1 WINDOW SELECTION GUIDE WSG-11 PART 2 - PERFORMANCE SPECIFICATIONS Voluntary Specifications for Aluminum, Vinyl (PVC) and Wood Windows

More information

Mounting System MCG 3.0 Membrane-Connected Glass. System description

Mounting System MCG 3.0 Membrane-Connected Glass. System description Mounting System MCG 3.0 Membrane-Connected Glass System description SUNOVA MCG 3.0 System Fields of application: Not suitable for: (please inquire for other SUNOVA systems) The SUNOVA MCG 3.0 system is

More information